York SMC 104, SMC-106, SMC-108, TSMC 108 Mk 3 Instruction Manual

Page 1

Instruction Manual

SMC 104-106-108/TSMC 108 Mk 3
Reciprocating Compressor
Christian X´s Vej 201, P.O. Box 1810, DK-8270 Højbjerg, Denmark
Phone +45 86 27 12 66 . Fax +45 86 27 44 08
Page 2
00.01
Specifications for SMC 104Ć106Ć108 Mk3 and TSMC 108 Mk3, SĆLĆE
The SMC/TSMC-type piston compressor can be fitted with a range of equipment, depend­ing on the function and requirements it is ex­pected to meet.
Some of these variants are discussed in this
Compressor type Designation
Serial number Refrigerant
Control
Compressor cooling
R717 R22R134aR404A R507_____
UNISAB II Control- and regulating system Analogue Control System Thermopump Water cooled top and side covers Air cooled top and side covers
instruction manual, even if they are not fea- tured on your particular unit.
The variants featured on the unit are marked with an x in the following diagram, with the serial number stated below.
Oil cooling (water-cooled side covers) Oil cooling OSSI/HE8S Coupling
Drive type
Explosion-proof electrical design
Oil pump drive
Equipment for parallel operation SABROE OVUR-type oil separator
V-belts
Pinion drive Chain drive
0178-910-EN
1
Page 3

Preface

The aim of this instruction manual is to provide the operators with a thorough knowledge of the compressor and the unit, at the same time providing information about:
this instruction manual to ensure reliable and efficient operation of the plant as SABROE is unable to provide a guarantee against damage occurring during the warranty period where this is attributable to incorrect
S the function and maintenance of the
operation.
individual components;
S service schedules; S procedure for dismantling and
reassembling of the compressor.
To prevent accidents during dismantling and assembly of compressors and components, these should only be carried out by authorized personnel.
The instruction manual also draws attention to typical sources of errors which may occur during operations. It states their cause and explains what should be done to rectify them.
The contents of this instruction manual must not be copied or passed on to any unauthorized person without Sabroe’s
It is imperative that the operators familiarize
permission.
themselves thoroughly with the contents of
In the space below you can enter the name and address of your local SABROE REPRESENTATIVE :
0171-500-EN 96.06
SABROE REFRIGERATION A/S
P.O. Box 1810, DK–8270 Højbjerg
Chr. Xs Vej 201, Århus, Denmark
Phone:
Telefax:
2
+45 86 27 12 66 +45 86 27 44 74
0171-702-EN
Page 4
List of Contents
Specifications for SMC 104-106-108 Mk3 and TSMC 108 Mk3, S-L-E 1. . . . . . . . . . . . . . .
Preface 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Contents 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
First Aid for accidents with Ammonia 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
First Aid for accidents with HFC/HCFC 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protecting the environment 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description of compressor 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Handling of the compressor, areas of application, safety equipment etc. 16. . . . . . . . . . . . .
Sound data for reciprocating and screw sompressor units - all types of compressors. 17.
Vibration data for compressors - all types 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compressor data for reciprocating compressor 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating limits 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R717 - Operating limits single stage compressors CMO, SMC 100 S-L, SMC 180 23. .
R717 - Operating limits single stage compressors SMC 100 E 24. . . . . . . . . . . . . . . . . . .
R717 - Operating limits two-stage compressors TCMO, TSMC 100 S-L-E, TSMC 180 25.
R22- Operating limits single stage compressors CMO, SMC 100 S-L, SMC 180 26. . . .
R22 - Operating limits two-stage compressors TCMO, TSMC 100 S-L, TSMC 180 27.
R134a - Operating limits single stage compressors CMO, SMC 100 S-L 28. . . . . . . . . .
R134a - Operating limits two-stage compressors TCMO, TSMC 100 S-L 29. . . . . . . . . .
R404A - Operating limits single stage compressors CMO, SMC 100 S-L 30. . . . . . . . . .
R404A - Operating limits two-stage compressors, TCMO, TSMC 100 S-L 31. . . . . . . . .
R507 - Operating limits single stage compressors CMO, SMC 100 S-L 32. . . . . . . . . . .
R507 - Operating limits two-stage compressors TCMO, TSMC 100 S-L 33. . . . . . . . . . .
R407 - Operating limits one-stage compressors CMO & SMC 34. . . . . . . . . . . . . . . . . . .
General operating instructions for CMO/TCMO, SMC/TSMC piston compressors 35. . . . .
Starting up compressor and plant 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stopping and starting-up compressor during a short period of standstill 36. . . . . . . . . . .
Stopping plant for brief periods (until 2-3 days) 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stopping plant for lengthy periods (more than 2-3 days) 37. . . . . . . . . . . . . . . . . . . . . . . .
Automatic plants 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure testing refrigeration plant 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pumping down refrigeration plant 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating log 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing the piston compressor 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure drop test: 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing refrigerant from compressor 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lubricating oil 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lubricating oil requirements 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General rules for use of lubricating oil in refrigeration compressors 46. . . . . . . . . . . . . . .
Instructions for choosing lubricating oil for refrigeration compressors 46. . . . . . . . . . . . .
Charging refrigeration compressor with lubricating oil 46. . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing oil in refrigeration compressor 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging the compressor with oil 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0178-910-EN
3
Page 5
Assessing the oil 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Visual assessment 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analytical evaluation 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Procedure 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The analysis 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Expected discharge gas temperatures 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing the refrigeration plant 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance of reciprocating compressor 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. If the compressor is operational 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. If the compressor is inoperative 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Top covers 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting top and water covers 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discharge valve 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tightness testing of discharge valve 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cylinder lining with suction valve 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting rod 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Piston 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shaft seal 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Crankshaft 67. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main bearings 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compressor lubricating system 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil pump 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chain-driven oil pump with inverse direction of rotation 72. . . . . . . . . . . . . . . . . . . . . . . . .
Oil pressure valve 74. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
By-pass valve pos. 24 75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil filter 76. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Suction filters 78. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stop valves 79. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unloaded start and capacity regulation on SMC and TSMC 100 and 180 compressors 81
Description of unloader mechanism and capacity regulation 81. . . . . . . . . . . . . . . . . . . . .
Pilot solenoid valves 83. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Schematic outlines 84. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard unloaded start and capacity regulation 85. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Schematic drawings 1 85. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Totally unloaded start and capacity regulation 86. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Schematic drawings 2 86. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relief cylinders 87. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating rods for heating the oil in reciprocating and screw compressors 88. . . . . . . . . . . . .
Stop valves pos. 23 and 42 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring cylinder lining insertion 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Checking clearance volume 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustment is made as follows: 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Checking lifting reserve 91. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Check lifting reserve: 91. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure gauges 93. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Undersize Bearing Diameters for Crankshaft 95. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sundry clearances and check dimensions 96. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
0178-910-EN
Page 6
Torque moments for screws and bolts 97. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigeration Plant Maintenance 99. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operational reliability 99. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pumping down the refrigeration plant 99. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dismantling plant 99. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tightness testing and pump-down of refrigeration plant 100. . . . . . . . . . . . . . . . . . . . . . . . .
Trouble-shooting on the Reciprocating Compressor Plant 101. . . . . . . . . . . . . . . . . . . . . . . . . .
Remedying malfunctions 110. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting lubricating oil for SABROE compressors 113. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data sheet for listed Sabroe oils 119. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of major oil companies 141. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alignment of unit, AMR coupling 143. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fitting and alignment of AMR-type coupling 146. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Boring of motor flange for AMR coupling 149. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V-belt drive for piston compressor types (T)CMO and (T)SMC 150. . . . . . . . . . . . . . . . . . . . . .
Oil Separator OVUR for SMC/TSMC 100 HPC - SMC/TSMC 180 152. . . . . . . . . . . . . . . . . . .
Connections on SMC 104-106-108 Mk3, HPC 104S-106S-108S 156. . . . . . . . . . . . . . . . . . . .
Connections on TSMC 108 Mk3 157. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil return in parallel operation for reciprocating compressors 158. . . . . . . . . . . . . . . . . . . . . . .
Reciprocating compressors used for air conditioning 161. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water-cooling of reciprocating compressors 162. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure loss in water cooling on SMC/TSMC/HPC compressors 165. . . . . . . . . . . . . . . .
Thermo pump cooling of R717 reciprocating compressors 166. . . . . . . . . . . . . . . . . . . . . . . . .
Principle drawings 167. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil cooling with an OSSI or HE8S oil cooler 175. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HFC and HCFC compressors: 175. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling of the intermediate gas on TCMO and TSMC 100 and 180 176. . . . . . . . . . . . . . . . .
Ordering Spare Parts 181. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Spare parts sets for compressors and units 182. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compressor block 182. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Spare part set for Basic Unit 182. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of parts for SMC/TSMC 0661-680. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tools for compressor SMC/TSMC 0661-684. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Spare Parts drawing 0661-521/0661-522. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Spare Parts drawings (in detail) 0661-520. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Piping diagram order specific. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring diagram order specific. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimension sketch order specific. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling water diagram order specific. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Foundation order specific. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Positioning of vibration dampers order specific. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0178-910-EN
5
Page 7
First Aid for accidents with Ammonia
(Chemical formula: NH3 - refrigerant no.: R717)
General
Ammonia is not a cumulative poison. It has a distinctive, pungent odour that even at very low, harmless concentrations is detectable by most persons. Since ammonia is self-alarm­ing, it serves at its own warning agent, so that no person will voluntarily remain in con­centrations which are hazardous. Since am­monia is lighter than air, adequate ventilation is the best means of preventing an accu­mulation.
Experience has shown that ammonia is ex­tremely hard to ignite and under normal conditions is a very stable compound. Under extremely high, though limited concentra­tions, ammonia can form ignitable mixtures with air and oxygen, and should be treated with respect.
Basic rules for first aid
1. Call a doctor immediately.
2. Be prepared: Keep an irrigation bottle available, containing a sterile isotonic (0.9%) NaCl-solution (salt water).
3. A shower bath or water tank should be available near all bulk installations with ammonia.
4. When applying first aid, the persons as­sisting should be duly protected to avoid further injury.
Inhalation
1. Move affected personnel into fresh air im­mediately, and loosen clothing restricting breathing.
2. Call a doctor/ambulance with oxygen
equipment immediately
3. Keep the patient still and warmly wrapped in blankets.
4. If mouth and throat are burnt (freeze or acid burn), let the conscious patient drink water, taking small mouthfuls.
5. If conscious and the mouth is not burnt, give hot, sweet tea or coffee (never feed an unconscious person).
6. Oxygen may be administered, but only when authorized by a doctor.
7. If breathing fails, apply artificial respira­tion.
Eye injuries from liquid splashes or concentrated vapour
1. Force the eyelids open and rinse eyes im­mediately for at least 30 minutes with the salt water solution just mentioned
2. Call a doctor immediately.
0170-008-EN 96.01
6
0178-910-EN
Page 8
Skin burns from liquid splashes or concentrated vapour
2. Call a doctor immediately.
1. Wash immediately with large quantities of water and continue for at least 15 minutes, removing contaminated clothing carefully while washing.
No plant can ever be said to be too safe.
Safety is a way of life.
3. After washing, apply wet compresses (wetted with a sterile isotonic (0.9%) NaCl-solution (salt water)) to affected areas until medical advice is available.
0178-910-EN
7
Page 9
First aid for accidents with HFC/HCFC
Refrigerant no.: R134a – R404A - R410A - R505A - R507 - R22, etc
General
HFC/HCFC form colourless and invisible gasses which are heavier than air and smell faintly of chloroform at high concentrations only. They are non-toxic, non-inflammable, non-explosive and non-corrosive under nor­mal operating conditions. When heated to above approx. 300 toxic, acid gas components, which are strongly irritating and aggessive to nose, eyes and skin and generally corrosive. Be­sides the obvious risk of unnoticeable, heavy gases displacing the atmospheric oxygen, inhalation of larger concentrations may have an accumulating, anaesthetic effect which may not be immediately apparent. 24 hours medical observation is, therefore, recom­mended.
°C they break down into
Inhalation
1. Move affected person into fresh air im­mediately. Keep the patient still and warm and loosen clothing restricting breathing.
2. If unconscious, call a doctor/ambulance with oxygen equipment immediately.
3. Give artificial respiration until a doctor au­thorizes other treatment.
Eye injuries
1. Force eyelids open and rinse with a sterile isotonic (0.9%) NaCl-solution (salt water) or pure running water continuously for 30 minutes.
2. Contact a doctor, or get the patient to a hospital immediately for medical advice.
Skin injuries – Freeze burns
Basic rules for first aid
1. When moving affected persons from low­lying or poorly ventilated rooms where high gas concentrations are suspected, the rescuer must be wearing a lifeline, and be under continuous observation from an assistant outside the room.
2. Adrenalin or similar heart stimuli must not be used.
No plant can ever be said to be too safe.
Safety is a way of life.
1. Wash immediately with large quantities of luke warm water to reheat the skin. Continue for at least 15 minutes, removing contaminated clothing carefully while washing.
2. Treat exactly like heat burns and seek medical advice.
3. Avoid direct contact with contaminated oil/ refrigerant mixtures from electrically burnt­out hermetic compressors.
8
0178-910-EN
Page 10
Protecting the environment
0170-009-EN 96.01
Increasing industrialisation threatens our en­vironment. It is therefore absolutely impera­tive that we protect nature against pollution.
To this end, many countries have passed le­gislation in an effort to reduce pollution and preserve the environment. These laws apply to all fields of industry, including refrigeration, and must be complied with.
Be especially careful with the following sub­stances:
S refrigerants S cooling media (brines etc) S lubricating oils.
Refrigerants usually have a natural boiling point which lies a good deal below 0°C. This means that liquid refrigerants can be extre­mely harmful if they come into contact with skin or eyes.
High concentrations of refrigerant vapours are suffocating when they displace air; if high
concentrations of refrigerant vapours are in­haled they attack the human nerve system.
When halogenated gasses come into contact with open flame or hot surfaces (over approx. 300°C) they decompose to produce poiso­nous chemicals, which have a very pungent odour, warning you of their presence.
In high concentrations, R717 causes respira­tory problems, and when ammonia vapour and air mix 15 to 28 vol. %, the combination is explosive and can be ignited by an electric spark or open flame.
Oil vapour in the ammonia vapour increases this risk significantly as the point of ignition falls below that of the mixture ratio stated.
Usually the strong smell of ammonia will give ample warning of its presence before concentrations become dangerous.
The following table shows the values for refri­gerant content in air, measured in volume %. Certain countries may, however, have an offi­cial limit which differs from those stated.
TWA Time weighted ave­rage during a week
Warning smell
0178-910-EN
Unit
vol.%
vol.%
Halogenated refrigerants
R134a R404A
HFC
R407C
0,1
0,2
R410A
0,1
HCFC
R507 R22
0,10,10,1
0,1
Ammonia
R717
0,005
0,002
9
Page 11
Further comments on refrigerants:
S If released to the atmosphere, haloge-
nated refrigerants of the type HCFC (e.g. R22) may cause a depletion of the ozone layer in the stratosphere. The ozone layer protects the earth from the ultraviolet rays of the sun. Refrigerants of the types HFC and HCFC are greenhouse gases with contribute to an intensification of the greenhouse effect. They must, therefore, never be released to the atmo­sphere. Use a separate compressor to draw the refrigerant into the plant con­denser/receiver or into separate refriger­ant cylinders.
S Most halogenated refrigerants are mis-
cible with oil. Oil drained from a refrigera­tion plant will often contain significant amounts of refrigerant. Therefore, reduce the pressure in the vessel or compressor as much as possible before draining the oil.
Halogenated refrigerants must never be mixed. Nor must R717 ever be mixed with halogenated refrigerants.

Purging a refrigeration plant

If it is necessary to purge air from a refrige­ration plant, make sure you observe the follo­wing:
S Refrigerants must not be released to the
atmosphere.
S When purging an R717 plant, use an ap-
proved air purger. The purged air must pass through an open container of water so that any R717 refrigerant remaining can be absorbed. The water mixture must be sent to an authorized incinerating plant.
S Halogenated refrigerants can not be ab-
sorbed by water. An approved air purger must be fitted to the plant. This must be checked regularly using a leak detector.
S Ammonia is easily absorbed by water:
At 15°C, 1 litre of water can absorb approx. 0,5 kg liquid ammonia (or approx. 700 litres ammonia vapour).
S Even small amounts of ammonia in water
(2-5 mg per litre) are enough to wreak havoc with marine life if allowed to pollute waterways and lakes.
S As ammonia is alkaline it will damage
plant life if released to the atmosphere in large quantities.
Refrigerant evacuated from a refrigerant plant shall be charged into refrigerant cylin­ders intended for this specific refrigerant.
If the refrigerant is not to be reused, return it to the supplier or to an authorized incinerat­ing plant.

Cooling media

Salt solutions (brines) of calcium chloride (CaCl used.
In recent years alcohol, glycol and halogena­ted compounds have been used in the brine production.
In general, all brines must be considered as harmful to nature and must be used with caution. Be very careful when charging or purging a refrigeration plant.
Never empty brines down a sewer or into the environment.
The brine must be collected in suitable con­tainers, clearly marked with the contents, and sent to an approved incinerating plant.
) or sodium chloride (NaCl) are often
2
10
0178-910-EN
Page 12

Lubricating oils

– alkyl benzene-based synthetic oil
Refrigeration compressors are lubricated by one of the following oil types, depending on the refrigerant, plant type and operating con­ditions.
– mineral oil
– semi-synthetic oil
Note
This instruction provides only general information. The owner of the refrigeration
plant is responsible for ensuring that all by-laws are complied with.
– polyalphaolefine-based synthetic oil – glycol-based synthetic oil. When you change the oil in the compressor
or drain oil from the refrigeration plant’s ves­sels, always collect the used oil in containers marked “waste oil” and send them to an ap­proved incinerating plant.
0178-910-EN
11
Page 13
Description of compressor SMC 104Ć106Ć108 Mk & TSMC 108 Mk 3, SĆLĆE
The SMC 100 and TSMC 100 compressors have 100 mm diameter pistons, as indicated by the first digit in the type designation. The number of cylinders in the compressor block is indicated by the following two digits, where, for example, SMC 108 is an 8-cylin­der compressor. SMC 100 is a one-stage compressor which compresses the gas in a single stage.
AARHUS DENMARK
Type Shop no Max. speed
Swept volume Working pressure
Test pressure
SABROE
Refrigerant Year
r.p.m. m3/h
bar bar
0171-481-EN 96.12
In the TSMC 100 two-stage compressors, the gas is compressed in two stages at a ratio of 1:3 between the number of high- and low­pressure cylinders. Thus, a TSMC 108 has 2 high-pressure cylinders and 6 low-pressure cylinders. The SMC 100 and TSMC 100 are available in three versions: an S-type with 80 mm stroke, an L-type with 100 mm stroke, and an E-type with 120 mm stroke. The compressor works on the refrigerants mentioned in the following chapter.
The type can be determined by the name­plate, located on the end face of the com­pressor, facing away from the coupling/belt drive. The following illustration shows a SABROE nameplate.
12
T0177093_2
Similarly, the name-plate indicates the com­pressor’s serial number, which is also stamp­ed into the compressor housing near the suc­tion chambers.
Whenever contacting SABROE about the compressor, its serial number should be stated.
In the compressors the pistons operate in cylinder linings, inserted in the compressor block with two cylinders under each top cov­er. The suction valves, of the ring-plate type, are mounted at the top of the cylinder linings. The pressure valves form the top of the cylin-
0178-910-EN
Page 14
der linings and are kept in position by a pow­erful safety spring. The safety spring allows the discharge valve unit to rise, providing a greater throughflow aperture in the event of liquid strokes in the cylinder. This prevents
At the axle end, the crankshaft is fitted with a balanced slide-ringtype seal consisting of a cast iron ring with an O-ring which rotates with the crankshaft, and a stationary
spring-loaded carbon ring. any overloading of the connecting rod bear­ings.
All compressors can be capacity-regulated
by connecting or disconnecting the cylinders The crankshaft is supported in slide bearings
able to assimilate both radial and axial forces. The oil pressure for the bearings and
in pairs. The following diagram shows the
capacity stages at which the compressors
can operate. the capacity regulating system is supplied
from the gearwheel oil pump incorporated in the compressor.
25% 33% 50% 67% 75% 100%
SMC 104 x x SMC 106 x x x
Capacity regulation is controlled by means of
solenoid valves mounted on the compressor.
SMC 108 x x x x TSMC 108 x x x
0178-910-EN
13
Page 15
Handling of the compressor, areas of application, safety equipment etc.
Direction of rotation
In order to reduce the noise level from the electric motors these are often executed with specially shaped fan wings, thus determining a particular direction of rotation.
In case you yourself order a motor you should take into consideration whether the motor is intended for direct coupling or for belt drive of the compressor.
The direction of rotation of the compressor for compressors CMO-TCMO and SMC­TSMC is indicated by an arrow cast into the compressor cover, near the shaft seal.
On the BFO compressors the direction of rotation is not indicated by an arrow but is standard as illustrated by the following sketch:
clearly marked with red paint. The weight of the unit is stated on the package as well as in the shipping documents.
During transportation and handling care should be taken not to damage any of the components, pipe or wiring connections.
Areas of application of the recipro­cating compressors
Compressor types: BFO 3-4-5 CMO-TCMO, SMC 100-TSMC 100 Mk3, S, L, E SMC 180-TSMC 180, HPO-HPC
In view of preventing an unintended applica­tion of the compressor, which could cause injuries to the operating staff or lead to tech­nical damage, the compressors may only be applied for the following purposes:
0170-119-EN 97.12
Seen towards shaft end
Handling of compressor and unit
For lifting of the compressor the large models are equipped with a threaded hole for mount­ing of the lifting eye. As to the weight of the compressor, see table on compressor data.
Note:
The compressor block alone may be lifted in the lifting eye. The same applies to the motor.
The unit is lifted by catching the lifting eyes welded onto the unit frame. These have been
The compressor may ONLY be used:
S As a refrigeration compressor with a num-
ber of revolutions and with operating limits as indicated in this manual or according to a written agreement with SABROE.
S With the following refrigerants:
1
R717 – R22 R410A1 – R5071 – R6001 – R600A1 –
1
R290
1
sors: SMC-TSMC 100 E (only R717) HPO and HPC (only R717 and R410A))
All other types of gas may only be used following a written approval from SABROE.
S As a heat pump:
– LPG1
) Exempted are the following compres-
– R134a1 – R404A1 –
14
0178-910-EN
Page 16
– BFO 3-4-5
CMO - TCMO and SMC - TSMC may be used with a max. discharge pressure of 25 bar.
– HPO – HPC may be used with a max.
discharge pressure of 40 bar.
manual handle, to which there is free ac­cess.
S It must be able to stop any dangerous si-
tuation, which may occur, as quickly as possible without this leading to any further danger.
S In an explosion-prone environment, pro-
vided the compressor is fitted with ap­proved explosion-proof equipment.
The compressor must NOT be used:
S For evacuating the refrigeration plant of air
and moisture,
S For putting the refrigeration plant under air
pressure in view of a pressure testing,
S As an air compressor.
Emergency device
The compressor control system must be equipped with an emergency device.
In case the compressor is delivered with a SABROE-control system this emergency de­vice is found as an integrated part of the con­trol.
The emergency device must be executed in a way to make it stay in its stopped position, following a stop instruction, until it is deliber­ately set back again. It must not be possible to block the emergency stop without a stop instruction being released.
It should only be possible to set back the emergency device by a deliberate act, and this set back must not cause the compressor to start operating. It should only make it pos­sible to restart it.
Combustion motors
If combustion motors are installed in rooms
containing refrigeration machinery or rooms
where there are pipes and components con-
taining refrigerant, you must make sure that
the combustion air for the motor is derived
from an area in which there is no refrigerant
gas, in case of leakage.
Failure to do so will involve a risk of the lubri-
cating oil from the combustion motor mixing
with the refrigerant; at worst, this may give
rise to corrosion and damage the motor.
Explosion-proof electrical execution
If the compressor is delivered in an explo-
sion-proof electrical execution, this is stated
in the table on page 1 of this instruction
manual.
Likewise, the compressor will, besides the
SABROE name plate, be equipped with an
Ex-name plate like the one illustrated below.
Other demands to the emergency device:
S It must be possible to operate it by means
of an easily recognizable and visible
0178-910-EN
T2516273_0
15
Page 17
The temperature of tangible surfaces
When a compressor is working, the surfaces that are in contact with the warm discharge gas also get warm. However, the temperatu­re depends on which refrigerants and under which operating conditions the compressor is working. Often, it exceeds 70°C which for metal surfaces may cause your skin to be burnt even at a light touch.
Consequently, the compressors will be equip­ped with yellow warning signs informing you that pipes, vessels and machine parts
close to the warning signs during operation are so hot that your skin may be burnt from 1 second’s touch or longer.
16
0178-910-EN
Page 18
Sound data for reciprocating and screw compressor units - all types of compressors
0170-114--EN 99.06
In the following tables the noise data of the compressors is stated in:
– A-weighted sound power level LW
(Sound Power Level)
– A-weighted sound pressure level LP
(Sound Pressure level)
The values for LW constitute an average of a large number of measurings on various units. The measurings have been carried out in ac­cordance with ISO 9614-2.
The values are further stated as average
sound pressure in a free field above a re­flecting plane at a distance of 1 meter from
a fictional frame around the unit. See fig. 1. Normally, the immediate sound pressure
lies between the LW and LP values and can be calculated provided that the acoustic data of the machine room is known.
For screw compressors the average values are indicated in the tables for the following components.
S SAB 81-83-85-87-89, SAB 128, Mk3,
SAB 163 Mk3, SAB 202, SAB 330, SV and FV:
Compressor block + IP23 special motor + oil separator.
S SAB 128 HR and SAB 163 HR:
Compressor block at max. number of revolutions + IP23 special motor + oil separator
S SAB 110:
Compressor block + IP23 standard motor + oil separator
Dimensional tolerances are:
±3 dB for SAB, SV and FV screw com­pressors ±5 dB for VMY screw compressors
As to the reciprocating compressors the
values are stated for the compressor block
only.
The dimensional values are stated for 100%
capacity.
Fig. 1
0178-910-EN
1 meter
1 meter
Fictional frame
Dimensional plane
Reflecting plane
17
Page 19
Note the following, however:
S at part load or if the compressor works
with a wrongly set V
the sound level can
i
sometimes be a little higher than the one indicated in the tables.
S the acoustics is another factor that can
change the sound level in a room. Please note that the sound conditions of the site have not been included in the stated dimensional values.
S additional equipment such as heat ex-
changers, pipes, valves etc. as well as the choice of a different motor type can in­crease the noise level in the machine room.
S as already mentioned, the stated sound
pressures are only average values above a fictional frame around the noise source. Thus, it is sometimes possible to measure higher values in local areas than the ones stated – for inst. near the compressor and motor.
S by contacting SABROE you can have
sound data calculated for other operating conditions.
The tables have been divided into reciprocat­ing and screw compressors, respectively. The reciprocating compressors are further divided into one- and two-stage compressors as well as in a heat pump. In each table the operating conditions of the compressor dur­ing noise measuring have been stated, just as the refrigerant used has been mentioned.
18
0178-910-EN
Page 20
RECIPROCATING COMPRESSORS One-stage
Evaporating temperature = –15°C Condensing temperature =+35°C Refrigerant = R22/R717 Number of revolutions =1450 rpm.
Two-stage
Evaporating temperature = –35°C
Condensing temperature = +35°C
Refrigerant = R22/R717
Number of revolutions =1450 rpm.
LW LPCompressor block
Compressor block LW LP
CMO 24 84 69 CMO 26 86 71 CMO 28 87 72
SMC 104 S 95 79 SMC 106 S 96 80 SMC 108 S 97 81 SMC 112 S 99 82 SMC 116 S 100 83 SMC 104 L 96 80 SMC 106 L 97 81 SMC 108 L 98 82 SMC 112 L 100 83 SMC 116 L 101 84 SMC 104 E 96 80 SMC 106 E 97 81 SMC 108 E 98 82 SMC 112 E 100 83 SMC 116 E 101 84
Evaporating temperature = –15°C Condensing temperature = +35°C Refrigerant = R22/R717 Number of revolutions = 900 rpm.
Compressor block LW LP
SMC 186 101 83 SMC 188 102 84
TCMO 28 81 66 TSMC 108 S 95 79 TSMC 116 S 97 81 TSMC 108 L 96 80 TSMC 116 L 98 82 TSMC 108 E 96 80
TSMC 116 E 98 82
Evaporating temperature = –35°C
Condensing temperature = +35°C
Refrigerant = R22/R717
Number of revolutions = 900 rpm.
Compressor block LW LP
TSMC 188 100 82
Heat pump
Evaporating temperature = +20°C
Condensing temperature = +70°C
Refrigerant = R22/R717
Number of revolutions =1450 rpm.
Compressor block LW LP
HPO 24 91 76 HPO 26 93 78 HPO 28 94 79 HPC 104 97 81 HPC 106 98 82 HPC 108 99 84
0178-910-EN
19
Page 21
SCREW COMPRESSORS
Evaporating temperature = –15°C Condensing temperature = +35°C Refrigerant = R22/R717 Number of revolutions = 2950 rpm.
*Number of revolutions = 6000 rpm.
Compressor block LW LP
Evaporating temperature = –35°C Condensing temperature = –5°C Refrigerant = R22/R717 Number of revolutions = 2950 rpm.
SAB 110 SM 98 81 SAB 1 10 SF 98 81 SAB 1 10 LM 98 81 SAB 1 10 LF 98 81
SAB 128 HM Mk2 102 84 SAB 128 HF Mk2 106 88 SAB 128 HM Mk3 101 84 SAB 128 HF Mk3 104 86 SAB 128 HR* 102 84
SAB 163 HM Mk2 105 86 SAB 163 HF Mk2 109 90 SAB 163 HM Mk3 103 86 SAB 163 HF Mk3 106 87 SAB 163 HR* 103 85
SAB 202 SM 104 85 SAB 202 SF 105 86 SAB 202 LM 104 85 SAB 202 LF 105 86
SAB 330 S 106 87 SAB 330 L 106 87 SAB 330 E 106 87
Compressor unit LW LP
SAB 163 BM 106 88 SAB 163 BF 110 92
Evaporating temperature = –15°C Condensing temperature =+35°C Refrigerant = R22/R717 Number of revolutions = 2950 rpm.
Compressor block LW LP
VMY 347 H 97 82 VMY 447 H 100 85 VMY 536 H 104 88
SV 17 100 83 SV 19 101 84
* 101 86
FV 19 SV 24 103 85 FV 24
* 104 86
SV 26 103 85
* 107 85
FV 26 SAB 81 101 86
SAB 83 102 85 SAB 85 103 86 SAB 87 105 86 SAB 89 108 85
Min liquid pressure for liquid injection, suction pressure bar (a) x 2+2 bar
20
Evaporating temperature = 0°C Condensing temperature =+35°C Refrigerant = R22/R717 Number of revolutions = 2950 rpm.
Compressor block LW LP
VMY 347 M 99 84 VMY 447 M 101 86 VMY 536 M 105 89
0178-910-EN
Page 22
Vibration data for compressors Ć all types
0170-115-EN 95.06
Vibration data for SABROE screw compres­sors comply with the following norm:
ISO 2372 group C
Depending on the laying of the foundation and the size of the motor a screw compres-
Vibration severity ranges and examples of their application to small machines (Class I) medium size ma­chines (Class II), large machines (Class III) and turbo machines (Class IV)
Ranges of vibration severity
Range
0.28
0.45
0.71
1.12
1.8
2.8
4.5
7.1
11.2 18
28 45
71
ms-velocity V (in mm/s)
at the range limits
0.28
0.45
0.71
1.12
1.8
2.8
4.5
7.1
11.2 18 28
45
Class I Class II Class III Class IV
A
B C
D
sor unit can - under normal circumstances -
be classified in Class III or IV according to
the following table from ISO 2372. Recip.
compressor units can be classified in class
IV, likewise under normal conditions.
Examples of quality judgement
for separate classes of machines
A
A
B
A
B
C
B
C
D
C
D
D
SABROE screw compressor unit: Group C, class III or IV SABROE recip. compressor unit: Group C, class IV.
Pay attention to the following, however:
S On placing the unit on the vibration
dampers delivered by SABROE (additional) the vibrations against the foundation are reduced by:
– 85-95% for screw compressor units – 80 % for recip. compressor units
S However, a higher vibration level may oc-
cur if:
0178-910-EN
– Motor and compressor have not been
aligned as described in the Instruction Manual.
– For screw compressors, if the compres-
sor runs at a wrong V
ratio.
i
– The pipe connections have been
executed in a way that makes them force pull or push powers on the compressor unit or they may transfer vibrations to the unit, caused by natural vibrations or con­nected machinery.
– The vibrations dampers have not been
fitted or loaded correctly as indicated on the foundation drawing delivered together with the order.
21
Page 23
Compressor data for reciprocating compressor
CMO 4, CMO 24-28, TCMO 28, SMC 104-116, TSMC 108-116, SMC 186-188, TSMC 188

Operating limits

SABROE prescribes operating limits within which the compressor and any additional equipment must operate. These limits for R717, R22, R134a, R404A, R507 and R407C are shown in the following tables, together with the main data for the compressor.
BoremmStrokemmMax/min
Compressor
type
Number of
cylinders
Speed
RPM
CMO 4 CMO 24 CMO 26 CMO 28 TCMO 28 SMC 104S SMC 106S SMC 108S SMC 112S SMC 116S TSMC 108S TSMC 116S SMC 104L SMC 106L SMC 108L SMC 112L SMC 116L TSMC 108L TSMC 116L SMC 104E SMC 106E SMC 108E SMC 112E SMC 116E TSMC 108E TSMC 116E SMC 186 SMC 188 TSMC 188
The maximum speed permitted can be lower than stated here depending on operating
conditions and refrigerant; please see the following diagrams.
Two - stage compressors (High Stage cylinders and Low Stage cylinders)
4 65 65 1800/900 93,2 200 4 70 70 1800/900 116 340 6 70 70 1800/900 175 380 8 70 70 1800/900 233 410
2+6 70 70 1800/900 175 410
4 100 80 1500/700 226 580 6 100 80 1500/700 339 675
8 100 80 1500/700 452 740 12 100 80 1500/700 679 1250 16 100 80 1500/700 905 1350
2+6 100 80 1500/700 339 775
4+12 100 80 1500/700 679 1400
4 100 100 1500/700 283 580
6 100 100 1500/700 424 675
8 100 100 1500/700 565 740 12 100 100 1500/700 848 1250 16 100 100 1500/700 1131 1350
2+6 100 100 1500/700 424 775
4+12 100 100 1500/700 757 1400
4 100 120 1500/700 339 600
6 100 120 1500/700 509 700
8 100 120 1500/700 679 770 12 100 120 1500/700 1018 1300 16 100 120 1500/700 1357 1400
2+6 100 120 1500/700 509 800
4+12 100 120 1500/700 1018 1450
6 180 140 1000/450 1283 2560
8 180 140 1000/450 1710 2840
2+6 180 140 1000/450 1283 2900
Swept
volume
max RPM*
3
m
/h
compr. block
Weight
(max.)
kg
0171-476-EN 99.04
22
0178-910-EN
Page 24
°F
158
140
TC
°C
70
60
R717
Operating limits
single stage
122
50
104
40
86
30
68
20
50
10
32
0
–10
14
Condensing temperature
–4
–20
–30
–22 –40
–40
–60 –50 –40 –30 –20 –10
–70
–76 –58 –40 –22 –4 14 32 50 68 86 104
–94
T245400_0/2
4
2
3
0 10 20 30 40
Evaporating temperature
compressors
1
CMO
SMC 100 S-L
SMC 180
°C
TE
°F
Type Area rpm Cooling
max min Booster Single and HP-stage compr.
CMO 20
SMC 100 S-L 3
SMC 180 2-3 1000 450 Water-cooled
1–2 Air-cooled top- and side covers # - or water-cooled
3-4 1-2 Air-cooled top- and side covers # - or water-cooled
4 1200 1 750
4 900
1800 900
1500
700
Water-cooled Thermopump or water-cooled
Water-cooled Thermopump or water-cooled
# Including refrigerant-cooled oil cooler Thermopump:
Top- and side covers are cooled by refrigerant injection.
Water-cooled:
Top- and side covers. Oil cooling included in the system.
Oil cooling included in the system
NB: At part load the discharge gas temp. must not exceed 150°C/302°F
0178-910-EN
23
Page 25
°F
158
140
TC
°C
70
60
1a
R717
Operating limits
single stage
122
50
104
40
86
30
68
20
50
10
32
0
14
–4
–22
–40
–10
–20
–30 –40
–60 –50 –40 –30 –20 –10 0 10 20 30 40
–70
–76 –58 –40 –22 –4 14 32 50 68 86 104
–94
Condensing temperature
T245400_0/2
compressors
SMC 100 E
2
1
°C
TE
°F
Evaporating temperature
Type Area rpm Cooling
max min Booster Single and HP-stage compr.
SMC 100E
Thermopump:
Top- and side covers are cooled by refrigerant injection.
1-(1a) 1500
2 1200
700 Water-cooled Thermopump or water
Water-cooled:
Top- and side covers. Oil cooling included in the system.
Oil cooling included in the system
NB: At part load the discharge gas temp. must not exceed 150°C/302°F
1a: In this area the compressor is not allowed to run at a capacity below 50%.
24
0178-910-EN
Page 26
TC
°C
°F
158
70
140
60
122
50
104
40
86
30
68
20
50
10
32
0
–10
14
Condensing temperature
–20
–4
–22
–30
–40
–40
–60 –50 –40 –30 –20 –10 0 10 20 30 40
–70
–76 –58 –40 –22 –4 14 32 50 68 86 104
–94
0177128_0 VIEW 3,1
1
2
Evaporating temperature
R717
Operating limits
two-stage
compressors
TCMO
TSMC 100 S-L-E
TSMC 180
°C
TE
°F
Type Area rpm Cooling Note
max min top and side
TCMO 1–2 1800 900 Thermopump or water-cooled
TSMC 100
S-L-E
TSMC 180
1-2 1500 700 Thermopump or water-cooled 1)
1 750 2 1000
450 Water-cooled
Oil cooling is always necessary. Thermopump:
Only the HP Stage top covers are cooled by a thermo pump Oil cooling included in the system
Part-load operation:
1)
Depending on the operating conditions and the presure on the compressor a by­pass system may be required.
Water-cooled:
Top- and side covers. Oil cooling included in the system.
See section: By-pass system for two-stage compressors.
1)
1)
0178-910-EN
25
Page 27
TC
°F
°C
70
158
140
60
50
122
104
40
30
86
68
20
10
50
32
0
14
–4
–22
–40
–10
–20
–30
–40
–60 –50 –40 –30 –20 –10 0 10 20 30 40
–70 –94
–76 –58 –40 –22 –4 14 32 50 68 86 104
Condensing temperature
0177128_0 VIEW 4,1
4
3
Evaporating temperature
R22
Operating limits
1
2
°C
TE
°F
single stage
compressors
CMO
SMC 100 S-L
SMC 180
Type Area rpm Oil-cooling Note
max min required
CMO
SMC 100 S
SMC 100 L
SMC 180
1 2 3 4 1 1000 2 1200 3 1500 4 1200 yes 1 Not applicable 2 1000 3 1200 4 1000 yes
1-2 Not applicable
3 At less than 50% capacity 4
1500
1800
750
900
700
700
450
Top covers: Air-cooled design only.
1)
When oil cooling is required there is a free choice between A and B - However, for
At less than 50% capacity
At less than 50% capacity
At less than 50% capacity
A: Water-cooled side covers B: Built-in refrigerant-cooled oil cooler with
thermostatic expansion valve.
1)
no no
yes
no no
no
yes
SMC 180 only A may be selected.
26
0178-910-EN
Page 28
°F
158
140
122
104
TC
°C
70
60
50
40
R22
Operating limits
two-stage
compressors
3
1
2
TCMO
86
30
68
20
10
50
0
32
14
–4
–22
–40
–10
–20
–30
–40
–60 –50 –40 –30 –20 –10 0 10 20 30 40
–70
–76 –58 –40 –22 –4 14 32 50 68 86 104
–94
Condensing temperature
0177128_0 VIEW 5,1
4
Type Area rpm
max min
TCMO
TSMC
100 S
TSMC
100 L
SMC 180
1-2 1500 3-4 1800
1 1000
2-3 1200
4 1500 1
2 1000 3-4 1200 1-2
3-4
750
Evaporating temperature
900 no
700 yes
700 yes
450
TSMC 100 S-L
TSMC 180
°C
TE
°F
Oil-cooling Note
yes
1)
2)
Not applicable
2)
2)
Not applicable
2)
required
Top covers: Air-cooled design only.
1)
When oil cooling is required there is a free choice between A and B - However, for SMC 180 only A may be selected.
A: Water-cooled side covers B: Built-in refrigerant-cooled oil cooler with
thermostatic expansion valve.
0178-910-EN
Part-load operation:
2)
Depending on the operating conditions and the presure on the compressor a by­pass system may be required.
See section: By-pass system for two-stage com-
pressors.
27
Page 29
°F
TC
°C
R134a
80 176
70
158
140
60
122
50
40
104
30
86
68
20
50
10
0
32
–10
14
Condensing temperature
–20
–4
–22
–30
Operating limits
1
2
single stage
compressors
CMO
SMC 100 S-L
3
–40
–40
–70 –94
T0177128_ V8,1
Type Area
CMO
SMC 100 S
SMC 100 L
–60 –50 –40 –30 –20 –10 0 10 20 30 40 –76 –58 –40 –22 –4 14 32 50 68 86 104
Evaporating temperature
rpm Oil-cooling Note
1)
no
no
no no no
no no
1-2
3 1
2 3
1 2
3
max min required
1200 1500 1500 1800 At less than 50% capacity 1000 1200 1200 1500 At less than 50% capacity
1000 1000 1200 At less than 50% capacity
900
700
700
At less than 50% capacity
°C
TE
°F
Not applicable
Top covers: Air-cooled design only.
1)
When oil cooling is required there is a free choice between A and B.
28
A: Water-cooled side covers B: Built-in refrigerant-cooled oil cooler with
thermostatic expansion valve.
0178-910-EN
Page 30
°F
158
140
122
104
TC
°C
70
60
50
40
R134a
Operating limits
1
2
two-stage
compressors
3
TCMO
86
30
20
68
10
50
32
0
14
–4
–22
–40
Type
TSMC
100 S
TSMC
100 L
–10
–20
–30
–40
–60 –50 –40 –30 –20 –10 0 10 20 30 40
–70
–76 –58 –40 –22 –4 14 32 50 68 86 104
–94
Area rpm
1-2 1500
3 1800
1 1000
2 1200
3 1500
1
2 1000
3 1200
Condensing temperature
T0177128_0 V8,1
TCMO 28
Evaporating temperature
max min
900
700
700
TSMC 100 S-L
°C
TE
°F
Oil-cooling Note
required
1)
1)
1)
1) 2)
Not applicable
1) 2)
1) 2)
1)
Oil cooling:
Not required.
Top- and side covers:
Only air-cooled.
0178-910-EN
2)
Part-load operation:
By-pass equipment required to maintain i termediate temperature at minimum load.
29
Page 31
°F
140
TC
°C
60
R404A
Operating limits
50
122
104
40
86
30
20
68
50
10
0
32
Condensing temperature
14
–10
–20
–4
–30
–22
–70
–60 –50 –40 –30 –20 –10 0 10 20 30 –76 –58 –40 –22 –4 14 32 50 68 86
–94
274263.1 Rev. 0
1
single stage
compressors
CMO
SMC 100 S-L
2
°C
TE
°F
Evaporating temperature
Type
Area
rpm Oil-cooling Note
max
1200 1500 1500 1800 At less than 50% capacity 1000 1200 1500 At less than 50% capacity 1000 no
1200
CMO 20
SMC 100 S
SMC 100 L
1
2 1
2 1
2
Top covers: Air-cooled design only.
1)
When oil cooling is required there is a free choice between A and B.
min
900
700
700
required
At less than 50% capacity
1)
no
no
no no
no
A: Water-cooled side covers B: Built-in refrigerant-cooled oil cooler with
thermostatic expansion valve.
30
0178-910-EN
Page 32
°F
140
TC
°C
60
R404A
Operating limits
50
122
40
104
30
86
68
20
50
32
14
10
–10
0
–70 –94
–60 –50 –40 –30 –20 –10 0
–76 –58 –40 –22 –414 32
Condensing temperature
274263.3 Rev. 0
1
2
Evaporating temperature
°C
°F
two-stage
compressors
TCMO
TSMC 100 S-L
TE
Type
TCMO 28
TSMC
100 S
TSMC
100 L
1)
Oil cooling:
Area rpm
1
2
1
2
1
2
Not required.
Top- and side covers:
Only air-cooled.
max
1800 900 1200
1500 1000 1200
min
700
700
Oil-cooling
required
2)
Part-load operation:
1)
1)
1)
1) 2)
1) 2)
1) 2)
1) 2)
Note
By-pass equipment required to maintain i termediate temperature at minimum load.
0178-910-EN
31
Page 33
°F
140
TC
°C
60
R507
Operating limits
50
122
40
104
86
30
68
20
10
50
0
32
14
–4
–22
–40
–10
–20
–30
–40
–60 –50 –40 –30 –20 –10 0 10 20 30
–70
–76 –58 –40 –22 –4 14 32 50 68 86
–94
Condensing temperature
74263.2 Rev. 0
1
single stage
compressors
CMO
SMC 100 S-L
2
°C
TE
°F
Evaporating temperature
Type Area
rpm Oil-cooling Note
max
1200 1500 1500 1800 At less than 50% capacity 1200 1200 1500 At less than 50% capacity 1000 no 1200
CMO 20
SMC 100 S
SMC 100 L
1 2
2 3
1 2
3 1 2
Top covers: Air-cooled design only.
1)
When oil cooling is required there is a free choice between A and B.
min
900
700
700
required
At less than 50% capacity
1)
no
no
no no
no
A: Water-cooled side covers B: Built-in refrigerant-cooled oil cooler with
thermostatic expansion valve.
32
0178-910-EN
Page 34
°F
140
122
TC
°C
60
50
R507
Operating limits
two-stage
compressors
40
104
30
86
20
68
10
50
Condensing temperature
0
32
–10
14
–70 –94
274263.4 Rev. 0
–60 –50 –40 –30 –20 –10 0 –76 –58 –40 –22 –414 32
Area rpm
Type
TCMO 28
TSMC
100 S
TSMC
100 L
1
2
1 1200
2 1500
1 1000
2 1200
1
2
Evaporating temperature
max min
1800 900
700
700
TCMO
TSMC 100 S-L
°C
TE
°F
Oil-cooling Note
required
1)
1)
1)
1) 2)
1) 2)
1) 2)
1) 2)
1)
Oil cooling:
Not required.
Top- and side covers:
Only air-cooled.
0178-910-EN
2)
Part-load operation:
By-pass equipment required to maintain i termediate temperature at minimum load.
33
Page 35
°F
140
122
TC
°C
60
50
R407C
Operating Limits
one-Stage
Compressor type
104
86
68
40
30
20
2
1
CMO & SMC
3
10
50
14
–4
–10
–20
–30
0
–60 –50 –40
–70
–76 –58 –40 –22 –4 14 32 50 68 86
–94
–30 –20 –10 0 10 20 30
Evaporating temperature
°C
TE
°F
32
Condensing temperature
–22
T245411_0 view 2
Type Area rpm Oil-cooling Note
1)
yes
no
no
yes
CMO
SMC 100 S
SMC 100 L SMC 100 L
SMC 180
max min required
1 1500 no 2 3 1 1200 2 1500 3 1200 yes 1 1000 2 1200 3 1000 yes 1 NOT APPLICABLE 2 At less than 50% capacity 3
1800
750
900
700
700
450
At less than 50% capacity
At less than 50% capacity
At less than 50% capacity
Top covers: Air-cooled design only.
1)
When oil cooling is required there is a free choice between A and B - However, for SMC 180 only A may be selected.
34
A: Water-cooled side covers B: Built-in refrigerant-cooled oil cooler with
thermostatic expansion valve.
0178-910-EN
Page 36
General operating instructions for CMO/TCMO, SMC/TSMC piston compressors
0171-461-EN 96.06

Starting up compressor and plant

S Before the initial start-up of the compres-
sor following a lengthy stand-still period of several months, the compressor must be prelubricated. Hereby, the bearings are lubricated and the oil system filled up with oil before the compressor is set run­ning. Carry out the prelubrication by connect­ing the oil pump to the prelubricating valve which in the more recent SMC­TSMC-HPC compressors is connected to the shaft seal housing pos. 6A and on the CMO-TCMO-HPO to the cover pos. 86H or 87K. As prelubricating pump we recom­mend SABROE’s hand-operated oil pump part no 3141-155, which is mounted as shown in fig. 1.
Fig. 1
To compressor
Cap
valve for prelubrication
Gasket
Optional hand­operated oilpump
For pre-lubrication use a clean new refriger­ant machine oil of the same type as the one found in the compressor, and pump as
follows:
Compressor
type
CMO TCMO HPO
SMC 104 106-108 TSMC 108 HPC
SMC 112-1 16 TSMC 116
SMC 186-188 TSMC 188
Pump strokes w.
SABROEs
hand-operated
oil pump
appr. 25
appr. 35
appr. 45
appr. 50
Estimated oil quantity
Liters
2.5
3.5
4.5
5.0
S The heating rod in the crankcase must be
energized at least 6-8 hours before start­ing up the compressor in order to boil any refrigerant out of the compressor oil. At the same time, the suction check valve must be open.
S Check oil level in crankcase. The oil level
must always be visible in the oil sight glass. See section: Charging the compres- sor with oil.
T0177131_0 V15
0178-910-EN
S Start condenser cooling, brine pumps,
fans at air coolers as well as any com­pressor cooling device.
S Check correct setting of safety auto-
matics on compressor.
S Open discharge stop valve at compressor. S Set capacity regulator to minimum capa-
city.
35
Page 37
S In order to avoid excessive pressure re-
duction in the compressor on start–up, the suction stop valve must be opened a few turns, as there is otherwise a risk of oil foaming in the crankcase.
S Open all other stop valves except for the
main valve in the liquid line and possible by-pass valves serving other purposes.
S Check that the time relay 3K13 keeps the
solenoid valve in the oil return line closed for 20-30 mins. after start-up of the com­pressor.
S Start compressor motor and check suction
and oil pressures.
S Carefully continue opening suction stop
valve to its full open position.
Stopping and starting-up com­pressor during a short period of standstill
Before stopping the compressor, its capacity must be reduced to the lowest capacity stage for a few minutes, before it stops.
During short periods of standstill, it is not necessary to shut off the suction stop valve and the discharge stop valve. The heating rod must be energized.
If the compressor is cooled by means of cool­ing water, the water flow must always be stopped during periods of standstill. This is normally done by means of a solenoid valve in the water inlet line to the compres­sor. Connect the solenoid valve to the start/stop relay of the compressor motor.
S Open main valve in liquid line.
S If the oil in the crankcase foams, or knock-
ing noises are heard from the compressor because droplets of liquid are being fed in with the suction gas, throttle suction stop valve immediately.
S The compressor is now operating.
Increase capacity stepwise, allowing the compressor to adjust to new conditions before switching to next stage. Check carefully whether oil is foaming and whether oil pressure is correct.
S Check whether oil return from oil separa-
tor is working. (Pay attention to any clog­ging of filter and nozzle.) The pipe should normally be warm.
Compressor start-up must always take place at the lowest capacity stage, after which ca­pacity is increased stepwise at suitable inter­vals, in order to avoid that a sudden exces­sive pressure reduction in the evaporation system causes liquid hammering in the com­pressor and oil foaming in the crankcase.
Stopping plant for brief periods (until 2-3 days)
S Shut off liquid supply to evaporators for a
few minutes before stopping the plant.
S Stop compressor and shut off suction and
discharge stop valves. Close valve in oil return.
S Stop condenser cooling, pumps, fans and
any compressor cooling.
S Do not leave plant for first 15 minutes after
start-up and never before it has stabilized.
36
S Cut off power supply to both master and
control currents.
0178-910-EN
Page 38
Stopping plant for lengthy periods (more than 2-3 days)
S Shut off main valve after receiver and
pump down evaporators. If necessary, ad­just low-pressure cut-out on unit to a lower pressure during evacuation.
S Allow temperature in evaporators to rise,
then repeat evacuation.
S When suction pressure has been reduced
to slightly over atmospheric, stop com­pressor. Shut off suction and discharge stop valves and close off stop valve in oil return.
S Shut off condenser cooling. If there is a
risk of freezing, draw off coolant.
S Cut off power supply to master and control
currents.
S Inspect receiver, condenser and pressure
vessels as well as piping connections and apparatus for leakage.

Automatic plants

– correct setting of safety automatics.

Pressure testing refrigeration plant

Before charging the plant with refrigerant, it must be pressure tested and pumped down.
Pressure test the plant with one of the follow­ing:
S dry air - pressurized cylinders containing
dry atmospheric air may be used - but never oxygen cylinders;
S air compressor for high pressure; S nitrogen.
Important
The plant compressors must not be used to pressurize the plant.
Water or other fluids must not be used for pressure testing.
If nitrogen is used, it is important to place a reducing valve with a pressure gauge be­tween the nitrogen cylinder and the plant.
S Refrigeration plant should normally be put
into operation as described in the Start-up section.Once started, switch over to auto­matic operation.
S Special instructions for automatic plant in
question should be followed to the letter.
S The following should be checked daily,
even on automatic plants: – correct oil charging, – automatic oil return, – correct oil pressure, – suction and condenser pressures,
discharge pipe temperature,
0178-910-EN
During pressure testing, it is important to en­sure that pressure transducers and other control equipment are not exposed to the testing pressure. The compressor stop valves must also be closed during pressure testing.
Plant safety valves must normally be blanked off during pressure testing, as their opening pressure is lower than the testing pressure.
Important
During this pressure testing, no person should be allowed to be present in rooms housing plant parts or in the vicin­ity of the plant outside the rooms.
37
Page 39
S The entire unit must be pressure tested in
accordance with the local regulations for pressure testing.
S The test pressure must never exceed the
disign pressure.
S If it is required that the compressor should
be pressure tested together with the unit or with the plant, the testing pressure must not exceed: For reciprocating compressors:
HP side: 24 bar LP side: 17.5 bar
S Please observe that manometers, pres-
sure controls, pressure transmitters and other control equipment are not exposed to testing pressure.
S Afterwards, reduce pressure to 10 bar for
a period of 24 hours - as an initial tight­ness test - as a tightly sealed plant will maintain this pressure throughout the peri­od.
During the tightness test, it is permitted to enter the room and approach the plant.
S By way of a second tightness test, ex-
amine all welds, flange joints etc. for leak­age by applying soapy water, while main­taining the 10 bar pressure.
atmospheric air and moisture. Evacuation must be carried out on all types of refrigera­tion plant, regardless of the type of refriger­ant with which the plant is to be charged.
Observe that HCFC and HFC refrigerants mix only minimally with water, and it is there­fore necessary to effect evacuation of such systems with particular care.
The boiling point of a fluid is defined as the temperature at which the steam pressure equals atmospheric pressure. For water, the boiling point is 100°C. Lowering the pressure also lowers the boiling point of the water.
The table sets out the boiling point of water at very low pressures:
Boiling point of
water °C
5 10 15 20
For evacuation, use a vacuum pump which bleeds the plant of air and steam.
At pressure
mm HG
6,63
9,14 12,73 17,80
When pressure testing, compile a pressure test report containing the following:
S date of pressure testing, S person carrying out the test, S comments.

Pumping down refrigeration plant

Following pressure testing, the refrigeration plant must be evacuated in order to eliminate
38
The vacuum pump must be able to lower the pressure to approx. 0.1 mm Hg (mercury col­umn) and must be fitted with a gas ballast valve. This valve should be used wherever possible to prevent water vapours condens­ing in the vacuum pump.
Important
Never use the refrigeration compressor to evacuate the plant.
0178-910-EN
Page 40
For a satisfactorily performed evacuation, the final pressure must be lower than 5 mm Hg. Attention is drawn to the fact that there may be a risk of any water left in the refrigeration plant freezing if ambient temperatures are lower than 10°C. In such instances, it will be necessary to supply heat to the component surroundings, as ice evaporates with difficul­ty.
It is recommended to carry out evacuation as follows:
S Evacuate to a pressure lower than 5 mm
Hg.
S Blow dry air or nitrogen into system to a
pressure corresponding to atmospheric.
Never use OXYGEN cylinders.
S Repeat evacuation to reduce pressure to
less than 5 mm Hg.
S Shut the vacuum pump off from refrigera-
tion plant and check that the pressure does not rise for the next couple of hours. If the system still contains water, this will evaporate and cause the pressure to rise, thereby indicating unsatisfactory evacua­tion and necessitating a repetition of the procedure.
0178-910-EN
39
Page 41

Operating log

In order to keep tabs on the operating state of the refrigeration plant, it is recommended that an operating log be kept.
This operating log should be kept at regular intervals, thus providing important informa­tion about the cause of any undesired changes in the operating state. (See following page)
Observation Measuring point Measurement unit
Date and timeTime
Suction pressure
Discharge pressure
Oil pressure
Oil temperature Suction gas temp.
Discharge gas temp.
Oil level in compressor
Compressor pressure gauge
UNISAB II Control
Compressor pressure gauge
UNISAB II Control
Compressor pressure gauge
UNISAB II Control
UNISAB II Control
Thermometer in suction pipe
immediately
before compressor
UNISAB II Control
Thermometer in discharge pipe
immediately after compressor but before oil separator
UNISAB II Control
Oil level sight glass
in compressor
°C or bar
°C or bar
bar
°C
C
°
°C
Must be visible in oil
sight glass
Recharding of oil on compressor
Compressor motor’s consumption in amps.
At the same time, attention should be paid to the following: (tick these off in the log, if you wish)
S whether the compressor’s cooling system is functioning correctly, S whether any unusual noise is coming from the compressor, S whether there are unusual vibrations in the compressor.
40
See section on oil
charging
Electrical panel
UNISAB II (additional)
Number of litres
Amps
0178-910-EN
Page 42
Servicing the piston compressor
0171-462-EN 99.03
In order to ensure problem-free operation, it is advisable to carry out regular servicing to the refrigeration plant. In this section, SABROE indicates some periodic services fixed on the basis of the number of operating hours from the first start-up or after over hand of the compressor.
The servicing schedules also depend on the speed of the compressor. If the compressor is running at less than 1200 rpm, SABROE permits extended service intervals. However, the compressor must always operate within the speed recommended by SABROE. See Description of compressor. Providing the compressor operates within the specified pressures and temperatures and the pre­scribed periodic services are performed, the compressor will have a long and efficient ser­vice life.
S The following must therefore be checked
daily:
Operating pressure, Operating temperatures, Oil level and pressure, Abnormal noise and vibrations.
The actual operating conditions should be entered in an operating log daily. See the Op­erating log section.
S Immediately after stopping compressor,
read off pressure on discharge and suc­tion side of compressor.
S Close discharge stop valve quickly and,
from moment of closure, time how long it takes for pressure to drop on high pres­sure side of compressor. Normally, the pressure drop should not be more than 3 bar over a period of 5 minutes or so.
If the pressure falls more quickly, this is due to internal leakage, which may occur:
S where pressure valve ring plates are in
bad contact with their seats (Pos. 20C
against Pos. 20A and 19H); S with defective seal Pos. 19T; ( not CMO) S with defective seal Pos. 19K; S because cylinder lining and top cover
have been tightened without long mount-
ing stopper having been fitted. Cylinder
lining is thus resting on rocker arms, Pos.
15A; (not CMO). S on safety valve, because valve cone does
not fit tightly against seat, or outer O-ring
Pos. 24B or inner O-ring Pos. 24C is de-
fective. (See Safety valve section.) During pressure drop testing, pay attention to
any piping connections to the discharge side of the compressor, which may have an influ­ence on the test result.
Pressure drop test:
Using the pressure drop test, it is possible to check the internal tightness of the compres­sor from discharge to suction side. The pres­sure drop test is performed with the compres­sor at standstill, as described below:
0178-910-EN

Removing refrigerant from compressor

Before the compressor can be dismantled, the refrigerant must be removed from the compressor, which can be done in the follow­ing ways:
41
Page 43
1. Run compressor at lowest capacity stage and throttle suction stop valve slowly until completely closed.
2. The compressor will then stop on the low pressure cut-out. This can be adjusted to stop compressor at a pressure lower than normal.
3. Close discharge stop valve and other pip­ing connections to compressor.
4. On HFC and HCFC compressors, remove remaining refrigerant gas using a pump­down compressor connected to purge val­ve Pos. 42.
42
Evacuating pump
R22
42
Water
R717
Connect the purge valve Pos. 42 to a sealed, empty vessel which in turn is connected to an open tank containing water.
The water will absorb the refrigerant, which can then be dispatched for proper destruc­tion. The moment the pressure is equalized, the valve must be reclosed in order to pre­vent water being sucked back into the com­pressor.
Note:
The following instructions apply to the compressor only. Servicing of the refrig­eration plant is described in a separate section. Service the compressor motor ac­cording to your own instructions. For the various scheduled services, SABROE can supply ready-made spare-part sets, which it would be an advantage to have before carrying out the scheduled service.
S On the R717 compressor, adopt the fol-
lowing method:
42
In the event that the compressor cannot op­erate, start evacuation as described under pt. 3, and remember also to close the suction stop valve.
0178-910-EN
Page 44

Scheduled services

No.
1
2
Operating
hours
< 1200 rpm
75 50
300 200
Operating
hours
> 1200 rpm
Activity
1.1 Remove and discard filter bag in suction filter. Clean suction filter. Following major repair work or in event of severe soiling of filter bag, it is recom­mended that a new filter bag be fitted for another period of 50 operating hours.
1.2 Check tension of driving belts.
2.1 Check or change oil. When changing oil, change oil filter cartridge, too. See following section:
Assessing the oil.
2.2 Clean suction filter.
2.3 Check that following function correctly: Solenoid valves Compressor cooling Thermopump Safety automatics Heating rod V-belt drive.
2.4 Retighten external piping connections.
2.5 Check oil return system from oil separator.
2.6 Retighten coupling.
3.1 Check or change oil. When changing oil, change oil filter cartridge, too. See following section:
Assessing the oil.
3.2 Clean suction filter.
3.3 Check that following function correctly: Solenoid valves Compressor cooling Thermopump Safety automaitcs
7500 50003
Heating rod V-belt drive Oil return system from oil separator.
3.4 For heat pump operation, inspect: Valve seats Cylinder linings Pistons, gudgeon pins and gudgeon pin bearings Piston and oil scraper rings.
0178-910-EN
Change suction and discharge valve ring plates.
3.5 Finish off with a pressure drop test.
43
Page 45
No.
4
Operating
hours
< 1200 rpm
15000 10000
Operating
> 1200 rpm
hours
Activity
4.1 Check or change oil. When changing oil, change oil filter cartridge, too. See following section: Assessing
the oil.
4.2 Clean suction filter.
4.3 Check following: Solenoid valves Oil cooling system Water cooling system for any deposits and clogging Thermopump Safety automatics Heating rod V-belt drive Coupling and alignment Oil return system from oil separator Valve seats Cylinder linings Pistons, gudgeon pins and gudgeon pin bearings Piston and oil scraper rings Unloading mechanism Seal for tightness
4.4 Change: Suction and discharge valve ring plates V-belts
4.5 Finish off with a pressure drop test.
5.1 Check V-belt drive
5.2 For heat pump operation, inspect:
Valve seats
5
22500 15000
Cylinder linings Pistons, gudgeon pins and gudgeon pin bearings Piston and oil scraper rings.
Change: Suction and discharge valve ring plates.
44
0178-910-EN
Page 46
No.
6
Operating
Hours
< 1200 rpm
30000 20000
Operating
> 1200 rpm
Hours
Activity
6.1 Change compressor oil, Change oil filter cartridge, Clean crankcase.
6.2 Clean suction filter.
6.3 Check following: Solenoid valves Oil cooling system Water cooling system for any deposits and clogging Thermopump Safety automatics Heating rod V-belt drive Coupling and alignment Valve seats Cylinder linings Pistons, gudgeon pins and gudgeon pin bearings Piston and oil scraper rings Unloading mechanism Seal for tightness Oil pump and drive Check valves.
10
6.4 Change: Suction and discharge valve ring plates V-belts Half-sections of bearing for connecting rod (does not apply to CMO compressors)
6.5 Finish off with a pressure drop test.
7 8
9
37500 25000 As for service no. 5 45000 30000 As for service no. 4
52500 35000 As for service no. 3 60000 40000 Major overhaul; contact SABROE Refrigeration
Then repeat scheduled services from no. 3 inclusive.
0178-910-EN
45
Page 47

Lubricating oil

Lubricating oil requirements
Above all, the refrigerator oil must provide satisfactory lubrication of the compressor, even at the relatively high temperatures oc­curring during compression. It must be inca­pable of coking at such high temperatures and must not precipitate solid constituents such as paraffin or wax at the lowest occur­ring temperatures. The oil must not have any corrosive effect, whether alone or mixed with refrigerant. According to the oil companies the oils mentioned in the Oil Recommenda­tion in this instruction manual comply with these conditions. See section on Choice of
lubricating oils.

General rules for use of lubricating oil in refrigeration compressors

S The refrigeration oil must be free of mois-
ture, which may give rise to operating mal­functions and attacks of corrosion.
The oil should therefore be purchased in con­tainers corresponding to the quantity to be used for a single, or at most, two top-ups. The oil containers must be kept carefully sealed. If all the oil in a container is not used in one go, the container should be tightly sealed and stored in a warm place to prevent the absorption of moisture.
Note:
It is inadvisable to reuse oil which has been drawn from a compressor or plant. This oil will have absorbed moisture from the air and may cause operating prob­lems. Always switch off the power to the heating rod before drawing off the oil.
S Only fresh, clean refrigeration machine oil
may be charged. Oil tapped from the
evaporator system in an ammonia plant must not be reused in the compressor.
S Use grade of oil originally prescribed for
compressor.
S As far as possible, avoid mixing different
types of oil. Mixed oil is generally inferior to the two original oils. Mixing various types of oil may give rise to formation of sludge, which will lodge in valves and fil­ters.
S If necessary to switch to another brand of
oil, this must be done at the same time as completely changing the oil in the com­pressor and tapping off all oil from the re­frigeration plant.
If, after reading the above, any doubt exists as to the type of oil which has been used on your compressor, you are recommended to contact SABROE, rather than risk charging with unsuitable oil.

Instructions for choosing lubricating oil for refrigeration compressors

The instructions in Choice of lubricating oils offer more detailed guidelines for choosing the lubricating oil best suited to each individ­ual case on the basis of the anticipated oper­ating conditions.
Charging refrigeration compressor with lubricating oil
Since all SABROE piston compressors are supplied with a special oil-charging valve on
46
0178-910-EN
Page 48
the crankcase, refrigeration oil may be topped up while the compressor is in opera­tion.
For this purpose, use a manual oil pump or adopt the following procedure:
Note:
When charging for the first time, use the oil pump; it goes without saying that the compressor must not be started unless already charged with oil.
S Reduce pressure in crankcase, e.g. by
throttling suction stop valve, until suction pressure gauge shows pressure slightly below atmospheric.
S Fill pipe connected to oil charging valve
with refrigerator oil and insert free end of pipe down into a receptacle containing fresh refrigerator oil.
S Open oil charging valve carefully, thereby
causing external air pressure to force oil into crankcase.
therefore, it is necessary to refill with re­frigeration oil after starting up for the first time and after charging with fresh refriger­ant.
For a while after the plant is started for the first time, keep an extra sharp eye on the oil level in the compressor, therefore.
Changing oil in refrigeration com­pressor
S Cut off power to heating rod. S Close compressor stop valves and valve
in oil return line from oil separator.
S Reduce pressure in compressor crank-
case to slightly above atmospheric by throttling suction stop valve while com­pressor is running at its lowest capacity stage. Alternatively, raise to slightly above atmospheric pressure by stopping com­pressor and closing suction stop valve. Pressure in crankcase will then rise gradu­ally.
S Avoid getting air or other impurities
sucked into compressor.
Note:
In order to achieve pressure below atmo­spheric, it will sometimes be necessary to reset the low-pressure cut-out so that the compressor can aspirate down to this pressure. Remember to reset the pressure cut-out to its normal setting after charging with oil.
When in operation, the compressor may be refilled with oil using the manual oil pump.
Note:
Since halocarbon refrigerants such as R22 mix with refrigeration oils, there will always be a good portion of oil blended with the refrigerant in the plant. Often,
S Oil in the crankcase can then be forced
out through drain valve Pos. 23 when compressor is at a standstill.
S Equalize pressure in compressor to atmo-
spheric through purge valve pos. 42. See
section on Environmental protection. S Dismantle side covers. S Replace oil filter cartridge with a new one. S Clean crankcase thoroughly, wiping with a
clean, dry linen cloth (not cotton waste). S Reassemble side covers. S Charge to correct level with fresh, clean
refrigerator oil according to SABROE’s oil
recommendations. S Connect heating cartridge.
0178-910-EN
47
Page 49
S Connect vacuum pump to compressor and
pump down to 5-7 mm Hg; close off con­nection.
Then open suction stop valve a few turns, filling compressor with refrigerant gas. In the case of R717, it will suffice to blast the compressor through by carefully opening suction stop valve while purge valve Pos.
42 is open. See section on Environmental protection, however. When smelling R717, close purge valve.
S Open discharge stop valve and valve in oil
return line; compressor is then ready for start-up as described in section
General operating instructions.
48
0178-910-EN
Page 50

Charging the compressor with oil

Compressor
Type Size
BFO
CMO
TCMO
SMC 100
TSMC 100
Mk 3 S-L-E
SMC 180
TSMC 180
Volume of oil
in crankcase
Litres
3 4 5
24 26 28
413
104 106 108
112 116
186 188
1,5
4 5
14 16 18
26 28 30 47 50
80 90
The oil level must be checked with extreme care, particularly when starting and charging with refrigerant.
The oil level must always be visible in the oil level sight glass. The below diagram illustrates, how many litres of oil a drop in the oil level of 10 mm is approximately equal to.
T0177162_0
The volume of oil stated in the table is the amount which must always be present in the crankcase.
As a rule, the compressor should be charged with oil after the plant is started for the first time, as some of the oil – especially on an HCFC installation – will be absorbed by the refrigerant in the plant.
The following determinants decide the total volume of oil a refrigeration plant should con­tain:
S type of refrigerant
S refrigerant charge (volume)
S size of plant
Compressor
type size
CMO/ TCMO
SMC / TSMC 100 S-L-E
SMC / TSMC
24 26 28
104 106 108
112 116
186 188
10 millimeter
difference in
oil levels equals
~1 litre of oil
~2 litres of oil
~6 litres of oil
~6 litres of oil
180

Assessing the oil

Refrigeration machine oil is a vital part of the compressor, as it not only lubricates and cools the movable parts of the compressor, it also prevents abrasive particles from en­tering the bearings.
S temperature range in which refrigeration
plant is to operate.
0178-910-EN
An analysis of the oil can give important in­formation on how the compressor is running.
49
Page 51
We would, therefore, advise that the oil anal- yses be carried out at the intervals prescri­bed.
An oil sample must be drawn off while the compressor is in operation, which gives a representative sample. Before taking the sample, clean the drain valve and tap a little oil off, to prevent any impurities which may have accumulated in the valve or the piping from mixing with the sample.
As a special offer to our customers SABROE has developed an analytical con­cept, in cooperation with Mobil Oil, which is able to analyse all oil makes. This will mean a uniform reporting of the results.
The analysis allows the following to be deter­mined:
S Whether or not the oil is still usable, if nec-
essary after filtering.

Visual assessment

If you pour the sample into a clean, transpar­ent glass bottle or a test-tube and hold it up to a clear light source, it will be easy to as­sess the quality. You can also compare the sample with the fresh oil of the same make and grade.
An oil which you approve on the grounds of a visual assessment must:
S be clear and shiny S not contain any visible particles S feel viscous, smooth and greasy when a
drop is rubbed between two fingers.
If you don’t feel that you can approve the oil by visual assessment, charge with new oil or send a sample to a laboratory for analysis.
Warning
If the oil sample is poured into a glass bottle, this must not be hermetically sealed until all the refrigerant in the oil sample has evapora­ted. Refrigerant in the oil may produce ex­cess pressure in the bottle with subsequent risks of explosion. Never fill a bottle up com­pletely. Do not send glass bottles through the postal service – use purpose-made plas­tic bottles. Please see below.
S Whether solid particles possibly present in
the oil originate from the bearings or other components exposed to wear and tear in which case the compressor must be in­spected.
S Each report will include the corresponding
measuring results from the previous 3 oil analyses. In this way you will be able to follow up on the state of both the oil and the compressor from one analysis to the next.

Procedure

S A form set with a plastic sampling bottle
and a dispatching envelope can be re­quested from the local Sabroe Refrigera­tion representation.
S The oil sample must be drained from the
cleaned oil drain valve into the sample bottle. Screw the lid loosely on and let the bottle stand for a few hours to enable re­frigerant contained in the oil sample to evaporate before sending it to the labora­tory.

Analytical evaluation

Naturally, the oil sample can be analysed by the oil company which supplies the oil.
50
S Please follow the Sampling and Shipping
Instructions enclosed in the form set in
which the addresses of the laboratory in Holland are also mentioned.
0178-910-EN
Page 52

The analysis

The following section states some average values that can be applied in practice. How­ever, you should be on the alert whenever the results of the analyses approach these values. In some cases the water content of 100 ppm in HCFC plants may be too much and thus lead to Cu–plating in the shaft seal. Similarly, a rise in the oil viscosity of max. 65% normally does not cause any operating problems as the refrigerant reduces the oil viscosity in the plant.
Wear particles expressed im ppm, are mea­sured for:
Lead max. 10
Copper max. 10
Silicon max. 25
Iron max. 100
Chrome max. 5
Nickel max. 5
Aluminium max. 10
Tin max. 10 A report is drawn up for every sample re-
ceived. This report indicates:
Kinematic viscocity at +40°C.
Max. indication from the specified value at +40°C stated in the tables of Selecting
lubricating oil for SABROE compressors
–15%
S Acid number (TAN). max.0.1 S Oxidation. max.7 S Water content (ppm). max.100 (HCFC) S Water content (ppm). max.600 (R717) S pH value. min.4 (HCFC) S pH value. min.5 (R717) S Strong acids (SAN). max.0 S The oil is filtered through two filters
(1,2 micron and 5 micron).
specified value +65%
Whether the oil can still be used – without
taking any further action. Whether the oil can be used after it has
been filtered through a very fine filter.
If this is necessary, the oil must be
pumped directly from the compressor unit
through a 3 micron filter and back to the
unit. The system must be completely
closed, to prevent the oil being affected by
moisture in the air. Whether the oil is no longer fit for use. The report will always be sent to the address
stated on the sample label included in the form set. A copy will be sent to SABROE Re­frigeration, so that we are in a position to ad­vise you, if required.
0178-910-EN
51
Page 53
Pressure and temperature settings for SABROE compressor types SMCĆTSMC and CMOĆTCMO
Refrigerant
R22
R134a
R404A
R507
R717
24 bar (standard)
22 bar (special)
12 bar
Safety valve on the compressor
HP
IP
xxx x
x
x
x
x
x
x
High and intermediate cut-out
Low-pressure cut-out
Oil pressure cut-out
Safety equipmentControl equipment
Discharge pipe thermostat
Oil thermostat Thermostat for
compressor cooling Thermo valve for
compressor cooling
Injection valve for intermediate cooling
By-pass valve
KP 5
(KP15)
KP 1
(KP15)
MP 55
KP 98
KP 98
T(E) X T(E) Y
T(E) F
TEAT
T(E) X TEA
PMC + CVC
Set so that the compressor stops at a pressure 2 bar lower than the
x
x
x
x
x
safety valve setting.
Set to a pressure with saturation temp.
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x x
x
x
x
x
x
x
°
C lower than the lowest evaporating5
temperature.
**
1)
°
C
°
C
°
C 80
°
C 55KP 77
° °
°
C 45
°
C
°
C-15
x
x x
x
Normally set at 4 Change to min. 10 superheat
Factory set.
x
Factory set. Adjust to min 10°C superheat
Adjust to min 10°C superheat
x
x
3,5 bar
* 120 * 150
-25
C
superheat.
C
See below.
°
See below.
C 75
0170-012-EN 96.04
Oil pressure regulating valve
Factory setting - can be adjusted, if required, to a breaking point 20°C higher than the
*
highest normal discharge pipe temperature. For TCMO, R717 TEAT 20-2 spec., the factory setting is 85°C.
**
Adjust the TEAT valves so that the expected discharge pipe temperature (-5°C/+10°C) is achie­ved at 100% compressor capacity. Increase the opening temperature 10°C by turning the spindle 5 turns clockwise. NB: Factory setting must always be increased by min. 10°C.
Adjustment of the TEAT valve must be carried out with the thermopump out of operation
1) 2)
SMC - TSMC - CMO2 - TCMO2 CMO4 0.8-1.2 bar
x
3.5 bar
x
x
x
x
SMC - TSMC - CMO2 - TCMO2 CMO4
4.5 bar
2)
52
4.5 bar
1.3 bar
0178-910-EN
Page 54
0170-105-EN 96.02
0178-910-EN
Suction gas superheat
Condensing temp. °C
Evaporating temperature
intermediate temperature
°
°
C
C
10
10
20
20
barCondensing pressure
°C
20
20 25
25 30
30 35
35 40
40 45
45 20
20 25
25 30
30 35
35 40
40 45
45
+10 0 -10 -20 -30 +10 0 -10 -20 -30 0 -10 -20 -30 -40 +10 0 -10 -20 -30
+10 0 -10 -20 -30 +10 0 -10 -20 -30 0 -10 -20 -30 -40 +10 0 -10 -20 -30
5.7
38
6.6
44
7.7
49
8.8
53
10.1
57
11.5
61
5.7
48
6.6
54
59
7.7
8.8
63
10.1
67
11.5
71
HFC - HCFC
Condensing pressure
Condensing pressure
Condensing pressure
R134a R22 R404A/R507 R717
41 45 50 54 59 63
51 55 60 64 69 73
Evaporating temperature
48
48 57
57 65
65 74
74 82
82 90
90 59
59 68
68 76
76 84
84 92
92 98
98
or
°C
61
61 69
69 77
77 85
85 94
94
100
100
72
72 80
80 88
88 96
96
103
103
109
109
76
76 84
84 92
92 99
99
106
106
112
112
88
88 95
95
102
102 109
109
115
115
121
121
91
91
101
101 108
108
115
115
120
120 126
126 103
103
110
110 117
117
123
123 128
128 133
133
or
intermediate temperature
43 48 53 58 63 67
53 58 63 68 73 77
°C
48 52 58 64 69 74
58 62 68 74 79 84
55 59 66 74 79 82
65 69 76 84 89 92
bar
8
8.2 9
9.5
11.
11.1
12.7 14
14.5
16.5 8
8.2 9
9.5
11
11.1
12
12.7
14
14.5
16
16.5
37
37 47
47 55
55 68
68 72
72 81
81 48
48 57
57 65
65 73
73 82
82 90
90
Evaporating temperature
or
intermediate temperature
bar
40 44 49 54 59 65
50 54
59
64 69 75
42 47 52 57 62 67
52 57 62 67 72 77
11.0
12.5
14.3
16.2
18.2
20.5
11.0
12.5
14.3
16.2
18.2
20.5
46 51 56 61 66 71
56 61 66 71 76 81
°C
53
62
58
67
63
71
67
75
72
79
77
83
63
72
68
77
73
81
77
85
82
89
87
93
Evaporating temperature
or
intermediate temperature
83
83 95
95
106
106
117
117
126
126
83
83 95
95
106
106
116
116
127
127 136
136
°C
102
102
113
113
123
123 133
133 143
143 103
103
114
114
125
125 134
134 144
144 154
154
bar
53 71 91 110 131
7.6 53 71 91 110 131
9.1
65
65
10.7
77
77
12.6
89
89
14.6
101
101
16.9
110
110
7.6
65
65
9.1
77
77
10.7
89
89
12.6
100
100
14.6
111
111
16.9
121
121
121
121 133
133 141
141 151
151 161
161 122
122 132
132 142
142 152
152 162
162 171
171
142
142 151
151 160
160 170
170
143
143 153
153 162
162
– –
– –

Expected discharge gas temperatures

53
30
30
20
20 25
25 30
30 35
35 40
40 45
45
5.7
6.6
7.7
8.8
10.1
11.5
58 64 69 73
77
81
61 65 70 74 79 83
63 68 73 78 83 87
68 72 78 84 89 94
75 79 86 94 99
102
8
8.2 9
9.5
11
11.1
12
12.7
14
14.5
16
16.5
11.0
12.5
14.3
16.2
18.2
20.5
60 64 69 74
79
85
62 67 72 76 82 87
66 71 76 81 86 91
59
70
83
97
59
70
83
69
78
78 86
86 95
95
101
101 108
108
91
91 98
98
106
106
111
111
117
117
69 75
75 84
84 92
92 99
99
Discharge gas temp. Discharge gas temp.
97
105
105
111
111
118
118
123
123 128
128
120
120 125
125 131
131 135
135 139
139
°CDischarge gas temp.°C
°C
113
113
73 78 83 87 92 97
103
°C
82 87 91 95 99
7.6
9.1
10.7
12.6
14.6
16.9
78
78
96
96
115
115
90
90
106
106
126
126
102
102
118
118
136
136
112
112
128
128
146
146
123
123
138
138
155
155
132
132
148
148
165
165
Discharge gas temp.
134
134 144
144 154
154 163
163
– –
153
153 163
163
°C
– –
– –
– –
Page 55

Servicing the refrigeration plant

During both start-up and operation it must be made sure that the plant is working correctly.
Compressor and condenser must be able to work satisfactorily, safety devices must be intact and the evaporator must function under load - that is to say:
S the desired temperatures are observed, S the oil pressure and discharge pipe
temperature on the compressor are correct,
Check Interval Activity
Condensing pressure Excessively high pressure may be
Pressure and temp.
S the condenser pressure is not excessively
high, and
S the plant otherwise works as it is sup-
posed to.
The service instructions outline some general guidelines for servicing the refrigeration plant, with some references to the instruction manual. The service instructions should therefore be read and followed carefully.
due to:
reduced cooling effect
air in the condenser.
Daily
Too low condenser pressure im­plies a risk of restricting the refri­gerant supply to the evaporator.
0171-470-EN 97.07
Filters
Dehumidi­fier
Discharge pipe temperature
Filter in – liquid line – thermostatic valve – suction line – oil return
Moisture in the sight-glass (on HFC/HCFC installations)
Clean when needed
When needed
Normal discharge pipe tempera­ture acc. to instructions.
Accumulated dirt causes reduced refrigerant supply to the evapora­tor.
If a filter has a hot inflow and cold discharge, this may be due to clogging of the component.
Some installations are provided with a sight-glass featuring mois­ture indicator; if the indicator col­our switches from green to yellow, there is moisture in the refrige­rant.
Change the drying filter regularly.
54
0178-910-EN
Page 56
Refrige­rant
Check Interval Activity
Refrigerant charge Inadequate charge results in re-
duced plant capacity and often leads to an excessively high dis­charge pipe temperature.
Leak detection
Periodically
The plant must be searched regu­larly for leaks. Flanges and joints settle during the plant’s initial op­eration period. They must therefo­re be tightened and checked.
Automatic controls
Electric motor
Con­denser
Safety pressure controls Automatic operating controls Alarms
Lubrication of electric mo­tors
Alignment of coupling V-belt drive
Corrosion Marine condensers are normally
Periodically
Periodically
Periodically – normally min. 4 times a year
Adjust operating point and check the function. Replace switch sys­tem if sticking.
Clean and lubricate according to supplier’s instructions. At temper­atures lower than -25°C, use spe­cial lubricant.
Check in accordance with the instructions of the instruction manual. Tighten loose V-belts, if any, or replace by new ones.
protected against galvanic corro­sion by the mounting of corrosion plugs in the condenser covers.
Metallic contact between corro­sion plug and cover is essential to proper functioning.
Evapora­tor
0178-910-EN
Frosting-up Problem-free operation is condi-
When needed
Oil draining (ammonia plant) Check evaporator, intermediate
Periodically
tional on the evaporator being kept free of ice. Defrost as and when required.
cooler, receiver, etc. for oil accu­mulation. Exercise caution; use a gas mask.
55
Page 57
Maintenance of reciprocating compressor
SMC 104-106-108 Mk3, TSMC 108 Mk3 - S, L and E SMC 112-116 and TSMC 116 Mk3 - S, L and E
General
When the compressor requires maintenance, it is important to follow the instructions given below. In order to make sure that the com­pressor is working correctly, the gauge mea­surements and screw torques must be strictly adhered to. Before opening the compressor, it is expedient to ensure that you have spares of those seals and gaskets to be stripped down or dismantled. An O-ring which has been exposed to oil and heat for any length of time may have expanded so much as to prevent it being refitted. All seals and gaskets used are resistant to oil, HFC/HCFC and ammonia. All O-rings are made of neoprene rubber.

Pump-down

Before opening up the compressor for in­spection, the pressure inside must be low­ered to slightly above atmospheric. This can be done in the following way, depending on whether the compressor is operational or de­fective.
1. If the compressor is operational
Run the compressor at minimum capacity at normal operating temperature.
Adjust the low-pressure cut-out so that the compressor stops at a suction pressure of approx. 0.1 bar.
the oil time to escape without the oil foaming. This is of great importance in compressors running on HFC/HCFC. An ammonia com­pressor can stand having the pressure re­duced somewhat more quickly without the oil foaming.
Once the pressure is down to approx. 0.1 bar, stop the compressor and perform the following steps in the order specified:
S Close suction stop valve. S Cut off power to compressor motor. S Close discharge stop valve. S Draw off last remains of refrigerant gas
through purge valve Pos. 42.
S Having ensured that power to compressor
motor cannot be inadvertently connected, the compressor is ready for opening.
S Remove all fuses, if any.
2. If the compressor is inoperative
S Leave heating rod in crankcase connected
for a couple of hours before compressor is due to be opened in order to heat up oil. Warm oil does not contain as much refrig­erant.
S Suction stop valve must be open while
heating rod is connected.
S Keep discharge stop valve closed.
0171-468–EN 00.01
Throttle the suction stop valve very slowly. Keep an eye on the suction pressure gauge.
The suction pressure must be lowered slowly enough to give the refrigerant dissolved in
56
S Close suction stop valve and disconnect
heating rod.
S Equalize pressure in compressor through
purge valve Pos. 42.
0178-910-EN
Page 58
S Once pressure has been equalized to at-
mospheric, compressor is ready for opening. Remember to make sure that power cannot be inadvertently connected, thereby starting the motor.
S Remove all fuses, if any.

Dismantling and assembly

The following sections describe the individual components. When dismantling and assem­bling, parts should generally be fitted in the same position from which they were taken, and should therefore be marked as they are removed. Further they should be thoroughly cleaned, checked and lubricated prior to be­ing reassembled.

Top covers

Dismantling top cover
Before dismantling the top cover, the relief mechanism must be deactivated; this is done by dismantling the short plug Pos. 12D and mounting the long plug from the tool kit instead. This moves the piston Pos. 12B to the opposite end of the relief cylinder.
Loosen and remove screws Pos. 2E, except for the two screws shown on the drawing.
de from a soft hammer while keeping the two screws fitted. This must be done be­cause of the powerful spring pressure bene­ath the top cover. After dismantling the two bolts - unscrewing them alternately - the top cover can be removed.
Fitting top cover
Before fitting the top cover, the long plug must be fitted into the relief cylinder. Check, in addition, that the gasket Pos. 2C is intact and, if necessary, check that the clearance volume and lifting reserve have been ad­justed as described later on in these instruc­tions.
If the gasket Pos. 2C needs to be replaced at all, the graphitized side must face the com­pressor frame. After placing the top cover loosely on top of the springs Pos. 21, it is recommended that all screws be mounted by hand, as they will jointly guide the top cover into position. Now tighten the top cover firmly with the two screws mentioned above, then with the remaining ones.
Finally, cross-tighten all the screws to the prescribed torque in the following sequence:
These screws should be loosened approx. 1 mm, then checking that the cover lifts off the gasket. If, to the contrary, it remains fastened to the gasket, loosen it with a blow on the si-
0178-910-EN
15
16
713 5
11
12
842 6
9
13 14
10
Once the top cover has been fitted, remove the long plug and insert the short plug. The top covers must be mounted as shown on the following chart.
57
Page 59

Mounting top and water covers

SMC 112 SMC 116 TSMC 116
SABROE
SABROE
SABROE
SABROE
SABROE
SABROE
SMC 104 SMC 106
SABROE
SABROE
SABROE
SABROE
SABROE
Shaft end
Shaft end
SABROE
SABROE
SABROE
SABROE
SABROE
SABROE
SABROE
SABROE
SMC 108 TSMC 108
SABROE
SABROE
SABROE
SABROE
SABROE
SABROE
SABROE
SABROE
Shaft endShaft end
SABROE
SABROE
SABROE
SABROE
SABROE
SABROE
Control end
Shaft end
Water covers
Right top covers
SABROE
Left top covers
SABROE
SABROE
SABROE
Shaft end
58
Side covers
T0177092_0
0178-910-EN
Page 60

Discharge valve

21
20E
20D
Pos. 20
20B 20A 20C 20G
As shown on the above drawing, the function of the discharge valve Pos. 20 is partly to al­low the compressed gas to pass from the compression chamber of the cylinder to the discharge chamber beneath the top covers and partly to create a seal from the discharge chamber to the cylinder.
Furthermore, the discharge valve acts as a safety device in the event of liquid refrigerant passing the valve together with the discharge gas, also called liquid stroke. Such stroke should normally not occur, as liquid cannot pass the valve as quickly as the compressed gas. This produces a violent increase in pres­sure in the compression chamber.
In order to avoid pressure of such intensity that it may damage the bearings in the com­pressor, the discharge valve is retained in position by the safety spring Pos. 21, which allows it to lift a little under the strain of in­creased pressure.
Liquid strokes are heard as a distinct hammering in the compressor; the cause must be found immediately and the mal­function rectified.
20F
Discharge valve types:
Depending on the refrigerant and operating conditions under which the compressor oper­ates, various discharge valves need to be used to achieve an optimal function. The dis­charge valves are selected as shown in the diagram below on the basis of the conden­sating or intermediate pressure temperature.
Refri-
gerant
R717
HFC/
HCFC
15°C v TC <
TC w
Marking
All pressure valves supplied from SABROE today are marked as described below and shown on the sketch.
Refrigerant R717 : All discharge valves are marked with one
groove.
Conditions Valve
TC w 15°C
45°C R404A-R507 50°C R22 70°C R134a
45°C R404A-R507 50°C R22 70°C R134a
type
LPTC t 15°C HP LPTC t 15°C
HP
VHP
0178-910-EN
59
Page 61
Refrigerants HFC/HCFC : All discharge valves are marked with two grooves.
S Tighten bottom nut Pos. 20E to torque of
10.2 Kpm 100 Nm. If need be, exert counterpressure with 5 mm Allen key on bolt head.
Marked with LP-HP or VHP
Marked with one groove for R717
two grooves for HFC/HCFC
Dismantling
S When top cover has been removed, spring
Pos. 21 and discharge valve Pos. 20 can be lifted out by hand. See dismantling of top cover.
S Tighten discharge valve in a soft-jawed
vice, then dismantle two nuts Pos. 20E together with spring guide Pos. 20F.
S Fit spring guide Pos. 20F and tighten top
nut to same torque: 10.2 Kpm 100 Nm.

Tightness testing of discharge valve

This is done by means of the pressure drop test as described elsewhere in this instruction manual.

Service life of discharge and suction valves

In order to ensure that the compressor al­ways works perfectly, it is advisable - at suit­able intervals - to replace the suction and dis­charge valve ring plates.
It is difficult to give altogether precise times for such replacements, as the durability of the valve ring plates depends on the follow­ing factors:
S Screw Pos. 20D, discharge valve seat
Pos. 20A and ring plate Pos. 20C can now be disassembled by hand.
S Remove valve springs Pos. 20G by hand.
Assembly
Before assembling the discharge valve, you must make sure that the valve springs Pos. 20G are in good order and fixed firmly in their apertures.
Assemble the discharge valve in reverse se­quence to that described above. Note the fol­lowing, however:
S If the compressor is exposed to liquid
stroke or moist refrigerant gas, the service life is reduced.
S Speed of the compressor:
At 900 rpm, the service life of the valve ring plates is considerably longer than at 1500 rpm.
S The compressor ratio at which the com-
pressor operates: At high compression ratios, the load on valve ring plates and springs is appreci­ably larger than at low compression ratios. When the valve ring plates are changed, the valve springs should also be replaced.
60
0178-910-EN
Page 62

Cylinder lining with suction valve

Marking of suction valve stop:
Marking of suction valve
Dismantling suction valve
Dismantling the screws Pos. 19N makes it possible for the guide ring Pos. 19J, suction valve stop Pos. 19H and ring plate Pos. 19F to be removed from the cylinder lining. The paper gasket Pos. 19T can be expected to disintegrate during dismantling and require replacement.
Mounting suction valve
one groove for R717 two grooves for
HFC/HCFC
T0177131_0 v3
The cylinder lining and suction valve form an integral unit which can be dismantled by re­moving the screws 19N.
In order to gain access to the cylinder lining or suction valve, the top cover, spring Pos. 21, and discharge valve Pos. 20 need to be disassembled.
Extracting cylinder lining
S Rotate crankshaft to position relevant pis-
ton at top dead centre.
S Fit the two T-shape extractors no. 3 from
tool kit into threaded holes in guide ring Pos. 19J.
Before reassembling the suction valve, you must ensure that the valve springs Pos. 19G are in good order and fixed firmly in their apertures.
Perform the assembly in reverse sequence to that described above. Note the following, however:
S Change paper gasket. S Before tightening screws 19N, ensure suc-
tion valve plate can be moved freely in its guide. Tighten screws Pos. 19N to torque of 1.4 Kpm 14 Nm.
Inserting cylinder lining
S Rotate crankshaft to position piston at top
dead centre.
S Check that long plug from tool kit is
screwed into relief cylinder; see Top cov-
ers section.
S Check that gasket Pos. 19K is in position
on frame.
S Carefully pull out cylinder lining with suc-
tion valve, checking that gasket Pos. 19K remains in frame.
S Insert protective plate no. 5 (from tool kit)
between piston and frame so the piston can rest on it. This will enable piston and piston rings to slide onto the protective plate without being damaged when the crankshaft is turned.
0178-910-EN
S Lubricate piston, piston rings and cylinder
face with clean refrigeration machine oil. Likewise, grease O-ring Pos. 19M on HP cylinder of TSMC compressor with clean refrigeration oil.
S Rotate piston rings on piston in order to
stagger ring gaps at 120° to each other. Press cylinder lining down over piston carefully. The chamfering on the cylinder
61
Page 63
interior will catch the piston rings and squeeze them to the diameter of the cylin­der. If possible, fit cylinder in same place from which it was taken.
S Press cylinder lining down manually, and
with no rotary movements, until it makes contact with gasket Pos. 19K.
S Check clearance volume, which is de-
scribed in section Control measurements
for insertion of new cylinder lining.
S Discharge valve Pos. 20 and safety head
spring Pos. 21 can then be fitted.
S Fit gasket and top cover.
S Once top cover is in position - see Top
covers section - remove long threaded plug and screw in short plug, having first checked aluminium gasket Pos. 12E and found it fit for use.

Connecting rod

The connecting rod pos. 17 is made of two parts carefully adapted to each other. The two parts are held together by means of two bolts secured with lock nuts.
Procedure for removing piston and connecting rod
S Bleed compressor of oil and refrigerant
and safeguard against any unintended start-up.
S Disconnect any water hoses and other
piping connections to top and side covers.
S Dismantle top and side covers.
S Remove spring Pos. 21, discharge valve
and cylinder liner.
S Remove nuts Pos. 17D; following this, the
bottom part of the connecting rod can be taken out by hand.
S Piston and connecting rod can then be
lifted out through the top cover opening on the frame.
The connecting rod Pos. 17 is equipped with independent bearings at both ends. The big end is fitted with two bearing half bushes Pos. 17A, consisting of a half-cylindrical steel plate internally coated with white metal. These bearing half bushes are secured in the connecting rod, partly through their fit in the connecting rod bore and partly by a spring which fits into a milled groove in the connect­ing rod. The opposite end of the connecting rod is fitted with the gudgeon pin bearing Pos. 17B, of which the following two types are found: See spare-parts drawing.
S The bearing bushing Pos. 17B-1 is made
of special bronze and is also used in R717 compressors. The bearing bushing is used in all SMC compressors and in the low pressure stage on TSMC compressors.
S The needle bearing Pos. 17B-2 is 2 mm
greater in outside diameter than the above bearing bush and must therefore be fitted in a piston rod bored to the diameter of this bearing. The needle bearing has no inner ring but fits the diameter of the gud­geon pin directly.
S If the bearings in the connecting rod are
worn so that the clearance is greater than that prescribed in the table entitled Vari-
ous clearances and adjustment measure­ments, they must be replaced with new
bearings. In this connection, note that un­dersized half sections of bearing can be supplied for use in the crankshaft where the journals have been ground to a corre-
62
0178-910-EN
Page 64
sponding undersize. See table in section on Diameters for undersized bearings.
Fitting bearings
S The bearing bushing or needle bearing
can be squeezed into or out of the con­necting rod in a vice or hydraulic press. Use softjaws in the vice and use tools which do not damage any components. The bearing bushing must be fitted as shown on the sketch, with the lubricating ducts facing sideways.
Fig. 1
Fig. 1
Note:
Sleeve to be fitted with lubri­cating ducts positioned as shown on dra­wing.
T0177131_0 v2,a
S Introduce connecting rod down through
top cover opening in frame and guide into position on crankshaft manually. Take care so that connecting rod bolts do not leave marks in crankshaft journals.
S Position connecting rod interior through
lateral opening on frame, and fit nuts.
Note:
The two parts of the connecting rod are numbered with the same number; this is only of importance when assembling. Parts with different numbers must not be assembled and it is important that the numbers are fitted in the same direction as shown in Fig. 2.
Fig. 2
Note:
Stamped number on the same side on as­sembly
Fitting connecting rod
Before fitting the connecting rod in the com­pressor stand, piston and piston rings must be fitted onto the connecting rod. See the follow­ing sections. In addition, the two connecting rod bolts Pos. 17C must be fitted as shown on the spare parts drawing.
S Fit bearing bushes into both parts of con-
necting rod.
916 916
T0177131_0 v2,b
S Tighten nuts Pos. 17D alternately with in-
creasing torque and finish off with torque wrench. Torque: 4.4 Kpm 43 Nm.
0178-910-EN
63
Page 65

Piston

The piston is made of aluminium and fitted with two piston rings, nearest the piston top, and an oil scraper ring.
Fig. 3
For compressors with: 80mm stroke lengths, type S, 100mm stroke lengths, type L, and with 120mm stroke lengths, type E. The difference is clearly seen from fig. 3.
Piston
Type S
70
120
50
Piston
Type L
The same piston and piston pin are used, irrespective of whether the connecting rod contains a sleeve or a needle bearing.
Fitting piston rings in piston
Before mounting the piston rings in the pis­ton, their fit in the cylinder lining should be checked by measuring the ring gap. See sec­tion entitled Various clearances and adjust- ment measurements.
Piston
Type E
60
110
50
60
40
T0177131_0 v1
S Fit one of the circlips pos. 18D into bore
reserved for piston pin.
S Heat piston to 70°C in oil or on hotplate. S After inserting bearing bush or needle
bearing, guide connecting rod into place in heated piston. The piston pin can now be positioned without the use of tools. It is sometimes possible to fit the piston rod by hand without a preliminary heating of the piston.
100
Assembling and stripping down piston and connecting rod
Adopt the following procedure when assem­bling piston and connecting rod:
64
S Fit last Seeger ring To strip, reverse sequence; however, do not
heat piston, but press piston pin out using a punch or mandrel.
0178-910-EN
Page 66

Shaft seal

10F 10D 10E 10H
10J 10A
5.5 mm 8C
8H
2 mm
8A 8F
10G 10B
8G 8B
3126-176-R
The purpose of the shaft seal is to create a tight seal along the crankshaft between the inside of the compressor and the atmo­sphere.
It comprises a slide ring Pos. 10E, manufac­tured from special-purpose cast iron, which is secured to the crankshaft by means of the locking ring Pos. 10H, tightening flange Pos. 10A and the four screws Pos. 10J with spring washers Pos. 10K.
The carbon slide ring Pos. 10F is pressed against the flat-machined, lapped slide ring at the end of Pos. 10E by a series of springs Pos. 10B. The carbon slide ring is prevented from rotating by means of the retention pin Pos. 8H.
T0177131_0 V13
It is recommended to exercise great care with the lapped slide surfaces. Even the slightest scratch or other damage to the slide surfaces will result in leaks.
The O-ring Pos. 10D creates a seal between the slide ring Pos. 10E and the crankshaft. O-ring Pos. 10G seals between the carbon slide ring Pos. 10F and the shaft seal cover Pos. 8A.
When the shaft seal is operating, a tiny amount of oil drifts out between the slide faces to lubricate them. An oil throw ring Pos. 8F has therefore been fitted to prevent this oil migrating along the axle to the transmission linkage.
The spring pressure, combined with the flat-lapped faces of the two slide rings, ensur­es an optimal seal between the faces, either when rotating or stationary.
0178-910-EN
The thrower ejects the oil into the groove in the shaft seal cover Pos. 8A and the oil is piped via the plastic hose to a plastic bottle positioned under the compressor.
65
Page 67
1. Dismantling and stripping down shaft
seal
1.1.Once the gas pressure in the compres­sor has been eliminated and the motor safeguarded against inadvertent start-up, dismantle coupling or V-belt disk.
Fig. 3
10G 8A8G 10F
8C
Note:
On units featuring coupling, there is no need to move the motor, as the coupling and the shaft seal can be taken out be­tween the two shaft ends.
1.2.Dismantle shaft seal cover Pos. 8A by alternately loosening bolts Pos. 8C so as to displace shaft seal cover outwards wit­hout jiggling. This will avoid damage to internal parts of the shaft seal.
1.3.Once the spring force is equalized and the bolts removed, the shaft seal cover can be taken off the shaft end by hand. Take care so that no damage is done to the carbon slide ring Pos. 10F which co­mes out with it.
1.4.The carbon slide ring Pos. 10F can be extracted by dismounting circlip pos. 8G as follows:
Mount tool no. 2 as illustrated in fig. 3 and tighten screw A so that the carbon slide ring does not touch the locking ring.
A
1.5.Dismantle slide ring 10E by turning the four Allen screws 10J a max. of 2-3 turns; the entire unit can then be taken out with the fingers or using two screwd­rivers inserted into the external groove on the slide ring Pos. 10E and moved in the direction of the arrow as illustrated in fig. 4.
Fig. 4
10A
Take care not to tighten screw A too much as this could damage the car­bon ring.
Circlip pos. 8G is now easily extracted by means of a screw driver without damag­ing the slide surface of the carbon slide ring.
After removing tool no. 2, the carbon slide ring pos. 10F, O-ring pos. 10G and springs pos. 10B (see fig. 2) can now be dismantled.
66
1.6.O-ring Pos. 10D can now be removed.
Assembling and mounting shaft seal
After thoroughly cleaning the crankshaft, check that its sealing faces are smooth and free of scratches, blows and wear marks. Then oil the crankshaft and the shaft seal components thoroughly with the same type of oil as used in the compressor.
0178-910-EN
Page 68
2. Unit with slide ring, Pos. 10E
2.1.Before fitting slide ring Pos. 10E, tighten screws Pos. 10J until there is approx. 2 mm spacing and parallelism between the two flanges. Check also that locking ring Pos. 10H is mounted as shown in the drawing and that O-ring Pos. 10D is in position.
2.2.Position slide ring Pos. 10E on shaft and ensure tightening flange makes contact with shaft shoulder.
2.3.Crosswise, tighten screws Pos. 10J alter­nately with Allen wrench from tool kit. The torque is specified in the instruction manual.
2.4.Check axial position of shaft seal by measuring distance from frame sealing face to slide face on Pos. 10E. This must measure approx. 5.5 mm, as shown in the drawing.
3. Unit with shaft seal cover Pos. 8A
3.1.Mount O-ring Pos. 10G and the ten spiral springs 10B in shaft seal cover Pos. 8A, then position carbon slide ring Pos. 10F carefully. Rotate carbon slide ring so slot fits in over retention pin Pos. 8H.
3.2.With tool no. 2 fitted as shown in fig. 3 press carbon slide ring pos. 10F against spring pos. 10B. Locking ring Pos. 8G can now be fitted. Observe closely that the carbon slide ring is not overloaded by misbalanced pressure and that its slide face is not damaged.
3.3.Give complete shaft seal cover an extra oiling on slide face of carbon slide ring and guide it in over shaft together with gasket Pos. 8B.
3.4.Gently pressing shaft seal cover and car­bon ring in against slide ring Pos. 10E without compressing springs Pos. 10B,
measure distance from gasket Pos. 8B to sealing face of shaft seal cover. This distance must be about 3 mm. Make sure the hose branch Pos. 8D fa­ces down.
3.5.Mount screws Pos. 8C and tighten even­ly, crosswise. This will avoid damaging the carbon slide ring. Tighten screws Pos. 8C to prescribed torque according to table in instruction manual.
3.6.Mount oil throw ring, as shown in drawing.
3.7.After mounting coupling half or V-belt disk, it must be possible to turn the crankshaft easily by hand.

Crankshaft

The crankshaft is made of heat-treated SG cast iron with fine strength and glide proper­ties. The bearing journals are superfinished and oil channels are bored for all lubricating points.
At the centre and end of the crankshaft, the oil channels are blanked off with 3 blind plugs on the SMC 104 - 106 - 108, and 6 plugs on the SMC 112 and 116.
When fitting the crankshaft, it should be checked that the plugs are mounted and tightened. By way of bores in the counter­weights, the crankshaft is dynamically bal­anced with regard to 1st and 2nd order forces.
The crankshaft is available in three versions: an S type for compressors with short strokes (80mm), an L type for longer stroke (100mm) and an E type for the longest strokes (120mm). The crankshafts have an S, L or E stamped into the connecting end.
0178-910-EN
67
Page 69
Dismantling crankshaft
Inspection
Dismantle the crankshaft through the pump end of the frame in the following way:
S Bleed compressor of oil and refrigerant
and safeguard against inadvertent start-up.
S Dismantle top and side covers. S Dismantle all cylinder linings. S Extract all pistons and connecting rods. S Pull off V-belt pulley or coupling half . S Dismantle shaft seal cover and shaft seal. S Dismantle cut-outs and pipes to manome-
ters, or piping connections to UNISAB.
S Dismantle end cover, Pos. 4A. S Dismantle oil filter.
Check bearing journals on connecting rods for wear and tear and, if necessary, measure diameter of journals. The maximum wear on the bearings is shown in the section Various clearances and adjustment measurements. In most instances, the permissible play in the bearing can be obtained by replacing the bearing half bushes. The bearing journals on the main bearings are normally subject to very little wear, but should be check mea­sured during main overhauls. If wear and tear exceeds the play stated, the crankshaft can normally be ground to 0.5 mm undersize. For the ground crankshaft, main bearings and connecting rod bearings with an undersize of
0.5 mm can be supplied as stated in the parts list.
The drawing for grinding the crankshaft to undersize is found in this instruction manual.
S Dismantle oil pump drive and oil pump. S On SMC/TSMC 112-116 loosen the
middle bearing by dismantling the plugs pos. 49H as well as gasket pos. 49J in both sides of the compressor. Next, dismantle screws pos. 49F and lock­ing plates pos. 49G.
S Rotate crankshaft to place connecting rod
journals on horizontal level.
S Dismantle bearing cover at pump end and
support the crankshaft by means of a board inserted through the side openings.
S After this the crankshaft can be drawn out
of the framne. The crankshaft must still be supported.
S The middle bearing on SMC/TSMC
112-116 can be dismantled by removing
screws pos. 49B and shims pos. 49C as well as guide pins pos. 49D.
Note:
After grinding the crankshaft, all lubricat­ing channels must be thoroughly cleaned with an approved cleansing fluid and blasted with compressed air. Remember to refit the blind plugs.
S Check sealing face for O-ring seal, Pos.
10D, on shaft seal. The surface must be bright and free of scratches and marks.
Refitting crankshaft
Refit the crankshaft in the reverse order to that for dismantling. Note the following, however:
S After the crankshaft has been inserted into
the housing, mount main bearing cover Pos. 5A using gasket Pos. 5D as a shim.
S Check end play on crankshaft by pressing
shaft up against pressure bearing Pos. 6C and measure clearance in the other bearing, using a feeler gauge.
68
0178-910-EN
Page 70
The permissible end play is indicated in the section Various clearances and adjust-
ment measurements.
End play adjustment is achieved by means of the gasket Pos. 5D.
The gasket can be supplied in the follow­ing thicknesses, see the spare parts list:
0.25mm 0.50mm 0.75mm 1.0mm

Main bearings

The main bearings pos. 5C and 6C are mounted on the main bearing covers and their purpose is to guide the crankshaft both radially and axially.
They consist of a steel bushing with collar. The collar and the inside of the bushing are provided with a thin white metal coating.
The bushing can be pressed out and re­placed by new ones and need no further machining after mounting.
On mounting the bushings it is recommended to secure them with Loctite 601.
When a new bearing bushing pos. 6C at the shaft seal end is put into place in cover pos. 6A the in- and outlets of the lubricating chan­nels must be positioned in a four o’clock position as illustrated on fig. 1 below. The bearing bushing pos. 5C is positioned with in- and outlets in a 12 o’clock position.
Fig. 1
Mounting of bearing bushing pos. 6C
12 o’clock
4 o’clock
Cover pos. 6A seen from the inside of the compressor
T0177167_0
The bearing bushings can be delivered with crankshafts ground to undersize. See Spare Parts List.
The crankshaft for the SMC 112 and 116, and for the TSMC 116, is fitted with a centre bear­ing. This is fitted with four sets of bearing half bushes of the same type as used in the con­necting rods. The centre bearing housing is made up of two half parts which must be clamped around the crankshaft before this is inserted into the compressor stand.
The half parts are assembled by means of four screws and guided together with the aid of cylindrical guide pins. The bearing housing is prevented from rotating by two screws Pos. 49F. These screws are accessible only when the threaded plug Pos. 49H has been removed. The screws can be removed using a box wrench NV 17 and crank from the tool set.
0178-910-EN
69
Page 71

Compressor lubricating system

19D 15D
19B 15A 15B
13
12
22
11
The oil pump pos. 11 sucks oil from the crankcase, through the filter element Pos. 33, where the oil passes the filter element pos. 33A and past the magnetic filter pos. 33J/K, as shown on the spare parts drawing. The pump forces the oil through an internal pipe, pos. 38A, until it reaches the shaft seal hous­ing.
The filter element Pos. 33A is a disposable filter which cannot be cleaned. See descrip­tion of oil filter.
The shaft seal housing forms a distribution chamber for the oil. The oil pressure in the shaft seal housing is adjusted by means of the oil pressure regulating valve Pos. 22, which is mounted in the shaft seal housing. The regulating valve can be adjusted from the outside by means of a screwdriver. Clockwise rotation increases the pressure; anticlockwise rotation lowers the pressure.
38A
33A
33
33J/K
T0177131_0 V10
Excess oil is returned through a bored chan­nel to the crankcase.
From the shaft seal housing, the oil is distrib­uted as follows:
S Through the bored channels in the crank-
shaft to lubricate main and connecting rod bearings. Lubrication of piston pin bear­ings is done by splash lubrication through a countersunk hole in the top of the con­necting rod.
S To the differential oil pressure cut-out and
the pressure gauge. The effective oil pres­sure can be read straight off the manome­ter (the suction pressure gauge of the compressor).
S Through external oil pipes, on to the regu-
lating cylinders Pos. 12 for unloaded start and capacity regulation.
70
0178-910-EN
Page 72

Oil pump

4A
11H 11Q
11R 11G
11T11M 11J
11L 11N
The oil pump is a gearwheel pump driven by the crankshaft via a pinion drive.
It is therefore important to ensure that the direction of rotation of the crankshaft is as indicated by the arrow on the bearing cover Pos. 6A.
If the crankshaft is to turn in the opposite di­rection of rotation, the oil pump can be fitted with a chain drive. See next section.
11P 11S
S When the four M6 screws pos. 11M secur-
ing the oil pump to the bearing cover have been removed, it can be taken out by hand.
Note:
The oil pump normally has a very long service life. Therefore, it is not worthwhile repairing it. Rather replace it with a new one.
Dismantling the oil pump
Having bled the compressor of oil and refriger­ant and secured it against inadvertent start-up, proceed as follows:
S Dismantle end cover Pos. 4A and side
covers Pos. 3.
S Dismantle internal oil pipes and nipples
screwed into pump.
S Dismantle nut Pos. 11J and extract gear-
wheel pos. 11G.
0178-910-EN
Mounting the oil pump
Before finally tightening the oil pump firmly to the bearing cover, the following adjustment must be made to the gearwheel drive:
The play between the two teeth when en­gaged must be 0.05-0.08mm measured with a feeler gauge. Repeat the measurement six times, turning the crankshaft 60° between each measurement, and adjust until the smallest play is measured to be as started above.
71
Page 73

Chain-driven oil pump with inverse direction of rotation

If the SMC 100 compressor is to run in the opposite direction of rotation to that shown by the arrow on the bearing cover Pos. 6A, the gearwheel drive on the oil pump must be re­placed with a chain drive.
To this end, use a set of replacement parts,
5 3 1
6
stores no. 3141-127. This set contains a chain, a chain wheel (springs for old shaft seals only) and a baffle for lubricating oil, as well as all screws needed.
In case the compressor is driven by an elec­tric motor, attention should be paid to the pre­scribed direction of rotation of the motor. See section: Direction of rotation of the com-
pressor.
7 8
4 2
1
Hub for the chain wheel 5 Endless chain
2
Hub for bottom chain wheel 6 Baffle for lubricating oil
3
Top chain wheel 7 Set screw M6 x 12
4
Bottom chain wheel 8 Spring washer for M6
Assembling instructions
The chain system can be mounted on all types of SMC/TSMC compressor. On older compressors, however, a little adjustment may be necessary, as detailed below:
S Dismantle the two gear wheels by remov-
ing screws Pos. 11Q and nut Pos. 11J.
S On older compressors, the oil pump is
linked to the principal bearing cover Pos. 5A by 2 guide pins and retained by four M6 screws. Remove two guide pins here and bore the free holes for screws up to a diameter of 8 mm. This should be done after the oil pump has been dismantled. On more recent compressors, the free
72
0178-910-EN
Page 74
holes are oval-cast to give scope for ad­justment, and there are no guide pins.
S Mount lubricating oil baffle as shown on
drawing. Drill two M6 threaded holes and tap, using baffle as template; position so that the baffle is at a tangent to the exter­nal diameter of the bearing bush D = 92 mm.
D92
T0177085_0
Adjusting the chain drive:
S Tighten chain by shifting oil pump. The
correct tension of the chain is shown on the sketch.
3.5 – 5.5mm
Screw dimensions: M6 x 12 mm Thread depth: 5 mm Drilling depth: 20 mm Core drill: 5 mm Secure screws with spring washers.
S Slightly tighten four screws securing oil
pump to bearing cover.
S Place chain wheel with hub Pos. 4 and 2
on pump shaft. The retainer nut can be tightened once the entire chain drive has been mounted.
S Place the assembled chain, hub and chain
wheel, Pos. 5, 1 and 3, in position; tighten wheel firmly with screws Pos. 11Q from gearwheel drive.
T0177085_0
Finally, when the proper centre distance has been established, secure oil pump tightly.
S Tighten chain wheel on oil pump.
Marking direction of rotation
The arrow on the end cover of the compres­sor should be cancelled out and replaced by one painted on the indicate the new direction of rotation.
0178-910-EN
73
Page 75

Oil pressure valve

The oil pressure valve pos. 22 regulates the oil pressure in the compressor. Mounted in the cover Pos. 6A, it connects directly with the oil pressure chamber in the shaft seal housing.
The oil pressure is regulated by a spring loaded cone, the spring pressure being ad­justed by turning an adjusting screw at the valve end. Use a screwdriver for this pur­pose.
Turning to the right (clockwise) raises the oil pressure; turning to the left (anticlockwise) lowers the pressure.
Adjustment
Oil pressure: 4.5 bar. The oil pressure can be read off the suction
pressure gauge or on UNISAB II.
On more recent compressor models the adjusting screw may be locked by means of an M6 pointed screw, fig. 1, which must be loosened before adjustment can take place.
Service
Since the oil pressure valve is not subject to any appreciable wear or soiling, it should not be disassembled during routine services.
Fig. 1
locking screw
In the event of a malfunction, the complete val­ve should be replaced.
22A
22B
T0177083_0
74
0178-910-EN
Page 76

By-pass valve pos. 24

The compressor is equipped with a built-in mechanical by-pass valve, fig. 1, which safe­guards it against any inadvertent excess pressure if the electrical safety equipment fails. The by-pass valve safeguards against any excess pressure between the discharge and suction sides of the compressor.
If the by-pass valve goes into action, the compressor must be immediately stopped and the cause established.
The by-pass valve is supplied ready-set and sealed in accordance with the adjustment pressures indicated in the table Pressure and temperature settings. The actual set pressure is stamped on the rating plate, pos. A.
Thus, watch out that hole pos. B does not get covered or clogged.
In case the pressure on the discharge side exceeds the set pressure so that the by-pass valve opens, the valve will remain open until the pressure on the discharge side has fallen to approx. half the set pressure. The valve then closes automatically. However, at great differential pressures across the compressor the valve may remain open. In that case, stop the compressor and close the discharge stop valve entirely. The equalization of pres­sure in the compressor will then close the safety valve and the compressor can be re­started.
The by-pass valve is supplied factory-set and sealed and need normally not be disassem­bled and readjusted.
The by-pass valve is of the high-lift type which makes it very sturdy and durable.
Further, the by-pass valve is independent of the pressure on the compressor suction side. Consequently, it only opens when the pres­sure on the discharge side exceeds the set pressure in relation to atmospheric.
Fig. 1
If necessary, control of function and set pres­sure must be made in accordance with local regulations for safety valves.
On the outside the by-pass valve is sealed with two O-rings, pos. 24B and 24C. Fasten it to the compressor housing by means of screws pos. 24D and washers pos. 24E.
24C 24B
A
0178-910-EN
B
T3137T02I_1
75
Page 77

Oil filter

All oil to the lubricating system of the com­pressor is filtered through a oil filter installed in the crankcase. The filtration element is a filter cartridge (Pos. 33A on the drawing) which is non-cleanable and must be replaced with a new one when the filter capacity is used up.
It is important, therefore, always to have an extra filter cartridge available.
Filter cartridge
As shown in fig. 1 the filter cartridge pos. 33A is a single unit consisting of a 60 m primary filter, a magnetic filter and a shield which co­vers half of the filter.
The filter cartridge is fastened to bracket pos. 33F by means of a lock nut pos. 33M and a washer pos. 33L. The gasket pos. 33B seals off the filter cartridge and the bracket pos. 33F.
Changing filter cartridge
The filter cartridge should be replaced at reg­ular intervals. See the section entitled Servic- ing compressors on this point. In particular, it should be remembered that the filter car­tridge must often be replaced after a relative­ly short operation time following initial start­up.
This is due to small particles of dirt origina­ting from the plant during the initial operating period.
Fig. 1
33L
33F 33M
Before changing the oil filter cartridge all pre­parations in connection with the opening of the compressor must be carried out in accor­dance with the instruction manual.
33A33B
filter cartridge pos. 33A and the gasket pos. 33B.
Proceed as follows:
S Dismount the lock nut pos. 33M and
washer pos. 33L and remove manually the
76
S Let the bracket pos. 33F stay mounted in
the compressor.
0178-910-EN
Page 78
S When mounting the new oil filter cartridge
as illustrated in Fig. 1, first place the gas­ket pos. 33B on the bracket pos. 33F.
the closed shield on the filter faces up- wards. Then fasten the filter by means of the lock nut pos. 33M and the washer pos. 33L.
S Then place the oil filter cartridge pos. 33A
on the bracket pos. 3Fand turn it so that
S Tighten the nut pos. 33M to a torque of
4.5 Nm.
0178-910-EN
77
Page 79

Suction filters

The purpose of the filters is to collect impuri­ties conveyed from the plant to the compres­sor with the suction gas and thus prevent them from penetrating into the compressor.
The suction filters therefore have a very fine mesh and as an additional precaution have a filter bag insert, which should normally be used for 50 operating hours from the initial start-up of the compressor. The filter bag is then removed and disposed of.
If the filter bag is badly soiled after the 50 op­erating hours mentioned, it is recommended that a new bag be fitted for an additional 50 operating hours. Similarly, a filter bag ought to be fitted for a period of 50 operating hours after any major repair work to the refrigera­tion plant.
Note:
Do not forget to remove the filter cartridge after 50 operating hours, as a blocked fil­ter bag may cause the suction filter to burst and thus contaminate the compres­sor to an extreme degree.
There are always two suction filters in the compressor and these are removed through the flanged opening in the bottom end of the filter housing. Attention is drawn to the fact that there are two types of suction filter, as detailed below:
On SMC compressors, the two suction fil­ters are identical and should only be fitted with an O-ring in the end facing up towards the suction stop valve. The filters are open at both ends.
TSMC 108
LP HP
On TSMC compressors, the suction filter
located on the lefthand side opposite the low­pressure cylinders (see drawing) is the same type as on SMC compressors, i.e. open at both ends and having an O-ring in the end facing up towards the suction stop valve.
TSMC 116
LP HP
The suction filter fitted on the righthand side opposite the high-pressure cylinders has a closed end-bottom which must face upwards and close towards the suction stop valve. This suction filter must be fitted with O-rings at both ends.
78
0178-910-EN
Page 80

Stop valves

AK AC A AJ
AD
E
F
D C
H Y
L
P
POS. 25
K
R
S
T
U
M
B
J
ZAGQGN
The suction and discharge stop valves are used to isolate the compressor from the re­frigeration plant.
They are closed completely by manual tight­ening and it is therefore advisable not to use any tool to close the valve, as this will simply overload the valve parts.
The valve seat is sealed with a teflon ring Pos. 25H which, if necessary, can be re­placed as follows:
Dismantling of valve:
S Once the pressure on the inlet and dis-
charge sides of the valve has been equal­ized to atmospheric, dismantle screws Pos. 25AJ. The valve throat Pos. 25B, and with it the entire valve insert, can then be removed.
S Turn spindle clockwise until cone and
threaded piece Pos. 25G can be removed by hand.
T0177131_0 V14
S Mount threaded piece Pos. 25G in a
soft-jawed vice and dismantle screw Pos. 25E.
Note:
The screw has a lefthand thread, and it is therefore inadvisable to leave the threaded piece in the valve holder while dismantling the screw, as the guide pin Pos. 25N will be overloaded.
S The front and rear pieces Pos. 25C and
25D can now be separated and the Teflon ring Pos. 25H removed. The Teflon ring will be flattened on one outer edge, which is normally of no impor­tance to its sealing ability providing it is free of scratches and marks.
S If required, the Teflon ring can be reversed
when reassembling so that the other outer edge seals towards the valve seat in the housing.
0178-910-EN
79
Page 81
Reassembly of valve:
Reassembly is done in the reverse order to that above. Note the following, however:
S Before mounting the complete valve in-
sert, the valve cone with threaded piece Pos. 25G must be screwed right into the valve neck Pos. 25B.
S The O-ring Pos. 25J may have expanded
under the influence of the oil in the plant and will normally have to be replaced with a new one.
The stop valve has a so-called retroseal, which enables the packing screw joint
Pos. 25M to be serviced even when there is excess pressure in the valve housing.
Adopt the following procedure:
S Using handwheel, open valve completely
to achieve a seal between valve cone and valve throat. The gasket Pos. 25Q acts as a sealing element.
S The packing screw joint Pos. 25M can
then be screwed out for inspection or re­placement of the O-ring Pos. 25R and 25P. Thoroughly lubricate all parts with oil before reassembling.
80
0178-910-EN
Page 82
Unloaded start and capacity regulation on SMC
0171-907-EN 96.02
and TSMC 100 and 180 compressors
SMC and TSMC compressors are equipped with an automatic unloader system to provide full relief to the compressor during the start-up phase. This reduces the starting torque of the compressor considerably.
Fig. 1
20
19D 15D 19B
15A
15B
13
The unloader system is also used to regulate the capacity of the compressor.
The following schematic outline shows the lubrication and hydraulics system on the compressors together with unloader me­chanism.
12
12J
2
50
2
2
3
1
11
Description of unloader mechanism and capacity regulation
No-load starting and capacity regulation are achieved by keeping the suction valve ring plate in the open position; the refrigerant gas thus aspired into the cylinder is not com­pressed but thrust back out through the suc­tion valve.
22
38
33
T0177131_0 V10
See the blue spare parts drawing of the cylin­der linings at the end of this manual.
Around each pair of cylinder linings a frame Pos. 13 is fitted, controlling two sets of rocker arms Pos. 15A. The frame is connected by means of a piston rod to the regulating piston in the unloading cylinder pos. 12.
0178-910-EN
81
Page 83
When the regulating piston is unaffected by the oil pressure - i.e. when the connected solenoid valve is de-energized or when the compressor is at standstill - the regulating piston and the en­tire frame are shifted to the right by the pres­sure from the springs Pos. 12J (see fig. 1) .
The tension springs Pos. 15D will thus raise the rocker arms Pos. 15A into the vertical po­sition, as these rotate in the ball sockets Pos. 15B.
This movement lifts the relief ring and the pins Pos. 19B, opening the suction valve by force.
If oil pressure is placed on the relief cylinder during operation, the unloader system is shifted to the left (see sketch). This lowers the rocker arms Pos. 15A, and the relief ring with pins Pos. 19B is moved away from the suction valve ring plate, allowing this to oper-
ate freely and close during the compression phase.
During operation, the unloader system can therefore regulate the capacity of the com­pressor by causing the solenoid valve - which is linked to the relief cylinder - to open or close for oil pressure to the relief cylinders, controlled by an electrical regulation system.
On TSMC compressors, attention is drawn to the two types of relief cylinder - for the LP and HP stage, respectively, as shown on the spare parts drawing.
Note:
Adjust the oil pressure on the regulating valve Pos. 22 to 4.5 bar. At an oil pressure lower than 3.5 bar (the breaking pressure for the safety automatices), there is a risk of the unloader system not being moved effectively and thus being damaged.
82
0178-910-EN
Page 84

Pilot solenoid valves

The pilot solenoid valve is an electromagnet­ic three-way valve which with a dead coil connects the unloading cylinder to the crank­case (the path for the oil flow from pipe 2 to pipe 3 is open). See fig. 1. If the coil is ener­gized, the valve switches so that the path for the oil flow from pipe 1 to pipe 2 is open and
The solenoid valves are integrated in blocks (fig. 2) with 1,2,3, or 4 solenoid valves in each block. In these blocks the solenoid valves have a collective supply of pressure oil (pipe 1) and a collective connection to the crankcase (pipe 3). Each individual solenoid valve has its own oil connection to the rele­vant unloading cylinder (pipe 2).
the connection to pipe 3 is closed off.
Sectional drawing of capacity regulating valve
Fig. 2
2
3
1
Danfoss 034F9034_1
0178-910-EN
83
Page 85

Schematic outlines

The following schematic outlines shows the oil pipe connections and the wiring diagram with cut-out functions.
The schematic outlines also indicate the per­centual capacity at which the compressor op­erates at the various capacity stages.
The lowest capacity percentage indicated on schematic outlines 1 corresponds to the low­est permissible capacity step at which the compressor may work by continous opera­tion.
In special instances, e.g. where the start-up phase is lengthy, it may prove necessary to relieve the compressor altogether until the motor has achieved a sufficient torque. In such cases, an extra solenoid valve marked ’S’ can be mounted as shown on schematic outlines 2.
The S-valve is connected to the regulating cylinder(s) not involved in capacity regula­tion.
The valve is designed to prevent fast rising oil pressure actuating the compressor cylin­ders before the motor starter has changed over to the delta position, or a gas or diesel motor has reached full rotation speed.
TSMC compressors are always equipped with S-valves and thus feature totally un­loaded start as standard.
Note:
Please note that the solenoid valve S must not be wired so as to form part of the capacity regulation. The compressor may operate totally un­loaded for no more than 5 minutes, as its operating temperature will otherwise be­come too high.
84
0178-910-EN
Page 86

Standard unloaded start and capacity regulation

The SMC and TSMC compressors always start totally unloaded and in their standard design will activate a number of cylinders corresponding to the lowest capacity stage once the oil pump has built up the necessary oil pressure.
See discussion of the ’S’ solenoid valve in the Totally unloaded start and capacity regu- lation section, however.
It is recommended that solenoid valves be wired so as not to receive the opening signal until the drive motor has achieved full torque.
Regulating sequence
The unloading is effected for two cylinders at a time by cutting off the voltage to the ac­companying solenoid valve.
The unloading must be effected in numerical order (1 - 2 - 3 - 4), while loading should be done in reverse order (4 - 3 - 2 - 1).
Note:
TSMC 116 must always have valves 3 and 4 connected simultaneously, as this capacity stage includes both low- and high-pressure cylinders.
The regulating sequence may be seen from the schematic drawings.
Schematic drawings 1
SMC/HPC 104
%
100
50
N
L
SMC/HPC 106 SMC 186
%
100
67 33
N
L
SMC/HPC 108 SMC 188
%
100
75 50
25
N
L
SMC 112
TSMC 108 TSMC 188
1
2
1
3
1
1 2
2
%
100
83
67
50 33
L
SMC 116
1 3
2 4
N
%
100
87 75
4
1
63
3
2
1 2 3
50
37 25
L
1 3 5
2 4 6
N
5
1
3
HP
%
100
67
4
2
33
0
6
L
S 1 2
N
S21
S
TSMC 116
3
1
%
7
100
5
83
67
1 2 5 S
HP
4
6
2
50
8
33
0
L
S 3 4
N
2
S
5
1
4
S
3
S
T1534070_1 rev.3
0178-910-EN
85
Page 87

Totally unloaded start and capacity regulation

Futher to the standard equipment, as shown on the previous page, the compressor may feature an extra solenoid valve marked S. TSMC compressors, however, are invariably equipped with this S-valve.
pacity. The ’S’ solenoid valve may therefore be used only as follows:
S Where total unloading is required until the
motor has achieved max. torque.
The ’S’ solenoid valve makes total unloading of the compressor possible, i.e. 0% capacity over a shorter period during operation. How­ever, the ’S’ solenoid valve must never be involved in normal capacity regulation, as there is a risk of the compressor overheating if operated for some length of time at 0% ca-
Schematic drawings 2
SMC/HPC 104
%
100
50
0
N
L
SMC/HPC 106 SMC 186
%
100
67 33
0
N
L
SMC/HPC 108
%
100
75 50
25
0
N
L
1
S
S 1
S
2
1
S
1
2
1
1 2 3
S
S
3
2
Compressor seen from the shaft end
SMC 112
%
100
83
67
50
33
S
0
L
2
3
1
S 1 3
S 2 4
N
S Where a refrigeration plant is occasionally
subject to brief operating stops and com­pressor stop is not desirable. The com­pressor may then be allowed to run for a maximum of 5 minutes at 0% capacity.
The regulating sequence may be seen from the schematic drawings:
SMC 188
S
1
2
1
2
T1534070_2 rev.3
3
S
3
5
6
4
S
Relief cylinder
Oil return Oil pressure
S
1
4
2
100
%
75 50
25
0
L
S 1 2 3
N
SMC 116
%
100
3
87 75
63
50
S
37 25
0
L
S 1 3 5
2 4
6
S
N
86
0178-910-EN
Page 88

Service

It will normally not be necessary to service the solenoid valves, and it is therefore re­commended not to strip them down. Should it be considered necessary to replace the sole­noid valve, however, unscrew it from the block and replace by a new one. See the spare parts list.
Regulating sequence
The schematic outlines show that disconnec­tion of a cylinder pair is done by cutting off the current to the relevant magnetic coil. Dis­connection must be done by numerically as­cending sequence, while connection should be done by numerically descending se­quence.
The automatic gear which controls the sol­enoid valves must cut off or connect the cur-
rent to the number of solenoid valves needed to supply the compressor with the capacity required.
Note:
When starting a compressor this must be done at the lowest capacity stage and it should be allowed to run for a few minutes (e.g. 3 to 5 minutes) before its capacity is in­creased. This will prevent the oil in the com­pressor from heavy foaming and the refriger­ant from being sucked into the compressor from the evaporating system; something which can lead to liquid strokes. For the same reasons the compressor should al­ways, when a new stage has been loaded, be allowed to run for 3 to 5 minutes at this stage before the next higher capacity stage is loaded. Unloading of capacity on the com­pressor can usually take place more quickly.
Automatic capacity regulation
Where there is an automatic capacity regulat­ing facility, solenoid valve control can be ef­fected in the following ways:
- using pressure cut-outs
- using thermostats
- using microelectronics such as e.g. the UNISAB II.
Piston rod
Pos.
Dimensions
1)
S mm L mm Part no. 104 106 108 112 116 108 116
12-1 12-2
12-3 12-4 12-5 12-7
12-1 12-2
12-3 12-4 184 257 3135-022
21.5
46.5
71.5
96.5
24.5
49.5 49 94
139
75
100 125 150
82
107 122 167
212
Relief
Cylinder
3135-149 3135-150
3135-151 3135-152 3135-161 3135-154
3135-019 3135-020
3135-021
11122 1 1111
Relief cylinders
The relief cylinders vary in type, depending on the position they have on the compressor. The chart below shows the number and di­mensions of the relief cylinders for the indi­vidual compressor types.
Number in each compressor
SMC 100 TSMC 100
1
222 1 1
1
2
1
2
2
1
2
1
1
1
SMC 180
186 188
1 1
1
TSMC 180
1 1 1
1
188
1 1
1
1) See spare parts drawing at the end of this instruction manual
0178-910-EN
87
Page 89
Heating rods, pos. 30
In order to keep the lubricating oil in the com­pressor warm during a period of standstill, the oil reservoir has one or two heating rods built in. Before start-up, the heating rod (s) must have been activated for 6-8 hours in order to ensure that there is only a minimum of refrigerant in the oil. When containing much refrigerant, the oil will lose its lubricat­ing property and the following operational in­terruptions may occur:
In reciprocating compressors there is a serious danger of vigorous oil foaming when the compressor starts as a result of a falling suction pressure.
For screw compressors starting with much refrigerant dissolved in the oil, there is a risk of the compressor being stopped by the Flow Switch as the oil will be foaming owing to the fall in pressure through oil pipe and oil filter.
As illustrated on the drawing the heating rod consists of an electric heating element, incor­porated in a dia. 30 mm pipe. The entire hea­ting cartridge is screwed on tight at the
1
/4” thread.
G 1
Note:
The heating rod must not be energized if the oil level in the reservoir is below the minimum mark in the sight glass, and it should generally be switched off during compressor operation. Remember to turn off the heating rod whenever the crank­case of the reciprocating compressor is opened for inspection.
The following table indicates which heating rods are used for the various compressor types. In the spare parts lists for compressor or unit you will find the current part numbers.
0170-017-EN 98.05
50
30
Power
Watt
270 270 270
460 460 460
80
Heating rods
Voltage
V
250 230
115*
250 230
115*
NV 50
G 1 1/4”
L1
mm
L2
mm
158 175
Marking: Prod. nr.
Watt Volt Manu. date
Ø 30
L1 L2
Used for:
CMO - TCMO - SMC 100 - TSMC 100
HPO - HPC, SMC 180 - TSMC 180 VMY 347 /447 – 536 SAB 110 – 128 – 163 – 202 – 330
88
* Can be delivered with a UL approval. All heating rods are executed in Degree of Protection IP54.
0178-910-EN
Page 90

Stop valves pos. 23 and 42

23G
0171-463-EN 95.03
Fig. 1
Fig. 2
23A 23D
Danv
42A 42H
42G 42F 42E 42C
23F
23C 23B 23E
The compressor is fitted with stop valves pos. 23 for charging of oil and pos. 42 for draining of oil. They are service-free valves and should as a rule not be dismantled.
The valves are safeguarded against inadver­tent opening by means of a red cap.
The red cap can further be used for opening or closing the valve by unscrewing it and turning it upside down. The square hole in the top of the cap fits the square in the valve spindle.
The valves are equipped with a blank nut pos. 23G/42H that prevents dirt from pene-
42D
42B
T0177156_0
trating the valves whenever they are not used.
S If the valve is used as an oil charging
valve it is fitted with a nut pos. 23C and threaded nipple pos. 23B as shown by fig. 1.
S If the valve is used as a purge valve it is
fitted with a screwed connection as illus­trated by fig. 2.
The purge valve is fitted either directly on the top cover or by means of an intermedi­ate connection in the cast pressure chan­nels in the frame.
0178-910-EN
89
Page 91

Monitoring cylinder lining insertion

When reassembling the slide linings, it is im­portant to check the clearance volume as described in section 1 below.
When mounting new cylinder linings, both the clearance volume and the so called lift- ing reserve must be checked in the order mentioned and as described in sections 1 and 2. It is recommended that the cylinder linings be marked so that they can be reas­sembled in the same place as before.
1. Checking clearance volume
After each cylinder lining assembly, it is rec­ommended that the clearance volume be checked. Adjustment of the clearance volume is done by means of gasket pos. 19K which, in addi­tion to its sealing function, is also used as an adjusting element. Consequently, the gaskets come in two sizes and may sometimes be used at the same time under the same cylin­der lining.
Gasket
thickness
19K
0.5mm
0.8mm
HPC
SMC 100
part no.
2356-111
2356-233
SMC 180
part no.
2356-116
2356-249
no. 1 from the tools kit. Fit the locking devices diagonally as shown in fig. 1.
Fig. 1
S-L for SMC 100 type S
pos. 19K
E for SMC 100 type E
S Turn crankshaft until piston is in top posi-
tion.
S Using a depth or slide gauge, measure ”X”
as shown in fig. 2
Fig. 2
Cylinder lining
X
0171-467-EN 98.01
Adjustment is made as follows:
S The rocker arm system is lowered by fit-
ting the long plug no. 4 from the tools kit in the unloading cylinder pos. 12 instead of screw pos. 12D.
S Insert an 0.5mm gasket pos. 19K and
mount cylinder lining.
S Press cylinder lining against gasket pos.
19K by means of two locking devices –
90
Piston
T0177131_0 v6
S ”X” must lie between the below mentioned
limits and may, as mentioned earlier, be adjusted by the use of gasket pos. 19K.
0178-910-EN
Page 92
Clearance
volume
”X” HPC
SMC 100
Mk1, Mk 2, Mk 3
SMC 180
Mk1, Mk 2
min. max.
mm mm
0.6
0.9
1.0
1.5
The rocker arms must be in their vertical position i.e. with the short screw pos. 12D and gasket 12E fitted. The measured dis­tances ”Y1 and Y2” may not vary more than max. 0.25mm.
S Adjustment of the lifting reserve can now
be performed if necessary. See point 2.
2. Checking lifting reserve
When fitting a new cylinder, or if the com- pressor is to be changed from running on R717 to some other refrigerant, or vice versa, or in the event of any major overhaul to the compressor, the lifting reserve must be checked.
Note:
The lifting reserve must not be checked until the clearance volume has been ad­justed. Start by checking that the mutual height of the rocker arms is the same as described in the following:
Having removed the cylinder lining, mea­sure distance ”Y” from the contact face of the cylinder lining in the frame to the top of the two rocker arms which interact on ei­ther side of the cylinder lining. See fig. 3.
In case this difference is greater, a shim Pos. 15E must be placed under the lowest rocker arm bearing pos. 15B or a shim re­moved from the highest bearing. Normally, there is no shim or max. 2 shims under the rocker arm bearing.
Check lifting reserve:
S The lifting reserve of the rocker arm is im-
portant in order to make sure that the rocker arm in its upright position can keep the suction valve ring plate open while the cylinder is unloaded. However, it must not be possible for them to be so upright that there is a risk of their jamming, this mak­ing them unable to be lowered again when the cylinder is put into service. Per­form the adjustment as follows:
Fig. 3
0178-910-EN
Block
Y1
Rocker arms
Y2
T0177131_0 v4
S Position cylinder lining incl. the correct
gasket pos. 19K in the compressor block and press down against rocker arms by hand.
S The rocker arms are in their upright posi-
tion as the normal plug pos. 12D as well as gasket pos. 12E have been mounted in the unloading cylinder.
91
Page 93
Fig. 4
S The difference in the two measurements
of ”Z” must be within the limits stipulated in the following table.
Z
pos. 19K
T0177131_0 v5
S Measure distance ”Z” as shown in fig. 4.
Note down the ”Z” measure.
S Replace normal plug pos. 12D with the
long plug no. 4 from the tools kit, lowering rocker arms in the process.
S Press cylinder lining down against gasket
pos. 19K using the two locking devices no. 1 as shown in fig. 1, and repeat measure­ment ”Z”.
Lifting reserve
”Z”
HPC SMC 100
Mk 1, Mk 2, Mk 3
SMC 180
Mk 1, Mk 2
Min.
mm
0,6
0,8
Max.
mm
1,0
1,5
S If the difference between the two mea-
surements does not fall within the parame­ters stated, it must be regulated by insert­ing or removing shims pos. 15E under the rocker arm bearings.
S It is important that the long threaded plug
is fitted while the top cover is being mounted.
Note:
Remember to put the normal plug in once the top cover has been tightened.
92
0178-910-EN
Page 94

Pressure gauges

0170-161-EN 95.06
The analog instrumentation on the compres­sor includes two pressure gauges: one that measures the discharge pressure on the compressor and one combined suction and oil pressure gauge. These pressure gauges are filled with glycerine, which both attenu­ates the deflections of the indicators and lu­bricates the gauge works.
However, a fluctuating ambient temperature has an influence on the volume of the glycer­ine (warm glycerine takes up more space than cold glycerine), which can affect the measuring accuracy of the gauge. Furthermore, it is essential that no excess pressure can possibly occur in the gauge housing, as this involves a risk of explosion of the housing.
Both these considerations have been effec­tively solved in the gauges by a combination of internal temperature compensation and the so-called blow-out safety device which is fitted in the back plate of the pressure gauge housing.
Adjustment to other temperature ranges:
A balancing screw on the rear of the instru­ment is firmly tightened at a temperature of 20°C – the normal ambient temperature.
temperature under which the instrument will be functioning.
Example:
If the mid–compensation range is to be moved from 20°C to 10°C, equalization must be performed at 10°C. When the screw is then retightened, the middle of the com­pensation range will have been moved down to 10°C. The total stretch of the compensa­tion range remains unchanged.
The middle of the compensation range. Tighten the balancing screw at this temperature
10
°C
-10°C
°C
0
+10
°C
20
30
°C
°C
50°C
°C
60
°C
70
T0177086_0
Cleaning and refilling glycerine­filled gauges
S Remove blow-out disk and temperature
compensator from back of housing.
S Wash gauge interior with warm water and
allow to dry carefully.
S Fill gauge housing with fresh glycerine un-
til it flows out of bleeder hole.
If ambient temperatures change considerably thus requiring a general shift in the com­pensation range, slacken the balancing screw for approx. 1 minute, then retighten. This must be done at the average operating
0178-910-EN
Note:The glycerine must be absolutely wa-
terfree.
S Refit compensator and blow-out disk in
gauge housing and cover centrehole in blow-out disk with a piece of tape.
93
Page 95
Note:
Glycerine should be refilled at a room tem­perature of 20°C; when mounted, and the compensator must be its normal shape as shown at the top of the following drawing.
S Clean gauge exterior with warm water. S Remove tape from centrehole. S Refit gauge.
T0177086_0
Balancing screw
Compensator
Blow-out
+20
-10
+60
°C
°C
°C
94
0178-910-EN
Page 96
Undersize Bearing Diameters for Crankshaft Reciprocating Compressors with 4 to 8 Cylinders
B
A
B
A
C
0171-904-EN 96.05
Compressor
CMO 2
SMC/TSMC
SMC/TSMC
SMC/TSMC
type
HPO
HPC,
100 S
100 L
100 E
R=2.5
Main bearing
First
grinding
–0.060 –0.070
–0.070
79.5 –0.080
A
59.5
79.5
Super
finish
or
Final
grinding
–0.060 –0.090
–0.070 –0.090
=0.35
R
a
a
b
45°
c
R=d
B
Connecting rod bearing
First
grinding
–0.030
54.5 54.5 –0.049
0.000
79.5 –0.010
Super
finish
or
Final
grinding
–0.035 –0.050
=0,20Ra=0,20
R
a
0.000
79.5 –0.020
R
=0.35
a
R=2.5
3559.5
40
50
60
C
mm mm mm mm mmmmmm mm mm
0.0
–0.1
0.0
–0.1
0.0
–0.1
0.0
–0.1
T0177137_0
abcd
0.0
1.0
0.2
0.2
–0.3
1
2.5
3
2.5
3.5
SMC/TSMC
180
–0.110
134.0 –0.120
134.0
R
a
–0.110 –0.140
=0,63
0.000
134.0 –0.010
Undersize bearings: See SABROE spare parts list.
0178-910-EN
–0.015
134.0 70 –0.040
=0,63
R
a
0.0
–0.1
0.16
1.15
5
6
95
Page 97

Sundry clearances and check dimensions

Bearing clearance
CMO 1 CMO 2 SMC 65 CMP 1 TCMO1 CMO4 HPO HPC
Main bearings Connecting rod
bearings Piston pin
bearings
Parallel to piston pin
At right angles
PistonNewGround down
to piston pin
If the maximum value has been exceeded, replace the parts.
manufactured max.
manufactured max.
manufactured max.
manufactured max.
manufactured max.
0.08
0.20
0.08
0.15
0.04
0.10
0.18 –
0.11
0.30
TCMO 2 TSMC 65
0.08
0.20
0.08
0.15
0.04
0.10
0.18 –
0.11
0.30
0.08
0.20
0.08
0.15
0.04
0.10
0.18 –
0.11
0.30
All measurements stated are in mm
SMC 100 TSMC 100 4–10 cyl.
0.08
0.20
0.10
0.20
0.04
0.10
0.20 –
0.15
0.40
Crankshaft end-play
min. max.
The end–play can be adjusted by means of the gasket under the bearing cover. The gasket is available in the following thicknesses: 0.3, 0.5, 0.75 and 1.0 mm.
0.30 0.30 0.30 0.40 0.75 0.95
0.55 0.55 0.55 0.64 1.00 1.20
SMC 100 SMC180 TSMC 100 12–16 cyl.
0.08
0.20
0.10
0.20
0.04
0.10
0.20 –
0.15
0.40
TSMC 180 Mk1 & Mk2
0.14
0.35
0.14
0.30
0.09
0.20
0.25 –
0.35
0.90
0171-901-EN 91.04
Piston ring gap
min. max.
The piston ring gap must be measured with the ring placed in the cylinder liner.
0.25 0.25 0.25 0.33 0.33 0.66
1.00 1.00 1.00 1.30 1.30 2.50
Dimensions of crankshaft bearing journal
Main bearing journals
Connecting rod bearing journals
Intermediate journals
Main bearing journals
Connecting rod bearing journals
Intermediate journals
Bushing and bearing halves can be supplied for all above journals.
–0.06 –0.06 –0.06 –0.07 –0.07 –0.11
55
50
54.5
49.5
–0.09 –0.025
–0.040
–0.06 –0.09
–0.025 –0.040
60
–0.09 –0.09 –0.09 –0.09 –0.14
–0.030 0 0 0 –0.015
55
–0.049 –0.02 –0.02 –0.02 –0.040
–0.06 –0.06 –0.07 –0.07 –0.11
59.5 –0.09 –0.09 –0.09 –0.09 –0.14
–0.025 0 0 0 –0.015
54.5 54.5 79.5 79.5 134 –0.040 –0.02 –0.02 –0.02 –0.040
55 80 80 135
55 80 80 135
54.5 79.5 79.5 134
80
79.5
–0.010 –0.029
–0.010
.
–0.029
96
0178-910-EN
Page 98

Torque moments for screws and bolts

Metric thread (ISO 8.8)
M 4 5 6 810 121416 18202224 27
0171-465-EN 94.12
Kpm ft.lbf. Nm
0.28
2.1
2.7
0.53
3.9
5.2
0.94
6.8
9.2
2.2 16 22
4.1 30 40
7.0 50 69
11
80
108
15 110 147
23 170 225
30 220 295
38 270 375
52 370 510
Metric thread (ISO 12.9)
M 4 5 6 810 121416 18202224 27 Kpm ft.lbf. Nm
0.42
3.0
4.1
0.78
5.7
7.6
1.4 10 14
3.2 23 31
6.1 44 60
10 75 98
16 120 157
23 160 225
34 240 335
44 320 430
55 400 540
76 550 745
Connecting rods with UNF thread
HPO/CMO HPC/SMC 100 SMC 180
68 490 670
100 720 980
0178-910-EN
T0177082_0
UNF Kpm ft.lbf. Nm
5/16”
2.1 15 20
3/8”
4.4 32 43
5/8”
17 130 167
97
Page 99
Bolt on discharge valve
HPO/CMO HPC/SMC 100 SMC 180
AMR
NORMEX
Kpm ft.lbf. Nm
A
Compressor type
HPO/CMO/TCMO
104-108
HPC/ SMC/ TSMC
A
SAB
112-116
186-188 128 163 128
3.2 23 32
Coupling
type
AMR225 AMR312S
AMR350S
AMR450S
H148 H168
225
Thread
5/16” 7/16”
1/2”
11/16”
M8 M8
5/16”
10.2 75
101
Torque (A)
Kpm. ft.lbf. Nm
3.5
5.6
13
28
2.2
2.2
3.5
255 344
25 40
95
200
16 16 25
35
34 55
128
275
22 22 34
Series 52
A
VMY
163 202
depending on the motor size
262
Series 52
200
225
262
312
Series 52 NORMEX
350
375
425
450
3/8” 7/16”
5/16”
5/16”
3/8”
7/16”
1/2”
9/16”
5/8”
11/16”
4.2
3.5
3.5
4.2
5.6
13
18
25
28
30
25
25
30
40
95
130
175
200
41
55405.6312
34
34
41
55
128
177
245
275
98
0178-910-EN
Page 100

Refrigeration Plant Maintenance

0171-464-EN 94.05

Operational reliability

The prime causes of operating malfunctions to the plant are:
1. Incorrect control of liquid supply to the evaporator.
2. Moisture in the plant.
3. Air in the plant.
4. Anti-freezing liquid is missing.
5. Congestion due to metal shavings and dirt.
6. Congestion due to iron oxides.
7. Congestion due to copper oxides.
8. Inadequate refrigerant charge.
Below, some information is given about ways of keeping contaminants out of the refrigera­ting system and at the same time facilitating day-to-day supervision of the refrigeration plant.

Pumping down the refrigeration plant

Before dismantling any parts of the refrigera­tion plant for inspection or repair, pump-down must be carried out.
1. Open suction and discharge stop valves on compressor.
bled of refrigerant. Adjust any constant­pressure valves to bring evaporator pres­sure down to atmospheric.
3. Start up the compressor. Adjust regulat­ing system to lower suction pressure.
4. Keep a close eye on the suction pres- sure gauge! When the suction pressure is equal to atmospheric, stop the compres­sor and quickly shut off the discharge stop valve. Shut off any stop valve in the oil re­turn line.
If the receiver has an extra stop valve in the feed line, this can be closed; practical­ly the entire refrigerant charge will then remain shut off in the receiver.
Note:
The receiver must not be overfilled! There should be a minimum gas volume of 5%.
5. A slight overpressure should normally re­main in the piping system - this safe­guards the system against the penetration of air and moisture.
6. Before dismantling parts, the operator
should put a gas mask on.
Dismantling plant
In order to prevent moisture penetrating into the refrigeration plant during any repair work, it is advisable to follow the rules below:
2. Close liquid stop valve after condenser or receiver so that liquid refrigerant can be collected in the tank. Any solenoid valves in the liquid line should be opened by force, adjusting the thermostat to its low­est position so that the liquid line can be
0178-910-EN
1. No component should be opened un­necessarily.
2. When dismantling the system, the pres­sure in the system should be a little higher than atmospheric.
99
Loading...