• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.
• Contact us by mail:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
The manufacturer recommends that the user read all sections of this manual and keep the manual for future reference.
FIRE OR EXPLOSION HAZARD - Failure to follow safety
warnings exactly could result in serious injury, death, or property damage.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS:
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone
(including cell phone) in your building.
•Leave the building immedia te l y.
•Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
SECTION I: USER’S INFORMATION
SAFETY
1.The furnace area must be kept clear and free of combustible materials, gasoline and other flammable vapors and liquids.
2.Insulating materials may be combustible. The furnace must be
kept free and clear of insulating materials. The furnace area must
be examined when installed in an attic or other insulated space or
when insulation is added to be sure that the insulation material has
been kept away from the furnace.
3.The furnace needs air for combustion in order to operate properly
and safely. Do not block or obstruct air openings on the furnace,
air openings to the area where the furnace is installed, or spaces
around the furnace.
4.Follow the instructions exactly as shown on the OPERATING
INSTRUCTION LABEL or the Start-up and Shutdown Instructions
on Page 3 of this manual when lighting the furnace or turning the
furnace off.
5.Should the gas supply fail to shut off or if overheating occurs, shut
off the gas valve to the furnace before shutting off the electrical
supply.
6.Do not use this furnace if any part has been under water. A flooddamaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. A qualified service agency
should be contacted to inspect the furnace and replace all gas
controls, control system parts, electrical parts that have been wet
or the furnace if deemed necessary.
271015-UUM-A-0407
271015-UUM-A-0407
CONTROL
BOARD
PRESUURE
SWITCH
SILICONE
TUBE
GAS VALVE
FLAME
SENSOR
VENT PIPE
FLUE
COLLAR
ELECTRICAL
JUNCTION BOX
SAFETY SHUTOFF
SWITCH
INDUCED DRAFT
ASSEMBLY
INDUCED DRAFT
MOTOR
LIMIT
SWITCH
IGNITOR
MANIFOLD
PIPE
FIGURE 1: Component Locations
7.NEVER. . .Store flammable materials of any kind near your furnace. Gasoline, solvents, and other volatile liquids should be
stored only in approved containers outside your home. These
materials vaporize easily and are extremely dangerous.
8.NEVER. . .Store cleaning materials near your furnace. Materials
such as bleaches, detergents, powdered cleansers, etc., can
cause corrosion of the heat exchangers.
9.NEVER. . . Use the area around your furnace as a storage area for
items which could block the normal flow of air. This flow of air is
required for ventilation of the various furnace components.
INSTRUCTIONS FOR EXAMINING THE FURNACE
INSTALLATION
It is the owner’s responsibility to ensure that an annual inspection of the
entire heating portion of the unit is made by a qualified service agency.
Examine the furnace as outlined below in steps “1 - 6” before each
heating season. Use Figure 3 for visual reference.
1.Examine the heat exchanger, vent pipe, combustion air passages,
vent connectors and chimney to be sure they are clear and free of
obstructions.
2.Examine the vent pipe making sure it is firmly in place, that it
slopes slightly upward and is physically sound without holes and
all of the connections are secure.
3.Examine the return-air duct connections to make sure they are
physically sound, sealed to the furnace casing, and the ducts terminate outside the space containing the furnace.
4.Examine the furnace casing making sure the physical support is
sound without sagging, cracks or gaps. Examine the furnace base
making sure it is physically sound without cracks, gaps or sagging
and has a good seal.
5.Examine the furnace casing for obvious signs of deterioration.
6.Examine the burner flames to make sure they are in good adjustment. Refer to the pictorial sketch shown in Figure 2 as a comparison to the actual flame.
BLUE CONE PORTION OF FLAME SHOULD
ENTER HEAT EXCHANGER TUBE
FIRE OR EXPLOSION HAZARD
This furnace is designed and approved for use with Nat-
ural Gas and (LP) Propane Gas ONLY. DO NOT BURN
ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the
furnace heat exchanger, which could result in Fire, Personal Injury, and/or Property Damage.
3
EXAMINE
RETURN AIR
DUCT
CONNECTION
6
REMOVE
PANEL
TO EXAMINE
BURNER
FLAMES
EXAMINE EXTERNAL
VENT PIPE
4
EXAMINE
FURNACE
CASING
FIGURE 3: Furnace Examination Checkpoints
5
EXAMINE ENTIRE
FURNACE CASING
SHOWN IN ALL
DRAWINGS
1
EXTERNAL HEAT
EXCHANGER
INTERNAL
VENT COMBUSTION
AIR PIPE. MUST
REMOVE PANEL TO
EXAMINE.
FIGURE 2: Burner Flame Drawing
4
EXAMINE
FURNACE
CASING
3
EXAMINE
RETURN AIR
DUCT
CONNECTION
6
REMOVE PANEL
TO EXAMINE
BURNER FLAMES
2Unitary Products Group
271015-UUM-A-0407
INLET
WRENCH
BOSS
INLET
PRESSURE
PORT
ON OFF
SWITCH
LOW STAGE REGULATOR
ADJUSTMENT
OUTLET
OUTLET
PRESSURE
PORT
VENT
PORT
HIGH STAGE REGULATOR
ADJUSTMENT
HOW YOUR GAS FURNACE WORKS
Your furna ce is a very easy appliance to take for granted. Season after
season, it sits there in your home, keeping you warm and comfortable.
For this reason, you may never have given much thought to the way
your furnace operates. In order to get the safest and most efficient operation from your furnace, you should understand how your furnace does
its job.
When you set your thermostat to provide more heat in your home, you
To Turn Off the Appliance:
1.Set the thermostat to lowest setting.
2.Turn off all electric power to the appliance if service is to be performed.
3.Remove burner access panel.
4.Move gas control switch to the “OFF” position. See Figure 4.
5.Replace burner access panel.
are starting the heating cycle of the furnace. First, the inducer motor
starts to purge the heat exchanger of any remaining gases. Next, the
hot surface ignitor glows and after a warm-up period the gas valve
opens and ignition occurs. A short time later, the blower starts and distributes the warm air throughout the home. When the temperature setting on your thermostat is reached, the gas valve closes, the main
burners are turned off, and the blower continues to run until the remaining warm air in the system is distributed. When the blower stops, the
Should overheating occur, or the gas valve fail to shut off,
turn the external manual gas valve in the gas supply line to
the furnace to the “off” position and let the furnace cool off
before shutting off the electrical power supply. Refer to
Figure 5.
heating cycle has ended.
START-UP AND SHUTDOWN INSTRUCTIONS
Read the Instructions Below Before Trying to Start the
Furnace
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal
injury, and/or loss of life.
A.This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the
burner by hand.
B.BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
C.Use only your hand to push the gas control switch to the “on” posi-
tion. Never use tools. If the switch will not operate by hand, don’t
try to repair it, call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D.Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
Operating Instructions:
1.STOP! Read the safety information above.
2.Set the thermostat to the lowest setting.
3.Turn off all electric power to the appliance.
4.Remove burner access panel.
5.Move gas control switch to the “OFF” position. Do not force. See
Figure 4.
6.Wait five (5) minutes to clear out any gas. If you then smell gas,
STOP! Follow “B” in the safety information above. If you don’t
smell gas, go to next step.
7.Move gas control switch to the “ON” position. Do not force. See
Figure 4.
8.Replace burner access panel.
9.Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may
take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate follow the instructions, “TO TURN OFF THE APPLIANCE” and call
your service technician or gas supplier.
Unitary Products Group3
FIGURE 4: Gas Valve
EXTERNAL MANUAL
SHUTOFF VALVE
TO GAS
SUPPLY
DRIP
LEG
TO GAS
SUPPLY
GROUNDED JOINT UNION
MAY BE INSTALLED
INSIDE OR OUTSIDE UNIT.
FIGURE 5: Gas Piping
NOTE: The spring-loaded safety cut-off switch, mounted under the
blower deck will automatically cut off the electrical power supply to the
furnace when the blower panel is removed. As a safety precaution, all
electrical power and the gas supply to the furnace should be turned off
before servicing.
FURNACE USER MAINTENANCE
Before proceeding, be sure the area is well ventilated. Turn
the thermostat OFF. If the blower is runni ng, wait until it
stops automatically. Turn OFF the gas and electrical power
supplies to the furnace. Check all metal parts and surfaces
to be sure they have cooled to room temperature before
you begin.
271015-UUM-A-0407
Every time the filters are changed the following items should be visually
inspected:
• Check vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and
that there are no obvious signs of deterioration.
• Check for dirt or lint on any surfaces or on components. Do not try
to clean any of the surfaces or components. Cleaning of the furnace and its components must be done by a qualified service professional.
If, during the inspection of your furnace, you find any of the following
conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor
to check and / or clean your furnace, or for more information if you have
questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the
front panels. Turn ON the gas and electrical power supplies to the furnace, and set thermostat to the desired temperature.
Air Filters
Dirty filters greatly restrict the flow of air and may cause damage to the
moving parts of the furnace. If the filters become clogged the heat
exchangers and blower motor could overheat resulting in a potentially
dangerous situation.The filters should be checked every 3 months. On
new construction, check the filters every week for the first four weeks
and every three weeks after that, especially if the indoor fan is running
continuously. When replacing the filter(s) you must use filters that are
the same size as those recommended in Table 1. use the following procedure to determine the filter size. Never operate your furnace without a
suitable air filter.
Removing Filters
Externally Mounted Air Filters
Some installations may have the air filter in a rack attached to the casing of the furnace or placed in the return air duct. You can gain access
to the filter by pulling on the door or unscrewing the retaining screw,
then slide the filter(s) out of its channel. Replace throw away filter(s)
with the same size new filter(s). Throw away filter(s) may be replaced
with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as
described in the manufacturer instructions or as described below and
then re-installed.
To replace the filter after cleaning you must do the following:
1.Slide filter into place.
2.Snap the door on or place the door in position and tighten the
retaining screws, if provided.
3.Make sure the door is secure to the end of the filter rack.
TABLE 1:
Filter Sizes
Cabinet SizeTop Return (in)Top Return (cm)
A(2) 14 x 20(2) 35.6 x 50.8
B(2) 14 x 20(2) 35.6 x 50.8
C(2) 14 x 20(2) 35.6 x 50.8
How to Clean your Filter
High-velocity filters may be cleaned with a vacuum cleaner or washed
with a garden hose. Be sure to shake off excess water and allow filter to
completely dry before re-installing the filter.
Blower Care
Even with good filters properly in place, blower wheels and motors will
become dust laden after long months of operation. The entire blower
assembly should be inspected annually. If the motor and wheel are
heavily coated with dust, they can be brushed and cleaned with a vacuum cleaner. If the blower cannot be properly cleaned without removing
it from the furnace, then this service must be performed by a qualified
service agency.
Make sure you DO NOT move the clip on weight on the
indoor fan wheel when cleaning the wheel. This weight is
used to balance the wheel. Moving the weight will cause
the fan wheel to vibrate.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not
require periodic oiling.
SECTION II: SERVICE AND MAINTENANCE
MANUAL
SAFETY SECTION
The following safety rules must be followed when servicing the
furnace.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, and death or property damage.
• Before servicing, disconnect all electrical power to the furnace.
• When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or
qualified service contractor once a year or before the start of every
heating season. The following items must be cleaned and serviced or
replaced if there are signs of deterioration.
1.The vent terminal screen (if applicable).
2.The furnace vent and combustion air intake passageways. Should
it be necessary to service the vent/air intake system, the manufacturer recommends this service be conducted by a qualified service
agency. The operation of this appliance requires the reassembly
and resealing of the vent/air intake system.
3.The furnace burners, ignitor and flame sensor.
4Unitary Products Group
271015-UUM-A-0407
FURNACE CLEANING SECTION
NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:
1.Turn off the electrical power to the unit.
2.Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3.Remove the upper access panel and remove the burner box
cover.
4.Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
5.Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.
6.Remove burners from the burner assembly.
7.Burners may be cleaned by rinsing in hot water.
8.Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
Lower Heat Exchanger Access
1.Turn off the electrical power to the unit and turn off gas supply at
the shutoff valve.
2.Remove the blower and burner compartment access doors. Disconnect the gas supply piping at the union to permit removal of the
entire burner and gas control assembly from the vestibule panel.
Use the wrench boss on the gas valve when removing or installing
this piping. See Figure 4.
3.Unplug the igniter from the wire harness. Disconnect sensor and
rollout switch wires located on top of the air shield. Identify and
note the location of all leads for ease of reinstallation. Also disconnect the wires at the side rollout switches (upflow only) and the
gas valve wires.
4.Remove the screws holding the burner assembly to the vestibule
panel and remove this assembly. Handle the assembly carefully
since it contains the igniter, which is fragile and easily broken. T he
lower portion of the heat exchanger will now be exposed. To clean
the burner assembly, use a vacuum cleaner, or remove the burners as outlined in burner cleaning, and clean in hot water.
Upper Heat Exchanger Access
1.Perform steps 1-4 above.
2.Disconnect vent piping from the vent motor assembly at the top
panel on the furnace (upflow only). On downflow models, the vent
pipe is attached to the vent motor outlet. Remove this screw
before proceeding.
3.Unplug the vent motor wires and ground wire. Remove the pressure switch tubing at the tap on the vent motor housing.
NOTE: It is recommended that replacement gaskets be available
before removing vent motor.
4.Remove six mounting screws that hold the vent motor to the
restrictor plate. The surface is gasketed and gasket can be reused
if it is carefully removed. It is necessary to remove this assembly to
gain access to the restrictor plate mounting holes. The assembly
may be vacuumed if cleaning is necessary. If any vent assembly
parts are damaged, replace with an entire new assembly (except
for gaskets).
5.Remove the perimeter screws attaching the restrictor plate assembly to the vestibule panel. The surface is also gasketed. The
assembly, including the flue baffle plate (rear) may be vacuumed
or cleaned with hot water if necessary.
6.The upper portion of the heat exchanger is now accessible. With a
long flexible wire brush, clean inside each tube at both the top and
bottom. The brush must pass around the rear heat exchanger
tubes. Vacuum loose scale and dirt from each tube.
7.Clean - Replace all components in reverse order. Re-gasket all
surfaces which required a gasket. Reconnect all wiring. Reattach
vent pipe and gas supply lines before restoring service to furnace.
Restore electrical power, check gas supply piping for leaks, and
then verify furnace operation.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.
1.Call for 1st stage only
• On a call for 1st stage heat, the thermostat closes a circuit
between R and W1.
• The Microprocessor in the Furnace Control runs a ‘Self Check’.
• The Control checks the Primary Limit, Auxiliary Limit, and Roll-
out Switches for closed contacts.
• The Control checks that the Low Fire Pressure Switch (1LP) is
open.
• The Inducer Motor is energized on high speed, closing the con-
tacts of 1LP.
• The Control checks that 1LP is closed.
• The Igniter is energized for 17 seconds.
• The Gas Valve is energized on 1st Stage (Low Fire).
• Flame Rectification is recognized within 7 seconds.
• The Inducer is switched to low speed.
• 30 seconds after flame is proven, the ‘Heat Low’ relay is ener-
gized providing 120 Volts AC to the Blower Motor.
• At the same time, the EAC and Hum relays are energized, pro-
viding 120 Volts AC to the EAC Hot and Hum terminals.
2.Call for 2nd Stage after 1st Stage is operating
• A call for 2nd Stage can be made by a 2-Stage thermostat, or by
the W2 delay timer on the furnace control.
• The Inducer Motor is shifted to high speed by the control, closing
the contacts of 2LP (The High Fire Pressure Switch.).
• The Control checks that 2LP is closed.
• The Gas Valve is energized on 2nd Stage (High Fire).
• The Control simultaneously de-energizes the Heat Low relay
and energizes the Heat High relay, providing 120 Volts AC to a
different speed of the Blower Motor.
3.2nd Stage is satisfied, 1st Stage still calling.
• If a Single Stage Thermostat is used, the Furnace will stay on
High Fire until the thermostat is satisfied.
• When the circuit between R and W2 is opened, the Control
switches the Inducer Motor to low speed, causing the contacts of
2LP to open.
• When 2LP opens, 2nd Stage of the Gas Valve is de-energized.
• 30 seconds later, the Control switches the Blower from Heat
High to Heat Low.
4.1st Stage Satisfied
• The Thermostat opens the circuit between R and W1
• Immediately the Gas Valve is de-energized and Flame Rectifica-
tion is lost.
• The Inducer Motor is de-energized after a 15 second Post Purge
and the Hum terminal is de-energized.
• The ‘Fan Off Delay’ circuit is initiated. The Delay time can be
field set at 60, 90, 120, or 180 seconds. It comes from the factory set at 60 seconds.
• The Heat Low terminal is de-energized; stopping the Blower and
the EAC terminal is de-energized.
Unitary Products Group5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.