Page 1
®
TECHNICAL GUIDE
STELLAR 2000
SPLIT-SYSTEM AIR CONDITIONERS
10 SEER
MODELS: H*DB018 THRU 060
(1 THRU 5 NOMINAL TONS, 1 PH)
H*DB036 THRU 076
(3 THRU 6-1/3 NOMINAL TONS, 3 PH)
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-d ate techni cal information.
Additional rating information can be found at
www.ariprimenet.org.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
TM
O
T
A
R
D
I
E
I
A
F
S
I
T
R
C
E
O
C
M
A
P
I
R
R
-
L
C
E
O
Y
N
R
Y
I
D
R
I
U
A
N
T
T
T
G
I
I
N
U
R
E
C
T
Q
N
U
E
I
E
P
M
R
T
I
N
F
O
I
I
A
C
T
A
C
T
R
E
I
S
O
N
I
2
S
D
T
R
A
A
N
D
system is listed
with ARI.
O
N
I
W
N
I
G
T
H
F
O
S
0
1
C
A
F
U
N
A
M
Certification applies only
when the complete
Models 018-048
Model 060
LISTED
036-21024-006 Rev. D (0403)
DESCRIPTION
The HDB Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be custommatched with one of YORK 's com plete line of evapo rator sections, each designed to serve a specific function. Matching
Air Handlers are available for upflow, downflow or horizontal
application to pro vide a complet e system. El ectric heater s are
available if required. Add-On coils are available for use with
upflow, downflow or horizontal fu rnaces.
WARRANTY
Single Phase Units:
5-year limited parts warranty.
5-year limited compress or warranty.
Three Phase Units:
1-year limited parts warranty.
5-year limited compress or warranty.
FEATURES
• QUALITY CONDENSER COILS - The coil is con structed
of enhanced copper tube and aluminum fins.
• COIL PROTECTION - Coils are protected fro m dama ge by
a polymer mesh applied between the coil face, and a PVC
coated steel coil guard.
• PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature.
This is accomplished by the simultaneous operation of
high pressure relief valve and a temperature sensor which
protects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the
compressor.
• DURABLE FINISH - Cabinet is made of powder painted
steel over pre-primered steel. The pre-treated galvanized
steel provides a better paint to steel bond, which resists
corrosion and rust creep. Special primer formulas and
automotive quality finish insure less fading when exposed
to sunlight.
• LOWER INSTALLED COST - Installation time and costs
are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Both quick connect and sweat connect
models are availabl e. Bo th s erv ic e v al ve s a re fi rml y a ffixed
to the unit. The sweat unit contains enough refrigerant for
matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is
required on the ground or roof.
• TOP DISCHARGE - The warm air from the top mounted
fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
• LOW OPERATING SOUND LEVEL - The upward air flow
carries the normal operating noise up away from the living
area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins
of the condenser coil muffle the normal fan motor and
compressor operating sounds.
• LOW MAINTENANCE - Long life permanently lubricated
motor- bearings need no annual servicing.
• EASY SERVICE ACCESS - Fully exposed refrigerant
connections, a single panel covering the electrical controls, and the molex plug in the control box connecting the
condenser fan make for easy servicing of the unit.
• SECURED SERVICE VALVES - Secured re-usable ser-
vice valves are provided on both the liquid and vapor
sweat connections for ease of evacuating and charging.
• U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordan ce with th e Uni tary Small Eq uipme nt certification program, which is based on ARI Standard 210/240.
Page 2
036-21024-006 Rev. D (0403)
Physical and Electrical Data - 1 Phase
MODEL
H4DB018 H4DB024 H4DB030 H4DB036 H5DB042 H5DB048 H4DB060
Unit Supply Voltage 208/230-1-60
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 13.0 15.2 16.9 23.0 27.2 31.9 37.6
Max. Overcurrent Device Amps
Compressor Type
Compressor Amps
3
Rated Load 9.7 11.5 12.8 17.1 20.5 24.4 28.8
Locked Rotor 54 60 68 86 120 140 165
2
20 25 25 35 40 50 55
Recip Recip Recip Recip Recip
Scroll
B
Scroll
Crankcase Heater No No NOo Yes Yes No No
Fan Motor Amps Rated Load 0.5 0.8 0.8 1.6 1.6 1.4 1.6
Fan Diameter Inches 18 18 18 18 18 18 24
Rated HP 1/12 1/8 1/8 1/4 1/4 1/4 1/4
Fan Motor
Nominal RPM 1100 1075 1075 1100 1100 1100 850
Nominal CFM 1850 1950 1950 2150 2200 2200 3000
Face Area Sq. Ft. 9.4 9.4 11.3 11.3 14.1 14.1 20.0
Coil
R o w s D e e p 1111111
Fin / Inches 16 16 18 18 18 16 18
Liquid Line OD 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line OD 5/8 5/8 3/4 3/4 7/8 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
3 - 14 3 - 10 4 - 7 4 - 9 5 - 11 6 - 0 8 - 0
Charge Per Foot, Oz. 0.68 0.68 0.68 0.68 0.70 0.70 0.70
Operating Weight Lbs. 124 134 135 140 155 176 210
PHYSICAL AND ELECTRICAL DATA - 3 Phase
B
H4DB H5DB H4DB H4DB H4DB H5DB H4DB H4DB H5DB H4DB
MODEL
036 048 060 076 036 048 060 076 048 060
25 46 58
Unit Supply Voltage
Normal Voltage Range
1
Minimum Circuit Ampacity
Max. Overcurrent Device Amps
Compressor Type
Compressor Amps
3
Rated Load
Locked Rotor
Crankcase Heater
Fan Motor Amps Rated Load
Fan Diameter Inches
Rated HP
Fan Motor
Nominal RPM
Nominal CFM
Face Area Sq. Ft.
Coil
Rows Deep
Fin / Inches
Liquid Line OD
Vapor Line OD
Unit Charge (Lbs. - Oz.)
4
Charge Per Foot, Oz.
Operating Weight Lbs.
2
25 30 30 40 15 15 15 20 15 15
Recip Scroll
10.9 14.1 16.0 18.9 5.8 7.1 8.0 9.5 5.6 6.4
78 105 125 146 40 55 67 73 44 50
Yes No No No Yes No No No No No
1.4 1.4 1.6 1.8 0.8 0.8 0.8 1.0 0.5 0.6
18 18 24 24 18 18 24 24 18 24
1/4 1/4 1/4 1/3 1/4 1/4 1/4 1/3 1/4 1/4
1100 1100 850 1100 1075 1075 850 1100 1075 850
2150 2150 3000 4200 2350 2150 3000 4200 2150 3000
11.3 14.1 20.0 20.0 11.3 14.1 20.0 20.0 14.1 20.0
1112111211
18 16 18 13 18 16 18 13 16 18
3/8 3/8 3/8 1/2 3/8 3/8 3/8 1/2 3/8 3/8
3/4 7/8 7/8 1-1/8 3/4 7/8 7/8 1-1/8 7/8 7/8
4 - 9 6 - 0 8 - 0 14 - 0 4 - 9 6 - 0 8 - 0 14 - 0 6 - 0 8 - 0
0.68 0.70 0.70 0.70 0.68 0.70 0.70 0.70 0.70 0.70
140 176 210 300 140 176 210 300 176 210
15.2 19.0 21.6 25.4 8.1 9.7 10.8 12.8 7.5 8.6
208/230-3-60 460-3-60 575-3-60
187 to 253 432 to 504 517 to 633
B
ScrollBScrollBRecip ScrollBScrollBScrollBScrollBScroll
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
B
2 Unitary Products Group
Page 3
036-21024-006 Rev. D (0403)
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase
OUTDOOR UNITS H4DB018 H4DB024 H4DB030 H4DB036 H4DB042 H5DB048 H4DB060
UNIT ORIFICE(S)
FACTORY CHARGE, LBS. - OZ. 3 - 14 3 - 10 4 - 7 4 - 9 5 - 9 6 - 0 8 - 0
INDOOR COIL
G1FA/G1UA024S14, 17 59 53 + 2 59 + 2 ----G1FA/G1UA030S14 65 57 + 4 57 + 4 67 + 0 ---G1FA/G1UA036S14, 17, 21 73 - 59 + 6 67 + 2 73 + 0 - - G1FA/G1UA048S17 84 - - - 75 + 14 81 + 0 - G1FA/G1UA048S21 84 - - - 75 + 21 81 + 5 84 + 6 G1FA/G1UA060S21, 24 90 ----- 8 4 + 6 9 0 + 0
G1NA030S17H 57 55 + 4 57 + 7 ----G1NA030S17K 63 - - 67 + 4 ---G1NA036S17J 67 - - - 73 + 2 - - G1NA036S21C 67 - - - 73 + 2 - - G1NA048S21D 78 - - - 75 + 8 78 + 3 84 + 0 G2FD024(S,H)14, 17 61 57 + 4 55 + 4 ----G2FD030(S,H)17 65 57 + 6 59 + 6 67 + 2 ---G2FD035(S,H)14 65 57 + 6 59 + 5 67 + 0 73 + 0 - - G2FD036(S,H)17 75 - 59 + 10 67 + 6 73 + 3 - - G2FD036(S,H)21 75 - 59 + 10 67 + 8 73 + 5 - G2FD042(S,H)21 78 - - - 75 + 8 81 + 1 - G2FD046(S,H)17 78 - - - 73 + 7 81 + 0 84 + 0 G2FD048(S,H)21, 24 84 - - - 75 + 20 81 + 8 84 + 3 G2FD060(S,H)24 90 ---- 8 1 + 1 3 8 4 + 6 9 0 + 0
G2FD061H24 90 ------9 0 + 5
G 1 H D 0 2 4 5 95 5 + 5 5 9 + 1 8 ----G1HD036 69 - 57 + 11 65 + 7 69 + 22 - - G1HD048 81 - - - 75 + 14 78 + 5 81 + 2 G 1 H D 0 6 0 9 3 -----8 4 + 9 9 3 + 0
F 2 R P 0 1 8 5 35 3 + 0-----F 2 R C 0 2 4 6 15 3 + 2 5 9 + 2 ----F 2 R C 0 3 0 6 5 --6 7 + 0---F2RC036 73 - - 67 + 2 73 + 0 - - F 2 R C / F 2 R P / F P 0 2 4 6 1 -5 9 + 4 ----F 2 R P / F P 0 3 0 6 5 - 5 9 + 6 6 7 + 2---F 2 R P / F P 0 3 6 7 5 --- 7 5 + 6--F 2 F P 0 4 0 6 3 - 5 7 + 1 5 ----F2RP/FP042 78 - - - 75 + 8 78 + 3 - F2FP045 78 - - - 78 + 25 - - F 2 F P 0 4 8 8 4 ---- 7 8 + 1 1 8 4 + 6 F 2 F P 0 6 0 9 0 -----8 4 + 8 9 0 + 0
FOOTNOTES:
1. These orifices are packed in the instruction/warranty packet of each outdoor unit.
2.
These orifices are factory-mounted in the flow control device of each indoor coil
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.
2. Verify the orifice size and the additional charge required for the specific evaporator coil in the system using the table above:
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge=Base Charge (as shipped) +adder for
evaporator +adder for line set.
5. If the orifice in the evaporator was changed verify the evaporator nameplate has been marked with the correct orifice size.
1
COIL ORIFICE
53, 55 59, 61 65, 67, 69 73, 75 73,78,81 81, 84 87, 90, 93
2
SYSTEM ORIFICE + ADDITIONAL CHARGE, OZ.
.
Unitary Products Group 3
Page 4
036-21024-006 Rev. D (0403)
Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase
OUTDOOR UNITS H*DB036 H*DB048 H*DB060 H*DB076
UNIT ORIFICE(S)
FACTORY CHARGE, LBS. - OZ. 4 - 9 6 -0 8 - 0 14-0
INDOOR COIL
G1FA/G1UA048S17 84 75 + 14 - - G1FA/G1UA048S21 84 75 + 21 84 + 6 - G1FA/G1UA060S21, 24 90 - 84 + 6 90 + 0 G1NA036S17J 67 73 + 2 - - G1NA036S21C 67 73 + 2 - - G1NA048S21D 78 75 + 8 84 + 0 - G2FD035(S,H)14 65 73 + 0 - - G2FD036(S,H)17 75 73 + 3 - - G2FD036(S,H)21 75 73 + 5 - - G2FD042(S,H)21 78 73 + 8 - - G2FD046(S,H)17 78 73 + 7 84 + 0 - G2FD048(S,H)21, 24 84 75 + 20 84 + 3 - G2FD060(S,H)24 90 - 84 + 6 90 + 0 G2FD061H24 90 - - 90 + 5 G1HD036 69 69 + 22 - - G1HD048 81 75 + 14 81 + 2 - G1HD060 93 - 84 + 9 90 + 0 F2RC/FC036 73 73 + 0 - - F2RP/FP036 75 75 + 6 - - F2RP/FP042 78 75 + 8 - - F2FP045 78 78 + 25 - - F2FP048 84 - 84 + 6 - F2FP060 90 - 84 + 8 90 + 0 K 4 E U 0 9 0 ----+ 0
FOOTNOTES:
1. These orifices are packed in the instruction/warranty packet of each outdoor unit.
2. These orifices are factory-mounted in the flow control device of each indoor coil.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.
2. Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
5. If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.
1
COIL ORIFICE
2
73, 75 81,84 90, 93 -
SYSTEM ORIFICE + ADDITIONAL CHARGE, OZ.
4 Unitary Products Group
Page 5
COOLING CAPACITY - With Air Handler Coils
036-21024-006 Rev. D (0403)
UNIT
MODEL
MODEL
AIR HANDLER
ELECTRIC
HEAT. KW
1
2
W
COIL
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
COOLING
SEER
W/O TXV
SEER
+ TXV
EER
3
1 PH 10 SEER AC WITH N1AH / G2FD
H4DB018 N1AHB0806 2,5,8,10 17 G2FD024(S,H)17 650 18.8 13.9 10.30 - 9.25
H4DB024
H4DB030
H4DB036
N1AHB0806 2,5,8,10 17 G2FD024(S,H)17 810 24.8 18.4 10.50 - 9.75
N1AHB0806 2,5,8,10 17 G2FD030(S,H)17 800 25.0 18.5 10.60 - 10.05
N1AHB1206 5,8,10,15,19 17 G2FD030(S,H)17 1000 29.0 21.5 10.60 - 9.90
N1AHB1206 5,8,10,15,19 17 G2FD036(S,H)17 1000 30.0 22.2 12.20 - 10.85
N1AHB1206 5,8,10,15,19 17 G2FD036(S,H)17 1200 35.6 26.3 10.20 - 9.40
N1AHB1206 5,8,10,15,19 17 G2FD046(S,H)17 1200 36.6 27.1 10.40 - 9.55
N1AHC1606 5,8,10,15,20 21 G2FD042(S,H)21 1400 39.5 29.2 10.00 - 9.00
H5DB042
N1AHC1606 5,8,10,15,20 21 G2FD046(S,H)21 1450 40.0 29.6 10.00 - 9.00
N1AHD2006 8,10,15,20,25,30 24 G2FD048(S,H)24 1450 40.5 30.0 10.40 - 9.30
N1AHC1606 5,8,10,15,20 21 G2FD048(S,H)21 1600 48.5 36.4 10.40 - 10.00
H5DB048
N1AHC1606 5,8,10,15,20 21 G2FD048(S,H)21 1600 48.5 36.4 10.40 - 10.00
N1AHD2006 8,10,15,20,25,30 24 G2FD060(S,H)24 1600 49.0 36.8 10.60 - 10.20
H4DB060 N1AHD2006 8,10,15,20,25,30 24 G2FD060(S,H)24 1950 57.5 42.6 10.00 - 9.55
3 PH 10 SEER AC / N1VS - VARIABLE SPEED
N1VSB12 10,15,18 17 G2FD036(S,H)17 1200 36.0 26.6 10.70 - 9.70
H4DB036
N1VSB12 10,15,18 17 G2FD046(S,H)17 1200 36.6 27.1 11.00 - 10.00
N1VSC16 10,15,18 21 G2FD048(S,H)21 1200 37.6 27.8 11.60 - 10.30
H5DB048 N1VSD20 10,15,18,30 24 G2FD060(S,H)24 1630 49.0 36.8 10.80 - 10.25
H4DB060 N1VSD20 10,15,18,30 24 G2FD061H24 1600 58.0 42.9 10.75 - 9.80
1 PH 10 SEER AC / N1VS - VARIABLE SPEED
H4DB018 N1VSB12 10,15,18 17 G2FD024(S,H)17 650 19.2 14.2 11.35 - 10.25
H4DB024
N1VSB12 10,15,18 17 G2FD024(S,H)17 870 25.6 18.9 11.80 - 11.05
N1VSB12 10,15,18 17 G2FD036(S,H)17 870 26.4 19.5 12.00 - 11.25
N1VSB12 10,15,18 17 G2FD036(S,H)17 1200 36.4 26.9 10.80 - 9.80
H4DB036
N1VSB12 10,15,18 17 G2FD046(S,H)17 1200 37.0 27.4 11.10 - 10.10
N1VSC16 10,15,18 21 G2FD048(S,H)21 1200 38.0 28.1 11.70 - 10.40
H5DB042 N1VSC16 10,15,18 21 G2FD048(S,H)21 1430 41.0 30.3 11.00 - 9.90
N1VSC16 10,15,18 21 G2FD048(S,H)21 1600 49.0 36.8 11.00 - 10.45
H5DB048
N1VSD20 10,15,18,30 24 G2FD048(S,H)24 1600 49.5 37.1 11.05 - 10.65
N1VSD20 10,15,18,30 24 G2FD060(S,H)24 1630 49.0 36.8 10.80 - 10.25
H4DB060
N1VSD20 10,15,18,30 24 G2FD060(S,H)24 1980 59.5 44.0 11.10 - 10.65
N1VSD20 10,15,18,30 24 G2FD061H24 1980 59.5 44.0 11.20 - 10.55
1 PH 10 SEER AC / F2RP / RC / FP / FC
H4DB018
F2RC/FC024 5,8,10 18 - 650 18.5 13.7 10.50 - 9.10
F2RP/FP018 2,5,8 18 - 650 18.0 13.3 10.00 - 9.00
F2RC/FC024 5,8,10 18 - 750 23.0 17.0 10.00 - 9.30
H4DB024
F2RP/FP024 5,8,10 18 - 750 23.8 17.6 10.20 - 9.10
F2RP/FP030 5,8,10,15 18 - 750 24.0 17.8 10.40 - 9.20
F2FP040 5,8,10,15 21 - 810 25.6 18.9 11.25 - 9.85
F2RC/FC030 5,8,10,15 18 - 1000 28.0 20.7 10.40 - 9.60
H4DB030
F2RC/FC036 5,8,10,15 21 - 1000 29.0 21.5 10.50 - 9.70
F2RP/FP030 5,8,10,15 18 - 1000 29.0 21.5 10.55 - 9.80
F2RP/FP036 5,8,10,15,19 21 - 1000 29.8 22.1 10.80 11.00 9.90
For Notes see Page 4.
Unitary Products Group 5
Page 6
036-21024-006 Rev. D (0403)
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT
MODEL
MODEL
AIR HANDLER
ELECTRIC
HEAT. KW
1
2
W
COIL
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
COOLING
SEER
W/O TXV
SEER
+ TXV
EER
3
1 PH 10 SEER AC / F2RP / RC / FP / FC (Continued)
F2RC/F2FC036 5,8,10,15 21 - 1200 35.4 26.2 10.10 - 9.35
H4DB036
F2RP/F2FP036 5,8,10,15,19 21 - 1200 36.8 27.2 10.50 - 9.65
F2RP/F2FP042 5,8,10,15 21 - 1200 37.0 27.4 10.50 - 9.60
F2FP045 5,8,10,15 24 - 1200 37.0 27.4 10.50 - 9.50
H5DB042
H5DB048
F2RP/F2FP042 5,8,10,15 21 - 1400 39.5 29.2 10.00 - 8.90
F2FP048 5,8,10,15,20,25 24 - 1400 40.0 29.6 10.00 - 9.00
F2FP048 5,8,10,15,20,25 24 - 1600 47.5 35.2 10.00 - 9.95
F2FP060 5,8,10,15,20,25 24 - 1600 48.0 35.5 10.00 - 9.85
H4DB060 F2FP060 5,8,10,15,20,25 24 - 1950 57.0 42.2 10.00 - 9.40
3 PH 10 SEER AC / F2RP / RC / FP / FC
4,5
F2RC/F2FC036 5,8,10,15 21 - 1200 35.0 25.9 10.00 - 9.25
H4DB036
F2RP/F2FP036 5,8,10,15,19 21 - 1200 36.4 26.9 10.40 - 9.55
F2RP/F2FP042 5,8,10,15 21 - 1200 36.6 27.1 10.40 - 9.50
H5DB048 F2FP048 5,8,10,15,20,25 24 - 1600 48.0 35.5 10.05 - 9.95
H4DB060 F2FP060 5,8,10,15,20,25 24 - 1950 57.0 42.2 10.00 - 9.40
3 PH SEER AC / K2EU
H4DB060 K 2EU060 10,16,25 36 - 1950 56.5 39.5 10.00 - 9.40
H4DB076 K 2EU090 10,16,25,36 52 - 2550 76.6 53.6 - - 10.30
1 PH 10 SEER AC / M1HC
H4DB018 M1HC018F01 0 40 - 460 16.8 12.4 10.30 - 9.60
H4DB024 M1HC024F01 0 40 - 830 24.2 17.9 11.00 - 11.10
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI S tandards 210.
Cooling MBH based on 80 °F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters.
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC
.
models. All ratings remain the same.
5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D. standard.
- = Not applicable
6 Unitary Products Group
Page 7
COOLING CAPACITY - With Upflow, Downflow and Horizontal Furnace and Coils
UNIT
MODEL
H4DB018
H4DB024
H4DB030
H4DB036S06
For Notes see Page 6.
FURNACE**
CFM RANGE
(MIN.-MAX.)
575
725
700
900
875
1125
1050
1350
COIL
W
14,17 G1FA024S14,17 650 18.4 13.6 10.15 - 9.10
14 G1FA030S14 650 18.8 13.9 10.30 - 9.25
- G1HD024 650 18.9 14.0 10.30 - 9.30
17 G1NA030S17H 650 19.0 14.1 10.50 - 9.35
14,17 G1UA024S14,17 650 18.4 13.6 10.15 - 9.10
14 G1UA030S14 650 18.8 13.9 10.30 - 9.25
14,17 G2FD024(S,H)14,17 650 18.8 13.9 10.30 - 9.25
17 G2FD030(S,H)17 650 19.0 14.1 10.50 - 9.35
14 G2FD035(S,H)14 650 19.0 14.1 10.50 - 9.35
14,17 G1FA024S14,17 800 24.6 18.2 10.30 - 9.95
14 G1FA030S14 810 24.8 18.4 10.50 - 9.75
17,21 G1FA036S17,21 800 25.0 18.5 10.60 - 10.05
17,21 G1FA036S17,21 800 25.0 18.5 - 11.00 10.05
- G1HD024 810 23.2 17.2 10.25 - 9.35
- G1HD036 810 25.6 18.9 10.80 - 9.95
17 G1NA030S17H 810 24.4 18.1 10.20 - 9.85
14,17 G1UA024S14,17 800 24.6 18.2 10.30 - 9.95
14 G1UA030S14 810 24.8 18.4 10.50 - 9.75
17,21 G1UA0 36S17,21 800 25.0 18.5 10.60 - 10.05
17,21 G1UA0 36S17,21 800 25.0 18.5 - 11.00 10.05
14,17 G2FD024S14,17 810 24.8 18.4 10.50 - 9.75
17 G2FD030(S,H)17 800 25.0 18.5 10.60 - 10.05
14 G2FD035(S,H)14 800 25.0 18.5 10.60 - 10.05
17 G2FD036(S,H)17 800 25.4 18.8 10.70 - 10.20
14 G1FA030S14 1000 28.8 21.3 10.60 - 9.90
14 G1FA036S14 1000 29.0 21.5 10.80 - 10.00
17,21 G1FA036S17,21 1000 29.0 21.5 10.80 - 10.00
17 G1FA048S17 1000 30.0 22.2 - 11.00 10.20
- G1HD036 1000 29.4 21.8 10.70 - 9.95
17 G1NA030S17K 1000 29.4 21.8 10.60 - 10.05
14 G1UA030S14 1000 28.8 21.3 10.60 - 9.90
14 G1UA036S14 1000 29.0 21.5 10.80 - 10.00
17,21 G1UA0 36S17,21 1000 29.0 21.5 10.80 - 10.00
17 G1UA048S17 1000 30.0 22.2 - 11.00 10.20
17 G2FD030(S,H)17 1000 29.0 21.5 10.60 - 9.90
14 G2FD035(S,H)14 1000 29.0 21.5 10.75 - 9.70
17 G2FD036(S,H)17 1000 30.0 22.2 12.20 - 10.85
17 G2FD036(S,H)17 1000 30.0 22.2 - 10.90 9.95
21 G2FD036(S,H)21 1000 30.0 22.2 - 11.00 10.05
21 G2FD042(S,H)21 1000 30.0 22.2 - 11.00 10.10
17 G2FD046(S,H)17 1000 31.0 22.9 12.45 - 11.10
17 G2FD046(S,H)17 1000 30.0 22.2 - 11.00 10.05
14 G1FA036S14 1200 35.4 26.2 10.00 - 9.30
17,21 G1FA036S17,21 1200 35.4 26.2 10.00 - 9.30
21 G1FA048S21 1200 37.0 27.4 - 10.60 9.75
- G1HD036 1200 35.4 26.2 10.00 - 9.30
- G1HD048 1200 36.8 27.2 10.20 - 9.60
17 G1NA036S17J 1200 35.6 26.3 10.20 - 9.40
21 G1NA036S21C 1200 35.6 26.3 10.20 - 9.40
21 G1NA048S21D 1200 36.8 27.2 10.40 - 9.65
14 G1UA036S14 1200 35.4 26.2 10.00 - 9.30
17,21 G1UA036S17,21 1200 35.4 26.2 10.00 - 9.30
17 G1UA048S17 1200 37.0 27.4 - 10.55 9.70
21 G1UA048S21 1200 37.0 27.4 - 10.60 9.75
14 G2FD035(S,H)14 1200 35.2 26.0 10.00 - 9.35
17 G2FD036(S,H)17 1200 35.6 26.3 10.20 - 9.40
21 G2FD036(S,H)21 1200 36.8 27.2 10.30 - 9.50
21 G2FD042(S,H)21 1200 36.8 27.2 10.40 - 9.65
17 G2FD046(S,H)17 1200 36.6 27.1 10.40 - 9.55
21,24 G2FD048(S,H)21,24 1200 37.2 27.5 - 10.60 9.85
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
COOLING
SEER W/O TDR
W/O TXV
036-21024-006 Rev. D (0403)
SEER + TDR
W/O TXV
EER
Unitary Products Group 7
Page 8
036-21024-006 Rev. D (0403)
COOLING CAPACITY - With Upflow, Downflow and Horizontal Furnace and Coils (Continued)
UNIT
MODEL
H4DB036S25,4
6
H5DB042
H5DB048
H4DB060S06
H4DB060S25,4
6
* Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one.
Refer to Quick Selection Chart for specific f urnace match-up.
**
FURNACE**
CFM RANGE
(MIN.-MAX.)
1050
1350
1225
1575
1400
1800
1700
2100
1700
2200
COIL
W
14 G1FA036S14 1200 35.0 25.9 10.00 - 9.20
17,21 G1FA036S17,21 1200 35.0 25.9 10.00 - 9.20
17 G1FA048S17 1200 36.6 27.1 - 10.45 9.60
21 G1FA048S21 1200 36.6 27.1 - 10.50 9.65
- G1HD036 1200 35.0 25.9 10.00 - 9.30
- G1HD048 1200 36.4 26.9 10.10 - 9.60
17 G1NA036S17J 1200 35.2 26.0 10.10 - 9.30
21 G1NA036S21C 1200 35.2 26.0 10.10 - 9.30
21 G1NA048S21D 1200 36.4 26.9 10.30 - 9.55
14 G1UA036S14 1200 35.0 25.9 10.00 - 9.20
17,21 G1UA0 36S17,21 1200 35.0 25.9 10.00 - 9.20
17 G1UA048S17 1200 36.6 27.1 - 10.45 9.60
21 G1UA048S21 1200 36.6 27.1 - 10.50 9.65
14 G2FD035(S,H)14 1200 34.8 25.8 10.00 - 9.25
17 G2FD036(S,H)17 1200 35.2 26.0 10.10 - 9.30
21 G2FD036(S,H)21 1200 36.4 26.9 10.20 - 9.40
21 G2FD042(S,H)21 1200 36.4 26.9 10.30 - 9.55
17 G2FD046(S,H)17 1200 36.2 26.8 10.30 - 9.45
21,24 G2FD048(S,H)21,24 1200 36.8 27.2 - 10.50 9.75
21 G1FA048S21 1425 40.5 30.0 10.40 - 9.50
- G1HD048 1400 40.0 29.6 10.00 - 9.10
21 G1NA048S21D 1400 39.5 29.2 10.00 - 9.05
21 G1UA048S21 1425 40.5 30.0 10.40 - 9.50
21 G2FD042S21 1400 39.5 29.2 10.00 - 9.00
17 G2FD046S17 1450 40.0 29.6 10.00 - 9.00
21,24 G2FD048S21,24 1450 40.5 30.0 10.40 - 9.30
24 G2FD060S24 1450 41.0 30.3 10.50 - 9.60
21 G1FA048S21 1600 47.5 35.6 10.20 - 9.95
21,24 G1FA060S21,24 1600 49.0 36.8 10.60 - 10.20
- G1HD048 1630 48.0 36.0 10.20 - 9.50
- G1HD060 1600 48.5 36.4 10.20 - 10.20
21 G1NA048S21D 1500 46.5 34.9 10.00 - 9.40
21 G1UA048S21 1600 47.5 35.6 10.20 - 9.95
21,24 G1UA0 60S21,24 1600 49.0 36.8 10.60 - 10.20
17 G2FD046(S,H)17 1500 47.5 35.6 10.20 - 9.10
21,24 G2FD048(S,H)21,24 1600 48.5 36.4 10.40 - 10.00
24 G2FD060(S,H)24 1600 49.0 36.8 10.60 - 10.20
21,24 G1FA060S21,24 1950 57.5 42.6 10.30 - 9.55
- G1HD060 2000 57.5 42.6 10.00 - 9.55
21,24 G1UA0 60S21,24 1950 57.5 42.6 10.30 - 9.55
24 G2FD060(S,H)24 1950 58.5 43.3 10.35 - 9.60
24 G2FD061H24 2000 58.5 43.3 10.35 - 9.55
21,24 G1FA060S21,24 1950 57.5 42.6 10.00 - 9.55
21,24 G1UA0 60S21,24 1950 57.5 42.6 10.00 - 9.55
24 G2FD060(S,H)24 1950 57.5 42.6 10.00 - 9.55
24 G2FD061H24 2000 58.5 43.3 10.35 - 9.55
MODEL
RATED
CFM
TOTAL SENS.
NET MBH
COOLING
SEER W/O TDR
W/O TXV
SEER + TDR
W/O TXV
EER
8 Unitary Products Group
Page 9
036-21024-006 Rev. D (0403)
CONTROL
WIRING
LOW VOLTAGE
JUNCTION BOX
POWER
WIRING
GROUND
LUG
ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
USE COPPER CONDUCTORS ONLY.
THERMOSTAT
TO
INDOOR
BLOWER
TO COIL
NEC
CLASS 2
WIRING
NEC
CLASS 1
WIRING
TO
POWER
SUPPLY
WEATHERPROOF
DISCONNECT
SWITCH
Seal opening(s) with permagum
or equivalent
24” SERVICEACCESS
CLEARANCE
48” OVERHEAD
CLEARANCE
12” REAR AND
SIDES
NOTE: All outdoorwiring must beweatherproof
COOLING PERFORMANCE
MODEL
SUCT. T/P @
COMPR.
AIR TEMP ON CONDENSER
75°F 95°F 115°F 75°F 95°F 115°F
MODEL
SUCT . T/P @
COMPR.
TEMP. PSIG MBH KW MBH KW MBH KW TEMP. PSIG MBH KW MBH KW MBH KW
H4DB018
35 61.5 17.3 1.38 14.7 1.51 12.0 1.66
40 68.5 19.3 1.43 16.5 1.58 13.7 1.74 40 68.5 45.2 3.15 34.2 4.09 24.0 5.39
45 76.0 21.4 1.48 18.4 1.65 15.4 1.83 45 76.0 49.2 3.23 37.3 4.18 26.4 5.48
H5DB042
35 61.5 41.4 3.09 31.1 4.01 21.7 5.31
50 84.0 23.5 1.53 20.4 1.73 17.1 1.92 50 84.0 53.3 3.32 40.6 4.28 28.9 5.58
H4DB024
35 61.5 27.0 1.84 21.6 2.02 16.5 2.17
40 68.5 29.9 1.90 24.1 2.11 18.7 2.29 40 68.5 50.4 4.28 45.6 4.07 40.7 6.03
45 76.0 33.0 1.97 26.7 2.19 20.9 2.40 45 76.0 54.8 4.37 49.8 5.18 44.6 6.17
H5DB048
35 61.5 46.2 4.18 41.6 4.96 36.9 5.89
50 84.0 36.0 2.02 29.4 2.28 23.3 2.51 50 84.0 59.3 4.47 54.0 5.30 48.6 6.31
H4DB030
35 61.5 29.1 2.48 23.0 2.66 17.4 2.81
40 68.5 32.5 2.58 25.8 2.77 19.6 2.93 40 68.5 58.4 4.31 52.8 5.10 47.1 6.03
45 76.0 36.0 2.68 28.7 2.88 21.9 3.06 45 76.0 63.4 4.42 57.6 5.21 51.5 6.16
H4DB060
35 61.5 53.6 4.21 48.3 4.99 42.8 5.90
50 84.0 39.5 2.78 31.6 2.99 24.3 3.18 50 84.0 68.6 4.53 62.4 5.33 56.1 6.29
H4DB036
35 61.5 39.9 3.43 30.8 3.62 22.5 3.81
40 68.5 44.1 3.55 34.3 3.76 25.2 3.97 40 68.5 84.5 5.53 76.9 6.64 69.3 8.00
45 76.0 48.3 3.67 37.8 3.89 28.1 4.11 45 76.0 92.6 5.70 84.3 6.81 76.0 8.17
H4DB076
35 61.5 76.9 5.37 69.9 6.43 62.9 7.84
50 84.0 52.7 3.78 41.5 4.02 31.1 4.25 50 84.0 101.0 5.88 92.1 6.99 83.1 8.36
NOTES:
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 15° superheat and 15° sub-cooling at condensing unit.
a. Increase capacity 1% for each 2° increase in sub-cooling.
b. Decrease capacity 1% for each 2° decrease in sub-cooling.
3. Sub-cooling in excess of 20° may result in excessively high condensing temperature with air on condenser above 115°F.
Maximum recommended condensing temperature is 140°F.
AIR TEMP ON CONDENSER
TYPICAL INSTALLATION
Unitary Products Group 9
Page 10
036-21024-006 Rev. D (0403)
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
208/230-1-60
230-1-50
CONTACTOR
TERMINALS
COIL
GND.
LUG
CYRGW
Y
R
GW
POWER WIRING
CONTROL WIRING
FACTORY WIRING
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
FURNACE OR AIR HANDLER TERMINAL BLOCK
ROOM THERMOSTAT
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
*
*
TYPICAL FIELD WIRING - 1 PHASE APPLICATION
TYPICAL FIELD WIRING - 3 PHASE APPLICATION
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
GND.
LUG
208/230-3-60
460-3-60
575-3-60
380/415-3-50
*
CONTACTOR
TERMINALS
COIL
CONDENSING UNIT
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
POWER WIRING
CONTROL WIRING
FACTORY WIRING
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
YRGW
ROOM THERMOSTAT
*
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
10 Unitary Products Group
Page 11
ACCESSORIES
48" OVERHEAD
CLEARANCE
C
B
A
5-1/2
2-3/8
3-1/8
VAPOR
CONNECTION
LIQUID CONNECTION
AIR IN
4 SIDES
Refer to Price Manual for specific model numbers.
Hard Start Kit - Provides increased starting torque for areas
with low voltage.
Compressor Blanket - Designed to further reduce the nor-
mal compressor operating sound. Refer to price pages for
specific match-ups.
Off Cycle Timer Delay - Provides a 5-minu te off cycle to prevent rapid recycling of the compressor.
Room Thermostats - A wide selection of com p a tib le thermosets are available to provide optimum performance and features for any installation.
1 Heat Stage only, manual, mechanical thermostat. Add subbase for 1H/1C.
1H/1C, manual change-over electronic non-programmable
thermostat.
1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the
price book or consult factory.
SOUND RATINGS
HDB
MODEL
018 76
024 76
030 78
036
042
048
060
076
1. Compressor Blanket Factory Installed.
* Rated in accordance with ARI Standard 270.
SOUND RATING
DECIBELS*
1
78
1
78
1
79
1
78
1
78
036-21024-006 Rev. D (0403)
All dimensions are in inches. They are subject to change without
notice. Certified dimensions will be provided upon request.
1 PHASE
Unit
Model
HDB
018 20-1/8 24 24
024 20-1/8 24 24
030 24-1/8 24 24
036 24-1/8 24 24
042 30-1/8 24 24
060 31-7/8 35 35
Dimensions
(Inches)
A
B C LIQUID VAPOR
Refrigerant Connection
Line Size
5/8
3/8
3/4
7/8 048 30-1/8 24 24
3 PHASE
Unit
Model
HDB
036 24-1/8 24 24
048 30-1/8 24 24
060 31-7/8 35 35
076 31-7/8 35 35 1/2 1-1/8
Dimensions
(Inches)
A B C Liquid Vapor
Refrigerant Connection
Line Size
3/4
3/8
7/8
Unitary Products Group 11
Page 12
036-21024-006 Rev. D (0403)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H4DB018
INDOOR COIL MODEL NO. G1FA024S14,17
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 550 600 650
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 22.1 20.3 18.5 16.8 22.4 20.6 18.8 17.1 22.6 20.8 19.0 17.3
S.C. 13.4 13.4 13.6 13.5 13.8 13.9 14.0 14.0 14.2 14.3 14.4 14.5
K.W 1.81 1.82 1.81 1.79 1.82 1.84 1.84 1.82 1.84 1.86 1.86 1.84
T.C. 21.3 19.5 17.7 16.0 21.5 19.8 17.9 16.3 21.8 19.9 18.1 16.4
S.C. 13.3 13.3 13.5 13.4 13.8 13.8 14.0 14.0 14.3 14.3 14.5 14.5
K.W 1.89 1.90 1.89 1.86 1.91 1.92 1.91 1.88 1.93 1.94 1.94 1.91
T.C. 19.9 18.2 16.4 14.9 20.2 18.4 16.6 15.2 20.3 18.6 16.8 15.4
S.C. 13.0 13.0 13.1 13.2 13.6 13.6 13.7 13.8 14.2 14.1 14.3 14.3
K.W 2.00 2.00 1.98 1.94 2.02 2.02 2.00 1.97 2.04 2.04 2.03 2.00
T.C. 18.4 16.7 15.0 13.6 18.5 16.9 15.2 13.8 18.7 17.0 15.4 13.9
S.C. 12.7 12.6 12.7 12.6 13.2 13.2 13.3 13.2 13.8 13.8 13.9 13.7
K.W 2.13 2.12 2.08 2.04 2.16 2.14 2.11 2.07 2.18 2.17 2.14 2.10
T.C. 16.6 14.9 13.5 12.1 16.7 15.1 13.6 12.4 16.8 15.3 13.8 12.7
S.C. 12.0 12.0 12.0 11.9 12.6 12.6 12.6 12.3 13.2 13.2 13.1 12.6
K.W 2.28 2.25 2.20 2.14 2.30 2.27 2.23 2.18 2.33 2.30 2.26 2.21
T.C. 14.8 13.1 12.0 10.6 14.9 13.3 12.0 11.0 14.9 13.6 12.2 11.5
S.C. 11.3 11.4 11.3 11.2 12.0 12.0 11.9 11.4 12.6 12.6 12.3 11.5
K.W 2.43 2.38 2.32 2.24 2.44 2.40 2.35 2.29 2.48 2.43 2.38 2.32
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than th ose listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
N1AHB08 G2FD024(S,H)17 1.02 1.02 1.01
N1VSB12 G2FD024(S,H)17 1.04 1.04 0.93
F2RC/F2FC024 1.01 1.01 1.02
F2RP/F2FP018 0.98 0.98 0.99
T.C. S.C. KW
Coil
G1FA030S14 1.02 1.02 1.01
G1HD024 1.03 1.03 1.01
G1NA030S17 1.03 1.03 1.00
G1UA024S14,17 1.00 1.00 1.00
G1UA030S14 1.02 1.02 1.01
G2FD024(S,H)14,17 1.02 1.02 1.01
G2FD030(S,H)17 1.03 1.04 1.00
G2FD035(S,H)14 1.03 1.04 1.00
M1HC018F01 0.91 0.91 0.87
T.C. S.C. KW
12 Unitary Products Group
Page 13
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H4DB024
INDOOR COIL MODEL NO. G1FA024S14,17
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 750 800 850
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 28.1 25.7 23.4 21.2 28.3 25.9 23.6 21.4 28.5 26.1 23.8 21.5
S.C. 17.3 17.3 17.4 17.4 17.7 17.7 17.8 17.8 18.1 18.1 18.2 18.2
K.W 2.15 2.10 2.04 1.99 2.18 2.12 2.07 2.02 2.20 2.15 2.10 2.04
T.C. 28.0 25.6 23.2 21.0 28.2 25.8 23.4 21.2 28.4 26.0 23.6 21.4
S.C. 17.7 17.7 17.8 17.8 18.1 18.2 18.3 18.3 18.6 18.6 18.8 18.8
K.W 2.31 2.25 2.18 2.11 2.34 2.27 2.21 2.14 2.36 2.30 2.23 2.17
T.C. 26.7 24.4 22.1 19.9 26.9 24.6 22.3 20.3 27.1 24.8 22.4 20.5
S.C. 17.7 17.7 17.8 17.8 18.2 18.2 18.3 18.5 18.7 18.7 18.8 19.0
K.W 2.52 2.44 2.36 2.28 2.55 2.47 2.39 2.32 2.57 2.50 2.42 2.35
T.C. 25.0 22.8 20.6 18.7 25.1 22.9 20.8 18.9 25.3 23.1 21.0 19.0
S.C. 17.4 17.3 17.5 17.5 18.0 17.9 18.2 18.0 18.5 18.5 18.7 18.5
K.W 2.74 2.66 2.56 2.48 2.77 2.68 2.59 2.51 2.79 2.71 2.62 2.54
T.C. 22.8 20.7 18.8 17.0 22.9 20.8 18.9 17.3 23.0 21.0 19.1 17.5
S.C. 16.7 16.6 16.8 16.5 17.2 17.2 17.3 17.3 17.8 17.7 17.7 17.5
K.W 2.96 2.85 2.75 2.66 2.98 2.88 2.78 2.70 3.01 2.92 2.82 2.73
T.C. 20.6 18.6 17.0 15.3 20.7 18.7 17.0 15.7 20.7 18.9 17.2 16.0
S.C. 16.0 15.9 16.1 15.5 16.4 16.5 16.4 16.6 17.1 16.9 16.7 16.5
K.W 3.18 3.04 2.94 2.84 3.19 3.08 2.97 2.89 3.23 3.13 3.02 2.92
036-21024-006 Rev. D (0403)
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature an d decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
N1AHB08 G2FD024(S,H)17 1.00 1.00 1.00
N1AHB08 G2FD030(S,H)17 1.02 1.02 1.00
N1VSB12 G2FD024(S,H)17 1.04 1.04 1.01
N1VSB12 G2FD036(S,H)17 1.07 1.07 0.94
F2RC/F2FC024 0.93 0.93 1.00
F2RP/F2FP024 0.97 0.97 1.06
F2RP/F2FP030 0.98 0.98 1.06
F2FP040 1.04 1.04 1.05
T.C. S.C. KW
Coil
G1HD024 0.94 0.95 1.00
G1HD036 1.04 1.04 1.04
G1NA030S17 0.99 0.99 1.00
G1UA024S14,17 1.00 1.00 1.00
G1UA030S14 1.01 1.01 1.03
G2FD024(S,H)14,17 1.01 1.01 1.03
G2FD036(S,H)17 1.03 1.03 1.01
G1FA036S17,21 1.02 1.02 1.01
G1UA036S17,21 1.02 1.02 1.01
G2FD030(S,H)17 1.02 1.02 1.01
G2FD035(S,H)14 1.02 1.02 1.01
G1FA030S14 1.01 1.01 1.03
M1HC024F01 0.98 0.98 0.88
T.C. S.C. KW
Unitary Products Group 13
Page 14
036-21024-006 Rev. D (0403)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H4DB030
INDOOR COIL MODEL NO. G1FA036S17,21, G2FD030(S,H)17
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 900 1000 1100
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 33.5 30.7 27.9 25.3 34.1 31.3 28.4 25.8 34.6 31.7 28.9 26.2
S.C. 21.0 21.1 21.2 20.8 21.8 21.9 22.1 20.9 22.6 22.7 22.9 21.7
K.W 2.63 2.55 2.46 2.38 2.68 2.60 2.51 2.43 2.72 2.64 2.55 2.47
T.C. 33.2 30.4 27.6 24.9 33.8 30.9 28.1 25.4 34.2 31.3 28.5 25.8
S.C. 21.1 21.1 21.3 20.9 22.0 22.0 22.3 21.1 22.8 22.9 23.1 21.9
K.W 2.81 2.72 2.62 2.53 2.86 2.77 2.67 2.58 2.90 2.81 2.72 2.62
T.C. 31.3 28.6 25.9 23.4 31.7 29.0 26.3 23.8 32.0 29.3 26.6 24.1
S.C. 20.5 20.6 20.8 20.4 21.4 21.5 21.8 20.6 22.2 22.3 22.6 21.4
K.W 2.98 2.89 2.78 2.68 3.03 2.94 2.84 2.74 3.07 2.98 2.88 2.78
T.C. 28.7 26.2 23.7 21.4 29.1 26.6 24.1 21.8 29.3 26.8 24.4 22.2
S.C. 19.5 19.6 19.8 19.5 20.5 20.7 21.0 19.8 21.5 21.5 21.9 20.8
K.W 3.15 3.05 2.95 2.84 3.20 3.10 2.99 2.89 3.23 3.14 3.03 2.93
T.C. 25.7 23.5 21.3 19.3 26.1 23.8 21.5 19.6 26.2 24.0 21.9 19.9
S.C. 18.5 18.5 18.7 18.5 19.6 19.5 19.7 18.6 20.5 20.5 20.8 19.6
K.W 3.30 3.20 3.09 2.98 3.34 3.25 3.14 3.04 3.38 3.28 3.18 3.08
T.C. 22.7 20.8 18.9 17.2 23.1 21.0 18.9 17.4 23.1 21.2 19.4 17.6
S.C. 17.5 17.4 17.6 17.5 18.7 18.3 18.4 17.4 19.5 19.5 19.7 18.4
K.W 3.45 3.35 3.23 3.12 3.48 3.40 3.29 3.19 3.53 3.42 3.33 3.23
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than th ose listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
N1AHB12 G2FD030(S,H)17 1.00 1.00 1.01
N1AHB12 G2FD036(S,H)17 1.03 1.03 0.95
N1VSB12 G2FD036(S,H)17 1.03 1.03 0.95
N1VSB12 G2FD046(S,H)17 1.07 1.07 0.96
F2RC/F2FC030 0.97 0.97 1.01
F2RC/F2FC036 1.00 1.00 1.03
F2RP/F2FP030 1.00 1.00 1.02
F2RP/F2FP036 1.03 1.03 1.04
F2RP/F2FP036 1.03 1.03 1.04
T.C. S.C. KW
Coil
G1FA036S14 1.00 1.00 1.00
G1FA048S17 1.03 1.03 1.01
G1HD036 1.01 1.01 1.02
G1NA030S17K 1.01 1.01 1.01
G1UA030S14 0.99 0.99 1.00
G1UA036S14 1.00 1.00 1.00
G1UA036S17,21 1.00 1.00 1.00
G1UA048S17 1.03 1.03 1.01
G2FD030(S,H)17 1.00 1.00 1.01
G2FD035(S,H)14 1.00 1.00 1.03
G2FD036(S,H)17 1.03 1.03 1.04
G2FD036(S,H)21 1.03 1.03 1.03
G2FD042(S,H)21 1.03 1.03 1.02
G2FD046(S,H)17 1.03 1.03 1.03
G1FA030S14 0.99 0.99 1.00
T.C. S.C. KW
14 Unitary Products Group
Page 15
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H4DB036
INDOOR COIL MODEL NO. G1FA036S17,21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 1100 1200 1300
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 41.4 37.9 34.5 31.3 41.9 38.4 35.0 31.8 42.3 38.8 35.4 32.1
S.C. 25.5 25.6 25.8 25.9 26.3 26.4 26.7 26.8 27.1 27.2 27.6 27.7
K.W 3.43 3.33 3.22 3.11 3.49 3.39 0.88 3.17 3.53 3.43 3.33 3.22
T.C. 40.9 37.5 34.0 30.9 41.3 37.9 34.4 31.2 41.7 38.2 34.8 31.6
S.C. 25.7 25.8 26.1 26.1 26.6 26.7 27.0 27.1 27.4 27.6 27.9 28.0
K.W 3.66 3.55 3.43 3.31 3.72 3.61 3.49 3.37 3.76 3.65 3.53 3.41
T.C. 38.3 35.1 31.9 28.8 38.6 35.4 32.2 29.3 39.0 35.8 32.5 29.7
S.C. 25.1 25.2 25.5 25.6 26.0 26.2 26.5 26.8 27.1 27.2 27.6 27.8
K.W 3.87 3.76 3.64 3.51 3.93 3.82 3.69 3.58 3.97 3.86 3.73 3.62
T.C. 35.0 32.1 29.2 26.5 35.3 32.3 29.3 26.8 35.5 32.5 29.7 27.1
S.C. 24.2 24.3 24.7 24.8 25.3 25.3 25.6 25.8 26.3 26.3 26.9 26.7
K.W 4.08 3.96 3.83 3.70 4.13 4.02 3.89 3.77 4.18 4.06 3.93 3.81
T.C. 31.3 28.7 26.1 23.8 31.5 28.9 26.4 24.5 31.6 29.0 26.5 24.8
S.C. 23.1 23.1 23.5 23.4 24.1 24.2 24.4 24.7 25.1 25.2 25.2 25.0
K.W 4.27 4.15 4.01 3.88 4.32 4.20 4.07 3.97 4.36 4.24 4.13 4.03
T.C. 27.6 25.3 23.0 21.1 27.7 25.5 23.5 22.2 27.7 25.5 23.3 22.5
S.C. 22.0 21.9 22.3 22.0 22.9 23.1 23.2 23.6 23.9 24.1 23.5 23.3
K.W 4.46 4.34 4.19 4.06 4.51 4.38 4.25 4.17 4.54 4.42 4.33 4.25
036-21024-006 Rev. D (0403)
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature an d decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
N1AHB12 G2FD036(S,H)17 1.01 1.01 0.99
N1AHB12 G2FD046(S,H)17 1.03 1.03 1.01
N1VSB12 G2FD036(S,H)17 1.03 1.03 0.98
N1VSB12 G2FD046(S,H)17 1.05 1.05 0.96
N1VSC16 G2FD048(S,H)21 1.07 1.07 0.96
F2RC/F2FC036 1.00 1.00 0.99
F2RP/F2FP036 1.04 1.04 1.00
F2RP/F2FP042 1.05 1.05 1.01
F2FP045 1.05 1.05 1.02
T.C. S.C. KW
Coil
G1FA036S14 1.00 1.00 1.00
G1FA048S17 1.05 1.05 1.00
G1FA048S21 1.05 1.05 1.00
G1HD036 1.00 1.00 1.00
G1HD048 1.04 1.04 1.01
G1NA036S17J 1.01 1.01 0.99
G1NA036S17D 0.99 0.99 1.03
G1NA036S21C 1.01 1.01 0.99
G1NA048S21D 1.04 1.04 1.00
G1UA036S14 1.00 1.00 1.00
G1UA036S17,21 1.00 1.00 1.00
G1UA048S17 1.05 1.05 1.00
G1UA048S21 1.05 1.05 1.00
G2FD035(S,H)14 0.99 0.99 0.99
G2FD036(S,H)21 1.04 1.04 1.02
G2FD042(S,H)21 1.04 1.04 1.00
G2FD046(S,H)17 1.03 1.03 1.01
G2FD048(S,H)21,24 1.05 1.05 0.99
G2FD036(S,H)17 1.01 1.01 0.99
M3HD048S 0.99 0.99 1.03
T.C. S.C. KW
Unitary Products Group 15
Page 16
036-21024-006 Rev. D (0403)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H5DB042
INDOOR COIL MODEL NO. G1FA048S21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 1300 1400 1500
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 48.0 44.1 40.1 36.5 48.4 44.5 40.5 36.9 48.8 44.8 40.9 37.5
S.C. 29.9 30.0 30.3 30.3 30.8 30.9 31.2 31.2 31.6 31.7 32.1 32.4
K.W 3.98 3.85 3.71 3.57 4.04 3.91 3.77 3.63 4.09 3.97 3.83 3.70
T.C. 46.3 42.5 38.7 35.3 46.6 42.8 39.0 35.7 46.9 43.1 39.3 36.0
S.C. 29.8 29.9 30.2 30.5 30.8 30.9 31.2 31.4 31.7 31.8 32.1 32.3
K.W 4.24 4.11 3.96 3.81 4.30 4.16 4.02 3.88 4.35 4.22 4.07 3.94
T.C. 43.8 40.2 36.6 33.4 44.2 40.5 37.0 33.8 44.3 40.8 37.3 34.1
S.C. 29.3 29.4 29.7 29.7 30.5 30.4 31.0 30.9 31.3 31.4 31.9 32.0
K.W 4.48 4.34 4.18 4.03 4.53 4.39 4.24 4.08 4.59 4.45 4.30 4.16
T.C. 40.8 37.5 34.2 31.1 41.1 37.7 34.5 31.5 41.3 38.0 34.7 32.3
S.C. 28.5 28.6 28.9 28.8 29.6 29.6 29.9 30.0 30.7 30.7 30.9 31.5
K.W 4.70 4.55 4.39 4.22 4.75 4.61 4.45 4.29 4.80 4.67 4.51 4.38
T.C. 37.8 34.7 31.7 28.9 37.9 34.9 31.9 29.7 38.3 35.2 32.2 30.1
S.C. 27.6 27.6 27.9 27.8 28.5 28.6 28.9 29.0 29.7 29.8 30.1 29.4
K.W 4.90 4.75 4.58 4.41 4.97 4.81 4.64 4.50 5.01 4.86 4.70 4.57
T.C. 34.8 31.9 29.2 26.7 34.7 32.1 29.3 27.9 35.3 32.4 29.7 27.9
S.C. 26.7 26.6 26.9 26.8 27.4 27.6 27.9 28.0 28.7 28.9 29.3 27.3
K.W 5.10 4.95 4.77 4.60 5.19 5.01 4.83 4.71 5.22 5.05 4.89 4.76
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than th ose listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
N1AHC16 G2FD042(S,H)21 0.98 0.98 1.03
N1AHC1606 G2FD046(S,H)21 0.99 0.99 1.04
N1AHD2006 G2FD048(S,H)24 1.00 1.00 1.02
N1VSC16 G2FD048(S,H)21 1.01 1.01 0.97
F2RP/F2FP042 0.98 0.98 1.04
F2FP048 0.99 0.99 1.04
T.C. S.C. KW
Coil
G1UA048S21 1.00 1.00 1.00
G2FD046(S,H)17 0.99 0.99 1.04
G2FD048(S,H)21,24 1.00 1.00 1.02
G2FD060(S,H)24 1.01 1.01 1.00
G1HD048 0.99 0.99 1.03
G2FD042(S,H)21 0.98 0.98 1.03
G1NA048S21D 0.98 0.98 1.02
T.C. S.C. KW
16 Unitary Products Group
Page 17
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H5DB048
INDOOR COIL MODEL NO. G1FA048S21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 1550 1600 1650
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 53.0 49.0 45.0 41.2 53.2 49.2 45.2 41.4 53.4 49.3 45.3 41.5
S.C. 34.5 34.8 35.3 35.6 35.0 35.2 35.8 36.0 35.4 35.6 36.3 36.5
K.W 4.06 3.98 3.91 3.85 4.08 4.00 3.93 3.86 4.10 4.02 3.95 3.88
T.C. 52.6 48.5 44.5 40.9 52.7 48.7 44.6 41.0 52.9 48.9 44.8 41.2
S.C. 34.9 35.1 35.8 36.1 35.4 35.7 36.3 36.6 36.0 36.2 36.7 37.0
K.W 4.44 4.35 4.26 4.19 4.45 4.36 4.28 4.21 4.47 4.38 4.30 4.23
T.C. 51.3 47.3 43.4 39.7 51.5 47.5 43.4 39.9 51.6 47.6 43.6 40.0
S.C. 34.9 35.1 35.8 35.8 35.4 35.6 36.1 36.3 35.9 36.1 36.6 36.8
K.W 4.72 4.62 4.53 4.45 4.73 4.64 4.55 4.47 4.76 4.66 4.57 4.49
T.C. 49.6 45.7 41.7 38.3 49.7 45.8 41.9 38.4 49.9 46.0 42.1 38.6
S.C. 34.4 34.7 35.0 35.2 34.9 35.2 35.7 35.7 35.5 35.7 36.4 36.3
K.W 5.00 4.90 4.81 4.71 5.01 4.91 4.81 4.73 5.03 4.94 4.84 4.76
T.C. 47.6 43.9 40.1 36.7 47.8 44.0 40.3 36.8 47.9 44.1 40.4 37.0
S.C. 33.6 33.8 34.4 34.4 34.3 34.4 35.1 34.9 34.7 34.9 35.4 35.5
K.W 5.29 5.18 5.08 4.98 5.30 5.20 5.09 5.00 5.33 5.22 5.12 5.02
T.C. 45.6 42.1 38.5 35.1 45.9 42.2 38.7 35.2 45.9 42.2 38.7 35.4
S.C. 32.8 32.9 33.8 33.6 33.7 33.6 34.5 34.1 33.9 34.1 34.4 34.7
K.W 5.58 5.46 5.35 5.25 5.59 5.49 5.37 5.27 5.63 5.50 5.40 5.28
036-21024-006 Rev. D (0403)
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature an d decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
N1AHC16 G2FD048(S,H)21 1.02 1.02 1.02
N1AHC16 G2FD048(S,H)24 1.02 1.02 1.00
N1AHD20 G2FD060(S,H)24 1.03 1.03 1.01
N1VSC16 G2FD048(S,H)21 1.03 1.03 0.98
N1VSD20 G2FD048(S,H)24 1.04 1.04 0.97
N1VSD20 G2FD060(S,H)24 1.03 1.03 1.00
F2FP048 1.00 0.99 1.00
F2FP060 1.01 1.00 1.02
T.C. S.C. KW
Coil
G1UA048S21 1.00 1.00 1.00
G2FD060(S,H)24 1.03 1.03 1.01
G1FA060S21,24 1.03 1.03 1.01
G2FD048(S,H)21,24 1.02 1.02 1.02
G1FD046S17 1.00 1.00 1.09
G1HD048 1.01 1.01 1.06
G1HD060 1.02 1.02 1.00
G1NA048S21D 0.98 0.98 1.04
G1UA060S21,24 1.03 1.03 1.01
T.C. S.C. KW
Unitary Products Group 17
Page 18
036-21024-006 Rev. D (0403)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H4DB060
INDOOR COIL MODEL NO. G1FA060S21,24
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 1700 1850 2000
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 33.7 58.8 53.8 49.2 64.3 59.3 54.4 49.7 64.8 59.8 54.8 50.5
S.C. 40.1 40.4 41.0 41.3 41.5 41.8 42.4 42.7 42.8 43.1 43.8 44.5
K.W 5.27 5.16 5.06 4.96 5.34 5.24 5.13 5.04 5.41 5.30 5.19 5.11
T.C. 63.1 58.1 53.1 48.4 63.7 58.7 53.6 49.3 64.1 59.1 54.1 49.8
S.C. 40.7 40.9 41.5 41.7 42.2 42.4 43.0 43.5 43.7 43.9 44.7 45.0
K.W 5.75 5.63 5.52 5.41 5.83 5.71 5.60 5.49 5.90 5.78 5.65 5.56
T.C. 62.1 57.2 52.2 47.7 62.7 57.5 52.5 48.2 63.1 58.0 53.1 48.6
S.C. 40.9 41.1 41.7 42.0 42.6 42.6 43.2 43.5 44.2 44.2 45.0 45.0
K.W 6.08 5.96 5.83 5.73 6.16 6.04 5.92 5.81 6.23 6.11 5.99 5.88
T.C. 60.4 55.5 50.5 46.1 60.9 55.9 51.2 46.7 61.2 56.3 51.6 47.2
S.C. 40.3 40.6 41.1 41.3 42.1 42.2 43.1 43.2 43.7 44.0 44.8 44.8
K.W 6.42 6.29 6.16 6.04 6.50 6.37 6.23 6.12 6.57 6.43 6.30 6.18
T.C. 58.2 53.4 48.7 44.5 58.7 53.9 49.3 44.9 59.1 59.3 49.7 45.5
S.C. 39.5 39.7 40.4 40.6 41.2 41.4 42.2 42.3 43.1 43.2 43.7 44.1
K.W 6.75 6.61 6.47 6.34 6.83 6.69 6.54 6.42 6.89 6.45 6.62 6.49
T.C. 56.0 51.3 46.9 42.9 56.5 51.9 47.4 43.1 57.0 62.3 47.8 43.8
S.C. 38.7 38.8 39.7 39.9 40.3 40.6 41.3 41.4 42.5 42.4 42.6 43.4
K.W 7.08 6.93 6.78 6.64 7.16 7.01 6.85 6.72 7.21 6.47 6.94 6.80
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than th ose listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
N1AHD20 G2FD060(S,H)24 1.02 1.02 1.02
N1VSD20 G2FD060(S,H)24 1.03 1.03 0.93
N1VSD20 G2FD061H24 1.03 1.03 0.94
F2FP060 0.99 0.99 1.02
T.C. S.C. KW
Coil
G1HD060 1.00 1.00 1.00
G1UA060S21,24 1.00 1.00 1.00
G2FD060(S,H)24 1.02 1.02 1.02
G2FD061H24 1.02 1.03 1.02
T.C. S.C. KW
H4DB060S25,46 ONLY
Coil
G2FD060S24 1.00 1.00 1.00
K2EU060 0.97 0.93 1.05
T.C. S.C. KW
18 Unitary Products Group
Page 19
036-21024-006 Rev. D (0403)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H4DB076
INDOOR COIL MODEL NO. KEU090A33A
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature an d decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM 1900 2550 3150
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
T.C. 75.4 72.8 70.5 78.2 75.5 73.4 81.0 78.2 76.2
S.C. 46.5 46.3 45.9 52.8 52.7 52.2 59.1 59.0 58.4
K.W 6 .11 6.03 5.97 6.42 6.32 6.29 6.72 6.62 6.60
T.C. 72.9 70.3 67.3 75.4 72.8 70.0 77.9 75.3 72.7
S.C. 45.7 45.4 44.6 52.2 51.9 51.1 58.6 58.3 57.5
K.W 6.67 6.56 6.51 7.01 6.89 6.85 7.34 7.22 7.19
T.C. 70.4 67.8 64.1 72.6 70.1 66.7 74.8 72.4 69.2
S.C. 44.9 44.5 43.3 51.5 51.1 50.0 58.1 57.6 56.6
K.W 7.23 7.09 7.05 7.60 7.46 7.42 7.96 7.82 7.78
T.C. 67.8 64.3 59.7 69.7 66.5 62.2 71.6 68.7 64.6
S.C. 44.2 43.3 41.7 50.6 49.8 48.1 57.0 56.2 54.5
K.W 8.01 7.87 7.78 8.39 8.26 8.16 8.76 8.65 8.54
T.C. 65.2 60.8 55.3 66.8 63.9 57.7 68.4 65.0 60.0
S.C. 43.3 42.0 40.0 49.6 49.5 46.2 55.9 54.8 52.4
K.W 8.78 8.64 8.50 9.17 8.99 8.90 9.56 9.48 9.30
T.C. 62.6 57.3 50.9 63.9 61.3 53.2 65.2 61.3 55.4
S.C. 42.4 40.7 38.3 48.6 49.2 44.3 54.8 53.4 50.3
K.W 9.55 9.41 9.22 9.96 9.72 9.64 10.36 10.31 10.06
Unitary Products Group 19
Page 20
MATCHING INDOOR COMPONENTS
ADD-ON COILS - FOR FURNACE APPLICATIONS
G1UA
1/2 CASED
UPFLOW
G1FA
FULL CASED
UPFLOW
* Available with factory installed horizontal drain pan.
G1HD
HORIZONTAL DUCT
AIR HANDLERS - FOR NON-FURNACE APPLICATIONS
G1NA
UNCASED
UPFLOW
G2FD*
MULTI-POSITION
(UPFLOW, HORIZONTAL
AND DOWNFLOW)
N1AH OR N1VS
MODULAR BLOWER
(UPFLOW, HORIZONTAL
AND DOWNFLOW)
Subject to change without notice. Printed in U.S.A. 036-21024-006 Rev. D (0403)
Copyright © by York International Corp. 2003. All rights reserved. Supersedes: 036-21024-006 Rev C (0203)
Unitary 5005 Norman
Product York OK
Group Drive 73069
G2FD
COIL
F2RC / F2FC OR
F2RP / F2FP / F2FV
FAN COIL UNITS (UPFLOW, HORIZONTAL)
F3RP / F3FP/