York ZX, ZY User Manual

CONTENTS
The “User” must read all sections of this manual and keep the manual for future ref­erence.
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Leave the building immediatel y.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the
fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
SAFETY INFORMATION . . . . . . . . . . . . . . . . 2
FOR YOUR SAFETY . . . . . . . . . . . . . . . . . . . . . . 2
SYSTEM OPERATION. . . . . . . . . . . . . . . . . . 2
THERMOSTATS. . . . . . . . . . . . . . . . . . . . . . . . . .2
INTERMITTENT IGNITION DEVICE . . . . . . . . . . 2
OPERATING INSTRUCTIONS. . . . . . . . . . . . . . .3
USER’S, MAINTENANCE
and
SERVICE INFORMATION
EXPLAIN UNIT FUNCTION . . . . . . . . . . . . . . 4
GENERAL MAINTENANCE. . . . . . . . . . . . . . 4
HEATING SYSTEM INSPECTION . . . . . . . . . . . . 4
AIR FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
BLOWER ASSEMBLY . . . . . . . . . . . . . . . . . . . . . 5
MOTORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CONDENSER COIL . . . . . . . . . . . . . . . . . . . . . . . 6
REGISTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . 6
BEFORE CALLING A SERVICE TECHNICIAN:. . 6
MANUAL
3 THRU 12.5 TON
SINGLE PACKAGE
AIR CONDITIONER
GAS/ELECTRIC
1046287-UUM-A-1013
1046287-UUM-A-1013
SAFETY INFORMATION
FOR YOUR SAFETY
Make sure that the furnace area is clear and free of combustible materials, gasoline and other flamma­ble vapors and liquids.
Be sure the furnace is clear and free of insulating material. Examine the furnace area after installa­tion of the furnace or the installation of additional insulation. Some types of insulation maybe com­bustible.
For proper and safe operation, the furnace needs air for combustion and ventilation. Do not block or obstruct air openings on the furnace or the space around the furnace. Maintain the required unit clearances.
For lighting or shutting down this furnace, refer to the lighting instructions provided adjacent to the burners in the unit and also located in this manual on Pages 7 and 8.
A blocked vent roll-out switch is provided in the burner compartment. This switch is a manual reset. If the furnace fails to operate, contact a qualified service technician.
SYSTEM OPERATION
THERMOSTAT S
Set your thermostat for either heating or cooling then set it for the desired temperature. DO NOT ADJUST THE THERMO­STAT RAPIDLY ON AND OFF, OR BACK AND FORTH FROM HEAT TO COOL. THIS COULD DAMAGE YOUR EQUIPMENT.
Always allow at least 5 minutes between changes. Find the temperature that is most comfortable to you and then LEAVE YOUR THERMOSTAT ALONE. (Exception is for night or vacation “set back” to conserve energy).
Manually moving the thermostat up or down will not speed up temperature changes in your rooms. This only causes the thermostat switch to function at your command rather than responding to room temperature.
Heat generated by devices other than the furnace may inter­fere with thermostat performance. Therefore, lamps, radios, television sets, etc. should not be placed near the thermostat.
Should the gas supply fail to shut off or if overheat­ing occurs, shut off the gas valve to the furn ace before shutting off the electrical supply. Then call a qualified service technician.
Do not use this furnace if any part has been under water. A flood-damaged furnace is extremely dan­gerous. Attempts to use the furnace can result in fire or explosion. A qualified service technician should be contacted to inspect th e fu rn ace and to replace all gas controls, control system parts, elec­trical parts that have been wet or the furnace if deemed necessary.
Determine the integrity of the installation regarding the flue gas vent, the return and supply air duct. All flue gas carrying areas external to the furnace must be clear and free of obstructions. The external vent should be attached and physically sound without holes or excessive corrosion. The return-air duct connection(s) should be physically sound and sealed to the furnace casing. The physical support of the furnace should be sound without sagging, cracks, gaps with no obvious signs of deterioration. The burner flames in operation should appear as detailed in figure 3. The manufacturer recommends that main burner, ignition device and controls are inspected by a qualified service technician before each heating season.
FIGURE 1- TYPICAL THERMOSTAT
INTERMITTENT IGNITION DEVICE
This furnace is equipped with an intermittent auto­matic ignition system. Do Not attempt to manually relight the burners. Personal injury could result.
When the thermostat calls for heat, gas is supplied and at the same time, sparking occurs to light the burner. With the burner lit, the flame sensor rod closes a circuit to the ign iter control which allows the burner to continue to fire.
When the room thermostat is satisfied, the electrical circuit to the gas valve is opened, closing main burner gas. If the burner should fail to light, contact your heating contractor or gas utility for service to insure that proper operating condi­tions are restored.
2 Johnson Controls Unitary Products
1046287-UUM-A-1013
INPUT
The correct heat capacity of the furnace is regulated by the burner orifices and the gas pressure. The proper orifices are furnished but the gas pressure regulator must be adjusted by the installer or gas utility service technician.
OPERA T ING INSTRUCTIONS
TO SHUT DOWN THE FURNACE:
1. Close the main gas shutoff valve(s).
2. Turn off the electric power supply. TO LIGHT THE FURNACE:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the
fire department.
- Installation and service must be per formed by a qualified installer, service agency or the gas supplier.
VENT SAFETY SYSTEM: This gas furnace is equipped with a manual reset high tem-
perature sensor or rollout sw itch wh ich in the unlik ely eve nt of a sustained main burner flame rollout will shut off the flow of gas by closing the main gas valve. The ignition modules will also be disabled, preventing the flow of gas to the valve. The switch is located inside the gas heat access panel above the burner inlet. Flame rollout can be caused by blockage of the power vent system, improper gas pressure or adjustment. If this event occurs the furnace will not operate properly. The gas supply to the furnace should be shut off and no attempt should be made to place the furnace in operation. The sys­tem should be inspected by a qualified service technician. Refer to Figure 2 for a typical installation.
100% SHUT OFF: The ignition modules are designed for 100% shut-off. If the
furnace fails to ignite after three ignition attempts, the flow of gas will be shut off and the ignition module will lock out. The module can be reset by:
A. Turning the system switch on the room thermost at to the
“OFF” position and back to the “HEAT” position.
B. Decreasing the set point of the room thermostat below
the temperature in the conditioned space and returning it to its original setting.
C. Opening and closing the unit's main disconnect switch.
1. Do not attempt to light manually.
2. Open the main gas shutoff valve(s).
3. Adjust the set point of the room thermostat above the temperature in the space.
4. Turn on the electric power supply.
5. The draft fan will operate. After an adequate purge time, the electric spark igniter will light the burners.
6. The burners will extinguish and relight automatically upon the demand of the room thermostat.
FIGURE 2- TYPICAL INSTALLATION
Johnson Controls Unitary Products 3
Loading...
+ 7 hidden pages