York PC9 User Manual

Page 1
USER’S INFORMATION, MAINTENANCE AND
EFFICIENCY RATING CERTIFIED
SERVICE MANUAL
MODELS: PC9 (Modulating Downflow/Horizontal With ECM Motor)
CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
TABLE OF CONTENTS
USER’S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INSTRUCTIONS FOR EXAMINING THE FURNACE
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . .3
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . .3
Read the Instructions Below Before Trying to Start the
Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . .4
Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . .5
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
CONTACT INFORMATION
• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.
• Contact us by mail:
York International
Consumer Relations
Norman, OK 73069
FURNACE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
FURNACE CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cleaning the Secondary Heat Exchanger . . . . . . . . . . . . . . . . . . .5
Cleaning the Vent / Air Intake System . . . . . . . . . . . . . . . . . . . . . .5
NORMAL OPERATION SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . .5
ADJUSTMENT OF FAN CONTROL SETTINGS . . . . . . . . . . . . . . . .6
Delay Taps Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Humidistat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . .7
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL . . . . . .7
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .10
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5005 York Drive
ISO 9001
Certified Quality
Management System
The manufacturer recommends that the user read all sec­tions of this manual and keep the manual for future refer­ence.
FIRE OR EXPLOSION HAZARD - Failure to follow
safety warnings exactly could result in serious injury, death, or property damage.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any elec trical switch; do not use any phone (including cell phone) in your building.
Leave the building immediately.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplie r, call the fire department.
— Installation and service must be performed by a
qualified installer, service agency or the gas sup­plier.
SECTION I: USER’S INFORMATION
SAFETY
1. The furnace area must be kept clear and free of combustible mate­rials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be kept free and clear of insulating materials. The furnace area must be examined when installed in an attic or other insulated space or when insulation is added to be sure that the insulation material has been kept away from the furnace.
3. The furnace needs air for combustion in order to operate properly and safely. Do not block or obstruct air openings on the furnace, air openings to the area where the furnace is installed, or spaces around the furnace.
4. Follow the instructions exactly as shown on the OPERATING INSTRUCTION LABEL or the Start-up and Shutdown Instructions on Page 3 of this manual when lighting the furnace or turning the furnace off.
5. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
6. Do not use this furnace if any part has been under water. A flood­damaged furnace is extremely dangerous. Attempts to use the fur­nace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
172988-YUM-A-0106
Page 2
172988-YUM-A-0106
VENT PIPE
BLOWER ACCESS PANEL
CONTROL BOARD
TRANSFORMER
PRESSURE SWITCH TUBING
PRESSURE SWITCHES
GAS VALV E
GAS REFERENCE HOSE
CONDENSATE HOSE
RAIN GUTTER
INDUCER HOUSING
INDUCER MOTOR
CONDENSATE DRAIN HOSE
CONDENSATE TRAP
LIMIT SWITCH
BURNER BOX
FIGURE 1: Component Locations
7. NEVER . . .Store flammable materials of any kind near your fur­nace. Gasoline, solvents, and other volatile liquids should be stored only in approved containers outside your home. These materials vaporize easily and are extremely dangerous.
8. NEVER . . .Store cleaning materials near your furnace. Materials such as bleaches, detergents, powdered cleansers, etc., can cause corrosion of the heat exchangers.
9. NEVER . . . Use the area around your furnace as a storage area for items which could block the normal flow of air. This flow of air is required for ventilation of the various furnace components.
FIRE OR EXPLOSION HAZARD This furnace is designed and approved for use with Nat-
ural Gas and (LP) Propane Gas ONLY. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the furnace heat exchanger, which could result in Fire, Per­sonal Injury, and/or Property Damage.
INSTRUCTIONS FOR EXAMINING THE FURNACE INSTALLATION
It is the owner’s responsibility to ensure that an annual inspection of the entire heating portion of the unit is made by a qualified service agency.
1. Examine the heat exchanger, through a field installed access panel located on the supply air plenum. Visually examine the exte­rior sections of the vent/combustion air piping and the vent con­nectors to be sure that they are physically sound without holes or excessive corrosion.
2. Examine the vent pipe making sure it is firmly in place, that it slopes slightly upward and is physically sound without holes and all of the connections are secure.
3. Examine the return-air duct connections to make sure they are physically sound, sealed to the furnace casing, and the ducts ter­minate outside the space containing the furnace.
4. Examine the furnace casing making sure the physical support is sound without sagging, cracks or gaps. Examine the furnace base making sure it is physically sound without cracks, gaps or sagging and has a good seal.
5. Examine the furnace casing for obvious signs of deterioration.
6. Examine the burner flames to make sure they are in good adjust­ment. Refer to the pictorial sketch shown in Figure 2 as a compari­son to the actual flame.
7. Examine the furnace as outlined above in steps 1 - 6 before each heating season. Use Figure 3 for visual reference.
MANIFOLD
FIGURE 2: Burner Flame Drawing
MAIN BURNER
BURNER FLAME
INNER FLAME CONES
COMBUSTION AIR TRANSITION (not shown)
3
EXAMINE RETURN AIR DUCT CONNECTION
BLOWER DOOR
2
REMOVE THIS PANEL TO EXAMINE VENT PIPE
4
EXAMINE FURNACE CASING
5
EXAMINE CASING FOR DETERIORATION
6
REMOVE THIS PANEL TO EXAMINE THE BURNER FLAMES
BURNER DOOR
1
PLACE A FIELD INSTALLED ACCESS PANEL LOCATED IN THE DOWNFLOW PLENUM TO EXAMINE THE HEAT EXCHANGER
4
EXAMINE FURNACE CASING
5
EXAMINE CASING FOR DETERIORATION
FIGURE 3: Furnace Examination Checkpoints
2 Unitary Products Group
Page 3
172988-YUM-A-0106
HOW YOUR GAS FURNACE WORKS
Your furnace is a very easy appliance to take for granted. Season after season, it sits there in your home, keeping you warm and comfortable. For this reason, you may never have given much thought to the way your furnace operates. In order to get the safest and most efficient oper­ation from your furnace, you should understand how your furnace does its job.
When you set your thermostat to provide more heat in your home, you are starting the heating cycle of the furnace. First, the inducer motor starts to purge the heat exchanger of any remaining gases. Next, the hot surface ignitor glows and after a warm-up period the gas valve opens and ignition occurs. A short time later, the blower starts and dis­tributes the warm air throughout the home. The furnace control will vary the amount of heat and the amount of airflow needed to maintain the proper temperature in the home.
START-UP AND SHUTDOWN INSTRUCTIONS
Read the Instructions Below Before Trying to Start the Furnace
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, and/or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the burner by hand.
B. BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
C. Use only your hand to push the gas control switch to the “on” posi-
tion. Never use tools. If the switch will not operate by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Operating Instructions:
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove burner door.
5. Move gas control switch to the “OFF” position. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to next step.
7. Move gas control switch to the “ON” position. Do not force.
8. Replace burner door.
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate fol­low the instructions, “TO TURN OFF THE APPLIANCE” and call your service technician or gas supplier.
To Turn Off the Appliance:
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be per­formed.
3. Remove burner access panel.
4. Move gas control switch to the “OFF” position.
5. Replace burner access panel.
Should overheating occur, or the gas valve fail to shut off, turn the external manual gas valve in the gas supply line to the furnace to the “off” position and let the furnace cool off before shutting off the electrical power supply. Refer to Figure 5.
MAIN REGULATOR ADJUSTMENT
INLET PRESSURE TAP
ON/OFF KNOB
FIGURE 4: Gas Valve - White Rodgers
EXTERNAL MANUAL SHUTOFF VALVE
TO GAS SUPPLY
DRIP LEG
TO GAS SUPPLY
GROUNDED JOINT UNION MAY BE INSTALLED INSIDE OR OUTSIDE UNIT.
FIGURE 5: Gas Piping
MANUAL SHUT-OFF VALV E
GAS PIPE
GAS PIPE
DRIP LEG
MANUAL SHUT-OFF VALVE
FIGURE 6: Horizontal Gas Piping NOTE: The spring-loaded safety cut-off switch, mounted on the blower
deck, behind the indoor fan access panel will automatically cut off the electrical power supply to the furnace when the blower panel is removed. As a safety precaution, all electrical power and the gas supply to the furnace should be turned off before servicing.
OUTLET PRESSURE TAP
DRIP LEG
GAS BURNERS
GAS VALVE
Unitary Products Group 3
Page 4
172988-YUM-A-0106
FURNACE USER MAINTENANCE
Before proceeding, be sure the area is well ventilated. Turn the thermostat OFF. If the blower is running, wait until it stops automatically. Turn OFF the gas and electrical power supplies to the furnace. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.
FILTER RACK
RACK AND FILTERS SECURED INSIDE BLOWER SECTION FOR SHIPMENT
CASING SIZE
14-1/2” 17-1/2”
21”
24-1/2”
DIMENSION FH
13-1/4” 12-1/2” 11-1/2”
9-3/4”
Blower Care
Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vac­uum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then this service must be performed by a qualified service agency.
The blower can be serviced/removed through the blower access panel on the inside of the furnace. If there is a combustion air pipe installed inside the furnace, it may have to be removed to access the blower access panel. After the combustion air pipe is removed, it is easy to remove the inside blower access panel by pushing it up, against a spring, or removing the screws of the access panel. Blower is now ready to be serviced through the opening.
If the blower has to be removed through the inside blower access panel, then the top flange, blower door switch and bottom flange will also have to be removed on some models, On some other models, top and bot­tom angles will have to be removed to slide the blower out of the fur­nace.
Make sure you DO NOT move the clip-on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.
Air Filters
The filters should be checked every 3 months. On new construction, check the filters every week for the first four weeks and every three weeks after that, especially if the indoor fan is running continuously. When replacing the filter(s), refer to Table 1 to be sure you install the right size filter for your furnace. Dirty filters greatly restrict the flow of air and may cause damage to the moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation.
Never operate your furnace without a suitable air filter.
Removing Filters
Most downflow furnaces have their filters located on the top of the fur­nace in an external filter rack. To check filters you should:
1. Follow the instructions to turn off the appliance before servicing.
2. Filters are installed in the return air plenum above the blower assembly. An “A” frame assembly supports the filters. Lift the filter slightly and remove for service.
3. Follow the instructions “HOW TO CLEAN YOUR FURNACE’S FIL­TER”.
4. Reverse the procedure to reinstall filters.
5. Follow the operating instructions to place appliance in operation.
NOTE: FILTER ACCESS THROUGH DUCKWORK MUST BE PROVIDED FOR REMOVAL AND CLEANING
FILTERS
DUCKWORK
FILTER
RACK
FH
FIGURE 7: Filter Rack Assembly and Attachment TABLE 1:
Filter Sizes
Input
BTU/H (kW)
(m
CFM
3
/min)
Cabinet
Size
Top Return
Filter in(cm)
60 (17.6) 1200 (34) B (2) 14 x 20 (36 x 51) 80 (23.4) 1200 (34) B (2) 14 x 20 (36 x 51)
80 (23.4) 1600 (45) C (2) 14 x 20 (36 x 51) 100 (29.3) 1600 (45) C (2) 14 x 20 (36 x 51) 100 (29.3) 2000 (57) C (2) 14 x 20 (36 x 51) 120 (35.1) 2000 (57) D (2) 14 x 20 (36 x 51)
Externally Mounted Air Filters
Some installations may have the air filter in a rack attached to the cas­ing of the furnace or placed in the return air duct. You can gain access to the filter by pulling on the door or unscrewing the retaining screw, then slide the filter(s) out of its channel. Replace throw away filter(s) with the same size new filter(s). Throw away filter(s) may be replaced with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described below and then re-installed.
How to Clean your Filter
High-velocity filters may be cleaned with a vacuum cleaner or washed with a garden hose. Be sure to shake off excess water and allow filter to completely dry before re-installing the filter.
To replace the filter after cleaning you must do the following:
1. Slide filter into place.
2. Snap the door on or place the door in position.
3. Make sure the door is secure to the end of the filter rack.
4. For filter grilles, place the filter into the grilles, close the grille cover and tighten the retaining screw.
Every time the filters are changed the following items should be visually inspected:
• Check combustion air and vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.
• Check the drain lines to make sure there are no cracks or leaks.
• Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the fur­nace and its components must be done by a qualified service pro­fessional.
4 Unitary Products Group
Page 5
172988-YUM-A-0106
If, during the inspection of your furnace, you find any of the following conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace. Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace. If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the fur­nace, and set thermostat to the desired temperature.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not require periodic oiling.
SECTION II: SERVICE AND MAIN TENANCE MANUAL
SAFETY
The following safety rules must be followed when servicing th e furnace.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, and death or property damage.
• Before servicing, disconnect all electrical power to the fur­nace.
• When servicing controls, label all wires prior to discon­necting. Reconnect wires correctly.
• Verify proper operation after servicing.
FURNACE MAINTENANCE
The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.
1. The vent terminal screen (if applicable).
2. The furnace vent and combustion air intake passageways. Should it be necessary to service the vent/air intake system, the manufac­turer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.
3. The furnace burners, ignitor and flame sensor.
4. The condensate collection and disposal system. If any disassem­bly of components containing flue or vent gases is required, a qualified service agency must perform the service.
FURNACE CLEANING
NOTE: The cleaning operations listed below must be performed
only by a qualified service agency.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation. If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the burner door and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
6. Remove burners from the burner assembly.
7. Burners may be cleaned by rinsing in hot water.
8. Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the burner door and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
6. Remove the vent pipe assembly, vent blower and condensate p an.
7. The heat exchanger is now exposed.
8. With a long flexible wire brush, clean inside each tube at both the top and bottom. The brush must pass around the rear heat exchanger tubes. Then vacuum loose the scale and dirt from each tube.
9. Replace all components in reverse order. Reconnect all wiring.
10. Restore electrical power and gas supply to the furnace.
11. Check furnace operation.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and danger­ous operation. Verify proper operation after servicing.
Cleaning the Secondary Heat Exchanger
1. Follow steps 1 - 7 under cleaning the Heat Exchanger.
2. Remove the vent piping from the vent blower housing. Disconnect the drain lines from the vent blower housing and from the conden­sate drain pan. Remove the vent blower housing blower and the condensate pan.
3. Using a stiff wire brush, remove the loose scale or soot from each tube.
4. Vacuum the secondary heat exchanger.
5. Finish the cleaning procedure by following steps 9 - 11 under cleaning the Heat Exchanger.
Cleaning the Vent / Air Intake System
Should it be necessary to service the vent / air intake system, the man­ufacturer recommends this service be conducted by a qualified service agency.
The operation of this appliance requires the reassembly and resealing of the vent / air intake system as specified in the “Combustion Air and Vent System” located in the Installation Manual.
NORMAL OPERATION SEQUENCE
The furnace control calculates the optimum firing rate each time the wall thermostat R and W contacts close or open (at the beginning and at the end of each call for heat) based on information from the thermo­stat and past demand. UNLIKE CONVENTIONAL SYSTEMS, THE WALL THERMOSTAT DOES NOT SIMPLY TURN THE FURNACE ON AND OFF. THE FURNACE CONTROL CALCULATES THE DEMAND AND MAY CONTINUE TO FIRE THE FURNACE DURING PORTIONS OF THE THERMOSTAT "OFF" CYCLE.
When the wall thermostat R and W contacts close, indicating a call for heat, the following sequence occurs:
Unitary Products Group 5
Page 6
172988-YUM-A-0106
1. The inducer is energized and ramps up its speed until airflow is proven by the pressure switch and by the pressure sensor on the control board.
2. The hot surface ignitor is energized.
3. After a 17-20 second igniter heatup, the gas valve opens and the burners light.
4. When the control senses that flame is present, the circulating blower starts at low speed.
5. The furnace fires at 70% of full rate for 30-45 seconds, then drops to the minimum (35%) firing rate.
6. The firing rate is automatically adjusted to meet demand, increas­ing gradually to maximum (100%) firing rate if the thermostat is not satisfied within a defined time.
7. When the thermostat R and W contacts open (thermostat is satis­fied) the furnace control recalculates the demand and a new firing rate.
a. If demand exceeds the minimum firing rate, the burners will
continue to fire at a recalculated reduced firing rate, decreas­ing if the thermostat remains off for a defined time.
b. If demand does not exceed the minimum firing rate, the burn-
ers will shut off immediately.
8. After the burners shut off, the circulating blower will continue to run until the temperature sensor detects that the supply air tempera­ture has dropped to the desired level, which should take from 30 to 90 seconds.
ADJUSTMENT OF FAN CONTROL SETTINGS
Cooling - The airflow delivered by the furnace during cooling operation can be adjusted to match the cooling capacity of the A/C condensing unit. This is done by moving the COOL and ADJ jumper on the control board to give the desired airflow.
The COOL jumper has four positions, which will deliver sufficient airflow in cooling mode for the cooling capacities shown in the Table 2.
TABLE 2:
Continuous Fan Operation - The airflow delivered by the furnace dur-
ing continuous fan operation can be adjusted as desired. This is done my moving the RECIRC jumper on the control board to give the desired airflow.
The jumper has three positions. The "A" position delivers maximum air­flow, 100% of the blower capacity. Position "B" delivers approximately 70% of the blower capacity. And Position "C" delivers minimum airflow, approximately 35% of the blower capacity.
Cooling Airflow - A/C Capacity in Tons
Models
Cool Jumper Position
DCBA 60/1200 1-1/2 2 2-1/2 3 80/1200 1-1/2 2 2-1/2 3 80/1600 2-1/2 3 3-1/2 4
100/1600 2-1/2 3 3-1/2 4 100/2000 3 3-1/2 4 5 120/2000 3 3-1/2 4 5
CFM INDICATOR
DIAGNOSTIC LIGHT
LOW VOLTAGE TERMINALS
ERROR BUTTON
TEST BUTTON
CONTINUOUS FAN SPEED JUMPER
ERROR
TEST
R
W
Y/Y2
Y1
HUM
G
HUMIDISTAT CONNECTED
C
YES
AIR
NO
RECIRC
CFM
DELAY
COOL
DELAY JUMPER
ADJUST
COOLING SPEED JUMPER
HUMIDIFIER TERMINALS
EAC TERMINALS
ADJUST JUMPER
FIGURE 8: Furnace Control Board
Delay Taps Selection
The set of jumper pins on the control board labeled "DELAY" are used to set the delay profiles for the furnace. These can be chosen so as to maximize the comfort and sound levels for various regions of the coun­try. Ta p A is the default profile. It pro vides a 30-second ramp-up from zero airflow to full capacity and a 30-second ramp-down from full capacity back to zero airflow. Whenever there is a change in airflow mode, such as from low heat to high heat, the motor will take 30 seconds to ramp from one speed to the other. Ta p B is the humid profile. This profile is best-suited for installations where the humidity is frequently very high during cooling season, such as in the southern part of the country. On a call for cooling, the blower will ramp up to 50% of full capacity and will stay there for two minutes, then will ramp up to 82% of full capacity and will stay there for five min­utes, and then will ramp up to full capacity, where it will stay until the wall thermostat is satisfied. In every case, it will take the motor 30 sec­onds to ramp from one speed to another. Tap C is the dry profile. This profile is best suited to parts of the country where excessive humidity is not generally a problem, where the sum­mer months are usually dry. On a call for cooling the motor will ramp up to full capacity and will stay there until the thermostat is satisfied. At the end of the cooling cycle, the blower will ramp down to 50% of full capac­ity where it will stay for 60 seconds. Then it will ramp down to zero. In every case, it will take the motor 30 seconds to ramp from one speed to another.
Ta p D is the normal profile, best suited for most of the cou ntry, where neither excessive humidity nor extremely dry conditions are the norm. On a call for cooling, the motor will ramp up to 63% of full capacity and will stay there for 90 seconds, then will ramp up to full capacity. At the end of the cooling cycle, the motor will ramp down to 63% of full capac­ity and will stay there for 30 seconds, then will ramp down to zero. In every case, it will take the motor 30 seconds to ramp from one speed to another.
Humidistat
When a humidistat is installed in the system, the “Humidistat con­nected?” jumper on the control board should be moved to the “YES” position. The cooling airflow will then be reduced by 15% whenever the humidistat indicates high humidity.
6 Unitary Products Group
Page 7
172988-YUM-A-0106
Hot Surface Ignition System
HOT SURFACE IGNITION SYSTEM Do not attempt to light this furnace by hand (with a match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1. Check to see that the power to the furnace and the ignition control module is ON.
2. The manual shut-off valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.
Never bypass any safety control to allow furnace opera­tion. To do so will allow furnace to operate under poten­tially hazardous conditions.
Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
FURNACE CONTROL DIAGNOSTICS
This furnace has built-in self-diagnostic capability. If a system problem occurs, a flashing LED shows a fault code. The LED can flash red, green or amber to indicate various conditions. The LED is located on the furnace control board and can be seen through the clear view po rt in the lower door of the furnace. To indicate an error condition, the LED will turn on for 1/4 second and off for 1/4 second. The pattern will be repeated the number of times equal to the flash code. For instance, a "six flash code" will be indicated by the LED turning on and off six times. There will be a two second off period between each set of flashes. The flash codes and an indication of their likely causes are listed below:
STEADY OFF - No 24V power to board. Check the 24 volt control cir­cuit fuse on the board. Check the circuit breaker or fuse on the 115 volt supply power to the furnace. Check that the 24 volt transformer.
One Green Flash - Normal Operation with no call for heat. Two Green Flashes - Indicator for "No error codes in memory". See
Diagnostic Fault Code Storage and Retrieval section below. Three Green Flashes - Indicator for "Error codes cleared from mem-
ory". See Diagnostic Fault Code Storage and Retrieval section below. Rapid Green Flash - Control is in "Factory Speedup" mode. This mode
is used only during factory run-testing of the furnace. To stop this mode, cycle power to the furnace off and then back on.
One Amber Flash - Normal operation with call for cooling. Two Amber Flashes - Normal operation with call for heat. Three Amber Flashes - Normal operation, burner is on at end of heat-
ing cycle after wall thermostat has been satisfied. Four Amber Flashes - Heating capacity is reduced due to restriction in
the circulating air system. Five Amber Flashes - Heating capacity is reduced due to restriction in
the combustion air or vent system. Rapid Amber Flash - Low flame sense current. Check for dirty or mis-
located flame sensor rod.
One Red Flash - Flame is present with no power being supplied to gas valve. This can be caused by a gas valve that is slow to close or that leaks gas through to the burners.
Two Red Flashes - Stuck closed pressure switch. The control confirm s that the pressure switch contacts are open at the beginning of each cycle. This could be caused by a faulty pressure switch or by mis-wiring of the pressure switch.
Three Red Flashes - Stuck open pressure switch. This indicates that the pressure switch is open when it should be closed. This could be caused by a faulty combustion air blower, blocked vent pipe, blocked air intake pipe, blocked condensate drain, faulty pressure switch hose or a faulty pressure switch.
Four Red Flashes - High limit switch open or 24 volt fuse is open. This may be caused by a dirty air filter, improperly sized duct system, faulty blower motor, restricted circulating airflow or an open fuse on the con­trol board.
Five Red Flashes - Rollout switch or auxiliary limit switch open. Check the rollout switch on the side of the burner box. It is a manual reset switch. To reset, push the small button in the center of the switch. If it cannot be reset or if the switch trips again, contact a qualified service­man. Check the limit switch mounted in the combustion air blower hous­ing.
Six Red Flashes - Current failure on modulating gas valve. Seven Red Flashes - Lockout due to no ignition. The control will try
three times for ignition. If flame cannot be established in three tries, the control will lockout for one hour and then will try again to light. Check gas supply, ignitor, gas valve, flame sensor.
Eight Red Flashes - Lockout due to too many flame recycles. This flash code occurs if flame is lost five times during a single heating cycle. This could be caused by a faulty gas valve, low gas pressure, or dirty flame sensor. The control will lock out for one hour and then will try again.
Nine Red Flashes - Reversed line polarity or improper grounding. Check polarity of the incoming power to the furnace. Check the ground­ing of the furnace, including the transformer ground and the L1 and neutral connections.
Ten Red Flashes - Unexpected gas flow present. Check gas valve wir­ing. If correct, replace gas valve.
Eleven Red Flashes - Main blower failure - This flash code occurs when the main limit opens and fails to reclose within five minutes, indi­cating that the blower motor or blower wheel has failed.
Twelve Red Flashes - ID plug is not present or not connected properly, check for loose plug or loose wires in plug.
Steady On Red - Control fault has been detected or there is 24 volts present without 115 volts. Check that there is 24 volts and 115 volts being supplied to the board. If so, then the board should be replaced.
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL
The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily. This memory will be retained even is power to the furnace is lost. Only a qualified service technician should use this feature.
The control stores up to five separate error codes. If more than five error codes have occurred since the last reset, only the five most recent will be retained. The furnace control board has a button, labeled "LAST ERROR" that is used to retrieve error codes. This function will only work if there are no active thermostat signals. So any call for heating, cooling or continuous fan must be terminated before attempting to retrieve error codes.
T o retrieve the error codes, push the LAST ERROR button. The LED on the control will then flash the error codes that are in memory, starting with the most recent. There will be a two-second pause between each flash code. After the error codes have all been displayed, the LED will resume the normal slow green flash after a five second pause. To repeat the series of error codes, push the button again.
If there are no error codes in memory, the LED will flash two green flashes. T o clear the memory , push the LAST ERROR button and hold it for more than five seconds. The LED will flash three green flashes when the memory has been cleared, then will resume th e normal slow green flash after a five-second pause.
Unitary Products Group 7
Page 8
172988-YUM-A-0106
SECTION III: REPLACEMENT PARTS LIST
35
33
45
11
13
14 46
10
7
30
15
16
1
62
55,56
22
52
21
23
54
18
72
71
69 68
19
5
9,37
47
25
2
64
59
50
18
49
54
26 14
48
27
80
28
57
2
4
60
5
51
6
44
53
31
43
24
20
14
46
63
10
43
37
9
6
29
39
31
8 Unitary Products Group
Page 9
172988-YUM-A-0106
ITEM DESCRIPTION
MOTOR
1 MOTOR, DIRECT DRIVE BLOWER 2 MOTOR, INDUCER ASSY
ELECTRICAL
3* CAPACITOR
4 SWITCH, LIMIT (INDUCER) 5 LIMIT, TEMPERATURE (Primary) 6 LIMIT, FLAME ROLL-OUT 7 CONTROL, FURNACE MODULE
7A* PLUG, JUMPER
8* SENSOR, THERMISTOR
9IGNITER 10 SENSOR, FLAME 11 SWITCH, PRESSURE
12* SWITCH, DOOR
13 TRANSFORMER 14 VALVE, GAS
AIR MOVING
14 HOUSING, BLOWER 15 WHEEL, BLOWER
17* BRACKET, BLOWER (2 Req’d)
FABRICATED PARTS
18 PANEL, BLOWER COVER
BRACKET, CONDENSATE TRAP
19 20 BURNER, MAIN GAS 21 COIL, CONDENSING 22 SHELF, BLOWER 23 HEAT EXCHANGER ASS’Y 24 MANIFOLD, GAS 25 SHIELD, PAN 26 PAN, CONDENSATE 27 PANEL, VEST ACCESS (Upper) 28 PANEL, BLOWER ACCESS (Lower) 29 WRAPPER, BURNER BOX 30 CHANNEL, TOE PLATE 31 COVER, GAS CONTROL
32* PANEL, BOTTOM
33 PANEL, TOP 34 SUPPORT, BURNER 35 WRAPPER, CABINET (Insulated)
36* PLATE, DIFFUSER
37 BRACKET, IGNITER
38* BRACKET, DOOR SWITCH
39 BOTTOM PANEL, BURNER BOX 40 41 42
ITEM DESCRIPTION
MISCELLANEOUS
43 PLUG, WINDOW, CLEAR - 1.5” 44 COMBUSTION AIR TRANSITION, 3-WAY
TUBING, SILICONE (Gray, .188 ID, 2.83 ft. Req’d)
45 46 TUBING, SILICONE (Preformed)
TUBING, SILICONE (Gray, .188 ID, 1.25 ft. Req’d)
47 48 GASKET, COMBUSTION BLOWER 49 GASKET, CONDENSATE PAN
GASKET, UPPER CONDENSATE PAN (2 Req’d)
50 51 GASKET, GAS CONTROLS 52 GASKET, CONDENSING COIL
GASKET, COMBUSTION AIR TRANSITION
53 54 VENT PIPE 2” X 15.25” LG. 55 GROMMET, MOTOR (3 Req’d) 56 FERRULE (3 Req’d)
COMBUSTION BLWR RESTRICTOR
57
58* INSERT, SILICONE
59 RESTRICTOR, TUBE
WASHER, FLAT FIBERGLASS (3 Req’d)
60
61* HARNESS, MAIN WIRING
62 MOUNT, 1 PC. MOTOR 63 ORIFICE, BURNER
(Natural #45)
64 TRAP, CONDENSATE 65* WIRING DIAGRAM 66* 45 DEG. STREET ELBOW 2” 67* DRAIN TUBE, CONDENSATE TRAP
68 DRAIN TUBE, COMBUSTION BLOWER
69 DRAIN TUBE,
CONDENSATE PAN
70* DRAIN TUBE, STRAIGHT 21” LG.
71 DRAIN TUBE, RAIN GUTTER
72 DRAIN HOSE ASSEMBLY 73* DRAIN TUBE, CONDENSATE 74* LOCKNUT, CONDUIT (1/2”) 75* ADAPTER, INSERT 76* BUSHING, THREADED 77* GROMMET, MANIFOLD 78* VENT PIPE ASSEMBLY 79* DRAIN TUBE, VENT PIPE
80 DOOR KN OB (Blac k) 81* SIGHT GLASS, OVAL
NOTE: *Not Shown
Major components and suggested stocking items are shown with shaded item number.
Unitary Products Group 9
Page 10
172988-YUM-A-0106
FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL
MODEL NO. DESCRIPTION USED WITH
1NP0680 PROPANE (LP) CONVERSION KIT WITH GAS VALVE ALL MODELS 1CT0302 CONCENTRIC INTAKE/VENT 2” 60, 80, 100 INPUT MBH 1CT0303 CONCENTRIC INTAKE/VENT 3” 100, 120 MBH 1NK0301 CONDENSATE NEUTRALIZER KIT ALL MODELS 1HT0901 SIDEWALL VENT TERMINATION KIT ALL MODELS 1CB0317 1CB0321 21” CABINET 1CB0324 24-1/2” CABINET
1TK0917 1TK0921 21” CABINET 1TK0924 24-1/2” CABINET
COMBUSTIBLE FLOOR BASE
COIL TRANSITION KIT
REPLACEMENT PART CONTACT INFORMATION
This is a generic parts list. To request a complete parts list, refer to the contact information below:
• Visit our website at www.source1parts.com for the following information:
1. Search for a part or browse the catalog.
2. Find a dealer or distributor.
3. Customer Service contact information. a. Click on the “Brand Links” button
b. Click on the “Customer Service” button
• You can contact us by mail. Just send a written request to:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
17-1/2” CABINET
17-1/2” CABINET
10 Unitary Products Group
Page 11
SECTION IV: WIRING DIAGRAM
172988-YUM-A-0106
FIGURE 9: Wiring Diagram
Unitary Products Group 11
Page 12
Limited Warranty
UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts that prove to have such def ects acco rding to th e ter ms out lined on t his warr ant y. This warranty covers only t he eq uipme nt de scribe d by the Prod uct Model Number and Serial Number listed on t he Warranty Registration Card. UPG warrants the primary heat exchangers in the product to be free from defects in factory workmanship and material under normal use and service and will at its option, repair or furnish a replaceme nt heat exchanger, either new or reconditioned, that meets the intended fit, use and function of the original heat exchanger for any heat exchanger furnished by UPG which proves to have such defects within the duration of warranty coverage. Alternatively, UPG may , at it s option, extend a replacement all owance to be applied toward th e purchase of a new furnace or packag ed unit marketed by UPG. The exact amount of the allowance will be determined at the discretion of UPG, based upon current market conditions, but in no case shall this allowance exceed thirty (30) percent of the original consumer pu rchase pr ice o f the fu rnace, exclu ding suc h items as du ctwork, w iring, piping and ins tallation costs. U PG shall have no responsibility hereunder for installation, shipping, handling or other charges except as specifically provided herein. For your benefit and protection, return the Warranty Registration Card to UPG promptly after installation. This will initiate the warranty period and all ow us to contact you, should it beco me necessary. In the abse n ce of a rec or de d Warranty Registration Card, the war ra nt y p eriod will begin upon product shipment from UPG.
This warranty extends only to the original consumer purchaser and is non-transferable. For this warranty to apply, the product must be installed accord ing to UPG recommendations and specifica tions , and in acc ordance with all l ocal, state, an d natio nal codes; and the pr oduct mus t not be removed f rom its plac e of original installation. The warranty period for repair or replacement parts provided hereunder shall not extend beyond the warranty peri od stated on the re ve rs e side of this warranty.
HEAT EXCHANGER
FURNACE TYPE
Original Owner
90% PC9
UPG strongly recommends regular periodic preventative maintenance on this equipment. The person most familiar with the equipment in your HVAC system is a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment, and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere. This warranty applies only to products installed in the United States and Canada.
This warranty does not cover any:
1. Shipping, labor, or material charges.
2. Damages resulting from transportation, installation, or servicing.
3. Damages re sulting from ac cident, abuse, fir e, flood, alterat ion, or acts of God (tampe ring, altering, defacing or removi ng the produc t serial number will serve to void this warranty).
4. Damages resulting from use of the product in a corrosive atmosphere.
5. Damages resulting from inadequacy or interruption of electrical service or fuel supply, improper voltage conditions, blown fuses, or other like damages.
6. Cleaning or replacement of filters.
7. Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporat or.
8. Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water; (IV) fouling or restriction of the water circuit by foreign material or li ke causes.
9. Damages resulting from operation with inadequate supply of air or water.
10. Damages resulting from use of components or accessories not approved by UPG (ve n t damp er s, etc.).
11. Increase in fuel or electric cost.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL­ITY AND FITNESS FOR A PARTICULAR PURPOSE.
SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU. SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES TO LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE DURA-
TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA­TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.
IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH­ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC­TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRACTORS. THE ABOVE LIMITATION ON CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITA TION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, OR FOR STRICT LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.
UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG, ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT . THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
Residential Applications
Subsequent Owner
Lifetime 20 10 5
Non-Residential
Applications
PARTS
EXCLUSIONS
For Owner's Information:
PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________ UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________
Subject to change without notice. Printed in U.S.A. 172988-YUM-A-0106 Copyright © by Unitary Products Group 2006. All rights reserved. Supersedes: Nothing
Unitary 5005 Norman Products York OK Group Drive 73069
Loading...