York NC - ND Technical Guide

Y
505428-YTG-N-0712
®

Description

Predator® condensing units and heat pumps are completely
TECHNICAL GUIDE
R-410A SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS AND AIR HANDLERS
PREDATOR® SERIES
CONDENSING UNIT MODELS
PC090-180 and PD180-240
HEAT PUMP UNIT MODELS
NC090-300 and ND120-240
AIR HANDLING UNIT MODELS
7.5 - 25 Ton 60 Hertz
assembled, piped and wired at the factory to provide a single-piece unit for shipment and rigging. Each unit is pressurized with a holding charge of refrigerant R-410A for storage and/or shipping.
The compact design, clean styling, small footprint, and quiet operation make these condensing units and heat pumps suitable for almost any outdoor location. On rooftops... because they weigh much less than a single package unit of similar capacity and are much easier to rig and support. On the ground... because the footprint is compact allowing a variety of applications.
Both the Predator® condensing units and heat pumps are equipped with reliable Simplicity® microprocessor controls to assure proper operation and unit protection for long product life. Products from 10 to 20 tons are available in single or dual (2 or 4 pipe) refrigerant circuits for redundancy in operation and various application choices such as one outdoor unit matched with two indoor units.
The Predator® air handling units are completely assembled units, including a well-insulated cabinet, a DX cooling coil with copper tubing, aluminum fins, expansion valve(s), distributor(s), 2” throwaway filters, a centrifugal blower, a blower motor, an adjustable belt drive, a blower motor contactor and a small holding charge of nitrogen.
YC/YD/PC Outdoor Units
Units are shipped in the vertical position ready for field installation, but can be easily converted to horizontal position. An added benefit of the Predator® air handling units is they are designed to operate with either a condensing unit or a heat pump and no field modification or special unit is required for heat pump applications.
(Except YC300)
Certified Quality
Management System
ISO 9001
NC/ND Indoor Units
YC/YD/PC/PD Outdoor Units
505428-YTG-N-0712

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Condensing Unit Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Outdoor Unit Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Air Handling Unit Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cooling and Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Air Handling and Hot Water Coil Accessory Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Air Handling and Steam Coil Accessory Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Weights And Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
2 Johnson Controls Unitary Products

Nomenclature

505428-YTG-N-0712
Configured Split Condenser Model Number Nomenclature
Product Category
Y = Split System, Condenser, AC, R-410A P = Split System, Condenser, HP, R-410A
Product Identifier
C = Standard Efficiency, 2-Pipe, R-410A D = Standard Efficiency, 4-Pipe, R-410A
Nominal Cooling Capacity - MBH
090 = 7.5 Ton 120 = 10 Ton 150 = 12.5 Ton 180 = 15 Ton 240 = 20 Ton 300 = 25 Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only
YC300
C00 A
2AAA
2
Installation Options
A = None B = Option 1 C = Option 2 D = Options 1 & 2
S = Options 5
T = Options 1 & 5
Options
1 = Disconnect
2 = Non Pwr’d Conv Outlet
5 = Pwr’d Conv Outlet
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Airflow
A = Standard Motor
A
Product Style
A = Style A
Product Generation
1 = First Generation 2 = Second Generation
AA = None AB = Phase Monitor AC = Coil Guard AE = Phase Monitor + Coil Guard EA = ElectroFin Condenser Coil EB = ElectroFin Condenser Coil + Phase Monitor EC = ElectroFin Condenser Coil + Coil Guard EE = ElectroFin Condenser Coil + Coil Guard + Phase Monitor LA = Low Ambient LB = Low Ambient + Phase Monitor LC = Low Ambient + Coil Guard LD = Low Ambient + Phase Monitor + Coil Guard LE = Low Ambient + Technicoat Cond. Coil LF = Low Ambient + Technicoat Cond. Coil + Phase Monitor LG = Low Ambient + Technicoat Cond. Coil + Coil Guard LH = Low Ambient + Technicoat Cond. Coil + Phase Monitor + Coil Guard LJ = Low Ambient + ElectroFin Cond. Coil LK = Low Ambient + ElectroFin Cond. Coil + Phase Monitor LL = Low Ambient + ElectroFin Cond. Coil + Coil Guard LM = Low Ambient + ElectroFin Cond. Coil + Phase Monitor + Coil Guard TA = Technicoat Condenser Coil TB = Technicoat Condenser Coil + Phase Monitor TC = Technicoat Condenser Coil + Coil Guard TE = Technicoat Condenser Coil + Coil Guard + Phase Monitor
Product Options
Configured Split Air Handler Model Number Nomenclature
N = Split System, Air Handler, AC & HP R-410A
C = Standard Efficiency, 2-Pipe, R-410A D = Standard Efficiency, 4-Pipe, R-410A
Nominal Cooling Capacity - MBH
090 = 7-1/2 Ton 120 = 10 Ton 180 = 15 Ton 240 = 20 Ton 300 = 25 Ton
C00 = Cooling Only
B = 1.5 HP Motor C = 2.0 HP Motor D = 3.0 HP Motor E = 5.0 HP Motor F = 7.5 HP Motor N = None (Motor Drive Kit Reg)
1. Motors are not shipped with 25 ton AH units.
Product Category
Product Identifier
Heat Type & Nominal Heat Capacity
Airflow
1
NC240
C00 B
A
6AAA
2
A = Style A
Product Generation
1 = First Generation 2 = Second Generation
Product Options
AA = No Options Installed EJ = ElectroFin Evaporator Coil TJ = Technicoat Evaporator Coil
Installation Options
A = None C = YCCS Ctrl CV Cooling/Elec Ht D = YCCS Ctrl COBP Cooling/Elec Ht E = YCCS Ctrl CV w/H F = YCCS Ctrl COBP w/H
0
2
0
2
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60 6 = 208/230/460-3-60
2. Models NC/ND240 Airflow Option "F" Only.
2
2
Product Style
Johnson Controls Unitary Products 3
505428-YTG-N-0712

Condensing Unit Features and Benefits

Features
• Meets or exceeds ASHRAE 90.1 standards.
• Scroll compressors provide both high efficiency and reliability.
Simplicity
• Dual refrigerant circuits on PD and YD models.
• Condensing unit coils are constructed of reliable and durable Micro-Channel aluminum tube and fins for long lasting, efficient operation. Mirco-Channel technology provides exceptional durability along with reduced product weight and less refrigerant charge. Heat pumps units are equipped with aluminum fin, copper tube coils providing durability, reliability and value.
• Multiple condensing unit and air handler match-ups provide a wide range of application choices from oversized indoor motors to dual indoor units matched­up with single outdoor units.
• Crankcase heaters that de-energize when compressors are operating.
• Both high and low pressure controls. Since these controls are self-contained, there are no capillary lines to be damaged.
• Internal compressor motor protection.
• Class 2, 24-volt thermostat control circuit protected by a re-settable breaker.
• Standard factory installed service valves.
• Filter-driers are shipped in the unit's control box for field installation in the liquid line leaving the outdoor unit.
• Copper stub-outs are factory mounted on the suction and liquid lines to simplify the field piping connections.
Simplicity® Controls provide stable cooling operation at ambient temperatures down to 40°F with low ambient kits available for operation to 0°F.
• Capacity staging for more economical operation and stable temperature levels within the conditioned space.
Simplicity® Controls prevent the unit from cycling on safety control with “Three Outs” technology preventing nuisance trips, but protecting the equipment when valid operational issues are experienced.
Simplicity® Controls monitor each safety independently (High pressure, low pressure, low voltage) allowing ease of troubleshooting if any problems arise.
• Inherently protected condenser fan motors.
• Technicoat or ElectroFin coated outdoor coils for sea coast or corrosive environment applications.
• Factory installed disconnect to allow power to be removed from the unit when performing periodic maintenance or for service.
• Factory installed powered or non-powered 115 volt GFI outlet.
• Factory installed phase monitor to protect the unit from phase loss or phase reversal.
4 Johnson Controls Unitary Products
®
Controls
Benefits
The Predator® condensing units and heat pumps can be applied on a rooftop or at ground level... due to their ample sub-cooling capacity which allows them to be located three or more stories below the evaporator coil.
After assembly, the unit is pressurized with a combination of Refrigerant R-410A and nitrogen for pressure testing and additional leak testing. During this pressure test, the operation of the high pressure control is checked. As the unit is being evacuated and dehydrated, the operation of the low pressure control is also checked.
Every compressor, condenser fan motor, crankcase heater, and electrical control circuit is checked to assure a trouble­free start-up and years of reliable operation. The condenser fan guards are vinyl-coated to provide additional rust protection and to enhance the appearance of the unit. Compressors are mounted on rubber isolators to reduce the transmission of vibration. Vertical discharge condenser fans direct sound upward and away from any surrounding structures.
All sheet metal parts are constructed of commercial grade galvanized steel. After fabrication, each part is thoroughly cleaned to remove any grease or dirt from its surfaces. The external parts are coated with a powder paint to assure a quality finish for many years. This UL approved coating system has passed the 1000 hour, 20% salt spray test per ASTM Standard B117.
All condensing unit and heat pump models include a 5-year limited warranty on the compressor(s) and 1-year limited warranty on all other parts. The matching line of air handling units carries a 1-year limited parts warranty.

Outdoor Unit Accessories

Coil Guards: Wireform coil guards for added protection of outdoor coils. Designed to mount on each side of the product if required to provide protection from minor impacts or large debris.
Hail Guards: Hood type hail guards designed to protect the outdoor coils from hail. Can be installed on a single side or both to provide protection from storms that may produce hail.
Low Ambient Kits: Kits designed to allow the cooling only units to operate between 0°F and 40°F in the cooling mode. Standard cooling is allowed to 40°F. (Not designed for operation on heat pump units).

Air Handling Unit Features and Benefits

Features
These air handlers can be arranged for a variety of air discharge patterns in either the horizontal or vertical position. Refer to the unit installation instructions for other application possibilities.
Benefits
Air handling units are designed with two distinct modules to provide maximum application flexibility. All are shipped as
505428-YTG-N-0712
single packages with the blower module mounted on top of the coil module. The blower module can be repositioned in the field to meet a large number of vertical and horizontal
BAS Control: York Commercial Comfort System (YCCS) provides split system integration for YCCS single zone, change-over bypass and VAV systems.
applications.
Easy Service: Serviceable expansion valves are provided on The 7.5 thru 20 Ton blower module includes the blower wheels along with factory-mounted motor and drive. The 25 Ton blower module includes the blower wheels with field mounted motor and drives. All models offer two motor horsepower options to meet both standard and high static
every unit. These valves are factory-installed to provide many
years of trouble-free operation. If service is required, it is not
necessary to unbraze any joints. The expansion valves also
include a tee fitting to allow easy installation of hot gas
bypass if required. airflow requirements.
Coil Protection: The indoor coils of these air handlers can The coil module includes direct expansion coils, 2 in. throwaway filters with the option to accept 4” filters, liquid line solenoid valves for capacity reduction, thermal expansion valves, distributors and a non-corrosive, composite
have factory applied Technicoat or Electrofin coating to
provide extended life to the indoor coil in standard
applications and additional corrosion protection on those
applications in sea coast or corrosive environments. condensate drain pan.
Accessories
Every air handling coil is pressurized with air and leak tested under water. After the headers are brazed onto the coil and the coil is installed in the unit, the coil is pressurized with nitrogen for pressure testing and additional leak testing. After the coil is evacuated and dehydrated, it is pressurized with a holding charge of nitrogen for storage and/or shipping.
These air handlers, combined with condensing units, provide years of quiet, efficient and dependable operation. These units are manufactured under ISO 9001 Quality System Certification.
Unit Installation
Units may be bottom-supported or ceiling-suspended and can be arranged to meet almost any space or duct requirements. Each unit is available with a choice of blower motors horsepower and other accessories to make them suitable for most applications.
Air Handling units are available in either two or four pipe configurations from 7.5 to 25 tons. The dual and single circuit options provide a wide variety of application and unit match­up possibilities.
Blower Motors: Different HP motors are available for each unit to meet almost any air delivery requirement. All motors are UL approved, have permanently lubricated ball bearings and are mounted within the insulated cabinet of the units to minimize the transmission of sound to the surrounding space.
1.5-5 HP motors are inherently protected. 7.5 HP motors require motor overload protection.
Overload Relay (7.5HP): These blower motors do not have inherent protection and require external motor overload protection. NC/ND240 "F" models Overload Relays are factory installed. NC300 models Overload Relays are field installed. Power wiring for blower motor is supplied in the Overload Relay Kit. See details in Overload Relay Kit and Overload Relay Setting Tables on Page 70.
Factory-Mounted Components
Part Load Operation: These air handlers with DX (Direct Expansion) coils rated at 10 tons of capacity and above have multiple coils with pre-piped distributors, expansion valves and solenoid valves. Field modifications are not required for part load operations. Capacity reduction not only provides
Base Sections: Base sections can be used to elevate units
above the floor. If desired, a moderate percentage of outdoor
air may be introduced through these sections by cutting an
access opening to accommodate the outdoor air duct
connection. These bases include a durable finish to match
the evaporator blower unit. The base may have to be
insulated for certain applications.
Hot Water Coils: Drainable water coils are available for field
installation between the blower and the coil modules of both
horizontal and vertical units. Since their casings match the
dimensions and the finish of the basic units, they become an
integral part of the unit after installation. The coils slide out of
their casings for easy installation. Hot water coils have
copper tubes that have been mechanically expanded into
aluminum fins. Both headers are located on the same end of
the coil. Coils are leak-tested at 325 psig under water and
dried before their connections are capped for storage and
shipping.
Steam Coils: Steam coils are available for installation
between the blower and coil modules of both horizontal and
vertical units. Since the casing matches the dimensions and
the finish of the basic unit, it becomes an integral part of the
unit after installation. The coil slides out of the casings for
easy installation and is pitched in the casings to facilitate
condensate drainage. The coil has copper tubes that have
been mechanically expanded into aluminum fins. Both
headers are located on the same end of the coil. The coil is
leak-tested at 325 psig and dried before the connections are
capped for storage and shipping.
Bottom Return: Air handling unit can be quickly converted to
bottom return for both vertical and horizontal applications. All
that is required is the removal of several screws and a single
panel on 7.5-15 ton and two panels on the 20 ton AHU.
Optional painted panel can be ordered to cover the side
return opening when utilizing the bottom return.
Supply Air Plenums: These fully insulated plenums are
available for free standing units located within the conditioned
space. They are shipped fully assembled for easy field
installation, are finished to match the exterior of the basic
unit, and include double deflection grills that can be adjusted
to vary the throw, spread and drop of the supply air. economical operation, but also maintains stable temperature
and humidity levels in the conditioned space.
Johnson Controls Unitary Products 5
505428-YTG-N-0712

Guide Specifications

Split System Cooling Only Condensing Units Models: YC090-300, YD120-240 & Split System Heat Pump Models: PC090-240, PD180-240
General
• Factory assembled, single piece, air cooled condensing unit designed for outdoor installation.
• Factory wired, piped, and tested for leakage and functionality to assure trouble-free installation and start­up.
• Rated in accordance with AHRI Standard 340/360.
• Manufactured in a facility registered under the ISO 9002 manufacturing quality standard.
• Designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration and comply with NEC.
• Cooling performance rated in accordance with DOE and AHRI test procedures.
• CSA listed and classified to UL 1995/CAN/CSA No. 236- M90 standards.
• One year limited parts warranty on complete unit with an additional four year compressor warranty.
Unit Operating Characteristics
Operating Range shall be between 125° F to 40° F in cooling as standard from factory.
• The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of _____ F. The power consumption at full load shall not exceed _____ kW.
• The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____ Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at _____ F wet bulb and _____ F dry bulb, and air entering the condensing unit at _____F.
• The system shall have an EER of _____ Btuh/ Watt or greater at standard AHRI conditions.
Unit Construction
• Constructed of zinc-coated, galvanized steel.
• Exterior surfaces bonded and coated with baked enamel finish by a powder paint process capable of withstanding a minimum of 1000 salt spray hours according to ASTM B117.
• Cabinet screws that comply with ASTM B117 salt spray test for a minimum of 750 hours.
• Permanently attached heavy-gage perimeter base rails with forklift slots and lifting holes.
• Removable access panels to all internal components.
• Separate access panel to controls.
• Access panels to allow outdoor coil cleaning.
Compressor(s)
• Hermetic scroll type, internally protected with high­pressure relief and over temperature protection.
• Two stage units operate in 50% capacity increments.
• Suction gas cooled
• Voltage range of ±10% of unit nameplate voltage.
• Neoprene isolators minimize sound transmission and vibration.
• Belly-band crankcase heaters keep refrigerant from diluting sump oil.
• Full charge of compressor oil
Outdoor Condenser Unit Coils
• Draw thru configuration
• Constructed with Micro-channel aluminum fins and aluminum tubing. All refrigerant tubing must share a common header.
Heat Pump Unit Outdoor Unit Coils
• Draw thru configuration
• Constructed with aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.
Condenser Fans
Installer Shall
• Furnish York® air-cooled condensing units, heat pump or equivalent in accordance with the performance schedule shown on the plans, and
• Unit shall be stored and handled in accordance with unit manufacturer's instructions.
• Install each unit as shown on the plans in accordance with the manufacturer’s recommendations and all applicable national and local codes
6 Johnson Controls Unitary Products
• Direct driven propeller-type fans
• Statically and dynamically balanced
• Aluminum blades riveted to corrosion resistant steel spider brackets.
• Arranged for vertical air discharge.
• Equipped with PVC coated steel wire safety guards.
505428-YTG-N-0712
Condenser Motors
• Totally enclosed, air over cooled.
• Inherent overload protection.
• Permanently lubricated bearings.
• Must cycle to allow cooling operation down to 40°F.
Refrigerant Piping
• Solid core filter-drier(s) ship loose for field installation.
• Liquid and suction line service valves with gauge ports.
• Suction and discharge line service ports accessible from unit. Ports capped for leak prevention.
• Liquid line magnetic check valves
• Holding charge of R410A refrigerant.
Electrical Requirements
• Single-point connection electrical power.
• Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits of ____ v to _____ v.
• Condenser fan motors and secondary of transformers shall be grounded.
Unit Controls
• All 24-volt control circuit, powered by a 24 volt transformer(s) and protected by a resettable breaker.
• Conventional thermostat must provide operation for both condensing units and heat pumps without an “O” output from the thermostat.
• Low voltage terminal strip for simple hook-up.
• Compressor motor protection shuts down unit for motor over-current, over-temperature or low voltage conditions.
• Safety lockouts provide reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor:
a. Loss-of-charge/Low-pressure switch. b. High-pressure switch. c. Control board diagnostics and fault code display. d. Safety lockouts send a 24 volt signal to the control
board's "X" terminal, allowing notification to the user via the thermostat fault light (if present).
e. Control board shall retain last 5 fault codes in non-
volatile memory, which will not be lost in the event of a power loss. An LED (light-emitting diode) indicator
flashes a fault code that indicates which safety switch has tripped.
Non-fused Disconnect Switch
• Factory-installed, internally mounted.
• Accessible from outside the unit.
• NEC and UL approved non-fused switch.
• Provides power off lockout capability.
Convenience Outlet
• Factory-installed, internally mounted.
• Accessible from outside the unit.
• 115V, 15 amp GFI receptacle with independent fuse protection.
• Required voltage provided by factory-installed step­down transformer or field supplied 115v circuit.
Low-ambient Head Pressure Control
• Standard operation down to 40 °F without a low ambient kit.
• Operation down to 0°F with a field-installed low ambient kit accessory. The controller modulates the fan motor speed in response to liquid line temperature or pressure.
Coil Guard
Factory or field installed decorative grille shall be placed on the units to protect condenser coil after installation.
Hail Guard Package
Field installed hail guard package shall protect coils against damage from hail and other flying debris.
Coated Condenser Coils
Special phenolic or epoxy polymer coating available as a factory option on both outdoor and indoor coils.
Each Unit Shall Be:
• Covered by a 1-year limited parts warranty on the complete unit and 5-year on compressor(s).
• In current production with published literature available to check performance, limitations, specifications, power requirements, dimensions, operation and appearance.
• Indoor unit shall be equipped with a V-belt drive option that will permit the blower RPM to be adjusted to meet the CFM requirements of the air delivery system. (Refer
Johnson Controls Unitary Products 7
505428-YTG-N-0712
Each Unit Enclosure Shall Have:
• Exterior panels of 18 gauge steel, finished with baked enamel to provide a long lasting quality appearance
• Removable panels to provide easy access to the internal components for maintenance and service on condensing units, heat pumps and air handlers
• Air handling units must have a filter rack that accepts both 2” and 4” filters.
• The dimensions of each unit shall not exceed those specified in the manufacture’s literature.
• The minimum application clearances for condensing units, heat pumps and air handlers must meet those specified in the manufacturer’s literature.
The Blower Motor Shall:
• Be mounted within the insulated cabinet to minimize the transmission of sound to the surrounding space, and any motor 7.5 HP or greater must have a service factor of 1.15.
The Evaporator Coil Shall:
• Consist of copper tubes arranged in staggered rows, mechanically expanded into aluminum fins,
• Be draw-through, and
• Include factory-mounted distributors, expansion valves and solenoid valves for capacity reduction.
The Blower Wheels Shall:
Be dynamically balanced to minimize the levels of sound and vibration generated by the unit.
8 Johnson Controls Unitary Products
505428-YTG-N-0712

Physical Data

YC090 - 300 and YD120 - 240 Physical Data
Single
Scroll
Models
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Component
Nominal Tonnage 7.5 10 10 12.5 12.5 15 15 20 20 25
REFRIGERANT
Refrigerant type R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A Holding charge (lb)
Operating Charge (lb)
DIMENSIONS (inches)
Length 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 Width 31.9 31.9 31.9 31.9 31.9 64.1 64.1 64.1 64.1 64.1 Height 44.5 50.0 50.0 50.0 50.0 44.5 44.5 50.0 50.0 50.0
WEIGHTS (lb)
Shipping 390 499 493 499 493 914 899 945 930 945 Operating 387 497 490 497 490 909 894 942 927 942
COMPRESSORS
Type Quantity 1 121212121
Nominal Capacity (Tons)
Capacity Stages
SYSTEM DATA
No. Refrigeration Circuits 1 121212121 Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 3/8 1 1/8 1 5/8 1 3/8 1 5/8 1 3/8 1 5/8 Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 5/8 7/8 5/8 7/8
OUTDOOR COIL DATA
Face area (Sq. Ft.) 23.8 29.0 29.0 29.0 29.0 47.5 47.5 58.1 58.1 58.1 Rows 1 111111111 Fins per inch 23 23 23 23 23 23 23 23 23 23 Tube diameter (in./MM) 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 Circuitry Type 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass Refrigerant Control --- --- --- --- --- --- --- --- --- ---
CONDENSER FAN DATA
No. Fans / Diameter (in.) 2/24 2/24 2/24 2/24 2/24 4/24 4/24 4/24 4/24 4/24 Type Axial Axial Axial Axial Axial Axial Axial Axial Axial Axial Drive type Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct No. speeds 1 111111111
Number of motors Motor HP (ea.) 1/3 3/4 3/4 3/4 3/4 1/3 1/3 3/4 3/4 3/4
4
Rotation RPM 850 1100 1100 1100 1100 850 850 1100 1100 1100
Nominal CFM
1
Holding Charge is the amount in the unit as shipped from the factory.
2
Includes matched indoor blower unit with 25 ft of piping.
3
All compressors include crankcase heaters.
4
When viewing the shaft end of the motor.
1
(each system)
System #1 14.0 18.0 9.9 24.0 11.5 27.0 13.5 33.5 18.8 35
2
System #2 --- --- 9.9 --- 11.5 --- 13.5 --- 18.8 ---
System #1 7.5 10 5 12.5 6.3 15 7.5 20 10 25 System #2 --- --- 5 --- 6.3 --- 7.5 --- 10 --­System #1 1 212121212 System #2 --- --- 1 --- 1 --- 1 --- 1 ---
3
System #1 2 222242424 System #2 --- --- --- --- --- --- 2 --- 2 ---
System #1 7500 9800 9800 9800 9800 15000 7500 19600 9800 19600 System #2 --- --- --- --- --- --- 7500 --- 9800 ---
YC090 YC120 YD120 YC150 YD150 YC180 YD180 YC240 YD240 YC300
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Single Scroll
CW CW CW CW CW CW CW CW CW CW
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Johnson Controls Unitary Products 9
505428-YTG-N-0712
PC090 - 240 and PD180 - 240 Physical Data
Component
PC090 PC120 PC180 PD180 PD240
Nominal Tonnage 7.5 10 15 15 20
REFRIGERANT
Refrigerant type R-410A R-410A R-410A R-410A R-410A Holding charge (lb)
Operating Charge (lb)
1
1.0 1.0 1.0 1.0 1.0
2
System #1 23.9 27.5 54.0 27.0 34.0 System #2 --- --- --- 27.0 34.0
DIMENSIONS (inches)
Length 59.1 59.1 59.1 59.1 59.1 Width 31.9 31.9 64.1 64.1 64.1 Height 44.5 50.0 44.5 44.5 50.0
WEIGHTS (lb)
Shipping 421 543 947 921 1090 Operating 430 574 968 942 1126
COMPRESSORS
3
Type Single Scroll Tandem Scroll Tandem Scroll Single Scroll Single Scroll Quantity 1 1 1 2 2
Cooling
Nominal Capacity (Tons)
Capacity Stages
System #1 7.5 10 15 7.5 10 System #2 --- --- --- 7.5 10 System #1 1 2 2 1 1 System #2 --- --- --- 1 1
Heating
Nominal Capacity (Tons) System #1 & #2 7.5 10 15 15 20 Capacity Stages System #1 & #2 1 1 1 1 1
SYSTEM DATA
No. Refrigeration Circuits 1 1 1 2 2 Suction Line OD (in.) 1 1/8 1 3/8 1 5/8 1 3/8 1 3/8 Liquid Line OD (in.) 5/8 7/8 7/8 5/8 5/8
OUTDOOR COIL DATA
Face area (Sq. Ft.) 23.8 29.0 47.5 47.5 58.1 Rows 2 2 2 2 2 Fins per inch 20 20 20 20 20 Tube diameter (in./MM) 0.38 / 10 0.38 / 10 0.38 / 10 0.38 / 10 0.38 / 10 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Refrigerant Control TXV TXV TXV TXV TXV
CONDENSER FAN DATA
No. Fans / Diameter (in.) 2/24 2/24 4/24 4/24 4/24 Type Axial Axial Axial Axial Axial Drive type Direct Direct Direct Direct Direct No. speeds 1 1 1 1 1
Number of motors Motor HP (ea.) 1/3 3/4 1/3 1/3 3/4
4
Rotation
System #1 2 2 4 2 2 System #2 --- --- --- 2 2
CW CW CW CW CW
RPM 850 1100 850 850 1100 Nominal CFM
1
Holding Charge is the amount in the unit as shipped from the factory.
2
Includes matched evaporator unit with 25 ft of piping.
3
All compressors include crankcase heaters.
4
When viewing the shaft end of the motor.
System #1 7500 9800 15000 7500 9800 System #2 --- --- --- 7500 9800
Models
10 Johnson Controls Unitary Products
505428-YTG-N-0712
NC090 - 240 and ND120 - 240 Indoor Unit Physical Data
Component
Nominal Tonnage 7 1/2 10 10 15 15 20 20
DIMENSIONS (inches)
Length Width Height
WEIGHTS (lb)
Unit Shipping Unit Operating With Standard Motor and Drive High Static Motor and Drive
INDOOR BLOWER (Forward Curve)
Diameter x Width 12 x 12 15 x 15 15 x 15 18 x 18 18 x 18 15 x 15 15 x 15 Quantity 1 111122
INDOOR COIL
Face area (Sq. Ft.) 10.6 10.6 10.6 18.3 18.3 20.0 20.0 Rows 3 443444 Fins per inch 15 15 15 15 15 15 15 Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Refrigerant Control TXV TXV TXV TXV TXV TXV TXV
SYSTEM DATA
No. Refrigeration Circuits 1 121212 Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 5/8 1 3/8 1 5/8 1 3/8 Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 7/8
FILTERS
Size and Quantity Per Model (In.)
FACE AREA (SQ. FT.) 11.1 11.1 11.1 20.0 20.0 22.2 22.2
Size and Quantity Per Model (In.)
FACE AREA (SQ. FT.) 11.1 11.1 11.1 18.0 18.0 22.2 22.2
16 x 25 x 2 4 4 4 --- --- 8 8 20 x 24 x 2 --- --- --- 6 6 --- ---
16 x 25 x 4 4 4 4 --- --- 8 8 20 x 24 x 4 --- --- --- 6 6 --- ---
NC090 NC120 ND120 NC180 ND180 NC240 ND240
56.0 56.0 56.0 74.5 74.5 98.5 98.5
30.0 30.0 30.0 33.0 33.0 30.0 30.0
65.0 65.0 65.0 75.0 75.0 65.0 65.0
526 573 575 796 796 938 938
498 539 541 764 764 873 873 500 550 552 792 792 903 903
Models
Johnson Controls Unitary Products 11
505428-YTG-N-0712
NC300 Indoor Unit Physical Data
Component
Nominal Tonnage 25
DIMENSIONS (inches)
Length Width Height
WEIGHTS
Unit Shipping Unit Operating With 5 hp Motor and Drive
7.5 hp Motor and Drive
INDOOR BLOWER (Forward Curve)
Diameter x Width 18 X 18 Quantity 2
INDOOR COIL
Face area (Sq. Ft.) 25.8 Rows 4 Fins per inch 16 Tube diameter 3/8 Circuitry Type Interlaced Refrigerant Control TEV
SYSTEM DATA
No. Refrigeration Circuits 1 Suction Line OD (in.) 2 1/8 Liquid Line OD (in.) 7/8
Size and Quantity Per
Model (In.)
FACE AREA (SQ. FT.) 34.7
ACCESSORY
HOT WATER COIL DATA
Face area (Sq. Ft.) 21.2 Rows 2 Fins per inch 12 Tube diameter (Copper) OD (In.) 1/2 Connections (Supply and Return) OD (In.) 1 3/8 Weight (lb) 150
SYSTEM COIL DATA
Face area (Sq. Ft.) 18.2 Rows 1 Fins per inch 8 Tube diameter (Copper) (In.) 1 Connection, (NPTE) (In.) Inlet 2 Outlet 1-1/2 Weight (lb) 160
1
Motors, Drive and Overload Kits must be
FILTERS
1
(lb)
20 x 25 x 2 10
ordered separately for the NC300. The Motor Drive and Overload Kits are to be field installed.
Models
NC300
100.1
38.1
74.6
1067
1130 1157
12 Johnson Controls Unitary Products

Unit Limitations

Condenser Unit limitations
Outdoor DB Temp
Size
(Tons)
090
(7.5)
090
(7.5)
120 (10)
120 (10)
150
(12.5)
180 (15)
180 (15)
240 (20)
240 (20)
300 (25)
Model
PC
YC
PC
YC/YD
YC/YD
PC/PD
YC/YD
PC/PD
YC/YD
YC
Unit Voltage
Applied Voltage
Min Max Max Min
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
1
Cooling (°F)
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
1. Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage. †. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.
Indoor DB Temp
Cooling (°F)
Max Min Max Min Max Min
Outdoor DB Temp
Heating (°F)
505428-YTG-N-0712
Indoor DB Temp
Heating (°F)
Johnson Controls Unitary Products 13
505428-YTG-N-0712
Air Handling Unit Limitations
Entering Air Temperature Degrees °F
Model Power Supply Voltage
Voltage Variation Supply Air Range CFM
Cooling DB/WB
Min. Max. Min. Max. Min. Max. Min. Max.
208/230-3-60 187 253 2,250 3,750 65/57 90/77 40 80
NC090
460-3-60 414 506 2,250 3,750 65/57 90/77 40 80 575-3-60 540 630 2,250 3,750 65/57 90/77 40 80
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
NC120
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80 575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
ND120
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80 575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
NC180
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80 575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
ND180
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80 575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
NC240
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80 575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
ND240
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80 575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
208/230-3-60 187 253 8,000 12,000 65/57 90/77 40 80
NC300
460-3-60 414 506 8,000 12,000 65/57 90/77 40 80 575-3-60 540 630 8,000 12,000 65/57 90/77 40 80
1
Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.
Heating DB
1
14 Johnson Controls Unitary Products
505428-YTG-N-0712

Cooling and Heating Ratings

Cooling And Heating Rating
Condensing Unit Only
Outdoor Unit
PC090 PC120 PC180 PD180 PD240
YC090 85 6.8 12.4 NC090 94 11.2 13.0 --- N/A N/A N/A N/A 3000 YC090 85 6.8 12.4 NC120 99 11.9 13.0 --- N/A N/A N/A N/A 3000 YC120 110 9.3 11.9 NC120 124 11.4 12.5 12.9 N/A N/A N/A N/A 4000 YD120 108 9.1 11.8 ND120 124 11.2 11.2 11.6 N/A N/A N/A N/A 4000 YC150 133 11.6 11.5 NC180 150 11.0 13.3 13.8 N/A N/A N/A N/A 5000 YD150 136 11.5 11.8 ND180 150 11.0 12.1 12.3 N/A N/A N/A N/A 5000 YC180 160 13.4 12.0 NC180 181 11.2 12.2 12.5 N/A N/A N/A N/A 6000 YC180 160 13.4 12.0 NC240 190 11.7 12.7 12.5 N/A N/A N/A N/A 6000 YD180 166 12.3 13.4 ND180 181 11.2 11.6 12.4 N/A N/A N/A N/A 6000 YD180 166 12.3 13.4 (2)NC090 187 11.2 -- -- N/A N/A N/A N/A 6000 YD180 166 12.3 13.4 (2)NC120 187 11.2 -- -- N/A N/A N/A N/A 6000 YD180 166 12.3 13.4 ND240 190 11.7 13.4 11.2 N/A N/A N/A N/A 6000 YC240 233 17.5 13.2 NC240 242 11.3 13.6 13.1 N/A N/A N/A N/A 8000 YD240 222 17.3 12.8 ND240 242 11.3 11.9 12.6 N/A N/A N/A N/A 8000 YD240 222 17.3 12.8 (2)NC120 240 11.6 -- -- N/A N/A N/A N/A 8000 YC300 271 23.7 11.4 NC300 299 10.2 12.2 -- N/A N/A N/A N/A 10000
1
Certified in accordance with the Unitary Large Equipment certification program, which is based on AHRI Standard 340/360. (Except YC300)
2
Condensing unit only ratings are at 45°F SST and 95°F entering-air temperature.
3
Gross capacity does not include heat added by blower motor. Refer to appropriate table for blower horsepower.
4
Heat Pumps designed for matched systems only.
4
4 4 4 4
Gross Capacity
(MBH)
2
KW EER
N/A N/A N/A NC090 92 11.0 11.4 --- 82 3.3 49 2.3 3000 N/A N/A N/A NC120 124 11.0 11.4 11.8 109 3.3 63 2.1 4000 N/A N/A N/A NC180 180 10.6 11.5 12.4 168 3.3 104 2.3 6000 N/A N/A N/A ND180 180 10.6 11.5 12.0 168 3.4 103 2.4 6000 N/A N/A N/A ND240 238 10.6 11.7 12.1 220 3.4 124 2.2 8000
Indoor
Unit
System Cooling Capacity
Gross Capacity
(MBH)
3
EER IEER IPLV
1
Capacity
Heating Capacity High Outdoor Low Outdoor Gross
2
(MBh)
COP
Gross
Capacity
(MBh)
1
2
COP
Rated
Airflow
(CFM)
LEGEND EER = Energy Efficiency Ratio AHRI = Air Conditioning and Refrigeration Institute IPLV = Integration Part-Load Value IEER = Integrated Energy Efficiency Ratio
Johnson Controls Unitary Products 15
505428-YTG-N-0712

Capacity Performance

Condenser and Air Handling Cooling Capacities YC090/NC090
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
WB (°F)
Total
Capacity
(MBh)
77 110.8 6.0 51.5 42.0 32.6 - - - 107.2 6.5 49.8 40.4 30.9 - - ­72 103.3 5.7 66.5 57.0 47.6 38.1 - - 99.9 6.3 64.9 55.4 46.0 36.5 - ­67 95.9 5.5 81.5 72.0 62.6 53.1 43.6 - 92.6 6.2 80.0 70.5 61.0 51.6 42.1 ­62 88.0 5.4 88.0 86.3 76.8 67.3 57.8 48.3 84.8 6.1 84.8 83.9 74.5 65.0 55.5 46.1 57 77.7 5.2 77.7 77.7 72.2 62.8 53.3 43.8 80.1 6.0 80.1 80.1 73.1 63.6 54.2 44.7 77 114.0 6.0 56.3 45.6 34.8 - - - 110.2 6.5 54.6 44.0 33.3 - - ­72 106.3 5.7 72.3 61.6 50.9 40.1 - - 102.7 6.3 70.8 60.2 49.6 38.9 - ­67 98.7 5.4 88.4 77.6 66.9 56.2 45.5 - 95.2 6.2 87.1 76.4 65.8 55.2 44.5 ­62 90.6 5.4 90.6 89.7 82.2 71.9 60.7 50.0 87.1 6.1 87.1 86.7 80.3 69.6 59.0 48.3 57 79.9 5.2 79.9 79.9 77.2 67.3 55.8 45.0 82.3 6.0 82.3 82.3 78.8 68.2 57.5 46.9 77 117.2 5.9 61.0 49.1 37.1 - - - 113.1 6.5 59.4 47.5 35.7 - - ­72 109.3 5.7 78.1 66.2 54.2 42.2 - - 105.4 6.4 76.8 65.0 53.1 41.3 - ­67 101.4 5.4 95.2 83.2 71.3 59.3 47.3 - 97.7 6.2 94.2 82.4 70.5 58.7 46.9 ­62 93.1 5.4 93.1 93.1 87.5 76.5 63.6 51.6 89.5 6.1 89.5 89.5 86.1 74.2 62.4 50.6 57 82.2 5.2 82.2 82.2 82.2 71.7 58.3 46.3 84.5 6.0 84.5 84.5 84.5 72.7 60.8 49.0 72 109.2 5.8 83.0 70.2 57.3 44.4 - - 105.4 6.4 81.6 68.8 56.0 43.2 - ­67 101.3 5.5 98.2 88.2 75.3 62.5 49.6 - 97.7 6.3 96.0 87.2 74.3 61.5 48.7 ­62 93.0 5.5 93.0 93.0 90.2 77.8 64.5 51.6 89.5 6.2 89.5 89.5 87.8 75.0 62.1 49.3 57 82.1 5.3 82.1 82.1 82.1 70.0 56.4 43.5 84.5 6.1 84.5 84.5 84.5 71.7 58.9 46.0 72 109.1 5.9 87.9 74.2 60.4 46.6 - - 105.5 6.5 86.5 72.6 58.8 45.0 - ­67 101.2 5.6 101.2 93.2 79.4 65.7 51.9 - 97.8 6.3 97.8 91.9 78.1 64.3 50.5 ­62 92.9 5.6 92.9 92.9 92.9 79.1 65.3 51.6 89.5 6.2 89.5 89.5 89.5 75.7 61.9 48.1 57 82.0 5.4 82.0 82.0 82.0 68.2 54.4 40.7 84.5 6.1 84.5 84.5 84.5 70.7 56.9 43.1
77 103.7 6.9 48.1 38.7 29.2 - - - 99.2 8.0 47.5 38.1 28.6 - - ­72 96.5 6.9 63.3 53.8 44.4 35.0 - - 92.2 8.0 62.1 52.6 43.2 33.7 - ­67 89.4 6.9 78.4 69.0 59.5 50.1 40.7 - 85.2 8.0 76.6 67.2 57.7 48.3 38.8 ­62 81.6 6.7 81.6 81.6 72.1 62.7 53.3 43.8 77.9 7.7 77.9 77.9 69.2 59.7 50.3 40.9 57 82.5 6.7 82.5 82.5 74.0 64.5 55.1 45.7 78.8 7.8 78.8 78.8 70.0 60.5 51.1 41.6 77 106.4 7.0 52.9 42.3 31.8 - - - 101.7 8.1 53.5 41.7 31.1 - - ­72 99.0 7.0 69.4 58.8 48.2 37.7 - - 94.5 8.1 68.1 57.5 46.9 36.3 - ­67 91.7 6.9 85.8 75.3 64.7 54.1 43.6 - 87.3 8.0 82.8 73.3 62.7 52.1 41.5 ­62 83.7 6.8 83.7 83.7 78.4 67.3 57.2 46.7 79.9 7.8 79.9 79.9 75.2 64.4 54.0 43.4 57 84.6 6.7 84.6 84.6 80.4 69.1 59.2 48.7 80.7 7.9 80.7 80.7 76.1 65.1 54.8 44.2 77 109.0 7.1 57.7 46.0 34.3 - - - 104.1 8.1 59.4 45.4 33.6 - - ­72 101.5 7.0 75.5 63.8 52.1 40.4 - - 96.8 8.1 74.2 62.5 50.7 38.9 - ­67 94.0 7.0 93.3 81.5 69.8 58.1 46.4 - 89.4 8.1 89.0 79.5 67.8 56.0 44.3 ­62 85.8 6.8 85.8 85.8 84.6 72.0 61.2 49.5 81.8 7.9 81.8 81.8 81.2 69.0 57.7 46.0 57 86.8 6.8 86.8 86.8 86.8 73.6 63.4 51.7 82.7 7.9 82.7 82.7 82.1 69.6 58.6 46.9 72 101.7 7.1 80.2 67.5 54.7 41.9 - - 96.9 8.1 79.2 66.3 53.5 40.7 - ­67 94.2 7.0 93.8 86.1 73.3 60.5 47.7 - 89.5 8.1 89.4 83.7 71.5 58.7 45.8 ­62 86.0 6.8 86.0 86.0 85.4 72.1 59.8 47.0 82.0 7.9 82.0 82.0 81.7 68.6 56.0 43.2 57 86.9 6.8 86.9 86.9 86.9 73.4 61.4 48.6 82.8 7.9 82.8 82.8 82.6 69.3 56.9 44.1 72 101.9 7.1 85.0 71.1 57.3 43.4 - - 97.1 8.1 84.1 70.2 56.3 42.4 - ­67 94.3 7.0 94.3 90.7 76.8 62.9 49.1 - 89.7 8.1 89.7 87.9 75.3 61.4 47.4 ­62 86.1 6.9 86.1 86.1 86.1 72.3 58.4 44.5 82.1 7.9 82.1 82.1 82.1 68.2 54.3 40.4 57 87.1 6.9 87.1 87.1 87.1 73.2 59.4 45.5 83.0 7.9 83.0 83.0 83.0 69.1 55.2 41.2
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
16 Johnson Controls Unitary Products
505428-YTG-N-0712
YC090/NC090 (Continued)
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
WB
(°F)
77 94.7 9.0 46.9 37.5 28.0 - - - 90.2 10.1 46.3 36.9 27.4 - - ­72 87.8 9.1 60.9 51.4 42.0 32.5 - - 83.4 10.2 59.7 50.2 40.8 31.3 - ­67 80.9 9.1 74.8 65.4 55.9 46.5 37.0 - 76.7 10.3 73.0 63.6 54.1 44.6 35.2 ­62 74.3 8.8 74.3 74.3 66.2 56.8 47.3 37.9 70.6 9.9 70.6 70.6 63.3 53.8 44.3 34.9 57 75.0 8.9 75.0 75.0 66.0 56.5 47.0 37.6 71.3 10.0 71.3 71.3 61.9 52.5 43.0 33.5 77 97.0 9.1 54.0 41.1 30.5 - - - 92.3 10.1 54.6 40.5 29.8 - - ­72 89.9 9.1 66.9 56.3 45.6 35.0 - - 85.3 10.2 65.7 55.0 44.3 33.7 - ­67 82.8 9.2 79.8 71.4 60.8 50.2 39.5 - 78.4 10.3 76.8 69.5 58.9 48.2 37.5 ­62 76.1 8.8 76.1 76.1 72.0 61.4 50.8 40.1 72.2 9.9 72.2 72.2 68.9 58.4 47.5 36.9 57 76.8 9.0 76.8 76.8 71.7 61.1 50.5 39.8 72.9 10.1 72.9 72.9 67.4 57.1 46.1 35.4 77 99.2 9.1 61.1 44.7 32.9 - - - 94.3 10.2 62.8 44.1 32.2 - - ­72 92.0 9.2 72.9 61.1 49.3 37.5 - - 87.2 10.3 71.7 59.8 47.9 36.1 - ­67 84.8 9.2 84.8 77.5 65.7 53.9 42.1 - 80.2 10.3 80.2 75.5 63.6 51.8 39.9 ­62 77.8 8.9 77.8 77.8 77.8 66.0 54.2 42.4 73.8 9.9 73.8 73.8 73.8 63.0 50.7 38.8 57 78.6 9.0 78.6 78.6 77.5 65.7 53.9 42.1 74.5 10.1 74.5 74.5 72.9 61.8 49.1 37.3 72 92.2 9.2 78.1 65.2 52.3 39.4 - - 87.4 10.2 77.0 64.1 51.2 38.2 - ­67 84.9 9.2 84.9 81.3 69.7 56.8 44.0 - 80.3 10.3 80.3 78.9 67.9 55.0 42.1 ­62 78.0 8.9 78.0 78.0 78.0 65.1 52.2 39.3 74.0 9.9 74.0 74.0 74.0 61.5 48.4 35.4 57 78.7 9.0 78.7 78.7 78.2 65.3 52.4 39.5 74.6 10.1 74.6 74.6 73.8 61.3 47.9 35.0 72 92.3 9.1 83.3 69.3 55.4 41.4 - - 87.5 10.2 82.4 68.4 54.4 40.4 - ­67 85.1 9.2 85.1 85.1 73.8 59.8 45.8 - 80.4 10.3 80.4 80.4 72.2 58.2 44.2 ­62 78.1 8.9 78.1 78.1 78.1 64.1 50.2 36.2 74.1 9.9 74.1 74.1 74.1 60.1 46.1 32.1 57 78.9 9.0 78.9 78.9 78.9 64.9 51.0 37.0 74.8 10.0 74.8 74.8 74.8 60.8 46.8 32.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 17
505428-YTG-N-0712
YC090/NC120
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
Total WB (°F)
77 105.1 6.0 49.2 40.2 31.1 - - - 108.2 6.6 50.3 41.2 32.1 - - ­72 100.1 5.8 63.3 54.2 45.1 36.0 - - 101.4 6.5 63.6 54.6 45.5 36.4 - ­67 95.1 5.7 77.3 68.2 59.1 50.0 40.9 - 94.6 6.3 77.0 67.9 58.8 49.7 40.7 ­62 87.9 5.6 87.9 80.9 71.8 62.7 53.7 44.6 87.7 6.2 87.7 80.9 71.8 62.7 53.7 44.6 57 83.1 5.5 83.1 83.1 76.8 67.7 58.6 49.5 84.1 6.2 84.1 84.1 77.2 68.2 59.1 50.0 77 109.8 6.0 53.6 43.4 33.2 - - - 112.0 6.7 54.5 44.3 34.1 - - ­72 104.5 5.9 68.6 58.3 48.1 37.9 - - 105.0 6.5 68.6 58.4 48.3 38.1 - ­67 99.3 5.7 83.5 73.3 63.1 52.9 42.6 - 97.9 6.4 82.8 72.6 62.4 52.2 42.1 ­62 91.8 5.6 91.8 86.9 76.7 66.8 56.2 46.0 90.7 6.2 90.7 86.4 76.2 66.0 55.8 45.7 57 86.7 5.6 86.7 86.7 82.0 72.3 61.5 51.3 87.1 6.2 87.1 87.1 82.0 71.8 61.6 51.4 77 114.5 6.1 58.0 46.6 35.3 - - - 115.8 6.7 58.7 47.4 36.1 - - ­72 109.0 5.9 73.9 62.5 51.2 39.8 - - 108.5 6.6 73.6 62.3 51.1 39.8 - ­67 103.5 5.8 89.8 78.4 67.1 55.7 44.4 - 101.2 6.4 88.6 77.3 66.0 54.7 43.4 ­62 95.7 5.7 95.7 92.9 81.5 70.8 58.8 47.5 93.8 6.3 93.8 91.9 80.6 69.3 58.0 46.7 57 90.4 5.6 90.4 90.4 87.1 76.9 64.4 53.1 90.0 6.3 90.0 90.0 86.7 75.4 64.1 52.8 72 110.2 6.0 77.6 65.3 53.1 40.8 - - 110.3 6.6 77.7 65.4 53.2 40.9 - ­67 104.6 5.8 94.1 81.8 69.5 57.3 45.0 - 102.9 6.5 93.3 81.0 68.8 56.5 44.3 ­62 96.7 5.7 96.7 95.3 84.5 72.6 60.0 47.7 95.3 6.3 95.3 94.4 84.0 71.7 59.5 47.2 57 91.4 5.6 91.4 91.4 89.8 78.0 65.2 53.0 91.5 6.3 91.5 91.5 89.8 77.6 65.3 53.1 72 111.4 6.0 81.3 68.1 54.9 41.8 - - 112.1 6.6 81.7 68.5 55.3 42.1 - ­67 105.8 5.9 98.4 85.2 72.0 58.8 45.6 - 104.5 6.5 97.9 84.7 71.5 58.3 45.1 ­62 97.8 5.7 97.8 97.8 87.5 74.3 61.1 47.9 96.8 6.4 96.8 96.8 87.3 74.1 60.9 47.7 57 92.4 5.7 92.4 92.4 92.4 79.2 66.0 52.8 93.0 6.3 93.0 93.0 93.0 79.8 66.6 53.4
77 111.4 7.2 51.3 42.3 33.2 - - - 107.2 8.2 49.9 40.9 31.8 - - ­72 102.8 7.1 64.0 54.9 45.9 36.8 - - 99.1 8.0 62.6 53.5 44.5 35.4 - ­67 94.2 7.0 76.7 67.6 58.5 49.5 40.4 - 90.9 7.9 75.3 66.2 57.1 48.1 39.0 ­62 87.4 6.8 87.4 80.9 71.8 62.7 53.6 44.6 84.0 7.8 84.0 79.3 70.2 61.1 52.0 43.0 57 85.2 6.8 85.2 85.2 77.7 68.6 59.6 50.5 82.3 7.7 82.3 82.3 74.9 65.8 56.8 47.7 77 114.2 7.3 55.3 45.2 35.0 - - - 110.2 8.3 53.9 43.8 33.6 - - ­72 105.4 7.2 68.7 58.5 48.4 38.2 - - 101.8 8.1 67.4 57.2 47.0 36.9 - ­67 96.6 7.0 82.1 71.9 61.8 51.6 41.5 - 93.4 8.0 80.8 70.6 60.5 50.3 40.1 ­62 89.6 6.9 89.6 85.9 75.8 65.3 55.5 45.3 86.3 7.9 86.3 83.7 74.3 63.9 53.9 43.8 57 87.4 6.8 87.4 87.4 82.0 71.3 61.7 51.6 84.6 7.8 84.6 84.6 79.3 68.8 58.9 48.8 77 117.1 7.3 59.3 48.1 36.9 - - - 113.1 8.3 58.0 46.7 35.5 - - ­72 108.0 7.2 73.4 62.2 50.9 39.7 - - 104.5 8.2 72.1 60.9 49.6 38.4 - ­67 99.0 7.1 87.5 76.2 65.0 53.8 42.5 - 95.9 8.1 86.3 75.0 63.8 52.5 41.3 ­62 91.9 6.9 91.9 91.0 79.7 67.9 57.3 46.0 88.6 7.9 88.6 88.2 78.3 66.8 55.8 44.6 57 89.6 6.9 89.6 89.6 86.3 74.0 63.8 52.6 86.9 7.8 86.9 86.9 83.6 71.8 61.1 49.8 72 110.4 7.2 77.7 65.5 53.3 41.1 - - 106.7 8.2 76.4 64.2 52.0 39.7 - ­67 101.2 7.1 92.5 80.2 68.0 55.8 43.6 - 97.9 8.1 91.3 79.0 66.8 54.6 42.3 ­62 93.9 7.0 93.9 93.4 83.4 70.9 59.0 46.8 90.5 8.0 90.5 90.3 82.0 69.7 57.6 45.3 57 91.5 6.9 91.5 91.5 89.9 77.1 65.5 53.2 88.7 7.9 88.7 88.7 87.1 74.6 62.6 50.4 72 112.8 7.3 82.1 68.9 55.7 42.4 - - 108.9 8.3 80.8 67.6 54.3 41.1 - ­67 103.3 7.1 97.4 84.2 71.0 57.8 44.6 - 100.0 8.1 96.3 83.0 69.8 56.6 43.4 ­62 95.9 7.0 95.9 95.9 87.1 73.9 60.7 47.5 92.4 8.0 92.4 92.4 85.8 72.5 59.3 46.1 57 93.5 6.9 93.5 93.5 93.5 80.3 67.1 53.9 90.5 7.9 90.5 90.5 90.5 77.3 64.1 50.9
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input (kW)
Sensible Capacity (MBh)
2
18 Johnson Controls Unitary Products
505428-YTG-N-0712
YC090/NC120 (Continued)
Air on
Evaporator Coil
CFM
2250
2625
3000
3375
3750
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
WB
(°F)
77 103.1 9.1 48.5 39.5 30.4 - - - 98.9 10.1 47.1 38.0 29.0 - - ­72 95.4 9.0 61.2 52.1 43.1 34.0 - - 91.6 9.9 59.8 50.7 41.7 32.6 - ­67 87.6 8.9 73.9 64.8 55.8 46.7 37.6 - 84.4 9.8 72.5 63.4 54.4 45.3 36.2 ­62 80.6 8.7 80.6 77.7 68.6 59.5 50.4 41.4 77.2 9.7 77.2 76.0 67.0 57.9 48.8 39.8 57 79.5 8.6 79.5 79.5 72.1 63.0 54.0 44.9 76.6 9.5 76.6 76.6 69.3 60.2 51.2 42.1 77 106.1 9.2 52.6 42.4 32.2 - - - 102.1 10.2 51.2 41.0 30.8 - - ­72 98.2 9.1 66.0 55.9 45.7 35.5 - - 94.6 10.1 64.7 54.5 44.3 34.2 - ­67 90.3 9.0 79.5 69.3 59.1 49.0 38.8 - 87.1 9.9 78.2 68.0 57.8 47.7 37.5 ­62 83.0 8.8 83.0 81.5 72.8 62.6 52.4 42.3 79.7 9.8 79.7 79.3 71.2 61.2 50.9 40.7 57 81.8 8.7 81.8 81.8 76.5 66.3 56.2 46.0 79.0 9.6 79.0 79.0 73.7 63.8 53.4 43.2 77 109.2 9.3 56.6 45.3 34.1 - - - 105.3 10.3 55.2 44.0 32.7 - - ­72 101.0 9.2 70.8 59.6 48.3 37.0 - - 97.5 10.2 69.5 58.3 47.0 35.7 - ­67 92.9 9.1 85.1 73.8 62.5 51.3 40.0 - 89.8 10.1 83.9 72.6 61.3 50.0 38.7 ­62 85.4 8.9 85.4 85.4 76.9 65.7 54.4 43.1 82.2 10.0 82.2 82.2 75.5 64.5 53.0 41.7 57 84.2 8.8 84.2 84.2 80.9 69.6 58.4 47.1 81.5 9.8 81.5 81.5 78.2 67.4 55.6 44.3 72 103.1 9.2 75.2 62.9 50.7 38.4 - - 99.4 10.2 73.9 61.6 49.3 37.1 - ­67 94.7 9.1 90.1 77.8 65.6 53.3 41.1 - 91.5 10.1 88.9 76.6 64.4 52.1 39.8 ­62 87.1 9.0 87.1 87.1 80.7 68.4 56.2 43.9 83.7 10.0 83.7 83.7 79.3 67.2 54.7 42.5 57 85.9 8.8 85.9 85.9 84.2 72.0 59.7 47.5 83.0 9.8 83.0 83.0 81.4 69.4 56.8 44.6 72 105.1 9.2 79.5 66.2 53.0 39.8 - - 101.3 10.2 78.2 64.9 51.7 38.4 - ­67 96.6 9.1 95.1 81.9 68.6 55.4 42.1 - 93.2 10.1 93.2 80.7 67.4 54.2 40.9 ­62 88.8 9.0 88.8 88.8 84.4 71.2 57.9 44.7 85.3 10.0 85.3 85.3 83.1 69.8 56.5 43.3 57 87.6 8.8 87.6 87.6 87.6 74.3 61.1 47.8 84.6 9.8 84.6 84.6 84.6 71.3 58.1 44.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 19
505428-YTG-N-0712
YC120/NC120
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
WB (°F)
77 142.3 7.5 64.7 52.6 40.5 - - - 139.4 8.5 67.1 54.6 42.1 - - ­72 133.9 7.4 84.4 72.2 60.1 48.0 - - 129.5 8.4 85.3 72.8 60.3 47.8 - ­67 125.5 7.3 104.0 91.9 79.8 67.7 55.6 - 119.6 8.3 103.4 90.9 78.5 66.0 53.5 ­62 115.0 7.3 115.0 109.5 94.2 82.0 69.9 57.8 111.3 8.2 111.3 108.6 96.1 83.6 71.1 58.6 57 111.2 7.2 111.2 111.2 99.9 87.8 75.7 63.6 108.8 8.3 108.8 108.8 99.2 86.7 74.2 61.7 77 151.4 7.5 72.3 58.7 45.2 - - - 147.0 8.5 74.2 60.2 46.1 - - ­72 142.4 7.4 94.1 80.6 67.0 53.5 - - 136.6 8.4 94.1 80.0 66.0 51.9 - ­67 133.4 7.3 116.0 102.5 88.9 75.4 61.8 - 126.1 8.3 114.0 99.9 85.9 71.8 57.8 ­62 122.3 7.3 122.3 119.6 105.0 92.1 77.9 64.4 117.4 8.3 117.4 116.1 105.2 91.1 77.1 63.1 57 118.3 7.2 118.3 118.3 111.3 98.6 84.2 70.7 114.8 8.3 114.8 114.8 108.6 94.6 80.5 66.5 77 160.5 7.5 79.8 64.9 49.9 - - - 154.6 8.6 81.3 65.7 50.1 - - ­72 150.9 7.4 103.9 88.9 73.9 59.0 - - 143.7 8.5 102.9 87.3 71.7 56.1 - ­67 141.4 7.3 128.0 113.0 98.0 83.0 68.1 - 132.7 8.4 124.5 108.9 93.3 77.7 62.1 ­62 129.6 7.3 129.6 129.6 115.9 102.2 86.0 71.0 123.5 8.3 123.5 123.5 114.3 98.7 83.1 67.5 57 125.4 7.2 125.4 125.4 122.8 109.5 92.8 77.8 120.7 8.3 120.7 120.7 118.0 102.4 86.8 71.2 72 154.4 7.5 110.8 94.3 77.8 61.4 - - 148.2 8.5 110.7 93.7 76.6 59.6 - ­67 144.7 7.4 138.0 119.7 103.2 86.8 70.3 - 136.9 8.4 132.8 116.7 99.7 82.6 65.6 ­62 132.6 7.3 132.6 132.6 124.4 108.6 91.5 75.0 127.4 8.3 127.4 127.4 122.1 105.1 88.0 70.9 57 128.3 7.3 128.3 128.3 127.0 111.4 94.0 77.6 124.6 8.3 124.6 124.6 123.2 106.1 89.1 72.0 72 157.9 7.5 117.6 99.7 81.7 63.8 - - 152.7 8.5 118.6 100.0 81.5 63.0 - ­67 148.0 7.4 148.0 126.4 108.5 90.5 72.6 - 141.1 8.4 141.1 124.6 106.1 87.6 69.1 ­62 135.6 7.3 135.6 135.6 132.9 114.9 97.0 79.1 131.3 8.3 131.3 131.3 129.9 111.4 92.9 74.4 57 131.2 7.3 131.2 131.2 131.2 113.2 95.3 77.4 128.4 8.4 128.4 128.4 128.4 109.9 91.4 72.8
77 136.4 9.5 69.6 56.7 43.8 - - - 127.0 10.7 66.5 53.5 40.6 - - ­72 125.1 9.4 86.2 73.3 60.5 47.6 - - 117.1 10.7 83.6 70.6 57.7 44.8 - ­67 113.7 9.3 102.9 90.0 77.1 64.2 51.3 - 107.2 10.6 100.7 87.8 74.8 61.9 48.9 ­62 107.7 9.2 107.7 107.7 98.1 85.2 72.3 59.4 100.8 10.5 100.8 100.8 93.7 80.8 67.9 54.9 57 106.5 9.3 106.5 106.5 98.6 85.7 72.8 59.9 100.2 10.6 100.2 100.2 91.6 78.7 65.8 52.8 77 142.6 9.5 76.1 61.6 47.1 - - - 133.4 10.8 75.3 58.7 44.1 - - ­72 130.7 9.4 94.0 79.5 64.9 50.4 - - 123.1 10.7 92.0 77.3 62.7 48.1 - ­67 118.9 9.4 111.9 97.4 82.8 68.3 53.7 - 112.7 10.6 108.7 96.0 81.3 66.7 52.0 ­62 112.6 9.2 112.6 112.6 105.3 90.2 76.3 61.7 106.0 10.5 106.0 106.0 101.9 86.9 72.6 57.9 57 111.3 9.4 111.3 111.3 105.9 90.5 76.8 62.3 105.3 10.6 105.3 105.3 99.5 84.5 70.3 55.6 77 148.8 9.6 82.7 66.5 50.3 - - - 139.9 10.8 84.1 63.9 47.6 - - ­72 136.4 9.5 101.8 85.6 69.4 53.2 - - 129.0 10.7 100.4 84.0 67.7 51.3 - ­67 124.0 9.4 120.9 104.7 88.5 72.3 56.1 - 118.2 10.6 116.6 104.1 87.8 71.5 55.1 ­62 117.4 9.2 117.4 117.4 112.6 95.1 80.2 64.0 111.1 10.5 111.1 111.1 110.0 93.0 77.3 60.9 57 116.1 9.4 116.1 116.1 113.2 95.3 80.8 64.6 110.5 10.6 110.5 110.5 107.4 90.2 74.7 58.4 72 142.0 9.5 110.7 93.0 75.4 57.7 - - 133.3 10.7 109.1 91.2 73.2 55.2 - ­67 129.1 9.4 127.5 113.8 96.1 78.5 60.8 - 122.1 10.6 121.3 112.3 95.0 77.0 59.0 ­62 122.2 9.3 122.2 122.2 119.8 101.5 84.5 66.9 114.8 10.5 114.8 114.8 114.3 96.0 78.3 60.4 57 120.8 9.4 120.8 120.8 119.4 100.9 84.1 66.4 114.1 10.6 114.1 114.1 112.6 94.2 76.7 58.7 72 147.5 9.5 119.5 100.4 81.3 62.2 - - 137.7 10.7 117.9 98.3 78.7 59.1 - ­67 134.1 9.4 134.1 122.8 103.7 84.6 65.5 - 126.1 10.7 126.1 120.4 102.1 82.5 62.9 ­62 127.0 9.3 127.0 127.0 127.0 107.9 88.8 69.7 118.5 10.5 118.5 118.5 118.5 99.0 79.4 59.8 57 125.6 9.4 125.6 125.6 125.6 106.5 87.4 68.3 117.8 10.6 117.8 117.8 117.8 98.2 78.7 59.1
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
20 Johnson Controls Unitary Products
505428-YTG-N-0712
YC120/NC120 (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
1
WB (°F)
77 117.5 12.0 63.4 50.4 37.4 - - - 108.0 13.2 60.3 47.2 34.1 - - ­72 109.1 11.9 81.0 68.0 55.0 41.9 - - 101.2 13.2 78.4 65.3 52.2 39.1 - ­67 100.8 11.9 98.6 85.6 72.6 59.5 46.5 - 94.3 13.1 94.3 83.4 70.3 57.2 44.1 ­62 94.0 11.8 94.0 94.0 89.4 76.4 63.4 50.4 87.2 13.0 87.2 87.2 85.1 72.0 59.0 45.9 57 94.0 11.8 94.0 94.0 84.7 71.7 58.7 45.7 87.8 13.1 87.8 87.8 77.8 64.7 51.7 38.6 77 124.2 12.0 74.4 55.8 41.1 - - - 115.1 13.2 73.6 53.0 38.1 - - ­72 115.4 11.9 89.9 75.2 60.4 45.7 - - 107.7 13.2 87.9 73.1 58.2 43.4 - ­67 106.6 11.9 105.5 94.6 79.8 65.1 50.3 - 100.4 13.1 100.4 93.2 78.3 63.5 48.6 ­62 99.4 11.8 99.4 99.4 98.4 83.6 68.9 54.1 92.8 13.0 92.8 92.8 92.8 80.4 65.2 50.3 57 99.4 11.8 99.4 99.4 93.2 78.5 63.7 49.0 93.5 13.1 93.5 93.5 86.9 72.4 57.2 42.3 77 131.0 12.0 85.5 61.3 44.8 - - - 122.1 13.2 86.9 58.7 42.1 - - ­72 121.7 11.9 98.9 82.4 65.9 49.5 - - 114.3 13.2 97.5 80.8 64.2 47.6 - ­67 112.3 11.9 112.3 103.5 87.1 70.6 54.1 - 106.5 13.1 106.5 103.0 86.3 69.7 53.1 ­62 104.8 11.8 104.8 104.8 107.3 90.8 74.4 57.9 98.5 13.1 98.5 98.5 98.5 88.7 71.4 54.8 57 104.8 11.8 104.8 104.8 101.7 85.2 68.7 52.2 99.2 13.1 99.2 99.2 95.9 80.1 62.7 46.0 72 124.7 11.9 107.6 89.3 71.0 52.8 - - 116.1 13.2 106.1 87.5 68.9 50.3 - ­67 115.2 11.9 115.2 110.8 93.8 75.5 57.2 - 108.2 13.1 108.2 108.2 92.6 74.0 55.4 ­62 107.4 11.8 107.4 107.4 108.7 90.4 72.1 53.8 100.0 13.1 100.0 100.0 100.0 84.9 65.9 47.3 57 107.4 11.8 107.4 107.4 105.9 87.6 69.3 51.0 100.7 13.1 100.7 100.7 99.1 80.9 61.9 43.3 72 127.8 12.0 116.3 96.2 76.1 56.1 - - 117.9 13.2 114.7 94.1 73.6 53.0 - ­67 118.0 11.9 118.0 118.0 100.5 80.4 60.4 - 109.9 13.1 109.9 109.9 98.9 78.4 57.8 ­62 110.1 11.8 110.1 110.1 110.1 90.0 69.9 49.8 101.6 13.0 101.6 101.6 101.6 81.0 60.4 39.9 57 110.1 11.9 110.1 110.1 110.1 90.0 69.9 49.8 102.3 13.1 102.3 102.3 102.3 81.7 61.2 40.6
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 21
505428-YTG-N-0712
YD120/ND120
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
WB (°F)
77 138.1 7.5 63.6 51.7 39.9 - - - 132.8 8.6 62.9 50.8 38.7 - - ­72 130.1 7.4 82.9 71.0 59.2 47.4 - - 124.4 8.4 81.7 69.6 57.5 45.4 - ­67 122.0 7.2 102.2 90.4 78.5 66.7 54.8 - 115.9 8.3 100.6 88.5 76.4 64.3 52.2 ­62 112.3 7.2 112.3 108.5 94.8 83.0 71.1 59.3 106.3 8.2 106.3 104.4 92.3 80.2 68.1 56.0 57 108.2 7.1 108.2 108.6 99.9 88.0 76.2 64.3 105.7 8.2 105.7 105.7 95.1 83.0 70.9 58.8 77 147.1 7.5 70.5 57.3 44.0 - - - 141.3 8.6 70.1 56.5 42.8 - - ­72 138.4 7.4 91.8 78.6 65.3 52.0 - - 132.4 8.4 91.0 77.3 63.6 50.0 - ­67 129.8 7.3 113.1 99.9 86.6 73.3 60.0 - 123.4 8.3 111.9 98.2 84.5 70.8 57.1 ­62 119.5 7.2 119.5 117.6 104.6 91.9 78.0 64.7 113.2 8.2 113.2 112.2 102.1 88.5 74.8 61.1 57 115.1 7.2 115.1 115.4 110.1 97.8 83.6 70.3 112.5 8.2 112.5 112.5 105.3 91.6 77.9 64.2 77 156.0 7.6 77.5 62.8 48.1 - - - 149.9 8.6 77.4 62.1 46.9 - - ­72 146.8 7.4 100.8 86.1 71.4 56.7 - - 140.4 8.4 100.3 85.0 69.8 54.5 - ­67 137.7 7.3 124.1 109.4 94.6 79.9 65.2 - 130.9 8.3 123.2 107.9 92.6 77.4 62.1 ­62 126.8 7.2 126.8 126.8 114.3 100.8 84.9 70.2 120.0 8.2 120.0 120.0 112.0 96.7 81.4 66.2 57 122.1 7.2 122.1 122.1 120.4 107.5 91.0 76.3 119.3 8.2 119.3 119.3 115.4 100.1 84.9 69.6 72 152.4 7.5 108.1 92.0 76.0 60.0 - - 145.8 8.5 107.7 91.1 74.5 57.9 - ­67 142.9 7.3 136.1 116.8 100.8 84.8 68.8 - 135.9 8.3 132.1 115.5 98.9 82.3 65.7 ­62 131.5 7.2 131.5 131.5 123.1 107.7 91.1 75.1 124.6 8.2 124.6 124.6 119.5 102.9 86.3 69.7 57 126.7 7.2 126.7 126.7 125.9 110.8 93.9 77.8 123.9 8.2 123.9 123.9 121.9 105.3 88.7 72.1 72 157.9 7.5 115.3 98.0 80.7 63.4 - - 151.2 8.5 115.2 97.2 79.2 61.2 - ­67 148.1 7.4 148.1 124.3 107.0 89.7 72.4 - 141.0 8.3 141.0 123.1 105.1 87.2 69.2 ­62 136.3 7.3 136.3 136.3 132.0 114.6 97.3 80.0 129.3 8.3 129.3 129.3 127.1 109.1 91.1 73.1 57 131.3 7.3 131.3 131.3 131.3 114.0 96.7 79.4 128.5 8.2 128.5 128.5 128.5 110.5 92.5 74.6
77 127.4 9.6 62.2 49.8 37.4 - - - 122.1 10.8 60.4 48.0 35.6 - - ­72 118.7 9.5 80.6 68.2 55.9 43.5 - - 112.7 10.7 78.3 65.8 53.4 41.0 - ­67 109.9 9.3 99.0 86.6 74.3 61.9 49.5 - 103.2 10.6 96.1 83.7 71.2 58.8 46.4 ­62 100.4 9.2 100.4 100.4 89.8 77.5 65.1 52.7 95.0 10.5 95.0 95.0 86.6 74.1 61.7 49.3 57 103.2 9.2 103.2 102.8 90.4 78.0 65.7 53.3 98.1 10.5 98.1 97.9 85.4 73.0 60.5 48.1 77 135.6 9.6 69.7 55.6 41.6 - - - 129.2 10.8 70.6 53.8 39.6 - - ­72 126.3 9.5 90.2 76.1 62.0 47.9 - - 119.2 10.7 87.9 73.7 59.5 45.3 - ­67 116.9 9.3 110.6 96.6 82.5 68.4 54.3 - 109.2 10.6 105.2 93.6 79.4 65.2 51.0 ­62 106.8 9.2 106.8 106.8 99.7 85.0 71.5 57.4 100.5 10.5 100.5 100.5 96.5 82.0 68.1 53.9 57 109.9 9.2 109.9 109.6 100.4 85.4 72.2 58.1 103.8 10.5 103.8 103.6 95.2 80.5 66.8 52.6 77 143.8 9.6 77.3 61.5 45.7 - - - 136.2 10.8 80.8 59.7 43.7 - - ­72 133.9 9.5 99.8 84.0 68.2 52.3 - - 125.7 10.7 97.5 81.6 65.6 49.6 - ­67 124.0 9.3 122.3 106.5 90.6 74.8 59.0 - 115.1 10.6 114.3 103.5 87.5 71.6 55.6 ­62 113.3 9.2 113.3 113.3 109.6 92.6 78.0 62.2 106.0 10.5 106.0 106.0 106.4 89.8 74.4 58.5 57 116.5 9.2 116.5 116.5 110.3 92.7 78.7 62.9 109.4 10.5 109.4 109.4 104.9 88.1 73.0 57.1 72 139.2 9.5 107.4 90.2 72.9 55.7 - - 131.0 10.7 105.2 87.7 70.3 52.8 - ­67 128.9 9.3 128.0 114.2 97.0 79.7 62.5 - 120.1 10.6 119.6 111.2 93.7 76.3 58.8 ­62 117.7 9.2 117.7 117.7 115.9 98.1 81.4 64.2 110.5 10.5 110.5 110.5 110.7 92.9 75.8 58.3 57 121.1 9.2 121.1 121.1 118.0 99.9 83.5 66.3 114.1 10.5 114.1 114.1 111.8 93.9 76.9 59.4 72 144.5 9.5 115.0 96.3 77.7 59.0 - - 136.4 10.7 112.9 93.9 74.9 56.0 - ­67 133.8 9.3 133.8 121.9 103.3 84.6 66.0 - 125.0 10.6 125.0 118.9 99.9 81.0 62.0 ­62 122.2 9.2 122.2 122.2 122.2 103.5 84.9 66.2 115.0 10.5 115.0 115.0 115.0 96.1 77.1 58.1 57 125.7 9.2 125.7 125.7 125.7 107.0 88.4 69.7 118.7 10.5 118.7 118.7 118.7 99.8 80.8 61.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
22 Johnson Controls Unitary Products
505428-YTG-N-0712
YD120/ND120 (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
1
WB (°F)
77 116.8 12.1 58.7 46.2 33.7 - - - 111.5 13.3 57.0 44.4 31.8 - - ­72 106.7 11.9 75.9 63.4 50.9 38.4 - - 100.7 13.2 73.6 61.1 48.5 35.9 - ­67 96.6 11.8 93.2 80.7 68.2 55.7 43.2 - 89.9 13.1 89.9 77.7 65.1 52.6 40.0 ­62 89.7 11.7 89.7 89.7 83.3 70.8 58.3 45.8 84.4 12.9 84.4 84.4 80.0 67.5 54.9 42.3 57 93.0 11.7 93.0 92.9 80.4 67.9 55.4 42.9 87.9 12.9 87.9 87.9 75.5 62.9 50.3 37.8 77 122.7 12.1 71.5 52.0 37.7 - - - 116.2 13.3 72.4 50.2 35.8 - - ­72 112.1 11.9 85.6 71.3 57.0 42.7 - - 105.0 13.2 83.3 68.9 54.5 40.1 - ­67 101.4 11.8 99.7 90.6 76.3 62.0 47.7 - 93.7 13.1 93.7 87.6 73.2 58.8 44.4 ­62 94.2 11.7 94.2 94.2 93.2 78.9 64.6 50.3 88.0 12.9 88.0 88.0 88.0 75.8 61.1 46.7 57 97.7 11.7 97.7 97.6 90.0 75.7 61.4 47.1 91.5 13.0 91.5 91.5 84.8 70.9 56.0 41.6 77 128.6 12.1 84.3 57.8 41.7 - - - 120.9 13.3 87.7 56.0 39.7 - - ­72 117.4 11.9 95.3 79.2 63.1 46.9 - - 109.2 13.2 93.0 76.8 60.5 44.2 - ­67 106.3 11.8 106.3 100.5 84.4 68.3 52.2 - 97.4 13.1 97.4 97.4 81.3 65.0 48.8 ­62 98.8 11.7 98.8 98.8 103.1 87.0 70.9 54.8 91.5 12.9 91.5 91.5 91.5 84.2 67.3 51.1 57 102.3 11.7 102.3 102.3 99.6 83.5 67.3 51.2 95.2 13.0 95.2 95.2 94.2 78.8 61.7 45.4 72 122.9 12.0 103.0 85.3 67.6 49.9 - - 114.7 13.2 100.8 82.9 65.0 47.0 - ­67 111.2 11.8 111.2 108.2 90.5 72.8 55.1 - 102.4 13.1 102.4 102.4 87.3 69.3 51.4 ­62 103.3 11.7 103.3 103.3 105.5 87.8 70.1 52.4 96.1 12.9 96.1 96.1 96.1 82.6 64.4 46.5 57 107.1 11.7 107.1 107.1 105.7 88.0 70.3 52.6 100.0 13.0 100.0 100.0 99.5 82.0 63.6 45.7 72 128.3 12.0 110.8 91.5 72.2 52.9 - - 120.2 13.3 108.7 89.0 69.4 49.8 - ­67 116.1 11.9 116.1 115.9 96.6 77.3 58.0 - 107.3 13.2 107.3 107.3 93.3 73.7 54.1 ­62 107.9 11.7 107.9 107.9 107.9 88.6 69.3 50.0 100.7 13.0 100.7 100.7 100.7 81.1 61.5 41.9 57 111.8 11.8 111.8 111.8 111.8 92.5 73.2 53.9 104.8 13.0 104.8 104.8 104.8 85.2 65.6 46.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 23
505428-YTG-N-0712
YC150/NC180
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
WB (°F)
77 178.5 10.2 87.6 71.1 54.7 - - - 172.2 11.3 84.0 67.6 51.2 - - ­72 168.2 9.9 111.9 95.4 78.9 62.4 - - 161.2 11.0 108.3 91.9 75.5 59.2 - ­67 157.9 9.6 136.1 119.6 103.1 86.7 70.2 - 150.1 10.7 132.5 116.2 99.8 83.4 67.1 ­62 144.8 9.4 144.8 144.8 129.3 112.8 96.3 79.8 138.9 10.6 138.9 138.9 126.4 110.1 93.7 77.3 57 149.7 9.5 149.7 149.7 137.7 121.2 104.7 88.3 143.9 10.7 143.9 143.9 130.6 114.3 97.9 81.5 77 184.7 10.2 94.2 77.2 58.5 - - - 177.6 11.3 92.4 73.7 55.0 - - ­72 174.0 9.9 121.8 103.1 84.4 65.7 - - 166.2 11.0 118.4 99.8 81.1 62.4 - ­67 163.4 9.6 149.5 129.0 110.3 91.6 72.9 - 154.7 10.8 144.5 125.8 107.1 88.4 69.8 ­62 149.9 9.4 149.9 149.9 138.2 119.8 100.8 82.1 143.2 10.6 143.2 143.2 135.7 117.0 98.4 79.7 57 154.9 9.5 154.9 154.9 147.3 129.1 109.8 91.1 148.4 10.7 148.4 148.4 140.2 121.6 102.9 84.2 77 190.9 10.3 100.7 83.2 62.3 - - - 182.9 11.3 100.8 79.8 58.8 - - ­72 179.9 9.9 131.8 110.8 89.9 68.9 - - 171.2 11.0 128.6 107.6 86.6 65.6 - ­67 168.8 9.6 162.9 138.4 117.5 96.5 75.5 - 159.4 10.8 156.5 135.5 114.5 93.5 72.5 ­62 154.9 9.4 154.9 154.9 147.2 126.8 105.3 84.3 147.5 10.6 147.5 147.5 145.0 124.0 103.0 82.0 57 160.1 9.6 160.1 160.1 156.9 137.0 114.9 94.0 152.9 10.7 152.9 152.9 149.8 128.8 107.8 86.8 72 182.3 10.1 142.7 119.7 96.7 73.7 - - 174.1 11.2 139.0 116.1 93.1 70.2 - ­67 171.1 9.8 168.1 149.4 126.4 103.4 80.4 - 162.1 10.9 160.6 146.0 123.1 100.1 77.2 ­62 157.0 9.6 157.0 157.0 153.1 130.4 107.1 84.1 150.0 10.7 150.0 150.0 148.8 125.8 102.9 79.9 57 162.2 9.7 162.2 162.2 160.6 138.1 114.6 91.6 155.5 10.8 155.5 155.5 153.9 131.0 108.1 85.1 72 184.7 10.2 153.7 128.6 103.6 78.5 - - 177.0 11.3 149.4 124.5 99.7 74.8 - ­67 173.4 9.9 173.4 160.4 135.4 110.4 85.3 - 164.8 11.0 164.8 156.6 131.7 106.8 81.9 ­62 159.0 9.7 159.0 159.0 159.0 134.0 108.9 83.9 152.5 10.8 152.5 152.5 152.5 127.6 102.7 77.8 57 164.4 9.8 164.4 164.4 164.4 139.3 114.3 89.2 158.1 10.9 158.1 158.1 158.1 133.2 108.3 83.4
77 166.0 12.3 80.3 64.1 47.8 - - - 159.9 14.1 79.0 62.8 46.6 - - ­72 154.1 12.1 104.7 88.4 72.2 55.9 - - 148.2 13.8 102.8 86.6 70.4 54.2 - ­67 142.3 11.9 129.0 112.7 96.5 80.2 64.0 - 136.4 13.5 126.7 110.5 94.2 78.0 61.8 ­62 132.9 11.7 132.9 132.9 123.6 107.4 91.1 74.9 130.6 13.4 130.6 130.6 122.0 105.8 89.6 73.4 57 138.2 11.8 138.2 138.2 123.6 107.3 91.1 74.8 134.7 13.5 134.7 134.7 119.4 103.2 87.0 70.8 77 170.5 12.3 90.6 70.2 51.6 - - - 163.0 14.0 91.5 68.6 50.0 - - ­72 158.3 12.1 115.0 96.4 77.8 59.1 - - 151.0 13.7 112.8 94.2 75.6 56.9 - ­67 146.1 11.9 139.5 122.6 104.0 85.3 66.7 - 139.1 13.5 134.2 119.8 101.2 82.5 63.9 ­62 136.5 11.7 136.5 136.5 133.2 114.3 95.9 77.3 133.1 13.4 133.1 133.1 130.9 112.1 93.6 75.0 57 142.0 11.8 142.0 142.0 133.2 114.0 95.9 77.3 137.3 13.5 137.3 137.3 128.1 109.2 90.9 72.2 77 175.0 12.3 100.8 76.3 55.3 - - - 166.1 13.9 104.0 74.4 53.4 - - ­72 162.5 12.1 125.4 104.4 83.4 62.3 - - 153.9 13.7 122.9 101.8 80.7 59.6 - ­67 150.0 11.9 150.0 132.5 111.5 90.4 69.4 - 141.7 13.4 141.7 129.1 108.1 87.0 65.9 ­62 140.1 11.7 140.1 140.1 142.8 121.2 100.7 79.7 135.6 13.3 135.6 135.6 139.8 118.5 97.7 76.6 57 145.7 11.8 145.7 145.7 142.8 120.7 100.7 79.7 140.0 13.4 140.0 140.0 136.9 115.3 94.8 73.7 72 165.9 12.2 135.3 112.4 89.5 66.7 - - 157.7 13.8 133.0 110.0 87.1 64.2 - ­67 153.1 12.0 153.1 142.6 119.7 96.8 73.9 - 145.2 13.5 145.2 138.0 116.6 93.7 70.8 ­62 143.1 11.8 143.1 143.1 144.4 121.2 98.6 75.7 138.9 13.4 138.9 138.9 141.0 118.0 95.2 72.3 57 148.7 11.9 148.7 148.7 147.3 123.9 101.5 78.6 143.4 13.5 143.4 143.4 141.8 118.6 96.0 73.1 72 169.3 12.3 145.2 120.5 95.7 71.0 - - 161.4 14.0 143.0 118.3 93.5 68.7 - ­67 156.3 12.1 156.3 152.7 128.0 103.2 78.5 - 148.6 13.7 148.6 146.9 125.2 100.4 75.6 ­62 146.0 11.9 146.0 146.0 146.0 121.3 96.5 71.8 142.2 13.6 142.2 142.2 142.2 117.5 92.7 67.9 57 151.8 12.0 151.8 151.8 151.8 127.0 102.3 77.6 146.8 13.7 146.8 146.8 146.8 122.0 97.2 72.5
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
24 Johnson Controls Unitary Products
505428-YTG-N-0712
YC150/NC180 (Continued)
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
1
WB (°F)
77 153.8 15.8 77.6 61.4 45.3 - - - 147.7 17.5 76.3 60.1 44.0 - - ­72 142.2 15.5 101.0 84.8 68.7 52.5 - - 136.2 17.2 99.2 83.0 66.9 50.8 - ­67 130.5 15.1 124.4 108.2 92.0 75.9 59.7 - 124.7 16.8 122.1 105.9 89.8 73.7 57.6 ­62 128.2 15.1 128.2 128.2 120.4 104.2 88.0 71.9 125.8 16.8 125.8 125.8 118.7 102.6 86.5 70.4 57 131.2 15.2 131.2 131.2 115.2 99.0 82.8 66.7 127.8 17.0 127.8 127.8 111.0 94.9 78.7 62.6 77 155.5 15.7 92.3 67.0 48.4 - - - 148.1 17.3 93.2 65.4 46.8 - - ­72 143.8 15.3 110.6 92.0 73.4 54.7 - - 136.5 17.0 108.4 89.8 71.2 52.5 - ­67 132.0 15.0 128.9 117.0 98.3 79.7 61.1 - 125.0 16.6 123.7 114.2 95.5 76.9 58.3 ­62 129.7 15.0 129.7 129.7 128.6 110.0 91.3 72.7 126.2 16.7 126.2 126.2 126.2 107.8 89.1 70.4 57 132.7 15.1 132.7 132.7 123.1 104.4 85.8 67.2 128.1 16.8 128.1 128.1 118.0 99.7 80.8 62.1 77 157.3 15.5 107.1 72.6 51.5 - - - 148.4 17.1 110.2 70.7 49.6 - - ­72 145.4 15.2 120.3 99.2 78.1 57.0 - - 136.8 16.8 117.7 96.6 75.4 54.3 - ­67 133.5 14.9 133.5 125.8 104.7 83.6 62.5 - 125.2 16.4 125.2 122.4 101.3 80.1 59.0 ­62 131.1 14.9 131.1 131.1 136.9 115.8 94.7 73.6 126.6 16.5 126.6 126.6 126.6 113.1 91.6 70.5 57 134.2 15.0 134.2 134.2 131.0 109.9 88.8 67.7 128.5 16.6 128.5 128.5 125.1 104.5 82.8 61.7 72 149.5 15.4 130.6 107.6 84.7 61.7 - - 141.3 17.0 128.2 105.2 82.3 59.3 - ­67 137.3 15.1 137.3 133.4 113.5 90.6 67.6 - 129.3 16.6 129.3 128.8 110.4 87.5 64.5 ­62 134.8 15.1 134.8 134.8 137.7 114.7 91.8 68.8 130.7 16.7 130.7 130.7 130.7 111.5 88.4 65.4 57 138.0 15.2 138.0 138.0 136.4 113.4 90.5 67.5 132.6 16.8 132.6 132.6 130.9 108.2 84.9 62.0 72 153.6 15.6 140.9 116.1 91.3 66.5 - - 145.7 17.2 138.7 113.9 89.1 64.3 - ­67 141.0 15.3 141.0 141.0 122.4 97.6 72.8 - 133.4 16.8 133.4 133.4 119.6 94.8 69.9 ­62 138.5 15.3 138.5 138.5 138.5 113.7 88.9 64.1 134.7 16.9 134.7 134.7 134.7 109.9 85.1 60.2 57 141.8 15.4 141.8 141.8 141.8 117.0 92.2 67.4 136.7 17.1 136.7 136.7 136.7 111.9 87.1 62.3
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 25
505428-YTG-N-0712
YD150/ND180
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
WB (°F)
77 170.2 10.0 80.1 64.2 48.3 - - - 173.7 11.0 81.5 65.4 49.3 - - ­72 164.1 9.7 106.1 90.2 74.3 58.4 - - 161.9 10.8 105.7 89.6 73.5 57.5 - ­67 157.9 9.5 132.0 116.1 100.2 84.3 68.5 - 150.1 10.6 129.8 113.8 97.7 81.7 65.6 ­62 142.4 9.3 142.4 140.8 122.7 106.8 90.9 75.1 139.3 10.4 139.3 138.5 122.4 106.4 90.3 74.2 57 141.3 9.3 141.3 141.3 129.9 114.0 98.1 82.2 140.0 10.4 140.0 140.0 127.0 111.0 94.9 78.8 77 182.4 10.0 89.5 72.3 53.8 - - - 182.2 11.1 91.1 72.7 54.3 - - ­72 175.5 9.7 119.7 101.2 82.7 64.2 - - 169.8 10.9 117.7 99.3 80.8 62.4 - ­67 168.7 9.5 149.8 130.0 111.5 93.0 74.5 - 157.4 10.7 144.3 125.9 107.4 89.0 70.5 ­62 152.3 9.4 152.3 151.5 136.6 118.9 99.7 81.2 146.1 10.5 146.1 145.7 134.6 116.1 97.7 79.2 57 151.2 9.3 151.2 151.2 144.6 126.8 107.6 89.1 146.8 10.5 146.8 146.8 139.7 121.2 102.8 84.3 77 194.5 10.0 98.9 80.4 59.3 - - - 190.7 11.1 100.8 80.0 59.2 - - ­72 187.0 9.8 133.3 112.2 91.1 70.0 - - 177.7 10.9 129.8 109.0 88.2 67.3 - ­67 179.5 9.5 167.6 143.9 122.8 101.7 80.6 - 164.8 10.7 158.8 138.0 117.1 96.3 75.5 ­62 162.2 9.4 162.2 162.2 150.6 131.0 108.4 87.3 152.9 10.5 152.9 152.9 146.8 125.9 105.1 84.3 57 161.1 9.4 161.1 161.1 159.2 139.6 117.0 95.9 153.7 10.5 153.7 153.7 152.3 131.4 110.6 89.8 72 187.6 9.8 141.9 119.6 97.2 74.8 - - 180.7 11.0 140.5 117.9 95.3 72.8 - ­67 180.3 9.6 174.3 153.5 131.1 108.7 86.4 - 167.5 10.8 164.6 149.3 126.7 104.1 81.5 ­62 162.8 9.5 162.8 162.8 156.9 135.3 112.2 89.8 155.4 10.6 155.4 155.4 152.4 129.8 107.2 84.7 57 161.6 9.4 161.6 161.6 160.7 139.0 115.9 93.5 156.3 10.6 156.3 156.3 155.6 133.0 110.4 87.8 72 188.2 9.9 150.6 126.9 103.3 79.6 - - 183.7 11.0 151.2 126.8 102.5 78.2 - ­67 181.0 9.7 181.0 163.0 139.4 115.7 92.1 - 170.3 10.8 170.3 160.6 136.2 111.9 87.6 ­62 163.3 9.5 163.3 163.3 163.3 139.7 116.0 92.3 158.0 10.6 158.0 158.0 158.0 133.7 109.4 85.1 57 162.1 9.5 162.1 162.1 162.1 138.5 114.8 91.1 158.8 10.6 158.8 158.8 158.8 134.5 110.2 85.9
77 177.3 12.0 82.9 66.6 50.4 - - - 162.9 13.7 78.3 62.1 45.9 - - ­72 159.8 11.9 105.3 89.0 72.8 56.6 - - 149.2 13.5 101.4 85.2 69.0 52.8 - ­67 142.3 11.8 127.7 111.4 95.2 79.0 62.7 - 135.4 13.3 124.6 108.4 92.2 76.0 59.7 ­62 136.2 11.5 136.2 136.2 122.1 105.9 89.7 73.4 128.0 13.0 128.0 128.0 118.2 102.0 85.7 69.5 57 138.7 11.5 138.7 138.7 124.1 107.9 91.7 75.5 131.1 13.1 131.1 131.1 116.6 100.4 84.2 68.0 77 182.1 12.1 92.8 73.1 54.7 - - - 168.7 13.7 90.6 68.8 50.3 - - ­72 164.1 12.0 115.8 97.4 79.0 60.6 - - 154.5 13.5 112.8 94.2 75.6 57.1 - ­67 146.2 11.9 138.8 121.7 103.3 84.9 66.5 - 140.3 13.4 134.9 119.6 101.0 82.4 63.9 ­62 139.8 11.6 139.8 139.8 132.5 113.4 95.7 77.3 132.6 13.1 132.6 132.6 129.5 110.6 92.4 73.8 57 142.5 11.6 142.5 142.5 134.7 115.6 97.9 79.5 135.8 13.2 135.8 135.8 127.7 108.8 90.6 72.1 77 186.8 12.2 102.7 79.6 59.0 - - - 174.5 13.8 103.0 75.6 54.7 - - ­72 168.4 12.1 126.4 105.8 85.2 64.7 - - 159.9 13.6 124.1 103.2 82.3 61.3 - ­67 150.0 12.0 150.0 132.0 111.5 90.9 70.3 - 145.2 13.4 145.2 130.8 109.9 88.9 68.0 ­62 143.5 11.7 143.5 143.5 142.9 120.8 101.8 81.2 137.2 13.1 137.2 137.2 140.9 119.2 99.0 78.1 57 146.2 11.7 146.2 146.2 145.3 123.3 104.2 83.6 140.5 13.2 140.5 140.5 138.9 117.2 97.1 76.2 72 173.8 12.1 139.0 116.3 93.5 70.7 - - 164.1 13.6 136.3 113.3 90.3 67.2 - ­67 154.8 12.0 154.8 145.1 122.3 99.5 76.7 - 149.0 13.5 149.0 141.4 120.5 97.5 74.5 ­62 148.1 11.7 148.1 148.1 147.8 124.3 102.3 79.5 140.7 13.2 140.7 140.7 142.6 119.2 96.6 73.5 57 150.9 11.7 150.9 150.9 150.4 126.9 104.9 82.1 144.2 13.2 144.2 144.2 143.4 120.0 97.3 74.3 72 179.2 12.1 151.7 126.8 101.8 76.8 - - 168.3 13.7 148.5 123.4 98.3 73.1 - ­67 159.6 12.0 159.6 158.1 133.1 108.1 83.2 - 152.8 13.5 152.8 152.0 131.2 106.1 81.0 ­62 152.7 11.7 152.7 152.7 152.7 127.7 102.8 77.8 144.3 13.2 144.3 144.3 144.3 119.2 94.1 69.0 57 155.6 11.7 155.6 155.6 155.6 130.6 105.6 80.6 147.8 13.3 147.8 147.8 147.8 122.7 97.6 72.5
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
26 Johnson Controls Unitary Products
505428-YTG-N-0712
YD150/ND180 (Continued)
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
1
WB (°F)
77 148.6 15.3 73.8 57.6 41.4 - - - 134.2 17.0 69.2 53.1 36.9 - - ­72 138.6 15.1 97.6 81.4 65.3 49.1 - - 128.0 16.7 93.8 77.6 61.5 45.3 - ­67 128.6 14.8 121.5 105.3 89.1 72.9 56.7 - 121.7 16.3 118.3 102.2 86.0 69.9 53.7 ­62 119.7 14.5 119.7 119.7 114.2 98.0 81.8 65.7 111.5 16.0 111.5 111.5 110.2 94.1 77.9 61.8 57 123.4 14.7 123.4 123.4 109.0 92.8 76.7 60.5 115.7 16.3 115.7 115.7 101.5 85.3 69.2 53.0 77 155.4 15.4 88.5 64.6 45.9 - - - 142.1 17.0 86.4 60.4 41.5 - - ­72 145.0 15.1 109.7 91.0 72.3 53.6 - - 135.4 16.6 106.7 87.8 68.9 50.0 - ­67 134.5 14.8 130.9 117.4 98.7 80.0 61.2 - 128.7 16.3 127.0 115.2 96.4 77.5 58.6 ­62 125.3 14.5 125.3 125.3 126.5 107.8 89.0 70.3 118.0 16.0 118.0 118.0 118.0 105.0 85.7 66.8 57 129.1 14.7 129.1 129.1 120.7 102.0 83.3 64.6 122.4 16.3 122.4 122.4 113.8 95.2 76.0 57.1 77 162.3 15.4 103.2 71.6 50.3 - - - 150.0 16.9 103.5 67.6 46.0 - - ­72 151.3 15.1 121.8 100.6 79.3 58.0 - - 142.8 16.6 119.6 98.0 76.3 54.7 - ­67 140.4 14.8 140.4 129.5 108.3 87.0 65.7 - 135.6 16.3 135.6 128.3 106.7 85.1 63.5 ­62 130.8 14.5 130.8 130.8 138.8 117.5 96.2 75.0 124.4 16.0 124.4 124.4 124.4 115.8 93.5 71.9 57 134.8 14.7 134.8 134.8 132.5 111.2 90.0 68.7 129.0 16.2 129.0 129.0 126.0 105.2 82.8 61.2 72 154.3 15.2 133.5 110.3 87.0 63.8 - - 144.6 16.7 130.8 107.3 83.8 60.3 - ­67 143.2 14.9 143.2 137.8 118.8 95.5 72.3 - 137.4 16.4 137.4 134.1 117.1 93.6 70.1 ­62 133.4 14.6 133.4 133.4 137.4 114.1 90.8 67.6 126.0 16.1 126.0 126.0 126.0 109.0 85.1 61.6 57 137.4 14.8 137.4 137.4 136.3 113.0 89.8 66.5 130.7 16.3 130.7 130.7 129.2 106.1 82.2 58.7 72 157.3 15.3 145.3 120.0 94.7 69.5 - - 146.4 16.8 142.0 116.6 91.2 65.8 - ­67 146.0 15.0 146.0 146.0 129.3 104.1 78.8 - 139.2 16.5 139.2 139.2 127.5 102.1 76.7 ­62 136.0 14.7 136.0 136.0 136.0 110.7 85.4 60.2 127.6 16.2 127.6 127.6 127.6 102.2 76.8 51.4 57 140.1 14.9 140.1 140.1 140.1 114.8 89.6 64.3 132.4 16.5 132.4 132.4 132.4 107.0 81.6 56.2
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 27
505428-YTG-N-0712
YC180/NC180
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
77 223.5 11.8 104.0 85.0 66.0 - - - 214.6 13.1 101.2 82.2 63.3 - - ­72 207.2 11.5 132.3 113.3 94.4 75.4 - - 198.3 12.8 129.0 110.1 91.2 72.2 - ­67 191.0 11.1 160.6 141.7 122.7 103.7 84.7 - 181.9 12.4 156.8 137.9 119.0 100.1 81.1 ­62 176.0 10.8 176.0 171.9 151.4 132.5 113.5 94.5 168.5 12.2 168.5 166.4 147.5 128.6 109.7 90.8 57 175.0 10.8 175.0 175.0 158.1 139.1 120.1 101.1 168.1 12.1 168.1 168.1 150.6 131.7 112.8 93.8 77 229.4 11.9 113.7 92.3 70.8 - - - 220.1 13.2 110.7 89.4 68.1 - - ­72 212.8 11.6 144.1 122.7 101.2 79.7 - - 203.3 12.8 140.7 119.4 98.1 76.8 - ­67 196.1 11.2 174.5 153.0 131.6 110.1 88.7 - 186.5 12.5 170.6 149.3 128.0 106.7 85.4 ­62 180.7 11.0 180.7 178.6 162.4 141.9 119.5 98.1 172.7 12.2 172.7 171.7 158.7 137.4 116.1 94.8 57 179.7 10.9 179.7 179.7 169.6 149.6 126.6 105.2 172.4 12.2 172.4 172.4 162.0 140.7 119.4 98.1 77 235.4 12.0 123.5 99.5 75.6 - - - 225.5 13.3 120.3 96.6 72.9 - - ­72 218.3 11.7 155.9 132.0 108.0 84.1 - - 208.3 12.9 152.3 128.6 105.0 81.3 - ­67 201.2 11.3 188.3 164.4 140.5 116.5 92.6 - 191.1 12.6 184.4 160.7 137.0 113.4 89.7 ­62 185.4 11.1 185.4 185.4 173.4 151.3 125.5 101.6 177.0 12.3 177.0 177.0 169.9 146.2 122.6 98.9 57 184.4 11.0 184.4 184.4 181.0 160.1 133.2 109.2 176.6 12.3 176.6 176.6 173.5 149.8 126.1 102.4 72 221.3 11.3 165.2 139.4 113.7 88.0 - - 213.7 13.6 165.8 140.1 114.5 88.8 - ­67 204.0 11.0 197.5 174.0 147.8 122.0 96.3 - 196.0 13.3 192.7 175.1 149.4 123.8 98.1 ­62 187.9 10.7 187.9 187.9 181.9 157.1 130.4 104.7 181.5 13.0 181.5 181.5 178.0 152.4 126.7 101.1 57 186.8 10.6 186.8 186.8 185.2 161.0 133.7 108.0 181.2 13.0 181.2 181.2 179.6 153.9 128.3 102.6 72 224.2 10.9 174.4 146.9 119.4 91.8 - - 219.0 14.3 179.2 151.6 123.9 96.3 - ­67 206.7 10.6 206.7 183.6 155.1 127.6 100.0 - 201.0 14.0 201.0 189.4 161.8 134.1 106.5 ­62 190.4 10.3 190.4 190.4 190.4 162.8 135.3 107.8 186.1 13.7 186.1 186.1 186.1 158.5 130.9 103.2 57 189.3 10.3 189.3 189.3 189.3 161.8 134.3 106.7 185.7 13.7 185.7 185.7 185.7 158.1 130.5 102.9
77 205.8 14.4 98.3 79.5 60.6 - - - 195.5 15.9 95.5 76.6 57.7 - - ­72 189.3 14.0 125.7 106.8 87.9 69.1 - - 179.9 15.7 122.5 103.6 84.7 65.9 - ­67 172.8 13.7 153.0 134.1 115.3 96.4 77.5 - 164.3 15.4 149.5 130.7 111.8 92.9 74.0 ­62 161.0 13.5 161.0 161.0 143.6 124.7 105.9 87.0 153.2 15.2 153.2 153.2 139.8 120.9 102.0 83.1 57 161.3 13.5 161.3 161.3 143.1 124.3 105.4 86.6 154.3 15.2 154.3 154.3 136.3 117.4 98.5 79.6 77 210.7 14.4 107.7 86.6 65.4 - - - 199.9 16.0 107.5 83.6 62.4 - - ­72 193.8 14.1 137.2 116.1 94.9 73.8 - - 183.9 15.8 134.0 112.8 91.6 70.4 - ­67 176.9 13.8 166.7 145.6 124.4 103.3 82.2 - 168.0 15.5 160.4 142.0 120.8 99.6 78.3 ­62 164.8 13.5 164.8 164.8 155.0 132.9 112.7 91.6 156.6 15.2 156.6 156.6 151.0 129.4 108.6 87.4 57 165.1 13.6 165.1 165.1 154.5 131.9 112.2 91.1 157.7 15.2 157.7 157.7 147.2 125.3 104.8 83.6 77 215.5 14.5 117.1 93.7 70.2 - - - 204.2 16.1 119.5 90.5 67.0 - - ­72 198.3 14.2 148.7 125.3 101.9 78.5 - - 187.9 15.8 145.4 121.9 98.4 74.9 - ­67 181.0 13.8 180.4 157.0 133.6 110.2 86.8 - 171.6 15.6 171.3 153.3 129.7 106.2 82.7 ­62 168.6 13.6 168.6 168.6 166.4 141.1 119.6 96.2 160.0 15.3 160.0 160.0 162.3 137.8 115.3 91.7 57 168.9 13.6 168.9 168.9 165.9 139.4 119.1 95.6 161.2 15.3 161.2 161.2 158.2 133.2 111.2 87.6 72 206.1 15.9 166.4 140.8 115.2 89.7 - - 192.5 16.7 159.1 133.4 107.7 82.0 - ­67 188.1 15.6 187.8 176.1 151.0 125.5 99.9 - 175.8 16.4 175.7 166.6 142.0 116.3 90.7 ­62 175.2 15.3 175.2 175.2 174.1 147.6 123.0 97.4 164.0 16.2 164.0 164.0 165.1 139.0 113.7 88.1 57 175.5 15.3 175.5 175.5 174.0 146.9 122.9 97.3 165.1 16.2 165.1 165.1 163.6 137.2 112.3 86.6 72 213.9 17.7 184.0 156.3 128.5 100.8 - - 197.2 17.6 172.7 144.9 117.0 89.2 - ­67 195.2 17.3 195.2 195.2 168.5 140.7 113.0 - 180.0 17.3 180.0 180.0 154.3 126.5 98.6 ­62 181.9 17.0 181.9 181.9 181.9 154.1 126.4 98.6 167.9 17.0 167.9 167.9 167.9 140.1 112.2 84.4 57 182.2 17.0 182.2 182.2 182.2 154.4 126.7 99.0 169.0 17.0 169.0 169.0 169.0 141.2 113.4 85.6
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
28 Johnson Controls Unitary Products
505428-YTG-N-0712
YC180/NC180 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB
(°F)
77 185.3 17.5 92.7 73.7 54.8 - - - 175.0 19.1 89.8 70.9 51.9 - - ­72 170.5 17.3 119.4 100.5 81.5 62.6 - - 161.1 18.9 116.2 97.3 78.4 59.4 - ­67 155.8 17.1 146.1 127.2 108.3 89.3 70.4 - 147.2 18.8 142.6 123.7 104.8 85.8 66.9 ­62 145.5 16.9 145.5 145.5 136.0 117.1 98.2 79.3 137.7 18.6 137.7 137.7 132.2 113.3 94.3 75.4 57 147.3 16.8 147.3 147.3 129.4 110.5 91.6 72.7 140.3 18.5 140.3 140.3 122.6 103.6 84.7 65.8 77 189.1 17.6 107.3 80.6 59.3 - - - 178.3 19.2 107.1 77.6 56.2 - - ­72 174.1 17.4 130.7 109.5 88.2 66.9 - - 164.2 19.1 127.5 106.2 84.8 63.5 - ­67 159.0 17.2 154.2 138.3 117.1 95.8 74.5 - 150.1 18.9 147.9 134.7 113.4 92.1 70.7 ­62 148.5 17.0 148.5 148.5 147.1 125.8 104.5 83.3 140.3 18.7 140.3 140.3 140.3 122.2 100.4 79.1 57 150.4 16.9 150.4 150.4 140.0 118.7 97.4 76.2 143.0 18.6 143.0 143.0 132.7 112.1 90.0 68.7 77 192.9 17.7 121.9 87.4 63.8 - - - 181.6 19.3 124.4 84.3 60.5 - - ­72 177.6 17.5 142.1 118.5 94.8 71.2 - - 167.3 19.2 138.8 115.0 91.3 67.6 - ­67 162.2 17.3 162.2 149.5 125.9 102.3 78.6 - 152.9 19.0 152.9 145.8 122.1 98.3 74.6 ­62 151.5 17.0 151.5 151.5 158.2 134.5 110.9 87.3 142.9 18.8 142.9 142.9 142.9 131.2 106.6 82.8 57 153.4 17.0 153.4 153.4 150.5 126.9 103.3 79.6 145.7 18.7 145.7 145.7 142.8 120.6 95.4 71.6 72 179.0 17.5 151.7 126.0 100.2 74.4 - - 165.5 18.3 144.4 118.5 92.7 66.8 - ­67 163.5 17.3 163.5 157.2 133.0 107.2 81.5 - 151.3 18.2 151.3 147.7 124.0 98.1 72.3 ­62 152.7 17.0 152.7 152.7 156.0 130.3 104.5 78.7 141.4 17.9 141.4 141.4 141.4 121.6 95.3 69.4 57 154.7 17.0 154.7 154.7 153.2 127.4 101.7 75.9 144.2 17.9 144.2 144.2 142.8 117.7 91.0 65.2 72 180.4 17.5 161.4 133.5 105.5 77.6 - - 163.7 17.4 150.1 122.1 94.1 66.0 - ­67 164.8 17.3 164.8 164.8 140.1 112.2 84.3 - 149.7 17.3 149.7 149.7 125.9 97.9 69.9 ­62 153.9 17.0 153.9 153.9 153.9 126.0 98.1 70.2 140.0 17.1 140.0 140.0 140.0 112.0 83.9 55.9 57 155.9 17.0 155.9 155.9 155.9 128.0 100.1 72.1 142.7 17.0 142.7 142.7 142.7 114.7 86.7 58.7
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 29
505428-YTG-N-0712
YC180/NC240
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
77 214.3 12.1 111.5 92.2 72.8 - - - 213.3 13.3 110.6 91.3 71.9 - - ­72 201.7 11.8 138.5 119.1 99.8 80.4 - - 199.0 13.0 137.0 117.6 98.3 78.9 - ­67 189.0 11.6 165.4 146.1 126.7 107.3 88.0 - 184.6 12.7 163.3 144.0 124.6 105.2 85.9 ­62 181.2 11.3 181.2 177.5 156.5 137.1 117.7 98.4 171.9 12.5 171.9 170.0 150.7 131.3 112.0 92.6 57 177.1 11.3 177.1 177.1 160.6 141.3 121.9 102.5 170.3 12.5 170.3 170.3 153.8 134.5 115.1 95.8 77 220.7 12.2 121.6 99.7 77.7 - - - 219.3 13.4 120.7 98.7 76.7 - - ­72 207.6 11.9 150.4 128.4 106.4 84.5 - - 204.6 13.1 148.8 126.8 104.9 82.9 - ­67 194.6 11.7 179.1 157.2 135.2 113.2 91.2 - 189.9 12.8 176.9 154.9 133.0 111.0 89.0 ­62 186.5 11.4 186.5 184.7 167.0 145.2 123.0 101.0 176.8 12.6 176.8 175.8 160.8 138.8 116.9 94.9 57 182.3 11.4 182.3 182.3 171.4 150.0 127.4 105.5 175.1 12.6 175.1 175.1 164.2 142.2 120.3 98.3 77 227.1 12.3 131.7 107.1 82.6 - - - 225.4 13.5 130.7 106.1 81.6 - - ­72 213.6 12.0 162.3 137.7 113.1 88.5 - - 210.2 13.2 160.6 136.0 111.5 86.9 - ­67 200.2 11.8 192.8 168.2 143.7 119.1 94.5 - 195.1 12.9 190.5 165.9 141.3 116.8 92.2 ­62 191.9 11.5 191.9 191.9 177.4 153.3 128.3 103.7 181.6 12.7 181.6 181.6 170.9 146.4 121.8 97.2 57 187.6 11.5 187.6 187.6 182.1 158.8 133.0 108.4 179.9 12.7 179.9 179.9 174.5 150.0 125.4 100.8 72 218.3 12.1 172.7 145.8 118.9 92.0 - - 214.0 13.3 170.8 143.9 117.0 90.1 - ­67 204.5 11.9 200.9 177.9 151.0 124.1 97.2 - 198.6 13.0 196.2 175.2 148.4 121.5 94.6 ­62 196.0 11.6 196.0 196.0 188.7 162.0 134.9 108.0 184.9 12.7 184.9 184.9 179.4 152.6 125.7 98.8 57 191.6 11.6 191.6 191.6 188.9 162.6 135.1 108.2 183.1 12.7 183.1 183.1 180.4 153.6 126.7 99.8 72 223.0 12.2 183.1 153.9 124.7 95.5 - - 217.7 13.4 180.9 151.7 122.6 93.4 - ­67 208.9 11.9 208.9 187.5 158.3 129.2 100.0 - 202.0 13.1 202.0 184.6 155.4 126.2 97.0 ­62 200.2 11.7 200.2 200.2 199.9 170.7 141.5 112.3 188.1 12.8 188.1 188.1 187.9 158.8 129.6 100.4 57 195.7 11.6 195.7 195.7 195.7 166.5 137.3 108.1 186.3 12.8 186.3 186.3 186.3 157.1 128.0 98.8
77 212.3 14.6 109.7 90.4 71.0 - - - 207.7 16.7 107.9 88.6 69.2 - - ­72 196.3 14.2 135.5 116.1 96.8 77.4 - - 191.8 16.2 133.6 114.2 94.9 75.5 - ­67 180.3 13.9 161.2 141.8 122.5 103.1 83.8 - 175.9 15.8 159.2 139.9 120.5 101.2 81.9 ­62 162.6 13.6 162.6 162.6 144.9 125.5 106.2 86.8 158.2 15.4 158.2 158.2 141.1 121.7 102.4 83.0 57 163.6 13.6 163.6 163.6 147.1 127.7 108.4 89.0 160.7 15.4 160.7 160.7 144.1 124.7 105.4 86.0 77 218.0 14.6 119.7 97.8 75.8 - - - 213.3 16.8 118.7 95.9 74.0 - - ­72 201.6 14.3 147.2 125.2 103.3 81.3 - - 197.0 16.3 145.3 123.3 101.4 79.4 - ­67 185.2 14.0 174.6 152.7 130.7 108.8 86.8 - 180.7 15.9 171.8 150.8 128.8 106.9 84.9 ­62 167.0 13.7 167.0 167.0 154.6 132.5 110.7 88.8 162.4 15.5 162.4 162.4 150.8 128.7 106.9 84.9 57 167.9 13.7 167.9 167.9 157.0 134.4 113.1 91.1 165.0 15.5 165.0 165.0 154.0 131.7 110.1 88.1 77 223.7 14.7 129.7 105.1 80.6 - - - 218.9 16.9 129.6 103.3 78.7 - - ­72 206.8 14.4 158.9 134.3 109.8 85.3 - - 202.1 16.4 157.0 132.5 107.9 83.4 - ­67 190.0 14.1 188.1 163.5 139.0 114.5 89.9 - 185.4 16.0 184.4 161.6 137.1 112.6 88.0 ­62 171.4 13.8 171.4 171.4 164.4 139.4 115.3 90.8 166.7 15.6 166.7 166.7 160.4 135.7 111.4 86.8 57 172.3 13.8 172.3 172.3 166.9 141.1 117.8 93.3 169.3 15.6 169.3 169.3 163.8 138.7 114.8 90.2 72 209.6 14.5 168.9 142.0 115.1 88.3 - - 205.1 16.5 167.0 140.1 113.2 86.4 - ­67 192.6 14.2 191.6 172.6 145.7 118.9 92.0 - 188.1 16.0 187.6 170.7 143.9 117.0 90.2 ­62 173.7 13.9 173.7 173.7 170.2 143.1 116.5 89.6 169.1 15.6 169.1 169.1 166.0 139.0 112.2 85.4 57 174.7 13.9 174.7 174.7 172.0 144.5 118.2 91.4 171.8 15.6 171.8 171.8 169.0 141.9 115.3 88.5 72 212.4 14.5 178.8 149.6 120.4 91.3 - - 208.0 16.5 176.9 147.8 118.6 89.4 - ­67 195.1 14.2 195.1 181.7 152.5 123.3 94.1 - 190.8 16.1 190.8 179.8 150.7 121.5 92.3 ­62 176.0 13.9 176.0 176.0 176.0 146.8 117.6 88.4 171.5 15.7 171.5 171.5 171.5 142.3 113.1 84.0 57 177.0 13.9 177.0 177.0 177.0 147.8 118.6 89.5 174.2 15.6 174.2 174.2 174.2 145.0 115.9 86.7
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
30 Johnson Controls Unitary Products
505428-YTG-N-0712
YC180/NC240 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB
(°F)
77 203.2 18.8 106.1 86.7 67.4 - - - 198.7 21.0 104.2 84.9 65.6 - - ­72 187.4 18.3 131.7 112.3 93.0 73.7 - - 182.9 20.3 129.8 110.4 91.1 71.8 - ­67 171.6 17.7 157.3 137.9 118.6 99.3 79.9 - 167.2 19.6 155.3 136.0 116.7 97.3 78.0 ­62 153.7 17.2 153.7 153.7 137.3 117.9 98.6 79.3 149.3 19.0 149.3 149.3 133.5 114.1 94.8 75.5 57 157.8 17.1 157.8 157.8 141.1 121.7 102.4 83.0 154.9 18.9 154.9 154.9 138.0 118.7 99.4 80.1 77 208.6 19.0 117.7 94.1 72.1 - - - 204.0 21.1 116.8 92.2 70.3 - - ­72 192.4 18.4 143.4 121.4 99.5 77.6 - - 187.8 20.4 141.5 119.6 97.6 75.7 - ­67 176.2 17.8 169.0 148.8 126.9 105.0 83.0 - 171.7 19.7 166.2 146.9 125.0 103.0 81.1 ­62 157.8 17.3 157.8 157.8 146.9 124.9 103.0 81.1 153.3 19.1 153.3 153.3 143.0 121.2 99.1 77.2 57 162.0 17.2 162.0 162.0 150.9 129.0 107.0 85.1 159.1 19.0 159.1 159.1 147.9 126.3 104.0 82.1 77 214.1 19.1 129.4 101.4 76.8 - - - 209.3 21.2 129.3 99.5 74.9 - - ­72 197.4 18.5 155.1 130.6 106.0 81.5 - - 192.8 20.5 153.2 128.7 104.1 79.6 - ­67 180.8 17.9 180.8 159.7 135.2 110.7 86.1 - 176.2 19.8 176.2 157.8 133.3 108.8 84.2 ­62 162.0 17.4 162.0 162.0 156.5 131.9 107.4 82.8 157.3 19.2 157.3 157.3 152.5 128.2 103.4 78.9 57 166.3 17.3 166.3 166.3 160.8 136.3 111.7 87.2 163.2 19.1 163.2 163.2 157.8 133.8 108.7 84.1 72 200.5 18.5 165.1 138.2 111.4 84.5 - - 195.9 20.5 163.2 136.3 109.5 82.6 - ­67 183.6 17.9 183.6 168.9 142.0 115.2 88.3 - 179.1 19.7 179.1 167.0 140.2 113.3 86.5 ­62 164.5 17.4 164.5 164.5 161.7 134.9 108.0 81.2 159.9 19.2 159.9 159.9 157.5 130.8 103.8 77.0 57 168.8 17.3 168.8 168.8 166.1 139.3 112.4 85.6 165.9 19.0 165.9 165.9 163.2 136.7 109.5 82.7 72 203.6 18.5 175.0 145.9 116.7 87.6 - - 199.1 20.4 173.1 144.0 114.9 85.7 - ­67 186.4 17.9 186.4 178.0 148.8 119.7 90.5 - 182.0 19.7 182.0 176.2 147.0 117.9 88.7 ­62 167.0 17.4 167.0 167.0 167.0 137.8 108.7 79.5 162.5 19.2 162.5 162.5 162.5 133.3 104.2 75.0 57 171.4 17.3 171.4 171.4 171.4 142.3 113.1 83.9 168.6 19.0 168.6 168.6 168.6 139.5 110.3 81.2
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 31
505428-YTG-N-0712
YD180 / Two NC090
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
77 216.0 12.0 105.9 88.7 71.5 - - - 208.8 13.2 103.4 86.2 69.0 - - ­72 200.4 11.7 130.4 113.2 96.0 78.8 - - 194.2 12.9 128.0 110.9 93.7 76.5 - ­67 184.8 11.4 154.8 137.7 120.5 103.3 86.1 - 179.6 12.6 152.7 135.5 118.3 101.2 84.0 ­62 173.1 11.2 173.1 164.2 147.0 129.8 112.6 95.4 165.4 12.4 165.4 161.0 143.8 126.6 109.4 92.3 57 165.6 11.1 165.6 165.6 150.2 133.0 115.8 98.6 162.3 12.3 162.3 162.3 147.5 130.3 113.1 95.9 77 222.3 12.1 114.8 95.5 76.2 - - - 215.7 13.2 112.2 93.0 73.7 - - ­72 206.2 11.8 140.8 121.5 102.3 83.0 - - 200.5 13.0 138.5 119.3 100.0 80.8 - ­67 190.2 11.5 166.9 147.6 128.3 109.0 89.8 - 185.4 12.7 164.9 145.6 126.3 107.1 87.8 ­62 178.1 11.2 178.1 173.7 156.5 137.8 118.0 98.7 170.8 12.4 170.8 168.6 153.5 134.2 115.0 95.7 57 170.4 11.2 170.4 170.4 159.9 141.5 121.4 102.1 167.6 12.4 167.6 167.6 157.4 138.2 118.9 99.6 77 228.6 12.1 123.6 102.2 80.9 - - - 222.5 13.3 121.1 99.7 78.4 - - ­72 212.1 11.9 151.3 129.9 108.5 87.1 - - 206.9 13.1 149.0 127.7 106.4 85.0 - ­67 195.6 11.6 178.9 157.6 136.2 114.8 93.4 - 191.3 12.8 177.0 155.7 134.3 113.0 91.6 ­62 183.2 11.3 183.2 183.2 166.1 145.8 123.4 102.0 176.2 12.5 176.2 176.2 163.2 141.9 120.5 99.2 57 175.2 11.3 175.2 175.2 169.7 149.9 127.0 105.6 172.9 12.5 172.9 172.9 167.4 146.0 124.7 103.3 72 216.4 11.9 159.1 136.1 113.1 90.1 - - 209.8 13.1 156.5 133.5 110.6 87.6 - ­67 199.6 11.6 188.8 164.9 141.9 118.9 95.9 - 193.9 12.8 185.6 162.6 139.7 116.7 93.7 ­62 186.9 11.4 186.9 186.9 173.4 150.9 127.4 104.4 178.7 12.6 178.7 178.7 169.7 146.7 123.8 100.8 57 178.8 11.3 178.8 178.8 176.1 153.9 130.1 107.1 175.3 12.5 175.3 175.3 172.5 149.6 126.6 103.7 72 220.7 12.0 166.9 142.3 117.7 93.0 - - 212.6 13.2 163.9 139.3 114.8 90.2 - ­67 203.5 11.7 198.6 172.3 147.7 123.0 98.4 - 196.6 12.9 194.1 169.5 145.0 120.4 95.8 ­62 190.6 11.4 190.6 190.6 180.6 156.0 131.4 106.8 181.1 12.6 181.1 181.1 176.1 151.6 127.0 102.4 57 182.4 11.4 182.4 182.4 182.4 157.8 133.2 108.6 177.7 12.6 177.7 177.7 177.7 153.1 128.5 104.0
77 201.7 14.3 100.9 83.7 66.6 - - - 197.4 16.0 98.8 81.6 64.5 - - ­72 188.0 14.1 125.7 108.5 91.4 74.2 - - 183.8 15.7 123.8 106.6 89.4 72.3 - ­67 174.3 13.8 150.5 133.4 116.2 99.1 81.9 - 170.2 15.4 148.7 131.6 114.4 97.2 80.0 ­62 157.8 13.5 157.8 157.8 140.6 123.4 106.3 89.1 156.2 15.2 156.2 156.2 139.1 121.9 104.8 87.6 57 159.0 13.5 159.0 159.0 144.7 127.6 110.4 93.3 155.4 15.2 155.4 155.4 140.6 123.4 106.2 89.1 77 209.0 14.4 109.7 90.5 71.2 - - - 204.0 16.1 107.4 88.2 69.0 - - ­72 194.9 14.2 136.3 117.0 97.8 78.6 - - 189.9 15.8 134.1 114.9 95.7 76.4 - ­67 180.7 13.9 162.8 143.6 124.4 105.1 85.9 - 175.8 15.5 160.9 141.6 122.4 103.1 83.9 ­62 163.5 13.6 163.5 163.5 150.5 130.7 112.0 92.7 161.4 15.3 161.4 161.4 148.8 129.3 110.4 91.1 57 164.8 13.6 164.8 164.8 154.9 134.8 116.4 97.2 160.6 15.3 160.6 160.6 150.4 130.8 111.9 92.7 77 216.4 14.5 118.5 97.2 75.9 - - - 210.6 16.2 116.1 94.8 73.5 - - ­72 201.7 14.2 146.8 125.5 104.2 82.9 - - 196.1 15.9 144.5 123.2 101.9 80.6 - ­67 187.0 14.0 175.1 153.8 132.5 111.2 89.9 - 181.5 15.6 173.0 151.7 130.4 109.1 87.8 ­62 169.3 13.7 169.3 169.3 160.3 137.9 117.7 96.4 166.6 15.4 166.6 166.6 158.6 136.7 116.0 94.7 57 170.5 13.7 170.5 170.5 165.0 142.1 122.4 101.1 165.8 15.3 165.8 165.8 160.2 138.1 117.6 96.3 72 203.1 14.3 153.9 131.0 108.0 85.1 - - 197.7 15.9 151.6 128.7 105.8 83.0 - ­67 188.3 14.0 182.4 160.3 137.4 114.5 91.6 - 183.1 15.7 178.8 158.3 135.4 112.5 89.6 ­62 170.5 13.8 170.5 170.5 166.0 142.5 120.2 97.2 168.0 15.4 168.0 168.0 164.0 140.9 118.2 95.4 57 171.7 13.7 171.7 171.7 169.0 145.3 123.2 100.2 167.2 15.4 167.2 167.2 164.4 141.1 118.7 95.8 72 204.5 14.3 160.9 136.4 111.9 87.4 - - 199.4 16.0 158.7 134.2 109.8 85.3 - ­67 189.6 14.1 189.6 166.8 142.3 117.8 93.2 - 184.7 15.7 184.7 164.9 140.4 115.9 91.4 ­62 171.7 13.8 171.7 171.7 171.7 147.1 122.6 98.1 169.5 15.5 169.5 169.5 169.5 145.0 120.5 96.1 57 173.0 13.8 173.0 173.0 173.0 148.4 123.9 99.4 168.6 15.4 168.6 168.6 168.6 144.1 119.7 95.2
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
32 Johnson Controls Unitary Products
505428-YTG-N-0712
YD180 / Two NC090 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB
(°F)
77 193.0 17.7 96.7 79.6 62.4 - - - 188.7 19.3 94.6 77.5 60.3 - - ­72 179.5 17.4 121.8 104.6 87.5 70.3 - - 175.3 19.0 119.9 102.7 85.5 68.3 - ­67 166.0 17.1 146.9 129.7 112.6 95.4 78.2 - 161.9 18.7 145.1 127.9 110.7 93.5 76.4 ­62 154.6 16.8 154.6 154.6 137.6 120.4 103.3 86.1 152.9 18.5 152.9 152.9 136.1 118.9 101.7 84.6 57 151.8 16.8 151.8 151.8 136.4 119.2 102.1 84.9 148.2 18.4 148.2 148.2 132.2 115.1 97.9 80.7 77 198.9 17.8 105.2 86.0 66.7 - - - 193.8 19.4 103.0 83.7 64.5 - - ­72 185.0 17.5 132.0 112.8 93.6 74.3 - - 180.0 19.1 129.9 110.7 91.5 72.2 - ­67 171.0 17.2 158.9 139.6 120.4 101.2 81.9 - 166.2 18.8 156.9 137.7 118.4 99.2 80.0 ­62 159.2 16.9 159.2 159.2 147.2 128.0 108.7 89.5 157.1 18.6 157.1 157.1 145.6 126.6 107.1 87.9 57 156.4 16.9 156.4 156.4 145.9 126.7 107.5 88.2 152.2 18.5 152.2 152.2 141.4 122.6 103.0 83.7 77 204.7 17.9 113.7 92.4 71.1 - - - 198.9 19.5 111.3 90.0 68.7 - - ­72 190.4 17.6 142.3 121.0 99.7 78.4 - - 184.8 19.2 140.0 118.7 97.4 76.1 - ­67 176.1 17.2 170.9 149.6 128.3 107.0 85.7 - 170.6 18.9 168.7 147.4 126.1 104.9 83.6 ­62 163.9 17.0 163.9 163.9 156.8 135.5 114.2 92.9 161.3 18.7 161.3 161.3 155.1 134.3 112.5 91.2 57 161.0 17.0 161.0 161.0 155.4 134.2 112.9 91.6 156.2 18.6 156.2 156.2 150.7 130.2 108.1 86.8 72 192.4 17.6 149.4 126.5 103.6 80.8 - - 187.0 19.3 147.1 124.3 101.4 78.6 - ­67 177.9 17.3 175.3 156.2 133.4 110.5 87.7 - 172.7 18.9 171.7 154.2 131.4 108.5 85.7 ­62 165.6 17.1 165.6 165.6 162.1 139.2 116.3 93.5 163.2 18.7 163.2 163.2 160.1 137.5 114.4 91.6 57 162.6 17.0 162.6 162.6 159.9 137.0 114.1 91.3 158.1 18.7 158.1 158.1 155.3 132.9 109.6 86.8 72 194.3 17.7 156.5 132.0 107.6 83.2 - - 189.2 19.3 154.2 129.9 105.5 81.1 - ­67 179.7 17.4 179.7 162.9 138.5 114.1 89.6 - 174.7 19.0 174.7 161.0 136.6 112.2 87.8 ­62 167.3 17.1 167.3 167.3 167.3 142.9 118.4 94.0 165.1 18.8 165.1 165.1 165.1 140.7 116.3 92.0 57 164.3 17.1 164.3 164.3 164.3 139.8 115.4 91.0 159.9 18.7 159.9 159.9 159.9 135.6 111.2 86.8
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 33
505428-YTG-N-0712
YD180 / Two NC120
Air on
Evaporator Coil
CFM
WB (°F)
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
75°F 85°F
77 241.0 12.0 121.2 97.8 74.3 - - - 237.1 13.2 119.7 96.2 72.6 - - ­72 222.0 11.7 154.8 131.4 107.9 84.4 - - 219.2 12.9 153.8 130.2 106.7 83.1 - ­67 203.0 11.4 188.4 165.0 141.5 118.0 94.5 - 201.4 12.6 187.8 164.2 140.7 117.1 93.6 ­62 191.6 11.2 191.6 191.6 168.1 144.6 121.1 97.6 188.1 12.3 188.1 187.8 164.3 140.7 117.2 93.6 57 189.3 11.2 189.3 189.5 166.0 142.6 119.1 95.6 189.2 12.4 189.2 188.9 165.3 141.8 118.2 94.7 77 247.3 12.1 136.7 106.3 79.7 - - - 242.9 13.3 135.8 104.6 78.0 - - ­72 227.8 11.8 168.9 142.3 115.8 89.2 - - 224.6 13.0 167.7 141.1 114.5 87.9 - ­67 208.3 11.5 201.0 178.4 151.8 125.3 98.7 - 206.4 12.6 199.5 177.6 151.0 124.4 97.8 ­62 196.6 11.2 196.6 196.6 180.4 153.4 127.3 100.8 192.7 12.4 192.7 192.6 176.3 149.8 123.2 96.6 57 194.3 11.3 194.3 194.4 178.2 152.5 125.1 98.5 193.9 12.5 193.9 193.7 177.5 150.9 124.3 97.7 77 253.6 12.2 152.2 114.8 85.1 - - - 248.7 13.3 151.8 112.9 83.3 - - ­72 233.6 11.9 182.9 153.3 123.7 94.1 - - 230.0 13.0 181.6 151.9 122.3 92.7 - ­67 213.6 11.5 213.6 191.8 162.2 132.6 103.0 - 211.3 12.7 211.3 191.0 161.3 131.7 102.1 ­62 201.6 11.3 201.6 201.6 192.7 162.3 133.5 103.9 197.3 12.5 197.3 197.3 188.4 158.8 129.2 99.6 57 199.3 11.4 199.3 199.3 190.3 162.5 131.1 101.5 198.5 12.5 198.5 198.5 189.6 160.0 130.4 100.8 72 238.5 11.9 193.5 161.5 129.6 97.6 - - 234.0 13.1 192.0 160.0 128.1 96.1 - ­67 218.1 11.6 218.1 201.9 169.9 138.0 106.1 - 215.0 12.8 215.0 200.9 168.9 136.9 105.0 ­62 205.8 11.4 205.8 205.8 201.3 169.0 137.4 105.5 200.7 12.5 200.7 200.7 196.3 164.3 132.3 100.3 57 203.4 11.4 203.4 203.4 199.0 167.9 135.1 103.1 201.9 12.6 201.9 201.9 197.5 165.5 133.5 101.6 72 243.3 12.0 204.1 169.8 135.5 101.2 - - 238.0 13.1 202.5 168.1 133.8 99.5 - ­67 222.5 11.7 222.5 212.0 177.7 143.4 109.1 - 218.6 12.8 218.6 210.8 176.5 142.1 107.8 ­62 210.0 11.4 210.0 210.0 210.0 175.7 141.4 107.1 204.1 12.6 204.1 204.1 204.1 169.8 135.4 101.1 57 207.6 11.5 207.6 207.6 207.6 173.3 139.0 104.7 205.4 12.6 205.4 205.4 205.4 171.0 136.7 102.4
95°F 105°F
77 233.2 14.3 118.3 94.6 71.0 - - - 229.8 15.1 117.0 93.3 69.7 - - ­72 216.5 14.0 152.7 129.1 105.5 81.9 - - 213.6 14.8 151.7 128.1 104.5 80.8 - ­67 199.8 13.7 187.1 163.5 139.9 116.3 92.7 - 197.4 14.5 186.4 162.8 139.2 115.6 92.0 ­62 184.5 13.4 184.5 184.1 160.5 136.8 113.2 89.6 185.1 14.2 185.1 183.8 160.2 136.5 112.9 89.3 57 189.1 13.5 189.1 188.2 164.6 141.0 117.4 93.8 187.3 14.3 187.3 185.9 162.2 138.6 115.0 91.4 77 238.5 14.4 134.9 102.9 76.3 - - - 233.4 15.8 135.0 101.2 74.6 - - ­72 221.5 14.1 166.5 139.8 113.2 86.6 - - 216.9 15.5 165.0 138.4 111.7 85.1 - ­67 204.4 13.8 198.1 176.8 150.2 123.6 97.0 - 200.5 15.2 195.0 175.5 148.9 122.3 95.6 ­62 188.8 13.5 188.8 188.5 172.3 146.1 119.0 92.4 187.9 14.9 187.9 187.3 171.3 144.9 118.1 91.5 57 193.4 13.6 193.4 193.0 176.7 149.3 123.5 96.9 190.3 14.9 190.3 189.5 173.6 146.5 120.3 93.7 77 243.9 14.5 151.5 111.1 81.5 - - - 237.0 16.4 153.0 109.1 79.5 - - ­72 226.4 14.2 180.2 150.6 121.0 91.4 - - 220.3 16.1 178.3 148.7 119.0 89.4 - ­67 209.0 13.9 209.0 190.1 160.5 130.9 101.3 - 203.6 15.8 203.6 188.2 158.6 129.0 99.3 ­62 193.0 13.6 193.0 193.0 184.1 155.3 124.9 95.2 190.8 15.5 190.8 190.8 182.5 153.3 123.2 93.6 57 197.8 13.7 197.8 197.8 188.9 157.5 129.6 100.0 193.2 15.5 193.2 193.2 184.9 154.4 125.6 96.0 72 229.5 14.2 190.6 158.6 126.6 94.5 - - 222.9 16.1 188.2 156.3 124.3 92.3 - ­67 211.8 13.9 211.8 199.9 167.9 135.9 103.9 - 206.0 15.8 206.0 197.0 165.6 133.6 101.7 ­62 195.6 13.7 195.6 195.6 191.2 159.6 127.2 95.2 193.1 15.5 193.1 193.1 188.9 157.1 124.9 93.0 57 200.5 13.7 200.5 200.5 196.0 163.1 132.0 100.0 195.5 15.5 195.5 195.5 191.3 158.9 127.4 95.4 72 232.6 14.3 200.9 166.5 132.1 97.7 - - 225.4 16.1 198.2 163.9 129.6 95.3 - ­67 214.7 14.0 214.7 209.6 175.2 140.8 106.5 - 208.3 15.8 208.3 205.8 172.6 138.3 104.0 ­62 198.3 13.7 198.3 198.3 198.3 163.9 129.5 95.1 195.3 15.5 195.3 195.3 195.3 161.0 126.7 92.4 57 203.2 13.8 203.2 203.2 203.2 168.8 134.4 100.0 197.7 15.5 197.7 197.7 197.7 163.4 129.1 94.8
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
Total Input
(kW)
Sensible Capacity (MBh)
2
1
34 Johnson Controls Unitary Products
505428-YTG-N-0712
YD180 / Two NC120 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB (°F)
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
77 226.4 15.9 115.7 92.1 68.4 - - - 223.0 16.7 114.4 90.8 67.1 - - ­72 210.6 15.6 150.7 127.1 103.5 79.8 - - 207.7 16.4 149.7 126.1 102.5 78.8 - ­67 194.9 15.3 185.7 162.1 138.5 114.9 91.2 - 192.4 16.1 185.0 161.4 137.8 114.1 90.5 ­62 185.6 15.0 185.6 183.5 159.8 136.2 112.6 89.0 186.1 15.8 186.1 183.2 159.5 135.9 112.3 88.7 57 185.6 15.0 185.6 183.5 159.9 136.3 112.6 89.0 183.8 15.8 183.8 181.1 157.5 133.9 110.3 86.7 77 228.3 17.1 135.1 99.6 72.9 - - - 223.2 18.5 135.2 97.9 71.3 - - ­72 212.4 16.8 163.5 136.9 110.3 83.6 - - 207.9 18.2 162.0 135.4 108.8 82.1 - ­67 196.5 16.5 191.9 174.2 147.6 121.0 94.3 - 192.6 17.9 188.9 172.9 146.3 119.6 93.0 ­62 187.1 16.2 187.1 186.1 170.4 143.7 117.1 90.5 186.3 17.5 186.3 184.8 169.4 142.6 116.1 89.5 57 187.1 16.2 187.1 186.1 170.4 143.8 117.1 90.5 184.0 17.5 184.0 182.6 167.2 141.0 114.0 87.3 77 230.2 18.3 154.5 107.1 77.4 - - - 223.4 20.2 156.0 105.1 75.4 - - ­72 214.2 18.0 176.3 146.7 117.1 87.4 - - 208.1 19.9 174.4 144.7 115.1 85.5 - ­67 198.2 17.7 198.2 186.3 156.7 127.1 97.4 - 192.7 19.6 192.7 184.4 154.8 125.1 95.5 ­62 188.7 17.3 188.7 188.7 180.9 151.2 121.6 92.0 186.5 19.2 186.5 186.5 179.3 149.2 120.0 90.3 57 188.7 17.3 188.7 188.7 180.9 151.3 121.6 92.0 184.2 19.1 184.2 184.2 176.9 148.2 117.7 88.0 72 216.2 17.9 185.9 154.0 122.0 90.1 - - 209.6 19.8 183.6 151.7 119.8 87.9 - ­67 200.1 17.6 200.1 194.1 163.4 131.4 99.5 - 194.2 19.5 194.2 191.3 161.1 129.2 97.3 ­62 190.5 17.3 190.5 190.5 186.6 154.7 122.7 90.8 187.9 19.1 187.9 187.9 184.3 152.2 120.5 88.6 57 190.5 17.3 190.5 190.5 186.6 154.7 122.8 90.8 185.5 19.0 185.5 185.5 181.9 150.5 118.1 86.2 72 218.3 17.9 195.5 161.3 127.0 92.8 - - 211.1 19.7 192.8 158.6 124.5 90.3 - ­67 202.0 17.6 202.0 202.0 170.0 135.8 101.6 - 195.6 19.4 195.6 195.6 167.4 133.3 99.1 ­62 192.3 17.2 192.3 192.3 192.3 158.1 123.8 89.6 189.3 19.0 189.3 189.3 189.3 155.2 121.0 86.9 57 192.3 17.2 192.3 192.3 192.3 158.1 123.9 89.6 186.9 18.9 186.9 186.9 186.9 152.8 118.6 84.5
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
Total Input (kW)
Sensible Capacity (MBh)
2
1
Johnson Controls Unitary Products 35
505428-YTG-N-0712
YD180/ND180
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
77 208.6 11.7 106.3 87.7 69.0 - - - 205.9 13.0 103.7 84.9 66.2 - - ­72 198.3 11.4 132.6 113.9 95.3 76.6 - - 192.8 12.7 129.9 111.1 92.4 73.6 - ­67 188.0 11.0 158.8 140.2 121.5 102.9 84.2 - 179.7 12.4 156.1 137.4 118.6 99.9 81.1 ­62 170.5 10.9 170.5 170.5 152.4 133.8 115.1 96.5 166.3 12.2 166.3 166.3 150.1 131.4 112.6 93.9 57 177.8 11.0 177.8 177.8 161.5 142.9 124.2 105.6 172.3 12.2 172.3 172.3 155.9 137.1 118.4 99.6 77 217.2 11.7 117.1 95.9 74.6 - - - 213.0 13.0 114.0 92.6 71.2 - - ­72 206.4 11.4 145.5 124.2 102.9 81.6 - - 199.5 12.7 142.3 120.9 99.5 78.1 - ­67 195.7 11.1 173.8 152.5 131.2 110.0 88.7 - 186.0 12.5 170.5 149.1 127.7 106.3 84.9 ­62 177.6 10.9 177.6 177.6 164.6 144.0 122.0 100.8 172.0 12.2 172.0 172.0 161.7 140.3 118.9 97.5 57 185.1 11.0 185.1 185.1 174.5 153.9 131.9 110.6 178.3 12.3 178.3 178.3 167.8 146.5 125.1 103.7 77 225.8 11.8 128.0 104.0 80.1 - - - 220.1 13.1 124.4 100.3 76.3 - - ­72 214.6 11.4 158.4 134.5 110.5 86.6 - - 206.1 12.8 154.6 130.6 106.6 82.5 - ­67 203.4 11.1 188.9 164.9 141.0 117.0 93.1 - 192.2 12.5 184.9 160.9 136.8 112.8 88.8 ­62 184.6 11.0 184.6 184.6 176.9 154.2 129.0 105.1 177.8 12.3 177.8 177.8 173.2 149.1 125.1 101.1 57 192.4 11.1 192.4 192.4 187.4 165.0 139.5 115.6 184.2 12.4 184.2 184.2 179.8 155.8 131.7 107.7 72 214.6 11.5 167.9 142.4 116.8 91.2 - - 206.7 12.9 164.3 138.6 113.0 87.3 - ­67 203.4 11.2 196.2 174.5 149.0 123.4 97.8 - 192.7 12.6 189.0 170.7 145.0 119.3 93.7 ­62 184.6 11.1 184.6 184.6 180.7 155.8 129.6 104.0 178.3 12.4 178.3 178.3 176.0 150.3 124.6 98.9 57 192.4 11.1 192.4 192.4 189.9 165.1 138.8 113.2 184.7 12.4 184.7 184.7 182.5 156.8 131.2 105.5 72 214.6 11.6 177.4 150.3 123.1 95.9 - - 207.2 12.9 174.0 146.6 119.3 92.0 - ­67 203.5 11.3 203.5 184.1 157.0 129.8 102.6 - 193.2 12.6 193.2 180.5 153.2 125.9 98.6 ­62 184.6 11.1 184.6 184.6 184.6 157.4 130.2 103.0 178.7 12.4 178.7 178.7 178.7 151.4 124.1 96.8 57 192.5 11.2 192.5 192.5 192.5 165.3 138.1 110.9 185.2 12.5 185.2 185.2 185.2 157.9 130.6 103.3
77 203.1 14.3 101.0 82.1 63.3 - - - 189.1 16.0 95.4 76.6 57.9 - - ­72 187.3 14.0 127.2 108.4 89.5 70.7 - - 175.6 15.7 122.5 103.8 85.0 66.3 - ­67 171.5 13.7 153.5 134.6 115.8 96.9 78.1 - 162.1 15.5 149.7 130.9 112.2 93.5 74.7 ­62 162.0 13.5 162.0 162.0 147.9 129.0 110.2 91.3 153.3 15.3 153.3 153.3 141.3 122.5 103.8 85.0 57 166.8 13.5 166.8 166.8 150.2 131.4 112.5 93.7 156.8 15.2 156.8 156.8 145.7 126.9 108.2 89.5 77 208.8 14.3 110.9 89.4 67.9 - - - 195.1 16.0 108.5 84.0 62.7 - - ­72 192.5 14.1 139.0 117.6 96.1 74.6 - - 181.2 15.8 134.8 113.4 92.1 70.8 - ­67 176.2 13.8 167.2 145.7 124.2 102.7 81.2 - 167.3 15.5 161.0 142.8 121.5 100.2 78.8 ­62 166.5 13.5 166.5 166.5 158.7 136.5 115.7 94.2 158.2 15.3 158.2 158.2 153.0 131.3 110.3 89.0 57 171.4 13.6 171.4 171.4 161.2 139.0 118.2 96.7 161.8 15.3 161.8 161.8 157.8 136.1 115.1 93.8 77 214.4 14.4 120.8 96.7 72.5 - - - 201.1 16.1 121.6 91.4 67.4 - - ­72 197.7 14.2 150.9 126.7 102.6 78.5 - - 186.8 15.8 147.0 123.1 99.1 75.2 - ­67 181.0 13.9 180.9 156.8 132.7 108.5 84.4 - 172.4 15.6 172.4 154.8 130.8 106.9 83.0 ­62 171.0 13.6 171.0 171.0 169.5 144.0 121.2 97.1 163.0 15.4 163.0 163.0 164.7 140.1 116.8 92.9 57 176.1 13.7 176.1 176.1 172.2 146.5 123.9 99.8 166.8 15.4 166.8 166.8 169.9 145.2 122.0 98.1 72 198.8 14.2 160.7 134.9 109.1 83.3 - - 186.7 15.9 156.8 131.0 105.1 79.2 - ­67 182.0 13.9 181.9 166.9 141.1 115.3 89.5 - 172.4 15.6 172.4 162.0 138.7 112.8 86.9 ­62 171.9 13.7 171.9 171.9 171.2 144.7 119.6 93.8 163.0 15.4 163.0 163.0 163.8 137.6 112.1 86.2 57 177.0 13.7 177.0 177.0 175.1 148.5 123.5 97.7 166.7 15.4 166.7 166.7 168.3 142.0 116.5 90.6 72 199.8 14.3 170.5 143.0 115.6 88.2 - - 186.7 15.9 166.7 138.9 111.0 83.2 - ­67 183.0 14.0 183.0 176.9 149.5 122.0 94.6 - 172.3 15.7 172.3 169.3 146.5 118.7 90.9 ­62 172.9 13.7 172.9 172.9 172.9 145.4 118.0 90.6 162.9 15.5 162.9 162.9 162.9 135.1 107.3 79.5 57 178.0 13.8 178.0 178.0 178.0 150.5 123.1 95.6 166.7 15.4 166.7 166.7 166.7 138.8 111.0 83.2
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
36 Johnson Controls Unitary Products
505428-YTG-N-0712
YD180/ND180 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB
(°F)
77 175.1 17.7 89.8 71.1 52.5 - - - 161.0 19.4 84.1 65.6 47.1 - - ­72 163.9 17.4 117.8 99.2 80.6 61.9 - - 152.2 19.1 113.1 94.6 76.1 57.6 - ­67 152.8 17.2 145.9 127.3 108.6 90.0 71.4 - 143.4 18.9 142.1 123.6 105.1 86.6 68.0 ­62 144.6 17.1 144.6 144.6 134.7 116.0 97.4 78.8 135.8 18.8 135.8 135.8 128.1 109.5 91.0 72.5 57 146.8 17.0 146.8 146.8 141.1 122.5 103.9 85.2 136.8 18.7 136.8 136.8 136.6 118.0 99.5 81.0 77 181.4 17.7 106.1 78.6 57.4 - - - 167.8 19.4 103.6 73.2 52.2 - - ­72 169.9 17.5 130.5 109.3 88.1 66.9 - - 158.6 19.2 126.2 105.2 84.1 63.1 - ­67 158.3 17.2 154.9 140.0 118.8 97.6 76.4 - 149.4 18.9 148.7 137.1 116.1 95.1 74.0 ­62 149.8 17.1 149.8 149.8 147.3 126.1 104.9 83.7 141.5 18.9 141.5 141.5 141.5 120.9 99.5 78.5 57 152.1 17.0 152.1 152.1 154.3 133.1 112.0 90.8 142.5 18.7 142.5 142.5 142.5 130.2 108.8 87.8 77 187.8 17.8 122.4 86.1 62.3 - - - 174.5 19.4 123.1 80.8 57.2 - - ­72 175.8 17.5 143.1 119.4 95.6 71.9 - - 164.9 19.2 139.2 115.7 92.2 68.6 - ­67 163.9 17.3 163.9 152.7 129.0 105.2 81.5 - 155.3 19.0 155.3 150.7 127.1 103.6 80.0 ­62 155.1 17.2 155.1 155.1 159.9 136.1 112.4 88.7 147.1 18.9 147.1 147.1 147.1 132.2 108.0 84.4 57 157.5 17.1 157.5 157.5 167.5 143.8 120.1 96.3 148.2 18.8 148.2 148.2 148.2 142.4 118.1 94.6 72 174.6 17.6 153.0 127.0 101.1 75.1 - - 162.6 19.2 149.2 123.1 97.0 71.0 - ­67 162.8 17.3 162.8 157.2 136.3 110.3 84.3 - 153.2 19.0 153.2 152.4 133.9 107.8 81.8 ­62 154.0 17.2 154.0 154.0 156.4 130.5 104.5 78.5 145.1 19.0 145.1 145.1 145.1 123.3 96.9 70.9 57 156.4 17.1 156.4 156.4 161.4 135.5 109.5 83.5 146.1 18.8 146.1 146.1 146.1 128.9 102.5 76.4 72 173.5 17.6 162.9 134.7 106.5 78.3 - - 160.3 19.3 159.1 130.5 101.9 73.3 - ­67 161.7 17.3 161.7 161.7 143.6 115.4 87.2 - 151.0 19.0 151.0 151.0 140.6 112.0 83.5 ­62 153.0 17.2 153.0 153.0 153.0 124.8 96.6 68.4 143.0 19.0 143.0 143.0 143.0 114.5 85.9 57.3 57 155.4 17.1 155.4 155.4 155.4 127.2 99.0 70.8 144.0 18.8 144.0 144.0 144.0 115.5 86.9 58.3
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 37
505428-YTG-N-0712
YD180/ND240
Air on
Evaporator Coil
CFM
WB (°F)
77 213.8 12.1 109.1 89.8 70.5 - - - 212.3 13.3 108.9 89.6 70.3 - - ­72 201.0 11.8 136.0 116.7 97.4 78.1 - - 197.9 13.0 134.7 115.4 96.1 76.9 - -
4500
67 188.1 11.5 162.8 143.5 124.2 104.9 85.6 - 183.4 12.7 160.6 141.3 122.0 102.7 83.4 ­62 171.4 11.3 171.4 168.3 149.0 129.7 110.4 91.1 166.5 12.5 166.5 164.9 145.6 126.3 107.0 87.7 57 175.2 11.3 175.2 175.2 157.4 138.1 118.8 99.5 168.8 12.5 168.8 168.8 151.2 131.9 112.6 93.3 77 220.6 12.2 120.2 98.1 76.0 - - - 219.0 13.4 120.0 97.9 75.8 - - ­72 207.3 11.9 149.2 127.0 104.9 82.8 - - 204.1 13.1 147.9 125.8 103.7 81.6 - -
5250
67 194.1 11.6 178.1 156.0 133.8 111.7 89.6 - 189.2 12.8 175.9 153.7 131.6 109.5 87.4 ­62 176.8 11.4 176.8 175.2 160.5 138.7 116.3 94.2 171.8 12.6 171.8 170.9 157.1 134.9 112.8 90.7 57 180.7 11.4 180.7 180.7 169.6 148.2 125.4 103.2 174.1 12.5 174.1 174.1 163.1 141.0 118.8 96.7 77 227.3 12.3 131.3 106.4 81.5 - - - 225.7 13.5 131.2 106.3 81.3 - - ­72 213.6 12.0 162.3 137.4 112.5 87.5 - - 210.4 13.2 161.2 136.2 111.3 86.4 - -
6000
67 200.0 11.7 193.3 168.4 143.5 118.5 93.6 - 195.0 12.9 191.1 166.2 141.2 116.3 91.4 ­62 182.2 11.5 182.2 182.2 172.1 147.8 122.2 97.3 177.0 12.7 177.0 177.0 168.5 143.6 118.7 93.7 57 186.3 11.5 186.3 186.3 181.8 158.2 132.0 107.0 179.5 12.6 179.5 179.5 175.0 150.0 125.1 100.2 72 217.5 12.1 172.8 145.5 118.2 90.9 - - 213.5 13.3 171.4 144.1 116.9 89.6 - -
6750
67 203.6 11.8 200.3 178.1 150.8 123.5 96.2 - 197.9 13.0 196.0 175.6 148.3 121.1 93.8 ­62 185.5 11.6 185.5 185.5 180.5 153.5 125.9 98.6 179.7 12.7 179.7 179.7 175.4 148.2 120.9 93.6 57 189.6 11.5 189.6 189.6 187.4 160.8 132.8 105.6 182.2 12.7 182.2 182.2 179.9 152.7 125.4 98.1 72 221.4 12.2 183.2 153.5 123.9 94.3 - - 216.7 13.3 181.7 152.1 122.5 92.8 - -
7500
67 207.3 11.9 207.3 187.7 158.1 128.4 98.8 - 200.9 13.0 200.9 185.0 155.4 125.8 96.2 ­62 188.8 11.6 188.8 188.8 188.8 159.2 129.5 99.9 182.4 12.8 182.4 182.4 182.4 152.8 123.1 93.5 57 193.0 11.6 193.0 193.0 193.0 163.4 133.7 104.1 184.9 12.8 184.9 184.9 184.9 155.3 125.7 96.1
77 210.9 14.5 108.6 89.3 70.0 - - - 205.7 16.4 106.6 87.3 68.0 - - ­72 194.8 14.2 133.5 114.2 94.9 75.7 - - 190.4 16.0 131.6 112.3 93.1 73.8 - -
4500
67 178.7 13.9 158.4 139.1 119.8 100.6 81.3 - 175.1 15.6 156.7 137.4 118.1 98.9 79.6 ­62 161.6 13.6 161.6 161.5 142.2 122.9 103.6 84.4 157.3 15.3 157.3 157.2 139.1 119.9 100.6 81.3 57 162.4 13.6 162.4 162.4 144.9 125.7 106.4 87.1 159.4 15.3 159.4 159.4 142.1 122.8 103.6 84.3 77 217.5 14.6 119.8 97.7 75.6 - - - 212.5 16.5 118.4 95.7 73.6 - - ­72 200.9 14.3 146.7 124.6 102.5 80.4 - - 196.6 16.1 144.9 122.8 100.7 78.6 - -
5250
67 184.4 14.0 173.6 151.5 129.4 107.3 85.2 - 180.8 15.8 171.3 149.9 127.8 105.7 83.6 ­62 166.7 13.7 166.7 166.7 153.6 131.2 109.4 87.2 162.5 15.4 162.5 162.4 150.5 128.3 106.3 84.2 57 167.5 13.7 167.5 167.5 156.5 133.8 112.3 90.2 164.7 15.4 164.7 164.7 153.7 131.3 109.5 87.4 77 224.2 14.7 131.1 106.2 81.2 - - - 219.2 16.6 130.3 104.1 79.1 - - ­72 207.1 14.4 160.0 135.0 110.1 85.2 - - 202.9 16.2 158.2 133.2 108.3 83.4 - -
6000
67 190.0 14.1 188.9 163.9 139.0 114.1 89.1 - 186.6 15.9 186.0 162.4 137.5 112.5 87.6 ­62 171.8 13.8 171.8 171.8 164.9 139.4 115.1 90.1 167.6 15.5 167.6 167.6 161.9 136.7 112.0 87.1 57 172.7 13.8 172.7 172.7 168.1 141.8 118.3 93.3 169.9 15.5 169.9 169.9 165.3 139.7 115.5 90.6 72 209.6 14.4 170.1 142.8 115.6 88.3 - - 205.0 16.3 168.2 140.9 113.7 86.4 - -
6750
67 192.3 14.2 191.7 173.1 145.9 118.6 91.4 - 188.5 15.9 188.2 171.5 144.3 117.0 89.7 ­62 173.9 13.9 173.9 173.9 170.4 142.9 115.9 88.7 169.4 15.5 169.4 169.4 166.5 139.1 112.0 84.8 57 174.7 13.9 174.7 174.7 172.4 144.5 117.9 90.7 171.7 15.5 171.7 171.7 169.4 141.8 114.9 87.6 72 212.0 14.5 180.2 150.6 121.0 91.4 - - 207.1 16.3 178.2 148.6 119.0 89.4 - -
7500
67 194.5 14.2 194.5 182.3 152.8 123.2 93.6 - 190.5 15.9 190.5 180.6 151.0 121.5 91.9 ­62 175.9 13.9 175.9 175.9 175.9 146.3 116.8 87.2 171.2 15.5 171.2 171.2 171.2 141.6 112.0 82.4 57 176.8 13.9 176.8 176.8 176.8 147.2 117.6 88.0 173.5 15.5 173.5 173.5 173.5 143.9 114.3 84.7
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
1
Total
Capacity
1
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
1
38 Johnson Controls Unitary Products
505428-YTG-N-0712
YD180/ND240 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 200.6 18.3 104.5 85.3 66.0 - - - 195.5 20.2 102.5 83.2 64.0 - - ­72 186.0 17.8 129.7 110.5 91.2 72.0 - - 181.6 19.6 127.9 108.6 89.4 70.1 - ­67 171.4 17.4 154.9 135.7 116.4 97.2 77.9 - 167.7 19.1 153.2 134.0 114.7 95.5 76.3 ­62 153.0 16.9 153.0 153.0 136.1 116.8 97.6 78.3 148.7 18.5 148.7 148.7 133.0 113.8 94.5 75.3 57 156.4 16.9 156.4 156.4 139.2 120.0 100.7 81.5 153.5 18.5 153.5 153.5 136.4 117.1 97.9 78.7 77 207.4 18.4 117.0 93.6 71.5 - - - 202.4 20.4 115.6 91.6 69.5 - - ­72 192.3 18.0 143.0 120.9 98.9 76.8 - - 188.1 19.8 141.2 119.1 97.0 75.0 - ­67 177.2 17.5 169.0 148.3 126.2 104.1 82.0 - 173.7 19.2 166.7 146.6 124.6 102.5 80.4 ­62 158.2 17.0 158.2 158.2 147.5 125.4 103.3 81.2 154.0 18.7 154.0 154.0 144.4 122.5 100.2 78.2 57 161.8 17.0 161.8 161.8 150.9 128.8 106.7 84.6 158.9 18.7 158.9 158.9 148.1 126.3 103.9 81.9 77 214.3 18.6 129.6 102.0 77.1 - - - 209.4 20.5 128.8 99.9 75.0 - - ­72 198.7 18.1 156.3 131.4 106.5 81.6 - - 194.5 20.0 154.5 129.6 104.7 79.8 - ­67 183.1 17.6 183.1 160.9 135.9 111.0 86.1 - 179.7 19.4 179.7 159.3 134.4 109.5 84.6 ­62 163.5 17.1 163.5 163.5 158.8 133.9 109.0 84.1 159.3 18.8 159.3 159.3 155.8 131.2 106.0 81.1 57 167.1 17.1 167.1 167.1 162.6 137.6 112.7 87.8 164.4 18.8 164.4 164.4 159.8 135.5 110.0 85.1 72 200.5 18.1 166.3 139.0 111.8 84.5 - - 196.0 19.9 164.4 137.1 109.8 82.6 - ­67 184.7 17.6 184.7 169.9 142.6 115.4 88.1 - 181.0 19.4 181.0 168.3 141.0 113.8 86.5 ­62 164.9 17.1 164.9 164.9 162.6 135.4 108.1 80.8 160.4 18.8 160.4 160.4 158.7 131.6 104.2 76.9 57 168.6 17.1 168.6 168.6 166.3 139.1 111.8 84.6 165.6 18.8 165.6 165.6 163.3 136.4 108.8 81.5 72 202.3 18.1 176.2 146.6 117.0 87.4 - - 197.4 19.9 174.2 144.6 115.0 85.4 - ­67 186.4 17.6 186.4 178.9 149.3 119.7 90.1 - 182.3 19.3 182.3 177.2 147.6 118.0 88.4 ­62 166.4 17.1 166.4 166.4 166.4 136.8 107.2 77.6 161.6 18.7 161.6 161.6 161.6 132.0 102.4 72.8 57 170.1 17.1 170.1 170.1 170.1 140.5 110.9 81.3 166.8 18.7 166.8 166.8 166.8 137.2 107.6 78.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
Total Input (kW)
Sensible Capacity (MBh)
2
1
Johnson Controls Unitary Products 39
505428-YTG-N-0712
YC240/NC240
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
WB (°F)
Total
Capacity
(MBh)
77 286.3 15.3 136.1 113.4 90.6 - - - 280.0 16.9 131.5 108.2 84.9 - - ­72 267.4 14.8 169.4 146.7 123.9 101.2 - - 260.2 16.5 166.3 143.0 119.7 96.4 - ­67 248.5 14.4 202.7 180.0 157.2 134.5 111.7 - 240.5 16.1 201.0 177.7 154.4 131.1 107.8 ­62 228.9 14.1 228.9 216.8 194.0 171.3 148.5 125.8 223.4 15.7 223.4 213.8 190.5 167.2 143.9 120.6 57 227.5 14.0 227.5 227.5 205.1 182.4 159.6 136.9 220.8 15.7 220.8 220.8 201.8 178.5 155.2 131.9 77 296.6 15.4 148.2 122.8 97.4 - - - 287.9 17.0 143.1 117.2 91.3 - - ­72 277.0 14.9 184.0 158.6 133.2 107.8 - - 267.6 16.6 180.5 154.5 128.6 102.7 - ­67 257.5 14.5 219.8 194.4 169.0 143.6 118.3 - 247.4 16.1 217.8 191.9 165.9 140.0 114.1 ­62 237.1 14.2 237.1 231.1 208.6 184.8 157.8 132.4 229.7 15.8 229.7 224.9 204.7 178.7 152.8 126.9 57 235.7 14.1 235.7 235.7 220.5 197.5 169.7 144.3 227.0 15.8 227.0 227.0 216.9 190.9 165.0 139.0 77 306.9 15.5 160.3 132.3 104.2 - - - 295.8 17.1 154.7 126.2 97.6 - - ­72 286.6 15.0 198.6 170.6 142.5 114.5 - - 275.0 16.7 194.7 166.1 137.5 108.9 - ­67 266.4 14.6 236.9 208.9 180.8 152.8 124.8 - 254.2 16.2 234.6 206.0 177.4 148.8 120.3 ­62 245.4 14.3 245.4 245.4 223.1 198.3 167.1 139.0 236.1 15.9 236.1 236.1 218.8 190.3 161.7 133.1 57 243.8 14.2 243.8 243.8 235.9 212.7 179.8 151.8 233.3 15.9 233.3 233.3 231.9 203.3 174.7 146.2 72 296.2 15.1 209.5 179.3 149.0 118.8 - - 282.3 16.7 205.3 174.3 143.2 112.2 - ­67 275.2 14.7 251.9 219.4 189.1 158.9 128.6 - 261.0 16.3 246.8 215.8 184.8 153.8 122.8 ­62 253.5 14.4 253.5 253.5 233.4 204.7 172.9 142.6 242.4 15.9 242.4 242.4 228.0 197.0 165.9 134.9 57 251.9 14.3 251.9 251.9 248.0 220.1 187.5 157.2 239.5 15.9 239.5 239.5 238.8 207.8 176.8 145.8 72 305.7 15.2 220.5 188.0 155.6 123.1 - - 289.7 16.8 215.9 182.4 149.0 115.5 - ­67 284.0 14.8 266.9 229.9 197.4 165.0 132.5 - 267.7 16.3 259.1 225.7 192.2 158.8 125.3 ­62 261.7 14.5 261.7 261.7 243.6 211.1 178.7 146.2 248.7 16.0 248.7 248.7 237.1 203.7 170.2 136.8 57 260.0 14.4 260.0 260.0 260.0 227.6 195.1 162.7 245.7 16.0 245.7 245.7 245.7 212.3 178.8 145.4
77 273.6 18.5 126.9 103.1 79.2 - - - 259.0 21.0 123.8 99.6 75.3 - - ­72 253.1 18.1 163.1 139.3 115.4 91.6 - - 239.6 20.4 159.8 135.6 111.3 87.1 - ­67 232.5 17.7 199.3 175.5 151.6 127.8 103.9 - 220.3 19.9 195.8 171.6 147.4 123.1 98.9 ­62 217.9 17.3 217.9 210.8 186.9 163.1 139.2 115.4 205.1 19.5 205.1 201.5 182.5 158.3 134.0 109.8 57 214.0 17.4 214.0 214.0 198.6 174.7 150.9 127.0 204.2 19.6 204.2 204.2 186.7 162.4 138.2 114.0 77 279.2 18.6 138.0 111.6 85.1 - - - 264.6 21.0 137.3 108.0 81.0 - - ­72 258.2 18.2 176.9 150.4 123.9 97.5 - - 244.8 20.5 173.8 146.8 119.7 92.7 - ­67 237.3 17.8 215.8 189.3 162.8 136.3 109.9 - 225.0 20.0 210.4 185.5 158.5 131.4 104.4 ­62 222.3 17.4 222.3 218.8 200.7 172.6 147.8 121.3 209.5 19.5 209.5 207.7 196.3 168.4 142.2 115.1 57 218.4 17.5 218.4 218.4 213.2 184.3 160.3 133.8 208.6 19.6 208.6 208.6 200.7 172.5 146.6 119.6 77 284.7 18.7 149.2 120.1 90.9 - - - 270.2 21.1 150.8 116.5 86.7 - - ­72 263.4 18.3 190.7 161.6 132.5 103.4 - - 250.0 20.6 187.8 158.0 128.1 98.2 - ­67 242.0 17.9 232.2 203.1 174.0 144.9 115.8 - 229.8 20.0 224.9 199.4 169.6 139.7 109.8 ­62 226.8 17.5 226.8 226.8 214.5 182.2 156.3 127.2 213.9 19.6 213.9 213.9 210.0 178.5 150.3 120.4 57 222.7 17.5 222.7 222.7 227.9 193.9 169.6 140.5 213.0 19.7 213.0 213.0 214.8 182.5 155.0 125.2 72 268.5 18.3 201.0 169.2 137.4 105.7 - - 255.2 20.7 198.4 166.0 133.5 101.1 - ­67 246.7 17.9 241.8 212.3 180.5 148.7 117.0 - 234.6 20.1 232.1 209.2 176.8 144.3 111.9 ­62 231.2 17.5 231.2 231.2 222.6 189.2 159.0 127.2 218.4 19.7 218.4 218.4 215.2 181.9 150.3 117.8 57 227.1 17.5 227.1 227.1 229.6 195.4 166.1 134.3 217.5 19.8 217.5 217.5 218.3 184.7 153.4 121.0 72 273.6 18.3 211.3 176.8 142.4 108.0 - - 260.4 20.7 209.0 174.0 139.0 104.0 - ­67 251.4 17.9 251.4 221.5 187.0 152.6 118.2 - 239.3 20.2 239.3 219.0 184.0 148.9 113.9 ­62 235.6 17.5 235.6 235.6 230.6 196.2 161.7 127.3 222.8 19.8 222.8 222.8 220.3 185.3 150.3 115.2 57 231.4 17.5 231.4 231.4 231.4 196.9 162.5 128.1 221.9 19.9 221.9 221.9 221.9 186.9 151.8 116.8
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
40 Johnson Controls Unitary Products
505428-YTG-N-0712
YC240/NC240 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB (°F)
77 244.4 23.4 120.7 96.0 71.4 - - - 229.9 25.9 117.5 92.5 67.5 - - ­72 226.2 22.8 156.5 131.9 107.2 82.6 - - 212.8 25.1 153.2 128.2 103.2 78.1 - ­67 208.0 22.1 192.4 167.7 143.1 118.5 93.8 - 195.7 24.3 188.9 163.9 138.9 113.8 88.8 ­62 192.2 21.6 192.2 192.2 178.1 153.5 128.8 104.2 179.4 23.8 179.4 179.4 173.7 148.6 123.6 98.6 57 194.4 21.8 194.4 194.4 174.8 150.2 125.5 100.9 184.6 23.9 184.6 184.6 162.9 137.9 112.9 87.8 77 250.0 23.5 136.5 104.5 76.9 - - - 235.5 25.9 135.8 101.0 72.8 - - ­72 231.4 22.8 170.8 143.1 115.5 87.9 - - 218.0 25.1 167.7 139.5 111.3 83.1 - ­67 212.8 22.1 205.0 181.7 154.1 126.5 98.9 - 200.5 24.3 199.6 178.0 149.8 121.6 93.4 ­62 196.7 21.7 196.7 196.7 191.8 164.2 136.5 108.9 183.8 23.8 183.8 183.8 183.8 159.9 130.9 102.7 57 198.9 21.8 198.9 198.9 188.3 160.6 133.0 105.4 189.1 24.0 189.1 189.1 175.8 148.8 119.4 91.2 77 255.7 23.5 152.4 113.0 82.4 - - - 241.1 25.9 154.0 109.5 78.1 - - ­72 236.6 22.8 185.0 154.4 123.7 93.1 - - 223.2 25.1 182.1 150.8 119.4 88.0 - ­67 217.6 22.2 217.6 195.7 165.1 134.5 103.9 - 205.3 24.3 205.3 192.1 160.7 129.3 97.9 ­62 201.1 21.7 201.1 201.1 205.5 174.9 144.3 113.6 188.2 23.9 188.2 188.2 188.2 171.2 138.2 106.9 57 203.3 21.8 203.3 203.3 201.7 171.1 140.5 109.8 193.6 24.0 193.6 193.6 188.6 159.7 125.9 94.5 72 241.9 23.0 195.9 162.8 129.7 96.5 - - 228.6 25.4 193.3 159.5 125.8 92.0 - ­67 222.4 22.3 222.4 206.1 173.0 139.9 106.8 - 210.3 24.6 210.3 203.0 169.3 135.5 101.7 ­62 205.6 21.9 205.6 205.6 207.8 174.6 141.5 108.4 192.7 24.1 192.7 192.7 192.7 167.4 132.8 99.0 57 207.9 22.0 207.9 207.9 207.0 173.9 140.8 107.7 198.3 24.2 198.3 198.3 195.8 163.2 128.2 94.4 72 247.2 23.2 206.8 171.2 135.6 100.0 - - 233.9 25.6 204.5 168.3 132.1 95.9 - ­67 227.3 22.5 227.3 216.5 180.9 145.3 109.7 - 215.2 24.8 215.2 214.0 177.8 141.6 105.4 ­62 210.0 22.0 210.0 210.0 210.0 174.4 138.8 103.2 197.3 24.3 197.3 197.3 197.3 163.5 127.4 91.2 57 212.4 22.2 212.4 212.4 212.4 176.8 141.2 105.6 202.9 24.5 202.9 202.9 202.9 166.7 130.5 94.3
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 41
505428-YTG-N-0712
YD240 / Two NC120
Air on
Evaporator Coil
CFM
WB (°F)
77 268.6 15.0 134.0 111.2 88.5 - - - 270.6 16.5 131.5 108.7 85.9 - - ­72 253.5 14.6 166.7 144.0 121.3 98.6 - - 252.1 16.1 164.6 141.8 119.0 96.1 - -
6000
67 238.3 14.2 199.5 176.8 154.1 131.3 108.6 - 233.6 15.7 197.6 174.8 152.0 129.2 106.4 ­62 214.5 13.9 214.5 210.2 187.4 164.7 142.0 119.3 213.4 15.4 213.4 208.2 185.4 162.6 139.8 117.0 57 213.5 13.9 213.5 216.8 196.1 173.3 150.6 127.9 212.8 15.4 212.8 212.8 190.9 168.1 145.3 122.5 77 280.9 15.1 145.1 119.6 94.1 - - - 280.0 16.6 142.7 117.1 91.5 - - ­72 265.0 14.7 179.9 154.5 129.0 103.5 - - 260.9 16.2 177.9 152.3 126.7 101.1 - -
7000
67 249.1 14.3 214.8 189.3 163.9 138.4 112.9 - 241.8 15.8 213.1 187.5 161.9 136.3 110.7 ­62 224.2 14.0 224.2 222.1 199.4 174.6 148.4 123.0 220.8 15.5 220.8 218.2 197.5 171.9 146.3 120.7 57 223.1 14.0 223.1 224.8 208.6 184.1 157.6 132.2 220.2 15.5 220.2 220.2 203.4 177.8 152.2 126.6 77 293.1 15.2 156.2 128.0 99.8 - - - 289.4 16.7 153.9 125.5 97.1 - - ­72 276.4 14.8 193.1 164.9 136.7 108.5 - - 269.6 16.3 191.2 162.8 134.5 106.1 - -
8000
67 259.8 14.4 230.1 201.9 173.7 145.5 117.3 - 249.9 16.0 228.6 200.2 171.8 143.4 115.1 ­62 234.0 14.1 234.0 234.0 211.3 184.5 154.9 126.7 228.2 15.6 228.2 228.2 209.6 181.2 152.8 124.4 57 232.8 14.1 232.8 232.8 221.0 194.8 164.6 136.4 227.5 15.6 227.5 227.5 215.8 187.4 159.1 130.7 72 278.2 14.9 206.2 175.3 144.3 113.4 - - 274.3 16.4 204.4 173.3 142.2 111.2 - -
9000
67 261.5 14.5 246.7 214.3 183.3 152.4 121.5 - 254.2 16.0 243.6 212.8 181.8 150.7 119.6 ­62 235.5 14.2 235.5 235.5 223.0 192.8 161.2 130.2 232.2 15.7 232.2 232.2 221.7 190.6 159.5 128.5 57 234.3 14.1 234.3 234.3 228.4 198.5 166.5 135.6 231.5 15.7 231.5 231.5 225.6 194.6 163.5 132.4 72 280.0 15.0 219.3 185.6 151.9 118.3 - - 279.0 16.5 217.5 183.8 150.0 116.3 - -
10000
67 263.2 14.6 263.2 226.7 193.0 159.3 125.6 - 258.6 16.1 258.6 225.5 191.7 158.0 124.2 ­62 236.9 14.2 236.9 236.9 234.8 201.1 167.4 133.8 236.1 15.8 236.1 236.1 233.8 200.1 166.3 132.6 57 235.7 14.2 235.7 235.7 235.7 202.1 168.4 134.7 235.4 15.8 235.4 235.4 235.4 201.7 167.9 134.2
77 272.5 18.0 129.1 106.2 83.3 - - - 233.1 17.0 161.4 149.9 138.5 - - ­72 250.7 17.6 162.4 139.5 116.6 93.7 - - 228.1 18.4 184.0 172.5 153.8 131.0 - -
6000
67 228.9 17.3 195.8 172.9 150.0 127.1 104.2 - 223.1 19.7 193.2 170.4 147.5 124.7 101.9 ­62 212.2 17.0 212.2 206.2 183.3 160.5 137.6 114.7 206.1 19.3 206.1 203.1 186.5 163.7 140.8 118.0 57 212.1 17.0 212.1 208.7 185.8 162.9 140.0 117.2 197.7 19.2 197.7 196.1 184.6 161.8 138.9 116.1 77 279.1 18.1 140.3 114.6 88.8 - - - 243.8 17.2 183.8 164.3 144.9 - - ­72 256.8 17.7 175.9 150.1 124.4 98.7 - - 239.1 18.5 194.4 175.0 151.9 126.8 - -
7000
67 234.5 17.4 211.5 185.7 160.0 134.3 108.5 - 234.3 19.9 198.4 173.3 148.2 123.0 97.9 ­62 217.3 17.1 217.3 214.3 195.6 169.1 144.1 118.4 216.4 19.5 213.5 205.4 186.9 161.4 136.6 111.5 57 217.2 17.1 217.2 215.5 198.2 171.5 146.8 121.0 207.4 19.4 207.4 206.5 195.0 169.3 144.7 119.6 77 285.6 18.2 151.5 123.0 94.4 - - - 254.6 17.3 206.2 178.8 151.3 - - ­72 262.8 17.8 189.3 160.8 132.2 103.6 - - 250.0 18.7 204.9 177.5 150.1 122.6 - -
8000
67 240.0 17.5 227.2 198.6 170.0 141.4 112.8 - 245.4 20.0 203.7 176.2 148.8 121.4 93.9 ­62 222.4 17.2 222.4 222.4 207.8 177.8 150.7 122.1 226.7 19.7 220.9 207.8 187.3 159.1 132.4 105.0 57 222.3 17.2 222.3 222.3 210.6 180.1 153.5 124.9 217.0 19.6 217.0 217.0 205.4 176.9 150.5 123.0 72 270.4 17.9 202.6 171.4 140.1 108.9 - - 258.5 18.8 220.4 198.2 172.7 142.1 - -
9000
67 246.9 17.6 240.5 211.4 180.2 149.0 117.8 - 253.9 20.1 228.3 198.7 168.1 137.5 106.9 ­62 228.9 17.2 228.9 228.9 220.3 188.4 157.9 126.7 234.5 19.8 231.6 225.0 212.1 181.2 150.9 120.3 57 228.7 17.2 228.7 228.7 222.9 190.7 160.5 129.3 224.4 19.6 224.4 224.4 218.6 187.5 157.4 126.8 72 278.0 18.0 215.8 181.9 148.1 114.3 - - 267.0 18.8 235.9 219.0 195.4 161.7 - -
10000
67 253.9 17.6 253.9 224.3 190.5 156.6 122.8 - 262.3 20.2 252.9 221.2 187.5 153.7 119.9 ­62 235.3 17.3 235.3 235.3 232.8 199.0 165.2 131.4 242.2 19.8 242.2 242.2 237.0 203.2 169.4 135.6 57 235.1 17.3 235.1 235.1 235.1 201.3 167.5 133.7 231.8 19.7 231.8 231.8 231.8 198.0 164.3 130.5
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
1
Total
Capacity
1
(MBh)
Total Input (kW)
Sensible Capacity (MBh)
2
1
42 Johnson Controls Unitary Products
505428-YTG-N-0712
YD240 / Two NC120 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB
(°F)
77 193.7 16.1 193.7 193.7 193.7 - - - 154.3 15.2 154.3 154.3 154.3 - - ­72 205.5 19.1 205.5 205.5 190.9 168.2 - - 182.9 19.8 182.9 182.9 182.9 182.9 - ­67 217.3 22.1 190.7 167.9 145.1 122.3 99.5 - 211.5 24.5 188.1 165.4 142.6 119.9 97.2 ­62 200.0 21.7 200.0 200.0 189.6 166.9 144.1 121.3 194.0 24.1 194.0 194.0 192.8 170.1 147.3 124.6 57 183.4 21.4 183.4 183.4 183.4 160.6 137.8 115.1 169.1 23.7 169.1 169.1 169.1 159.4 136.7 114.0 77 208.6 16.3 227.3 214.1 201.0 - - - 173.4 15.4 173.4 173.4 173.4 - - ­72 221.4 19.3 213.0 199.9 179.4 154.9 - - 203.6 20.1 203.6 203.6 203.6 183.0 - ­67 234.1 22.3 185.4 160.9 136.4 111.8 87.3 - 233.9 24.8 172.4 148.5 124.5 100.6 76.6 ­62 215.5 22.0 209.7 196.6 178.2 153.7 129.1 104.6 214.5 24.5 205.9 187.7 169.5 145.9 121.6 97.7 57 197.5 21.7 197.5 197.5 191.7 167.2 142.7 118.1 187.7 24.0 187.7 187.7 187.7 165.1 140.6 116.7 77 223.6 16.5 260.9 234.6 208.3 - - - 192.5 15.7 192.5 192.5 192.5 - - ­72 237.2 19.6 220.5 194.2 167.9 141.6 - - 224.4 20.4 224.4 211.0 185.8 160.6 - ­67 250.9 22.6 180.2 153.9 127.6 101.3 75.0 - 256.3 25.2 156.8 131.6 106.4 81.2 56.1 ­62 230.9 22.3 219.4 193.1 166.8 140.5 114.2 87.9 235.1 24.8 217.9 178.4 146.3 121.8 95.9 70.8 57 211.7 22.0 211.7 211.7 200.1 173.8 147.5 121.2 206.4 24.4 206.4 206.4 194.8 170.7 144.5 119.3 72 246.6 19.6 238.3 225.1 205.3 175.3 - - 234.7 20.5 234.7 234.7 234.7 208.5 - ­67 260.8 22.7 216.1 186.0 156.0 126.0 96.0 - 267.7 25.2 203.8 173.3 143.9 114.5 85.1 ­62 240.1 22.3 234.3 221.1 203.9 173.9 143.9 113.9 245.6 24.9 237.0 217.3 195.7 166.7 136.9 107.5 57 220.1 22.0 220.1 220.1 214.3 184.3 154.3 124.3 215.8 24.4 215.8 215.8 210.0 181.1 151.2 121.7 72 256.0 19.6 256.0 256.0 242.8 209.0 - - 245.0 20.5 245.0 245.0 245.0 245.0 - ­67 270.8 22.7 251.9 218.2 184.5 150.7 117.0 - 279.2 25.3 250.9 215.1 181.5 147.8 114.1 ­62 249.2 22.4 249.2 249.2 241.1 207.4 173.7 139.9 256.2 24.9 256.2 256.2 245.2 211.6 177.9 144.2 57 228.5 22.1 228.5 228.5 228.5 194.8 161.0 127.3 225.1 24.4 225.1 225.1 225.1 191.5 157.8 124.2
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
Total Input
(kW)
Sensible Capacity (MBh)
2
1
Johnson Controls Unitary Products 43
505428-YTG-N-0712
YD240/ND240
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
WB (°F)
Total
Capacity
(MBh)
77 292.8 14.7 136.9 111.9 87.0 - - - 284.3 16.4 135.2 110.2 85.1 - - ­72 272.9 14.4 174.4 149.4 124.5 99.5 - - 263.5 16.1 171.7 146.7 121.7 96.6 - ­67 253.0 14.0 211.9 186.9 162.0 137.0 112.0 - 242.6 15.8 208.2 183.2 158.2 133.2 108.1 ­62 231.8 13.8 231.8 220.2 195.2 170.2 145.2 120.2 225.5 15.5 225.5 219.3 194.3 169.2 144.2 119.2 57 224.6 13.7 224.6 224.6 207.1 182.1 157.1 132.1 219.3 15.5 219.3 219.3 201.5 176.5 151.5 126.5 77 302.2 14.8 149.9 121.7 93.5 - - - 292.0 16.5 147.3 119.2 91.1 - - ­72 281.7 14.5 190.2 162.0 133.8 105.6 - - 270.5 16.2 186.4 158.3 130.2 102.2 - ­67 261.1 14.2 230.5 202.3 174.1 145.9 117.7 - 249.1 15.9 225.5 197.4 169.3 141.3 113.2 ­62 239.3 13.9 239.3 233.5 209.9 182.9 153.5 125.3 231.5 15.6 231.5 228.4 208.0 179.9 151.8 123.8 57 231.8 13.9 231.8 231.8 222.6 196.1 166.2 138.0 225.2 15.6 225.2 225.2 215.7 187.7 159.6 131.5 77 311.7 14.9 162.8 131.4 100.0 - - - 299.6 16.6 159.4 128.2 97.1 - - ­72 290.5 14.6 206.0 174.5 143.1 111.7 - - 277.6 16.3 201.0 169.9 138.8 107.7 - ­67 269.3 14.3 249.1 217.7 186.2 154.8 123.4 - 255.6 16.0 242.7 211.6 180.5 149.4 118.3 ­62 246.8 14.0 246.8 246.8 224.5 195.6 161.7 130.3 237.6 15.7 237.6 237.6 221.7 190.5 159.4 128.3 57 239.1 14.0 239.1 239.1 238.1 210.2 175.3 143.9 231.1 15.7 231.1 231.1 229.9 198.8 167.7 136.6 72 299.4 14.9 217.9 184.4 150.9 117.3 - - 284.7 16.6 212.0 178.6 145.2 111.7 - ­67 277.5 14.6 267.1 229.8 196.3 162.8 129.3 - 262.2 16.3 255.6 222.1 188.7 155.3 121.9 ­62 254.3 14.3 254.3 254.3 236.8 204.5 169.7 136.2 243.7 16.0 243.7 243.7 231.8 198.4 165.0 131.5 57 246.4 14.2 246.4 246.4 245.9 214.1 178.9 145.4 237.0 16.0 237.0 237.0 236.4 203.0 169.6 136.2 72 308.2 15.2 229.9 194.2 158.6 123.0 - - 291.8 16.9 222.9 187.2 151.5 115.8 - ­67 285.7 14.8 285.0 242.0 206.4 170.8 135.2 - 268.7 16.5 268.4 232.7 197.0 161.3 125.6 ­62 261.9 14.6 261.9 261.9 249.0 213.4 177.7 142.1 249.7 16.3 249.7 249.7 241.9 206.2 170.5 134.8 57 253.7 14.5 253.7 253.7 253.7 218.1 182.5 146.9 242.9 16.3 242.9 242.9 242.9 207.2 171.5 135.8
77 275.8 18.1 133.4 108.4 83.3 - - - 262.8 20.3 129.8 104.7 79.5 - - ­72 254.0 17.8 169.0 143.9 118.8 93.8 - - 242.0 20.1 164.8 139.7 114.6 89.5 - ­67 232.2 17.5 204.5 179.5 154.4 129.3 104.3 - 221.1 19.8 199.8 174.7 149.6 124.5 99.4 ­62 219.1 17.2 219.1 218.4 193.3 168.3 143.2 118.2 208.7 19.6 208.7 208.3 185.8 160.7 135.6 110.5 57 214.1 17.3 214.1 214.1 196.0 170.9 145.9 120.8 205.0 19.6 205.0 205.0 186.2 161.1 136.0 110.9 77 281.7 18.2 144.7 116.7 88.8 - - - 268.8 20.4 144.0 113.4 85.3 - - ­72 259.4 17.9 182.5 154.6 126.7 98.7 - - 247.4 20.1 179.0 150.9 122.8 94.7 - ­67 237.1 17.6 220.4 192.5 164.6 136.6 108.7 - 226.1 19.9 214.1 188.4 160.3 132.2 104.1 ­62 223.7 17.3 223.7 223.4 206.1 176.9 150.2 122.3 213.4 19.7 213.4 213.2 199.1 170.4 142.9 114.8 57 218.6 17.4 218.6 218.6 208.9 179.2 153.0 125.1 209.7 19.7 209.7 209.7 199.6 170.6 143.4 115.2 77 287.5 18.3 155.9 125.1 94.3 - - - 274.7 20.5 158.2 122.1 91.0 - - ­72 264.8 18.0 196.1 165.3 134.5 103.7 - - 252.9 20.2 193.2 162.1 131.0 99.9 - ­67 242.0 17.7 236.3 205.5 174.7 143.9 113.1 - 231.1 19.9 228.3 202.2 171.1 140.0 108.8 ­62 228.4 17.4 228.4 228.4 218.8 185.5 157.2 126.4 218.1 19.7 218.1 218.1 212.5 180.1 150.3 119.1 57 223.1 17.4 223.1 223.1 221.8 187.5 160.1 129.3 214.3 19.8 214.3 214.3 212.9 180.1 150.7 119.6 72 270.1 18.3 206.1 172.7 139.4 106.1 - - 258.4 20.5 202.9 169.4 136.0 102.5 - ­67 246.9 18.0 244.1 214.5 181.1 147.8 114.5 - 236.1 20.2 234.7 211.0 177.5 144.1 110.6 ­62 233.0 17.7 233.0 233.0 226.8 192.3 160.2 126.9 222.8 20.0 222.8 222.8 219.3 185.2 152.4 118.9 57 227.6 17.7 227.6 227.6 226.9 191.9 160.3 127.0 218.9 20.0 218.9 218.9 218.2 183.9 151.3 117.8 72 275.4 18.6 216.0 180.2 144.4 108.6 - - 263.8 20.8 212.6 176.7 140.9 105.1 - ­67 251.8 18.2 251.8 223.4 187.6 151.8 116.0 - 241.1 20.5 241.1 219.8 184.0 148.2 112.3 ­62 237.6 18.0 237.6 237.6 234.9 199.1 163.3 127.5 227.5 20.3 227.5 227.5 226.1 190.3 154.5 118.6 57 232.1 18.0 232.1 232.1 232.1 196.3 160.5 124.7 223.6 20.3 223.6 223.6 223.6 187.7 151.9 116.1
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
44 Johnson Controls Unitary Products
505428-YTG-N-0712
YD240/ND240 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB (°F)
77 249.8 22.6 126.1 101.0 75.8 - - - 236.8 24.9 122.5 97.3 72.0 - - ­72 229.9 22.3 160.6 135.4 110.3 85.1 - - 217.9 24.6 156.4 131.2 106.0 80.8 - ­67 210.1 22.0 195.1 169.9 144.8 119.6 94.4 - 199.0 24.3 190.3 165.1 139.9 114.7 89.5 ­62 198.2 21.9 198.2 198.2 178.3 153.1 128.0 102.8 187.8 24.3 187.8 187.8 170.7 145.5 120.3 95.1 57 196.0 21.9 196.0 196.0 176.5 151.3 126.1 101.0 187.0 24.2 187.0 187.0 166.7 141.5 116.3 91.1 77 255.8 22.7 143.3 110.0 81.7 - - - 242.9 24.9 142.6 106.7 78.2 - - ­72 235.5 22.4 175.5 147.2 118.9 90.6 - - 223.6 24.7 172.0 143.5 115.0 86.6 - ­67 215.2 22.1 207.7 184.4 156.1 127.8 99.5 - 204.2 24.4 201.3 180.3 151.8 123.4 94.9 ­62 203.0 22.0 203.0 203.0 192.2 163.9 135.7 107.4 192.7 24.3 192.7 192.7 185.3 157.5 128.4 99.9 57 200.8 22.0 200.8 200.8 190.3 162.0 133.7 105.4 191.9 24.3 191.9 191.9 181.0 153.4 124.1 95.6 77 261.9 22.8 160.5 119.1 87.7 - - - 249.1 25.0 162.8 116.1 84.4 - - ­72 241.1 22.5 190.4 159.0 127.5 96.1 - - 229.3 24.8 187.5 155.8 124.1 92.3 - ­67 220.3 22.2 220.3 198.8 167.4 136.0 104.6 - 209.4 24.5 209.4 195.5 163.8 132.0 100.3 ­62 207.8 22.1 207.8 207.8 206.2 174.8 143.3 111.9 197.6 24.4 197.6 197.6 197.6 169.4 136.4 104.7 57 205.5 22.1 205.5 205.5 204.1 172.7 141.3 109.8 196.7 24.4 196.7 196.7 195.3 165.3 131.8 100.1 72 246.6 22.7 199.8 166.1 132.5 98.8 - - 234.9 25.0 196.6 162.8 129.0 95.2 - ­67 225.3 22.4 225.3 207.6 173.9 140.3 106.6 - 214.6 24.7 214.6 204.1 170.3 136.5 102.7 ­62 212.6 22.3 212.6 212.6 211.8 178.2 144.5 110.9 202.4 24.6 202.4 202.4 202.4 171.1 136.7 102.9 57 210.3 22.3 210.3 210.3 209.5 175.9 142.3 108.6 201.6 24.6 201.6 201.6 200.8 167.9 133.2 99.4 72 252.2 23.0 209.2 173.3 137.4 101.6 - - 240.5 25.2 205.7 169.9 134.0 98.1 - ­67 230.4 22.7 230.4 216.3 180.4 144.6 108.7 - 219.7 24.9 219.7 212.7 176.8 141.0 105.1 ­62 217.4 22.5 217.4 217.4 217.4 181.5 145.7 109.8 207.3 24.8 207.3 207.3 207.3 172.8 136.9 101.0 57 215.0 22.5 215.0 215.0 215.0 179.1 143.3 107.4 206.4 24.8 206.4 206.4 206.4 170.5 134.7 98.8
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 45
505428-YTG-N-0712
YC300/NC300
Air on
Evaporator Coil
CFM
7500
8750
10000
11250
12500
7500
8750
10000
11250
12500
WB (°F)
Total
Capacity
(MBh)
77 390.0 20.3 208.7 177.2 145.6 - - - 362.1 23.0 180.5 148.9 117.3 - - ­72 360.6 19.9 242.2 210.6 179.1 147.5 - - 336.8 22.5 224.3 192.7 161.1 129.5 - ­67 331.2 19.5 275.6 244.1 212.5 181.0 149.4 - 311.5 21.9 268.0 236.5 204.9 173.3 141.7 ­62 305.3 18.6 305.3 311.5 279.9 248.4 216.8 185.2 295.7 21.4 295.7 289.4 257.8 226.2 194.6 163.0 57 308.5 18.5 308.5 314.3 282.8 251.2 219.7 188.1 298.5 21.3 298.5 293.5 261.9 230.3 198.7 167.1 77 399.4 20.7 217.9 188.8 153.3 - - - 368.5 23.2 196.3 160.6 124.8 - - ­72 369.3 20.4 258.8 223.4 187.9 152.4 - - 342.8 22.7 242.9 207.2 171.4 135.7 - ­67 339.2 20.0 299.8 258.0 222.5 187.0 151.5 - 317.1 22.2 289.5 253.8 218.0 182.3 146.6 ­62 312.8 19.0 312.8 315.9 293.5 259.6 222.5 187.0 300.9 21.6 300.9 297.8 274.3 238.6 202.9 167.1 57 316.1 18.9 316.1 319.0 296.4 262.8 225.5 190.0 303.8 21.5 303.8 301.3 278.8 243.0 207.3 171.6 77 408.8 21.2 227.1 200.4 161.0 - - - 374.9 23.4 212.1 172.2 132.4 - - ­72 378.0 20.8 275.5 236.1 196.7 157.3 - - 348.8 22.9 261.5 221.7 181.8 141.9 - ­67 347.2 20.4 323.9 271.8 232.4 193.0 153.6 - 322.6 22.4 311.0 271.1 231.2 191.3 151.5 ­62 320.3 19.4 320.3 320.3 307.0 270.9 228.2 188.8 306.2 21.8 306.2 306.2 290.9 251.1 211.2 171.3 57 323.7 19.3 323.7 323.7 310.1 274.3 231.3 191.9 309.1 21.7 309.1 309.1 295.6 255.7 215.9 176.0 72 390.1 20.5 302.2 259.4 216.7 173.9 - - 360.2 22.9 285.4 241.8 198.2 154.6 - ­67 358.3 20.2 346.7 299.2 256.5 213.7 170.9 - 333.2 22.3 327.4 295.7 252.1 208.5 164.9 ­62 330.5 19.2 330.5 330.5 323.9 282.8 238.4 195.6 316.2 21.8 316.2 316.2 308.6 265.0 221.4 177.8 57 334.0 19.1 334.0 334.0 327.2 286.2 241.7 198.9 319.3 21.7 319.3 319.3 312.5 268.9 225.3 181.7 72 402.1 20.3 328.9 282.7 236.6 190.5 - - 371.7 22.8 309.2 261.9 214.6 167.3 - ­67 369.4 19.9 369.4 326.6 280.5 234.4 188.3 - 343.8 22.3 343.8 320.3 272.9 225.6 178.3 ­62 340.7 18.9 340.7 340.7 340.7 294.6 248.5 202.4 326.3 21.8 326.3 326.3 326.3 278.9 231.6 184.3 57 344.3 18.8 344.3 344.3 344.3 298.2 252.1 205.9 329.4 21.6 329.4 329.4 329.4 282.1 234.8 187.5
77 334.1 25.7 152.2 120.6 89.0 - - - 325.6 28.6 147.7 116.1 84.4 - - ­72 313.0 25.0 206.4 174.7 143.1 111.4 - - 300.7 27.9 200.5 168.9 137.2 105.6 - ­67 291.9 24.3 260.5 228.8 197.2 165.5 133.9 - 275.8 27.3 253.3 221.6 190.0 158.4 126.7 ­62 286.0 24.3 286.0 267.3 235.6 204.0 172.3 140.7 266.2 27.0 266.2 251.2 219.5 187.9 156.3 124.6 57 288.6 24.1 288.6 272.7 241.0 209.4 177.8 146.1 273.7 26.8 273.7 255.7 224.1 192.5 160.8 129.2 77 337.6 25.6 174.7 132.3 96.4 - - - 328.2 28.6 177.7 128.5 92.4 - - ­72 316.3 25.0 226.9 191.0 155.0 119.0 - - 303.2 28.0 222.3 186.2 150.2 114.1 - ­67 294.9 24.3 279.2 249.6 213.6 177.6 141.6 - 278.1 27.3 266.8 244.0 207.9 171.9 135.8 ­62 289.0 24.3 289.0 279.6 255.2 217.6 183.2 147.3 268.4 27.1 268.4 260.9 240.2 203.3 168.1 132.0 57 291.6 24.1 291.6 283.7 261.1 223.3 189.1 153.1 275.9 26.9 275.9 266.9 245.2 208.2 173.1 137.0 77 341.1 25.6 197.1 144.1 103.8 - - - 330.9 28.7 207.8 140.8 100.4 - - ­72 319.6 24.9 247.5 207.2 166.9 126.5 - - 305.6 28.1 244.1 203.6 163.1 122.6 - ­67 298.0 24.3 298.0 270.3 230.0 189.7 149.3 - 280.4 27.4 280.4 266.3 225.9 185.4 144.9 ­62 292.0 24.2 292.0 292.0 274.8 231.2 194.2 153.8 270.6 27.1 270.6 270.6 260.8 218.7 179.8 139.4 57 294.6 24.0 294.6 294.6 281.1 237.2 200.5 160.2 278.2 27.0 278.2 278.2 266.2 223.9 185.3 144.8 72 330.4 25.2 268.6 224.1 179.7 135.3 - - 316.3 28.2 265.2 220.4 175.6 130.8 - ­67 308.1 24.5 308.1 292.1 247.7 203.3 158.8 - 290.2 27.5 290.2 282.1 243.2 198.4 153.5 ­62 301.9 24.4 301.9 301.9 293.3 247.2 204.4 160.0 280.0 27.2 280.0 280.0 275.1 229.5 185.5 140.7 57 304.6 24.3 304.6 304.6 297.9 251.6 209.0 164.6 287.9 27.1 287.9 287.9 281.9 236.2 192.3 147.5 72 341.2 25.4 289.6 241.1 192.5 144.0 - - 327.0 28.3 286.4 237.2 188.1 139.0 - ­67 318.2 24.7 318.2 313.9 265.4 216.8 168.3 - 300.0 27.6 300.0 297.8 260.5 211.3 162.2 ­62 311.8 24.7 311.8 311.8 311.8 263.3 214.7 166.2 289.5 27.4 289.5 289.5 289.5 240.4 191.2 142.1 57 314.6 24.5 314.6 314.6 314.6 266.1 217.6 169.0 297.6 27.2 297.6 297.6 297.6 248.5 199.3 150.2
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
46 Johnson Controls Unitary Products
505428-YTG-N-0712
YC300/NC300 (Continued)
Air on
Evaporator Coil
CFM
7500
8750
10000
11250
12500
1
WB (°F)
77 317.1 31.5 143.2 111.6 79.9 - - - 308.6 34.3 138.7 107.1 75.4 - - ­72 288.5 30.8 194.6 163.0 131.4 99.7 - - 276.2 33.7 188.8 157.2 125.5 93.9 - ­67 259.8 30.2 246.1 214.4 182.8 151.2 119.5 - 243.8 33.1 238.9 207.2 175.6 144.0 112.4 ­62 246.4 29.7 246.4 235.1 203.5 171.8 140.2 108.6 226.6 32.4 226.6 219.0 187.4 155.7 124.1 92.5 57 258.8 29.6 258.8 238.8 207.2 175.5 143.9 112.3 243.9 32.3 243.9 221.9 190.3 158.6 127.0 95.4 77 318.9 31.6 180.8 124.6 88.5 - - - 309.5 34.7 183.9 120.7 84.5 - - ­72 290.1 31.0 217.6 181.5 145.4 109.2 - - 277.0 34.0 212.9 176.7 140.6 104.4 - ­67 261.3 30.4 254.4 238.4 202.3 166.1 130.0 - 244.4 33.4 242.0 232.8 196.6 160.4 124.2 ­62 247.8 29.9 247.8 242.1 225.1 189.0 152.9 116.7 227.2 32.6 227.2 223.4 210.1 174.7 137.7 101.5 57 260.2 29.7 260.2 250.2 229.2 193.1 157.0 120.9 244.6 32.6 244.6 233.5 213.3 178.0 140.9 104.7 77 320.7 31.8 218.4 137.6 97.0 - - - 310.4 35.0 229.1 134.3 93.6 - - ­72 291.7 31.2 240.6 200.0 159.3 118.7 - - 277.7 34.3 237.1 196.3 155.6 114.8 - ­67 262.7 30.5 262.7 262.3 221.7 181.1 140.5 - 245.1 33.7 245.1 245.1 217.6 176.8 136.1 ­62 249.2 30.0 249.2 249.2 246.8 206.1 165.5 124.9 227.8 32.9 227.8 227.8 227.8 193.6 151.2 110.4 57 261.7 29.9 261.7 261.7 251.3 210.7 170.0 129.4 245.2 32.9 245.2 245.2 236.3 197.4 154.8 114.1 72 302.2 31.2 261.9 216.7 171.5 126.3 - - 288.2 34.2 258.5 213.0 167.4 121.8 - ­67 272.2 30.5 272.2 272.0 238.6 193.5 148.3 - 254.3 33.6 254.3 254.3 234.1 188.5 143.0 ­62 258.2 30.0 258.2 258.2 257.0 211.8 166.6 121.4 236.3 32.8 236.3 236.3 236.3 194.1 147.7 102.1 57 271.1 29.9 271.1 271.1 265.9 220.8 175.6 130.4 254.4 32.8 254.4 254.4 250.0 205.3 158.9 113.3 72 312.8 31.2 283.2 233.4 183.7 133.9 - - 298.6 34.1 279.9 229.6 179.2 128.8 - ­67 281.7 30.6 281.7 281.7 255.6 205.8 156.0 - 263.5 33.5 263.5 263.5 250.6 200.3 149.9 ­62 267.2 30.0 267.2 267.2 267.2 217.4 167.7 117.9 244.9 32.7 244.9 244.9 244.9 194.5 144.2 93.8 57 280.6 29.9 280.6 280.6 280.6 230.9 181.1 131.4 263.6 32.7 263.6 263.6 263.6 213.2 162.9 112.5
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 47
505428-YTG-N-0712
Condenser Only Cooling Capacities Condenser Only Ratings
Suction Press.
Model
Corresponding Temp.
PSIG °F MBH KW EER MBH KW EER MBH KW EER MBH KW EER MBH KW EER MBH KW EER
YC090
YC120
YD120
YC150
YD150
YC180
YD180
YC240
YD240
YC300
and
108 35 78 4.8 16.1 75 5.3 14.2 72 5.8 12.4 68 6.5 10.3 61 7.6 8.1 55 8.6 6.4 120 40 88 5.0 17.6 84 5.5 15.5 81 5.9 13.6 76 6.7 11.4 70 7.7 9.1 64 8.7 7.3 131 45 98 5.1 19.1 94 5.6 16.7 89 6.1 14.7 85 6.8 12.4 79 7.8 10.0 72 8.9 8.2 143 50 108 5.3 20.5 103 5.8 17.8 98 6.2 15.7 93 6.9 13.4 87 8.0 10.9 81 9.0 9.0 157 55 118 5.4 21.8 112 5.9 18.9 107 6.4 16.7 102 7.1 14.4 96 8.1 11.8 90 9.2 9.8 108 35 102 6.5 15.8 95 7.3 13.1 89 8.0 11.1 84 9.0 9.3 78 10.3 7.6 73 11.4 6.4 120 40 120 6.6 18.1 111 7.4 15.1 104 8.2 12.8 97 9.1 10.6 90 10.4 8.7 84 11.5 7.3 131 45 138 6.7 20.4 128 7.5 17.1 119 8.3 14.4 110 9.3 11.9 102 10.5 9.7 94 11.6 8.1 143 50 155 6.9 22.6 145 7.6 19.0 134 8.4 16.0 123 9.4 13.2 114 10.6 10.8 105 11.7 8.9 157 55 173 7.0 24.7 161 7.7 20.8 149 8.5 17.5 136 9.5 14.4 126 10.7 11.8 115 11.8 9.7 108 35 106 6.4 16.3 96 7.2 13.4 88 7.9 11.2 82 8.8 9.3 73 9.8 7.5 65 11.1 5.9 120 40 120 6.5 18.4 111 7.3 15.2 103 8.0 12.8 95 9.0 10.5 85 10.0 8.5 78 11.3 6.9 131 45 136 6.7 20.5 126 7.4 17.0 117 8.2 14.3 108 9.1 11.8 97 10.2 9.5 90 11.5 7.9 143 50 152 6.8 22.5 142 7.5 18.7 132 8.3 15.8 120 9.3 13.0 109 10.4 10.5 103 11.6 8.8 157 55 168 6.9 24.4 157 7.7 20.4 146 8.5 17.2 133 9.4 14.1 121 10.6 11.4 115 11.8 9.8 108 35 190 8.2 23.2 190 9.1 20.8 113 9.8 11.5 105 11.1 9.5 102 12.4 8.2 98 13.8 7.1 120 40 190 8.5 22.4 190 9.4 20.3 127 10.1 12.6 118 11.3 10.4 113 12.6 8.9 108 14.1 7.7 131 45 190 8.8 21.7 190 9.6 19.8 140 10.3 13.6 131 11.5 11.3 123 12.8 9.6 118 14.4 8.2 143 50 190 9.1 21.0 190 9.8 19.3 154 10.6 14.5 144 11.8 12.2 134 13.0 10.3 127 14.6 8.7 157 55 190 9.3 20.3 190 10.1 18.9 168 10.9 15.4 156 12.0 13.0 145 13.2 10.9 137 14.9 9.2 108 35 132 8.4 15.7 124 9.2 13.5 119 9.9 11.9 109 11.0 9.9 103 12.4 8.3 94 13.6 6.9 120 40 149 8.6 17.4 140 9.4 14.9 133 10.2 13.1 123 11.2 10.9 116 12.7 9.1 107 13.9 7.7 131 45 166 8.7 19.0 156 9.6 16.3 148 10.4 14.2 136 11.5 11.8 128 13.0 9.9 119 14.3 8.3 143 50 183 8.9 20.5 173 9.8 17.6 163 10.7 15.2 149 11.7 12.7 141 13.3 10.6 131 14.6 9.0 157 55 200 9.1 21.9 189 10.0 18.8 177 10.9 16.2 163 12.0 13.6 153 13.5 11.3 144 14.9 9.6 108 35 169 9.7 17.4 153 10.8 14.3 135 11.5 11.7 125 12.7 9.8 116 14.5 8.0 104 16.0 6.5 120 40 184 10.1 18.2 170 11.0 15.4 154 11.9 13.0 142 13.0 10.9 133 14.8 9.0 121 16.4 7.4 131 45 198 10.4 19.1 186 11.3 16.4 172 12.2 14.1 160 13.4 12.0 149 15.1 9.9 137 16.7 8.2 143 50 213 10.7 19.8 203 11.6 17.5 191 12.6 15.2 178 13.7 13.0 166 15.4 10.7 153 17.0 9.0 157 55 227 11.0 20.6 219 11.9 18.4 210 12.9 16.2 196 14.0 14.0 182 15.7 11.6 169 17.3 9.8 108 35 160 10.1 15.9 149 11.0 13.6 141 11.6 12.2 136 12.8 10.6 127 14.5 8.8 121 16.3 7.4 120 40 179 10.2 17.6 168 11.2 15.0 158 11.9 13.3 151 13.1 11.5 141 14.8 9.5 133 16.6 8.0 131 45 199 10.3 19.2 186 11.3 16.5 175 12.2 14.4 166 13.4 12.3 154 15.1 10.2 145 16.8 8.6 143 50 218 10.5 20.8 205 11.5 17.8 192 12.5 15.4 180 13.8 13.1 168 15.4 10.9 157 17.1 9.2 157 55 238 10.6 22.4 224 11.7 19.2 209 12.8 16.4 195 14.1 13.9 181 15.7 11.5 169 17.4 9.7 108 35 215 12.5 17.2 200 13.6 14.7 185 14.8 12.5 171 16.3 10.5 155 18.2 8.5 139 19.7 7.0 120 40 244 13.1 18.7 228 14.2 16.1 213 15.3 13.9 197 16.9 11.7 180 18.8 9.6 163 20.5 7.9 131 45 274 13.6 20.1 257 14.8 17.4 240 15.9 15.2 223 17.4 12.8 204 19.4 10.5 186 21.2 8.8 143 50 303 14.2 21.4 286 15.4 18.6 268 16.4 16.4 249 18.0 13.8 229 20.0 11.4 210 21.9 9.6 157 55 332 14.8 22.5 315 15.9 19.7 296 17.0 17.5 275 18.6 14.8 253 20.6 12.3 233 22.6 10.3 108 35 210 12.4 17.0 196 13.6 14.3 184 15.1 12.2 173 16.7 10.4 157 18.9 8.3 137 21.2 6.5 120 40 237 12.7 18.6 221 14.0 15.8 208 15.4 13.5 195 17.0 11.5 179 19.2 9.4 161 21.4 7.5 131 45 264 13.1 20.1 247 14.3 17.3 231 15.7 14.8 217 17.3 12.6 201 19.5 10.3 184 21.7 8.5 143 50 291 13.5 21.6 273 14.7 18.6 255 15.9 16.0 239 17.6 13.6 223 19.8 11.3 207 22.0 9.4 157 55 317 13.8 22.9 299 15.0 19.9 279 16.2 17.2 261 17.9 14.6 245 20.1 12.2 230 22.3 10.4 108 35 271 17.3 15.7 245 18.6 13.2 215 20.0 10.8 201 22.5 9.0 193 24.9 7.8 188 26.9 7.0 120 40 310 17.8 17.4 282 19.3 14.6 253 20.7 12.2 236 23.1 10.2 223 25.6 8.7 213 27.9 7.6 131 45 348 18.4 19.0 320 20.0 16.0 290 21.4 13.6 271 23.7 11.4 253 26.3 9.6 238 28.8 8.3 143 50 387 18.9 20.4 357 20.6 17.3 328 22.2 14.8 306 24.2 12.6 283 27.1 10.4 263 29.7 8.8 157 55 425 19.5 21.8 395 21.3 18.5 365 22.9 16.0 340 24.8 13.7 313 27.8 11.2 288 30.7 9.4
65 75 85 95 105 115
Temperature of Air on Condenser Coil °F
48 Johnson Controls Unitary Products
Heat Pump and Air Handling Cooling Capacities PC090/NC090 Cooling Capacities
Air on
Evaporator Coil
CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
Total WB (°F)
Capacity
(MBh)
77 112.8 5.9 54.5 44.9 35.3 - - - 107.0 6.5 51.9 42.4 32.9 - - ­72 104.8 5.8 68.7 59.1 49.5 40.0 - - 99.3 6.4 66.3 56.8 47.3 37.9 - ­67 96.7 5.7 82.9 73.4 63.8 54.2 44.6 - 91.7 6.3 80.8 71.3 61.8 52.3 42.8 ­62 89.0 5.5 89.0 89.0 80.5 70.9 61.3 51.7 84.4 6.2 84.4 84.4 76.5 67.0 57.5 48.0 57 88.9 5.6 88.9 88.9 80.5 70.9 61.4 51.8 84.6 6.2 84.6 84.6 75.7 66.2 56.8 47.3 77 117.0 5.9 58.7 48.7 37.9 - - - 110.7 6.6 57.0 46.2 35.5 - - ­72 108.6 5.8 74.8 64.0 53.2 42.5 - - 102.7 6.5 72.5 61.8 51.1 40.4 - ­67 100.3 5.7 90.9 79.3 68.5 57.8 47.0 - 94.8 6.3 88.1 77.4 66.7 56.0 45.3 ­62 92.3 5.6 92.3 92.3 86.5 76.2 64.9 54.1 87.3 6.2 87.3 87.3 82.6 71.9 61.1 50.4 57 92.2 5.6 92.2 92.2 86.6 76.3 65.0 54.2 87.5 6.2 87.5 87.5 81.7 71.0 60.3 49.6 77 121.1 5.9 63.0 52.6 40.6 - - - 114.3 6.6 62.0 50.1 38.1 - - ­72 112.5 5.8 80.9 68.9 56.9 45.0 - - 106.1 6.5 78.7 66.8 54.9 42.9 - ­67 103.8 5.7 98.9 85.3 73.3 61.3 49.3 - 97.9 6.4 95.4 83.5 71.6 59.6 47.7 ­62 95.6 5.6 95.6 95.6 92.5 81.5 68.6 56.6 90.2 6.3 90.2 90.2 88.6 76.7 64.8 52.8 57 95.4 5.6 95.4 95.4 92.6 81.7 68.6 56.6 90.4 6.2 90.4 90.4 87.7 75.8 63.9 51.9 72 114.6 5.8 88.6 75.6 62.6 49.6 - - 108.6 6.5 85.9 73.0 60.0 47.1 - ­67 105.7 5.7 103.3 93.6 80.6 67.6 54.6 - 100.3 6.4 99.0 91.3 78.3 65.4 52.4 ­62 97.4 5.6 97.4 97.4 95.8 83.3 69.8 56.8 92.3 6.3 92.3 92.3 91.6 78.6 65.7 52.7 57 97.2 5.6 97.2 97.2 95.8 83.3 69.7 56.7 92.5 6.3 92.5 92.5 91.2 78.3 65.3 52.3 72 116.6 5.8 96.3 82.3 68.3 54.2 - - 111.2 6.5 93.1 79.2 65.2 51.2 - ­67 107.7 5.7 107.7 101.9 87.9 73.8 59.8 - 102.6 6.4 102.6 99.0 85.1 71.1 57.1 ­62 99.1 5.6 99.1 99.1 99.1 85.1 71.0 57.0 94.5 6.3 94.5 94.5 94.5 80.5 66.5 52.6 57 99.0 5.6 99.0 99.0 99.0 84.9 70.9 56.8 94.7 6.3 94.7 94.7 94.7 80.7 66.7 52.8
77 101.2 7.2 49.3 39.9 30.6 - - - 100.5 8.0 59.5 50.1 40.7 - - ­72 93.9 7.1 63.9 54.6 45.2 35.8 - - 90.2 7.9 67.7 58.3 48.9 39.4 - ­67 86.6 7.0 78.6 69.2 59.8 50.4 41.0 - 79.9 7.8 75.8 66.4 57.0 47.6 38.2 ­62 79.8 6.9 79.8 79.8 72.5 63.1 53.7 44.4 74.8 7.7 74.8 74.8 67.3 57.9 48.5 39.0 57 80.3 6.8 80.3 80.3 70.9 61.5 52.1 42.8 74.9 7.7 74.9 74.9 65.7 56.2 46.8 37.4 77 104.3 7.3 55.2 43.8 33.1 - - - 103.7 8.0 68.8 55.1 44.4 - - ­72 96.8 7.1 70.2 59.6 49.0 38.3 - - 93.0 8.0 74.6 63.9 53.3 42.6 - ­67 89.3 7.0 85.3 75.4 64.8 54.2 43.5 - 82.4 7.9 80.4 72.8 62.1 51.4 40.8 ­62 82.3 6.9 82.3 82.3 78.6 67.5 57.4 46.7 77.2 7.7 77.2 77.2 73.3 62.4 52.0 41.3 57 82.8 6.9 82.8 82.8 76.9 65.7 55.6 45.0 77.2 7.7 77.2 77.2 71.5 60.6 50.2 39.5 77 107.5 7.3 61.0 47.6 35.7 - - - 106.8 8.1 78.1 60.0 48.1 - - ­72 99.7 7.2 76.5 64.6 52.8 40.9 - - 95.9 8.0 81.5 69.6 57.7 45.8 - ­67 92.0 7.0 92.0 81.7 69.8 57.9 46.1 - 84.9 7.9 84.9 79.1 67.2 55.3 43.4 ­62 84.7 6.9 84.7 84.7 84.7 71.9 61.0 49.1 79.6 7.8 79.6 79.6 79.3 66.9 55.5 43.6 57 85.3 6.9 85.3 85.3 82.9 69.9 59.1 47.2 79.6 7.7 79.6 79.6 77.4 64.9 53.6 41.6 72 102.7 7.2 83.2 70.3 57.4 44.6 - - 98.8 8.0 87.6 76.1 63.2 50.2 - ­67 94.8 7.1 94.8 88.9 76.0 63.1 50.2 - 87.5 7.9 87.5 84.2 73.6 60.6 47.7 ­62 87.3 6.9 87.3 87.3 87.3 73.9 61.5 48.6 82.0 7.8 82.0 82.0 81.8 68.6 55.9 43.0 57 87.8 6.9 87.8 87.8 86.6 73.2 60.8 48.0 82.0 7.8 82.0 82.0 80.9 67.7 55.0 42.1 72 105.7 7.2 89.9 76.0 62.1 48.2 - - 101.7 8.0 93.8 82.7 68.7 54.7 - ­67 97.5 7.1 97.5 96.1 82.2 68.3 54.4 - 90.1 7.9 90.1 89.4 79.9 65.9 52.0 ­62 89.8 7.0 89.8 89.8 89.8 75.9 62.0 48.1 84.4 7.8 84.4 84.4 84.4 70.4 56.4 42.4 57 90.4 6.9 90.4 90.4 90.4 76.5 62.6 48.7 84.4 7.8 84.4 84.4 84.4 70.5 56.5 42.5
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
505428-YTG-N-0712
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 49
505428-YTG-N-0712
PC090/NC090 Cooling Capacities (Continued)
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
1
WB (°F)
77 99.8 8.8 69.7 60.3 50.9 - - - 99.1 9.6 79.9 70.5 61.0 - - ­72 86.5 8.7 71.4 62.0 52.6 43.1 - - 82.7 9.5 75.2 65.7 56.3 46.8 - ­67 73.1 8.7 73.1 63.7 54.2 44.8 35.4 - 66.4 9.5 66.4 60.9 51.5 42.0 32.6 ­62 69.9 8.5 69.9 69.9 62.0 52.6 43.2 33.7 64.9 9.4 64.9 64.9 56.8 47.3 37.9 28.4 57 69.5 8.5 69.5 69.5 60.4 50.9 41.5 32.1 64.1 9.4 64.1 64.1 55.1 45.6 36.2 26.7 77 103.0 8.8 82.4 66.4 55.7 - - - 102.3 9.6 92.7 77.7 67.0 - - ­72 89.2 8.8 78.9 68.2 57.6 46.9 - - 85.4 9.6 83.3 72.6 61.9 51.2 - ­67 75.5 8.7 75.5 70.1 59.4 48.7 38.0 - 68.5 9.6 68.5 67.4 56.7 46.0 35.3 ­62 72.1 8.6 72.1 72.1 67.9 57.3 46.6 35.9 67.0 9.4 67.0 67.0 62.6 52.1 41.2 30.5 57 71.7 8.6 71.7 71.7 66.1 55.4 44.8 34.1 66.2 9.4 66.2 66.2 60.7 50.3 39.3 28.6 77 106.2 8.9 95.1 72.5 60.5 - - - 105.6 9.7 105.6 84.9 73.0 - - ­72 92.0 8.8 86.4 74.5 62.6 50.6 - - 88.1 9.6 88.1 79.4 67.5 55.5 - ­67 77.8 8.7 77.8 76.5 64.6 52.6 40.7 - 70.7 9.6 70.7 70.7 62.0 50.0 38.0 ­62 74.4 8.6 74.4 74.4 73.8 61.9 50.0 38.0 69.2 9.5 69.2 69.2 68.4 56.9 44.5 32.5 57 73.9 8.6 73.9 73.9 71.9 59.9 48.0 36.1 68.3 9.5 68.3 68.3 66.4 54.9 42.4 30.5 72 94.8 8.8 92.1 81.9 68.9 55.9 - - 90.9 9.7 90.9 87.7 74.6 61.5 - ­67 80.2 8.8 80.2 79.6 71.1 58.1 45.1 - 72.9 9.6 72.9 72.9 68.7 55.6 42.5 ­62 76.7 8.6 76.7 76.7 76.4 63.4 50.4 37.4 71.3 9.5 71.3 71.3 71.0 58.1 44.8 31.7 57 76.2 8.6 76.2 76.2 75.2 62.2 49.2 36.2 70.4 9.5 70.4 70.4 69.5 56.7 43.3 30.3 72 97.7 8.8 97.7 89.3 75.2 61.1 - - 93.7 9.7 93.7 93.7 81.8 67.6 - ­67 82.6 8.8 82.6 82.6 77.7 63.6 49.5 - 75.2 9.6 75.2 75.2 75.2 61.2 47.0 ­62 79.0 8.7 79.0 79.0 79.0 64.9 50.8 36.7 73.5 9.5 73.5 73.5 73.5 59.3 45.2 31.0 57 78.5 8.6 78.5 78.5 78.5 64.4 50.3 36.3 72.6 9.5 72.6 72.6 72.6 58.4 44.2 30.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
50 Johnson Controls Unitary Products
PC120/NC120
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
WB (°F)
77 140.5 7.5 70.2 58.2 46.2 - - - 134.2 8.6 65.0 52.8 40.6 - - ­72 133.6 7.5 87.5 75.5 63.5 51.5 - - 127.3 8.5 84.4 72.2 59.9 47.7 - ­67 126.6 7.4 104.8 92.8 80.8 68.9 56.9 - 120.3 8.5 103.8 91.5 79.3 67.1 54.8 ­62 120.2 7.4 120.2 120.2 107.7 95.7 83.8 71.8 113.2 8.4 113.2 113.2 101.2 88.9 76.7 64.5 57 121.8 7.3 121.8 123.0 114.5 102.5 90.5 78.6 117.1 8.4 117.1 117.1 106.6 94.4 82.2 69.9 77 147.3 7.7 74.8 62.4 49.1 - - - 140.4 8.7 71.4 57.6 43.7 - - ­72 140.0 7.6 93.9 80.6 67.3 54.1 - - 133.2 8.7 92.3 78.4 64.6 50.7 - ­67 132.8 7.6 112.9 98.8 85.5 72.3 59.0 - 125.9 8.6 113.2 99.3 85.5 71.6 57.8 ­62 126.0 7.6 126.0 126.0 114.2 101.0 87.6 74.4 118.5 8.5 118.5 118.5 109.0 95.2 81.3 67.5 57 127.7 7.5 127.7 128.3 121.4 108.7 94.9 81.6 122.5 8.5 122.5 122.5 114.9 101.1 87.2 73.4 77 154.1 7.8 79.4 66.6 52.0 - - - 146.6 8.9 77.8 62.3 46.9 - - ­72 146.5 7.8 100.2 85.7 71.1 56.6 - - 139.0 8.8 100.2 84.7 69.2 53.8 - ­67 138.9 7.8 121.1 104.8 90.2 75.7 61.1 - 131.5 8.7 122.5 107.1 91.6 76.2 60.7 ­62 131.8 7.8 131.8 131.8 120.6 106.3 91.5 76.9 123.7 8.7 123.7 123.7 116.9 101.4 86.0 70.5 57 133.6 7.6 133.6 133.6 128.3 114.8 99.2 84.6 127.9 8.6 127.9 127.9 123.2 107.7 92.3 76.8 72 148.2 7.7 110.0 94.1 78.1 62.2 - - 140.9 8.7 108.1 91.5 74.8 58.1 - ­67 140.5 7.7 131.6 115.2 99.3 83.4 67.5 - 133.2 8.6 128.7 115.6 99.0 82.3 65.6 ­62 133.4 7.7 133.4 133.4 127.8 112.0 95.9 80.0 125.3 8.6 125.3 125.3 121.9 105.3 88.6 71.9 57 135.2 7.5 135.2 135.2 132.5 117.2 100.7 84.8 129.6 8.6 129.6 129.6 127.2 110.6 93.9 77.2 72 150.0 7.6 119.7 102.4 85.1 67.9 - - 142.7 8.6 116.1 98.2 80.3 62.5 - ­67 142.2 7.5 142.2 125.6 108.3 91.1 73.8 - 134.9 8.5 134.9 124.2 106.3 88.4 70.5 ­62 134.9 7.5 134.9 134.9 134.9 117.6 100.4 83.1 127.0 8.5 127.0 127.0 127.0 109.1 91.2 73.3 57 136.7 7.4 136.7 136.7 136.7 119.5 102.2 84.9 131.3 8.5 131.3 131.3 131.3 113.4 95.5 77.6
77 128.0 9.7 59.9 47.4 34.9 - - - 120.6 10.9 59.2 46.6 34.0 - - ­72 121.0 9.6 81.3 68.8 56.3 43.8 - - 113.1 10.8 79.6 67.0 54.4 41.8 - ­67 114.1 9.5 102.8 90.3 77.8 65.3 52.8 - 105.6 10.7 100.0 87.4 74.7 62.1 49.5 ­62 106.3 9.3 106.3 106.3 94.7 82.2 69.7 57.2 101.1 10.6 101.1 101.1 90.6 78.0 65.4 52.8 57 112.4 9.5 112.4 111.3 98.8 86.3 73.8 61.3 104.8 10.7 104.8 104.2 92.7 80.1 67.5 54.9 77 133.6 9.8 68.0 52.7 38.3 - - - 126.1 11.0 69.7 51.8 37.3 - - ­72 126.3 9.7 90.7 76.3 61.9 47.4 - - 118.3 10.9 88.6 74.1 59.6 45.1 - ­67 119.0 9.6 113.4 99.8 85.4 71.0 56.5 - 110.4 10.8 107.6 96.5 82.0 67.5 53.0 ­62 111.0 9.4 111.0 111.0 103.9 89.4 75.1 60.6 105.7 10.7 105.7 105.7 99.3 84.8 70.3 55.8 57 117.3 9.6 117.3 116.7 108.4 93.4 79.6 65.1 109.5 10.8 109.5 109.3 101.6 86.9 72.6 58.1 77 139.1 9.9 76.2 58.1 41.7 - - - 131.6 11.1 80.1 56.9 40.5 - - ­72 131.6 9.8 100.1 83.7 67.4 51.0 - - 123.4 11.0 97.7 81.3 64.9 48.5 - ­67 124.0 9.7 124.0 109.4 93.0 76.6 60.3 - 115.2 10.9 115.2 105.6 89.2 72.8 56.4 ­62 115.6 9.5 115.6 115.6 113.2 96.5 80.5 64.1 110.3 10.8 110.3 110.3 108.1 91.6 75.3 58.9 57 122.2 9.7 122.2 122.2 118.1 100.6 85.4 69.0 114.3 10.9 114.3 114.3 110.6 93.6 77.8 61.4 72 133.5 9.7 106.3 88.9 71.5 54.0 - - 124.9 10.9 104.6 86.9 69.3 51.7 - ­67 125.8 9.6 125.8 116.1 98.6 81.2 63.8 - 116.6 10.8 116.6 110.6 95.3 77.7 60.1 ­62 117.3 9.5 117.3 117.3 116.1 98.5 81.2 63.8 111.6 10.7 111.6 111.6 110.5 92.8 75.3 57.6 57 124.0 9.6 124.0 124.0 122.0 104.0 87.1 69.7 115.7 10.8 115.7 115.7 113.8 95.9 78.6 61.0 72 135.4 9.6 112.5 94.0 75.5 57.0 - - 126.3 10.9 111.5 92.6 73.8 55.0 - ­67 127.6 9.5 127.6 122.8 104.3 85.8 67.3 - 118.0 10.8 118.0 115.5 101.5 82.6 63.8 ­62 119.0 9.4 119.0 119.0 119.0 100.5 82.0 63.5 112.9 10.7 112.9 112.9 112.9 94.1 75.2 56.4 57 125.8 9.5 125.8 125.8 125.8 107.3 88.8 70.3 117.0 10.7 117.0 117.0 117.0 98.2 79.4 60.5
Total
Capacity
(MBh)
505428-YTG-N-0712
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
(kW)
Total Input
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 51
505428-YTG-N-0712
PC120/NC120 (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
1
WB (°F)
77 113.3 12.1 58.5 45.8 33.1 - - - 105.9 13.2 57.8 45.0 32.1 - - ­72 105.2 12.0 77.8 65.1 52.4 39.7 - - 97.3 13.2 76.1 63.2 50.4 37.6 - ­67 97.2 11.9 97.2 84.4 71.7 59.0 46.3 - 88.7 13.1 88.7 81.5 68.7 55.8 43.0 ­62 95.9 11.8 95.9 95.9 86.5 73.8 61.1 48.4 90.6 13.1 90.6 90.6 82.5 69.6 56.8 43.9 57 97.1 11.8 97.1 97.1 86.6 73.9 61.2 48.4 89.5 13.0 89.5 89.5 80.5 67.7 54.8 42.0 77 118.7 12.2 71.3 50.8 36.2 - - - 111.3 13.4 72.9 49.8 35.2 - - ­72 110.2 12.1 86.5 72.0 57.4 42.8 - - 102.2 13.3 84.4 69.8 55.1 40.5 - ­67 101.8 12.0 101.8 93.1 78.5 64.0 49.4 - 93.2 13.2 93.2 89.8 75.1 60.4 45.8 ­62 100.4 11.9 100.4 100.4 94.8 80.2 65.6 51.0 95.2 13.2 95.2 95.2 90.2 75.6 60.9 46.2 57 101.8 12.0 101.8 101.8 94.8 80.3 65.7 51.1 94.0 13.2 94.0 94.0 88.1 73.7 58.8 44.1 77 124.1 12.3 84.0 55.8 39.4 - - - 116.6 13.5 88.0 54.6 38.2 - - ­72 115.3 12.2 95.2 78.8 62.4 45.9 - - 107.1 13.4 92.8 76.3 59.9 43.4 - ­67 106.4 12.1 106.4 101.8 85.4 68.9 52.5 - 97.7 13.3 97.7 97.7 81.5 65.1 48.6 ­62 105.0 12.1 105.0 105.0 103.0 86.6 70.1 53.7 99.7 13.3 99.7 99.7 97.9 81.6 65.0 48.5 57 106.4 12.1 106.4 106.4 103.1 86.7 70.2 53.8 98.5 13.3 98.5 98.5 95.6 79.7 62.7 46.2 72 116.3 12.1 102.8 85.0 67.2 49.4 - - 107.6 13.3 101.0 83.1 65.1 47.1 - ­67 107.3 12.0 107.3 105.0 92.0 74.2 56.4 - 98.1 13.3 98.1 98.1 88.7 70.7 52.7 ­62 105.9 12.0 105.9 105.9 104.9 87.1 69.3 51.5 100.2 13.2 100.2 100.2 99.3 81.4 63.3 45.4 57 107.3 12.0 107.3 107.3 105.7 87.9 70.1 52.3 98.9 13.2 98.9 98.9 97.5 79.8 61.5 43.6 72 117.2 12.1 110.4 91.2 72.0 52.9 - - 108.1 13.3 108.1 89.8 70.3 50.8 - ­67 108.3 12.0 108.3 108.3 98.6 79.5 60.3 - 98.6 13.2 98.6 98.6 95.8 76.3 56.8 ­62 106.8 11.9 106.8 106.8 106.8 87.6 68.5 49.3 100.7 13.2 100.7 100.7 100.7 81.2 61.7 42.2 57 108.2 11.9 108.2 108.2 108.2 89.0 69.9 50.7 99.4 13.1 99.4 99.4 99.4 79.9 60.4 40.9
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
52 Johnson Controls Unitary Products
PC180/NC180
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB
(°F)
77 223.0 12.5 104.1 85.2 66.4 - - - 216.7 13.8 104.7 85.9 67.0 - - ­72 209.3 12.3 134.7 115.8 97.0 78.1 - - 200.9 13.6 133.0 114.1 95.2 76.3 - ­67 195.7 12.1 165.2 146.4 127.6 108.7 89.9 - 185.0 13.4 161.2 142.3 123.4 104.5 85.7 ­62 176.7 11.8 176.7 176.7 152.0 133.2 114.3 95.5 169.4 13.0 169.4 169.4 151.2 132.4 113.5 94.6 57 179.6 11.8 179.6 179.6 159.1 140.3 121.4 102.6 173.1 13.1 173.1 173.1 154.4 135.5 116.7 97.8 77 229.0 12.6 113.8 93.3 71.8 - - - 221.4 13.9 114.8 93.3 71.7 - - ­72 215.0 12.4 147.9 126.3 104.8 83.3 - - 205.2 13.6 145.0 123.5 101.9 80.3 - ­67 200.9 12.2 181.9 159.4 137.8 116.3 94.8 - 189.1 13.4 175.2 153.7 132.1 110.5 88.9 ­62 181.4 11.8 181.4 181.4 164.3 143.6 121.3 99.8 173.0 13.1 173.0 173.0 161.9 140.3 118.7 97.1 57 184.5 11.9 184.5 184.5 171.9 151.4 128.9 107.4 176.9 13.1 176.9 176.9 165.3 143.7 122.1 100.6 77 235.0 12.6 123.5 101.4 77.2 - - - 226.1 13.9 124.9 100.6 76.4 - - ­72 220.6 12.4 161.0 136.9 112.7 88.5 - - 209.6 13.7 157.1 132.8 108.6 84.3 - ­67 206.2 12.2 198.5 172.3 148.1 123.9 99.8 - 193.1 13.4 189.3 165.0 140.8 116.5 92.2 ­62 186.2 11.9 186.2 186.2 176.7 154.1 128.3 104.1 176.7 13.1 176.7 176.7 172.5 148.2 124.0 99.7 57 189.3 11.9 189.3 189.3 184.8 162.6 136.4 112.2 180.6 13.2 180.6 180.6 176.1 151.8 127.6 103.3 72 223.2 12.5 170.5 144.3 118.1 91.9 - - 213.0 13.7 168.5 142.1 115.7 89.3 - ­67 208.6 12.3 204.8 181.5 155.3 129.1 102.9 - 196.2 13.5 194.3 176.4 150.0 123.6 97.3 ­62 188.4 11.9 188.4 188.4 183.6 158.3 131.3 105.1 179.6 13.2 179.6 179.6 177.5 151.1 124.7 98.3 57 191.6 12.0 191.6 191.6 189.3 164.1 136.9 110.7 183.6 13.2 183.6 183.6 181.3 154.9 128.5 102.2 72 225.9 12.6 179.9 151.7 123.5 95.3 - - 216.4 13.8 179.9 151.4 122.9 94.4 - ­67 211.1 12.4 211.1 190.7 162.5 134.3 106.1 - 199.4 13.5 199.4 187.8 159.3 130.8 102.3 ­62 190.6 12.0 190.6 190.6 190.6 162.4 134.2 106.0 182.5 13.2 182.5 182.5 182.5 154.0 125.5 97.0 57 193.8 12.1 193.8 193.8 193.8 165.6 137.4 109.2 186.5 13.3 186.5 186.5 186.5 158.0 129.5 101.0
77 210.5 15.1 105.4 86.5 67.6 - - - 192.8 16.7 98.9 80.0 61.1 - - ­72 192.4 14.9 131.3 112.4 93.4 74.5 - - 177.2 16.5 125.6 106.7 87.8 68.9 - ­67 174.4 14.6 157.1 138.2 119.3 100.4 81.4 - 161.6 16.3 152.4 133.5 114.6 95.7 76.8 ­62 162.0 14.3 162.0 162.0 150.5 131.6 112.6 93.7 150.1 16.0 150.1 150.1 142.4 123.5 104.6 85.7 57 166.6 14.4 166.6 166.6 149.8 130.8 111.9 93.0 155.1 16.1 155.1 155.1 137.9 119.0 100.1 81.2 77 213.8 15.2 115.9 93.2 71.6 - - - 196.5 16.7 114.1 86.9 65.3 - - ­72 195.5 14.9 142.2 120.6 99.0 77.3 - - 180.6 16.5 137.1 115.5 93.8 72.2 - ­67 177.2 14.6 168.6 148.0 126.3 104.7 83.1 - 164.7 16.3 160.1 144.1 122.4 100.8 79.2 ­62 164.7 14.4 164.7 164.7 159.4 136.9 116.1 94.5 153.0 16.1 153.0 153.0 152.2 130.1 108.9 87.3 57 169.2 14.4 169.2 169.2 158.6 136.0 115.3 93.7 158.1 16.1 158.1 158.1 147.3 125.2 104.1 82.4 77 217.2 15.2 126.3 99.9 75.6 - - - 200.2 16.8 129.3 93.8 69.4 - - ­72 198.6 14.9 153.1 128.8 104.5 80.1 - - 184.1 16.5 148.6 124.2 99.9 75.5 - ­67 180.0 14.6 180.0 157.7 133.4 109.0 84.7 - 167.9 16.3 167.9 154.7 130.3 106.0 81.6 ­62 167.3 14.4 167.3 167.3 168.3 142.3 119.6 95.3 155.9 16.1 155.9 155.9 162.0 136.8 113.2 88.9 57 171.9 14.4 171.9 171.9 167.5 141.1 118.8 94.5 161.1 16.1 161.1 161.1 156.7 131.4 108.0 83.7 72 202.8 15.0 166.5 139.9 113.4 86.8 - - 187.4 16.6 160.8 134.3 107.7 81.1 - ­67 183.8 14.7 183.8 171.3 144.7 118.2 91.6 - 170.9 16.4 170.9 163.6 140.5 113.9 87.3 ­62 170.8 14.4 170.8 170.8 171.3 143.9 118.2 91.6 158.7 16.1 158.7 158.7 161.7 134.7 108.6 82.0 57 175.6 14.5 175.6 175.6 173.3 145.8 120.2 93.6 164.0 16.2 164.0 164.0 161.8 134.7 108.6 82.1 72 207.0 15.0 179.8 151.0 122.2 93.5 - - 190.7 16.6 173.1 144.3 115.5 86.7 - ­67 187.6 14.7 187.6 184.9 156.1 127.3 98.5 - 173.9 16.4 173.9 172.5 150.7 121.9 93.1 ­62 174.3 14.4 174.3 174.3 174.3 145.5 116.7 87.9 161.5 16.2 161.5 161.5 161.5 132.7 103.9 75.1 57 179.2 14.5 179.2 179.2 179.2 150.4 121.6 92.8 166.8 16.2 166.8 166.8 166.8 138.1 109.3 80.5
Total
Capacity
(MBh)
505428-YTG-N-0712
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 53
505428-YTG-N-0712
PC180/NC180 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 175.1 18.3 92.4 73.5 54.6 - - - 157.4 19.9 85.8 67.0 48.1 - - ­72 162.0 18.1 120.0 101.1 82.2 63.3 - - 146.7 19.8 114.3 95.5 76.6 57.8 - ­67 148.8 18.0 147.6 128.7 109.8 91.0 72.1 - 136.1 19.6 136.1 124.0 105.1 86.3 67.4 ­62 138.1 17.8 138.1 138.1 134.4 115.5 96.6 77.7 126.2 19.5 126.2 126.2 126.2 107.5 88.6 69.7 57 143.6 17.8 143.6 143.6 126.1 107.2 88.3 69.4 132.1 19.6 132.1 132.1 114.2 95.4 76.5 57.6 77 179.2 18.3 112.3 80.6 58.9 - - - 161.8 19.9 110.6 74.3 52.6 - - ­72 165.7 18.1 132.0 110.4 88.7 67.1 - - 150.8 19.8 126.9 105.3 83.6 62.0 - ­67 152.3 18.0 151.7 140.2 118.6 96.9 75.3 - 139.9 19.6 139.9 136.3 114.7 93.0 71.4 ­62 141.3 17.8 141.3 141.3 145.0 123.4 101.7 80.1 129.7 19.5 129.7 129.7 129.7 116.6 94.6 72.9 57 146.9 17.8 146.9 146.9 136.1 114.4 92.8 71.1 135.7 19.6 135.7 135.7 124.8 103.6 81.5 59.9 77 183.2 18.3 132.3 87.6 63.3 - - - 166.2 19.9 135.3 81.5 57.1 - - ­72 169.5 18.1 144.0 119.6 95.3 70.9 - - 154.9 19.8 139.5 115.1 90.6 66.2 - ­67 155.8 18.0 155.8 151.6 127.3 102.9 78.5 - 143.6 19.6 143.6 143.6 124.2 99.8 75.4 ­62 144.5 17.8 144.5 144.5 155.7 131.3 106.9 82.5 133.2 19.5 133.2 133.2 133.2 125.8 100.5 76.1 57 150.2 17.9 150.2 150.2 146.0 121.6 97.3 72.9 139.4 19.6 139.4 139.4 135.3 111.9 86.5 62.1 72 171.9 18.2 155.2 128.6 102.0 75.4 - - 156.4 19.8 149.5 122.9 96.3 69.7 - ­67 158.0 18.0 158.0 155.9 136.3 109.7 83.1 - 145.1 19.7 145.1 145.1 132.0 105.4 78.8 ­62 146.6 17.8 146.6 146.6 152.1 125.6 99.0 72.4 134.5 19.5 134.5 134.5 134.5 116.4 89.4 62.7 57 152.4 17.9 152.4 152.4 150.3 123.7 97.1 70.5 140.8 19.6 140.8 140.8 138.8 112.7 85.5 58.9 72 174.3 18.2 166.3 137.5 108.8 80.0 - - 158.0 19.9 158.0 130.8 102.0 73.2 - ­67 160.2 18.1 160.2 160.2 145.3 116.5 87.7 - 146.5 19.8 146.5 146.5 139.9 111.1 82.3 ­62 148.6 17.9 148.6 148.6 148.6 119.8 91.0 62.3 135.8 19.6 135.8 135.8 135.8 107.0 78.2 49.4 57 154.5 18.0 154.5 154.5 154.5 125.7 96.9 68.1 142.2 19.7 142.2 142.2 142.2 113.4 84.6 55.8
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
54 Johnson Controls Unitary Products
PD180/ND180
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB
(°F)
77 231.4 12.4 111.6 93.0 74.5 - - - 219.9 13.7 106.4 87.9 69.5 - - ­72 215.6 12.0 142.9 124.4 105.8 87.2 - - 204.0 13.4 138.2 119.7 101.2 82.8 - ­67 199.7 11.7 174.3 155.7 137.2 118.6 100.0 - 188.1 13.1 169.9 151.4 133.0 114.5 96.0 ­62 183.7 11.4 183.7 183.7 170.7 152.1 133.6 115.0 174.3 12.8 174.3 174.3 163.8 145.3 126.9 108.4 57 184.6 11.4 184.6 184.6 173.2 154.6 136.1 117.5 175.3 12.8 175.3 175.3 164.8 146.3 127.8 109.4 77 233.6 12.4 117.3 98.2 76.9 - - - 222.0 13.7 114.1 92.9 71.7 - - ­72 217.6 12.1 151.9 130.6 109.3 88.0 - - 206.0 13.4 146.9 125.7 104.5 83.3 - ­67 201.6 11.7 186.5 163.0 141.7 120.4 99.1 - 189.9 13.1 179.7 158.5 137.2 116.0 94.8 ­62 185.5 11.4 185.5 185.5 176.3 155.6 133.7 112.4 176.0 12.8 176.0 176.0 169.1 147.9 126.6 105.4 57 186.3 11.4 186.3 186.3 178.9 158.5 136.3 115.0 177.0 12.8 177.0 177.0 170.1 148.8 127.6 106.4 77 235.8 12.4 123.1 103.4 79.4 - - - 224.2 13.7 121.8 97.9 73.9 - - ­72 219.7 12.1 160.9 136.9 112.8 88.7 - - 208.0 13.4 155.6 131.7 107.7 83.8 - ­67 203.5 11.7 198.8 170.3 146.2 122.2 98.1 - 191.8 13.1 189.4 165.5 141.5 117.6 93.6 ­62 187.2 11.4 187.2 187.2 182.0 159.2 133.8 109.8 177.7 12.9 177.7 177.7 174.3 150.4 126.4 102.5 57 188.0 11.4 188.0 188.0 184.6 162.4 136.5 112.4 178.7 12.9 178.7 178.7 175.4 151.4 127.5 103.5 72 222.5 12.1 171.1 144.6 118.1 91.7 - - 210.6 13.5 165.7 139.4 113.2 86.9 - ­67 206.2 11.8 203.8 179.6 153.2 126.7 100.2 - 194.2 13.2 193.0 174.9 148.6 122.4 96.1 ­62 189.7 11.5 189.7 189.7 187.0 161.2 134.1 107.6 180.0 12.9 180.0 180.0 178.3 152.0 125.7 99.5 57 190.5 11.5 190.5 190.5 188.8 163.3 135.9 109.4 181.0 12.9 181.0 181.0 179.3 153.1 126.8 100.5 72 225.4 12.2 181.3 152.4 123.5 94.6 - - 213.3 13.6 175.8 147.2 118.6 90.0 - ­67 208.9 11.8 208.9 189.0 160.1 131.2 102.3 - 196.7 13.2 196.7 184.4 155.8 127.2 98.6 ­62 192.1 11.5 192.1 192.1 192.1 163.2 134.3 105.5 182.2 13.0 182.2 182.2 182.2 153.6 125.0 96.4 57 193.0 11.5 193.0 193.0 193.0 164.1 135.2 106.3 183.3 13.0 183.3 183.3 183.3 154.7 126.1 97.5
77 208.3 15.1 101.3 82.9 64.5 - - - 192.0 17.0 96.4 77.9 59.4 - - ­72 192.4 14.8 133.4 115.0 96.6 78.3 - - 177.3 16.7 128.6 110.2 91.7 73.2 - ­67 176.4 14.5 165.5 147.2 128.8 110.4 92.0 - 162.5 16.4 157.1 142.5 124.0 105.5 87.0 ­62 164.9 14.3 164.9 164.9 156.9 138.5 120.2 101.8 153.2 16.2 153.2 153.2 149.2 130.7 112.3 93.8 57 166.1 14.3 166.1 166.1 156.3 138.0 119.6 101.2 155.2 16.2 155.2 155.2 146.0 127.5 109.0 90.6 77 210.5 15.1 110.9 87.6 66.5 - - - 193.9 17.0 110.4 82.4 61.2 - - ­72 194.3 14.8 141.9 120.8 99.7 78.5 - - 179.0 16.7 136.8 115.7 94.5 73.4 - ­67 178.2 14.5 172.8 153.9 132.8 111.7 90.6 - 164.1 16.4 161.4 149.0 127.8 106.6 85.5 ­62 166.5 14.3 166.5 166.5 161.8 140.1 119.6 98.5 154.7 16.2 154.7 154.7 154.2 132.7 111.9 90.7 57 167.8 14.3 167.8 167.8 161.2 139.2 119.0 97.9 156.8 16.2 156.8 156.8 150.5 128.9 108.2 87.0 77 212.6 15.1 120.6 92.3 68.5 - - - 195.8 17.0 124.4 86.9 63.1 - - ­72 196.3 14.8 150.3 126.5 102.7 78.8 - - 180.8 16.7 145.0 121.2 97.3 73.5 - ­67 180.0 14.5 180.0 160.6 136.8 113.0 89.2 - 165.7 16.4 165.7 155.5 131.6 107.8 83.9 ­62 168.2 14.3 168.2 168.2 166.7 141.6 119.0 95.2 156.2 16.2 156.2 156.2 159.2 134.7 111.5 87.6 57 169.5 14.3 169.5 169.5 166.1 140.4 118.4 94.6 158.3 16.2 158.3 158.3 155.0 130.2 107.3 83.4 72 198.7 14.9 160.3 134.2 108.2 82.1 - - 183.0 16.8 155.6 129.3 103.0 76.7 - ­67 182.2 14.6 182.2 170.2 144.1 118.0 92.0 - 167.8 16.5 167.8 161.5 139.3 113.0 86.7 ­62 170.3 14.3 170.3 170.3 169.5 142.8 117.4 91.3 158.2 16.2 158.2 158.2 159.7 133.0 107.1 80.8 57 171.6 14.4 171.6 171.6 169.9 142.9 117.7 91.6 160.3 16.3 160.3 160.3 158.6 131.9 106.0 79.7 72 201.2 14.9 170.3 142.0 113.6 85.3 - - 185.3 16.8 166.3 137.5 108.8 80.0 - ­67 184.5 14.6 184.5 179.8 151.4 123.1 94.8 - 169.9 16.5 169.9 167.5 147.1 118.3 89.6 ­62 172.4 14.4 172.4 172.4 172.4 144.1 115.7 87.4 160.1 16.3 160.1 160.1 160.1 131.4 102.6 73.9 57 173.7 14.5 173.7 173.7 173.7 145.3 117.0 88.7 162.3 16.4 162.3 162.3 162.3 133.5 104.8 76.0
Total
Capacity
(MBh)
505428-YTG-N-0712
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 55
505428-YTG-N-0712
PD180/ND180 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 175.7 18.9 91.5 72.9 54.3 - - - 159.4 20.8 86.6 67.9 49.2 - - ­72 162.2 18.6 123.9 105.3 86.8 68.2 - - 147.1 20.5 119.1 100.5 81.8 63.1 - ­67 148.6 18.2 148.6 137.8 119.2 100.6 82.0 - 134.7 20.1 134.7 133.1 114.4 95.7 77.1 ­62 141.5 18.1 141.5 141.5 141.5 123.0 104.4 85.8 129.9 20.0 129.9 129.9 129.9 115.2 96.5 77.8 57 144.4 18.1 144.4 144.4 135.6 117.1 98.5 79.9 133.6 20.1 133.6 133.6 125.3 106.6 88.0 69.3 77 177.4 18.9 109.8 77.2 56.0 - - - 160.8 20.9 109.2 72.0 50.7 - - ­72 163.7 18.6 131.8 110.6 89.4 68.2 - - 148.4 20.5 126.8 105.5 84.3 63.0 - ­67 150.0 18.3 150.0 144.0 122.8 101.6 80.4 - 135.9 20.1 135.9 135.9 117.8 96.5 75.3 ­62 142.9 18.1 142.9 142.9 146.6 125.4 104.2 82.9 131.0 20.0 131.0 131.0 131.0 118.0 96.4 75.2 57 145.8 18.1 145.8 145.8 139.8 118.5 97.3 76.1 134.8 20.1 134.8 134.8 129.1 108.2 86.5 65.2 77 179.0 18.9 128.1 81.5 57.6 - - - 162.3 20.9 131.9 76.1 52.2 - - ­72 165.2 18.6 139.8 115.9 92.0 68.2 - - 149.7 20.5 134.5 110.6 86.7 62.8 - ­67 151.4 18.3 151.4 150.3 126.4 102.6 78.7 - 137.1 20.1 137.1 137.1 121.3 97.4 73.5 ­62 144.2 18.1 144.2 144.2 151.7 127.8 103.9 80.1 132.2 20.0 132.2 132.2 132.2 120.9 96.4 72.5 57 147.1 18.2 147.1 147.1 143.9 120.0 96.1 72.3 136.0 20.1 136.0 136.0 132.8 109.8 85.0 61.1 72 167.3 18.7 151.0 124.5 97.9 71.4 - - 151.6 20.6 146.3 119.6 92.8 66.1 - ­67 153.3 18.3 153.3 152.8 134.6 108.0 81.5 - 138.9 20.2 138.9 138.9 129.8 103.0 76.3 ­62 146.0 18.1 146.0 146.0 149.8 123.2 96.7 70.2 133.9 20.0 133.9 133.9 133.9 113.5 86.4 59.6 57 149.0 18.2 149.0 149.0 147.4 120.9 94.3 67.8 137.7 20.1 137.7 137.7 136.1 109.9 82.6 55.9 72 169.4 18.7 162.2 133.0 103.9 74.7 - - 153.5 20.6 153.5 128.6 99.0 69.4 - ­67 155.3 18.4 155.3 155.3 142.7 113.5 84.3 - 140.7 20.3 140.7 140.7 138.3 108.7 79.1 ­62 147.9 18.2 147.9 147.9 147.9 118.7 89.5 60.3 135.6 20.1 135.6 135.6 135.6 106.0 76.4 46.8 57 150.9 18.3 150.9 150.9 150.9 121.7 92.5 63.3 139.5 20.2 139.5 139.5 139.5 109.9 80.3 50.6
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
56 Johnson Controls Unitary Products
PD240/ND240
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
WB (°F)
77 314.8 15.1 142.6 118.0 93.5 - - - 300.0 17.0 137.0 112.4 87.8 - - ­72 285.9 14.8 177.4 152.9 128.3 103.8 - - 271.7 16.7 171.9 147.4 122.8 98.3 - ­67 257.1 14.5 212.3 187.7 163.2 138.6 114.0 - 243.5 16.4 206.9 182.4 157.8 133.2 108.7 ­62 239.1 14.2 239.1 225.1 200.5 175.9 151.4 126.8 227.5 16.1 227.5 219.3 194.7 170.2 145.6 121.1 57 239.5 14.3 239.5 237.8 213.3 188.7 164.1 139.6 230.2 16.2 230.2 227.8 203.3 178.7 154.1 129.6 77 321.1 15.2 154.7 127.4 100.0 - - - 305.7 17.1 148.9 121.5 94.1 - - ­72 291.7 14.9 192.0 164.7 137.3 110.0 - - 276.9 16.8 186.4 159.0 131.6 104.2 - ­67 262.3 14.6 229.3 201.9 174.6 147.2 119.9 - 248.1 16.5 223.9 196.5 169.1 141.7 114.4 ­62 243.9 14.3 243.9 236.9 214.5 188.2 159.8 132.5 231.9 16.2 231.9 227.7 208.7 181.3 154.0 126.6 57 244.3 14.5 244.3 243.5 228.2 203.0 173.5 146.1 234.5 16.3 234.5 233.4 217.9 190.5 163.1 135.7 77 327.5 15.3 166.9 136.7 106.6 - - - 311.4 17.2 160.9 130.7 100.5 - - ­72 297.5 15.0 206.6 176.5 146.3 116.2 - - 282.1 16.9 200.9 170.7 140.5 110.2 - ­67 267.5 14.8 246.3 216.2 186.0 155.9 125.7 - 252.8 16.6 240.9 210.7 180.5 150.2 120.0 ­62 248.8 14.4 248.8 248.8 228.6 200.4 168.3 138.1 236.2 16.2 236.2 236.2 222.7 192.5 162.3 132.1 57 249.2 14.6 249.2 249.2 243.2 217.3 182.9 152.7 238.9 16.4 238.9 238.9 232.5 202.2 172.0 141.8 72 303.3 15.2 219.3 184.7 150.2 115.7 - - 287.2 17.1 212.0 178.0 144.0 110.1 - ­67 272.7 14.9 262.1 225.5 191.0 156.5 122.0 - 257.4 16.8 251.5 219.1 185.1 151.1 117.1 ­62 253.6 14.6 253.6 253.6 234.7 201.2 165.6 131.1 240.5 16.4 240.5 240.5 228.4 194.4 160.4 126.5 57 254.0 14.7 254.0 254.0 249.7 217.3 180.6 146.1 243.3 16.6 243.3 243.3 238.4 204.4 170.4 136.4 72 309.0 15.4 231.9 193.0 154.1 115.2 - - 292.4 17.3 223.1 185.4 147.6 109.9 - ­67 277.8 15.1 277.8 234.9 196.0 157.1 118.2 - 262.0 17.0 262.0 227.4 189.7 151.9 114.2 ­62 258.4 14.7 258.4 258.4 240.8 201.9 163.0 124.1 244.8 16.6 244.8 244.8 234.1 196.4 158.6 120.9 57 258.8 14.9 258.8 258.8 256.2 217.3 178.4 139.5 247.6 16.8 247.6 247.6 244.3 206.6 168.8 131.1
77 285.2 18.9 131.3 106.8 82.2 - - - 264.8 21.2 126.0 101.4 76.8 - - ­72 257.5 18.6 166.4 141.9 117.3 92.8 - - 240.1 20.9 161.0 136.3 111.7 87.1 - ­67 229.9 18.2 201.5 177.0 152.4 127.9 103.3 - 215.3 20.5 195.9 171.3 146.7 122.1 97.5 ­62 216.0 18.0 216.0 213.5 189.0 164.4 139.9 115.3 203.2 20.2 203.2 202.0 183.1 158.5 133.9 109.2 57 220.8 18.1 220.8 217.8 193.2 168.7 144.1 119.6 209.8 20.4 209.8 206.5 181.9 157.3 132.6 108.0 77 290.2 19.0 143.1 115.7 88.3 - - - 269.2 21.3 142.0 110.2 82.7 - - ­72 262.1 18.6 180.8 153.4 126.0 98.5 - - 244.1 20.9 175.3 147.8 120.3 92.8 - ­67 234.0 18.3 218.5 191.1 163.7 136.3 108.8 - 219.0 20.6 208.6 185.4 157.9 130.4 102.9 ­62 219.8 18.0 219.8 218.6 202.9 174.5 148.1 120.7 206.6 20.3 206.6 206.0 197.1 169.1 142.1 114.6 57 224.7 18.2 224.7 223.2 207.5 177.9 152.6 125.2 213.3 20.5 213.3 211.7 195.8 167.2 140.8 113.3 77 295.2 19.0 154.9 124.6 94.3 - - - 273.7 21.4 158.1 119.0 88.5 - - ­72 266.6 18.7 195.2 164.9 134.6 104.3 - - 248.1 21.0 189.7 159.3 128.9 98.4 - ­67 238.0 18.4 235.5 205.2 174.9 144.6 114.3 - 222.6 20.7 221.3 199.6 169.2 138.8 108.3 ­62 223.6 18.1 223.6 223.6 216.9 184.6 156.3 126.0 210.0 20.4 210.0 210.0 211.2 179.7 150.3 119.9 57 228.6 18.3 228.6 228.6 221.8 187.2 161.2 130.9 216.9 20.6 216.9 216.9 209.7 177.2 148.9 118.5 72 271.1 19.0 204.8 171.3 137.9 104.4 - - 252.2 21.2 199.3 165.7 132.2 98.6 - ­67 242.1 18.6 240.8 212.6 179.1 145.7 112.3 - 226.2 20.9 225.6 207.1 173.6 140.0 106.4 ­62 227.4 18.3 227.4 227.4 222.1 187.7 155.2 121.8 213.4 20.6 213.4 213.4 213.0 179.0 145.9 112.4 57 232.5 18.5 232.5 232.5 227.1 191.5 160.2 126.8 220.4 20.8 220.4 220.4 215.2 180.5 148.0 114.5 72 275.7 19.2 214.3 177.7 141.1 104.5 - - 256.2 21.5 208.9 172.2 135.5 98.8 - ­67 246.1 18.8 246.1 219.9 183.4 146.8 110.2 - 229.8 21.1 229.8 214.6 177.9 141.2 104.6 ­62 231.2 18.6 231.2 231.2 227.3 190.8 154.2 117.6 216.8 20.8 216.8 216.8 214.9 178.2 141.5 104.8 57 236.4 18.7 236.4 236.4 232.5 195.9 159.3 122.7 223.9 21.0 223.9 223.9 220.6 183.9 147.2 110.5
Total
Capacity
(MBh)
505428-YTG-N-0712
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 57
505428-YTG-N-0712
PD240/ND240 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB (°F)
77 244.4 23.6 120.7 96.0 71.4 - - - 224.0 25.9 115.4 90.7 65.9 - - ­72 222.6 23.2 155.5 130.8 106.2 81.5 - - 205.1 25.5 150.0 125.3 100.6 75.8 - ­67 200.8 22.8 190.3 165.6 140.9 116.3 91.6 - 186.2 25.1 184.7 159.9 135.2 110.5 85.7 ­62 190.4 22.5 190.4 190.4 177.2 152.5 127.8 103.2 177.6 24.8 177.6 177.6 171.3 146.5 121.8 97.1 57 198.8 22.8 198.8 195.2 170.5 145.8 121.2 96.5 187.8 25.1 187.8 183.9 159.2 134.4 109.7 85.0 77 248.3 23.6 140.9 104.7 77.1 - - - 227.3 25.9 139.8 99.1 71.4 - - ­72 226.1 23.2 169.8 142.2 114.6 87.0 - - 208.1 25.5 164.3 136.6 108.9 81.3 - ­67 204.0 22.9 198.7 179.8 152.2 124.6 97.0 - 188.9 25.2 188.8 174.1 146.4 118.7 91.1 ­62 193.4 22.6 193.4 193.4 191.3 163.7 136.1 108.5 180.2 24.8 180.2 180.2 180.2 158.3 130.1 102.4 57 201.9 22.8 201.9 200.1 184.1 156.5 128.9 101.3 190.6 25.1 190.6 188.6 172.4 145.8 117.0 89.3 77 252.1 23.7 161.2 113.3 82.7 - - - 230.6 26.0 164.3 107.6 76.9 - - ­72 229.6 23.3 184.1 153.6 123.1 92.5 - - 211.1 25.6 178.6 148.0 117.3 86.7 - ­67 207.1 22.9 207.1 194.0 163.4 132.9 102.4 - 191.7 25.2 191.7 188.3 157.7 127.0 96.4 ­62 196.4 22.6 196.4 196.4 205.4 174.9 144.4 113.8 182.8 24.9 182.8 182.8 182.8 170.1 138.4 107.8 57 205.1 22.9 205.1 205.1 197.7 167.2 136.6 106.1 193.3 25.2 193.3 193.3 185.7 157.2 124.4 93.7 72 233.2 23.5 193.9 160.2 126.5 92.8 - - 214.2 25.8 188.4 154.6 120.8 87.0 - ­67 210.3 23.2 210.3 201.6 168.0 134.3 100.6 - 194.5 25.5 194.5 194.5 162.4 128.6 94.8 ­62 199.4 22.8 199.4 199.4 203.9 170.3 136.6 102.9 185.4 25.1 185.4 185.4 185.4 161.6 127.3 93.5 57 208.3 23.1 208.3 208.3 203.2 169.5 135.9 102.2 196.1 25.4 196.1 196.1 191.3 158.5 123.7 89.9 72 236.7 23.8 203.6 166.8 129.9 93.1 - - 217.2 26.1 198.2 161.3 124.3 87.4 - ­67 213.5 23.4 213.5 209.3 172.5 135.7 98.9 - 197.2 25.7 197.2 197.2 167.1 130.2 93.2 ­62 202.5 23.1 202.5 202.5 202.5 165.6 128.8 92.0 188.1 25.4 188.1 188.1 188.1 153.1 116.1 79.2 57 211.4 23.4 211.4 211.4 208.7 171.9 135.1 98.3 198.9 25.7 198.9 198.9 196.8 159.9 123.0 86.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
58 Johnson Controls Unitary Products
505428-YTG-N-0712
Heat Pump And Air Handler Heating Capacities
PC090 / NC090
Air Over Evaporator Coil
CFM DB (°F) -10 0 10 20 30 40 50 60
55
2250
3000
3750
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
70
80
55
70
80
55
70
80
Capacity1 &
kW
MBH 34.0 39.6 46.2 53.9 62.9 73.5 86.0 100.6
KW 4.9 5.3 5.6 6.0 6.3 6.7 7.0 7.3
MBH 31.0 36.6 43.2 50.9 60.0 70.6 83.0 97.6
KW 5.8 6.1 6.5 6.8 7.1 7.5 7.8 8.2
MBH 28.7 34.3 40.9 48.6 57.7 68.3 80.7 95.3
KW 6.4 6.8 7.1 7.4 7.8 8.1 8.5 8.8
MBH 35.3 40.9 47.5 55.2 64.3 74.9 87.3 101.9
KW 4.7 5.1 5.4 5.8 6.1 6.5 6.8 7.1
MBH 32.4 38.0 44.5 52.3 61.3 71.9 84.4 99.0
KW 5.6 5.9 6.3 6.6 6.9 7.3 7.6 8.0
MBH 30.1 35.7 42.3 50.0 59.0 69.6 82.1 96.7
KW 6.2 6.5 6.9 7.2 7.6 7.9 8.3 8.6
MBH 36.6 42.2 48.8 56.5 65.6 76.2 88.6 103.2
KW 5.2 5.6 5.9 6.3 6.6 7.0 7.3 7.6
MBH 33.7 39.3 45.8 53.6 62.6 73.2 85.7 100.3
KW 6.1 6.4 6.8 7.1 7.4 7.8 8.1 8.5
MBH 31.4 37.0 43.6 51.3 60.3 70.9 83.4 98.0
KW 6.7 7.0 7.4 7.7 8.1 8.4 8.8 9.1
Outdoor Temperature (°F @ 72% RH)
PC120 / NC120
Air Over Evaporator Coil
CFM DB (°F) -10 0 10 20 30 40 50 60
55
3000
4000
5000
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
70
80
55
70
80
55
70
80
Capacity1 &
kW
MBH 29.1 36.4 45.3 56.0 69.0 84.7 103.8 126.8
KW 6.9 7.3 7.6 8.0 8.3 8.7 9.1 9.4
MBH 26.3 33.6 42.4 53.1 66.1 81.8 100.9 124.0
KW 8.2 8.6 8.9 9.3 9.7 10.0 10.4 10.7
MBH 24.2 31.5 40.4 51.1 64.1 79.8 98.8 121.9
KW 9.2 9.6 10.0 10.3 10.7 11.1 11.4 11.8
MBH 37.4 44.7 53.5 64.3 77.2 93.0 112.0 135.1
KW 6.7 7.1 7.4 7.8 8.1 8.5 8.9 9.2
MBH 34.5 41.8 50.7 61.4 74.4 90.1 109.2 132.2
KW 8.0 8.4 8.7 9.1 9.5 9.8 10.2 10.6
MBH 32.5 39.8 48.6 59.3 72.3 88.0 107.1 130.2
KW 9.0 9.4 9.8 10.1 10.5 10.9 11.2 11.6
MBH 44.1 51.4 60.3 71.0 84.0 99.7 118.7 141.8
KW 6.9 7.2 7.6 8.0 8.3 8.7 9.0 9.4
MBH 41.3 48.6 57.4 68.1 81.1 96.8 115.9 138.9
KW 8.2 8.6 8.9 9.3 9.6 10.0 10.4 10.7
MBH 39.2 46.5 55.3 66.1 79.0 94.8 113.8 136.9
KW 9.2 9.6 9.9 10.3 10.7 11.0 11.4 11.7
Outdoor Temperature (°F @ 72% RH)
Johnson Controls Unitary Products 59
505428-YTG-N-0712
PC180 / NC180
Air Over Evaporator Coil
CFM DB (°F) -10 0 10 20 30 40 50 60
55
4500
70
80
55
6000
70
80
55
7500
70
80
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Capacity1 &
kW
MBH 68.2 80.0 93.8 110.0 129.1 151.5 177.8 208.7
KW 11.8 12.2 12.7 13.2 13.7 14.1 14.6 15.1
MBH 61.5 73.2 87.0 103.2 122.3 144.7 171.0 201.9
KW 13.5 14.0 14.4 14.9 15.4 15.9 16.3 16.8
MBH 57.6 69.3 83.1 99.3 118.4 140.8 167.1 198.0
KW 15.0 15.5 16.0 16.4 16.9 17.4 17.9 18.3
MBH 74.0 85.8 99.6 115.8 134.9 157.3 183.6 214.5
KW 11.2 11.7 12.2 12.6 13.1 13.6 14.1 14.6
MBH 67.3 79.0 92.8 109.0 128.1 150.5 176.8 207.7
KW 12.9 13.4 13.9 14.4 14.8 15.3 15.8 16.3
MBH 63.4 75.1 88.9 105.1 124.2 146.6 172.9 203.8
KW 14.5 14.9 15.4 15.9 16.4 16.8 17.3 17.8
MBH 72.4 84.1 97.9 114.1 133.2 155.6 181.9 212.8
KW 12.0 12.5 13.0 13.4 13.9 14.4 14.9 15.4
MBH 65.6 77.3 91.1 107.4 126.4 148.8 175.1 206.0
KW 13.7 14.2 14.7 15.2 15.6 16.1 16.6 17.1
MBH 61.7 73.4 87.3 103.5 122.5 144.9 171.2 202.1
KW 15.3 15.7 16.2 16.7 17.2 17.6 18.1 18.6
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
Outdoor Temperature (°F @ 72% RH)
PD180 / ND180
Air Over Evaporator Coil
CFM DB (°F) -10 0 10 20 30 40 50 60
55
4500
70
80
55
6000
70
80
55
7500
70
80
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Capacity1 &
kW
MBH 65.6 77.0 90.3 105.8 123.9 145.1 169.7 198.5
KW 10.0 10.5 11.1 11.6 12.2 12.7 13.3 13.8
MBH 62.2 73.6 86.9 102.4 120.5 141.6 166.3 195.1
KW 12.0 12.5 13.1 13.6 14.2 14.7 15.3 15.8
MBH 59.5 70.9 84.1 99.7 117.8 138.9 163.6 192.4
KW 13.4 13.9 14.5 15.0 15.6 16.1 16.7 17.2
MBH 71.6 83.0 96.3 111.8 129.9 151.0 175.7 204.5
KW 9.6 10.2 10.7 11.3 11.8 12.4 12.9 13.4
MBH 68.1 79.5 92.8 108.3 126.5 147.6 172.3 201.1
KW 11.6 12.2 12.7 13.3 13.8 14.3 14.9 15.4
MBH 65.4 76.8 90.1 105.6 123.7 144.9 169.6 198.3
KW 13.0 13.6 14.1 14.7 15.2 15.8 16.3 16.9
MBH 74.0 85.4 98.7 114.2 132.4 153.5 178.2 207.0
KW 11.3 11.8 12.4 12.9 13.5 14.0 14.6 15.1
MBH 70.6 82.0 95.3 110.8 128.9 150.1 174.7 203.5
KW 13.3 13.8 14.4 14.9 15.5 16.0 16.6 17.1
MBH 67.9 79.3 92.6 108.1 126.2 147.4 172.0 200.8
KW 14.7 15.3 15.8 16.4 16.9 17.5 18.0 18.5
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
Outdoor Temperature (°F @ 72% RH)
60 Johnson Controls Unitary Products
505428-YTG-N-0712
PD240 / ND240
Air Over Evaporator Coil
CFM DB (°F) -10 0 10 20 30 40 50 60
55
6000
70
80
55
8000
70
80
55
10000
70
80
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Capacity1 &
kW
MBH 64.6 79.5 97.4 118.8 144.3 174.9 211.4 255.1
KW 15.7 16.5 17.3 18.1 19.0 19.8 20.6 21.4
MBH 69.5 84.4 102.3 123.7 149.2 179.8 216.3 260.0
KW 15.4 16.2 17.0 17.9 18.7 19.5 20.3 21.2
MBH 63.3 78.3 96.2 117.5 143.1 173.6 210.2 253.8
KW 17.2 18.0 18.8 19.6 20.5 21.3 22.1 23.0
MBH 71.6 86.6 104.5 125.8 151.4 181.9 218.5 262.1
KW 15.1 15.9 16.8 17.6 18.4 19.2 20.1 20.9
MBH 76.5 91.5 109.4 130.7 156.3 186.8 223.4 267.0
KW 14.8 15.6 16.5 17.3 18.1 19.0 19.8 20.6
MBH 70.4 85.3 103.2 124.6 150.1 180.7 217.2 260.9
KW 16.6 17.4 18.3 19.1 19.9 20.7 21.6 22.4
MBH 73.3 88.3 106.1 127.5 153.1 183.6 220.1 263.8
KW 15.3 16.1 17.0 17.8 18.6 19.4 20.3 21.1
MBH 78.2 93.2 111.0 132.4 158.0 188.5 225.0 268.7
KW 15.0 15.8 16.7 17.5 18.3 19.1 20.0 20.8
MBH 72.1 87.0 104.9 126.3 151.8 182.4 218.9 262.6
KW 16.8 17.6 18.5 19.3 20.1 20.9 21.8 22.6
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
Outdoor Temperature (°F @ 72% RH)
Johnson Controls Unitary Products 61
505428-YTG-N-0712

Air Handling and Hot Water Coil Accessory Heating Capacity

NC300 / 1HW0406
UNIT
MODEL
NC300 1HW0406 50
1
NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.
HOT WATER
COIL MODEL
These capacities do not include any blower motor heat.
1
GPM CFM
6,000 204 263 325 384 443
8,000 236 304 372 440 508 10,000 265 341 416 492 568 12,000 291 374 457 540 623
ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE °F.
70 90 110 130 150
Hot Water Coil Capacity Correction And Pressure Drop Vs GPM1
HOT WATER COIL MODEL GPM
25 0.4 0.79
1HW0406
1
For pressure drop in feet (water), multiply these values by 2.31.
50 1.0 1.00 75 1.8 1.04
100 3.4 1.07
PRESSURE DROP
CAPACITY (MBH)
PSI
CAPACITY CORRECTION
FACTOR
Air Handling and Steam Coil Accessory Heating Capacity NC300 / 1NF0454
1
UNIT
MODEL
NC300 1NF0454
1
These capacities do not include any blower motor heat.
STEAM COIL
MODEL
CFM DRY BULB TEMPERATURE OF AIR ENTERING COIL (°F)
6,000 471 424 380 330
8,000 535 483 432 380 10,000 592 535 478 422 12,000 642 580 518 456
CAPACITY (MBH) @ 2 PSIG
10 30 50 70
Steam Coil Capacity Correction Factors For High Steam Pressure
STEAM PRESSURE (PSIG) 5101520 25
CAPACITY CORRECTION FACTOR 1.05 1.12 1.19 1.25 1.30
NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH
62 Johnson Controls Unitary Products
505428-YTG-N-0712

Airflow Performance

NC090 Upflow and Horizontal Airflow Performance
NC090 Upflow
Available External Static Pressure - IWG
(CFM)
2250 754 0.8 828 0.9 902 1.0 988 1.1 1051 1.3 1116 1.4 1183 1.5 2500 707 0.8 777 0.9 851 1.0 925 1.1 996 1.3 1059 1.4 1124 1.5 1191 1.7 2750 735 0.9 805 1.1 879 1.2 953 1.3 1012 1.4 1076 1.6 1141 1.7 3000 705 1.0 767 1.1 837 1.2 911 1.3 973 1.5 1035 1.6 1099 1.7 1164 1.9 3250 741 1.1 802 1.3 872 1.4 947 1.5 1002 1.7 1064 1.8 1127 2.0 3500 780 1.4 842 1.5 912 1.6 974 1.8 1035 1.9 1097 2.1 1161 2.2 3750 823 1.6 884 1.7 954 1.9 1012 2.0 1072 2.2 1134 2.3 Exceeds BHP Limitations
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
NC090 Horizontal
(CFM)
2250 747 0.8 816 0.9 889 1.0 954 1.2 1013 1.3 1071 1.5 1128 1.6 2500 703 0.8 768 0.9 837 1.0 909 1.1 977 1.2 1036 1.4 1094 1.5 1151 1.7 2750 728 0.9 793 1.0 862 1.1 934 1.2 998 1.4 1056 1.5 1114 1.7 3000 696 0.9 757 1.1 822 1.2 891 1.3 961 1.4 1019 1.6 1077 1.7 1135 1.9 3250 729 1.1 790 1.3 855 1.4 924 1.5 984 1.6 1042 1.8 1100 1.9 1159 2.1 3500 766 1.3 826 1.5 892 1.6 953 1.6 1010 1.9 1069 2.0 1127 2.2 3750 806 1.6 867 1.7 932 1.8 984 1.9 1041 2.1 1099 2.3 Exceeds BHP Limitations
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP & Field
Supplied Drive
Standard 1.5 HP & Drive High Static 2 HP & Drive
Available External Static Pressure - IWG
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP & Field
Supplied Drive
Standard 1.5 HP & Drive High Static 2 HP & Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
Johnson Controls Unitary Products 63
505428-YTG-N-0712
NC/ND120 Upflow and Horizontal Airflow Performance
NC/ND120 Upflow
Available External Static Pressure - IWG
(CFM)
2500 671 0.8 728 0.9 788 1.0 853 1.1 926 1.3 975 1.5 1026 1.6 1077 1.7 2750 684 0.9 741 1.0 801 1.1 866 1.2 933 1.4 982 1.6 1032 1.7 1084 1.8 3000 701 1.0 757 1.1 817 1.3 882 1.4 941 1.5 991 1.7 1041 1.8 1092 2.0 3250 664 1.0 719 1.1 776 1.3 836 1.4 903 1.5 952 1.7 1002 1.8 1052 2.0 3500 685 1.1 741 1.3 797 1.4 858 1.5 917 1.7 966 1.9 1015 2.0 1066 2.2 3750 653 1.1 709 1.3 764 1.4 821 1.6 884 1.7 933 1.9 982 2.0 1031 2.2 1082 2.3 4000 679 1.3 735 1.5 790 1.6 847 1.8 903 1.9 952 2.1 1001 2.3 1050 2.4 4250 707 1.5 762 1.6 818 1.8 875 1.9 924 2.1 973 2.3 1022 2.5 1072 2.7 4500 737 1.7 792 1.9 850 2.0 899 2.2 948 2.4 997 2.6 1046 2.8 4750 768 1.9 824 2.1 877 2.2 926 2.5 975 2.7 1024 2.9 1073 3.0 5000 801 2.1 856 2.3 906 2.5 956 2.8 1005 3.0 1053 3.2 High Static 3 HP & Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
NC/ND120 Horizontal
(CFM)
2500 686 0.8 730 0.9 778 0.9 840 1.0 917 1.3 964 1.5 1011 1.6 1060 1.7 2750 698 0.9 742 1.0 790 1.0 852 1.1 924 1.4 971 1.6 1019 1.7 1067 1.9 3000 714 1.0 758 1.1 806 1.1 868 1.2 935 1.6 981 1.7 1029 1.9 1078 2.0 3250 684 1.0 734 1.2 778 1.2 826 1.3 902 1.6 948 1.7 995 1.9 1042 2.0 3500 707 1.2 757 1.3 801 1.4 849 1.4 917 1.7 964 1.9 1010 2.0 1058 2.2 3750 669 1.2 734 1.4 784 1.5 828 1.6 890 1.7 936 1.9 982 2.1 1029 2.2 1076 2.4 4000 699 1.4 764 1.6 814 1.7 858 1.8 910 2.0 956 2.1 1002 2.3 1049 2.4 4250 732 1.6 798 1.8 847 1.9 887 2.0 933 2.2 978 2.4 1025 2.5 1071 2.7 4500 769 1.8 834 2.0 884 2.1 911 2.3 957 2.4 1003 2.6 1049 2.8 4750 808 2.1 874 2.3 891 2.3 937 2.5 983 2.7 1029 2.9 1075 3.1 5000 850 2.3 873 2.4 919 2.6 965 2.8 1011 3.0 1057 3.2 High Static 3 HP & Field Supplied Drive
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP & Field
Supplied Drive
Standard 2 HP & Drive High Static 3 HP & Drive
Available External Static Pressure - IWG
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP & Field
Supplied Drive
Standard 2 HP & Drive High Static 3 HP & Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
64 Johnson Controls Unitary Products
505428-YTG-N-0712
NC/ND180 Upflow and Horizontal Airflow Performance
NC/ND180 Upflow
Available External Static Pressure - IWG
(CFM)
4500 583 1.1 634 1.3 688 1.5 738 1.9 782 2.3 827 2.6 4750 592 1.2 643 1.4 700 1.8 744 2.1 788 2.4 833 2.7 5000 602 1.2 653 1.4 707 1.9 751 2.2 795 2.6 840 2.9 5250 613 1.3 664 1.5 716 2.1 759 2.4 804 2.7 848 3.1 5500 577 1.1 625 1.4 676 1.6 725 2.3 768 2.6 813 2.9 857 3.2 5750 590 1.2 638 1.4 689 1.7 735 2.5 778 2.8 822 3.1 6000 603 1.3 651 1.6 702 2.3 745 2.7 789 3.0 833 3.3 6250 617 1.5 664 1.7 714 2.6 757 2.9 801 3.2 845 3.5 6500 587 1.4 631 1.6 679 1.8 726 2.8 769 3.1 813 3.4 857 3.8 6750 601 1.6 645 1.8 693 2.0 739 3.0 782 3.4 826 3.7 7000 616 1.8 660 2.0 710 2.9 753 3.3 796 3.6 839 3.9 7250 632 2.1 675 2.3 725 3.2 767 3.6 810 3.9 854 4.2 7500 647 2.3 691 2.5 740 3.5 782 3.9 825 4.2 High Static 5 HP & Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 3 HP & Field Supplied Drive Standard 3 HP & Drive High Static 5 HP & Drive
NC/ND180 Horizontal
Available External Static Pressure - IWG
(CFM)
4500 585 1.5 634 1.6 687 1.8 735 2.0 780 2.5 827 2.7 875 2.9 4750 595 1.6 644 1.7 697 1.9 741 2.4 787 2.7 834 2.9 5000 605 1.7 655 1.8 708 2.0 749 2.6 795 2.9 842 3.1 5250 617 1.8 666 2.0 719 2.1 757 2.8 804 3.1 851 3.3 5500 582 1.8 629 1.9 678 2.1 731 2.3 767 3.0 813 3.2 860 3.4 5750 594 1.9 642 2.1 691 2.2 737 2.4 778 3.2 824 3.4 871 3.7 6000 608 2.1 655 2.2 705 2.4 744 3.1 789 3.4 835 3.7 6250 622 2.2 670 2.4 719 2.6 756 3.3 801 3.6 847 3.9 6500 589 2.2 637 2.4 684 2.6 733 2.7 769 3.6 814 3.9 860 4.1 6750 604 2.4 652 2.6 699 2.8 738 3.5 782 3.8 827 4.1 873 4.4 7000 620 2.6 667 2.8 715 3.0 752 3.8 796 4.1 841 4.4 7250 636 2.8 683 3.0 731 3.2 766 4.1 811 4.4 856 4.7 7500 652 3.0 700 3.2 738 4.0 781 4.4 825 4.7 High Static 5 HP & Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 3 HP & Field Supplied Drive Standard 3 HP & Drive High Static 5 HP & Drive
Johnson Controls Unitary Products 65
505428-YTG-N-0712
NC/ND240 Upflow and Horizontal Airflow Performance
NC/ND240 Upflow
Available External Static Pressure - IWG
(CFM)
6000 732 2.2 789 2.6 846 2.9 900 3.1 959 4.0 1008 4.5 1056 4.9 1102 5.2 1146 5.3 6250 685 1.9 742 2.3 799 2.7 856 3.0 910 3.3 967 4.2 1016 4.7 1064 5.1 1110 5.4 1154 5.5 6500 696 2.1 752 2.5 809 2.8 866 3.2 920 3.4 976 4.4 1025 4.9 1072 5.3 1118 5.6 6750 706 2.2 763 2.6 820 3.0 877 3.3 935 4.0 985 4.6 1034 5.1 1081 5.5 1127 5.8 7000 718 2.4 774 2.8 831 3.2 888 3.5 945 4.2 994 4.8 1043 5.3 1091 5.7 1137 6.0 7250 729 2.6 786 3.0 843 3.3 900 3.6 954 4.5 1004 5.0 1053 5.5 1100 5.9 1146 6.2 7500 741 2.8 798 3.1 855 3.5 912 3.8 965 4.7 1014 5.3 1063 5.8 1111 6.2 7750 700 2.6 754 2.9 810 3.3 868 3.7 925 4.3 975 4.9 1025 5.5 1074 6.0 1121 6.4 8000 712 2.8 767 3.1 823 3.5 881 3.9 936 4.6 986 5.2 1036 5.8 1085 6.3 1132 6.7 8250 726 3.0 780 3.3 837 3.7 894 4.1 948 4.9 998 5.5 1047 6.0 1096 6.5 1144 6.9 8500 740 3.2 794 3.6 850 3.9 908 4.3 959 5.1 1010 5.8 1059 6.3 1108 6.8 8750 754 3.4 808 3.8 865 4.2 922 4.8 972 5.4 1022 6.0 1071 6.6 1120 7.1 9000 768 3.6 823 4.0 879 4.4 934 5.1 984 5.7 1034 6.4 1084 6.9 1133 7.4 9250 783 3.9 838 4.3 894 4.6 947 5.4 997 6.1 1047 6.7 1097 7.2 9500 799 4.1 853 4.5 910 4.9 961 5.8 1011 6.4 1061 7.0 1110 7.6 9750 815 4.4 869 4.8 925 5.5 974 6.1 1024 6.7 1074 7.3 1124 7.9
10000 831 4.7 885 5.0 939 5.9 988 6.5 1038 7.1 1088 7.7 1138 8.3 High Static 7.5 HP & Field Supplied Drive
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP &
Field Supplied Drive
High Static 5 HP & Drive High Static 7.5 HP & Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
NC/ND240 Horizontal
Available External Static Pressure - IWG
(CFM)
6000 708 2.0 754 2.3 801 2.6 849 2.8 898 2.9 976 4.0 1021 4.4 1066 4.8 1111 5.1 1155 5.3 6250 715 2.1 761 2.4 808 2.7 856 2.9 906 3.0 984 4.2 1029 4.6 1074 5.0 1118 5.3 1163 5.5 6500 723 2.3 769 2.6 816 2.8 864 3.0 947 3.9 991 4.4 1036 4.8 1081 5.2 1126 5.4 6750 731 2.4 777 2.7 824 3.0 872 3.2 955 4.1 999 4.6 1044 5,0 1089 5.3 1134 5.6 7000 740 2.5 786 2.8 833 3.1 881 3.3 963 4.3 1007 4.7 1052 5.2 1097 5.5 1142 5.8 7250 749 2.7 796 3.0 842 3.3 890 3.5 971 4.5 1015 4.9 1060 5.3 1105 5.7 1150 6.0 7500 712 2.6 759 2.9 806 3.2 852 3.4 900 3.6 979 4.7 1024 5.1 1069 5.5 1114 5.9 1158 6.2 7750 722 2.8 770 3.0 816 3.3 863 3.6 945 4.4 988 4.9 1033 5.3 1078 5.8 1123 6.1 8000 733 2.9 781 3.2 827 3.5 874 3.8 954 4.6 998 5.1 1042 5.5 1087 6.0 1132 6.3 8250 745 3.1 793 3.4 839 3.7 886 4.0 964 4.8 1007 5.3 1052 5.8 1096 6.2 1141 6.5 8500 757 3.3 805 3.6 851 3.9 898 4.2 974 5.1 1017 5.6 1062 6.0 1107 6.4 1152 6.8 8750 770 3.6 818 3.8 864 4.1 942 4.8 984 5.3 1028 5.8 1072 6.3 1117 6.7 9000 784 3.8 831 4.1 878 4.4 953 5.1 995 5.6 1039 6.1 1083 6.5 1128 6.9 9250 798 4.0 845 4.3 923 4.9 964 5.4 1006 5.9 1050 6.3 1094 6.8 1139 7.2 9500 812 4.3 859 4.6 935 5.2 976 5.7 1018 6.2 1062 6.6 1106 7.1 1151 7.5 9750 827 4.5 908 5.1 947 5.5 988 6.0 1030 6.5 1074 6.9 1118 7.4
10000 842 4.8 921 5.4 960 5.8 1001 6.3 1043 6.8 1087 7.3 1131 7.7 High Static 7.5 HP & Field Supplied Drive
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP &
Field
Supplied
Drive
Standard 5 HP & Drive High Static 7.5 HP & Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
66 Johnson Controls Unitary Products
505428-YTG-N-0712
NC300 Airflow Performance
CFM
7500 600 2.04 648 2.50 694 3.00 738 3.54 781 4.08 823 4.63 863 5.16 903 5.66 942 6.10 981 6.49 7750 603 2.17 652 2.63 698 3.13 742 3.67 785 4.22 827 4.76 867 5.29 907 5.79 946 6.24 984 6.62 8000 608 2.32 656 2.78 702 3.28 747 3.81 789 4.36 831 4.91 871 5.44 911 5.93 950 6.38 989 6.77 8250 613 2.48 661 2.93 707 3.44 752 3.97 795 4.52 836 5.07 877 5.60 916 6.09 955 6.54 994 6.92 8500 619 2.65 667 3.10 713 3.61 758 4.14 800 4.69 842 5.24 882 5.77 922 6.26 961 6.71 1000 7.09 8750 575 2.43 625 2.83 673 3.28 720 3.79 764 4.32 807 4.87 848 5.42 889 5.95 928 6.44 967 6.89 1006 7.27 9000 581 2.62 632 3.02 680 3.47 726 3.98 771 4.51 814 5.06 855 5.61 896 6.14 935 6.63 974 7.08 1013 7.46 9250 589 2.82 639 3.21 687 3.67 734 4.17 778 4.71 821 5.26 862 5.80 903 6.33 942 6.83 982 7.28 9500 596 3.02 647 3.42 695 3.88 741 4.38 786 4.91 829 5.46 870 6.01 910 6.54 950 7.03 989 7.48
9750 604 3.23 655 3.63 703 4.09 749 4.59 794 5.13 836 5.67 878 6.22 918 6.75 958 7.25 10000 613 3.45 663 3.85 711 4.31 758 4.81 802 5.34 845 5.89 886 6.44 927 6.97 966 7.46 10250 621 3.68 672 4.07 720 4.53 766 5.03 811 5.57 853 6.12 895 6.66 935 7.19 10500 630 3.9 680 4.30 729 4.76 775 5.26 819 5.80 862 6.34 904 6.89 944 7.42 10750 639 4.14 689 4.53 738 4.99 784 5.50 828 6.03 871 6.58 913 7.12 11000 648 4.37 699 4.77 747 5.23 793 5.73 837 6.27 880 6.82 922 7.36 11250 657 4.62 708 5.01 756 5.47 802 5.97 847 6.51 890 7.06 11500 667 4.86 717 5.26 766 5.71 812 6.22 856 6.75 899 7.30 11750 676 5.11 727 5.50 775 5.96 821 6.46 866 7.00 12000 686 5.36 737 5.75 785 6.21 831 6.71 876 7.25 12250 696 5.61 746 6.00 795 6.46 841 6.97 885 7.50 12500 706 5.86 756 6.26 805 6.72 851 7.22
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP & Field
supplied
Drive
1
Avaiable External Static Pressure - IWG
5 HP Motor & Drive 7.5 HP Motor & Drive
High static 7.5 HP & Field Supplied Drive
1. NC300 requires the selection, purchase and field installation of the Supply Fan Motor, Drive Kit and Motor Overloads (See Following Page for Item Selection Tables).
RPM Selection
Unit Model HP Max BHP Motor Sheave Blower Sheave
NC090
NC/ND120
NC/ND180
NC/ND240
1 2
Std. 1.5 1.73 1VL40 AK69 -
HS 2 2.30 1VL40 AK56 -
Std. 2 2.30 1VL40 AK74 -
HS 3 3.45 1VP56 AK84 -
Std. 3 3.45 1VP50 AK114 -
HS 5 5.75 2VP50 2B5V94 707 745 782 819 856 894 -
Std. 5 5.75 2VP50 2B5V94 686 722 758 794 830 866 -
HS 7.5 8.63 2VP65 2B5V94 925 960 996 1031 1067 1103 1138
Setting not available. Setting not recommended for use with Type B v-belts.
6 Turns
Open
5 Turns
Open
1 1 1 1 1
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
690 743 796 849 902 955 863 929 995 1062 1128 1194 641 690 739 789 838 887 906 949 992 1035 1078 1121 565 596 627 659 690 721
NC090 - 240 And ND120 - 240 Blower Motor And Drive Data
Blower Motor Data Drive Data
Unit
Model
NC090
NC/ND120
NC/ND180
NC/ND240
HP RPM SF
Std 1.5 HS 2 56HZ 1VL40 863 - 1194 2.6 - 3.6 0.875 AK56 5.2 1.000 1 40.3 A39
Std. 2
HS 3 56HZ 1VP56 906 - 1121 4.2 - 5.2 0.875 AK84 8.0 1.000 1 48.3 A47
Std. 3
HS 5 184T 2VP50 707 - 894 3.7 - 4.7 1.125 2B5V94 9.7 1.000 2 41.8 B40
Std. 5
HS 7.5 213T 2VP65 925 - 1138 5.2 - 6.4 1.375 2B5V94 9.7 1.188 2 46.8 B45
1725 1.15
1725 1.15
1725 1.15
1725 1.15
Frame
Model
Size
Number
56 1VL40 690 - 955 2.6 - 3.6 0.875 AK69 6.5 1.000 1 42.3 A41
56HZ 1VL40 641 - 887 2.6 - 3.6 0.875 AK74 7.0 1.000 1 45.3 A44
56HZ 1VP50 565 - 721 3.6 - 4.6 0.875 AK114 11.0 1.000 1 45.3 A44
184T 2VP50 686 - 866 3.7 - 4.7 1.125 2B5V94 9.7 1.188 2 41.8 B40
Blower
RPM
Range
Adjustable Motor Sheave
Pitch
Diameter
(in.)
Bore
(in.)
Model
Number
Fixed Blower Sheave Belts
Pitch
Diameter
(in.)
Bore (in.) Qty.
Pitch
Length
(in.)
Fully
Closed
2 2
Desig­nation
Johnson Controls Unitary Products 67
505428-YTG-N-0712
NC300 Drive Kit Data
Unit
Model
NC300
Drive Kit Model
Number
1LD0440 2VP56 575 - 719 4.0 - 5.0 1 1/8 2AK124 12.0 1 3/16 2 63.3 A62 1LD0407 2VP60 659 - 815 4.2 - 5.2 1 3/8 2AK114 11.0 1 3/16 2 63.3 A62 1LD0442 2VP71 762 - 906 5.3 - 6.3 1 3/8 2AK124 12.0 1 3/16 2 63.3 A62
Sheave Number
Adjustable Motor Sheave Fixed Blower Sheave Belts
Model
Blower
RPM
Range
Pitch
Diameter
(in.)
Bore
(in.)
Sheave
Model
Number
Pitch
Diameter
(in.)
Bore
(in.)
Qty.
Pitch
Length
(in.)
Desig­nation
NC300 Motor Kit Data
Unit Model HP
NC300
7.5
Motor Kit
Model
Number
2LP04605133
5
2LP04605158 575 2LP04607133 2LP04607158 575
Frame
Size
184
213
Voltage
(3PH-60HZ)
208/230/460
208/230/460
NC300 Overload Relay Kit
UNIT VOLTAGE 208/230V 460V 575V
MODEL MOTOR HP OVERLOAD RELAY KIT
NC300
5 2MP04708500 2MP04708300 2MP04708300
7.5 2MP04708700 2MP04708400 2MP04708300
NC300 Overload Relay Setting
UNIT VOLTAGE 208/230V 460V 575V
MODEL MOTOR HP OVERLOAD RELAY SETTING (Full Load Amps)
NC300
1
Motors with Service Factor of 1.15 or Greater: Adjust overload relay dial to the motor nameplate Full Load Amps (FLA).
2
Motors with Service Factor Less Than 1.15: Adjust overload relay dial
5 14/13 6.5 5
7.5 21/20 9.5 7.5
based on the formula: Motor nameplate FLA x 0.90 = relay setting
1,2
68 Johnson Controls Unitary Products
Additional Static Resistance
Model CFM
2250 0.03 0.10 0.02 0.01 0.02 0.03 0.04 --- 2500 0.03 0.11 0.03 0.01 0.02 0.03 0.05 --- 2750 0.02 0.11 0.03 0.01 0.03 0.04 0.07 ---
NC090
NC/ND120
NC/ND180
3000 0.02 0.12 0.04 0.01 0.03 0.05 0.08 --- 3250 0.01 0.13 0.04 0.02 0.04 0.06 0.09 --- 3500 0.00 0.14 0.05 0.02 0.04 0.07 0.10 --- 3750 0.00 0.15 0.06 0.02 0.05 0.08 0.12 --- 3000 0.08 0.12 0.04 0.01 0.03 0.05 0.08 --- 3250 0.07 0.13 0.04 0.02 0.04 0.06 0.09 --- 3500 0.07 0.14 0.05 0.02 0.04 0.07 0.10 --- 3750 0.06 0.15 0.06 0.02 0.05 0.08 0.12 --- 4000 0.05 0.16 0.07 0.03 0.06 0.09 0.14 --- 4250 0.04 0.18 0.08 0.03 0.06 0.10 0.15 --- 4500 0.03 0.19 0.09 0.03 0.07 0.11 0.17 --- 4750 0.02 0.21 0.10 0.04 0.08 0.13 0.19 --- 5000 0.00 0.23 0.11 0.04 0.09 0.14 0.21 --- 4500 0.07 0.11 0.03 0.03 0.07 0.11 0.17 0.21 4750 0.06 0.11 0.03 0.04 0.08 0.13 0.19 0.22 5000 0.06 0.11 0.04 0.04 0.09 0.14 0.21 0.24 5250 0.06 0.12 0.04 0.05 0.10 0.15 0.23 0.26 5500 0.05 0.12 0.04 0.05 0.11 0.17 0.25 0.29 5750 0.05 0.12 0.05 0.06 0.12 0.19 0.28 0.32 6000 0.05 0.13 0.05 0.06 0.13 0.20 0.30 0.35 6250 0.04 0.14 0.06 0.07 0.14 0.22 0.33 0.38 6500 0.03 0.14 0.06 0.07 0.15 0.24 0.35 0.42 6750 0.03 0.15 0.07 0.08 0.17 0.26 0.38 0.47 7000 0.02 0.16 0.07 0.08 0.18 0.28 0.41 0.50 7250 0.01 0.16 0.08 0.09 0.19 0.30 0.44 0.53 7500 0.00 0.17 0.08 0.10 0.20 0.32 0.47 0.56
Wet Indoor
Coil
505428-YTG-N-0712
1
2” Filters
Bottom
Return
10 16 26 36 50
Electric Heat kW
Model CFM
Wet Indoor
Coil
6000 0.08 0.12 0.06 0.01 0.03 0.05 6250 0.08 0.13 0.06 0.02 0.03 0.05 6500 0.08 0.13 0.07 0.02 0.04 0.06 6750 0.07 0.14 0.07 0.02 0.04 0.06 7000 0.07 0.14 0.08 0.02 0.04 0.07 7250 0.06 0.15 0.08 0.02 0.05 0.07 7500 0.06 0.16 0.09 0.02 0.05 0.08 7750 0.05 0.16 0.09 0.02 0.05 0.08
NC/ND240
8000 0.05 0.17 0.10 0.03 0.06 0.09 8250 0.04 0.18 0.10 0.03 0.06 0.09 8500 0.04 0.19 0.11 0.03 0.06 0.10 8750 0.03 0.20 0.12 0.03 0.07 0.11 9000 0.02 0.21 0.12 0.03 0.07 0.11 9250 0.01 0.22 0.13 0.04 0.08 0.12 9500 0.00 0.23 0.00 0.04 0.08 0.13 9750 0.00 0.24 0.00 0.04 0.09 0.13
10000 0.00 0.25 0.00 0.04 0.09 0.14
1
Pressure drop added by condensate over a dry coil.
2” Filters
Bottom
Return
Electric Heat kW
20 32 52
Johnson Controls Unitary Products 69
505428-YTG-N-0712
Additional Static Resistance (Continued)
Model CFM Hot Water Coil Steam Coil
8000 0.06 0.11 9000 0.07 0.14
NC300
10000 0.08 0.17 11000 0.09 0.20 12000 0.10 0.23
CFM Static Pressure and Power-Altitude and Temperature Corrections
The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.
The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In
order to use the indoor blower tables for high altitude applications, certain corrections are necessary.
A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Altitude Factors Table and Temperature Correction Figure.
70 Johnson Controls Unitary Products
505428-YTG-N-0712
Altitude/Temperature Correction Factors Table
Air
Temp.
40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701 70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688 80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676 90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663
100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
1.100
1.050
1.000
0.950
0.900
0.850
0.800
Correction Factor
0.750
0.700
0.650
Altitude (Ft.)
Sea Level
1000 ft
2000 ft
3000 ft
4000 ft
5000 ft
6000 ft 7000 ft
8000 ft
9000 ft
10000 ft
0.600 40 50 60 70 80 90 100
Air Temperature (ºF)
Altitude/Temperature Correction Factors Figure
The examples below will assist in determining the airflow performance of the product at altitude.
Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: At an elevation of 5,000 ft. the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, the Altitude/Temperature Correction Factors table must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. The table shows the correction factor to be 0.832.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit
blower tables to select the blower speed and the BHP requirement.
Solution: As in the example above, no temperature information is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft. Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation. BHP at 5,000 ft. = 3.2 x .832 = 2.66
Johnson Controls Unitary Products 71
505428-YTG-N-0712
Drive Selection
1. Determine Upflow or Horizontal supply duct Application.
2. Determine desired airflow.
3. Calculate or measure the amount of external static pressure.
4. Using the operating point, determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.)
5. Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.
6. Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor.
8. Determine turns open to obtain the desired operation point.
Example
1. 3250 CFM
2. 1.4 iwg
3. Using the supply air blower performance table below, the following data point was located: 1100 RPM & 1.8 BHP.
4. Using the RPM selection table below, Model X is found.
5. 1.8 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6. 1100 RPM is within the range of the 2 HP drives.
7. Using the 2 HP motor and drive, 1 turn open will achieve 1128 RPM.
Airflow Performance
Example Supply Air Blower Performance
Available External Static Pressure - IWG
(CFM)
3000 696 0.9 757 1.1 822 1.2 891 1.3 961 1.3 1019 1.5 1077 1.6 1135 1.8 3250 729 1.1 790 1.3 855 1.4 924 1.5 984 1.6 1042 1.7 1100 1.8 1159 2.0 3500 766 1.3 826 1.5 892 1.6 953 1.6 1010 1.8 1069 1.9 1127 2.0
RPM Selection
Unit Model HP
X
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 HP & Drive High Static 2 HP & Drive
Max BHP
Std. 1.5 1.73 1VL40 AK69 N/A 690 743 796 849 902 955
HS 2 2.30 1VL40 AK56 N/A 863 929 995 1062 1128 1194
Motor
Sheave
Blower Sheave
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Fully
Closed
72 Johnson Controls Unitary Products

Sound Performance

Outdoor Sound Power Levels (dB), 60 Hz
Size
(Tons)
090
(7.5)
120
(10.0)
150
(12.5)
180
(15.0)
240
(20.0)
300
(25.0)
1
Rated in accordance with AHRI 270 Standard.
Model PC090 89 88 90 89 87 84 81 77 72
YC090 89 88 89 89 87 84 81 78 73 PC120 89 88 90 89 87 84 81 77 72 YC120 90 91 87 90 88 85 80 76 70 YD120 90 92 89 91 88 85 80 77 71 YC150 91 96 88 90 89 86 82 77 71 YD150 91 92 92 92 89 86 81 78 73 PC180 93 93 96 93 90 89 84 77 71 PD180 93 93 96 93 90 89 84 77 71 YC180 89 88 90 89 87 84 81 77 72 YD180 89 88 90 89 87 84 81 77 72 PC240 93 93 96 93 90 89 84 77 71 PD240 93 93 96 93 90 89 84 77 71 YC240 93 93 96 93 90 89 84 77 71 YD240 93 93 96 93 90 89 84 77 71
YC300 93 93 96 93 90 89 84 77 71
Sound
Rating
1
505428-YTG-N-0712
Octave Bands (Hz)
63 125 250 500 1000 2000 4000 8000
Johnson Controls Unitary Products 73
505428-YTG-N-0712

Electrical Data

Electrical Data For Outdoor Models Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet
Compressors Outdoor Fan Motor Pwr Conv Outlet
Model
YC090
YC120
YD120
YC150
YD150
YC180
YD180
YC240
YD240
YC300
1
2
Power
Supply
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 - 35.5 45
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 - 17.6 25 575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 - 13.1 20
208/230-3-60 2 18.1 28.3 137 208/230-1-60 3/4 2 3.0 - 46.8 60
460-3-60 2 9.0 14.0 62 460-1-60 3/4 2 1.6 - 23.5 30 575-3-60 2 6.8 10.6 50 575-1-60 3/4 2 1.4 - 18.0 20
208/230-3-60 2 17.3 27 123 208/230-1-60 3/4 2 3.0 - 45.0 60
460-3-60 2 9.6 15 70 460-1-60 3/4 2 1.6 - 24.8 30 575-3-60 2 7.7 12 53 575-1-60 3/4 2 1.4 - 20.0 25
208/230-3-60 2 22.4 35 149 208/230-1-60 3/4 2 3.0 - 56.5 70
460-3-60 2 10.6 17 75 460-1-60 3/4 2 1.6 - 27.1 35 575-3-60 2 7.7 12 54 575-1-60 3/4 2 1.4 - 20.0 25
208/230-3-60 2 23.1 36 160 208/230-1-60 3/4 2 3.0 - 58.0 80
460-3-60 2 12.2 19 87 460-1-60 3/4 2 1.6 - 30.7 40 575-3-60 2 8.7 14 62 575-1-60 3/4 2 1.4 - 22.3 30
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 - 79.8 100
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 - 44.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 - 32.9 45
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 - 79.8 100
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 - 44.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 - 32.9 45
208/230-3-60 2 48.1 75 245 208/230-1-60 3/4 4 3.0 - 120.3 150
460-3-60 2 18.6 29 125 460-1-60 3/4 4 1.6 - 48.3 60 575-3-60 2 14.7 23 100 575-1-60 3/4 4 1.4 - 38.5 50
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power Supply
HP Qty
FLA
(each)
FLA
Minimum
Circuit
Ampacity
1
Maximum Fuse Size
2
(A)
74 Johnson Controls Unitary Products
Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet
Compressors Outdoor Fan Motor Pwr Conv Outlet
Model
YC090
YC120
YD120
YC150
YD150
YC180
YD180
YC240
YD240
YC300
1
2
Power
Supply
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 10.0 45.5 60
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 5.0 22.6 30 575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 4.0 17.1 25
208/230-3-60 2 18.1 28.3 137 208/230-1-60 3/4 2 3.0 10.0 56.8 70
460-3-60 2 9.0 14.0 62 460-1-60 3/4 2 1.6 5.0 28.5 35 575-3-60 2 6.8 10.6 50 575-1-60 3/4 2 1.4 4.0 22.0 25
208/230-3-60 2 17.3 27 123 208/230-1-60 3/4 2 3.0 10.0 55.0 70
460-3-60 2 9.6 15 70 460-1-60 3/4 2 1.6 5.0 29.8 35 575-3-60 2 7.7 12 53 575-1-60 3/4 2 1.4 4.0 24.0 30
208/230-3-60 2 22.4 35 149 208/230-1-60 3/4 2 3.0 10.0 66.5 80
460-3-60 2 10.6 17 75 460-1-60 3/4 2 1.6 5.0 32.1 40 575-3-60 2 7.7 12 54 575-1-60 3/4 2 1.4 4.0 24.0 30
208/230-3-60 2 23.1 36 160 208/230-1-60 3/4 2 3.0 10.0 68.0 90
460-3-60 2 12.2 19 87 460-1-60 3/4 2 1.6 5.0 35.7 45 575-3-60 2 8.7 14 62 575-1-60 3/4 2 1.4 4.0 26.3 30
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 5.0 49.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 4.0 36.9 45
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 5.0 49.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 4.0 36.9 45
208/230-3-60 2 48.1 75 245 208/230-1-60 3/4 4 3.0 10.0 130.3 175
460-3-60 2 18.6 29 125 460-1-60 3/4 4 1.6 5.0 53.3 70 575-3-60 2 14.7 23 100 575-1-60 3/4 4 1.4 4.0 42.5 50
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
FLA
505428-YTG-N-0712
Minimum
Circuit
Ampacity
1
Maximum Fuse Size
2
(A)
Johnson Controls Unitary Products 75
505428-YTG-N-0712
Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet
Compressors Outdoor Fan Motor Pwr Conv Outlet
Model
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power Supply
HP Qty
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 - 35.5 45
PC090
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 - 17.6 25 575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 - 13.1 20
208/230-3-60 2 18.1 28.3 137 208/230-1-60 3/4 2 3.0 - 46.8 60
PC120
460-3-60 2 9.0 14.0 62 460-1-60 3/4 2 1.6 - 23.5 30 575-3-60 2 6.8 10.6 50 575-1-60 3/4 2 1.4 - 18.0 20
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
PC180
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
PD180
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 - 79.8 100
PD240
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 - 44.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 - 32.9 45
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC). Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
FLA
(each)
FLA
Minimum
Circuit
Ampacity
1
Maximum Fuse Size
2
(A)
Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet
Compressors Outdoor Fan Motor Pwr Conv Outlet
Model
PC090
PC120
PC180
PD180
PD240
1
2
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power Supply
HP Qty
FLA
(each)
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 10.0 45.5 60
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 5.0 22.6 30 575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 4.0 17.1 25
208/230-3-60 2 18.1 28.3 137 208/230-1-60 3/4 2 3.0 10.0 56.8 70
460-3-60 2 9.0 14.0 62 460-1-60 3/4 2 1.6 5.0 28.5 35 575-3-60 2 6.8 10.6 50 575-1-60 3/4 2 1.4 4.0 22.0 25
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 5.0 49.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 4.0 36.9 45
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
FLA
Minimum
Circuit
Ampacity
1
Maximum Fuse Size
2
(A)
76 Johnson Controls Unitary Products
Electrical Data For Indoor Models
Electrical Data - Indoor Units
Motor HP Power Supply
208-3-60 5.0
230-3-60 5.2
1.5
460-3-60 2.5
575-3-60 2.0
208-3-60 6.6
230-3-60 6.8
2.0
460-3-60 3.4
575-3-60 2.4
Supply Blower
Motor
Electric Heat Option
FLA Model KW Stages Amps
NC090C00B
None --- --- --- 6.3 15 10 KW 7.5 1 20.8 32.3 35 16 KW 12 2 33.4 47.9 50 26 KW 19.5 2 54.2 74.0 80 36 KW 27 2 75.1 100.1 110
None --- --- --- 6.5 15 10 KW 10 1 24.1 36.6 40 16 KW 16 2 38.5 54.6 60 26 KW 26 2 62.5 84.7 90 36 KW 36 2 86.6 114.8 125
None --- --- --- 3.1 15 10 KW 10 1 12.0 18.2 20 16 KW 16 2 19.2 27.2 30 26 KW 26 2 31.3 42.2 45 36 KW 36 2 43.3 57.3 60
None --- --- --- 2.5 15 10 KW 10 1 9.6 14.5 15 16 KW 16 2 15.4 21.7 25 26 KW 26 2 25.0 33.8 35 36 KW 36 2 34.6 45.8 50
NC090C00C, (NC/ND)120C00C
None --- --- --- 8.3 15 10 KW 7.5 1 20.8 34.3 35 16 KW 12 2 33.4 49.9 50 26 KW 19.5 2 54.2 76.0 80 36 KW 27 2 75.1 102.1 110
None --- --- --- 8.5 15 10 KW 10 1 24.1 38.6 40 16 KW 16 2 38.5 56.6 60 26 KW 26 2 62.5 86.7 90 36 KW 36 2 86.6 116.8 125
None --- --- --- 4.3 15 10 KW 10 1 12.0 19.3 20 16 KW 16 2 19.2 28.3 30 26 KW 26 2 31.3 43.3 45 36 KW 36 2 43.3 58.4 60
None --- --- --- 3.0 15 10 KW 10 1 9.6 15.0 20 16 KW 16 2 15.4 22.2 25 26 KW 26 2 25.0 34.3 35 36 KW 36 2 34.6 46.3 50
MCA
(Amps)
505428-YTG-N-0712
1
Max Fuse
Breaker
3
(Amps)
2
Size
/
Johnson Controls Unitary Products 77
505428-YTG-N-0712
Electrical Data - Indoor Units (Continued)
Motor HP Power Supply
208-3-60 9.6
230-3-60 9.4
3.0
460-3-60 4.7
575-3-60 3.6
208-3-60 14.0
230-3-60 13.2
5.0
460-3-60 6.6
575-3-60 5.2
Supply Blower
Electric Heat Option
Motor
FLA Model KW Stages Amps
(NC/ND)120C00D, (NC/ND)180C00D
None --- --- --- 12.0 15 10 KW 7.5 1 20.8 38.1 40 16 KW 12 2 33.4 53.7 60 26 KW 19.5 2 54.2 79.8 80 36 KW 27 2 75.1 105.8 110
4
50 KW
36 2 104.2 116.2 125
None --- --- --- 11.8 15 10 KW 10 1 24.1 41.8 45 16 KW 16 2 38.5 59.9 60 26 KW 26 2 62.5 89.9 90 36 KW 36 2 86.6 120.0 125
4
50 KW
48 2 120.3 132.0 150
None --- --- --- 5.9 15 10 KW 10 1 12.0 20.9 25 16 KW 16 2 19.2 29.9 30 26 KW 26 2 31.3 45.0 45 36 KW 36 2 43.3 60.0 70
4
50 KW
48 2 60.1 66.0 70
None --- --- --- 4.5 15 10 KW 10 1 9.6 16.5 20 16 KW 16 2 15.4 23.7 25 26 KW 26 2 25.0 35.8 40 36 KW 36 2 34.6 47.8 50
4
50 KW
48 2 48.1 52.6 60
(NC/ND)180C00E
None --- --- --- 17.5 20 10 KW 7.5 1 20.8 43.6 45 16 KW 12 2 33.4 59.2 60 26 KW 19.5 2 54.2 85.3 90 36 KW 27 2 75.1 111.3 125 50 KW 36 2 104.2 121.7 125
None --- --- --- 16.5 20 10 KW 10 1 24.1 46.6 50 16 KW 16 2 38.5 64.6 70 26 KW 26 2 62.5 94.7 100 36 KW 36 2 86.6 124.8 125 50 KW 48 2 120.3 136.8 150
None --- --- --- 8.3 15 10 KW 10 1 12.0 23.3 25 16 KW 16 2 19.2 32.3 35 26 KW 26 2 31.3 47.3 50 36 KW 36 2 43.3 62.4 70 50 KW 48 2 60.1 68.4 70
None --- --- --- 6.5 15 10 KW 10 1 9.6 18.5 20 16 KW 16 2 15.4 25.7 30 26 KW 26 2 25.0 37.8 40 36 KW 36 2 34.6 49.8 50 50 KW 48 2 48.1 54.6 60
MCA
(Amps)
1
Max Fuse
Breaker
3
(Amps)
Size
2
/
78 Johnson Controls Unitary Products
Electrical Data - Indoor Units (Continued)
Supply
Motor HP Power Supply
208-3-60 14.0
230-3-60 13.2
5.0
460-3-60 6.6
575-3-60 5.2
208-3-60 16.7 None --- --- --- 21.0 35
5.0
7.5
7.5
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
(NC/ND)180C00D Models Only
5
Motors are not shipped with these models. Motor and Drive Kits are required.
230-3-60 15.2 None --- --- --- 19.0 30 460-3-60 7.6 None --- --- --- 10.0 15 575-3-60 6.1 None --- --- --- 8.0 15
208-3-60 20.4
230-3-60 19.4
460-3-60 9.7
575-3-60 7.8
208-3-60 24.2 None --- --- --- 30.0 35 230-3-60 22.0 None --- --- --- 28.0 30 460-3-60 11.0 None --- --- --- 14.0 15 575-3-60 9.0 None --- --- --- 8.0 15
Blower
Motor
FLA Model KW Stages Amps
(NC/ND)240C00E
None --- --- --- 17.5 20 20 KW 15 1 41.7 69.6 70 32 KW 24 2 66.7 100.9 110 52 KW 39.1 2 108.4 125.9 150
None --- --- --- 16.5 20 20 KW 20 1 48.1 76.6 80 32 KW 32 2 77.0 112.7 125 52 KW 52 2 125.1 141.6 150
None --- --- --- 8.3 15 20 KW 20 1 24.1 38.3 40 32 KW 32 2 38.5 56.4 60 52 KW 52 2 62.5 70.8 80
None --- --- --- 6.5 15 20 KW 20 1 19.2 30.6 35 32 KW 32 2 30.8 45.0 45 52 KW 52 2 50.0 56.5 60
NC300C00N
(NC/ND)240C00F
None --- --- --- 25.5 30 20 KW 15 1 41.7 77.6 80 32 KW 24 2 66.7 108.9 110 52 KW 39.1 2 108.4 133.9 150
None --- --- --- 24.3 25 20 KW 20 1 48.1 84.4 90 32 KW 32 2 77.0 120.5 125 52 KW 52 2 125.1 149.3 150
None --- --- --- 12.1 15 20 KW 20 1 24.1 42.2 45 32 KW 32 2 38.5 60.2 70 52 KW 52 2 62.5 74.7 80
None --- --- --- 9.8 15 20 KW 20 1 19.2 33.8 35 32 KW 32 2 30.8 48.2 50 52 KW 52 2 50.0 59.8 60
NC300C00N
Electric Heat Option
5
5
MCA
(Amps)
505428-YTG-N-0712
1
Max Fuse
Breaker
3
(Amps)
2
Size
/
Johnson Controls Unitary Products 79
505428-YTG-N-0712

Typical Wiring Diagrams

Air Conditioning Condensing Units
Typical YC090 Wiring Diagram
80 Johnson Controls Unitary Products
Typical YC120 - 150 Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 81
505428-YTG-N-0712
Typical YD120 - 150 Wiring Diagram
82 Johnson Controls Unitary Products
Typical YC180 Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 83
505428-YTG-N-0712
Typical YC240 Wiring Diagram
84 Johnson Controls Unitary Products
Typical YC300 Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 85
505428-YTG-N-0712
Typical YD180 - 240 Wiring Diagram
86 Johnson Controls Unitary Products
Heat Pump Units
Typical PC090 Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 87
505428-YTG-N-0712
Typical PC120 Wiring Diagram
88 Johnson Controls Unitary Products
Typical PC180 - 240 Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 89
505428-YTG-N-0712
Typical PD180 - 240 Wiring Diagram
90 Johnson Controls Unitary Products
Air Handling Units
Typical NC090 Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 91
505428-YTG-N-0712
Typical NC120 thru 240, 1.5 thru 5 HP Blower Motor Only Wiring Diagram
92 Johnson Controls Unitary Products
Typical NC 240, 7.5 HP Blower Motor 208/230 V Only Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 93
505428-YTG-N-0712
Typical NC 240, 7.5 HP Blower Motor 460/575 V Only Wiring Diagram
94 Johnson Controls Unitary Products
Typical NC300 Indoor Unit Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 95
505428-YTG-N-0712
Typical ND120 thru 240, 1.5 thru 5 HP Blower Motor Only Wiring Diagram
96 Johnson Controls Unitary Products
Typical ND 240, 7.5 HP Blower Motor 208/230 V Only Wiring Diagram
505428-YTG-N-0712
Johnson Controls Unitary Products 97
505428-YTG-N-0712
Typical ND 240, 7.5 HP Blower Motor 460/575 V Only Wiring Diagram
98 Johnson Controls Unitary Products
505428-YTG-N-0712

Weights And Dimensions

Corner Weights & Center of Gravity AC/HP Units
Model
PC090 421 430 17.3 33 110 130 103 87 PC120 543 574 16.4 32.3 153 161 134 127 PC180 947 968 32.5 33 266 274 217 211 PD180 921 942 34 32.5 243 275 225 199 PD240 1090 1126 31.2 31.8 311 295 253 267 YC090 390 387 17 32.3 99 113 94 82 YC120 499 497 17.3 32.3 124 147 122 103 YD120 493 490 17.4 32.5 123 147 120 100 YC150 499 497 17 32.3 127 145 120 105 YD150 493 490 17.4 32.5 123 147 120 100 YC180 914 909 32.5 31.5 239 246 215 209 YD180 899 894 32.5 31.5 235 242 212 206 YC240 945 942 30.3 31.0 261 234 212 236 YD240 930 927 32.7 31.8 244 255 218 210 YC300 945 942 30.3 31.0 261 234 212 236
Weight (lbs.) Center of Gravity (in.) 4 Point Load Location (lbs.)
Shipping Operating X Y A B C D
LEFT
LEFT
A
REAR
B
FRONT
WIDTH
DIM X
D
C
DIM Y
YC090, YC120, YD120,
CG
LENGTH
RIGHT
PC090, PC120,
YC150, YD150
NOTE: Front of unit is considered the side having the unit
control box.
FRONT
WIDTH
DIM X
D
CG
C
DIM Y
LENGTH
RIGHT
PC180, PD180, PC240, PD240, YC180, YD180, YC240, YD240, YC300
A
REAR
B
Johnson Controls Unitary Products 99
505428-YTG-N-0712
RIGHT
7.000
24.000
31.758
FRONT
REAR
FRONT
LEFT
CONVENIENCE
OUTLET
A
2X (Ø 1.375) KNOCKOUT
30.994
2X (Ø 0.875) KNOCKOUT
12.126
9.876
4.751
7.00010.000
3.883
3.664
2.933
1.664
7.000
23.000
37.000
58.500
RIGHT
7.000
SYSTEM 2
15.53
10.60
8.98
7.52
12.70
6.26
SYSTEM 1
REAR LEFT
Unit Dimensions PC090, PC120, YC090, YC/YD120, YC/YD150
Unit Height Dimensions
MODEL A
PC090 44.5 PC120 50.0 YC090 44.5 YC120 50.0 YD120 50.0 YC150 50.0 YD150 50.0
2X (Ø 1.375) KNOCKOUT
4.875
4.132
2.382
1.882
10.000
2X (Ø 0.875) KNOCKOUT
12.000
100 Johnson Controls Unitary Products
Loading...