York N1VSD10A06, N1VSD14A06, N2VSD20A06 Installation Instruction

®
TYPE OF APPLICATIONS
UPFLOW DOWNFL OW
HORIZONTAL
ELECTRIC FURNACE
WITH 018 - 024 COIL
WITH 030 - 061 COIL
*
*Right hand ret urn may be used by remov ing Horizo ntal Drain Pa n
WITH 024 COIL
VARIABLE SPEED AIR HANDLERS
FOR USE WITH SPLIT SYSTEM COOLING AND HEAT PUMP
CAUTION
THE ENCL OSED I NST AL LAT I ON INSTRUCTI ONS AND ANY APPL I CABL E
LOCAL , STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITE D
TO, BUIL DING, ELECTRICAL, AND MECHANICAL CODES.
T HIS PRODUCT MUST BE INSTALLED IN STRICT COMPL IANCE WITH
WARNING
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAM AGE.
INCORRECT INSTALLA TION MAY CREATE A CONDITION WHERE THE
INSTALLATION INSTRUCTION
GENERAL
This instruction covers the installation of the following variable speed blower sections.
N1VSD10A06 N1VSD14A06 N2VSD20A06
The blower section is the basic component of an indoor modular system which may be combined with various accessories listed below to make an evaporator blower, evaporator blower with electric heat, heat pump blower, and heat pump blower with electric heat.
Because of the many ways this Air Handler may be applied and the large variety of available accessories, the indoor portion of the cooling or heat pump system comes to you in modules. These modules must be field assembled to meet the specific needs of the owner.
If this variable speed air handler is installed with a two stage (H*DS) outdoor condensing unit, a thermal expansion valve kit must be installed on the indoor side.
Check modules (accessories, etc.) received, against plans to be sure all required modules are available for assembly .
Supersedes: 535.03-N1Y (1293)
N*VS BLOWER SECTIONS
CAUTIONS WARNINGS
and/or equipment damage may result if installation procedures are not handled properly .
535.03-N1Y (594)
035-10809
are given to prevent equipment damage.
are given to alert the installer that personal injury
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. See Form 50.15-NM for more information.
REFERENCE
This instruction should be used in conjunction with installation instructions supplied with each accessory as well as the matching outdoor section.
Installer should pay particular attention to the words: NOTE, CAUTION and WA RNING.
NOTES
are intended to clarify or make the installation easier.
FIGURE 1 - Typical Component Application
535.03-N1Y
LIMIT ATIONS
These units must be wired and installed in accordance with all national and local safety codes.
Voltage limits are as follows:
Air Handler
Voltage
208/230 (06) 187-253
*Utilization range “A” in accordance with ARI Std. 110.
Air flow must be within the minimum and maximum limits ap­proved for electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp. °F Dry Bulb Temp. °F
MIN. MAX. MIN. MAX.
57 72 65 95
*Normal Operating
Voltage Range
3. Precautions should be taken to locate the unit and ductwork so that supply air does not short circuit to the return air.
4. If evaporator coil is used, locate to permit installation of a trapped condensate line to an open drain.
5. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil as is specified by most local building codes.
If the coil is provided with a secondary drain it should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secon­dary drain is not used it must be capped.
6. If unit is located in an area of high humidity, ie. an uncondi­tioned garage or attic, nuisance sweating of casing may occur. On these installations a wrap of 2" fiberglass insulation with vinyl vapor barrier should be used.
7. Proper electrical supply must be available.
CLEARANCE
Clearance must be provided for:
1. Refrigerant piping and connections - minimum 12" recommended.
2. Maintenance and servicing access - minimum 36" from front of unit recommended for blower motor / coil replacement.
3. Condensate drain line.
4. Filter removal - minimum 36" recommended.
LOCA TION
Location is usually predetermined. Check with owner’s or dealer’s installation plans. If location has not been decided, consider the following in choosing a suitable location:
MINIMUM CLEARANCE OF 1" ALL SIDES
8. Clearances must also be taken into consideration, and pro­vided for as follows:
a. Maintenance and servicing thru the front or access side of
unit with both sides and rear of unit having zero inch clearance.
b. When no electric heat is used, the unit as well as all duct
work and plenum are designed for zero clearance to combustible material.
c. If electric heat is used or anticipated, be sure a minimum
clearance of one inch is allowed on all sides of the supply
FLEXIBLE DUCT
3’
COLLAR
FIGURE 2 - Duct Clearance
1. Select a location with adequate structural support, space for service access, clearance for air return and supply duct connections.
2. Normal operating sound levels may be objectionable if the air handler is placed directly over some rooms such as bed­rooms, study, etc. A flexible duct collar is recommended as shown in Figure 2 to minimize noise.
2 Unitary Products Group
FIGURE 3 - Typical Wiring and Piping
air duct and plenum. This clearance must be maintained up to 3 feet a long the supply air duct. See Figure 2.
535.03-N1Y
liquid line connection and distributor . The orifice is identified on a label next to the liquid connection.
When a discharge plenum forms part of the duct work, it too must have one inch clearance on all sides.
DUCT CONNECTIONS
NOTE: The electric heat accessory should be installed before the
supply air duct is attached to the supply air openings.
Air supply and return may be handled in one of several ways best suited to the installation. See Figure 4 for Air Handler inlet and outlet dimensions. Inlet dimensions of Air Handler are the same as coil casing outlet dimensions.
The vast majority of problems encountered with combination heating and cooling systems can be linked to improperly designed or installed duct systems. It is therefore highly important to the success of an installation that the duct system be properly de­signed and installed.
Use flexible duct collars to minimize the transmission of vibra­tion/noise into the conditioned space. If electric heat is used non-flammable material must be used.
Duct work should be fabricated and installed in accordance with local and/or national codes. This includes the standards of the National Fire Protection Association for Installation of Air Conditioning and Ventilating Systems, NFPA No. 90A and Warm Air Heating and Air Conditioning Systems, NFP A No. 90B.
INDOOR UNIT PREPARATION
Prepare Air Handler for installation as follows: Each accessory is provided with its own instruction.
1. Attach coil casing to blower section in a way appropriate to indoor unit application.
See Form 535.01-N5V for G*HC or G*FC Coils and Form 535.01-N6V for G*HT Coils
Confirm the orifice size before connecting line. The G*HC and G*FC coils will have an orifice installed in the fitting between the
The orifice that is shipped with the coil is based on the “most sold” combination, but it may have to be changed, depending on the capacity and efficiency of the outdoor unit, elevation differences, and/or long total line lengths. See coil instruction and Application Data (Form 690.01-AD1V) for detailed piping guidelines.
If a thermal expansion valve kit is installed, the orifice must be removed.
The G*HT coils have a thermal expansion valve installed in the liquid line. An orifice is not included in this coil. Be sure the G*HT coil has been listed as a matched coil in the outdoor unit technical guide.
NOTE: If a humidistat accessory is installed with the system, a
thermal expansion valve kit or G*HT coil must be installed on the indoor side.
If a two stage (H*DS) outdoor condensing unit is installed with this variable speed air handler a thermal expansion valve kit must be installed.
2. Install Combustible Floor Base accessory if applicable. The floor base is required on blower-heater combinations with greater than zero clearance in a downflow position on a combustible floor.
See Form 535.01- N1.5V
NOTE: Instructions for installing accessories are included with the
accessories.
3. Attach Filter Rack Accessory if applicable. The filter rack is designed for use with G*HC, G*FC or G*HT coil or blower section.
See Form 535.01- N1.4V
CAUTION: Equipment should never be operated without filters.
4. Attach Suspension Kit if applicable. The suspension kit is designed to be used with all sizes of air handlers whenever the application requires horizontal or vertical suspension of the unit.
See Form 535.01 - N1.3V
5. Install Air Handler operating controls. A transformer accessory or an electric heater accessory must be supplied for the operation of the Air Handler .
See Form 535.03 - N1.1V See Form 535.01 - N4.1V
Unitary Products Group 3
024
535.03-N1Y
NOTES: Power wiring may be brought into the unit through one of the knockouts in either the top or the right side panel. Multiple knockouts are provided to accommodate all of the electric heat and transformer accessories that are available. Use the knockouts that provide the best wire routing for the accessory being used.
024
024
Coil
Model
Blower
*
**G*HT coil models o nly.
GHC,
Size
GFC,
GHT
024
D10
030 14-1/4 22-3/4 54-1/2 3-1/4 6-3/8 14-7/8 16-7/8 036
D14
042 20-1/4 27-7/8 59-5/8 6 8-1/8 20 22 048 060
D20
60D**
061**
G*HT coils are available as sweat connect only.
A B C D E F G H J K L M Liquid Vapor Liquid Vapor
16-1/4 1 12-1/8 3-7/8 12-1/8
22-1/4 3-5/8 14-7/8 3-7/8 12-1/8
26-1/4 5-5/8 14-7/8 3-7/8 12-1/8 24-1/4
Dimensions
14-1/4 22-3/4 54-1/2 3-1/2 1-1/2 1-3/4 3-1/2
20-1/4 22-3/4 54-1/2 6 7-3/8 14-7/8 16-7/8
27-7/8 59-5/8 8 6-3/4 20 22 31-3/8 63-1/8 7-1/4 7-5/8 23-1/2 25-1/2
Refrigerant*
Connections
Quick
Connect
F-6 F-11
Line
Sizes
5/16 5/8 5/16 3/4
3/8 7/8
FIGURE 4 - DIMENSIONS
4 Unitary Products Group
Loading...
+ 8 hidden pages