SPLIT-SYSTEM AIR CONDITIONERS
10 SEER
MODELS:
H*RA018 THRU 060
(1.5 THRU 5 NOMINAL TONS, 1 PH)
H*RA036 THRU 090
(3 THRU 7.5 NOMINAL TONS, 3 PH)
MODELS: 018 - 060 (1 PH & 3 PH)
MODELS: 076 - 090 (3 PH)
O
T
A
R
D
I
E
I
A
F
S
I
T
R
C
E
O
C
M
A
P
I
R
R
-
L
C
E
O
Y
N
R
Y
I
D
R
I
U
A
T
T
I
C
N
U
A
F
U
N
A
M
C
E
R
T
I
A
R
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.
I
Certification applies only
when the complete
system is listed
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.ariprimenet.org.
R
E
Q
U
I
P
M
F
I
C
A
T
I
O
N
S
T
A
N
with ARI.
N
T
G
I
O
N
I
W
N
I
G
T
H
T
F
N
E
O
S
N
O
I
T
0
C
E
S
1
2
D
R
A
D
LISTED
036-21121-002 Rev. B (0103)
DESCRIPTION
The 10 SEER Series condensing unit is the outdoor part of a
versatile system of air conditioning. It is designed to be custom-matched with one of UPG’s complete line of evaporator
sections, each designed to serve a specific function. Matching Air Handlers are available for upflow, downflow or horizontal applications to provide a complete system. Electric
Heaters are available if required. Add-On coils are available
for use with upflow, downflow or horizontal furnaces and air
handlers.
WARRANTY
Single Phase Units:
5-year limited parts warranty.
5-year limited compressor warranty.
Three Phase Units:
1-year limited parts warranty.
5-year limited compressor warranty.
FEATURES
• QUALITY CONDENSER COILS - The coil is constructed
of enhanced copper tube and aluminum fins.
• COIL PROTECTION - Coils are protected from damage by
a polymer mesh applied between the coil face, and a PVC
coated steel coil guard.
• PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature.
This is accomplished by the simultaneous operation of
high pressure relief valve and a temperature sensor which
protects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the
compressor.
• DURABLE FINISH - The cabinet is made of pre-painted
steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust
creep. Special primer formulas and matted desert sand finish insure less fading when exposed to sunlight.
• LOWER INSTALLED COST - Installation time and costs
are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only.
The unit contains enough refrigerant for matching indoor
coils and 15 feet of interconnecting piping. The small base
dimension means less space is required on the ground or
roof.
• TOP DISCHARGE - The warm air from the top mounted
fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
• LOW OPERATING SOUND LEVEL - The upward air flow
carries the normal operating noise up away from the living
area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins
of the condenser coil muffle the normal fan motor and
compressor operating sounds.
• LOW MAINTENANCE - Long life permanently lubricated
motor-bearings need no annual servicing.
• EASY SERVICE ACCESS - Fully exposed refrigerant connections, a single panel covering the electrical controls
and the molex plug in the control box connecting the condenser fan, make for easy servicing of the unit.
• SECURED SERVICE VALVES - Secured re-usable ser-
vice valves are provided on both the liquid and vapor
sweat connections for ease of evacuating and charging.
• U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot valve.
H1RA
042S25
H1RA
048S25
H1RA
060S25
208/230 – 3 – 60
H1RA
076S25
H1RA
090S25
H1RA
036S25
H1RA
042S46
H1RA
048S46
460 - 3 - 60
H1RA
060S46
H1RA
076S46
H1RA
090S46
187 to 252432 to 504
253030354050151515152025
ScrollBScroll
B
DualRecipRecipRecip
Scroll
B
Scroll
B
Dual
.68.68.70.701.261.26.68.68.70.701.261.26
2Unitary Products Group
Page 3
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 PHASE
ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line
tubing.
2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaportor + adder for line set.
5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
Unitary Products Group3
Page 4
036-21121-002 Rev. B (0103)
Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 PHASE
ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS
Outdoor Unit H1RA036H1RA042H1RA048H1RA060H1RA076H1RA090
1. These orifices are packed in the instruction/warranty packet of each outdoor unit.
2. These orifices are factory mounted in the flow control device of each indoor coil.
3. The TXV is factory mounted in the coil or air handler.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line
tubing.
2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaportor + adder for line set.
5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters. Three phase units require three phase 2HK heaters.
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC
5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.
6. H*BA-(T,W)090 is field convertible to two stage operation. Its IPLV = 11.2.
— = Not Applicable.
.
models. All ratings remain the same.
53.8/
89.0
COOLING
SEER
W/O TXV
SEER
+ TXV
------
EER
3
9.63/
9.30
Unitary Products Group5
Page 6
036-21121-002 Rev. B (0103)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils
Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one.
** Refer to Quick Selection Chart for specific furnace match-up.
*** This coil is for upflow application only.
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 15° superheat and 15° sub-cooling at condensing unit.
a. Increase capacity 1% for each 2° increase in sub-cooling.
b. Decrease capacity 1% for each 2° decrease in sub-cooling.
3. Sub-cooling in excess of 20° may result in excessively high condensing temperature with air on condenser above 115°F.
Maximum recommended condensing temperature is 140°F.
* For the most current accessory information, refer to the
price book or consult factory.
SOUND RATINGS*
UNIT MODEL
0187.6
0247.8
0308.2
0368.2
0428.2
0488.2
0608.0
076--
0909.0
*Rated in accordance with ARI Standard 270.
036-21121-002 Rev. B (0103)
SOUND
RATINGS
DECIBELS
TYPICAL INSTALLATION
60” OVERHEAD
CLEARANCE
10” CLEARANCE
COIL AREA
NOTE: ALL OUTDOOR WIRING MUST
BE WEATHERPROOF.
MINIMUM 18” SERVICE ACCESS
CLEARANCE ON ONE SIDE
WEATHERPROOF
DISCONNECT
SWITCH
CONTROL ACCESS PANEL
THERMOSTAT
TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK
NEC CLASS 1 WIRING
NEC CLASS 2 WIRING
TO INDOOR COIL
SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT
Unitary Products Group9
Page 10
036-21121-002 Rev. B (0103)
TYPICAL FIELD WIRING - 1 Phase Application
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
GND.
LUG
POWER WIRING
208/230-1-60
230-1-50
CONTACTOR
TERMINALS
COIL
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
*
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
Y
POWER WIRING
CONTROL WIRING
FACTORY WIRING
R
GW
*
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
TYPICAL FIELD WIRING - 3 Phase Application
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
GND.
LUG
POWER WIRING
208/230-3-60
460-3-60
*
CONTACTOR
TERMINALS
COIL
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
ROOM THERMOSTAT
POWER WIRING
CONTROL WIRING
FACTORY WIRING
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
YRGW
ROOM THERMOSTAT
*
10Unitary Products Group
Page 11
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.H1RA018S06
INDOOR COIL MODEL NO.G1FA024S14,17
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM
ID CFM550650750
ID DB (°F)858070858070858070
ID WB (°F)726757726757726757
T.C.20.619.718.120.719.818.520.819.818.9
S.C.12.712.812.313.313.513.413.713.814.0
K.W1.681.651.641.721.711.701.751.741.73
T.C.20.619.317.420.919.618.021.119.818.4
S.C.12.712.611.913.513.413.114.114.013.8
K.W1.581.541.531.621.591.581.651.631.62
T.C.19.017.515.519.518.016.119.818.216.5
S.C.12.812.411.513.713.312.814.514.113.6
K.W1.971.911.902.021.961.952.052.001.99
T.C.18.416.614.218.917.115.019.217.415.4
S.C.12.511.810.713.612.812.014.413.712.8
K.W1.821.771.751.881.821.801.911.861.83
T.C.16.314.511.916.915.012.717.215.213.1
S.C.12.311.210.013.512.411.214.313.212.0
K.W2.242.192.142.312.242.192.352.282.22
T.C.14.312.39.714.913.010.515.213.110.8
S.C.12.010.69.313.311.910.414.212.811.2
K.W2.662.612.532.742.662.582.792.702.61
036-21121-002 Rev. B (0103)
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air HandlerCoil
N1AHB0806G2FD024(S,H)171.061.060.99
F2RC/F2FC0240.970.970.99
G1FA030S141.061.060.99
G1HD0241.031.030.95
G1NA024S17G1.000.940.98
G1UA024S14,171.001.001.00
G1UA030S141.061.060.99
G2FD024(S,H)14,171.061.060.99
G2FD030(S,H)171.081.081.00
G2FD035(S,H)141.081.081.00
T.C.S.C.KW
Unitary Products Group11
Page 12
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.H1RA024S06
INDOOR COIL MODEL NO.G1FA024S14, 17
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
AIR CONDITIONER MODEL NO.H2RA036S06, H1RA036S(25,46)
INDOOR COIL MODEL NO.G1FA036S17,21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
Air HandlerCoil
N1AHB1206G2FD036(S,H)171.011.001.00
N1AHB1206G2FD046(S,H)171.021.021.00
F2RC/F2FC0361.000.861.00
F2RP/F2FP0361.021.011.00
F2RP/F2FP0421.021.011.01
G1FA036S141.001.001.00
G1FA048S171.041.041.01
G1FA048S211.071.071.04
G1HD0361.021.021.05
G2FD046(S,H)171.021.021.00
G1HD0481.041.041.05
G1NA036S17J1.021.021.01
G1NA036S21C1.021.021.00
G1UA036S141.001.001.00
G1UA036S17,211.001.001.00
G1UA048S171.041.041.01
G1UA048S211.071.071.04
G2FD035(S,H)140.990.990.99
G2FD036(S,H)171.011.001.00
G2FD036(S,H)211.011.001.00
G2FD042(S,H)211.021.021.00
ID CFM115012501350
ID DB (°F)858070858070858070
ID WB (°F)726757726757726757
T.C.38.336.134.437.936.334.638.036.434.9
S.C.24.023.724.024.124.524.724.725.325.2
K.W3.193.143.093.233.203.143.263.233.18
T.C.36.934.632.236.934.932.637.035.233.0
S.C.24.223.722.924.724.623.925.325.524.8
K.W3.453.393.303.503.443.363.533.493.40
T.C.35.533.230.035.833.630.436.034.031.0
S.C.24.323.621.925.424.923.626.025.624.4
K.W3.713.633.523.763.693.583.803.753.62
T.C.33.230.426.733.430.827.233.631.327.7
S.C.23.722.520.724.523.621.925.424.623.0
K.W3.973.843.714.023.913.774.063.963.81
T.C.31.027.623.531.128.224.231.328.524.4
S.C.23.121.319.623.922.620.724.823.721.6
K.W4.224.063.904.294.133.944.334.184.00
T.C.28.724.820.228.925.621.129.025.721.0
S.C.22.520.218.423.221.619.624.222.720.2
K.W4.474.284.094.564.354.114.604.404.19
3 Phase
T.C.S.C.KW
Air HandlerCoil
N1AHB1246G2FD036(S,H)171.001.000.98
N1AHB1246G2FD046(S,H)211.021.021.00
F2RC/F2FC0361.000.861.00
G1FA048S211.071.071.04
G1NA036S17J1.021.021.01
G1NA036S21C1.021.021.00
G1UA036S17,211.001.001.00
G1UA048S211.071.071.04
G2FD036(S,H)171.011.001.00
G2FD036(S,H)211.011.001.00
T.C.S.C.KW
14Unitary Products Group
Page 15
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.H1RA042S06, H1RA042S(25,46)
INDOOR COIL MODEL NO.G1FA048S21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
Air HandlerCoil
N1AHC1606G2FD042(S,H)210.960.960.99
N1AHC1606G2FD048(S,H)211.001.001.01
F2RP/F2FP0420.960.950.99
F2FP0480.990.990.99
G1FA048S170.981.001.00
G1FA060S21,241.021.021.00
G1HD0480.990.991.01
G1NA036S21C0.980.930.99
G1NA048S21D0.990.941.00
G1UA048S170.981.001.00
G1UA048S211.001.001.00
G1UA060S21,241.021.031.00
G2FD042(S,H)210.960.960.99
G2FD046(S,H)170.980.981.00
G2FD048(S,H)21,241.001.001.01
G2FD060(S,H)241.021.021.00
ID CFM120014001600
ID DB (°F)858070858070858070
ID WB (°F)726757726757726757
T.C.47.244.141.247.544.641.947.945.142.6
S.C.30.229.629.431.931.131.033.632.632.6
K.W3.903.853.784.053.993.944.194.144.09
T.C.45.542.138.545.942.839.346.343.440.2
S.C.29.828.928.131.430.730.033.032.531.9
K.W4.134.063.964.284.214.134.434.364.29
T.C.43.940.235.744.341.036.844.841.837.8
S.C.29.528.226.930.930.329.132.432.431.2
K.W4.364.274.144.524.434.314.674.594.49
T.C.40.536.332.041.237.132.842.038.033.7
S.C.28.126.725.129.928.827.231.730.929.3
K.W4.584.444.304.744.604.474.894.774.64
T.C.37.132.328.338.233.328.939.234.229.6
S.C.26.825.123.329.027.225.431.129.427.4
K.W4.814.624.454.964.784.625.104.954.79
T.C.33.728.424.535.129.425.036.430.425.4
S.C.25.523.521.528.025.723.530.527.925.5
K.W5.044.794.615.184.964.785.325.134.94
3 Phase
T.C.S.C.KW
Air HandlerCoil
N1AHC1646G2FD042(S,H)210.980.991.00
N1AHC1646G2FD048(S,H)210.991.011.01
F2RP/F2FP0420.950.950.99
F2FP0480.990.990.99
G1FA060S21,241.021.021.00
G1NA036S21C0.980.930.99
G1NA048S21D0.990.941.00
G1UA048S211.001.001.00
G1UA060S21,241.021.031.00
G2FD042(S,H)210.960.960.99
G2FD046(S,H)170.980.981.00
G2FD048(S,H)21,241.001.001.01
T.C.S.C.KW
Unitary Products Group15
Page 16
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.H1RA048S06, H1RA048S(25,46)
INDOOR COIL MODEL NO.G1FA048S21
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM205018001550
ID DB (°F)858070858070858070
ID WB (°F)726757726757726757
T.C.64.761.958.264.161.257.263.660.556.2
S.C.46.344.942.943.342.140.340.339.337.7
K.W5.185.135.035.085.024.924.974.914.81
T.C.62.859.655.462.358.654.361.857.653.3
S.C.45.944.341.942.841.239.239.738.236.5
K.W4.944.864.775.585.505.405.485.405.28
T.C.60.957.352.760.456.051.559.954.750.3
S.C.45.743.540.842.440.238.039.237.035.2
K.W6.196.106.006.095.995.875.985.885.74
T.C.57.253.448.456.652.347.456.051.146.4
S.C.44.642.139.341.339.036.638.035.933.8
K.W6.826.706.566.716.596.446.606.476.31
T.C.53.549.544.152.848.543.352.147.542.4
S.C.43.640.537.740.237.635.136.834.732.4
K.W7.477.327.147.357.197.017.227.066.88
T.C.49.845.639.949.044.839.248.243.938.5
S.C.42.539.036.139.036.333.635.633.631.0
K.W8.127.947.727.997.797.587.847.657.45
Air HandlerCoil
N1AHD2006G2FD060(S,H)241.001.001.00
F2FP0601.001.021.02
G1HD0600.991.001.01
G1NA048S21D0.910.870.96
G1NA060S24T0.980.990.99
G1UA060S21,241.001.001.00
G2FD060(S,H)241.001.001.00
G2FD061H241.021.021.02
T.C.S.C.KW
Unitary Products Group17
Page 18
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.H1RA060S(25,46)
INDOOR COIL MODEL NO.G2FD060S24A
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM145017001950
ID DB (°F)858070858070858070
ID WB (°F)726757726757726757
T.C.61.258.556.361.859.156.962.359.657.5
S.C.37.637.437.140.139.939.542.542.341.8
K.W4.664.574.514.674.584.534.684.584.55
T.C.60.658.055.061.258.655.861.959.356.7
S.C.37.637.336.540.239.939.142.842.541.7
K.W5.265.135.085.275.145.105.285.155.11
T.C.60.057.453.760.758.554.861.459.055.8
S.C.37.537.135.940.339.838.843.142.641.6
K.W5.865.705.655.875.715.675.885.725.68
T.C.58.154.650.058.955.751.359.756.852.7
S.C.36.936.034.439.839.037.342.741.940.2
K.W6.546.396.296.566.426.306.576.456.32
T.C.56.251.846.357.153.247.957.954.549.5
S.C.36.234.932.939.338.135.942.341.238.8
K.W7.237.076.927.257.126.947.267.176.97
T.C.54.349.042.655.250.644.556.252.346.4
S.C.35.633.831.438.737.234.441.940.537.4
K.W7.927.767.557.947.837.587.967.907.62
Air HandlerCoil
N1AHD2046G2FD060(S,H)241.001.001.00
F2FP0601.001.001.05
G1FA060S21,241.001.001.00
G1NA060S24T0.980.981.01
G1UA060S21,241.001.001.00
T.C.S.C.KW
18Unitary Products Group
Page 19
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.H1RA076S(25,46)
INDOOR COIL MODEL NO.K4EV090
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM210026003100
ID DB (°F)858070858070858070
ID WB (°F)726757726757726757
T.C.79.176.373.982.079.276.984.982.079.9
S.C.48.848.648.155.455.354.762.061.961.3
K.W5.985.905.846.286.186.156.586.486.46
T.C.76.473.770.679.176.373.481.779.076.2
S.C.47.947.646.854.754.453.561.561.260.3
K.W6.536.426.376.866.746.707.187.077.04
T.C.73.871.167.276.173.569.978.475.972.6
S.C.47.146.745.454.053.652.460.960.459.4
K.W7.086.946.907.437.307.267.797.657.61
T.C.71.167.462.673.169.765.275.172.067.7
S.C.46.445.443.753.152.250.559.858.957.2
K.W7.847.707.618.218.087.998.578.468.36
T.C.68.463.758.070.067.060.471.768.262.9
S.C.45.444.142.052.051.948.558.657.555.0
K.W8.598.468.328.978.808.719.369.289.10
T.C.65.660.153.467.064.355.768.464.358.1
S.C.44.542.740.251.051.646.557.556.052.8
K.W9.359.219.029.749.519.4310.1410.099.84
Coil
G2FD090(S,H)351.000.991.01
T.C.S.C.KW
Unitary Products Group19
Page 20
036-21121-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.H1RA090S(25,46)
INDOOR COIL MODEL NO.K4EV090
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
ID CFM240030003600
ID DB (°F)858070858070858070
ID WB (°F)726757726757726757
T.C.104.297.290.1108.1100.592.8112.1103.895.5
S.C.76.571.065.678.772.866.981.074.668.2
K.W8.308.218.138.338.258.188.368.298.23
T.C.99.192.485.8102.094.787.5104.897.089.1
S.C.72.567.462.374.068.462.875.569.463.4
K.W8.978.868.759.018.908.799.048.948.84
T.C.94.087.781.595.889.082.197.590.182.7
S.C.68.663.859.069.364.058.770.064.258.5
K.W9.649.509.379.689.559.419.729.599.45
T.C.88.282.276.189.883.977.991.485.679.7
S.C.68.763.758.769.264.359.469.864.960.1
K.W10.3310.149.9610.3810.2110.0310.4310.2710.10
T.C.82.576.670.883.978.873.885.381.076.7
S.C.59.955.450.960.256.352.460.557.253.9
K.W11.0210.7910.5511.0810.8710.6511.1410.9510.76
T.C.76.771.165.578.073.869.679.276.573.7
S.C.55.551.246.855.752.449.255.853.751.6
K.W11.7111.4311.1511.7811.5311.2811.8611.6311.41
Coil
G2FD090(S,H)351.011.011.01
T.C.S.C.KW
20Unitary Products Group
Page 21
MATCHING INDOOR COMPONENTS
ADD-ON COILS - FOR FURNACE APPLICATIONS
036-21121-002 Rev. B (0103)
G1UA
1/2 CASED
UPFLOW
G1FA
FULL CASED
UPFLOW
* Available with factory installed horizontal drain pan.
AIR HANDLERS - FOR NON-FURNACE APPLICATIONS
N1AH OR N1VS
MODULAR BLOWER
(UPFLOW, HORIZONTAL
AND DOWNFLOW)
G1HD
HORIZONTAL DUCT
G2FD*
MULTI-POSITION
(UPFLOW, HORIZONTAL
AND DOWNFLOW)
G1NA
UNCASED
UPFLOW
G2FD090 is upflow only.
Unitary Products Group21
G2FD
COIL
LIGHT COMMERCIAL
APPLICATIONS
F2RC / F2FC OR
F2RC / F2FP
FAN COIL UNITS
(UPFLOW, HORIZONTAL)