These Category IV, highly efficient, compact, condensing
type furnaces are designed for residential and commercial
installations in a basement, closet, alcove, recreation room or
garage where the ambient temperature is above 32°F, or
higher. They may be either side wall or thru-roof vented using
approved plastic type combustion air and vent piping. All
units are factory assembled, wired and tested to assure
dependable and economical installation and operation.
WARRANTY
Lifetime limited warranty on both heat exchangers to the original purchaser; a 20-year limited warranty from original installation date to subsequent purchaser.
10-year warranty on the heat exchanger in commercial applications.
5-year limited parts warranty.
FEATURES
•Compact, easy to install, ideal height 40" cabinet
•Blower-off delay for cooling SEER improvement.
•Easy to connect power/control wiring.
•Built-in, high level self diagnostics with fault code display.
•Low unit amp requirement for easy replacement application.
•Integrated control module for reliable, economical operation.
•May be installed as either two-pipe (sealed combustion)
or single pipe vent (using indoor combustion air)
•T op intake & vent connection allows installation in narrow
locations.
•Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
•Induced combustion system with inshot main burners for
quiet, efficient operation.
•No special vent termination kit required.
•100% shut off main gas valve for extra safety.
•PSC four speed, direct drive motor with large, quiet
blower.
•24V , 40 V A control transformer and blower relay supplied
for add-on cooling.
GY9S040A12UP1140/A1651/27.011 x 82014119
GY9S060B12UP1160/B1701/27.011 x 82014133
GY9S080B12UP1180/B1751/27.011 x 82014140
GY9S080C16UP1180/C1753/410.211 x 102014155
GY9S080C20UP1180/C170112.711 x 112012157
GY9S100C16UP11100/C1753/410.211 x 102014160
GY9S100C20UP11100/C170112.711 x 112012162
GY9S120D20UP11120/D170112.711 x 112012178
GY9S135D20UP11135/D175112.711 x 112012178
Nominal external static pressure is 0.50” w.c. at furnace outlet ahead of cooling coils.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
NOTES:
1. For altitudes above 2000 ft. reduce capacit y 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
Johnson Controls Unitary Products3
277805-YTG-A-1106
BLOWER PERFORMANCE CFM
Airflow with Bottom or One Side Return - without Filters (CFM)
MODELS
Speed
Tap
0.10.20.30.40.50.60.70.80.91.0
HIGH16351590153514801415134012801185NRNR
GY9S040A12UP11
M-HI1245122512051185116011101065995NRNR
M-LO10051000995975955925885825NRNR
LOW775770765750725680655620NRNR
HIGH1650160515701525146514101350127511701060
GY9S060B12UP11
GY9S080B12UP11
M-HI11651185117511651150114011001050970875
M-LO895915935940940920905860815750
LOW710725725725720700685660625560
HIGH2300221021202020193018301715159514801350
GY9S080C20UP11
GY9S100C20UP11
M-HI1950190018301755168015951500139012701155
M-LO161015451490144013901315123011551050920
LOW132512701225117511051045990905890790
HIGH1960195519251890183017651695161516001485
GY9S080C16UP11
GY9S100C16UP11
M-HI1565156015601575154515301475142513651260
M-LO1230127512851300131013001280124511901070
LOW930945965975975975975950910850
HIGH2560248524102320222021352035192017851650
GY9S120D20UP11
GY9S135D20UP11
M-HI2090205019901970188518201760167515451405
M-LO1695167516651615156515101460138512851140
LOW1175115011351110108510551005980970845
Airflow with Two Side Returns or with Bottom and One Side Return - Without Filters (CFM)
MODELS
Speed
Tap
0.10.20.30.40.50.60.70.80.91.0
HIGH2465238022952195209519951875176016201470
GY9S080C20UP11
GY9S100C20UP11
M-HI2085203519601880180017051605148513601235
M-LO172516251595154014851405131512351125995
LOW1420136013101255118011201070970950845
HIGH2615253524502385228521752075194518251670
GY9S120D20UP11
GY9S135D20UP11
M-HI2055204520151985193218551785173016051470
M-LO1690165016201600157015251470139513001200
LOW134513351335128512501230118011151010850
NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM).
2. Return air is through side opposite motor (left side) for one side return (worst case).
3. Airflows above 1800 CFM require either return from two sides or one side plus bottom.
4. Motor voltage at 115 V.
5. NR = Operation at this static pressure is not recommended.
External Static Pressure, Inches W.C
External Static Pressure, Inches W.C.
4Johnson Controls Unitary Products
277805-YTG-A-1106
FILTER PERFORMANCE
The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower performance of the system, apply the filter drop value for the filter being used or select an appropriate value from the “Filter
Performance” table shown below.
NOTE: The filter pressure drop values in the “Filter Performance” table shown below are typical values for the type of
filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter
manufacturer.
RECOMMENDED FILTER SIZES
Nominal CFM Cabinet Size Side Return Filter in.
1200A16 x 2514 x 25
1200B16 x 2516 x 25
1600C16 x 2520 x 25
2000C16 x 2520 x 25
2000D(2) 16 x 2522 x 25
NOTES:
1. Air velocity through throwaway type filters may not exceed 300
feet per minute. All velocities over this require the use of high
velocity filters.
2. Air flows above 1800 CFM require e ither return from two sides or
one side plus bottom.
APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1.Select the filter type.
2.Select the number of return air openings or calculate the
return opening size in square inches to determine the
proper filter pressure drop.
3.Determine the External System Static Pressure (ESP)
without the filter.
4.Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 3 to determine the
total system static.
5.If total system static matches a ESP value in the airflow
table (i.e. 0.20, 0.60, etc,) the system airflow corresponds to the intersection of the ESP column and Model/
Blower Speed row .
6.If the total system static falls between ESP values in the
table (i.e. 0.58, 0.75, etc.), the static pressure may be
rounded to the nearest value in the table determining the
airflow using Step 5 or calculate the airflow by using the
following example.
Example: For a 120,000 Btuh furnace with 2 return openings
and operating on high speed blower, it is found that total system static is 0.58" w.c. To determine the system airflow, complete the following steps:
1.Obtain the airflow values at 0.50" & 0.60" ESP.
Airflow @ 0.50": 2285 CFM
Airflow @ 0.60": 2175 CFM
2.Subtract the airflow @ 0.50" from the airflow @ 0.60" to
obtain airflow difference.
2175 - 2285 = -110 CFM
3.Subtract the total system static from 0.50" and divide this
difference by the difference in ESP values in the table,
0.60" - 0.50", to obtain a percentage.
(0.58 - 0.50) / (0.60 - 0.50) = 0.8
4.Multiply percentage by airflow difference to obtain airflow
reduction.
(0.8) x (-110) = -88
5.Subtract airflow reduction value to airflow @ 0.50" to
obtain actual airflow @ 0.58" ESP.
2288 - 88 = 2197
ACCESSORIES
PROPANE (LP) CONVERSION KIT -
1NP0347 - All Models
This accessory conversion kit may be used to convert natural
gas units for propane (LP) operation. Conversions must be
made by qualified distributor or dealer personnel.
CONCENTRIC VENT TERMINATION -
1CT0302 (2")
1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole.
SIDEWALL VENT TERMINATION KIT 1HT0901 (3”) and 1HT0902 (2”)
For use on sidewall, two-pipe installations only. Provides a
more attractive termination for locations where the terminal is
visible on the side of the home.
CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartridge has a 1/2" plastic tube fittings for installation in the drain line. Calcium carbonate refill media is also
available from the Source 1 Parts (p/n 026-30228-000).
EXTERNAL SIDE RETURN FILTER RACK -
1SF0101 - Fits all cabinet sizes
Attaches to side of furnace cabinet in side return applications.
Holds any 16x25x1 permanent or disposable filter.
SIDE RETURN FILTER -
1SR0302 - All Models
1SR0200 - All Models
BOTTOM RETURN FILTER -
1BR0114 or 1BR0214 - For 14-1/2” cabinets
1BR0117 or 1BR0217 - For 17-1/2” cabinets
1BR0121 or 1BR0221 - For 21” cabinets
1BR0124 or 1BR0224 - For 24-1/2” cabinets
INTERNAL FILTER WITH FIBER FILTER -
1HF0801 - All Models
HIGH ALTITUDE PRESSURE SWITCHES -
For installation where the altitude is less than 8,000 feet it is
not required that the pressure switch be changed. For altitudes above 8,000 feet see kits below. Conversion must be
made by qualified distributor or dealer personnel.