DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
• Operating Efficiency - All PCE4 air conditioner models are
rated at 14.0 SEER and 11.0 EER for cooling operation.
• On Site Flexibility - All model sizes use a compact design
cabinet in one of two footprints. This provides installer flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
insure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.
• Utility Connections Made Easy - Electric utility access provided through the bottom or the side of the unit. Utility connections can be made quickly and with a minimum amount of
field labor. A field supplied and field installed electrical disconnect switch must be installed.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the evaporator coil to collect
and drain all condensate, preventing build-up of stagnant
condensate. The condensate pan conforms to ASHRAE 6289 standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection i s
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder
paint finish ensures less fading when exposed to sunlight,
and provides superior corrosion resistance (1000 hour salt
spray tested).
Continued on next page.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5126749-YTG-A-0715
• Full Perimeter Base Rails - The easily removable base rails
provide a solid foundation for the entire unit and protects the
unit during shipment. The rails provide fork lift access from all
sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On
applications where the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications
where height is limited, the base rails may be removed by
removing 2 screws in each corner.
• Attractive Appearance - A single-piece top cover containing
a top-discharge condenser fan arrangement requires less
square footage on installation and provides a wider variety of
installations. The one-piece design adds greater water integrity . Rounded corners with water drip edges add to the attractive appearance.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
• Low Operating Sound Level - The upward air flow ca rries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design.
• Fan System - All models operate over a wide range of
design conditions with a standard ECM indoor fan motor.
These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements.
The cooling speed is factory-set and can be field-adjusted to
a second speed. The heating speed is factory set to maintain
mid point rise at the units heating input, but can be field
adjusted. This allows maximum comfort conditions.
• Simple Control Circuit - Field thermostat wiring connects to
color coded leads using twist on wire connections. Cooli ng
controls use contactor and relays for simple application and
troubleshooting. Mate-n-lock plug connectors are used. T he
electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate
access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
• Protected Compressor - The compressor is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the
compressor if undesirable operating conditions occur.
• Pressure Switches - A high pressure switch is standard in
all units. It is an automatic reset switch. When discharge
pressure reaches 650 psi, the compressor will de-energize
until pressure reaches 450 psi.
• Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat transfer
for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils will use tin-coated
copper tubing with aluminum fins for effective heat transfer.
• Electric Heat - All electric heat models use 6HK electric
heat, which are available in 230v/1/60 from 2 kW to 25 kW,
230v/3/60 10kW to 25kW, and 460v/3/60 10kW to 25kW.
Most kits stageable above 10 kW. Single phase single point
field wiring kits are available for all applications except 25kW.
• Low Maintenance - Long life, permanently lubric ated condenser and evaporator fan motor bearings need no annu al
maintenance, adding greater reliability to the unit. Slide-out
blower assembly and evaporator coil assembly can be easily
removed for cleaning.
• Easy Service Access - Individual access panels are provided in access to all major components - compressors,
evaporator coils, blower, controls/electric heat kits, filters,
etc. that makes servicing easy. Removing these panels allow
easy removal of the components such as the blower assembly for maintenance and ease of troubleshooting.
• Replacement Parts - T
ing to replace any of the components of these units and the
number of new components have been reduced to minimize
the inventory of unique parts.
he installer requires no special train-
2Johnson Controls Unitary Products
5126749-YTG-A-0715
OUTDOOR FAN MOTOR
OUTDOOR FAN
COIL GUARD PANEL
OUTDOOR COIL
(Behind Panel)
CONTACTOR
TRANSFORMER
CAPACITOR
BLOWER MOTOR
TXV
INDOOR COIL
INDOOR BLOWER
COMPRESSOR
REMOVABLE
BASE RAILS
A0411-001
OPTIONAL
ELECTRIC HEAT KIT
NOMENCLATURE
PCE4A24502X1A
1234689
1. Model Family
PCE - packaged A/C with electric heat,
PHE - packaged heat pump with electric heat,
PCG - packaged A/C with gas heat,
PHG - packaged heat pump with gas heat,
• Economizer for Downflow Applications
(S1-2EE04708424, S1-2EE04708524) - Modulating inte-
grated economizer provides simultaneous operation
between mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor and relief damper.
Separate field accessories of single/dual enthalpy kits are
also available.
• Economizer for Horizontal Applications (S1-2EE04708624, S1-2EE04708724) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy
are available.
• Single/Dual Enthalpy Sensor (S1-2EC04700624) - Sensor
replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry
bulb temperature from outdoors plus the enthalpy content of
the outdoor air.
• CO2 Sensor Kit (S1-2AQ04700824) - Sensor kit detects
CO2 levels automatically and overrides the economizer
when CO2 levels rise above the preset limits.
• Outdoor Temperature Sensor Kit (S1-2EC04700724S1-2EC04700724v) - Additional outdoor
air temperature sensor kit used with economizers.
• Filter/Frame Kit (Single Phase Only) (S1-1FF0602, S1-1FF0601) - Kit contains the necessary
hardware to field install return air filters into the base unit.
The filter rack is suitable for either 1" or 2" filters. (filters not
supplied) This kit is available for single phase horizontal or
vertical duct applications.
• Motorized Fresh Air Damper (S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/
return applications. Damper capable of providing 0% through
50% of outdoor air (field supplied). Closes on power loss,
includes hood and screen assembly.
• Low Ambient Kit (S1-2LA04700824) - Kit provides necessary hardware to convert unit to operate in cooling cycle
down to 0º F. Standard unit operation 45º F.
• Rectangle to Round (Horizontal) Adapter (S1-1AK0110, S1-1AK0111) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit over current horizontal duct
openings on the base unit. Transition is from rectangle to 12"
round for the 1AK0110 kit and from rectangle to 14" round for
the 1AK0111 kit.
• Rectangle to Round (Downflow) Adap ter (S1-1AK0108, S1-1AK0109) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit into current downflow duct
openings on the roof curb. Transition is from rectangle to 16"
round for the 1AK0108 kit and from rectangle to 18" round for
the 1AK0109 kit.
• Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hi nge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 8 inch high roof curbs.
• Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA appro ved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed for assembly through hinge pins in each
corner. Kit also provides seal strip to assure air tight seal.
These are 14 inch high roof curbs.
• Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) -
Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications and unit mounted down supply/return applications.
Includes hood and screen assembly.
• Transformer Kit (S1-2EC06700124) -
sary ha
furnished 40 VA transformer capability to 75 VA transformer
capability. (Required on installations with economizer or
motorized damper).
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.
• Loss of Charge Sensor (S1-2LC00024) - Kit provides Loss
of Charge sensor and wiring to provide safe shutdown of
compressor.
• Single Point Wiring Accessory Kits for 6HK Electric HeatApplications (S1-SPWK*) - Kits provide field option for connecting electrical power supplies to the field installed 6HK
kits to allow single point connections for single phase electric
heat applications with the exception of 25kW kits.
• Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PHE4
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PCE4 pr ice pages
for more details.
• Wall Thermostat - The units are designed to operate with
standard, 24-volt electronic non power stealing and electromechanical thermostats. All units can operate with single
stage heat/single stage cool thermostats - with or without the
economizer.
* For additional kit numbers refer to the price pages.
rdware
to provide single phase models from factory
Kit provides neces-
4Johnson Controls Unitary Products
5126749-YTG-A-0715
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. These packaged cooling and heating air
conditioners are designed for outdoor installation. Only utility
and duct connections are required at the point of installation. Air
Conditioning units provide electric cooling and electric h eating,
with field installed electric heat kits from 2 kW to 25 kW for
heating operation.
DESCRIPTION
Units shall be factory-assembled, single packaged, Air
Conditioners with Electric Cooling/Electric Heating units,
designed for outdoor installation. They shall have built in, equal
size, field convertible duct connections for supply/return or
horizontal supply/return. The units shall be factory wired, piped,
charged with R-410A Refrigerant and factory tested prior to
shipment. All models shall be rated in accordance with DOE
and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed to the UL 1995/CAN/CSA
No. 236-M90 standards.
• Operating Efficiency - All models shall be rated at a minimum of 14.0 SEER and 11.0 EER for cooling and heating
operation rated in accordance with DOE requirements.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the condenser
coil muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design. Sound ratings as tested
under AHRI test procedures shall be less than 77 dbA for all
models.
UNIT CABINET
Unit cabinet shall be a single piece design, with drip e dges and
no-seam corners to provide optimum water integrity. Unit shall
have a rigidly mounted condenser coil guard to provide
protection from objects and personnel after installation. Indoo r
blower section shall be insulated with foil-faced or foam
insulation, fastened to prevent insulation from entering the air
stream. Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable tran sit
of equipment, overhead rigging, for truck access and proper
sealing on roof curb applications. Base rails shall be easily
removable, when required to lower unit height. Filters shall be
field installed, furnished and be accessible through a removable
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit.
• Durable Finish - The cabinet shall be is made of G90 gal vanized steel with a powder paint coating for appearance and
protection. The pre-treated galvanized steel shall provide a
better paint-to-steel bond, which resists corrosion and rust
creep. Powder paint finish shall provide superior corrosion
resistance (1000 hour salt spray tested).
• On Site Flexibility - All model sizes shall use a compact
design cabinet in one of two footprints. This provides installer
flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Attractive Appearance - A single-piece top cover containing
a top-discharge condenser fan arrangement shall be used
which requires less square footage on installation and provides a wider variety of installations. The one-piece design
adds greater water integrity. Rounded corners with water drip
edges add to the attractive appearance and prevent wate r
penetration.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Utility Connections Made Easy - Electric utility access shall
be provided through the bottom or the side of the unit. Utility
connections should be made quickly and with a minimum
amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
• Easy Service Access - Individual access panels are provided in access to all major components - compressors,
indoor coils, blower, controls/electric heat kits, filters, etc. that
makes servicing easy. Removing these panels allow easy
removal of the components such as the blower assembly for
maintenance and ease of troubleshooting.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
Indoor Blower Assembly - Fan shall be direct drive design.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance. Fan assembly
shall be a slide-out design for easy removal and cleaning.
Indoor blower motors shall be equipped with a standard high
efficiency brushless DC motor (constant torque) also known as
a standard ECM motor.
Outdoor Fan Assembly - The outdoor fan shall be of the
direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated bearings and internally protected
against overload conditions.
Johnson Controls Unitary Products5
5126749-YTG-A-0715
REFRIGERANT COMPONENTS
• Protected Compressor - The compressor shall be a fully
hermetic type, direct drive compressor, that is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the
compressor if undesirable operating conditions occur. The
hermetic motor shall be suction gas cooled and have a voltage range of +/- 10% of the unit nameplate voltage. Compressors shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a
dedicated, independent mounting.
• Indoor Coils - Indoor coils shall be of the direct expansion,
draw through design and have aluminum plate fins mechanically bonded to seamless internally enhanced tin-coated
copper tubes with all joints brazed.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the indoor coil to collect and
drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 62-89
standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Outdoor Coils - Outdoor coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced co pper tubes with all joints brazed, and be a draw through
design.
Refrigerant Circuit and Refrigerant Safety Components
shall include: Thermal expansion devices (TXV's) shall be
factory mounted and provided, Filter/strainer to eliminate any
foreign matter, reversing valves to control refrigerant flow.
CONTROLS
• Simple Control Circuit - Field thermostat wiring connects to
color coded leads using twist on wire connections. Cooli ng
controls use contactor and relays for simple application and
troubleshooting. Mate-n-lock plug connectors are used. T he
electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate
access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
• Pressure Switches - A high pressure switch is standard in
all units. It is an automatic reset switch. When discharge
pressure reaches 650 psi, the compressor will de-energize
until pressure reaches 450 psi.
• Factory Testing - Installation time and costs are reduced by
easy power and control wiring connections. All units are
completely wired, charged with R-410A and tested prior to
shipment. Test stations using a state-of-the-art computerized
process system shall be used to insure product quality.
Refrigerant charge and component part numbers are verified
via computer bar code scans during assembly. Vital run test
statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties
are monitored and recorded by the system to insure unit performance. This data could be provided by serial number
tracking if requested.
• Electric Heat - All electric heat models use 6HK electric
heat, which are available in 230v/1/60 from 2 kW to 25 kW,
230v/3/60 10kW to 25kW, and 460v/3/60 10kW to 25kW.
Most kits stageable above 10 kW. Single point accessory kits
are available for single phase models. Single phase single
point field wiring kits are available for all applications except
25kW. Electric heat kits must be certified to UL 1995 standard requirements.
6Johnson Controls Unitary Products
5126749-YTG-A-0715
Physical Data
MODELS
NOMINAL TONNAGE
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)23.730.137.243.547.755.0
AHRI net capacity (MBH)22.829.034.640.745.552.5
EER11.011.011.011.011.011.0
SEER14.014.014.014.014.014.0
Nominal CFM80010001200140016002000
System power (KW)2.12.63.23.84.24.8
Refrigerant typeR410AR410AR410AR410AR410AR410A
Refrigerant charge (lb-oz)5-49-28-39-414-414-2
Face area (Sq. Ft.)15.315.315.317.324.126.3
Rows122222
Fins per inch222222222222
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry TypeInterlacedInterlacedInterlacedInterlacedInterlacedInterlaced
Indoor Coil Data
Face area (Sq. Ft.)3.43.43.43.44.44.4
Rows233333
Fins per inch161616161616
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry TypeInterlacedInterlacedInterlacedInterlacedInterlacedInterlaced
Refrigerant controlTXVTXVTXVTXVTXVTXV
Outdoor Fan Data
Fan diameter (Inch)242424242626
TypePropPropPropPropPropProp
Drive typeDirectDirectDirectDirectDirectDirect
No. speeds111111
Motor HP each 1/4 1/41/41/4 1/3 1/3
RPM850850850850850850
Nominal total CFM240024002400240032003200
Direct Drive Indoor Blower Data
Fan Size (Inch)11 x 811 x 811 x 1011 x 1011 x 1011 x 10
TypeCentrifugalCentrifugalCentrifugalCentrifugalCentrifugalCentrifugal
Motor HP each 1/2 1/2 1/2 3/4 3/41
RPM1200 Max1200 Max1200 Max1200 Max1200 Max1200 Max
Frame size484848484848
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. Filter sizes: A=20x20, B=20x30.