York B3CH 048, B3CH060 User Manual

®
SUNLINE 2000
SINGLE PACKAGE HEAT PUMPS
INSTALLATION INSTRUCTION
GENERAL
YORK Model BCH units are single package heat pumps designed for outdoor installation on a rooftop or a slab. Supplemental electric heaters are available as field-installed accessories. The units are manufactured under ISO 9002 Quality System Certification.
Units are completely assembled on rigid, permanently attachedbaserails.Allpiping,refrigerant charge, andelectrical wiring is factory-installed and tested. The units require only electricpowerandductconnectionsatthe point of installation.
The supplemental electric heaters have nickel-chrome elements and utilize single point power connection.
Supersedes: 511.13-N1YI (900)/035-12984-000
MODELS B3CH 048 AND 060
(WORLD 50 HZ)
530.18-N7.1V -Electric Heater Accessory
530.18-N7.2V -Fuse Block Accessory
Renewal Parts:
Refer to Parts Manual for complete listing of replacement parts on this equipment.
All forms referenced in this instruction may be ordered from:
Standard Register Toll Free Tel: (405) 691-1126 Toll Free Fax: (405) 799-7746
035-12984-001-A-0204
INSPECTION
Assoonasaunit is received, itshouldbeinspectedforpossible damage during transit. If damage is evident, the extent of the damageshould be noted on thecarrier's freight bill. Aseparate request for inspection by the carrier's agent should be made in writing. See local distributor for additional information.
APPROVALS
These units are designed and manufactured as follows:
1. For use as a heat pump only unit or a heat pump unit with supplemental electric heat.
2. For outdoor installation only.
REFERENCE
Additional information on the design, installation, operation and service of this equipment is available in the following reference forms:
55.70-N1 -General Installation
55.70-N2 -Pre-start & Post-start Check List
530.18-N1.2V -Economizer Accessory
530.18-N1.4V -Fixed Outdoor Air Damper Accessory
530.18-N1.6V -Motorized Outdoor Air Damper Accy.
Installershouldpay particular attentionto thewords: NOTE, CAUTIONand WARNING.Notes installation easier. Cautions and/or equipment damage may result if installation procedure is not handled properly.
are given to prevent equipment damage. Warnings are given to alert installer that personal injury
TH IS P RO DU CT MU ST BE INS TAL LED IN STR IC T C O M P LIANCE W ITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE
LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED
TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
CAUTION
WARNING
areintended to clarifyor makethe
035-12984-001-A-0204
TABLE OF CONTENTS
General Inspection Reference Approvals Nomenclature
................................................................................
............................................................................
............................................................................
............................................................................
......................................................................
INSTALLATION
Limitations Location Condensate Drainage Precaution Rigging and Handling Clearances Ductwork Filters Condensate Drain Service Access Blower Speed Selection Disconnect Switch Bracket For Optional Belt-Drive Compressors Thermostat Power and Control Wiring
Electric Heaters...................................................................4
Optional Economizer Rain Hood.........................................6
...........................................................................
...............................................................................
.......................................
..........................................................
..........................................................................
.............................................................................
...................................................................................
...............................................................
....................................................................
......................................................
............
.......................................................................
..........................................................................
...................................................
OPERATION
Cooling System .................................................................12
Preliminary Operation Cooling ..........................................12
Cooling Sequence of Operation ........................................12
Heating Sequence of Operation........................................12
Defrost Sequence of Operation.........................................12
Lockout Control Checking Supply Airflow Secure Owner's Approval
.................................................................
....................................................
..................................................
13 13 14
1 1
Normal Maintenance
1 1 2
No. Description Page
1 Unit Application Data
3 3 3 3 3 3 4 4 4 4
2 Air Flow Limitations 3 Physical Data 4 Supply Air Perferformance — BCH048 5 Supply Air Performance — BCH060 6 Motor and Drive Data - Belt-Drive Blower..10 7 Static Resistances 8 Electrical Data — Basic Unit 9 Electrical Data — Heat Pump
10 Belt-Drive Supply Air Motor Pulley Adj.
4 4 4 4
No. Description Page
1 Center of Gravity........................................ 3
2 Recommended Drain Piping...................... 4
3 Typical Field Wiring.................................... 5
4 Economizer Rain Hood Assembly.............. 6
5 Adjusting Enthalpy Setpoint....................... 7
6 Dimensions and Clearances...................... 8 & 9
7 Defrost Initiation Times .............................. 12
8 Ambient Modified Time/Temp. Control....... 12
9 Belt Adjusment 10 Hole Loc. for Press. Drop Readings 11 Press. Drop versus Supply Airflow
MAINTENANCE
.........................................................
TABLES
..................................
....................................
.............................................
......
..........
......................................
......................
....................
.......
FIGURES
...........................................
...........
.............
14
3 5
7 10 10
10 11 11 13
13 13 13
PRODUCT NOMENCLATURE
B 3 C H A
PRODUCT CATEGORY
B = Single Package Heat Pump
(Air Cooled)
PRODUCT GENERATION
3 = Third Generation
PRODUCT IDENTIFIER
CH = Heat Pump
2 Unitary Products Group
NOMINAL COOLING CAPACITY
40 8 5 0
048 = 4 Ton 060 = 5 Ton
VOLTAGE CODE
50 = 380/415-3+N-50
FACTORYINSTALLED HEAT
A = No Supplemental Heat
INSTALLATION
LIMITATIONS
These units must be installed in accordance with national and local or municiple safety codes: Refer to Table 1 for Unit Application Data.
If components are to be added to a unit to meet local codes, they
TABLE 1 - UNIT APPLICATION DATA
Voltage Variation
Min. / Max.
°C 14 / 22
°F 57 / 72
°C 7 / 49
°F 45 / 120
°C -23
°F -10
Cooling
Heating
Wet Bulb Temperature of Air on Indoor Coil, Min./Max.
Dry Bulb Temperature of Air on Outdoor Coil, Min./Max.
Minimum Dry Bulb Temperature
of Air on Outdoor Coil
aretobeinstalledatthedealer'sand / or the customer'sexpense.
342 / 457
035-12984-001-A-0204
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any packaginguntil the unitis near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreaders, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit.
BEFORE LIFTING AUNIT,MAKE SURE THATITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY.
Units may also be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 1067mm (42 in.).
Remove the nesting brackets from the four corners on top of the unit. All screws that are removed when taking these brackets off must be replaced on the unit.
APPROXINATE CENTER OF GRAVITY
BACK
CONDENSER COIL END
LOCATION
Use the following guidelines to select a suitable location for these units.
1. Unit is designed for outdoor installation only.
2. Outdoor coil must have an unlimited supply of air.
3. For ground level installation, use a level concrete slab with a minimum thickness of 102mm (4 in.). The length and widthshould be at least 152mm (6 in.) greater than the unit base rails. Do not tie slab to the building foundation.
4. Roof structures must be able to support the weight of the unit and its options and / or accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame.
CAUTION: If a unit is to be installed on a roof curb or special frame
other than a YORK roof curb, gasketing must be applied toallsurfacesthatcomeincontactwith the unit underside.
5. Maintain level tolerance to 13mm (
1
in.) maximum across
2
the entire length or width of the unit.
6. Elevate the unit sufficiently to prevent any blockage of the airentrances by snowin areas wherethere will besnow ac cumulation. Check the local weather bureau for the ex pected snow accumulation in your area.
OUTDOORCOIL CONDENSATEDRAINAGE PRECAUTION
Condensatedrainsfromtheoutdoorcoil during theheatingand defrost cycles. Normally this condensate may be allowed to drain directly onto the ground/roof. A gravel bed is recommended to prevent mud splashing.
WARNING:Theunit should notbe installed in an area wheremud
or ice could cause personal injury. Remember that condensate drips from the outdoor coil during heat and defrost cycles and that this condensate freezes when the temperature of the outdoor air is below 0°C (32
°
F).
1140
44
502
3
19
7
8
4
FIG. 1 - CENTER OF GRAVITY
RefertoTable3forunitweightsandtoFigure 1 for approximate center of gravity.
CLEARANCES
All units require certain clearances for proper operation and service. Refer to Figure 6 for the clearances required for combustibleconstruction,servicing,andproperunitoperation.
WARNING:Do not permit overhanging structures or shrubs to
obstruct outdoor air discharge outlet.
DUCTWORK
A closed return duct system shall be used. This does not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be madewithflexiblejointstominimizethetransmission of noise.
-
­Thesupply and return air duct systems should be designed for
theairflowandstatic requirements of thejob.Theyshould NOT be sized to match the dimensions of the duct connections on the unit.
CAUTION: When fastening ductwork to the side duct flanges
on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Outdoor ductwork must be insulated and water proofed.
Refer to Figure 6 for information concerning side and bottom supply and return air duct openings.
FILTERS
Each unit is supplied with 25mm (1 in.) filters . Replacement
1035
40
FRONT
2089
3
4
1
82
4
51mm (2 in.) filters may be used without modification to the filter racks. Filters must always be installed ahead of the evaporator coil and must be kept clean or replaced with same
Unitary Products Group 3
-
035-12984-001-A-0204
size and type. Dirty filters reduce the capacity of the unit and result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in Table 3.
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain linefromthe19mm(
76 3"
51 2"
3
in.)PVCfemaleconnectionon the unit to
4
FIG. 2 - RECOMMENDED DRAIN PIPING
spill into an open drain.
NOTE: The condensate drain line MUST be trapped to pro
vide proper drainage. See Figure 2.
SERVICE ACCESS
Access to all serviceable components is provided by the following removable panels:
Compressor compartment
Heater compartment
Blower compartment
Main control box
Filter compartment
Motor Access (on units w/belt-drive option)
Refer to Figure 6 for location of these access panels.
BLOWER SPEED SELECTION
Threeblowermotor speeds areavailable on theBCH048 units. The speed selection is determined by the airflow and ESP requirements of the applications. BCH060 units have an adjustable motor pulley to achieve the above conditions.
BCH048 units are shipped with the black wire (labeled #8) connectedto the high speed tapon the blower motor.If a lower blower speed is desired, this wire should be moved to the medium or low speed tap on the motor.
DISCONNECT SWITCH BRACKET FOR UNITS WITH OPTIONAL BELT-DRIVE BRACKET
A special bracket for mounting a field-supplied disconnect switch is provided in each BCH060. The bracket is shipped inside the blower compartment taped to the top of the blower housing. Install the bracket on the left hand side of the unit as shownin Figure6. Severalexisting screws at the top of the unit and one approximately midway down from the top will be used for mounting the bracket. Screws should be loosened only ­NOT REMOVED. Mounting holes in the bracket have elongated keyways allowing easy installation. Re-tighten screws after bracket is in place to ensure panels will remain leak tight.
After this unit is installed, back out the compressor bolts until the sleeve clears the top grommet.
CAUTION: Do Not
loosen compressor mounting bolts.
THERMOSTAT
The room thermostat should be located on an inside wall approximately 1422mm (56 in.) above the floor where it is not subjected to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with thermostat for general installation procedure. Color coded insulated wires (#18 AWG) should be used to connect thermostat to unit. See Figure 3 for wiring details.
NOTE: On units with economizer, remove jumper “J1" from
An “Emergency Heat” position is provided with the thermostat.In the “Emergency Heat” position, the thermostat allowselectricresistanceheatonly.The compressorislocked out. Apilot light on the thermostat indicates that the switch is
-
on “EM HT”.
terminals 8 and 10 on plug connector J3/P7 on the re layboardin the unitcontrolbox. Refer totheunitwiring labels located on the inside of the control box access panel.
POWER AND CONTROL WIRING
Voltagetolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1.
The wiring harness furnished with this unit is an integral partof the unit. Field alteration to comply with electrical codes should not be required.
A disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. Refer to Figure 6forinstallationlocation.If any of thewiresuppliedwith the unit mustbe replaced, replacement wire must be of the typeshown on the wiring diagram.
Electrical lines must be sized properly to carry the load. USE COPPERCONDUCTORSONLY.Eachunit must bewired with a separate branch circuit fed directly from the meter panel and properly protected.
CAUTION: When connecting electrical power and control wir
Refer to Figure 3 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information. Refer to Tables 8 and 9 for electrical data.
ing to the unit, waterproof type connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation. The above waterproofing conditions also apply when installing a field-supplied disconnect switch.
ELECTRIC HEATERS
Supplemental electric heaters may be ordered as a field­installed accessory. Refer to Form 530.18-N7.1V for installation instruction. These approved heaters are located within the central compartment of the unit (see Figure 6 for access panel) with the heating elements extending into the supply air chamber.
-
-
COMPRESSORS
On some units the compressor is mounted on springs which have been tightened down for shipment only.
4 Unitary Products Group
Fuses are supplied, where required, by the factory. Some kW sizes require fuses and others do not. Refer to the electric
TABLE 2 - AIR FLOW LIMITATIONS
NOMINAL
HEATER
SIZE
KW
7 10 15 20 30
VOLTAGE
380/415-3+N-50
CONTROL WIRING
UNIT MODEL SIZE, NOMINAL TONS
MINIMUM SUPPLYAIR CFM
1,300 1,300 1,300 1,300
45
1,600 1,600 1,600 1,600
1,600
035-12984-001-A-0204
1 Typical 24-volt thermostat with subbase
-2ET03700424 for manual changeover.
2
Only required on units with supplemental electric heat.
Note: The thermostat terminals shown above are typical. Check thermostat and unit wiring diagrams for correct wiring connections.
POWER WIRING
CONTACTOR
TO REMOTE SENSOR 2ET04701324 IF USED
1 Typical Electronic programmable thermostat 2ET04701124 with subbase for
either manual or automatic changeover.
2
Only required on units with economizer. Remove jumper L2 from terminals
4 and 9 on jumper plug P7. The outdoor air intake dampers will return to their fully closed position when the thermostat switches to the “unoccupied” mode.
3
Second stage cooling may be used on units with economizer. Remove jumper
J1 from terminals 8 and 10 on jumper plug connector P7.
4
Only required on units with supplemental electric heat.
NEUTRAL TERMINAL BLOCK
FIELD-SUPPLIED
DISCONNECT
GROUND LUG
REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, THE WIRING AND THE OVERCURRENT PROTECTION.
FIG. 3 - TYPICAL FIELD WIRING
Unitary Products Group 5
035-12984-001-A-0204
heater accessory installation instruction for the heater electrical data.
The minimum air flow limitations across these heaters are listed in Table 2.
OPTIONAL ECONOMIZER RAIN HOOD
The following procedure should be used when assembling an economizer rain hood onto a unit. Refer to Figure 4. The outdoor and return air dampers, damper actuator, the linkage and all the controls are factory mounted as part of the economizer option.
All of the hood components, including the filters, the gasketing and the hardware for assembling are located above the top filter racks within the filter section. The outdoor air sensor is in thebagofpartslocatedatthebottomofthe return air section.
1. With filter section access panel removed, take out hood components, filters and sensor described above. Remove and discard outdoor air opening cover on back unit (Upper right hand corner).
2. Remove the 13mm ( panel (located to the right side of the outdoor air opening). Insert the two loose wires from inside the unit, into the 13mm (
1
in.) bushing provided. Insert wires and bushing
2
into knockout. Snap bushing into place.
3. Mount the outdoor air sensor to the rear panel, just below the knockout described in Step 2. Secure with two self­drilling screws at dimples (B) provided in the panel.
NOTE: Sensor must be positioned so that the sensing ports
are at the top (louvers pointing downward) and termi­nal connections to the right.
4. Connectthe two wires, indicated in Step2, to the sensor as follows:
Wire #73 to terminal (+)
Wire #74 to terminal (S)
5. Assemble the LH and RH side plates to the top cover (2 screws each side) to form the hood. Apply gasketing to the
1
in.) knockout (A) in the units rear
2
flangesurface on each side plate.Extend gasketing 6mm (
1
in.) beyond top and bottom of each flange to insure ade
4
quatecorner sealing. Securethis assembly tothe unit back panel(upper right hand corner). First,remove screw(C) on unit top cover. Then slip flange of hood cover in under flange of unit top cover, replace screw (C), engaging hole (E)in hood flange and tighten. Attach the two sideplates to theunit panel by usingtwo self-drillingscrews for eachside plate at dimples (D) provided in the panel.
6. Position fillpiece at bottom of hood, between the two side plates but do not secure at this time. (Slotted openings MUSTbedownwardfor drainage). Afterfillpieceisproperly positioned, note where contactis made with the unit panel. Remove fillpiece and apply gasket material to this area to provide a seal. Reposition fillpiece and secure with 2 screws.
7. Install the two filters into the hood assembly, sliding down along retainers on side plates, into fillpiece at bottom of hood.
NOTE: Install filters so that “Air Flow” arrows point toward the
unit.
8. Install filter cover over the end of the hood with one screw (center of hood), securing filters into position.
CAUTION: When proceeding with steps 9 and 10, extreme
care must be exercised while turning both the set point and minimum position adjusting screws to prevent twisting them off.
9. The enthalpy set point for the dampers may now be set by selectingthe desired set-pointfrom graph inFigure 5. Fora singleenthalpy economizer,carefully turn the set-point ad­justing screw to the “A”, “B”, “C” or “D” setting correspond­ing to the lettered curve. For a dual enthalpy economizer, carefully turn the set-point adjusting screw fully clockwise past the “D” setting.
10.To check that the damper blades move smoothly without binding, carefully turn the minimum position adjusting
-
GASKETED FLANGE
L. H. SIDE PLATE
FILTER COVER
FILTERS
HOOD COVER
FILLPIECE
OUTDOOR AIR OPENING COVER
D
E
D
GASKETED FLANGE
R. H. SIDE PLATE
C
D
A
B
D
SIDE DUCT
APPLICATION SHOWN
OUTDOOR AIR SENSOR
GASKET
FILTER SECTION ACCESS PANEL
FIG. 4 - ECONOMIZER RAIN HOOD ASSEMBLY (OPTION)
6 Unitary Products Group
035-12984-001-A-0204
FIG. 5 - ENTHALPY SET POINT ADJUSTMENT
TABLE 3 - PHYSICAL DATA
MODELS
CENTRIFUGAL BLOWER (Dia. x
SUPPLYAIR
BLOWER
INDOOR
COIL
OUTDOOR
FAN
OUTDOOR
COIL
AIR
FILTERS
(SEE NOTE)
CHARGE REFRIGERANT 22 (kg / lbs./oz.) 4.2 / 9.2 3.7 / 8/4
NOTE: Filter racks are adapted for 1" or 2" thick filters.
Unitary Products Group 7
Wd.,mm/in.) FAN MOTOR HP(Direct-Drive Units) FAN MOTOR HP(Belt-Drive Units)
ROWS DEEP FINS PER 25mm (1 inch) FACE AREA(m
PROPELLER DIA. (mm/in.) FAN MOTOR kW/HP NOM. CFM TOTAL
ROWS DEEP FINS PER 25mm (1 inch) FACE AREA(m
QUANTITY PER UNIT (14" x 20" x 1") QUANTITY PER UNIT (14" X 25" X 1") TOTAL FACE AREA (m
2
2
/ft2)
/ft2)
2
/ ft2.)
305 x254
12 x 10
0.47 / 5.1 610 / 24
0.37 / 0.5
BCH
048 060
305 x 254
0.75 NA
3
15
4,200
1
20
17.1
2 1
6.3
12 x 10
0.47 / 5.1 610 / 24
0.37 / 0.5
4,500
NA
1.5 3
15
1
20
17.1 2
1
6.3
Basic Unit
Electric Heat (Nominal Kw)
Economizer Motorized Outdoor Air
Damper Barometric Relief/Fixed
Outdoor Air Intake Damper Roof Mounting Curb Belt-Drive Blower
WEIGHTS (kg/lbs)
048 270 / 595 060 281 / 620
OPTIONS / ACCESSORIES
5 - 7 kW 8.2 / 18 10 - 15 kW 10.4 / 23 20 - 30 kW 12.7 / 28
22.7 / 50
21.8 / 48
4.5 / 10
41.7 / 92
2.3 / 5
035-12984-001-A-0204
(Direct-Drive Units)
829
32-5/8"
2090
82-1/4"
OUTDOOR COIL
RETURN AIR
137
5-3/8
1140
44-7/8"
200
7-7/8"
445
17-1/2"
213
8-3/8"
171
6-3/4"
206
8-1/8"
165
6-1/2"
292
11-1/2"
445
17-1/2"
UTILITIES ENTRY DATA
HOLE
A 5mm (7/8") * B 51mm (2") *
*Knockouts in the bottom of the unit can be located by the slice
in the insulation.
**Do not remove the 2" knockout ring.
KNOCKOUT
SIZE
(DIA.)
64
2-1/2
SUPPLYAIR
OUTDOOR AIR
OUTDOOR AIR
(Economizer)
All dimensions are in millimeters and inches.They are subject to change without notice. Certified dimensions will be pro­vided upon request.
USED FOR
Control Wiring (Side or Bottom)**
Power Wiring (Side or Bottom)
Front 610mm (24") Back
Left Side (Filter Access) Right Side (OD Coil) 610mm (24")
Below Unit Above Unit
NOTE:
Units and ductwork are approved for zero clearance to combustible materials when
equipped with electric heaters.
1
Units may be installed on combustible floors made from wood or class A, B or C roof covering material.
2
Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.
1
2
25mm (12") (Less Economizer) 914mm (36") (With Economizer)
610mm (24") (Less Economizer) 914mm (36") (With Economizer)
0mm (0")
1829mm (72") (For Outdoor Air Discharge)
FIGURE 6 - DIMENSIONS & CLEARANCES
8 Unitary Products Group
437
1
17
REAR VIEW
SIDE SUPPLYAND RETURN AIR DUCT OPENINGS
035-12984-001-A-0204
DUCT COVERS - Units are shipped with all air duct openings covered. For side
duct applications;
1.Remove and discard the supply and return air duct covers.
2.Connect ductwork to duct flanges on the rear of the
292
1
11
2
unit.
For bottom
1. Remove the side supply air duct cover to gain ac
duct applications;
-
cess
to the bottom supply air knockout panel.
76 3"
2. Remove and discard the bottom knockout panel.
3. Replace the side duct cover.
4
117
292
11
5
2
165
6
437
1
2
1
17
2
200
7
7
8
4. With filter section access panel removed from the
1
2
unit, remove and discard the bottom return air knockout panel.
8
REAR VIEW
DETAIL “A” UNIT WITH ECONOMIZER RAINHOOD
698
27
1
2
41
5
1
8
3
“ CONDEN-
4
SATE
638
1
27
2
267
1
19
2
DRAIN CONN. (Must be trapped)
502
3
19
4
1140
7
44
8
L.H. END VIEW
260
1
10
A
89
4
1
3
2
111
3
4
8
210
8
DETAIL “B”
REAR VIEW
416
3
16
8
117
5
4
8
454
7
17
8
184
7
1
4
260
1
10
4
1340
44
B
7
8
L.H. END VIEW
UNIT WITH FIXED OUTDOOR AIR / BAROMETRIC RELIEF RAINHOOD
FIGURE 6 - DIMENSIONS & CLEARANCES (continued)
Unitary Products Group 9
1
4
035-12984-001-A-0204
TABLE 4 - SUPPLY AIR PERFORMANCE - BCH048
380 / 415 VOLTS - SIDE DUCT APPLICATIONS
MODEL
048
MODEL
048
*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEATPUMP UNITS WITH SIDE DUCT AIRFLOWS.
MOTOR
SPEED
HI MED LOW
MOTOR
SPEED
HI MED LOW
3
/s Watts m3/s Watts m3/s Watts m3/s Watts m3/s Watts m3/s Watts m3/s Watts m3/s Watts m3/s Watts
m
-
-
-
-
0.85
0.77
910 810
0.84
0.76
880 780
0.94
0.82
0.75
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts
-
-
-
­1810 1635
910 810
1780 1610
880 780
2000 1740 1580
Available External Static Pressure - Pa*
1010
0.92
975
0.90
945 850 760
0.80
0.73
825 740
0.79
0.73
800
730
0.87
0.76
0.71
Available External Static Pressure - IWG*
1010
1950
975
1905
945 850 760
1700 1555
825 740
1665 1540
800
730
1840 1620 1510
910 775 715
910 775 715
0.83
0.74
0.69
1770 1560 1460
825 740 690
825 740 690
0.78
0.70
0.66
1660 1480 1400
825 700 660
825 700 660
0.72
0.66
0.61
1530 1390 1300
TABLE 5 - SUPPLY BLOWER PERFORMANCE - BCH060
MODEL
AIR FLOW
3
m
/s / CFM
223 / 0.90 248 / 1.00 273 / 1.10 298 / 1.20 322 / 1.30 347 / 1.40 372 / 1.50
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
1.18 / 2500 --------------
1.13 / 2400 1193 1665 ------------
1.08 / 2300 1170 1580 1202 1620 ----------
1.04 / 2200 1148 1480 1180 1530 ----------
0.99 / 2100 1121 1385 1155 1425 1190 1475 --------
0.94 / 2000 1100 1285 1133 1340 1169 1385 1205 1445 ------
060
0.90 / 1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 ----
0.85 / 1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 ----
0.80 / 1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - -
0.75 / 1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150
0.71 / 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110
*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN
HEATPUMP UNITS WITH SIDE DUCT AIRFLOWS.
Available External Static Pressure -Pa/ IWG*
775 660 615
775 660 615
TABLE 6 - MOTOR AND DRIVE DATA - Belt-Drive Blower
MOTOR*
FRAME
SIZE
SERVICE
FACTOR
MODEL
BLOWER
RANGE
(RPM)
kW/HP RPM
BCH060 850 - 1180 0.75/1.0 1450 56 1.15
*All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any
heating device.
ADJUSTABLE
MOTOR PULLEY
PITCH
DIA.
mm (in.)
BORE
mm (in.)
71 - 97
(2.8 - 3.8)
22 127 (5.0) 25 (1) 947 (37.3) A36
FIXED
BLOWER PULLEY
PITCH
DIA.
mm (in.)
BORE
mm (in.)
PITCH
LENGTH
(mm in.)
BELT
DESIG-
NATION
TABLE 7 - STATIC RESISTANCES*
EXTERNAL STATIC PRESSURE DROP
RESISTANCE, Pa/IWG
3
DESCRIPTION
Economizer/Motorized Damper Electric Heaters
1
Bottom Duct Connections
1Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table. 2
The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
1, 2
5 - 15 KW 10 / 0.04 12 / 0.05 15 / 0.06 17 / 0.07 20 / 0.08 25 / 0.10 30 / 0.12 35 / 0.14 40 / 0.16
20 - 30 KW 15 / 0.06 17 / 0.07 20 / 0.08 22 / 0.09 27 / 0.11 32 / 0.13 37 / 0.15 42 / 0.17 50 / 0.20
1
0.47/1000 0.57/1200 0.66/1400 0.75/1600 0.85/1800 0.94/2000 1.04/2200 1.13/2400 1.232600 17 / 0.07 20 / 0.08 22 / 0.09 27 / 0.11 32 / 0.13 37 / 0.15 42 / 0.17 50 / 0.20 57 / 0.23
15 / 0.06 17 / 0.07 20 / 0.08 22 / 0.09 25 / 0.10 27 / 0.11 30 / 0.12 35 / 0.14 40 / 0.16
10 Unitary Products Group
m
/s/CFM
035-12984-001-A-0204
TABLE 8 - ELECTRICAL DATA - Basic Unit
SUPPLY
AIR
BLOWER
MOTOR,
FLA
TOTAL
UNIT
AMPACITY,
AMPS
MODEL
BCH
POWER SUPPLY
VOLTAGE
LIMITATIONS
COMPRESSOR OUTDOOR
MIN. MAX. RLA LRA
FAN
MOTOR,
FLA
048 380/415-3+N-50 342 457 9.6 66 1.8 4.0 18.3 25 25 10 (6MM 060 380/415-3+N-50 342 457 10.0 75 1.8 2.6 16.9 25 25 10 (6MM
NOTES: 1. Dual element, time delay type.
2. Based on 75°C copper conductors.
MAX.
FUSE
SIZE,
(SEE NOTE 1)
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
(SEE NOTE 2)
MIN. WIRE SIZE, AWG
2
)
2
)
TABLE 9 - ELECTRICAL DATA
HEATER
MODEL
BCH
POWER SUPPLY
048 380/415-3+N-50
060 380/415-3+N-50
ACCESSORY
MODEL
NUMBER
2CE04510746* 2CE04511046* 2CE04511546* 2CE04512046*
2CE04510746* 2CE04511046* 2CE04511546* 2CE04512046* 2CE04513046*
- Heat Pump with Supplemental Electric Heat
SUPPLY
AIR
BLOWE
R
MOTOR
FLA
4.0
2.6
ELECTRIC HEATERS
KW STAGES
4.3 / 5.1
6.3 / 7.5
8.5 /
10.2
12 / 14.6
4.3 / 5.1
6.3 / 7.5
8.5 /
10.2
12 / 14.6
18 / 22
1 1 1 2
1 1 1 2 2
TOTAL
AMPS
7.1
10.5
14.1
20.3
7.1
10.5
14.1
20.3
30.0
TOTAL
UNIT
AMPACITY
AMPS
26.5
30.3
34.5
41.1
25.7
30.0
34.6
42.2
54.3
MAX.
FUSE
SIZE,
(SEE NOTE 1)
AMPS
30 35 40 45
30 35 40 45 60
MAX.
HACR
BREAKER
SIZE,
AMPS
30 35 40 45
30 35 40 45 60
MIN.
WIRE
SIZE, AWG
(SEE NOTE 2)
10 (6mm 8 (10mm 8 (10mm 8 (10mm
10 (6mm 8 (10mm 8 (10mm 8 (10mm 6 (16mm
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
Unitary Products Group 11
035-12984-001-A-0204
OPERATION
screw fully clockwise and then energize and de-energize terminals “R” to “G”. With terminals “R” to “G” energized, turnthe minimumposition screwcounterclockwise until the desired minimum position has been attained.
11.Replace the filter section access panel.
COOLING SYSTEM
The unit has an air-cooled condenser and is factory-charged with Refrigerant-22.
250
200
150
100
T3 - 110 Minute Setting (Factory Set Point)
T2 - 80 Minute Setting
The compressor is hermetically sealed, internally sprung, mounted on spring isolators and inherently (internally) protected. If there is an abnormal temperature rise in the compressor,theprotectoropens to shut downthecompressor.
PRELIMINARY OPERATION COOLING
After the installation has been completed, the crankcase heaterofthecompressor must beenergizedforat least 4hours before starting the unit. After this initial warm-up, the compressor should be given three false starts (energized just long enough to make a few revolutions) with a 5 minute delay between each start before being put into full time service.
NOTE: Prior to each cooling season, the crankcase heater
mustbe energizedat least 10 hours before the system is put into operation.
COOLING SEQUENCE OF OPERATION
When the thermostat calls for cooling, the compressor and the outdoor fan motor will be energized through terminal “Y1" and the supply air blower motor will be energized through terminal ”G" (if the fan switch on the subbase is set in the “AUTO” position). The supply air blower motor will run continuously if the fan switch is set in the “ON” position.
The reversing valve is energized thru the “O” circuit when the subbase is in the cooling mode.
HEATING SEQUENCE OF OPERATION
The following sequence of operation is based on using a standardYORK heatpumpthermostatwithtwoheatingstages.
FIRST STAGE HEAT When the thermostat callsfor heating, the compressor and the
outdoor fan motor will be energized through terminal “Y1" and the supply air blower motor will be energized through terminal ”G" (if the fan switch on the subbase is set in the “AUTO” position). The supply air blower motor will run continuously if the fan switch is set in the “ON” position.
50
T1 - 50 Minute Setting
0
TIME BETWEEN DEFROST CYCLES, MINUTES
-10
20
10
0
OUTDOOR AMBIENT, DEG. F
40
30
50
FIG. 7 - DEFROST INITIATION TIMES
adjusted to defrost at 80 minutes (T2) or 50 minutes (T1) in areas with high humidity.
The curve in Figure 7 shows how defrost initiation times are automatically compensated for changes in outdoor temperature.
EXAMPLE: If the time is factory set on pin T-3 (110 minutes at 2°C(35°F)outdoor)and the outdoortemperatureclimbsto 7°C (45°F), the time initiation cycle decreases to 100 minutes.
If the outdoor temperature drops to -12°C (10°F) where ice is less likely to form, the 110 minute interval increases to 150 minutes.
Two requirements must be met before a defrost cycle can be initiated.
1. The defrost time cycle must be complete.
2. The liquid line temperature must be less than -2°C (28°F). Defrost terminates when the liquid line sensor reaches 13°C
(55°F) or after 10 minutes. The defrost time cycle restarts 10 minutes after the start of the
defrost cycle even though the liquid sensor terminated defrost after 3 minutes.
T2 - 80 MINUTE SETTING
T3 - 110 MINUTE SETTING
(Factory Set Point)
T1 - 50 MINUTE SETTING
60
SECOND STAGE HEAT If compressor operation can not satisfy the heating
requirements, second stage heat will energize supplemental electric heat (if supplied) thru the “W1" circuit.
DEFROST SEQUENCE OF OPERATION
The BCH has a unique “ambient modified” time-temperature
SHORTING PEGS TO OVERRIDE TIMER FOR SERVICE
MOVABLE JUMPER WIRE TO CHANGE DEFROST TIMER
defrost control that automatically adjusts to changes in the outdoor temperature. The defrost control will shorten the defrostinitiation time periodsabove 2°C (35°F)and will extend thedefrost initiation timeperiods below 2°C(35°F). The control is factory set to defrost at 110 minutes (T3), but it can be field
FIG. 8 - AMBIENT MODIFIED TIME/TEMPERATURE
CONTROL
12 Unitary Products Group
035-12984-001-A-0204
During troubleshooting, the defrost time can be reduced to 20 secondsby shortingout theSW1 testpegs onthe module. The pegs are 13mm (
1
in.) long, 1mm (
2
3
in.) apart and are
16
mounted on a white base. See Figure 8.
LOCKOUT CONTROL
Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode:
1.
The discharge line temperature reaches 124°C (255°F) (102°C [215°F] reset) or,
2. The discharge pressure reaches 2770 kPa (398 PSIG) (2158 kPa [310 PSIG] reset) or,
3.
The suction line freezestat equals -3°C (26°F) (3°C [38°F] reset) or,
4. Thelow-pressure cut-outequals 49 kPa (7 PSIG) (153 kPa [22 PSIG] reset).
A lock-outl energizes the emergency heat light on the thermostat and the red LED light on the unit relay board. Turning the thermostat switch to “Off” then back to “On”, will reset the system.
NOTICE TO OWNER: If a lockout occurs, check for the following problems before
calling a serviceman:
1. Dirty filters.
2. Snow accumulation.
3. Leaf or debris blockage.
After eliminating the problem, attempt to restartthe system as follows:
turn the system switch on the thermostat to its “OFF”
position for 10 seconds.
turn it back to its original position.
If the unit doesn't start, call a serviceman.
NOTE: Models with an anti-recycle accessory will have a 5-
minute delay before starting.
FIG. 9 - BELTADJUSTMENT
obtain the desired supply airflow. Refer to Table 6 for blower motor drive data. The tension on the belts should be adjusted as shown in Figure 9.
Startthe supply airblower motor.Adjust the resistancesin both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer.
To check the supply airflow after the initial balancing has been completed:
CHECKING SUPPLY AIRFLOW
419
The speed of the supply air blower will depend on the required airflow, the unit accessories and the static resistances of both
1
16
2
the supply and the return air duct systems. With this information, the speed for the supply air blower can be
TABLE 10 - BELT-DRIVE SUPPLY AIR
MOTOR PULLEY ADJUSTMENT
TURNS
OPEN*
5 4 3 2 1 0
*Pulley can be adjusted in half-turn increments.
determined from the blower performance and static resistance data on Tables 4, 5 and 7.
Knowing the required blower RPM and the blower motor kW (HP), the speed setting for the supply air motor can be determined.
The setting (turns open) for the optional belt-drive supply air pulley can be determined from Table 10.
OPTIONAL BELT-DRIVE BLOWER
Allunits with belt-driveblowers havesingle speed motors. The
variable pitch pulley on the blower motor can be adjusted to
Unitary Products Group 13
BLOWER DRIVE RANGE (RPM)
060 850
916 982
1048
1114
1180
DAMPER ASSEMBLY
FILTERS
DUCT FLANGES (Back of Unit)
L.H. END VIEW
(Filter Access End)
FIG. 10 - HOLE LOCATIONS (PRESS. DROPREADING)
1. Drill two 8mm ( Figure 10.
2. Insertat least203mm (8in.) of6mm ( of these holes for sufficient penetration into the air flow on both sides of the indoor coil.
NOTE: The tubes must be inserted and held in a position per
pendiculartotheairflowso that velocity pressuredoes not affect the static pressure readings.
5
in.) holes in the side panels as shown in
16
435
1
17
8
5
“ HOLES
16
INDOOR COIL
FRONT OF UNIT
1
in.)tubing intoeach
4
533 21"
-
035-12984-001-A-0204
3. Usingan inclinedmanometer,determine the pressuredrop across a dry indoor coil. Since the moisture on an indoor coilmayvarygreatly,measuringthe pressure drop acrossa wet coil under field conditions would be inaccurate. To ensurea dry coil, the compressorsshould be de-energized while the test is being run.
4. Knowing the pressure drop across a dry coil, the actual airflow throughtheunitcanbedeterminedfrom the curve inFigure11.
WARNING:Failureto properlyadjust thetotal system air quan
Afterreadings have been obtained, remove the tubes and seal the drilled holes in the side panels. 8mm ( 029-13880) are available through normal parts ordering
tity can result in poor system performance.
5
in.) dot plugs (P/N
16
-
procedures.
NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE
TAKINGANY TEST MEASUREMENTS TO ENSURE A DRY INDOOR COIL.
SECURE OWNER'S APPROVAL:When the system is functioning properly,secure the owner's approval. Show him the location of all disconnect switches and the thermostat. Teachhim how to start and stop the unit and how to adjust temperature settings within the limitations of the system.
MAINTENANCE
NORMAL MAINTENANCE
CAUTION: Prior to any of the following maintenance proce-
dures, shut off all power to the unit to prevent per­sonal injury.
FILTERS- Inspect once a month. Replace disposable or clean permanent type as necessary. DO NOT replace permanent type with disposable.
MOTORS-Indoor fan andoutdoor fan motorsare permanently lubricated and require no maintenance.
OUTDOORCOIL- Dirtshouldnot be allowedtoaccumulate on theoutdoorcoilsurface or other partsintheaircircuit. Cleaning should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean coil, be sure power to the unit is shut off prior to cleaning.
NOTE: Exercise care when cleaning the coil so that the coil
fins are not damaged. Do not permit the outdoor air discharge to be ob
structed by overhanging structures of shrubs.
-
14 Unitary Products Group
035-12984-001-A-0204
Unitary Products Group 15
Unitary Products Group 5005 York Drive, Norman, Ok 73069 Subject to change without notice. Printed in U.S.A. Copyright by York International Corporation 2004. All Rights Reserved.
Supersedes: 511.13-N1YI (900) / 035-12984-000
035-12984-001-A-0204
Loading...