IMPROPER INSTALLATION MAY CREATE A
CONDITION WHERE THE OPERATION OF THE
PRODUCT COULD CAUSE PERSONAL INJURY
OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE INJURY OR PROPERTY DAMAGE.
REFER TO THIS MANUAL FOR ASSISTANCE
OR ADDITIONAL INFORMATION, CONSULT A
QUALIFIED INST ALLER, SER VICE AGENCY OR
THE GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED IN
STRICT COMPLIANCE WITH THE ENCLOSED
INSTALLATION INSTRUCTIONS AND ANY
APPLICABLE LOCAL, STATE, AND NATIONAL
CODES INCLUDING BUT NOT LIMITED TO,
BUILDING, ELECTRICAL AND MECHANICAL
CODES.
This Category IV, dual certified, direct vent and 1-pipe vent
furnace is designed for residential or commercial installation
in a basement, closet, recreation room, garage or other location provided space temperature is 32°F or higher. For applications in below freezing locations, refer to “BELOW
FREEZING LOCATIONS” section on page 5.
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should
be made in writing. Also, before installation the unit should be
checked for screws or bolts which may have loosened in transit. There are no shipping or spacer brackets which need to
be removed.
NOTES, CAUTIONS & WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION and WARNING. NOTES are intended to
clarify or make the installation easier. CAUTIONS are given
to prevent equipment damage. WARNINGS are given to alert
the installer that personal injury and/or equipment or property
damage may occur if installation procedures are not handled
properly.
The furnace area must not be used as a broom
closet or for any other storage purposes, as a fire
hazard bay be created. Never store items such as
The cooling coil must be installed in the supply air
duct, downstream of the furnace. Cooled air may
not be passed over the heat exchanger.
the following on, near or in contact with the furnace.
VENT SAFETY CHECK PROCEDURE
1.Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners or other cleaning tools.
2.Soap powders, bleaches, waxes or other cleaning
compounds; plastic items or containers; gasoline,
kerosene, cigarette lighter fluid, dry cleaning fluids
or other volatile fluid.
3.Paint thinners and other painting compounds.
This furnace may not be common vented with any
other appliance, since it requires separate, properly-sized air intake and vent lines. The furnace
shall not be connected to any type of B, BW or L
4.Paper bags, boxes or other paper products
Never operate the furnace with the blower door
vent or vent connector, and not connected to any
portion of a factory-built or masonry chimney.
removed. To do so could result in serious personal
injury and/or equipment damage.
Unitary Products Group3
If this furnace is replacing a common-vented furnace, it may
be necessary to resize the existing vent line and chimney to
Page 4
650.75-N4U035-14370-000
prevent oversizing problems for the new combination of units.
Refer to the National Gas Code (ANSI Z223.1) or CAN/CGA
B149.1 or.2 Installation Code (latest editions).
The following steps shall be followed with each appliance
connected to the venting system placed in operation, while
any other appliances connected to the venting system are not
in operation:
1.Seal any unused openings in the venting system.
2.Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223.1, or the CAN/CGA B149 Installation Codes and
these instructions. Determine that there is no blockage
or restriction, leakage, corrosion or other deficiencies
which could cause an unsafe condition.
3.Insofar as is practical, close all building doors and windows and all doors between the space in which the appliance(s) is located and other spaces of the building. Turn
on clothes dryers. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
4.Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so the
appliance shall operate continuously.
5.Test for draft hood equipped appliance spillage at the
draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle.
Downflow/horizontal models are AGA/CGA listed for downflow application into a manufactured (mobile) home.
Upflow models or horizontal applications are not approved for
mobile homes.
A manufactured (mobile) home installation must conform with
the Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280, or when this standard is not applicable, the Standard for Manufactured Home Installations (Manufactured Home Sites, Communities and Set-Ups), ANSI
A225.1, and/or CAN/CSA-Z240 MH Series, Mobile Homes.
CLEARANCES FOR ACCESS
Ample clearances should be provided to permit easy access
to the unit. The following minimum clearances are recommended:
1.Twenty-four (24) inches between the front of the furnace
and an adjacent wall or another appliance, when access
is required for servicing and cleaning.
2.Eighteen (18) inches at the side where access is
required for passage to the front when servicing or for
inspection or replacement of flue/vent connections.
:
NOTE
In all cases, accessibility clearances shall take precedence over clearances for combustible materials where
accessibility clearances are greater.
6.After it has been determined that each appliance connected to the venting system properly vents when tested
as outlined above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning appliance
to their previous conditions of use.
7.If improper venting is observed during any of the above
tests, the venting system must be corrected.
8.Any corrections to the common venting system must be
in accordance with the National Fuel Gas Code Z223.1
or CAN/CGA B149.1 or.2 Installation Code (latest editions). If the common vent system must be resized, it
should be resized to approach the minimum size as
determined using the appropriate tables in Appendix G
of the above codes.
SPECIFIC UNIT INFORMATION
LIMITATIONS & LOCATION
This furnace should be installed in accordance with all
national and local building/safety codes and requirements, or
in the absence of local codes, with the National Fuel Gas
Code ANSI Z223.1 or CAN/CGA B149.1 or.2 Installation
Code (latest editions), local plumbing or waste water codes,
and other applicable codes.
Do not install the furnace in an unconditioned
space or garage that could experience ambient
temperatures of 32F (0C) or lower. For application
in below freezing locations, See “BELOW FREEZING LOCATIONS” on page 5
The furnace is not to be used for temporary heating of buildings or structures under construction.
This unit must be installed in a level (1/4”) position
side-to-side and front-to-back to provide proper
condensate drainage.
Do not allow return air temperature to be below
55°F for extended periods. To do so may cause
condensation to occur in the main fired heat
exchanger.
4Unitary Products Group
Page 5
035-14370-000650.75-N4U
vent chilled air from entering the furnace, and if manually
operated, must be equipped with means to prevent operation
of either unit unless the damper is in the full heat or cool position.
Furnaces shall not be installed directly on carpeting, tile or other combustible material other than
The furnace shall be located:
wood flooring. An accessory combustible floor
base is available to allow direct installation of
downflow models on combustible flooring.
1.Where a minimum amount of air intake/vent pipin
elbows will be required.
g and
Furnace shall be installed so the electrical components are protected from water.
The size of the unit should be based on an acceptable heat
loss calculation for the structure.
Check the rating plate to make certain the unit is equipped for
the type of gas supplied, and proper electrical characteristics
are available.
For installations above 2,000 feet, reduce input 4% for each
1,000 feet above sea level. Refer to Form 650.75-N2.1V for
correct pressure switch/orifice or other required conversion
information.
A furnace installed in a residential
that all burners and burner ignition devices are located not
less that 18" above the garage floor, and located or protected
to prevent damage by vehicles.
Allow clearances from combustible materials as listed under
Clearances to Combustibles, ensuring that service access is
allowed for both the burners and blower.
When the furnace is used in conjunction with a cooling coil,
the furnace must be installed parallel with or on the upstream
side of the cooling unit to avoid condensation in the primary
heat exchanger.
When a parallel flow arrangement is used, the dampers or
other means used to control air flow shall be adequate to pre-
garage shall be located so
2.As centralized with the air distribution as possible.
3.In an area where ventilation facilities provide for safe limits of ambient temperature under normal operating conditions. Ambient temperatures must not fall below 32°F
(0°C).
4.Where it will not interfere with proper air circulation in the
confined space.
5.Where the outdoor combustion air/vent terminal will not
be blocked or restricted.
6.Where it will not interfere with the cleanin
removal of other appliances.
g, servicing or
CLEARANCES TO COMBUSTIBLES
Minimum clearances from combustible construction are
shown in Table 3, “UNIT CLEARANCES TO COMBUSTIBLES,” on page 8.
BELOW FREEZING LOCATIONS
If this furnace is installed in any area where the ambient temperature may drop below 32° F, a UL listed self regulated
heat tape must be installed. It is recommended that self regulating heat tape rated at 3 watts per foot be used. This must
be installed around the condensate drain lines in the unconditioned space. Always install the heat tape per the manufacturer's instructions. Cover the self-regulating heat tape with
fiberglass or other heat resistant, insulating material.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition).
For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V.
Wire size based on copper conductors, 60°C, 3% voltage drop.
Continuous return air temperature must not be below 55°F.
-
2
MIN
SIZE (AWG
@ 75
ONE WAY
WIRE
)
FT
.
2
6Unitary Products Group
Page 7
035-14370-000650.75-N4U
T
B
3/4
C ondensate
D rain A ccess
3-1/4 X 3
45
Air Intake
3-5/8 x 3-5/8
C onn. S ize/
(
G
Pipe S ize)
A
FRO N TLEFT SIDE
B
Power
20
Wiring
7/8" K .O .
1-7/8
E
OP IMAGE/RETURN END
D
FRO N T
Vent C onnection
(v e n t s iz e )
5-3/8
F
1-3/8
3 7/8
BOTTOM IM AG E/SU PPLY END
ALL DIMENSIONS ARE IN INCHES, AND ARE APPROXIMATE.
H
19-1/4
G A S IN L E T
A
C
FRO N T
1-3/8
8
D
20
T'STAT W IR ING
7/8" K .O .
1 -3 /4
5-1/4
3-3/4
G A S IN L E T
1-1/4" X 2-1/2"
2 -3 /4
(V ent C onnection)
35
18-1/2
16-3/4
1-1/4
7 -1 /2
6 -1 /4
4 -1 /8
3-3/4
C ondensate
D rain A ccess
3-1/4 X 3
6-1/2
Air Intake
3-5/8 x 3-5/8
C onn. S ize/
(
G
Pipe Size)
1-1/4
ALT. G AS IN LET
1-1/4" X 2-1/2"
2 8 -1 /2
RIGHT SIDE
MODELS P*DH/
FG9-DH/G9TDH
40 /37 / 800 / A 14-1/213-1/411-3/425-1/82-1/22
60 /55 / 1200 / B 17-1/216-1/414-3/426-5/82-1/42
80 /75 / 1200 / B 17-1/216-1/414-3/426-5/82-1/42
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition).
For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V.
Wire size based on copper conductors, 60°C, 3% voltage drop.
Continuous return air temperature must not be below 55°F.
Special floor base or air conditioning coil required for use on combustible floor.
2.
Minimum of 8” clearance required to install condensate removal system.
3.
Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the
furnace jacket and building joists, studs or framing.
LEFT
SIDE
UPFLOW MODELS (P*UR / FG9-UP / G9T-UP)
RIGHT
SIDE
FLUE
FLOOR/
BOTTOM
1
1"
COMBUSTIBLE
CLOSETALCOVEATTIC
YESYESYESNO
2
NOYESYES
When the furnace is used in conjunction with a cooling coil,
the furnace must be installed parallel with, or on the upstream
side of the cooling unit to avoid condensation in the primary
heat exchanger.
If this unit is installed in an unconditioned space
and an extended power failure occurs, there will
be potential damage to the condensate trap, drain
lines and internal unit components. Following a
power failure situation,
Do Not Operate the Unit
Until Inspection and Repair Are Performed.
When a parallel flow arrangement is used, the dampers or
other means used to control air flow must be adequate to prevent chilled air from entering the furnace, and if manually
operated, must be equipped with means to prevent operating
of either unit unless the damper is in the full heat or cool position.
LINE
CONTACT
YES
3
DUCTWORK
The duct system's design and installation must:
1.Handle an air volume appropriate for the served space
and within the operating parameters of the furnace specifications.
2.Be installed in accordance with standards of NFPA
(National Fire Protection Association) as outlined in
NFPA pamphlets 90A and 90B (latest editions) or applicable national, provincial, local fire and safety codes.
3.Create a closed duct system. The supply duct system
must be connected to the furnace outlet and the return
duct system must be connected to the furnace inlet. Both
supply and return duct systems must terminate outside
the space containing the furnace.
4.Generally complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and to and from the conditioned space.
UPFLOW MODELS
SUPPLY PLENUM CONNECTION
Attach the supply plenum to the furnace outlet duct connection flanges.
This is typically through the use of S
cleat material when a metal plenum is
used. The use of an approved flexible
duct connector is recommended on all
installations. This connection should be
sealed to prevent air leakage.
If a matching cooling coil is used, it
may be placed directly on the furnace
outlet and sealed to prevent leakage.
Follow the coil instructions for installing
the supply plenum.
On all installations without a coil, a removable access panel
is recommended in the outlet duct such that smoke or
reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This
access cover shall be attached in such a manner as to prevent leaks.
The cooling coil must be installed in the supply air
duct downstream of the furnace.
8Unitary Products Group
Page 9
035-14370-000650.75-N4U
g
g
g
g
g
g
g
g
g
g
F
RETURN DUCT CONNECTION
Return air may enter the furnace through the side(s) or bottom depending on the type of application.
not be connected into the rear panel of the unit.
Return air may
See the
specific type application installation for details. Be sure to see
the Filters section of this instruction.
CLIPS
POSITION WIRE RETAINER
(PROVIDED) UNDER FLANGE
FILTER
(PROVIDED
UPFLOW FILTER INSTALLATION
All applications require the use of a filter. A high velocity filter
and retainer are provided for field installation.
Internal Installation
1.Select desired filter position (left/ri
Remove the correspondin
cabinet cut-outs per instruc-
ht side, or bottom).
tions provided.
2.Install snap-in retainer clips into the correspondin
from the outside rear of the cabinet (Refer to Fi
To prevent cabinet air leaks, install snap-in plu
slots
ure 3.)
s (provided) into the unused slots at the outside rear of the
cabinet.
FURNACE
(REAR CABINET)
LEFT
RIGHT
SIDE
SLOTS
BOTTOM SLOTS
CABINET
SLOT
FILTER SUPPORT
CLIPS (PROVIDED)
SIDE
SLOTS
PLUG UNUSED
CABINET SLOTS
WITH PLUGS
(PROVIDED)
RIGHT SIDE
INSTALLATION
SHOWN
FURNACE
FRONT
FIGURE 4 : SIDE FILTER RETAINER PLACEMENT
5.Position the filter between the wire retainer and the cabinet wall (or floor) so it completely covers the cabinet air
opening and secure the filter in place at the front of the
cabinet by fastening the closed (looped) end of the
retainer wire under the flanged edge of the cabinet.
When properly installed the filter should fit flush with all
four sides of the cabinet wall.
NOTE:
Air velocity through throw-away type filters may not
exceed 300 feet per minute. All velocities over this require the
use of high velocity filters.
Side Return - External Filter
Locate and knock out the square corner locators. These indicate the size of the cutout to be made in the furnace side
panel (Refer to Figure 5).
FIGURE 3 : FURNACE FILTER SLOT LOCATIONS
3.Install the wire retainer inside the cabinet. Insert the
open ends of the wire retainer into the clip loops at the
rear of the blower compartment. The retainer wire should
pivot freely like a hin
cabinet. (Refer to Fi
4.Install the filter(s) provided. Cut filter if necessary to
match air openin
beyond openin
from bypassin
from inside the filter. Shorten the rods, if necessary, to
match final filter size.
Unitary Products Group9
e, on the clips at the rear of the
ure 4.)
in cabinet. Filter should extend
edge as much as possible to prevent air
the filter. DO NOT remove stiffening rods
FR O N T O
FU RN A CE
CORNER
MARKINGS
FIGURE 5 : SIDE RETURN CUTOUT MARKINGS
Install the side filter rack following the instructions provided
with that accessory. If a filter(s) is provided at another location in the return air system, the ductwork may be directly
attached to the furnace side panel.
Page 10
650.75-N4U035-14370-000
NOTE:
Some accessories such as electronic air cleaners and
pleated media may require a larger side opening.
DOWNFLOW/HORIZONTAL MODELSDOWNFLOW APPLICATION
DOWNFLOW FILTERS
A top return filter rack is supplied with
All installations must have a filter installed.
The return duct may be attached to the furnace by S-cleat,
bend tabs or other approved methods. Be sure to seal the
duct to the furnace to prevent air leakage.
Those applications over 1800 CFM require either return from
two sides, one side and the bottom, or bottom only. For bottom only application, see data and notes on blower performance data tables in this manual.
Where the return duct system is not complete, the return connection must run full size to a location outside the utility room
or basement. For further details, consult Section 5.3 (Air for
Combustion and Ventilation) of the National Fuel Gas Code,
ANSI Z223.1, or CAN/CGA B149.1 or.2, Installation Code latest editions.
Bottom Return
Bottom return applications normally pull return air throu
gh a
base platform or return air plenum. Be sure the return platform structure is suitable to support the weight of the furnace.
Be sure to seal the furnace to plenum connection to prevent
air leakage. (Refer to Figure 3 on page 9) and (Refer to
Table 1 on page 6).
The bottom panel is equipped with a perforated opening for
easy removal. Tabs must be cut with sheet metal snips to
allow removing knock-out. Scribe marks are included for
forming flanges for attachment of the return air ductwork.
NOTE:
If an external mounted filter rack is being used, see
the instructions provided with that accessory for proper hole
cut size.
Upflow attic installations must meet all minimum clearances
to combustibles and have floor support with required service
accessibility.
A
DUCTW ORK
FIGURE 6 : DOWNFLOW FILTERS
the furnace. Two 14" x 20" permanent
washable filters are supplied with each
unit.
Downflow furnaces typically are
installed with the filters located above
the furnace, extending into the return
air duct.
Any branch duct must attach to the vertical ductwork above the filter height
(FH) and for proper installation refer to
Figure 6.
F IL T E R R A C K
(FACTO RY SU PPLIED )
R A C K A N D F IL T E R S S E C U R E D
A
NOTE: FILTER ACCESS THRU DUCTW O RK M UST BE PRO VIDED FOR
REMOVAL AND CLEANING
C R O S S S E C T IO N A -A
(W ITH PLENU M AND FILTERS)
IN SIDE BLO W ER SECTIO N
FO R S HIPM EN T
C A S IN G S IZ E D IM E N S IO N F H
1 4 -1 /2 " 1 3 -1 /4 "
1 7 -1 /2 " 1 2 -1 /2 "
2 1 " 1 1 - 1 /2 "
2 4 -1 /2 " 9 -3 /4 "
FILTER S
FILTER
RACK
BRANCH
DUCTS
FH
10Unitary Products Group
The filter rack (provided) should be secured to the center of
the front and rear flanges at the furnace top. Drill a hole
through the front and rear duct flange into the filter rack and
secure it with a sheet metal screw.
Refer to the unit rating plate for furnace model then see the
dimensions page of this instruction for return air plenum
dimensions. Install the plenum following instructions under
Ductwork in this instruction.
Page 11
035-14370-000650.75-N4U
VENT (MAINTAIN
REQUIRED CLEARANCES
TO COMBUSTIBLES)
GAS PIPING
SEDIMENT TRAP
12"
30" MIN
WORK AREA
SHEET METAL
IN FRONT OF FURNACE
COMBUSTION
AIR OPENINGS IS
RECOMMENDED
RETURN AIR
SUPPLY AIR
LINE CONTACT ONLY PERMISSIBLE
BETWEEN LINES FORMED BY THE
INTERSECTION OF FURNACE TOP
AND TWO SIDES AND BUILDING
JOISTS, STUDS OR FRAMING
Installations on combustible material or floors must use a
combustible floor base (shown in Figure 7 - 1CB0314, 17, 21
& 24) as specified on the rating plate or a matching cooling
coil. Follow the instructions supplied with the combustible
floor base accessory.
This base can be replaced with a matching cooling coil, properly sealed to prevent leaks. Follow the cooling coil instructions for installing the plenum.
Downflow furnaces may be installed horizontally with the supply airflow toward the left or right by laying the unit on the left
or right side panel.
Do not install the unit on the rear panel.
After determining the best orientation, lay the unit on top of
the shipping carton to protect the finish. The appropriate electrical knock-outs for power wiring, control wiring and gas piping should be removed at this time.
For horizontal application, return air may enter through the
end only.
Return air may not be connected into the rear
panel of the unit.
HORIZONTAL FILTERS
All filters and mounting provision must be field supplied. Filters(s) may be located in the duct system external to the furnace or in a return filter grille(s).
ATTIC INSTALLATION
All downflow application supply duct systems must be
designed and installed in accordance with the standards of
NFPA 90A and 90B, and/or all local codes.
Unitary Products Group11
FIGURE 8 : TYPICAL ATTIC INSTALLATION
Page 12
650.75-N4U035-14370-000
g
This appliance is design certified for line contact for furnaces
installed horizontally. The intersection of the furnace top and
sides form a line. This line may be in contact with combustible
material. Refer to “Where it will not interfere with the cleanin
servicing or removal of other appliances." Section on page 5
in this manual for additional information.
Secure a platform constructed of plywood or other building
material to the floor joists. Sheet metal, 12" in front of the furnace combustion air openings is recommended. (Refer to
Figure 9.)
Note:
The unit must be elevated to allow clearnace fo the
condensate trap and drain pipe
. .
If this furnace is installed over a finished space, a
condensate safety pan must be installed.
adequate height to ensure the unit will not be subject to water
damage.
,
When suspending the furnace from rafters or floor joists
using rod, pipe or straps, refer to Physical Data and,Table 3,
“UNIT CLEARANCES TO COMBUSTIBLES,” on page 8, for
furnace weights to determine suitable means of suspension.
Angle supports should be placed at the supply aire end and
near the blower deck. (Refer to Figure 9.)
Do not support
at return air end of unit.
Units may also be suspended by using straps or other material at the same location. All four suspension points must be
level to ensure quiet furnace operation.
In any application where temperatures below
freezing are possible, See “BELOW FREEZING
LOCATIONS” on page 5
GAS PIPING
When a furnace is installed in an attic or other
insulated space, keep all insulating materials at
least 12" away from furnace and burner combustion air openings.
NOTE:
See crawl space installation for suspending the furnace in attic installations.
ANGLE IRON
BRACKET
1" MAX BETWEEN
ROD & FURNACE
6" MIN BETWEEN
ROD & FURNACE
SUPPORT
ROD
1" MAX BETWEEN
ROD & FURNACE
FIGURE 9 : TYPICAL FURNACE INSTALLATION
USING SUSPENSION MATERIALS
CRAWL SPACE INSTALLATION
The furnace can be hung from floor hoists or installed on suitable blocks or pad. Blocks or pad installations shall provide
The gas supply must be installed in accordance with the current National Fuel Gas Code, ANSI Z223.1 (in the U.S.) or
CAN-B149.1 or.2 (in Canada) installation codes and all applicable local and utility requirements. All pipe and fitting material, pipe size and installation procedures must comply with
the appropriate code. Some utilities may require larger pipe
sizes than shown in the code. Gas piping may be connected
from either side of the furnace. Each side of the unit has two
gas pipe entry knockouts.
For downflow/horizontal models,
piping before determining the correct gas pipe entry
plan your combustion air
. Use 90
degree service elbow(s), or short nipples and conventional 90
degree elbow(s) to enter through the cabinet access holes..
An overpressure protection device, such as a
pressure regulator, which conforms to the National
Fuel Gas Code, ANSI Z223.1 (U.S.) or CANB149.1 or.2 (Canada) and acts to limit the downstream pressure to a value that does not exceed
0.5 PSI (14" w.c.), must be installed in the gas piping system upstream of the furnace. Failure to do
so may result in a fire or explosion or cause damage to the furnace or some of its components.
12Unitary Products Group
Page 13
035-14370-000650.75-N4U
g
G
NOTE
An accessible manual shutoff valve must be installed
:
upstream of the furnace gas controls and within 6 feet of the
furnace.
The installation of a ground joint union and drip leg are
required. (Refer to Figure 10.) Maximum and minimum supply gas pressures are shown below.
INLET GAS PRESSURE RANGE
Natural GasPropane (LP)
Minimum4.5 In. W.C.11 In. W.C.
Maximum13.8 In. W. C.13.8 In. W.C.
EXTERNAL M ANUAL
SH U TOFF VALVE
TO G AS
SUPPLY
DROP LEG
GROUND JOINT UNION
M AY BE IN S TALLE D
IN S ID E O R O U T S ID E U N IT
GAS VALVE
TO G AS
SUPPLY
DROP LE
FIGURE 10 : GAS PIPING
NOTE
A 1/8” NPT plug is included in the inlet side of the gas
:
valve for measuring incoming gas pressure.
The furnace must be isolated from the gas supply piping system by closing its individual external manual shutoff valve
during any pressure testing of the gas supply piping system
at pressures equal to or less than 1/2 psig (3.48 kPa).
Compounds used on threaded joints of gas piping
must be resistant to the action of liquefied petroleum gases. After connections are made, leak-test
all pipe connections.
After all gas piping connections are completed,
leak test all joints, fittings and furnace connections
with rich soap and water solution, commercially
available bubble type leak detection fluid, or other
approved means.
Do not use an open flame or other source of ignition for leak testing.
ELECTRICAL POWER CONNECTION
Field wiring to the unit must conform to and be grounded in
accordance with the provisions of the National Electrical
Code ANSI/NFPA No. 70-latest edition, Canadian Electric
Code C22.1 Part 1 - (latest edition) and/or local codes. Electric wires which are field installed shall conform with the temperature limitation for 63°F/35°C rise wire when installed in
accordance with instructions. Specific electrical data is given
for the furnace on its rating plate and inRefer to Table 1 on
page 6.
Provide a power supply separate from all other circuits. Install
overcurrent protection and disconnect switch per local/
national electrical codes. The switch should be close to the
unit for convenience in servicing. With the disconnect switch
in the OFF position, check all wiring against the unit wiring
label. Also, see the wiring diagram in this instruction.
NOTE
The furnace’s control system depends on correct
:
polarity of the power supply and a proper ground connection.
“FURNACE CONTROL DIAGNOSTICS" Section on pa
for symptoms of reversed power supply polarity.
e37
The furnace and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2
psig (3.48 kPa).
Never apply a pipe wrench to the body of the combination automatic gas valve. A wrench must be
placed on the projection or wrench boss of the
valve when installing piping to it.
Unitary Products Group13
Use copper conductors only.
Connect the power supply as shown on the unit wiring label
on the inside of the blower compartment door and Figures 11
& 12. The black furnace lead must be connected to the L1
(hot) wire from the power supply. The white furnace lead
must be connected to neutral. Also, the green equipment
ground wire must be connected to the power supply ground.
Remove the screws retaining the wiring box cover. Route the
power wiring through the unit top panel with a conduit con-
Page 14
650.75-N4U035-14370-000
nector or other proper connection. Make wiring connections,
(Refer to Figure 11.) Replace the wiring box cover and
screws.
L1
(HOT)
N
BLK
GRD
WHI
GRN
WIRING INSIDE
JUNCTION BOX
: BLK/BLK
WHI/WHI
GRN/GRN
JUNCTION
BOX
BURNER COMPARTMENT
DOOR SWITCH
TRANSFORMER
IGNITION MODULE
G
R
W
C
Y
Y
HUM
EAC
XFMR
LINE
CIR
HUM
EAC
XFMR
LINE
PARK
PARK
HEAT
COOL
CLASS 2 SYSTEM
CONTROL WIRING
TO THERMOSTAT
L1
(HOT)
JUNCTION
BOX
N
GRD
WHI
BLK
GRN
WIRING INSIDE
JUNCTION BOX
: BLK/BLK
WHI/WHI
GRN/GRN
BLOWER COMPARTMENT
VENT PIPE
C
O
O
L
H
E
A
T
P
A
R
K
P
A
R
K
L
I
N
E
X
F
M
IGNITION MODULE
R
E
A
C
H
U
M
C
I
R
L
I
N
E
X
F
M
R
E
A
C
H
U
M
Y
Y
C
R
W
G
CLASS 2 SYSTEM
CONTROL WIRING
TO THERMOSTAT
FLUE CHASE
TRANSFORMER
DOOR
SWITCH
BURNER COMPARTMENT
FIGURE 12 : DOWNFLOW / HORIZONTAL MODELS
(P*DH / FG9-DH / G9T-DH) ELECTRICAL WIRING
BLOWER COMPARTMENT
FIGURE 11 : UPFLOW MODELS (P*UR / FG9-UP /
G9T-UP) ELECTRICAL WIRING
An alternate wiring method is to use a field provided 2 x 4 box
and cover on the outside of the furnace. Route the furnace
leads into the box using a protective bushing where the wires
pass through the furnace panel.
NOTE:
The power connection leads and wiring box on upflow
units may be relocated to the left side of the furnace. Remove
the screws and cut wire tie holding excess wiring. Reposition
on the left side of the furnace and fasten using holes provided.
ELECTRICAL CONTROL CONNECTIONS
Install the field-supplied thermostat. The thermostat instructions for wiring are packed with the thermostat. With the thermostat set in the OFF position and the main electrical source
disconnected, complete the low-voltage wiring from the thermostat to the terminal board on the ignition module. Connect
Class 2 control wiring as shown in Figures 13 & 14. Electronic
thermostats may require a common connection as shown
dashed in Figure 14.
Set the heat anticipator in the room thermostat to
.45 amps. Setting it lower will cause short cycles.
Setting it higher will cause the room temperature to
exceed the setpoints
FIGURE 13 : POWER WIRING CONNECTIONS
ROOM
THERMOSTAT
R
W
G
Y
C
FURNACE
CONTROL
R
W
G
Y
C
CONDENSING
UNIT
TO AIR CONDITIONER
CONTROLS
FIGURE 14 : TYPICAL HEATING AND COOLING
14Unitary Products Group
Page 15
035-14370-000650.75-N4U
g
g
g
g
R
NOTE.
Some electronic thermostats do not have adjustable
heat anticipators. They may have other type cycle rate
vent connection (top right of unit) back to the outdoors. Refer
to Figure 15 and Figure 16.
adjustments. Follow the thermostat manufacturer's instructions.
The 24-volt, 40 VA transformer is sized for the furnace components only , and should not be connected to power auxiliary
devices such as humidifiers, air cleaners, etc. The transformer may provide power for an air conditioning unit contactor.
COMBUSTION AIR AND VENT SYSTEM
This furnace is certified to be installed with one of
three possible intake/vent configurations.
1.Two-pipe with a sealed combustion intake/vent system
outdoor combustion air.
usin
2.Sin
3.Two-pipe intake/vent system usin
Be sure to follow the appropriate venting section details,
related information and limitations for your type of installation.
le pipe vent system using combustion air from the
area surroundin
the furnace.
combustion air from a
ventilated attic space and a vent pipe to the outside.
CONNECTS TO COLLAR
O N T O P O F B U R N E R B O X
VENT PIPE
IN T O S O C K E T J U S T
UND ER TO P PAN EL
O FF
O N
M
P
C
132
CEMENTS
FIGURE 15 : UPFLOW A IR INTAKE/VENT LOCATIONS
(MODELS P*UR / FG9-UP /G9T-UP)
VENT PIPE PASSES
THRO UG H TOP PANEL
COOL
HEAT
PARK
PARK
LINE
XFMR
EAC
HUM
CIR
LINE
XFMR
EAC
HUM
YWRG
C
1.
Vent must be increased to 3" on this model.
Note 1: Any vent pipe size change must be made out-
side furnace casing in a vertical pipe section
to allow proper drainage of condensate.
Note 2: An offset using two 45 degree elbows will be
required for plenum clearance when the vent
is increased to 3”.
METHOD ONE: TWO PIPE SEALED COMBUSTION
AIR & VENT SYSTEM
COMBUSTION AIR INTAKE/VENT CONNECTIONS
This type installation requires outdoor combustion air. Two
separate, properly-sized pipes must be used. One bringing
air from the outdoors to the furnace combustion air intake collar on the burner box, and a second pipe from the furnace
OPTIONAL
L E F T S ID E
COM BUSTION AIR
PIPE RO UTING
COM BUSTION AIR PIPE
CONNECTS TO CO LLAR
ON BOTTOM OF BURNE
BOX
The intake/vent should be located either through the wall
(horizontal or side vent) or through the roof (vertical vent).
Care should be taken to locate side vented systems where
trees or shrubs will not block or restrict supply air from entering or combustion products from leaving the terminal.
Also, the terminal assembly should be located as far as possible from a swimming pool or a location where swimming
pool chemicals might be stored. Be sure the terminal assembly follows the outdoor clearances listed in Table 3 for U.S.
installations: In Canada, refer to CAN/CGA-B149.1 or.2
Unitary Products Group15
Page 16
650.75-N4U035-14370-000
Installation Code (latest edition-Venting Systems and Air
Supply).
COMBUSTION AIR/VENT PIPE SIZING
To select the proper size piping for combustion air intake and
venting, refer to Table 4 or Table 5. The size will be determined by a combination of furnace model, total length of run,
and the number of elbows required. The following rules must
also be observed.Long radius elbows are required for all
units.
1.Long radius elbows are required for all units.
2.Elbows are assumed to be 90 degrees. Two 45 degree
elbows count as one 90 degree elbow.
3.Elbow count refers to combustion air piping and vent piping separately. For example, if the table allows for 5
elbows, this will allow a maximum of 5 elbows in the
combustion air piping and a maximum of 5 elbows in the
vent piping.
4.Three vent terminal elbows (two for vent pipe and one for
air intake pipe) are already accounted for and should not
be counted in the allowable total indicated in the table
(see vent termination section). These parts are shown
shaded.
For downflow/horizontal models only two additional
elbows are also accounted for and also should not be
counted. These parts are shown shaded.
5.Combustion air and vent piping must be of the same
diameter.
6. All combustion air/vent pipe and fittings must conform to
American National Standards Institute (ANSI) standards
and American Society for Testing and Materials (ASTM)
standards D1785 (Schedule 40 PVC), D2665 (PVCDWV), F891 (PVC-DWV Cellular Core). D2241 (SDR-21
and SDR-26 PVC), D2261 (ABS-DWV), or F628 (Schedule 40 ABS. Pipe cement and primer must conform to
ASTM Standards D2564 (PVC) or D2235 (ABS).
7.The use of flexible connectors or no hub connectors in
the vent system is not allowed. This type connection is
allowed in the combustion air pipe near the furnace for
air conditioning coil accessibility.
TABLE 4: INTAKE/VENT PIPING - 2 PIPE SYSTEM
Models P*UR/
FG9-UP/G9T-UP
40 / 37 / 800 / A
60 / 55 / 1000 / B
80 / 75 / 1200 / C
80 / 75 / 1600 / C
100 / 95 / 1400 / C
100 / 95 / 2000 / C
40 / 37 / 800 / A
60 / 55 / 1000 / B
80 / 75 / 1200 / C
80 / 75 / 1600 / C
100 / 95 / 1400 / C
100 / 95 / 2000 / C
120 / 112 / 2000 / D
140 / 130 / 2000 / D
1.
Elbow count does not include the elbows required for
the termination. See Step 4 under Combustion Air/Vent
Pipe Sizing
Pipe
Size
3" Only654N/A
Max. Elbows vs. One Way Vent
Length (Ft.)
5 - 40455075
2”654N/A
3”8765
1
TABLE 5: INT AKE/VENT PIPING 2-PIPE SYSTEM
Models P*DH/
FG9-DH/G9T-DH
40 /37 / 800 / A
60 /55 / 1200 / B
80 /75 / 1200 / B
80 /75 / 1600 / C
100 /95 / 2000 / C
40 /37 / 800 / A
60 /55 / 1200 / B
80 /75 / 1200 / B
80 /75 / 1600 / C
100 /95 / 2000 / C
120 /112 / 2000 / D 3" Only654N/A
1.
Elbow count does not include (2) 90 ° elbows required
to pipe intake into burner box or those required for the
termination. See Step 4 under Combustion Air/Vent
Pipe Sizing
Pipe Size
2”654N/A
3”8765
Max. Elbows vs. One Way
Vent Length (Ft.)
5-30354060
1
16Unitary Products Group
VENT TERMINATION (2-PIPE)
Side wall horizontal vent terminals and roof mounted vertical
terminals may be field fabricated. Standard PVC/SRD fittin
gs
may be used. Terminal configuration must comply as detailed
in this section.
Page 17
035-14370-000650.75-N4U
g
g
g
g
VENT
OVERHANG
COMBUSTION AIR
12" SEPARATION BETWEEN
BOTTOM OF COMBUSTION AIR
AND BOTTOM OF VENT
MAINTAIN 12" CLEARANCE ABOVE
HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE, WHICHEVER IS GREATER
12" MINIMUM
90°
VENT
OVERHANG
COMBUSTION AIR
(ELBOW PARALLEL TO WALL)
12" SEPARATION BETWEEN
BOTTOM OF COMBUSTION AIR
AND BOTTOM OF VENT
MAINTAIN 12" CLEARANCE ABOVE
HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE, WHICHEVER IS GREATER
12" MINIMUM
90°
NOTE
Combustion air and vent pipes must terminate
:
together in the same atmospheric zone, either through a roof
or sidewall.
NOTE
Accessory concentric intake/vent terminations,
:
models 1CT0302 and 1CT0303 are available and
approved for use with these furnaces. Refer to Form
650.75-N2.4V for installation details.
When selecting the location for combustion air/vent termination the following should be considered:
1.Comply with all clearance requirements as listed below.
2.Termination should be positioned where vent vapors will
not dama
e plants or shrubs or air conditioning equip-
ment.
3.Termination should be located where it will not be
affected by wind
allow recirculation of flue
usts, light snow, airborne leaves or
ases.
4.Termination should be located where it will not be dam-
ed or exposed to flying stones, balls, etc.
a
5.Termination should be positioned where vent vapors are
not objectionable.
17 to Figure 22.Sidewall termination may require sealing or
shielding of building surfaces with a corrosive resistance
material to protect against combustion product corrosion.
* Does not apply to multiple installations of this furnace
model. Refer to “VENTING MULTIPLE
UNITS" Section on page 17 .
FIGURE 18 : HORIZONTAL TERMINATION RAISED
CONFIGURATION FOR ADDITIONAL
CLEARANCE
VENTING MULTIPLE UNITS
In Canada, refer to CAN/CGA-B149.1 or.2 Installation
Code (latest edition - Venting Systems and Air Supply)
NOTE
Consideration must be given for degradation of build-
:
Each unit must have its own intake/vent piping and termination. Do not use common pipes for combustion air or venting.
The vent terminals must be located as shown in Figure 21
and FIGURE 22.
ing materials by flue gases.
NOTE
Shaded components of the combustion air/vent sys-
:
tem shown in the following figures are considered to be part
of the vent terminal. These components should not be
counted when determining piping limitations. Refer to Figure
Unitary Products Group17
Page 18
650.75-N4U035-14370-000
R
OVERHANG
12" MINIMUM
VENT
90°
COMBUSTION AIR
18" MAXIMUM
12" SEPARATION BETWEEN
BOTTOM OF COMBUSTION AIR
AND BOTTOM OF VENT
MAINTAIN 12" CLEARANCE ABOVE
HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE, WHICHEVER IS GREATE
FIGURE 19 : HORIZONTAL TERMINATION CON-
FIGURATION WITH HORIZONTAL
EXTENSION
12" VERTICAL SEPARATION
BETWEEN COMBUSTION
AIR AND VENT
VENT
COMBUSTION AIR
6"
FIGURE 22 : DOUBLE ROOFTOP TERMINATION
PIPING ASSEMBLY
The final assembly procedure for the vent/combustion air piping is as follows:
1.Cut piping to the proper length, beginning at the furnace.
2.Deburr the piping inside and outside.
3.Chamfer the outer edges of the piping.
4.Dry-fit the entire vent/combustion air piping assembly.
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
MAXIMUM OF 24" ABOVE ROOF
FIGURE 20 : VERTICAL TERMINATION
VENT
COMBUSTION AIR
2"
FIGURE 21 : DOUBLE SIDEWALL TERMINATION
5.Disassemble the piping and apply cement primer and
cement per the cement manufacturer's instructions.
Primer and cement must conform to ASTM D2564 for
PVC, or ASTM D2235 for ABS piping.
Solvent cements are flammable and must be used
in well-ventilated areas only . Keep them away from
heat, sparks and open flames (including pilots). Do
not breathe vapors and avoid contact with skin and
eyes.
6.All joints must be made to provide a permanent, air-tight,
water-tight seal.
7.Support the combustion air and vent piping such that it is
angled 1/4” per linear foot so that condensate will flow
back toward the furnace. Piping should be supported
with pipe hangers to prevent sagging. Maximum spacing
between hangers is five (5) feet, except SDR-PVC piping, where maximum spacing is three (3) feet.
8.Seal around the openings where the combustion air and
vent piping pass through the roof of side wall.
18Unitary Products Group
Page 19
035-14370-000650.75-N4U
S
VENT PIPE PASSES
THRO UG H TOP PANEL
COOL
HEAT
Vent piping must be insulated with 1/2” Armaflex
insulation if it will be subjected to freezing temperatures such as routing through unheated areas or
through an unused chimney.
PARK
PARK
LINE
XFMR
EAC
HUM
CIR
LINE
XFMR
EAC
HUM
YWRG
C
When combustion air pipe is installed above a suspended ceiling, the pipe must be insulated with 1/
2” Armaflex type insulation. The combustion air
pipe should also be insulated when it passes
through a warm, humid space.
Note
Vent pipe must be sloped 1/4” per foot to allow conden-
:
G AS PIPIN G
KNO CKO U TS
sate to flow back to the furnace.
METHOD TWO: ONE PIPE SYSTEM
This type installation will use combustion air from within the
space surrounding the furnace. This may be from within the
space in a non-confined location or it may be brought into the
furnace area from outdoors. It is not directly ducted into the
furnace. A single, properly sized pipe from the furnace vent
connector to the outdoors must be provided.
For upflow models combustion air is brought into the furnace
through the unit top panel opening. It is not necessary to
install a pipe into the intake collar on top of the burner box.
Refer to Figure 23 .
COMBUSTION AIR
VENT PIPE
INTO SOCKET JUST
UNDER TOP PANEL
OFF
ON
M
P
C
132
CEMENT
C O M B U S T IO N A IR
FIGURE 24 : DOWNFLOW / HORIZONTAL VENT
PIPE CONNECTION (P*DH/ FG9-DH /
G9T-DH)
For downflow/horizontal models, remove a minimum of two
gas piping knockouts for combustion air access. It is not necessary to install a pipe into the intake collar on bottom of the
burner box. For details, refer to Figure 24.
COMBUSTION AIR
All installations must comply with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI
Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or.2
Installation Code - latest editions.
An unconfined space
Btu/hr input rating for all appliances installed in that area.
Rooms communicating directly with the space containing the
appliances are considered part of the unconfined space, if
openings are not furnished with doors.
A confined space
1000 Btu/hr input rating for all appliances installed in that
area.
is not less than 50 cubic feet per 1000
is an area with less than 50 cubic feet per
FIGURE 23 : UPFLOW VENT PIPE CONNECTION
(P*UR / FG9-UP / G9T-UP)
For downflow/horizontal models combustion air is brought
into the furnace through the unit side panel openings.
Unitary Products Group19
The following must be considered to obtain proper air for
combustion and ventilation in confined spaces.
Air Source from Inside the Building -
Two permanent
openings, one within 12 inches of the top of the confined
space and one within 12 inches of the bottom, shall each
have a free area of not less than one square inch per 1,000
Page 20
650.75-N4U035-14370-000
g
Btuh of total input rating of all appliances located in the
space. The openings shall communicate freely with interior
areas having adequate infiltration from the outside.
NOTE
At least 100 square inches free area shall be used for
:
each opening.
Air Source from Outdoors -
1.Two permanent openings, one within 12 inches of the
top of the confined space and one within 12 inches of the
bottom, shall communicate directly, or by means of
ducts, with the outdoors or to such crawl or attic spaces
that freely communicate with the outdoors.
Vertical Ducts -
a.
Each opening must have a free
area of not less than one square inch per 4,000 Btuh
of total input of all appliances located in the space.
EXAMPLE:
Total Input of All Appliances
4000
Horizontal Ducts -
b.
= Square Inches Free Area
Each openin
must have a free
area of not less than one square inch per 2,000 Btuh
of total input of all appliances located in the space.
NOTE
Ducts must have the same cross-sectional area as
:
the free area in the opening to which they are connected. The
minimum dimension of rectangular ducts shall be three
inches.
TABLE 6: ESTIMATED FREE AREA
Wood or Metal
Louvers or Grilles
2
Screens
1.
Do not use less than 1/4 in. mesh
2.
Free area or louvers an grilles varies widely; installer
should follow louver or grille manufacturer’s instructions.
Wood 20-25%
Metal 60-70%
1/4 in. mesh or larger 100%
Special Combustion and Ventilation Considerations
Operation of a mechanical exhaust, such as an exhaust fan,
kitchen ventilation system, clothes dryer or fireplace may create conditions requiring special attention to avoid unsatisfactory operation of gas appliances.
Specially Engineered Installations
The above requirements shall be permitted to be waived
where special engineering, approved by the authority having
jurisdiction, provides an adequate supply of air for combustion, ventilation and dilution of flue gases.
Combustion Air Quality
The recommended source of combustion air is to use the outdoor air supply. Excessive exposure to contaminated combustion air will result in safety and performance related
problems. However, the use of indoor air in most applications
is acceptable, except as follows:
1
1
2.One permanent opening, commencing within 12 inches
of the top of the enclosure shall be permitted where the
equipment has clearances of at least 1 inch from the
sides and back and 6 inches from the front of the appliance. The opening shall communicate through a vertical
or horizontal duct to the outdoors, or spaces (crawl or
attic) that freely communicate with the outdoors and shall
have a minimum free area of:
a.1 sq. in. per 3000 Btu per hr of the total input rating
of all equipment located in the enclosure.
b.Not less than the sum of the areas of all vent con-
nectors in the confined space.
3.Louvers, Grilles and Screens
a.In calculating free area, consideration must be given
to the blocking effects of louvers, grilles and
screens.
b.If the free area of a specific louver or grille is not
known, refer to Table 6, to estimate free area.
NOTE
If mechanically operated louvers are used, a means
:
to prevent main burner ignition and operation must be provided should louvers close during startup or operation.
1.If the furnace is installed in a confined space it is recommended that the necessary combustion air come from
the outdoors by way of attic, crawl space, air duct or
direct openin
g.
2.If indoor combustion air is used, there must be no exposure to the installations or substances listed in 3 below.
3.The following types of installations may require OUTDOOR AIR for combustion, due to chemical exposure.
a.Commercial buildings
b.Buildings with indoor pools
c.Furnaces installed in laundry rooms
d.Furnaces installed in hobby or craft rooms
e.Furnaces installed near chemical storage areas
Exposure to the following substances in the combustion air
supply may also require OUTDOOR AIR for combustion.
f.Permanent wave solutions
g.Chlorinated waxes and cleaners
h.Chlorine based swimming pool chemicals
i.Water softening chemicals
20Unitary Products Group
Page 21
035-14370-000650.75-N4U
g
g
g
g
g
j.De-icing salts or chemicals
k.Carbon tetrachloride
l.Halogen type refrigerants
m. Cleaning solvents (such as perchloroethylene)
n.Printing inks, paint removers, varnishes, etc.
o.Hydrochloric acids
p.Cements and glues
q.Antistatic fabric softeners for clothes dryers
r.Masonry acid washing chemicals
VENT PIPE SIZING (1-PIPE SYSTEM)
Refer to Table 7 to select the proper size piping for venting.
The size will be determined by a combination of furnace
model, total length of run, and the number of elbows required.
The following rules must also be observed.
NOTE
Furnace vent pipe connections are sized for 2-in. pipe.
:
Any pipe size change must be made outside the furnace casing in a vertical pipe section to allow proper drainage of vent
connections.
NOTE
An offset using two 45 degree elbows may be required
:
for plenum clearance when the vent is increased to 3".
1.Long radius elbows are required for all units.
2.Elbows are assumed to be 90 de
elbows count as one 90 de
rees. Two 45 degree
ree elbow.
3.One Vent terminal elbow is already accounted for and
should not be counted in the allowable total indicated in
the table. See “VENT TERMINAL LOCATION
CLEARANCES" Section on pa
e 21 . This part is shown
shaded.
4.All vent pipe and fittin
s must conform to American
National Standards Institute (ANSI) standards and American Society for Testin
and Materials (ASTM) standards
D1785 (Schedule 40 PVC), D2665 (PVC-DWV), F891
(PVC-DWV Cellular Core), D2241 (SDR-21 and SDR-26
PVC), D2261 (ABS-DWV), or F628 (Schedule 40 ABS.
Pipe cement and primer must conform to ASTM Standards D2564 (PVC) or D2235 (ABS).
5.The use of flexible connectors or no hub connectors in
the vent system is not allowed.:
TABLE 7: VENT PIPING / 1-PIPE SYSTEM (ALL
MODELS)
Max. Elbows vs. One Way V ent
ModelPipe Size
5-40455075
All Models Except:
120 / 112 / 2000 / D
140 / 130 / 2000 / D
All Models Except:
120 / 112 / 2000 / D
140 / 130 / 2000 / D
120 / 112 / 2000 / D
140 / 130 / 2000 / D
2”654N/A
3”8765
3” Only654N/A
VENT TERMINATION (1-PIPE SYSTEM)
Side wall horizontal vent terminals and roof mounted vertical
terminals may be field fabricated. Standard PVC/SRD fittings
may be used. Terminal configuration must comply as detailed
in this section.
When selecting the locations for vent termination, the following should be considered:
1.Comply with all clearance requirements. (Refer to Figure
25 on page 22)
2.Termination should be positioned where vent vapors will
not damage plants or shrubs or air conditioning equipment.
3.Termination should be located where it will not be
affected by wind gusts, light snow, airborne leaves or
allow recirculation of flue gases.
4.Termination should be located where it will not be dam-
aged or exposed to flying stones, balls, etc.
5. Termination should be positioned where vent vapors are
not objectionable.
In Canada, refer to CAN/CGA-B149.1 or.2 Installation
Code (latest edition - Venting Systems and Air Supply)
VENT TERMINAL LOCATION CLEARANCES
The vent must be installed with the following minimum clearances(Refer to Figure 25 on page 22), and complying with
local codes or utility requirements or other authority having
jurisdiction.
Length (Ft.)
Unitary Products Group21
1.1 foot above grade and above normal snow levels.
2.Not above any walkway.
3.4 feet below, 4 feet horizontally from, or 1 foot above any
door/window or gravity air inlet to the building, or from
gas or electric meters.
Page 22
650.75-N4U035-14370-000
R
R
SOFFIT
VENTS
6'
10' RECOMMENDED
ELECTRIC
METER
FURNACE VENT
INSIDE
CORNER
4'4'
4'
4'
4'
4'
FRESH AIR
3'
1' PLUS
SNOW CLEARANCE
INTAKE
10'
12"
MAINTAIN 12" CLEARANCE ABOVE
HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE, WHICHEVER IS GREATE
VENT ELBOW
FIGURE 25 : VENT TERMINAL CLEARANCES
(1-PIPE SYSTEM) - U.S. ONLY
4.6 feet from any inside corner formed by two exterior
walls. 10 feet is recommended where possible.
5.At least 4 feet horizontally from any soffit or undereave
vent.
6.10 feet from any forced air inlet to the building. Any fresh
air or make up inlet as for a dryer or furnace area is considered to be a forced air inlet.
7.Avoid areas where condensate drippage may cause
problems such as above planters, patios, or adjacent to
windows where steam may cause fogging.
NOTE
Consideration must be given for degradation of build-
:
ing materials by flue gases.
NOTE
Shaded components of the vent system shown in Fig-
:
ure 25 through Figure 28are considered to be termination.
These components should not be counted when determining
pipe diameter. Sidewall termination may require sealing or
shielding of building surfaces with a corrosive resistant material due to vent system corrosive combustion products.
FIGURE 26 : HORIZONTAL TERMINATION CON-
FIGURATION WITH 12” MINIMUM
CLEARANCE
12" MINIMUM
90°
VENT
MAINTAIN 12" CLEARANCE ABOVE
HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE, WHICHEVER IS GREATE
FIGURE 27 : HORIZONTAL TERMINATION RAISED
CONFIGURATION FOR ADDITIONAL
CLEARANCE
22Unitary Products Group
VENT
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
MAXIMUM OF 24" ABOVE ROOF
FIGURE 28 : ROOFTOP TERMINATION
Page 23
035-14370-000650.75-N4U
g
g
g
g
g
g
g
g
g
g
gging
g
g
g
g
12" M IN IM UM BETW EEN
BO TTOM O F ELBOW AN D
ANY M ATERIAL
12"
MINIMUM
PIPING ASSEMBLY
The final assembly procedure for the vent piping is as follows:
1.Cut pipin
2.Deburr the pipin
3.Chamfer the outer ed
4.Dry-fit the entire vent pipin
5.Disassemble the pipin
to the proper length, beginning at the furnace.
inside and outside.
es of the piping.
system.
and apply cement primer and
cement per the cement manufacturer's instructions.
Primer and cement must conform to ASTM D2564 for
PVC, or ASTM D2235 for ABS pipin
.
Solvent cements are flammable and must be used
in well-ventilated areas only . Keep them away from
heat, sparks and open flames (including pilots). Do
not breathe vapors and avoid contact with skin and
eyes.
6.All joints must be made to provide a permanent, air ti
water ti
ht seal.
ht.
In Canada, refer to CAN/CGA-B149.1 or.2 Installation
Code (latest edition - Venting Systems and Air Supply)
COMBUSTION AIR INTAKE
Refer to Table 4 on page 16, for intake pipe sizing, allowable
length and elbow usage. Follow all notes, procedures and
required materials in the Two-Pipe Sealed Combustion section (Method 1) when installing the combustion air pipe within
the unit and into the ventilated attic space.
COMBUSTION AIR TERMINATION
Refer to Figure 29 for required termination method and configuration for the intake pipe. For attic termination, use two 90
elbows with the open end in a downward position. Be sure to
maintain 12" clearance above any insulation, flooring or other
material.
Be sure to instruct the owner not to block this
intake pipe.
7.Support the vent pipin
ear foot so that condensate will flow back towards the
furnace. Pipin
prevent sa
5 feet, except SDR-PVC pipin
in
8.Seal around the openin
throu
Vent piping must be insulated with 1/2” Armaflex
insulation if it will be subjected to freezing temperatures such as routing through unheated areas or
through an unused chimney.
NOTE:
densate to flow back to the furnace.
METHOD THREE: TWO PIPE SYSTEM USING COMBUSTION AIR FROM A VENTILATED ATTIC SPACE
This type installation requires two properly sized pipes. One
brings combustion air from a properly ventilated attic space
and a second pipe from the furnace vent connection (top right
of unit) exits to the outdoors.
such that it is angled 1/4” per lin-
should be supported with pipe hangers to
. Maximum spacing between hangers is
, where maximum spac-
is 3 feet.
s where the vent piping passes
h the roof or side wall.
Vent pipe must be sloped 1/4” per foot to allow con-
FIGURE 29 : ATTIC COMBUSTION AIR TERMINA-
TION
COMBUSTION AIR REQUIREMENTS
The ventilated attic space from which the combustion air is
taken must comply with the requirements shown on page 11
in this instruction or in Section 5.3, Air for Combustion and
Ventilation of the National Fuel Gas Code, ANSI Z223.1 (latest edition).
VENT PIPE
For vent pipe sizing, allowable length and elbow usage, see
Refer to Table 7 on page 21. Follow all notes, installation procedures and required materials in the “METHOD TWO ONE
PIPE SYSTEM, on page 19” to install the vent pipe from the
unit to the outdoors.
Unitary Products Group23
Page 24
650.75-N4U035-14370-000
VENT TERMINATION
The vent pipe termination must be installed within the allowable locations shown in Figure 24 and Section 7.8 in the
National Fuel Gas Code, ANSI Z223.1 (current edition). Follow all local agency and utility requirements if more restrictive
than those shown. Vent termination must be as shown in Figure 27through Figure 28.
In Canada, refer to CAN/CGA-B149.1 or .2 Installation Code (latest edition - Venting Systems and Air Supply)
HORIZONTAL VENT APPLICATIONS
If installing a horizontal venting system through any unconditioned space such as an attic or crawl space, it is recommended, but not required, that a vent drain be added to the
vent pipe to prevent the accumulation of excess condensate
in the inducer motor during operational cycles. (Refer to Figures 30 and 31).
FIGURE 30 : HORIZONTAL VENT DRAIN -
UPFLOW MODELS P*UR/FG9-UP/
G9T-UP
To install the vent drain, complete the following steps:
1.Place a tee of the proper diameter for the vent system
being installed (2" or 3") in the horizontal run closest to
the furnace.
FIGURE 31 : HORIZONTAL VENT DRAIN -
DOWNFLOW/HORIZONTAL MODELS
P*DH/FG9-DH/G9T-DH
2.Place a reducer bushing of proper diameter in the stem
portion of the tee. The recommended size for the
reducer is 5/8”.
3.Place a piece of 5/8” diameter or other selected size pipe
a minimum of 3" long into the reducer to serve as a nipple.
NOTE
Tee, reducer and nipple must be properly cemented
:
together using the appropriate method and materials specified in the Combustion Air Intake/Vent Connections section of
these instructions.
4.Connect a piece of flexible drain tubing such as EPDM
rubber, Vinyl or PVC to the nipple.
5.Loop the drain tubing to provide a trap.
6.Connect the discharge end of the drain tube to the condensate disposal system externally to the furnace.
CONDENSATE PIPING
The condensate drain connection is packed in the furnace for
field installation. It consists of a formed hose with a 1/2” NPT
male connection. A 1/2” FM x 3/4” PVC slip coupling is provided.
24Unitary Products Group
Page 25
035-14370-000650.75-N4U
This drain hose may be installed to allow left or right side condensate drain connection. (Refer to Figure 32.)Cut the hose
to allow for proper fit for left or right exit.
LH DRAIN
RH DRAIN
FIGURE 32 : UPFLOW MODELS P*UR/FG9-UP/
G9T-UP
For horizontal left airflow (inducer and vent low) or horizontal
right airflow (inducer and vent high), install condensate drain
hoses as follows:
RIGHT AIRLOW (Inducer High) - Three hoses are required.
Hoses are supplied with furnace. Refer to Figure 34 and
Table 8 for application.
LEFT AIRFLOW (Inducer Low) - Two hoses are required.
Inducer outlet to trap is supplied. Condensate pan to trap
must be field supplied using 5/8” I.D. hose material. Refer to
Figure 34 and Table 8, for hose placement and sizing.
TABLE 8: HORIZONTAL CONDENSATE DRAIN HOSE
SIZES - MODELS P*DH / FG9-DH / G9T-DH
CABINET SIZE (IN.)
DIMEN.
A4-1/24-3/43-1/25-1/4
B7-1/210-1/21417-1/2
C13-1/216-1/22023-1/2
D3-3/83-1/43-1/43-1/4
RIGHT AIRFLOW (INDUCER HIGH)
14-1/217-1/22124-1/2
LEFT AIRFLOW (INDUCER LOW)
CONDENSATE
T R A P T U B IN G
FIGURE 33 : DOWNFLOW/HORIZONTAL MODELS
P*DH/FG9-DH/G9T-DH
To install the drain hose assembly, remove the 7/8” knockout
in the side panel. Remove the conduit nut from the 1/2” male
fitting. Push the male fitting through the hole and reinstall the
nut. The use of the 3/4” PVC coupling is optional.
Conversion for Horizontal Applications
Remove the condensate trap and its mounting bracket from
the unit side panel. Remove all drain hoses.
Reinstall the trap/bracket on the side panel which will be on
the bottom when the unit is located horizontally. Use the original mounting screws.
Refer to Figure 34 for hose locations and Table8 for hose
cut lengths. All hoses are identified as shown in Figure 34.
Plug all unused condensate trap, condensate pan
and inducer drain connection points using plugs
provided.
Drain Connection:
The following steps apply to all models.
For horizontal application, also follow the procedure for relocating the trap assembly and installing drain hoses.
1.It is recommended that either 1/2” or 3/4” PVC or equiva-
lent pipe be field installed as drain pipe. The condensate
piping may be tied together with the air conditioning condensate drain if the air conditioning condensate drain
line is trapped upstream of the tie-in and the combined
drains are constructed of the same material.
2.All pipe joints must be cleaned, de-burred and cemented
using PVC primer and cement.
3.The furnace contains an internal trap. Therefore, no
external trap should be used.
4.If a condensate pump is used, it must be suitable for use
with acidic water.
5.Where required, a field-supplied neutralizer can be
installed in the drain line, external to the furnace.
NOTE
The condensate drain from the furnace may be con-
:
nected in common with the drain from an air conditioning coil
Unitary Products Group25
Page 26
650.75-N4U035-14370-000
RIGHT AIRFLO W
(INDUCER HIGH)
HOSE
ID E N T .
NUMBERS
1 - C ON DENSATE PAN TO TRAP
"A " D IM E N S IO N
2 - INDUCER BOTTOM TO TRAP
"B " D IM E N S IO N
3 - INDUCER O UTLET TO TRAP
"C " D IM E N S IO N
LEFT A IR FLOW
(INDUCER LOW )
HOSE
ID E N T .
NUMBERS
4 - INDUCER OUTLET TO TRAP
U S E A S P R O V ID E D
if allowed by local code. Follow the instructions with the coil
for trapping the drain.
SAFETY CONTROLS
Control Circuit Fuse:
the 24 volt transformer from overload caused by control circuit wiring errors. This is an ATO 3, automotive type fuse and
is located in the unit wiring harness between the control
transformer and the furnace control.
Blower Door Safety Switch:
Electrical Interlock Switch mounted in the blower compartment. This switch interrupts all power at the unit when the
panel covering the blower compartment is removed.
Blower and burner must never be operated without
the blower panel in place.
A 3 amp. fuse is provided to protect
This unit is equipped with an
Electrical supply to this unit is dependent upon the panel that
covers the blower compartment being in place and properly
positioned.
Main power to the unit must still be interrupted at
the main power disconnect switch before any service or repair work is to be done to the unit. Do not
rely upon the interlock switch as a main power disconnect.
Rollout Switch Controls:
This control is mounted on the
burner box assembly. If the temperature in the burner compartment exceeds its set point, the igniter control and the gas
valve are de-energized. The operation of this control indicates a malfunction in the combustion air blower, heat
exchanger or a blocked vent pipe connection. Corrective
action is required. This is a manual reset control and must be
reset before operation can continue.
Pressure Switches:
This furnace is supplied with pressure
switches which monitor the flow through the combustion air/
vent piping system. These switches de-energize the ignition
26Unitary Products Group
Page 27
035-14370-000650.75-N4U
g
g
g
control module and the gas valve if any of the following conditions are present. Refer to Figure 35 for tubing connections.
1LP
UPFLOW
1LP2LP
Auxiliary Limit Controls
Downflow/horizontal units have a single limit switch munted
on the blower assembly. This is a manual reset control and
gives high temperature protection in the event of a blower
motor failure.
START-UP AND ADJUSTMENTS
The initial start-up of the furnace requires the following additional procedures:
1.When the gas supply is initially connected to the furnace,
the gas piping may be full of air. In order to purge this air,
it is recommended that the ground union be loosened
until the odor of gas is detected. When gas is detected,
immediately retighten the union and check for leaks.
Allow five minutes for any gas to dissipate before continuing with the start-up procedure.
Be sure proper ventilation is available to dilute and
carry away any vented gas.
DOWNFLOW / HORIZONTAL
FIGURE 35 : PRESSURE SWITCH TUBING ROUTING
1.Blocka
2.Blocka
3.Failure of combustion air blower motor (1LP).
4.Blocka
• Upflow units (1LP)
• Downflow/Horizontal Units
Limit Control
There are high temperature limit control(s) located on the furnace vestibule panel near the gas valve. These are automatic
reset control and provides over temperature protection due to
reduced airflow, such as a dirty filter.
e of combustion air piping or terminal. (1LP)
e of vent piping or terminal (1LP).
e of condensate drain piping:
• Downflow (1LP)
• Horizontal Left (1LP)
• Horizontal Right (2LP)
Perform the following procedures only after the
condensate trap has been properly piped to a
drain connection using the procedure in this
instruction.
2.The condensate trap must be filled with water before putting the furnace into operation. The recommended procedure is as follows:
a.Disconnect the condensate drain hose from the
induced draft blower discharge.
b.Elevate this hose and fill with water using a funnel.
c.Replace the condensate drain hose and clamps.
NOTE
If this procedure is not followed, the unit may not prop-
:
erly drain on initial start up.
3.All electrical connections made in the field and in the factory should be checked for proper tightness.
IGNITION SYSTEM SEQUENCE
1.Turn the gas supply ON at external valve and main gas
valve.
2.Set the thermostat above room temperature to call for
heat.
Unitary Products Group27
Page 28
650.75-N4U035-14370-000
3.System start-up will occur as follows:
a.The induced draft blower motor will start and oper-
ate on low speed. Shortly after venter start-up, the
hot surface igniter will glow for about 17 seconds.
Wrench
Boss
Wiring
Terminals
Outlet
b.The ignition module will energize (open) the main
gas valve on low fire for seven seconds.
c.After flame is established, the supply air blower will
start in about 30 seconds.
NOTE
Burner ignition may not be satisfactory on first start-up
:
due to residual air in line.
4.With furnace in operation, paint the pipe joints and valve
gasket lines with a rich soap and water solution, Bubbles
indicate a gas leak. Take appropriate steps to stop the
leak. If the leak persists, replace the component.
DO NOT omit this test! Never use a flame to check
for gas leaks.
GAS VALVE OPERATION
The manual valve knob is a two-position (ON-OFF) type. To
turn the valve ON, rotate knob clockwise or counterclockwise
to line up the word ON on the knob with the indicator on the
cover casting (Refer to Figure 36).
CHECKING GAS INPUT (NATURAL GAS)
NOTE
Front door of burner box must be secured when
:
checking gas input.
1.Turn off all other gas appliances connected to the gas
meter.
2.With the furnace turned on, measure the time needed for
one revolution of the hand on the smallest dial on the
meter. A typical domestic gas meter usually has a 1/2 or
1 cubic foot test dial.
3.Using the number of seconds for each revolution and the
size of the test dial increment, find the cubic feet of gas
consumed per hour, (Refer to Table 9 on page 29).
To find the BTUH input use the following formula:
Inlet
ON - OFF Switch
Main
Regulator
Adjust
Outlet
Pressure
Tap
FIGURE 36 : GAS VALVES -
(TOP ) W HITE - R ODG E R S 36E 2 4
(BOTTOM) HONEYWELL VR8205
(approved for field replacement)
lated. Higher temperatures (over 60° F) will speed up the
meter and make it read high.
Temperatures under 60° F will slow it and make it read low.
The barometric pressure above 30.0" will slow the meter and
below 30.0" speed up the meter. At some conditions the
meter may be off significantly. an error of
mon. The gas meter correction factor is calculated as follows:
(Barometric Pressure) x 520
= Meter Correction Factor
(Temperature F + 460) x 30
+
5% is not uncom-
Cu. Ft. Gas x meter correction factor x Gas BTU Content =
BTU Per Hour Input
The gas meter is affected by both the temperature and also
the barometric pressure. The meter should be correct at 60°
F, and 30.0" barometric pressure. At all other conditions it will
be inaccurate, although the correction factor is easily calcu-
28Unitary Products Group
Example 1: 28.9" Barometric Pressure, 80° F
(28.9) x 520= 15028
= .928 Correction Factor
(80 + 460) x 30= 16200
Contact your gas supplier for actual BTU content of the gas.
Page 29
035-14370-000650.75-N4U
g
g
g
g
g
EXAMPLE - CHECKING GAS INPUT
It is found by measurement that it takes 26 seconds for the
hand on the 1 cubic foot dial to make a revolution with only a
120,000 Btuh furnace running. Using this information, locate
26 seconds in the first column of Table 9, “
as rate (cubic feet
per hour),” on page 29. Read across to the column headed
cubic foot
where you will see that 138 cubic feet of gas per
hour are consumed by the furnace at that rate.
With the barometer at 28.9" and a 70° F temperature, the cor-
rection factor will be.945. If the local gas heating value is 935
BTU per cubic foot the calculations will be as follows:
138 cu. ft/hrx.945 correction factor x 935 BTU/cu. ft. =
121,933 BTU/Hr.
The calculated firing rate of 121,933 BTU per hour is within
+
2% tolerance of our nominal 120,000 furnace..
the
+
If the actual input is not within
2% of the furnace rating, with
allowance being made for the permissible range of the regulator setting (0.3 inches W.C.), replace the orifice spuds with
spud of the proper size.
Be sure to relight any gas appliance that were
turned off at the start of this input check.
ADJUSTMENT OF MANIFOLD GAS PRESSURE
Manifold gas pressure may be measured by two different procedures. It may be measured with the burner box cover in
place or it may be measured with the burner box cover
removed. Follow the appropriate section, 2a or 2b in the
instructions below.
1.Turn
2.Read the inlet
as off at main gas valve. Revove 1/8” Allen socket
head pipe plu
from the manifold end of the main gas
valve. Install the proper manometer tube adapter into
this openin
.
as pressure using either of the two meth-
ods below.
Reading the gas pressure with the burner box
a.
cover in place
- Disconnect the pressure reference
hose from the right side of the burner box. Using a
tee fitting and a short piece of hose, connect the
negative side of the manometer to the burner box
pressure reference port. Connect the positive side
of the manometer to the adapter previously installed
in the gas valve Refer to Figures 39 and 40 on
page 31.
- Remove the screws securing the
burner box front cover plate. Remove the cover. It is
gasketed and may stick in place. Connect the positive side of the manometer to the adapter previously
installed in the gas valve as shown in Refer to Figures 39 and 40 on page 31. There will be no second
connection to the manometer as it will reference
atmospheric pressure.
NOTE:
The screw-off cap for the pressure regulator must be
removed entirely to gain access to the adjustment screw.
Loosening or tightening the cap does not adjust the flow of
gas.
OF
CUBIC FOOT
1
Unitary Products Group29
Page 30
650.75-N4U035-14370-000
3.Refer to Figure 36 on page 28, for location of pressure
regulator adjustment cap and screw on main gas valve.
4.Turn gas and electrical supplies ON. Start furnace and
observe manifold pressure on manometer.
5.Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following:.
Natural Gas ..............................................................3.5” W.C.
Propane (LP) Gas ....................................................10.0” W.C.
If gas valve regulator is turned in, or clockwise, manifold
pressure is increased. If screw is turned out, or counterclockwise, manifold pressure will decrease.
If manifold pressure is too high, an over-fire condition exists which could cause heat exchanger failure. If the manifold pressure is too low, sooting
and eventual clogging of the heat exchanger could
occur.
All direct-drive blowers have multi-speed motors. The blower
motor speed taps are located in the control box in the blower
compartment. Refer to Figure 37, and the unit wiring label to
change the blower speed.
You may select a heating speed and a cooling speed. They
may be the same speed or a different speed.To use the same
speed tap for heating and cooling, the heat terminal and cool
terminal must be connected using a jumper wire and connected to the desired motor lead. Place all unused motor
leads on Park terminals. Two Park terminals are provided. .
Do not energize more than one motor speed at a
time or damage to the motor will result.
ADJUSTMENT OF FAN-OFF CONTROL SETTINGS
This furnace is equipped with a time-on/time-off heating fan
control. The fan on is fixed at 30 seconds. The fan off is field
adjustable from 60 to 180 seconds. The fan off is factory set
to 60 seconds. Adjust the off time by repositioning the fan off
switches. (Refer to Figure 37.)
Once the correct gas pressure to the burners has
been established, turn the gas valve knob to OFF
and turn the electrical supply switch to OFF; then
remove the pressure tap at the gas valve and reinstall the plug, using a compound (on the threads)
resistant to the action of LP gases. Replace the
burner box front cover or the pressure reference
hose.
Be sure that gas valve regulator cap and burner
box to gas valve pressure reference hose is reconnected.
Turn the electrical and gas supplies back on, and with the
burners in operation, check for gas leakage around the plug
with a soap and water solution.
ADJUSTMENT OF TEMPERATURE RISE
The temperature rise, or temperature difference between the
return air and the heated air from the furnace, must be within
the range shown on the furnace rating plate. Application limitations are shown in Table 1 or 2. After the temperature rise
has been determined, the cfm can be calculated.
After about 20 minutes of operation, determine the furnace
temperature rise. Take readings of both the return air and the
heated air in the ducts, about six feet from the furnace where
they will not be affected by radiant heat.
Increase the blower speed to decrease the temperature rise;
decrease the blower speed to increase the rise.
FIGURE 37 : TYPICAL HEAT/COOL SPEED TAP
CONNECTIONS
The fan-off setting must be long enough to adequately cool
the furnace, but not so long that cold air is blown into the
heated space. The fan-off timing may be adjusted by setting
the option switches located (Refer to Figure 37) on the control board as follows:
To Delay Fan-Off
By:
60 Sec.ONON
90 Sec.OFFON
120 Sec.ONOFF
180 Sec.OFFOFF
Set Switch
1 2
30Unitary Products Group
Page 31
035-14370-000650.75-N4U
HUM
EAC
EAC
HUM
115 VOLT
ELECTRONIC
AIR CLEANER
EAC HOT
HUM HOT
BLK
BLK
WHI
WHI
115 VOLT
HUMIDIFIER
SWITCHED
CIRCUITS
NEUTRALS
W
N
For units using a Texas Instruments control, connect the
jumper at the desired off timing. Refer to Figure 37 on
page 30, 60 second off timing shown.
ACCESSORY CONNECTIONS
Do not exceed 1.0 amp loading.
The furnace control will allow power switching control of various accessories. Refer to Figure 38
Electronic Air Cleaner Connection
Two 1/4” spade terminals (EAC and EAC N) for electronic air
cleaner connections are located on the control board. The
terminals provide 120 VAC (1.0 amp maximum) durin
lating blower operation.
OUTLET
PRESSURE
TAP
BURNER BOX
PRESSURE
REFERENCE HOSE
.
g circu-
GAS
VALVE
Humidifier Connection
Two 1/4” spade terminals (HUM and HUM N) for humidifier
connections are located on the control board. The terminals
provide 120 VAC (1.0 amp maximum) during heat speed
AIRFLOW DATA - DOWNFLOW/HORIZONTAL MODELS: P*DH/FG9-DH/G9T-DH
MODELS
Input/Output/Airflow/
cabinet
40 / 37 / 800 / A
60 / 55 / 1200 / B
80 / 75 / 1200 / B
80 / 75 / 1600 / C
100 / 95 / 2000 / C
120 / 112 / 2000 / D
Airflow expressed in standard cubic feet per minute.
Notes: 1. Air filter installed. All filters must be high velocity, cleanable type.
2. Motor voltage at 115 V.
SPEED TAP
HI118211641136110110631018967904824724
MED954938919899876838798744686588
LOW650643634620602577542494440335
HI1567155215321517148414411384131512431166
MED11751173116911591144112610891039985910
LOW881879871861842826795756724664
HI1603157915581522148514331380131112331139
MED12501230121011901160112510831029955889
LOW925904891873845829793761685618
HI2024196019111855178016981627154014581387
MED1479147114651452142913931359130012381163
LOW——1210120811981175114911101052982
HI2272220021282061198418901810171016271519
MED1980193318871838176917011626153514261328
LOW1573154615261498146414171359129012221132
HI2281221521442065200219031820172016181505
MED1945190218491794173816751604153514261343
LOW1507148514631433139813581305124911721095
0.10.20.30.40.50.60.70.80.91.0
EXTERNAL STATIC PRESSURE, INCHES WC
Unitary Products Group33
Page 34
650.75-N4U035-14370-000
OPERATION AND MAINTENANCE
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer to the schematic wiring diagrams in the back of
this manual for component location.
CONTINUOUS BLOWER
On cooling/heating thermostats with fan switch, when the fan
switch is set in the ON position, a circuit is completed
between terminals R and G of the thermostat. The blower
motor is energized through the low heat terminal and runs on
the selected speed. This allows constant air circulation at
lower flow rate.
INTERMITTENT BLOWER - COOLING
On cooling/heating thermostats with fan switch, when the fan
switch is set in the auto position and the thermostat calls for
cooling, a circuit is completed between the R, Y and G terminals.
The motor is energized through the cool fan terminal and
runs on the selected speed. The fan off setting is fixed at 60
seconds for SEER enhancement.
HEATING CYCLE
When the system switch is set on HEAT and the fan is set on
AUTO, and the room thermostat calls for heat, a circuit is
completed between terminals R and W of the thermostat.
When the proper amount of combustion air is being provided,
a pressure switch activates the ignition control
If flame is not detected within the seven second sensing
period, the gas valve is de-energized. The control is
equipped with a re-try option. This provides a 60 second wait
following an unsuccessful ignition attempt (flame not
detected).
After the 60 second wait, the ignition sequence is restarted
with an additional 10 seconds of igniter warm-up time. If this
ignition attempt is unsuccessful, one more re-try will be made
before lockout.
A momentary loss of gas supply, flame blowout, or a shorted
or open condition in the flame probe circuit will be sensed
within 0.8 seconds.
The gas valve will deenergize and the control will restart the
ignition sequence immediately. Recycles will begin and the
burner will operate normally if the gas supply returns, or the
fault condition is corrected prior to the last ignition attempt.
Otherwise, the control will lockout.
The control will repeat the ignition sequence for a total of two
recycles if flame is lost within the first 10 seconds of establishment.
If flame is established for more than 10 seconds after ignition,
the control will clear the ignition attempt (retry) counter. If
flame is lost after 10 seconds, it will restart the ignition
sequence. This can occur a maximum of five times.
During burner operation, a momentary loss of power of 50
milliseconds or longer will drop out the main gas valve. When
the power is restored, the gas valve will remain de-energize
and a restart of the ignition sequence will begin immediately
Hot Surface Ignition System
The ignition control provides a 17-second warm-up period.
The gas valve then opens for seven seconds.
As gas starts to flow and ignition occurs, the flame sensor
begins its sensing function. If a flame is detected within seven
seconds after ignition, normal furnace operation continues
until the thermostat circuit between R and W is opened. After
flame is present for 30 seconds, the circulating blower is
energized.
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a
potential shock hazard from the components of the
hot surface ignition system. The furnace can only
be lit automatically by its hot surface ignition system.
When the thermostat circuit opens, the ignition control is deenergized. With the ignition control de-energized, the gas
flow stops and the burner flames are extinguished. The venter continues to operate for 15 seconds after the gas flow
stops.
The blower motor continues to operate for the amount of time
set by the fan-off delay switches located on the control board.
The heating cycle is then complete, and the unit is ready for
the start of the next heating cycle.
34Unitary Products Group
.
Page 35
035-14370-000650.75-N4U
FIGURE 41 : FURNACE CONTROL EVENT SCHEDULE
MAINTENANCE
Air Filters
The filters must be checked periodically for dirt accumulation.
Dirty filters greatly restrict the flow of air and may cause damage to the system.
Clean the filters at least every three months. On new construction, check the filters every week for the first four weeks.
Inspect the filters every three weeks after that, especially if
the system is running constantly .
All filters used with the furnace are the high-velocity, cleanable type. Clean these filters by washing in warm water.
Make sure to shake all the water out of the filter and have it
reasonably dry before installing it in the furnace. When
replacing filters, be sure to use the same size and type as
originally supplied.
Filter Removal - Upflow Models
The ends of the retainer are attached to the rear panel in two
metal loops. Refer to Table 42 on page 35. The ends must be
squeezed together to free them from the loops. The retainer
may then be moved to the new location and the ends inserted
in the loops on the rear panel at the new location. Loops are
provided for retainer location to accommodate filter application on the bottom or either side of the furnace.
Swing the retainer toward the center of the furnace. This will
expose the filter to allow removal. To reinstall the filter, simply
reverse this procedure.
FIGURE 42 : UPFLOW FILTER RETAINER
Filter Removal - Downflow Models
1.Turn off electrical power supply to the furnace at disconnect switch. Remove access doors.
To remove a filter from the bottom location, push the closed
end of the filter retainer to the left until it clears the lip on the
front of the furnace base, which acts as a catch for the
retainer. When the retainer is clear of the flange, it will pivot in
the loops.
Unitary Products Group35
2.Filters are installed in the plenum area above the blower
assembly . Filters rest against the side of the plenum wall
and are supported in the middle by a frame. Lift filter
slightly to dislodge and remove for service.
3.Remove the filter and follow the cleaning instructions
above. DO NOT remove the filter stiffener rods, if pro-
Page 36
650.75-N4U035-14370-000
vided. When reinstalling the filter(s) be sure it completely
covers the plenum opening.
To reinstall the filters, simply reverse this procedure.
Horizontal Applications
In most horizontal applications the filter is located in the
return air duct near the furnace or in a filter grille.
When replacing filters, DO NOT use a type with
excessively high pressure drop. Some high efficiency filters available will cause the furnace to
operate improperly and could result in a safety
hazard.
Lubrication
Blower motors in these furnaces are permanently lubricated
and do not require periodic oiling.
Blower Care
Even with good filters properly in place, blower wheels and
motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they
can be brushed and cleaned with a vacuum cleaner.
6.To reassemble, reverse the procedure, restore power to
the furnace and verify operation.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt
accumulation.
If cleaning is required, follow this procedure:
1.Turn off the electrical power to the unit.
2.Turn off the gas supply at the external manual shutoff
valve and loosen the ground union joint.
3.Remove the upper access panel and remove the burner
box cover.
4.Remove the screws that hold the burner box assembly to
the vest panel and remove the assembly.
5.Remove burners from the burner assembly.
6.Burners may be cleaned by rinsin
7.Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
1.Turn off the main manual gas valve external to the furnace.
2.Turn off electrical power to the furnace.
3.Remove the upper access panel and remove the burner
box cover.
g in hot water.
The procedure for removing the direct drive blower assembly
for cleaning is as follows:
1.Disconnect the electrical supply to the furnace and
remove remove the access doors.
2.On downflow/horizontal models only, remove the two
wires leading to the auxiliary limit mounted on the side
opposite the blower motor.
3.On downflow/horizontal models only, remove four top
panel screws and lift the top panel enough to disengage
and remove the flue chase assembly.
4.Remove blower assembly mounting screws and slide the
blower assembly out of the slots in the deck. If the two
shipping screws were not previously removed, also
remove and discard these two screws located on each
front corner of the blower assembly.
5.On downflow models only, note the wire/terminal location
and then remove the blower wiring from the furnace control. Remove the protective boot and disconnect run
capacitor wires. Remove the screws securing the electrical panel to the blower housing. Pull blower assembly
out of the unit. When cleaning or servicing the blower
assembly, DO NOT remove or change the balance clips
on the blower wheel.
4.Disconnect wires from flame sensor, rollout switch and
HSI igniter. Remove igniter carefully, as it is easily broken.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
5.Remove the screws that hold the burner box assembly to
the vestibule panel and remove the assembly . The upper
portion of the heat exchanger will now be exposed.
6.Remove the upper cover plate at the top of the furnace.
Remove the internal baffle.
7.The upper portion of the heat exchanger is now
exposed.
8.With a long flexible wire brush, clean inside each tube at
both the top and bottom. The brush must pass around
the rear heat exchanger tubes. Vacuum loose scale and
dirt from each tube.
36Unitary Products Group
Page 37
035-14370-000650.75-N4U
g
g
g
g
g
g
g
g
g
g
g
g
g
50A50-241 IGNITION CONTROL (P/N 031-01266-000)
Normal flame sense current is approximately
2.0 microamps DC (
µ
a)
Low flame signal control lockout point is
0.15 microamps (DC (
µ
a)
9.Clean - vacuum all burners.
10. Replace all components in reverse order. Reconnect all
wirin
.
11. Restore electrical power and
12. Check furnace operation.
Cleaning the Secondary Heat Exchanger
1.Follow steps 1 thru 10 under Cleanin
Exchan
2.Remove the vent pipin
nect the drain lines from the venter and from the condensate drain pan. Remove the venter blower and the
condensate pan. The turbulators can then be
removed from the secondary heat exchan
3.With a stiff wire brush, brush out loose scale or soot.
4.Vacuum the secondary heat exchan
5.Finish the cleanin
12 under Cleanin
Vent/Air Intake
Should it be necessary to service the vent/air intake system,
the manufacturer recommends this service be conducted by
a qualified service agency.
The operation of this appliance requires the reassembly and
resealing of the vent/air intake system as specified on Page
11.
er.
procedure by following steps 10 thru
the Primary Heat Exchanger.
as supply to the furnace.
the Primary Heat
from the venter housing. Discon-
ently
er.
er.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1.Check to see that the power to the furnace and the i
tion control module is ON.
ni-
troubleshooting section in this manual to check the system's
operation..
POWER SUPPLY POLARITY - 50A50-241 Control
Only
lowing unit operation will occur. On a call for heat, the
inducer will run, the HSI will glow and the gas valve will
energize and the burners will ignite. The burners will
immediately extinguish and the unit will recycle. This will
occur 3 times and then the unit will lockout. A “7” flash
code will be displayed. This code means the flame could
not be established. This occurs because the control cannot sense flame with the power supply polarity reversed.
If the power supply polarity is reversed, the fol-
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self diagnostic capability. If a system
problem occurs, a fault code is shown by a blinking LED. It is
located behind a clear view port in the blower compartment
door. DO NOT remove the furnace blower compartment
panel OR turn off furnace power as either action will clear the
control's memory of the fault.
The control continuously monitors its own operation and the
operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the
light will stay on continuously. In this case, the entire control
should be replaced as the control is not field repairable.
If the sensed failure is in the system (external to the control),
the LED will flash in the following flash-pause sequences to
indicate failure status.
Flash sequence codes 2 thru 9 are as follows. LED will turn
on for 1/4 second and off for 1/4 second. This pattern will be
repeated the number of times equal to the code. For example, six on flashes equals a number 6 fault code.
All flash code sequences are broken by a 2 second off period
2.The manual shutoff valves in the
must be open.
3.Make sure all wirin
4.Review the sequence of operation.
Start the system by setting the thermostat above the room
temperature. Observe the system's response. Then use the
connections are secure.
Unitary Products Group37
as line to the furnace
.
CONTINUOUS FLASHING (1 sec on - 1 sec off):
cates that flame was sensed when there was not a call for
heat. With this fault code the control will also turn on both the
inducer motor and supply air blower. This fault would typically
This indi-
Page 38
650.75-N4U035-14370-000
be caused by a gas valve that leaks through or is slow closing.
2 FLASH:
switch contacts are stuck in the closed position. The control
confirms these contacts are open at the beginning of each
heat cycle. This would indicate a faulty pressure switch or
mis-wiring.
3 FLASH:
contact did not close at the beginning of the heat cycle. This
could be caused by a number of problems; faulty inducer,
blocked vent pipe, high winds at vent terminal, broken pressure switch hose or faulty pressure switch.
4 FLASH:
its normally closed contacts. With this fault code the control
will operate the supply air blower and inducer. This condition
may be caused by: dirty filter, improperly sized duct system,
incorrect blower speed setting, incorrect firing rate or faulty
blower motor.
5 FLASH:
tacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air,
proper inducer operation, primary heat exchanger failure or
burner problem. Be sure to reset the switch after correcting
the failure condition.
This indicates that the normally open pressure
This indicates the normally open pressure switch
This indicates the auxiliary limit switch has opened
This fault is indicated if the normally closed con-
NOTE:
The control will blink one time when initially powered.
This is normal and not an indication of any malfunction.
RESET FROM LOCKOUT:
out condition break the line voltage supply or 24 volt signal
from the thermostat for 30 seconds.
To reset the control from any lock-
Do not try to repair controls. Replace defective
controls with Source 1 Parts.
Never adjust pressure switch to allow furnace
operation.
Never jump pressure switch or rewire in an
attempt to allow furnace operation. To do so will
allow furnace to operate under potentially hazardous conditions.
6 FLASH:
pressure switch opened 5 times during the call for heat. This
could be caused by a number of problems; blocked vent or
combustion air intake, high winds at vent terminal, faulty
inducer, cracked pressure switch hose, or a blockage in the
condensate drainage system.
7 FLASH:
established. This no-light condition occurred 3 times during
the call for heat before locking out. This may be caused by
low gas pressure, faulty gas valve, faulty hot surface igniter
or burner problem.
8 FLASH:
during the heating cycle. This could be caused by low gas
pressure or faulty gas valve.
LED ON CONSTANTLY:
furnace control discovered during its self-check procedure.
Replace the control.
60 MINUTE AUTOMATIC RESET FROM LOCKOUT:
control includes a watchdog type circuit that will reset from a
lockout condition after 60 minutes. Operational faults 6, 7 & 8
will be reset. This provides protection to an unoccupied structure if a temporary conditions exists causing a unit malfunction. An example would be a low incoming gas supply
pressure condition preventing unit operation. When the gas
pressure was restored, at some point the watchdog would
restart the unit and provide heat for the house.
This indicates that after the unit was operating, the
This fault code indicates that flame could not be
This fault is indicated if the flame is lost 5 times