York H-RE024 User Manual

036-21315-001 Rev. A (0502)
®
TECHNICAL GUIDE
SPLIT-SYSTEM AIR CONDITIONERS
14 SEER
MODELS: H*RE024 THRU 060 (2 THRU 5 NOMINAL TONS)
O
T
A
R
D
I
E
I
A
F
S
I
T
R
C
E
O
C
R
E
R
U
T C
A
F
U N
A
M
C
E
A
CERTIFICATION APPLIES ONLY
WHEN THE COMPLETE
SYSTEM IS LISTED
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at www.york.com for the most up-to-date technical information.
Additional rating information can be found at www.ari.org.
Y
R
A
T
I N
U
R
E
Q
U
I
E
P
M
R
T
I
F
I
C
A
T
R
I
S
O
N
I
S
T
A
N
D
WITH ARI.
M
A
P
I
R
-
L
C
O
Y
N
I
D
I
N
T
G
I
O
N I
W
N
I
G
T
H
T
F
N
O
S
N
O
I
T
0
C
E
1
2
D
R
A
LISTED
DESCRIPTION
The 14 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be cus­tom-matched with one of UPG’s complete line of evaporator sections, with each serving a specific function. Matching Air Handlers are available for upflow, downflow, or horizontal applications to provide a complete system. Electric Heaters are available, if required. Add-On coils are available for use with upflow, downflow, or horizontal furnaces and air han­dlers.
WARRANTY
5-year limited parts warranty.
10-year limited compressor warranty.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed of copper tube and aluminum fins.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi­tions occur. A liquid line filter-drier further protects the compressor.
DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and desert sand matted-textured finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimen­sion means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and com­pressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, a single panel covering the electrical controls, and the molex plug in the control box connecting the con­denser fan make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment cer­tification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21315-001 Rev. A (0502)
h
.
Physical and Electrical Data
MODEL
Unit Supply Voltage 208 / 230 - 1 – 60
Normal Voltage Range Minimum Circuit Ampacity 12.1 14.9 18.1 17.8 20.6 31.8
Max Overcurrent Device Amps
Compressor Type
Compressor Amps
Crankcase Heater No No No No No No Fan Motor Amps Rated Load .5 1.3 1.3 1.3 1.3 1.4 Fan Diameter Inches 22 22 22 24 24 24
Fan Motor
Coil
Liquid Line OD 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line OD 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8
Unit Charge (Lbs - Oz) Charge Per Foot, oz. 0.70 0.70 0.70 0.76 0.76 0.76 Operating Weight Lbs 209 228 219 240 264 270
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. All scrolls listed with superscript “B” are Bristol scrolls. All scrolls listed with superscripts “C” are Copeland scrolls.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
1
2
3
Rated Load 9.3 10.9 13.5 13.2 15.5 24.3 Locked Rotor 57 64 73 95 109 150
Rated HP 1/15 1/4 1/4 1/4 1/4 1/3 Nominal RPM 830 825 825 825 825 1100 Nominal CFM 2,260 3,300 3,300 3,300 3,300 3,500 Face Area Sq Ft 19.65 23.58 23.58 22.5 27.0 27.0 Rows Deep 1 1 1 2 2 2 Fin /Inch 18 18 18 18 18 18
4
H1RE024S06 H1RE030S06 H1RE036S06 H2RE042S06 H2RE048S06 H2RE060S06
187 to 252
20 20 25 30 35 50
Inertia Inertia
Scroll
C
Scroll
C
Scroll
C
Scroll
8 - 0 9 - 14 9 - 6 14 - 0 14 - 3 15 - 13
B
All dimensions are in inches. They are subject to change wit out notice. Certified dimensions will be provided upon request
C
Unit
Model
Dimensions
(Inches)
Refrigerant
Connection
Line Size
A B C Liquid Vapor
024 33 37 27
A
036 39 37 27 042 32 43 32
3/8
7/8030 39 37 27
1-1/8048 38 43 32
060 38 43 32
1. Included Fan Guard * Reducer Fan Guard
B
2 Unitary Products Group
036-21315-001 Rev. A (0502)
COOLING CAPACITY - With Air Handler Coils
COOLING
SEER
W/O TXV
SEER
+ TXV
3
UNIT MODEL
MODEL
AIR HANDLER
ELECTRIC
HEAT KW
2
W
COIL
MODEL
1
RATED
CFM
NET MBH
TOTAL SENS.
1 PH 14 SEER AC WITH N-AH / G2FD
H1RE024S06 N1AHB0806 2,5,8,10 17 G2FD036S17 800 25.2 18.1 - 14.00 12.35
H1RE030S06 N1AHB1206 5,8,10,15,19 17 G2FD036S17 1000 28.8 20.7 - 13.10 11.80
N1AHB1206 5,8,10,15,19 17 G2FD036S17 1200 34.0 24.5 - 13.35 11.80
H1RE036S06
N1AHB1206 5,8,10,15,19 17 G2FD046S17 1200 35.0 25.6 - 14.00 12.20
N1AHD1406 5,8,10,15 24 G2FD048S24 1200 35.4 25.7 - 14.00 12.50
N1AHD1406 5,8,10,15 24 G2FD060S24 1200 36.0 26.1 - 14.20 12.80
N1AHC1606 5,8,10,15,20 21 G2FD042S21 1400 39.0 28.2 - 13.25 11.35
H2RE042S06
N1AHC1606 5,8,10,15,20 21 G2FD048S21 1400 39.5 28.9 - 13.50 11.60
N1AHD1406 5,8,10,15 24 G2FD060S24 1400 40.5 29.6 - 14.00 12.00
H2RE048S06
H2RE060S06
N1AHD2006 8,10,15,20,25,30 24 G2FD060S24 1600 46.5 33.9 - 13.85 11.80
N1AHD2006 8,10,15,20,25,30 24 G2FD061H24 1600 47.0 34.3 - 14.00 11.90
N1AHD2006 8,10,15,20,25,30 24 G2FD060S24 1900 53.5 37.1 - 13.50 12.00
N1AHD2006 8,10,15,20,25,30 24 G2FD061H24 2050 54.5 39.1 - 13.50 12.10
1 PH 14 SEER AC / N1VS - VARIABLE SPEED
H1RE024S06
H1RE030S06
H1RE036S06
N1VSB12 10,15,18 17 G2FD036S17 870 25.6 18.1 - 15.00 13.85
N1VSB12 10,15,18 17 G2FD046S17 870 26.2 18.9 - 15.50 14.15
N1VSB12 10,15,18 17 G2FD036S17 1000 29.4 20.7 - 14.50 12.95
N1VSB12 10,15,18 17 G2FD046S17 1070 30.0 21.6 - 15.35 13.60
N1VSB12 10,15,18 17 G2FD046S17 1250 35.2 25.6 - 14.00 12.40
N1VSC16 10,15,18 21 G2FD048S21 1285 36.0 25.7 - 15.00 13.60
N1VSC16 10,15,18 21 G2FD048S21 1420 40.5 28.9 - 14.50 12.50
H2RE042S06
N1VSC16 10,15,18 21 G2FD048S21 1420 40.5 28.9 - 14.50 12.50
N1VSD20 10,15,18,30 24 G2FD060S24 1420 41.5 29.6 - 15.50 13.20
H2RE048S06
H2RE060S06
H1RE024S06
H1RE030S06
N1VSC16 10,15,18 21 G2FD048S21 1590 46.0 33.2 - 14.30 12.20
N1VSD20 10,15,18,30 24 G2FD060S24 1600 47.0 33.9 - 14.65 12.40
N1VSD20 8,10,15,20,25,30 24 G2FD060S24 1780 53.5 36.3 - 13.75 12.35
N1VSD20 8,10,15,20,25,30 24 G2FD061H24 1780 54.5 37.0 - 14.00 12.60
1 PH 14 SEER AC / F2RP / RC / FP / FC / FV
4,5
F2RP/FP036 5,8,10,15,19 21 - 800 25.0 18.0 - 13.80 12.30
F2FP040 5,8,10,15 21 - 800 25.4 17.4 - 14.00 12.75
F2RP/FP036 5,8,10,15,19 21 - 1000 29.8 21.5 - 13.85 12.40
F2FP045 5,8,10,15 24 - 1000 30.6 21.5 - 14.00 12.70
F2RP/FP036 5,8,10,15,19 21 - 1200 34.4 24.8 - 13.50 12.10
H1RE036S06
F2RP/FP042 5,8,10,15 21 - 1200 34.4 24.8 - 13.30 11.90
F2FP045 5,8,10,15 24 - 1200 36.0 25.5 - 14.00 12.65
H2RE042S06
H2RE048S06
H2RE060S06
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
F2FP045 5,8,10,15 24 - 1400 40.5 29.8 - 14.00 12.00
F2FP048 5,8,10,15,20,25 24 - 1400 39.5 28.9 - 13.25 11.30
F2FP060 5,8,10,15,20,25 24 - 1600 46.0 33.4 - 13.00 11.25
F2FV060 8,10,15,20,25 24 - 1625 47.5 34.9 - 15.50 13.20
F2FP060 10,15,20,25 24 -- 1900 53.0 36.7 - 13.00 11.60
F2FV060 10,15,20,25 24 -- 1900 53.5 36.3 - 13.75 12.35
EER
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters.
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC
5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.
- = Not applicable
. models. All ratings remain the same.
Unitary Products Group 3
036-21315-001 Rev. A (0502)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils
UNIT MODEL
H1RE024S06
H1RE030S06
H1RE036S06
H2RE042S06
H2RE048S06
For Notes See Page 5.
FURNACE**
CFM RANGE
(MIN.-MAX.)
700 900
875
112 5
1050 1350
1225 1575
1400 1800
W
14 G1FA036S14 800 25.0 18.0 13.85 - 12.30
17,21 G1FA036S17,21 800 24.8 17.9 13.85 - 12.20
- G1HD036 800 25.0 18.1 14.00 - 12.35 17 G1NA036S17L 800 24.0 16.6 13.50 - 12.00 21 G1NA048S21D 800 24.0 16.6 13.50 - 12.00 14 G1UA036S14 800 25.0 18.0 13.85 - 12.30
17,21 G1UA036S17,21 800 24.8 17.9 13.85 - 12.20
17 G2FD030S17 800 24.8 17.9 13.85 - 12.20 14 G2FD035S14 800 24.8 17.9 13.85 - 12.20 17 G2FD036S17 800 25.2 18.1 14.00 - 12.35 21 G2FD036S21 800 25.2 18.1 14.00 - 12.45 14 G1FA036S14 1000 28.4 20.0 13.00 - 11.75
17,21 G1FA036S17,21 1000 28.4 20.0 13.00 - 11.65 21,24 G1FA048S21,24 1000 30.0 21.8 14.00 - 12.40
- G1HD048 1000 30.0 21.5 14.00 - 12.40 17 G1NA036S17L 1000 29.0 20.0 - 13.50 11.95 24 G1NA042S24W 1000 29.0 20.7 - 14.00 12.00 21 G1NA048S21D 1000 29.0 20.0 - 13.50 11.95 14 G1UA036S14 1000 28.4 20.0 13.00 - 11.75
17,21 G1UA036S17,21 1000 28.4 20.0 13.00 - 11.65 21,24 G1UA048S21,24 1000 30.0 21.8 14.00 - 12.40
17 G2FD030S17 1000 28.4 20.4 13.00 - 11.65 17 G2FD036S17 1000 28.8 20.7 13.10 - 11.80 21 G2FD036S21 1000 28.8 21.0 13.10 - 12.10
21,24 G2FD048S21,24 1000 30.2 21.8 - 14.00 12.50 21,24 G1FA048S21,24 1200 35.2 25.3 14.00 - 12.30
- G1HD048 1200 34.8 25.0 13.75 - 12.30 17 G1NA036S17L 1200 33.0 23.4 - 13.00 11.30 24 G1NA042S24W 1200 34.6 25.0 - 14.00 12.00 21 G1NA048S21D 1200 33.0 23.4 - 13.00 11.30
21,24 G1UA048S21,24 1200 35.2 25.3 14.00 - 12.30
17 G2FD036S17 1200 34.0 24.5 13.35 - 11.80 21 G2FD036S21 1200 34.0 24.8 13.35 - 12.05 21 G2FD042S21 1200 34.8 25.4 13.70 - 12.10 17 G2FD046S17 1200 35.0 25.6 14.00 - 12.20
21,24 G2FD048S21,24 1200 35.2 25.7 14.00 - 12.45 21,24 G1FA048S21,24 1400 39.0 28.4 - 13.50 11.45 21,24 G1FA060S21,24 1400 40.5 29.6 - 14.00 11.80
- G1HD048 1400 39.0 28.4 - 13.25 11.50 24 G1NA042S24W 1400 40.5 29.5 - 14.00 11.75 21 G1NA048S21D 1400 39.0 27.3 - 13.00 11.50
21,24 G1UA048S21,24 1400 39.0 28.4 - 13.50 11.45 21,24 G1UA060S21,24 1400 40.5 29.6 - 14.00 11.80
21 G2FD042S21 1400 39.0 28.2 - 13.25 11.35 17 G2FD046S17 1400 39.0 28.6 - 13.50 11.45
21,24 G2FD048S21,24 1400 39.5 28.9 - 13.50 11.60
24 G2FD060S24 1400 40.5 29.6 - 14.00 11.80
21,24 G1FA048S21,24 1600 45.0 32.6 - 13.40 11.50 21,24 G1FA060S21,24 1600 46.5 33.9 - 13.85 11.80
- G1HD048 1600 45.0 32.4 - 13.25 11.45 24 G1NA042S24W 1500 46.5 32.8 - 14.00 11.85 21 G1NA048S21D 1400 44.0 29.0 - 13.00 11.50
21,24 G1UA048S21,24 1600 45.0 32.6 - 13.40 11.50 21,24 G1UA060S21,24 1600 46.5 33.9 - 13.85 11.80 21,24 G2FD048S21,24 1600 45.5 33.2 - 13.50 11.60
24 G2FD060S24 1600 46.5 33.9 - 13.85 11.80 24 G2FD061H24 1600 47.0 34.3 - 14.00 11.90
COIL
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
COOLING
SEER + TXV
W/O TDR
SEER + TXV
+ TDR*
1
EER
4 Unitary Products Group
036-21315-001 Rev. A (0502)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils (Continued)
COOLING
SEER + TXV
W/O TDR
UNIT MODEL
FURNACE**
CFM RANGE
(MIN.-MAX.)
W
COIL
MODEL
RATED
CFM
TOTAL SENS.
21,24 G1FA060S21,24 1900 53.5 37.1 - 13.25 12.00
24 G2FD060S24 1900 53.5 37.1 - 13.25 12.00
H2RE060S06
1650 2150
24 G2FD061H24 2050 54.5 39.1 - 13.25 12.10
- G1HD060 1900 52.5 36.0 - 13.00 11.75
24 G1NA060S24T 1900 53.0 35.9 - 13.00 11.90
21,24 G1UA060S21,24 1900 53.5 37.1 - 13.25 12.00
1. TXV = Use 1TV700 Series Kit.
* Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one. **
Refer to Quick Selection Chart for specific furnace match-up.
NET MBH
COOLING CAPACITY - With Variable Speed Furnaces
COOLING
SEER
W/O TXV
3
UNIT MODEL
VARIABLE SPEED FURNACE MODEL
COIL MODEL
1
W
RATED
CFM
NET MBH
TOTAL SENS.
1 PH 14 SEER AC / P1DU / P1XD / P1XU - VARIABLE SPEED
P1DUA12V G1FA036S14 14 870 25.4 18.0 - 15.00 13.60 P1DUA12V G1UA036S14 14 870 25.4 18.0 - 15.00 13.60 P1DUA12V G2FD035S14 14 870 25.2 17.9 - 15.00 13.50
H1RE024S06
P1XDB12V G2FD030S17 17 830 26.0 17.9 - 15.00 13.65 P1XUB12V G1FA036S17 17 870 25.4 18.0 - 15.50 13.75 P1XUB12V G1UA036S17 17 870 25.4 18.0 - 15.50 13.75 P1XUB12V G2FD030S17 17 870 25.4 17.9 - 15.50 13.75 P1XUB12V G2FD036S17 17 870 25.8 18.1 - 15.50 13.90 P1DUA12V G1FA036S14 14 1000 28.8 20.0 - 13.50 12.50 P1DUA12V G1UA036S14 14 1000 28.8 20.0 - 13.50 12.50
H1RE030S06
P1DUB16V G2FD036S17 17 1000 30.0 20.7 - 14.50 13.35 P1XDB12V G2FD036S17 17 1040 30.2 20.7 - 14.00 12.50 P1XUB12V G2FD036S17 17 1020 29.2 20.7 - 14.00 12.65 P1DUB16V G2FD036S17 17 1200 34.4 24.5 - 14.00 12.70 P1DUC20V G1FA048S21 21 1200 36.2 25.3 - 15.50 14.15 P1DUC20V G1UA048S21 21 1200 36.2 25.3 - 15.50 14.15
H1RE036S06
P1DUC20V G2FD036S21 21 1200 34.6 24.8 - 14.65 13.05 P1DUC20V G2FD048S21 21 1200 36.0 25.7 - 15.50 13.95 P1XDB12V G2FD036S17 17 1130 34.8 24.5 - 14.20 12.60 P1XDD20V G2FD048S24 24 1195 36.2 25.7 - 14.50 13.10 P1XUB12V G2FD036S17 17 1200 34.4 24.5 - 14.00 12.65 P1DUC20V G1FA048S21 21 1400 39.5 28.4 - 14.50 12.45 P1DUC20V G1FA060S21 21 1400 41.0 29.6 - 15.00 12.80 P1DUC20V G1UA048S21 21 1400 39.5 28.4 - 14.50 12.45 P1DUC20V G1UA060S21 21 1400 41.0 29.6 - 15.00 12.80
H2RE042S06
P1DUC20V G2FD042S21 21 1400 39.5 28.2 - 14.00 12.30 P1DUC20V G2FD048S21 21 1420 40.0 28.9 - 14.50 12.60 P1DUC20V G2FD048S21 21 1420 40.0 28.9 - 14.50 12.50 P1XDD20V G2FD048S24 24 1365 41.0 28.9 - 14.40 12.50 P1XDD20V G2FD060S24 24 1420 41.5 33.8 - 14.40 12.55 P1DUC20V G1FA060S21 21 1605 46.5 33.9 - 14.00 12.20
H2RE048S06
P1DUC20V G1UA060S21 21 1605 46.5 33.9 - 14.00 12.20 P1DUC20V G2FD048S21 21 1605 45.5 33.2 - 13.50 12.00 P1XDD20V G2FD060S24 24 1580 47.0 33.9 - 13.80 12.20 P1XDD20V G2FD060S24 24 1580 52.5 34.3 - 13.50 12.2 P1DUC20V G1FA060S21 21 1630 53.0 34.9 - 13.60 12.4 P1DUC20V G1UA060S21 21 1630 53.0 34.9 - 13.60 12.4 P1XUC20V G1FA060S21 21 1590 53.0 34.5 - 13.50 12.4
H2RE060S06
P1XUC20V G1UA060S21 21 1590 53.0 34.5 - 13.50 12.4 P1XUD20V G1FA060S24 24 1560 53.0 34.4 - 13.75 12.5 P1XUD20V G1UA060S24 24 1560 53.0 34.4 - 13.75 12.5 P1XUD20V G2FD060S24 24 1560 53.0 34.4 - 13.75 12.5 P1XUD20V G2FD061H24 24 1560 53.5 34.9 - 14.00 12.8
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. TXV = Use 1TV700 Series Kit.
3. Variable speed furnaces have B.O.D (Blower on Delay) standard.
SEER + TXV
+ TDR*
SEER
+ TXV
1
EER
EER
2
Unitary Products Group 5