York H-RA018, H-RA036, 060, 090 User Manual

®
TECHNICAL GUIDE
SPLIT-SYSTEM AIR CONDITIONERS 10 SEER MODELS: H*RA018 THRU 060
(1.5 THRU 5 NOMINAL TONS, 1 PH) H*RA036 THRU 090
(3 THRU 7.5 NOMINAL TONS, 3 PH)
MODELS: 018 - 060 (1 PH & 3 PH)
O
T
A
R
D
I
E
I
A
F
S
I
T
R
C
E
O
C
M
A
P
I
R
R
-
L
C
E
O
Y
N
R
Y
I
D
R
I
U
A
T
T
I
C
N
U
A
F
U N
A
M
C E
R T
I
A
R
I
CERTIFICATIONAPPLIES ONLY
WHEN THE COMPLETE
SYSTEM IS LISTED
WITH ARI.
Due to continuous product improvement, specifica­tions are subject to change without notice.
Visit us on the web at www.york.com for the most up-to-date technical information.
Additional rating information can be found at www.ariprimenet.org.
N
T
G
I
O
N I
W
N
I
G
T
H
R
E
T
Q
F
N
U
I
E
P
M
O
S
N
F
O
I
I
C
T
A
0
C
T
E
I
S
O
N
1
2
S
D
T
R
A
A
N
D
LISTED
036-21121-002 Rev. A (0602)
DESCRIPTION
The 10 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be cus­tom-matched with one of UPG’s complete line of evaporator sections, each designed to serve a specific function. Match­ing Air Handlers are available for upflow, downflow or hori­zontal applications to provide a complete system. Electric Heaters are available if required. Add-On coils are available for use with upflow, downflow or horizontal furnaces and air handlers.
WARRANTY
Single Phase Units:
5-year limited parts warranty. 5-year limited compressor warranty.
Three Phase Units:
1-year limited parts warranty. 5-year limited compressor warranty.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed of enhanced copper tube and aluminum fins.
COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi­tions occur. A liquid line filter-drier further protects the compressor.
DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a bet­ter paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted desert sand fin­ish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connec­tions. Discharge line heat exchanger knockouts are pro­vided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, a single panel covering the electrical controls and the molex plug in the control box connecting the con­denser fan, make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment cer­tification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21121-002 Rev. A (0602)
Physical and Electrical Data - 1 Phase
MODEL
Unit Supply Voltage 208/230 – 1 – 60
Normal Voltage Range
Minimum Circuit Ampacity 12.5 15.6 17.5 21.5 26.1 30.1 37.3
Max. Overcurrent Device Amps
Compressor Type
Compressor Amps
Crankcase Heater No No No No No No No
Fan Motor Amps Rated Load 0.5 0.5 0.5 1.4 1.4 1.3 1.3
Fan Diameter Inches 18 18 18 18 18 22 22
Fan Motor
Face Area Sq. Ft. 8.00 8.00 9.15 9.15 12.58 15.72 15.72
Coil
Rows Deep 1111111
Fin / Inches 14 14 18 18 18 18 22
Liquid Line OD 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line OD 5/8 5/8 3/4 3/4 3/4 7/8 7/8
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.
Operating Weight Lbs. 118 123 135 137 161 176 188
1
3
Rated Load 9.6 12.1 13.6 16.1 19.8 23 28.8
Locked Rotor 54 57 73 82 97 110 160
Rated HP 1/12 1/12 1/12 1/4 1/4 1/4 1/4
Nominal RPM 1,100 1,100 1,100 1,100 1,100 850 850
Nominal CFM 1,850 1,850 1,900 2,750 2,750 3,250 3,300
4
4
H1RA018S06 H1RA024S06 H2RA030S06 H2RA036S06 H1RA042S06 H1RA048S06 H3RA060S06
187 to 252
2
20 25 30 35 40 45 60
Recip Recip Recip Recip Recip Recip
Scroll
3 - 6 3 - 11 3 - 14 3 - 15 5 - 4 7 - 5 6 - 2
0.66 0.66 0.68 0.68 0.68 0.70 .070
B
Physical and Electrical Data - 3 Phase
MODEL
H1RA
036S25
Unit Supply Voltage
Normal Voltage Range
1
Minimum Circuit Ampacity 15.0 17.4 17.3 21.3 25.8 37.7 8.0 8.4 8.3 10.8 13.0 18.1
Max. Overcurrent Device Amps
3
Compressor Type
Compressor Amps
Rated Load 10.9 12.8 11.7 16.0 18.9 29.4 5.8 6.1 6.1 8.0 9.5 14.0
Locked Rotor 78 78 78 125 146 260 40 39 39 67 73 128
2
Recip Recip Recip
Crankcase Heater No No No No No Yes No No No No No Yes
Fan Motor Amps Rated Load 1.4 1.4 1.3 1.3 2.2 4.6 .8 .8 .7 .8 1.2 2.3
Fan Diameter Inches 18 18 22 22 24 24 18 18 22 22 24 24
Rated HP 1/4 1/4 1/4 1/4 1/3 3/4 1/4 1/4 1/5 1/4 1/3 3/4
Fan Motor
Nominal RPM 1,100 1,100 850 850 1100 1100 1,100 1,100 850 850 1100 1100
Nominal CFM 2,750 2,750 3,250 3,450 4000 5000 2,750 2,750 3,250 3,450 4000 5000
Face Area Sq. Ft. 9.15 12.58 15.72 23.58 18.0 22.5 9.15 12.58 15.72 23.58 18.0 22.5
Coil
Rows Deep 111122111122
Fin / Inches 18 18 18 18 16 16 18 18 18 18 16 16
Liquid Line OD 3/8 3/8 3/8 3/8 1/2 1/2 3/8 3/8 3/8 3/8 1/2 1/2
Vapor Line OD 3/4 3/4 7/8 7/8 1-1/8 1-1/8 3/4 3/4 7/8 7/8 1-1/8 1-1/8
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.
4
4
3 - 15 5 - 4 7 - 5 9 - 7 12-3 15-3 3 - 15 5 - 4 7 - 5 9 - 7 12-3 15-3
Operating Weight Lbs. 170 176 206 228 219 368 170 176 206 228 219 368
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
3.
4.
The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub-
tract the amount of refrigerant, using the difference in length multiplied by the per foot valve.
H1RA
042S25
H1RA
048S25
H1RA
060S25
208/230 – 3 – 60
H1RA
076S25
H1RA
090S25
H1RA
036S25
H1RA
042S46
H1RA
048S46
460 - 3 - 60
H1RA
060S46
H1RA
076S46
H1RA
090S46
187 to 252 432 to 504
25 30 30 35 40 50 15 15 15 15 20 25
ScrollBScroll
B
Dual Recip Recip Recip
Scroll
B
Scroll
B
Dual
.68 .68 .70 .70 1.26 1.26 .68 .68 .70 .70 1.26 1.26
2 Unitary Products Group
036-21121-002 Rev. A (0602)
COOLING CAPACITY - With Air Handler Coils
COOLING
SEER
W/O TXV
SEER
+ TXV
-- -- --
EER
3
9.63/
9.30
UNIT MODEL
MODEL
AIR HANDLER
ELECTRIC
HEAT KW
2
W
COIL
MODEL
1
RATED
CFM
NET MBH
TOTAL SENS.
1 PH 10 SEER AC WITH N1AH / G2FD
H1RA018S06 N1AHB0806 2,5,8,10 17 G2FD024S17 650 19.0 14.1 10.50 - 9.80
H1RA024S06
H2RA030S06
H2RA036S06
H1RA042S06
H1RA048S06
N1AHB0806 2,5,8,10 17 G2FD024S17 800 24.4 18.1 10.50 - 9.55 N1AHB0806 2,5,8,10 17 G2FD030S17 850 25.0 18.5 10.60 - 9.65 N1AHB1206 5,8,10,15,19 17 G2FD030S17 1000 29.0 21.5 10.30 - 9.45 N1AHB1206 5,8,10,15,19 17 G2FD036S17 1000 30.0 22.2 10.50 - 9.65 N1AHB1206 5,8,10,15,19 17 G2FD036S17 1200 33.8 25.0 10.00 - 9.20
N1AHB1206 5,8,10,15,19 17 G2FD046S17 1200 34.4 25.5 10.15 - 9.30 N1AHC1606 5,8,10,15,20 21 G2FD042S21 1400 39.5 29.2 10.00 - 9.00 N1AHC1606 5,8,10,15,20 21 G2FD048S21 1450 41.0 30.3 10.10 - 9.15 N1AHC1606 5,8,10,15,20 21 G2FD048S21 1600 46.0 34.0 10.10 - 9.50 N1AHD2006 8,10,15,20,25,30 24 G2FD060S24 1600 47.0 34.8 10.40 - 9.70
H3RA060S06 N1AHD2006 8,10,15,20,25,30 24 G2FD060S24 1800 56.0 40.2 10.50 - 9.35
3 PH 10 SEER AC WITH N1AH / G2FD
H1RA036 S(25,46)
H1RA042S(25,46)
N1AHB1246 10,15 21 G2FD036S17 1200 33.8 25.0 10.00 - 9.20
N1AHB1246 10,15 21 G2FD042S21 1400 40.0 30.1 10.00 9.05 N1AHC1646 10,15 21 G2FD042S21 1400 39.5 29.2 10.00 - 9.00 N1AHC1646 10,15 24 G2FD048S21 1450 41.0 30.3 10.10 - 9.15 N1AHC1646 10,15 21 G2FD048S21 1600 46.0 34.0 10.10 - 9.50
H1RA048S(25,46)
N1AHD2046 10,15,29 24 G2FD048S24 1600 24.6 34.0 10.10 - 9.50 N1AHD2046 10,15,29 24 G2FD048S24 1600 46.0 34.0 10.10 - 9.50
H1RA060S(25,46)
N1AHD2046 10,15,29 24 G2FD060S24 1750 58.5 39.8 10.00 - 10.25
1 PH 10 SEER AC / F2RP / RC / FC
4,5
F2RC/F2FC024 5,8,10 18 - 650 17.4 12.9 10.00 - 9.00
H1RA018S06
F2RP/F2FP018 2,5,8 18 - 650 17.4 12.3 10.00 - 9.00 F2RP/F2FP024 5,8,10 18 - 650 17.4 12.9 10.00 - 9.00
H1RA024S06
H2RA030S06
F2RP/F2FP024 5,8,10 18 - 800 23.4 17.3 10.00 - 9.00 F2RP/F2FP030 5,8,10,15 18 - 800 23.6 17.5 10.00 - 9.10 F2RP/F2FP030 5,8,10,15 18 - 1000 28.4 21.0 10.00 - 9.50 F2RP/F2FP036 5,8,10,15,19 21 - 1000 28.0 20.0 10.00 - 9.00 F2RC/F2FC036 5,8,10,15 21 - 1200 33.6 21.5 10.00 - 9.10
H2RA036S06
F2RP/F2FP036 5,8,10,15,19 21 - 1200 34.4 25.2 10.20 - 9.30 F2RP/F2FP042 5,8,10,15 21 - 1200 34.4 25.2 10.15 - 9.20
H1RA042S06
H1RA048S06
F2RP/F2FP042 5,8,10,15 21 - 1400 39.5 28.9 10.00 - 9.00
F2FP048 5,8,10,15,20,25 24 - 1400 40.5 30.0 10.00 - 9.20 F2FP048 5,8,10,15,20,25 24 - 1600 45.5 33.7 10.00 - 9.15 F2FP060 5,8,10,15,20,25 24 - 1600 46.5 34.4 10.00 - 9.70
H3RA060S06 F2FP060 5,8,10,15,20,25 24 - 1800 56.0 41.0 10.00 - 9.15
3 PH 10 seer AC with F2RP / FP
H1RA036 S(25,46)
H1RA042S(25,46)
H1RA048S(25,46)
H1RA060S(25,46)
F2RC/F2FC036 5,8,10,15 21 - 1200 33.6 25.2 10.00 - 9.10 F2RP/F2FP042 5,8,10,15 21 - 1400 39.0 29.2 10.00 - 9.00
F2FP048 5,8,10,15,20,25 24 - 1400 40.5 30.4 10.00 - 9.00 F2FP048 5,8,10,15,20,25 24 - 1600 45.5 33.7 10.00 - 9.15 F2FP060 5,8,10,15,20,25 24 - 1750 58.5 39.8 10.00 - 9.80
3 PH 10 seer AC WITH K4EV
6
H1RA076S25,46 K4EV090 10,16,26,36 22 -- 2600 73.5 -- -- -- 10.00
H1RA090S25,46 K4EV090 10,16,26,36 22 -- 3280
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1 G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number. 2 Single phase units require single phase 2HK heaters. Three phase units require three phase 2HK heaters. 3 TXV = Use 1TV700 Series Kit.
4 To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC 5 FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.
6 H*BA-(T,W)090 is field convertible to two stage operation. Its IPLV = 11.2. — = Not Applicable.
. models. All ratings remain the same.
53.8/
89.0
Unitary Products Group 3
036-21121-002 Rev. A (0602)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils
UNIT MODEL
H1RA018S06
H1RA024S06
H2RA030S06
H2RA036S06
For Notes See Page 5.
FURNACE**
CFM RANGE
(MIN.-MAX.)
575 725
700 900
875
112 5
1050 1350
COIL
W
14,17 G1FA024S14,17 650 18.0 13.3 10.00 - 9.20
14 G1FA030S14 650 19.0 14.1 10.50 - 9.80
- G1HD024 655 18.5 13.7 10.50 - 10.00
17 G1NA024S17G 650 18.0 12.5 10.00 - 9.40
14,17 G1UA024S14,17 650 18.0 13.3 10.00 - 9.20
14 G1UA030S14 650 19.0 14.1 10.50 - 9.80
14,17 G2FD024S14,17 650 19.0 14.1 10.50 - 9.80
17 G2FD030S17 650 19.4 14.4 10.50 - 9.90 14 G2FD035S14 650 19.4 14.4 10.50 - 9.90
14,17 G1FA024S14,17 850 23.8 17.6 10.00 - 9.15
14 G1FA030S14 800 24.4 18.1 10.50 - 9.55 14 G1FA036S14 800 24.0 18.1 10.00 - 9.00
17,21 G1FA036S17,21 850 25.0 18.5 10.00 - 8.95
- G1HD024 820 23.2 17.2 10.00 - 8.80
- G1HD036 800 24.4 18.1 10.60 - 9.80 17 G1NA030S17H 800 23.6 17.5 10.00 - 9.00 21 G1NA030S21B 800 23.6 17.5 10.00 - 9.00
14,17 G1UA024S14,17 850 23.8 17.6 10.00 - 9.15
14 G1UA030S14 800 24.4 18.1 10.50 - 9.55 14 G1UA036S14 800 24.0 18.5 10.00 - 9.00
17,21 G1UA036S17,21 850 25.0 18.5 10.00 - 8.95 14,17 G2FD024S14,17 800 24.4 18.5 10.50 - 9.55
17 G2FD030S17 850 25.0 18.5 10.60 - 9.65 14 G2FD035S14 850 25.0 18.9 10.60 - 9.65 17 G2FD036S17 850 25.6 18.9 10.70 - 9.70 14 G1FA030S14 1000 28.0 20.7 10.00 - 9.30 14 G1FA036S14 1000 29.2 20.3 10.25 - 9.40
17,21 G1FA036S17,21 1000 29.0 21.5 10.45 - 9.45
- G1HD036 1000 29.6 21.9 10.00 - 9.55 17 G1NA030S17K 1000 29.0 20.4 10.00 - 9.30 21 G1NA030S21M 1050 29.0 20.4 10.00 - 9.20 14 G1UA036S14 1000 29.2 20.3 10.25 - 9.40
17,21 G1UA036S17,21 1000 29.0 21.5 10.45 - 9.45
17 G2FD030S17 1000 29.0 21.5 10.30 - 9.45 14 G2FD035S14 1000 29.0 21.5 10.30 - 9.45 21 G2FD036S21 1000 30.0 22.2 10.50 - 9.65 14 G1FA036S14 1200 33.6 24.9 10.00 - 9.10
17,21 G1FA036S17,21 1200 33.6 24.9 10.00 - 9.10
17 G1FA048S17 1200 35.0 25.9 10.30 - 9.40
21,24 G1FA048S21,24 1200 36.0 26.6 10.40 - 9.40
- G1HD036 1200 34.4 25.5 10.00 - 8.90
- G1HD048 1165 34.8 25.8 10.00 - 8.95 17 G1NA036S17J 1200 34.4 25.5 10.00 - 9.20 21 G1NA036S21C 1200 34.4 25.5 10.00 - 9.30 14 G1UA036S14 1200 33.6 24.9 10.00 - 9.10
17,21 G1UA036S17,21 1200 33.6 24.9 10.00 - 9.10
17 G1UA048S17 1200 35.0 25.9 10.30 - 9.40
21,24 G1UA048S21,24 1200 36.0 26.6 10.40 - 9.40
14 G2FD035S14 1200 33.4 24.7 10.00 - 9.10 17 G2FD036S17 1200 33.8 25.0 10.00 - 9.20 21 G2FD036S21 1200 33.8 25.0 10.00 - 9.20 21 G2FD042S21 1200 34.4 25.5 10.15 - 9.30 17 G2FD046S17 1200 34.4 25.5 10.15 - 9.30
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
COOLING
SEER + TXV
W/O TDR
SEER + TXV
+ TDR*
1
EER
4 Unitary Products Group
036-21121-002 Rev. A (0602)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils (Continued)
UNIT MODEL
FURNACE**
CFM RANGE
(MIN.-MAX.)
W
COIL
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
17,21 G1FA036S17,21 1200 33.6 24.9 10.00 - 9.10 21,24 G1FA048S21,24 1200 36.0 26.6 10.40 - 9.40
17 G1NA036S17J 1200 34.4 25.5 10.00 - 9.20
H1RA036S25,46
1050 1350
21 G1NA036S21C 1200 34.4 25.5 10.00 - 9.30 17,21 G1UA036S17,21 1200 33.6 24.9 10.00 - 9.10 21,24 G1UA048S21,24 1200 36.0 26.6 10.40 - 9.40
17 G2FD036S17 1200 33.8 25.0 10.00 - 9.20
21 G2FD036S21 1200 33.8 25.0 10.00 - 9.20
17 G1FA048S17 1380 40.0 30.2 10.00 - 9.05 21,24 G1FA048S21,24 1400 41.0 30.3 10.00 - 9.25 21,24 G1FA060S21,24 1400 42.0 31.0 10.00 - 9.45
- G1HD048 1390 40.5 30.0 10.00 - 9.05 21 G1NA036S21C 1400 40.0 28.3 10.00 - 9.15 21 G1NA048S21D 1400 40.5 28.6 10.00 - 9.15
H1RA042S06
1225 1575
17 G1UA048S17 1380 40.0 30.2 10.00 - 9.05
21,24 G1UA048S21,24 1400 41.0 30.3 10.00 - 9.25 21,24 G1UA060S21,24 1400 42.0 31.1 10.00 - 9.45
21 G2FD042S21 1400 39.5 29.2 10.00 - 9.00 17 G2FD046S17 1380 40.0 29.6 10.00 - 9.05
21,24 G2FD048S21,24 1450 41.0 30.3 10.10 - 9.15
24 G2FD060S24 1450 42.0 31.0 10.10 - 9.50
21,24 G1FA048S21,24 1400 41.0 30.3 10.00 - 9.25 21,24 G1FA060S21,24 1400 42.0 31.0 10.00 - 9.45
21 G1NA036S21C 1400 40.0 28.3 10.00 - 9.15 21 G1NA048S21D 1400 40.5 28.6 10.00 - 9.15
21,24 G1UA048S21,24 1400 41.0 30.3 10.00 - 9.25 21,24 G1UA060S21,24 1400 42.0 31.1 10.00 - 9.45
H1RA042S25,46
1225 1575
21 G2FD042S21 1400 39.5 29.2 10.00 - 9.00 17 G2FD046S17 1380 40.0 29.6 10.00 - 9.05
21,24 G2FD048S21,24 1450 41.0 30.3 10.10 - 9.15
17 G1FA048S17 1500 44.5 33.5 10.00 - 9.15
21,24 G1FA048S21,24 1600 45.5 33.7 10.00 - 9.45 21,24 G1FA060S21,24 1600 47.0 34.8 10.40 - 9.70
- G1HD048 1600 45.5 33.7 10.00 - 9.50
- G1HD060 1600 46.5 34.4 10.20 - 9.65 21 G1NA048S21D 1400 46.5 34.4 10.00 - 9.50 17 G1UA048S17 1500 44.5 33.5 10.00 - 9.15
21,24 G1UA048S21,24 1600 45.5 33.7 10.00 - 9.45
H1RA048S06
1400 1800
21,24 G1UA060S21,24 1600 47.0 34.8 10.40 - 9.70
17 G2FD046S17 1500 44.5 32.9 10.00 - 9.15
21,24 G2FD048S21,24 1600 46.0 34.0 10.10 - 9.50
24 G2FD060S24 1600 47.0 34.0 10.40 - 9.70
21,24 G1FA048S21,24 1600 45.5 33.5 10.00 - 9.45
H1RA048S25,46
1400 1800
21 G1NA048S21D 1400 46.5 34.4 10.00 - 9.50
21,24 G1UA048S21,24 1600 45.5 33.5 10.00 - 9.45 21,24 G2FD048S21,24 1600 46.0 34.0 10.10 - 9.50 21,24 G1FA060S21,24 1800 56.0 40.2 10.50 - 9.35
- G1HD060 2000 55.5 40.0 10.50 - 9.15 21 G1NA048S21D 1500 51.0 34.8 10.00 - 8.90 24 G1NA060S24T 1800 55.0 39.8 10.50 - 9.25
21,24 G1UA060S21,24 1800 56.0 40.2 10.50 - 9.35
H3RA060S06
1600 2100
24 G2FD060S24 1800 56.0 40.2 10.50 - 9.35 24 G2FD061H24 2000 57.0 40.9 10.50 - 9.35
21,24 G1FA060S21,24 1750 58.5 39.8 10.00 - 10.25
H1RA060S25,46
1525 1975
24 G1NA060S24T 1750 57.5 39.1 10.00 - 10.00
21,24 G1UA060S21,24 1750 58.5 39.8 10.00 - 10.25
24 G2FD060S24 1750 58.5 39.8 10.00 - 10.25
H1RA076S25,46 2500-3000 35 G2FD090S35*** 3200 73.5 52.9 -- -- 10.00 H1RA090S25,46 2500-3000 35 G2FD090S35*** 4000 90.0 64.8 -- -- 9.35
1 TXV = Use 1TV700 Series Kit.
* Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one.
** Refer to Quick Selection Chart for specific furnace match-up. *** This coil is for upflow application only.
COOLING
SEER + TXV
W/O TDR
SEER + TXV
+ TDR*
1
EER
Unitary Products Group 5
036-21121-002 Rev. A (0602)
COOLING PERFORMANCE
AIR TEMP ON CONDENSER
75°F95°F115°F75°F95°F115°F
MODEL
H1RA048S06
H1RA048S(25,46)
H3RA060S06
H1RA060S(25,46)
H1RA076S(25,46)
H1RA090S(25,46)
SUCT. T/P
@ COMPR.
35 61.5 39.9 4.18 32.3 4.63 27.0 4.94
35 61.5 49.4 4.15 43.8 5.13 38.2 6.34
35 61.5 54.4 4.46 50.5 4.74 46.3 5.08
35 61.5 77.4 5.06 63.4 6.08 50.6 7.35
35 61.5 84.0 8.28 72.9 9.11 61.7 9.87
MODEL
H1RA018S06
H1RA024S06
H2RA030S06
H2RA036S06
H1RA036 S(25,46)
H1RA042S06
H1RA042S(25,46)
SUCT. T/P
@ COMPR.
TEMP. PSIG MBH KW MBH KW MBH KW TEMP. PSIG MBH KW MBH KW MBH KW
35 61.5 16.2 1.66 13.1 1.84 11.0 1.96
40 68.5 17.7 1.67 14.9 1.88 12.8 2.04 40 68.5 43.6 4.21 36.7 4.73 31.4 5.14
45 76.0 19.3 169 16.7 1.92 14.2 2.11 45 76.0 47.6 4.26 41.1 4.84 34.9 5.32
50 84.0 20.8 1.70 18.5 1.96 15.9 2.18 50 84.0 51.1 4.28 45.5 4.94 39.0 5.48
35 61.521.02.2317.02.4614.22.63
40 68.5 22.9 2.24 19.3 2.52 16.5 2.74 40 68.5 54.0 4.19 48.2 5.14 42.3 6.35
45 76.0 25.0 2.27 21.6 2.58 18.3 2.83 45 76.0 58.4 4.27 52.4 5.25 46.3 6.47
50 84.0 26.8 2.28 23.9 2.63 20.5 2.92 50 84.0 62.7 4.32 56.9 5.38 50.2 5.61
35 61.525.12.6820.32.9717.03.17
40 68.5 27.4 2.70 23.1 3.04 19.7 3.30 40 68.5 60.1 4.44 56.0 4.83 51.6 5.18
45 76.0 29.9 2.74 25.8 3.10 21.9 3.41 45 76.0 65.8 4.53 61.6 4.92 56.9 5.26
50 84.0 32.1 2.75 28.6 3.17 24.5 3.51 50 84.0 71.9 4.62 67.5 5.01 62.6 5.36
35 61.530.53.2824.73.6420.63.88
40 68.5 33.3 3.31 28.1 3.72 24.0 4.04 40 68.5 84.5 5.21 69.2 6.23 55.4 7.49
45 76.0 36.4 3.35 31.4 3.80 26.7 4.18 45 76.0 91.8 5.37 75.3 6.38 60.3 7.64
50 84.0 39.1 3.36 34.8 3.88 29.9 4.31 50 84.0 99.4 5.54 81.7 6.55 65.6 7.80
35 61.535.83.8328.94.2524.24.53
40 68.5 39.1 3.86 32.9 4.34 28.2 4.72 40 68.5 92.5 8.50 80.8 9.41 68.9 10.26
45 76.0 42.6 3.90 36.8 4.53 31.3 4.87 45 76.0 101.3 8.73 89.0 9.72 76.5 10.66
50 84.0 45.8 3.93 40.8 4.63 35.0 5.03 50 84.0 110.4 8.95 97.5 10.03 84.4 11.08
NOTES:
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 1superheat and 1sub-cooling at condensing unit. a. Increase capacity 1% for each increase in sub-cooling. b. Decrease capacity 1% for each decrease in sub-cooling.
3. Sub-cooling in excess of 2may result in excessively high condensing temperature with air on condenser above 115°F. Maximum recommended condensing temperature is 140°F.
AIR TEMP ON CONDENSER
DIMENSIONS - 1 Phase
C
A
UNIT
MODEL
DIMENSIONS
(INCHES)
1
A
B C Liquid Vapor
018 17 35 23 024 17 35 23 5/8” 030 19 35 23 3/4” 036 19 35 23 3/4” 042 25 35 23 3/4” 048 27 37 27 7/8”
B
060 27 37 27 7/8”
REFRIGERANT
CONNECTION
LINE SIZE
5/8”
3/8”
DIMENSIONS - 3 Phase
UNIT
MODEL
DIMENSIONS
(INCHES)
1
A
B C Liquid Vapor
036 19 35 23 3/8” 3/4 042 25 35 23 3/8 3/4 048 27 37 27 3/8” 7/8 060 39 37 27 3/8” 7/8 076 26 43 32 1/2 1-1/8 090 32 43 32 1/2 1-1/8
1 Including Fan guard.
REFRIGERANT
CONNECTION
LINE SIZE
6 Unitary Products Group