York ZF120, ZF102, ZF150, ZF090, ZF078 Technical Manual

5167798-YTG-J-0218
®
TECHNICAL GUIDE R-410A ZF SERIES
6.5 - 12.5 TON 60 Hertz
ZF 6.5 THROUGH 10 TON

Description

ASHRAE 90.1 COMPLIANT
®
YORK common footprint cabinet and common roof curb for all 6.5 through 12.5 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or fra me.
All Predator full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.
Predator side airflow and down airflow, with corresponding economizer if economizer option is desired.
Predator® units are available in the following configurations: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory-installed options or field-installed accessories.
All units provide constant supply air volume. A variab le ai r volume (VAV) option, which features a variable frequency drive (VFD), is available on 6.5 through 12.5 ton models.
Predator® units are convertible single packages with a
®
units are self-contained and assembled on rigid
®
units in all tonnage sizes are convertible between
ZF12.5 TON
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5167798-YTG-J-0218
Roof curbs in eight- and fourteen-inch heights. Roof curbs for transitioning from York Sunline™ footprint to the ZF Series footprints are also available (field installed accessory)
Base rails w/forklift slots (three sides) and lifting holes
Compressor #2 access (high­efficiency compressor)
Dual stage cooling for maximum comfort
Second model nameplate inside hinged access panel
Terminal block for hi-voltage connection
Smart Equipment™ control board
w/screw connector for T-stat wiring and network connections
Disconnect location (optional disconnect switch)
Filter Access (2” or 4” filter options)
Filter drier (solid core)
Slide-out motor and blower assembly for easy adjustment and service
Belt-drive blower motor
Power ventor motor
20-guage aluminized steel tubular heat exchanger for long life (stainless steel option)
Two-stage gas heating to maintain warm, comfortable temperature
Intelligent control board for safe and efficient operation
Compressor #
1 access
(high-e
fficiency compressor)
Toolless door latch
Side entry power and control wiring knockouts
VFD Location (optional)
Slide-out drain pan with 3/4” NPT, female connection
ZF Series utilize Micro-Channel Aluminum Tube/Aluminum Fin Condenser

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Prior Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Component Location

Cooling With Gas Heat

2 Johnson Controls Unitary Products

Nomenclature

Z F 090 CA2 A 1
A
1A A 2
Product Category
Z = A/C, Single Pkg., R-410A
B = Standard Static D = High Static E = VFD/VAV Std Static G = VFD/VAV High Static H = VFD/VAV w/Bypass Std Static K = VFD/VAV w/Bypass High Static L = VFD/VAV Customer Std Static N = VFD/VAV Customer High Static P = VFD IntelliSpeed Std Static R = VFD IntelliSpeed High Static S = VFD w/Byp IntelliSp Std Static U = VFD w/Byp IntelliSp Hi Static V = VFD Cust IntelliSp Std Static X = VFD Cust IntelliSp Hi Static
Blower Option
Product Generation
1 = First Generation 2 = Second Generation
C = Cooling Only E = Electric Heat
Heat Type
09 = 9 KW (078,090,102) 18 = 18 KW (078,090,102,120,150) 24 = 24 KW (078,090,102,120,150) 36 = 36 KW (078,090,102,120,150) 54 = 54 KW (120,150)
12 = 120 MBH Input (078, 090, 102) 18 = 180 MBH Input (078,090,102,120,150) 24 = 240 MBH Input (120,150)
Heat Capacity
078 = 6.5 Ton
Nominal Cooling Capacity
090 = 7.5 Ton 102 = 8.5 Ton 120 = 10.0 Ton 150 = 12.5 Ton
Product Identifier
F = Pkg AC Std Eff
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Additional Options
1 = STD Throwaway Filter 2 = 2" Pleated Filters (Merv 8) 3 = 4" Pleated Filters (Merv 13) 4 = Coil Guard (CG), STD Filter 5 = 2" Pleated Filter,CG 6 = 4" Pleated Filter,CG
A = Std Cabinet E = SSD (SST Drain Pan) R = Reverse Drain Pan
A = No Economizer B = Economizer w/Barometric RLF D = Economizer w/Power EXH H = Motorized Damper
Outdoor Air Option
1 = No Service Options 2 = DSC (Disconnect Switch) 3 = NCO (Non-PWR Conv. Outlet) 4 = PCO (Powered Conv. Outlet) 5 = DSC,NCO 6 = DSC,PCO
A = No Sensors B = PHM (Phase Monitor) C = DFS (Dirty Filter Switch) D = SSD (Supply Air Smoke DET) E = RSD (Return Air Smoke DET) F = PHM,DFS G = PHM,SSD H = PHM,RSD J = DFS,SSD K = DFS,RSD L = SSD,RSD M = PHM,DFS,SSD N = PHM,DFS,RSD P = PHM,SSD,RSD Q = DFS,SSD,RSD R = PHM,DFS,SSD,RSD
Refrigeration
A = Standard Refrigeration B = ECC (E-Coat Cond Coil) C = EEC (E-Coat Evap Coil) D = HGBP (Hot Gas Bypass) F = ECC,EEC G = ECC,EEC,HGBP J = ECC,HGBP M = EEC,HGBP
Service Options
A = Stand Alone Smart Equipment™ C = BACnet MSTP,Mdbs,N2 COM Card D = CPC Control, DFS, APS F = Fault Detection Diagnostics G = Novar UCM Ctrl, DFS, APS H = Hnywll Excel 10 CTRL,DFS,APS M = Verasys Single Zone N = Verasys Change Over Bypass P = Verasys VAV Q = Verasys Single Zone W/FDD R = Verasys COBP W/FDD T = Verasys VAV W/FDD
Controls Option
6.5-12.5 Ton York® Model Number Nomenclature
Two Stage Natural Gas Heat Options
N = 2 Stage Gas Aluminized Steel S = 2 Stage Gas Stainless Steel
00
00 = Cooling Only
Gas MBH Input (Unit Size Allowed)
Electric Heat (Unit Size Allowed)
Sensors
A
Cabinet Options
5167798-YTG-J-0218
Johnson Controls Unitary Products 3
5167798-YTG-J-0218
Z F 090 N10 A 2 A AA 7 0 1 2 4 A
Product Category
Z = A/C, Single Pkg., R-410A
C00 = Cooling Only. No heat installed
Heat Type and Nominal Heat Capacity
N10 = 100 MBH Output Aluminized Steel N15 = 150 MBH Output Aluminized Steel N20 = 200 MBH Output Aluminized Steel S10 = 100 MBH Output Stainless Steel S15 = 150 MBH Output Stainless Steel S20 = 200 MBH Output Stainless Steel
E09 = 9 KW E18 = 18 KW E24 = 24 KW E36 = 36 KW E54 = 54 KW
Gas Heat Options
Electric Heat Options
078 = 6.5 Ton
Nominal Cooling Capacity
090 = 7.5 Ton 102 = 8.5 Ton 120 = 10.0 Ton 150 = 12.5 Ton
Product Identifier
F = 11.2 + EER A/C
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Product Style
A = Style A B = Style B C = Style C
A = No Options Installed
Installation Options
B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Option
s 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
Options
6.5-12.5 Ton York® Model Number Nomenclature For Units Produced Before 2-01-2016
Product Generation
7 = Seventh Generation
SS Drain Pan
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
CPC Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
2" Pleated Filters, MERV 7
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller) Shipping Bag
York Commercial Comfort System (YCCS) Rtu Controller
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume, VFD (not available with factory installed BAS options)
Variable Air Volume, VFD Ready (for customer-provided, field-installed drive)
Variable Air Volume, VFD and Manual Bypass (not available with factory installed BAS options)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch
Additional Options
RC = Coil Guard, Shipping Bag & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch
4" Pleated Filters, MERV 13
EA = E-Coat Condenser Coil EJ = E-Coat Evaporator Coil ES = E-Coat Cond & Evap Coils
IntelliSpeed with VFD
IntelliSpeed, VFD and Manual Bypass
IntelliSpeed, VFD Ready (for customer-provided, field-installed drive)
Airow
Simplicity®Smart Equipment w/Comm Card (BACnet, N2, Mod-Bus)
A = Std. Motor D = Std. Motor/Motorized Damper (Downow Only) H = Std Motor/Low Leak Econ/Barometric Relief (Downow & Horizontal End Return Only) J = Std Motor/Low Leak Econ/Power Exhaust (Downow & Horizontal End Return Only) N = Hi Static R = Hi Static/Motorized Damper (Downow Only) V = Hi Static Mtr/Low Leak Econ/Barometric Relief (Downow & Horizontal End Return Only) W = Hi Static Mtr/Low Leak Econ/Power Exhaust (Downow & Horizontal End Return Only)
Fault Detection and Diagnostics (FDD)

Prior Nomenclature

4 Johnson Controls Unitary Products
5167798-YTG-J-0218

Features and Benefits

Standard Features

Service Friendly - The Predator® incorporates a number of key features for ease of serviceability.
Service time is reduced through the use of hinged, toolless panels. Such panels provide access to frequently inspected components and areas, including the control box, compressors, filters, indoor motor & blower, and the heating section. The panels are screwed in place at the factory to prevent access by children or other unauthorized persons. It is recommended that the panels be secured with screws once service is complete.
Service windows have been placed in both condenser section walls. Rotation of the cover allows easy access to the condenser coils for cleaning or inspection.
The Smart Equipment™ control board provides alarm messages to help quickly identify any faults.
All units use the same standard filter size. This standardization removes any confusion on which filter sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing the drain pan cover plate on the rear of the unit. Once the plate is removed, the drain pan slides out through the rear of the unit.
All Predator located inside the control access door. This is to prevent deterioration of the nameplate through weathering.
• Coil Technology – ZF condensers utilize Micro-Channel “all aluminum” condensers which provide improved heat transfer capabilities and reduced charge volumes.
Environmentally Aware - For improved Indoor Air Quality, a combination of aluminum foil faced and elastometric rubber insulations are used exclusively throughout the units.
Balanced Heating – The Predator Heating Comfort” with a balance between 1st and 2nd stage gas heating. The first stage of a gas heat Predator provides 60% of the heating capacity. Balanced heating allows the unit to better maintain desired temperatures.
Convertible Airflow Design – The side duct openings are covered when they leave the factory. If a side supply/ return is desired, the installer simply removes the two side duct covers from the outside of the unit and installs them over the down shot openings. No panel cutting is required. Convertible airflow design allows maximum field flexibility and minimum inventory.
System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low­pressure switches. Internal compressor protection is standard on all compressors. Phase Monitors are standard on units with scroll compressors. This accessory monitors the incoming power to the unit and protects the unit from phase loss and reversed phase rotation.
®
units have a second model nameplate
®
offers “Ultimate
®
unit
Advanced Controls - Smart Equipment™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.
The Smart Equipment™ control board used in this product will effectively operate the cooling system down to 0°F when this product is applied in a comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process cooling applications (computer rooms, switchgear, etc.), please reference applications bulletin AE-011-07 or call the applications department for Unitary Products @ 1­877-UPG-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30°F.
Units will come with the new state of the art Smart Equipment™ control system. The new unit control incorporates the best of the already proven Simplicity™ unitary controls and creates a more robust, intelligent control. The goal of this control is to utilize cutting edge technology making the equipment easier to install, operate, and service. All units are Factory commissioned, configured, and run tested.
Versatile - The Smart Equipment™ control can be configured to use with a standard thermostat (easy to connect screw terminals), A zone sensor, or can be setup to communicate with multiple BAS communication protocols to integrate with building automation systems.
Reduce field installed complexity - Each unit will comes equipped with factory installed supply air, return air, and outdoor air temperature sensors providing key temperature readings thus reduce field installed complexity.
On-board USB Port - The new control comes with a long list of features including data logging, current and previous system faults and software update capabilities
Johnson Controls Unitary Products 5
5167798-YTG-J-0218
using the on board USB port and common flash drive. Energy use monitoring capabilities allow custom tailoring to allow a system to work more efficiently at all times and occupancy levels. Self test and start-up reports also available from the board VIA the USB port.
Embedded LCD Display - The board has a easy to read, built-in LCD display and easy to use navigation joystick and buttons allowing the user to quickly navigate the menus displaying unit status, options, current function, supply, return and outdoor temperatures, fault codes and other information.
Safety Monitoring - The control monitors the outdoor, supply, and return air temperatures and the high and low pressure switch status on the independent refrigerant circuits. On units with heating the gas valve and high temperature limit switches are monitored on gas and electric heating units. The control also monitors the voltage supplied to the unit and will protect the unit if low voltage due to a brown out, or other electrical issue occurs.
Low Ambient - An integrated low-ambient control allows units to operate in the cooling mode down to 0°F outdoor ambient without additional components or intervention. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
Anti-Short Cycle Protection - To aid compressor life, an anti- short cycle delay is incorporated into the standard control. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti­short cycle delay can be temporarily overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and/or heating capacity.
Nuisance Trip Protection and Three Strikes - To prevent nuisance calls, the control board uses a three times, you're out philosophy. The high, low-pressure switch, anti-freeze protection, low voltage or heating high limit must trip three times within two hours before the unit control board will lock out the associated compressor.An alarm message will be displayed on the LCD screen.
Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.
Low Limit Control (LLC) - To prevent the supply air from dropping below a specified set point, when there is a demand for cooling during cold outside conditions. (Programmable Set point)
Reliable - From the beginning - All units undergo computer automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. For the long term - All units are painted with a long lasting, powder paint that
stands up over the life of the unit. The paint used has been proven by a 1000 hour salt spray test.
Full Perimeter Base Rails - The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer rigging holes so that an overhead crane can be used to place the units on a roof.
Easy Installation - Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. All units are shipped with 2" throw-away filters installed.
Wide Range of Indoor Airflows - All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/ or static pressure requirement.
Warranty - All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry a 5-year warranty. Aluminized steel (10 yr.) and stainless steel tubular heat exchangers carry a 15- year warranty.

Factory Installed Options

YORK® offers several equipment options factory installed, for the Predator®line.
Optional Factory Installed Economizers - Predator units offer a variety of optional factory installed economizers with low leak dampers. The outdoor air dry bu lb sensor enables economizer operation if the outdoor air temperature is less than the set point of the economizer logic module. See economizer options section to determine the correct economizer for your application.
Down flow / End Return Economizers (with barometric relief and fresh air hood) - All units offer a va riety of optional factory installed down flow eco no mizers th at are shipped, installed and wired with low l ea k da mpers designed to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each economizer goes through a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual enthalpy (wit h field installed kit) can be selected. The economizer has spring return , fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the outdoor air dry bulb temperature or the outdoor air enthalpy i nput. The optional (field installed) single or dual enthalpy kits provi de additional inputs to monitor outdoor air/ or return air humidity and temperature for true enthalpy co ntrol. The installer needs only to assemble the outdoor air hood, attach the enthalpy control the hood and mo un t the hood to the unit (Hood and control are provided).
Power Exhaust - This factory option allows down flow or horizontal end return economizer operation. The power
exhaust must be removed from the unit and mounted in the horizontal end return duct work when applying
6 Johnson Controls Unitary Products
5167798-YTG-J-0218
the product in the horizontal, end return configuration.
Motorized Outdoor Air Damper - The motoriz ed outdoor air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry.
Alternate Indoor Blower Motor - For applications with high static restrictions, units are offered with optional indoor motors that provide higher static output and/or higher airflow, depending upon the installer’s needs.
Variable Air Volume (VAV; 6.5 through 12.5 ton, only ­A factory-installed variable frequency drive (VFD), mounted in the Blower Access compartment, is used to control the speed of the indoor blower motor in order to maintain a constant static pressure in the supply duct. A duct pressure transducer is provided with the unit. The drive comes completely wired and pre-programmed from the factory.
An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower Motor Access compartment. The switch can be used to either route power to the VFD for modulating control of the blower motor, to bypass the drive and operate the motor at full speed, or to power the drive (and not the motor) for diagnostic purposes.
VAV is not available with the factory-installed 3rd. party BAS controllers. VAV is only factory installed with the Smart Equipment™ Controller.
A ‘VFD-ready’ option provides the provisions for a customer-installed drive. The unit comes with a mounting bracket installed in the Blower Access compartment which may accommodate other vendor’s drives depending on their size. In order to utilize the unit’s mounting bracket, the maximum recommended drive dimensions are limited to approximately 9” H x 5” W x 7.5” D.
If the drive will not fit in the allotted space, then it will have to be mounted elsewhere; either within the building on a perpendicular wall which is not subjected to excessive temperature, vibration, humidity, dust, corrosive gas, explosive gas, etc., or within an appropriate enclosure rated for outside installation to safeguard against moisture, dust and excessive heat. A terminal block located in the control box is provided for field connection of the VFD controls.
IntelliSpeed™ Supply Fan Control Option (ASHRAE
90.1 compliant, section 6.4.3.10) - Units configured with
the IntelliSpeed™ Supply Fan Option will contain a VFD for multi-speed supply fan operation. This option allows the supply fan RPM to vary based on the number of compressors or heating stages energized. The economizer's minimum position will also be configurable to vary based on the supply fan VFD frequency output.
Aluminized Steel Gas Heat Exchanger - For applications in non-corrosive environments.
Stainless Steel Gas Heat Exchanger - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
Stainless Steel Drain Pan - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
Electric Heaters - The electric heaters range from 9kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. All heaters are intended for single point power supply.
Disconnect Switch - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
Convenience Outlet - (Non-Powered/Powered) - This option locates a 120V single-phase GFCI outlet with cover, on the corner of the unit housing adjacent to the compressors. The “Non-powered” option requires the installer to provide the 120V single-phase power source and wiring. The “Powered” option is powered by a stepdown transformer in the unit. Factory installed option only.
Smoke Detectors - The smoke detectors stop operation of the unit and provide a fault message to the control board. Smoke detectors are available for both the supply and/or return air configurations.
Filters – 2” Pleated MERV 8 or 4” Pleated MERV 13 are available to meet LEED requirements. A 2” Throwaway is shipped as standard.
Factory-installed smoke detectors may be subjected to extreme temperatures during "off" times due to outside air infiltration. These smoke detectors have an operational range of -4 °F to 158°F. Smoke detectors installed in areas that could be outside this range will have to be relocated to prevent false alarms.
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on units with Scroll Compressors.)
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
E-Coat Condenser Coils - The condenser coils are coated with an epoxy polymer coating to protect against corrosion.
E-Coat Evaporator Coils - The evaporator coils are coated with an epoxy polymer coating to protect against corrosion.
Johnson Controls Unitary Products 7
5167798-YTG-J-0218
Hot Gas Bypass - Allows operation during low load conditions while avoiding coil frosting and damage to compressor. When suction pressure falls below valve setpoint, the valve modulates hot gas to the inlet of the evaporator.
HGBP is standard on all units with VAV, and optional with constant-volume units.

Control Options

Smart Equipment™ with Communication Option Control - The York® Smart Equipment™ with
Communication Option Control is factory installed. It includes all the features of the Smart Equipment™ control with an additional gateway to BACnet MS/TP (programmable to Modbus or N2 protocols).
FDD (Fault Detection and Diagnostics) - Refrigerant side A factory installed control system option on the commercial equipment that constantly monitors refrigerant circuit pressures, refrigerant circuit temperatures, as well as the environmental temperatures and humidity via multiple sensor inputs.
• Provides a building owner, techni ci an or contractor with
the operational characteristics of the RTUs entire refrigerant circuit to ensure the unit is functioning at its specified performance level.
• Provides alarms if the unit is not functioning optimally.
• Remotely accessible via the Mobile Access Porta l
(MAP) gateway as well as scrolled on the UCB LCD screen.
Novar® BAS Control - The Novar® building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, with optional dirty filter indicator switch and air proving switch.
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, with optional dirty filter indicator switch, and air proving switch.
Verasys - Verasys provides a simple user experience with configurable self-recognizing controllers without the need for any additional tools. Verasys creates enhanced integration of HVACR equipment, zoning, and controls. Contractors are able to offer a complete bundled solution of equipment and controls to serve the light commercial market.

Field Installed Accessories

YORK® offers several equipment accessories for field installation, for the Predator
Down flow and End Return Economizers (with fresh air hood and barometric relief) - All units offer a variety of optional factory installed down flow economizers that are shipped, installed and wired with low leak dampers designed
®
line.
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each econo mizer goes through a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual enthalpy (with field installed kit) can be selected. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the outdoor air dry bulb temperature or the outdoor air enthalpy input. The dual enthalpy kit provides a second input used to monitor the return air (field installed). The installer needs only to assemble the outdoor air hood, attach the enthalpy control the hood and mount the hood to the unit (Hood and control are provided).
Single or Dual Enthalpy Control, Accessories - These kits contain the required components to convert a dry bulb economizer to a single enthalpy and/or dual enthalpy economizer.
Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed economizers.
Power Exhaust - This accessory installs in the unit with a down flow or horizontal end return economizer. Power exhaust plugs into the connector in the unit bulkhead.
User must purchase the 1EH0408 barometric relief and hood kit when applying the product in a horizontal flow application. The power exha us t must be mounted in the horizontal end return ductwork.
Manual Outdoor Air Damper - Like the motorized outdoor air damper, each manual outdoor air damper incl udes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
Sensor - Senses CO2 levels and automatically
CO
2
overrides the economizer when levels rise above the preset limits.
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.
Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be
8 Johnson Controls Unitary Products
5167798-YTG-J-0218
installed to prevent the flue exhaust from entering nearby fresh air intakes.
Gas Heat High Altitude Kit - This kit converts a gas heat unit to operate at high altitudes, 2,000 to 6,000 feet. Conversion kits are available for natural gas and propane.
Gas Heat Propane Conversion Kit - This kit converts a gas-fired heater from natural gas to propane. It contains the main burner orifices and gas valve replacement springs.
Gas Piping Kit - Contains pipe nipples, fittings and gas cock required for gas supply connection with external shut off.
Electric Heaters - The electric heaters range from 9 kW to 54kW and are available in all the voltage options of the base units. The 54kW/208-240 volt, Field-installed heater kit is not available with VAV units due to a lack of space to accommodate the heater’s fuse block accessory.
Cooling units include an adapter panel for easy installation of the electric heaters. Necessary hardware and connectors are included with the heaters. All heaters are intended for single point power supply.
Metal Frame Filter Kit - Metal frame with polyester filter medium.
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available in 8” and 14” heights. For applications with security concerns, burglar bars are available for the duct openings of the roof curbs.
Roof Curb Transition - Single Piece Adapter (10” High) ­Roof curbs for transitioning from Sunline™ units to Predator
®
units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24­volt electronic and electro-mechanical thermostats. All units (with or without an economizer) operate with two­stage heat/two-stage cool or two-stage cooling only thermostats, depending upon unit configuration.
Johnson Controls Unitary Products 9
5167798-YTG-J-0218
Accessories
Field Installed Accessories - Non-Electrical
MODEL VOLTAGE DESCRIPTION WHERE USED
1BD0408 All Burglar Bars, Downflow All Cabinets 1CG0419 All Coil Guard (Electric / Electric Models), 50” Tall Standard Cabinets 1CG0420 All Coil Guard (Gas / Electric Models), 50" Tall Standard Cabinets 1CG0427 All Coil Guard (Electric / Electric Models), 42” Tall Cabinets 1CG0428 All Coil Guard (Gas / Electric Models), 42" Tall Cabinets
All Tall (50") Standard Cabinets, (Excludes 12.5T "V" 1HG0411 All Hail Guard Kit 1HG0415 All Hail Guard Kit All Short (42") Standard Cabinets 1FE0411 All Flue Exhaust Extension Kit All Cabinets 1FF0414 All 2" only Metal Filter Frame Kit All Tall 50" Cabinets 1FF0415 All 2" only Metal Filter Frame Kit All Tall 42" Cabinets 1FL0402 All Permanent 2" only Filter Kit Includes (4) Four Filters) All Tall 50" Cabinets 1FL0423 All Permanent 2" only Filter Kit (Includes (4) four Filters) All Tall 42" Cabinets 1GP0405 All Gas Piping Kit All Cabinets 1HA0442 All High Altitude Kit for Natural Gas All 6 - 12T Cabinets 1HA0443 All High Altitude Kit for Propane All 6 - 12T Cabinets 1NP0442 All Propane Conversion Kit All 6 - 12T Cabinets 1RC0470 All Roof Curb, 8" Height All Cabinets 1RC0471 All Roof Curb, 14" Height All Cabinets
1RC0472 All
1WC0412 All
Roof Curb, Transition (7.5 T thru 12.5T Sunline to Predator 3- 12T) All Cabinets Wooden Crate for extra protection during shipping and handling
cabinets)
Standard Cabinets Only (not applicable to units 119" in
length)
Field Installed Accessories - Electric Heat
MODEL VOLTAGE DESCRIPTION WHERE USED
2TP04520925 230
9kW Electric Heat All 50" Cabinet 6.5 and 8.5 Ton Models2TP04520946 460 2TP04520958 575 2TP04531825 230
18kW Electric Heat All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04531846 460 2TP04521858 575 2TP04532425 230
24kW Electric Heat All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04532446 460 2TP04522458 575 2TP04533625 230
36kW Electric Heat All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04533646 460 2TP04523658 575 2TP04525425 230
54kW Electric Heat All 50" 10 and 12.5 Ton Models2TP04525446 460 2TP04525458 575 2TP04540925 230
9kW Electric Heat All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04540946 460 2TP04540958 575 2TP04541825 230
18kW Electric Heat All 42" 6.5, 7.5 and 8.5 Ton Models2TP04541846 460 2TP04541858 575 2TP04542425 230
24kW Electric Heat All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04542446 460 2TP04542458 575 2TP04543625 230
36kW Electric Heat All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04543646 460 2TP04543658 575
10 Johnson Controls Unitary Products
5167798-YTG-J-0218
Accessories (Continued)
Field Installed Accessories - Fresh Air
MODEL VOLTAGE DESCRIPTION WHERE USED
1FA0413 All Manual Outside Air Damper 0-35%, Downflow All Cabinets 1FA0414 All Manual Outside Air Damper 0-100%, Downflow All Cabinets
1EH0408 All 2EC0401 All Single Enthalpy Control All Cabinets
2EC0402 All Dual Enthalpy Control (Includes 2 Sensors) All Cabinets
2EE04707624 All
2EE04707424 All
2EE04706924 All Horizontal Economizer without Barometric Relief All Cabinets 2MD04703824 All Motorized Damper, Downflow without Barometric Relief All Cabinets 2MD04703924 All Motorized Damper, Horizontal without Barometric Relief All Cabinets 2PE04704706* 230 Power Exhaust 230V Downflow or Horizontal All Cabinets 2PE04704746* 460 Power Exhaust 460V Downflow or Horizontal All Cabinets 2PE04704758* 575 Power Exhaust 575V Downflow or Horizontal All Cabinets
Barometric Relief Kit for Power Exhaust, Horizontal
Application
Economizer for Downflow, End Return Horizontal, or
ERV Applications. Includes FA Hood, Exhaust Hood w/
Baro Relief
Economizer for Downflow, End Return Horizontal, or
ERV Applications. Includes FA Hood, Exhaust Hood w/
Baro Relief
Field Installed Accessories - Controls
MODEL VOLTAGE DESCRIPTION WHERE USED
2AP0401 All Air Proving Switch All Units 2AQ04700324 All CO2 Space Accessory All Units 2AQ04700424 All CO2 Unit Accessory All Units 2DF0402 All Dirty Air Switch All Units
Wall Mounted humidity sensor-For use with MagnaDry 2SH0401 All
2SD04700824 All Smoke Detector for Supply All Gen 5 units and greater with 2" & 4" Filters 2SD04700924 All Smoke Detector for Return All Gen 5 units and greater with 2" & 4" Filters 2SD04701024 All Smoke Detector for Supply and Return All Gen 5 units and greater with 2" & 4" Filters S1-YK­MAP1810-0P
S1-MP-PRTKIT­0P
Reheat or space humidity input to Smart Equipment™
board.
MAP (Mobile Access Portal) Gateway- For use with
All
Smart Equipment™ Control.
MAP (Multiple Access Portal) Gateway Kit- Replacement
MAP gateway protective case, lanyard and
All
communication cable. Use only to replace worn or
damaged components.
All Cabinets
All 50" Cabinets
All 42" Cabinets
All Cabinets
All Units
All Units
Field Installed Accessories - Electrical
MODEL VOLTAGE DESCRIPTION WHERE USED
2LA04704632 All Low Ambient Kit 3 - 10T Units 2LA04704633 All Low Ambient Kit 12.5T Units

Guide Specifications

GENERAL
Units shall be manufactured by York International Unitary Products in an ISO 9001 certified facility. YORK® Predator units are convertible single packages with a common footprint cabinet and common roof curb for all 6.5 through 12.5 ton models. All units have two compressors with independent R­410A refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All Predator units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged with R-410A, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow. Independent economizer designs are used on
®
side and down discharge applications, as well as all tonnage sizes. Predator
®
units are available in the following configurations: cooling only, cooling with electric heat, cooling with gas heat, heat pump, and heat pump with electric heat. Electric heaters are available as factory-installed options or field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/ Elec), designed for outdoor installation. They shall have built in
®
field convertible duct connections for down discharge supply/return or horizontal discharge supply/return and be available with factory installed options or field installed accessories. The units shall be factory wired, piped and charged with R-410A refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and AHRI test procedures. Units
Johnson Controls Unitary Products 11
5167798-YTG-J-0218
shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with exterior surfaces coated with a non-chalking, powder paint finish, certified at 1000 hour salt spray test per ASTM-B117 standards. Indoor blower sections shall be insulated with up to 1” thick insulation coated on the airside. Either aluminum foil faced or elastometric rubber insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with toolless access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2” filters shall be furnished as standard and be accessible through hinged access door. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating bypass of the coils. Condensate pan shall be slide out design, constructed of a non corrosive material, internally sloped and conforming to ASHRAE 62-B9 standards. Condensate connection shall be a minimum of ¾” I.D. female and be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the ser­vice factor. Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with forward curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Entire blower assembly and motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and staged independently. A cleaning window shall be provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or – 10% of the unit nameplate voltage.
b. Shall have internal spring isolation an d sound muffling to
minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b. Evaporator coils shall be of th e direct expansion, draw-
thru design.
c. Condenser coils shall have Mirco-Channel aluminum
tube, aluminum fins.
d. Condenser coils shall be of the direct expansion, draw-
thru design.
Refrigerant Circuit and Refrigerant Safety Components shall include:
a. Independent fixed-orifice or thermally operated
expansion devices.
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
d. The unit shall have two independent re frigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.
1.Loss-of-charge/Low-pressure switch.
2.High-pressure switch.
3.Freeze condition sensor on evaporator coil. If any of these safety devices trip, the LCD screen will display the alarm message.
c. Unit shall incorporate "AUTO RESET" compressor over
temperature, over current protection.
d. Unit shall operate wi th conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
e. Unit control board shall have on-board diagnostics and
fault message display.
f. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to a selectable value as low as 0 °F.
g. Control board shall monitor each refrigerant safety switch
independently.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of aluminized steel and shall be designed with induced draft com-
12 Johnson Controls Unitary Products
5167798-YTG-J-0218
bustion with post purge logic, energy saving direct spark igni­tion, and redundant main gas valve. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 40 ºF. Burners shall be of the in-shot type, con­structed of aluminum-coated steel. All gas piping shall enter the unit cabinet at a single location, through either the side or bot­tom, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol­lowing minimum protection:
a. Primary and auxiliary high-temperature limit switches. b. Induced draft pressure sensor. c. Flame roll out switch (manual reset). d. Flame proving controls. e. All two stage units shall have two in dependent stages of
capacity (60% 1
st
stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements, shall be provided in a range of 9 thru 54 KW, offering two states of capacity all sizes. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating element system from operating at an excessive temperature. The Heat­ing Section assembly shall slide out of the unit for easy mainte­nance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of AHRI Stan­dard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 ºF outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Y ears, Heat Exchanger – 10 Yea rs, Elect. Heat Elem. – 5 Years, Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
DRY BULB AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall be designed to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/sq. ft. at 1" of static
pressure. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief and power exhaust.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2- position, spring-return damper actuator. A unit­mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de­energized. Dampers shall fully close on power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
ALTERNATE INDOOR BLOWER MOTOR – For applications with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow.
Variable Air Volume (VAV) – The VAV option using a variable frequency drive (VFD) shall be available on 6.5 through 12.5 ton, models for applications requiring a constant supply-duct static pressure. Units equipped for VAV shall be controlled by a duct pressure transducer with a 0 - 5” WC pressure range. The pressure transducer shall provide a 0 - 5 VDC output signal to a VAV control board which, in turn shall provide a 2 - 10 VDC speed reference signal to the VFD. The VAV control board shall operate using factory-installed Supply Air, Return Air and Outside Air Temperature Sensors with a nominal resistance of 10,000 Ohms. Units equipped with VFD’s shall have factory-installed manual bypass as an option.
CONVENIENCE OUTLET (POWERED/NON-POWERED) Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors.
ELECTRIC HEAT - Electric Heaters range from 9 kW to 54 kW and are available in all the voltage options of the base unit.
PHASE MONITOR - Designed to prevent damage in out­of-phase condition.
COIL GUARD - Designed to prevent condenser coil damage.
BAS CONTROLS HARDWARE - Include supply air sensor, return air sensor, dirty filter indicator and air proving switch.
DIRTY FILTER SWITCH – This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high­pressure drop across the filters.
Johnson Controls Unitary Products 13
5167798-YTG-J-0218
BREAKER – An HACR breaker can be factory installed on gas heat units or cooling units with electric heat.
DISCONNECT SWITCH - A disconnect can be factory installed on a cooling only units sized for the largest electric heat available.
STAINLESS STEEL HEAT EXCHANGER – For applications in a corrosive environment, this option provides a full stainless steel heat exchanger assembly.
SMOKE DETECTOR – A smoke detector can be factory mounted and wired in the supply and/or return air compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
ROOF CURB - 14” and 8” high, full perimeter knockdown curb, with hinged design for quick assembly.
BAROMETRIC RELIEF DAMPER – (Unit mounted – Downflow, Duct Mounted – Horizontal) – Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit during economizer operation.
PROPANE CONVERSION KIT – Contains new orifices and gas valve springs to convert from natural to L.P. gas.
ECONOMIZER (Downflow and Horizontal flow)
POWER EXHAUST – (Unit mount – Downflow, Duct mount – Horizontal flow)
DUAL ENTHALPY KIT - Provides a second input to economizer to monitor return air.
14 Johnson Controls Unitary Products

Physical Data

ZF078-150 Physical Data

5167798-YTG-J-0218
Component
ZF078 ZF090 ZF102 ZF120 ZF150
Models
Nominal Tonnage 6.5 7.5 8.5 10 12.5
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Mbh) 81000 86500 104000 126000 156000 AHRI net capacity (Mbh) 78000 84000 101000 118000 149500 EER 11.2 11.2 IEER with Constant Volume 12.91/12.7 IEER with Intellispeed 13.9 IEER with VAV 13.41/13.2
1
/13.7
2 2 2
12.91/12.7
2
/11.0
11.21/11.0
- 12.91/12.7
13.1 14.01/13.8
2
13.11/12.9
2 2 2 2
11.21/11.0
14.41/14.2
13.21/13.0
2
11.01/10.8
2
--
2 2
12.81/12.6
12.61/12.4
2
2
1
CFM 2500 2500 3400 4000 4050 System power (KW) 6.95 7.87 8.90 10.70 13.40 Refrigerant type R-410A R-410A R-410A R-410A R-410A Refrigerant charge (lb-oz)
System 1 4-8 4-10 5-12 8-4 7-10 System 2 4-8 4-8 5-12 7-2 7-4
AHRI HEATING PERFORMANCE
Heating model N12 N18 N12 N18 N12 N18 N18 N24 N18 N24 Heat input (K Btu) 120 180 120 180 120 180 180 240 180 240 Heat output (K Btu) 96 144 96 144 96 144 144 192 144 192 AFUE % ---------­Steady state efficiency (%) 80808080808080808080 No. burners 4646466868 No. stages 2
3
3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
2 Temperature Rise Range (ºF) 20-50 35-65 15-45 30-60 10-40 25-55 20-50 35-65 10-40 25-55 Gas Limit Setting (ºF) 165 165 165 165 215 195 195 150 195 150 Gas piping connection (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
DIMENSIONS (inches)
Length 89 89 89 89 119-1/2 Width 5959595959 Height 42 42 50-3/4 50-3/4 50-3/4
OPERATING WT. (lbs.) 860 880 1007 1060 1253
COMPRESSORS
4
Type Recip Scroll Recip Recip Scroll Quantity 2 2 2 2 2 Unit Capacity Steps (%) 50 / 100 50 / 100 50 / 100 50 / 100 50 / 100
CONDENSER COIL DATA
Face area (Sq. Ft.) 18.5 23.8 29.0 29.0 29 Rows 11111 Fins per inch 23 23 23 23 23 Tube diameter (in.)/mm .71/18 .71/18 .71/18 1/25 1/25
Circuitry Type
2-pass
Microchannel
2-pass
Microchannel
2-pass
Microchannel
2-pass
Microchannel
2-pass
Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 10.6 10.6 13.2 13.2 13.2 Rows 33344 Fins per inch 15 15 15 15 15 Tube diameter 0.375 0.375 0.375 0.375 0.375
Johnson Controls Unitary Products 15
5167798-YTG-J-0218
ZF078-150 Physical Data (Continued)
Component
ZF078 ZF090 ZF102 ZF120 ZF150
Models
Nominal Tonnage 6.5 7.5 8.5 10 12.5
Circuitry Type Intertwined Intertwined Intertwined Intertwined Intertwined Refrigerant control TXV TXV TXV TXV TXV
CONDENSER FAN DATA
Quantity of Fans 2 2 2 2 4 Fan diameter (Inch) 24 24 24 24 24 Type Prop Prop Prop Prop Prop Drive type Direct Direct Direct Direct Direct Quantity of motors 2 2 2 2 4 Motor HP each 1/3 1/3 3/4 3/4 3/4 No. speeds 1 1 1 1 1 RPM 850 850 1110 1110 1110 Total CFM 6200 7600 9500 9500 11200
BELT DRIVE EVAP FAN DATA
Quantity 1 1 1 1 1 Fan Size (Inch) 12 x 12 12 x 12 15 x 15 15 x 15 15 x 15 Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Motor Sheave 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VP56 Blower Sheave AK74 AK64 AK74 AK61 AK89 AK74 AK84 AK74 AK74 BK77 Belt A49 A49 A49 A49 A56 A54 A56 A54 A54 BX55 Motor HP each 1-1/2 2 1-1/2 3 2 3 2 3 3 5 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725 Frame size 56 56 56 56 56 56 56 56 56 184T
FILTERS
Quantity - Size
4 - (24 x 16 x 2)
5, 6
4 - (24 x 16 x 2)
4 - (24 x 16 x 4)74 - (24 x 16 x 4)64 - (24 x 20 x 4)64 - (24 x 20 x 4)64 - (24 x 20 x 4)
4, 5
4 - (24 x 20 x 2)
4, 5
4 - (24 x 20 x 2)
4, 5
4 - (24 x 20 x 2)
1. Cooling Only Unit or Cooling Unit with Electric Heat
2. Cooling Unit with Gas Heat
3. 1ST Stage 60% of 2nd Stage
4. ZF090 and ZF150 have crankcase heaters standard
5. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3
6. 2 In. Pleated, Optional, MERV 8
7. 4 In. Pleated, Optional, MERV 13
4, 5
6
16 Johnson Controls Unitary Products

ZF078-150 Unit Limitations

5167798-YTG-J-0218
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120 (10)
150
(12.5)
Model Unit Voltage
208/230-3-60 187 252 125
ZF
ZF
ZF
ZF
ZF
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (° F)
Johnson Controls Unitary Products 17
5167798-YTG-J-0218

Capacity Performance

ZF078-150 Cooling Capacities

ZF078 (6.5 Ton)

Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB (°F)
77 102.9 5.0 41.5 34.0 26.6 - - - 96.2 5.6 39.9 32.5 25.0 - - ­72 94.8 5.0 53.8 46.4 38.9 31.5 - - 88.3 5.5 51.6 44.2 36.7 29.3 - ­67 86.7 5.0 66.1 58.7 51.3 43.8 36.4 - 80.3 5.5 63.3 55.8 48.4 41.0 33.6 ­62 79.2 5.0 79.2 72.4 61.4 54.0 46.6 39.1 72.8 5.4 72.8 69.4 58.6 51.1 43.7 36.3 77 106.6 5.0 46.7 38.0 29.3 - - - 99.6 5.6 44.9 36.2 27.6 - - ­72 98.2 5.0 60.3 51.5 42.8 34.1 - - 91.4 5.5 57.8 49.1 40.4 31.7 - ­67 89.8 5.0 73.8 65.1 56.3 47.6 38.9 - 83.1 5.5 70.6 61.9 53.3 44.6 35.9 ­62 82.0 5.0 82.0 77.5 67.5 58.8 50.0 41.3 75.4 5.4 75.4 73.1 64.4 55.8 47.1 38.4 57 79.2 4.9 79.2 79.2 71.1 62.4 53.6 44.9 74.4 5.4 74.4 74.4 66.4 57.7 49.1 40.4 77 110.2 5.0 52.0 41.9 31.9 - - - 103.0 5.6 49.9 40.0 30.1 - - ­72 101.6 5.0 66.7 56.7 46.7 36.6 - - 94.4 5.5 63.9 54.0 44.1 34.2 - ­67 92.9 5.0 81.5 71.4 61.4 51.4 41.3 - 85.9 5.5 78.0 68.1 58.1 48.2 38.3 ­62 84.8 5.0 84.8 82.5 73.6 63.6 53.5 43.5 77.9 5.4 77.9 76.8 70.3 60.4 50.5 40.6 57 81.9 4.9 81.9 81.9 77.5 67.5 57.4 47.4 76.9 5.4 76.9 76.9 72.5 62.5 52.6 42.7 77 113.9 5.0 57.2 45.9 34.5 - - - 106.3 5.6 54.9 43.7 32.6 - - ­72 104.9 5.0 73.2 61.9 50.5 39.2 - - 97.5 5.5 70.1 58.9 47.8 36.6 - ­67 95.9 5.0 89.2 77.8 66.5 55.2 43.8 - 88.7 5.5 85.3 74.2 63.0 51.8 40.7 ­62 87.6 5.0 87.6 87.6 79.7 68.3 57.0 45.7 80.4 5.5 80.4 80.4 76.2 65.0 53.8 42.7 57 84.6 4.9 84.6 84.6 83.9 72.6 61.2 49.9 79.4 5.4 79.4 79.4 78.5 67.3 56.2 45.0 72 107.2 5.0 78.2 65.9 53.6 41.4 - - 99.5 5.6 75.3 63.1 51.0 38.8 - ­67 98.0 5.0 94.6 82.9 70.6 58.4 46.1 - 90.5 5.5 88.8 79.3 67.2 55.0 42.9 ­62 89.5 5.0 89.5 89.5 85.5 73.3 61.0 48.7 82.0 5.5 82.0 82.0 79.9 67.8 55.6 43.5 57 86.5 4.9 86.5 86.5 86.1 73.8 61.6 49.3 81.0 5.4 81.0 81.0 80.5 68.4 56.2 44.1 72 109.4 5.0 83.1 70.0 56.8 43.6 - - 101.4 5.6 80.4 67.3 54.2 41.0 - ­67 100.1 5.0 100.1 87.9 74.7 61.6 48.4 - 92.3 5.5 92.3 84.5 71.4 58.3 45.1 ­62 91.4 5.0 91.4 91.4 91.4 78.2 65.0 51.8 83.6 5.5 83.6 83.6 83.6 70.5 57.4 44.2 57 88.3 4.9 88.3 88.3 88.3 75.1 61.9 48.7 82.5 5.4 82.5 82.5 82.5 69.4 56.3 43.1
77 89.6 6.1 38.3 30.9 23.5 - - - 82.4 6.7 33.7 28.5 21.2 - - ­72 81.7 6.1 49.3 41.9 34.5 27.1 - - 74.8 6.6 46.6 39.3 31.9 24.6 - ­67 73.9 6.0 60.4 53.0 45.6 38.2 30.8 - 67.2 6.5 59.4 50.0 42.7 35.4 28.1 ­62 66.5 5.9 66.5 66.5 55.7 48.3 40.9 33.5 61.3 6.4 61.3 61.3 51.7 44.4 37.1 29.8 77 92.6 6.1 43.0 34.4 25.8 - - - 85.1 6.7 40.4 31.9 23.4 - - ­72 84.5 6.1 55.2 46.6 38.0 29.4 - - 77.3 6.6 52.3 43.8 35.3 26.8 - ­67 76.5 6.0 67.4 58.8 50.2 41.6 33.0 - 69.4 6.5 64.2 55.7 47.2 38.7 30.2 ­62 68.7 5.9 68.7 68.7 61.4 52.8 44.2 35.6 63.3 6.4 63.3 63.3 57.2 48.6 40.1 31.6 57 69.5 5.9 69.5 69.5 61.7 53.1 44.5 35.9 61.4 6.4 61.4 61.4 53.9 45.4 36.9 28.4 77 95.7 6.2 47.8 38.0 28.2 - - - 87.8 6.8 47.1 35.3 25.6 - - ­72 87.3 6.1 61.1 51.3 41.5 31.8 - - 79.7 6.7 58.1 48.4 38.7 29.0 - ­67 79.0 6.0 74.4 64.7 54.9 45.1 35.3 - 71.7 6.5 69.0 61.4 51.7 42.0 32.3 ­62 71.0 5.9 71.0 71.0 67.0 57.2 47.4 37.6 65.3 6.4 65.3 65.3 62.6 52.9 43.2 33.5 57 71.8 6.0 71.8 71.8 67.4 57.6 47.8 38.0 63.3 6.4 63.3 63.3 59.0 49.3 39.6 29.9 77 98.7 6.2 52.6 41.6 30.6 - - - 90.5 6.8 53.7 38.7 27.8 - - ­72 90.1 6.1 67.0 56.0 45.1 34.1 - - 82.2 6.7 63.8 52.9 42.0 31.1 - ­67 81.5 6.0 81.5 70.5 59.5 48.5 37.5 - 73.9 6.6 73.9 67.1 56.2 45.3 34.4 ­62 73.3 6.0 73.3 73.3 72.7 61.7 50.7 39.7 67.3 6.5 67.3 67.3 68.0 57.2 46.3 35.4 57 74.1 6.0 74.1 74.1 73.1 62.1 51.1 40.1 65.3 6.4 65.3 65.3 64.1 53.2 42.4 31.5 72 91.7 6.1 72.4 60.3 48.3 36.3 - - 83.6 6.7 69.1 57.1 45.1 33.2 - ­67 83.0 6.0 83.0 75.8 63.8 51.7 39.7 - 75.2 6.6 75.1 70.9 60.4 48.4 36.5 ­62 74.6 6.0 74.6 74.6 74.3 62.2 50.2 38.2 68.5 6.5 68.5 68.5 68.9 56.9 44.9 33.0 57 75.5 6.0 75.5 75.5 74.9 62.9 50.9 38.8 66.4 6.4 66.4 66.4 65.9 53.9 41.9 30.0 72 93.4 6.1 77.7 64.6 51.5 38.4 - - 85.1 6.7 74.3 61.3 48.3 35.2 - ­67 84.4 6.0 84.4 81.1 68.1 55.0 41.9 - 76.4 6.6 76.4 74.8 64.6 51.5 38.5 ­62 75.9 6.0 75.9 75.9 75.9 62.8 49.7 36.6 69.7 6.5 69.7 69.7 69.7 56.6 43.6 30.5 57 76.8 6.0 76.8 76.8 76.8 63.7 50.6 37.5 67.6 6.4 67.6 67.6 67.6 54.5 41.5 28.5
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
18 Johnson Controls Unitary Products
5167798-YTG-J-0218
ZF078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB (°F)
77 75.2 7.3 29.2 26.1 18.9 - - - 68.0 7.9 28.3 22.9 16.6 - - ­72 67.9 7.1 43.8 36.6 29.3 22.1 - - 60.9 7.7 41.0 33.9 26.8 19.6 - ­67 60.5 7.0 58.4 47.1 39.8 32.6 25.4 - 53.8 7.5 53.8 44.1 36.9 29.8 22.7 ­62 56.1 6.8 56.1 56.1 47.7 40.5 33.3 26.0 50.9 7.3 50.9 50.9 43.7 36.6 29.4 22.3 77 77.6 7.3 37.8 29.4 20.9 - - - 70.1 7.9 37.5 26.8 18.5 - - ­72 70.0 7.2 49.4 41.0 32.6 24.2 - - 62.7 7.7 46.5 38.1 29.8 21.5 - ­67 62.4 7.0 61.0 52.6 44.2 35.8 27.4 - 55.4 7.5 55.4 49.5 41.2 32.9 24.5 ­62 57.8 6.9 57.8 57.8 52.9 44.5 36.1 27.7 52.4 7.4 52.4 52.4 48.7 40.4 32.1 23.8 57 53.2 6.8 53.2 53.2 46.1 37.7 29.2 20.8 45.1 7.2 45.1 45.1 38.3 29.9 21.6 13.3 77 80.0 7.4 46.3 32.6 23.0 - - - 72.1 8.0 46.8 30.8 20.4 - - ­72 72.2 7.2 55.0 45.4 35.8 26.2 - - 64.6 7.8 51.9 42.4 32.9 23.4 - ­67 64.3 7.0 63.6 58.2 48.6 39.0 29.4 - 57.0 7.6 57.0 54.9 45.4 35.9 26.4 ­62 59.6 6.9 59.6 59.6 58.2 48.6 39.0 29.4 53.9 7.4 53.9 53.9 53.8 44.3 34.8 25.3 57 54.8 6.8 54.8 54.8 50.6 41.0 31.4 21.8 46.4 7.2 46.4 46.4 42.2 32.7 23.2 13.7 77 82.3 7.4 54.9 35.9 25.1 - - - 74.2 8.0 56.0 34.7 22.3 - - ­72 74.3 7.2 60.6 49.8 39.0 28.2 - - 66.4 7.8 57.3 46.7 36.0 25.3 - ­67 66.2 7.1 66.2 63.7 52.9 42.1 31.4 - 58.6 7.6 58.6 58.6 49.7 39.0 28.3 ­62 61.4 7.0 61.4 61.4 63.4 52.6 41.9 31.1 55.5 7.5 55.5 55.5 55.5 48.1 37.4 26.8 57 56.5 6.9 56.5 56.5 55.2 44.4 33.6 22.8 47.7 7.3 47.7 47.7 46.2 35.6 24.9 14.2 72 75.5 7.3 65.8 53.9 42.0 30.1 - - 67.4 7.8 62.5 50.7 38.9 27.0 - ­67 67.3 7.1 67.3 66.1 57.0 45.1 33.2 - 59.5 7.6 59.5 59.5 53.6 41.8 30.0 ­62 62.4 7.0 62.4 62.4 63.4 51.5 39.7 27.8 56.3 7.5 56.3 56.3 56.3 46.2 34.4 22.6 57 57.4 6.9 57.4 57.4 56.8 44.9 33.0 21.1 48.4 7.3 48.4 48.4 47.7 35.9 24.1 12.3 72 76.8 7.3 71.0 58.0 45.0 32.0 - - 68.5 7.9 67.6 54.7 41.7 28.8 - ­67 68.4 7.1 68.4 68.4 61.1 48.1 35.1 - 60.5 7.7 60.5 60.5 57.6 44.6 31.7 ­62 63.4 7.0 63.4 63.4 63.4 50.4 37.5 24.5 57.2 7.5 57.2 57.2 57.2 44.3 31.3 18.4 57 58.4 6.9 58.4 58.4 58.4 45.4 32.4 19.4 49.1 7.4 49.1 49.1 49.1 36.2 23.3 10.3
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 19
5167798-YTG-J-0218

ZF090 (7.5 Ton)

Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB (°F)
77 112.9 4.9 50.2 41.8 33.4 - - - 109.6 6.0 47.9 40.1 32.4 - - ­72 104.5 5.0 63.5 55.1 46.7 38.3 - - 100.0 6.0 60.0 52.3 44.5 36.8 - ­67 96.0 5.0 76.8 68.4 60.0 51.6 43.2 - 90.4 6.0 72.2 64.4 56.7 48.9 41.2 ­62 91.1 4.8 91.1 75.9 68.7 60.3 51.9 43.5 83.2 5.9 83.2 75.6 66.6 58.9 51.1 43.4 77 116.4 5.1 53.9 45.0 36.1 - - - 113.0 6.1 52.3 43.7 35.1 - - ­72 107.6 5.1 68.3 59.4 50.5 41.5 - - 103.2 6.0 65.5 56.9 48.2 39.6 - ­67 98.9 5.2 82.7 73.7 64.8 55.9 47.0 - 93.3 6.0 78.7 70.0 61.4 52.8 44.1 ­62 93.9 5.0 93.9 83.7 74.3 65.3 56.4 47.5 85.9 6.0 85.9 80.8 72.1 63.5 54.9 46.3 57 75.0 5.2 75.0 75.0 69.4 60.5 51.6 42.7 78.0 6.1 78.0 78.0 71.8 63.1 54.5 45.9 77 119.8 5.2 57.7 48.2 38.8 - - - 116.5 6.1 56.8 47.3 37.8 - - ­72 110.8 5.3 73.1 63.7 54.2 44.8 - - 106.4 6.1 71.0 61.5 51.9 42.4 - ­67 101.8 5.4 88.6 79.1 69.7 60.2 50.8 - 96.2 6.1 85.1 75.6 66.1 56.6 47.1 ­62 96.7 5.1 96.7 91.6 79.8 70.4 60.9 51.5 88.5 6.0 88.5 86.0 77.7 68.2 58.7 49.2 57 77.2 5.4 77.2 77.2 74.6 65.2 55.7 46.3 80.4 6.1 80.4 80.4 77.3 67.8 58.2 48.7 77 123.2 5.4 61.4 51.4 41.5 - - - 120.0 6.2 61.2 50.9 40.5 - - ­72 114.0 5.5 77.9 68.0 58.0 48.0 - - 109.5 6.2 76.4 66.0 55.6 45.3 - ­67 104.7 5.5 94.4 84.5 74.5 64.6 54.6 - 99.0 6.2 91.6 81.2 70.8 60.4 50.0 ­62 99.5 5.3 99.5 99.5 85.3 75.4 65.4 55.5 91.2 6.1 91.2 91.2 83.2 72.8 62.4 52.1 57 79.4 5.6 79.4 79.4 79.4 69.8 59.8 49.9 82.8 6.2 82.8 82.8 82.8 72.4 62.0 51.6 72 115.0 5.4 84.2 72.8 61.4 50.0 - - 110.9 6.1 82.3 70.6 59.0 47.3 - ­67 105.7 5.4 100.6 90.2 78.8 67.4 56.0 - 100.3 6.1 96.5 86.7 75.0 63.4 51.7 ­62 100.4 5.2 100.4 100.4 93.1 81.7 70.3 58.9 92.3 6.0 92.3 92.3 88.2 76.5 64.8 53.1 57 80.1 5.4 80.1 80.1 80.1 68.9 57.5 46.1 83.8 6.1 83.8 83.8 83.8 72.1 60.4 48.7 72 116.1 5.2 90.4 77.6 64.7 51.9 - - 112.2 6.0 88.2 75.2 62.3 49.3 - ­67 106.7 5.3 106.7 96.0 83.1 70.3 57.5 - 101.5 6.0 101.5 92.2 79.3 66.3 53.3 ­62 101.4 5.1 101.4 101.4 100.9 88.0 75.2 62.4 93.4 6.0 93.4 93.4 93.1 80.2 67.2 54.2 57 80.8 5.3 80.8 80.8 80.8 68.0 55.1 42.3 84.8 6.1 84.8 84.8 84.8 71.8 58.9 45.9
77 106.2 7.1 45.6 38.5 31.4 - - - 96.9 8.0 38.4 32.9 25.9 - - ­72 95.5 7.0 56.6 49.5 42.4 35.3 - - 88.1 7.9 52.0 45.0 38.0 30.9 - ­67 84.8 6.9 67.6 60.5 53.4 46.3 39.2 - 79.3 7.9 65.6 57.1 50.0 43.0 36.0 ­62 75.3 7.0 75.3 75.3 64.5 57.4 50.3 43.2 72.7 7.9 72.7 71.6 60.1 53.0 46.0 39.0 77 109.7 7.0 50.7 42.4 34.1 - - - 99.7 7.9 45.2 36.8 28.4 - - ­72 98.7 7.0 62.7 54.4 46.0 37.7 - - 90.7 7.9 58.5 50.1 41.7 33.3 - ­67 87.7 6.9 74.6 66.3 58.0 49.6 41.3 - 81.7 7.8 71.8 63.4 55.0 46.6 38.1 ­62 77.8 7.0 77.8 77.8 70.0 61.7 53.4 45.0 74.9 7.9 74.9 74.1 66.0 57.5 49.1 40.7 57 80.9 6.9 80.9 80.9 74.1 65.7 57.4 49.1 76.5 7.8 76.5 75.7 68.1 59.7 51.3 42.8 77 113.3 7.0 55.9 46.3 36.7 - - - 102.6 7.8 52.0 40.6 30.9 - - ­72 101.9 6.9 68.8 59.2 49.6 40.1 - - 93.3 7.8 65.0 55.2 45.4 35.6 - ­67 90.5 6.8 81.7 72.1 62.5 53.0 43.4 - 84.0 7.8 77.9 69.7 59.9 50.1 40.3 ­62 80.3 6.9 80.3 80.3 75.6 66.0 56.4 46.8 77.0 7.8 77.0 76.6 71.9 62.1 52.3 42.5 57 83.5 6.9 83.5 83.5 79.9 70.4 60.8 51.2 78.7 7.8 78.7 78.3 74.2 64.4 54.6 44.8 77 116.8 7.0 61.1 50.3 39.4 - - - 105.5 7.8 58.7 44.5 33.3 - - ­72 105.1 6.9 74.9 64.1 53.3 42.5 - - 95.9 7.7 71.4 60.2 49.1 37.9 - ­67 93.4 6.8 88.8 77.9 67.1 56.3 45.5 - 86.4 7.7 84.1 76.0 64.8 53.6 42.5 ­62 82.9 6.9 82.9 82.9 81.1 70.3 59.5 48.6 79.2 7.7 79.2 79.2 77.8 66.6 55.4 44.3 57 86.1 6.8 86.1 86.1 85.8 75.0 64.2 53.3 80.9 7.7 80.9 80.9 80.2 69.1 57.9 46.7 72 106.7 6.9 80.5 68.5 56.6 44.6 - - 97.2 7.7 76.3 64.2 52.1 39.9 - ­67 94.8 6.8 92.5 83.2 71.2 59.3 47.3 - 87.5 7.7 86.4 80.4 68.7 56.6 44.5 ­62 84.1 6.9 84.1 84.1 83.3 71.3 59.3 47.3 80.2 7.7 80.2 80.2 79.5 67.4 55.3 43.2 57 87.5 6.8 87.5 87.5 87.3 75.3 63.4 51.4 81.9 7.7 81.9 81.9 81.6 69.5 57.4 45.3 72 108.3 6.9 86.1 72.9 59.8 46.7 - - 98.5 7.7 81.1 68.1 55.0 42.0 - ­67 96.2 6.8 96.2 88.5 75.4 62.2 49.1 - 88.7 7.7 88.7 84.8 72.7 59.6 46.6 ­62 85.4 6.9 85.4 85.4 85.4 72.3 59.2 46.1 81.2 7.7 81.2 81.2 81.2 68.2 55.1 42.1 57 88.8 6.8 88.8 88.8 88.8 75.7 62.6 49.4 83.0 7.7 83.0 83.0 83.0 70.0 56.9 43.9
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
20 Johnson Controls Unitary Products
5167798-YTG-J-0218
ZF090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB (°F)
77 87.5 8.8 31.3 27.3 20.4 - - - 78.2 9.7 23.0 21.8 14.9 - - ­72 80.7 8.8 47.5 40.5 33.5 26.6 - - 73.2 9.8 42.9 36.0 29.1 22.2 - ­67 73.8 8.9 63.7 53.7 46.7 39.7 32.8 - 68.3 9.9 61.8 50.3 43.4 36.5 29.6 ­62 70.1 8.8 70.1 67.8 55.6 48.7 41.7 34.7 67.5 9.8 67.5 64.1 51.2 44.3 37.4 30.5 77 89.7 8.7 39.6 31.2 22.7 - - - 79.7 9.6 34.1 25.5 17.0 - - ­72 82.7 8.8 54.3 45.8 37.3 28.8 - - 74.7 9.7 50.1 41.5 33.0 24.4 - ­67 75.7 8.8 68.9 60.5 52.0 43.5 35.0 - 69.6 9.8 66.1 57.5 49.0 40.4 31.9 ­62 71.9 8.8 71.9 70.4 61.9 53.4 44.9 36.4 68.9 9.7 68.9 66.6 57.8 49.2 40.7 32.1 57 72.1 8.8 72.1 70.6 62.1 53.6 45.1 36.6 67.6 9.7 67.6 65.4 56.1 47.5 39.0 30.4 77 92.0 8.7 48.0 35.0 25.0 - - - 81.3 9.5 45.2 29.3 19.1 - - ­72 84.7 8.7 61.1 51.1 41.1 31.1 - - 76.2 9.6 57.2 47.0 36.8 26.6 - ­67 77.5 8.7 74.2 67.2 57.2 47.2 37.2 - 71.0 9.7 70.4 64.8 54.6 44.4 34.2 ­62 73.7 8.7 73.7 72.9 68.1 58.1 48.1 38.1 70.3 9.6 70.3 69.2 64.4 54.2 44.0 33.8 57 73.8 8.7 73.8 73.1 68.4 58.4 48.4 38.4 69.0 9.6 69.0 67.9 62.6 52.4 42.2 32.0 77 94.2 8.6 56.4 38.8 27.3 - - - 82.9 9.4 56.3 33.0 21.2 - - ­72 86.8 8.6 67.9 56.4 44.9 33.4 - - 77.6 9.5 64.4 52.5 40.7 28.8 - ­67 79.4 8.6 79.4 74.0 62.5 51.0 39.5 - 72.4 9.6 72.4 72.0 60.2 48.3 36.5 ­62 75.5 8.6 75.5 75.5 74.4 62.9 51.4 39.9 71.8 9.5 71.8 71.8 71.0 59.2 47.3 35.5 57 75.6 8.6 75.6 75.6 74.6 63.1 51.6 40.1 70.4 9.5 70.4 70.4 69.1 57.2 45.4 33.5 72 87.7 8.6 72.0 59.8 47.5 35.3 - - 78.2 9.5 67.8 55.4 43.0 30.7 - ­67 80.2 8.6 80.2 77.5 66.2 54.0 41.7 - 72.9 9.6 72.9 72.9 63.7 51.3 39.0 ­62 76.2 8.6 76.2 76.2 75.7 63.5 51.2 39.0 72.3 9.5 72.3 72.3 71.9 59.6 47.2 34.8 57 76.4 8.6 76.4 76.4 75.9 63.7 51.5 39.2 70.9 9.5 70.9 70.9 70.2 57.9 45.5 33.1 72 88.6 8.6 76.1 63.2 50.2 37.3 - - 78.7 9.5 71.2 58.3 45.4 32.6 - ­67 81.1 8.6 81.1 81.1 69.9 57.0 44.0 - 73.5 9.6 73.5 73.5 67.2 54.4 41.5 ­62 77.0 8.6 77.0 77.0 77.0 64.1 51.1 38.1 72.8 9.5 72.8 72.8 72.8 59.9 47.1 34.2 57 77.2 8.6 77.2 77.2 77.2 64.2 51.3 38.3 71.4 9.5 71.4 71.4 71.4 58.5 45.6 32.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 21