York N1VSD10A06, N1VSD14A06, N2VSD20A06 Installation Instruction

Page 1
®
TYPE OF APPLICATIONS
UPFLOW DOWNFL OW
HORIZONTAL
ELECTRIC FURNACE
WITH 018 - 024 COIL
WITH 030 - 061 COIL
*
*Right hand ret urn may be used by remov ing Horizo ntal Drain Pa n
WITH 024 COIL
VARIABLE SPEED AIR HANDLERS
FOR USE WITH SPLIT SYSTEM COOLING AND HEAT PUMP
CAUTION
THE ENCL OSED I NST AL LAT I ON INSTRUCTI ONS AND ANY APPL I CABL E
LOCAL , STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITE D
TO, BUIL DING, ELECTRICAL, AND MECHANICAL CODES.
T HIS PRODUCT MUST BE INSTALLED IN STRICT COMPL IANCE WITH
WARNING
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAM AGE.
INCORRECT INSTALLA TION MAY CREATE A CONDITION WHERE THE
INSTALLATION INSTRUCTION
GENERAL
This instruction covers the installation of the following variable speed blower sections.
N1VSD10A06 N1VSD14A06 N2VSD20A06
The blower section is the basic component of an indoor modular system which may be combined with various accessories listed below to make an evaporator blower, evaporator blower with electric heat, heat pump blower, and heat pump blower with electric heat.
Because of the many ways this Air Handler may be applied and the large variety of available accessories, the indoor portion of the cooling or heat pump system comes to you in modules. These modules must be field assembled to meet the specific needs of the owner.
If this variable speed air handler is installed with a two stage (H*DS) outdoor condensing unit, a thermal expansion valve kit must be installed on the indoor side.
Check modules (accessories, etc.) received, against plans to be sure all required modules are available for assembly .
Supersedes: 535.03-N1Y (1293)
N*VS BLOWER SECTIONS
CAUTIONS WARNINGS
and/or equipment damage may result if installation procedures are not handled properly .
535.03-N1Y (594)
035-10809
are given to prevent equipment damage.
are given to alert the installer that personal injury
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. See Form 50.15-NM for more information.
REFERENCE
This instruction should be used in conjunction with installation instructions supplied with each accessory as well as the matching outdoor section.
Installer should pay particular attention to the words: NOTE, CAUTION and WA RNING.
NOTES
are intended to clarify or make the installation easier.
FIGURE 1 - Typical Component Application
Page 2
535.03-N1Y
LIMIT ATIONS
These units must be wired and installed in accordance with all national and local safety codes.
Voltage limits are as follows:
Air Handler
Voltage
208/230 (06) 187-253
*Utilization range “A” in accordance with ARI Std. 110.
Air flow must be within the minimum and maximum limits ap­proved for electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp. °F Dry Bulb Temp. °F
MIN. MAX. MIN. MAX.
57 72 65 95
*Normal Operating
Voltage Range
3. Precautions should be taken to locate the unit and ductwork so that supply air does not short circuit to the return air.
4. If evaporator coil is used, locate to permit installation of a trapped condensate line to an open drain.
5. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil as is specified by most local building codes.
If the coil is provided with a secondary drain it should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secon­dary drain is not used it must be capped.
6. If unit is located in an area of high humidity, ie. an uncondi­tioned garage or attic, nuisance sweating of casing may occur. On these installations a wrap of 2" fiberglass insulation with vinyl vapor barrier should be used.
7. Proper electrical supply must be available.
CLEARANCE
Clearance must be provided for:
1. Refrigerant piping and connections - minimum 12" recommended.
2. Maintenance and servicing access - minimum 36" from front of unit recommended for blower motor / coil replacement.
3. Condensate drain line.
4. Filter removal - minimum 36" recommended.
LOCA TION
Location is usually predetermined. Check with owner’s or dealer’s installation plans. If location has not been decided, consider the following in choosing a suitable location:
MINIMUM CLEARANCE OF 1" ALL SIDES
8. Clearances must also be taken into consideration, and pro­vided for as follows:
a. Maintenance and servicing thru the front or access side of
unit with both sides and rear of unit having zero inch clearance.
b. When no electric heat is used, the unit as well as all duct
work and plenum are designed for zero clearance to combustible material.
c. If electric heat is used or anticipated, be sure a minimum
clearance of one inch is allowed on all sides of the supply
FLEXIBLE DUCT
3’
COLLAR
FIGURE 2 - Duct Clearance
1. Select a location with adequate structural support, space for service access, clearance for air return and supply duct connections.
2. Normal operating sound levels may be objectionable if the air handler is placed directly over some rooms such as bed­rooms, study, etc. A flexible duct collar is recommended as shown in Figure 2 to minimize noise.
2 Unitary Products Group
FIGURE 3 - Typical Wiring and Piping
Page 3
air duct and plenum. This clearance must be maintained up to 3 feet a long the supply air duct. See Figure 2.
535.03-N1Y
liquid line connection and distributor . The orifice is identified on a label next to the liquid connection.
When a discharge plenum forms part of the duct work, it too must have one inch clearance on all sides.
DUCT CONNECTIONS
NOTE: The electric heat accessory should be installed before the
supply air duct is attached to the supply air openings.
Air supply and return may be handled in one of several ways best suited to the installation. See Figure 4 for Air Handler inlet and outlet dimensions. Inlet dimensions of Air Handler are the same as coil casing outlet dimensions.
The vast majority of problems encountered with combination heating and cooling systems can be linked to improperly designed or installed duct systems. It is therefore highly important to the success of an installation that the duct system be properly de­signed and installed.
Use flexible duct collars to minimize the transmission of vibra­tion/noise into the conditioned space. If electric heat is used non-flammable material must be used.
Duct work should be fabricated and installed in accordance with local and/or national codes. This includes the standards of the National Fire Protection Association for Installation of Air Conditioning and Ventilating Systems, NFPA No. 90A and Warm Air Heating and Air Conditioning Systems, NFP A No. 90B.
INDOOR UNIT PREPARATION
Prepare Air Handler for installation as follows: Each accessory is provided with its own instruction.
1. Attach coil casing to blower section in a way appropriate to indoor unit application.
See Form 535.01-N5V for G*HC or G*FC Coils and Form 535.01-N6V for G*HT Coils
Confirm the orifice size before connecting line. The G*HC and G*FC coils will have an orifice installed in the fitting between the
The orifice that is shipped with the coil is based on the “most sold” combination, but it may have to be changed, depending on the capacity and efficiency of the outdoor unit, elevation differences, and/or long total line lengths. See coil instruction and Application Data (Form 690.01-AD1V) for detailed piping guidelines.
If a thermal expansion valve kit is installed, the orifice must be removed.
The G*HT coils have a thermal expansion valve installed in the liquid line. An orifice is not included in this coil. Be sure the G*HT coil has been listed as a matched coil in the outdoor unit technical guide.
NOTE: If a humidistat accessory is installed with the system, a
thermal expansion valve kit or G*HT coil must be installed on the indoor side.
If a two stage (H*DS) outdoor condensing unit is installed with this variable speed air handler a thermal expansion valve kit must be installed.
2. Install Combustible Floor Base accessory if applicable. The floor base is required on blower-heater combinations with greater than zero clearance in a downflow position on a combustible floor.
See Form 535.01- N1.5V
NOTE: Instructions for installing accessories are included with the
accessories.
3. Attach Filter Rack Accessory if applicable. The filter rack is designed for use with G*HC, G*FC or G*HT coil or blower section.
See Form 535.01- N1.4V
CAUTION: Equipment should never be operated without filters.
4. Attach Suspension Kit if applicable. The suspension kit is designed to be used with all sizes of air handlers whenever the application requires horizontal or vertical suspension of the unit.
See Form 535.01 - N1.3V
5. Install Air Handler operating controls. A transformer accessory or an electric heater accessory must be supplied for the operation of the Air Handler .
See Form 535.03 - N1.1V See Form 535.01 - N4.1V
Unitary Products Group 3
Page 4
024
535.03-N1Y
NOTES: Power wiring may be brought into the unit through one of the knockouts in either the top or the right side panel. Multiple knockouts are provided to accommodate all of the electric heat and transformer accessories that are available. Use the knockouts that provide the best wire routing for the accessory being used.
024
024
Coil
Model
Blower
*
**G*HT coil models o nly.
GHC,
Size
GFC,
GHT
024
D10
030 14-1/4 22-3/4 54-1/2 3-1/4 6-3/8 14-7/8 16-7/8 036
D14
042 20-1/4 27-7/8 59-5/8 6 8-1/8 20 22 048 060
D20
60D**
061**
G*HT coils are available as sweat connect only.
A B C D E F G H J K L M Liquid Vapor Liquid Vapor
16-1/4 1 12-1/8 3-7/8 12-1/8
22-1/4 3-5/8 14-7/8 3-7/8 12-1/8
26-1/4 5-5/8 14-7/8 3-7/8 12-1/8 24-1/4
Dimensions
14-1/4 22-3/4 54-1/2 3-1/2 1-1/2 1-3/4 3-1/2
20-1/4 22-3/4 54-1/2 6 7-3/8 14-7/8 16-7/8
27-7/8 59-5/8 8 6-3/4 20 22 31-3/8 63-1/8 7-1/4 7-5/8 23-1/2 25-1/2
Refrigerant*
Connections
Quick
Connect
F-6 F-11
Line
Sizes
5/16 5/8 5/16 3/4
3/8 7/8
FIGURE 4 - DIMENSIONS
4 Unitary Products Group
Page 5
ELECTRICAL CON NECT IONS
12.5, 15 & 20 KW CONTROL BOARDS
FIGURE 5 - Line Power Connections
Wire Transformer Kit or Electric Heater per wiring diagram on th e accessory . T ypical field wiring is shown in Figures 9, 10 and 11.
CAUTION: Break off tab must be removed from 2HW electric
heat control boards for variable speed operation. See Figure 6.
NOTE: All wiring must comply with local and national electrical
code requirements. Read and heed all unit caution labels.
LINE POWER CONNECTIONS
Power may be brought into the unit through the supply air end of the unit (top when unit is vertical) or the right side panel. Use the hole appropriate to the unit’s orientation in each installation to bring conduit from the disconnect. The power lead conduit should
GRD. LUG
WITHOUT CIRCUIT BREAKER
GRD.
POWER SUPPLY
CIRCUIT BREAKERS
POWER WIRING
GRD. LUG
WITH CIRCUIT BREAKER
535.03-N1Y
be terminated at the transformer or electric heater box. Refer to Tables 2 and 5 for single source wire sizes. Also see Figure 5.
ALTERNATE LINE POWER CONNECTI ONS
When desired or required by local conditions the units equipped with circuit breakers may be field converted to use multiple power sources, this will permit the use of smal ler size power wire but will require a greater number of wires. To accomplish this field con­version refer to Figure 5 - (Dual Supply) as an example and proceed as follows.
1. Remove the jumper bar assembly and cover at the line side connection to the circuit breakers.
2. Select the proper wire size from Table 3.
DUAL SUPPLYSINGLE SUPPLY
GRD.
POWER SUPPLY
GRD. LUG
GRD.
NOTE: Two circuits permit smaller wire.
CIRCUIT BREAKERS
POWER
SUPPLY 1
WITH CIRCUIT BREAKER
POWER
SUPPLY 2
FIELD REMOVED BUSSBAR
5, 7.5 & 10 KW CONTROL BO ARDS
NOTE: LINE VOLTAGE POWER CONNECTS DIRECTLY T O 10 KW BOARDS
EDGE CONNECTOR (For Wiring Harness that attaches to Connection Board)
BREAK OFF TABS (For V ariable Speed Air Handler ONL Y - must be removed)
FIGURE 6 - Typical Electric Heat Control Boards
EDGE CONNECTOR (For Wiring Harness that attaches to Connection Board)
- (5-20KW Single Phase)
BREAK OFF TABS (For V ariable Speed Air Handler ONL Y - must be removed)
Unitary Products Group 5
Page 6
JUMPER IN “A” CFM POSITION
535.03-N1Y
FAN MOTOR SPEED TAP RECEPTACLE ON TRANSFORMER OR HEATER ACCESSORY
208/230V
Field supplied low voltage wiring must be kept as short as possi­ble and away from the blower motor wires. Refer to Table 2, 3 or 5 for minimum wire size.
PURPLE
BLUE
GRD.
5 PIN CONNECTOR
PURPLE
BLUE
VARIABLE SPEED MOTOR
WIRE HARNESS TO CONNECTOR BOARD (16 PIN CONNECTOR)
FIGURE 7 - Blower Connections
LOW VOLTAGE CO NT ROL CO NNECT ION S
Use 7/8 inch knockout on the left hand side panel to bring low voltage wiring into air handler.
CAUTION: Use 7/8 inch plastic bushing provided to prevent
All field control wiring to be connected at screw terminals of connector board. See Figure 8.
Remove control wiring harness supplied with 2HW electric heat accessory and discard. Every connector board is supplied with a complete electric heat wiring harness connected to the lower right hand corner of connector board (See Figure 8). Plug in free end of wiring harness to electric heat control board. If the transformer kit is installed, discard electric heat wiring harness attached to connector board. Install wiring harness provided with transformer accessory at the connection in lower right hand corner of connec­tor board.
chafing wires.
The 24 volt power supply is provided by an internally wired low voltage transformer. However , if the unit is connected to a 208 volt power supply the low voltage transformer must be rewired to the 208 volt tap. See the unit wiring label.
See Figure 9, 10 and 1 1 for low voltage terminal connections. If thermostat used has an adjustable heat anticipator, see Table
below for proper setting.
HEAT ANTICIPATOR SETTING
Electric Heater with
Cooling or
Electric Heater Only
2HW 5 - 20 0.1 Amps
KW
Adjustable
Heat
Anticipator
BLOWER SPEED SEL ECTI ON
All variable speed air handlers (N*VS) are designed to deliver constant CFM regardless of the external static pressure (ESP) in the ductwork. Therefore, if too many supply registers are closed, a filter becomes clogged, or there is a restriction in the ductwork, the motor will automatically operate at a higher speed to compen­sate for the higher ESP. This may result in a higher operating sound level.
To Set Cooling CFM: Refer to the outdoor unit technical guide for the recommended
airflow with the matching evaporator coil. Refer to the label on the blower housing or T able 1 for the possible HI speed cooling and/or
SCREW TERMINAL BOARD
HUMIDISTAT ACCESSORY JUMPER
FIGURE 8 - N*VS Connector Board
HEA T PUMP JU MPER
BLOWER MOTOR INTERFACE HARNESS CONNECTS HERE
JUMPER IN STORED POSITION
(Vertically on RH side, pins “A” and “B”)
COOL TAP
(Horizontally jumper two “A” pins)
ELECTRIC
HEA T TAP
ADJ TAP
DELA Y
PROFILE TAP
ELECTRIC HEA T OR TRANSFORMER WIRING HARNESS CONNEC TS HE RE
6 Unitary Products Group
Page 7
heat pump CFM selections. Find the recommended system air­flow in the table for the installed Air Handler model.
Moving up the table, identify the “COOL” tap jumper position (“A”, “B”, “C” or No Jumper). Go to the connector board and set the jumper horizontally for the “COOL” tap position. See Figure 8 for the layout of the connector board.
NOTE: No jumper indicates the jumper should be removed or
placed in the “store” position (see Figure 8).
To Set Heat Pump CFM: The heat pump CFM setting is the same as the cooling CFM. No
additional CFM setting is required, however, you mu st remove the jumper at the bottom of the connector board labeled “Remove for Heat Pump” for heat pump operation. (See Figure 8.)
To Set Electric Heat CFM: The blower speed required for the Electric Heat is different than
cooling. Refer to the label on the blower housing or Table 1 for the possible CFM selections. Refer to Table 4 for the minimum required CFM for the electric heater installed. Find the desired airflow in Table 1. Moving up the table, identify the “HEAT” tap jumper position. Go to the connector board and set the jumper horizontally for the “HEA T” ta p position.
CAUTION: DO NOT change the “ADJ” tap position on the con-
nector board as this will change your cooling CFM previously selected.
To Set Delay Profile: Every variable speed air handler has multiple “blower off delay”
profiles to optimize system performance and efficiency .
535.03-N1Y
Refer to Table below for the type of system installed. set the “DELA Y” jumper tap position horizontally on the connector board for the appropriate setting.
Delay Profile
“DELA Y” T ap Unit Type Jumper at “A” System wo/TXV or wo/ S.V. Jumper at “B” System w/TXV or w/ S. V. Jumper at “C” Two Stage Condensor
No Jumper Test Mode
TXV= Thermal Expansion Valve SV= Solenoid Valve
To Install Humidistat Accessory: If the system is used with a humidistat accessory, connect the field
wires to screw terminals “R” and “BK” on the connector board. See Figures 10 or 11.
IMPORTANT : Remove the jumper at the bottom of the connector board marked “Remove for Humidistat” for humidistat operation.
MAINTENANCE
One permanent high velocity washable filter is provided with each filter rack. This filter may be cleaned with a vacuum cleaner or washed with warm water using a mild detergent. Do not use a high velocity water stream. No coating is required. Install filter with cloth mesh towards blower . Never turn a dirty filter to allow air flow in the opposite direction.
Filters must be cleaned when they become dirty. Inspect at least once per month. The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions. Clean filters keep unit efficiency high.
COIL CLEA NING
If the coil needs to be cleaned, it should be washed with Calgon Coilclean (mix one part Coilclean to seven parts water). Allow solution to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted surfaces.
Unitary Products Group 7
Page 8
535.03-N1Y
TABLE 1 - CFM / TAP SELECT IO N
MODEL HI SPEED COOLING AND HEAT PUMP CFM SELECTION
“COOL” Tap
Cubic Foot Per Minut e (CF M) 610 650 850 900 Jumper at “B” 680 720 950 1000 No Jumper
N1VSD10
N1VSD14
N2VSD20
750 800 1050 1100 Jumper at “C”
ELECTRIC HEAT CFM SELECTION
“HEAT” Tap
Jumper at “A” Jumper at “B” Jumper at “C” No Jumper
Cubic Foot Per Minut e (CF M) 900 1000 1050 1100
HI SPEED COOLING AND HEAT PUMP CFM SELECTION
“COOL” Tap
Cubic Foot Per Minut e (CF M) 900 1050 1210 1260 Jumper at “B”
1000 1175 1350 1400 No Jumper 1100 1300 1485 1540 Jumper at “C”
ELECTRIC HEAT CFM SELECTION
“HEAT” Tap
Jumper at “A” Jumper at “B” Jumper at “C” No Jumper
Cubic Foot Per Minut e (CF M)
1100 1200 1300 1400
HI SPEED COOLING AND HEAT PUMP CFM SELECTION
“COOL” Tap
Cubic Foot Per Minut e (CF M)
1050 1500 1550 1625 Jumper at “B” 1150 1660 1750 1800 No Jumper 1350 1900 2000 2090 Jumper at “C”
“ADJ” TapJumper at “A” Jumper at “B” Jumper at “C” No Jumper
“ADJ” TapJumper at “A” Jumper at “B” Jumper at “C” No Jumper
“ADJ” TapJumper at “A” Jumper at “B” Jumper at “C” No Jumper
ELECTRIC HEAT CFM SELECTION
“HEAT” Tap
Jumper at “A” Jumper at “B” Jumper at “C” No Jumper
Cubic Foot Per Minut e (CF M)
1300 1300 1450 1600
T A BLE 2 - ELECTRICAL DATA / TRANSFORMER KIT
BLOWER
SIZE N1VSD10 N1VSD14 5.4 5.4 15 14 N2VSD20 8.8 8.8 15 14
TRANFORMER
KIT
2TT6700506
208/230V
TABLE 3 - ELECTRICAL DATA / HEATER ACCESSORY
Blower
Size
N1VSD10
N1VSD14
N2VSD20
* NOTE: 60°C and 90° C wire may be used. Reference the latest edition of National Electrical Code for proper wire size.
Heater Accessory Model No.
2HW06501306 48/56 11/ 13 50/60 15/15 8/6 14/14 2HW06501506 48/56 23/26 50/60 25/30 8/6 10/10 2HW06502006 48/56 45/52 50/60 50/60 8/6 8/6 2HW06501306 51/58 11/ 13 60/60 15/15 6/6 14/14 2HW06501506 51/58 23/26 60/60 25/30 6/6 10/10 2HW06502006 51/58 45/52 60/60 50/60 6/6 8/6 2HW06501306 54/61 11/ 13 60/60 15/15 6/6 14/14 2HW06501506 54/61 23/26 60/60 25/30 6/6 10/10 2HW06502006 54/61 45/52 60/60 50/60 6/6 8/6
Min. Circuit Ampac ity Max. Time Delay Fuse
Circuit Circuit Circuit
1st 2nd 1st 2nd 1st 2nd
208/240 208/240 208/240 208/240 208/240 208/240
MIN. CIRCUIT AMPACITY
208 230
2.8 2.8 15 14
MAX. T.D. FUSE SIZE MIN. WIRE SIZE AWG.
/ MULTI-POWER SOURCE
75°C Wire Size - AWG*
8 Unitary Products Group
Page 9
TABLE 4 - ELECTRICAL DA TA / HEA TER ACCESSORY
Blower
Size
N1VSD10
N1VSD14
N2VSD20
Heater Accessory Model No.
2HW06500506 900 3.8/5.0 13.0/17.1 3.8/5.0 ­2HW06500806 950 5.0/7.5 19.1/25.6 3.8/5.0 1.8/2.5 2HW06501006 1000 7.5/10.0 25.6/34.2 3.8/5.0 3.8/5.0 2HW26501006 1000 7.5/10.0 25.6/34.2 3.8/5.0 3.8/5.0 2HW06501306 1050 9.4/12.5 32.1/42.7 3.8/5.0 5.6/7.5 2HW06501506 1100 11.3/15.0 38.6/51.2 3.8/5.0 7.5/10.0 2HW06502006 1100 15.0/20.0 51.2/68.3 3.8/5.0 11.3/15.0 2HW06500506 1100 3.8/5.0 13.0/17.1 3.8/5.0 ­2HW06500806 1100 5.0/7.5 19.1/25.6 3.8/5.0 1.8/2.5 2HW06501006 1200 7.5/10.0 25.6/34.2 3.8/5.0 3.8/5.0 2HW26501006 1200 7.5/10.0 25.6/34.2 3.8/5.0 3.8/5.0 2HW06501306 1300 9.4/12.5 32.1/42.7 3.8/5.0 5.6/7.5 2HW06501506 1300 11.3/15. 0 38.6/51.2 3.8/5.0 7.5/10.0 2HW06502006 1400 15.0/20.0 51.2/68.3 3.8/5.0 11.3/15.0 2HW06500506 1200 3.8/5.0 13.0/17.1 3.8/5.0 ­2HW06500806 1200 5.0/7.5 19.1/25.6 3.8/5.0 1.8/2.5 2HW06501006 1300 7.5/10.0 25.6/34.2 3.8/5.0 3.8/5.0 2HW26501006 1300 7.5/10.0 25.6/34.2 3.8/5.0 3.8/5.0 2HW06501306 1450 9.4/12.5 32.1/42.7 3.8/5.0 5.6/7.5 2HW06501506 1450 11.3/15. 0 38.6/51.2 3.8/5.0 7.5/10.0 2HW06502006 1600 15.0/20.0 51.2/68.3 3.8/5.0 11.3/15.0
Min. CFM
Cooling or
Heat Pump
208/230-1-60 HEA TERS
535.03-N1Y
Total Heat
1
KW Staging
KW MBH 1st 2nd
208/240 208/240 208/240 208/240
TABLE 5 - ELECT RICAL DATA / HEATER ACCESSORY
Blower
Size
Heater Accessory Model No.
Min. Ckt. Ampacity
2HW06500506 26/30 30/35 10/8 NONE 2HW06500806 37/43 40/45 8/8 NONE 2HW06501006 48/56 50/60 8/6 NONE
N1VSD10
2HW26501006 48/56 50/60 8/6 BREAKER 2HW06501306 60/68 60/70 6/4 BREAKER 2HW06501506 71/82 80/90 4/4 BREAKER 2HW06502006 94/108 100/125 3/2 BREAKER 2HW06500506 28/31 30/35 10/8 NONE 2HW06500806 39/44 40/45 8/8 NONE 2HW06501006 51/58 60/60 6/6 NONE
N1VSD14
2HW26501006 51/58 60/60 6/6 BREAKER 2HW06501306 62/71 70/80 6/4 BREAKER 2HW06501506 73/83 80/90 4/4 BREAKER 2HW06502006 96/110 100/110 3/2 BREAKER 2HW06500506 31/35 35/35 8/8 NONE 2HW06500806 43/48 45/50 8/8 NONE 2HW06501006 54/61 60/60 6/6 NONE
N2VSD20
2HW26501006 54/61 60/60 6/6 BREAKER 2HW06501306 65/74 70/80 6/4 BREAKER 2HW06501506 76/87 80/90 4/4 BREAKER 2HW06502006 99/113 100/125 3/2 BREAKER
NOTE: Air handler and heater accessory may be com bined without a coil fo r electric furnace applica t io ns. Model Number suf fix i nd ica tes voltage. 06=208/230 -1-6 0. * NOTE: 60°C and 90°C wire may be used. Referrence the latest e dition of Natio na l Ele ctrical Co de for proper wire size.
Field Wiring - 208/240 Max. Overcurrent
Prot. Amps/Type
208/230-1-60 HEAT ER S
Wire Size, AWG*
75°C Copper
Factory-Installed
Over-Current
Protection
1
KW & MBH CONVERSIONS:
208-VOLT
FOR
230-VOLT 240-VOLT .918
Unitary Products Group 9
OPERATION, MULTIPLY
240-VOLT
TABULATED KW & MBH BY
.751
Page 10
THERMO STAT
Y
G W
OUTDOOR UNIT
O
R
B Y
O
X R
W
66
C Y
R
G
CONNECTOR BOARD
X or L
B or C
60
53
O X
("HUMIDISTAT" JUMPER MUST BE REMOVED)
DEHUMIDIFICATION CONTROL CONNECTION
NOT USED
NOT USED
BK
535.03-N1Y
CONNECTOR
THERMOSTAT
R Y
G W
NOT USED
DEHUMIDIFICATION CONTROL CONNECTION
("HUMIDISTAT" JUMPER MUST BE REMOVED)
BOARD
COOLING UNITS 208/230 VOLT
MODELS H*DA and H*DH
THERMOSTAT
TWO STAGE COOLING MUST BE USED
X or L
C or B
R C
Y G
BK
R
Y1 Y2
G
W1
W2
OUTDOOR UNIT
INDO OR UNIT CONNECTO R BOARD
O
WIRE NUT
X
R
C
Y Y1 Y2
G
W/W1 W2 BK
HEAT PUMPS 208/230 VOLT
MODELS E*FB and E*FH
OUTDOOR UNIT
NO
RED
BLU
BLK
YEL
BRN
H*DS CONTROL BOAR D
DEHUMIDIFICATION CONTROL CONNECTION
("HUMIDISTAT" JUMPER MUST BE REMOVED)
R C
Y2 OUT
Y1 Y2
FIGURE 9 - Control Wiring / Transformer Accessory
10 Unitary Products Group
COOLING UNIT 208/230 MODELS H*DS
Page 11
INDOOR UNIT CONNECTOR BOARD
O
THERMOSTAT
R
Y
G W
X R C
Y Y1 Y2
G
DEHUMIDIFICATION CONTROL CONNECTION
("HUMIDISTAT" JUMPER MUST BE REMOVED)
FIELD INSTALLED JUMPER
W/W1
W2 BK
COOLING WITH ELECTRIC HEAT MODELS H*DA and H*DH
535.03-N1Y
OUTDOOR UNIT
INDO OR UNIT
THERMOSTAT
TWO STAGE COOLING MUST BE USED
X or L
R
C or B
CONNECTOR BOARD
O X
R
C Y
Y1 Y2
G
W1
W2
Y1 Y2
G
W/W1 W2 BK
COOLING WITH ELECTRIC HEAT MODEL H*DS
FIGURE 10 - Control Wiring / Electric Heat
WIRE NUT
- COOLING
OUTDOOR UNIT
NO
RED
BLU
BLK YEL
BRN
H*DS CONTROL BOAR D
R C
Y2 OUT
Y1 Y2
DEHUMIDIFICATION CONTROL CONNECTION
("HUMIDISTAT" JUMPER MUST BE REMOVED)
Unitary Products Group 11
Page 12
THERMOSTAT
G
X or L
R
OUTDOOR HEATPUMP
R
C Y
G
O X
W/W1
W2
INDOOR UNIT CONNECTOR BOARD
("HUMIDISTAT" JUMPER MUST BE REMOVED)
Y1 Y2
BK
DEHUMIDIFICATION CONTROL CONNECTION
O
Y
W E T
X
B
R
O
Y
W
66
C or B
FIELD INSTALLED JUMPER
1
1
OUTDOOR THERMISTOR
**
**
HEAT PUMP (1 Phase)
THERMOSTAT
G
X or L
R
OUTDOOR HEATPUMP
R
C Y
G
O X
W2
INDOOR UNIT CONNECTOR BOARD
("HUMIDISTAT" JUMPER MUST BE REMOVED)
Y1 Y2
BK
DEHUMIDIFICATION CONTROL CONNECTION
O
Y
W
E
T
X
B
R
O
Y
W
66
B or C
FIELD INSTALLED JUMPER
1
1
OUTDOOR THERMISTOR
60 53
W/W1
**
**
MODELS E*FB
**TERMINAL NOT A V AILABLE ON ALL THERMOST ATS.
IMPORTANT NOTE:
HEA T PUMP JUMPER A T BOTTOM OF THE CONNECTOR BOARD MUST BE REMOVED WHEN AIR HANDLER IS USED WITH A HEAT PUMP UNIT.
FIGURE 11 - Control Wiring with Electric Heat
P.O. Box 1592, Yo rk, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in U.S.A Copyright  by York International Co rp ora tion 1993. All Rights Reserved.
HEAT PUMP MODELS E*FH
- HEAT PUMP
Supersedes: 535.03-N1Y
Loading...