GAS-FIRED
CONDENSING / HIGH EFFICIENCY
UPFLOW MODULATING FURNACES
WITH ECM MOTORS
NATURAL GAS
60 - 120 MBH INPUT
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.gamanet.org.
246813-YTG-D-0108
DESCRIPTION
These Category IV, highly efficient, compact, condensing
type furnaces are designed for residential and commercial
installations in a basement, closet, alcove, recreation room or
garage where the ambient temperature is above 32°F, or
higher. They may be either side wall or thru-roof vented using
approved plastic type combustion air and vent piping. All
units are factory assembled, wired and tested to assure
dependable and economical installation and operation.
WARRANTY
Lifetime limited warranty on both heat exchangers to the original purchaser; a 20-year limited warranty from original installation date to subsequent purchaser.
10-year warranty on the heat exchanger in commercial applications.
5-year limited parts warranty.
FEATURES
• Modulating heating operation includes:
- Modulating gas valve
- Modulating inducer operation
• Provides increased comfort level & very quiet unit operation
• Compact, easy to install, ideal height 40" cabinet
• Blower-off delay for cooling SEER improvement.
• Easy to connect power/control wiring.
• Built-in, high level self diagnostics with fault code display.
• Low unit amp requirement for easy replacement application.
• Integrated control module for reliable, economical operation.
• May be installed as either two-pipe (direct vent) or single
pipe vent (using indoor combustion air)
• Top intake & vent connection allows installation in narrow
locations.
• Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
• Induced combustion system with inshot main burners for
quiet, efficient operation.
• No special vent termination kit required.
• 100% shut off main gas valve for extra safety.
• ECM high efficiency direct drive motor with large, quiet
blower.
• 24V, 40 VA control transformer and blower relay supplied
for add-on cooling.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
NOTES:
1. Wire size based on copper conductors, 60°C, 3% voltage drop.
2. Continuous return air temperature must not be below 55°F.
3. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
Unitary Products Group3
Page 4
246813-YTG-D-0108
For additional connection diagrams for all UPG e quipment refer to “Line Voltage System Wiring” document available on-line at
www.upgnet.com in the Product Catalog Section.
AC 26ATwo Stage Air Conditioner – Variable Speed Modulating Furnace
11308001100740B B
12208501220830A A
10407301000670B A
11207701090720A C
920650900610C B
950660880610B C
740540680510D B
860610810580C A
690540630500D A
790570730530C C
630530590500D C
PC9C16N080UP11
PC9C16N100UP11
PC9C20N100UP11
CFMCFM
HighLowHighLowCOOL TapADJ Tap
1660111022101480A B
1550105017801180B B
1610107020401350A A
144096016201050B A
147099018401250A C
137092015601010C B
12908501470940BC
HighLowCOOL TapADJ Tap
22801510A B
18601190B B
20901370A A
16301060B A
18801250A C
16201030C B
1500960BC
1410880DB
1490920CA
1290790DA
1360840CC
1140690D C
All CFM’s are shown at 0.5” w.c. external static pressure.These unit s have variable speed motors that automatically adjust to provide constant CFM from 0.0” to
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c.
external static pressure is not recommended.
NOTE: At some settings, LOW COOL airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Con-
sult the instructions for the electronic air cleaner for further details.
JUMPER SETTINGS
JUMPER SETTINGS
JUMPER SETTINGS
NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM).
2. Return air is through side opposite motor (left side).
3. In order to stay within the velocity rating the filters, airflows above 1800 CFM require either return from two sides or one side plus bottom.
4. Motor voltage at 115V.
Unitary Products Group9
Page 10
246813-YTG-D-0108
FILTER PERFORMANCE
The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower performance of the system, apply the filter drop value for the fil-
NOTE: The filter pressure drop values in the “Filter Performance” table shown are typical values for the type of filter
listed and should only be used as a guideline. Actual pressure drop ratings for each filter type vary between filter manufacturer.
ter being used or select an appropriate value from the “Filter
Performance” table shown.
FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)
APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1.Select the filter type.
2.Select the number of return air openings or calculate the
return opening size in square inches to determine the
proper filter pressure drop.
4.Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 3 to determine the
total system static.
5.If total system static matches a ESP value in the airflow
table (i.e. 0.20, 0.60, etc,) the system airflow corresponds to the intersection of the ESP column and Model/
Blower Speed row.
3.Determine the External System Static Pressure (ESP)
without the filter.
UNIT CLEARANCES TO COMBUSTIBLES
Application
Upflow130000CombustibleYesYes
ACCESSORIES
PROPANE (LP) CONVERSION KIT 1NP0680 - All units
This accessory conversion kit must be used to convert natural gas (N) units for propane (LP) operation. Conversions
must be made by qualified distributor or dealer personnel.
CONCENTRIC VENT TERMINATION -
1CT0302 (2")
1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole.
CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartidge has a 1/2" plastic tube fittings for installation in the drain line. Calcium carbonate refill media is also
avaiable from the Source 1 Parts (p/n 026-30228-000).
SIDEWALL VENT TERMINATION -
1HT0901 (3")
1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.
TopFrontRearLeft SideRight SideFlue
In.In.In.In.In.In.
SIDE RETURN FILTER -
1SR0302 - All Models
1SR0200 - All Models
1SR0101 - All Models
BOTTOM RETURN FILTER -
1BR0114 or 1BR0214 - For 14-1/2” cabinets
1BR0117 or 1BR0217 - For 17-1/2” cabinets
1BR0121 or 1BR0221 - For 21” cabinets
1BR0124 or 1BR0224 - For 24-1/2” cabinets
ROOM THERMOSTATS - A wide selection of compatible
thermosets are available to provide optimum performance
and features for any installation.