York PS8-DH User Manual

TECHNICAL GUIDE
AFFINITY MODELS: PS8*DH
GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW/HORIZONTAL FURNACES STANDARD & Low NOx
NATURAL GAS 40 - 130 MBH INPUT
EFFICIENCY RATING CERTIFIED
279744-YTG-A-0407
DESCRIPTION
These high efficiency, downflow/horizontal compact units employ induced combustion, reliable hot surface ignition and high heat transfer tubular heat exchangers.
These furnaces are designed for residential installation in a closet, attic or garage and are ideal for commerci al applica­tions. All units are factory assembled, wired and tested to assure safe dependable and economical installation and operation.
These units are Category I listed and may be common vented with another gas appliance as allowed by the National Fuel Gas Code ANSI Z223.1 (latest edition).
WARRANTY
20-year limited warranty on the heat exchanger. 10-year heat exchanger warranty on commercial applica-
tions. 5-year limited parts warranty.
FEATURES
Downflow/Horizontal models may be easily applied without any field conversion
Top vent connection allows installation in narrow loca­tions
Electronic hot surface ignition with high reliability and dependability
100% shut off main gas valve for added safety
High quality inducer motor for quiet operation
Standard terminals for controlling humidifiers & EAC's
40 VA control transformer, fuse protected
Easy to connect power and control wiring
Efficiency ratings of 80 AFUE attained by using tubular heat exchangers
Cooling relay standard for easy installation of add-on cooling
Blower off-delay for cooling SEER improvement
Multi-speed PSC, direct-drive blower motors to match cooling requirements
Adjustable fan-off settings to eliminate "cold-blow"
Compact 40-in height allows installation in small space confines
All models are propane convertible
Low NOx models have been designed to meet specific code requirements.
All models are propane convertible.
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specific ations are subject to change without notice.
Visit us on the web at www.york.com for the most up-to-date technical information.
Additional rating information can be found at www.gamanet.org.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
279744-YTG-A-0407
B
A
FRONT
20
3/4
40
B
1-7/8
D
FRONT
TOP IMAGE
5
20
T’STAT WIRING
7/8” K.O.
GAS INLET
1-1/4” X 2-1/2”
2-1/2
28-1/2
30-1/8
LEFT SIDE
4” Dia.
3-3/4
(VENT CONNECTION)
1-1/4
BOTTOM IMAGE
20
FRONT
D
31-1/8
A
C
1-1/8
7-3/8
5-3/4
ALT. GAS INLET
1-1/4” X 2-1/2”
RIGHT SIDE
CABINET AND DUCT DIMENSIONS
Models CFM
Cabinet
Size
ABCD
PS8A12(N,L)040DH11 1200 A 14 1/2 13 1/4 12 10 3/8 PS8A12(N,L)060DH11 1200 A 14 1/2 13 1/4 12 10 3/8 PS8A12(N,L)080DH11 1200 A 14 1/2 13 1/4 12 10 3/8 PS8B16(N,L)080DH11 1600 B 17 1/2 16 1/4 15 11 3/4 PS8B12(N,L)100DH11 1200 B 17 1/2 16 1/4 15 11 3/4 PS8C16(N,L)100DH11 1600 C 21 19 3/4 18-1/2 13 1/2 PS8C20(N,L)100DH11 2000 C 21 19 3/4 18-1/2 13 1/2 PS8C16(N,L)115DH11 1600 C 21 19 3/4 18-1/2 13 1/2 PS8C20(N,L)115DH11 2000 C 21 19 3/4 18-1/2 13 1/2 PS8D20(N,L)130DH11 2000 D 24 1/2 23 1/4 22 15 1/4
Cabinet Dimension
2 Unitary Products Group
279744-YTG-A-0407
RATINGS & PHYSICAL / ELECTRICAL DATA
Models
PS8A12(N,L)040DH11 40 32 1200 14-1/2 9.0 80.0 20 - 50 PS8A12(N,L)060DH11 60 48 1200 14-1/2 9.0 80.0 25 - 55 PS8A12(N,L)080DH11 80 64 1200 14-1/2 9.0 80.0 35 - 65 PS8B16(N,L)080DH11 80 64 1600 17-1/2 12.0 80.0 25 - 55 PS8B12(N,L)100DH11 100 80 1200 17-1/2 12.0 80.0 40 - 70 PS8C16(N,L)100DH11 100 80 1600 21 12.0 80.0 25 - 55 PS8C20(N,L)100DH11 100 80 2000 21 14.0 80.0 25 - 55 PS8C16(N,L)115DH11 115 92 1600 21 12.0 80.0 35 - 65 PS8C20(N,L)115DH11 115 92 2000 21 14.0 80.0 30 - 60 PS8D20(N,L)130DH11 130 104 2000 24-1/2 14.0 80.0 40 - 70
Models
PS8A12(N,L)040DH11 40 150 1/3 6.2 10 x 8 20 14 100 PS8A12(N,L)060DH11 60 155 1/3 6.2 10 x 8 20 14 110 PS8A12(N,L)080DH11 80 165 1/3 6.2 10 x 8 20 14 120 PS8B16(N,L)080DH11 80 160 3/4 11.0 11 x 10 20 14 130 PS8B12(N,L)100DH11 100 170 1/2 7.0 10 x 8 20 14 125 PS8C16(N,L)100DH11 100 155 3/4 11.0 11 X 10 20 14 140 PS8C20(N,L)100DH11 100 155 1 12.2 11 x 11 20 12 140 PS8C16(N,L)115DH11 115 165 3/4 11.0 11 x 10 20 14 150 PS8C20(N,L)115DH11 115 160 1 12.2 11 x 11 20 12 150 PS8D20(N,L)130DH11 130 170 1 12.2 11 x 11 20 12 160
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes. The furnace shall be installed so that the electrical components are protected from water. Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Input Output
MBH MBH CFM In. °F
Input
MBH °F Hp Amps In. Lbs.
Max. Outlet
Air Temp
Nominal
Airflow
Blower
Cabinet
Width
Blower
Size
Total Unit
Amps
Max
Over-Current
Protect
AFUE
Min. wire Size
(awg) @ 75 ft
one way
Air Temp.
Operation
Rise
Weight