York BP 090 User Manual

TECHNICAL
TECHNICAL
GUIDE 50 HZ
HIGH EFFICIENCY SINGLE PACKAGE HEAT PUMPS
BP 090 & 120 7-1/2 and 10 NOMINAL TONS
9.1 EER
®
259336-YTG-B-0606
®
DESCRIPTION
YORK® Predator® heat pump units are convertible single pack­ages with a common footprint cabinet and common roof curb for all 7-1/2 and 10 ton models. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame.
®
All Predator on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.
All units are convertible between side and down airflow. Indepen­dent economizer designs are used on side and down discharge applications, as well as all tonnage sizes.
heat pump units are self-contained and assembled
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . 5
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . 6
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
LIST OF FIGURES
Fig. # Pg.#
1 PREDATOR® COMPONENT LOCATION. . . . . . . . . . .3
2 UNIT 4 POINT LOAD. . . . . . . . . . . . . . . . . . . . . . . . . .25
3 UNIT CENTER OF GRAVITY. . . . . . . . . . . . . . . . . . . .25
4 UNIT 6 POINT LOAD. . . . . . . . . . . . . . . . . . . . . . . . . .25
5 UNIT DIMENSIONS. . . . . . . . . . . . . . . . . . . . . . . . . . .26
6 PREDATOR® ROOF CURB DIMENSIONS . . . . . . . .27
7 SUNLINE™ TO PREDATOR® TRANSITION
ROOF CURBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
8 BOTTOM DUCT OPENINGS. . . . . . . . . . . . . . . . . . . .28
9 REAR DUCT DIMENSIONS. . . . . . . . . . . . . . . . . . . . .28
10 DOWNFLOW ECONOMIZER HOOD DETAIL. . . . . . .29
11 FACTORY INSTALLED DOWNFLOW ECONOMIZER30 12 FIELD INSTALLED DOWNFLOW ECONOMIZER
W/POWER EXHAUST. . . . . . . . . . . . . . . . . . . . . . . . .30
13 FIELD INSTALLED HORIZONTAL ECONOMIZER
W/POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . .31
14 SLAB ECONOMIZER DOWNFLOW W/POWER
EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
15 SLAB ECONOMIZER END RETURN W/POWER
EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
16 7-1/2 & 10 TON HEAT PUMP WITH OR WITHOUT
ELECTRIC HEAT WIRING DIAGRAM. . . . . . . . . . . . .33
LIST OF TABLES
Tbl. # Pg.#
1 PHYSICAL DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2 BP CAPACITY RATINGS. . . . . . . . . . . . . . . . . . . . . . . .8
3 COOLING CAPACITY 7-1/2 TON HP COOL
IMPERIAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4 COOLING CAPACITY 7-1/2 TON HP COOL
METRIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5 COOLING CAPACITY 10 TON HP COOL
IMPERIAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
6 COOLING CAPACITY 10 TON HP COOL
METRIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7 HEATING APPLICATION DATA 7-1/2 TON HP HEAT
(IMPERIAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
8 HEATING APPLICATION DATA 7 1/2 TON HP HEAT
(METRIC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
9 HEATING APPLICATION DATA 10 TON HP HEAT (IM-
PERIAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
259336-YTG-B-0606
Pg.#
Tbl. # 10 HEATING APPLICATION DATA 10 TON HP HEAT
(METRIC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
11 ELECTRICAL DATA - 7-1/2 TON HP . . . . . . . . . . . . .17
12 ELECTRICAL DATA - 10 TON HP . . . . . . . . . . . . . . .17
13 UNIT VOLTAGE LIMITATIONS. . . . . . . . . . . . . . . . . .17
14 ELECTRIC HEAT MULTIPLIERS . . . . . . . . . . . . . . . .17
15 BLOWER PERFORMANCE 7-1/2 TON
STANDARD MOTOR - SIDE DUCT (IMPERIAL) . . . .18
16 BLOWER PERFORMANCE 7-1/2 TON
STANDARD MOTOR - SIDE DUCT (METRIC). . . . . .18
17 BLOWER PERFORMANCE 7-1/2 TON
OPTIONAL MOTOR - SIDE DUCT (IMPERIAL) . . . . .18
18 BLOWER PERFORMANCE 7-1/2 TON OPTIONAL
MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . . . .19
19 BLOWER PERFORMANCE 10 TON STANDARD
MOTOR - SIDE DUCT (IMPERIAL). . . . . . . . . . . . . . .19
20 BLOWER PERFORMANCE 10 TON STANDARD
MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . . . .19
21 BLOWER PERFORMANCE 10 TON OPTIONAL
MOTOR - SIDE DUCT (IMPERIAL). . . . . . . . . . . . . . .20
22 BLOWER PERFORMANCE 10 TON OPTIONAL
MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . . . .20
23 BLOWER PERFORMANCE 7-1/2 TON STANDARD
MOTOR - DOWNSHOT (IMPERIAL). . . . . . . . . . . . . .21
24 BLOWER PERFORMANCE 7-1/2 TON STANDARD
MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . . . .21
25 BLOWER PERFORMANCE 7-1/2 TON OPTIONAL
MOTOR - DOWNSHOT (IMPERIAL). . . . . . . . . . . . . .21
26 BLOWER PERFORMANCE 7-1/2 TON OPTIONAL
MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . . . .22
27 BLOWER PERFORMANCE 10 TON STANDARD
MOTOR - DOWNSHOT (IMPERIAL). . . . . . . . . . . . . .22
28 BLOWER PERFORMANCE 10 TON STANDARD
MOTOR - DOWNSHOT (METRIC). . . . . . . . . . . . . . .22
29 BLOWER PERFORMANCE 10 TON OPTIONAL
MOTOR - DOWNSHOT (IMPERIAL). . . . . . . . . . . . . .23
30 BLOWER PERFORMANCE 10 TON OPTIONAL
MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . . . .23
31 ADDITIONAL STATIC RESISTANCE - IMPERIAL . . .24
32 ADDITIONAL STATIC RESISTANCE - METRIC. . . . .24
33 ELECTRIC HEAT MINIMUM SUPPLY AIR -
IMPERIAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
34 ELECTRIC HEAT MINIMUM SUPPLY AIR -
METRIC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
35 INDOOR BLOWER SPECIFICATIONS. . . . . . . . . . . .25
36 4 POINT LOAD WEIGHT. . . . . . . . . . . . . . . . . . . . . . .25
37 6 POINT LOAD WEIGHT. . . . . . . . . . . . . . . . . . . . . . .26
38 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
39 UNIT CLEARANCES. . . . . . . . . . . . . . . . . . . . . . . . . .26
40 ECONOMIZER USAGE. . . . . . . . . . . . . . . . . . . . . . . .29
2 Unitary Products Group
259336-YTG-B-0606
Simplicity
w/screw connectors for T­stat wiring and network
Terminal block for hi-voltage connection
Second Model Nameplate Inside Control Door
Dual stage cool­ing for maximum comfort (7-1/2 ­12-1/2 Only)
Compressor #2 Access (High-Eff Compressor)
Base Rails w/ Forklift Slots (3 Sides) & Lifting Holes
Roof curbs in eight- and fourteen-inch heights. Roof curbs for transitioning from Sunline™ footprint to the BP series footprint are also available (field installed accessory)
connection
Control board
Tool-less Door Latch
Disconnect location (optional disconnect switch)
Side entry power and control wiring knockouts
Filter access (2” throw-away)
Compressor #1 Access (High-Eff Compressor)
Filter drier (solid core)
Condenser section
Slide-out motor and blower assembly for easy adjustment and service.
Belt-drive blower motor
Slide-out drain pain with steel 3/4” NPT Connection
FIGURE 1 - PREDATOR® COMPONENT LOCATION
FEATURES
High Efficiency – High efficiency units reach as high as
9.1 EER.
®
Service Friendly – The Predator ber of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common assembly. This facilit ates greater access to all the indoor airflow components, thus simplifying maintenance and adjustment.
Service time is reduced through the use of hinged, tool­less panels. Such panels provide access to frequently inspected components and areas, including the control box, compressors, filters, indoor motor & blower, and the heating section. The panels are screwed in place at the factory to prevent access by children or other unautho­rized persons. It is recommended that the panels be secured with screws once service is complete.
incorporates a num-
Service windows have been placed in both condenser section walls. Rotation of the cover allows easy access to the condenser coils for cleaning or inspection.
The unit control board utilizes flash codes to aid in diag­nosis of unit malfunctions. Unique flash codes quickly identify the source of the unit alarm.
All units use the same standard filter size. This stan­dardization removes any confusion on which filter sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to per­mit easy cleaning. The drain pan is accessed by remov­ing the drain pan cover plate on the rear of the unit. Once the plate is removed, the drain pan slides out through the rear of the unit.
®
All Predator
units have a second model nameplate located inside the control access door. This is to prevent deterioration of the nameplate through weathering.
Unitary Products Group 3
259336-YTG-B-0606
Environmentally Aware – For improved Indoor Air Quality, foil faced insulation is used exclusively through­out the units.
Convertible Airflow Design – The side duct openings are covered when they leave the factory. If a side sup­ply/return is desired, the installer simply removes the two side duct covers from the outside of the unit and installs them over the down shot openings. No panel cutting is required. Convertible airflow design allows maximum field flexibility and minimum inventory.
System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil frost­ing when the economizer operates at low outdoor air tem­peratures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low­pressure switches. Internal compressor protection is stan­dard on all compressors. Crankcase heaters are standard on reciprocating compressors. Scroll compressors do not require crankcase heaters. Phase Monitors are standard on units with scroll compressors. This accessory monitors the incoming power to the unit and protects the unit from phase loss and reversed phase rotation.
Advanced Controls - Simplicity™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to 0°F (-17.8°C) outdoor ambient without additional assistance. Optionally, the- control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti-short cycle delay can be temporarily overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling fan delay times are independent of one ano ther. All units are programmed with default values based upon their configuration of cooling and heating.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats and the temperature limit switch on electric heat units. The unit control board will alarm on compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip
three times within two hours before the unit control board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
Reliable – From the beginning – All units undergo com­puter automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. All Predator
®
units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint used has been proven by a 750 hour salt spray test.
Flexible Placement – All models and configurations share the same cabinet/footprint and thus the same roof curb. You have the flexibility to set one curb and choose the correct tonnage size after the internal loads have been determined.
To further simplify planning and installation, Predator cabinets are designed to fit your roof. With the optional roof curb, the unit ductwork is designed to fit around 24” (610 mm) on-center joists or between 48” (1219 mm) on­center joists.
The drain pan can be rotated to drain to either the front or the rear of the unit. Additionally, the drain pan can be fitted to drain through the roof curb. As it is sometimes difficult to have a level installation, the drain pan features a generous slope to ensure proper drainage.
Full Perimeter Base Rails – The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer fork­lift access from 3 sides, and rigging holes are available so that an overhead crane can be used to place the units on a roof.
Easy Installation – Electric utility knockouts are supplied in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a field sup­plied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor.
All units are shipped with 2” (51 mm) throw-away filters installed.
Wide Range of Indoor Airflows – All indoor fan motors are belt-drive type providing maximum flexibility to handle most airflow requirements. For high static applications, factory installed alternate indoor fan motors are available. With the optional indoor fan motor, all units can supply nominal airflow at up to 1.5” (375 Pa) ESP.
®
4 Unitary Products Group
259336-YTG-B-0606
FACTORY INSTALLED OPTIONS
YORK® offers several equipment options factory installed, for the Predator® line.
Optional Factory Installed Economizers - Predator units offer a variety of optional factory installed econo­mizers with low leak dampers. The outdoor air enthalpy sensor enables economizer operation if the outdoor enthalpy is less than the setpoint of the economizer logic module. See Table 41 to determine the correct econo­mizer for your application.
Downflow Economizer - (With barometric relief) -
The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The installer needs only to assemble and mount the outdoor air hood (Pro­vided). The economizer has spring return, fully modu­lating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to econo­mizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the
economizer control accepts an optional CO demand ventilation. With single enthalpy input, the
economizer control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With a dual input kit installed, the econ­omizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.
Horizontal Economizer - (Without barometric
relief) - All features as the downflow economizer exist except you must order the barometric relief separately. You must order a 1EH0408 if you are
installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizers only.
BAS Ready Economizer -(With barometric relief)
- The economizer is provided with a Belimo actuator that requires a 0-10V DC input from an external source (i.e., field installed building automation sys­tem controller). Power exhaust options are avail­able. The economizer is 2% low leakage type with spring return and fully modulating dampers capable of introducing up to 100% outside air. Also include 2” (51 mm) pleated filters.
Power Exhaust (Downflow only) - This accessory installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized out­door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out­door air dampers open to the preset position when th e indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
input for
2
Alternate Indoor Blower Motor - For applications with high static restrictions, units are offered with optional indoor motors that provide higher static output and/or higher airflow, depending upon the installer’s needs.
Electric Heaters - The electric heaters range from 9kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. All heaters are intended for single point power supply.
Disconnect Switch - For heat pumps with electric heat, a HACR breaker sized to the unit is provided. For heat pump only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. Available for both the supply and/or return air.
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during "off" times due to out side air infiltration. These smoke detectors have an operational limit of 32 °F to 131°F. Smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on unit s with Scroll Compressors.)
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pres­sure switch that energizes the fault light on the unit ther­mostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
Technicoat Condenser Co ils - The condenser coils are coated with a phenolic coating for protection against cor­rosion due to harsh environments.
Technicoat Evaporator C oil - The evaporator coils are coated with a phenolic coating for protection against cor­rosion due to harsh environments.
Novar® BAS Control - The Novar® ETC-3 building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
Johnson Controls BAS Control - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
Unitary Products Group 5
259336-YTG-B-0606
CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto­mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
FIELD INSTALLED ACCESSORIES
YORK® offers several equipment accessories for field instal­lation, for the Predator
Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the econo­mizer control accepts an optional CO ventilation.With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit pro­vides a second input used to monitor the return air. With a dual input kit installed, the economizer control com­pares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maxi­mum efficiency possible
Horizontal Economizer - (Without barometric relief) ­All features as the downflow economizer exist except you must order the barometric relief separately. You
must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizers only.
Dual Enthalpy Control, Accessory - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed slab economizers.
Power Exhaust - This accessory installs in the unit with a down flow economizer. Power exhaust plugs into the connector in the unit bulkhead. You must purchase
1EH0408 barometric relief/power exhaust hood when applying to a horizontal flow application.
Manual Outdoor Air Damper - Like the motorized out­door air damper, each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.
®
line.
input for demand
2
Motorized Outdoor Air Damper - The motorized out­door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
CO
Sensor - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the preset limits.
Dirty Filter Switch - This kit includes a differential pres­sure switch that energizes the fault light on the unit ther­mostat, indicating that there is an abnormally high pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.
Electric Heaters - The electric heaters range from 9 kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. Cooling units include an adapter panel for easy installation of the elec­tric heaters. Necessary hardware and connectors are included with the heaters. All heaters are intended for single point power supply.
Metal Frame Filter Kit - Metal frame with polyester filter medium.
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available in 8” (203 mm) and 14” (356 mm) heights. For applica­tions with security concerns, burglar bars are available for the duct openings of the roof curbs.
Roof Curb Transition - Single Piece Adapter (10” (254 mm) High) - Roof curbs for transitioning from Sunline™ units to Predator
®
Magnum. Fits 7.5 to 12.5 Sunline™
roof curbs only.
Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24- volt electronic and electro-mechanical thermostats. All units (with or without an economizer) operate with two­stage heat/two-stage cool or two-stage cooling only ther­mostats, depending upon unit configuration.
6 Unitary Products Group
259336-YTG-B-0606
NOMENCLATURE
B P 090 C00 A 7 A AA 3 0 1 2 4 A
7.5-10.0 Ton York® Model Number Nomenclature
Product Category
B = HP, Single Pkg., R-22
Product Identifier
P = 9.3-10.6 EER HP
Nominal Cooling Capacity
090 = 7.5 Ton 120 = 10.0 Ton
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No heat installed
Electric Heat Options
E09 = 9 KW E18 = 18 KW E24 = 24 KW E36 = 36 KW E54 = 54 KW
Airflow
A = Std. Motor B = Std. Motor/Econo./Barometric Relief (Downflow
Only) C = Std. Motor/Econo./Power Exhaust (Downflow Only) D = Std. Motor/Motorized Damper (Downflow Only) E = Std. Motor/Horizontal Economizer (No Baro.) F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only) G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only) N = Hi Static Mtr. P = Hi Static Mtr./Econo./Barometric Relief
(Downflow Only) Q = Hi Static Mtr./Econo./Power Exhaust
(Downflow Only) R = Hi Static Mtr./Motorized Damper (Downflow Only) S = Hi Static Mtr./Horizontal Economizer (No Baro.) T = Hi Static Mtr./Slab Econo./Power Exhaust
(Downflow Only) U = Hi Static Mtr./Slab Econo./Barometric Relief
(Downflow only)
Voltage
7 = 380/415-3-50
Product Style
A = Style A B = Style B C = Style C
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
Honeywell Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
BAS Ready Unit with Belimo Economizer
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
3 = Third Generation 4 = Fourth Generation
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed B = Option 1 C=Option2 D=Options1&2 E = Option 3 F = Option 4 G = Options 1 & 3 H=Options1&4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N=Options2&3 P = Options 2 & 4 Q = Options 2, 3, & 4 R=Options3&4 S = Option 5 T=Options1&5 U=Options1,3,&5 V = Options 1, 4, & 5 W=Options1,3,4,&5 X=Options3&5 Y=Options4&5 Z = Options 3, 4 & 5
Configuration Options (not required for all units)
Additional Options
RC = Coil Guard, Shipping Bag & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils
Options
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5=Pwr'dConv.Outlet
Unitary Products Group 7
TABLE 1: PHYSICAL DATA
Blower, Centrifugal Dia. X Wd. in. (Dia. X Wd. mm) 15 x 15 (381 x 381) 15 x 15 (381 x 381)
Evaporator
Blower
Evaporator Coil
Condenser Fan
(2 per Unit)
Condenser Coil
(2 per unit)
Refrigerant
Charge
Compressors
Air Filters
MODELS
COMPONENT
090 120
Motor, Standard HP (kW) 1-1/2 (1.1) 2 (1.5)
Motor, Optional HP (kW) 2 (1.5) 4 (3)
Rows 3 4
Fins per Inch (2.54 cm.) 15 15
Height in. (mm) 40 (1020) 40 (1020)
2
Face Area ft.
Propeller Dia. in., each (mm) 24 (610) 24 (610)
Motor HP, each (kW) 3/4 (.56) 3/4 (.56)
CFM, Nominal (each) 4000 4000
Fins per Inch (2.54 cm) 20 20
Height in., each (mm) 44 (1120) 44 (1120)
Face Area ft.
System 1 lb./oz. (kg) 9 lbs. 4 oz. (4.20) 15 lbs. 4 oz. (6.92) System 2 lb./oz. (kg) 9 lbs. 0 oz. (4.06) 15 lbs. 0 oz. (6.80)
Size Wd. x Ht. x Thickness in.
(Wd. x Ht x Thickness mm)
Number Per Unit 4 4
each (m2)
Rows (each) 1 2
2
each (mm)
Quantity 2 2
Type Recip Scroll
13.2 (1.23) 13.2 (1.23)
14.5 (1.35) 14.5 (1.35)
25x20x2
(635 x 508 x 51)
259336-YTG-B-0606
25x20x2
(635 x 508 x 51)
TABLE 2: BP CAPACITY RATINGS
SIZE
(TONS)
7-1/2 (090)
10
(120)
8 Unitary Products Group
COOLING CAPACITY ARI RATINGS
MBH EER IPLV
93 9.1 7.5 3000 86 3.1 44 2.0 84 9, 18, 24 34
120 9.4 9.4 4000 116 3.15 75 2.25 85 18, 24, 34 54
* Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb. † Rated in accordance with ARI 270 standard. ‡ See Table 14.
*
CFM
MBH @
47° F
HEATING CAPACITY
COP @
47°F
MBH @
17°F
COP @
17°F
SOUND RATING
(dB)
NOM ELEC
HEAT CAP
(kW)
259336-YTG-B-0606
TABLE 3: COOLING CAPACITY 7-1/2 TON HP COOL IMPERIAL
Air On
Evap. Coil
WB
CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
Cap.
(°F)
(MBH)
72 109 8.7 61 55 48 42 35 #N/A #N/A 104 9.4 58 52 45 39 33 #N/A #N/A 67 98 8.4 74 68 62 55 49 42 36 92 8.9 72 66 59 53 46 40 34 62 89 8.0 88 81 75 69 62 56 49 83 8.6 83 79 73 66 60 53 47 57 95 8.0 93 87 80 74 68 61 55 84 8.5 84 82 75 69 62 56 50 72 112 8.8 67 59 52 44 36 #N/A #N/A 106 9.5 64 56 49 41 34 #N/A #N/A 67 101 8.5 81 74 66 58 51 43 36 94 9.0 79 71 64 56 49 41 33 62 92 8.1 91 88 80 73 65 58 50 85 8.7 85 83 78 70 63 55 48 57 97 8.1 97 93 86 79 71 63 56 86 8.6 86 85 81 73 66 58 51 72 115 8.9 73 64 55 46 38 #N/A #N/A 109 9.6 70 61 52 43 35 #N/A #N/A 67 104 8.5 88 79 70 62 53 44 35 97 9.1 86 77 68 59 51 42 33 62 94 8.2 94 94 86 77 68 59 51 88 8.8 88 88 83 75 66 57 48 57 100 8.1 100 100 92 83 75 66 57 88 8.7 88 88 86 78 69 60 51 72 117 8.9 78 68 58 48 38 #N/A #N/A 112 9.7 75 65 55 45 35 #N/A #N/A 67 106 8.6 94 84 74 64 54 44 34 99 9.2 92 82 72 62 52 42 32 62 96 8.2 96 96 90 80 70 60 50 90 8.9 90 90 88 78 68 58 48 57 102 8.2 102 102 97 87 77 67 57 91 8.8 91 91 90 80 70 60 50 72 120 9.0 83 72 61 50 38 #N/A #N/A 115 9.8 80 69 58 47 35 #N/A #N/A 67 108 8.6100897866554433102 9.3 98877664534231 62 98 8.3 98 98 94 83 72 61 50 92 8.9 92 92 92 81 70 59 48 57 104 8.2 104 104 101 90 79 68 57 93 8.9 93 93 93 82 71 60 49
72 101 10.1 60 53 47 40 34 #N/A #N/A 98 10.9 61 55 48 42 35 #N/A #N/A 67 88 9.6 74 67 61 54 48 42 35 84 10.3 75 69 62 56 50 43 37 62 79 9.2 79 77 74 67 61 54 48 74 9.9 74 74 74 68 62 55 49 57 79 9.2 79 78 75 68 62 55 49 74 9.9 74 74 74 68 61 55 48 72 102 10.2 64 56 48 41 33 #N/A #N/A 99 10.9 63 56 48 41 33 #N/A #N/A 67 89 9.7 78 71 63 56 48 40 33 84 10.3 78 70 63 55 47 40 32 62 80 9.3 80 79 76 69 61 54 46 75 9.9 75 75 75 67 59 52 44 57 80 9.2 80 80 77 70 62 55 47 74 9.9 74 74 74 67 59 51 44 72 104 10.2 68 59 50 41 33 #N/A #N/A 99 10.9 66 57 48 39 31 #N/A #N/A 67 90 9.7 83 74 65 57 48 39 30 84 10.3 80 71 63 54 45 36 28 62 81 9.3 81 81 79 70 62 53 44 75 9.9 75 75 75 66 57 49 40 57 81 9.3 81 81 80 72 63 54 45 74 9.9 74 74 74 66 57 48 39 72 106 10.3 73 63 53 43 33 #N/A #N/A 100 11.0 72 62 52 42 32 #N/A #N/A 67 92 9.8 88 79 69 59 49 39 30 85 10.4 83 77 67 57 47 37 27 62 83 9.4 83 83 82 72 62 52 42 76 10.0 76 76 76 66 56 46 36 57 83 9.4 83 83 83 73 63 53 43 75 9.9 75 75 75 65 55 45 35 72 108 10.4 79 68 56 45 34 #N/A #N/A 102 11.0 77 66 55 44 33 #N/A #N/A 67 94 9.9 92 85 73 62 51 40 29 86 10.5 86 82 71 60 49 38 27 62 85 9.5 85 85 85 73 62 51 40 77 10.0 77 77 77 66 54 43 32 57 85 9.4 85 85 85 74 62 51 40 76 10.0 76 76 76 65 54 43 32
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
Tot.
96 80 70 69 95 79 69 68 94 78 68 67 95 78 69 68 95 79 69 68
Tot.
*
Input
(kW)
Temperature of Air on Condenser Coil 105°F Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
11.6 62 56 50 43 37 #N/A #N/A
11.0 77 70 64 58 51 45 38
10.5 70 70 70 69 62 56 50
10.5 69 69 69 67 60 54 48
11.6 63 55 48 40 33 #N/A #N/A
11.0 77 70 62 54 47 39 32
10.5 69 69 69 65 58 50 43
10.5 68 68 68 63 56 48 40
11.5 64 55 46 38 29 #N/A #N/A
11.0 77 69 60 51 42 34 25
10.5 68 68 68 62 53 44 35
10.4 67 67 67 60 51 42 33
11.6 70 60 50 40 30 #N/A #N/A
11.0 78 74 64 55 45 35 25
10.5 69 69 69 60 50 40 30
10.5 68 68 68 58 48 38 28
11.6 76 65 54 42 31 #N/A #N/A
11.1 79 79 69 58 47 36 24
10.6 69 69 69 58 47 35 24
10.5 68 68 68 57 46 34 23
86 83 80 77 74 71 68 86 83 80 77 74 71 68
Sensible Capacity (MBH)
Return Dry Bulb (°F)
*
Tot.
Cap.
(MBH)
Tot.
*
Input
Sensible Capacity (MBH)
Return Dry Bulb (°F)
(kW)
* These capacities are gross ratings. For net
capacity , deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate Blower Perfor­mance Table for the kW of the supply air blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply air blower motor.
*
Unitary Products Group 9
TABLE 4: COOLING CAPACITY 7-1/2 TON HP COOL METRIC
Return
Air
3
m
s
1.06
1.24
1.42
1.53
1.77
1.06
1.24
1.42
1.53
1.77
1.06
1.24
1.42
1.53
1.77
Gross
WB
Cap.
(°C)
(kW)
32 8.7 17 16 14 12 11 #N/A #N/A 30 9.4 17 15 13 12 10 #N/A #N/A
22
29 8.4 21 20 18 16 15 13 11 27 8.9 21 19 17 16 14 12 11
19
26 8.0 25242220191715 24 8.6 24232120181615
17
28 8.0 27252422201917 25 8.5 25242220191715
14
33 8.8 19 17 15 13 11 #N/A #N/A 31 9.5 18 16 14 12 10 #N/A #N/A
22
30 8.5 23 21 19 17 15 13 11 28 9.0 23 21 19 17 15 13 11
19
27 8.1 26262422201816 25 8.7 25242321191715
17
29 8.1 28272523211917 25 8.6 25252422201816
14
34 8.9 21 18 16 14 12 #N/A #N/A 32 9.6 20 18 15 13 11 #N/A #N/A
22
30 8.5 25 23 21 18 16 14 11 28 9.1 25 22 20 18 15 13 11
19
28 8.2 28272523211816 26 8.8 26262422201815
17
29 8.1 29292725222018 26 8.7 26262523211816
14
34 8.9 22 20 17 14 12 #N/A #N/A 33 9.7 21 19 16 13 11 #N/A #N/A
22
31 8.6 27 24 22 19 16 14 11 29 9.2 26 24 21 18 16 13 11
19
28 8.2 28282624211916 26 8.9 26262623211815
17
30 8.2 30302826232018 27 8.8 27272624211816
14
35 9.0 24 21 18 15 12 #N/A #N/A 34 9.8 23 20 17 14 11 #N/A #N/A
22
32 8.6 29 26 23 20 17 14 11 30 9.3 28 25 22 19 16 13 10
19
29 8.3 29292825221916 27 8.9 27272724211815
17
31 8.2 31313027242118 27 8.9 27272724211916
14
30 10.1 17 15 14 12 10 #N/A #N/A 29 10.9 17 16 14 12 11 #N/A #N/A
22
26 9.6 21 20 18 16 14 13 11 25 10.3 22201817151312
19
23 9.2 23222220181615 22 9.9 22222220181715
17
23 9.2 23232220181715 22 9.9 22222220181715
14
30 10.2 18 16 14 12 10 #N/A #N/A 29 10.9 18 16 14 12 10 #N/A #N/A
22
26 9.7 22 20 18 17 15 13 11 25 10.3 22201816141210
19
23 9.3 23232220181614 22 9.9 22222220181614
17
24 9.2 24232321191715 22 9.9 22222220181614
14
30 10.2 19 17 15 12 10 #N/A #N/A 29 10.9 19 16 14 12 10 #N/A #N/A
22
27 9.7 24211917151210 25 10.32321181614119
19
24 9.3 24242321191614 22 9.9 22222220171513
17
24 9.3 24242421191714 22 9.9 22222219171513
14
31 10.3 21 18 16 13 10 #N/A #N/A 29 11.0 20 18 15 13 10 #N/A #N/A
22
27 9.8 25232018151210 25 10.42422201714129
19
24 9.4 24242421191614 22 10.022222220171412
17
24 9.4 24242422191614 22 9.9 22222219171412
14
32 10.4 22 19 17 14 11 #N/A #N/A 30 11.0 22 19 16 13 10 #N/A #N/A
22
28 9.9 27242219161310 25 10.52524211815129
19
25 9.5 25252522191613 22 10.022222220171411
17
25 9.4 25252522191613 22 10.022222219171411
14
28 11.6 18 16 15 13 11 #N/A #N/A
22
23 11.0 22 20 19 17 15 14 12
19
20 10.5 20 20 20 20 19 17 15
17
20 10.5 20 20 20 20 18 16 15
14
28 11.6 18 16 14 12 10 #N/A #N/A
22
23 11.0 22 20 18 16 14 12 10
19
20 10.5 20 20 20 19 17 15 13
17
20 10.5 20 20 20 19 17 15 13
14
28 11.5 18 16 14 11 9 #N/A #N/A
22
23 11.0 22 20 18 15 13 11 8
19
20 10.5 20 20 20 18 16 14 11
17
20 10.4 20 20 20 18 15 13 11
14
28 11.6 20 17 15 12 9 #N/A #N/A
22
23 11.0 23 22 19 16 14 11 8
19
20 10.5 20 20 20 18 15 13 10
17
20 10.5 20 20 20 17 15 12 10
14
28 11.6 22 19 16 13 10 #N/A #N/A
22
23 11.1 23 23 20 17 14 11 9
19
20 10.6 20 20 20 17 14 11 8
17
20 10.5 20 20 20 17 14 11 8
14
Outdoor Ambient Temperature (C) 29 Outdoor Ambient Temperature (C) 35
Tot.
*
Input
(kW)
30 28 27 25 23 22 20 30 28 27 25 23 22 20
Sensible Capacity (kW)
Return Dry Bulb (°C)
*
Outdoor Ambient Temperature (C) 41 Outdoor Ambient Temperature (C) 46
Outdoor Ambient Temperature (C) 52
259336-YTG-B-0606
Gross
Cap. (kW)
Tot.
*
Input
Sensible Capacity (kW)
Return Dry Bulb (°C)
(kW)
* These capacities are gross ratings. For net
capacity , deduct air blower motor , kW . Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply air blower motor.
*
10 Unitary Products Group
259336-YTG-B-0606
TABLE 5: COOLING CAPACITY 10 TON HP COOL IMPERIAL
Air On
Evap. Coil
WB
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
Cap.
(°F)
(MBH)
72 130 9.9 78 69 61 52 44 35 26 127 11.0 77 69 60 51 43 34 26 67 123 9.7 100 91 83 74 66 57 49 119 10.8 98 90 81 72 64 55 47 62 115 9.6 115 109 100 92 83 75 66 111 10.6 111 109 100 92 83 74 66 57 113 9.5 113 110 102 93 85 76 68 109 10.6 109 107 99 90 81 73 64 72 134 10.0 86 76 66 56 46 36 26 130 11.1 86 75 65 55 45 35 25 67 127 9.8 110 100 90 80 70 60 50 122 10.9 108 98 88 78 68 58 48 62 119 9.6 119 116 109 99 89 79 69 115 10.7 115 113 109 99 89 79 69 57 117 9.6 117 115 111 101 91 81 70 113 10.7 113 112 107 97 87 77 67 72 137 10.1 95 83 71 60 48 36 25 134 11.2 94 82 71 59 47 36 24 67 131 9.9 121 109 98 86 74 63 51 126 10.9 119 107 95 84 72 61 49 62 122 9.7 122 122 118 107 95 83 72 118 10.7 118 118 118 106 95 83 71 57 120 9.6 120 120 120 108 97 85 73 116 10.7 116 116 116 104 93 81 69 72 140 10.1 102 89 76 63 49 36 23 136 11.2 102 89 76 62 49 36 23 67 133 9.9 128 117 104 90 77 64 51 128 11.0 124 116 102 89 76 62 49 62 124 9.7 124 124 122 109 96 82 69 120 10.7 120 120 120 106 93 80 66 57 122 9.7 122 122 122 109 95 82 69 118 10.8 118 118 118 104 91 78 65 72 142 10.1 110 95 80 65 51 36 21 138 11.2 110 96 81 66 51 36 21 67 135 9.9 135 125 110 95 80 65 50 129 11.0 129 124 109 94 79 64 49 62 126 9.7 126 126 126 111 96 81 66 121 10.8 121 121 121 106 91 76 62 57 124 9.7 124 124 124 109 94 79 64 119 10.8 119 119 119 104 90 75 60
72 121 12.3 75 66 58 49 41 32 24 116 13.6 73 64 56 47 38 30 21 67 111 12.1 95 86 78 69 61 52 44 104 13.3 92 83 75 66 58 49 40 62 104 11.7 104 101 93 84 76 67 58 97 12.9 97 94 85 77 68 60 51 57 103 11.8 103 100 92 83 75 66 58 97 12.9 97 94 85 77 68 59 51 72 125 12.4 83 73 63 53 43 33 23 119 13.7 81 71 61 51 41 31 21 67 114 12.2 104 95 85 75 65 55 45 106 13.5 100 92 82 72 62 52 42 62 107 11.8 107 106 101 91 81 71 61 100 13.0 100 98 94 84 74 64 53 57 106 11.9 106 105 101 90 80 70 60 100 13.1 100 98 94 84 73 63 53 72 128 12.5 92 80 69 57 45 34 22 122 13.9 90 78 67 55 43 32 20 67 118 12.3 114 104 93 81 69 58 46 109 13.6 109 101 90 78 66 55 43 62 110 11.9 110 110 110 99 87 75 64 103 13.2 103 103 103 91 79 68 56 57 109 12.0 109 109 109 98 86 74 63 102 13.2 102 102 102 91 79 67 56 72 130 12.5 100 87 74 61 47 34 21 124 13.9 99 85 72 59 46 32 19 67 119 12.3 118 111 100 86 73 60 47 111 13.6 111 107 97 84 71 57 44 62 112 12.0 112 112 112 99 85 72 59 104 13.2 104 104 104 91 78 65 51 57 111 12.0 111 111 111 98 84 71 58 104 13.2 104 104 104 91 78 64 51 72 132 12.5 109 94 79 64 49 34 20 127 13.9 107 93 78 63 48 33 18 67 121 12.3 121 119 107 92 77 62 47 113 13.6 113 113 104 89 75 60 45 62 114 12.0 114 114 114 99 84 69 54 106 13.2 106 106 106 91 77 62 47 57 113 12.0 113 113 113 98 83 68 53 106 13.2 106 106 106 91 76 61 47
72 111 14.870625345362819 67 96 14.6 89 80 71 63 54 46 37 62 90 14.0 90 86 78 69 61 52 44 57 91 14.1 91 87 78 70 61 53 44 72 113 15.079695949392919 67 99 14.8 96 89 79 69 59 49 39 62 93 14.2 93 91 86 76 66 56 46 57 93 14.3 93 91 87 77 67 57 46 72 116 15.288766553413018 67 101 14.9 101 99 87 75 64 52 40 62 95 14.4 95 95 95 83 71 60 48 57 95 14.4 95 95 95 84 72 60 49 72 118 15.297847057443117 67 103 14.9 103 103 94 81 68 55 41 62 97 14.4 97 97 97 84 70 57 44 57 97 14.4 97 97 97 84 71 58 44 72 121 15.2 106 91 76 61 46 31 16 67 105 14.9 105 105 102 87 72 57 42 62 99 14.4 99 99 99 84 69 54 39 57 100 14.4 100 100 100 85 70 55 40
Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
Tot.
Tot.
*
Input
(kW)
Temperature of Air on Condenser Coil 105°F Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
Sensible Capacity (MBH)
Return Dry Bulb (°F)
*
Tot.
Cap.
(MBH)
Tot.
*
Input
Sensible Capacity (MBH)
Return Dry Bulb (°F)
(kW)
* These capacities are gross ratings. For net
capacity , deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate Blower Perfor­mance Table for the kW of the supply air blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply air blower motor.
*
Unitary Products Group 11