YORK
common footprint cabinet and common roof curb for all 6.5
through 12.5 ton models. All units have two compressors with
independent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications and
can be easily installed on a roof curb, slab, or fra me.
All Predator
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
Predator
side airflow and down airflow, with corresponding economizer if
economizer option is desired.
Predator® units are available in the following configurations:
cooling only, cooling with electric heat, and cooling with gas
heat. Electric heaters are available as factory-installed options
or field-installed accessories.
All units provide constant supply air volume. A variab le ai r
volume (VAV) option, which features a variable frequency drive
(VFD), is available on 6.5 through 12.5 ton models.
Predator® units are convertible single packages with a
®
units are self-contained and assembled on rigid
®
units in all tonnage sizes are convertible between
ZF12.5 TON
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5167798-YTG-J-0218
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
York Sunline™ footprint to
the ZF Series footprints
are also available (field
installed accessory)
Base rails w/forklift
slots (three sides)
and lifting holes
Compressor #2
access (highefficiency
compressor)
Dual stage
cooling for
maximum
comfort
Second model
nameplate
inside hinged
access panel
Terminal block for
hi-voltage connection
Smart Equipment™ control board
w/screw connector for T-stat
wiring and network connections
Disconnect location
(optional disconnect switch)
Filter Access
(2” or 4” filter options)
Filter drier
(solid core)
Slide-out motor and
blower assembly for
easy adjustment
and service
Belt-drive
blower motor
Power ventor motor
20-guage aluminized
steel tubular heat
exchanger for long
life (stainless steel
option)
Two-stage gas
heating to maintain
warm, comfortable
temperature
Intelligent control
board for safe and
efficient operation
Compressor #
1 access
(high-e
fficiency compressor)
Toolless
door latch
Side entry power
and control wiring
knockouts
VFD Location (optional)
Slide-out drain pan
with 3/4” NPT,
female connection
ZF Series utilize Micro-Channel
Aluminum Tube/Aluminum Fin
Condenser
B = Standard Static
D = High Static
E = VFD/VAV Std Static
G = VFD/VAV High Static
H = VFD/VAV w/Bypass Std Static
K = VFD/VAV w/Bypass High Static
L = VFD/VAV Customer Std Static
N = VFD/VAV Customer High Static
P = VFD IntelliSpeed Std Static
R = VFD IntelliSpeed High Static
S = VFD w/Byp IntelliSp Std Static
U = VFD w/Byp IntelliSp Hi Static
V = VFD Cust IntelliSp Std Static
X = VFD Cust IntelliSp Hi Static
A = No Sensors
B = PHM (Phase Monitor)
C = DFS (Dirty Filter Switch)
D = SSD (Supply Air Smoke DET)
E = RSD (Return Air Smoke DET)
F = PHM,DFS
G = PHM,SSD
H = PHM,RSD
J = DFS,SSD
K = DFS,RSD
L = SSD,RSD
M = PHM,DFS,SSD
N = PHM,DFS,RSD
P = PHM,SSD,RSD
Q = DFS,SSD,RSD
R = PHM,DFS,SSD,RSD
Refrigeration
A = Standard Refrigeration
B = ECC (E-Coat Cond Coil)
C = EEC (E-Coat Evap Coil)
D = HGBP (Hot Gas Bypass)
F = ECC,EEC
G = ECC,EEC,HGBP
J = ECC,HGBP
M = EEC,HGBP
Service Options
A = Stand Alone Smart Equipment™
C = BACnet MSTP,Mdbs,N2 COM Card
D = CPC Control, DFS, APS
F = Fault Detection Diagnostics
G = Novar UCM Ctrl, DFS, APS
H = Hnywll Excel 10 CTRL,DFS,APS
M = Verasys Single Zone
N = Verasys Change Over Bypass
P = Verasys VAV
Q = Verasys Single Zone W/FDD
R = Verasys COBP W/FDD
T = Verasys VAV W/FDD
Controls Option
6.5-12.5 Ton York® Model Number Nomenclature
Two Stage Natural Gas Heat Options
N = 2 Stage Gas Aluminized Steel
S = 2 Stage Gas Stainless Steel
A = Std. Motor
D = Std. Motor/Motorized Damper (Downow Only)
H = Std Motor/Low Leak Econ/Barometric Relief (Downow
& Horizontal End Return Only)
J = Std Motor/Low Leak Econ/Power Exhaust (Downow
& Horizontal End Return Only)
N = Hi Static
R = Hi Static/Motorized Damper (Downow Only)
V = Hi Static Mtr/Low Leak Econ/Barometric Relief
(Downow & Horizontal End Return Only)
W = Hi Static Mtr/Low Leak Econ/Power Exhaust
(Downow & Horizontal End Return Only)
Fault Detection and Diagnostics (FDD)
Prior Nomenclature
4Johnson Controls Unitary Products
5167798-YTG-J-0218
Features and Benefits
Standard Features
• Service Friendly - The Predator® incorporates a number
of key features for ease of serviceability.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
The Smart Equipment™ control board provides alarm
messages to help quickly identify any faults.
All units use the same standard filter size. This
standardization removes any confusion on which filter
sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
All Predator
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
• Coil Technology – ZF condensers utilize Micro-Channel
“all aluminum” condensers which provide improved heat
transfer capabilities and reduced charge volumes.
• Environmentally Aware - For improved Indoor Air
Quality, a combination of aluminum foil faced and
elastometric rubber insulations are used exclusively
throughout the units.
• Balanced Heating – The Predator
Heating Comfort” with a balance between 1st and 2nd stage
gas heating. The first stage of a gas heat Predator
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and lowpressure switches. Internal compressor protection is
standard on all compressors. Phase Monitors are standard
on units with scroll compressors. This accessory monitors
the incoming power to the unit and protects the unit from
phase loss and reversed phase rotation.
®
units have a second model nameplate
®
offers “Ultimate
®
unit
• Advanced Controls - Smart Equipment™ control boards
have standardized a number of features previously
available only as options or by utilizing additional controls.
The Smart Equipment™ control board used in this
product will effectively operate the cooling system
down to 0°F when this product is applied in a comfort
cooling application for people. An economizer is
typically included in this type of application. When
applying this product for process cooling applications
(computer rooms, switchgear, etc.), please
reference applications bulletin AE-011-07 or call the
applications department for Unitary Products @ 1877-UPG-SERV for guidance. Additional
accessories may be needed for stable operation at
temperatures below 30°F.
• Units will come with the new state of the art Smart Equipment™ control system. The new unit control
incorporates the best of the already proven Simplicity™
unitary controls and creates a more robust, intelligent
control. The goal of this control is to utilize cutting edge
technology making the equipment easier to install,
operate, and service. All units are Factory commissioned,
configured, and run tested.
• Versatile - The Smart Equipment™ control can be
configured to use with a standard thermostat (easy to
connect screw terminals), A zone sensor, or can be setup
to communicate with multiple BAS communication
protocols to integrate with building automation systems.
• Reduce field installed complexity - Each unit will comes
equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key
temperature readings thus reduce field installed
complexity.
• On-board USB Port - The new control comes with a long
list of features including data logging, current and
previous system faults and software update capabilities
Johnson Controls Unitary Products5
5167798-YTG-J-0218
using the on board USB port and common flash drive.
Energy use monitoring capabilities allow custom tailoring
to allow a system to work more efficiently at all times and
occupancy levels. Self test and start-up reports also
available from the board VIA the USB port.
• Embedded LCD Display - The board has a easy to read,
built-in LCD display and easy to use navigation joystick
and buttons allowing the user to quickly navigate the
menus displaying unit status, options, current function,
supply, return and outdoor temperatures, fault codes and
other information.
• Safety Monitoring - The control monitors the outdoor,
supply, and return air temperatures and the high and low
pressure switch status on the independent refrigerant
circuits. On units with heating the gas valve and high
temperature limit switches are monitored on gas and
electric heating units. The control also monitors the
voltage supplied to the unit and will protect the unit if low
voltage due to a brown out, or other electrical issue
occurs.
• Low Ambient - An integrated low-ambient control allows
units to operate in the cooling mode down to 0°F outdoor
ambient without additional components or intervention.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an
anti- short cycle delay is incorporated into the standard
control. Compressor reliability is further ensured by
programmable minimum run times. For testing, the antishort cycle delay can be temporarily overridden with the
push of a button.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units are
programmed with default values based upon their
configuration of cooling and/or heating capacity.
• Nuisance Trip Protection and Three Strikes - To
prevent nuisance calls, the control board uses a three
times, you're out philosophy. The high, low-pressure
switch, anti-freeze protection, low voltage or heating high
limit must trip three times within two hours before the unit
control board will lock out the associated compressor.An
alarm message will be displayed on the LCD screen.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the
life of all compressors. This option is selectable on the unit
control board.
• Low Limit Control (LLC) - To prevent the supply air from
dropping below a specified set point, when there is a
demand for cooling during cold outside conditions.
(Programmable Set point)
• Reliable - From the beginning - All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term - All
units are painted with a long lasting, powder paint that
stands up over the life of the unit. The paint used has
been proven by a 1000 hour salt spray test.
• Full Perimeter Base Rails - The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer rigging
holes so that an overhead crane can be used to place the
units on a roof.
• Easy Installation - Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. Utility connections can be made quickly and with a
minimum amount of field labor. All units are shipped with
2" throw-away filters installed.
• Wide Range of Indoor Airflows - All supply air blowers
are equipped with a belt drive that can be adjusted to
meet the exact requirements of the job. A high static drive
option is available for applications with a higher CFM and/
or static pressure requirement.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
(10 yr.) and stainless steel tubular heat exchangers carry
a 15- year warranty.
Factory Installed Options
YORK® offers several equipment options factory installed, for
the Predator®line.
• Optional Factory Installed Economizers - Predator units
offer a variety of optional factory installed economizers
with low leak dampers. The outdoor air dry bu lb sensor
enables economizer operation if the outdoor air
temperature is less than the set point of the economizer
logic module. See economizer options section to
determine the correct economizer for your application.
• Down flow / End Return Economizers (with barometric relief and fresh air hood) - All units offer a va riety of
optional factory installed down flow eco no mizers th at are
shipped, installed and wired with low l ea k da mpers
designed to meet ASHRAE 90.1-2010, AMCA 511 Class
1A damper, and the International Energy Conservation
Code (IECC) certification requirements by achieving
leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
economizer goes through a rigorous 60,000 cycle test. Dry
bulb, single enthalpy, and dual enthalpy (wit h field installed
kit) can be selected. The economizer has spring return ,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor air dry bulb
temperature or the outdoor air enthalpy i nput. The optional
(field installed) single or dual enthalpy kits provi de
additional inputs to monitor outdoor air/ or return air
humidity and temperature for true enthalpy co ntrol. The
installer needs only to assemble the outdoor air hood,
attach the enthalpy control the hood and mo un t the hood
to the unit (Hood and control are provided).
• Power Exhaust - This factory option allows down flow or
horizontal end return economizer operation. The power
exhaust must be removed from the unit and mounted
in the horizontal end return duct work when applying
6Johnson Controls Unitary Products
5167798-YTG-J-0218
the product in the horizontal, end return
configuration.
• Motorized Outdoor Air Damper - The motoriz ed outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry.
• Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
• Variable Air Volume (VAV; 6.5 through 12.5 ton, only A factory-installed variable frequency drive (VFD),
mounted in the Blower Access compartment, is used to
control the speed of the indoor blower motor in order to
maintain a constant static pressure in the supply duct. A
duct pressure transducer is provided with the unit. The
drive comes completely wired and pre-programmed from
the factory.
An optional, factory-installed manual bypass switch
available with factory-installed VFD can be found in the
Blower Motor Access compartment. The switch can be
used to either route power to the VFD for modulating
control of the blower motor, to bypass the drive and
operate the motor at full speed, or to power the drive (and
not the motor) for diagnostic purposes.
VAV is not available with the factory-installed 3rd. party
BAS controllers. VAV is only factory installed with the
Smart Equipment™ Controller.
A ‘VFD-ready’ option provides the provisions for a
customer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment which
may accommodate other vendor’s drives depending on
their size. In order to utilize the unit’s mounting bracket,
the maximum recommended drive dimensions are limited
to approximately 9” H x 5” W x 7.5” D.
If the drive will not fit in the allotted space, then it will have
to be mounted elsewhere; either within the building on a
perpendicular wall which is not subjected to excessive
temperature, vibration, humidity, dust, corrosive gas,
explosive gas, etc., or within an appropriate enclosure
rated for outside installation to safeguard against
moisture, dust and excessive heat. A terminal block
located in the control box is provided for field connection
of the VFD controls.
• IntelliSpeed™ Supply Fan Control Option (ASHRAE
90.1 compliant, section 6.4.3.10) - Units configured with
the IntelliSpeed™ Supply Fan Option will contain a VFD
for multi-speed supply fan operation. This option allows
the supply fan RPM to vary based on the number of
compressors or heating stages energized. The
economizer's minimum position will also be configurable
to vary based on the supply fan VFD frequency output.
• Aluminized Steel Gas Heat Exchanger - For
applications in non-corrosive environments.
• Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
• Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• Electric Heaters - The electric heaters range from 9kW to
54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
• Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to the unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
• Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source and
wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
• Smoke Detectors - The smoke detectors stop operation
of the unit and provide a fault message to the control
board. Smoke detectors are available for both the supply
and/or return air configurations.
• Filters – 2” Pleated MERV 8 or 4” Pleated MERV 13 are
available to meet LEED requirements. A 2” Throwaway is
shipped as standard.
Factory-installed smoke detectors may be subjected to
extreme temperatures during "off" times due to outside air
infiltration. These smoke detectors have an operational
range of -4 °F to 158°F. Smoke detectors installed in areas
that could be outside this range will have to be relocated to
prevent false alarms.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• E-Coat Condenser Coils - The condenser coils are
coated with an epoxy polymer coating to protect against
corrosion.
• E-Coat Evaporator Coils - The evaporator coils are
coated with an epoxy polymer coating to protect against
corrosion.
Johnson Controls Unitary Products7
5167798-YTG-J-0218
• Hot Gas Bypass - Allows operation during low load
conditions while avoiding coil frosting and damage to
compressor. When suction pressure falls below valve
setpoint, the valve modulates hot gas to the inlet of the
evaporator.
HGBP is standard on all units with VAV, and optional with
constant-volume units.
Control Options
• Smart Equipment™ with Communication Option
Control - The York® Smart Equipment™ with
Communication Option Control is factory installed. It
includes all the features of the Smart Equipment™ control
with an additional gateway to BACnet MS/TP
(programmable to Modbus or N2 protocols).
• FDD (Fault Detection and Diagnostics) - Refrigerant side A factory installed control system option on the
commercial equipment that constantly monitors
refrigerant circuit pressures, refrigerant circuit
temperatures, as well as the environmental temperatures
and humidity via multiple sensor inputs.
• Provides a building owner, techni ci an or contractor with
the operational characteristics of the RTUs entire
refrigerant circuit to ensure the unit is functioning at its
specified performance level.
• Provides alarms if the unit is not functioning optimally.
• Remotely accessible via the Mobile Access Porta l
(MAP) gateway as well as scrolled on the UCB LCD
screen.
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Includes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, with optional dirty
filter indicator switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, with optional
dirty filter indicator switch, and air proving switch.
• Verasys - Verasys provides a simple user experience
with configurable self-recognizing controllers without the
need for any additional tools. Verasys creates enhanced
integration of HVACR equipment, zoning, and controls.
Contractors are able to offer a complete bundled solution
of equipment and controls to serve the light commercial
market.
Field Installed Accessories
YORK® offers several equipment accessories for field
installation, for the Predator
• Down flow and End Return Economizers (with fresh air hood and barometric relief) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers designed
®
line.
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper,
and the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/sq. ft. at 1" of static pressure. Each econo mizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to 100%
outdoor air. As the outdoor air intake dampers open, the
return air dampers close. The changeover from mechanical
refrigeration to economizer operation is regulated by the
outdoor air dry bulb temperature or the outdoor air enthalpy
input. The dual enthalpy kit provides a second input used to
monitor the return air (field installed). The installer needs only
to assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and control
are provided).
• Single or Dual Enthalpy Control, Accessories - These
kits contain the required components to convert a dry bulb
economizer to a single enthalpy and/or dual enthalpy
economizer.
• Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed economizers.
• Power Exhaust - This accessory installs in the unit with a
down flow or horizontal end return economizer. Power
exhaust plugs into the connector in the unit bulkhead.
User must purchase the 1EH0408 barometric relief
and hood kit when applying the product in a
horizontal flow application. The power exha us t must
be mounted in the horizontal end return ductwork.
• Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper incl udes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
Sensor- Senses CO2 levels and automatically
• CO
2
overrides the economizer when levels rise above the
preset limits.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
• Coil Guard - Field installed decorative wire coil guard.
• Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
• Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
8Johnson Controls Unitary Products
5167798-YTG-J-0218
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
• Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
• Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
• Gas Piping Kit - Contains pipe nipples, fittings and gas cock
required for gas supply connection with external shut off.
• Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. The 54kW/208-240 volt, Field-installed heater
kit is not available with VAV units due to a lack of space to
accommodate the heater’s fuse block accessory.
Cooling units include an adapter panel for easy
installation of the electric heaters. Necessary hardware
and connectors are included with the heaters. All heaters
are intended for single point power supply.
• Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from Sunline™ units to
Predator
®
units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
Johnson Controls Unitary Products9
5167798-YTG-J-0218
Accessories
Field Installed Accessories - Non-Electrical
MODELVOLTAGE DESCRIPTIONWHERE USED
1BD0408AllBurglar Bars, DownflowAll Cabinets
1CG0419AllCoil Guard(Electric / Electric Models), 50” Tall Standard Cabinets
1CG0420AllCoil Guard(Gas / Electric Models), 50" Tall Standard Cabinets
1CG0427AllCoil Guard(Electric / Electric Models), 42” Tall Cabinets
1CG0428AllCoil Guard(Gas / Electric Models), 42" Tall Cabinets
All Tall (50") Standard Cabinets, (Excludes 12.5T "V"
1HG0411AllHail Guard Kit
1HG0415AllHail Guard KitAll Short (42") Standard Cabinets
1FE0411AllFlue Exhaust Extension KitAll Cabinets
1FF0414All2" only Metal Filter Frame KitAll Tall 50" Cabinets
1FF0415All2" only Metal Filter Frame KitAll Tall 42" Cabinets
1FL0402AllPermanent 2" only Filter Kit Includes (4) Four Filters)All Tall 50" Cabinets
1FL0423AllPermanent 2" only Filter Kit (Includes (4) four Filters)All Tall 42" Cabinets
1GP0405AllGas Piping KitAll Cabinets
1HA0442AllHigh Altitude Kit for Natural GasAll 6 - 12T Cabinets
1HA0443AllHigh Altitude Kit for PropaneAll 6 - 12T Cabinets
1NP0442AllPropane Conversion KitAll 6 - 12T Cabinets
1RC0470AllRoof Curb, 8" HeightAll Cabinets
1RC0471AllRoof Curb, 14" HeightAll Cabinets
1RC0472All
1WC0412All
Roof Curb, Transition (7.5 T thru 12.5T Sunline to
Predator 3- 12T)All Cabinets
Wooden Crate for extra protection during shipping and
handling
cabinets)
Standard Cabinets Only (not applicable to units 119" in
length)
Field Installed Accessories - Electric Heat
MODELVOLTAGE DESCRIPTIONWHERE USED
2TP04520925230
9kW Electric HeatAll 50" Cabinet 6.5 and 8.5 Ton Models2TP04520946460
2TP04520958575
2TP04531825230
18kW Electric HeatAll 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04531846460
2TP04521858575
2TP04532425230
24kW Electric HeatAll 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04532446460
2TP04522458575
2TP04533625230
36kW Electric HeatAll 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models2TP04533646460
2TP04523658575
2TP04525425230
54kW Electric HeatAll 50" 10 and 12.5 Ton Models2TP04525446460
2TP04525458575
2TP04540925230
9kW Electric HeatAll 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04540946460
2TP04540958575
2TP04541825230
18kW Electric HeatAll 42" 6.5, 7.5 and 8.5 Ton Models2TP04541846460
2TP04541858575
2TP04542425230
24kW Electric HeatAll 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04542446460
2TP04542458575
2TP04543625230
36kW Electric HeatAll 42" Cabinet 6.5, 7.5 and 8.5 Ton Models2TP04543646460
2TP04543658575
10Johnson Controls Unitary Products
5167798-YTG-J-0218
Accessories (Continued)
Field Installed Accessories - Fresh Air
MODELVOLTAGE DESCRIPTIONWHERE USED
1FA0413AllManual Outside Air Damper 0-35%, DownflowAll Cabinets
1FA0414AllManual Outside Air Damper 0-100%, DownflowAll Cabinets
2EC0402AllDual Enthalpy Control (Includes 2 Sensors)All Cabinets
2EE04707624All
2EE04707424All
2EE04706924AllHorizontal Economizer without Barometric ReliefAll Cabinets
2MD04703824AllMotorized Damper, Downflow without Barometric ReliefAll Cabinets
2MD04703924AllMotorized Damper, Horizontal without Barometric Relief All Cabinets
2PE04704706*230Power Exhaust 230V Downflow or HorizontalAll Cabinets
2PE04704746*460Power Exhaust 460V Downflow or HorizontalAll Cabinets
2PE04704758*575Power Exhaust 575V Downflow or HorizontalAll Cabinets
Barometric Relief Kit for Power Exhaust, Horizontal
Application
Economizer for Downflow, End Return Horizontal, or
ERV Applications. Includes FA Hood, Exhaust Hood w/
Baro Relief
Economizer for Downflow, End Return Horizontal, or
ERV Applications. Includes FA Hood, Exhaust Hood w/
Baro Relief
Field Installed Accessories - Controls
MODELVOLTAGE DESCRIPTIONWHERE USED
2AP0401AllAir Proving SwitchAll Units
2AQ04700324AllCO2 Space AccessoryAll Units
2AQ04700424AllCO2 Unit AccessoryAll Units
2DF0402AllDirty Air SwitchAll Units
Wall Mounted humidity sensor-For use with MagnaDry
2SH0401All
2SD04700824AllSmoke Detector for SupplyAll Gen 5 units and greater with 2" & 4" Filters
2SD04700924AllSmoke Detector for ReturnAll Gen 5 units and greater with 2" & 4" Filters
2SD04701024AllSmoke Detector for Supply and ReturnAll Gen 5 units and greater with 2" & 4" Filters
S1-YKMAP1810-0P
S1-MP-PRTKIT0P
Reheat or space humidity input to Smart Equipment™
2LA04704632 All Low Ambient Kit3 - 10T Units
2LA04704633AllLow Ambient Kit 12.5T Units
Guide Specifications
GENERAL
Units shall be manufactured by York International Unitary
Products in an ISO 9001 certified facility. YORK® Predator
units are convertible single packages with a common footprint
cabinet and common roof curb for all 6.5 through 12.5 ton
models. All units have two compressors with independent R410A refrigeration circuits to provide 2 stages of cooling. The
units were designed for light commercial applications and can
be easily installed on a roof curb, slab, or frame. All Predator
units are self-contained and assembled on rigid full perimeter
base rails allowing for 3-way forklift access and overhead
rigging. Every unit is completely charged with R-410A, wired,
piped, and tested at the factory to provide a quick and easy
field installation. All units are convertible between side and
down airflow. Independent economizer designs are used on
®
side and down discharge applications, as well as all tonnage
sizes. Predator
®
units are available in the following
configurations: cooling only, cooling with electric heat, cooling
with gas heat, heat pump, and heat pump with electric heat.
Electric heaters are available as factory-installed options or
field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
®
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410A refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and AHRI test procedures. Units
Johnson Controls Unitary Products11
5167798-YTG-J-0218
shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No.
236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Either aluminum foil
faced or elastometric rubber insulation shall be used in the
unit’s compartments and be fastened to prevent insulation from
entering the air stream. Cabinet doors shall be hinged with
toolless access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, fork truck access and proper
sealing on roof curb applications. Disposable 2” filters shall be
furnished as standard and be accessible through hinged access
door. Fan performance measuring ports shall be provided on
the outside of the cabinet to allow accurate air measurements
of evaporator fan performance without removing panels or
creating bypass of the coils. Condensate pan shall be slide out
design, constructed of a non corrosive material, internally
sloped and conforming to ASHRAE 62-B9 standards.
Condensate connection shall be a minimum of ¾” I.D. female
and be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
b. Shall have internal spring isolation an d sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed. Special Phenolic
coating shall be available as a factory option.
b. Evaporator coils shall be of th e direct expansion, draw-
thru design.
c. Condenser coils shall have Mirco-Channel aluminum
tube, aluminum fins.
d. Condenser coils shall be of the direct expansion, draw-
thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice or thermally operated
expansion devices.
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The unit shall have two independent re frigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor.
1.Loss-of-charge/Low-pressure switch.
2.High-pressure switch.
3.Freeze condition sensor on evaporator coil. If any of
these safety devices trip, the LCD screen will display
the alarm message.
c. Unit shall incorporate "AUTO RESET" compressor over
temperature, over current protection.
d. Unit shall operate wi th conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
e. Unit control board shall have on-board diagnostics and
fault message display.
f. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
a selectable value as low as 0 °F.
g. Control board shall monitor each refrigerant safety switch
independently.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft com-
12Johnson Controls Unitary Products
5167798-YTG-J-0218
bustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall
be of the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 40 ºF. Burners shall be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the
unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
e. All two stage units shall have two in dependent stages of
capacity (60% 1
st
stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two states
of capacity all sizes. The heating section shall have a primary
limit control(s) (automatic reset) to prevent the heating element
system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be
wired for a single point power supply with branch circuit fusing
(where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit
shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Y ears,
Heat Exchanger – 10 Yea rs, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
• DRY BULB AUTOMATIC ECONOMIZER - Outdoor and
return air dampers that are interlocked and positioned by
a fully-modulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall be designed to meet ASHRAE 90.1-2010, AMCA
511 Class 1A damper, and the International Energy
Conservation Code (IECC) certification requirements by
achieving leakage rates of 3 cfm/sq. ft. at 1" of static
pressure. Changeover from compressor to economizer
operation shall be provided by an integral electronic
enthalpy control that feeds input into the basic module.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Available with barometric relief and power exhaust.
• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2- position, spring-return damper actuator. A unitmounted potentiometer shall be provided to adjust the
outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to
the fully closed position when the indoor fan motor is deenergized. Dampers shall fully close on power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
• Variable Air Volume (VAV) – The VAV option using a
variable frequency drive (VFD) shall be available on 6.5
through 12.5 ton, models for applications requiring a
constant supply-duct static pressure. Units equipped for
VAV shall be controlled by a duct pressure transducer
with a 0 - 5” WC pressure range. The pressure transducer
shall provide a 0 - 5 VDC output signal to a VAV control
board which, in turn shall provide a 2 - 10 VDC speed
reference signal to the VFD. The VAV control board shall
operate using factory-installed Supply Air, Return Air and
Outside Air Temperature Sensors with a nominal
resistance of 10,000 Ohms. Units equipped with VFD’s
shall have factory-installed manual bypass as an option.
• CONVENIENCE OUTLET (POWERED/NON-POWERED)
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
• ELECTRIC HEAT - Electric Heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAS CONTROLS HARDWARE - Include supply air
sensor, return air sensor, dirty filter indicator and air
proving switch.
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
–
Johnson Controls Unitary Products13
5167798-YTG-J-0218
• BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
• STAINLESS STEEL HEAT EXCHANGER – For
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
14Johnson Controls Unitary Products
Physical Data
ZF078-150 Physical Data
5167798-YTG-J-0218
Component
ZF078ZF090ZF102ZF120ZF150
Models
Nominal Tonnage6.57.58.51012.5
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Mbh)8100086500104000126000156000
AHRI net capacity (Mbh) 7800084000101000118000149500
EER11.211.2
IEER with Constant Volume12.91/12.7
IEER with Intellispeed13.9
IEER with VAV13.41/13.2
1
/13.7
2
2
2
12.91/12.7
2
/11.0
11.21/11.0
-12.91/12.7
13.114.01/13.8
2
13.11/12.9
2
2
2
2
11.21/11.0
14.41/14.2
13.21/13.0
2
11.01/10.8
2
--
2
2
12.81/12.6
12.61/12.4
2
2
1
CFM25002500340040004050
System power (KW)6.957.878.9010.7013.40
Refrigerant typeR-410AR-410AR-410AR-410AR-410A
Refrigerant charge (lb-oz)
System 14-84-105-128-47-10
System 24-84-85-127-27-4
2
Temperature Rise Range (ºF)20-5035-6515-4530-6010-4025-5520-5035-6510-4025-55
Gas Limit Setting (ºF)165165165165215195195150195150
Gas piping connection (in.)3/43/43/43/43/43/43/43/43/43/4
Quantity of Fans22224
Fan diameter (Inch)2424242424
TypePropPropPropPropProp
Drive typeDirectDirectDirectDirectDirect
Quantity of motors22224
Motor HP each1/31/33/43/43/4
No. speeds11111
RPM850850111011101110
Total CFM620076009500950011200
BELT DRIVE EVAP FAN DATA
Quantity11111
Fan Size (Inch)12 x 1212 x 1215 x 1515 x 1515 x 15
TypeCentrifugalCentrifugalCentrifugalCentrifugalCentrifugal
Motor Sheave1VM501VM501VM501VM501VM501VM501VM501VM501VM501VP56
Blower SheaveAK74AK64AK74AK61AK89AK74AK84AK74AK74BK77
BeltA49A49A49A49A56A54A56A54A54BX55
Motor HP each1-1/221-1/23232335
RPM1725172517251725172517251725172517251725
Frame size565656565656565656184T
FILTERS
Quantity - Size
4 - (24 x 16 x 2)
5, 6
4 - (24 x 16 x 2)
4 - (24 x 16 x 4)74 - (24 x 16 x 4)64 - (24 x 20 x 4)64 - (24 x 20 x 4)64 - (24 x 20 x 4)
4, 5
4 - (24 x 20 x 2)
4, 5
4 - (24 x 20 x 2)
4, 5
4 - (24 x 20 x 2)
1. Cooling Only Unit or Cooling Unit with Electric Heat
2. Cooling Unit with Gas Heat
3. 1ST Stage 60% of 2nd Stage
4. ZF090 and ZF150 have crankcase heaters standard
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products21