York P*UR 140, P*UR 80, FG9-UP 40, FG9-UP 60, P*UR 60 Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTION
CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . 3
SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . 4
UPFLOW MODELS . . . . . . . . . . . . . . . . . . . . . . . . . 8
DOWNFLOW / HORIZONTAL MODELS -
HORIZONTAL APPLICATION . . . . . . . . . . . . . . . . 11
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ELECTRICAL POWER CONNECTION . . . . . . . . . 13
HIGH EFFICIENCY
GAS-FIRED FURNACES TUBULAR
HEAT EXCHANGER SERIES
UPFLOW MODELS: P*UR / FG9-UP / G9T-UP
40 - 140 MBH INPUT
DOWNFLOW/HORIZONTAL MODELS: P*DH / FG9-DH / G9T-DH
40 - 120 MBH INPUT
COMBUSTION AIR AND VENT SYSTEM . . . . . . . 15
HORIZONTAL VENT APPLICATIONS . . . . . . . . . 24
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . 24
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . 26
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . 27
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . 32
AIRFLOW DATA - UPFLOW . . . . . . . . . . . . . . . . . 33
AIRFLOW DATA - DOWNFLOW/HORIZONTAL . 33
OPERATION AND MAINTENANCE . . . . . . . . . . . 34
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 37
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . 37
WIRING DIAGRAM - UPFLOW MODELS . . . . . . . 39
WIRING DIAGRAM - DOWNFLOW/HORIZONTAL 40
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
START TO INSTALL YOUR FURNACE.
SAVE THIS MANUAL
035-14370-000 REV A (899) Form 650.75-N4U
Page 2
650.75-N4U 035-14370-000
TABLE OF CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . 3
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
NOTES, CAUTIONS & WARNINGS . . . . . . . . . . . . . . . . 3
VENT SAFETY CHECK PROCEDURE . . . . . . . . . . . . . 3
SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . . . . . . . 4
LIMITATIONS & LOCATION . . . . . . . . . . . . . . . . . . . . . .4
CLEARANCES FOR ACCESS . . . . . . . . . . . . . . . . . . . .4
CLEARANCES TO COMBUSTIBLES . . . . . . . . . . . . . . .5
BELOW FREEZING LOCATIONS . . . . . . . . . . . . . . . . . .5
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
UPFLOW MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SUPPLY PLENUM CONNECTION . . . . . . . . . . . . . . . . .8
RETURN DUCT CONNECTION . . . . . . . . . . . . . . . . . . . 9
UPFLOW FILTER INSTALLATION . . . . . . . . . . . . . . . . .9
I
NTERNAL INSTALLATION
S
IDE RETURN
B
OTTOM RETURN
- E
. . . . . . . . . . . . . . . . . . . . . . . . .9
XTERNAL FILTER
. . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DOWNFLOW/HORIZONTAL MODELS
DOWNFLOW APPLICATION . . . . . . . . . . . . . . . . . . . .10
DOWNFLOW FILTERS . . . . . . . . . . . . . . . . . . . . . . . . .10
SUPPLY AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . .11
DOWNFLOW / HORIZONTAL MODELS - HORIZONTAL
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
HORIZONTAL FILTERS. . . . . . . . . . . . . . . . . . . . . . . . 11
ATTIC INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . .11
CRAWL SPACE INSTALLATION . . . . . . . . . . . . . . . . .12
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ELECTRICAL POWER CONNECTION . . . . . . . . . . . . . . .13
ELECTRICAL CONTROL CONNECTIONS . . . . . . . . . . .14
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . . . 15
METHOD ONE: TWO PIPE SEALED COMBUSTION AIR
& VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
COMBUSTION AIR INTAKE/VENT CONNECTIONS 15
COMBUSTION AIR/VENT PIPE SIZING . . . . . . . . . . 16
VENT TERMINATION (2-PIPE). . . . . . . . . . . . . . . . . 16
VENT CLEARANCES (2-PIPE) U.S. ONLY . . . . . . . 17
VENTING MULTIPLE UNITS. . . . . . . . . . . . . . . . . . . 17
PIPING ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . .18
METHOD TWO: ONE PIPE SYSTEM . . . . . . . . . . . . . . 19
COMBUSTION AIR . . . . . . . . . . . . . . . . . . . . . . . . . . .19
A
IR SOURCE FROM OUTDOORS
S
PECIAL COMBUSTION AND VENTILATION
C
ONSIDERATIONS
S
PECIALLY ENGINEERED INSTALLATIONS
C
OMBUSTION AIR QUALITY
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
- . . . . . . . . . . . . . . . . . .20
. . . . . . . . . . . . 20
. . . . . . . . . . . . . . . . . . . . . . 20
VENT PIPE SIZING (1-PIPE SYSTEM) . . . . . . . . . . .21
VENT TERMINATION (1-PIPE SYSTEM) . . . . . . . . .21
VENT TERMINAL LOCATION CLEARANCES . . . . .21
PIPING ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . .23
METHOD THREE: TWO PIPE SYSTEM USING COM­BUSTION AIR FROM A VENTILATED ATTIC SPACE . 23
COMBUSTION AIR INTAKE . . . . . . . . . . . . . . . . . . . 23
COMBUSTION AIR TERMINATION . . . . . . . . . . . . . 23
COMBUSTION AIR REQUIREMENTS. . . . . . . . . . . . 23
VENT PIPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
VENT TERMINATION. . . . . . . . . . . . . . . . . . . . . . . . . 24
HORIZONTAL VENT APPLICATIONS . . . . . . . . . . . . . . . 24
CONDENSATE PIPING 24
C
ONVERSION FOR HORIZONTAL APPLICATIONS
. . . . . . . 25
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
L
IMIT CONTROL
A
UXILIARY LIMIT CONTROLS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
. . . . . . . . . . . . . . . . . . . . . 27
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . 27
IGNITION SYSTEM SEQUENCE . . . . . . . . . . . . . . . . . 27
GAS VALVE OPERATION . . . . . . . . . . . . . . . . . . . . . . 28
CHECKING GAS INPUT (NATURAL GAS) . . . . . . . . . 28
ADJUSTMENT OF MANIFOLD GAS PRESSURE . . . . 29
ADJUSTMENT OF TEMPERATURE RISE . . . . . . . . . . 30
ADJUSTMENT OF FAN-OFF CONTROL SETTINGS . 30
ACCESSORY CONNECTIONS . . . . . . . . . . . . . . . . . . 31
E
LECTRONIC AIR CLEANER CONNECTION
H
UMIDIFIER CONNECTION
. . . . . . . . . . . . . . . . . . . . . . . 31
. . . . . . . . . . . 31
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . 32
AIRFLOW DATA - UPFLOW . . . . . . . . . . . . . . . . . . . . . . 33
AIRFLOW DATA - DOWNFLOW/HORIZONTAL . . . . . . . 33
OPERATION AND MAINTENANCE . . . . . . . . . . . . . . . . . 34
SEQUENCE OF OPERATION. . . . . . . . . . . . . . . . . . . . 34
CONTINUOUS BLOWER . . . . . . . . . . . . . . . . . . . . . . . 34
INTERMITTENT BLOWER - COOLING . . . . . . . . . . . . 34
HEATING CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
H
OT SURFACE IGNITION SYSTEM
. . . . . . . . . . . . . . . . . 34
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
A
IR FILTERS
F
ILTER REMOVAL
F
ILTER REMOVAL
H
ORIZONTAL APPLICATIONS
L
UBRICATION
B
LOWER CARE
B
URNER REMOVAL/CLEANING
C
LEANING THE HEAT EXCHANGER
C
LEANING THE SECONDARY HEAT EXCHANGER
V
ENT/AIR INTAKE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
- U
PFLOW MODELS
- D
OWNFLOW MODELS
. . . . . . . . . . . . . . 35
. . . . . . . . . . . . 35
. . . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . 36
. . . . . . . 37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . 37
WIRING DIAGRAM - UPFLOW MODELS. . . . . . . . . . . . . 39
WIRING DIAGRAM - DOWNFLOW/HORIZONTAL . . . . . 40
2 Unitary Products Group
Page 3
035-14370-000 650.75-N4U
GENERAL INFORMATION
DESCRIPTION
IMPROPER INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALIFIED INST ALLER, SER VICE AGENCY OR THE GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING BUT NOT LIMITED TO, BUILDING, ELECTRICAL AND MECHANICAL CODES.
This Category IV, dual certified, direct vent and 1-pipe vent furnace is designed for residential or commercial installation in a basement, closet, recreation room, garage or other loca­tion provided space temperature is 32°F or higher. For appli­cations in below freezing locations, refer to “BELOW FREEZING LOCATIONS” section on page 5.
INSPECTION
As soon as a unit is received, it should be inspected for possi­ble damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. Also, before installation the unit should be checked for screws or bolts which may have loosened in tran­sit. There are no shipping or spacer brackets which need to be removed.
NOTES, CAUTIONS & WARNINGS
The installer should pay particular attention to the words: NOTE, CAUTION and WARNING. NOTES are intended to
clarify or make the installation easier. CAUTIONS are given to prevent equipment damage. WARNINGS are given to alert the installer that personal injury and/or equipment or property damage may occur if installation procedures are not handled properly.
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard bay be created. Never store items such as
The cooling coil must be installed in the supply air duct, downstream of the furnace. Cooled air may not be passed over the heat exchanger.
the following on, near or in contact with the fur­nace.
VENT SAFETY CHECK PROCEDURE
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
This furnace may not be common vented with any other appliance, since it requires separate, prop­erly-sized air intake and vent lines. The furnace shall not be connected to any type of B, BW or L
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door
vent or vent connector, and not connected to any portion of a factory-built or masonry chimney.
removed. To do so could result in serious personal injury and/or equipment damage.
Unitary Products Group 3
If this furnace is replacing a common-vented furnace, it may be necessary to resize the existing vent line and chimney to
Page 4
650.75-N4U 035-14370-000
prevent oversizing problems for the new combination of units. Refer to the National Gas Code (ANSI Z223.1) or CAN/CGA B149.1 or.2 Installation Code (latest editions).
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1, or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and win­dows and all doors between the space in which the appli­ance(s) is located and other spaces of the building. Turn on clothes dryers. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall oper­ate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
Downflow/horizontal models are AGA/CGA listed for down­flow application into a manufactured (mobile) home.
Upflow models or horizontal applications are not approved for mobile homes.
A manufactured (mobile) home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when this standard is not applica­ble, the Standard for Manufactured Home Installations (Man­ufactured Home Sites, Communities and Set-Ups), ANSI A225.1, and/or CAN/CSA-Z240 MH Series, Mobile Homes.
CLEARANCES FOR ACCESS
Ample clearances should be provided to permit easy access to the unit. The following minimum clearances are recom­mended:
1. Twenty-four (24) inches between the front of the furnace and an adjacent wall or another appliance, when access is required for servicing and cleaning.
2. Eighteen (18) inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue/vent connections.
:
NOTE
In all cases, accessibility clearances shall take prece­dence over clearances for combustible materials where accessibility clearances are greater.
6. After it has been determined that each appliance con­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the venting system must be corrected.
8. Any corrections to the common venting system must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1 or.2 Installation Code (latest edi­tions). If the common vent system must be resized, it should be resized to approach the minimum size as determined using the appropriate tables in Appendix G of the above codes.
SPECIFIC UNIT INFORMATION
LIMITATIONS & LOCATION
This furnace should be installed in accordance with all national and local building/safety codes and requirements, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1 or CAN/CGA B149.1 or.2 Installation Code (latest editions), local plumbing or waste water codes, and other applicable codes.
Do not install the furnace in an unconditioned space or garage that could experience ambient temperatures of 32F (0C) or lower. For application in below freezing locations, See “BELOW FREEZ­ING LOCATIONS” on page 5
The furnace is not to be used for temporary heat­ing of buildings or structures under construction.
This unit must be installed in a level (1/4”) position side-to-side and front-to-back to provide proper condensate drainage.
Do not allow return air temperature to be below 55°F for extended periods. To do so may cause condensation to occur in the main fired heat exchanger.
4 Unitary Products Group
Page 5
035-14370-000 650.75-N4U
vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool posi­tion.
Furnaces shall not be installed directly on carpet­ing, tile or other combustible material other than
The furnace shall be located:
wood flooring. An accessory combustible floor base is available to allow direct installation of downflow models on combustible flooring.
1. Where a minimum amount of air intake/vent pipin elbows will be required.
g and
Furnace shall be installed so the electrical compo­nents are protected from water.
The size of the unit should be based on an acceptable heat loss calculation for the structure.
Check the rating plate to make certain the unit is equipped for the type of gas supplied, and proper electrical characteristics are available.
For installations above 2,000 feet, reduce input 4% for each 1,000 feet above sea level. Refer to Form 650.75-N2.1V for correct pressure switch/orifice or other required conversion information.
A furnace installed in a residential that all burners and burner ignition devices are located not less that 18" above the garage floor, and located or protected to prevent damage by vehicles.
Allow clearances from combustible materials as listed under Clearances to Combustibles, ensuring that service access is allowed for both the burners and blower.
When the furnace is used in conjunction with a cooling coil, the furnace must be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the primary heat exchanger.
When a parallel flow arrangement is used, the dampers or other means used to control air flow shall be adequate to pre-
garage shall be located so
2. As centralized with the air distribution as possible.
3. In an area where ventilation facilities provide for safe lim­its of ambient temperature under normal operating con­ditions. Ambient temperatures must not fall below 32°F (0°C).
4. Where it will not interfere with proper air circulation in the confined space.
5. Where the outdoor combustion air/vent terminal will not be blocked or restricted.
6. Where it will not interfere with the cleanin removal of other appliances.
g, servicing or
CLEARANCES TO COMBUSTIBLES
Minimum clearances from combustible construction are shown in Table 3, “UNIT CLEARANCES TO COMBUSTI­BLES,” on page 8.
BELOW FREEZING LOCATIONS
If this furnace is installed in any area where the ambient tem­perature may drop below 32° F, a UL listed self regulated heat tape must be installed. It is recommended that self regu­lating heat tape rated at 3 watts per foot be used. This must be installed around the condensate drain lines in the uncondi­tioned space. Always install the heat tape per the manufac­turer's instructions. Cover the self-regulating heat tape with fiberglass or other heat resistant, insulating material.
Unitary Products Group 5
Page 6
650.75-N4U 035-14370-000
4
Models P*XU &
G9D—UH
60 / 55 / 1200 / “B”
80 / 75 / 1200 / “B”
1.
C
4
C
12-3/4
16-1/4
16-1/4
19-3/4
19-3/4
19-3/4
23-1/4
2 (3)
23-1/4
2 (3)
1
DIMENSIONS - UPFLOW MODELS: P*UR/FG9-UP/G9T-UP
B
B
45
3/4
3/4
G A S O U T L E T 1-1/4" X 2-1/2" (A ll gas pipe connections 1/2" N P T)
45
B
A
A
20
FRO N T LEFT SIDE
FRO N T LEFT SIDE
A
C
(W IT H K .O . REM OVED )
BO TTO M IM AG E
(F R O N T )
20
D
In ta k e
onnection
B
FRO N T
TO P IM AG E
D
In ta k e
onnection
E
Vent C onnection (v e n t s iz e )
FRONT
28-1/2
TO P IM AG E
23
ALL DIMENSIONS ARE IN INCHES, AND ARE APPROXIMATE.
20
20
G A S O U T L E T 1-1/4" X 2-1/2" (A ll gas pipe connections 1/2" N P T)
OPTIONAL SIDE
OPTIONAL SIDE
RETURN CUT-OUT
RETURN CUT-OUT
(EITHER SIDE)
(EITHER SIDE)
28-1/2
28-1/2
28-1/2
7-5/8
E
Vent C onnection (v e n t s iz e )
3/4" FLANG E
7-5/8
3-1/4
3-1/4
7/8" H O LE POW ER W IRING
POW ER W IRING
1-3/4
1-3/4
T'STAT W IR ING
T'STAT W IR ING
7/8" K .O .
7/8" K.O .
A
C
9-7/8
6-7/8
6-7/8
(W IT H K .O .
23
DRAIN
CONDENSATE
REM O VED)
Models P*UR/
FG9-UP/G9T—UP
40 / 37 / 800 / A 14-1/2
BO TTO M IM A G E
(F R O N T )
60 / 55 / 1000 / B 17-1/2 80 / 75 / 1200 / B 17-1/2
80 / 75 / 1600 / C 21 100 / 95 / 1400 / C 21 100 / 95 / 2000 / C 21
120 / 112 / 2000 / D 24-1/2
140 / 130 / 2000 / D 24-1/2
1.
Vent pipe must be increased to 3” on this model.
4-1/8
4-1/8
7/8" H O LE
9-7/8
CONDENSATE DRAIN
7-5/8
7-5/8
1-1/4
1-1/4
1-3/4
1-3/4
14-1/2
14-1/2
22-3/4
22-3/4
RIGHT SIDE
RIGHT SIDE
3/4"
ABCDE
FLANG E
10-1/8 2 2 13-1/8 2 2 13-1/8 2 2
80 / 75 / 1600 / “C” 21 19
16-5/8 2 2
100 / 95 / 1400 / “C” 21 19
16-5/8 2 2
100 / 95 /2000 / “C 21 19
16-5/8 2 2 20-1/8 3
120 / 112 / 2000 / “D” 24-1/2 23
20-1/8 3
Vent pipe must be increased
1
1
3/
3/
A
17-1/2 16 17-1/2 16
1
FIGURE 1 :
TABLE 1: RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS (P*UR/FG9-UP/G9T-UP)
MODELS P*UR/FG9-UP/
G9T—UP
INPUT
MBH
OUTPUT
MBH
NOM
CFM
.
CABINET
WIDTH
IR
MEAN AIR
CFM
TEMP
RISE
1
A
TEMP
RISE °F
AFUE
@
OUTLET
TEMP
MAX
AIR
.
F
. °
DIA (IN
BLOWER
WIDTH
)
IN
(
MAX
OVER
CURRENT
PROTECT
TOTAL
HP
UNIT
AMPS
.)
40 37 800 14-1/2 92.4 35 - 65 685 165 9 6 1/4 9.0 20 14 60 55 1000 17-1/2 92.2 45 - 75 850 175 10 6 1/3 9.0 20 14 80 74 1200 17-1/2 92.0 35 - 65 1160 165 11 8 1/2 9.0 20 14
80 76 1600 21 94.3 30 - 60 1540 160 11 8 3/4 12.0 20 14 100 93 1400 21 92.2 45 - 75 1465 175 10 10 1/2 9.0 20 14 100 94 2000 21 93.0 30 - 60 1955 160 11 10 1 12.0 20 14 120 112 2000 24-1/2 92.0 45 - 75 1730 175 11 10 1 12.0 20 14 140 130 2000 24-1/2 92.0 45 - 75 2005 175 11 10 1 12.0 20 14
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition). For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V. Wire size based on copper conductors, 60°C, 3% voltage drop. Continuous return air temperature must not be below 55°F.
-
2
MIN
SIZE (AWG
@ 75
ONE WAY
WIRE
)
FT
.
2
6 Unitary Products Group
Page 7
035-14370-000 650.75-N4U
T
B
3/4
C ondensate
D rain A ccess
3-1/4 X 3
45
Air Intake
3-5/8 x 3-5/8
C onn. S ize/
(
G
Pipe S ize)
A
FRO N T LEFT SIDE
B
Power
20
Wiring
7/8" K .O .
1-7/8
E
OP IMAGE/RETURN END
D
FRO N T
Vent C onnection
(v e n t s iz e )
5-3/8
F
1-3/8
3 7/8
BOTTOM IM AG E/SU PPLY END
ALL DIMENSIONS ARE IN INCHES, AND ARE APPROXIMATE.
H
19-1/4
G A S IN L E T
A
C
FRO N T
1-3/8
8
D
20
T'STAT W IR ING
7/8" K .O .
1 -3 /4
5-1/4
3-3/4
G A S IN L E T 1-1/4" X 2-1/2"
2 -3 /4
(V ent C onnection)
35
18-1/2
16-3/4
1-1/4
7 -1 /2
6 -1 /4
4 -1 /8
3-3/4
C ondensate D rain A ccess 3-1/4 X 3
6-1/2
Air Intake
3-5/8 x 3-5/8
C onn. S ize/
(
G
Pipe Size)
1-1/4
ALT. G AS IN LET
1-1/4" X 2-1/2"
2 8 -1 /2
RIGHT SIDE
MODELS P*DH/ FG9-DH/G9TDH
40 /37 / 800 / A 14-1/2 13-1/4 11-3/4 2 5-1/8 2-1/2 2 60 /55 / 1200 / B 17-1/2 16-1/4 14-3/4 2 6-5/8 2-1/4 2 80 /75 / 1200 / B 17-1/2 16-1/4 14-3/4 2 6-5/8 2-1/4 2
80 /75 / 1600 / C 21 19-3/4 18-1/4 2 8-3/8 2-1/4 2
100 /95 / 2000 / C 21 19-3/4 18-1/4 2 8-3/8 2-1/4 2
120 /112 / 2000 / D 24-1/2 23-1/4 21-3/4
1.
Vent pipe must be increased to 3” on this model.
ABCDEFG
1
2 (3)
10-1/8 2-1/4 3
FIGURE 2 : DIMENSIONS - DOWNFLOW/HORIZONTAL MODELS: P*DH/FG9-DH/G9T-DH
TABLE 2: RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS (P*DH/FG9-DH/G9T-DH)
MODELS P*DH/FG9-DH/
1
A
TEMP
RISE °F
INPUT
MBH
G9T—DH
OUTPUT
MBH
CABINET
NOM
CFM
WIDTH
.
AFUE
40 37 800 14-1/2 91.0 25 - 55 856 155 10 6 1/4 9.0 20 14 60 55 1200 17-1/2 91.0 35 - 65 1018 165 11 8 1/2 9.0 20 14 80 75 1200 17-1/2 91.0 35 - 65 1370 165 11 8 1/2 9.0 20 14
80 75 1600 21 91.0 30 - 60 1563 160 11 8 3/4 12.0 20 14 100 95 2000 21 91.0 40 - 70 1582 170 11 10 1 12.0 20 14 120 112 2000 24-1/2 91.0 40 - 70 1885 170 11 10 1 12.0 20 14
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition). For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V. Wire size based on copper conductors, 60°C, 3% voltage drop. Continuous return air temperature must not be below 55°F.
IR
MEAN AIR
CFM
TEMP
RISE
@
OUTLET
TEMP
MAX
AIR
.
BLOWER
DIA
F
. °
(IN)
WIDTH
IN
.)
(
HP
TOTAL
UNIT
AMPS
MAX
OVER
CURRENT
PROTECT
-
2
WIRE
MIN
SIZE (AWG
FT
@ 75
ONE WAY
)
.
2
Unitary Products Group 7
Page 8
650.75-N4U 035-14370-000
TABLE 3: UNIT CLEARANCES TO COMBUSTIBLES
APPLICATION TOP FRONT REAR
UPFLOW 1 3 0 0 0 0 COMBUSTIBLE YES YES YES NO
DOWNFLOW / HORIZONTAL MODELS (P*DH / FG9-DH / G9T-DH)
DOWNFLOW130000
HORIZONTAL 0 3 0 1 1 0
1.
Special floor base or air conditioning coil required for use on combustible floor.
2.
Minimum of 8” clearance required to install condensate removal system.
3.
Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building joists, studs or framing.
LEFT SIDE
UPFLOW MODELS (P*UR / FG9-UP / G9T-UP)
RIGHT
SIDE
FLUE
FLOOR/
BOTTOM
1
1"
COMBUSTIBLE
CLOSET ALCOVE ATTIC
YES YES YES NO
2
NO YES YES
When the furnace is used in conjunction with a cooling coil, the furnace must be installed parallel with, or on the upstream side of the cooling unit to avoid condensation in the primary heat exchanger.
If this unit is installed in an unconditioned space and an extended power failure occurs, there will be potential damage to the condensate trap, drain lines and internal unit components. Following a power failure situation,
Do Not Operate the Unit
Until Inspection and Repair Are Performed.
When a parallel flow arrangement is used, the dampers or other means used to control air flow must be adequate to pre­vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operating of either unit unless the damper is in the full heat or cool posi­tion.
LINE CON­TACT
YES
3
DUCTWORK
The duct system's design and installation must:
1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace spec­ifications.
2. Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90A and 90B (latest editions) or appli­cable national, provincial, local fire and safety codes.
3. Create a closed duct system. The supply duct system must be connected to the furnace outlet and the return duct system must be connected to the furnace inlet. Both supply and return duct systems must terminate outside the space containing the furnace.
4. Generally complete a path for heated or cooled air to cir­culate through the air conditioning and heating equip­ment and to and from the conditioned space.
UPFLOW MODELS
SUPPLY PLENUM CONNECTION
Attach the supply plenum to the fur­nace outlet duct connection flanges. This is typically through the use of S cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage.
If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. Follow the coil instructions for installing the supply plenum.
On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi­cate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to pre­vent leaks.
The cooling coil must be installed in the supply air duct downstream of the furnace.
8 Unitary Products Group
Page 9
035-14370-000 650.75-N4U
g
g
g
g
g
g
g
g
g
g
F
RETURN DUCT CONNECTION
Return air may enter the furnace through the side(s) or bot­tom depending on the type of application.
not be connected into the rear panel of the unit.
Return air may
See the specific type application installation for details. Be sure to see the Filters section of this instruction.
CLIPS
POSITION WIRE RETAINER (PROVIDED) UNDER FLANGE
FILTER
(PROVIDED
UPFLOW FILTER INSTALLATION
All applications require the use of a filter. A high velocity filter and retainer are provided for field installation.
Internal Installation
1. Select desired filter position (left/ri
Remove the correspondin
cabinet cut-outs per instruc-
ht side, or bottom).
tions provided.
2. Install snap-in retainer clips into the correspondin
from the outside rear of the cabinet (Refer to Fi To prevent cabinet air leaks, install snap-in plu
slots
ure 3.)
s (pro­vided) into the unused slots at the outside rear of the cabinet.
FURNACE
(REAR CABINET)
LEFT
RIGHT SIDE SLOTS
BOTTOM SLOTS CABINET SLOT
FILTER SUPPORT CLIPS (PROVIDED)
SIDE SLOTS
PLUG UNUSED CABINET SLOTS WITH PLUGS (PROVIDED)
RIGHT SIDE INSTALLATION SHOWN
FURNACE
FRONT
FIGURE 4 : SIDE FILTER RETAINER PLACEMENT
5. Position the filter between the wire retainer and the cabi­net wall (or floor) so it completely covers the cabinet air opening and secure the filter in place at the front of the cabinet by fastening the closed (looped) end of the retainer wire under the flanged edge of the cabinet. When properly installed the filter should fit flush with all four sides of the cabinet wall.
NOTE:
Air velocity through throw-away type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.
Side Return - External Filter
Locate and knock out the square corner locators. These indi­cate the size of the cutout to be made in the furnace side panel (Refer to Figure 5).
FIGURE 3 : FURNACE FILTER SLOT LOCATIONS
3. Install the wire retainer inside the cabinet. Insert the open ends of the wire retainer into the clip loops at the rear of the blower compartment. The retainer wire should pivot freely like a hin cabinet. (Refer to Fi
4. Install the filter(s) provided. Cut filter if necessary to match air openin beyond openin from bypassin from inside the filter. Shorten the rods, if necessary, to match final filter size.
Unitary Products Group 9
e, on the clips at the rear of the
ure 4.)
in cabinet. Filter should extend
edge as much as possible to prevent air
the filter. DO NOT remove stiffening rods
FR O N T O FU RN A CE
CORNER MARKINGS
FIGURE 5 : SIDE RETURN CUTOUT MARKINGS
Install the side filter rack following the instructions provided with that accessory. If a filter(s) is provided at another loca­tion in the return air system, the ductwork may be directly attached to the furnace side panel.
Page 10
650.75-N4U 035-14370-000
NOTE:
Some accessories such as electronic air cleaners and
pleated media may require a larger side opening.
DOWNFLOW/HORIZONTAL MODELS­DOWNFLOW APPLICATION
DOWNFLOW FILTERS
A top return filter rack is supplied with
All installations must have a filter installed.
The return duct may be attached to the furnace by S-cleat, bend tabs or other approved methods. Be sure to seal the duct to the furnace to prevent air leakage.
Those applications over 1800 CFM require either return from two sides, one side and the bottom, or bottom only. For bot­tom only application, see data and notes on blower perfor­mance data tables in this manual.
Where the return duct system is not complete, the return con­nection must run full size to a location outside the utility room or basement. For further details, consult Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1, or CAN/CGA B149.1 or.2, Installation Code ­latest editions.
Bottom Return
Bottom return applications normally pull return air throu
gh a base platform or return air plenum. Be sure the return plat­form structure is suitable to support the weight of the furnace. Be sure to seal the furnace to plenum connection to prevent air leakage. (Refer to Figure 3 on page 9) and (Refer to Table 1 on page 6).
The bottom panel is equipped with a perforated opening for easy removal. Tabs must be cut with sheet metal snips to allow removing knock-out. Scribe marks are included for forming flanges for attachment of the return air ductwork.
NOTE:
If an external mounted filter rack is being used, see the instructions provided with that accessory for proper hole cut size.
Upflow attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.
A
DUCTW ORK
FIGURE 6 : DOWNFLOW FILTERS
the furnace. Two 14" x 20" permanent washable filters are supplied with each unit.
Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air duct.
Any branch duct must attach to the ver­tical ductwork above the filter height (FH) and for proper installation refer to Figure 6.
F IL T E R R A C K (FACTO RY SU PPLIED )
R A C K A N D F IL T E R S S E C U R E D
A
NOTE: FILTER ACCESS THRU DUCT­W O RK M UST BE PRO VIDED FOR REMOVAL AND CLEANING
C R O S S S E C T IO N A -A (W ITH PLENU M AND FILTERS)
IN SIDE BLO W ER SECTIO N FO R S HIPM EN T
C A S IN G S IZ E D IM E N S IO N F H 1 4 -1 /2 " 1 3 -1 /4 " 1 7 -1 /2 " 1 2 -1 /2 " 2 1 " 1 1 - 1 /2 " 2 4 -1 /2 " 9 -3 /4 "
FILTER S
FILTER RACK
BRANCH DUCTS
FH
10 Unitary Products Group
The filter rack (provided) should be secured to the center of the front and rear flanges at the furnace top. Drill a hole through the front and rear duct flange into the filter rack and secure it with a sheet metal screw.
Refer to the unit rating plate for furnace model then see the dimensions page of this instruction for return air plenum dimensions. Install the plenum following instructions under Ductwork in this instruction.
Page 11
035-14370-000 650.75-N4U
VENT (MAINTAIN REQUIRED CLEARANCES TO COMBUSTIBLES)
GAS PIPING
SEDIMENT TRAP
12"
30" MIN WORK AREA
SHEET METAL IN FRONT OF FURNACE COMBUSTION AIR OPENINGS IS RECOMMENDED
RETURN AIR
SUPPLY AIR
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY THE INTERSECTION OF FURNACE TOP AND TWO SIDES AND BUILDING JOISTS, STUDS OR FRAMING
DOWNFLOW / HORIZONTAL MODELS ­HORIZONTAL APPLICATION
DOWNFLOW FURNACE
WARM AIR PLENUM WITH 1" FLANGES
FIBERGLASS INSULATION
FIBERGLASS TAPE UNDER FLANGE
COMBUSTIBLE FLOOR BASE ACCESSORY
FIGURE 7 : COMBUSTIBLE FLOOR BASE
ACCESS’Y
SUPPLY AIR DUCTS
Installations on combustible material or floors must use a combustible floor base (shown in Figure 7 - 1CB0314, 17, 21 & 24) as specified on the rating plate or a matching cooling coil. Follow the instructions supplied with the combustible floor base accessory.
This base can be replaced with a matching cooling coil, prop­erly sealed to prevent leaks. Follow the cooling coil instruc­tions for installing the plenum.
Downflow furnaces may be installed horizontally with the sup­ply airflow toward the left or right by laying the unit on the left or right side panel.
Do not install the unit on the rear panel.
After determining the best orientation, lay the unit on top of the shipping carton to protect the finish. The appropriate elec­trical knock-outs for power wiring, control wiring and gas pip­ing should be removed at this time.
For horizontal application, return air may enter through the end only.
Return air may not be connected into the rear
panel of the unit.
HORIZONTAL FILTERS
All filters and mounting provision must be field supplied. Fil­ters(s) may be located in the duct system external to the fur­nace or in a return filter grille(s).
ATTIC INSTALLATION
All downflow application supply duct systems must be designed and installed in accordance with the standards of NFPA 90A and 90B, and/or all local codes.
Unitary Products Group 11
FIGURE 8 : TYPICAL ATTIC INSTALLATION
Page 12
650.75-N4U 035-14370-000
g
This appliance is design certified for line contact for furnaces installed horizontally. The intersection of the furnace top and sides form a line. This line may be in contact with combustible material. Refer to “Where it will not interfere with the cleanin servicing or removal of other appliances." Section on page 5 in this manual for additional information.
Secure a platform constructed of plywood or other building material to the floor joists. Sheet metal, 12" in front of the fur­nace combustion air openings is recommended. (Refer to Figure 9.)
Note:
The unit must be elevated to allow clearnace fo the
condensate trap and drain pipe
. .
If this furnace is installed over a finished space, a condensate safety pan must be installed.
adequate height to ensure the unit will not be subject to water damage.
,
When suspending the furnace from rafters or floor joists using rod, pipe or straps, refer to Physical Data and,Table 3, “UNIT CLEARANCES TO COMBUSTIBLES,” on page 8, for furnace weights to determine suitable means of suspension.
Angle supports should be placed at the supply aire end and near the blower deck. (Refer to Figure 9.)
Do not support
at return air end of unit.
Units may also be suspended by using straps or other mate­rial at the same location. All four suspension points must be level to ensure quiet furnace operation.
In any application where temperatures below freezing are possible, See “BELOW FREEZING LOCATIONS” on page 5
GAS PIPING
When a furnace is installed in an attic or other insulated space, keep all insulating materials at least 12" away from furnace and burner combus­tion air openings.
NOTE:
See crawl space installation for suspending the fur­nace in attic installations.
ANGLE IRON BRACKET
1" MAX BETWEEN ROD & FURNACE
6" MIN BETWEEN ROD & FURNACE
SUPPORT ROD
1" MAX BETWEEN ROD & FURNACE
FIGURE 9 : TYPICAL FURNACE INSTALLATION
USING SUSPENSION MATERIALS
CRAWL SPACE INSTALLATION
The furnace can be hung from floor hoists or installed on suit­able blocks or pad. Blocks or pad installations shall provide
The gas supply must be installed in accordance with the cur­rent National Fuel Gas Code, ANSI Z223.1 (in the U.S.) or CAN-B149.1 or.2 (in Canada) installation codes and all appli­cable local and utility requirements. All pipe and fitting mate­rial, pipe size and installation procedures must comply with the appropriate code. Some utilities may require larger pipe sizes than shown in the code. Gas piping may be connected from either side of the furnace. Each side of the unit has two gas pipe entry knockouts.
For downflow/horizontal models,
piping before determining the correct gas pipe entry
plan your combustion air
. Use 90 degree service elbow(s), or short nipples and conventional 90 degree elbow(s) to enter through the cabinet access holes..
An overpressure protection device, such as a pressure regulator, which conforms to the National Fuel Gas Code, ANSI Z223.1 (U.S.) or CAN­B149.1 or.2 (Canada) and acts to limit the down­stream pressure to a value that does not exceed
0.5 PSI (14" w.c.), must be installed in the gas pip­ing system upstream of the furnace. Failure to do so may result in a fire or explosion or cause dam­age to the furnace or some of its components.
12 Unitary Products Group
Page 13
035-14370-000 650.75-N4U
g
G
NOTE
An accessible manual shutoff valve must be installed
:
upstream of the furnace gas controls and within 6 feet of the furnace.
The installation of a ground joint union and drip leg are required. (Refer to Figure 10.) Maximum and minimum sup­ply gas pressures are shown below.
INLET GAS PRESSURE RANGE
Natural Gas Propane (LP)
Minimum 4.5 In. W.C. 11 In. W.C.
Maximum 13.8 In. W. C. 13.8 In. W.C.
EXTERNAL M ANUAL
SH U TOFF VALVE
TO G AS SUPPLY
DROP LEG
GROUND JOINT UNION
M AY BE IN S TALLE D
IN S ID E O R O U T S ID E U N IT
GAS VALVE
TO G AS SUPPLY
DROP LE
FIGURE 10 : GAS PIPING
NOTE
A 1/8” NPT plug is included in the inlet side of the gas
:
valve for measuring incoming gas pressure.
The furnace must be isolated from the gas supply piping sys­tem by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 psig (3.48 kPa).
Compounds used on threaded joints of gas piping must be resistant to the action of liquefied petro­leum gases. After connections are made, leak-test all pipe connections.
After all gas piping connections are completed, leak test all joints, fittings and furnace connections with rich soap and water solution, commercially available bubble type leak detection fluid, or other approved means.
Do not use an open flame or other source of igni­tion for leak testing.
ELECTRICAL POWER CONNECTION
Field wiring to the unit must conform to and be grounded in accordance with the provisions of the National Electrical Code ANSI/NFPA No. 70-latest edition, Canadian Electric Code C22.1 Part 1 - (latest edition) and/or local codes. Elec­tric wires which are field installed shall conform with the tem­perature limitation for 63°F/35°C rise wire when installed in accordance with instructions. Specific electrical data is given for the furnace on its rating plate and in Refer to Table 1 on page 6.
Provide a power supply separate from all other circuits. Install overcurrent protection and disconnect switch per local/ national electrical codes. The switch should be close to the unit for convenience in servicing. With the disconnect switch in the OFF position, check all wiring against the unit wiring label. Also, see the wiring diagram in this instruction.
NOTE
The furnace’s control system depends on correct
:
polarity of the power supply and a proper ground connection. “FURNACE CONTROL DIAGNOSTICS" Section on pa for symptoms of reversed power supply polarity.
e37
The furnace and its individual shutoff valve must be discon­nected from the gas supply piping system during any pres­sure testing of that system at test pressures in excess of 1/2 psig (3.48 kPa).
Never apply a pipe wrench to the body of the com­bination automatic gas valve. A wrench must be placed on the projection or wrench boss of the valve when installing piping to it.
Unitary Products Group 13
Use copper conductors only.
Connect the power supply as shown on the unit wiring label on the inside of the blower compartment door and Figures 11 & 12. The black furnace lead must be connected to the L1 (hot) wire from the power supply. The white furnace lead must be connected to neutral. Also, the green equipment ground wire must be connected to the power supply ground.
Remove the screws retaining the wiring box cover. Route the power wiring through the unit top panel with a conduit con-
Page 14
650.75-N4U 035-14370-000
nector or other proper connection. Make wiring connections, (Refer to Figure 11.) Replace the wiring box cover and screws.
L1
(HOT)
N
BLK
GRD
WHI
GRN
WIRING INSIDE JUNCTION BOX
: BLK/BLK
WHI/WHI
GRN/GRN
JUNCTION BOX
BURNER COMPARTMENT
DOOR SWITCH
TRANSFORMER
IGNITION MODULE
G
R
W
C
Y
Y
HUM
EAC
XFMR
LINE
CIR
HUM
EAC
XFMR
LINE
PARK
PARK
HEAT
COOL
CLASS 2 SYSTEM CONTROL WIRING TO THERMOSTAT
L1
(HOT)
JUNCTION BOX
N
GRD
WHI
BLK
GRN
WIRING INSIDE JUNCTION BOX
: BLK/BLK
WHI/WHI
GRN/GRN
BLOWER COMPARTMENT
VENT PIPE
C
O
O
L
H
E
A
T
P
A
R
K
P
A
R
K
L
I
N
E
X
F
M
IGNITION MODULE
R
E
A
C
H
U
M
C
I
R
L
I
N
E
X
F
M
R
E
A
C
H
U
M
Y
Y
C
R
W
G
CLASS 2 SYSTEM CONTROL WIRING TO THERMOSTAT
FLUE CHASE
TRANSFORMER
DOOR SWITCH
BURNER COMPARTMENT
FIGURE 12 : DOWNFLOW / HORIZONTAL MODELS
(P*DH / FG9-DH / G9T-DH) ELECTRI­CAL WIRING
BLOWER COMPARTMENT
FIGURE 11 : UPFLOW MODELS (P*UR / FG9-UP /
G9T-UP) ELECTRICAL WIRING
An alternate wiring method is to use a field provided 2 x 4 box and cover on the outside of the furnace. Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel.
NOTE:
The power connection leads and wiring box on upflow units may be relocated to the left side of the furnace. Remove the screws and cut wire tie holding excess wiring. Reposition on the left side of the furnace and fasten using holes pro­vided.
ELECTRICAL CONTROL CONNECTIONS
Install the field-supplied thermostat. The thermostat instruc­tions for wiring are packed with the thermostat. With the ther­mostat set in the OFF position and the main electrical source disconnected, complete the low-voltage wiring from the ther­mostat to the terminal board on the ignition module. Connect Class 2 control wiring as shown in Figures 13 & 14. Electronic thermostats may require a common connection as shown dashed in Figure 14.
Set the heat anticipator in the room thermostat to .45 amps. Setting it lower will cause short cycles. Setting it higher will cause the room temperature to exceed the setpoints
FIGURE 13 : POWER WIRING CONNECTIONS
ROOM THERMOSTAT
R W
G
Y
C
FURNACE CONTROL
R
W G
Y
C
CONDENSING UNIT
TO AIR CONDITIONER
CONTROLS
FIGURE 14 : TYPICAL HEATING AND COOLING
14 Unitary Products Group
Page 15
035-14370-000 650.75-N4U
g
g
g
g
R
NOTE.
Some electronic thermostats do not have adjustable
heat anticipators. They may have other type cycle rate
vent connection (top right of unit) back to the outdoors. Refer to Figure 15 and Figure 16.
adjustments. Follow the thermostat manufacturer's instruc­tions.
The 24-volt, 40 VA transformer is sized for the furnace com­ponents only , and should not be connected to power auxiliary devices such as humidifiers, air cleaners, etc. The trans­former may provide power for an air conditioning unit contac­tor.
COMBUSTION AIR AND VENT SYSTEM
This furnace is certified to be installed with one of three possible intake/vent configurations.
1. Two-pipe with a sealed combustion intake/vent system outdoor combustion air.
usin
2. Sin
3. Two-pipe intake/vent system usin
Be sure to follow the appropriate venting section details, related information and limitations for your type of installation.
le pipe vent system using combustion air from the
area surroundin
the furnace.
combustion air from a
ventilated attic space and a vent pipe to the outside.
Furnace Intake / Vent Connection Size (All Models)
40 - 100 MBH 120 - 140 MBH
Intake 2” 3"
Vent 2”
1
2"
C O M B U S T IO N A IR P IP E
PASSES THRO UG H TO P PANEL
CONNECTS TO COLLAR O N T O P O F B U R N E R B O X
VENT PIPE
IN T O S O C K E T J U S T UND ER TO P PAN EL
O FF
O N
M
P
C
132
CEMENTS
FIGURE 15 : UPFLOW A IR INTAKE/VENT LOCATIONS
(MODELS P*UR / FG9-UP /G9T-UP)
VENT PIPE PASSES THRO UG H TOP PANEL
COOL HEAT PARK PARK LINE XFMR EAC HUM
CIR LINE XFMR EAC HUM
YWRG
C
1.
Vent must be increased to 3" on this model.
Note 1: Any vent pipe size change must be made out-
side furnace casing in a vertical pipe section to allow proper drainage of condensate.
Note 2: An offset using two 45 degree elbows will be
required for plenum clearance when the vent is increased to 3”.
METHOD ONE: TWO PIPE SEALED COMBUSTION AIR & VENT SYSTEM
COMBUSTION AIR INTAKE/VENT CONNECTIONS
This type installation requires outdoor combustion air. Two separate, properly-sized pipes must be used. One bringing air from the outdoors to the furnace combustion air intake col­lar on the burner box, and a second pipe from the furnace
OPTIONAL L E F T S ID E COM BUSTION AIR PIPE RO UTING
COM BUSTION AIR PIPE CONNECTS TO CO LLAR ON BOTTOM OF BURNE BOX
FIGURE 16 : DOWNFLOW / HORIZONTAL AIR
INTAKE/VENT LOCATIONS (MODELS P*DH / FG9-DH /G9T-DH)
The intake/vent should be located either through the wall (horizontal or side vent) or through the roof (vertical vent). Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air from enter­ing or combustion products from leaving the terminal.
Also, the terminal assembly should be located as far as pos­sible from a swimming pool or a location where swimming pool chemicals might be stored. Be sure the terminal assem­bly follows the outdoor clearances listed in Table 3 for U.S. installations: In Canada, refer to CAN/CGA-B149.1 or.2
Unitary Products Group 15
Page 16
650.75-N4U 035-14370-000
Installation Code (latest edition-Venting Systems and Air Supply).
COMBUSTION AIR/VENT PIPE SIZING
To select the proper size piping for combustion air intake and venting, refer to Table 4 or Table 5. The size will be deter­mined by a combination of furnace model, total length of run, and the number of elbows required. The following rules must also be observed.Long radius elbows are required for all units.
1. Long radius elbows are required for all units.
2. Elbows are assumed to be 90 degrees. Two 45 degree elbows count as one 90 degree elbow.
3. Elbow count refers to combustion air piping and vent pip­ing separately. For example, if the table allows for 5 elbows, this will allow a maximum of 5 elbows in the combustion air piping and a maximum of 5 elbows in the vent piping.
4. Three vent terminal elbows (two for vent pipe and one for air intake pipe) are already accounted for and should not be counted in the allowable total indicated in the table (see vent termination section). These parts are shown shaded.
For downflow/horizontal models only two additional elbows are also accounted for and also should not be counted. These parts are shown shaded.
5. Combustion air and vent piping must be of the same diameter.
6. All combustion air/vent pipe and fittings must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards D1785 (Schedule 40 PVC), D2665 (PVC­DWV), F891 (PVC-DWV Cellular Core). D2241 (SDR-21 and SDR-26 PVC), D2261 (ABS-DWV), or F628 (Sched­ule 40 ABS. Pipe cement and primer must conform to ASTM Standards D2564 (PVC) or D2235 (ABS).
7. The use of flexible connectors or no hub connectors in the vent system is not allowed. This type connection is allowed in the combustion air pipe near the furnace for air conditioning coil accessibility.
TABLE 4: INTAKE/VENT PIPING - 2 PIPE SYSTEM
Models P*UR/
FG9-UP/G9T-UP
40 / 37 / 800 / A 60 / 55 / 1000 / B 80 / 75 / 1200 / C 80 / 75 / 1600 / C
100 / 95 / 1400 / C 100 / 95 / 2000 / C
40 / 37 / 800 / A 60 / 55 / 1000 / B 80 / 75 / 1200 / C 80 / 75 / 1600 / C
100 / 95 / 1400 / C 100 / 95 / 2000 / C
120 / 112 / 2000 / D
140 / 130 / 2000 / D
1.
Elbow count does not include the elbows required for the termination. See Step 4 under Combustion Air/Vent Pipe Sizing
Pipe Size
3" Only 6 5 4 N/A
Max. Elbows vs. One Way Vent
Length (Ft.)
5 - 40 45 50 75
2”654N/A
3”8765
1
TABLE 5: INT AKE/VENT PIPING 2-PIPE SYSTEM
Models P*DH/
FG9-DH/G9T-DH
40 /37 / 800 / A 60 /55 / 1200 / B 80 /75 / 1200 / B 80 /75 / 1600 / C
100 /95 / 2000 / C
40 /37 / 800 / A 60 /55 / 1200 / B 80 /75 / 1200 / B 80 /75 / 1600 / C
100 /95 / 2000 / C
120 /112 / 2000 / D 3" Only 6 5 4 N/A
1.
Elbow count does not include (2) 90 ° elbows required to pipe intake into burner box or those required for the termination. See Step 4 under Combustion Air/Vent Pipe Sizing
Pipe Size
2” 6 5 4 N/A
3” 8 7 6 5
Max. Elbows vs. One Way
Vent Length (Ft.)
5-30 35 40 60
1
16 Unitary Products Group
VENT TERMINATION (2-PIPE)
Side wall horizontal vent terminals and roof mounted vertical terminals may be field fabricated. Standard PVC/SRD fittin
gs may be used. Terminal configuration must comply as detailed in this section.
Page 17
035-14370-000 650.75-N4U
g
g
g
g
VENT
OVERHANG
COMBUSTION AIR
12" SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT
MAINTAIN 12" CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATER
12" MINIMUM
90°
VENT
OVERHANG
COMBUSTION AIR (ELBOW PARALLEL TO WALL)
12" SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT
MAINTAIN 12" CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATER
12" MINIMUM
90°
NOTE
Combustion air and vent pipes must terminate
:
together in the same atmospheric zone, either through a roof or sidewall.
NOTE
Accessory concentric intake/vent terminations,
:
models 1CT0302 and 1CT0303 are available and approved for use with these furnaces. Refer to Form
650.75-N2.4V for installation details.
When selecting the location for combustion air/vent termina­tion the following should be considered:
1. Comply with all clearance requirements as listed below.
2. Termination should be positioned where vent vapors will not dama
e plants or shrubs or air conditioning equip-
ment.
3. Termination should be located where it will not be affected by wind allow recirculation of flue
usts, light snow, airborne leaves or
ases.
4. Termination should be located where it will not be dam-
ed or exposed to flying stones, balls, etc.
a
5. Termination should be positioned where vent vapors are not objectionable.
17 to Figure 22. Sidewall termination may require sealing or shielding of building surfaces with a corrosive resistance material to protect against combustion product corrosion.
FIGURE 17 : HORIZONTAL TERMINATION CON-
FIGURATION WITH 12” MINIMUM CLEARANCE
VENT CLEARANCES (2-PIPE) U.S. ONLY
Dryer Vent. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft.
Plumbing Vent Stack. . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft.
Gas Appliance Vent Terminal . . . . . . . . . . . . . . . . . . . 3 ft.*
From any mechanical fresh air intake. . . . . . . . . . . . . . 1 ft.
From any door, window or non-mechanical fresh air or
combustion air intake . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ft.
Above grade and anticipated snow depth. . . . . . . . . . . 1 ft.
Above grade when adjacent to public walkway. . . . . . . 7 ft.
From electric, gas meters, regulators and relief equipment -
min. horizontal distance . . . . . . . . . . . . . . . . . . . . . . . . 4 ft.
* Does not apply to multiple installations of this furnace
model. Refer to “VENTING MULTIPLE UNITS" Section on page 17 .
FIGURE 18 : HORIZONTAL TERMINATION RAISED
CONFIGURATION FOR ADDITIONAL CLEARANCE
VENTING MULTIPLE UNITS
In Canada, refer to CAN/CGA-B149.1 or.2 Installation Code (latest edition - Venting Systems and Air Supply)
NOTE
Consideration must be given for degradation of build-
:
Each unit must have its own intake/vent piping and termina­tion. Do not use common pipes for combustion air or venting. The vent terminals must be located as shown in Figure 21 and FIGURE 22.
ing materials by flue gases.
NOTE
Shaded components of the combustion air/vent sys-
:
tem shown in the following figures are considered to be part of the vent terminal. These components should not be counted when determining piping limitations. Refer to Figure
Unitary Products Group 17
Page 18
650.75-N4U 035-14370-000
R
OVERHANG
12" MINIMUM
VENT
90°
COMBUSTION AIR
18" MAXIMUM
12" SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT
MAINTAIN 12" CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATE
FIGURE 19 : HORIZONTAL TERMINATION CON-
FIGURATION WITH HORIZONTAL EXTENSION
12" VERTICAL SEPARATION BETWEEN COMBUSTION AIR AND VENT
VENT
COMBUSTION AIR
6"
FIGURE 22 : DOUBLE ROOFTOP TERMINATION
PIPING ASSEMBLY
The final assembly procedure for the vent/combustion air pip­ing is as follows:
1. Cut piping to the proper length, beginning at the furnace.
2. Deburr the piping inside and outside.
3. Chamfer the outer edges of the piping.
4. Dry-fit the entire vent/combustion air piping assembly.
MAINTAIN 12" MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24" ABOVE ROOF
FIGURE 20 : VERTICAL TERMINATION
VENT
COMBUSTION AIR
2"
FIGURE 21 : DOUBLE SIDEWALL TERMINATION
5. Disassemble the piping and apply cement primer and cement per the cement manufacturer's instructions. Primer and cement must conform to ASTM D2564 for PVC, or ASTM D2235 for ABS piping.
Solvent cements are flammable and must be used in well-ventilated areas only . Keep them away from heat, sparks and open flames (including pilots). Do not breathe vapors and avoid contact with skin and eyes.
6. All joints must be made to provide a permanent, air-tight, water-tight seal.
7. Support the combustion air and vent piping such that it is angled 1/4” per linear foot so that condensate will flow back toward the furnace. Piping should be supported with pipe hangers to prevent sagging. Maximum spacing between hangers is five (5) feet, except SDR-PVC pip­ing, where maximum spacing is three (3) feet.
8. Seal around the openings where the combustion air and vent piping pass through the roof of side wall.
18 Unitary Products Group
Page 19
035-14370-000 650.75-N4U
S
VENT PIPE PASSES THRO UG H TOP PANEL
COOL HEAT
Vent piping must be insulated with 1/2” Armaflex insulation if it will be subjected to freezing temper­atures such as routing through unheated areas or through an unused chimney.
PARK PARK LINE XFMR EAC HUM
CIR LINE XFMR EAC HUM
YWRG
C
When combustion air pipe is installed above a sus­pended ceiling, the pipe must be insulated with 1/ 2” Armaflex type insulation. The combustion air pipe should also be insulated when it passes through a warm, humid space.
Note
Vent pipe must be sloped 1/4” per foot to allow conden-
:
G AS PIPIN G KNO CKO U TS
sate to flow back to the furnace.
METHOD TWO: ONE PIPE SYSTEM
This type installation will use combustion air from within the space surrounding the furnace. This may be from within the space in a non-confined location or it may be brought into the furnace area from outdoors. It is not directly ducted into the furnace. A single, properly sized pipe from the furnace vent connector to the outdoors must be provided.
For upflow models combustion air is brought into the furnace through the unit top panel opening. It is not necessary to install a pipe into the intake collar on top of the burner box. Refer to Figure 23 .
COMBUSTION AIR
VENT PIPE
INTO SOCKET JUST UNDER TOP PANEL
OFF
ON
M P
C
132
CEMENT
C O M B U S T IO N A IR
FIGURE 24 : DOWNFLOW / HORIZONTAL VENT
PIPE CONNECTION (P*DH/ FG9-DH / G9T-DH)
For downflow/horizontal models, remove a minimum of two gas piping knockouts for combustion air access. It is not nec­essary to install a pipe into the intake collar on bottom of the burner box. For details, refer to Figure 24.
COMBUSTION AIR
All installations must comply with Section 5.3, Air for Com­bustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or.2 Installation Code - latest editions.
An unconfined space
Btu/hr input rating for all appliances installed in that area. Rooms communicating directly with the space containing the
appliances are considered part of the unconfined space, if openings are not furnished with doors.
A confined space
1000 Btu/hr input rating for all appliances installed in that area.
is not less than 50 cubic feet per 1000
is an area with less than 50 cubic feet per
FIGURE 23 : UPFLOW VENT PIPE CONNECTION
(P*UR / FG9-UP / G9T-UP)
For downflow/horizontal models combustion air is brought into the furnace through the unit side panel openings.
Unitary Products Group 19
The following must be considered to obtain proper air for combustion and ventilation in confined spaces.
Air Source from Inside the Building -
Two permanent openings, one within 12 inches of the top of the confined space and one within 12 inches of the bottom, shall each have a free area of not less than one square inch per 1,000
Page 20
650.75-N4U 035-14370-000
g
Btuh of total input rating of all appliances located in the space. The openings shall communicate freely with interior areas having adequate infiltration from the outside.
NOTE
At least 100 square inches free area shall be used for
:
each opening.
Air Source from Outdoors -
1. Two permanent openings, one within 12 inches of the top of the confined space and one within 12 inches of the bottom, shall communicate directly, or by means of ducts, with the outdoors or to such crawl or attic spaces that freely communicate with the outdoors.
Vertical Ducts -
a.
Each opening must have a free area of not less than one square inch per 4,000 Btuh of total input of all appliances located in the space.
EXAMPLE:
Total Input of All Appliances
4000
Horizontal Ducts -
b.
= Square Inches Free Area
Each openin
must have a free area of not less than one square inch per 2,000 Btuh of total input of all appliances located in the space.
NOTE
Ducts must have the same cross-sectional area as
:
the free area in the opening to which they are connected. The minimum dimension of rectangular ducts shall be three inches.
TABLE 6: ESTIMATED FREE AREA
Wood or Metal
Louvers or Grilles
2
Screens
1.
Do not use less than 1/4 in. mesh
2.
Free area or louvers an grilles varies widely; installer should follow louver or grille manufacturer’s instruc­tions.
Wood 20-25% Metal 60-70%
1/4 in. mesh or larger 100%
Special Combustion and Ventilation Considerations
Operation of a mechanical exhaust, such as an exhaust fan, kitchen ventilation system, clothes dryer or fireplace may cre­ate conditions requiring special attention to avoid unsatisfac­tory operation of gas appliances.
Specially Engineered Installations
The above requirements shall be permitted to be waived where special engineering, approved by the authority having jurisdiction, provides an adequate supply of air for combus­tion, ventilation and dilution of flue gases.
Combustion Air Quality
The recommended source of combustion air is to use the out­door air supply. Excessive exposure to contaminated com­bustion air will result in safety and performance related problems. However, the use of indoor air in most applications is acceptable, except as follows:
1 1
2. One permanent opening, commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appli­ance. The opening shall communicate through a vertical or horizontal duct to the outdoors, or spaces (crawl or attic) that freely communicate with the outdoors and shall have a minimum free area of:
a. 1 sq. in. per 3000 Btu per hr of the total input rating
of all equipment located in the enclosure.
b. Not less than the sum of the areas of all vent con-
nectors in the confined space.
3. Louvers, Grilles and Screens a. In calculating free area, consideration must be given
to the blocking effects of louvers, grilles and screens.
b. If the free area of a specific louver or grille is not
known, refer to Table 6, to estimate free area.
NOTE
If mechanically operated louvers are used, a means
:
to prevent main burner ignition and operation must be pro­vided should louvers close during startup or operation.
1. If the furnace is installed in a confined space it is recom­mended that the necessary combustion air come from the outdoors by way of attic, crawl space, air duct or direct openin
g.
2. If indoor combustion air is used, there must be no expo­sure to the installations or substances listed in 3 below.
3. The following types of installations may require OUT­DOOR AIR for combustion, due to chemical exposure.
a. Commercial buildings b. Buildings with indoor pools c. Furnaces installed in laundry rooms d. Furnaces installed in hobby or craft rooms e. Furnaces installed near chemical storage areas
Exposure to the following substances in the combustion air supply may also require OUTDOOR AIR for combustion.
f. Permanent wave solutions g. Chlorinated waxes and cleaners h. Chlorine based swimming pool chemicals i. Water softening chemicals
20 Unitary Products Group
Page 21
035-14370-000 650.75-N4U
g
g
g
g
g
j. De-icing salts or chemicals k. Carbon tetrachloride l. Halogen type refrigerants m. Cleaning solvents (such as perchloroethylene) n. Printing inks, paint removers, varnishes, etc. o. Hydrochloric acids p. Cements and glues q. Antistatic fabric softeners for clothes dryers r. Masonry acid washing chemicals
VENT PIPE SIZING (1-PIPE SYSTEM)
Refer to Table 7 to select the proper size piping for venting. The size will be determined by a combination of furnace model, total length of run, and the number of elbows required. The following rules must also be observed.
NOTE
Furnace vent pipe connections are sized for 2-in. pipe.
:
Any pipe size change must be made outside the furnace cas­ing in a vertical pipe section to allow proper drainage of vent connections.
NOTE
An offset using two 45 degree elbows may be required
:
for plenum clearance when the vent is increased to 3".
1. Long radius elbows are required for all units.
2. Elbows are assumed to be 90 de elbows count as one 90 de
rees. Two 45 degree
ree elbow.
3. One Vent terminal elbow is already accounted for and should not be counted in the allowable total indicated in the table. See “VENT TERMINAL LOCATION CLEARANCES" Section on pa
e 21 . This part is shown
shaded.
4. All vent pipe and fittin
s must conform to American National Standards Institute (ANSI) standards and Amer­ican Society for Testin
and Materials (ASTM) standards D1785 (Schedule 40 PVC), D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core), D2241 (SDR-21 and SDR-26 PVC), D2261 (ABS-DWV), or F628 (Schedule 40 ABS. Pipe cement and primer must conform to ASTM Stan­dards D2564 (PVC) or D2235 (ABS).
5. The use of flexible connectors or no hub connectors in the vent system is not allowed.:
TABLE 7: VENT PIPING / 1-PIPE SYSTEM (ALL
MODELS)
Max. Elbows vs. One Way V ent
Model Pipe Size
5-40 45 50 75
All Models Except:
120 / 112 / 2000 / D
140 / 130 / 2000 / D
All Models Except: 120 / 112 / 2000 / D 140 / 130 / 2000 / D
120 / 112 / 2000 / D 140 / 130 / 2000 / D
2” 6 5 4 N/A
3” 8 7 6 5
3” Only 6 5 4 N/A
VENT TERMINATION (1-PIPE SYSTEM)
Side wall horizontal vent terminals and roof mounted vertical terminals may be field fabricated. Standard PVC/SRD fittings may be used. Terminal configuration must comply as detailed in this section.
When selecting the locations for vent termination, the follow­ing should be considered:
1. Comply with all clearance requirements. (Refer to Figure 25 on page 22)
2. Termination should be positioned where vent vapors will
not damage plants or shrubs or air conditioning equip­ment.
3. Termination should be located where it will not be
affected by wind gusts, light snow, airborne leaves or allow recirculation of flue gases.
4. Termination should be located where it will not be dam-
aged or exposed to flying stones, balls, etc.
5. Termination should be positioned where vent vapors are
not objectionable.
In Canada, refer to CAN/CGA-B149.1 or.2 Installation Code (latest edition - Venting Systems and Air Supply)
VENT TERMINAL LOCATION CLEARANCES
The vent must be installed with the following minimum clear­ances(Refer to Figure 25 on page 22), and complying with local codes or utility requirements or other authority having jurisdiction.
Length (Ft.)
Unitary Products Group 21
1. 1 foot above grade and above normal snow levels.
2. Not above any walkway.
3. 4 feet below, 4 feet horizontally from, or 1 foot above any
door/window or gravity air inlet to the building, or from gas or electric meters.
Page 22
650.75-N4U 035-14370-000
R
R
SOFFIT VENTS
6' 10' RECOMMENDED
ELECTRIC METER
FURNACE VENT
INSIDE CORNER
4' 4'
4'
4'
4'
4'
FRESH AIR
3'
1' PLUS SNOW CLEARANCE
INTAKE
10'
12"
MAINTAIN 12" CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATE
VENT ELBOW
FIGURE 25 : VENT TERMINAL CLEARANCES
(1-PIPE SYSTEM) - U.S. ONLY
4. 6 feet from any inside corner formed by two exterior walls. 10 feet is recommended where possible.
5. At least 4 feet horizontally from any soffit or undereave vent.
6. 10 feet from any forced air inlet to the building. Any fresh air or make up inlet as for a dryer or furnace area is con­sidered to be a forced air inlet.
7. Avoid areas where condensate drippage may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
NOTE
Consideration must be given for degradation of build-
:
ing materials by flue gases.
NOTE
Shaded components of the vent system shown in Fig-
:
ure 25 through Figure 28 are considered to be termination. These components should not be counted when determining pipe diameter. Sidewall termination may require sealing or shielding of building surfaces with a corrosive resistant mate­rial due to vent system corrosive combustion products.
FIGURE 26 : HORIZONTAL TERMINATION CON-
FIGURATION WITH 12” MINIMUM CLEARANCE
12" MINIMUM
90°
VENT
MAINTAIN 12" CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATE
FIGURE 27 : HORIZONTAL TERMINATION RAISED
CONFIGURATION FOR ADDITIONAL CLEARANCE
22 Unitary Products Group
VENT
MAINTAIN 12" MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24" ABOVE ROOF
FIGURE 28 : ROOFTOP TERMINATION
Page 23
035-14370-000 650.75-N4U
g
g
g
g
g
g
g
g
g
g
gging
g
g
g
g
12" M IN IM UM BETW EEN BO TTOM O F ELBOW AN D ANY M ATERIAL
12"
MINIMUM
PIPING ASSEMBLY
The final assembly procedure for the vent piping is as follows:
1. Cut pipin
2. Deburr the pipin
3. Chamfer the outer ed
4. Dry-fit the entire vent pipin
5. Disassemble the pipin
to the proper length, beginning at the furnace.
inside and outside.
es of the piping.
system.
and apply cement primer and cement per the cement manufacturer's instructions. Primer and cement must conform to ASTM D2564 for PVC, or ASTM D2235 for ABS pipin
.
Solvent cements are flammable and must be used in well-ventilated areas only . Keep them away from heat, sparks and open flames (including pilots). Do not breathe vapors and avoid contact with skin and eyes.
6. All joints must be made to provide a permanent, air ti water ti
ht seal.
ht.
In Canada, refer to CAN/CGA-B149.1 or.2 Installation Code (latest edition - Venting Systems and Air Supply)
COMBUSTION AIR INTAKE
Refer to Table 4 on page 16, for intake pipe sizing, allowable length and elbow usage. Follow all notes, procedures and required materials in the Two-Pipe Sealed Combustion sec­tion (Method 1) when installing the combustion air pipe within the unit and into the ventilated attic space.
COMBUSTION AIR TERMINATION
Refer to Figure 29 for required termination method and con­figuration for the intake pipe. For attic termination, use two 90 elbows with the open end in a downward position. Be sure to maintain 12" clearance above any insulation, flooring or other material.
Be sure to instruct the owner not to block this intake pipe.
7. Support the vent pipin ear foot so that condensate will flow back towards the furnace. Pipin prevent sa 5 feet, except SDR-PVC pipin in
8. Seal around the openin throu
Vent piping must be insulated with 1/2” Armaflex insulation if it will be subjected to freezing temper­atures such as routing through unheated areas or through an unused chimney.
NOTE:
densate to flow back to the furnace.
METHOD THREE: TWO PIPE SYSTEM USING COM­BUSTION AIR FROM A VENTILATED ATTIC SPACE
This type installation requires two properly sized pipes. One brings combustion air from a properly ventilated attic space and a second pipe from the furnace vent connection (top right of unit) exits to the outdoors.
such that it is angled 1/4” per lin-
should be supported with pipe hangers to
. Maximum spacing between hangers is
, where maximum spac-
is 3 feet.
s where the vent piping passes
h the roof or side wall.
Vent pipe must be sloped 1/4” per foot to allow con-
FIGURE 29 : ATTIC COMBUSTION AIR TERMINA-
TION
COMBUSTION AIR REQUIREMENTS
The ventilated attic space from which the combustion air is taken must comply with the requirements shown on page 11 in this instruction or in Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 (lat­est edition).
VENT PIPE
For vent pipe sizing, allowable length and elbow usage, see Refer to Table 7 on page 21. Follow all notes, installation pro­cedures and required materials in the “METHOD TWO ONE PIPE SYSTEM, on page 19” to install the vent pipe from the unit to the outdoors.
Unitary Products Group 23
Page 24
650.75-N4U 035-14370-000
VENT TERMINATION
The vent pipe termination must be installed within the allow­able locations shown in Figure 24 and Section 7.8 in the National Fuel Gas Code, ANSI Z223.1 (current edition). Fol­low all local agency and utility requirements if more restrictive than those shown. Vent termination must be as shown in Fig­ure 27through Figure 28.
In Canada, refer to CAN/CGA-B149.1 or .2 Installation Code (lat­est edition - Venting Systems and Air Supply)
HORIZONTAL VENT APPLICATIONS
If installing a horizontal venting system through any uncondi­tioned space such as an attic or crawl space, it is recom­mended, but not required, that a vent drain be added to the vent pipe to prevent the accumulation of excess condensate in the inducer motor during operational cycles. (Refer to Fig­ures 30 and 31).
FIGURE 30 : HORIZONTAL VENT DRAIN -
UPFLOW MODELS P*UR/FG9-UP/ G9T-UP
To install the vent drain, complete the following steps:
1. Place a tee of the proper diameter for the vent system being installed (2" or 3") in the horizontal run closest to the furnace.
FIGURE 31 : HORIZONTAL VENT DRAIN -
DOWNFLOW/HORIZONTAL MODELS P*DH/FG9-DH/G9T-DH
2. Place a reducer bushing of proper diameter in the stem portion of the tee. The recommended size for the reducer is 5/8”.
3. Place a piece of 5/8” diameter or other selected size pipe a minimum of 3" long into the reducer to serve as a nip­ple.
NOTE
Tee, reducer and nipple must be properly cemented
:
together using the appropriate method and materials speci­fied in the Combustion Air Intake/Vent Connections section of these instructions.
4. Connect a piece of flexible drain tubing such as EPDM rubber, Vinyl or PVC to the nipple.
5. Loop the drain tubing to provide a trap.
6. Connect the discharge end of the drain tube to the con­densate disposal system externally to the furnace.
CONDENSATE PIPING
The condensate drain connection is packed in the furnace for field installation. It consists of a formed hose with a 1/2” NPT male connection. A 1/2” FM x 3/4” PVC slip coupling is pro­vided.
24 Unitary Products Group
Page 25
035-14370-000 650.75-N4U
This drain hose may be installed to allow left or right side con­densate drain connection. (Refer to Figure 32.) Cut the hose to allow for proper fit for left or right exit.
LH DRAIN
RH DRAIN
FIGURE 32 : UPFLOW MODELS P*UR/FG9-UP/
G9T-UP
For horizontal left airflow (inducer and vent low) or horizontal right airflow (inducer and vent high), install condensate drain hoses as follows:
RIGHT AIRLOW (Inducer High) - Three hoses are required. Hoses are supplied with furnace. Refer to Figure 34 and Table 8 for application.
LEFT AIRFLOW (Inducer Low) - Two hoses are required. Inducer outlet to trap is supplied. Condensate pan to trap must be field supplied using 5/8” I.D. hose material. Refer to Figure 34 and Table 8, for hose placement and sizing.
TABLE 8: HORIZONTAL CONDENSATE DRAIN HOSE
SIZES - MODELS P*DH / FG9-DH / G9T-DH
CABINET SIZE (IN.)
DIMEN.
A 4-1/2 4-3/4 3-1/2 5-1/4 B 7-1/2 10-1/2 14 17-1/2
C 13-1/2 16-1/2 20 23-1/2
D 3-3/8 3-1/4 3-1/4 3-1/4
RIGHT AIRFLOW (INDUCER HIGH)
14-1/2 17-1/2 21 24-1/2
LEFT AIRFLOW (INDUCER LOW)
CONDENSATE T R A P T U B IN G
FIGURE 33 : DOWNFLOW/HORIZONTAL MODELS
P*DH/FG9-DH/G9T-DH
To install the drain hose assembly, remove the 7/8” knockout in the side panel. Remove the conduit nut from the 1/2” male fitting. Push the male fitting through the hole and reinstall the nut. The use of the 3/4” PVC coupling is optional.
Conversion for Horizontal Applications
Remove the condensate trap and its mounting bracket from the unit side panel. Remove all drain hoses.
Reinstall the trap/bracket on the side panel which will be on the bottom when the unit is located horizontally. Use the orig­inal mounting screws.
Refer to Figure 34 for hose locations and Table8 for hose cut lengths. All hoses are identified as shown in Figure 34.
Plug all unused condensate trap, condensate pan and inducer drain connection points using plugs provided.
Drain Connection:
The following steps apply to all models. For horizontal application, also follow the procedure for relo­cating the trap assembly and installing drain hoses.
1. It is recommended that either 1/2” or 3/4” PVC or equiva-
lent pipe be field installed as drain pipe. The condensate piping may be tied together with the air conditioning con­densate drain if the air conditioning condensate drain line is trapped upstream of the tie-in and the combined drains are constructed of the same material.
2. All pipe joints must be cleaned, de-burred and cemented
using PVC primer and cement.
3. The furnace contains an internal trap. Therefore, no
external trap should be used.
4. If a condensate pump is used, it must be suitable for use
with acidic water.
5. Where required, a field-supplied neutralizer can be
installed in the drain line, external to the furnace.
NOTE
The condensate drain from the furnace may be con-
:
nected in common with the drain from an air conditioning coil
Unitary Products Group 25
Page 26
650.75-N4U 035-14370-000
RIGHT AIRFLO W (INDUCER HIGH)
HOSE ID E N T . NUMBERS
1 - C ON DENSATE PAN TO TRAP "A " D IM E N S IO N
2 - INDUCER BOTTOM TO TRAP "B " D IM E N S IO N
3 - INDUCER O UTLET TO TRAP "C " D IM E N S IO N
LEFT A IR FLOW (INDUCER LOW )
HOSE ID E N T . NUMBERS
4 - INDUCER OUTLET TO TRAP U S E A S P R O V ID E D
5 - CO ND ENSATE PAN TO TRAP "D " D IM E N S IO N
A
1
23
D
5
C
B
4
FIGURE 34 : HORIZONTAL APPLICATION CONDENSATE DRAIN CONNECTION (MODELS P*DH / FG9-DH /
G9T-DH)
if allowed by local code. Follow the instructions with the coil for trapping the drain.
SAFETY CONTROLS
Control Circuit Fuse:
the 24 volt transformer from overload caused by control cir­cuit wiring errors. This is an ATO 3, automotive type fuse and is located in the unit wiring harness between the control transformer and the furnace control.
Blower Door Safety Switch:
Electrical Interlock Switch mounted in the blower compart­ment. This switch interrupts all power at the unit when the panel covering the blower compartment is removed.
Blower and burner must never be operated without the blower panel in place.
A 3 amp. fuse is provided to protect
This unit is equipped with an
Electrical supply to this unit is dependent upon the panel that covers the blower compartment being in place and properly positioned.
Main power to the unit must still be interrupted at the main power disconnect switch before any ser­vice or repair work is to be done to the unit. Do not rely upon the interlock switch as a main power dis­connect.
Rollout Switch Controls:
This control is mounted on the burner box assembly. If the temperature in the burner com­partment exceeds its set point, the igniter control and the gas valve are de-energized. The operation of this control indi­cates a malfunction in the combustion air blower, heat exchanger or a blocked vent pipe connection. Corrective action is required. This is a manual reset control and must be reset before operation can continue.
Pressure Switches:
This furnace is supplied with pressure switches which monitor the flow through the combustion air/ vent piping system. These switches de-energize the ignition
26 Unitary Products Group
Page 27
035-14370-000 650.75-N4U
g
g
g
control module and the gas valve if any of the following condi­tions are present. Refer to Figure 35 for tubing connections.
1LP
UPFLOW
1LP2LP
Auxiliary Limit Controls
Downflow/horizontal units have a single limit switch munted on the blower assembly. This is a manual reset control and gives high temperature protection in the event of a blower motor failure.
START-UP AND ADJUSTMENTS
The initial start-up of the furnace requires the following addi­tional procedures:
1. When the gas supply is initially connected to the furnace, the gas piping may be full of air. In order to purge this air, it is recommended that the ground union be loosened until the odor of gas is detected. When gas is detected, immediately retighten the union and check for leaks. Allow five minutes for any gas to dissipate before con­tinuing with the start-up procedure.
Be sure proper ventilation is available to dilute and carry away any vented gas.
DOWNFLOW / HORIZONTAL
FIGURE 35 : PRESSURE SWITCH TUBING ROUTING
1. Blocka
2. Blocka
3. Failure of combustion air blower motor (1LP).
4. Blocka
• Upflow units (1LP)
• Downflow/Horizontal Units
Limit Control
There are high temperature limit control(s) located on the fur­nace vestibule panel near the gas valve. These are automatic reset control and provides over temperature protection due to reduced airflow, such as a dirty filter.
e of combustion air piping or terminal. (1LP) e of vent piping or terminal (1LP).
e of condensate drain piping:
• Downflow (1LP)
• Horizontal Left (1LP)
• Horizontal Right (2LP)
Perform the following procedures only after the condensate trap has been properly piped to a drain connection using the procedure in this instruction.
2. The condensate trap must be filled with water before put­ting the furnace into operation. The recommended pro­cedure is as follows:
a. Disconnect the condensate drain hose from the
induced draft blower discharge. b. Elevate this hose and fill with water using a funnel. c. Replace the condensate drain hose and clamps.
NOTE
If this procedure is not followed, the unit may not prop-
:
erly drain on initial start up.
3. All electrical connections made in the field and in the fac­tory should be checked for proper tightness.
IGNITION SYSTEM SEQUENCE
1. Turn the gas supply ON at external valve and main gas valve.
2. Set the thermostat above room temperature to call for heat.
Unitary Products Group 27
Page 28
650.75-N4U 035-14370-000
3. System start-up will occur as follows: a. The induced draft blower motor will start and oper-
ate on low speed. Shortly after venter start-up, the hot surface igniter will glow for about 17 seconds.
Wrench Boss
Wiring Terminals
Outlet
b. The ignition module will energize (open) the main
gas valve on low fire for seven seconds.
c. After flame is established, the supply air blower will
start in about 30 seconds.
NOTE
Burner ignition may not be satisfactory on first start-up
:
due to residual air in line.
4. With furnace in operation, paint the pipe joints and valve gasket lines with a rich soap and water solution, Bubbles indicate a gas leak. Take appropriate steps to stop the leak. If the leak persists, replace the component.
DO NOT omit this test! Never use a flame to check for gas leaks.
GAS VALVE OPERATION
The manual valve knob is a two-position (ON-OFF) type. To turn the valve ON, rotate knob clockwise or counterclockwise to line up the word ON on the knob with the indicator on the cover casting (Refer to Figure 36).
CHECKING GAS INPUT (NATURAL GAS)
NOTE
Front door of burner box must be secured when
:
checking gas input.
1. Turn off all other gas appliances connected to the gas meter.
2. With the furnace turned on, measure the time needed for one revolution of the hand on the smallest dial on the meter. A typical domestic gas meter usually has a 1/2 or 1 cubic foot test dial.
3. Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour, (Refer to Table 9 on page 29).
To find the BTUH input use the following formula:
Inlet
ON - OFF Switch
Main Regulator Adjust
Outlet Pressure Tap
FIGURE 36 : GAS VALVES -
(TOP ) W HITE - R ODG E R S 36E 2 4 (BOTTOM) HONEYWELL VR8205
(approved for field replacement)
lated. Higher temperatures (over 60° F) will speed up the meter and make it read high.
Temperatures under 60° F will slow it and make it read low. The barometric pressure above 30.0" will slow the meter and below 30.0" speed up the meter. At some conditions the meter may be off significantly. an error of mon. The gas meter correction factor is calculated as follows:
(Barometric Pressure) x 520
= Meter Correction Factor
(Temperature F + 460) x 30
+
5% is not uncom-
Cu. Ft. Gas x meter correction factor x Gas BTU Content = BTU Per Hour Input
The gas meter is affected by both the temperature and also the barometric pressure. The meter should be correct at 60° F, and 30.0" barometric pressure. At all other conditions it will be inaccurate, although the correction factor is easily calcu-
28 Unitary Products Group
Example 1: 28.9" Barometric Pressure, 80° F
(28.9) x 520 = 15028
= .928 Correction Factor
(80 + 460) x 30 = 16200
Contact your gas supplier for actual BTU content of the gas.
Page 29
035-14370-000 650.75-N4U
g
g
g
g
g
EXAMPLE - CHECKING GAS INPUT
It is found by measurement that it takes 26 seconds for the hand on the 1 cubic foot dial to make a revolution with only a 120,000 Btuh furnace running. Using this information, locate 26 seconds in the first column of Table 9, “
as rate (cubic feet
per hour),” on page 29. Read across to the column headed
cubic foot
where you will see that 138 cubic feet of gas per
hour are consumed by the furnace at that rate. With the barometer at 28.9" and a 70° F temperature, the cor-
rection factor will be.945. If the local gas heating value is 935 BTU per cubic foot the calculations will be as follows:
138 cu. ft/hrx.945 correction factor x 935 BTU/cu. ft. = 121,933 BTU/Hr.
The calculated firing rate of 121,933 BTU per hour is within
+
2% tolerance of our nominal 120,000 furnace..
the
+
If the actual input is not within
2% of the furnace rating, with allowance being made for the permissible range of the regu­lator setting (0.3 inches W.C.), replace the orifice spuds with spud of the proper size.
Be sure to relight any gas appliance that were turned off at the start of this input check.
ADJUSTMENT OF MANIFOLD GAS PRESSURE
Manifold gas pressure may be measured by two different pro­cedures. It may be measured with the burner box cover in place or it may be measured with the burner box cover removed. Follow the appropriate section, 2a or 2b in the instructions below.
1. Turn
2. Read the inlet
as off at main gas valve. Revove 1/8” Allen socket
head pipe plu
from the manifold end of the main gas valve. Install the proper manometer tube adapter into this openin
.
as pressure using either of the two meth-
ods below.
Reading the gas pressure with the burner box
a.
cover in place
- Disconnect the pressure reference hose from the right side of the burner box. Using a tee fitting and a short piece of hose, connect the negative side of the manometer to the burner box pressure reference port. Connect the positive side of the manometer to the adapter previously installed in the gas valve Refer to Figures 39 and 40 on page 31.
TABLE 9 : GAS RATE (CUBIC FEET PER HOUR)
TEST DIAL
SIZE
SECONDS FOR ONE
REVOLUTION
1
10 180 360 12 150 300 14 129 257 16 113 225 18 100 200 20 90 180 22 82 164 24 75 150 26 69 138 28 64 129 30 60 120 32 56 113 34 53 106 36 50 100 38 47 95 40 45 90 42 43 86 44 41 82 46 39 78 48 37 75 50 36 72 52 35 69 54 34 67 56 32 64 58 31 62 60 30 60
Reading the gas pressure with the burner box
b.
cover removed
CUBIC FOOT
1/2
- Remove the screws securing the burner box front cover plate. Remove the cover. It is gasketed and may stick in place. Connect the posi­tive side of the manometer to the adapter previously installed in the gas valve as shown in Refer to Fig­ures 39 and 40 on page 31. There will be no second connection to the manometer as it will reference atmospheric pressure.
NOTE:
The screw-off cap for the pressure regulator must be removed entirely to gain access to the adjustment screw. Loosening or tightening the cap does not adjust the flow of gas.
OF
CUBIC FOOT
1
Unitary Products Group 29
Page 30
650.75-N4U 035-14370-000
3. Refer to Figure 36 on page 28, for location of pressure regulator adjustment cap and screw on main gas valve.
4. Turn gas and electrical supplies ON. Start furnace and observe manifold pressure on manometer.
5. Adjust manifold pressure by adjusting gas valve regula­tor screw for the appropriate gas per the following:.
Natural Gas ..............................................................3.5” W.C.
Propane (LP) Gas ....................................................10.0” W.C.
If gas valve regulator is turned in, or clockwise, manifold pressure is increased. If screw is turned out, or counterclock­wise, manifold pressure will decrease.
If manifold pressure is too high, an over-fire condi­tion exists which could cause heat exchanger fail­ure. If the manifold pressure is too low, sooting and eventual clogging of the heat exchanger could occur.
All direct-drive blowers have multi-speed motors. The blower motor speed taps are located in the control box in the blower compartment. Refer to Figure 37, and the unit wiring label to change the blower speed.
You may select a heating speed and a cooling speed. They may be the same speed or a different speed.To use the same speed tap for heating and cooling, the heat terminal and cool terminal must be connected using a jumper wire and con­nected to the desired motor lead. Place all unused motor leads on Park terminals. Two Park terminals are provided. .
Do not energize more than one motor speed at a time or damage to the motor will result.
ADJUSTMENT OF FAN-OFF CONTROL SETTINGS
This furnace is equipped with a time-on/time-off heating fan control. The fan on is fixed at 30 seconds. The fan off is field adjustable from 60 to 180 seconds. The fan off is factory set to 60 seconds. Adjust the off time by repositioning the fan off switches. (Refer to Figure 37.)
Once the correct gas pressure to the burners has been established, turn the gas valve knob to OFF and turn the electrical supply switch to OFF; then remove the pressure tap at the gas valve and re­install the plug, using a compound (on the threads) resistant to the action of LP gases. Replace the burner box front cover or the pressure reference hose.
Be sure that gas valve regulator cap and burner box to gas valve pressure reference hose is recon­nected.
Turn the electrical and gas supplies back on, and with the burners in operation, check for gas leakage around the plug with a soap and water solution.
ADJUSTMENT OF TEMPERATURE RISE
The temperature rise, or temperature difference between the return air and the heated air from the furnace, must be within the range shown on the furnace rating plate. Application limi­tations are shown in Table 1 or 2. After the temperature rise has been determined, the cfm can be calculated.
After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts, about six feet from the furnace where they will not be affected by radiant heat.
Increase the blower speed to decrease the temperature rise; decrease the blower speed to increase the rise.
FIGURE 37 : TYPICAL HEAT/COOL SPEED TAP
CONNECTIONS
The fan-off setting must be long enough to adequately cool the furnace, but not so long that cold air is blown into the heated space. The fan-off timing may be adjusted by setting the option switches located (Refer to Figure 37) on the con­trol board as follows:
To Delay Fan-Off
By:
60 Sec. ON ON
90 Sec. OFF ON 120 Sec. ON OFF 180 Sec. OFF OFF
Set Switch
1 2
30 Unitary Products Group
Page 31
035-14370-000 650.75-N4U
HUM
EAC
EAC
HUM
115 VOLT ELECTRONIC AIR CLEANER
EAC HOT
HUM HOT
BLK
BLK
WHI
WHI
115 VOLT HUMIDIFIER
SWITCHED CIRCUITS
NEUTRALS
W
N
For units using a Texas Instruments control, connect the jumper at the desired off timing. Refer to Figure 37 on page 30, 60 second off timing shown.
ACCESSORY CONNECTIONS
Do not exceed 1.0 amp loading.
The furnace control will allow power switching control of vari­ous accessories. Refer to Figure 38
Electronic Air Cleaner Connection
Two 1/4” spade terminals (EAC and EAC N) for electronic air cleaner connections are located on the control board. The terminals provide 120 VAC (1.0 amp maximum) durin lating blower operation.
OUTLET
PRESSURE
TAP
BURNER BOX
PRESSURE
REFERENCE HOSE
.
g circu-
GAS
VALVE
Humidifier Connection
Two 1/4” spade terminals (HUM and HUM N) for humidifier
connections are located on the control board. The terminals
provide 120 VAC (1.0 amp maximum) during heat speed
operation of the circulating blower..
FIGURE 38 : ACCESSORY CONNECTIONS
GAS
VALVE
BURNER BOX
OUTLET
PRESSURE
TAP
PRESSURE REFERENCE HOSE (NOT USED)
BURNER BOX
ITH COVER
U-TUBE
MANOMETER
FIGURE 39 : UPFLOW MODELS (P*UR/ FG9-UP / G9T-UP) - READING GAS PRESSURE
WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED
BURN ER BO X
BURN ER BO X PRESSUR E REFERENCE HO SE
TEE FITTIN G
FIGURE 40 : DOWNFLOW/HORIZONTAL MODELS (P*DH/ FG9-DH / G9T-DH) - READING GAS PRESSURE
WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED
Unitary Products Group 31
W ITH CO VER
OUTLET PRESSUR E TAP
GAS
VALVE
6 5 4 3 2 1 0 1 2 3 4 5 6
6 5 4 3 2 1 0 1 2 3 4 5 6
TEE
FITTING
3.5 IN.
WATER COLUMN
GAS PRESSURE
SHOWN
3.5 IN.
W ATER COLUMN
GAS PR ESSURE
SHO W N
U-TUBE
MANOMETER
BURNER BOX WITH COVER REMOVED
BURN ER BO X PRESSUR E REFERENCE HO SE (NO T USED)
BURN ER BO X W ITH CO VER REM OVED
OUTLET PRESSUR E TAP
GAS VALVE
6 5 4 3 2 1 0 1 2 3 4 5 6
6 5 4 3 2 1 0 1 2 3 4 5 6
WATER COLUM
GAS PRESSURE
SHOWN
U-TUBE
MANOMETER
3.5 IN . W ATER COLUMN GAS PR ESSURE
SHO W N
U-TUBE
MANOMETER
3.5 IN.
Page 32
650.75-N4U 035-14370-000
FURNACE ACCESSORIES
ELECTRICAL
2TH07700124 Single Stage Thermostat, One-Stage Heat/One-Stage Cool 2TH13700424 Deluxe 24V Thermostat - with heat only subbase (must be used w/subbase 2TB17700424) 2TB17700424 Subbase (24V) One-Stage Heat/One-Stage Cool 2ET07700224 Programmable, Electronic Thermostat, One-Stage Heat/One-Stage Cool 2TC03700124 Twinning Control
NON-ELECTRICAL
1NP0347 Propane (LP) Conversion Kit 1NP0349 Propane (LP) Conversion Kit 1PS0306 1PS0307 1PS0308 1PS0309 1PS0310 1SR0302 External Side Filter Rack (6-Pack) 1BR0314 External Bottom Filter Rack - Cabinet “A” 1BR0317 External Bottom Filter Rack - Cabinet “B” 1BR0321 External Bottom Filter Rack - Cabinet “C” 1BR0324 External Bottom Filter Rack - Cabinet “D” 1CT0302 Concentric Vent Termination - 2” V ent Pipe 1CT0303 Concentric Vent Termination - 3” V ent Pipe 1CB0314 Combustible Floor Base - Cabinet “A” 1CB0317 Combustible Floor Base - Cabinet “B” 1CB0321 Combustible Floor Base - Cabinet “C” 1CB0324 Combustible Floor Base - Cabinet “D”
High Altitude Pressure Switch (See Form 650.75-N2.1V for proper application)
32 Unitary Products Group
Page 33
035-14370-000 650.75-N4U
AIRFLOW DATA - UPFLOW MODELS: P*UR/FG9-UP/G9T-UP
MODELS
Input/Output/Airflow/
cabinet
40 / 37 / 800 / A
60 / 55 / 1000 / B
80 / 75 / 1200 / B
100 / 75 / 1600 / C
100 / 95 / 1400 / C
100 / 95 / 2000 / C
120 / 112 / 2000 / D
140 / 130 / 2000 / D
Airflow expressed in standard cubic feet per minute. Notes: 1. Return air is through side opposite motor (left side).
2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
3. Air filter installed. All filters must be high velocity, cleanable type.
4. Motor voltage at 115 V.
SPEED TAP
HI 1051 1005 977 985 835 757 665 450 — MED 900 887 851 810 752 693 609 403 — LOW 581 577 569 542 468
HI 1220 1200 1190 1152 1115 1065 1012 950 872 771 MED 920 915 900 880 842 803 740 650 LOW 725 729 715 700 681 653 600 525
HI 1431 1395 1355 1317 1263 1226 1165 1101 1029 937 MED 1188 1076 1065 1046 1023 994 955 906 842 752 LOW 832 823 811 805 794 766 742 672 624 561
HI 1879 1837 1794 1740 1688 1627 1559 1485 1406 1314 MED 1379 1374 1348 1340 1313 1271 1232 1158 1978 LOW 1196 1181 1141 1095 1053 1001 936
HI 1742 1672 1602 1519 1433 1348 1232 1098 934 766 MED 1390 1360 1320 1265 1176 1082 965 810 656 LOW 1097 1061 1035 1000 927 830 708 574
HI 2300 2229 2168 2100 2026 1939 1855 1758 1661 1546 MED 1937 1897 1855 1808 1737 1673 1597 1511 1425 1305 LOW 1579 1564 1533 1481 1461 1415 1350 1291 1205 1093
HI 2366 2298 2226 2153 2065 1988 1890 1808 1712 1600 MED 2000 1961 1920 1874 1821 1757 1685 1606 1510 1430 LOW 1588 1578 1545 1525 1492 1455 1399 1340 1260 1163
HI 2343 2275 2204 2132 2047 1968 1871 1791 1695 1585 MED 1981 1942 1901 1856 1803 1740 1669 1591 1490 1416 LOW 1575 1562 1530 1510 1477 1440 1386 1327 1248 1152
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
EXTERNAL STATIC PRESSURE, INCHES WC
AIRFLOW DATA - DOWNFLOW/HORIZONTAL MODELS: P*DH/FG9-DH/G9T-DH
MODELS
Input/Output/Airflow/
cabinet
40 / 37 / 800 / A
60 / 55 / 1200 / B
80 / 75 / 1200 / B
80 / 75 / 1600 / C
100 / 95 / 2000 / C
120 / 112 / 2000 / D
Airflow expressed in standard cubic feet per minute. Notes: 1. Air filter installed. All filters must be high velocity, cleanable type.
2. Motor voltage at 115 V.
SPEED TAP
HI 1182 1164 1136 1101 1063 1018 967 904 824 724
MED 954 938 919 899 876 838 798 744 686 588
LOW 650 643 634 620 602 577 542 494 440 335
HI 1567 1552 1532 1517 1484 1441 1384 1315 1243 1166
MED 1175 1173 1169 1159 1144 1126 1089 1039 985 910
LOW 881 879 871 861 842 826 795 756 724 664
HI 1603 1579 1558 1522 1485 1433 1380 1311 1233 1139
MED 1250 1230 1210 1190 1160 1125 1083 1029 955 889
LOW 925 904 891 873 845 829 793 761 685 618
HI 2024 1960 1911 1855 1780 1698 1627 1540 1458 1387
MED 1479 1471 1465 1452 1429 1393 1359 1300 1238 1163
LOW 1210 1208 1198 1175 1149 1110 1052 982
HI 2272 2200 2128 2061 1984 1890 1810 1710 1627 1519
MED 1980 1933 1887 1838 1769 1701 1626 1535 1426 1328
LOW 1573 1546 1526 1498 1464 1417 1359 1290 1222 1132
HI 2281 2215 2144 2065 2002 1903 1820 1720 1618 1505
MED 1945 1902 1849 1794 1738 1675 1604 1535 1426 1343
LOW 1507 1485 1463 1433 1398 1358 1305 1249 1172 1095
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
EXTERNAL STATIC PRESSURE, INCHES WC
Unitary Products Group 33
Page 34
650.75-N4U 035-14370-000
OPERATION AND MAINTENANCE
SEQUENCE OF OPERATION
The following describes the sequence of operation of the fur­nace. Refer to the schematic wiring diagrams in the back of this manual for component location.
CONTINUOUS BLOWER
On cooling/heating thermostats with fan switch, when the fan switch is set in the ON position, a circuit is completed between terminals R and G of the thermostat. The blower motor is energized through the low heat terminal and runs on the selected speed. This allows constant air circulation at lower flow rate.
INTERMITTENT BLOWER - COOLING
On cooling/heating thermostats with fan switch, when the fan switch is set in the auto position and the thermostat calls for cooling, a circuit is completed between the R, Y and G termi­nals.
The motor is energized through the cool fan terminal and runs on the selected speed. The fan off setting is fixed at 60 seconds for SEER enhancement.
HEATING CYCLE
When the system switch is set on HEAT and the fan is set on AUTO, and the room thermostat calls for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, a pressure switch activates the ignition control
If flame is not detected within the seven second sensing period, the gas valve is de-energized. The control is equipped with a re-try option. This provides a 60 second wait following an unsuccessful ignition attempt (flame not detected).
After the 60 second wait, the ignition sequence is restarted with an additional 10 seconds of igniter warm-up time. If this ignition attempt is unsuccessful, one more re-try will be made before lockout.
A momentary loss of gas supply, flame blowout, or a shorted or open condition in the flame probe circuit will be sensed within 0.8 seconds.
The gas valve will deenergize and the control will restart the ignition sequence immediately. Recycles will begin and the burner will operate normally if the gas supply returns, or the fault condition is corrected prior to the last ignition attempt. Otherwise, the control will lockout.
The control will repeat the ignition sequence for a total of two recycles if flame is lost within the first 10 seconds of estab­lishment.
If flame is established for more than 10 seconds after ignition, the control will clear the ignition attempt (retry) counter. If flame is lost after 10 seconds, it will restart the ignition sequence. This can occur a maximum of five times.
During burner operation, a momentary loss of power of 50 milliseconds or longer will drop out the main gas valve. When the power is restored, the gas valve will remain de-energize and a restart of the ignition sequence will begin immediately
Hot Surface Ignition System
The ignition control provides a 17-second warm-up period. The gas valve then opens for seven seconds.
As gas starts to flow and ignition occurs, the flame sensor begins its sensing function. If a flame is detected within seven seconds after ignition, normal furnace operation continues until the thermostat circuit between R and W is opened. After flame is present for 30 seconds, the circulating blower is energized.
Do not attempt to light this furnace by hand (with a match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition sys­tem.
When the thermostat circuit opens, the ignition control is de­energized. With the ignition control de-energized, the gas flow stops and the burner flames are extinguished. The ven­ter continues to operate for 15 seconds after the gas flow stops.
The blower motor continues to operate for the amount of time set by the fan-off delay switches located on the control board. The heating cycle is then complete, and the unit is ready for the start of the next heating cycle.
34 Unitary Products Group
.
Page 35
035-14370-000 650.75-N4U
FIGURE 41 : FURNACE CONTROL EVENT SCHEDULE
MAINTENANCE
Air Filters
The filters must be checked periodically for dirt accumulation. Dirty filters greatly restrict the flow of air and may cause dam­age to the system.
Clean the filters at least every three months. On new con­struction, check the filters every week for the first four weeks. Inspect the filters every three weeks after that, especially if the system is running constantly .
All filters used with the furnace are the high-velocity, clean­able type. Clean these filters by washing in warm water. Make sure to shake all the water out of the filter and have it reasonably dry before installing it in the furnace. When replacing filters, be sure to use the same size and type as originally supplied.
Filter Removal - Upflow Models
The ends of the retainer are attached to the rear panel in two metal loops. Refer to Table 42 on page 35. The ends must be squeezed together to free them from the loops. The retainer may then be moved to the new location and the ends inserted in the loops on the rear panel at the new location. Loops are provided for retainer location to accommodate filter applica­tion on the bottom or either side of the furnace.
Swing the retainer toward the center of the furnace. This will expose the filter to allow removal. To reinstall the filter, simply reverse this procedure.
FIGURE 42 : UPFLOW FILTER RETAINER
Filter Removal - Downflow Models
1. Turn off electrical power supply to the furnace at discon­nect switch. Remove access doors.
To remove a filter from the bottom location, push the closed end of the filter retainer to the left until it clears the lip on the front of the furnace base, which acts as a catch for the retainer. When the retainer is clear of the flange, it will pivot in the loops.
Unitary Products Group 35
2. Filters are installed in the plenum area above the blower assembly . Filters rest against the side of the plenum wall and are supported in the middle by a frame. Lift filter slightly to dislodge and remove for service.
3. Remove the filter and follow the cleaning instructions above. DO NOT remove the filter stiffener rods, if pro-
Page 36
650.75-N4U 035-14370-000
vided. When reinstalling the filter(s) be sure it completely covers the plenum opening.
To reinstall the filters, simply reverse this procedure.
Horizontal Applications
In most horizontal applications the filter is located in the return air duct near the furnace or in a filter grille.
When replacing filters, DO NOT use a type with excessively high pressure drop. Some high effi­ciency filters available will cause the furnace to operate improperly and could result in a safety hazard.
Lubrication
Blower motors in these furnaces are permanently lubricated and do not require periodic oiling.
Blower Care
Even with good filters properly in place, blower wheels and motors will become dust laden after long months of opera­tion. The entire blower assembly should be inspected annu­ally. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vacuum cleaner.
6. To reassemble, reverse the procedure, restore power to the furnace and verify operation.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shutoff valve and loosen the ground union joint.
3. Remove the upper access panel and remove the burner box cover.
4. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
5. Remove burners from the burner assembly.
6. Burners may be cleaned by rinsin
7. Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
1. Turn off the main manual gas valve external to the fur­nace.
2. Turn off electrical power to the furnace.
3. Remove the upper access panel and remove the burner box cover.
g in hot water.
The procedure for removing the direct drive blower assembly for cleaning is as follows:
1. Disconnect the electrical supply to the furnace and remove remove the access doors.
2. On downflow/horizontal models only, remove the two wires leading to the auxiliary limit mounted on the side opposite the blower motor.
3. On downflow/horizontal models only, remove four top panel screws and lift the top panel enough to disengage and remove the flue chase assembly.
4. Remove blower assembly mounting screws and slide the blower assembly out of the slots in the deck. If the two shipping screws were not previously removed, also remove and discard these two screws located on each front corner of the blower assembly.
5. On downflow models only, note the wire/terminal location and then remove the blower wiring from the furnace con­trol. Remove the protective boot and disconnect run capacitor wires. Remove the screws securing the electri­cal panel to the blower housing. Pull blower assembly out of the unit. When cleaning or servicing the blower assembly, DO NOT remove or change the balance clips on the blower wheel.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily bro­ken.
Label all wires prior to disconnection when servic­ing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
5. Remove the screws that hold the burner box assembly to the vestibule panel and remove the assembly . The upper portion of the heat exchanger will now be exposed.
6. Remove the upper cover plate at the top of the furnace. Remove the internal baffle.
7. The upper portion of the heat exchanger is now exposed.
8. With a long flexible wire brush, clean inside each tube at both the top and bottom. The brush must pass around the rear heat exchanger tubes. Vacuum loose scale and dirt from each tube.
36 Unitary Products Group
Page 37
035-14370-000 650.75-N4U
g
g
g
g
g
g
g
g
g
g
g
g
g
50A50-241 IGNITION CONTROL (P/N 031-01266-000)
Normal flame sense current is approximately
2.0 microamps DC (
µ
a)
Low flame signal control lockout point is
0.15 microamps (DC (
µ
a)
9. Clean - vacuum all burners.
10. Replace all components in reverse order. Reconnect all wirin
.
11. Restore electrical power and
12. Check furnace operation.
Cleaning the Secondary Heat Exchanger
1. Follow steps 1 thru 10 under Cleanin Exchan
2. Remove the vent pipin nect the drain lines from the venter and from the conden­sate drain pan. Remove the venter blower and the condensate pan. The turbulators can then be removed from the secondary heat exchan
3. With a stiff wire brush, brush out loose scale or soot.
4. Vacuum the secondary heat exchan
5. Finish the cleanin 12 under Cleanin
Vent/Air Intake
Should it be necessary to service the vent/air intake system, the manufacturer recommends this service be conducted by a qualified service agency.
The operation of this appliance requires the reassembly and resealing of the vent/air intake system as specified on Page
11.
er.
procedure by following steps 10 thru
the Primary Heat Exchanger.
as supply to the furnace.
the Primary Heat
from the venter housing. Discon-
ently
er.
er.
TROUBLESHOOTING
The following visual checks should be made before trouble­shooting:
1. Check to see that the power to the furnace and the i tion control module is ON.
ni-
troubleshooting section in this manual to check the system's operation..
POWER SUPPLY POLARITY - 50A50-241 Control Only
lowing unit operation will occur. On a call for heat, the inducer will run, the HSI will glow and the gas valve will energize and the burners will ignite. The burners will immediately extinguish and the unit will recycle. This will occur 3 times and then the unit will lockout. A “7” flash code will be displayed. This code means the flame could not be established. This occurs because the control can­not sense flame with the power supply polarity reversed.
If the power supply polarity is reversed, the fol-
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self diagnostic capability. If a system problem occurs, a fault code is shown by a blinking LED. It is located behind a clear view port in the blower compartment door. DO NOT remove the furnace blower compartment panel OR turn off furnace power as either action will clear the control's memory of the fault.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indi­cate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced as the control is not field repairable.
If the sensed failure is in the system (external to the control), the LED will flash in the following flash-pause sequences to indicate failure status.
Flash sequence codes 2 thru 9 are as follows. LED will turn on for 1/4 second and off for 1/4 second. This pattern will be repeated the number of times equal to the code. For exam­ple, six on flashes equals a number 6 fault code.
All flash code sequences are broken by a 2 second off period
2. The manual shutoff valves in the must be open.
3. Make sure all wirin
4. Review the sequence of operation.
Start the system by setting the thermostat above the room temperature. Observe the system's response. Then use the
connections are secure.
Unitary Products Group 37
as line to the furnace
.
CONTINUOUS FLASHING (1 sec on - 1 sec off):
cates that flame was sensed when there was not a call for heat. With this fault code the control will also turn on both the inducer motor and supply air blower. This fault would typically
This indi-
Page 38
650.75-N4U 035-14370-000
be caused by a gas valve that leaks through or is slow clos­ing.
2 FLASH:
switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or mis-wiring.
3 FLASH:
contact did not close at the beginning of the heat cycle. This could be caused by a number of problems; faulty inducer, blocked vent pipe, high winds at vent terminal, broken pres­sure switch hose or faulty pressure switch.
4 FLASH:
its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.
5 FLASH:
tacts in the rollout switch opens. The rollout control is manu­ally reset. If it has opened, check for proper combustion air, proper inducer operation, primary heat exchanger failure or burner problem. Be sure to reset the switch after correcting the failure condition.
This indicates that the normally open pressure
This indicates the normally open pressure switch
This indicates the auxiliary limit switch has opened
This fault is indicated if the normally closed con-
NOTE:
The control will blink one time when initially powered.
This is normal and not an indication of any malfunction.
RESET FROM LOCKOUT:
out condition break the line voltage supply or 24 volt signal from the thermostat for 30 seconds.
To reset the control from any lock-
Do not try to repair controls. Replace defective controls with Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
Never jump pressure switch or rewire in an attempt to allow furnace operation. To do so will allow furnace to operate under potentially hazard­ous conditions.
6 FLASH:
pressure switch opened 5 times during the call for heat. This could be caused by a number of problems; blocked vent or combustion air intake, high winds at vent terminal, faulty inducer, cracked pressure switch hose, or a blockage in the condensate drainage system.
7 FLASH:
established. This no-light condition occurred 3 times during the call for heat before locking out. This may be caused by low gas pressure, faulty gas valve, faulty hot surface igniter or burner problem.
8 FLASH:
during the heating cycle. This could be caused by low gas pressure or faulty gas valve.
LED ON CONSTANTLY:
furnace control discovered during its self-check procedure. Replace the control.
60 MINUTE AUTOMATIC RESET FROM LOCKOUT:
control includes a watchdog type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6, 7 & 8 will be reset. This provides protection to an unoccupied struc­ture if a temporary conditions exists causing a unit malfunc­tion. An example would be a low incoming gas supply pressure condition preventing unit operation. When the gas pressure was restored, at some point the watchdog would restart the unit and provide heat for the house.
This indicates that after the unit was operating, the
This fault code indicates that flame could not be
This fault is indicated if the flame is lost 5 times
This indicated an internal fault in the
This
38 Unitary Products Group
Page 39
035-14370-000 650.75-N4U
WIRING DIAGRAM - UPFLOW MODELS: P*UR / FG9-UP / G9T-UP
NOTE:
THE FURNACE’S CONTROL SYSTEM DEPENDS ON CORRECT POLARITY OF THE POWER SUPPLY
.
Unitary Products Group 39
Page 40
WIRING DIAGRAM - DOWNFLOW/HORIZONTAL MODELS: P*DF / FG9-DH / G9T-DH
NOTE:
THE FURNACE’S CONTROL SYSTEM DEPENDS ON CORRECT POLARITY OF THE POWER SUPPLY
.
Subject to change without notice. Printed in U.S.A. Copyright © by Unitary Products Group 1999. All rights reserved. Supersedes: 650.75-N4U (599) 650.75-N1U (899)
Unitary 5005 York Norman Product Drive OK
Group North 73069
Loading...