York PHE6B36, PHE6B48, PHE6B60 Installation Manual

Page 1
®
INSTALLATION MANUAL
SINGLE PACKAGE HEAT PUMP / ELECTRIC HEAT
MODELS: PHE6 SERIES 3 – 5 TONS (3 PHASE)
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AIRFLOW PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
LIST OF FIGURES
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Bottom Duct Dimensions (inches) . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Rear Duct Dimensions (inches) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Field Control Wiring Diagram For Heat Pump Models . . . . . . 7
Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 7
LIST OF TABLES
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical Data - 208-3-60 - Single Source Power . . . . . . . . . . . . . . . 8
Electrical Data For 208-3-60 Multi Source Power . . . . . . . . . . . . . . . 8
Electrical Data - 230-3-60 Single Source Power . . . . . . . . . . . . . . . . 9
Electrical Data For 230-3-60 Multi Source Power . . . . . . . . . . . . . . . 9
Single-point Wiring Kit Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Airflow Performance - Side Duct Application . . . . . . . . . . . . . . . . . . 12
®
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
TYPICAL WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Demand Defrost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Blower Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Measuring External Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . .17
Connection Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Ladder Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Electric Heat Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Recommended Blower Speed for Electric Heat . . . . . . . . . . . . . . . .13
Electric Heat Blower Off Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Indoor Blower Control Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . .14
Delay Profile Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Demand Defrost Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Test Pins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Demand Defrost Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Thermostat Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
SECTION I: GENERAL INFORMATION
PHE units are factory assembled heat pumps designed for outdoor installation on a roof top or a slab. Field-installed optional electric heater accessories are available to provide supplemental electric heat com­bined with electric cooling and heating.
The units are completely assembled on rigid, removable base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require only electric power condensate drain and duct connections at the point of installation.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
Johnson Controls Unitary Products 5285477-UIM-A-1016
WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property dam­age.
!
WARNING
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal­function, death, personal injury and/or property damage. Only a
qualified contractor, installer or service agency should install this product.
Page 2
5285477-UIM-A-1016
!
CAUTION
This product must be installed in strict compliance with the installa­tion instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
!
WARNING
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. Improper installation, adjustment, alteration, service or mainte­nance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
!
CAUTION
This system uses R-410A refrigerant which operates at higher pres­sures than R-22. No other refrigerant may be used in this system. Gage sets, hoses, refrigerant containers and recovery systems must be designed to handle R-410A. If you are unsure, consult the equip­ment manufacturer. Failure to use R-410A compatible servicing equipment may result in property damage or injury.
Due to system pressure, moving parts, and electrical components, installation and servicing of air conditioning equipment can be hazard­ous. Only qualified, licensed service personnel should install, repair, or service this equipment. Unlicensed personnel can perform basic main­tenance functions of cleaning coils and filters and replacing filters.
Observe all precautions in the literature, labels, and tags accompanying the equipment whenever working on air conditioning equipment. Be sure to follow all other applicable safety precautions and codes includ­ing.
Wear safety glasses and work gloves. Use quenching cloth and have a fire extinguisher available during brazing operations.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing.
REPLACEMENT PARTS
Contact your local Unitary Products parts distribution center for autho­rized replacement parts.
SECTION III: MODEL NUMBER NOMENCLATURE
PHE 4 A 24 2 1 A
1234689
1. Model Family PHE - packaged heat pump with electric heat PCG - packaged A/C with gas heat, PHG - packaged heat pump with gas heat, PCE - packaged A/C with electric heat,
2. Nominal Cooling Efficiency 4 = 14 SEER, 6 = 16 SEER, etc.
3. Cabinet Size A = small 35 x 51, B = large 45 x 51
4. Nominal Air Conditioning Cooling Capacity BTUx1000 24 = 24,000 BTU, etc.
Examples:
PHE6B4221A is a packaged heat pump, 16 SEER, 3-1/2 ton, large cabinet, 230 volt, single phase model, (first generation, first release).
5. Gas Heating Input BTU/Hr x 1000 050 = 50,000 BTU/Hr. input, blank = electric heat
6. Voltage-Phase-Frequency 2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
7. NOx Approval X = low-NOx, blank = not low-Nox
8. Generation Level 1 = first generation
9. Revision Level A = original release, B = second release
SECTION IV: INSTALLATION
LIMITATIONS
These units must be installed in accordance with the following national and local safety codes.
1. National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions).
2. Local plumbing and waste water codes and other applicable local codes.
2 Johnson Controls Unitary Products
Refer to Tables 2-3 for unit weight & dimensions, Tables 5-9 for electri­cal data and Table 10 for physical data.
If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense.
Size of unit for proposed installation should be based on heat loss/heat gain calculations made in accordance with industry recognized proce­dures such as the Air Conditioning Contractors of America (manual J).
Page 3
5285477-UIM-A-1016
OUTDOOR COIL
ECM BLOWER MOTOR CONTROL BOARD
AMBIENT TEMPERATURE SENSOR
OUTDOOR TXV
REVERSING VALV E
INDOOR TXV
COMPRESSOR
INDOOR COIL
REMOVABLE BASE RAILS
FIGURE 1: Component Location Table 1: Unit Limitations
Model Unit Voltage
B36 208/230-3-60 187 252 125 B48 208/230-3-60 187 252 125 B60 208/230-3-60 187 252 125
FAN MOTOR
OUTDOOR FAN
BLOWER MOTOR
COIL GUARD PANEL
DEFROST CONTROL BOARD
CAPACITOR
TRANSFORMER
OPTIONAL ELECTRIC HEAT KIT
INDOOR BLOWER
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (°F)
A0588-001
Johnson Controls Unitary Products 3
Page 4
5285477-UIM-A-1016
LOCATION
Use the following guidelines to select a suitable location for these units:
1. Unit is designed for
2. Outdoor coils must have an unlimited supply of air. Where a choice of location is possible, position the unit on either north or east side of building.
3. Suitable for mounting on roof curb.
outdoor installation only.
!
CAUTION
Before lifting, make sure the unit weight is distributed equally on the rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.
!
WARNING
Do not attach supply and return duct work to the bottom of the unit base pan as the drain pan could be compromised.
4. For ground level installation, a level pad or slab should be used. The thickness and size of the pad or slab used should meet local codes and support unit weight. Do not tie the slab to the building foundation.
5. Roof structures must be able to support the weight of the unit and its options/accessories. Unit must be installed on a solid, level roof curb or appropriate angle iron frame.
6. Maintain level tolerance to 1/8” across the entire width and length of unit.
!
WARNING
Do not permit overhanging structures or shrubs to obstruct outdoor air discharge outlet.
CLEARANCES
All units require certain clearances for proper operation and service. Refer to Table 4 for the clearances required for construction, servicing and proper unit operation.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreader bars, whose length exceeds the largest dimension across the unit,
MUST be used across the top of the unit.
!
CAUTION
If a unit is to be installed on a roof curb other than a Unitary Products roof curb, gasket or sealant must be applied to all surfaces that come in contact with the unit underside.
!
CAUTION
All panels must be secured in place when the unit is lifted. The outdoor coils should be protected from rigging cable damage with plywood or other suitable material.
"D"
CENTER OF
COMPRESSOR
"A"
FRONT OF UNIT
X
FIGURE 2: Unit 4 Point Load Weight
"B"
GRAVITY
Y
A0295-001
"C"
Table 2: Weights and Dimensions
Model Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.)
Shipping Operating X Y ABCD
PHE6B36 453 448 29 15 158 108 101 86 PHE6B48 501 496 29 15 168 130 119 84 PHE6B60 528 523 30 15 177 136 128 87
4 Johnson Controls Unitary Products
Page 5
HIGH VOLTAGE CONNECTION 7/8”
HIGH VOLTAGE CONNECTION 1-3/32”
COMPRESSOR ACCESS PANEL
5285477-UIM-A-1016
COIL GUARD
C
HEAT SECTION ACCESS PANEL
CONDENSATE DRAIN
BLOWER ACCESS PANEL
A
CONTROL / HEAT ACCESS PANEL
B
LOW VOLTAGE CONNECTION
A0379-001
FIGURE 3: Unit Dimensions
Table 3: Unit Dimensions
Model
ABC
Dimensions (inches)
B36 51-1/4 45-3/4 49 B48 51-1/4 45-3/4 53 B60 51-1/4 45-3/4 55
Table 4: Unit Clearances
Direction Distance (inches) Direction Distance (inches)
1
Top
36 Right Side 36
Side Opposite Ducts 36 Left Side 24
Duct Panel 0 Bottom 2
1. Minimum Clearance of 1inch all sides of supply air duct for the first 3 foot of duct for 20 & 25 kW., zero inches there after. For all other heaters, zero inch clearance all sides for entire length of duct.
2. Units must be installed outdoors. Over hanging structure or shrubs should not obscure outdoor air discharge outlet.
3. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
NOTE: For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch? between combustible roof curb material and this supply
air duct.
3
1
Johnson Controls Unitary Products 5
Page 6
5285477-UIM-A-1016
D
C
A
B
A
Model A B C D E F
36, 48, 60 14 13.5 5 3.5 47.5 42
FIGURE 4: Bottom Duct Dimensions (inches)
16
RETURN AIR DUCT
SUPPLY AIR DUCT
VIEW LOOKING UP AT BOTTOM OF UNIT
F
1.75
E
A0343-001
DUCTWORK
NOTICE
All units are shipped in the horizontal supply/return configuration. It is important to reduce the possibility of any air leakage through the bot­tom duct covers (resulting from cut, torn, or rolled gasket) due to improper handling or shipping processes. To ensure a good tight seal, it is recommended that silicone caulk and/or foil tape be applied along the cover edges.
These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the following steps:
1. Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws securing each duct cover (save these screws to use in Step 2).
2. Install the duct covers (removed in step one) to the rear supply and return air duct openings. Secure with the screws used in step one.
3. Seal duct covers with silicone caulk.
Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.
A closed return duct system shall be used. This shall not preclude use of economizers or ventilation air intake. Flexible duct connectors are recommended in the supply and return duct work to minimize the trans­mission of vibration and noise.
!
CAUTION
When fastening duct work to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Outdoor duct work must be insulated and water­proofed.
SUPPLY
15.6
6.75
A0344-001
Model A B
36, 48, 60 13.6 14
FIGURE 5: Rear Duct Dimensions (inches)
AIR DUCT
A
B
RETURN AIR DUCT
A
4.3
NOTICE
Be sure to note supply and return openings.
Refer to Figures 4 and 5 for information concerning rear and bottom supply and return air duct openings.
FILTERS
Proper filter size is very important. Filter size, type and pressure drop should always be considered during duct system design.
All 3 phase units include a filter frame kit which is shipped inside the unit from production. Field installation is required.
A filter rack and high velocity filters are standard on three phase units. Filters must always be used and must be kept clean. When filters
become dirt laden, insufficient air will be delivered by the blower, decreasing your units efficiency and increasing operating costs and wear-and-tear on the unit and controls.
Filters should be checked monthly; this is especially important since this unit is used for both heating and cooling.
6 Johnson Controls Unitary Products
Page 7
5285477-UIM-A-1016
p
CONDENSATE DRAIN
A condensate trap must be installed in the condensate drain. The plumbing must conform to local codes.
Use Teflon tape or pipe thread compound if needed.
!
CAUTION
Hand tighten only.
SERVICE ACCESS
Access to all serviceable components is provided at the following loca­tions:
• Coil guards
• Unit top panel
• Corner posts
• Blower access panel
• Control access panel
• Indoor coil access panel
• Compressor access panel
• Heat section access panel
Refer to Figure 3 for location of these access locations and minimum clearances in Table 4.
!
CAUTION
This system uses R-410A refrigerant which operates at higher pres­sures than R-22. No other refrigerant may be used in this system. Gauge sets, hoses, refrigerant containers and recovery systems must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing equipment may result in property damage or injury.
!
WARNING
Wear safety glasses and gloves when handling refrigerants. Failure to follow this warning can cause serious personal injury.
Refer to Figure 13 for the R-410A Quick Reference Guide.
THERMOSTAT
The room thermostat should be located on an inside wall approximately 60" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Sealant should be used behind thermostat to prevent air infiltration. Follow manufacturer's instructions enclosed with the thermostat for general installation proce­dure. Color coded insulated wires (minimum #18 AWG) should be used to connect thermostat to unit. See Figure 6.
If a field supplied electric heat kit is installed, this unit requires the use of a 3 heat / 2 cool (3H/2C) heat pump thermostat for proper operation. For units installed with 6HK heat kits of 18 kW and larger, a 4H/2C heat pump thermostat should be used. Do not use power stealing thermo­stats.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be
maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1.
The wiring entering the cabinet must be provided with mechanical strain relief.
A fused disconnect switch should be field provided for the unit. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.
Electrical service must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the main distribution panel and properly fused.
Refer to Figures 6 and 7 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.
Unit comes wired for 230 volt power. If supply power is 208 volt, wires connected to the control transformer 230V tap must be moved to the 208V tap.
Minimum wire size of 18 AWG wire should be used for all eld installed control wiring.
THERMOSTAT
C
R
O
YorY1
Y2
G
W2
W1
HUM
NOTE:
Heat Antici
FIGURE 6: Typical Field Control Wiring Diagram For Heat Pump
FIGURE 7: Typical Field Power Wiring Diagram
ator should be set at 0.35 AMPS for all models.
Models
&217$&725
*5281'
/8*
5()(572(/(&75,&$/ '$7$7$%/(6726,=( 7+(',6&211(&7
YELLOW/BLACK
WHITE/BLACK
),(/'6833/,('
CONTROL HARNESS
BLUE
RED
ORANGE
YELLOW
GREEN
WHITE
GRAY
',6&211(&7
C
R
O
Y1
Y2
G
W2
W1
HUM
7+5(( 3+$6(
32:(5
6833<
$
A0560-001
NOTICE
In some horizontal applications, the service disconnects on the elec­tric heat kits must be rotated 180° so the up position of the discon­nect is the ON position. This service disconnect orientation change is required by UL1995, Article 26.19 (in reference to all circuit break­ers).
Johnson Controls Unitary Products 7
Page 8
5285477-UIM-A-1016
Table 5: Electrical Data - 208-3-60 - Single Source Power
Model
Compressor
OD Fan
Motor
Blower
Motor
Electric Heat Option
Heater Kit
Heater
kW
Stages
Heater
Amps
MCA
(Total
Unit)
1
Fuse
Max
2
or
Breaker
3
Size (Total
MCA
(Unit Less
Heater)
Unit)
RLA LRA MCC FLA FLA 208 208 208 208 208 208 208 208
none -- -- -- 20.0 30 20.0 30 - -
PHE6B36 11.6 73.0 18.1 1.7 3.8
6HK06501025 7.2 1 20.0 45.0 50 20.0 30 25.0 25 6HK06501525 10.8 1 30.0 57.5 60 20.0 30 37.5 40
none -- -- -- 24.6 35 24.6 35 - -
6HK06501025 7.2 1 20.0 49.6 50 24.6 35 25.0 25
PHE6B48 14.0 83.1 21.9 1.7 5.4
6HK06501525 10.8 1 30.0 62.1 70 24.6 35 37.5 40 6HK06501825 13.0 1 36.1 69.7 70 24.6 35 45.1 50 6HK16502025 14.4 2 40.0 74.6 80 24.6 35 50.0 *
none -- -- -- 29.0 45 29.0 45 - -
6HK06501025 7.2 1 20.0 53.9 60 29.0 45 25.0 25
PHE6B60 16.2 110.0 25.3 1.7 7.0
6HK06501525 10.8 1 30.0 66.4 70 29.0 45 37.5 40 6HK06501825 13.0 1 36.1 74.1 80 29.0 45 45.1 50 6HK16502025 14.4 2 40.0 78.9 80 29.0 45 50.0 * 6HK16502525 18.0 2 50.0 91.4 100 29.0 45 62.5 *
NOTES: Single-source power MCA and MOP requirements are given here for reference if the unit is to be installed with a field-installed single-point power modification. * - Breakers for heaters are included in the 20kW and 25kW heater kits.
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size to be field installed.
1
Max
2
Fuse
Breaker
3
Size
(Unit
Less
Heater)
or
1
MCA
Unit
(Heater
Only)
Max
2
Fuse
or
Breaker
3
Size
(Heater
Only)
Table 6: Electrical Data For 208-3-60 Multi Source Power
Electric Heat Option
Heater Kit
Model
Compressor
OD Fan
Motor
Blower
Motor
RLA LRA MCC FLA FLA 208 208 208 208 208 208 208 208
MULTI SOURCE:
MULTI SOURCE: COMPRESSOR CIRCUIT
AND HEAT CIRCUITS
CIRCUIT #1 COMPRESSOR CIRCUIT #2 1ST STAGE HEAT CIRCUIT #3 2ND STAGE HEAT
none -- -- -- 20.0 30 -- -- -- --
PHE6B36 11.6 73.0 18.1 1.7 3.8
6HK06501025 7.2 1 20.0 20.0 30 25.0 25 -- -­6HK06501525 10.8 1 30.0 20.0 30 37.5 40 -- --
none -- -- -- 24.6 35 -- -- -- --
6HK06501025 7.2 1 20.0 24.6 35 25.0 25 -- --
PHE6B48 14.0 83.1 21.9 1.7 5.4
6HK06501525 10.8 1 30.0 24.6 35 37.5 40 -- -­6HK06501825 13.0 1 36.1 24.6 35 45.1 50 -- -­6HK16502025 14.4 2 40.0 24.6 35 25.0 25 25.0 25
none -- -- -- 29.0 45 -- -- -- --
6HK06501025 7.2 1 20.0 29.0 45 25.0 25 -- --
PHE4B60 16.2 110.0 25.3 1.7 7.0
6HK06501525 10.8 1 30.0 29.0 45 37.5 40 -- -­6HK06501825 13.0 1 36.1 29.0 45 45.1 50 -- -­6HK16502025 14.4 2 40.0 20.0 45 25.0 25 25.0 25 6HK16502525 18.0 2 50.0 29.0 45 31.3 35 31.3 35
1. Minimum Circuit Ampacity.
Heater
kW
Stages
Heater
Amps
MULTI SOURCE
MCA
Amps
Max Fuse
1
Breaker
Size
or
MCA Amps
1
Fuse or Breaker
Max
MCA1 Amps
Size
CIRCUIT #1 CIRCUIT #2 CIRCUIT #3
Max
Fuse or
Breaker
Size
8 Johnson Controls Unitary Products
Page 9
5285477-UIM-A-1016
Table 7: Electrical Data - 230-3-60 Single Source Power
1
Max
2
Fuse
or
Breaker
3
Size
(Unit
Less
Heater)
1
MCA
Unit
(Heater
Only)
Fuse
Breaker
Size
(Heater
Max
2
3
Only)
Model
Compressor
OD
Fan
Motor
Blower
Motor
Electric Heat Option
Heater Kit
Heater
kW
Stages
Heater
Amps
MCA (Total
Unit)
1
Max
2
Fuse
or
Breaker
3
Size (Total
MCA
(Unit Less
Heater)
Unit)
RLA LRA MCC FLA FLA 230 230 230 230 230 230 230 230
none -- -- -- 20.0 30 20.0 30 - -
PHE6B36 11.6 73.0 18.1 1.7 3.8
6HK06501025 8.8 1 22.1 47.6 50 20.0 30 27.6 30 6HK06501525 13.2 1 33.1 61.4 70 20.0 30 41.4 45
none -- -- -- 24.6 35 24.6 35 - -
6HK06501025 8.8 1 22.1 52.2 60 24.6 35 27.6 30
PHE6B48 14.0 83.1 21.9 1.7 5.4
6HK06501525 13.2 1 33.1 66.0 70 24.6 35 41.4 45 6HK06501825 15.9 1 39.9 74.5 80 24.6 35 49.9 50 6HK16502025 17.6 2 44.2 79.8 80 24.6 35 55.2 *
none -- -- -- 29.0 45 29.0 45 - -
6HK06501025 8.8 1 22.1 56.6 60 29.0 45 27.6 30
PHE6B60 16.2 110.0 25.3 1.7 7.0
6HK06501525 13.2 1 33.1 70.4 80 29.0 45 41.4 45 6HK06501825 15.9 1 39.9 78.8 80 29.0 45 49.9 50 6HK16502025 17.6 2 44.2 84.2 90 29.0 45 55.2 * 6HK16502525 22.0 2 55.2 98.0 100 29.0 45 69.0 *
NOTES: Single-source power MCA and MOP requirements are given here for reference if the unit is to be installed with a field-installed single-point power modification.
* - Breakers for heaters are included in the 20kW and 25kW heater kits.
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size to be field installed.
or
Table 8: Electrical Data For 230-3-60 Multi Source Power
Electric Heat Option
Heater Kit
Model
Compressor
OD Fan
Motor
Blower
Motor
RLA LRA MCC FLA FLA
MULTI SOURCE:
MULTI SOURCE: COMPRESSOR CIRCUIT
AND HEAT CIRCUITS
CIRCUIT #1 COMPRESSOR CIRCUIT CIRCUIT #2 1ST STAGE HEAT CIRCUIT #3 2ND STAGE HEAT
none -- -- -- 20.0 30 -- -- -- --
PHE6B36 11.6 73.0 18.1 1.7 3.8
6HK06501025 8.8 1 22.1 20.0 30 27.6 30 -- -­6HK06501525 13.2 1 33.1 20.0 30 41.4 45 -- --
none -- -- -- 24.6 35 -- -- -- --
6HK06501025 8.8 1 22.1 24.6 35 27.6 30 -- --
PHE6B48 14.0 83.1 21.9 1.7 5.4
6HK06501525 13.2 1 33.1 24.6 35 41.4 45 -- -­6HK06501825 15.9 1 39.9 24.6 35 49.9 50 -- -­6HK16502025 17.6 2 44.2 24.6 35 27.6 30 27.6 30
none -- -- -- 29.0 45 -- -- -- --
6HK06501025 8.8 1 22.1 29.0 45 27.6 30 -- --
PHE4B60 16.2 110.0 25.3 1.7 7.0
6HK06501525 13.2 1 33.1 29.0 45 41.4 45 -- -­6HK06501825 15.9 1 39.9 29.0 45 49.9 50 -- -­6HK16502025 17.6 2 44.2 29.0 45 27.6 30 27.6 30 6HK16502525 22.0 2 55.2 29.0 45 34.5 35 34.5 35
1. Minimum Circuit Ampacity.
Heater
kW
Stages
230 230 230 230 230 230 230 230
Heater
Amps
MCA Amps
Max Fuse
1
Breaker
MULTI SOURCE
or
Size
MCA1 Amps
Max Fuse or Breaker
Size
MCA1 Amps
CIRCUIT #1 CIRCUIT #2 CIRCUIT #3
Max
Fuse or
Breaker
Size
Johnson Controls Unitary Products 9
Page 10
5285477-UIM-A-1016
Table 9: Physical Data
NOMINAL TONNAGE AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH) 36.5 49.1 60.0 AHRI net capacity (MBH) 36.0 48.0 58.0 EER 12.5 12.5 12.0 SEER 16.0 16.0 16.0 Nominal CFM 1200 1600 1800 System power (KW) 3.0 3.6 4.6 Refrigerant type R410A R410A R410A Refrigerant charge (lb-oz) 11-13 12-13 15-8
AHRI Heating Performance
47 Capacity Rating (MBH) 33.8 45.5 56.0 System Power (kW/COP) 3.6 3.7 3.6 17 F Capacity Rating (MBH) 19.6 26.0 32.0 HSPF (BTU/Watts-hr.) 8.0 8.0 8.0
Dimensions (inches)
Length 51-1/4 51-1/4 51-1/4 Width 45-3/4 45-3/4 45-3/4 Height 49 53 55 Operating WT. (lbs.) 448 496 523
Compressors
Type Scroll Scroll Scroll Stages 2 2 2
Outdoor Coil Data
Face area (Sq. Ft.) 19.5 23.8 25.9 Rows 2 2 2 Fins per inch 22 22 22 Tube diameter 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Refrigerant control TXV TXV TXV Table 10 Continued on next page.
Indoor Coil Data
Face area (Sq. Ft.) 6.3 6.3 6.3 Rows 3 3 4 Fins per inch 16 16 16 Tube diameter 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Refrigerant control TXV TXV TXV
Outdoor Fan Data
Fan diameter (Inch) 26 26 26 Type Prop Prop Prop Drive type Direct Direct Direct No. speeds 1 1 1 Motor HP each 1/3 1/3 1/3 RPM 850 850 850 Nominal total CFM 3200 3200 3200
Direct Drive Indoor Blower Data
Fan Size (Inch) 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Motor HP each 1/2 3/4 1 RPM 1200 Max 1200 Max 1200 Max Frame size 48 48 48
Filters
Filter size B B B
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable
Quantity - Size
filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for replacement filter sizes. Filter sizes: A=20x20, B=20x30.
PHE6B36 PHE6B48 PHE6B60
3.0 4.0 5.0
10 Johnson Controls Unitary Products
Page 11
5285477-UIM-A-1016
COMPRESSORS
!
CAUTION
This system uses R-410A refrigerant which operates at higher pres­sures than R-22. No other refrigerant may be used in this system.
The compressor used in this product is specifically designed to operate with R-410A refrigerant and cannot be interchanged. Compressors used in PHE6 models contain two internal bypass ports which enable the compressor to operate at 67% part load capacity.
!
CAUTION
Scroll compressors require proper rotation to operate properly. Fail­ure to check and correct rotation may result in property damage.
NOTICE
Three-phase, scroll compressors operate in only one direction. If the scroll is drawing low amperage, has similar suction and discharge pressures, or is producing a high noise level, the scroll is misphased.
Check compressor rotation. If the scroll is misphased, change the incoming line connection phasing to obtain the proper rotation.
The compressor uses polyolester (POE oil), Mobile 3MA POE. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oil can absorb 15 times as much water as other oils designed for HCFC and
CFC refrigerants. If refrigerant circuit is opened, take all necessary pre­cautions to avoid exposure of the oil to the atmosphere.
!
CAUTION
Do not leave the system open to the atmosphere. Unit damage could occur due to moisture being absorbed by the POE oil in the system. This type of oil is highly susceptible to moisture absorption
POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.
!
CAUTION
Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take precautions to protect roofing.
Procedures which risk oil leakage include, but are not limited to, com­pressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure switch, metering device or coil.
!
CAUTION
Do not loosen compressor mounting bolts.
Units are shipped with compressor mountings which are factory­adjusted and ready for operation.
Johnson Controls Unitary Products 11
Page 12
5285477-UIM-A-1016
SECTION V: AIRFLOW PERFORMANCE
Table 10: Airflow Performance - Side Duct Application
External Static Pressure (Inches WC)
Model Jumper Position
High Cool/Heat
PHE6B36
Low Cool/Heat
Electric Heat
High Cool/Heat
PHE6B48
Low Cool/Heat
Electric Heat
High Cool/Heat
PHE6B60
Low Cool/Heat
Electric Heat
NOTES:
1.Airflow tested with dry coil conditions, without air filters, at 230 volts.
2.Applications above 0.8" w.c. external static pressure are not recommended.
3.Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4.Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5.Minimal variations in airflow performance data results from using downflow duct applications. Data above may be used in those cases.
6. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM
A
1345 1318 1271 1222 1172
B
1264 1211 1170 1115 1056
C
1232 1178 1131 1077 1012
D
1058 999 931 859 762
A
1153 1095 1036 979 899
B
1015 952 884 802 709
C
882 805 741 625 556
D
805 718 642 523 436
A
1190 1133 1079 1026 953
B
1112 1054 991 928 840
C
955 886 821 721 642
D
856 776 708 591 516
A
1851 1809 1781 1746 1707
B
1689 1652 1630 1597 1556
C
1614 1578 1554 1520 1477
D
1374 1333 1298 1255 1204
A
1473 1435 1406 1368 1320
B
1374 1333 1298 1255 1204
C
1322 1278 1238 1191 1138
D
1286 1241 1197 1149 1095
A
1441 1407 1373 1325 1279
B
1327 1286 1242 1192 1143
C
1187 1136 1084 1028 968
D
1087 1031 974 909 832
A
2149 2114 2077 2030 1989
B
2013 1977 1941 1898 1860
C
1936 1900 1864 1822 1783
D
1719 1685 1642 1600 1555
A
1629 1591 1546 1502 1455
B
1558 1516 1469 1423 1375
C
1453 1406 1355 1305 1255
D
1410 1361 1307 1255 1204
A
1743 1712 1666 1623 1580
B
1485 1436 1380 1329 1283
C
1382 1324 1265 1210 1162
D
1205 1131 1066 1005 953
1108 1035 961 894 841
981 894 826 775 729 929 853 790 738 690 694 635 582 523 459 810 751 697 643 588 646 582 528 467 402 501 415 359 297 228 376 294 247 193 118 861 798 742 689 638 760 701 648 591 532 584 508 453 391 324
459 375 321 262 191 1656 1609 1552 1518 1460 1504 1461 1404 1368 1310 1424 1382 1324 1286 1228 1145 1100 1044 993 933 1264 1220 1164 1119 1060 1145 1100 1044 993 933 1077 1030 975 920 859 1032 984 930 872 810 1232 1182 1108 1042 1039 1081 1024 949 881 834
886 827 767 702 657
750 704 653 600 537 1948 1905 1859 1816 1768 1816 1772 1726 1677 1630 1739 1695 1649 1597 1551 1508 1465 1418 1372 1327 1409 1362 1315 1266 1220 1329 1280 1232 1181 1135 1207 1153 1100 1047 997 1155 1100 1044 992 938 1540 1493 1449 1404 1370 1234 1185 1139 1084 1032 1108 1059 1012 952 891
892 841 793 724 644
12 Johnson Controls Unitary Products
Page 13
5285477-UIM-A-1016
Table 11: Electric Heat Multipliers
Voltage
Nominal Applied
240
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.
208 0.75 230 0.92
kW Capacity Multipliers
Table 12: Recommended Blower Speed for Electric Heat
Model
10 15 18 20 25
Heater kW
PHE6B36 C (ML) A (HI) -- -- -­PHE6B48 D (LO) C (ML) B (MH) A (HI) -­PHE6B60 D (LO) D (LO) C (ML) B (MH) A (HI)
NOTE: The recommended HEAT speed selections above will give approximately a 45 degree temperature rise at 0.3" static with 230V power supply. If lower or higher heating airflow is desired, or if duct static or voltage are different than specified, other speed taps may be used.
Table 13: Electric Heat Blower Off Delay
Model ID Blower Off Delay In Seconds
PHE6B36 60 PHE6B48 110 PHE6B60 110
1
Table 14: Additional Static Resistance
Size (Tons) CFM Wet Indoor Coil Economizer
1
Filter/Frame Kit
700 0.01 0.00 0.04 800 0.02 0.01 0.06 900 0.03 0.01 0.08
36 (3.0)
1000 0.04 0.01 0.10 1100 0.05 0.01 0.13 1200 0.06 0.02 0.16 1300 0.07 0.03 0.17 1400 0.08 0.04 0.18 1100 0.02 0.02 0.04 1200 0.03 0.02 0.04 1300 0.04 0.02 0.05 1400 0.05 0.03 0.05
48 (4.0)
1500 0.06 0.04 0.06 1600 0.07 0.04 0.07 1700 0.07 0.04 0.08 1800 0.08 0.04 0.09 1900 0.09 0.05 0.10 2000 0.09 0.05 0.11 1100 0.02 0.02 0.04 1200 0.03 0.02 0.04 1300 0.04 0.02 0.05 1400 0.05 0.03 0.05
60 (5.0)
1500 0.06 0.04 0.06 1600 0.07 0.04 0.07 1700 0.07 0.04 0.08 1800 0.08 0.04 0.09 1900 0.09 0.05 0.10 2000 0.09 0.05 0.11
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
2. Filter pressure drop based on standard filter media tested at velocities not to exceed 300 ft/min.
SECTION VI: OPERATION
The unit is controlled by a heat pump heating/cooling thermostat. If an electronic thermostat is used, make sure it has a common connec-
tion. DO NOT use a power stealing thermostat. This unit has a multi-stage compressor, therefore the unit has two
stages of mechanical heat, and two stages of mechanical cooling. The unit may be controlled using a single stage heat / single stage cool (1H/ 1C) heat pump thermostat, but the second stage cooling or heating is not available unless the unit control is physically wired for full capacity operation. For optimum performance, it is recommend to use a four stage heat / two stage cool (4H/2C) heat pump thermostat. If a 15 kW or smaller heat kit is installed, use a three stage heat / two stage cool (3H/ 2C) heat pump thermostat.
COOLING SEQUENCE OF OPERATION
A call for a compressor cooling signal from the thermostat is initiated at the “Y1” terminal (for OD compressor) and the “O” terminal (for revers­ing valve).
The control cycles the compressor and indoor blower to second stage cooling speed anytime a second stage cooling “Y2” call is received during a first stage cooling “Y1” call. The control does not operate on second stage cooling without a call on the “Y2” thermostat input.
1. On a call for cooling, the thermostat sends 24 volts to “Y” and “O” on the defrost control board. The reversing valve solenoid is energized. After the antishort cycle period is complete, the contactor coil “M” is energized. Power is supplied to the compressor and outdoor fan motor, and the reversing valve is switched to the cooling position. The indoor blower is controlled by the indoor blower control board. It operates on the “LOW COOL” or “HIGH COOL” speed based on the 24 VAC input from the defrost control board. If the control receives an “O” input without a “Y” input, it energizes the reversing valve only.
2. When the demand for cooling has been satisfied, the 24 volt “Y” signal is removed, and the contactor is de-energized. The indoor blower motor continues to run and ramps down after a 60 second delay.
Johnson Controls Unitary Products 13
Page 14
5285477-UIM-A-1016
Dehumidification/Humidity Switch Input
This model unit features a built in de-humidification feature for advanced dehumidification during cooling operation. The unit indoor blower control is designed to work with a humidity control that closes when the humidity is below the set-point. The control is open when the humidity is above the set-point. This humidity control may be referred to as a humidistat or dehumidistat.
To use this feature, the control HUM STAT jumper must be set to YES and a humidistat is connected from the low voltage R and HUM color coded leads. During cooling operation if the humidity level is above the humidistat set point, the indoor blower speed is reduced by approxi­mately 15%.
Safety Controls
!
WARNING
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any mainte­nance other than those procedures recommended in this Installation Manual. Failure to heed this warning could result in serious injury and possible damage to this equipment.
The control circuit includes the following safety controls: High Pressure Switch (HPS) - The switch protects against excessive
discharge pressures and the defrost control locks out compressor oper­ation.
Loss of Charge Switch (LCS) - The switch protects against loss of charge due to a leak in the system.
The above pressure switch is specifically designed to operate with R­410A systems. R-22 pressure switches must not be used as replace­ments for the R-410A pressure switches.
Indoor Circulating Blower
When the thermostat calls for “FAN,” the thermostat terminal “G” is energized signaling the indoor blower control board to operate the cir­culating blower to run continuously.
If a call for “COOL” occurs on “Y1,” the indoor blower runs at the “LOW COOL” speed based on the “COOL” jumper setting. If a call for cool is present on “Y1”+”Y2,” the indoor blower runs at the “HIGH COOL” speed based on the “COOL” jumper setting.
If a call for “HEAT” occurs “W1” or “W1”+“W2”, the circulating blower runs at the heat speed based on the “HEAT” jumper setting.
When the thermostat ends the call for “FAN,” the thermostat terminal “G” is de-energized, and the indoor blower control board stops the cir­culating blower operation.
Table 15: Indoor Blower Control Fault Codes
Flashes Fault Condition
LAMP OFF No Power to control
LAMP ON Internal control failure
SLOW RED Control normal operation
RAPID RED Test Mode
7 RED Call for heat and cool at the same time 8 RED Model ID plug not inserted 9 RED Internal fault self corrected, attempting normal operation
Delay Profiles
The Delay Profiles for each Delay jumper setting are shown in Table 16. The levels shown in the Pre-Run, Short-Run, and Run Periods are a percentage of the fan speed corresponding to the thermostat call. The Post-Run and Off Delay levels are derived from the level of the previous state, not the fan speed corresponding to the thermostat call. If in Delay Profile B and in the Short-Run Period (82% of capacity) and the thermo-
stat call is removed, this causes control to enter the Post-Run state. The Post-Run state level for Delay Profile B is 100% of the previous level, so the level during the Post-Run state is 82%.
TABLE 16 : Delay Profile Descriptions
Cooling
Delay
Profile
*The Post-Run and Off Delay levels are derived from the level of the previous state, not the fan speed corresponding to the thermostat call.
Period
Level%
Pre-Run Bypass Bypass Bypass Bypass
Short-Run Bypass Bypass Bypass Bypass
A
B
C
D
Run 100 No Limit 100 No Limit Post-Run* 100 1 100 .5 Off Delay* Bypass Bypass Bypass Bypass
Pre-Run 50 2 Bypass Bypass
Short-Run 82 5 Bypass Bypass
Run 100 No Limit 100 No Limit Post-Run* 100 1 100 .5 Off Delay* Bypass Bypass Bypass Bypass
Pre-Run Bypass Bypass Bypass Bypass
Short-Run Bypass Bypass Bypass Bypass
Run 100 No Limit 100 No Limit Post-Run* 100 1 100 .5 Off Delay* 50 1 Bypass Bypass
Pre-Run Bypass Bypass Bypass Bypass
Short-Run 63 1.55 Bypass Bypass
Run 100 No Limit 100 No Limit Post-Run* 100 1 100 .5 Off Delay* 63 0.5 Bypass Bypass
Time in State
(Minutes)
Heat Pump
Heating
Level%
Time in
State
(Minutes)
HEATING SEQUENCE OF OPERATION
1. On a call for heating, the thermostat sends 24 volts to “Y1” or “Y1”+“Y2” on the defrost control board. After the anti-short cycle period is complete, the 24 volt signal from “Y1” energizes contactor coil “M” to supply power for the compressor and outdoor fan motor. The indoor blower control operates the indoor blower motor at the “LOW COOL” speed. If the 24 volt signal from “Y2” is present, the defrost control board energizes the 2nd stage compressor solenoid and signals the indoor blower control to operate the indoor blower motor at the “HIGH COOL” speed. The reversing valve remains in the heating position. Indoor blower speeds are selected by the “COOL” jumper on the indoor blower control board.
2. If the heat pump cannot meet the heating demand using mechanical (compressor) heating, the indoor thermostat may energize axillary (electric) heating to supplement the mechanical heating if an electric heat kit was field installed. The room thermostat sends a 24 VAC sig­nal on “W1” or “W1”+“W2.” The “W1” signal is received by the indoor blower control board which then energizes the “HT1” output for elec­tric heat. When a call for mechanical heating and supplemental heat­ing is present, the indoor blower control operates the indoor blower at either the “Y1”+”Y2” or the “W1” speed whichever is higher based on the “COOL” and “HEAT” jumper selection.
NOTICE
The “W1” must be energized with “W2” in order to enable indoor air flow.
nd
A 2
stage auxiliary electric heating “W2” from the thermostat is to
be wired directly to the second stage heat kit input.
14 Johnson Controls Unitary Products
Page 15
5285477-UIM-A-1016
'()5267 &859( 6(/(&7,21
-803(5
7(673,16
67$786/('
3. When the heating demand is satisfied, the electric heat is de-ener­gized when the 24 volt “W” signal is removed, and the “M” contactor is de-energized when the 24 volt “Y” signal is removed.
When the fan switches on the thermostat is in the “ON” position, the indoor blower continues to run. When the fan switch is in the “AUTO” position, the indoor blower motor ramps down after the blower off delay.
4. Refer to Table 13 for more information on electrical heat blower OFF delay.
DEFROST OPERATION
The demand defrost control implements a temperature differential (”delta-T”) demand defrost algorithm. The heat pump is allowed to oper­ate in the heating mode until the combination of outdoor ambient and outdoor coil temperatures indicate that defrosting is necessary. When coil temperature is below the initiate point for the ambient temperature continuously for 4-1/2 minutes, the heat pump is put into a defrost cycle. This 4-1/2 minute timer eliminates unnecessary defrost cycles caused by refrigeration surges such as those that occur at the start of a heating cycle.
A timed inhibit feature prevents the system from responding to a call for defrost less than 40 minutes after the initiation of the previous defrost. After the 40 minute inhibit time has expired, temperature conditions must call for defrost continuously for 4-1/2 minutes before a defrost cycle is initiated. A temperature inhibit feature prohibits defrost if the coil temperature is above 40°F.
A forced-defrost feature puts the system into a defrost period every 6 hours and 4 minutes of accumulated compressor run-time to recirculate lubricants, unless the coil temperature is above 40°F and the ambient temperature is above 50°F . All defrost timing occurs only while the com­pressor is on.
During the defrost mode, the reversing valve is energized, the outdoor fan is de-energized, the compressor is energized, and the defrost con­trol provides a 24 volt signal from terminal “W1OUT” to energize electric heat stage 1 if the unit is equipped with electric heat.
By selecting “LO” on the “DEFROST HEAT” jumper, “W1 OUT” is ener­gized during defrost. By selecting “HI” on the “DEFROST HEAT” jumper, “W1 OUT” and “W2 OUT” are energized during defrost.
For trouble shooting purposes, the defrost cycle can be manually initi­ated by shorting the “TEST” pins together for 5 seconds while “Y” is energized. After removing the short, defrost will terminate normally during the “TEST” mode.
Table 17: Demand Defrost Selection
Unit Pin Position
048, 060 2
036 — 042 3 036 — 060
*
For extreme environments as necessary only.
*
4
FIGURE 8: Demand Defrost Control
Johnson Controls Unitary Products 15
+27+($738036(/(&7,21
'()52676833/(0(17$/ +($76(/(&7,21
$
Page 16
5285477-UIM-A-1016
,1'225$,5)/2:6(/(&7,21
67$786/('
$03&21752/)86(
FIGURE 9: Blower Control
Heat Pump Safety Switch Operation
The unit is equipped with a safety package. The refrigeration system will be protected against high refrigerant pressure and a loss of charge switch. If either of these safety switches open, the unit will be shut off for the 5 minute anti-short cycle time. Once this has expired, a six hour elapsed run timer begins. If a second opening of a safety switch occurs during this six hour period, the compressor will be locked out.
Resetting the lockout function is accomplished by:
1. Removing power from the control's thermostat 1st stage (Y) input for longer than 2 seconds.
2. Removing power from “R” for more than 2 seconds.
3. Shorting the “TEST” pins together for more than 2 seconds while “Y” is energized.
4. Shorting the “TEST” pins together for more than 5 seconds while “Y” is de-energized.
Table 18: Test Pins
Test Pin Shorted With Y Call Without Y Call
greater than 2 sec Bypass ASCD Show error codes greater than 5 sec Forced defrost Clear error codes
Demand Defrost Fault Code Display
The control provides fault codes using the Status LED display. Table 19 describes the LED displays for fault codes. On the LED display, the control displays a single fault code only. The control displays the fault code on the LED display repeatedly with a 2 second off period between repetitions of the fault code. If multiple fault codes are present at the same time, the LED displays only the highest priority fault. The other active faults may be accessed via the LAST ERROR button on the con­trol board.
$&+36(/(&7,21
'(+80,',67$76(/(&7,21
02'(/ ,'3/8*
-803(5
$
Table 19 shows the LED display representation for specified faults. For instance, a red LED display of 10 flashes indicates a control failure.
When any fault code is present, the control does not display the current status code for the stage of operation.
Table 19: Demand Defrost Fault Codes
Description STATUS LED
High -pressure switch fault (not in lockout yet) 2 Flashes System in high-pressure switch lockout (last mode of
operation was normal compressor) System in high-pressure switch lockout (last mode of
operation was defrost) System in loss of charge switch lockout (last mode of
operation was normal compressor) Low Voltage (less than 19.2VAC) preventing further
relay outputs for greater than 2 seconds Low Voltage (less than 16VAC) stopped current relay
outputs for greater than 2 seconds
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
Liquid Line sensor failure (Open or Shorted) 8 Flashes Outdoor ambient sensor failure (Open or Shorted) 9 Flashes Control Failure 10 Flashes
Electric Heat Limit Switch Operation
The 6HK single phase heat kits utilize a normally closed line voltage limit switch and a normally closed fusible link. If the fusible link opens, it must be replaced with the appropriate OEM part and the cause must be investigated and corrected.
16 Johnson Controls Unitary Products
Page 17
Table 20: Thermostat Signals
Signal State Board Function
G
W
G & W
G & Y
G, Y & O
ON Indoor blower instant on
OFF Indoor blower off after 60-second delay
Indoor blower instant on
ON
Electric heat stages on (if so equipped) Electric heat stages off (if so equipped)
OFF
Indoor blower off after off delay Indoor blower instant on in heating speed
ON
Electric heat stages on (if so equipped)
W OFF
Y OFF
G, Y & O
Electric heat stages off (if so equipped) Indoor blower switches to continuous fan speed Outdoor fan instant on Indoor blower instant on in cooling speed
ON
Compressor on (after any anti-short cycle delay) System operates in heat pump heating mode Compressor instant off Outdoor fan instant off Indoor blower switches to continuous fan speed Compressor instant off
G & Y
Outdoor fan instant off
OFF
Indoor blower off after 60 second delay Outdoor fan instant on Indoor blower instant on in cooling speed Compressor on (after any anti-short cycle delay)
ON
Reversing valve energized System operates in cooling mode Compressor instant off Outdoor fan instant off
Y & O
OFF
Reversing valve off Indoor blower switches to continuous fan speed Compressor instant off Outdoor fan instant off
OFF
Reversing valve off Per Delay Profiles Paragraph and Table 16
5285477-UIM-A-1016
STARTUP
1. Check the electrical supply voltage being supplied. Be sure that it is within the specified range on the unit data plate.
2. Make sure all electrical connections are tight.
3. If unit is connected to 208 volt supply power, the control transformer must be wired accordingly.
4. Turn unit electrical power on.
5. Set the room thermostat to COOL mode and lower the desired tem­perature setting lower than the room temperature to create a call for cooling.
!
CAUTION
Scroll compressors require proper rotation to operate properly. Fail­ure to check and correct rotation may result in property damage.
NOTICE
Three-phase, scroll compressors operate in only one direction. If the scroll is drawing low amperage, has similar suction and discharge pressures, or is producing a high noise level, the scroll is misphased.
6. Check compressor rotation. If the scroll is misphased, change the incoming line connection phasing to obtain the proper rotation.
7. Measure the total system duct static, and set the blower motor cool­ing speed appropriately per airflow performance tables.
8. Make sure all unit panels are in place and secure and that an air fil­ter is installed.
EXTERNAL STATIC PRESSURE SETUP
To measure external static pressure:
• Measure the supply air static pressure
• Record this positive number
• Measure the return air static pressure
• Record this negative number
• Treat the negative number as a positive and add the two numbers together
• This is total system static
FIGURE 10: Measuring External Static Pressure
Johnson Controls Unitary Products 17
Page 18
5285477-UIM-A-1016
SECTION VII: MAINTENANCE
NORMAL MAINTENANCE
!
WARNING
Prior to any of the following maintenance procedures, shut off all power to the unit, to avoid personal injury.
Periodic maintenance consists of changing or cleaning filters and gen­eral cleaning of the outdoor coil.
FILTERS - Inspect once a month. Replace Disposable or clean Perma­nent Type as necessary. DO NOT replace Permanent Type with Dis­posable.
MOTORS - Indoor and outdoor fan motors are permanently lubricated and require no maintenance.
OUTDOOR COIL - Dirt should not be allowed to accumulate on the out­door coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep the coil clean. If water is used to clean the coil, be sure that the power to the unit is shut off prior to cleaning.
NOTICE
DO NOT use a pressure washer as coil fin damage will occur.
!
CAUTION
Exercise care when cleaning the coil so that the coil fins are not dam­aged. Do not permit the hot outdoor air discharge to be obstructed by over­hanging structures or shrubs.
TROUBLESHOOTING
!
WARNING
Troubleshooting of components necessarily requires opening the electrical control box with the power connected to the unit. Use extreme care when working with live circuit! Check the unit name­plate for the correct range before making any connections with line terminals.
!
CAUTION
The wire number or color and terminal designations referred to may vary. Check the wiring label inside the control box access panel for the correct wiring.
18 Johnson Controls Unitary Products
Page 19
SECTION VIII: TYPICAL WIRING DIAGRAMS
2 STAGE HEAT PUMP WITH OR WITHOUT
ELECTRIC HEAT - 208/230-3-60
CONNECTION WIRING DIAGRAM
CAUTION
!
OPEN ALL DISCONNECTS
BEFORE SERVICING THIS UNIT.
208/230V LINE VOLTAGE FIELD INSTALLED POWER 24V LOW VOLTAGE FIELD INSTALLED CONTROL
P3
C
BLU (42)
HUM
Y/Y2
PWM
HT1 HT2
HT COM
24 VAC
6
WHT/BLK (44)
5 4 3 2 1
LOW
GRY (18)
O
ORN (41)
W1
WHT (46)
W2
Y1
YEL (48)
YEL/BLK (49)
G
GRN (19)
R
RED (50)
C
P1
WHT (45)
BLU (43)
BLU (27) RED (25) ORN (37) YEL (36)
YEL/BLK (23)
GRN (19)
WHT/BLK (20)
WHT (21) GRY (18)
MODEL ID
PLUG
2 STAGE
BLOWER
CONTROL
3A
FUSE
SECOND STAGE
RELAY / SEQUENCER
FIRST STAGE
RELAY / SEQUENCER
24V COMMON
FEMALE 6HK* ELEC. HEAT
KIT CONNECTOR
C R
O Y1 Y2
G
W2 W1
HUM
THERMOSTAT
VOLTAGE BOX
PWM COM
PWM ENA
Notes:
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL, AND/OR NATIONAL CODES IN EFFECT AT THE TIME OF UNIT INSTALLATION.
2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. IF ANY OF THE WIRING AS SUPPLIED WITH UNIT MUST BE REMOVED, IT MUST BE REPLACED WITH TYPE 105 C 600 VOLT WIRE OR EQUIVALENT AND CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING.
3. FACTORY WIRED FOR 230 VOLT 3 PHASE SUPPLY POWER. FOR 208 VOLT 3 PHASE SUPPLY POWER, MOVE BLACK WIRES FROM THE 230 VOLT TAP TO THE 208 VOLT TAP ON THE TRANSFORMER.
4. MOTORS ARE INHERENTLY PROTECTED.
5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE AND MINIMUM CIRCUIT AMPACITY.
FIGURE 11: Connection Wiring Diagram
YEL (48)
WHT (47)
HI PRESSURE
YEL/BLK (23)
YEL (36)
ORN (40)
RED (39)
1P
C
STATUS TEST
BLU (26)
BLU (30)
RED (33)
RED/WHT (51)
FOR THREE-PHASE POWER.
A SINGLE PHASE SUPPLY
LOSS OF CHARGE
YEL/BLK (41)
WHT/BLK (22)
R
O
Y1
Y2
W1 OUT
BLU (52)
24V SEC
75VA
XFMR
230V
208V
TRANSFORMER
BLU/WHT (7)
NOTICE
THIS UNIT IS WIRED
DO NOT CONNECT TO
REV. VALVE
YEL (13)
HPS IN
Y1 OUT
Y2 OUT
W2 OUT
2 STAGE
DEMAND DEFROST
CONTROL
GRN (31)
COM
PUR/WHT (6)
SOLENOID
COIL
SENSOR
BRN (15)
LT BLU (14)
RV
LCS OUT
BLK (1)
BLU (29)
BRN (15)
C
RVG
PUR (3)
YEL (38)
YEL/BLK (24)
M
M2
GRN (5)
BLU (16)
3
P2P
COIL
OUTDOOR FAN RELAY
BLK (2)
BLU (16)
WHT (17)
AMBG
COILG
BLK/WHT (10)
YEL (13)
LT BLU (14)
LCS IN
HPS OUT
PUR (4)
Demand Defrost Control Fault Codes
Flashes Fault Condition
LAMP OFF
STEADY RED
SLOW RED
RAPID RED
No Power to control Compressor operation active - Compressor
contactor energized. Control normal operation - No call for compressor. Control normal operation - ASCD (Anti Short Cycle
Delay) active
2 RED
High Pressure Switch fault (Not yet in lockout)
3 RED
System in high pressure switch lockout (Last mode of operation was normal compressor)
4 RED
System in high pressure switch lockout (Last mode of operation was defrost)
5 RED
System in low pressure switch lockout (Last mode of operation was normal compressor)
6 RED
Low Voltage (<19.2 VAC) preventing further relay outputs for >2 seconds
7 RED
Low Voltage (<16 VAC) stopped current relay outputs for >2 seconds
8 RED
Liquid Line sensor failure (Open or Shorted)
9 RED
Outdoor ambient sensor failure (Open or Shorted)
10 RED
Control Failure
Blower Control Fault Codes
Flashes Fault Condition
LAMP OFF
LAMP ON
SLOW RED
RAPID RED
No Power to control Internal control failure Control normal operation Test Mode
7 RED
Call for heat and cool at the same time
8 RED
Model ID plug not inserted
9 RED
Internal fault self corrected, attempting normal operation
T
AMBIENT SENSOR
BLU (28)
2
3
5
6
T
WHT (17)
AMB
1
4
1
ID BLWR
MOTOR
CAP
F
C
RED (12)
BLK/WHT (32)
CONTACTOR
5285477-UIM-A-1016
BLK
L1
3
YEL
L3
COMPR.
L2
BLU
BLU
BRN/WHT (9)
GRN (8) RED (11)
TEMPERATURE
BLK
BLK/WHT (35)
L2
T2
L3
T3
T1
L1
SWITCH
BLK
1 2
BRN
3 4
GRN
5
6
RED
BLU
CRANKCASE
BLK
BLK (34)
USE COPPER
CONDUCTORS
POWER SUPPLY
208/230-1-60
OD FAN MOTOR
HEATER
5291017-UWD-A-0916
1
BLK
ONLY
Johnson Controls Unitary Products 19
Page 20
5285477-UIM-A-1016
2 STAGE HEAT PUMP WITH OR WITHOUT
CAUTION
!
OPEN ALL DISCONNECTS
BEFORE SERVICING THIS UNIT.
NOTICE
THIS UNIT IS WIRED
FOR THREE-PHASE POWER.
DO NOT CONNECT TO
A SINGLE PHASE SUPPLY
208/230V LINE VOLTAGE FIELD INSTALLED POWER 24V LOW VOLTAGE FIELD INSTALLED CONTROL
Notes:
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL, AND/OR NATIONAL CODES IN EFFECT AT THE TIME OF UNIT INSTALLATION.
2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. IF ANY OF THE WIRING AS SUPPLIED WITH UNIT MUST BE REMOVED, IT MUST BE REPLACED WITH TYPE 105 C 600 VOLT WIRE OR EQUIVALENT AND CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING.
3. FACTORY WIRED FOR 230 VOLT 3 PHASE SUPPLY POWER. FOR 208 VOLT 3 PHASE SUPPLY POWER, MOVE BLACK WIRES FROM THE 230 VOLT TAP TO THE 208 VOLT TAP ON THE TRANSFORMER.
4. MOTORS ARE INHERENTLY PROTECTED.
5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE AND MINIMUM CIRCUIT AMPACITY.
WIRING DIAGRAM FOR HEATER KIT: 6HK06501825
GND
L3
L2
L1
BLK
BLU
BLU
BLU BLU BLU
YEL YEL YEL YEL
BLK BLK BLK
BLK
BLK
OPTIONAL ELECTRIC HEATER ACCESSORY
SEE HEATER WIRING DIAGRAM FOR ALTERNATE
HEATER ACCESSORY KITS.
LS
HE6
HE3
HE2
YEL
RLY 6
BLU
RLY 5
BLK
RLY 4
YEL
BLU
BLU
FL
FL
FL
BLU
BLU
BLK
BLU
WHT
YEL
BLU
WHT
ELECTRIC HEAT - 208/230-3-60
LADDER WIRING DIAGRAM
Demand Defrost Control Fault Codes
Flashes Fault Condition
LAMP OFF
STEADY RED
SLOW RED
RAPID RED
RAPID RED
LS
FL
HE5
HE4
FL
HE1
FL
RLY 3
BLU
RLY 2
WHT
BLK
BLU
RLY 1
WHT
YEL
No Power to control Compressor operation active - Compressor
contactor energized. Control normal operation - No call for compressor. Control normal operation - ASCD (Anti Short Cycle
Delay) active
2 RED
High Pressure Switch fault (Not yet in lockout)
3 RED
System in high pressure switch lockout (Last mode of operation was normal compressor)
4 RED
System in high pressure switch lockout (Last mode of operation was defrost)
5 RED
System in low pressure switch lockout (Last mode of operation was normal compressor)
6 RED
Low Voltage (<19.2 VAC) preventing further relay outputs for >2 seconds
7 RED
Low Voltage (<16 VAC) stopped current relay outputs for >2 seconds
8 RED
Liquid Line sensor failure (Open or Shorted)
9 RED
Outdoor ambient sensor failure (Open or Shorted)
10 RED
Control Failure
Blower Control Fault Codes
Flashes Fault Condition
LAMP OFF
SLOW RED
No Power to control
LAMP ON
Internal control failure Control normal operation Test Mode
7 RED
Call for heat and cool at the same time
8 RED
Model ID plug not inserted
9 RED
Internal fault self corrected, attempting normal operation
T-STAT
W1 W2
HUM
BRN
WHT
BLU
PUR
RED/WHT
BLK
6
6
5
5
4
4
3
3
2
2
1
1
VOLTAGE
C R
O Y1 Y2
G
WHT/BLK
WHT
BLU
LOW
BOX
BLU RED
ORN
YEL
YEL/BLK
WHT
WHT/BLK
GRN
GRY
WHT
BLU
BLK
BRN/WHT
COM
XFMR
BLU
C
M
ID MOTOR
ID BLWR
MOTOR
HT2
HT COM
YEL
M2
1
C
3A
BLU
CAPACITOR
C
RED
YEL
YEL/BLK
COIL
SENSOR
BLU
3P
COIL
24 VAC
FUSE
GROUND
LUG
BLK/WHT
T3
RED
F
RUPKLB
PUR
BLU
BLU
T
BLU
WHT
AMBG
COILG
T2
CONT. COIL
2ND STAGE
COMPRESSOR
SOLENOID
T
AMBIENT
SENSOR
WHT
AMB
BLU
L2L3
CRANKCASE
T1
BLK/WHT
Y1
Y2
BLKBLK
GRN
1
OD FAN MOTOR
BLK
W1 OUT
W2 OUT
BLU
YEL
YEL/BLK
Y1 OUT
Y2 OUT
HEATER
KLB
RED
YEL
PRES.
P
2
L1
WHT/BLK WHT ORN RED
C
R
O
2 STAGE DEMAND DEFROST
RED
GRN
YEL/BLK
YEL
WHT
ORN
GRY
C
O
Y1
W1
W2
HUM
Y/Y2
PLUG
2 STG BLOWER
MODEL ID
CONTROL
BLK
COMPRESSOR
230V
BLU
VALVE
LOSS OF CHARGE
YEL
HI
HPS IN
HPS OUT
CONTROL
R
G
PWM COM
3
ID BLWR
208V
24V SEC
BLU
REV.
LT. BLU
LT. BLU
LCS IN
LCS OUT
PUR/WHT
RED/WHT
PWM ENA
TEMP.
SWITCH
L3L1
L2
1
MOTOR
75VA
BRN
RV
BLU/WHT
PWM
GRN
BRN
RVG
HT1
5291017-UWD-A-0916
FIGURE 12: Ladder Wiring Diagram
20 Johnson Controls Unitary Products
Page 21
5285477-UIM-A-1016
R-410A QUICK REFERENCE GUIDE
Refer to Installation Instructions for specific installation requirements
R-410A refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A. R-410A refrigerant cylinders are rose colored. Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400, or DOT BW400. Recovery equipment must be rated for R-410A. DO NOT use R-410A service equipment on R-22 systems. All hoses, gages, recovery cylinders, charging cylinders and recovery equipment must be dedicated for use on R-410A systems only. Manifold sets must be at least 700 psig high side, and 180 psig low side, with 550 psig retard. All hoses must have a service pressure rating of 800 psig. Leak detectors must be designed to detect HFC refrigerants. Systems must be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose. R-410A can only be used with POE type oils. POE type oils rapidly absorb moisture from the atmosphere.
Vacuum pumps will not remove moisture from R-410A refrigerant oils.
Do not use liquid line driers with a rated working pressure rating less than 600 psig. Do not install suction line driers in the liquid line. A liquid line drier is required on every unit. Do not use a R-22 TXV. If a TXV is to be used, it must be a R-410A TXV. Never open system to atmosphere when under a vacuum. If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all lter driers.
FIGURE 13: R-410A Quick Reference Guide
Johnson Controls Unitary Products 21
Page 22
5285477-UIM-A-1016
NOTES
22 Johnson Controls Unitary Products
Page 23
SECTION IX: START UP SHEET
Residential Package Unit Heat Pump
with Electric Heat Start-Up Sheet
Proper start-up is critical to customer comfort and equipment longevity
Start-Up Date
Owner Information
Name Address
City State or Province Zip or Postal Code
Equipment Data
Equipment Data
Unit Model # Unit Serial #
Start-Up TechnicianCompany Name
Daytime Phone
General Information
Residential
Commercial
Unit Location and Connections
Unit is level and installed on:
Condensate drain properly connected per the installation instructions Condensate trap has been primed with water
Filters
Filters installed Filter located inside Filter located outside
(Check all that apply)
New Construction
Retrot
(Check all that apply)
Slab Roof curb Supply Return
Number of lters Filter size
Roof level
Grade level
Duct connections are complete:
Down ow
Side ow
5285477-UIM-A-1016
Additional Kits & Accessories Installed
Refrigerant safety kit Low ambient kit
EconomizerTransformer kit Roof curb kit
Manual fresh air damper kit Motorized fresh air damper kit
Electrical Connections & Inspection
Three phaseSingle phase
Low voltage present at control board "R & C"
Line voltage present at disconnect
208 volts AC 230 volt AC 460 volts AC 575 volts AC
Measured voltage "L1 to L2" "L2 to L3" "L1 to L3"
Two stage compressorSingle stage compressor
(Check all that apply)
Anti-recycle timer
(Check all that apply)
Transformer wired properly for primary supply voltageInspect wires and electrical connections
Air Flow Setup
Blower Type
&
Set-Up
Variable Speed
Standard ECM
PSC
COOL
ADJUST A B C D
DELAY
HEAT
1 2 3 4 5
Low Medium Low Medium Medium High High
Crank case heater
Burglar bar kit
Measured voltage "R" and "C" outdoor unit control board
Total amperes "L1" "L2" "L3"Compressor amperes "L1" "L2" "L3"
A B C D
A
A
B
B
Filter frame kit
Hail guard kit
Ground connected
C D
C D
Supply static (inches of water column) Supply air dry bulb temperature
Return static (inches of water column)
Total external static pressure
Johnson Controls Unitary Products 23
Return air dry bulb temperature
Temperature drop
Outside air dry bulb temperature
Return air wet bulb temperature
Supply air wet bulb temperature
Page 1 of 2 (7/7/16)
Page 24
Refrigerant Charge and Metering Device
R-410A R-22
TXV Fixed Orice
TXV# / Orice size
Data plate - lbs / Oz
Discharge line
temperature
Suction line temperature
Suction pressure
Superheat
Discharge pressure
Liquid line temperature
Subcooling
Electric Heat (Supplemental and Emergency Heat)
Electric heat kit - Model number Serial number Rated KW
Single Phase
Measured Amperage
Three Phase
Heater 1
Heater 4
Heater 2
Heater 5
Heater 3
Heater 6
Number
of elements
Heating return air
dry bulb temperature
Measured Voltage
Heater 1
Heater 4
Heating supply air
dry bulb temperature
Heater 2
Heater 5
Air temperature rise
Clean Up Job Site
Job site has been cleaned, indoor and outdoor debris removed from job site
Tools have been removed from unit
All panels have been installed
Unit Operation and Cycle Test
Operate the unit through continuous fan cycles from the thermostat, noting and correcting any problems
Operate the unit through cooling cycles from the thermostat, noting and correcting any problems
Operate the unit through mechanical heating cycles from the thermostat, noting and correcting any problems
Operate the unit through emergency heating cycles from the thermostat, noting and correcting any problems
Owner Education
Provide owner with the owner's manual
Explain operation of system to equipment owner
Explain thermostat use and programming (if applicable) to owner
Explain the importance of regular lter replacement and equipment maintenance
Comments and Additional Job Details
Heater 3
Heater 6
Subject to change without notice. Published in U.S.A. 5285477-UIM-A-1016 Copyright © 2016 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing
Page 2 of 2 (7/7/16)
York International Corp.
5005 Y ork Drive
Norman, OK 73069
Loading...