York H1RA042S06, H2RA030S06, H1RA048S06, H3RA060S06, H1RA036S25 Technical Manual

...
Page 1
®
TECHNICAL GUIDE
SPLIT-SYSTEM AIR CONDITIONERS 10 SEER MODELS: H*RA018 THRU 060
(1.5 THRU 5 NOMINAL TONS, 1 PH) H*RA036 THRU 090
(3 THRU 7.5 NOMINAL TONS, 3 PH)
MODELS: 018 - 060 (1 PH & 3 PH)
O
T
A
R
D
I
E
I
A
F
S
I
T
R
C
E
O
C
M
A
P
I
R
R
-
L
C
E
O
Y
N
R
Y
I
D
R
I
U
A
T
T
I
C
N
U
A
F
U
N
A
M
C E
R T
I
A
R
This product was manufactured in a plant whose quality system is certified/registered as being in conformity with ISO 9001.
I
Certification applies only
when the complete
system is listed
Due to continuous product improvement, specifica­tions are subject to change without notice.
Visit us on the web at www.york.com for the most up-to-date technical information.
Additional rating information can be found at www.ariprimenet.org.
R
E
Q
U
I
P
M
F
I
C
A
T
I
O
N
S
T
A
N
with ARI.
N
T
G
I
O
N I
W
N
I
G
T
H
T
F
N
E
O
S
N
O
I
T
0
C
E
S
1
2
D
R
A
D
LISTED
036-21121-002 Rev. B (0103)
DESCRIPTION
The 10 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be cus­tom-matched with one of UPG’s complete line of evaporator sections, each designed to serve a specific function. Match­ing Air Handlers are available for upflow, downflow or hori­zontal applications to provide a complete system. Electric Heaters are available if required. Add-On coils are available for use with upflow, downflow or horizontal furnaces and air handlers.
WARRANTY
Single Phase Units:
5-year limited parts warranty. 5-year limited compressor warranty.
Three Phase Units:
1-year limited parts warranty. 5-year limited compressor warranty.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed of enhanced copper tube and aluminum fins.
COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi­tions occur. A liquid line filter-drier further protects the compressor.
DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a bet­ter paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted desert sand fin­ish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connec­tions. Discharge line heat exchanger knockouts are pro­vided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, a single panel covering the electrical controls and the molex plug in the control box connecting the con­denser fan, make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment cer­tification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
036-21121-002 Rev. B (0103)
Physical and Electrical Data - 1 Phase
MODEL
Unit Supply Voltage 208/230 – 1 – 60
Normal Voltage Range
Minimum Circuit Ampacity 12.5 15.6 17.5 21.5 26.1 30.1 37.3
Max. Overcurrent Device Amps
Compressor Type
Compressor Amps
Crankcase Heater No No No No No No No
Fan Motor Amps Rated Load 0.5 0.5 0.5 1.4 1.4 1.3 1.3
Fan Diameter Inches 18 18 18 18 18 22 22
Fan Motor
Face Area Sq. Ft. 8.00 8.00 9.15 9.15 12.58 15.72 15.72
Coil
Rows Deep 1111111
Fin / Inches 14 14 18 18 18 18 22
Liquid Line OD 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line OD 5/8 5/8 3/4 3/4 3/4 7/8 7/8
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.
Operating Weight Lbs. 118 123 135 137 161 176 188
1
3
Rated Load 9.6 12.1 13.6 16.1 19.8 23 28.8
Locked Rotor 54 57 73 82 97 110 160
Rated HP 1/12 1/12 1/12 1/4 1/4 1/4 1/4
Nominal RPM 1,100 1,100 1,100 1,100 1,100 850 850
Nominal CFM 1,850 1,850 1,900 2,750 2,750 3,250 3,300
4
4
H1RA018S06 H1RA024S06 H2RA030S06 H2RA036S06 H1RA042S06 H1RA048S06 H3RA060S06
187 to 252
2
20 25 30 35 40 45 60
Recip Recip Recip Recip Recip Recip
Scroll
3 - 6 3 - 11 3 - 14 3 - 15 5 - 4 7 - 5 6 - 2
0.66 0.66 0.68 0.68 0.68 0.70 .070
B
Physical and Electrical Data - 3 Phase
MODEL
H1RA
036S25
Unit Supply Voltage
Normal Voltage Range
1
Minimum Circuit Ampacity 15.0 17.4 17.3 21.3 25.8 37.7 8.0 8.4 8.3 10.8 13.0 18.1
Max. Overcurrent Device Amps
3
Compressor Type
Compressor Amps
Rated Load 10.9 12.8 11.7 16.0 18.9 29.4 5.8 6.1 6.1 8.0 9.5 14.0
Locked Rotor 78 78 78 125 146 260 40 39 39 67 73 128
2
Recip Recip Recip
Crankcase Heater No No No No No Yes No No No No No Yes
Fan Motor Amps Rated Load 1.4 1.4 1.3 1.3 2.2 4.6 .8 .8 .7 .8 1.2 2.3
Fan Diameter Inches 18 18 22 22 24 24 18 18 22 22 24 24
Rated HP 1/4 1/4 1/4 1/4 1/3 3/4 1/4 1/4 1/5 1/4 1/3 3/4
Fan Motor
Nominal RPM 1,100 1,100 850 850 1100 1100 1,100 1,100 850 850 1100 1100
Nominal CFM 2,750 2,750 3,250 3,450 4000 5000 2,750 2,750 3,250 3,450 4000 5000
Face Area Sq. Ft. 9.15 12.58 15.72 23.58 18.0 22.5 9.15 12.58 15.72 23.58 18.0 22.5
Coil
Rows Deep 111122111122
Fin / Inches 18 18 18 18 16 16 18 18 18 18 16 16
Liquid Line OD 3/8 3/8 3/8 3/8 1/2 1/2 3/8 3/8 3/8 3/8 1/2 1/2
Vapor Line OD 3/4 3/4 7/8 7/8 1-1/8 1-1/8 3/4 3/4 7/8 7/8 1-1/8 1-1/8
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.
4
4
3 - 15 5 - 4 7 - 5 9 - 7 12-3 15-3 3 - 15 5 - 4 7 - 5 9 - 7 12-3 15-3
Operating Weight Lbs. 170 176 206 228 219 368 170 176 206 228 219 368
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot valve.
H1RA
042S25
H1RA
048S25
H1RA
060S25
208/230 – 3 – 60
H1RA
076S25
H1RA
090S25
H1RA
036S25
H1RA
042S46
H1RA
048S46
460 - 3 - 60
H1RA
060S46
H1RA
076S46
H1RA
090S46
187 to 252 432 to 504
25 30 30 35 40 50 15 15 15 15 20 25
ScrollBScroll
B
Dual Recip Recip Recip
Scroll
B
Scroll
B
Dual
.68 .68 .70 .70 1.26 1.26 .68 .68 .70 .70 1.26 1.26
2 Unitary Products Group
Page 3
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 PHASE
036-21121-002 Rev. B (0103)
Outdoor Unit
Unit Orifice (s)
Factory R-22 Charge, lbs-oz 3 - 6 3 - 11 3 - 14 3 - 15 5 - 4 7 - 5 6 - 2
1
Indoor Coil Coil Orifice
G2FD024(S,H)14/176153 + 1459 + 6— ————
G2FD030(S,H)176553 + 23 59 + 867 + 3————
G2FD035(S,H)14 65 53 + 23 59 + 8 67 + 3 71 + 0
G2FD036(S,H)17 75 59 + 12 67 + 6 71 + 3
G2FD036(S,H)21 75 69 + 9 71 + 3
G2FD042(S,H)21 78 71 + 7 75 + 1
G2FD046(S,H)17 78 71 + 7 75 + 1 78 + 6
G2FD048(S,H)21/2478———— 75 + 981 + 15—
G2FD060(S,H)2490————78 + 1481 + 2096 + 6
G1HD024 59 55 + 6 61 + 1
G1HD036 69 63 + 7 67 + 7 73 + 9
G1HD048 81 73 + 15 78 + 8 78 + 9
G1HD060 93 81 + 16 96 + 1
G1FA/G1UA024S14/175955 + 359 + 0— ————
G1FA/G1UA030S146553 + 1459 + 665 + 0————
G1FA/G1UA036S14 73 59 + 4 67 +4 73 + 0
G1FA/G1UA03617/21 73 59 + 4 67 + 2 73 + 0
G1FA/G1UA048S17 84 75 + 11 75 + 1 81 + 13
G1FA/G1UA048S21 84 75 + 11 81 + 7 81 + 13
G1FA/G1UA060S24 90 81 + 14 81 + 20 96 + 6
G1NA024S17G 5151 + 0— —————
G1NA030S17H 57—57 + 0—————
G1NA030S17K 63— —63 + 4————
G1NA030S21B 57—57 + 0 —————
G1NA030S21M 63——63 + 4————
G1NA036S17J 67———67 + 7———
G1NA036S21C 67———67 + 7———
G1NA048S21D 78————78 + 078 + 4—
G1NA048S24P 78————78 + 078 + 4—
G1NA060S24T 87 96 + 0
G1NF024SOF 63
G1NF036SOF 67
G1NF048SOF 78————
G1NF060SOF 87——————96 + 11
F2RP/F2FP018 5351 + 0————— —
F2RC/F2FC024 6155 + 3——————
F2RP/F2FP024 6155 + 661 + 0—————
F2RP/F2FP030 65— 61 + 267 + 2————
F2RC/F2FC036 75 71 + 0
F2RP/F2FP036 75 67 + 8 73 + 4
F2RP/F2FP042 78 73 + 8 75 + 1
F2FP048 84————73 + 8 87 + 6—
F2FP060 90————— 87 + 1096 + 6
FOOTNOTES:
1. These orifices are packed in the customer packet of each outdoor unit.
2. These orifices are factory mounted in the flow control device of each indoor coil.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011 .
H1RA018S06 H1RA024S06 H2RA030S06 H2RA036S06 H1RA042S06 H1RA048S06 H3RA060S06
51,53,55 59,61,63 67 71,73,75 75,78,81 78,81,84,87 96
2
57 + 0
System Orifice - Additional Charge, Oz
3
63 + 4
3
———
67 + 7
3
———
78 + 0
3
78 + 4
3
PROCEDURES:
ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line tubing.
2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaportor + adder for line set.
5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
Unitary Products Group 3
Page 4
036-21121-002 Rev. B (0103)
Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 PHASE
ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS
Outdoor Unit H1RA036 H1RA042 H1RA048 H1RA060 H1RA076 H1RA090
Unit Orifice (s)
Factory R-22 Charge, lbs-oz 3 - 15 5 - 4 7 - 5 9 - 7 12 - 3 15 - 3
1
67, 71, 73 75, 78, 81 81 90
Indoor Coil
Coil Orifice
2
System Orifice + Additional Charge, Oz
G1NA036S17J 67 61 + 2 —————
G1NA036S21C 67 61 + 2 —————
G1NA048S21D 78 78 + 0 78 + 4
G1NA048S24P 78 78 + 0 78 + 4
G1NA060S24T 87 87 + 0
G1FA/G1UA03617/21 73 61 + 0 —————
G1FA/G1UA048S17 84 78 + 5 ————
G1FA/G1UA048S21 84 63 + 13 78 + 6 81 + 13
G1FA/G1UA060S24 90 78 + 16 90 + 5
G2FD036(S,H)17 75 61 + 3 —————
G2FD036(S,H)21 75 61 + 5 —————
G2FD042(S,H)21 78 78 + 0 ————
G2FD046(S,H)17 78 78 + 5 ————
G2FD048(S,H)21/24 78 78 + 9 81 + 15
G2FD060(S,H)24 90 90 + 5
F2RC036 7561 + 0—————
F2RP042 78
78 + 0
702 + 0
————
F2FP048 84 78 + 9 81 + 15
F2FP060 90 90 + 5
K4EU090KDBC090
TXV
3
———— 0 0
Footnotes:
1. These orifices are packed in the instruction/warranty packet of each outdoor unit.
2. These orifices are factory mounted in the flow control device of each indoor coil.
3. The TXV is factory mounted in the coil or air handler.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line tubing.
2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaportor + adder for line set.
5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
4 Unitary Products Group
Page 5
036-21121-002 Rev. B (0103)
COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
MODEL
AIR HANDLER
ELECTRIC
HEAT KW
2
W
COIL
MODEL
1
RATED
CFM
NET MBH
TOTAL SENS.
1 PH 10 SEER AC WITH N1AH / G2FD
H1RA018S06 N1AHB0806 2,5,8,10 17 G2FD024(S,H)17 650 19.0 14.1 10.50 - 9.80
H1RA024S06
H2RA030S06
H2RA036S06
H1RA042S06
H1RA048S06
N1AHB0806 2,5,8,10 17 G2FD024(S,H)17 800 24.4 18.1 10.50 - 9.55 N1AHB0806 2,5,8,10 17 G2FD030(S,H)17 850 25.0 18.5 10.60 - 9.65 N1AHB1206 5,8,10,15,19 17 G2FD030(S,H)17 1000 29.0 21.5 10.30 - 9.45 N1AHB1206 5,8,10,15,19 17 G2FD036(S,H)17 1000 30.0 22.2 10.50 - 9.65 N1AHB1206 5,8,10,15,19 17 G2FD036(S,H)17 1200 33.8 25.0 10.00 - 9.20
N1AHB1206 5,8,10,15,19 17 G2FD046(S,H)17 1200 34.4 25.5 10.15 - 9.30 N1AHC1606 5,8,10,15,20 21 G2FD042(S,H)21 1400 39.5 29.2 10.00 - 9.00 N1AHC1606 5,8,10,15,20 21 G2FD048(S,H)21 1450 41.0 30.3 10.10 - 9.15 N1AHC1606 5,8,10,15,20 21 G2FD048(S,H)21 1600 46.0 34.0 10.10 - 9.50 N1AHD2006 8,10,15,20,25,30 24 G2FD060(S,H)24 1600 47.0 34.8 10.40 - 9.70
H3RA060S06 N1AHD2006 8,10,15,20,25,30 24 G2FD060(S,H)24 1800 56.0 40.2 10.50 - 9.35
3 PH 10 SEER AC WITH N1AH / G2FD
H1RA036 S(25,46)
H1RA042S(25,46)
N1AHB1246 10,15 21 G2FD036(S,H)17 1200 33.8 25.0 10.00 - 9.20
N1AHB1246 10,15 21 G2FD042(S,H)21 1400 40.0 30.1 10.00 9.05 N1AHC1646 10,15 21 G2FD042(S,H)21 1400 39.5 29.2 10.00 - 9.00 N1AHC1646 10,15 24 G2FD048(S,H)21 1450 41.0 30.3 10.10 - 9.15 N1AHC1646 10,15 21 G2FD048(S,H)21 1600 46.0 34.0 10.10 - 9.50
H1RA048S(25,46)
N1AHD2046 10,15,29 24 G2FD048(S,H)24 1600 24.6 34.0 10.10 - 9.50 N1AHD2046 10,15,29 24 G2FD048(S,H)24 1600 46.0 34.0 10.10 - 9.50
H1RA060S(25,46) N1AHD2046 10,15,29 24 G2FD060(S,H)24 1750 58.5 39.8 10.00 - 10.25
1 PH 10 SEER AC / F2RP / RC / FC
4,5
F2RC/F2FC024 5,8,10 18 - 650 17.4 12.9 10.00 - 9.00
H1RA018S06
F2RP/F2FP018 2,5,8 18 - 650 17.4 12.3 10.00 - 9.00 F2RP/F2FP024 5,8,10 18 - 650 17.4 12.9 10.00 - 9.00
H1RA024S06
H2RA030S06
F2RP/F2FP024 5,8,10 18 - 800 23.4 17.3 10.00 - 9.00 F2RP/F2FP030 5,8,10,15 18 - 800 23.6 17.5 10.00 - 9.10 F2RP/F2FP030 5,8,10,15 18 - 1000 28.4 21.0 10.00 - 9.50 F2RP/F2FP036 5,8,10,15,19 21 - 1000 28.0 20.0 10.00 - 9.00 F2RC/F2FC036 5,8,10,15 21 - 1200 33.6 21.5 10.00 - 9.10
H2RA036S06
F2RP/F2FP036 5,8,10,15,19 21 - 1200 34.4 25.2 10.20 - 9.30 F2RP/F2FP042 5,8,10,15 21 - 1200 34.4 25.2 10.15 - 9.20
H1RA042S06
H1RA048S06
F2RP/F2FP042 5,8,10,15 21 - 1400 39.5 28.9 10.00 - 9.00
F2FP048 5,8,10,15,20,25 24 - 1400 40.5 30.0 10.00 - 9.20 F2FP048 5,8,10,15,20,25 24 - 1600 45.5 33.7 10.00 - 9.15 F2FP060 5,8,10,15,20,25 24 - 1600 46.5 34.4 10.00 - 9.70
H3RA060S06 F2FP060 5,8,10,15,20,25 24 - 1800 56.0 41.0 10.00 - 9.15
3 PH 10 seer AC with F2RP / FP
H1RA036 S(25,46)
H1RA042S(25,46)
H1RA048S(25,46)
H1RA060S(25,46)
F2RC/F2FC036 5,8,10,15 21 - 1200 33.6 25.2 10.00 - 9.10 F2RP/F2FP042 5,8,10,15 21 - 1400 39.0 29.2 10.00 - 9.00
F2FP048 5,8,10,15,20,25 24 - 1400 40.5 30.4 10.00 - 9.00 F2FP048 5,8,10,15,20,25 24 - 1600 45.5 33.7 10.00 - 9.15 F2FP060 5,8,10,15,20,25 24 - 1750 58.5 39.8 10.00 - 9.80
3 PH 10 seer AC WITH K4EV
6
H1RA076S25,46 K4EV090 10,16,26,36 22 -- 2600 73.5 -- -- -- 10.00
H1RA090S25,46 K4EV090 10,16,26,36 22 -- 3280
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters. Three phase units require three phase 2HK heaters.
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC
5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.
6. H*BA-(T,W)090 is field convertible to two stage operation. Its IPLV = 11.2. — = Not Applicable.
.
models. All ratings remain the same.
53.8/
89.0
COOLING
SEER
W/O TXV
SEER
+ TXV
-- -- --
EER
3
9.63/
9.30
Unitary Products Group 5
Page 6
036-21121-002 Rev. B (0103)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils
UNIT MODEL
H1RA018S06
H1RA024S06
H2RA030S06
H2RA036S06
For Notes See Page 5.
FURNACE**
CFM RANGE
(MIN.-MAX.)
575 725
700 900
875
1125
1050 1350
COIL
W
14,17 G1FA024S14,17 650 18.0 13.3 10.00 - 9.20
14 G1FA030S14 650 19.0 14.1 10.50 - 9.80
- G1HD024 655 18.5 13.7 10.50 - 10.00
17 G1NA024S17G 650 18.0 12.5 10.00 - 9.40
14,17 G1UA024S14,17 650 18.0 13.3 10.00 - 9.20
14 G1UA030S14 650 19.0 14.1 10.50 - 9.80
14,17 G2FD024(S,H)14,17 650 19.0 14.1 10.50 - 9.80
17 G2FD030(S,H)17 650 19.4 14.4 10.50 - 9.90 14 G2FD035(S,H)14 650 19.4 14.4 10.50 - 9.90
14,17 G1FA024S14,17 850 23.8 17.6 10.00 - 9.15
14 G1FA030S14 800 24.4 18.1 10.50 - 9.55 14 G1FA036S14 800 24.0 18.1 10.00 - 9.00
17,21 G1FA036S17,21 850 25.0 18.5 10.00 - 8.95
- G1HD024 820 23.2 17.2 10.00 - 8.80
- G1HD036 800 24.4 18.1 10.60 - 9.80 17 G1NA030S17H 800 23.6 17.5 10.00 - 9.00 21 G1NA030S21B 800 23.6 17.5 10.00 - 9.00
14,17 G1UA024S14,17 850 23.8 17.6 10.00 - 9.15
14 G1UA030S14 800 24.4 18.1 10.50 - 9.55 14 G1UA036S14 800 24.0 18.5 10.00 - 9.00
17,21 G1UA036S17,21 850 25.0 18.5 10.00 - 8.95 14,17 G2FD024(S,H)14,17 800 24.4 18.5 10.50 - 9.55
17 G2FD030(S,H)17 850 25.0 18.5 10.60 - 9.65 14 G2FD035(S,H)14 850 25.0 18.9 10.60 - 9.65 17 G2FD036(S,H)17 850 25.6 18.9 10.70 - 9.70 14 G1FA030S14 1000 28.0 20.7 10.00 - 9.30 14 G1FA036S14 1000 29.2 20.3 10.25 - 9.40
17,21 G1FA036S17,21 1000 29.0 21.5 10.45 - 9.45
- G1HD036 1000 29.6 21.9 10.00 - 9.55 17 G1NA030S17K 1000 29.0 20.4 10.00 - 9.30 21 G1NA030S21M 1050 29.0 20.4 10.00 - 9.20 14 G1UA036S14 1000 29.2 20.3 10.25 - 9.40
17,21 G1UA036S17,21 1000 29.0 21.5 10.45 - 9.45
17 G2FD030(S,H)17 1000 29.0 21.5 10.30 - 9.45 14 G2FD035(S,H)14 1000 29.0 21.5 10.30 - 9.45 21 G2FD036(S,H)21 1000 30.0 22.2 10.50 - 9.65 14 G1FA036S14 1200 33.6 24.9 10.00 - 9.10
17,21 G1FA036S17,21 1200 33.6 24.9 10.00 - 9.10
17 G1FA048S17 1200 35.0 25.9 10.30 - 9.40
21,24 G1FA048S21 1200 36.0 26.6 10.40 - 9.40
- G1HD036 1200 34.4 25.5 10.00 - 8.90
- G1HD048 1165 34.8 25.8 10.00 - 8.95 17 G1NA036S17J 1200 34.4 25.5 10.00 - 9.20 21 G1NA036S21C 1200 34.4 25.5 10.00 - 9.30 14 G1UA036S14 1200 33.6 24.9 10.00 - 9.10
17,21 G1UA036S17,21 1200 33.6 24.9 10.00 - 9.10
17 G1UA048S17 1200 35.0 25.9 10.30 - 9.40
21,24 G1UA048S21 1200 36.0 26.6 10.40 - 9.40
14 G2FD035(S,H)14 1200 33.4 24.7 10.00 - 9.10 17 G2FD036(S,H)17 1200 33.8 25.0 10.00 - 9.20 21 G2FD036(S,H)21 1200 33.8 25.0 10.00 - 9.20 21 G2FD042(S,H)21 1200 34.4 25.5 10.15 - 9.30 17 G2FD046(S,H)17 1200 34.4 25.5 10.15 - 9.30
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
COOLING
SEER
W/O TXV
SEER + TXV
1
EER
6 Unitary Products Group
Page 7
036-21121-002 Rev. B (0103)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils (Continued)
UNIT MODEL
FURNACE**
CFM RANGE
(MIN.-MAX.)
W
COIL
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
17,21 G1FA036S17,21 1200 33.6 24.9 10.00 - 9.10 21,24 G1FA048S21 1200 36.0 26.6 10.40 - 9.40
17 G1NA036S17J 1200 34.4 25.5 10.00 - 9.20
H1RA036S25,46
1050 1350
21 G1NA036S21C 1200 34.4 25.5 10.00 - 9.30 17,21 G1UA036S17,21 1200 33.6 24.9 10.00 - 9.10 21,24 G1UA048S21 1200 36.0 26.6 10.40 - 9.40
17 G2FD036(S,H)17 1200 33.8 25.0 10.00 - 9.20
21 G2FD036(S,H)21 1200 33.8 25.0 10.00 - 9.20
17 G1FA048S17 1380 40.0 30.2 10.00 - 9.05 21,24 G1FA048S21 1400 41.0 30.3 10.00 - 9.25 21,24 G1FA060S21,24 1400 42.0 31.0 10.00 - 9.45
- G1HD048 1390 40.5 30.0 10.00 - 9.05 21 G1NA036S21C 1400 40.0 28.3 10.00 - 9.15 21 G1NA048S21D 1400 40.5 28.6 10.00 - 9.15
H1RA042S06
1225 1575
17 G1UA048S17 1380 40.0 30.2 10.00 - 9.05
21,24 G1UA048S21 1400 41.0 30.3 10.00 - 9.25 21,24 G1UA060S21,24 1400 42.0 31.1 10.00 - 9.45
21 G2FD042(S,H)21 1400 39.5 29.2 10.00 - 9.00 17 G2FD046(S,H)17 1380 40.0 29.6 10.00 - 9.05
21,24 G2FD048(S,H)21,24 1450 41.0 30.3 10.10 - 9.15
24 G2FD060(S,H)24 1450 42.0 31.0 10.10 - 9.50
21,24 G1FA048S21 1400 41.0 30.3 10.00 - 9.25 21,24 G1FA060S21,24 1400 42.0 31.0 10.00 - 9.45
21 G1NA036S21C 1400 40.0 28.3 10.00 - 9.15 21 G1NA048S21D 1400 40.5 28.6 10.00 - 9.15
21,24 G1UA048S21 1400 41.0 30.3 10.00 - 9.25 21,24 G1UA060S21,24 1400 42.0 31.1 10.00 - 9.45
H1RA042S25,46
1225 1575
21 G2FD042(S,H)21 1400 39.5 29.2 10.00 - 9.00 17 G2FD046(S,H)17 1380 40.0 29.6 10.00 - 9.05
21,24 G2FD048(S,H)21,24 1450 41.0 30.3 10.10 - 9.15
17 G1FA048S17 1500 44.5 33.5 10.00 - 9.15
21,24 G1FA048S21 1600 45.5 33.7 10.00 - 9.45 21,24 G1FA060S21,24 1600 47.0 34.8 10.40 - 9.70
- G1HD048 1600 45.5 33.7 10.00 - 9.50
- G1HD060 1600 46.5 34.4 10.20 - 9.65 21 G1NA048S21D 1400 46.5 34.4 10.00 - 9.50 17 G1UA048S17 1500 44.5 33.5 10.00 - 9.15
21,24 G1UA048S21 1600 45.5 33.7 10.00 - 9.45
H1RA048S06
1400 1800
21,24 G1UA060S21,24 1600 47.0 34.8 10.40 - 9.70
17 G2FD046(S,H)17 1500 44.5 32.9 10.00 - 9.15
21,24 G2FD048(S,H)21,24 1600 46.0 34.0 10.10 - 9.50
24 G2FD060(S,H)24 1600 47.0 34.0 10.40 - 9.70
21,24 G1FA048S21 1600 45.5 33.5 10.00 - 9.45
H1RA048S25,46
1400 1800
21 G1NA048S21D 1400 46.5 34.4 10.00 - 9.50
21,24 G1UA048S21 1600 45.5 33.5 10.00 - 9.45 21,24 G2FD048(S,H)21,24 1600 46.0 34.0 10.10 - 9.50 21,24 G1FA060S21,24 1800 56.0 40.2 10.50 - 9.35
- G1HD060 2000 55.5 40.0 10.50 - 9.15 21 G1NA048S21D 1500 51.0 34.8 10.00 - 8.90 24 G1NA060S24T 1800 55.0 39.8 10.50 - 9.25
21,24 G1UA060S21,24 1800 56.0 40.2 10.50 - 9.35
H3RA060S06
1600 2100
24 G2FD060(S,H)24 1800 56.0 40.2 10.50 - 9.35 24 G2FD061H24 2000 57.0 40.9 10.50 - 9.35
21,24 G1FA060S21,24 1750 58.5 39.8 10.00 - 10.25
H1RA060S25,46
1525 1975
24 G1NA060S24T 1750 57.5 39.1 10.00 - 10.00
21,24 G1UA060S21,24 1750 58.5 39.8 10.00 - 10.25
24 G2FD060(S,H)24 1750 58.5 39.8 10.00 - 10.25
H1RA076S25,46 2500-3000 35 G2FD090(S,H)35*** 3200 73.5 52.9 -- -- 10.00 H1RA090S25,46 2500-3000 35 G2FD090(S,H)35*** 4000 90.0 64.8 -- -- 9.35
1. TXV = Use 1TV700 Series Kit.
*
Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up. *** This coil is for upflow application only.
COOLING
SEER
W/O TXV
SEER + TXV
1
EER
Unitary Products Group 7
Page 8
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE
AIR TEMP ON CONDENSER
MODEL
H1RA018S06
H1RA024S06
H2RA030S06
H2RA036S06
H1RA036 S(25,46)
H1RA042S06
H1RA042S(25,46)
SUCT. T/P
@ COMPR.
TEMP. PSIG MBH KW MBH KW MBH KW TEMP. PSIG MBH KW MBH KW MBH KW
35 61.5 16.2 1.66 13.1 1.84 11.0 1.96
40 68.5 17.7 1.67 14.9 1.88 12.8 2.04 40 68.5 43.6 4.21 36.7 4.73 31.4 5.14
45 76.0 19.3 169 16.7 1.92 14.2 2.11 45 76.0 47.6 4.26 41.1 4.84 34.9 5.32
50 84.0 20.8 1.70 18.5 1.96 15.9 2.18 50 84.0 51.1 4.28 45.5 4.94 39.0 5.48
35 61.5 21.0 2.23 17.0 2.46 14.2 2.63
40 68.5 22.9 2.24 19.3 2.52 16.5 2.74 40 68.5 54.0 4.19 48.2 5.14 42.3 6.35
45 76.0 25.0 2.27 21.6 2.58 18.3 2.83 45 76.0 58.4 4.27 52.4 5.25 46.3 6.47
50 84.0 26.8 2.28 23.9 2.63 20.5 2.92 50 84.0 62.7 4.32 56.9 5.38 50.2 5.61
35 61.5 25.1 2.68 20.3 2.97 17.0 3.17
40 68.5 27.4 2.70 23.1 3.04 19.7 3.30 40 68.5 60.1 4.44 56.0 4.83 51.6 5.18
45 76.0 29.9 2.74 25.8 3.10 21.9 3.41 45 76.0 65.8 4.53 61.6 4.92 56.9 5.26
50 84.0 32.1 2.75 28.6 3.17 24.5 3.51 50 84.0 71.9 4.62 67.5 5.01 62.6 5.36
35 61.5 30.5 3.28 24.7 3.64 20.6 3.88
40 68.5 33.3 3.31 28.1 3.72 24.0 4.04 40 68.5 84.5 5.21 69.2 6.23 55.4 7.49
45 76.0 36.4 3.35 31.4 3.80 26.7 4.18 45 76.0 91.8 5.37 75.3 6.38 60.3 7.64
50 84.0 39.1 3.36 34.8 3.88 29.9 4.31 50 84.0 99.4 5.54 81.7 6.55 65.6 7.80
35 61.5 35.8 3.83 28.9 4.25 24.2 4.53
40 68.5 39.1 3.86 32.9 4.34 28.2 4.72 40 68.5 92.5 8.50 80.8 9.41 68.9 10.26
45 76.0 42.6 3.90 36.8 4.53 31.3 4.87 45 76.0 101.3 8.73 89.0 9.72 76.5 10.66
50 84.0 45.8 3.93 40.8 4.63 35.0 5.03 50 84.0 110.4 8.95 97.5 10.03 84.4 11.08
AIR TEMP ON CONDENSER
75°F95°F115°F75°F95°F115°F
MODEL
H1RA048S06
H1RA048S(25,46)
H3RA060S06
H1RA060S(25,46)
H1RA076S(25,46)
H1RA090S(25,46)
SUCT. T/P
@ COMPR.
35 61.5 39.9 4.18 32.3 4.63 27.0 4.94
35 61.5 49.4 4.15 43.8 5.13 38.2 6.34
35 61.5 54.4 4.46 50.5 4.74 46.3 5.08
35 61.5 77.4 5.06 63.4 6.08 50.6 7.35
35 61.5 84.0 8.28 72.9 9.11 61.7 9.87
NOTES:
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 1superheat and 1sub-cooling at condensing unit. a. Increase capacity 1% for each increase in sub-cooling. b. Decrease capacity 1% for each decrease in sub-cooling.
3. Sub-cooling in excess of 2may result in excessively high condensing temperature with air on condenser above 115°F. Maximum recommended condensing temperature is 140°F.
DIMENSIONS - 1 Phase
C
A
UNIT
MODEL
DIMENSIONS
(INCHES)
1
A
B C Liquid Vapor 018 17 35 23 024 17 35 23 5/8”*
030 19 35 23 3/4” 036 19 35 23 3/4” 042 25 35 23 3/4” 048 27 37 27 7/8”
B
060 27 37 27 7/8”
1. Including Fan guard.
* Reducer Required.
REFRIGERANT
CONNECTION
LINE SIZE
5/8”*
3/8”
DIMENSIONS - 3 Phase
UNIT
MODEL
DIMENSIONS
(INCHES)
1
A
B C Liquid Vapor
036 19 35 23 3/8” 3/4 042 25 35 23 3/8 3/4 048 27 37 27 3/8” 7/8 060 39 37 27 3/8” 7/8 076 26 43 32 1/2 1-1/8 090 32 43 32 1/2 1-1/8
1. Including Fan guard. * Reducer Required.
REFRIGERANT
CONNECTION
LINE SIZE
8 Unitary Products Group
Page 9
ACCESSORIES*
Refer to Price Manual for specific model numbers.
Hard Start Kit - Provides increased starting torque for areas with low voltage.
Compressor Blanket - Designed to further reduce the nor­mal compressor operating sound. Refer to price pages for specific match-ups.
Off Cycle Timer Delay - Provides a 5-minute off cycle to pre­vent rapid recycling of the compressor.
Room Thermostats - A wide selection of compatible thermo­sets are available to provide optimum performance and fea­tures for any installation.
1 Heat Stage only, manual, mechanical thermostat. Add sub­base for 1H/1C.
1H/1C, manual change-over electronic non-programmable thermostat.
1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the price book or consult factory.
SOUND RATINGS*
UNIT MODEL
018 7.6
024 7.8
030 8.2
036 8.2
042 8.2
048 8.2
060 8.0
076 --
090 9.0
*Rated in accordance with ARI Standard 270.
036-21121-002 Rev. B (0103)
SOUND
RATINGS
DECIBELS
TYPICAL INSTALLATION
60” OVERHEAD CLEARANCE
10” CLEARANCE COIL AREA
NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE
WEATHERPROOF DISCONNECT SWITCH
CONTROL ACCESS PANEL
THERMOSTAT
TO FURNACE OR AIR HANDLER TERMINAL BLOCK
NEC CLASS 1 WIRING
NEC CLASS 2 WIRING
TO INDOOR COIL
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
Unitary Products Group 9
Page 10
036-21121-002 Rev. B (0103)
TYPICAL FIELD WIRING - 1 Phase Application
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
GND.
LUG
POWER WIRING
208/230-1-60
230-1-50
CONTACTOR TERMINALS
COIL
24 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE (NEC CLASS 2)
*
TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
Y
POWER WIRING CONTROL WIRING
FACTORY WIRING
R
GW
*
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
TYPICAL FIELD WIRING - 3 Phase Application
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
24 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE (NEC CLASS 2)
TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.
GND.
LUG
POWER WIRING
208/230-3-60
460-3-60
*
CONTACTOR TERMINALS
COIL
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
ROOM THERMOSTAT
POWER WIRING CONTROL WIRING FACTORY WIRING
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
YRGW
ROOM THERMOSTAT
*
10 Unitary Products Group
Page 11
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA018S06
INDOOR COIL MODEL NO. G1FA024S14,17
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM
ID CFM 550 650 750
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
T.C. 20.6 19.7 18.1 20.7 19.8 18.5 20.8 19.8 18.9
S.C. 12.7 12.8 12.3 13.3 13.5 13.4 13.7 13.8 14.0
K.W 1.68 1.65 1.64 1.72 1.71 1.70 1.75 1.74 1.73
T.C. 20.6 19.3 17.4 20.9 19.6 18.0 21.1 19.8 18.4
S.C. 12.7 12.6 11.9 13.5 13.4 13.1 14.1 14.0 13.8
K.W 1.58 1.54 1.53 1.62 1.59 1.58 1.65 1.63 1.62
T.C. 19.0 17.5 15.5 19.5 18.0 16.1 19.8 18.2 16.5
S.C. 12.8 12.4 11.5 13.7 13.3 12.8 14.5 14.1 13.6
K.W 1.97 1.91 1.90 2.02 1.96 1.95 2.05 2.00 1.99
T.C. 18.4 16.6 14.2 18.9 17.1 15.0 19.2 17.4 15.4
S.C. 12.5 11.8 10.7 13.6 12.8 12.0 14.4 13.7 12.8
K.W 1.82 1.77 1.75 1.88 1.82 1.80 1.91 1.86 1.83
T.C. 16.3 14.5 11.9 16.9 15.0 12.7 17.2 15.2 13.1
S.C. 12.3 11.2 10.0 13.5 12.4 11.2 14.3 13.2 12.0
K.W 2.24 2.19 2.14 2.31 2.24 2.19 2.35 2.28 2.22
T.C. 14.3 12.3 9.7 14.9 13.0 10.5 15.2 13.1 10.8
S.C. 12.0 10.6 9.3 13.3 11.9 10.4 14.2 12.8 11.2
K.W 2.66 2.61 2.53 2.74 2.66 2.58 2.79 2.70 2.61
036-21121-002 Rev. B (0103)
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
N1AHB0806 G2FD024(S,H)17 1.06 1.06 0.99
F2RC/F2FC024 0.97 0.97 0.99
G1FA030S14 1.06 1.06 0.99
G1HD024 1.03 1.03 0.95
G1NA024S17G 1.00 0.94 0.98
G1UA024S14,17 1.00 1.00 1.00
G1UA030S14 1.06 1.06 0.99
G2FD024(S,H)14,17 1.06 1.06 0.99
G2FD030(S,H)17 1.08 1.08 1.00
G2FD035(S,H)14 1.08 1.08 1.00
T.C. S.C. KW
Unitary Products Group 11
Page 12
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA024S06
INDOOR COIL MODEL NO. G1FA024S14, 17
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM 600 800 1000
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 28.3 25.9 22.7 21.4 28.7 25.1 24.4 21.8 27.5 26.6 24.5 20.9
S.C. 16.9 16.9 15.4 17.0 17.7 16.8 17.0 17.8 17.1 18.0 17.3 17.3
K.W 2.04 1.94 1.78 1.78 2.05 1.87 1.89 1.80 1.97 1.98 1.89 1.72
T.C. 28.5 26.0 22.8 21.4 28.9 25.2 24.4 21.8 27.7 26.7 24.6 20.9
S.C. 17.5 17.5 16.0 17.6 18.5 17.6 17.9 18.7 18.0 19.0 18.2 18.3
K.W 2.25 2.14 1.95 1.95 2.28 2.06 2.07 1.96 2.18 2.18 2.07 1.88
T.C. 26.9 24.5 21.4 20.1 27.3 23.7 23.0 20.6 26.2 25.2 23.0 19.8
S.C. 17.4 17.4 15.9 17.5 18.5 17.6 17.9 18.8 18.1 19.0 18.3 18.4
K.W 2.42 2.28 2.06 2.06 2.44 2.20 2.20 2.08 2.34 2.32 2.21 1.99
T.C. 24.7 22.4 19.5 18.3 24.8 21.6 20.9 18.6 23.8 22.8 21.1 17.9
S.C. 16.8 16.8 15.3 16.9 17.9 16.9 17.3 17.9 17.6 18.4 17.6 17.5
K.W 2.52 2.37 2.15 2.14 2.54 2.30 2.29 2.17 2.43 2.43 2.30 2.07
T.C. 22.0 19.9 17.4 16.3 22.2 19.3 18.6 16.9 21.2 20.4 18.8 16.2
S.C. 15.8 15.7 14.3 15.8 17.0 16.2 16.2 16.7 16.7 17.5 16.8 16.1
K.W 2.60 2.45 2.23 2.20 2.63 2.36 2.37 2.25 2.51 2.50 2.37 2.17
T.C. 19.4 17.5 15.3 14.2 19.5 16.9 16.3 15.1 18.6 17.9 16.5 14.6
S.C. 14.7 14.7 13.3 14.6 16.0 15.4 15.1 15.4 15.9 16.6 15.9 14.6
K.W 2.68 2.53 2.31 2.26 2.71 2.43 2.44 2.33 2.59 2.57 2.44 2.27
Air Handler Coil
N1AHB0806 G2FD024(S,H)14,17 0.98 0.98 0.91
N1AHB0806 G2FD030(S,H)17 1.00 1.00 0.93
F2RP/F2FP024 0.94 0.94 0.93
F2RP/F2FP030 0.94 0.95 0.93
G1FA030S14 0.98 0.98 0.91
G1HD024 0.93 0.93 0.94
G1HD036 0.98 0.98 0.89
G1NA030S17H 0.94 0.95 0.94
G1NA030S21B 0.944 0.946 0.939
G1UA024S14,17 0.95 0.95 0.93
G1UA030S14 0.98 0.98 0.91
G1UA036S17,21 1.00 1.00 1.00
G2FD024(S,H)14,17 0.98 0.98 0.91
G2FD030(S,H)17 1.00 1.00 0.93
G2FD035(S,H)14 1.00 1.00 0.93
G2FD036(S,H)17 1.02 1.02 0.94
T.C. S.C. KW
12 Unitary Products Group
Page 13
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H2RA030S06
INDOOR COIL MODEL NO. G1FA036S17,21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM 800 1000 1200
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 33.9 31.1 28.7 25.6 34.4 31.5 29.1 26.0 34.7 31.8 29.4 26.3
S.C. 20.5 20.6 19.7 20.7 21.4 21.4 20.6 21.6 22.2 22.2 21.4 22.5
K.W 2.69 2.64 2.59 2.52 2.78 2.73 2.68 2.61 2.86 2.81 2.76 2.69
T.C. 33.0 30.2 27.8 24.9 33.4 30.6 28.2 25.5 33.7 30.9 28.5 25.9
S.C. 20.6 20.7 19.9 20.9 21.6 21.7 20.9 22.1 22.6 22.6 21.7 23.0
K.W 2.87 2.79 2.72 2.64 2.94 2.88 2.82 2.75 3.02 2.96 2.90 2.84
T.C. 31.3 28.7 26.4 23.7 31.7 29.0 26.7 24.1 31.9 29.2 27.1 24.4
S.C. 20.3 20.4 19.5 20.8 21.5 21.5 20.7 21.6 22.4 22.5 21.7 22.7
K.W 3.07 2.98 2.91 2.81 3.15 3.07 3.00 2.92 3.25 3.16 3.10 2.99
T.C. 29.3 26.7 24.6 22.0 29.5 27.0 25.0 22.4 29.7 27.2 25.2 23.1
S.C. 19.9 19.9 19.2 20.0 21.0 21.0 20.1 21.1 22.1 22.1 21.1 22.2
K.W 3.27 3.17 3.09 2.98 3.37 3.27 3.19 3.07 3.45 3.37 3.28 3.19
T.C. 26.9 24.5 22.6 20.3 27.1 24.8 22.9 21.0 27.2 25.1 23.1 21.4
S.C. 19.2 19.1 18.3 19.1 20.3 20.3 19.3 20.2 21.2 21.2 20.2 20.6
K.W 3.48 3.37 3.26 3.14 3.57 3.47 3.36 3.26 3.67 3.56 3.46 3.35
T.C. 24.5 22.3 20.7 18.6 24.7 22.6 20.9 19.6 24.7 23.0 21.1 19.7
S.C. 18.5 18.3 17.4 18.2 19.6 19.6 18.4 19.3 20.3 20.3 19.3 19.0
K.W 3.69 3.57 3.43 3.30 3.77 3.67 3.53 3.45 3.89 3.75 3.64 3.51
Air Handler Coil
N1AHB1206 G2FD030(S,H)17 1.00 1.00 1.00
N1AHB1206 G2FD036(S,H)17 1.03 1.03 1.01
F2RP/F2FP030 0.98 0.98 0.97
F2RP/F2FP036 0.97 0.93 1.01
G1FA030S14 0.97 0.96 0.98
G1FA036S14 1.01 0.94 1.01
G1HD036 1.02 1.02 1.01
G1NA030S17K 1.00 0.95 1.02
G1NA030S21M 1.00 0.95 1.03
G1UA036S14 1.01 0.94 1.01
G1UA036S17,21 1.00 1.00 1.00
G2FD030(S,H)17 1.00 1.00 1.00
G2FD035(S,H)14 1.00 1.00 1.00
G2FD036(S,H)21 1.03 1.03 1.01
T.C. S.C. KW
Unitary Products Group 13
Page 14
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H2RA036S06, H1RA036S(25,46)
INDOOR COIL MODEL NO. G1FA036S17,21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
Air Handler Coil
N1AHB1206 G2FD036(S,H)17 1.01 1.00 1.00
N1AHB1206 G2FD046(S,H)17 1.02 1.02 1.00
F2RC/F2FC036 1.00 0.86 1.00
F2RP/F2FP036 1.02 1.01 1.00
F2RP/F2FP042 1.02 1.01 1.01
G1FA036S14 1.00 1.00 1.00
G1FA048S17 1.04 1.04 1.01
G1FA048S21 1.07 1.07 1.04
G1HD036 1.02 1.02 1.05
G2FD046(S,H)17 1.02 1.02 1.00
G1HD048 1.04 1.04 1.05
G1NA036S17J 1.02 1.02 1.01
G1NA036S21C 1.02 1.02 1.00
G1UA036S14 1.00 1.00 1.00
G1UA036S17,21 1.00 1.00 1.00
G1UA048S17 1.04 1.04 1.01
G1UA048S21 1.07 1.07 1.04
G2FD035(S,H)14 0.99 0.99 0.99
G2FD036(S,H)17 1.01 1.00 1.00
G2FD036(S,H)21 1.01 1.00 1.00
G2FD042(S,H)21 1.02 1.02 1.00
ID CFM 1150 1250 1350
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
T.C. 38.3 36.1 34.4 37.9 36.3 34.6 38.0 36.4 34.9
S.C. 24.0 23.7 24.0 24.1 24.5 24.7 24.7 25.3 25.2
K.W 3.19 3.14 3.09 3.23 3.20 3.14 3.26 3.23 3.18
T.C. 36.9 34.6 32.2 36.9 34.9 32.6 37.0 35.2 33.0
S.C. 24.2 23.7 22.9 24.7 24.6 23.9 25.3 25.5 24.8
K.W 3.45 3.39 3.30 3.50 3.44 3.36 3.53 3.49 3.40
T.C. 35.5 33.2 30.0 35.8 33.6 30.4 36.0 34.0 31.0
S.C. 24.3 23.6 21.9 25.4 24.9 23.6 26.0 25.6 24.4
K.W 3.71 3.63 3.52 3.76 3.69 3.58 3.80 3.75 3.62
T.C. 33.2 30.4 26.7 33.4 30.8 27.2 33.6 31.3 27.7
S.C. 23.7 22.5 20.7 24.5 23.6 21.9 25.4 24.6 23.0
K.W 3.97 3.84 3.71 4.02 3.91 3.77 4.06 3.96 3.81
T.C. 31.0 27.6 23.5 31.1 28.2 24.2 31.3 28.5 24.4
S.C. 23.1 21.3 19.6 23.9 22.6 20.7 24.8 23.7 21.6
K.W 4.22 4.06 3.90 4.29 4.13 3.94 4.33 4.18 4.00
T.C. 28.7 24.8 20.2 28.9 25.6 21.1 29.0 25.7 21.0
S.C. 22.5 20.2 18.4 23.2 21.6 19.6 24.2 22.7 20.2
K.W 4.47 4.28 4.09 4.56 4.35 4.11 4.60 4.40 4.19
3 Phase
T.C. S.C. KW
Air Handler Coil
N1AHB1246 G2FD036(S,H)17 1.00 1.00 0.98
N1AHB1246 G2FD046(S,H)21 1.02 1.02 1.00
F2RC/F2FC036 1.00 0.86 1.00
G1FA048S21 1.07 1.07 1.04
G1NA036S17J 1.02 1.02 1.01
G1NA036S21C 1.02 1.02 1.00
G1UA036S17,21 1.00 1.00 1.00
G1UA048S21 1.07 1.07 1.04
G2FD036(S,H)17 1.01 1.00 1.00
G2FD036(S,H)21 1.01 1.00 1.00
T.C. S.C. KW
14 Unitary Products Group
Page 15
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA042S06, H1RA042S(25,46)
INDOOR COIL MODEL NO. G1FA048S21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
Air Handler Coil
N1AHC1606 G2FD042(S,H)21 0.96 0.96 0.99
N1AHC1606 G2FD048(S,H)21 1.00 1.00 1.01
F2RP/F2FP042 0.96 0.95 0.99
F2FP048 0.99 0.99 0.99
G1FA048S17 0.98 1.00 1.00
G1FA060S21,24 1.02 1.02 1.00
G1HD048 0.99 0.99 1.01
G1NA036S21C 0.98 0.93 0.99
G1NA048S21D 0.99 0.94 1.00
G1UA048S17 0.98 1.00 1.00
G1UA048S21 1.00 1.00 1.00
G1UA060S21,24 1.02 1.03 1.00
G2FD042(S,H)21 0.96 0.96 0.99
G2FD046(S,H)17 0.98 0.98 1.00
G2FD048(S,H)21,24 1.00 1.00 1.01
G2FD060(S,H)24 1.02 1.02 1.00
ID CFM 1200 1400 1600
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
T.C. 47.2 44.1 41.2 47.5 44.6 41.9 47.9 45.1 42.6
S.C. 30.2 29.6 29.4 31.9 31.1 31.0 33.6 32.6 32.6
K.W 3.90 3.85 3.78 4.05 3.99 3.94 4.19 4.14 4.09
T.C. 45.5 42.1 38.5 45.9 42.8 39.3 46.3 43.4 40.2
S.C. 29.8 28.9 28.1 31.4 30.7 30.0 33.0 32.5 31.9
K.W 4.13 4.06 3.96 4.28 4.21 4.13 4.43 4.36 4.29
T.C. 43.9 40.2 35.7 44.3 41.0 36.8 44.8 41.8 37.8
S.C. 29.5 28.2 26.9 30.9 30.3 29.1 32.4 32.4 31.2
K.W 4.36 4.27 4.14 4.52 4.43 4.31 4.67 4.59 4.49
T.C. 40.5 36.3 32.0 41.2 37.1 32.8 42.0 38.0 33.7
S.C. 28.1 26.7 25.1 29.9 28.8 27.2 31.7 30.9 29.3
K.W 4.58 4.44 4.30 4.74 4.60 4.47 4.89 4.77 4.64
T.C. 37.1 32.3 28.3 38.2 33.3 28.9 39.2 34.2 29.6
S.C. 26.8 25.1 23.3 29.0 27.2 25.4 31.1 29.4 27.4
K.W 4.81 4.62 4.45 4.96 4.78 4.62 5.10 4.95 4.79
T.C. 33.7 28.4 24.5 35.1 29.4 25.0 36.4 30.4 25.4
S.C. 25.5 23.5 21.5 28.0 25.7 23.5 30.5 27.9 25.5
K.W 5.04 4.79 4.61 5.18 4.96 4.78 5.32 5.13 4.94
3 Phase
T.C. S.C. KW
Air Handler Coil
N1AHC1646 G2FD042(S,H)21 0.98 0.99 1.00
N1AHC1646 G2FD048(S,H)21 0.99 1.01 1.01
F2RP/F2FP042 0.95 0.95 0.99
F2FP048 0.99 0.99 0.99
G1FA060S21,24 1.02 1.02 1.00
G1NA036S21C 0.98 0.93 0.99
G1NA048S21D 0.99 0.94 1.00
G1UA048S21 1.00 1.00 1.00
G1UA060S21,24 1.02 1.03 1.00
G2FD042(S,H)21 0.96 0.96 0.99
G2FD046(S,H)17 0.98 0.98 1.00
G2FD048(S,H)21,24 1.00 1.00 1.01
T.C. S.C. KW
Unitary Products Group 15
Page 16
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA048S06, H1RA048S(25,46)
INDOOR COIL MODEL NO. G1FA048S21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
Air Handler Coil
N1AHC1606 G2FD048(S,H)21 1.01 1.01 1.01
N1AHD2006 G2FD060(S,H)24 1.03 1.03 1.01
F2FP048 1.00 1.00 1.03
F2FP060 1.02 1.02 1.00
G1FA048S17 0.98 0.99 1.01
G1FA060S21,24 1.03 1.03 1.01
G1HD048 1.00 1.00 0.99
G1HD060 1.02 1.02 1.00
ID CFM 1200 1400 1600
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 53.4 48.9 45.1 40.2 54.3 49.8 45.9 41.3 54.9 50.3 46.4 41.8
S.C. 32.2 32.3 31.0 32.5 34.0 34.0 32.7 34.7 35.2 35.3 33.9 35.9
K.W 4.32 4.15 4.00 3.83 4.44 4.26 4.11 3.95 4.53 4.36 4.21 4.04
T.C. 52.0 47.5 43.7 39.2 52.7 48.3 44.5 40.0 53.2 48.7 45.2 40.5
S.C. 32.2 32.3 31.1 32.7 34.1 34.1 32.8 34.7 35.4 35.5 34.5 36.0
K.W 4.62 4.43 4.26 4.07 4.74 4.55 4.38 4.18 4.84 4.65 4.48 4.28
T.C. 49.0 44.9 41.3 36.9 49.6 45.5 42.0 37.6 50.0 45.8 42.4 38.3
S.C. 31.6 31.6 30.4 31.8 33.5 33.7 32.4 33.8 34.9 35.0 33.7 35.6
K.W 4.91 4.70 4.51 4.31 5.02 4.81 4.64 4.43 5.13 4.92 4.74 4.53
T.C. 45.6 41.6 38.4 34.3 46.0 42.2 39.0 35.0 46.2 42.5 39.3 36.2
S.C. 30.5 30.6 29.5 30.9 32.6 32.8 31.5 32.8 34.1 34.2 32.7 34.5
K.W 5.18 4.96 4.76 4.54 5.30 5.07 4.88 4.67 5.39 5.18 4.99 4.83
T.C. 41.8 38.3 35.3 31.7 42.3 38.8 35.8 33.0 42.5 39.0 36.2 33.5
S.C. 29.3 29.5 28.2 29.6 31.6 31.4 30.1 31.5 33.0 32.9 31.5 32.0
K.W 5.42 5.18 4.98 4.76 5.52 5.31 5.10 4.94 5.63 5.41 5.21 5.06
T.C. 38.0 35.0 32.3 29.1 38.6 35.4 32.7 31.0 38.8 35.5 33.2 30.8
S.C. 28.1 28.4 26.9 28.3 30.6 30.0 28.7 30.2 31.9 31.6 30.4 29.5
K.W 5.66 5.40 5.20 4.98 5.74 5.55 5.32 5.21 5.87 5.64 5.43 5.29
3 Phase
T.C. S.C. KW
Air Handler Coil
N1AHC1646 G2FD048(S,H)21 1.01 1.01 1.00
N1AHD2046 G2FD048(S,H)24 1.01 1.01 1.00
N1AHD2046 G2FD060(S,H)24 1.03 1.03 1.00
F2FP048 1.00 1.00 1.03
G1FA048S21 1.00 1.00 1.00
G1NA048S21D 1.02 1.02 1.02
G1UA048S21 1.00 1.00 1.00
G2FD048(S,H)21,24 1.01 1.01 1.01
T.C. S.C. KW
16 Unitary Products Group
Page 17
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H3RA060S06
INDOOR COIL MODEL NO. G1FA060S21,24
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM 2050 1800 1550
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
T.C. 64.7 61.9 58.2 64.1 61.2 57.2 63.6 60.5 56.2
S.C. 46.3 44.9 42.9 43.3 42.1 40.3 40.3 39.3 37.7
K.W 5.18 5.13 5.03 5.08 5.02 4.92 4.97 4.91 4.81
T.C. 62.8 59.6 55.4 62.3 58.6 54.3 61.8 57.6 53.3
S.C. 45.9 44.3 41.9 42.8 41.2 39.2 39.7 38.2 36.5
K.W 4.94 4.86 4.77 5.58 5.50 5.40 5.48 5.40 5.28
T.C. 60.9 57.3 52.7 60.4 56.0 51.5 59.9 54.7 50.3
S.C. 45.7 43.5 40.8 42.4 40.2 38.0 39.2 37.0 35.2
K.W 6.19 6.10 6.00 6.09 5.99 5.87 5.98 5.88 5.74
T.C. 57.2 53.4 48.4 56.6 52.3 47.4 56.0 51.1 46.4
S.C. 44.6 42.1 39.3 41.3 39.0 36.6 38.0 35.9 33.8
K.W 6.82 6.70 6.56 6.71 6.59 6.44 6.60 6.47 6.31
T.C. 53.5 49.5 44.1 52.8 48.5 43.3 52.1 47.5 42.4
S.C. 43.6 40.5 37.7 40.2 37.6 35.1 36.8 34.7 32.4
K.W 7.47 7.32 7.14 7.35 7.19 7.01 7.22 7.06 6.88
T.C. 49.8 45.6 39.9 49.0 44.8 39.2 48.2 43.9 38.5
S.C. 42.5 39.0 36.1 39.0 36.3 33.6 35.6 33.6 31.0
K.W 8.12 7.94 7.72 7.99 7.79 7.58 7.84 7.65 7.45
Air Handler Coil
N1AHD2006 G2FD060(S,H)24 1.00 1.00 1.00
F2FP060 1.00 1.02 1.02
G1HD060 0.99 1.00 1.01
G1NA048S21D 0.91 0.87 0.96
G1NA060S24T 0.98 0.99 0.99
G1UA060S21,24 1.00 1.00 1.00
G2FD060(S,H)24 1.00 1.00 1.00
G2FD061H24 1.02 1.02 1.02
T.C. S.C. KW
Unitary Products Group 17
Page 18
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA060S(25,46)
INDOOR COIL MODEL NO. G2FD060S24A
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM 1450 1700 1950
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
T.C. 61.2 58.5 56.3 61.8 59.1 56.9 62.3 59.6 57.5
S.C. 37.6 37.4 37.1 40.1 39.9 39.5 42.5 42.3 41.8
K.W 4.66 4.57 4.51 4.67 4.58 4.53 4.68 4.58 4.55
T.C. 60.6 58.0 55.0 61.2 58.6 55.8 61.9 59.3 56.7
S.C. 37.6 37.3 36.5 40.2 39.9 39.1 42.8 42.5 41.7
K.W 5.26 5.13 5.08 5.27 5.14 5.10 5.28 5.15 5.11
T.C. 60.0 57.4 53.7 60.7 58.5 54.8 61.4 59.0 55.8
S.C. 37.5 37.1 35.9 40.3 39.8 38.8 43.1 42.6 41.6
K.W 5.86 5.70 5.65 5.87 5.71 5.67 5.88 5.72 5.68
T.C. 58.1 54.6 50.0 58.9 55.7 51.3 59.7 56.8 52.7
S.C. 36.9 36.0 34.4 39.8 39.0 37.3 42.7 41.9 40.2
K.W 6.54 6.39 6.29 6.56 6.42 6.30 6.57 6.45 6.32
T.C. 56.2 51.8 46.3 57.1 53.2 47.9 57.9 54.5 49.5
S.C. 36.2 34.9 32.9 39.3 38.1 35.9 42.3 41.2 38.8
K.W 7.23 7.07 6.92 7.25 7.12 6.94 7.26 7.17 6.97
T.C. 54.3 49.0 42.6 55.2 50.6 44.5 56.2 52.3 46.4
S.C. 35.6 33.8 31.4 38.7 37.2 34.4 41.9 40.5 37.4
K.W 7.92 7.76 7.55 7.94 7.83 7.58 7.96 7.90 7.62
Air Handler Coil
N1AHD2046 G2FD060(S,H)24 1.00 1.00 1.00
F2FP060 1.00 1.00 1.05
G1FA060S21,24 1.00 1.00 1.00
G1NA060S24T 0.98 0.98 1.01
G1UA060S21,24 1.00 1.00 1.00
T.C. S.C. KW
18 Unitary Products Group
Page 19
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA076S(25,46)
INDOOR COIL MODEL NO. K4EV090
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM 2100 2600 3100
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
T.C. 79.1 76.3 73.9 82.0 79.2 76.9 84.9 82.0 79.9
S.C. 48.8 48.6 48.1 55.4 55.3 54.7 62.0 61.9 61.3
K.W 5.98 5.90 5.84 6.28 6.18 6.15 6.58 6.48 6.46
T.C. 76.4 73.7 70.6 79.1 76.3 73.4 81.7 79.0 76.2
S.C. 47.9 47.6 46.8 54.7 54.4 53.5 61.5 61.2 60.3
K.W 6.53 6.42 6.37 6.86 6.74 6.70 7.18 7.07 7.04
T.C. 73.8 71.1 67.2 76.1 73.5 69.9 78.4 75.9 72.6
S.C. 47.1 46.7 45.4 54.0 53.6 52.4 60.9 60.4 59.4
K.W 7.08 6.94 6.90 7.43 7.30 7.26 7.79 7.65 7.61
T.C. 71.1 67.4 62.6 73.1 69.7 65.2 75.1 72.0 67.7
S.C. 46.4 45.4 43.7 53.1 52.2 50.5 59.8 58.9 57.2
K.W 7.84 7.70 7.61 8.21 8.08 7.99 8.57 8.46 8.36
T.C. 68.4 63.7 58.0 70.0 67.0 60.4 71.7 68.2 62.9
S.C. 45.4 44.1 42.0 52.0 51.9 48.5 58.6 57.5 55.0
K.W 8.59 8.46 8.32 8.97 8.80 8.71 9.36 9.28 9.10
T.C. 65.6 60.1 53.4 67.0 64.3 55.7 68.4 64.3 58.1
S.C. 44.5 42.7 40.2 51.0 51.6 46.5 57.5 56.0 52.8
K.W 9.35 9.21 9.02 9.74 9.51 9.43 10.14 10.09 9.84
Coil
G2FD090(S,H)35 1.00 0.99 1.01
T.C. S.C. KW
Unitary Products Group 19
Page 20
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA090S(25,46)
INDOOR COIL MODEL NO. K4EV090
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM 2400 3000 3600
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
T.C. 104.2 97.2 90.1 108.1 100.5 92.8 112.1 103.8 95.5
S.C. 76.5 71.0 65.6 78.7 72.8 66.9 81.0 74.6 68.2
K.W 8.30 8.21 8.13 8.33 8.25 8.18 8.36 8.29 8.23
T.C. 99.1 92.4 85.8 102.0 94.7 87.5 104.8 97.0 89.1
S.C. 72.5 67.4 62.3 74.0 68.4 62.8 75.5 69.4 63.4
K.W 8.97 8.86 8.75 9.01 8.90 8.79 9.04 8.94 8.84
T.C. 94.0 87.7 81.5 95.8 89.0 82.1 97.5 90.1 82.7
S.C. 68.6 63.8 59.0 69.3 64.0 58.7 70.0 64.2 58.5
K.W 9.64 9.50 9.37 9.68 9.55 9.41 9.72 9.59 9.45
T.C. 88.2 82.2 76.1 89.8 83.9 77.9 91.4 85.6 79.7
S.C. 68.7 63.7 58.7 69.2 64.3 59.4 69.8 64.9 60.1
K.W 10.33 10.14 9.96 10.38 10.21 10.03 10.43 10.27 10.10
T.C. 82.5 76.6 70.8 83.9 78.8 73.8 85.3 81.0 76.7
S.C. 59.9 55.4 50.9 60.2 56.3 52.4 60.5 57.2 53.9
K.W 11.02 10.79 10.55 11.08 10.87 10.65 11.14 10.95 10.76
T.C. 76.7 71.1 65.5 78.0 73.8 69.6 79.2 76.5 73.7
S.C. 55.5 51.2 46.8 55.7 52.4 49.2 55.8 53.7 51.6
K.W 11.71 11.43 11.15 11.78 11.53 11.28 11.86 11.63 11.41
Coil
G2FD090(S,H)35 1.01 1.01 1.01
T.C. S.C. KW
20 Unitary Products Group
Page 21
MATCHING INDOOR COMPONENTS
ADD-ON COILS - FOR FURNACE APPLICATIONS
036-21121-002 Rev. B (0103)
G1UA 1/2 CASED UPFLOW
G1FA FULL CASED UPFLOW
* Available with factory installed horizontal drain pan.
AIR HANDLERS - FOR NON-FURNACE APPLICATIONS
N1AH OR N1VS MODULAR BLOWER (UPFLOW, HORIZONTAL AND DOWNFLOW)
G1HD HORIZONTAL DUCT
G2FD* MULTI-POSITION (UPFLOW, HORIZONTAL AND DOWNFLOW)
G1NA UNCASED UPFLOW
G2FD090 is upflow only.
Unitary Products Group 21
G2FD COIL
LIGHT COMMERCIAL APPLICATIONS
F2RC / F2FC OR F2RC / F2FP FAN COIL UNITS (UPFLOW, HORIZONTAL)
Page 22
036-21121-002 Rev. B (0103)
NOTES
22 Unitary Products Group
Page 23
036-21121-002 Rev. B (0103)
Unitary Products Group 23
Page 24
Subject to change without notice. Printed in U.S.A. 036-21121-002 Rev. B (0103) Copyright © by York International Corp. 2003. All rights reserved. Supersedes: 036-21121-002 Rev. A (0602)
Unitary 5005 Norman Products York OK Group Drive 73069