York K4EU120A50A, K5EU090A50A User Manual

®
CAUTION
THE ENCLOSED INST ALL ATION INSTRUCT I ONS AND ANY APPL ICABLE
LOCAL, STA T E , AND NAT IONAL CODES INCLUDING, BUT NOT LI MITED
TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH
WARNING
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAM AGE.
I NCORRECT INSTAL LATION MAY CREATE A CONDITION WHERE THE
SUNLINE™ SPLIT-SYSTEM
EVAPORATOR BLOWERS
(AIR COOLED)
INSTALLATION INSTRUCTION
MODELS K5EU090A50A & K4EU120A50A
Supersedes: Nothing 550.39-N4YI (894)
035-12122
(WORLD 50 HZ)
GENERAL
These completely assembled blower units are manufac­tured under ISO 9002 Quality System Certification and include a well-insulated cabinet, a DX cooling coil with copper tubes and aluminum fins, an expansion valve, a distributor, throwaway filters, a centrifugal blower, a blower motor, a blower motor contactor, an adjustable belt drive and a small holding charge of Refrigerant-22. Blower motors and adjustable drives are factory­installed on all units.
The units are shipped in the vertical position with a vertical air discharge. The blower section can be repositioned as shown in Figure1 for horizontal applications.
REFERENCE
Additional information for the accessories on this equip ment is available in the following instructions:
Electric Heater - 550.13-N10.1V
Supply Air Plenum - 550.13-N10.2V
Return Air Grille - 550.13-N10.3V
Base - 550.13-N10.4V
Installer should pay particular attention to the words: NOTE, CAU TION and WARNING. Notes stallation easier. Cautions
are intended to clarify or make the in
are given to prevent equipment damage. Warnings are given to alert installer that personal injury
Hot Water & Steam Coil - 550.13-N10.7V
Renewal Parts:
Refer to Parts Manual for complete listing of replacement parts on this equipment.
All forms may be ordered from:
Publications Distribution Center Unitary Products Group P.O. Box 1592, York, PA 17405
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's de livery receipt. A separate request for inspection by the
-
-
-
-
550.39-N4YI
TABLE OF CONTENTS
General
Reference
Inspection
Nomenclature
................................................................................
............................................................................
............................................................................
......................................................................
INSTALLATION
Limitations
Location
Clearances
Rigging and Handling
Vertical/horizontal Installation
Duct Connections
Refrigerant Mains
Drain Connection
Supply Air Blower Adjustment
Power and Control Wiring
...........................................................................
...............................................................................
..........................................................................
..........................................................
..............................................
................................................................
................................................................
.................................................................
.............................................
..................................................
11
MAINTENANCE
Filters.................................................................................12
Evaporator Coil..................................................................12
Lubrication.........................................................................12
Drain Pan ..........................................................................12
Belts...................................................................................12
1
1
1
2
No.
1 Unit Application Data
2 Physical Data
3 Supply Air Blower Motor Pulley Adjustment
3
3
4
4
4 Blower Performance
5 Accessory Static Resistance (IWG/pA)
6 Electrical Data
7 Blower Motor and Drive Data
4
4
5
6
6
No.
1 Unit Suspension Mounting (Horizontal)
2 Vertical and Horizontal Appplication
3 Supply Air Duct Connection
4 Electric Heater Accessory
TABLES
Description Page
............................................
.......................................................
.........
.............................................
................
......................................................
...............................
FIGURES
Description Page
................
.....................
.................................
....................................
3
5
7
8
9
9
11
3
4
4
4
5 Recommended Drain Piping ................................ 6
6 Typical Motor Mounting Assembly ....................... 7
7 Pressure Drop Across Dry Coil vs Supply Air ...... 7
8 Hole Locations (Pressure Drop Readings)........... 7
9 Unit Dimensions and Clearances.........................10
10 Typical Field Wiring (Cooling only).......................11
PRODUCT NOMENCLATURE
K 4 E U 5 02 A
PRODUCT CATEGORY
= Split-System Evaporator Blowerwith
Motor and Drive
PRODUCT GENERATION
4,5 = Design Level
PRODUCT IDENTIFIER
EU = Evaporator Blower Unit
2 Unitary Products Group
1 0
NOMINAL COOLING
CAPACITY
090 = 90 Mbh (26.36kW) 120 = 120 Mbh (35.13kW)
VOLTAGE CODE
50 = 380/415-3-50
FACTORY INSTALLED HEAT
A = Not Applicable
INSTALLATION
carrier's agent should be made in writing. See Local Dis tributor for additional information.
LIMITATIONS
These units must be installed in accordance with applicable na tional, local and municipal safety codes.
LOCATION
These blower units are not designed for outdoor installation. They must be locatedwithin the building structure, either inside or outside the conditioned space.
These Evaporator Blower sections allow for vertical or horizon tal installation in any area offering proper electrical supply, duct
TABLE 1 - UNIT APPLICATION DATA
They may be installed either with ductwork ormatching plenum
-
and inlet grille. The unit should be located as close to the condensing unit as
practical and positioned to minimize bends in the refrigerant piping.
­Units being installed vertically or horizontally can be set directly
on a floor or platform, or they can be supported by metal or wooden beams.
­Units being installed horizontally can be suspended from
above. Four frame to accommodate hanger rods. Knockouts must be re
3
" (9.5mm) weld nuts are provided in the unit
8
moved from the unit panels to expose these weld nuts. Refer to Figure 1 for their location and the individual load on each hanger rod.
WARNING: Be careful when attaching the hanger rods. They
-
must not be allowed to turn or slip.
550.39-N4YI
-
MODEL
KEU090 380/415-3-50 342 457 2400 / 1.3 3600 / 1.7 68/57(20/14) 95/72(18/22) 40(4.4) 77(25)
KEU120 380/415-3-50 342 457 3200 / 1.5 4800 / 2.3 65/57(20/14) 95/72(18/22) 40(4.4) 77(25)
* Utilization Range “A” in accordance with ARI Standard 110.
Power Supply
Voltage
Variation*
Min. Max. Min. Max. Min. Max. Min. Max.
Supply Air Range
CFM/m
3
/s
Entering Air Temperature, °F(°C)
Cooling-db/wb Heating-db
and drain connections.
(66.7).
44-7/8 (1140)
(1251) 49-1/4
(35)
1-3/8
(25.7)
Model
KEU090 26
KEU120 26
Center of Gravity
Dimensions, (In./mm)
A B W1 W2 W3 W4 TOTAL
1
/ 667 23
4
5
/ 676 24
8
3
/ 603 85 /38.5 93 / 42.2 70 / 32 77 / 34.9 325 / 147.4
4
1
/ 613 85 /38.5 93 / 42.2 70 / 32 80 / 36.2 330 / 149.7
8
Weight Distribution
(lbs/kg)
FIG. 1 - UNIT SUSPENSION MOUNTING (Horizontal)
Unitary Products Group 3
550.39-N4YI
CLEARANCES
The clearances listed on the unit dimension drawing (Figure 9) are required for the proper service and opera tion of the unit.
RIGGING AND HANDLING
Be careful when moving the unit. Do not remove any packaging until the unit is near its final location.
The packaging consists of a bottom wooden skid that can be lifted with a fork truck from any direction, a card board container that covers the entire unit, and strapping that secures the cardboard container to the bottom of the skid.
These units can be rigged with slings under the bottom skid.
-
-
from crushing the unit panels and frame.
Before rigging any unit, determine its weight from Ta ble 2. Before rigging a unit for horizontal installation, make sure that its weight will be distributed equally.
VERTICAL/HORIZONTAL INSTALLATION
The unit is shipped for vertical installation with a vertical air discharge as shownin Figure 2, but maybe converted for horizontal installation as shown in Figure 2 by inter­changing the solid bottom panel and the return air duct flange.
DUCT CONNECTIONS
All ducts should be designed and installed in accordance with applicable national and/or local codes.
Refer to Figure 3 for suggested method of connecting supply air ductwork.
-
FIG. 3 - SUPPLY AIR DUCT CONNECTION
Ducts should be sized no smaller than the duct flanges on the unit or the accessory electric heater (if used). Ref er to the unit dimensions (Figure 1) and the heater detail (Figure 4) for these sizes.
Use flexible fiber glass or plastic cloth collars or other non-flammable material at the unit duct connections to minimize the transmission of noise and vibration.
Insulate all ductwork running through unconditioned ar­eas to prevent moisture condensation and to provide more economical operation.
The return air duct flange is factory-mounted on the front of the unit, but it can be reversed with the solid bottom panel for hori zontal applications. When the return air grille is used, the duct connection frame is not used.
NOTE: If return air duct is not used, applicable lnstalltion
The field installed air plenum and return air grille accessories should be used in place of ductwork only when a free blow/free return application is practical.
codes may limit the unit to installation only in a single story residence.
-
-
(489)
(565)
FIG. 2 - VERTICAL AND HORIZONTAL APPLICATION
4 Unitary Products Group
FIG. 4 - ELECTRIC HEATER ACCESSORY
(25)