York SVY48 User Manual

Page 1
TECHNICAL GUIDE
SINGLE PIECE VARIABLE SPEED AIR HANDLERS
FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS
MODELS: AVY24 THRU 60 AND SVY48 THRU 60
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specifications are subject to change without notice.
www.ahridirectory.org.
256819-YTG-J-1208
DESCRIPTION
The Affinity Air Handler line offers the ultimate in comfort, sound and application flexibility. The Affinity models utilize a whisper quiet variable speed motor that provides humidity control and the lowest operating cost in the industry. The AVY air handler is shipped ready to be installed in all positions, upflow, downflow, horizontal left or right, with minor adjustments. The SVY 48 & 60 models are upflow only models designed into a shorter cabi­net, for those special applications where reduced height is required. No special kits are required to install this deluxe prod­uct in any position.
All JCI Unitary Products air handlers and coils use a TXV to pro­vide our customers with the optimum performance and refriger­ant control required for 13 + Seer systems. Air handlers can be ordered with either a R-22 or R-410A TXV factory installed. Air handlers are also available with “Flex-coils” without a factory installed metering device, where for added flexibility, a R-22 or R-410A TXV can be field installed to meet your refrigerant choice.
FEATURE
Thermal Expansion Valve - Provides the ultimate refrigerant
control required for today’s high efficient product. The UPG bolt­on TXV provides easy installation to convert the air handler to the required refrigerant, which is a true bolt-on design that does not require brazing to replace or install.
MicroBlue
with the MicroBlue removal of condensate during the refrigeration cycle and reduce the possibility of water blow-off. The MicroBlueTM coat­ing also reduces the growth of germ causing microbes for a healthier home environment.
Insulated Cabinet - All air handler cabinets are thermally insu­lated with 1” foil faced insulation (R-4.2) to prev ent sweating. For applications in extreme humidity conditions an optional, field installed, external insulating wrap kit is also available.
Factory - Sealed to achieve 2% or less leakage rate with or with­out field installed filter at 1.0” water gauge external static pres­sure.
Durable Finish Inside and Out - Air handler casings are made of pre-painted galvanized steel which provides a better paint to steel bond that resists corrosion and rust creep. All internal coil sheet metal parts are made of G90 galvanized.
New 4 HK Heat Kit - Installation friendly, easy service, more robust, unique to new design.
ECM Variable Speed M otor - Designed for efficient, quiet oper­ation with added indoor comfort control. With the use of a humi­distat, the motor will monitor the humidity in the home and automatically keep the desired humidity level in both winter and summer seasons. The ECM motor utilizes only 24% of the energy used by standard blower motors to reduce your overall heating and cooling costs.
ClimaTrak Comfort Settings - Installers can set an operating cycle for the ECM motor that works best in a particular climate. Homeowners benefit from an operating cycle that maximizes their indoor comfort level regardless of whether they live in a dry, temperate, or humid climate.
TM
Coated Fins - All air handler coils are treated
TM
hydrophilic coating to enhance the
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
256819-YTG-J-1208
DIMENSIONS
F
18-9/32”
TOP OUTLET DIMENSIONS
J
CIRCUIT
BREAKER
PANEL
BLOWER COMPARTMENT
D
7-11/32”
1-1/2”
10-3/8”
K
BOTTOM INLET
A
C
B
DIMENSIONS
REFRIGERANT CONNECTIONS
E
DRAIN CONNECTIONS
FOR UPFLOW AND
DOWNFLOW APPLICATIONS
FILTER ACCESS
DRAIN PAN CONNECTIONS FOR HORIZONTALAPPLICATIONS
DIMENSIONS
1
Models
Dimensions (Inches)
AB C
DEF
Wiring Knockouts
JK
Height Width Depth Power Control Liquid Vapor
AVY24B**H21 46 17.5 AVY36C**H21 52 21 17-1/8 17-13/32 18-3/32 7/8” AVY48D**H21 57 24.5 22-1/8 20-29/32 21-19/32 7/8” SVY48D**N21 52 24.5 17-1/8 20-29/32 21-19/32 7/8” AVY60D**H21 57 24.5 22-1/8 20-29/32 21-19/32 7/8’
21.5
(w/o cladding)
22.5
(with cladding)
12-3/8 13-29/32 14-19/32
7/8” (1/2”) 1 3/8” (1”)
1 23/32” (1 1/4”)
7/8” (1/2”) 3/8”
SVY60D**N21 52 24.5 17-1/8 20-29/32 21-19/32 7/8”
1. Actual size (Conduit size). ** Thermal expansion device indicators - “2_” indicates R-22 TXV is factory installed, “3X” indicates unit is a “Flex Coil” models with a field installed
R-22 or R-410A TXV, and “4_” indicates R-410A TXV is factory installed. Letter indicates TXV size as required, see outdoor unit technical infor­mation for proper matches and requirements.
Refrigerant
Connections
Line Size
3/4”
2 Johnson Controls Unitary Products
Page 3
256819-YTG-J-1208
COIL TECHNICAL DATA
Models Application
Refrig.
Conn. Types
AVY24B3XH21 AVY24B2AH21 2A AVY24B4EH21 4E AVY24B4FH21 4F
Cooling /
Heat Pump
Sweat 3.89 2 14 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
AVY24B4KH21 4K AVY36C3XH21 AVY36C2AH21 2A AVY36C4EH21 4E AVY36C4FH21 4F AVY36C4GH21 4G
Cooling /
Heat Pump
Sweat 4.86 3 12 (2) 20 x 17.5 1 x 0.866 3/8 Enhanced
AVY36C4HH21 4H
AVY36C4KH21 4K AVY36C4MH21 4M AVY48D3XH21 AVY48D2CH21
AVY48D4FH21 AVY48D4HH21
AVY48D4JH21
Cooling /
Heat Pump
Sweat 5.83 3 11 (2) 24 x 17.5 1 x 0.866 3/8 Enhanced
AVY48D4KH21
SVY48D3XN21 None SVY48D2CN21 2C
AVY60D3XH21
AVY60D2CH2
AVY60D4HH21
AVY60D4JH21 AVY60D4KH21
SVY60D3XN21 None SVY60D2CN21 2C
Note: H models are available with a factory installed horizontal drain pan.
Cooling /
Heat Pump
Sweat 5.83 3 11 (2) 24 x 17.5 1 x 0.866 3/8 Enhanced
Face Area
(Sq. Ft.)
Rows
Deep
Fin
Per In.
Coil Size
Tube
Geometry
Tube
Dia.
Fin
Type
TXV
None
None
None
2C 4F 4H
4J
4K
None
2C 4H
4J
4K
COOLING CAPACITY
Models Rated CFM
AVY24B**H21 800
AVY36C**H21 1200
AVY48D**H21 SVY48D**N21
AVY60D**H21 SVY60D**N21
1600
1850
Entering Air °F
(Dry / Wet Bulb)
FULL-CASED “A” TYPE MULTI-POSITION
MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG
35 / 61.5 40 / 68.5 45 / 76.0 50 / 84.0
85/72 35.0 31.8 28.4 24.7 80/67 32.2 29.1 25.7 22.3 75/62 26.4 23.4 21.0 17.1 70/57 21.4 18.6 20.2 12.1 85/72 51.3 46.7 41.7 36.8 80/67 41.1 36.3 31.8 27.1 75/62 32.1 27.0 29.4 21.9 70/57 27.6 25.4 23.5 18.3 85/72 100.5 86.4 72.0 56.8 80/67 80.4 67.5 55.0 42.1 75/62 62.7 49.9 40.7 34.0 70/57 53.9 47.2 36.81 28.71 85/72 119.9 101.0 82.0 62.2 80/67 96.0 79.2 62.6 45.8 75/62 74.8 58.6 46.2 37.0 70/57 64.3 55.4 43.2 33.7
Johnson Controls Unitary Products 3
Page 4
256819-YTG-J-1208
Air Handler Air Flow Data
24B 36C
High Low High Low COOL Tap ADJ Tap 1088 707 1387 905 A B
830 542 1151 753 B B 948 617 1201 783 A A 716 465 1009 657 B A 854 556 1086 703 A C 612 462 953 622 C B 637 460 901 588 B C 531 460 754 493 D B 542 462 831 540 C A 462 462 657 460 D A 474 460 751 494 C C 461 464 588 461 D C
48D 60D JUMPER SETTINGS
High Low High Low COOL Tap ADJ Tap 2138 1442 2364 1545 A B 1759 1162 1962 1271 B B 2009 1311 2123 1374 A A 1612 1052 1763 1146 B A 1773 1166 1905 1237 A C 1530 989 1777 1158 C B 1459 947 1580 1021 B C 1359 886 1596 1030 D B 1388 904 1583 1019 C A 1221 806 1413 929 D A 1244 808 1412 926 C C 1118 715 1277 841 D C
HIGH / LOW SPEED COOLING AND HEAT PUMP AIRFLOW
CFM
JUMPER SETTINGS
HIGH / LOW SPEED ELECTRIC HEAT AIRFLOW
CFM
24B 36C
High Low High Low HEAT Tap ADJ Tap 1088 828 1387 908 A N / A
954 714 1228 804 B N / A 829 614 1151 756 C N / A 678 523 923 609 D N / A
48D 60D JUMPER SETTINGS
High Low High Low HEAT Tap ADJ Tap 2111 1417 2363 1488 A N / A 1858 1252 2174 1252 B N / A 1480 985 1868 1061 C N / A 1250 840 1387 823 D N / A
1. Airflow at nominal voltage, bottom return at 0.5 external static pressure, tested without filter installed, dry coil conditions.
2. These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure.
3. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static.
4. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.
5. Both the COOL and the ADJUST tap must be set to obtain the cooling airflow desired (CFM).
6. The ADJ tap does not affect the HEAT tap setting.
7. Fan only airflow (CFM) = 63% of jumper selected COOL tap and ADJUST tap.
8. Low speed cooling used only with two stage outdoor units. (Speed is preset to 65% of high speed).
9. Dehumidification speed is 85% of jumper selected COOL tap and ADJUST tap.
10. When operating in both heat pump and electric heat modes, the airflow (CFM) will be per HEAT Tap CFM values only.
11. At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details.
12. Airflow (CFM) indicator light (LED2) flashes once for every 100 CFM (i.e.: 12 Flashes is 1200 CFM) – blinks are approximate +/- 10%.
JUMPER SETTINGS
4 Johnson Controls Unitary Products
Page 5
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow
Capacity Factor
80% 90% Rated CFM 110% 120%
0.96 0.98 1.00 1.02 1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
256819-YTG-J-1208
Models
Blower - Diameter x Width 10 x 7 10 x 7 10 x 10 10 x 10 Motor Voltage 230
Amps Full Load (230) 2.8 4.3 5.5 7.0
1
Filter
Shipping / Operating Weight (lbs.) 140/134 170/164
1.Field supplied.
HP 1/3 1/2 3/4 1 Nominal RPM 1200 1200 1200 1200
Type DISPOSABLE OR PERMANENT Size 16 x 20 x1 20 x 20 x1 22 x 20 x1 22 x 20 x1 Permanent Type Kit 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK
AVY24B**H21 AVY36C**H21
AVY48D**H21 SVY48D**N21
AV - 196/185 SV - 194/181
AVY60D**H21 SVY60D**N21
AV - 199/188 SV - 195/184
ELECTRICAL DATA - COOLING ONLY (60 Hz)
Total Motor Amps Minimum Circuit Ampacity
Models
AVY24B**H21 3.2 2.8 4.0 3.5 15 14 AVY36C**H21 4.7 4.3 5.9 5.4 15 14 AVY48D**H21 6.1 5.0 7.6 6.9 15 14 SVY48D**N21 6.1 5.0 7.6 6.9 15 14 AVY60D**H21 7.8 7.0 9.7 8.8 15 14 SVY60D**N21 7.8 7.0 9.7 8.8 15 14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
60 Hertz 60 Hertz
208V 230V 208V 230V
Max. O.C.P.
Amps/Type
1
Minimum Wire
Size A.W.G.
Johnson Controls Unitary Products 5
Page 6
256819-YTG-J-1208
ELECTRICAL DATA - 208/230-1-60
Models Heat Kits*
4HK*6500206 0.5 Heat-D 1.9 2.5 6.4 8.5 1.9 2.5 1.9 2.5 1.9 2.5 4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8
AVY24B**H21
AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
1. See conversion Table 10. * May be 0 (no breaker) or 1 (with breaker).
4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5 4HK*6501006 0.5 Heat-B 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6
4HK165N1506 0.5 Heat-A 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4
4HK*6500506 0.5 Heat-C 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8 4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5
4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6 4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4 4HK16501806 0.5 Heat-A 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6
4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8
4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5
4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6 4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4 4HK16501806 0.5 Heat-B 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6 4HK16502006 0.5 Heat-B 14.4 19.2 49.2 65.5 3.6 4.8 7.2 9.6 14.4 19.2 4HK16502506 0.5 Heat-B 18.0 24.0 61.5 81.9 3.6 4.8 10.8 14.4 18.0 24
4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8
4HK*6500806 0.5 Heat-D 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5
4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6 4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4 4HK16501806 0.5 Heat-C 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6 4HK16502006 0.5 Heat-C 14.4 19.2 49.2 65.5 3.6 4.8 7.2 9.6 14.4 19.2 4HK16502506 0.5 Heat-C 18.0 24.0 61.5 81.9 3.6 4.8 10.8 14.4 18.0 24
Max.
Static
Min.
Speed Tap
Total Heat
KW MBH W1 Only W2 Only W1 & W2
208v 230v 208v 230v 208v 230v 208v 230v 208v 230v
1
kW Staging
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
FOR
208V 230V 240V .918 220V 240V .840
OPERATION MULTIPLY
240V
TABULATED KW & MBH BY
COMFORT SETTINGS SELECTION
Delay Tap Comfort Setting
ANormal BHumid CDry D Temperate
.751
6 Johnson Controls Unitary Products
Page 7
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60
256819-YTG-J-1208
Field Wiring
Max. O.C.P.
Models
Heat Kit -
Single Phase*
Heater
Amps
240V
Min. Circuit Ampacity
208V 230V 208V 230V 208V 230V
4HK*6500206 10.4 15.28 16.53 20 20 12 12 4HK*6500506 20.0 25.67 28.50 30 30 10 10
AVY24B**H21
4HK*6500806 31.3 37.85 42.63 45 45 8 8 4HK*6501006 40.0 47.33 53.50 50 60 8 6
4HK165N1506 60.0 69.00 78.50 70 90 4 3
4HK*6500506 20.0 27.54 30.38 30 35 10 10 4HK*6500806 31.3 39.73 44.50 45 45 8 8
AVY36C**H21
4HK*6501006 40.0 49.21 55.38 50 60 8 6 4HK16501506 60.0 70.88 80.38 70 90 4 3 4HK16501806 73.3 85.32 97.00 90 100 4 3 4HK*6500506 20.0 29.29 31.88 35 35 8 8 4HK*6500806 31.3 41.48 46.00 45 50 8 8
AVY48D**H21 SVY48D**N21
4HK*6501006 40.0 50.96 56.88 60 60 6 6 4HK16501506 60.0 72.63 81.88 90 90 3 3 4HK16501806 73.3 87.07 98.50 90 100 3 2 4HK16502006 80.0 94.29 106.88 100 125 3 1 4HK16502506 100.0 115.96 131.88 125 150 1 1/0 4HK*6500506 20.0 31.42 33.75 35 35 8 8 4HK*6500806 31.3 43.60 47.88 45 50 8 8
AVY60D**H21 SVY60D**N21
4HK*6501006 40.0 53.08 58.75 60 60 6 6 4HK16501506 60.0 74.75 83.75 90 90 3 3 4HK16501806 73.3 89.19 100.38 90 110 3 2 4HK16502006 80.0 96.42 108.75 100 125 3 1 4HK16502506 100.0 118.08 133.75 125 150 1 1/0
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. * May be 0 (no breaker) or 1 (with breaker).
Amps/Type
1
75°C Wire Size - AWG
ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60
Amps/Type
Models
Heater
Model
Min. Circuit Ampacity
Max. O.C.P.
Circuit Circuit Circuit
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
AVY24B**H21 4HK165N1506 47.5 / 53.5 21.7 / 25.0 50 / 60 25 / 25 8 / 6 10 / 10 — AVY36C**H21
4HK16501506 48.5 / 55.4 21.7 / 25.0 50 / 60 25 / 25 8 / 6 10 / 10 — 4HK16501806 44.9 / 51.2 39.8 / 45.8 45 / 60 40 / 50 8 / 8 8 / 8 — 4HK16501506 51.0 / 56.9 21.7 / 25.0 60 / 60 25 / 25 6 / 6 10 / 10
AVY48D**H21 SVY48D**N21
4HK16501806 47.4 / 52.7 39.8 / 45.8 50 / 60 40 / 60 6 / 6 8 / 6 — 4HK16502006 51.0 / 56.9 43.4 / 50.0 60 / 60 45 / 50 6 / 6 8 / 8 — 4HK16502506 51.0 / 56.9 43.4 / 50.0 21.7 / 25.0 60 / 60 45 / 50 25 / 25 6 / 6 8 / 8 10 / 10 4HK16501506 53.1 / 58.8 21.7 / 25.0 60 / 60 25 / 25 6 / 6 10 / 10
AVY60D**H21 SVY60D**N21
4HK16501806 49.5 / 54.6 39.8 / 45.8 50 / 60 40 / 60 6 / 6 8 / 6 — 4HK16502006 53.1 / 58.8 43.4 / 50.0 60 / 60 45 / 50 6 / 6 8 / 8 — 4HK16502506 53.1 / 58.8 43.4 / 50.0 21.7 / 25.0 60 / 60 45 / 50 25 / 25 6 / 6 8 / 8 10 / 10
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
1
75°C Wire Size - AWG
Johnson Controls Unitary Products 7
Page 8
256819-YTG-J-1208
ELECTRICAL DATA - 208/230-3-60
Models
AVY24B**H21 4HK06501025 0.5 Heat-B 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6 AVY36C**H21
AVY48D**H21 SVY48D**N21
AVY60D**H21 SVY60D**N21
1. See conversion table on Page 5.
Heat Kit -
Three Phase
4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6 4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4 4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6 4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4 4HK06501825 0.5 Heat-B 12.9 17.2 44.7 58.7 12.9 17.2 12.9 17.2 12.9 17.2 4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6 4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4 4HK16502525 0.5 Heat-C 18.0 24.0 61.4 81.4 9.0 12.0 18.0 24.0 18.0 24.0
Max.
Static
Min.
Speed
Tap
208V 230V 208V 230V 208V 230V 208V 230V 208V 230V
Total Heat
KW MBH W1 Only W2 Only W1 + W2
1
KW Staging
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60
Models
AVY24B**H21 4HK06501025 23.1 28.5 32.4 30 35 10 8 AVY36C**H21
AVY48D**H21 SVY48D**N21
AVY60D**H21 SVY60D**N21
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
Heat Kit -
Three Phase
4HK06501025 23.1 30.4 34.3 30 35 10 8 4HK06501525 34.7 42.9 48.8 45 50 8 8 4HK06501025 23.1 31.3 35.1 35 35 8 8 4HK06501525 34.7 43.8 49.6 45 50 8 8 4HK06501825 41.4 51.0 58.0 60 60 6 6 4HK06501025 23.1 33.8 37.6 35 40 8 8 4HK06501525 34.7 46.3 52.1 50 60 8 6
Heater
Amps
240V
Min. Circuit Ampacity
208V 230V 208V 230V 208V 230V
Field Wiring
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60
Circuit
1
Amps/Type
Minimum Circuit Ampacity
Models
AVY60D**H21 SVY60D**N21
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
Heater
Model
4HK16502525 41.0 / 44.9 31.3 / 36.1 - / - 45 / 45 35 / 40 - / - 8 / 8 8 / 8 - / -
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Max. O.C.P.
75°C Wire Size - AWG
8 Johnson Controls Unitary Products
Page 9
256819-YTG-J-1208
ACCESSORIES
Refer to Price Manual for specific model numbers where not shown.
TXV Kits - TXV kits are available for “Flex-coil” applications and converting R-22 to R-410A or as a service replacement. All kits are bolt-on and require no brazing to install.
Electric Heaters - 4HK models shown under electrical data include sequential operation and temperature dual limit switches for safe, efficient oper ation. Circuit breakers are pro­vided where shown.
External Insulating Wrap Kit - Provides a vinyl covered ther­mal insulation wrap, providing additional thermal insulation pro­tection to prevent sweating in applications where extreme high humidity is present. Air Handler cover (or wrap) has Velcro edges for easy installation and access.
S1-1JV0117 S1-1JV0121 S1-1JV0124 S1-1JV0224 (SV* models only)
Humidstat - S1-2HU16700124 Control when used with ECM variable speed models will moni-
tor humidity level in both winter and summer seasons. Adjusts blower speed and airflow provided to maintain desired humidity levels.
LIMITATIONS
These units must be wired and installed in accordance with all national and local safety codes.
Voltage limits are as follows:
1
Air Handler Voltage Voltage code
208/230-1-60 06 187-253
1.Rated in accordance with ARI Standard 110, utilization range “A”.
Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp.°F Dry Bulb Temp. °F
Min. Max. Min. Max.
57 72 65 95
Normal Operating
Voltage Range
COOLING MODELS WITH ELECTRIC HEAT WIRING
Air Handler Control Wiring
Typical A/C - Cooling only Applications
THERMOSTAT
RR
G
Y
W1
W2
C
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
AIR HANDLER
BOARD
G
Y/Y2
Y1
W2
W1
O
HUM
X/L
COM
1-STAGE
AIR CONDITIONING
Y
HUMIDISTAT
C
THERMOSTAT
*
Typical A/C with Electric Heat Applications
RR
G
Y
W2
W1
C
Air Handler Control Wiring
AIR HANDLER
BOARD
G
Y/Y2
Y1
W2
W1
O
HUM
X/L
COM
1-STAGE
AIR CONDITIONING
Y
HUMIDISTAT
C
*
Johnson Controls Unitary Products 9
Page 10
TWO-STAGE COOLING WIRING
CONTROL WIRING - Air Handler & New UPG HP Systems
Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”
THERMOSTAT
RR R
GG
Y2
Y1
E
W
O O
X/L X/L X/L
C
* Optional dehumidification humidistat switch contacts open on humidity rise. NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
Conventional Application - Not Hot Heat Pump
AIR HANDLER
BOARD
Y/Y2
Y1
W2
W1
O
HUM
COM
HUMIDISTAT
2 - STAGE SCROLL
HEAT PUMP
Y2
Y2 OUT
Y1
W2 OUT
W1 OUT
W
*
BS
C
TYPICAL APPLICATIONS
UPFLOW DOWNFLOW
HORIZONTAL RIGHT
HORIZONTAL LEFT
Subject to change without notice. Printed in U.S.A. 256819-YTG-J-1208 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 256819-YTG-I-0808
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069