York H-BE-F018 User Manual

TECHNICAL
TECHNICAL
GUIDE
GUIDE
SPLIT-SYSTEM AIR CONDITIONERS
14 SEER – R-22 MODELS:
H*BE-F018 THRU 060 (1.5 THRU 5 NOMINAL TONS)
ISO 9001
Certified Quality
Management System
LISTED
Visit us on the web at www.york.com Additional rating information can be found at
www.ahridirectory.org
332018-BTG-D-0208
DESCRIPTION
The 14 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be cus­tom-matched with one of UPG’s complete line of evaporator sections, with each serving a specific function. Matching Air Handlers are available for upflow, downflow, or horizontal applications to provide a complete system. Electric Heaters are available, if required. Add-On coils are availa ble for use with upflow, downflow, or horizontal furnaces and air han­dlers.
WARRANTY
5-year limited parts warranty.
10-year limited compressor warranty.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed of copper tube and aluminum fins.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi­tions occur. A liquid line filter-drier further protects the compressor.
DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and desert sand matted-textured finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimen­sion means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and com­pressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, a single panel covering the electrical controls, and the molex plug in the control box connecting the con­denser fan make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment cer­tification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
332018-BTG-D-0208
Physical and Electrical Data
MODEL HABE-F018S HDBE-F024S HCBE-F030S HABE-F036S HBBE-F042S HBBE-F048S HCBE-F060S
Unit Supply Voltage 208-230V, 1φ, 60Hz Normal Voltage Range
1
Minimum Circuit Ampacity 8.5 10.5 16.9 18.1 17.8 20.6 33.5 Max. Overcurrent Device Amps Min. Overcurrent Device Amps
2
3
15 15 25 25 30 35 50 15 15 20 20 20 25 35
Compressor Type Recip Recip Recip Scroll Scroll Scroll Scroll Compressor Amps
Rated Load 6.4 8.0 12.8 13.5 13.2 15.5 25.6
Locked Rotor 36 40.5 68 73 95 109 150 Crankcase Heater No No No No No No No Fan Motor Amps Rated Load 0.5 0.5 0.8 1.5 1.5 1.5 1.5 Fan Diameter Inches 22 22 22 22 24 24 24
Rated HP 1/15 1/15 1/8 1/4 1/4 1/4 1/4 Fan Motor
Nominal RPM 830 830 1075 850 850 850 850
Nominal CFM 2,100 2,000 2,800 3,300 3,300 3,300 3,600
Face Area Sq Ft 15.71 15.71 23.58 23.58 22.50 27.00 27.00 Coil
Rows Deep1111222
Fin /Inch 22 22 22 18 18 18 18 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 3/4 3/4 7/8 7/8 1 1/8 1 1/8 1 1/8
Unit Charge (Lbs - Oz)
4
5 - 9 6 - 0 8 - 2 9 - 14 14 - 15 15 - 5 16 - 5
Charge Per Foot, oz. 0.68 0.68 0.70 0.68 0.76 0.76 0.76 Operating Weight Lbs 170 181 193 219 240 264 279
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
187 to 252
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
C
Unit
Model
018 27 37 27
A
024 27 37 27 030 39 37 27 036 39 37 27 042 32 43 32 048 38 43 32
Dimensions
1
A
Refrigerant Connection
(Inches)
Service Valve Size
B C Liquid Vapor
3/8
3/4
7/8
1-1/8
060 38 43 32 7/8*
B
1. Included Fan Guard. * Adapter fitting required for 1-1/8” line set.
2 Unitary Products Group
332018-BTG-D-0208
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase
Outdoor Unit HABE-F018S HDBE-F024S HCBE-F030S HABE-F036S HBBE-F042S HBBE-F048S HCBE-F060S Required TXV
Factory Charge, lbs-oz 5 - 9 6 - 0 8 - 2 9 - 14 14 - 15 15 - 5 16 - 5
1
1TVM2A1 1TVM2A1 1TVM2A1 1TVM702 1TVM703 1TVM703 1TVM2C1
Indoor Coil
FC/MC/PC24A2A 0–––––– FC/MC/PC24B2A 0–––––– FC/MC/PC30A2A 0–––––– FC/MC/PC30B2A 0––—––– FC/MC/PC32A2A –0––––– FC/MC/PC35B2A –0––––– FC/MC/PC35C2A –0––––– FC/MC/PC36A2A ––0–––– FC/MC/PC36B2A ––0–––– FC/MC/PC36C2A ––0–––– FC/PC60C2C ––––––0* FC/MC/PC60D2C ––––––0* MC61D2C ––––––0 FC/MC62D2C ––––––0 HC30A2A 0–––––– HC36B2A –00–––– HC60D2C ––––––0* HD24A2A ––––––– HD36B2A –00–––– HD60D2C ––––––0* UC24A2A 0–––––– UC24B2A 0–––––– UC30A2A 0–––––– UC30B2A 0–––––– UC36A2A ––0–––– UC36B2A ––0–––– UC36C2A ––0–––– UC60C2C ––––––0* UC60D2C ––––––0* AHP24B2A 0–––––– AHP30B2A –00–––– AHP/SHP60D2C ––––––0 AV24B2A 0–––––– AV36C2A –00–––– AV/SV60D2C ––––––0 FC/MC/PC24A3X 2A + 0–––––– FC/MC/PC24B3X 2A + 0–––––– FC/MC/PC30A3X 2A + 0–––––– FC/MC/PC30B3X 2A + 0–––––– FC/MC/PC35B3X –2A + 0––––– FC/MC/PC35C3X –2A + 0––––– FC/MC/PC36A3X ––2A + 0–––– FC/MC/PC36B3X ––2A + 0–––– FC/MC/PC36C3X ––2A + 0–––– FC/MC/PC37C3X 702 + 9 – FC/MC/PC42B3X 702 + 0 – FC/MC/PC42X3X 702 + 0 – FC/MC/PC43B3X 702 + 9 – FC/MC/PC43C3X 702 + 9 – FC/MC/PC48C3X 702 + 12 703 + 9* – For Notes See Page 4.
2,3
TXV4 + Charge Adder, Oz
Unitary Products Group 3
332018-BTG-D-0208
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)
Outdoor Unit HABE-F018S HDBE-F024S HCBE-F030S HABE-F036S HBBE-F042S HBBE-F048S HCBE-F060S Required TXV
Factory Charge, lbs-oz 5 - 9 6 - 0 8 - 2 9 - 14 14 - 15 15 - 5 16 - 5
1
1TVM2A1 1TVM2A1 1TVM2A1 1TVM702 1TVM703 1TVM703 1TVM2C1
Indoor Coil
FC/MC/PC48D3X 702 + 12 703 + 9* – FC/PC60C3X ––––703 + 13 703 + 6* 2C + 0* FC/MC/PC60D3X ––––703 + 13 703 + 6* 2C + 0* MC61D3X –––––703 + 13 2C + 0 FC/MC62D3X –––––703 + 13 2C + 0 HC30A3X 2A + 0–––––– HC36B3X –2A + 02A + 0–––– HC42C3X 702 + 9 703 + 6* – HC60D3X ––––703 + 13 703 + 6* 2C + 0* HD24A3X ––––––– HD36B3X 2A + 0 2A + 0 702 + 5 – HD48C3X ––––703 + 0* 703 + 0* – HD60D3X ––––––2C + 0* UC24A3X 2A + 0–––––– UC24B3X 2A + 0–––––– UC30A3X 2A + 0–––––– UC30B3X 2A + 0–––––– UC36A3X ––2A + 0–––– UC36B3X ––2A + 0–––– UC36C3X ––2A + 0–––– UC42B3X 702 + 0 – UC42C3X 702 + 0 – UC48C3X 702 + 12 703 + 9* – UC48D3X 702 + 12 703 + 9* – UC60C3X ––––703 + 13 703 + 6* 2C + 0* UC60D3X ––––703 + 13 703 + 6* 2C + 0* AHP24B3X 2A + 0–––––– AHP30B3X –2A + 02A + 0–––– AHP42C3X 702 + 9 – AHP/SHP48D3X ––––703 + 13 703 + 6* – AHP/SHP60D3X 702 + 17 703 + 13 703 + 6 2C + 0 AV24B3X 2A + 0–––––– AV36C3X 2A + 0 2A + 0 702 + 9 – AV/SV48D3X ––––703 + 13 703 + 6 – AV/SV60D3X ––––703 + 13 703 + 6 2C + 0 F*FP040 ––2A + 0–––– F4FV060H06T2C –––––703 + 6 0
FOOTNOTES:
PROCEDURES:
2,3
1. A TXV kit must be used with these coils to obtain system performance.
2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
3. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
4. If no TXV is listed, the indoor coil has the correct valve factory installed.
* Does not achieve 14 SEER with PSC furnaces. For ratings, see technical guide or visit www.aridirectory.org/ari/unitary.html
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of
interconnecting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
TXV4 + Charge Adder, Oz
4 Unitary Products Group
332018-BTG-D-0208
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
MODEL W
COIL MODEL
1
RATED
CFM
TOTAL SENS.
1 PH 14 SEER AC WITH MA
HABE-F018S
MA08B 17 FC/MC24B 600 17.5 12.1 14.00 12.00 MA08B 17 FC/MC30B 600 17.5 12.1 14.00 12.00
HDBE-F024S MA08B 17 FC/MC35 B 800 23.0 16.6 14.00 12.00 HCBE-F030S MA12B 17 FC/MC36 B 1000 29.0 20.0 14.00 12.00
HABE-F036S
MA14D 24 FC/MC42D 1200 35.0 25.6 14.00 11.50 MA14D 24 FC/MC48D 1200 35.2 25.7 14.00 11.50 MA14D 24 FC/MC48D 1400 39.5 28.9 13.50 11.00
HBBE-F042S
MA14D 24 FC/MC60D 1400 40.5 29.6 14.00 11.50 MA16C 21 FC60C 1400 40.5 29.6 14.00 11.50 MA16C 21 FC/MC48C 1600 45.0 33.2 13.50 11.00 MA20D 24 FC/MC48D 1600 45.0 33.2 13.50 11.00
HBBE-F048S
MA16C 21 FC60C 1600 46.5 33.9 13.85 11.00 MA20D 24 FC/MC60D 1600 46.5 33.9 13.85 11.00 MA20D 24 MC61D 1600 47.0 34.3 14.00 11.50 MA20D 24 FC/MC60D 1800 55.0 38.5 14.00 12.00
HCBE-F060S
MA20D 24 MC61D 1800 55.5 38.9 14.00 11.50 MA20D 24 FC/MC62D 1800 55.5 38.9 14.00 11.50
1 PH 14 SEER AC WITH MV - VARIABLE SPEED
HABE-F018S
MV12B 17 FC/MC24B 600 17.8 12.1 15.00 12.00 MV12B 17 FC/MC30B 600 17.8 12.1 15.00 12.00
HDBE-F024S MV12B 17 FC/MC35 B 800 23.4 16.7 15.00 12.00 HCBE-F030S
HABE-F036S
HBBE-F042S
HBBE-F048S
MV12B 17 FC/MC36B 1000 29.4 19.9 15.00 12.00 MV16C 21 FC/MC36C 1000 29.4 19.9 15.00 12.00 MV16C 21 FC/MC42C 1250 35.2 25.6 15.00 12.00 MV16C 21 FC/MC48C 1285 36.0 25.7 15.00 12.00 MV16C 21 FC/MC48C 1420 40.5 28.9 14.50 12.00 MV20D 24 FC/MC60D 1420 41.5 29.6 15.00 12.00 MV20D 24 FC/MC48D 1590 46.0 33.2 14.50 12.00 MV20D 24 FC/MC60D 1600 47.0 33.9 14.65 12.00 MV20D 24 FC/MC60D 1800 55.0 37.5 14.25 12.00
HCBE-F060S
MV20D 24 MC61D 1800 55.5 37.9 14.25 12.00 MV20D 24 FC/MC62D 1800 55.5 37.9 14.25 12.00
1 PH 13 SEER AC WITH AV / SV / FV - VARIABLE SPEED
HABE-F018S AV24 17 600 17.8 12.1 15.00 12.00 HDBE-F024S AV36 21 800 23.4 16.7 15.00 12.00 HCBE-F030S AV36 21 1000 29.4 19.9 15.00 12.00 HABE-F036S AV36 21 1200 35.2 25.6 15.00 12.00
HBBE-F042S
AV/SV48 24 1400 40.5 29.0 15.00 12.00 AV/SV60 24 1400 40.5 29.0 15.00 12.00 AV/SV48 24 1600 46.5 33.2 15.00 12.00
HBBE-F048S
AV/SV60 24 1600 46.0 33.2 15.00 12.00 F*FV060 24 1625 46.5 34.9 15.00 12.50
HCBE-F060S
AV/SV60 24 1800 55.0 37.5 14.25 11.50 F*FV060 24 1850 55.0 39.2 14.10 11.50
1 PH 14 SEER AC WITH AHP / F*FP
HABE-F018S AHP24 17 655 18.0 12.7 15.00 12.00 HDBE-F024S AHP30 17 830 23.0 16.7 14.00 12.00
HCBE-F030S
HABE-F036S
HBBE-F042S
HBBE-F048S
AHP30 17 1015 29.6 24.0 14.00 12.00
F*FP040 21 1015 29.6 24.0 14.00 12.00
AHP36 21 1200 35.0 25.1 14.00 12.00
AHP42 21 1200 35.0 25.1 14.00 11.50
AHP/SHP48 24 1400 40.5 29.8 14.00 12.00 AHP/SHP60 24 1400 40.5 29.8 14.00 12.00 AHP/SHP48 24 1600 46.5 33.6 13.85 11.00 AHP/SHP60 24 1600 46.5 33.6 14.00 12.00
HCBE-F060S AHP/SHP60 24 1850 55.0 39.2 14.00 12.00
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total ele ctric power input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
Go to www.ari.org/aridirectory for the latest additional matches.
Unitary Products Group 5
COOLING
NET MBH
SEER EER