GAS-FIRED
CONDENSING / HIGH EFFICIENCY
DOWNFLOW / HORIZONTAL
MODULATING FURNACES
WITH ECM MOTOR
NATURAL GAS
60 - 120 MBH INPUT
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.gamanet.org.
246815-YTG-D-0108
DESCRIPTION
These Category IV, highly efficient, compact, condensing
type furnaces are designed for residential and commercial
installations in a basement, closet, alcove, recreation room or
garage where the ambient temperature is above 32°F, or
higher. They may be either side wall or thru-roof vented using
approved plastic type combustion air and vent piping. All
units are factory assembled, wired and tested to assure
dependable and economical installation and operation.
WARRANTY
Lifetime limited warranty on both heat exchangers to the original purchaser; a 20-year limited warranty from original installation date to subsequent purchaser.
10-year warranty on the heat exchanger in commercial applications.
5-year limited parts warranty.
FEATURES
• Modulating heating operation includes:
- Modulating gas valve
- Modulating inducer operation
• Provides increased comfort level & very quiet unit operation
• Compact, easy to install, ideal height 40" cabinet.
• Blower-off delay for cooling SEER improvement.
• Easy to connect power/control wiring.
• Built-in, high level self diagnostics with fault code display.
• Low unit amp requirement for easy replacement application.
• Integrated control module for reliable, economical operation.
• High velocity filter available for easy field installation.
• May be installed as either two-pipe (direct vent) or single
pipe vent (using indoor combustion air)
• Top intake & vent connection allows installation in narrow
locations.
• Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
• Induced combustion system with inshot main burners for
quiet, efficient operation.
• No special vent termination kit required.
• 100% shut off main gas valve for extra safety.
• ECM High-efficiency, direct drive motor with large, quiet
blower.
• 24V, 40 VA control transformer and blower relay supplied
for add-on cooling.
°FHP AmpsIn.Amps
PC9B12N060DH111701/27.711 x 892014136115-1-60
PC9B12N080DH111701/27.711 x 892014143115-1-60
PC9C16N080DH111703/49.611 x 10122014159115-1-60
PC9C16N100DH111703/49.611 x 10122014163115-1-60
PC9C20N100DH11170112.811 x 11142012165115-1-60
PC9D20N120DH11170112.811 x 11142012182115-1-60
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local code s.
The furnace shall be installed so that the electrical components are protected from water.
Output
Max/Min
Blower
Nominal
Airflow
Blower
Size
Cabinet WidthAFUE
Total
Unit
Max.
Over-current
Min. Wire Size
(awg) @ 75 ft.
Protect
One Way
Air Temp. Rise
Maximum Input
Approximate
Operating
Weight
Air Temp. Rise
Minimum Input
Power Supply
(Voltage-PH-Hz
2Unitary Products Group
Page 3
246815-YTG-D-0108
AIR FLOW DATA
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
PC9B12N060DH11PC9B12N080DH11
CFMCFM
HighLowHighLowCOOL TapADJ Tap
13309001310890AB
11308001100740BB
12208501220830AA
10407301000670BA
11207701090720AC
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c.
static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static
pressure is not recommended.
NOTE: At some settings, LOW COOL airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the
instructions for the electronic air cleaner for further details.
JUMPER SETTINGS
JUMPER SETTINGS
JUMPER SETTINGS
NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM).
Unitary Products Group3
Page 4
246815-YTG-D-0108
FILTER PERFORMANCE
FILTER SIZES
The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower performance of the system, apply the filter drop value for the filter being used or select an appropriate value from the “Filter
Performance” table shown.
NOTE: The filter pressure drop values in the “Filter Performance” table shown are typical values for the type of filter
CFM
1200B(2) 14 x 20
1600C(2) 14 x 20
2000C(2) 14 x 20
2000D(2) 14 x 20
NOTE: All filters must be high velocity cleanable type.
Cabinet
Size
listed and should only be used as a guideline. Actual pressure drop ratings for each filter type vary between filter manufacturer.
FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)
APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1.Select the filter type.
2.Determine the External System Static Pressure (ESP)
without the filter.
3.Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 2 to determine the
total system static.
If total system static matches a ESP value in the airflow table
(i.e. 0.20, 0.60, etc,) the system airflow corresponds to the
intersection of the ESP column and Model/Blower Speed row
UNIT CLEARANCES TO COMBUSTIBLES
Application
Downflow1300 0 0
Horizontal0301100YesYesYes
* Combustible floor base or air conditioning coil required for use on combustible floor.
† Line contact only permitted between lines formed by t he i ntersectio n of the r ear panel and side panel (top in horizontal position) of the furnace jacket and build-
ing joists, studs or framing.
TopFrontRearLeft Side Right SideFlueFloor/Bottom
In.In.In.In.In.In.In.
*
1
ClosetAlcoveAttic
YesYesYesNA
Line
Contact
Yes
.
†
4Unitary Products Group
Page 5
246815-YTG-D-0108
For additional connection diagrams for all UPG equi pment refer to “Line Voltage System Wiring” document available on-line at
www.upgnet.com in the Product Catalog Section.
AC 26ATwo Stage Air Conditioner – Variable Speed Modulating Furnace