THE ENCLOSED INSTAL L ATI ON INSTRUCT I ONS AND ANY APPL I CABL E
LOCAL, STAT E , AND NATIONAL CODES INCLUDING, BUT NOT LIMI T E D
TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
THIS PRODUCT MUST B E INSTALLED IN STRICT COMPLIANCE WITH
WARNING
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY
OR PROPERTY DAM AGE.
I NCORRECT INSTALLATI ON MAY CREATE A CONDITI ON WHERE THE
SUNLINE™ SPLIT-SYSTEM
EVAPORATOR BLOWER
(AIR COOLED)
INSTALLATION INSTRUCTION
GENERAL
This completely assembled blower unit is manufactured under
ISO 9002 Quality System Certification and includes a wellinsulated cabinet, a DX cooling coil with copper tubes and aluminum fins, an expansion valve, a distributor, throwaway filters, a centrifugal blower, a blower motor, a blower motor
contactor, an adjustable belt drive and a small holding charge
of Refrigerant-22.
The unit is shipped in the vertical position with a vertical air discharge.Theblowersection canbe repositionedas shownin Figure1 for horizontal applications.
REFERENCE
This instruction covers the installation of the evaporator blower
unit. For information on the installation and operation of the
matching condensing unit refer to Form 035-17263-000.
Additional information for the accessories on this equipment is
available in the following instructions:
Assoonas aunit isreceived, itshouldbe inspectedfor possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier's delivery receipt. A
separate request for inspection by the carrier's agent should
be made in writing. See Local Distributor for additional information.
Product Category
K = Split-System Evaporator Blower
Product Generation
1,2,3 = Design Level
Product Identifier
EU = Evaporator Blower Unit
NominalCooling Capacity
180 = 180Mbh (52.7kW)
NOMENCLATURE
EU
K
3
180
50
A
•
Electric Heater - 550.13-N10.1V
•
Supply Air Plenum - 550.13-N10.2V
•
Return Air Grille - 550.13-N10.3V
•
Base - 550.13-N10.4V
•
Hot Water & Steam Coil - 550.13-N10.7V
•
Suspension Mounting - 550.13-N7.1
Renewal Parts:
•
Refer to Parts Manual for complete listing of replacement
parts on this equipment.
areintended toclarify ormake theinstallation easier. Cautionsare givento preventequipment dam
aregivento alertinstallerthat personalinjury and/or equipmentdamage may resultif installationprocedureis not
Refrigerant Line Connections
A = Cooling Only
Voltage Code
50 = 380/415-3-50
-
-
Page 2
035-12124-000 Rev. A(0501)I
INSTALLATION
LIMITATIONS
Theseunits mustbeinstalled inaccordancewithapplicablena
tional, local and municipal safety codes.
If components are to be added to a unit to meet local codes,
theyare tobe installedatthedealer'sand/or thecustomer's ex
pense. Refer to Table 2 for Unit Application Data.
LOCATION
This blowerunit is notdesigned for outdoorinstallation. Itmust
be locatedwithin the buildingstructure, either insideor outside
the conditioned space.
The unit should be located as close to the condensing unit as
practical and positioned to minimize bends in the refrigerant
piping.
Unitsbeing installedverticallyorhorizontallycan besetdirectly
on a floor or platform, or they can be supported by metal or
wooden beams.
Units being installed horizontally can also be suspended from
above. Refer to the suspension accessory instruction installa
tion procedures.
CLEARANCES
The clearanceslisted on theunit dimension drawing(Figure 7)
are required for the proper service and operation of the unit.
RIGGING AND HANDLING
Becareful whenmovingtheunit.Do notremove anypackaging
until the unit is near its final location.
The packaging consists of a bottom wooden skid that can be
lifted witha fork truck from anydirection, a clear heavy milbag
that coversthe entire unit,and strapping thatsecures the clear
bag to the bottom of the skid.
Refer to data in Table 7 for complete motor specifications.
2
Filters are throwaway type. Twoinch (50mm)filters may be used, if required by
removing the 1" (25mm) filter retaining angles provided in the filter rack.
All ducts should be designed and installed in accordance with
applicable national and/or local codes.
Ducts should be sized no smaller than the duct flanges on the
unit or the accessory electric heater(ifused).Refer to the unit
dimensions(Figure7) andthe heaterdetail (Figure2) forthese
sizes.
The field installed air plenum and return air grille accessories
shouldbeused inplace of ductworkonly whenafree blow/free
return application is practical.
(25)
(489)
(565)
FIG. 2 - ELECTRIC HEATER ACCESSORY
REFRIGERANT MAINS
-
Many service problems can be avoided by taking adequate pre
-
cautionsto providean internallycleananddrysystem,andbyus
ing procedures and materials that conform with established
standards.
Hard drawncoppertubing should be usedwhere no appreciable amount of bending around pipes or other obstructions in
necessary.Use long radius ells whereverpossible.If soft copper is used, care should be taken to avoid sharp bends which
may cause a restriction.
Pack fiberglass insulation and asealing material such asPermagum aroundrefrigerant lines wherethey penetrate awallto
reduce vibration and to retain some flexibility.
Support all refrigerant lines at minimumintervalswithsuitable
hangers, brackets or clamps.
Braze all copper to copper joints witH Sil-Fos 5 or equivalent
brazing material. Do not use soft solder.
Never braze or solder liquid and suction lines together. The
complete suction line should be insulated with no less the
(12mm) ARMAFLEX or equivalent.
If it is desirable to tape or wire the liquid and suction lines to
gether for support purposes, they must be completely insu
lated from each other.
INSTALLING REFRIGERANTMAINS
The units are evacuated and dehydrated at the factory and
shipped with a holding charge of Refrigerant-22. The suction
and liquid connections are sealed with copper disks.
WARNING: Provisions for recovering refrigerant releases
If the unit has already lost itsholdingcharge, it should be leak
tested and the necessary repairs should be made. If the unit
has maintaineditsholding charge, you can assume that ithas
no leaks and proceed with the installation.
Make sure the refrigerant in the lines has been recovered,
then drill a small hole through the discs to prevent any inter
nal pressure from blowing them off and to allow the flow of
dry nitrogen through the connections when unbrazing the
closures.
must be available during all phases of installation,
leak testing and charging. Do NOT release refrig
erantinto theatmosphere. ASchradervalveispro
vided on the coil header for recovering refrigerant
holding charge.
-
-
1
"
2
-
-
-
-
-
Unitary Products Group3
Page 4
035-12124-000 Rev. A(0501)
NOTE: To minimize the possibility of system failure due to dirt
andmoisture, afilter-driermustbeinstalledineachliq
uid line as close to the evaporator as possible. Filterdriers are not supplied with the evaporator blowers.
They aresuppliedwith the matching condensing sec
tions.
The temperature required to make or break a brazed joint is
sufficiently high to cause oxidation of the copper unless an
inert atmosphere is provide.
times whenheatis being applied anduntilthe joint
has cooled.
The liquid, suction and drain connections inside the unit must
be piped to the outside. Refer to Unit Dimensions for loca
-
tions of the access openings in the unit panel.
Protective grommets are supplied by the factory for field
placement into these access openings.
The blower units are shipped with the coil section side pan
els suitable for right hand piping connections when viewed
from the return air side of the unit.
The refrigerant piping and the condensate drain connection
may be routed through either side of the unit.
If left hand piping is required, the two panels on the right side
of the coil section can be interchanged with the single panel
on the left hand side of the coil section.
When left hand piping connections are installed, the suction
line must be insulated to prevent moisture from condensing
and being carried into the blower section.
EXPANSION VALVE BULB
The expansion valve bulb must be fastened in a 4 o'clock po-
sition to the suction line outside the cabinet after the piping
connections have been made. Use the clamps supplied with
the valve.
DRAIN CONNECTION
The drain line MUST be trapped because the coil is located
on the negative side of the supply air blower. It must also be
protected from freezing temperatures.
7
A
" (22.2mm) OD stub connection is provided within the
8
cabinet on both ends of the condensate drain pan for either
left hand or right hand piping connections. Refer to Figure 3
for recommended drain piping.
-
The drain line is usually located on the same end of the coil
section as the refrigerant connections. The line should be in
-
sulated where moisture drippage will be objectionable or
cause damage to the area. Seal the unused drain connec
tion with a suitable mastic.
The 3" (76mm) dimension must equal or exceed the nega
tive static pressure developed by the supply air blower. If it
does not, condensate will not drain properly and may over
flow the drain pan. The trap must be at least 2" (50mm) deep
to maintain a water seal under all operating conditions, espe
cially during blower start-up.
SUPPLY AIR BLOWER ADJUSTMENT
The RPM of the supply air blower will depend on the re
quired airflow, the unit accessories and the static resistances
of both the supply and the return air duct systems. With this
information, the RPM for the supply air blower can be deter
mined from the blower performance in Table 5
Knowing the required blower RPM and the blower motor HP,
the setting (turns open) for the supply air motor pulley can be
determined from Table 3..
TABLE 3 - SUPPLY AIR BLOWER MOTOR PULLEY
ADJUSTMENT
TURNS OPEN*
5615
4652
3689
2726
1763
0800
* Pulleys can be adjusted in half-turn increments.
Each motor pulley has:
1.Athreaded barrel with two flats (or notched recesses) 180
degrees apart.
2.Amovable flange with one set screw.
After the movable flange has been rotated to the proper
number of “turns open”, the set screw should be tightened
against the flat on the barrel to lock the movable flange in
place. If the pulley includes a locking collar, the locking collar
must be loosened to adjust the setting of the movable
flange.
BLOWER DRIVE RANGE (RPM)
615-800
-
-
-
-
-
-
-
Note the following:
1.The supply airflow must be within the limitations shown in
Table 2.
(76)
(50)
2.All pulleys can be adjusted in half-turn increments.
3.Thetensionon the belt should be adjusted for a deflection
3
of
" (5mm)per foot (305mm) ofbelt span withanapplied
16
force of approximately 3 lbs (1.4kg). This adjustment is
madebymoving theblower motor mountingplate. Referto
Figure 4. Turningthe adjustment bolt (B) moves the motor
mounting plate up or down. Note - Never loosen the two
nuts (C). Four hex nuts (A) have to be loosed to move the
mounting plate and retightened after the mounting plate
FIG 3 - RECOMMENDED DRAIN PIPING
4Unitary Products Group
has been moved to the proper position.
Page 5
4.All pulleys are factory aligned.
5.All supply air motor pulleys are factory set at two “turns
open.”
After the supplyair blower motor is operating, adjusttheresis
tances in both the supply and the return duct systems to bal
ancetheair distributionthroughout theconditioned space.The
job specifications may require that this balancing be done by
035-12124-000 Rev. A(0501)I
operation, check the belt and pulleys for tightness and align
ment.
Afterreadingshave beenobtained, removethetubes andseal
up the drilled holes in the side panel with
tity can result in extensive blower damage.
5
" (8mm) dia. dot
16
(559)
(8)
(457
-
-
FIG 4 - TYPICAL MOTOR MOUNTING ASSEMBLY
someone other than the equipment installer.
Tocheck thesupplyair airflowafter thethe initialbalancing has
been completed:
5
1.Drilltwo holes
Figure 5.
2.Insert at least 8" (200mm) of
each of these holes for sufficient penetration into the air
flow on both sides of the evaporator coil.
NOTE: The tubes must be inserted and held in a position per
pendicular to the airflowso that velocity pressure will
not affect the static pressure reading.
3.Usingan inclinedmanometer,determine thepressuredrop
across a dry evaporator coil. Since the moisture on an
evaporator coil may vary greatly, measuring the pressure
dropacrossa wetcoilunder fieldconditionswould beinac
curate. To assure a dry coil, the refrigerant system should
be de-energized while the test is being run.
" (8mm)dia.in the side panelas shown in
16
1
" (6.3mm) O.D. tubing into
4
(254)
(8)
FIG 5 - HOLE LOCATIONS
TO DETERMINE PRESSURE DROP READINGS
ACROSS THE DRY EVAPORATOR
Unit resistance is based on a wet evaporator coil and clean filters.
2
Availablestatic pressure inIWG (Pa) toovercome the resistanceof the ductsystem and anyaccessories added tothe unit. Referto Table6 for theresistanceof these
accessories and to Table7 foradditional motorand drive data
NOTE: Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device.
LEGEND:
RPM range for standard
factory-mounted drive components.
* Add these pressures to the ESP values in the respective blower performance table.
EXTERNAL STATIC PRESSURE DROPRESISTANCE
4800 /
3
/s
2.26
5400 /
2.55
Exceeds the output limitation of the standard
factory-mounted blower motor.
IWG/pA
6000 /
2.83
6600 /
3.11
7200 /
3.40
6Unitary Products Group
Page 7
UNIT
035-12124-000 Rev. A(0501)
FIG 7 - UNIT DIMENSIONS AND CLEARANCES
ACCESSORIES
•ELECTRIC HEATER
Add 15" (381mm) to Unit Height when using 10, 16, 26 or 36kW Heater
•SUPPLYAIR PLENUM
Add 27" (686mm) to Unit Height when used
•BASE
Add 24" (610mm) to Unit Height when used
MINIMUM CLEARANCES (in./mm)
Side with RETURN AIR opening- 24 / 610
Side with SUPPLYAIR opening- 24 / 610
Side with PIPING CONNECTIONS- 61 / 1549
Side opposite PIPING CONNECTIONS - 26 / 660
Bottom-
NOTES:
1
Overall dimension of the unit will vary if an electric heater, a supply air plenum or a base is used.
2
This dimension is required for removal of the DX coil. Only 26" (660mm) is required for normal serv
icing.
3
If the DX coil has to be removed, this dimension is required to loosen screws that secure the coil to
the unit frame. This dimension will also be required for blower motor access if the piping
connections are made on the opposite side of the unit.
4
Allow enough clearance to trap the condensate drain line.
All dimensions are in millimeters and inches. They are subject to change without notice. Certified dimensions will be
provided upon request.
1
2
3
4
-
Unitary Products Group7
Page 8
TABLE 7 - BLOWER MOTOR AND DRIVE DATA
Motor
(HP/kW)
3 / 2.2615/800
Blower
Range
(RPM)
Adjustable Motor PulleyFixed Blower PulleyBelt
Pitch Dia
(In./mm)
3.4 - 4.4 / 86
- 112
Bore
(In./mm)
7
/ 22.2
8
POWER AND CONTROL WIRING
Install electrical wiring in accordance with appli
cable national, local and municipal codes. The
unit should be grounded in accordance with
these codes.
Route the power wires into the unit through one
7
of the
with the supply air opening and connect them to
the terminals on blower motor contactor 10M.
Route the control wires into the unit through the
other
them to the terminals on block 4TB. Refer to
the unit drawing in Figure 7 for the locations of
these knockouts.
If the unit includes an electric heat accessory,
route the power wires into heater control box instead of the unit. Refer to the electric heat instructions for additional installation information.
" (22.2mm) dia.knockouts in the panel
8
7
" (22.2mm) dia.knockout and connect
8
Pitch Dia.
(In./mm)
8.0 / 2031 / 25A5455.3 / 1405
Bore
(In./mm)
Designation
-
TERMINALS ON
1-STAGE COOLING
THERMOSTAT
2TH0870124
Pitch Lg.
(In./mm)
MOTOR SPECIFICATIONS
•1450 RPM
•380/415-3-50
•Solid base
•56 Frame
•Inherently protected
•Permanently lubricated
ball bearings
TERMINALSONBLOCK 3TB OF
THE BLOWER UNIT
Refer to Table 4 to size the disconnect switch,
the power wiring and the fuses. Refer to Figure
8 for typical field wiring.
FIG 8 - TYPICALFIELD WIRING (Cooling only)
NOTE:Threephase motorrotation maybeincor-
rect when the unitisfirststarted up. Re
verse phase (leads L1 and L2) at
contactor to obtain the correct rotation.
to assure good air flow and filtering action.
EVAPORATOR COIL—Donotallowdirt toaccumulate onthe
evaporatorcoil orother partsofthe evaporatoraircircuit.Clean
as often as necessary to assure good system performance.
Use a brush, vacuum cleaner attachment or other suitable
means.
Subject to change without notice. Printed in U.S.A
Copyright by York International Corporation
LUBRICATION — The bearings for the blower shaft and the
blower motors are permanently lubricated and should not re
quire additional lubricant.
DRAIN PAN — The drain pan should be inspected regularly
to assure proper drainage.
BELTS — Maintain belt tension to extend belt life. Replace
when signs of failure begin to appear.