York K4EU120A50A, K5EU090A50A User Manual

Page 1
®
CAUTION
THE ENCLOSED INST ALL ATION INSTRUCT I ONS AND ANY APPL ICABLE
LOCAL, STA T E , AND NAT IONAL CODES INCLUDING, BUT NOT LI MITED
TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH
WARNING
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAM AGE.
I NCORRECT INSTAL LATION MAY CREATE A CONDITION WHERE THE
SUNLINE™ SPLIT-SYSTEM
EVAPORATOR BLOWERS
(AIR COOLED)
INSTALLATION INSTRUCTION
MODELS K5EU090A50A & K4EU120A50A
Supersedes: Nothing 550.39-N4YI (894)
035-12122
(WORLD 50 HZ)
GENERAL
These completely assembled blower units are manufac­tured under ISO 9002 Quality System Certification and include a well-insulated cabinet, a DX cooling coil with copper tubes and aluminum fins, an expansion valve, a distributor, throwaway filters, a centrifugal blower, a blower motor, a blower motor contactor, an adjustable belt drive and a small holding charge of Refrigerant-22. Blower motors and adjustable drives are factory­installed on all units.
The units are shipped in the vertical position with a vertical air discharge. The blower section can be repositioned as shown in Figure1 for horizontal applications.
REFERENCE
Additional information for the accessories on this equip ment is available in the following instructions:
Electric Heater - 550.13-N10.1V
Supply Air Plenum - 550.13-N10.2V
Return Air Grille - 550.13-N10.3V
Base - 550.13-N10.4V
Installer should pay particular attention to the words: NOTE, CAU TION and WARNING. Notes stallation easier. Cautions
are intended to clarify or make the in
are given to prevent equipment damage. Warnings are given to alert installer that personal injury
Hot Water & Steam Coil - 550.13-N10.7V
Renewal Parts:
Refer to Parts Manual for complete listing of replacement parts on this equipment.
All forms may be ordered from:
Publications Distribution Center Unitary Products Group P.O. Box 1592, York, PA 17405
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's de livery receipt. A separate request for inspection by the
-
-
-
-
Page 2
550.39-N4YI
TABLE OF CONTENTS
General
Reference
Inspection
Nomenclature
................................................................................
............................................................................
............................................................................
......................................................................
INSTALLATION
Limitations
Location
Clearances
Rigging and Handling
Vertical/horizontal Installation
Duct Connections
Refrigerant Mains
Drain Connection
Supply Air Blower Adjustment
Power and Control Wiring
...........................................................................
...............................................................................
..........................................................................
..........................................................
..............................................
................................................................
................................................................
.................................................................
.............................................
..................................................
11
MAINTENANCE
Filters.................................................................................12
Evaporator Coil..................................................................12
Lubrication.........................................................................12
Drain Pan ..........................................................................12
Belts...................................................................................12
1
1
1
2
No.
1 Unit Application Data
2 Physical Data
3 Supply Air Blower Motor Pulley Adjustment
3
3
4
4
4 Blower Performance
5 Accessory Static Resistance (IWG/pA)
6 Electrical Data
7 Blower Motor and Drive Data
4
4
5
6
6
No.
1 Unit Suspension Mounting (Horizontal)
2 Vertical and Horizontal Appplication
3 Supply Air Duct Connection
4 Electric Heater Accessory
TABLES
Description Page
............................................
.......................................................
.........
.............................................
................
......................................................
...............................
FIGURES
Description Page
................
.....................
.................................
....................................
3
5
7
8
9
9
11
3
4
4
4
5 Recommended Drain Piping ................................ 6
6 Typical Motor Mounting Assembly ....................... 7
7 Pressure Drop Across Dry Coil vs Supply Air ...... 7
8 Hole Locations (Pressure Drop Readings)........... 7
9 Unit Dimensions and Clearances.........................10
10 Typical Field Wiring (Cooling only).......................11
PRODUCT NOMENCLATURE
K 4 E U 5 02 A
PRODUCT CATEGORY
= Split-System Evaporator Blowerwith
Motor and Drive
PRODUCT GENERATION
4,5 = Design Level
PRODUCT IDENTIFIER
EU = Evaporator Blower Unit
2 Unitary Products Group
1 0
NOMINAL COOLING
CAPACITY
090 = 90 Mbh (26.36kW) 120 = 120 Mbh (35.13kW)
VOLTAGE CODE
50 = 380/415-3-50
FACTORY INSTALLED HEAT
A = Not Applicable
Page 3
INSTALLATION
carrier's agent should be made in writing. See Local Dis tributor for additional information.
LIMITATIONS
These units must be installed in accordance with applicable na tional, local and municipal safety codes.
LOCATION
These blower units are not designed for outdoor installation. They must be locatedwithin the building structure, either inside or outside the conditioned space.
These Evaporator Blower sections allow for vertical or horizon tal installation in any area offering proper electrical supply, duct
TABLE 1 - UNIT APPLICATION DATA
They may be installed either with ductwork ormatching plenum
-
and inlet grille. The unit should be located as close to the condensing unit as
practical and positioned to minimize bends in the refrigerant piping.
­Units being installed vertically or horizontally can be set directly
on a floor or platform, or they can be supported by metal or wooden beams.
­Units being installed horizontally can be suspended from
above. Four frame to accommodate hanger rods. Knockouts must be re
3
" (9.5mm) weld nuts are provided in the unit
8
moved from the unit panels to expose these weld nuts. Refer to Figure 1 for their location and the individual load on each hanger rod.
WARNING: Be careful when attaching the hanger rods. They
-
must not be allowed to turn or slip.
550.39-N4YI
-
MODEL
KEU090 380/415-3-50 342 457 2400 / 1.3 3600 / 1.7 68/57(20/14) 95/72(18/22) 40(4.4) 77(25)
KEU120 380/415-3-50 342 457 3200 / 1.5 4800 / 2.3 65/57(20/14) 95/72(18/22) 40(4.4) 77(25)
* Utilization Range “A” in accordance with ARI Standard 110.
Power Supply
Voltage
Variation*
Min. Max. Min. Max. Min. Max. Min. Max.
Supply Air Range
CFM/m
3
/s
Entering Air Temperature, °F(°C)
Cooling-db/wb Heating-db
and drain connections.
(66.7).
44-7/8 (1140)
(1251) 49-1/4
(35)
1-3/8
(25.7)
Model
KEU090 26
KEU120 26
Center of Gravity
Dimensions, (In./mm)
A B W1 W2 W3 W4 TOTAL
1
/ 667 23
4
5
/ 676 24
8
3
/ 603 85 /38.5 93 / 42.2 70 / 32 77 / 34.9 325 / 147.4
4
1
/ 613 85 /38.5 93 / 42.2 70 / 32 80 / 36.2 330 / 149.7
8
Weight Distribution
(lbs/kg)
FIG. 1 - UNIT SUSPENSION MOUNTING (Horizontal)
Unitary Products Group 3
Page 4
550.39-N4YI
CLEARANCES
The clearances listed on the unit dimension drawing (Figure 9) are required for the proper service and opera tion of the unit.
RIGGING AND HANDLING
Be careful when moving the unit. Do not remove any packaging until the unit is near its final location.
The packaging consists of a bottom wooden skid that can be lifted with a fork truck from any direction, a card board container that covers the entire unit, and strapping that secures the cardboard container to the bottom of the skid.
These units can be rigged with slings under the bottom skid.
-
-
from crushing the unit panels and frame.
Before rigging any unit, determine its weight from Ta ble 2. Before rigging a unit for horizontal installation, make sure that its weight will be distributed equally.
VERTICAL/HORIZONTAL INSTALLATION
The unit is shipped for vertical installation with a vertical air discharge as shownin Figure 2, but maybe converted for horizontal installation as shown in Figure 2 by inter­changing the solid bottom panel and the return air duct flange.
DUCT CONNECTIONS
All ducts should be designed and installed in accordance with applicable national and/or local codes.
Refer to Figure 3 for suggested method of connecting supply air ductwork.
-
FIG. 3 - SUPPLY AIR DUCT CONNECTION
Ducts should be sized no smaller than the duct flanges on the unit or the accessory electric heater (if used). Ref er to the unit dimensions (Figure 1) and the heater detail (Figure 4) for these sizes.
Use flexible fiber glass or plastic cloth collars or other non-flammable material at the unit duct connections to minimize the transmission of noise and vibration.
Insulate all ductwork running through unconditioned ar­eas to prevent moisture condensation and to provide more economical operation.
The return air duct flange is factory-mounted on the front of the unit, but it can be reversed with the solid bottom panel for hori zontal applications. When the return air grille is used, the duct connection frame is not used.
NOTE: If return air duct is not used, applicable lnstalltion
The field installed air plenum and return air grille accessories should be used in place of ductwork only when a free blow/free return application is practical.
codes may limit the unit to installation only in a single story residence.
-
-
(489)
(565)
FIG. 2 - VERTICAL AND HORIZONTAL APPLICATION
4 Unitary Products Group
FIG. 4 - ELECTRIC HEATER ACCESSORY
(25)
Page 5
550.39-N4YI
Table 2 - PHYSICAL DATA
Model KEU090 KEU120 Rows Deep 3 3 Rows High 27 32
Evaporator Coil
Centrifugal Blower Wheel Dia. x Width
Blower Motor* Nominal Rating (HP/kW) 1
Filters (4 Req'd)
Weight (Lbs,/kg) Operating 325 / 147 330 / 150
Accessory Weights(Lbs/kg)
*All of these 1450 RPMmotors havea solid base, a 56 frame,inherent protection and permanently lubricated ballbearings. Refer to Table 7 for additional motor anddrive
data.
NOTE: Refer to the appropriate condensing unit installation instruction for charging data.
Finned Length (in./mm) 46 / 1168 46 / 1168 Fin/Inch 13 13 Tube O.D. (in./mm) Face Area (Ft
Size
Face Area (Ft.
Electric Heaters
Supply Air Plenum 102 / 46 102 / 46 Base 60 / 27 60 / 27 Return Air Grille 15 / 6.8 15 / 6.8 Hot Water Coil 105 / 48 117 / 53
.2/m2
) 8.6 / 0.80 10.2 / 0.95
inches 15 x15 15 x 15
mm 381 x 381 381 x 381
inches 16 x 25 x 1 16 x 25 x 1
2/m2
) 11.1 / 1.03 11.1 / 1.03
mm 406 x 635 x 25 406 x 635 x 25
10 kW 63 / 28.6 63 / 28.6 16kW 66 / 30 66 / 30 26kW 71/32 71/32 36 kW 74 / 33.6 74 / 33.6
3
/ 9.5
8
1
/ 1.12 2 / 1.5
2
3
8
/ 9.5
REFRIGERANT MAINS
Many service problems can be avoided by taking adequate pre­cautions to provide an internally clean and dry system, and by us­ing procedures and materials that conform with established standards.
Hard drawn copper tubing should be used where no apprecia ble amount of bending around pipes or other obstructions in necessary. Use long radius ells wherever possible. If soft cop per is used, care should be taken to avoid sharp bends which may cause a restriction.
Pack fiber glass insulation and a sealing material such as Per magum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility.
Support all refrigerant lines at minimum intervals (8 ft./2.4m) with suitable hangers, brackets or clamps.
Braze all copper to copper joints witH Sil-Fos 5 or equivalent brazing material. Do not use soft solder.
Never braze or solder liquid and suction lines together. The complete suction line should be insulated with no less the
1
If it is desirable to tape or wire the liquid and suction lines to gether for support purposes, they must be completely insulated from each other.
INSTALLING REFRIGERANT MAINS
The units are evacuated and dehydrated at the factory and shipped with a holding charge (1 lb./2.2kg) of Refrigerant-22. The suction and liquid connections are sealed with copper disks.
WARNING: Provisions for recovering refrigerant releases
must be available during all phases of installation, leak testing and charging. Do NOT release refrig­erant into theatmosphere. ASchrader valve is pro­vided for refrigerant recovery.
If the unit has already lost its holding charge, it should be leak
­tested and the necessary repairs should be made. If the unit has maintained its holding charge, you can assume that it has
­no leaks and proceed with the installation.
Make sure the refrigerant in the lines has been recovered, then drill a small hole through the discs to prevent any internal pres
­sure from blowing them off and to allow the flow of dry nitrogen through the connections when unbrazing the closures.
NOTE: To minimize the possibility of system failure due to dirt
and moisture, a filter-drier must be installed in each liquid line as close to the evaporator as possible. Filter-driers are not supplied with theevaporator blow ers. They are supplied with the matching condensing
"
2
sections.
The temperature required to make or break a brazed joint is sufficiently high to cause oxidation of the copper
-
unless an inert atmosphere is provide.
CAUTION: Dry nitrogen should flow through a brazed joint at
all times when heat is being applied and until the joint has cooled.
The liquid, suction and drain connections inside the unit must be piped to the outside. Refer to Unit Dimensions for locations and dimensions of these connection.
-
-
Unitary Products Group 5
Page 6
550.39-N4YI
Before brazing the refrigerantlines tothese connections, remove the short panel from the unit frame and slide it (along with the grommets) onto the refrigerant lines. Af ter the brazed joints have cooled, slide the panel back into place and secure it to the unit frame.
NOTE: These units can only be piped from one side of
the unit.
EXPANSION VALVE BULB
On KEU090 units the expansion valve bulb must be fas tened in a 4o'clock positionto thesuction lineoutside the cabinet after the piping connections have been made.
On KEU120 units fasten the expansion valve bulb on the suction header 8" (203mm) below the top of the header and adjacent to the coil.
Use the clamps provided with the valve to secure the bulb in position.
DRAIN CONNECTION
The drain line MUST be trapped because the coil is lo cated on the negative side of the supply air blower. It must also be protected from freezing temperatures.
7
A
" (22.2mm) OD stub connection is provided within
8
the cabinet on both ends of the condensate drain pan for either left hand or right hand piping connections. Refer to Figure 5 for recommended drain piping.
The drain line is located on the same end of the coil sec­tion as the refrigerant connections. The line should be in­sulated where moisture drippage will be objectionable or cause damage to the area. Seal the unused drain con­nection with a suitable mastic.
NOTE: Refer to Figure 9 for minimum clearance require
ments.
-
SUPPLY AIR BLOWER ADJUSTMENT
The RPM of the supply air blower will depend on the re quired airflow, the unit accessories and the static resis tances of both the supply and the return air duct systems. With this information, the RPM for the supply air blower can be determined from the blower perform ance in Table 4.
-
Knowing the required blower RPM and the blower motor HP, the setting (turns open) for the supply air motor pulley can be determined from Table 3.
Each motor pulley has:
1. A threaded barrel with two flats (or notched recesses) 180 degrees apart.
2. A movable flange with one set screw.
After the movable flange has been rotated to the proper number of “turns open”, the set screw should be tight ened against the flat on the barrel to lock the movable
­flange in place. If the pulley includes a locking collar, the
locking collar must be loosened to adjust the setting of the movable flange.
Note the following:
1. The supply airflow must be within the limitations shown in Table 1.
2. All pulleys can be adjusted in half-turn increments.
3. The tension on the belt should be adjusted for a deflection
3
of
" (5mm) per foot (305mm) of belt span with an applied
16
force of approximately 3 lbs (1.4kg). This adjustment is made by moving the blower motor mounting plate. Refer to Figure 6. Turning the adjustment bolt (B) moves the motor mounting plate up or down. Note - Never loosen the two nuts (C). Four hex nuts (A) have to be loosed to move the mounting plate and retightened after the mounting plate has been moved to the proper position.
-
-
-
-
-
4. All pulleys are factory aligned.
5. All supply air motor pulleys are factory set at three “turns
(76)
open.”
After the supply air blower motor is operating, adjust the
(64)
resistances in both the supply and the return duct sys tems to balance the air distribution throughout the condi tioned space. The job specifications may require that this balancing be done by someone otherthan theequip ment installer.
FIG. 5 - RECOMMENDED DRAIN PIPING
The 3" (76mm) dimension must equal or exceed the negative static pressure developed by the supply air blower. If it does not, condensate will not drain properly and may overflow the drainpan. The trap mustbe atleast
1
2
" (63mm) deep to maintain a water seal under all oper
2
ating conditions, especially during blower start-up.
6 Unitary Products Group
To check the supply air airflow after the the initial balancing has been completed:
1. Drill two holes Figure 8.
2. Insert at least 8" (200mm) of
-
each of these holes for sufficient penetration into the air flow on both sides of the evaporator coil.
NOTE: The tubes must be inserted and held in a position per
pendicular to the air flow so that velocity pressure will not affect the static pressure reading.
5
" (8mm) dia. in the side panel as shown in
16
1
" (6.3mm) O.D. tubing into
4
-
-
-
-
Page 7
3. Using an inclined manometer, determine the pressure drop across a dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inac curate. To assure a dry coil, the refrigerant system should be de-energized while the test is being run.
After readings have been obtained, remove the tubes and seal up the drilled holes in the side panel with plugs (P/N 029-13880) available through normal parts ordering procedure.
-
5
" (8mm) dia. dot
16
550.39-N4YI
4. Knowing the pressure drop across a dry coil, the actual air flow through the unit can be determined from the curve in Figure 7.
If the airflow is above or below the specified valve, the supply air motor pulley may have to be readjusted. After one hour of operation, check the belt and pulleys for tightness and align ment.
WARNING: Failure to properly adjust the total system air quan
tity can result in extensive blower damage.
TABLE 3 - SUPPLY AIR BLOWER MOTOR PULLEY
ADJUSTMENT
BLOWER DRIVE RANGE (RPM)
TURNS OPEN*
5 650 700 4 690 740 3 730 780 2 770 830 1 810 870 0 850 910
* Pulleys can be adjusted in half-turn increments.
KEU090 KEU120
650 -850 700 - 910
-
-
-
FIG. 7 - PRESSURE DROP ACROSS A DRY
EVAPORATOR COIL VS SUPPLY AIR CFM
DIMENSIONS (in./mm)
ABCD
3/76 3/76 14/356 12/305
NOTE: DE-ENERGIZE THE REFRIGERANT SYSTEM BEF
ORE TAKING ANY TEST MEASUREMENTS TO AS SURE A DRY EVAPORATOR COIL.
FIG. 8 - HOLE LOCATIONS
FIG 6 - TYPICAL MOTOR MOUNTING ASSEMBLY
Unitary Products Group 7
(PRESSURE DROP READINGS)
-
-
Page 8
550.39-N4YI
TABLE 4 - BLOWER PERFORMANCE
1
KEU090 - SUPPLY AIR BLOWER PERFORMANCE
BLOWER
SPEED
RPM
ESP
(IWG)
2
OUTPUT
(BHP)
INPUT
(kW)
ESP
(IWG)
2
OUTPUT
(BHP)
- (CFM)
INPUT
(KW)
ESP2 (IWG)
AIRFLOW
OUTPUT
(BHP)
INPUT
(kW)
ESP
(IWG)
2
OUTPUT
(BHP)
INPUT
(kW)
ESP
(IWG)
2
OUTPUT
(BHP)
INPUT
(kW
2400 CFM 2700 CFM 3000 CFM 3300 CFM 3600CFM 600 0.35 0.62 0.59 0.26 0.70 0.66 0.13 0.78 0.73 -----­655 0.49 0.70 0.66 0.41 0.78 0.72 0.30 0.87 0.82 0.07 0.96 0.90 - - ­700 0.60 0.77 0.73 053 0.85 0.80 043 0.95 0.89 0.29 1.06 0.99 0.12 1.17 1.09 800 0.92 0.97 0.90 0.85 1.06 0.99 0.77 1.18 1.10 0.65 1.30 1.21 0.49 1.42 1.32 880 1.18 1.11 1.04 1.11 1.24 1.16 1.03 1.37 1.28 0.91 1.50 1.38 0.77 1.64 1.53 900 1.24 1.15 1.07 1.18 1.28 1.19 1.10 1.42 1.32 0.98 1.55 1.43 0.84- 1.70 1.57
1000 1.58 1.35 1.26 1.53 1.48 1.38 1.46 1.63 1.48 1.37 1.81 1.65 1.24 2.02 1.85
OUTPUT
(kW)
1
-(m3/s)
INPUT
(kW)
ESP
(Pa)
AIRFLOW
2
OUTPUT
(kW)
INPUT
(kW)
ESP
(Pa)
2
OUTPUT
(kW)
INPUT
(kW)
ESP
(Pa)
2
OUTPUT
(kW)
INPUT
(kW)
KEU090 - SUPPLY AIR BLOWER PERFORMANCE
BLOWER
SPEED
RPM
ESP
(Pa)
2
OUTPUT
1.1 m
INPUT
(kW)
(kW)
3
/s 1.3 m3/s 1.4 m3/s 1.6 m3/s 1.7 m3/s
ESP
(Pa)
2
600 87 0.46 0.59 64 0.52 0.66 32 0.45 0.73 -----­655 122 0.52 0.66 102 0.58 0.72 74 0.65 0.82 17 0.72 0.90 - - ­700 149 0.57 0.73 131 0.63 0.80 107 0.71 0.89 72 0.79 0.99 30 0.87 1.09 800 228 0.72 0.90 211 0.79 0.99 191 0.88 1.10 161 0.97 1.21 122 1.06 1.32 880 293 0.83 1.04 275 0.92 1.16 255 1.02 1.28 226 1.12 1.38 191 1.22 1.53 900 308 0.86 1.07 293 0.95 1.19 273 1.06 1.32 243 1.15 1.43 208 1.27 1.57
1000 392 1.01 1.26 379 1.10 1.38 362 1.21 1.48 340 1.35 1.65 308 1.50 1.85
KEU120- SUPPLY AIR BLOWER PERFORMANCE1(CFM)
BLOWE
R
SPEED
RPM
ESP
(IWG)
2
OUTPUT
(BHP)
INPUT
(kW)
ESP
(IWG)
2
OUTPUT
(BHP)
INPUT
(kW)
3200 3600 4000 4400 4800
ESP
(IWG)
AIRFLOW
2
OUTPUT
(BHP)
INPUT
(kW)
ESP
(IWG)
2
OUTPUT
(BHP)
INPUT
(kW)
ESP
(IWG)
2
OUTPUT
(BHP)
INPUT
(kW)
700 0.49 1.01 0.94 0.34 1.17 1.09 0.14 1.33 1.24 -----­800 0.84 1.25 1.16 0.71 1.42 1.32 0.53 1.60 1.48 0.30 1.80 1.64 - - ­900 1.18 1.48 1.38 1.06 1.70 1.57 0.91 1.92 1.75 0.70 2.18 1.99 0.43 2.45 2.24 950 1.37 1.61 1.50 1.26 1.86 1.71 1.11 2.12 1.95 0.90 2.39 2.18 0.65 2.67 2.44
1000 1.56 1.75 1.62 1.46 2.02 1.85 1.32 2.30 2.10 1.13 2.60 2.38 0.87 2.90 2.65
(kW)
1(m3
INPUT
(kW)
/s)
ESP
(Pa)
AIRFLOW
2
OUTPUT
(kW)
INPUT
(kW)
ESP
(Pa)
2
OUTPUT
(kW)
INPUT
(kW)
ESP
(Pa)
2
OUTPUT
(kW)
INPUT
(kW)
KEU120 - SUPPPLY AIR BLOWER PERFORMANCE
BLOWE
R
SPEED
RPM
ESP
(Pa)
2
OUTPUT
1.5 m
INPUT
(kW)
(kW)
3
/s 1.7m3/s 1.9 m3/s 2.0 m3/s 2.3 m3/s
ESP
(Pa)
2
OUTPUT
700 122 0.75 0.94 84 0.87 1.09 35 0.99 1.24 -----­800 208 0.93 1.16 176 1.05 1.32 131 1.19 1.48 74 1034 1.64 - - ­900 293 1.10 1.38 263 1.27 1.57 226 1.43 1.75 174 1.62 1.99 107 1.83 2.24 950 340 1.20 1.50 312 1.39 1.71 275 1.58 1.95 223 1.78 2.18 161 1.99 2.44
1000 387 1.30 1.62 362 1.50 1.85 327 1.71 2.10 280 1.94 2.38 216 2.16 2.65
1
Unit resistance is based on a wet evaporator coil and clean filters.
2
Available static pressure in IWG (Pa) to overcome the resistance of the duct system and any accessories added to the unit. Refer to Table 6 for the resistance of these
accessories and to Table 7 for additional motor and drive data
NOTE: Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device.
LEGEND:
RPM range for the standard factory-mounted drive com ponents.
­Exceeds the BHP limitation of the standard
factory-mounted blower motor
8 Unitary Products Group
Page 9
TABLE 5 - ACCESSORY STATIC RESISTANCE (IWG)
KEU090
ACCESSORY
BLOWER CFM/m
10k W 0.01 / 2.5 0.01 / 2.5 0.01/ 2.5 0.02 / 5.0 0.02/ 5.0
Electric
Heat
16 kW 0.01 / 2.5 0.02 / 5.0 0.02 / 5.0 0.03 / 7.4 0.04/ 10.0
26 kW 0.03 / 7.4 0.4/ 10.0 0.05 / 12.4 0.06/ 15.0 0.07 / 17.4
36 kW 0.05 / 12.4 0.07 / 17.4 0.08 / 20.0 0.10 / 25.0 0.11 / 27.0
Supply Air Plenum 0.03 / 7.4 0.03 / 7.4 0.04 / 10.0 0.05 / 12.4 0.06 / 15.0
Return Air Grille 0.02 / 5.0 0.03 / 7.4 0.04 / 10.0 0.05 / 12.4 0.06 / 15.0
Add these pressures to the ESP values in the respective blower performance table.
EXTERNAL STATIC PRESSURE DROP RESISTANCE
3
/s 2400 / 1.1 2700 / 1.3 3000 / 1.4 3300 / 1.6 3600 / 1.7
KEU120
550.39-N4YI
IWG/pA
ACCESSORY
BLOWER CFM/m
EXTERNAL STATIC PRESSURE DROP RESISTANCE
IWG/pA
3
/s 3200 / 1.5 3600 / 1.7 4000 / 1.9 4400 / 2.1 4800 / 2.3
10 kW 0.02 / 5.0 0.02 / 5.0 0.03 / 7.4 0.03 / 7.4 0.04 / 10.0
Electric
Heat
16 kW 0.03 / 7.4 0.04 / 10.0 0.05 / 12.4 0.06 / 15.0 0.07 / 17.4
26 kW 0.06 / 15.0 0.07 / 17.4 0.09 / 22.3 0.11 / 27.0 0.13 / 32.2
36 kW 0.09 / 22.3 0.11 / 27.0 0.14 / 35.0 0.17 / 42.2 0.20 / 50.0
Supply Air Plenum 0.05 / 12.4 0.06 / 15.0 0.07 / 17.4 0.08 / 20.0 0.10 / 25.0
Return Air Grille 0.05 / 12.4 0.06 / 15.0 0.07 / 17.4 0.08 / 20.0 0.10 / 25.0
Add these pressures to the ESP values in the respective blower performance table.
TABLE 6 - ELECTRICAL DATA
Model
KEU090 1
Blower Motor
HP/kW
1
/1.1 380/415-3-50 3.7 5 650 / 197
2
Power Supply FLA
KEU120 2 / 1.5 380/415-3-50 4.5 5 500 / 152
* Dual element, time delay fuses.
** Based on three 60° C, 14 AWG, insulated copper conductors in steel conduit and a 3% voltage drop.
Maximum
Fuse Size* Amps
Maximum
Wire Length* * Ft.(m)
Unitary Products Group 9
Page 10
550.39-N4YI
ACCESSORIES
•ELECTRIC HEATER Add 15" (381mm) to Unit Height when using 10, 16, 26 or 36kW Heater
•SUPPLY AIR PLENUM Add 27" (686mm) to Unit Height when used
•BASE Add 24" (610mm) to Unit Height when used
MINIMUM CLEARANCES (in./mm)
Side with RETURN AIR opening - 24 / 610 Side with SUPPLY AIR opening - 24 / 610 Side with PIPING CONNECTIONS - 61 / 1549 Side opposite PIPING CONNECTIONS - 26 / 66 Bottom -
!
"
FIG 9 - UNIT DIMENSIONS AND CLEARANCES
Overall dimension of the unit will vary if an electric heater, a supply
air plenum or a base is used.
This dimension is required for removal of the DX coil. Only 26" is required for normal servicing.
!
If the DX coil has to be removed, this dimension is required to loosen screws that secure the coil to the unit frame. This dimension will also be required for blower motor access if the piping connections are made on the opposite side of the unit.
"
Allow enough clearance to trap the condensate drain line.
All dimensions are in millimeters and inches. They are subject to change without notice. Certified dimensions will be provided upon request.
10 Unitary Products Group
Page 11
TABLE 7 - BLOWER MOTOR AND DRIVE DATA
Model
KEU090
Motor
(HP/kW)*
1
1
/ 1.1
2
Blower Range
(RPM)
650/850
KEU120 2 / 1.5 700/910
*All motorsare 1450 RPMand have a56 frame, inherentprotection and permanently lubricated ball bearingsThe motorshave a solidbase and a1.15 serv ice factor. All 3-phase motors are wired for 380/415V power supply.
Adjustable Motor Pulley Fixed Blower Pulley Belt
Pitch Dia
(In./mm)
3.4 - 4.4 / 86-112
3.4 - 4.4 / 86-112
Bore
(In./mm)
7
/ 22.2
8
7
/ 22.2
8
Pich Dia.
(In./mm)
Bore
(In./mm)
Designa
tion
-
7.5 / 190 1 / 25 A37 38.3 / 973
7.0 / 178 1 / 25 A37 38.3 / 973
Pitch Lg.
(In./mm)
550.39-N4YI
MOTOR SPECIFICA
TIONS
•1450 RPM
•380/415-3-50
•Solid base
•56 Frame
•Inherently protected
Permanently lubricated
ball bearings
-
-
POWER AND CONTROL WIRING
Install electrical wiring in accordance with applicable national, local and municipal codes. The unit should be grounded in ac cordance with these codes.
Remove the 1 Route the power wiring conduit through this opening. Connect the conduit to the required field-supplied fitting and the power wiring to blower motor contactor 10M in unit control box.
3
" (35mm) knockout from the unit rear panel.
8
4 - WIRE
CONTROL WIRING
Route the low voltage control wiring through the hole (with bushing) in the units rear panel. Add
­duit fitting to the control wiring through thisopening and connect them to the ter
7
" (22.2mm) hole in the unit control box, route
8
minals on block 4TB. Refer to Table 6 to size the disconnect switch, the power wiring
and the fuses. Refer to Figure 10 for typical field wiring.
NOTE: Three phase motor rotation may be incorrect when the
unit is first started up. Reverse phase (leads L1 and L2) at contactor to obtain the correct rotation.
LUG ON NEUTRAL TERMI­NAL BLOCK
1
" (25mm) con
2
7
" (22.2mm)
8
-
-
TERMINALS ON 1-STAGE COOLING THERMOSTAT 2TH0870124
TERMINALS ON BLOCK 3TB OF THE BLOWER UNIT
FIG. 10 - TYPICAL FIELD WIRING (Cooling only)
Unitary Products Group 11
Page 12
MAINTENANCE
FILTERS — The filters must bereplaced as oftenas necessary
to assure good air flow and filtering action.
Refer to the unit dimension detail (Figure 9) for the location of the filter access panel.
EVAPORATOR COIL — Do not allow dirt to accumulate on the evaporator coil or other parts of the evaporator air circuit.Clean as often as necessary to assure good system performance. Use a brush, vacuum cleaner attachment or other suitable means.
LUBRICATION — The bearings for the blower shaft and the blower motors are permanently lubricated and should not require additional lubricant.
DRAIN PAN — The drain pan should be inspected regu larly to assure proper drainage.
BELTS — Maintain belt tension to extend belt life. Re place when signs of failure begin to appear.
-
-
Unitary Products Group P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in U.S.A Copyright © by York International Corporation 1994. All Rights Reserved.
550.39-N4YI
Loading...