York P*UR 140, P*UR 80, FG9-UP 40, FG9-UP 60, P*UR 60 Installation Instructions Manual

...
INSTALLATION INSTRUCTION
CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . 3
SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . 4
UPFLOW MODELS . . . . . . . . . . . . . . . . . . . . . . . . . 8
DOWNFLOW / HORIZONTAL MODELS -
HORIZONTAL APPLICATION . . . . . . . . . . . . . . . . 11
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ELECTRICAL POWER CONNECTION . . . . . . . . . 13
HIGH EFFICIENCY
GAS-FIRED FURNACES TUBULAR
HEAT EXCHANGER SERIES
UPFLOW MODELS: P*UR / FG9-UP / G9T-UP
40 - 140 MBH INPUT
DOWNFLOW/HORIZONTAL MODELS: P*DH / FG9-DH / G9T-DH
40 - 120 MBH INPUT
COMBUSTION AIR AND VENT SYSTEM . . . . . . . 15
HORIZONTAL VENT APPLICATIONS . . . . . . . . . 24
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . 24
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . 26
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . 27
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . 32
AIRFLOW DATA - UPFLOW . . . . . . . . . . . . . . . . . 33
AIRFLOW DATA - DOWNFLOW/HORIZONTAL . 33
OPERATION AND MAINTENANCE . . . . . . . . . . . 34
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 37
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . 37
WIRING DIAGRAM - UPFLOW MODELS . . . . . . . 39
WIRING DIAGRAM - DOWNFLOW/HORIZONTAL 40
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
START TO INSTALL YOUR FURNACE.
SAVE THIS MANUAL
035-14370-000 REV A (899) Form 650.75-N4U
650.75-N4U 035-14370-000
TABLE OF CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . 3
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
NOTES, CAUTIONS & WARNINGS . . . . . . . . . . . . . . . . 3
VENT SAFETY CHECK PROCEDURE . . . . . . . . . . . . . 3
SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . . . . . . . 4
LIMITATIONS & LOCATION . . . . . . . . . . . . . . . . . . . . . .4
CLEARANCES FOR ACCESS . . . . . . . . . . . . . . . . . . . .4
CLEARANCES TO COMBUSTIBLES . . . . . . . . . . . . . . .5
BELOW FREEZING LOCATIONS . . . . . . . . . . . . . . . . . .5
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
UPFLOW MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SUPPLY PLENUM CONNECTION . . . . . . . . . . . . . . . . .8
RETURN DUCT CONNECTION . . . . . . . . . . . . . . . . . . . 9
UPFLOW FILTER INSTALLATION . . . . . . . . . . . . . . . . .9
I
NTERNAL INSTALLATION
S
IDE RETURN
B
OTTOM RETURN
- E
. . . . . . . . . . . . . . . . . . . . . . . . .9
XTERNAL FILTER
. . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DOWNFLOW/HORIZONTAL MODELS
DOWNFLOW APPLICATION . . . . . . . . . . . . . . . . . . . .10
DOWNFLOW FILTERS . . . . . . . . . . . . . . . . . . . . . . . . .10
SUPPLY AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . .11
DOWNFLOW / HORIZONTAL MODELS - HORIZONTAL
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
HORIZONTAL FILTERS. . . . . . . . . . . . . . . . . . . . . . . . 11
ATTIC INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . .11
CRAWL SPACE INSTALLATION . . . . . . . . . . . . . . . . .12
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ELECTRICAL POWER CONNECTION . . . . . . . . . . . . . . .13
ELECTRICAL CONTROL CONNECTIONS . . . . . . . . . . .14
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . . . 15
METHOD ONE: TWO PIPE SEALED COMBUSTION AIR
& VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
COMBUSTION AIR INTAKE/VENT CONNECTIONS 15
COMBUSTION AIR/VENT PIPE SIZING . . . . . . . . . . 16
VENT TERMINATION (2-PIPE). . . . . . . . . . . . . . . . . 16
VENT CLEARANCES (2-PIPE) U.S. ONLY . . . . . . . 17
VENTING MULTIPLE UNITS. . . . . . . . . . . . . . . . . . . 17
PIPING ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . .18
METHOD TWO: ONE PIPE SYSTEM . . . . . . . . . . . . . . 19
COMBUSTION AIR . . . . . . . . . . . . . . . . . . . . . . . . . . .19
A
IR SOURCE FROM OUTDOORS
S
PECIAL COMBUSTION AND VENTILATION
C
ONSIDERATIONS
S
PECIALLY ENGINEERED INSTALLATIONS
C
OMBUSTION AIR QUALITY
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
- . . . . . . . . . . . . . . . . . .20
. . . . . . . . . . . . 20
. . . . . . . . . . . . . . . . . . . . . . 20
VENT PIPE SIZING (1-PIPE SYSTEM) . . . . . . . . . . .21
VENT TERMINATION (1-PIPE SYSTEM) . . . . . . . . .21
VENT TERMINAL LOCATION CLEARANCES . . . . .21
PIPING ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . .23
METHOD THREE: TWO PIPE SYSTEM USING COM­BUSTION AIR FROM A VENTILATED ATTIC SPACE . 23
COMBUSTION AIR INTAKE . . . . . . . . . . . . . . . . . . . 23
COMBUSTION AIR TERMINATION . . . . . . . . . . . . . 23
COMBUSTION AIR REQUIREMENTS. . . . . . . . . . . . 23
VENT PIPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
VENT TERMINATION. . . . . . . . . . . . . . . . . . . . . . . . . 24
HORIZONTAL VENT APPLICATIONS . . . . . . . . . . . . . . . 24
CONDENSATE PIPING 24
C
ONVERSION FOR HORIZONTAL APPLICATIONS
. . . . . . . 25
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
L
IMIT CONTROL
A
UXILIARY LIMIT CONTROLS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
. . . . . . . . . . . . . . . . . . . . . 27
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . 27
IGNITION SYSTEM SEQUENCE . . . . . . . . . . . . . . . . . 27
GAS VALVE OPERATION . . . . . . . . . . . . . . . . . . . . . . 28
CHECKING GAS INPUT (NATURAL GAS) . . . . . . . . . 28
ADJUSTMENT OF MANIFOLD GAS PRESSURE . . . . 29
ADJUSTMENT OF TEMPERATURE RISE . . . . . . . . . . 30
ADJUSTMENT OF FAN-OFF CONTROL SETTINGS . 30
ACCESSORY CONNECTIONS . . . . . . . . . . . . . . . . . . 31
E
LECTRONIC AIR CLEANER CONNECTION
H
UMIDIFIER CONNECTION
. . . . . . . . . . . . . . . . . . . . . . . 31
. . . . . . . . . . . 31
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . 32
AIRFLOW DATA - UPFLOW . . . . . . . . . . . . . . . . . . . . . . 33
AIRFLOW DATA - DOWNFLOW/HORIZONTAL . . . . . . . 33
OPERATION AND MAINTENANCE . . . . . . . . . . . . . . . . . 34
SEQUENCE OF OPERATION. . . . . . . . . . . . . . . . . . . . 34
CONTINUOUS BLOWER . . . . . . . . . . . . . . . . . . . . . . . 34
INTERMITTENT BLOWER - COOLING . . . . . . . . . . . . 34
HEATING CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
H
OT SURFACE IGNITION SYSTEM
. . . . . . . . . . . . . . . . . 34
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
A
IR FILTERS
F
ILTER REMOVAL
F
ILTER REMOVAL
H
ORIZONTAL APPLICATIONS
L
UBRICATION
B
LOWER CARE
B
URNER REMOVAL/CLEANING
C
LEANING THE HEAT EXCHANGER
C
LEANING THE SECONDARY HEAT EXCHANGER
V
ENT/AIR INTAKE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
- U
PFLOW MODELS
- D
OWNFLOW MODELS
. . . . . . . . . . . . . . 35
. . . . . . . . . . . . 35
. . . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . 36
. . . . . . . 37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . 37
WIRING DIAGRAM - UPFLOW MODELS. . . . . . . . . . . . . 39
WIRING DIAGRAM - DOWNFLOW/HORIZONTAL . . . . . 40
2 Unitary Products Group
035-14370-000 650.75-N4U
GENERAL INFORMATION
DESCRIPTION
IMPROPER INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALIFIED INST ALLER, SER VICE AGENCY OR THE GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING BUT NOT LIMITED TO, BUILDING, ELECTRICAL AND MECHANICAL CODES.
This Category IV, dual certified, direct vent and 1-pipe vent furnace is designed for residential or commercial installation in a basement, closet, recreation room, garage or other loca­tion provided space temperature is 32°F or higher. For appli­cations in below freezing locations, refer to “BELOW FREEZING LOCATIONS” section on page 5.
INSPECTION
As soon as a unit is received, it should be inspected for possi­ble damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. Also, before installation the unit should be checked for screws or bolts which may have loosened in tran­sit. There are no shipping or spacer brackets which need to be removed.
NOTES, CAUTIONS & WARNINGS
The installer should pay particular attention to the words: NOTE, CAUTION and WARNING. NOTES are intended to
clarify or make the installation easier. CAUTIONS are given to prevent equipment damage. WARNINGS are given to alert the installer that personal injury and/or equipment or property damage may occur if installation procedures are not handled properly.
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard bay be created. Never store items such as
The cooling coil must be installed in the supply air duct, downstream of the furnace. Cooled air may not be passed over the heat exchanger.
the following on, near or in contact with the fur­nace.
VENT SAFETY CHECK PROCEDURE
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
This furnace may not be common vented with any other appliance, since it requires separate, prop­erly-sized air intake and vent lines. The furnace shall not be connected to any type of B, BW or L
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door
vent or vent connector, and not connected to any portion of a factory-built or masonry chimney.
removed. To do so could result in serious personal injury and/or equipment damage.
Unitary Products Group 3
If this furnace is replacing a common-vented furnace, it may be necessary to resize the existing vent line and chimney to
650.75-N4U 035-14370-000
prevent oversizing problems for the new combination of units. Refer to the National Gas Code (ANSI Z223.1) or CAN/CGA B149.1 or.2 Installation Code (latest editions).
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1, or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and win­dows and all doors between the space in which the appli­ance(s) is located and other spaces of the building. Turn on clothes dryers. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall oper­ate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
Downflow/horizontal models are AGA/CGA listed for down­flow application into a manufactured (mobile) home.
Upflow models or horizontal applications are not approved for mobile homes.
A manufactured (mobile) home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when this standard is not applica­ble, the Standard for Manufactured Home Installations (Man­ufactured Home Sites, Communities and Set-Ups), ANSI A225.1, and/or CAN/CSA-Z240 MH Series, Mobile Homes.
CLEARANCES FOR ACCESS
Ample clearances should be provided to permit easy access to the unit. The following minimum clearances are recom­mended:
1. Twenty-four (24) inches between the front of the furnace and an adjacent wall or another appliance, when access is required for servicing and cleaning.
2. Eighteen (18) inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue/vent connections.
:
NOTE
In all cases, accessibility clearances shall take prece­dence over clearances for combustible materials where accessibility clearances are greater.
6. After it has been determined that each appliance con­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the venting system must be corrected.
8. Any corrections to the common venting system must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1 or.2 Installation Code (latest edi­tions). If the common vent system must be resized, it should be resized to approach the minimum size as determined using the appropriate tables in Appendix G of the above codes.
SPECIFIC UNIT INFORMATION
LIMITATIONS & LOCATION
This furnace should be installed in accordance with all national and local building/safety codes and requirements, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1 or CAN/CGA B149.1 or.2 Installation Code (latest editions), local plumbing or waste water codes, and other applicable codes.
Do not install the furnace in an unconditioned space or garage that could experience ambient temperatures of 32F (0C) or lower. For application in below freezing locations, See “BELOW FREEZ­ING LOCATIONS” on page 5
The furnace is not to be used for temporary heat­ing of buildings or structures under construction.
This unit must be installed in a level (1/4”) position side-to-side and front-to-back to provide proper condensate drainage.
Do not allow return air temperature to be below 55°F for extended periods. To do so may cause condensation to occur in the main fired heat exchanger.
4 Unitary Products Group
035-14370-000 650.75-N4U
vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool posi­tion.
Furnaces shall not be installed directly on carpet­ing, tile or other combustible material other than
The furnace shall be located:
wood flooring. An accessory combustible floor base is available to allow direct installation of downflow models on combustible flooring.
1. Where a minimum amount of air intake/vent pipin elbows will be required.
g and
Furnace shall be installed so the electrical compo­nents are protected from water.
The size of the unit should be based on an acceptable heat loss calculation for the structure.
Check the rating plate to make certain the unit is equipped for the type of gas supplied, and proper electrical characteristics are available.
For installations above 2,000 feet, reduce input 4% for each 1,000 feet above sea level. Refer to Form 650.75-N2.1V for correct pressure switch/orifice or other required conversion information.
A furnace installed in a residential that all burners and burner ignition devices are located not less that 18" above the garage floor, and located or protected to prevent damage by vehicles.
Allow clearances from combustible materials as listed under Clearances to Combustibles, ensuring that service access is allowed for both the burners and blower.
When the furnace is used in conjunction with a cooling coil, the furnace must be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the primary heat exchanger.
When a parallel flow arrangement is used, the dampers or other means used to control air flow shall be adequate to pre-
garage shall be located so
2. As centralized with the air distribution as possible.
3. In an area where ventilation facilities provide for safe lim­its of ambient temperature under normal operating con­ditions. Ambient temperatures must not fall below 32°F (0°C).
4. Where it will not interfere with proper air circulation in the confined space.
5. Where the outdoor combustion air/vent terminal will not be blocked or restricted.
6. Where it will not interfere with the cleanin removal of other appliances.
g, servicing or
CLEARANCES TO COMBUSTIBLES
Minimum clearances from combustible construction are shown in Table 3, “UNIT CLEARANCES TO COMBUSTI­BLES,” on page 8.
BELOW FREEZING LOCATIONS
If this furnace is installed in any area where the ambient tem­perature may drop below 32° F, a UL listed self regulated heat tape must be installed. It is recommended that self regu­lating heat tape rated at 3 watts per foot be used. This must be installed around the condensate drain lines in the uncondi­tioned space. Always install the heat tape per the manufac­turer's instructions. Cover the self-regulating heat tape with fiberglass or other heat resistant, insulating material.
Unitary Products Group 5
650.75-N4U 035-14370-000
4
Models P*XU &
G9D—UH
60 / 55 / 1200 / “B”
80 / 75 / 1200 / “B”
1.
C
4
C
12-3/4
16-1/4
16-1/4
19-3/4
19-3/4
19-3/4
23-1/4
2 (3)
23-1/4
2 (3)
1
DIMENSIONS - UPFLOW MODELS: P*UR/FG9-UP/G9T-UP
B
B
45
3/4
3/4
G A S O U T L E T 1-1/4" X 2-1/2" (A ll gas pipe connections 1/2" N P T)
45
B
A
A
20
FRO N T LEFT SIDE
FRO N T LEFT SIDE
A
C
(W IT H K .O . REM OVED )
BO TTO M IM AG E
(F R O N T )
20
D
In ta k e
onnection
B
FRO N T
TO P IM AG E
D
In ta k e
onnection
E
Vent C onnection (v e n t s iz e )
FRONT
28-1/2
TO P IM AG E
23
ALL DIMENSIONS ARE IN INCHES, AND ARE APPROXIMATE.
20
20
G A S O U T L E T 1-1/4" X 2-1/2" (A ll gas pipe connections 1/2" N P T)
OPTIONAL SIDE
OPTIONAL SIDE
RETURN CUT-OUT
RETURN CUT-OUT
(EITHER SIDE)
(EITHER SIDE)
28-1/2
28-1/2
28-1/2
7-5/8
E
Vent C onnection (v e n t s iz e )
3/4" FLANG E
7-5/8
3-1/4
3-1/4
7/8" H O LE POW ER W IRING
POW ER W IRING
1-3/4
1-3/4
T'STAT W IR ING
T'STAT W IR ING
7/8" K .O .
7/8" K.O .
A
C
9-7/8
6-7/8
6-7/8
(W IT H K .O .
23
DRAIN
CONDENSATE
REM O VED)
Models P*UR/
FG9-UP/G9T—UP
40 / 37 / 800 / A 14-1/2
BO TTO M IM A G E
(F R O N T )
60 / 55 / 1000 / B 17-1/2 80 / 75 / 1200 / B 17-1/2
80 / 75 / 1600 / C 21 100 / 95 / 1400 / C 21 100 / 95 / 2000 / C 21
120 / 112 / 2000 / D 24-1/2
140 / 130 / 2000 / D 24-1/2
1.
Vent pipe must be increased to 3” on this model.
4-1/8
4-1/8
7/8" H O LE
9-7/8
CONDENSATE DRAIN
7-5/8
7-5/8
1-1/4
1-1/4
1-3/4
1-3/4
14-1/2
14-1/2
22-3/4
22-3/4
RIGHT SIDE
RIGHT SIDE
3/4"
ABCDE
FLANG E
10-1/8 2 2 13-1/8 2 2 13-1/8 2 2
80 / 75 / 1600 / “C” 21 19
16-5/8 2 2
100 / 95 / 1400 / “C” 21 19
16-5/8 2 2
100 / 95 /2000 / “C 21 19
16-5/8 2 2 20-1/8 3
120 / 112 / 2000 / “D” 24-1/2 23
20-1/8 3
Vent pipe must be increased
1
1
3/
3/
A
17-1/2 16 17-1/2 16
1
FIGURE 1 :
TABLE 1: RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS (P*UR/FG9-UP/G9T-UP)
MODELS P*UR/FG9-UP/
G9T—UP
INPUT
MBH
OUTPUT
MBH
NOM
CFM
.
CABINET
WIDTH
IR
MEAN AIR
CFM
TEMP
RISE
1
A
TEMP
RISE °F
AFUE
@
OUTLET
TEMP
MAX
AIR
.
F
. °
DIA (IN
BLOWER
WIDTH
)
IN
(
MAX
OVER
CURRENT
PROTECT
TOTAL
HP
UNIT
AMPS
.)
40 37 800 14-1/2 92.4 35 - 65 685 165 9 6 1/4 9.0 20 14 60 55 1000 17-1/2 92.2 45 - 75 850 175 10 6 1/3 9.0 20 14 80 74 1200 17-1/2 92.0 35 - 65 1160 165 11 8 1/2 9.0 20 14
80 76 1600 21 94.3 30 - 60 1540 160 11 8 3/4 12.0 20 14 100 93 1400 21 92.2 45 - 75 1465 175 10 10 1/2 9.0 20 14 100 94 2000 21 93.0 30 - 60 1955 160 11 10 1 12.0 20 14 120 112 2000 24-1/2 92.0 45 - 75 1730 175 11 10 1 12.0 20 14 140 130 2000 24-1/2 92.0 45 - 75 2005 175 11 10 1 12.0 20 14
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition). For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V. Wire size based on copper conductors, 60°C, 3% voltage drop. Continuous return air temperature must not be below 55°F.
-
2
MIN
SIZE (AWG
@ 75
ONE WAY
WIRE
)
FT
.
2
6 Unitary Products Group
035-14370-000 650.75-N4U
T
B
3/4
C ondensate
D rain A ccess
3-1/4 X 3
45
Air Intake
3-5/8 x 3-5/8
C onn. S ize/
(
G
Pipe S ize)
A
FRO N T LEFT SIDE
B
Power
20
Wiring
7/8" K .O .
1-7/8
E
OP IMAGE/RETURN END
D
FRO N T
Vent C onnection
(v e n t s iz e )
5-3/8
F
1-3/8
3 7/8
BOTTOM IM AG E/SU PPLY END
ALL DIMENSIONS ARE IN INCHES, AND ARE APPROXIMATE.
H
19-1/4
G A S IN L E T
A
C
FRO N T
1-3/8
8
D
20
T'STAT W IR ING
7/8" K .O .
1 -3 /4
5-1/4
3-3/4
G A S IN L E T 1-1/4" X 2-1/2"
2 -3 /4
(V ent C onnection)
35
18-1/2
16-3/4
1-1/4
7 -1 /2
6 -1 /4
4 -1 /8
3-3/4
C ondensate D rain A ccess 3-1/4 X 3
6-1/2
Air Intake
3-5/8 x 3-5/8
C onn. S ize/
(
G
Pipe Size)
1-1/4
ALT. G AS IN LET
1-1/4" X 2-1/2"
2 8 -1 /2
RIGHT SIDE
MODELS P*DH/ FG9-DH/G9TDH
40 /37 / 800 / A 14-1/2 13-1/4 11-3/4 2 5-1/8 2-1/2 2 60 /55 / 1200 / B 17-1/2 16-1/4 14-3/4 2 6-5/8 2-1/4 2 80 /75 / 1200 / B 17-1/2 16-1/4 14-3/4 2 6-5/8 2-1/4 2
80 /75 / 1600 / C 21 19-3/4 18-1/4 2 8-3/8 2-1/4 2
100 /95 / 2000 / C 21 19-3/4 18-1/4 2 8-3/8 2-1/4 2
120 /112 / 2000 / D 24-1/2 23-1/4 21-3/4
1.
Vent pipe must be increased to 3” on this model.
ABCDEFG
1
2 (3)
10-1/8 2-1/4 3
FIGURE 2 : DIMENSIONS - DOWNFLOW/HORIZONTAL MODELS: P*DH/FG9-DH/G9T-DH
TABLE 2: RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS (P*DH/FG9-DH/G9T-DH)
MODELS P*DH/FG9-DH/
1
A
TEMP
RISE °F
INPUT
MBH
G9T—DH
OUTPUT
MBH
CABINET
NOM
CFM
WIDTH
.
AFUE
40 37 800 14-1/2 91.0 25 - 55 856 155 10 6 1/4 9.0 20 14 60 55 1200 17-1/2 91.0 35 - 65 1018 165 11 8 1/2 9.0 20 14 80 75 1200 17-1/2 91.0 35 - 65 1370 165 11 8 1/2 9.0 20 14
80 75 1600 21 91.0 30 - 60 1563 160 11 8 3/4 12.0 20 14 100 95 2000 21 91.0 40 - 70 1582 170 11 10 1 12.0 20 14 120 112 2000 24-1/2 91.0 40 - 70 1885 170 11 10 1 12.0 20 14
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition). For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V. Wire size based on copper conductors, 60°C, 3% voltage drop. Continuous return air temperature must not be below 55°F.
IR
MEAN AIR
CFM
TEMP
RISE
@
OUTLET
TEMP
MAX
AIR
.
BLOWER
DIA
F
. °
(IN)
WIDTH
IN
.)
(
HP
TOTAL
UNIT
AMPS
MAX
OVER
CURRENT
PROTECT
-
2
WIRE
MIN
SIZE (AWG
FT
@ 75
ONE WAY
)
.
2
Unitary Products Group 7
650.75-N4U 035-14370-000
TABLE 3: UNIT CLEARANCES TO COMBUSTIBLES
APPLICATION TOP FRONT REAR
UPFLOW 1 3 0 0 0 0 COMBUSTIBLE YES YES YES NO
DOWNFLOW / HORIZONTAL MODELS (P*DH / FG9-DH / G9T-DH)
DOWNFLOW130000
HORIZONTAL 0 3 0 1 1 0
1.
Special floor base or air conditioning coil required for use on combustible floor.
2.
Minimum of 8” clearance required to install condensate removal system.
3.
Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building joists, studs or framing.
LEFT SIDE
UPFLOW MODELS (P*UR / FG9-UP / G9T-UP)
RIGHT
SIDE
FLUE
FLOOR/
BOTTOM
1
1"
COMBUSTIBLE
CLOSET ALCOVE ATTIC
YES YES YES NO
2
NO YES YES
When the furnace is used in conjunction with a cooling coil, the furnace must be installed parallel with, or on the upstream side of the cooling unit to avoid condensation in the primary heat exchanger.
If this unit is installed in an unconditioned space and an extended power failure occurs, there will be potential damage to the condensate trap, drain lines and internal unit components. Following a power failure situation,
Do Not Operate the Unit
Until Inspection and Repair Are Performed.
When a parallel flow arrangement is used, the dampers or other means used to control air flow must be adequate to pre­vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operating of either unit unless the damper is in the full heat or cool posi­tion.
LINE CON­TACT
YES
3
DUCTWORK
The duct system's design and installation must:
1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace spec­ifications.
2. Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90A and 90B (latest editions) or appli­cable national, provincial, local fire and safety codes.
3. Create a closed duct system. The supply duct system must be connected to the furnace outlet and the return duct system must be connected to the furnace inlet. Both supply and return duct systems must terminate outside the space containing the furnace.
4. Generally complete a path for heated or cooled air to cir­culate through the air conditioning and heating equip­ment and to and from the conditioned space.
UPFLOW MODELS
SUPPLY PLENUM CONNECTION
Attach the supply plenum to the fur­nace outlet duct connection flanges. This is typically through the use of S cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage.
If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. Follow the coil instructions for installing the supply plenum.
On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi­cate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to pre­vent leaks.
The cooling coil must be installed in the supply air duct downstream of the furnace.
8 Unitary Products Group
035-14370-000 650.75-N4U
g
g
g
g
g
g
g
g
g
g
F
RETURN DUCT CONNECTION
Return air may enter the furnace through the side(s) or bot­tom depending on the type of application.
not be connected into the rear panel of the unit.
Return air may
See the specific type application installation for details. Be sure to see the Filters section of this instruction.
CLIPS
POSITION WIRE RETAINER (PROVIDED) UNDER FLANGE
FILTER
(PROVIDED
UPFLOW FILTER INSTALLATION
All applications require the use of a filter. A high velocity filter and retainer are provided for field installation.
Internal Installation
1. Select desired filter position (left/ri
Remove the correspondin
cabinet cut-outs per instruc-
ht side, or bottom).
tions provided.
2. Install snap-in retainer clips into the correspondin
from the outside rear of the cabinet (Refer to Fi To prevent cabinet air leaks, install snap-in plu
slots
ure 3.)
s (pro­vided) into the unused slots at the outside rear of the cabinet.
FURNACE
(REAR CABINET)
LEFT
RIGHT SIDE SLOTS
BOTTOM SLOTS CABINET SLOT
FILTER SUPPORT CLIPS (PROVIDED)
SIDE SLOTS
PLUG UNUSED CABINET SLOTS WITH PLUGS (PROVIDED)
RIGHT SIDE INSTALLATION SHOWN
FURNACE
FRONT
FIGURE 4 : SIDE FILTER RETAINER PLACEMENT
5. Position the filter between the wire retainer and the cabi­net wall (or floor) so it completely covers the cabinet air opening and secure the filter in place at the front of the cabinet by fastening the closed (looped) end of the retainer wire under the flanged edge of the cabinet. When properly installed the filter should fit flush with all four sides of the cabinet wall.
NOTE:
Air velocity through throw-away type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.
Side Return - External Filter
Locate and knock out the square corner locators. These indi­cate the size of the cutout to be made in the furnace side panel (Refer to Figure 5).
FIGURE 3 : FURNACE FILTER SLOT LOCATIONS
3. Install the wire retainer inside the cabinet. Insert the open ends of the wire retainer into the clip loops at the rear of the blower compartment. The retainer wire should pivot freely like a hin cabinet. (Refer to Fi
4. Install the filter(s) provided. Cut filter if necessary to match air openin beyond openin from bypassin from inside the filter. Shorten the rods, if necessary, to match final filter size.
Unitary Products Group 9
e, on the clips at the rear of the
ure 4.)
in cabinet. Filter should extend
edge as much as possible to prevent air
the filter. DO NOT remove stiffening rods
FR O N T O FU RN A CE
CORNER MARKINGS
FIGURE 5 : SIDE RETURN CUTOUT MARKINGS
Install the side filter rack following the instructions provided with that accessory. If a filter(s) is provided at another loca­tion in the return air system, the ductwork may be directly attached to the furnace side panel.
650.75-N4U 035-14370-000
NOTE:
Some accessories such as electronic air cleaners and
pleated media may require a larger side opening.
DOWNFLOW/HORIZONTAL MODELS­DOWNFLOW APPLICATION
DOWNFLOW FILTERS
A top return filter rack is supplied with
All installations must have a filter installed.
The return duct may be attached to the furnace by S-cleat, bend tabs or other approved methods. Be sure to seal the duct to the furnace to prevent air leakage.
Those applications over 1800 CFM require either return from two sides, one side and the bottom, or bottom only. For bot­tom only application, see data and notes on blower perfor­mance data tables in this manual.
Where the return duct system is not complete, the return con­nection must run full size to a location outside the utility room or basement. For further details, consult Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1, or CAN/CGA B149.1 or.2, Installation Code ­latest editions.
Bottom Return
Bottom return applications normally pull return air throu
gh a base platform or return air plenum. Be sure the return plat­form structure is suitable to support the weight of the furnace. Be sure to seal the furnace to plenum connection to prevent air leakage. (Refer to Figure 3 on page 9) and (Refer to Table 1 on page 6).
The bottom panel is equipped with a perforated opening for easy removal. Tabs must be cut with sheet metal snips to allow removing knock-out. Scribe marks are included for forming flanges for attachment of the return air ductwork.
NOTE:
If an external mounted filter rack is being used, see the instructions provided with that accessory for proper hole cut size.
Upflow attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.
A
DUCTW ORK
FIGURE 6 : DOWNFLOW FILTERS
the furnace. Two 14" x 20" permanent washable filters are supplied with each unit.
Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air duct.
Any branch duct must attach to the ver­tical ductwork above the filter height (FH) and for proper installation refer to Figure 6.
F IL T E R R A C K (FACTO RY SU PPLIED )
R A C K A N D F IL T E R S S E C U R E D
A
NOTE: FILTER ACCESS THRU DUCT­W O RK M UST BE PRO VIDED FOR REMOVAL AND CLEANING
C R O S S S E C T IO N A -A (W ITH PLENU M AND FILTERS)
IN SIDE BLO W ER SECTIO N FO R S HIPM EN T
C A S IN G S IZ E D IM E N S IO N F H 1 4 -1 /2 " 1 3 -1 /4 " 1 7 -1 /2 " 1 2 -1 /2 " 2 1 " 1 1 - 1 /2 " 2 4 -1 /2 " 9 -3 /4 "
FILTER S
FILTER RACK
BRANCH DUCTS
FH
10 Unitary Products Group
The filter rack (provided) should be secured to the center of the front and rear flanges at the furnace top. Drill a hole through the front and rear duct flange into the filter rack and secure it with a sheet metal screw.
Refer to the unit rating plate for furnace model then see the dimensions page of this instruction for return air plenum dimensions. Install the plenum following instructions under Ductwork in this instruction.
035-14370-000 650.75-N4U
VENT (MAINTAIN REQUIRED CLEARANCES TO COMBUSTIBLES)
GAS PIPING
SEDIMENT TRAP
12"
30" MIN WORK AREA
SHEET METAL IN FRONT OF FURNACE COMBUSTION AIR OPENINGS IS RECOMMENDED
RETURN AIR
SUPPLY AIR
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY THE INTERSECTION OF FURNACE TOP AND TWO SIDES AND BUILDING JOISTS, STUDS OR FRAMING
DOWNFLOW / HORIZONTAL MODELS ­HORIZONTAL APPLICATION
DOWNFLOW FURNACE
WARM AIR PLENUM WITH 1" FLANGES
FIBERGLASS INSULATION
FIBERGLASS TAPE UNDER FLANGE
COMBUSTIBLE FLOOR BASE ACCESSORY
FIGURE 7 : COMBUSTIBLE FLOOR BASE
ACCESS’Y
SUPPLY AIR DUCTS
Installations on combustible material or floors must use a combustible floor base (shown in Figure 7 - 1CB0314, 17, 21 & 24) as specified on the rating plate or a matching cooling coil. Follow the instructions supplied with the combustible floor base accessory.
This base can be replaced with a matching cooling coil, prop­erly sealed to prevent leaks. Follow the cooling coil instruc­tions for installing the plenum.
Downflow furnaces may be installed horizontally with the sup­ply airflow toward the left or right by laying the unit on the left or right side panel.
Do not install the unit on the rear panel.
After determining the best orientation, lay the unit on top of the shipping carton to protect the finish. The appropriate elec­trical knock-outs for power wiring, control wiring and gas pip­ing should be removed at this time.
For horizontal application, return air may enter through the end only.
Return air may not be connected into the rear
panel of the unit.
HORIZONTAL FILTERS
All filters and mounting provision must be field supplied. Fil­ters(s) may be located in the duct system external to the fur­nace or in a return filter grille(s).
ATTIC INSTALLATION
All downflow application supply duct systems must be designed and installed in accordance with the standards of NFPA 90A and 90B, and/or all local codes.
Unitary Products Group 11
FIGURE 8 : TYPICAL ATTIC INSTALLATION
650.75-N4U 035-14370-000
g
This appliance is design certified for line contact for furnaces installed horizontally. The intersection of the furnace top and sides form a line. This line may be in contact with combustible material. Refer to “Where it will not interfere with the cleanin servicing or removal of other appliances." Section on page 5 in this manual for additional information.
Secure a platform constructed of plywood or other building material to the floor joists. Sheet metal, 12" in front of the fur­nace combustion air openings is recommended. (Refer to Figure 9.)
Note:
The unit must be elevated to allow clearnace fo the
condensate trap and drain pipe
. .
If this furnace is installed over a finished space, a condensate safety pan must be installed.
adequate height to ensure the unit will not be subject to water damage.
,
When suspending the furnace from rafters or floor joists using rod, pipe or straps, refer to Physical Data and,Table 3, “UNIT CLEARANCES TO COMBUSTIBLES,” on page 8, for furnace weights to determine suitable means of suspension.
Angle supports should be placed at the supply aire end and near the blower deck. (Refer to Figure 9.)
Do not support
at return air end of unit.
Units may also be suspended by using straps or other mate­rial at the same location. All four suspension points must be level to ensure quiet furnace operation.
In any application where temperatures below freezing are possible, See “BELOW FREEZING LOCATIONS” on page 5
GAS PIPING
When a furnace is installed in an attic or other insulated space, keep all insulating materials at least 12" away from furnace and burner combus­tion air openings.
NOTE:
See crawl space installation for suspending the fur­nace in attic installations.
ANGLE IRON BRACKET
1" MAX BETWEEN ROD & FURNACE
6" MIN BETWEEN ROD & FURNACE
SUPPORT ROD
1" MAX BETWEEN ROD & FURNACE
FIGURE 9 : TYPICAL FURNACE INSTALLATION
USING SUSPENSION MATERIALS
CRAWL SPACE INSTALLATION
The furnace can be hung from floor hoists or installed on suit­able blocks or pad. Blocks or pad installations shall provide
The gas supply must be installed in accordance with the cur­rent National Fuel Gas Code, ANSI Z223.1 (in the U.S.) or CAN-B149.1 or.2 (in Canada) installation codes and all appli­cable local and utility requirements. All pipe and fitting mate­rial, pipe size and installation procedures must comply with the appropriate code. Some utilities may require larger pipe sizes than shown in the code. Gas piping may be connected from either side of the furnace. Each side of the unit has two gas pipe entry knockouts.
For downflow/horizontal models,
piping before determining the correct gas pipe entry
plan your combustion air
. Use 90 degree service elbow(s), or short nipples and conventional 90 degree elbow(s) to enter through the cabinet access holes..
An overpressure protection device, such as a pressure regulator, which conforms to the National Fuel Gas Code, ANSI Z223.1 (U.S.) or CAN­B149.1 or.2 (Canada) and acts to limit the down­stream pressure to a value that does not exceed
0.5 PSI (14" w.c.), must be installed in the gas pip­ing system upstream of the furnace. Failure to do so may result in a fire or explosion or cause dam­age to the furnace or some of its components.
12 Unitary Products Group
Loading...
+ 28 hidden pages