York NC - ND Technical Guide

Y
505428-YTG-N-0712
®

Description

Predator® condensing units and heat pumps are completely
TECHNICAL GUIDE
R-410A SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS AND AIR HANDLERS
PREDATOR® SERIES
CONDENSING UNIT MODELS
PC090-180 and PD180-240
HEAT PUMP UNIT MODELS
NC090-300 and ND120-240
AIR HANDLING UNIT MODELS
7.5 - 25 Ton 60 Hertz
assembled, piped and wired at the factory to provide a single-piece unit for shipment and rigging. Each unit is pressurized with a holding charge of refrigerant R-410A for storage and/or shipping.
The compact design, clean styling, small footprint, and quiet operation make these condensing units and heat pumps suitable for almost any outdoor location. On rooftops... because they weigh much less than a single package unit of similar capacity and are much easier to rig and support. On the ground... because the footprint is compact allowing a variety of applications.
Both the Predator® condensing units and heat pumps are equipped with reliable Simplicity® microprocessor controls to assure proper operation and unit protection for long product life. Products from 10 to 20 tons are available in single or dual (2 or 4 pipe) refrigerant circuits for redundancy in operation and various application choices such as one outdoor unit matched with two indoor units.
The Predator® air handling units are completely assembled units, including a well-insulated cabinet, a DX cooling coil with copper tubing, aluminum fins, expansion valve(s), distributor(s), 2” throwaway filters, a centrifugal blower, a blower motor, an adjustable belt drive, a blower motor contactor and a small holding charge of nitrogen.
YC/YD/PC Outdoor Units
Units are shipped in the vertical position ready for field installation, but can be easily converted to horizontal position. An added benefit of the Predator® air handling units is they are designed to operate with either a condensing unit or a heat pump and no field modification or special unit is required for heat pump applications.
(Except YC300)
Certified Quality
Management System
ISO 9001
NC/ND Indoor Units
YC/YD/PC/PD Outdoor Units
505428-YTG-N-0712

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Condensing Unit Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Outdoor Unit Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Air Handling Unit Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cooling and Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Air Handling and Hot Water Coil Accessory Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Air Handling and Steam Coil Accessory Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Weights And Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
2 Johnson Controls Unitary Products

Nomenclature

505428-YTG-N-0712
Configured Split Condenser Model Number Nomenclature
Product Category
Y = Split System, Condenser, AC, R-410A P = Split System, Condenser, HP, R-410A
Product Identifier
C = Standard Efficiency, 2-Pipe, R-410A D = Standard Efficiency, 4-Pipe, R-410A
Nominal Cooling Capacity - MBH
090 = 7.5 Ton 120 = 10 Ton 150 = 12.5 Ton 180 = 15 Ton 240 = 20 Ton 300 = 25 Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only
YC300
C00 A
2AAA
2
Installation Options
A = None B = Option 1 C = Option 2 D = Options 1 & 2
S = Options 5
T = Options 1 & 5
Options
1 = Disconnect
2 = Non Pwr’d Conv Outlet
5 = Pwr’d Conv Outlet
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Airflow
A = Standard Motor
A
Product Style
A = Style A
Product Generation
1 = First Generation 2 = Second Generation
AA = None AB = Phase Monitor AC = Coil Guard AE = Phase Monitor + Coil Guard EA = ElectroFin Condenser Coil EB = ElectroFin Condenser Coil + Phase Monitor EC = ElectroFin Condenser Coil + Coil Guard EE = ElectroFin Condenser Coil + Coil Guard + Phase Monitor LA = Low Ambient LB = Low Ambient + Phase Monitor LC = Low Ambient + Coil Guard LD = Low Ambient + Phase Monitor + Coil Guard LE = Low Ambient + Technicoat Cond. Coil LF = Low Ambient + Technicoat Cond. Coil + Phase Monitor LG = Low Ambient + Technicoat Cond. Coil + Coil Guard LH = Low Ambient + Technicoat Cond. Coil + Phase Monitor + Coil Guard LJ = Low Ambient + ElectroFin Cond. Coil LK = Low Ambient + ElectroFin Cond. Coil + Phase Monitor LL = Low Ambient + ElectroFin Cond. Coil + Coil Guard LM = Low Ambient + ElectroFin Cond. Coil + Phase Monitor + Coil Guard TA = Technicoat Condenser Coil TB = Technicoat Condenser Coil + Phase Monitor TC = Technicoat Condenser Coil + Coil Guard TE = Technicoat Condenser Coil + Coil Guard + Phase Monitor
Product Options
Configured Split Air Handler Model Number Nomenclature
N = Split System, Air Handler, AC & HP R-410A
C = Standard Efficiency, 2-Pipe, R-410A D = Standard Efficiency, 4-Pipe, R-410A
Nominal Cooling Capacity - MBH
090 = 7-1/2 Ton 120 = 10 Ton 180 = 15 Ton 240 = 20 Ton 300 = 25 Ton
C00 = Cooling Only
B = 1.5 HP Motor C = 2.0 HP Motor D = 3.0 HP Motor E = 5.0 HP Motor F = 7.5 HP Motor N = None (Motor Drive Kit Reg)
1. Motors are not shipped with 25 ton AH units.
Product Category
Product Identifier
Heat Type & Nominal Heat Capacity
Airflow
1
NC240
C00 B
A
6AAA
2
A = Style A
Product Generation
1 = First Generation 2 = Second Generation
Product Options
AA = No Options Installed EJ = ElectroFin Evaporator Coil TJ = Technicoat Evaporator Coil
Installation Options
A = None C = YCCS Ctrl CV Cooling/Elec Ht D = YCCS Ctrl COBP Cooling/Elec Ht E = YCCS Ctrl CV w/H F = YCCS Ctrl COBP w/H
0
2
0
2
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60 6 = 208/230/460-3-60
2. Models NC/ND240 Airflow Option "F" Only.
2
2
Product Style
Johnson Controls Unitary Products 3
505428-YTG-N-0712

Condensing Unit Features and Benefits

Features
• Meets or exceeds ASHRAE 90.1 standards.
• Scroll compressors provide both high efficiency and reliability.
Simplicity
• Dual refrigerant circuits on PD and YD models.
• Condensing unit coils are constructed of reliable and durable Micro-Channel aluminum tube and fins for long lasting, efficient operation. Mirco-Channel technology provides exceptional durability along with reduced product weight and less refrigerant charge. Heat pumps units are equipped with aluminum fin, copper tube coils providing durability, reliability and value.
• Multiple condensing unit and air handler match-ups provide a wide range of application choices from oversized indoor motors to dual indoor units matched­up with single outdoor units.
• Crankcase heaters that de-energize when compressors are operating.
• Both high and low pressure controls. Since these controls are self-contained, there are no capillary lines to be damaged.
• Internal compressor motor protection.
• Class 2, 24-volt thermostat control circuit protected by a re-settable breaker.
• Standard factory installed service valves.
• Filter-driers are shipped in the unit's control box for field installation in the liquid line leaving the outdoor unit.
• Copper stub-outs are factory mounted on the suction and liquid lines to simplify the field piping connections.
Simplicity® Controls provide stable cooling operation at ambient temperatures down to 40°F with low ambient kits available for operation to 0°F.
• Capacity staging for more economical operation and stable temperature levels within the conditioned space.
Simplicity® Controls prevent the unit from cycling on safety control with “Three Outs” technology preventing nuisance trips, but protecting the equipment when valid operational issues are experienced.
Simplicity® Controls monitor each safety independently (High pressure, low pressure, low voltage) allowing ease of troubleshooting if any problems arise.
• Inherently protected condenser fan motors.
• Technicoat or ElectroFin coated outdoor coils for sea coast or corrosive environment applications.
• Factory installed disconnect to allow power to be removed from the unit when performing periodic maintenance or for service.
• Factory installed powered or non-powered 115 volt GFI outlet.
• Factory installed phase monitor to protect the unit from phase loss or phase reversal.
4 Johnson Controls Unitary Products
®
Controls
Benefits
The Predator® condensing units and heat pumps can be applied on a rooftop or at ground level... due to their ample sub-cooling capacity which allows them to be located three or more stories below the evaporator coil.
After assembly, the unit is pressurized with a combination of Refrigerant R-410A and nitrogen for pressure testing and additional leak testing. During this pressure test, the operation of the high pressure control is checked. As the unit is being evacuated and dehydrated, the operation of the low pressure control is also checked.
Every compressor, condenser fan motor, crankcase heater, and electrical control circuit is checked to assure a trouble­free start-up and years of reliable operation. The condenser fan guards are vinyl-coated to provide additional rust protection and to enhance the appearance of the unit. Compressors are mounted on rubber isolators to reduce the transmission of vibration. Vertical discharge condenser fans direct sound upward and away from any surrounding structures.
All sheet metal parts are constructed of commercial grade galvanized steel. After fabrication, each part is thoroughly cleaned to remove any grease or dirt from its surfaces. The external parts are coated with a powder paint to assure a quality finish for many years. This UL approved coating system has passed the 1000 hour, 20% salt spray test per ASTM Standard B117.
All condensing unit and heat pump models include a 5-year limited warranty on the compressor(s) and 1-year limited warranty on all other parts. The matching line of air handling units carries a 1-year limited parts warranty.

Outdoor Unit Accessories

Coil Guards: Wireform coil guards for added protection of outdoor coils. Designed to mount on each side of the product if required to provide protection from minor impacts or large debris.
Hail Guards: Hood type hail guards designed to protect the outdoor coils from hail. Can be installed on a single side or both to provide protection from storms that may produce hail.
Low Ambient Kits: Kits designed to allow the cooling only units to operate between 0°F and 40°F in the cooling mode. Standard cooling is allowed to 40°F. (Not designed for operation on heat pump units).

Air Handling Unit Features and Benefits

Features
These air handlers can be arranged for a variety of air discharge patterns in either the horizontal or vertical position. Refer to the unit installation instructions for other application possibilities.
Benefits
Air handling units are designed with two distinct modules to provide maximum application flexibility. All are shipped as
505428-YTG-N-0712
single packages with the blower module mounted on top of the coil module. The blower module can be repositioned in the field to meet a large number of vertical and horizontal
BAS Control: York Commercial Comfort System (YCCS) provides split system integration for YCCS single zone, change-over bypass and VAV systems.
applications.
Easy Service: Serviceable expansion valves are provided on The 7.5 thru 20 Ton blower module includes the blower wheels along with factory-mounted motor and drive. The 25 Ton blower module includes the blower wheels with field mounted motor and drives. All models offer two motor horsepower options to meet both standard and high static
every unit. These valves are factory-installed to provide many
years of trouble-free operation. If service is required, it is not
necessary to unbraze any joints. The expansion valves also
include a tee fitting to allow easy installation of hot gas
bypass if required. airflow requirements.
Coil Protection: The indoor coils of these air handlers can The coil module includes direct expansion coils, 2 in. throwaway filters with the option to accept 4” filters, liquid line solenoid valves for capacity reduction, thermal expansion valves, distributors and a non-corrosive, composite
have factory applied Technicoat or Electrofin coating to
provide extended life to the indoor coil in standard
applications and additional corrosion protection on those
applications in sea coast or corrosive environments. condensate drain pan.
Accessories
Every air handling coil is pressurized with air and leak tested under water. After the headers are brazed onto the coil and the coil is installed in the unit, the coil is pressurized with nitrogen for pressure testing and additional leak testing. After the coil is evacuated and dehydrated, it is pressurized with a holding charge of nitrogen for storage and/or shipping.
These air handlers, combined with condensing units, provide years of quiet, efficient and dependable operation. These units are manufactured under ISO 9001 Quality System Certification.
Unit Installation
Units may be bottom-supported or ceiling-suspended and can be arranged to meet almost any space or duct requirements. Each unit is available with a choice of blower motors horsepower and other accessories to make them suitable for most applications.
Air Handling units are available in either two or four pipe configurations from 7.5 to 25 tons. The dual and single circuit options provide a wide variety of application and unit match­up possibilities.
Blower Motors: Different HP motors are available for each unit to meet almost any air delivery requirement. All motors are UL approved, have permanently lubricated ball bearings and are mounted within the insulated cabinet of the units to minimize the transmission of sound to the surrounding space.
1.5-5 HP motors are inherently protected. 7.5 HP motors require motor overload protection.
Overload Relay (7.5HP): These blower motors do not have inherent protection and require external motor overload protection. NC/ND240 "F" models Overload Relays are factory installed. NC300 models Overload Relays are field installed. Power wiring for blower motor is supplied in the Overload Relay Kit. See details in Overload Relay Kit and Overload Relay Setting Tables on Page 70.
Factory-Mounted Components
Part Load Operation: These air handlers with DX (Direct Expansion) coils rated at 10 tons of capacity and above have multiple coils with pre-piped distributors, expansion valves and solenoid valves. Field modifications are not required for part load operations. Capacity reduction not only provides
Base Sections: Base sections can be used to elevate units
above the floor. If desired, a moderate percentage of outdoor
air may be introduced through these sections by cutting an
access opening to accommodate the outdoor air duct
connection. These bases include a durable finish to match
the evaporator blower unit. The base may have to be
insulated for certain applications.
Hot Water Coils: Drainable water coils are available for field
installation between the blower and the coil modules of both
horizontal and vertical units. Since their casings match the
dimensions and the finish of the basic units, they become an
integral part of the unit after installation. The coils slide out of
their casings for easy installation. Hot water coils have
copper tubes that have been mechanically expanded into
aluminum fins. Both headers are located on the same end of
the coil. Coils are leak-tested at 325 psig under water and
dried before their connections are capped for storage and
shipping.
Steam Coils: Steam coils are available for installation
between the blower and coil modules of both horizontal and
vertical units. Since the casing matches the dimensions and
the finish of the basic unit, it becomes an integral part of the
unit after installation. The coil slides out of the casings for
easy installation and is pitched in the casings to facilitate
condensate drainage. The coil has copper tubes that have
been mechanically expanded into aluminum fins. Both
headers are located on the same end of the coil. The coil is
leak-tested at 325 psig and dried before the connections are
capped for storage and shipping.
Bottom Return: Air handling unit can be quickly converted to
bottom return for both vertical and horizontal applications. All
that is required is the removal of several screws and a single
panel on 7.5-15 ton and two panels on the 20 ton AHU.
Optional painted panel can be ordered to cover the side
return opening when utilizing the bottom return.
Supply Air Plenums: These fully insulated plenums are
available for free standing units located within the conditioned
space. They are shipped fully assembled for easy field
installation, are finished to match the exterior of the basic
unit, and include double deflection grills that can be adjusted
to vary the throw, spread and drop of the supply air. economical operation, but also maintains stable temperature
and humidity levels in the conditioned space.
Johnson Controls Unitary Products 5
505428-YTG-N-0712

Guide Specifications

Split System Cooling Only Condensing Units Models: YC090-300, YD120-240 & Split System Heat Pump Models: PC090-240, PD180-240
General
• Factory assembled, single piece, air cooled condensing unit designed for outdoor installation.
• Factory wired, piped, and tested for leakage and functionality to assure trouble-free installation and start­up.
• Rated in accordance with AHRI Standard 340/360.
• Manufactured in a facility registered under the ISO 9002 manufacturing quality standard.
• Designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration and comply with NEC.
• Cooling performance rated in accordance with DOE and AHRI test procedures.
• CSA listed and classified to UL 1995/CAN/CSA No. 236- M90 standards.
• One year limited parts warranty on complete unit with an additional four year compressor warranty.
Unit Operating Characteristics
Operating Range shall be between 125° F to 40° F in cooling as standard from factory.
• The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of _____ F. The power consumption at full load shall not exceed _____ kW.
• The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____ Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at _____ F wet bulb and _____ F dry bulb, and air entering the condensing unit at _____F.
• The system shall have an EER of _____ Btuh/ Watt or greater at standard AHRI conditions.
Unit Construction
• Constructed of zinc-coated, galvanized steel.
• Exterior surfaces bonded and coated with baked enamel finish by a powder paint process capable of withstanding a minimum of 1000 salt spray hours according to ASTM B117.
• Cabinet screws that comply with ASTM B117 salt spray test for a minimum of 750 hours.
• Permanently attached heavy-gage perimeter base rails with forklift slots and lifting holes.
• Removable access panels to all internal components.
• Separate access panel to controls.
• Access panels to allow outdoor coil cleaning.
Compressor(s)
• Hermetic scroll type, internally protected with high­pressure relief and over temperature protection.
• Two stage units operate in 50% capacity increments.
• Suction gas cooled
• Voltage range of ±10% of unit nameplate voltage.
• Neoprene isolators minimize sound transmission and vibration.
• Belly-band crankcase heaters keep refrigerant from diluting sump oil.
• Full charge of compressor oil
Outdoor Condenser Unit Coils
• Draw thru configuration
• Constructed with Micro-channel aluminum fins and aluminum tubing. All refrigerant tubing must share a common header.
Heat Pump Unit Outdoor Unit Coils
• Draw thru configuration
• Constructed with aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.
Condenser Fans
Installer Shall
• Furnish York® air-cooled condensing units, heat pump or equivalent in accordance with the performance schedule shown on the plans, and
• Unit shall be stored and handled in accordance with unit manufacturer's instructions.
• Install each unit as shown on the plans in accordance with the manufacturer’s recommendations and all applicable national and local codes
6 Johnson Controls Unitary Products
• Direct driven propeller-type fans
• Statically and dynamically balanced
• Aluminum blades riveted to corrosion resistant steel spider brackets.
• Arranged for vertical air discharge.
• Equipped with PVC coated steel wire safety guards.
505428-YTG-N-0712
Condenser Motors
• Totally enclosed, air over cooled.
• Inherent overload protection.
• Permanently lubricated bearings.
• Must cycle to allow cooling operation down to 40°F.
Refrigerant Piping
• Solid core filter-drier(s) ship loose for field installation.
• Liquid and suction line service valves with gauge ports.
• Suction and discharge line service ports accessible from unit. Ports capped for leak prevention.
• Liquid line magnetic check valves
• Holding charge of R410A refrigerant.
Electrical Requirements
• Single-point connection electrical power.
• Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits of ____ v to _____ v.
• Condenser fan motors and secondary of transformers shall be grounded.
Unit Controls
• All 24-volt control circuit, powered by a 24 volt transformer(s) and protected by a resettable breaker.
• Conventional thermostat must provide operation for both condensing units and heat pumps without an “O” output from the thermostat.
• Low voltage terminal strip for simple hook-up.
• Compressor motor protection shuts down unit for motor over-current, over-temperature or low voltage conditions.
• Safety lockouts provide reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor:
a. Loss-of-charge/Low-pressure switch. b. High-pressure switch. c. Control board diagnostics and fault code display. d. Safety lockouts send a 24 volt signal to the control
board's "X" terminal, allowing notification to the user via the thermostat fault light (if present).
e. Control board shall retain last 5 fault codes in non-
volatile memory, which will not be lost in the event of a power loss. An LED (light-emitting diode) indicator
flashes a fault code that indicates which safety switch has tripped.
Non-fused Disconnect Switch
• Factory-installed, internally mounted.
• Accessible from outside the unit.
• NEC and UL approved non-fused switch.
• Provides power off lockout capability.
Convenience Outlet
• Factory-installed, internally mounted.
• Accessible from outside the unit.
• 115V, 15 amp GFI receptacle with independent fuse protection.
• Required voltage provided by factory-installed step­down transformer or field supplied 115v circuit.
Low-ambient Head Pressure Control
• Standard operation down to 40 °F without a low ambient kit.
• Operation down to 0°F with a field-installed low ambient kit accessory. The controller modulates the fan motor speed in response to liquid line temperature or pressure.
Coil Guard
Factory or field installed decorative grille shall be placed on the units to protect condenser coil after installation.
Hail Guard Package
Field installed hail guard package shall protect coils against damage from hail and other flying debris.
Coated Condenser Coils
Special phenolic or epoxy polymer coating available as a factory option on both outdoor and indoor coils.
Each Unit Shall Be:
• Covered by a 1-year limited parts warranty on the complete unit and 5-year on compressor(s).
• In current production with published literature available to check performance, limitations, specifications, power requirements, dimensions, operation and appearance.
• Indoor unit shall be equipped with a V-belt drive option that will permit the blower RPM to be adjusted to meet the CFM requirements of the air delivery system. (Refer
Johnson Controls Unitary Products 7
505428-YTG-N-0712
Each Unit Enclosure Shall Have:
• Exterior panels of 18 gauge steel, finished with baked enamel to provide a long lasting quality appearance
• Removable panels to provide easy access to the internal components for maintenance and service on condensing units, heat pumps and air handlers
• Air handling units must have a filter rack that accepts both 2” and 4” filters.
• The dimensions of each unit shall not exceed those specified in the manufacture’s literature.
• The minimum application clearances for condensing units, heat pumps and air handlers must meet those specified in the manufacturer’s literature.
The Blower Motor Shall:
• Be mounted within the insulated cabinet to minimize the transmission of sound to the surrounding space, and any motor 7.5 HP or greater must have a service factor of 1.15.
The Evaporator Coil Shall:
• Consist of copper tubes arranged in staggered rows, mechanically expanded into aluminum fins,
• Be draw-through, and
• Include factory-mounted distributors, expansion valves and solenoid valves for capacity reduction.
The Blower Wheels Shall:
Be dynamically balanced to minimize the levels of sound and vibration generated by the unit.
8 Johnson Controls Unitary Products
505428-YTG-N-0712

Physical Data

YC090 - 300 and YD120 - 240 Physical Data
Single
Scroll
Models
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Component
Nominal Tonnage 7.5 10 10 12.5 12.5 15 15 20 20 25
REFRIGERANT
Refrigerant type R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A Holding charge (lb)
Operating Charge (lb)
DIMENSIONS (inches)
Length 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 Width 31.9 31.9 31.9 31.9 31.9 64.1 64.1 64.1 64.1 64.1 Height 44.5 50.0 50.0 50.0 50.0 44.5 44.5 50.0 50.0 50.0
WEIGHTS (lb)
Shipping 390 499 493 499 493 914 899 945 930 945 Operating 387 497 490 497 490 909 894 942 927 942
COMPRESSORS
Type Quantity 1 121212121
Nominal Capacity (Tons)
Capacity Stages
SYSTEM DATA
No. Refrigeration Circuits 1 121212121 Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 3/8 1 1/8 1 5/8 1 3/8 1 5/8 1 3/8 1 5/8 Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 5/8 7/8 5/8 7/8
OUTDOOR COIL DATA
Face area (Sq. Ft.) 23.8 29.0 29.0 29.0 29.0 47.5 47.5 58.1 58.1 58.1 Rows 1 111111111 Fins per inch 23 23 23 23 23 23 23 23 23 23 Tube diameter (in./MM) 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 Circuitry Type 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass Refrigerant Control --- --- --- --- --- --- --- --- --- ---
CONDENSER FAN DATA
No. Fans / Diameter (in.) 2/24 2/24 2/24 2/24 2/24 4/24 4/24 4/24 4/24 4/24 Type Axial Axial Axial Axial Axial Axial Axial Axial Axial Axial Drive type Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct No. speeds 1 111111111
Number of motors Motor HP (ea.) 1/3 3/4 3/4 3/4 3/4 1/3 1/3 3/4 3/4 3/4
4
Rotation RPM 850 1100 1100 1100 1100 850 850 1100 1100 1100
Nominal CFM
1
Holding Charge is the amount in the unit as shipped from the factory.
2
Includes matched indoor blower unit with 25 ft of piping.
3
All compressors include crankcase heaters.
4
When viewing the shaft end of the motor.
1
(each system)
System #1 14.0 18.0 9.9 24.0 11.5 27.0 13.5 33.5 18.8 35
2
System #2 --- --- 9.9 --- 11.5 --- 13.5 --- 18.8 ---
System #1 7.5 10 5 12.5 6.3 15 7.5 20 10 25 System #2 --- --- 5 --- 6.3 --- 7.5 --- 10 --­System #1 1 212121212 System #2 --- --- 1 --- 1 --- 1 --- 1 ---
3
System #1 2 222242424 System #2 --- --- --- --- --- --- 2 --- 2 ---
System #1 7500 9800 9800 9800 9800 15000 7500 19600 9800 19600 System #2 --- --- --- --- --- --- 7500 --- 9800 ---
YC090 YC120 YD120 YC150 YD150 YC180 YD180 YC240 YD240 YC300
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Single Scroll
CW CW CW CW CW CW CW CW CW CW
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Johnson Controls Unitary Products 9
505428-YTG-N-0712
PC090 - 240 and PD180 - 240 Physical Data
Component
PC090 PC120 PC180 PD180 PD240
Nominal Tonnage 7.5 10 15 15 20
REFRIGERANT
Refrigerant type R-410A R-410A R-410A R-410A R-410A Holding charge (lb)
Operating Charge (lb)
1
1.0 1.0 1.0 1.0 1.0
2
System #1 23.9 27.5 54.0 27.0 34.0 System #2 --- --- --- 27.0 34.0
DIMENSIONS (inches)
Length 59.1 59.1 59.1 59.1 59.1 Width 31.9 31.9 64.1 64.1 64.1 Height 44.5 50.0 44.5 44.5 50.0
WEIGHTS (lb)
Shipping 421 543 947 921 1090 Operating 430 574 968 942 1126
COMPRESSORS
3
Type Single Scroll Tandem Scroll Tandem Scroll Single Scroll Single Scroll Quantity 1 1 1 2 2
Cooling
Nominal Capacity (Tons)
Capacity Stages
System #1 7.5 10 15 7.5 10 System #2 --- --- --- 7.5 10 System #1 1 2 2 1 1 System #2 --- --- --- 1 1
Heating
Nominal Capacity (Tons) System #1 & #2 7.5 10 15 15 20 Capacity Stages System #1 & #2 1 1 1 1 1
SYSTEM DATA
No. Refrigeration Circuits 1 1 1 2 2 Suction Line OD (in.) 1 1/8 1 3/8 1 5/8 1 3/8 1 3/8 Liquid Line OD (in.) 5/8 7/8 7/8 5/8 5/8
OUTDOOR COIL DATA
Face area (Sq. Ft.) 23.8 29.0 47.5 47.5 58.1 Rows 2 2 2 2 2 Fins per inch 20 20 20 20 20 Tube diameter (in./MM) 0.38 / 10 0.38 / 10 0.38 / 10 0.38 / 10 0.38 / 10 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Refrigerant Control TXV TXV TXV TXV TXV
CONDENSER FAN DATA
No. Fans / Diameter (in.) 2/24 2/24 4/24 4/24 4/24 Type Axial Axial Axial Axial Axial Drive type Direct Direct Direct Direct Direct No. speeds 1 1 1 1 1
Number of motors Motor HP (ea.) 1/3 3/4 1/3 1/3 3/4
4
Rotation
System #1 2 2 4 2 2 System #2 --- --- --- 2 2
CW CW CW CW CW
RPM 850 1100 850 850 1100 Nominal CFM
1
Holding Charge is the amount in the unit as shipped from the factory.
2
Includes matched evaporator unit with 25 ft of piping.
3
All compressors include crankcase heaters.
4
When viewing the shaft end of the motor.
System #1 7500 9800 15000 7500 9800 System #2 --- --- --- 7500 9800
Models
10 Johnson Controls Unitary Products
505428-YTG-N-0712
NC090 - 240 and ND120 - 240 Indoor Unit Physical Data
Component
Nominal Tonnage 7 1/2 10 10 15 15 20 20
DIMENSIONS (inches)
Length Width Height
WEIGHTS (lb)
Unit Shipping Unit Operating With Standard Motor and Drive High Static Motor and Drive
INDOOR BLOWER (Forward Curve)
Diameter x Width 12 x 12 15 x 15 15 x 15 18 x 18 18 x 18 15 x 15 15 x 15 Quantity 1 111122
INDOOR COIL
Face area (Sq. Ft.) 10.6 10.6 10.6 18.3 18.3 20.0 20.0 Rows 3 443444 Fins per inch 15 15 15 15 15 15 15 Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Refrigerant Control TXV TXV TXV TXV TXV TXV TXV
SYSTEM DATA
No. Refrigeration Circuits 1 121212 Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 5/8 1 3/8 1 5/8 1 3/8 Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 7/8
FILTERS
Size and Quantity Per Model (In.)
FACE AREA (SQ. FT.) 11.1 11.1 11.1 20.0 20.0 22.2 22.2
Size and Quantity Per Model (In.)
FACE AREA (SQ. FT.) 11.1 11.1 11.1 18.0 18.0 22.2 22.2
16 x 25 x 2 4 4 4 --- --- 8 8 20 x 24 x 2 --- --- --- 6 6 --- ---
16 x 25 x 4 4 4 4 --- --- 8 8 20 x 24 x 4 --- --- --- 6 6 --- ---
NC090 NC120 ND120 NC180 ND180 NC240 ND240
56.0 56.0 56.0 74.5 74.5 98.5 98.5
30.0 30.0 30.0 33.0 33.0 30.0 30.0
65.0 65.0 65.0 75.0 75.0 65.0 65.0
526 573 575 796 796 938 938
498 539 541 764 764 873 873 500 550 552 792 792 903 903
Models
Johnson Controls Unitary Products 11
505428-YTG-N-0712
NC300 Indoor Unit Physical Data
Component
Nominal Tonnage 25
DIMENSIONS (inches)
Length Width Height
WEIGHTS
Unit Shipping Unit Operating With 5 hp Motor and Drive
7.5 hp Motor and Drive
INDOOR BLOWER (Forward Curve)
Diameter x Width 18 X 18 Quantity 2
INDOOR COIL
Face area (Sq. Ft.) 25.8 Rows 4 Fins per inch 16 Tube diameter 3/8 Circuitry Type Interlaced Refrigerant Control TEV
SYSTEM DATA
No. Refrigeration Circuits 1 Suction Line OD (in.) 2 1/8 Liquid Line OD (in.) 7/8
Size and Quantity Per
Model (In.)
FACE AREA (SQ. FT.) 34.7
ACCESSORY
HOT WATER COIL DATA
Face area (Sq. Ft.) 21.2 Rows 2 Fins per inch 12 Tube diameter (Copper) OD (In.) 1/2 Connections (Supply and Return) OD (In.) 1 3/8 Weight (lb) 150
SYSTEM COIL DATA
Face area (Sq. Ft.) 18.2 Rows 1 Fins per inch 8 Tube diameter (Copper) (In.) 1 Connection, (NPTE) (In.) Inlet 2 Outlet 1-1/2 Weight (lb) 160
1
Motors, Drive and Overload Kits must be
FILTERS
1
(lb)
20 x 25 x 2 10
ordered separately for the NC300. The Motor Drive and Overload Kits are to be field installed.
Models
NC300
100.1
38.1
74.6
1067
1130 1157
12 Johnson Controls Unitary Products

Unit Limitations

Condenser Unit limitations
Outdoor DB Temp
Size
(Tons)
090
(7.5)
090
(7.5)
120 (10)
120 (10)
150
(12.5)
180 (15)
180 (15)
240 (20)
240 (20)
300 (25)
Model
PC
YC
PC
YC/YD
YC/YD
PC/PD
YC/YD
PC/PD
YC/YD
YC
Unit Voltage
Applied Voltage
Min Max Max Min
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
1
Cooling (°F)
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
1. Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage. †. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.
Indoor DB Temp
Cooling (°F)
Max Min Max Min Max Min
Outdoor DB Temp
Heating (°F)
505428-YTG-N-0712
Indoor DB Temp
Heating (°F)
Johnson Controls Unitary Products 13
505428-YTG-N-0712
Air Handling Unit Limitations
Entering Air Temperature Degrees °F
Model Power Supply Voltage
Voltage Variation Supply Air Range CFM
Cooling DB/WB
Min. Max. Min. Max. Min. Max. Min. Max.
208/230-3-60 187 253 2,250 3,750 65/57 90/77 40 80
NC090
460-3-60 414 506 2,250 3,750 65/57 90/77 40 80 575-3-60 540 630 2,250 3,750 65/57 90/77 40 80
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
NC120
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80 575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
ND120
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80 575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
NC180
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80 575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
ND180
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80 575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
NC240
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80 575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
ND240
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80 575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
208/230-3-60 187 253 8,000 12,000 65/57 90/77 40 80
NC300
460-3-60 414 506 8,000 12,000 65/57 90/77 40 80 575-3-60 540 630 8,000 12,000 65/57 90/77 40 80
1
Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.
Heating DB
1
14 Johnson Controls Unitary Products
505428-YTG-N-0712

Cooling and Heating Ratings

Cooling And Heating Rating
Condensing Unit Only
Outdoor Unit
PC090 PC120 PC180 PD180 PD240
YC090 85 6.8 12.4 NC090 94 11.2 13.0 --- N/A N/A N/A N/A 3000 YC090 85 6.8 12.4 NC120 99 11.9 13.0 --- N/A N/A N/A N/A 3000 YC120 110 9.3 11.9 NC120 124 11.4 12.5 12.9 N/A N/A N/A N/A 4000 YD120 108 9.1 11.8 ND120 124 11.2 11.2 11.6 N/A N/A N/A N/A 4000 YC150 133 11.6 11.5 NC180 150 11.0 13.3 13.8 N/A N/A N/A N/A 5000 YD150 136 11.5 11.8 ND180 150 11.0 12.1 12.3 N/A N/A N/A N/A 5000 YC180 160 13.4 12.0 NC180 181 11.2 12.2 12.5 N/A N/A N/A N/A 6000 YC180 160 13.4 12.0 NC240 190 11.7 12.7 12.5 N/A N/A N/A N/A 6000 YD180 166 12.3 13.4 ND180 181 11.2 11.6 12.4 N/A N/A N/A N/A 6000 YD180 166 12.3 13.4 (2)NC090 187 11.2 -- -- N/A N/A N/A N/A 6000 YD180 166 12.3 13.4 (2)NC120 187 11.2 -- -- N/A N/A N/A N/A 6000 YD180 166 12.3 13.4 ND240 190 11.7 13.4 11.2 N/A N/A N/A N/A 6000 YC240 233 17.5 13.2 NC240 242 11.3 13.6 13.1 N/A N/A N/A N/A 8000 YD240 222 17.3 12.8 ND240 242 11.3 11.9 12.6 N/A N/A N/A N/A 8000 YD240 222 17.3 12.8 (2)NC120 240 11.6 -- -- N/A N/A N/A N/A 8000 YC300 271 23.7 11.4 NC300 299 10.2 12.2 -- N/A N/A N/A N/A 10000
1
Certified in accordance with the Unitary Large Equipment certification program, which is based on AHRI Standard 340/360. (Except YC300)
2
Condensing unit only ratings are at 45°F SST and 95°F entering-air temperature.
3
Gross capacity does not include heat added by blower motor. Refer to appropriate table for blower horsepower.
4
Heat Pumps designed for matched systems only.
4
4 4 4 4
Gross Capacity
(MBH)
2
KW EER
N/A N/A N/A NC090 92 11.0 11.4 --- 82 3.3 49 2.3 3000 N/A N/A N/A NC120 124 11.0 11.4 11.8 109 3.3 63 2.1 4000 N/A N/A N/A NC180 180 10.6 11.5 12.4 168 3.3 104 2.3 6000 N/A N/A N/A ND180 180 10.6 11.5 12.0 168 3.4 103 2.4 6000 N/A N/A N/A ND240 238 10.6 11.7 12.1 220 3.4 124 2.2 8000
Indoor
Unit
System Cooling Capacity
Gross Capacity
(MBH)
3
EER IEER IPLV
1
Capacity
Heating Capacity High Outdoor Low Outdoor Gross
2
(MBh)
COP
Gross
Capacity
(MBh)
1
2
COP
Rated
Airflow
(CFM)
LEGEND EER = Energy Efficiency Ratio AHRI = Air Conditioning and Refrigeration Institute IPLV = Integration Part-Load Value IEER = Integrated Energy Efficiency Ratio
Johnson Controls Unitary Products 15
505428-YTG-N-0712

Capacity Performance

Condenser and Air Handling Cooling Capacities YC090/NC090
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
WB (°F)
Total
Capacity
(MBh)
77 110.8 6.0 51.5 42.0 32.6 - - - 107.2 6.5 49.8 40.4 30.9 - - ­72 103.3 5.7 66.5 57.0 47.6 38.1 - - 99.9 6.3 64.9 55.4 46.0 36.5 - ­67 95.9 5.5 81.5 72.0 62.6 53.1 43.6 - 92.6 6.2 80.0 70.5 61.0 51.6 42.1 ­62 88.0 5.4 88.0 86.3 76.8 67.3 57.8 48.3 84.8 6.1 84.8 83.9 74.5 65.0 55.5 46.1 57 77.7 5.2 77.7 77.7 72.2 62.8 53.3 43.8 80.1 6.0 80.1 80.1 73.1 63.6 54.2 44.7 77 114.0 6.0 56.3 45.6 34.8 - - - 110.2 6.5 54.6 44.0 33.3 - - ­72 106.3 5.7 72.3 61.6 50.9 40.1 - - 102.7 6.3 70.8 60.2 49.6 38.9 - ­67 98.7 5.4 88.4 77.6 66.9 56.2 45.5 - 95.2 6.2 87.1 76.4 65.8 55.2 44.5 ­62 90.6 5.4 90.6 89.7 82.2 71.9 60.7 50.0 87.1 6.1 87.1 86.7 80.3 69.6 59.0 48.3 57 79.9 5.2 79.9 79.9 77.2 67.3 55.8 45.0 82.3 6.0 82.3 82.3 78.8 68.2 57.5 46.9 77 117.2 5.9 61.0 49.1 37.1 - - - 113.1 6.5 59.4 47.5 35.7 - - ­72 109.3 5.7 78.1 66.2 54.2 42.2 - - 105.4 6.4 76.8 65.0 53.1 41.3 - ­67 101.4 5.4 95.2 83.2 71.3 59.3 47.3 - 97.7 6.2 94.2 82.4 70.5 58.7 46.9 ­62 93.1 5.4 93.1 93.1 87.5 76.5 63.6 51.6 89.5 6.1 89.5 89.5 86.1 74.2 62.4 50.6 57 82.2 5.2 82.2 82.2 82.2 71.7 58.3 46.3 84.5 6.0 84.5 84.5 84.5 72.7 60.8 49.0 72 109.2 5.8 83.0 70.2 57.3 44.4 - - 105.4 6.4 81.6 68.8 56.0 43.2 - ­67 101.3 5.5 98.2 88.2 75.3 62.5 49.6 - 97.7 6.3 96.0 87.2 74.3 61.5 48.7 ­62 93.0 5.5 93.0 93.0 90.2 77.8 64.5 51.6 89.5 6.2 89.5 89.5 87.8 75.0 62.1 49.3 57 82.1 5.3 82.1 82.1 82.1 70.0 56.4 43.5 84.5 6.1 84.5 84.5 84.5 71.7 58.9 46.0 72 109.1 5.9 87.9 74.2 60.4 46.6 - - 105.5 6.5 86.5 72.6 58.8 45.0 - ­67 101.2 5.6 101.2 93.2 79.4 65.7 51.9 - 97.8 6.3 97.8 91.9 78.1 64.3 50.5 ­62 92.9 5.6 92.9 92.9 92.9 79.1 65.3 51.6 89.5 6.2 89.5 89.5 89.5 75.7 61.9 48.1 57 82.0 5.4 82.0 82.0 82.0 68.2 54.4 40.7 84.5 6.1 84.5 84.5 84.5 70.7 56.9 43.1
77 103.7 6.9 48.1 38.7 29.2 - - - 99.2 8.0 47.5 38.1 28.6 - - ­72 96.5 6.9 63.3 53.8 44.4 35.0 - - 92.2 8.0 62.1 52.6 43.2 33.7 - ­67 89.4 6.9 78.4 69.0 59.5 50.1 40.7 - 85.2 8.0 76.6 67.2 57.7 48.3 38.8 ­62 81.6 6.7 81.6 81.6 72.1 62.7 53.3 43.8 77.9 7.7 77.9 77.9 69.2 59.7 50.3 40.9 57 82.5 6.7 82.5 82.5 74.0 64.5 55.1 45.7 78.8 7.8 78.8 78.8 70.0 60.5 51.1 41.6 77 106.4 7.0 52.9 42.3 31.8 - - - 101.7 8.1 53.5 41.7 31.1 - - ­72 99.0 7.0 69.4 58.8 48.2 37.7 - - 94.5 8.1 68.1 57.5 46.9 36.3 - ­67 91.7 6.9 85.8 75.3 64.7 54.1 43.6 - 87.3 8.0 82.8 73.3 62.7 52.1 41.5 ­62 83.7 6.8 83.7 83.7 78.4 67.3 57.2 46.7 79.9 7.8 79.9 79.9 75.2 64.4 54.0 43.4 57 84.6 6.7 84.6 84.6 80.4 69.1 59.2 48.7 80.7 7.9 80.7 80.7 76.1 65.1 54.8 44.2 77 109.0 7.1 57.7 46.0 34.3 - - - 104.1 8.1 59.4 45.4 33.6 - - ­72 101.5 7.0 75.5 63.8 52.1 40.4 - - 96.8 8.1 74.2 62.5 50.7 38.9 - ­67 94.0 7.0 93.3 81.5 69.8 58.1 46.4 - 89.4 8.1 89.0 79.5 67.8 56.0 44.3 ­62 85.8 6.8 85.8 85.8 84.6 72.0 61.2 49.5 81.8 7.9 81.8 81.8 81.2 69.0 57.7 46.0 57 86.8 6.8 86.8 86.8 86.8 73.6 63.4 51.7 82.7 7.9 82.7 82.7 82.1 69.6 58.6 46.9 72 101.7 7.1 80.2 67.5 54.7 41.9 - - 96.9 8.1 79.2 66.3 53.5 40.7 - ­67 94.2 7.0 93.8 86.1 73.3 60.5 47.7 - 89.5 8.1 89.4 83.7 71.5 58.7 45.8 ­62 86.0 6.8 86.0 86.0 85.4 72.1 59.8 47.0 82.0 7.9 82.0 82.0 81.7 68.6 56.0 43.2 57 86.9 6.8 86.9 86.9 86.9 73.4 61.4 48.6 82.8 7.9 82.8 82.8 82.6 69.3 56.9 44.1 72 101.9 7.1 85.0 71.1 57.3 43.4 - - 97.1 8.1 84.1 70.2 56.3 42.4 - ­67 94.3 7.0 94.3 90.7 76.8 62.9 49.1 - 89.7 8.1 89.7 87.9 75.3 61.4 47.4 ­62 86.1 6.9 86.1 86.1 86.1 72.3 58.4 44.5 82.1 7.9 82.1 82.1 82.1 68.2 54.3 40.4 57 87.1 6.9 87.1 87.1 87.1 73.2 59.4 45.5 83.0 7.9 83.0 83.0 83.0 69.1 55.2 41.2
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
16 Johnson Controls Unitary Products
505428-YTG-N-0712
YC090/NC090 (Continued)
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
WB
(°F)
77 94.7 9.0 46.9 37.5 28.0 - - - 90.2 10.1 46.3 36.9 27.4 - - ­72 87.8 9.1 60.9 51.4 42.0 32.5 - - 83.4 10.2 59.7 50.2 40.8 31.3 - ­67 80.9 9.1 74.8 65.4 55.9 46.5 37.0 - 76.7 10.3 73.0 63.6 54.1 44.6 35.2 ­62 74.3 8.8 74.3 74.3 66.2 56.8 47.3 37.9 70.6 9.9 70.6 70.6 63.3 53.8 44.3 34.9 57 75.0 8.9 75.0 75.0 66.0 56.5 47.0 37.6 71.3 10.0 71.3 71.3 61.9 52.5 43.0 33.5 77 97.0 9.1 54.0 41.1 30.5 - - - 92.3 10.1 54.6 40.5 29.8 - - ­72 89.9 9.1 66.9 56.3 45.6 35.0 - - 85.3 10.2 65.7 55.0 44.3 33.7 - ­67 82.8 9.2 79.8 71.4 60.8 50.2 39.5 - 78.4 10.3 76.8 69.5 58.9 48.2 37.5 ­62 76.1 8.8 76.1 76.1 72.0 61.4 50.8 40.1 72.2 9.9 72.2 72.2 68.9 58.4 47.5 36.9 57 76.8 9.0 76.8 76.8 71.7 61.1 50.5 39.8 72.9 10.1 72.9 72.9 67.4 57.1 46.1 35.4 77 99.2 9.1 61.1 44.7 32.9 - - - 94.3 10.2 62.8 44.1 32.2 - - ­72 92.0 9.2 72.9 61.1 49.3 37.5 - - 87.2 10.3 71.7 59.8 47.9 36.1 - ­67 84.8 9.2 84.8 77.5 65.7 53.9 42.1 - 80.2 10.3 80.2 75.5 63.6 51.8 39.9 ­62 77.8 8.9 77.8 77.8 77.8 66.0 54.2 42.4 73.8 9.9 73.8 73.8 73.8 63.0 50.7 38.8 57 78.6 9.0 78.6 78.6 77.5 65.7 53.9 42.1 74.5 10.1 74.5 74.5 72.9 61.8 49.1 37.3 72 92.2 9.2 78.1 65.2 52.3 39.4 - - 87.4 10.2 77.0 64.1 51.2 38.2 - ­67 84.9 9.2 84.9 81.3 69.7 56.8 44.0 - 80.3 10.3 80.3 78.9 67.9 55.0 42.1 ­62 78.0 8.9 78.0 78.0 78.0 65.1 52.2 39.3 74.0 9.9 74.0 74.0 74.0 61.5 48.4 35.4 57 78.7 9.0 78.7 78.7 78.2 65.3 52.4 39.5 74.6 10.1 74.6 74.6 73.8 61.3 47.9 35.0 72 92.3 9.1 83.3 69.3 55.4 41.4 - - 87.5 10.2 82.4 68.4 54.4 40.4 - ­67 85.1 9.2 85.1 85.1 73.8 59.8 45.8 - 80.4 10.3 80.4 80.4 72.2 58.2 44.2 ­62 78.1 8.9 78.1 78.1 78.1 64.1 50.2 36.2 74.1 9.9 74.1 74.1 74.1 60.1 46.1 32.1 57 78.9 9.0 78.9 78.9 78.9 64.9 51.0 37.0 74.8 10.0 74.8 74.8 74.8 60.8 46.8 32.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 17
505428-YTG-N-0712
YC090/NC120
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
Total WB (°F)
77 105.1 6.0 49.2 40.2 31.1 - - - 108.2 6.6 50.3 41.2 32.1 - - ­72 100.1 5.8 63.3 54.2 45.1 36.0 - - 101.4 6.5 63.6 54.6 45.5 36.4 - ­67 95.1 5.7 77.3 68.2 59.1 50.0 40.9 - 94.6 6.3 77.0 67.9 58.8 49.7 40.7 ­62 87.9 5.6 87.9 80.9 71.8 62.7 53.7 44.6 87.7 6.2 87.7 80.9 71.8 62.7 53.7 44.6 57 83.1 5.5 83.1 83.1 76.8 67.7 58.6 49.5 84.1 6.2 84.1 84.1 77.2 68.2 59.1 50.0 77 109.8 6.0 53.6 43.4 33.2 - - - 112.0 6.7 54.5 44.3 34.1 - - ­72 104.5 5.9 68.6 58.3 48.1 37.9 - - 105.0 6.5 68.6 58.4 48.3 38.1 - ­67 99.3 5.7 83.5 73.3 63.1 52.9 42.6 - 97.9 6.4 82.8 72.6 62.4 52.2 42.1 ­62 91.8 5.6 91.8 86.9 76.7 66.8 56.2 46.0 90.7 6.2 90.7 86.4 76.2 66.0 55.8 45.7 57 86.7 5.6 86.7 86.7 82.0 72.3 61.5 51.3 87.1 6.2 87.1 87.1 82.0 71.8 61.6 51.4 77 114.5 6.1 58.0 46.6 35.3 - - - 115.8 6.7 58.7 47.4 36.1 - - ­72 109.0 5.9 73.9 62.5 51.2 39.8 - - 108.5 6.6 73.6 62.3 51.1 39.8 - ­67 103.5 5.8 89.8 78.4 67.1 55.7 44.4 - 101.2 6.4 88.6 77.3 66.0 54.7 43.4 ­62 95.7 5.7 95.7 92.9 81.5 70.8 58.8 47.5 93.8 6.3 93.8 91.9 80.6 69.3 58.0 46.7 57 90.4 5.6 90.4 90.4 87.1 76.9 64.4 53.1 90.0 6.3 90.0 90.0 86.7 75.4 64.1 52.8 72 110.2 6.0 77.6 65.3 53.1 40.8 - - 110.3 6.6 77.7 65.4 53.2 40.9 - ­67 104.6 5.8 94.1 81.8 69.5 57.3 45.0 - 102.9 6.5 93.3 81.0 68.8 56.5 44.3 ­62 96.7 5.7 96.7 95.3 84.5 72.6 60.0 47.7 95.3 6.3 95.3 94.4 84.0 71.7 59.5 47.2 57 91.4 5.6 91.4 91.4 89.8 78.0 65.2 53.0 91.5 6.3 91.5 91.5 89.8 77.6 65.3 53.1 72 111.4 6.0 81.3 68.1 54.9 41.8 - - 112.1 6.6 81.7 68.5 55.3 42.1 - ­67 105.8 5.9 98.4 85.2 72.0 58.8 45.6 - 104.5 6.5 97.9 84.7 71.5 58.3 45.1 ­62 97.8 5.7 97.8 97.8 87.5 74.3 61.1 47.9 96.8 6.4 96.8 96.8 87.3 74.1 60.9 47.7 57 92.4 5.7 92.4 92.4 92.4 79.2 66.0 52.8 93.0 6.3 93.0 93.0 93.0 79.8 66.6 53.4
77 111.4 7.2 51.3 42.3 33.2 - - - 107.2 8.2 49.9 40.9 31.8 - - ­72 102.8 7.1 64.0 54.9 45.9 36.8 - - 99.1 8.0 62.6 53.5 44.5 35.4 - ­67 94.2 7.0 76.7 67.6 58.5 49.5 40.4 - 90.9 7.9 75.3 66.2 57.1 48.1 39.0 ­62 87.4 6.8 87.4 80.9 71.8 62.7 53.6 44.6 84.0 7.8 84.0 79.3 70.2 61.1 52.0 43.0 57 85.2 6.8 85.2 85.2 77.7 68.6 59.6 50.5 82.3 7.7 82.3 82.3 74.9 65.8 56.8 47.7 77 114.2 7.3 55.3 45.2 35.0 - - - 110.2 8.3 53.9 43.8 33.6 - - ­72 105.4 7.2 68.7 58.5 48.4 38.2 - - 101.8 8.1 67.4 57.2 47.0 36.9 - ­67 96.6 7.0 82.1 71.9 61.8 51.6 41.5 - 93.4 8.0 80.8 70.6 60.5 50.3 40.1 ­62 89.6 6.9 89.6 85.9 75.8 65.3 55.5 45.3 86.3 7.9 86.3 83.7 74.3 63.9 53.9 43.8 57 87.4 6.8 87.4 87.4 82.0 71.3 61.7 51.6 84.6 7.8 84.6 84.6 79.3 68.8 58.9 48.8 77 117.1 7.3 59.3 48.1 36.9 - - - 113.1 8.3 58.0 46.7 35.5 - - ­72 108.0 7.2 73.4 62.2 50.9 39.7 - - 104.5 8.2 72.1 60.9 49.6 38.4 - ­67 99.0 7.1 87.5 76.2 65.0 53.8 42.5 - 95.9 8.1 86.3 75.0 63.8 52.5 41.3 ­62 91.9 6.9 91.9 91.0 79.7 67.9 57.3 46.0 88.6 7.9 88.6 88.2 78.3 66.8 55.8 44.6 57 89.6 6.9 89.6 89.6 86.3 74.0 63.8 52.6 86.9 7.8 86.9 86.9 83.6 71.8 61.1 49.8 72 110.4 7.2 77.7 65.5 53.3 41.1 - - 106.7 8.2 76.4 64.2 52.0 39.7 - ­67 101.2 7.1 92.5 80.2 68.0 55.8 43.6 - 97.9 8.1 91.3 79.0 66.8 54.6 42.3 ­62 93.9 7.0 93.9 93.4 83.4 70.9 59.0 46.8 90.5 8.0 90.5 90.3 82.0 69.7 57.6 45.3 57 91.5 6.9 91.5 91.5 89.9 77.1 65.5 53.2 88.7 7.9 88.7 88.7 87.1 74.6 62.6 50.4 72 112.8 7.3 82.1 68.9 55.7 42.4 - - 108.9 8.3 80.8 67.6 54.3 41.1 - ­67 103.3 7.1 97.4 84.2 71.0 57.8 44.6 - 100.0 8.1 96.3 83.0 69.8 56.6 43.4 ­62 95.9 7.0 95.9 95.9 87.1 73.9 60.7 47.5 92.4 8.0 92.4 92.4 85.8 72.5 59.3 46.1 57 93.5 6.9 93.5 93.5 93.5 80.3 67.1 53.9 90.5 7.9 90.5 90.5 90.5 77.3 64.1 50.9
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input (kW)
Sensible Capacity (MBh)
2
18 Johnson Controls Unitary Products
505428-YTG-N-0712
YC090/NC120 (Continued)
Air on
Evaporator Coil
CFM
2250
2625
3000
3375
3750
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
WB
(°F)
77 103.1 9.1 48.5 39.5 30.4 - - - 98.9 10.1 47.1 38.0 29.0 - - ­72 95.4 9.0 61.2 52.1 43.1 34.0 - - 91.6 9.9 59.8 50.7 41.7 32.6 - ­67 87.6 8.9 73.9 64.8 55.8 46.7 37.6 - 84.4 9.8 72.5 63.4 54.4 45.3 36.2 ­62 80.6 8.7 80.6 77.7 68.6 59.5 50.4 41.4 77.2 9.7 77.2 76.0 67.0 57.9 48.8 39.8 57 79.5 8.6 79.5 79.5 72.1 63.0 54.0 44.9 76.6 9.5 76.6 76.6 69.3 60.2 51.2 42.1 77 106.1 9.2 52.6 42.4 32.2 - - - 102.1 10.2 51.2 41.0 30.8 - - ­72 98.2 9.1 66.0 55.9 45.7 35.5 - - 94.6 10.1 64.7 54.5 44.3 34.2 - ­67 90.3 9.0 79.5 69.3 59.1 49.0 38.8 - 87.1 9.9 78.2 68.0 57.8 47.7 37.5 ­62 83.0 8.8 83.0 81.5 72.8 62.6 52.4 42.3 79.7 9.8 79.7 79.3 71.2 61.2 50.9 40.7 57 81.8 8.7 81.8 81.8 76.5 66.3 56.2 46.0 79.0 9.6 79.0 79.0 73.7 63.8 53.4 43.2 77 109.2 9.3 56.6 45.3 34.1 - - - 105.3 10.3 55.2 44.0 32.7 - - ­72 101.0 9.2 70.8 59.6 48.3 37.0 - - 97.5 10.2 69.5 58.3 47.0 35.7 - ­67 92.9 9.1 85.1 73.8 62.5 51.3 40.0 - 89.8 10.1 83.9 72.6 61.3 50.0 38.7 ­62 85.4 8.9 85.4 85.4 76.9 65.7 54.4 43.1 82.2 10.0 82.2 82.2 75.5 64.5 53.0 41.7 57 84.2 8.8 84.2 84.2 80.9 69.6 58.4 47.1 81.5 9.8 81.5 81.5 78.2 67.4 55.6 44.3 72 103.1 9.2 75.2 62.9 50.7 38.4 - - 99.4 10.2 73.9 61.6 49.3 37.1 - ­67 94.7 9.1 90.1 77.8 65.6 53.3 41.1 - 91.5 10.1 88.9 76.6 64.4 52.1 39.8 ­62 87.1 9.0 87.1 87.1 80.7 68.4 56.2 43.9 83.7 10.0 83.7 83.7 79.3 67.2 54.7 42.5 57 85.9 8.8 85.9 85.9 84.2 72.0 59.7 47.5 83.0 9.8 83.0 83.0 81.4 69.4 56.8 44.6 72 105.1 9.2 79.5 66.2 53.0 39.8 - - 101.3 10.2 78.2 64.9 51.7 38.4 - ­67 96.6 9.1 95.1 81.9 68.6 55.4 42.1 - 93.2 10.1 93.2 80.7 67.4 54.2 40.9 ­62 88.8 9.0 88.8 88.8 84.4 71.2 57.9 44.7 85.3 10.0 85.3 85.3 83.1 69.8 56.5 43.3 57 87.6 8.8 87.6 87.6 87.6 74.3 61.1 47.8 84.6 9.8 84.6 84.6 84.6 71.3 58.1 44.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 19
505428-YTG-N-0712
YC120/NC120
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
WB (°F)
77 142.3 7.5 64.7 52.6 40.5 - - - 139.4 8.5 67.1 54.6 42.1 - - ­72 133.9 7.4 84.4 72.2 60.1 48.0 - - 129.5 8.4 85.3 72.8 60.3 47.8 - ­67 125.5 7.3 104.0 91.9 79.8 67.7 55.6 - 119.6 8.3 103.4 90.9 78.5 66.0 53.5 ­62 115.0 7.3 115.0 109.5 94.2 82.0 69.9 57.8 111.3 8.2 111.3 108.6 96.1 83.6 71.1 58.6 57 111.2 7.2 111.2 111.2 99.9 87.8 75.7 63.6 108.8 8.3 108.8 108.8 99.2 86.7 74.2 61.7 77 151.4 7.5 72.3 58.7 45.2 - - - 147.0 8.5 74.2 60.2 46.1 - - ­72 142.4 7.4 94.1 80.6 67.0 53.5 - - 136.6 8.4 94.1 80.0 66.0 51.9 - ­67 133.4 7.3 116.0 102.5 88.9 75.4 61.8 - 126.1 8.3 114.0 99.9 85.9 71.8 57.8 ­62 122.3 7.3 122.3 119.6 105.0 92.1 77.9 64.4 117.4 8.3 117.4 116.1 105.2 91.1 77.1 63.1 57 118.3 7.2 118.3 118.3 111.3 98.6 84.2 70.7 114.8 8.3 114.8 114.8 108.6 94.6 80.5 66.5 77 160.5 7.5 79.8 64.9 49.9 - - - 154.6 8.6 81.3 65.7 50.1 - - ­72 150.9 7.4 103.9 88.9 73.9 59.0 - - 143.7 8.5 102.9 87.3 71.7 56.1 - ­67 141.4 7.3 128.0 113.0 98.0 83.0 68.1 - 132.7 8.4 124.5 108.9 93.3 77.7 62.1 ­62 129.6 7.3 129.6 129.6 115.9 102.2 86.0 71.0 123.5 8.3 123.5 123.5 114.3 98.7 83.1 67.5 57 125.4 7.2 125.4 125.4 122.8 109.5 92.8 77.8 120.7 8.3 120.7 120.7 118.0 102.4 86.8 71.2 72 154.4 7.5 110.8 94.3 77.8 61.4 - - 148.2 8.5 110.7 93.7 76.6 59.6 - ­67 144.7 7.4 138.0 119.7 103.2 86.8 70.3 - 136.9 8.4 132.8 116.7 99.7 82.6 65.6 ­62 132.6 7.3 132.6 132.6 124.4 108.6 91.5 75.0 127.4 8.3 127.4 127.4 122.1 105.1 88.0 70.9 57 128.3 7.3 128.3 128.3 127.0 111.4 94.0 77.6 124.6 8.3 124.6 124.6 123.2 106.1 89.1 72.0 72 157.9 7.5 117.6 99.7 81.7 63.8 - - 152.7 8.5 118.6 100.0 81.5 63.0 - ­67 148.0 7.4 148.0 126.4 108.5 90.5 72.6 - 141.1 8.4 141.1 124.6 106.1 87.6 69.1 ­62 135.6 7.3 135.6 135.6 132.9 114.9 97.0 79.1 131.3 8.3 131.3 131.3 129.9 111.4 92.9 74.4 57 131.2 7.3 131.2 131.2 131.2 113.2 95.3 77.4 128.4 8.4 128.4 128.4 128.4 109.9 91.4 72.8
77 136.4 9.5 69.6 56.7 43.8 - - - 127.0 10.7 66.5 53.5 40.6 - - ­72 125.1 9.4 86.2 73.3 60.5 47.6 - - 117.1 10.7 83.6 70.6 57.7 44.8 - ­67 113.7 9.3 102.9 90.0 77.1 64.2 51.3 - 107.2 10.6 100.7 87.8 74.8 61.9 48.9 ­62 107.7 9.2 107.7 107.7 98.1 85.2 72.3 59.4 100.8 10.5 100.8 100.8 93.7 80.8 67.9 54.9 57 106.5 9.3 106.5 106.5 98.6 85.7 72.8 59.9 100.2 10.6 100.2 100.2 91.6 78.7 65.8 52.8 77 142.6 9.5 76.1 61.6 47.1 - - - 133.4 10.8 75.3 58.7 44.1 - - ­72 130.7 9.4 94.0 79.5 64.9 50.4 - - 123.1 10.7 92.0 77.3 62.7 48.1 - ­67 118.9 9.4 111.9 97.4 82.8 68.3 53.7 - 112.7 10.6 108.7 96.0 81.3 66.7 52.0 ­62 112.6 9.2 112.6 112.6 105.3 90.2 76.3 61.7 106.0 10.5 106.0 106.0 101.9 86.9 72.6 57.9 57 111.3 9.4 111.3 111.3 105.9 90.5 76.8 62.3 105.3 10.6 105.3 105.3 99.5 84.5 70.3 55.6 77 148.8 9.6 82.7 66.5 50.3 - - - 139.9 10.8 84.1 63.9 47.6 - - ­72 136.4 9.5 101.8 85.6 69.4 53.2 - - 129.0 10.7 100.4 84.0 67.7 51.3 - ­67 124.0 9.4 120.9 104.7 88.5 72.3 56.1 - 118.2 10.6 116.6 104.1 87.8 71.5 55.1 ­62 117.4 9.2 117.4 117.4 112.6 95.1 80.2 64.0 111.1 10.5 111.1 111.1 110.0 93.0 77.3 60.9 57 116.1 9.4 116.1 116.1 113.2 95.3 80.8 64.6 110.5 10.6 110.5 110.5 107.4 90.2 74.7 58.4 72 142.0 9.5 110.7 93.0 75.4 57.7 - - 133.3 10.7 109.1 91.2 73.2 55.2 - ­67 129.1 9.4 127.5 113.8 96.1 78.5 60.8 - 122.1 10.6 121.3 112.3 95.0 77.0 59.0 ­62 122.2 9.3 122.2 122.2 119.8 101.5 84.5 66.9 114.8 10.5 114.8 114.8 114.3 96.0 78.3 60.4 57 120.8 9.4 120.8 120.8 119.4 100.9 84.1 66.4 114.1 10.6 114.1 114.1 112.6 94.2 76.7 58.7 72 147.5 9.5 119.5 100.4 81.3 62.2 - - 137.7 10.7 117.9 98.3 78.7 59.1 - ­67 134.1 9.4 134.1 122.8 103.7 84.6 65.5 - 126.1 10.7 126.1 120.4 102.1 82.5 62.9 ­62 127.0 9.3 127.0 127.0 127.0 107.9 88.8 69.7 118.5 10.5 118.5 118.5 118.5 99.0 79.4 59.8 57 125.6 9.4 125.6 125.6 125.6 106.5 87.4 68.3 117.8 10.6 117.8 117.8 117.8 98.2 78.7 59.1
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
20 Johnson Controls Unitary Products
505428-YTG-N-0712
YC120/NC120 (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
1
WB (°F)
77 117.5 12.0 63.4 50.4 37.4 - - - 108.0 13.2 60.3 47.2 34.1 - - ­72 109.1 11.9 81.0 68.0 55.0 41.9 - - 101.2 13.2 78.4 65.3 52.2 39.1 - ­67 100.8 11.9 98.6 85.6 72.6 59.5 46.5 - 94.3 13.1 94.3 83.4 70.3 57.2 44.1 ­62 94.0 11.8 94.0 94.0 89.4 76.4 63.4 50.4 87.2 13.0 87.2 87.2 85.1 72.0 59.0 45.9 57 94.0 11.8 94.0 94.0 84.7 71.7 58.7 45.7 87.8 13.1 87.8 87.8 77.8 64.7 51.7 38.6 77 124.2 12.0 74.4 55.8 41.1 - - - 115.1 13.2 73.6 53.0 38.1 - - ­72 115.4 11.9 89.9 75.2 60.4 45.7 - - 107.7 13.2 87.9 73.1 58.2 43.4 - ­67 106.6 11.9 105.5 94.6 79.8 65.1 50.3 - 100.4 13.1 100.4 93.2 78.3 63.5 48.6 ­62 99.4 11.8 99.4 99.4 98.4 83.6 68.9 54.1 92.8 13.0 92.8 92.8 92.8 80.4 65.2 50.3 57 99.4 11.8 99.4 99.4 93.2 78.5 63.7 49.0 93.5 13.1 93.5 93.5 86.9 72.4 57.2 42.3 77 131.0 12.0 85.5 61.3 44.8 - - - 122.1 13.2 86.9 58.7 42.1 - - ­72 121.7 11.9 98.9 82.4 65.9 49.5 - - 114.3 13.2 97.5 80.8 64.2 47.6 - ­67 112.3 11.9 112.3 103.5 87.1 70.6 54.1 - 106.5 13.1 106.5 103.0 86.3 69.7 53.1 ­62 104.8 11.8 104.8 104.8 107.3 90.8 74.4 57.9 98.5 13.1 98.5 98.5 98.5 88.7 71.4 54.8 57 104.8 11.8 104.8 104.8 101.7 85.2 68.7 52.2 99.2 13.1 99.2 99.2 95.9 80.1 62.7 46.0 72 124.7 11.9 107.6 89.3 71.0 52.8 - - 116.1 13.2 106.1 87.5 68.9 50.3 - ­67 115.2 11.9 115.2 110.8 93.8 75.5 57.2 - 108.2 13.1 108.2 108.2 92.6 74.0 55.4 ­62 107.4 11.8 107.4 107.4 108.7 90.4 72.1 53.8 100.0 13.1 100.0 100.0 100.0 84.9 65.9 47.3 57 107.4 11.8 107.4 107.4 105.9 87.6 69.3 51.0 100.7 13.1 100.7 100.7 99.1 80.9 61.9 43.3 72 127.8 12.0 116.3 96.2 76.1 56.1 - - 117.9 13.2 114.7 94.1 73.6 53.0 - ­67 118.0 11.9 118.0 118.0 100.5 80.4 60.4 - 109.9 13.1 109.9 109.9 98.9 78.4 57.8 ­62 110.1 11.8 110.1 110.1 110.1 90.0 69.9 49.8 101.6 13.0 101.6 101.6 101.6 81.0 60.4 39.9 57 110.1 11.9 110.1 110.1 110.1 90.0 69.9 49.8 102.3 13.1 102.3 102.3 102.3 81.7 61.2 40.6
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 21
505428-YTG-N-0712
YD120/ND120
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
WB (°F)
77 138.1 7.5 63.6 51.7 39.9 - - - 132.8 8.6 62.9 50.8 38.7 - - ­72 130.1 7.4 82.9 71.0 59.2 47.4 - - 124.4 8.4 81.7 69.6 57.5 45.4 - ­67 122.0 7.2 102.2 90.4 78.5 66.7 54.8 - 115.9 8.3 100.6 88.5 76.4 64.3 52.2 ­62 112.3 7.2 112.3 108.5 94.8 83.0 71.1 59.3 106.3 8.2 106.3 104.4 92.3 80.2 68.1 56.0 57 108.2 7.1 108.2 108.6 99.9 88.0 76.2 64.3 105.7 8.2 105.7 105.7 95.1 83.0 70.9 58.8 77 147.1 7.5 70.5 57.3 44.0 - - - 141.3 8.6 70.1 56.5 42.8 - - ­72 138.4 7.4 91.8 78.6 65.3 52.0 - - 132.4 8.4 91.0 77.3 63.6 50.0 - ­67 129.8 7.3 113.1 99.9 86.6 73.3 60.0 - 123.4 8.3 111.9 98.2 84.5 70.8 57.1 ­62 119.5 7.2 119.5 117.6 104.6 91.9 78.0 64.7 113.2 8.2 113.2 112.2 102.1 88.5 74.8 61.1 57 115.1 7.2 115.1 115.4 110.1 97.8 83.6 70.3 112.5 8.2 112.5 112.5 105.3 91.6 77.9 64.2 77 156.0 7.6 77.5 62.8 48.1 - - - 149.9 8.6 77.4 62.1 46.9 - - ­72 146.8 7.4 100.8 86.1 71.4 56.7 - - 140.4 8.4 100.3 85.0 69.8 54.5 - ­67 137.7 7.3 124.1 109.4 94.6 79.9 65.2 - 130.9 8.3 123.2 107.9 92.6 77.4 62.1 ­62 126.8 7.2 126.8 126.8 114.3 100.8 84.9 70.2 120.0 8.2 120.0 120.0 112.0 96.7 81.4 66.2 57 122.1 7.2 122.1 122.1 120.4 107.5 91.0 76.3 119.3 8.2 119.3 119.3 115.4 100.1 84.9 69.6 72 152.4 7.5 108.1 92.0 76.0 60.0 - - 145.8 8.5 107.7 91.1 74.5 57.9 - ­67 142.9 7.3 136.1 116.8 100.8 84.8 68.8 - 135.9 8.3 132.1 115.5 98.9 82.3 65.7 ­62 131.5 7.2 131.5 131.5 123.1 107.7 91.1 75.1 124.6 8.2 124.6 124.6 119.5 102.9 86.3 69.7 57 126.7 7.2 126.7 126.7 125.9 110.8 93.9 77.8 123.9 8.2 123.9 123.9 121.9 105.3 88.7 72.1 72 157.9 7.5 115.3 98.0 80.7 63.4 - - 151.2 8.5 115.2 97.2 79.2 61.2 - ­67 148.1 7.4 148.1 124.3 107.0 89.7 72.4 - 141.0 8.3 141.0 123.1 105.1 87.2 69.2 ­62 136.3 7.3 136.3 136.3 132.0 114.6 97.3 80.0 129.3 8.3 129.3 129.3 127.1 109.1 91.1 73.1 57 131.3 7.3 131.3 131.3 131.3 114.0 96.7 79.4 128.5 8.2 128.5 128.5 128.5 110.5 92.5 74.6
77 127.4 9.6 62.2 49.8 37.4 - - - 122.1 10.8 60.4 48.0 35.6 - - ­72 118.7 9.5 80.6 68.2 55.9 43.5 - - 112.7 10.7 78.3 65.8 53.4 41.0 - ­67 109.9 9.3 99.0 86.6 74.3 61.9 49.5 - 103.2 10.6 96.1 83.7 71.2 58.8 46.4 ­62 100.4 9.2 100.4 100.4 89.8 77.5 65.1 52.7 95.0 10.5 95.0 95.0 86.6 74.1 61.7 49.3 57 103.2 9.2 103.2 102.8 90.4 78.0 65.7 53.3 98.1 10.5 98.1 97.9 85.4 73.0 60.5 48.1 77 135.6 9.6 69.7 55.6 41.6 - - - 129.2 10.8 70.6 53.8 39.6 - - ­72 126.3 9.5 90.2 76.1 62.0 47.9 - - 119.2 10.7 87.9 73.7 59.5 45.3 - ­67 116.9 9.3 110.6 96.6 82.5 68.4 54.3 - 109.2 10.6 105.2 93.6 79.4 65.2 51.0 ­62 106.8 9.2 106.8 106.8 99.7 85.0 71.5 57.4 100.5 10.5 100.5 100.5 96.5 82.0 68.1 53.9 57 109.9 9.2 109.9 109.6 100.4 85.4 72.2 58.1 103.8 10.5 103.8 103.6 95.2 80.5 66.8 52.6 77 143.8 9.6 77.3 61.5 45.7 - - - 136.2 10.8 80.8 59.7 43.7 - - ­72 133.9 9.5 99.8 84.0 68.2 52.3 - - 125.7 10.7 97.5 81.6 65.6 49.6 - ­67 124.0 9.3 122.3 106.5 90.6 74.8 59.0 - 115.1 10.6 114.3 103.5 87.5 71.6 55.6 ­62 113.3 9.2 113.3 113.3 109.6 92.6 78.0 62.2 106.0 10.5 106.0 106.0 106.4 89.8 74.4 58.5 57 116.5 9.2 116.5 116.5 110.3 92.7 78.7 62.9 109.4 10.5 109.4 109.4 104.9 88.1 73.0 57.1 72 139.2 9.5 107.4 90.2 72.9 55.7 - - 131.0 10.7 105.2 87.7 70.3 52.8 - ­67 128.9 9.3 128.0 114.2 97.0 79.7 62.5 - 120.1 10.6 119.6 111.2 93.7 76.3 58.8 ­62 117.7 9.2 117.7 117.7 115.9 98.1 81.4 64.2 110.5 10.5 110.5 110.5 110.7 92.9 75.8 58.3 57 121.1 9.2 121.1 121.1 118.0 99.9 83.5 66.3 114.1 10.5 114.1 114.1 111.8 93.9 76.9 59.4 72 144.5 9.5 115.0 96.3 77.7 59.0 - - 136.4 10.7 112.9 93.9 74.9 56.0 - ­67 133.8 9.3 133.8 121.9 103.3 84.6 66.0 - 125.0 10.6 125.0 118.9 99.9 81.0 62.0 ­62 122.2 9.2 122.2 122.2 122.2 103.5 84.9 66.2 115.0 10.5 115.0 115.0 115.0 96.1 77.1 58.1 57 125.7 9.2 125.7 125.7 125.7 107.0 88.4 69.7 118.7 10.5 118.7 118.7 118.7 99.8 80.8 61.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
22 Johnson Controls Unitary Products
505428-YTG-N-0712
YD120/ND120 (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
1
WB (°F)
77 116.8 12.1 58.7 46.2 33.7 - - - 111.5 13.3 57.0 44.4 31.8 - - ­72 106.7 11.9 75.9 63.4 50.9 38.4 - - 100.7 13.2 73.6 61.1 48.5 35.9 - ­67 96.6 11.8 93.2 80.7 68.2 55.7 43.2 - 89.9 13.1 89.9 77.7 65.1 52.6 40.0 ­62 89.7 11.7 89.7 89.7 83.3 70.8 58.3 45.8 84.4 12.9 84.4 84.4 80.0 67.5 54.9 42.3 57 93.0 11.7 93.0 92.9 80.4 67.9 55.4 42.9 87.9 12.9 87.9 87.9 75.5 62.9 50.3 37.8 77 122.7 12.1 71.5 52.0 37.7 - - - 116.2 13.3 72.4 50.2 35.8 - - ­72 112.1 11.9 85.6 71.3 57.0 42.7 - - 105.0 13.2 83.3 68.9 54.5 40.1 - ­67 101.4 11.8 99.7 90.6 76.3 62.0 47.7 - 93.7 13.1 93.7 87.6 73.2 58.8 44.4 ­62 94.2 11.7 94.2 94.2 93.2 78.9 64.6 50.3 88.0 12.9 88.0 88.0 88.0 75.8 61.1 46.7 57 97.7 11.7 97.7 97.6 90.0 75.7 61.4 47.1 91.5 13.0 91.5 91.5 84.8 70.9 56.0 41.6 77 128.6 12.1 84.3 57.8 41.7 - - - 120.9 13.3 87.7 56.0 39.7 - - ­72 117.4 11.9 95.3 79.2 63.1 46.9 - - 109.2 13.2 93.0 76.8 60.5 44.2 - ­67 106.3 11.8 106.3 100.5 84.4 68.3 52.2 - 97.4 13.1 97.4 97.4 81.3 65.0 48.8 ­62 98.8 11.7 98.8 98.8 103.1 87.0 70.9 54.8 91.5 12.9 91.5 91.5 91.5 84.2 67.3 51.1 57 102.3 11.7 102.3 102.3 99.6 83.5 67.3 51.2 95.2 13.0 95.2 95.2 94.2 78.8 61.7 45.4 72 122.9 12.0 103.0 85.3 67.6 49.9 - - 114.7 13.2 100.8 82.9 65.0 47.0 - ­67 111.2 11.8 111.2 108.2 90.5 72.8 55.1 - 102.4 13.1 102.4 102.4 87.3 69.3 51.4 ­62 103.3 11.7 103.3 103.3 105.5 87.8 70.1 52.4 96.1 12.9 96.1 96.1 96.1 82.6 64.4 46.5 57 107.1 11.7 107.1 107.1 105.7 88.0 70.3 52.6 100.0 13.0 100.0 100.0 99.5 82.0 63.6 45.7 72 128.3 12.0 110.8 91.5 72.2 52.9 - - 120.2 13.3 108.7 89.0 69.4 49.8 - ­67 116.1 11.9 116.1 115.9 96.6 77.3 58.0 - 107.3 13.2 107.3 107.3 93.3 73.7 54.1 ­62 107.9 11.7 107.9 107.9 107.9 88.6 69.3 50.0 100.7 13.0 100.7 100.7 100.7 81.1 61.5 41.9 57 111.8 11.8 111.8 111.8 111.8 92.5 73.2 53.9 104.8 13.0 104.8 104.8 104.8 85.2 65.6 46.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 23
505428-YTG-N-0712
YC150/NC180
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
WB (°F)
77 178.5 10.2 87.6 71.1 54.7 - - - 172.2 11.3 84.0 67.6 51.2 - - ­72 168.2 9.9 111.9 95.4 78.9 62.4 - - 161.2 11.0 108.3 91.9 75.5 59.2 - ­67 157.9 9.6 136.1 119.6 103.1 86.7 70.2 - 150.1 10.7 132.5 116.2 99.8 83.4 67.1 ­62 144.8 9.4 144.8 144.8 129.3 112.8 96.3 79.8 138.9 10.6 138.9 138.9 126.4 110.1 93.7 77.3 57 149.7 9.5 149.7 149.7 137.7 121.2 104.7 88.3 143.9 10.7 143.9 143.9 130.6 114.3 97.9 81.5 77 184.7 10.2 94.2 77.2 58.5 - - - 177.6 11.3 92.4 73.7 55.0 - - ­72 174.0 9.9 121.8 103.1 84.4 65.7 - - 166.2 11.0 118.4 99.8 81.1 62.4 - ­67 163.4 9.6 149.5 129.0 110.3 91.6 72.9 - 154.7 10.8 144.5 125.8 107.1 88.4 69.8 ­62 149.9 9.4 149.9 149.9 138.2 119.8 100.8 82.1 143.2 10.6 143.2 143.2 135.7 117.0 98.4 79.7 57 154.9 9.5 154.9 154.9 147.3 129.1 109.8 91.1 148.4 10.7 148.4 148.4 140.2 121.6 102.9 84.2 77 190.9 10.3 100.7 83.2 62.3 - - - 182.9 11.3 100.8 79.8 58.8 - - ­72 179.9 9.9 131.8 110.8 89.9 68.9 - - 171.2 11.0 128.6 107.6 86.6 65.6 - ­67 168.8 9.6 162.9 138.4 117.5 96.5 75.5 - 159.4 10.8 156.5 135.5 114.5 93.5 72.5 ­62 154.9 9.4 154.9 154.9 147.2 126.8 105.3 84.3 147.5 10.6 147.5 147.5 145.0 124.0 103.0 82.0 57 160.1 9.6 160.1 160.1 156.9 137.0 114.9 94.0 152.9 10.7 152.9 152.9 149.8 128.8 107.8 86.8 72 182.3 10.1 142.7 119.7 96.7 73.7 - - 174.1 11.2 139.0 116.1 93.1 70.2 - ­67 171.1 9.8 168.1 149.4 126.4 103.4 80.4 - 162.1 10.9 160.6 146.0 123.1 100.1 77.2 ­62 157.0 9.6 157.0 157.0 153.1 130.4 107.1 84.1 150.0 10.7 150.0 150.0 148.8 125.8 102.9 79.9 57 162.2 9.7 162.2 162.2 160.6 138.1 114.6 91.6 155.5 10.8 155.5 155.5 153.9 131.0 108.1 85.1 72 184.7 10.2 153.7 128.6 103.6 78.5 - - 177.0 11.3 149.4 124.5 99.7 74.8 - ­67 173.4 9.9 173.4 160.4 135.4 110.4 85.3 - 164.8 11.0 164.8 156.6 131.7 106.8 81.9 ­62 159.0 9.7 159.0 159.0 159.0 134.0 108.9 83.9 152.5 10.8 152.5 152.5 152.5 127.6 102.7 77.8 57 164.4 9.8 164.4 164.4 164.4 139.3 114.3 89.2 158.1 10.9 158.1 158.1 158.1 133.2 108.3 83.4
77 166.0 12.3 80.3 64.1 47.8 - - - 159.9 14.1 79.0 62.8 46.6 - - ­72 154.1 12.1 104.7 88.4 72.2 55.9 - - 148.2 13.8 102.8 86.6 70.4 54.2 - ­67 142.3 11.9 129.0 112.7 96.5 80.2 64.0 - 136.4 13.5 126.7 110.5 94.2 78.0 61.8 ­62 132.9 11.7 132.9 132.9 123.6 107.4 91.1 74.9 130.6 13.4 130.6 130.6 122.0 105.8 89.6 73.4 57 138.2 11.8 138.2 138.2 123.6 107.3 91.1 74.8 134.7 13.5 134.7 134.7 119.4 103.2 87.0 70.8 77 170.5 12.3 90.6 70.2 51.6 - - - 163.0 14.0 91.5 68.6 50.0 - - ­72 158.3 12.1 115.0 96.4 77.8 59.1 - - 151.0 13.7 112.8 94.2 75.6 56.9 - ­67 146.1 11.9 139.5 122.6 104.0 85.3 66.7 - 139.1 13.5 134.2 119.8 101.2 82.5 63.9 ­62 136.5 11.7 136.5 136.5 133.2 114.3 95.9 77.3 133.1 13.4 133.1 133.1 130.9 112.1 93.6 75.0 57 142.0 11.8 142.0 142.0 133.2 114.0 95.9 77.3 137.3 13.5 137.3 137.3 128.1 109.2 90.9 72.2 77 175.0 12.3 100.8 76.3 55.3 - - - 166.1 13.9 104.0 74.4 53.4 - - ­72 162.5 12.1 125.4 104.4 83.4 62.3 - - 153.9 13.7 122.9 101.8 80.7 59.6 - ­67 150.0 11.9 150.0 132.5 111.5 90.4 69.4 - 141.7 13.4 141.7 129.1 108.1 87.0 65.9 ­62 140.1 11.7 140.1 140.1 142.8 121.2 100.7 79.7 135.6 13.3 135.6 135.6 139.8 118.5 97.7 76.6 57 145.7 11.8 145.7 145.7 142.8 120.7 100.7 79.7 140.0 13.4 140.0 140.0 136.9 115.3 94.8 73.7 72 165.9 12.2 135.3 112.4 89.5 66.7 - - 157.7 13.8 133.0 110.0 87.1 64.2 - ­67 153.1 12.0 153.1 142.6 119.7 96.8 73.9 - 145.2 13.5 145.2 138.0 116.6 93.7 70.8 ­62 143.1 11.8 143.1 143.1 144.4 121.2 98.6 75.7 138.9 13.4 138.9 138.9 141.0 118.0 95.2 72.3 57 148.7 11.9 148.7 148.7 147.3 123.9 101.5 78.6 143.4 13.5 143.4 143.4 141.8 118.6 96.0 73.1 72 169.3 12.3 145.2 120.5 95.7 71.0 - - 161.4 14.0 143.0 118.3 93.5 68.7 - ­67 156.3 12.1 156.3 152.7 128.0 103.2 78.5 - 148.6 13.7 148.6 146.9 125.2 100.4 75.6 ­62 146.0 11.9 146.0 146.0 146.0 121.3 96.5 71.8 142.2 13.6 142.2 142.2 142.2 117.5 92.7 67.9 57 151.8 12.0 151.8 151.8 151.8 127.0 102.3 77.6 146.8 13.7 146.8 146.8 146.8 122.0 97.2 72.5
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
24 Johnson Controls Unitary Products
505428-YTG-N-0712
YC150/NC180 (Continued)
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
1
WB (°F)
77 153.8 15.8 77.6 61.4 45.3 - - - 147.7 17.5 76.3 60.1 44.0 - - ­72 142.2 15.5 101.0 84.8 68.7 52.5 - - 136.2 17.2 99.2 83.0 66.9 50.8 - ­67 130.5 15.1 124.4 108.2 92.0 75.9 59.7 - 124.7 16.8 122.1 105.9 89.8 73.7 57.6 ­62 128.2 15.1 128.2 128.2 120.4 104.2 88.0 71.9 125.8 16.8 125.8 125.8 118.7 102.6 86.5 70.4 57 131.2 15.2 131.2 131.2 115.2 99.0 82.8 66.7 127.8 17.0 127.8 127.8 111.0 94.9 78.7 62.6 77 155.5 15.7 92.3 67.0 48.4 - - - 148.1 17.3 93.2 65.4 46.8 - - ­72 143.8 15.3 110.6 92.0 73.4 54.7 - - 136.5 17.0 108.4 89.8 71.2 52.5 - ­67 132.0 15.0 128.9 117.0 98.3 79.7 61.1 - 125.0 16.6 123.7 114.2 95.5 76.9 58.3 ­62 129.7 15.0 129.7 129.7 128.6 110.0 91.3 72.7 126.2 16.7 126.2 126.2 126.2 107.8 89.1 70.4 57 132.7 15.1 132.7 132.7 123.1 104.4 85.8 67.2 128.1 16.8 128.1 128.1 118.0 99.7 80.8 62.1 77 157.3 15.5 107.1 72.6 51.5 - - - 148.4 17.1 110.2 70.7 49.6 - - ­72 145.4 15.2 120.3 99.2 78.1 57.0 - - 136.8 16.8 117.7 96.6 75.4 54.3 - ­67 133.5 14.9 133.5 125.8 104.7 83.6 62.5 - 125.2 16.4 125.2 122.4 101.3 80.1 59.0 ­62 131.1 14.9 131.1 131.1 136.9 115.8 94.7 73.6 126.6 16.5 126.6 126.6 126.6 113.1 91.6 70.5 57 134.2 15.0 134.2 134.2 131.0 109.9 88.8 67.7 128.5 16.6 128.5 128.5 125.1 104.5 82.8 61.7 72 149.5 15.4 130.6 107.6 84.7 61.7 - - 141.3 17.0 128.2 105.2 82.3 59.3 - ­67 137.3 15.1 137.3 133.4 113.5 90.6 67.6 - 129.3 16.6 129.3 128.8 110.4 87.5 64.5 ­62 134.8 15.1 134.8 134.8 137.7 114.7 91.8 68.8 130.7 16.7 130.7 130.7 130.7 111.5 88.4 65.4 57 138.0 15.2 138.0 138.0 136.4 113.4 90.5 67.5 132.6 16.8 132.6 132.6 130.9 108.2 84.9 62.0 72 153.6 15.6 140.9 116.1 91.3 66.5 - - 145.7 17.2 138.7 113.9 89.1 64.3 - ­67 141.0 15.3 141.0 141.0 122.4 97.6 72.8 - 133.4 16.8 133.4 133.4 119.6 94.8 69.9 ­62 138.5 15.3 138.5 138.5 138.5 113.7 88.9 64.1 134.7 16.9 134.7 134.7 134.7 109.9 85.1 60.2 57 141.8 15.4 141.8 141.8 141.8 117.0 92.2 67.4 136.7 17.1 136.7 136.7 136.7 111.9 87.1 62.3
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 25
505428-YTG-N-0712
YD150/ND180
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
WB (°F)
77 170.2 10.0 80.1 64.2 48.3 - - - 173.7 11.0 81.5 65.4 49.3 - - ­72 164.1 9.7 106.1 90.2 74.3 58.4 - - 161.9 10.8 105.7 89.6 73.5 57.5 - ­67 157.9 9.5 132.0 116.1 100.2 84.3 68.5 - 150.1 10.6 129.8 113.8 97.7 81.7 65.6 ­62 142.4 9.3 142.4 140.8 122.7 106.8 90.9 75.1 139.3 10.4 139.3 138.5 122.4 106.4 90.3 74.2 57 141.3 9.3 141.3 141.3 129.9 114.0 98.1 82.2 140.0 10.4 140.0 140.0 127.0 111.0 94.9 78.8 77 182.4 10.0 89.5 72.3 53.8 - - - 182.2 11.1 91.1 72.7 54.3 - - ­72 175.5 9.7 119.7 101.2 82.7 64.2 - - 169.8 10.9 117.7 99.3 80.8 62.4 - ­67 168.7 9.5 149.8 130.0 111.5 93.0 74.5 - 157.4 10.7 144.3 125.9 107.4 89.0 70.5 ­62 152.3 9.4 152.3 151.5 136.6 118.9 99.7 81.2 146.1 10.5 146.1 145.7 134.6 116.1 97.7 79.2 57 151.2 9.3 151.2 151.2 144.6 126.8 107.6 89.1 146.8 10.5 146.8 146.8 139.7 121.2 102.8 84.3 77 194.5 10.0 98.9 80.4 59.3 - - - 190.7 11.1 100.8 80.0 59.2 - - ­72 187.0 9.8 133.3 112.2 91.1 70.0 - - 177.7 10.9 129.8 109.0 88.2 67.3 - ­67 179.5 9.5 167.6 143.9 122.8 101.7 80.6 - 164.8 10.7 158.8 138.0 117.1 96.3 75.5 ­62 162.2 9.4 162.2 162.2 150.6 131.0 108.4 87.3 152.9 10.5 152.9 152.9 146.8 125.9 105.1 84.3 57 161.1 9.4 161.1 161.1 159.2 139.6 117.0 95.9 153.7 10.5 153.7 153.7 152.3 131.4 110.6 89.8 72 187.6 9.8 141.9 119.6 97.2 74.8 - - 180.7 11.0 140.5 117.9 95.3 72.8 - ­67 180.3 9.6 174.3 153.5 131.1 108.7 86.4 - 167.5 10.8 164.6 149.3 126.7 104.1 81.5 ­62 162.8 9.5 162.8 162.8 156.9 135.3 112.2 89.8 155.4 10.6 155.4 155.4 152.4 129.8 107.2 84.7 57 161.6 9.4 161.6 161.6 160.7 139.0 115.9 93.5 156.3 10.6 156.3 156.3 155.6 133.0 110.4 87.8 72 188.2 9.9 150.6 126.9 103.3 79.6 - - 183.7 11.0 151.2 126.8 102.5 78.2 - ­67 181.0 9.7 181.0 163.0 139.4 115.7 92.1 - 170.3 10.8 170.3 160.6 136.2 111.9 87.6 ­62 163.3 9.5 163.3 163.3 163.3 139.7 116.0 92.3 158.0 10.6 158.0 158.0 158.0 133.7 109.4 85.1 57 162.1 9.5 162.1 162.1 162.1 138.5 114.8 91.1 158.8 10.6 158.8 158.8 158.8 134.5 110.2 85.9
77 177.3 12.0 82.9 66.6 50.4 - - - 162.9 13.7 78.3 62.1 45.9 - - ­72 159.8 11.9 105.3 89.0 72.8 56.6 - - 149.2 13.5 101.4 85.2 69.0 52.8 - ­67 142.3 11.8 127.7 111.4 95.2 79.0 62.7 - 135.4 13.3 124.6 108.4 92.2 76.0 59.7 ­62 136.2 11.5 136.2 136.2 122.1 105.9 89.7 73.4 128.0 13.0 128.0 128.0 118.2 102.0 85.7 69.5 57 138.7 11.5 138.7 138.7 124.1 107.9 91.7 75.5 131.1 13.1 131.1 131.1 116.6 100.4 84.2 68.0 77 182.1 12.1 92.8 73.1 54.7 - - - 168.7 13.7 90.6 68.8 50.3 - - ­72 164.1 12.0 115.8 97.4 79.0 60.6 - - 154.5 13.5 112.8 94.2 75.6 57.1 - ­67 146.2 11.9 138.8 121.7 103.3 84.9 66.5 - 140.3 13.4 134.9 119.6 101.0 82.4 63.9 ­62 139.8 11.6 139.8 139.8 132.5 113.4 95.7 77.3 132.6 13.1 132.6 132.6 129.5 110.6 92.4 73.8 57 142.5 11.6 142.5 142.5 134.7 115.6 97.9 79.5 135.8 13.2 135.8 135.8 127.7 108.8 90.6 72.1 77 186.8 12.2 102.7 79.6 59.0 - - - 174.5 13.8 103.0 75.6 54.7 - - ­72 168.4 12.1 126.4 105.8 85.2 64.7 - - 159.9 13.6 124.1 103.2 82.3 61.3 - ­67 150.0 12.0 150.0 132.0 111.5 90.9 70.3 - 145.2 13.4 145.2 130.8 109.9 88.9 68.0 ­62 143.5 11.7 143.5 143.5 142.9 120.8 101.8 81.2 137.2 13.1 137.2 137.2 140.9 119.2 99.0 78.1 57 146.2 11.7 146.2 146.2 145.3 123.3 104.2 83.6 140.5 13.2 140.5 140.5 138.9 117.2 97.1 76.2 72 173.8 12.1 139.0 116.3 93.5 70.7 - - 164.1 13.6 136.3 113.3 90.3 67.2 - ­67 154.8 12.0 154.8 145.1 122.3 99.5 76.7 - 149.0 13.5 149.0 141.4 120.5 97.5 74.5 ­62 148.1 11.7 148.1 148.1 147.8 124.3 102.3 79.5 140.7 13.2 140.7 140.7 142.6 119.2 96.6 73.5 57 150.9 11.7 150.9 150.9 150.4 126.9 104.9 82.1 144.2 13.2 144.2 144.2 143.4 120.0 97.3 74.3 72 179.2 12.1 151.7 126.8 101.8 76.8 - - 168.3 13.7 148.5 123.4 98.3 73.1 - ­67 159.6 12.0 159.6 158.1 133.1 108.1 83.2 - 152.8 13.5 152.8 152.0 131.2 106.1 81.0 ­62 152.7 11.7 152.7 152.7 152.7 127.7 102.8 77.8 144.3 13.2 144.3 144.3 144.3 119.2 94.1 69.0 57 155.6 11.7 155.6 155.6 155.6 130.6 105.6 80.6 147.8 13.3 147.8 147.8 147.8 122.7 97.6 72.5
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
26 Johnson Controls Unitary Products
505428-YTG-N-0712
YD150/ND180 (Continued)
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
1
WB (°F)
77 148.6 15.3 73.8 57.6 41.4 - - - 134.2 17.0 69.2 53.1 36.9 - - ­72 138.6 15.1 97.6 81.4 65.3 49.1 - - 128.0 16.7 93.8 77.6 61.5 45.3 - ­67 128.6 14.8 121.5 105.3 89.1 72.9 56.7 - 121.7 16.3 118.3 102.2 86.0 69.9 53.7 ­62 119.7 14.5 119.7 119.7 114.2 98.0 81.8 65.7 111.5 16.0 111.5 111.5 110.2 94.1 77.9 61.8 57 123.4 14.7 123.4 123.4 109.0 92.8 76.7 60.5 115.7 16.3 115.7 115.7 101.5 85.3 69.2 53.0 77 155.4 15.4 88.5 64.6 45.9 - - - 142.1 17.0 86.4 60.4 41.5 - - ­72 145.0 15.1 109.7 91.0 72.3 53.6 - - 135.4 16.6 106.7 87.8 68.9 50.0 - ­67 134.5 14.8 130.9 117.4 98.7 80.0 61.2 - 128.7 16.3 127.0 115.2 96.4 77.5 58.6 ­62 125.3 14.5 125.3 125.3 126.5 107.8 89.0 70.3 118.0 16.0 118.0 118.0 118.0 105.0 85.7 66.8 57 129.1 14.7 129.1 129.1 120.7 102.0 83.3 64.6 122.4 16.3 122.4 122.4 113.8 95.2 76.0 57.1 77 162.3 15.4 103.2 71.6 50.3 - - - 150.0 16.9 103.5 67.6 46.0 - - ­72 151.3 15.1 121.8 100.6 79.3 58.0 - - 142.8 16.6 119.6 98.0 76.3 54.7 - ­67 140.4 14.8 140.4 129.5 108.3 87.0 65.7 - 135.6 16.3 135.6 128.3 106.7 85.1 63.5 ­62 130.8 14.5 130.8 130.8 138.8 117.5 96.2 75.0 124.4 16.0 124.4 124.4 124.4 115.8 93.5 71.9 57 134.8 14.7 134.8 134.8 132.5 111.2 90.0 68.7 129.0 16.2 129.0 129.0 126.0 105.2 82.8 61.2 72 154.3 15.2 133.5 110.3 87.0 63.8 - - 144.6 16.7 130.8 107.3 83.8 60.3 - ­67 143.2 14.9 143.2 137.8 118.8 95.5 72.3 - 137.4 16.4 137.4 134.1 117.1 93.6 70.1 ­62 133.4 14.6 133.4 133.4 137.4 114.1 90.8 67.6 126.0 16.1 126.0 126.0 126.0 109.0 85.1 61.6 57 137.4 14.8 137.4 137.4 136.3 113.0 89.8 66.5 130.7 16.3 130.7 130.7 129.2 106.1 82.2 58.7 72 157.3 15.3 145.3 120.0 94.7 69.5 - - 146.4 16.8 142.0 116.6 91.2 65.8 - ­67 146.0 15.0 146.0 146.0 129.3 104.1 78.8 - 139.2 16.5 139.2 139.2 127.5 102.1 76.7 ­62 136.0 14.7 136.0 136.0 136.0 110.7 85.4 60.2 127.6 16.2 127.6 127.6 127.6 102.2 76.8 51.4 57 140.1 14.9 140.1 140.1 140.1 114.8 89.6 64.3 132.4 16.5 132.4 132.4 132.4 107.0 81.6 56.2
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 27
505428-YTG-N-0712
YC180/NC180
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
77 223.5 11.8 104.0 85.0 66.0 - - - 214.6 13.1 101.2 82.2 63.3 - - ­72 207.2 11.5 132.3 113.3 94.4 75.4 - - 198.3 12.8 129.0 110.1 91.2 72.2 - ­67 191.0 11.1 160.6 141.7 122.7 103.7 84.7 - 181.9 12.4 156.8 137.9 119.0 100.1 81.1 ­62 176.0 10.8 176.0 171.9 151.4 132.5 113.5 94.5 168.5 12.2 168.5 166.4 147.5 128.6 109.7 90.8 57 175.0 10.8 175.0 175.0 158.1 139.1 120.1 101.1 168.1 12.1 168.1 168.1 150.6 131.7 112.8 93.8 77 229.4 11.9 113.7 92.3 70.8 - - - 220.1 13.2 110.7 89.4 68.1 - - ­72 212.8 11.6 144.1 122.7 101.2 79.7 - - 203.3 12.8 140.7 119.4 98.1 76.8 - ­67 196.1 11.2 174.5 153.0 131.6 110.1 88.7 - 186.5 12.5 170.6 149.3 128.0 106.7 85.4 ­62 180.7 11.0 180.7 178.6 162.4 141.9 119.5 98.1 172.7 12.2 172.7 171.7 158.7 137.4 116.1 94.8 57 179.7 10.9 179.7 179.7 169.6 149.6 126.6 105.2 172.4 12.2 172.4 172.4 162.0 140.7 119.4 98.1 77 235.4 12.0 123.5 99.5 75.6 - - - 225.5 13.3 120.3 96.6 72.9 - - ­72 218.3 11.7 155.9 132.0 108.0 84.1 - - 208.3 12.9 152.3 128.6 105.0 81.3 - ­67 201.2 11.3 188.3 164.4 140.5 116.5 92.6 - 191.1 12.6 184.4 160.7 137.0 113.4 89.7 ­62 185.4 11.1 185.4 185.4 173.4 151.3 125.5 101.6 177.0 12.3 177.0 177.0 169.9 146.2 122.6 98.9 57 184.4 11.0 184.4 184.4 181.0 160.1 133.2 109.2 176.6 12.3 176.6 176.6 173.5 149.8 126.1 102.4 72 221.3 11.3 165.2 139.4 113.7 88.0 - - 213.7 13.6 165.8 140.1 114.5 88.8 - ­67 204.0 11.0 197.5 174.0 147.8 122.0 96.3 - 196.0 13.3 192.7 175.1 149.4 123.8 98.1 ­62 187.9 10.7 187.9 187.9 181.9 157.1 130.4 104.7 181.5 13.0 181.5 181.5 178.0 152.4 126.7 101.1 57 186.8 10.6 186.8 186.8 185.2 161.0 133.7 108.0 181.2 13.0 181.2 181.2 179.6 153.9 128.3 102.6 72 224.2 10.9 174.4 146.9 119.4 91.8 - - 219.0 14.3 179.2 151.6 123.9 96.3 - ­67 206.7 10.6 206.7 183.6 155.1 127.6 100.0 - 201.0 14.0 201.0 189.4 161.8 134.1 106.5 ­62 190.4 10.3 190.4 190.4 190.4 162.8 135.3 107.8 186.1 13.7 186.1 186.1 186.1 158.5 130.9 103.2 57 189.3 10.3 189.3 189.3 189.3 161.8 134.3 106.7 185.7 13.7 185.7 185.7 185.7 158.1 130.5 102.9
77 205.8 14.4 98.3 79.5 60.6 - - - 195.5 15.9 95.5 76.6 57.7 - - ­72 189.3 14.0 125.7 106.8 87.9 69.1 - - 179.9 15.7 122.5 103.6 84.7 65.9 - ­67 172.8 13.7 153.0 134.1 115.3 96.4 77.5 - 164.3 15.4 149.5 130.7 111.8 92.9 74.0 ­62 161.0 13.5 161.0 161.0 143.6 124.7 105.9 87.0 153.2 15.2 153.2 153.2 139.8 120.9 102.0 83.1 57 161.3 13.5 161.3 161.3 143.1 124.3 105.4 86.6 154.3 15.2 154.3 154.3 136.3 117.4 98.5 79.6 77 210.7 14.4 107.7 86.6 65.4 - - - 199.9 16.0 107.5 83.6 62.4 - - ­72 193.8 14.1 137.2 116.1 94.9 73.8 - - 183.9 15.8 134.0 112.8 91.6 70.4 - ­67 176.9 13.8 166.7 145.6 124.4 103.3 82.2 - 168.0 15.5 160.4 142.0 120.8 99.6 78.3 ­62 164.8 13.5 164.8 164.8 155.0 132.9 112.7 91.6 156.6 15.2 156.6 156.6 151.0 129.4 108.6 87.4 57 165.1 13.6 165.1 165.1 154.5 131.9 112.2 91.1 157.7 15.2 157.7 157.7 147.2 125.3 104.8 83.6 77 215.5 14.5 117.1 93.7 70.2 - - - 204.2 16.1 119.5 90.5 67.0 - - ­72 198.3 14.2 148.7 125.3 101.9 78.5 - - 187.9 15.8 145.4 121.9 98.4 74.9 - ­67 181.0 13.8 180.4 157.0 133.6 110.2 86.8 - 171.6 15.6 171.3 153.3 129.7 106.2 82.7 ­62 168.6 13.6 168.6 168.6 166.4 141.1 119.6 96.2 160.0 15.3 160.0 160.0 162.3 137.8 115.3 91.7 57 168.9 13.6 168.9 168.9 165.9 139.4 119.1 95.6 161.2 15.3 161.2 161.2 158.2 133.2 111.2 87.6 72 206.1 15.9 166.4 140.8 115.2 89.7 - - 192.5 16.7 159.1 133.4 107.7 82.0 - ­67 188.1 15.6 187.8 176.1 151.0 125.5 99.9 - 175.8 16.4 175.7 166.6 142.0 116.3 90.7 ­62 175.2 15.3 175.2 175.2 174.1 147.6 123.0 97.4 164.0 16.2 164.0 164.0 165.1 139.0 113.7 88.1 57 175.5 15.3 175.5 175.5 174.0 146.9 122.9 97.3 165.1 16.2 165.1 165.1 163.6 137.2 112.3 86.6 72 213.9 17.7 184.0 156.3 128.5 100.8 - - 197.2 17.6 172.7 144.9 117.0 89.2 - ­67 195.2 17.3 195.2 195.2 168.5 140.7 113.0 - 180.0 17.3 180.0 180.0 154.3 126.5 98.6 ­62 181.9 17.0 181.9 181.9 181.9 154.1 126.4 98.6 167.9 17.0 167.9 167.9 167.9 140.1 112.2 84.4 57 182.2 17.0 182.2 182.2 182.2 154.4 126.7 99.0 169.0 17.0 169.0 169.0 169.0 141.2 113.4 85.6
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
28 Johnson Controls Unitary Products
505428-YTG-N-0712
YC180/NC180 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB
(°F)
77 185.3 17.5 92.7 73.7 54.8 - - - 175.0 19.1 89.8 70.9 51.9 - - ­72 170.5 17.3 119.4 100.5 81.5 62.6 - - 161.1 18.9 116.2 97.3 78.4 59.4 - ­67 155.8 17.1 146.1 127.2 108.3 89.3 70.4 - 147.2 18.8 142.6 123.7 104.8 85.8 66.9 ­62 145.5 16.9 145.5 145.5 136.0 117.1 98.2 79.3 137.7 18.6 137.7 137.7 132.2 113.3 94.3 75.4 57 147.3 16.8 147.3 147.3 129.4 110.5 91.6 72.7 140.3 18.5 140.3 140.3 122.6 103.6 84.7 65.8 77 189.1 17.6 107.3 80.6 59.3 - - - 178.3 19.2 107.1 77.6 56.2 - - ­72 174.1 17.4 130.7 109.5 88.2 66.9 - - 164.2 19.1 127.5 106.2 84.8 63.5 - ­67 159.0 17.2 154.2 138.3 117.1 95.8 74.5 - 150.1 18.9 147.9 134.7 113.4 92.1 70.7 ­62 148.5 17.0 148.5 148.5 147.1 125.8 104.5 83.3 140.3 18.7 140.3 140.3 140.3 122.2 100.4 79.1 57 150.4 16.9 150.4 150.4 140.0 118.7 97.4 76.2 143.0 18.6 143.0 143.0 132.7 112.1 90.0 68.7 77 192.9 17.7 121.9 87.4 63.8 - - - 181.6 19.3 124.4 84.3 60.5 - - ­72 177.6 17.5 142.1 118.5 94.8 71.2 - - 167.3 19.2 138.8 115.0 91.3 67.6 - ­67 162.2 17.3 162.2 149.5 125.9 102.3 78.6 - 152.9 19.0 152.9 145.8 122.1 98.3 74.6 ­62 151.5 17.0 151.5 151.5 158.2 134.5 110.9 87.3 142.9 18.8 142.9 142.9 142.9 131.2 106.6 82.8 57 153.4 17.0 153.4 153.4 150.5 126.9 103.3 79.6 145.7 18.7 145.7 145.7 142.8 120.6 95.4 71.6 72 179.0 17.5 151.7 126.0 100.2 74.4 - - 165.5 18.3 144.4 118.5 92.7 66.8 - ­67 163.5 17.3 163.5 157.2 133.0 107.2 81.5 - 151.3 18.2 151.3 147.7 124.0 98.1 72.3 ­62 152.7 17.0 152.7 152.7 156.0 130.3 104.5 78.7 141.4 17.9 141.4 141.4 141.4 121.6 95.3 69.4 57 154.7 17.0 154.7 154.7 153.2 127.4 101.7 75.9 144.2 17.9 144.2 144.2 142.8 117.7 91.0 65.2 72 180.4 17.5 161.4 133.5 105.5 77.6 - - 163.7 17.4 150.1 122.1 94.1 66.0 - ­67 164.8 17.3 164.8 164.8 140.1 112.2 84.3 - 149.7 17.3 149.7 149.7 125.9 97.9 69.9 ­62 153.9 17.0 153.9 153.9 153.9 126.0 98.1 70.2 140.0 17.1 140.0 140.0 140.0 112.0 83.9 55.9 57 155.9 17.0 155.9 155.9 155.9 128.0 100.1 72.1 142.7 17.0 142.7 142.7 142.7 114.7 86.7 58.7
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 29
505428-YTG-N-0712
YC180/NC240
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
77 214.3 12.1 111.5 92.2 72.8 - - - 213.3 13.3 110.6 91.3 71.9 - - ­72 201.7 11.8 138.5 119.1 99.8 80.4 - - 199.0 13.0 137.0 117.6 98.3 78.9 - ­67 189.0 11.6 165.4 146.1 126.7 107.3 88.0 - 184.6 12.7 163.3 144.0 124.6 105.2 85.9 ­62 181.2 11.3 181.2 177.5 156.5 137.1 117.7 98.4 171.9 12.5 171.9 170.0 150.7 131.3 112.0 92.6 57 177.1 11.3 177.1 177.1 160.6 141.3 121.9 102.5 170.3 12.5 170.3 170.3 153.8 134.5 115.1 95.8 77 220.7 12.2 121.6 99.7 77.7 - - - 219.3 13.4 120.7 98.7 76.7 - - ­72 207.6 11.9 150.4 128.4 106.4 84.5 - - 204.6 13.1 148.8 126.8 104.9 82.9 - ­67 194.6 11.7 179.1 157.2 135.2 113.2 91.2 - 189.9 12.8 176.9 154.9 133.0 111.0 89.0 ­62 186.5 11.4 186.5 184.7 167.0 145.2 123.0 101.0 176.8 12.6 176.8 175.8 160.8 138.8 116.9 94.9 57 182.3 11.4 182.3 182.3 171.4 150.0 127.4 105.5 175.1 12.6 175.1 175.1 164.2 142.2 120.3 98.3 77 227.1 12.3 131.7 107.1 82.6 - - - 225.4 13.5 130.7 106.1 81.6 - - ­72 213.6 12.0 162.3 137.7 113.1 88.5 - - 210.2 13.2 160.6 136.0 111.5 86.9 - ­67 200.2 11.8 192.8 168.2 143.7 119.1 94.5 - 195.1 12.9 190.5 165.9 141.3 116.8 92.2 ­62 191.9 11.5 191.9 191.9 177.4 153.3 128.3 103.7 181.6 12.7 181.6 181.6 170.9 146.4 121.8 97.2 57 187.6 11.5 187.6 187.6 182.1 158.8 133.0 108.4 179.9 12.7 179.9 179.9 174.5 150.0 125.4 100.8 72 218.3 12.1 172.7 145.8 118.9 92.0 - - 214.0 13.3 170.8 143.9 117.0 90.1 - ­67 204.5 11.9 200.9 177.9 151.0 124.1 97.2 - 198.6 13.0 196.2 175.2 148.4 121.5 94.6 ­62 196.0 11.6 196.0 196.0 188.7 162.0 134.9 108.0 184.9 12.7 184.9 184.9 179.4 152.6 125.7 98.8 57 191.6 11.6 191.6 191.6 188.9 162.6 135.1 108.2 183.1 12.7 183.1 183.1 180.4 153.6 126.7 99.8 72 223.0 12.2 183.1 153.9 124.7 95.5 - - 217.7 13.4 180.9 151.7 122.6 93.4 - ­67 208.9 11.9 208.9 187.5 158.3 129.2 100.0 - 202.0 13.1 202.0 184.6 155.4 126.2 97.0 ­62 200.2 11.7 200.2 200.2 199.9 170.7 141.5 112.3 188.1 12.8 188.1 188.1 187.9 158.8 129.6 100.4 57 195.7 11.6 195.7 195.7 195.7 166.5 137.3 108.1 186.3 12.8 186.3 186.3 186.3 157.1 128.0 98.8
77 212.3 14.6 109.7 90.4 71.0 - - - 207.7 16.7 107.9 88.6 69.2 - - ­72 196.3 14.2 135.5 116.1 96.8 77.4 - - 191.8 16.2 133.6 114.2 94.9 75.5 - ­67 180.3 13.9 161.2 141.8 122.5 103.1 83.8 - 175.9 15.8 159.2 139.9 120.5 101.2 81.9 ­62 162.6 13.6 162.6 162.6 144.9 125.5 106.2 86.8 158.2 15.4 158.2 158.2 141.1 121.7 102.4 83.0 57 163.6 13.6 163.6 163.6 147.1 127.7 108.4 89.0 160.7 15.4 160.7 160.7 144.1 124.7 105.4 86.0 77 218.0 14.6 119.7 97.8 75.8 - - - 213.3 16.8 118.7 95.9 74.0 - - ­72 201.6 14.3 147.2 125.2 103.3 81.3 - - 197.0 16.3 145.3 123.3 101.4 79.4 - ­67 185.2 14.0 174.6 152.7 130.7 108.8 86.8 - 180.7 15.9 171.8 150.8 128.8 106.9 84.9 ­62 167.0 13.7 167.0 167.0 154.6 132.5 110.7 88.8 162.4 15.5 162.4 162.4 150.8 128.7 106.9 84.9 57 167.9 13.7 167.9 167.9 157.0 134.4 113.1 91.1 165.0 15.5 165.0 165.0 154.0 131.7 110.1 88.1 77 223.7 14.7 129.7 105.1 80.6 - - - 218.9 16.9 129.6 103.3 78.7 - - ­72 206.8 14.4 158.9 134.3 109.8 85.3 - - 202.1 16.4 157.0 132.5 107.9 83.4 - ­67 190.0 14.1 188.1 163.5 139.0 114.5 89.9 - 185.4 16.0 184.4 161.6 137.1 112.6 88.0 ­62 171.4 13.8 171.4 171.4 164.4 139.4 115.3 90.8 166.7 15.6 166.7 166.7 160.4 135.7 111.4 86.8 57 172.3 13.8 172.3 172.3 166.9 141.1 117.8 93.3 169.3 15.6 169.3 169.3 163.8 138.7 114.8 90.2 72 209.6 14.5 168.9 142.0 115.1 88.3 - - 205.1 16.5 167.0 140.1 113.2 86.4 - ­67 192.6 14.2 191.6 172.6 145.7 118.9 92.0 - 188.1 16.0 187.6 170.7 143.9 117.0 90.2 ­62 173.7 13.9 173.7 173.7 170.2 143.1 116.5 89.6 169.1 15.6 169.1 169.1 166.0 139.0 112.2 85.4 57 174.7 13.9 174.7 174.7 172.0 144.5 118.2 91.4 171.8 15.6 171.8 171.8 169.0 141.9 115.3 88.5 72 212.4 14.5 178.8 149.6 120.4 91.3 - - 208.0 16.5 176.9 147.8 118.6 89.4 - ­67 195.1 14.2 195.1 181.7 152.5 123.3 94.1 - 190.8 16.1 190.8 179.8 150.7 121.5 92.3 ­62 176.0 13.9 176.0 176.0 176.0 146.8 117.6 88.4 171.5 15.7 171.5 171.5 171.5 142.3 113.1 84.0 57 177.0 13.9 177.0 177.0 177.0 147.8 118.6 89.5 174.2 15.6 174.2 174.2 174.2 145.0 115.9 86.7
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
30 Johnson Controls Unitary Products
Loading...
+ 98 hidden pages