These packaged heat pumps are designed for outdoor
installation. Only utility and duct connections are required
at the point of installation.
Field-installed electric heater accessories are available to
provide electric heat, if required.
STANDARD FEATURES / BENEFITS
OPERATING EFFICIENCY
All units provide high operating efficiencies of 13 SEER, 3.3
COP or greater, and 7.6 HSPF. All efficiencies exceed legislated minimum levels.
ON SITE FLEXIBILITY
All model sizes share a common, compact design cabinet
with a single footprint. The installer has the flexibility of setting one curb or pad and placing the proper tonnage unit
after the internal load has been determined. Field convertible duct connections, from side shot to down shot, allows
the installer greater flexibility and the need to carry less
inventory.
LOWER INSTALLATION COST
Installation time and costs are reduced by easy power and
control wiring connections. The small base dimension
means less space is required on the ground or roof. Plus,
the installer can fit this unit between the wheel wells of full
size pick-up truck. All models are under 500 pounds.
FACTORY MOUNTED TXV
All units are completely wired, charged with R-22 and
tested prior to shipment. Unique test stations, are used to
insure product quality. Refrigerant charge, and component
part numbers are verified via computers at manufacturing
point. Vital run test statistics, such as, system pressure,
motor currents, air velocity and temperature unit vibration
are monitored and recorded by the system to insure unit
performance.
Equal size, side supply and return duct connections allow
easy hook-up of ducts to match low crawl spaces without
transition pieces.
UTILITY CONNECTIONS MADE EASY
Electrical utility knockouts are provided through the bottom,
as well as the side of the unit. Utility connections can be
made quickly and with a minimum amount of field labor. A
field supplied and field installed electrical disconnect
switch must be installed.
CONVERTIBLE AIRFLOW DESIGN
The bottom duct openings are covered when they leave the
factory. They are ready for a side supply / side return application. If a bottom supply / bottom return application is
desired, you simply remove the two panels from the bottom
of the unit and place them in the side supply / side return
duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows
maximum field flexibility and minimum inventory.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21528-001-A-0303
CONDENSATE PAN
A non-corrosive, long-lasting, water-tight pan is positioned below the evaporator coil to collect and drain all
condensate; less collection of stagnate condensate will
build-up. The condensate pan conforms to ASHRAE
62-89 standards (Ventilation for Acceptable Indoor Air
Quality).
CONDENSATE DRAIN
The heavy duty, inch NPTI copper connection is more
tolerable during installation and is more durable over
time. The connection is rigidly mounted to assure
proper fit and leak tight seal.
DURABLE FINISH
With a heavy duty cabinet made of powder-painted,
galvanized steel, the neutral color blends into surrounding areas. The powered paint provides a better
paint to steel bond, which resists corrosion and rust
creep. The special primer formulas and glossy earth
tone finish insure less fading when exposed to sunlight
and offers a more attractive on site appearance. This
paint finish exceeds ASTM-B117 standards for 750
hours salt spray rating, the highest in the industry.
TOP DISCHARGE
The top discharge condenser fan does not disrupt
neighboring areas and does not dry-out vegetation surrounding the unit. The warm air from the top mounted
fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit
applications.
OUTDOOR COIL GRILLE
A multi-piece totally enclosed, rigidly mounted outdoor
coil grille provides protection from objects and personnel after installation. It also provides protection during
transit and installation.
LOW OPERATING SOUND LEVEL
The upward air flow carries the normal operating noise
up and away from the living area. The rigid top panel
effectively isolates any motor sound. Isolator mounted
compressor and the rippled fins of the condenser coil,
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in
sound alterations with it's ìSuper-Structureî design.
This design strategically places embossments in the
pan for optimum strength and rigidity.
FULL PERIMETER BASE RAILS
The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides.
Rigging holes are, provided also so that an overhead
crane can be used to place the unit on a roof. On applications when the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications where height is limited, the 2-3/8 inch high base
rails may be removed on location.
MORE ATTRACTIVE APPEARANCE
A single piece ìWater Shedî top cover containing a top
discharge condenser fan arrangement requires less
square footage on installation and provides a wider
variety of installations. The one piece design adds
greater water integrity. Rounded corners with water
drip edges add to the attractive appearance. The cabinet panels have a non-fibrous insulation that reduces
insulation fibers into conditioned area.
FAN SYSTEM
All models operate over a wide range of design conditions with an (E.C.M.) electronically commutated motor
that automatically adjusts the blower speed to meet a
wide range of static requirements. These units easily
match all types of applications and provides greater on
site flexibility to match comfort requirements.
SIMPLE CONTROL CIRCUIT
A low voltage printed circuit board contains a low voltage terminal strip. The electrical control box is not
located in the compressor compartment. All wiring
internal to the unit is color/number coded.
CONTROLS
Reliable demand defrost control provides defrost.
Defrost control also provides an ìXî terminal to provide
a 24 volt signal for room thermostat ìLEDî indication of
unit lockout, plus, built in 5 minute anti-short cycle protection.
2Unitary Products Group
03 6-21528-00 1-A-0303
PROTECTED COMPRESSOR
The compressor is internally protected against high
pressure and temperature. This is accomplished by the
simultaneous operation of high pressure relief valve
and a temperature sensor which protects the compressor, if undesirable operating conditions occur.
EXCLUSIVE COIL DESIGN
Grooved copper tubes and enhanced aluminum fin
construction improves heat transfer for maximum efficiency and durability.
LOW MAINTENANCE
Long life, permanently lubricated condenser and evaporator fan motor bearings, need no annual maintenance. Blower assembly can be easily cleaned by the
unique ìSlip Trackî slide-out blower assembly.
SECURED SERVICE ACCESS PORTS
Protected, externally mounted, re-usable service
access ports are provided on both the high and low
lines for ease of evacuating and charging the system.
EASY SERVICE ACCESS
rate field accessories of single enthalpy and dual
enthalpy are also available.
SINGLE ENTHALPY SENSOR
Sensor replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by
sensing the dry bulb temperature from outdoors, plus
the enthalpy content of the outdoor air.
DUAL ENTHALPY SENSOR
Additional sensor to single enthalpy sensor. Sensor
selects both the return air temperature dry bulb and
humidity, in conjunction with the single enthalpy, to
determine the most economical mix. Single Enthalpy
sensor also required.
UPGRADE PRESSURE PACKAGE
Contains screw in type High pressure, Low Pressure/
Loss of Charge switch, freeze protection switch and
lockout relay. Switches are placed onto existing
Schrader ports located in the unit by furnished adapters. When abnormal conditions are sensed through the
pressure switches, the unit will lock out, preventing any
further operation until reset or problem is corrected.
Package agency approved.
A large, single hinged panel covers the electrical controls and makes servicing easy. The blower compartment has an additional large panel with a built-in
handle tab. Removing this panel will allow the blower
assembly to slide-out for easy removal for maintenance and ease of trouble shooting.
REPLACEMENT PARTS
The installer has no need to carry an inventory of
unique parts or needs special training to replace any of
the components parts for these units. All are easily
obtained from Source 1 or other major part houses.
FIELD-INSTALLED ACCESSORIES
ECONOMIZER DOWN DISCHARGE / SUPPLY KIT
Modulating integrated economizer provides simultaneous operation between the mechanical cooling and
economizer operation. Independent blade design
insures proper control and less than 1% leak rate.
Includes hood and mesh bird screen filter integrated
into the hood, dry bulb sensor and relief damper. Sepa-
HAIL GUARD KIT
Kit contains protected grilles made of expanded aluminum grilles with full perimeter 1-1/2 inch frame. Sloped
hoods are also included to assure maximum protection.
FILTER / FRAME KIT (SINGLE PHASE ONLY)
Kit contains the necessary hardware to field install
return air filters into the base unit. Pre-cut filter racks
and appropriate cleanable standard size filters are
shipped in one kit (1" filter is supplied). This kit is available for single phase horizontal or vertical duct application only. Standard in all 3 Phase models.
MOTORIZED FRESH AIR DAMPER
Designed for duct mounted side return and unit
mounted down shot return applications. Damper capable of providing 0% thru 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen
assembly.
Unitary Products Group3
036-21528-001-A-0303
RECTANGLE TO ROUND ADAPTERS
Kit includes one supply and one return air rectangle to
round duct adapter. Adapters are preformed and
designed to fit over current duct openings on the base
unit. Transition is from 15" square to 14" round.
ROOF CURBS
NRCA approved curbs provide proper fit to base unit
for rooftop installations. Curbs are designed to be
assembled through hinge pins in each corner. Kit also
provides seal strip to assure a water tight seal. Eight
and 14 inch high roof curbs are available.
MANUAL OUTDOOR DAMPER
Provides 0% thru 50% outdoor air capability (field
adjustable). Designed for duct mounted side return and
unit mounted down shot applications. Includes hood
and screen assembly.
WALL THERMOSTAT
The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units
can operate with single stage heat / single stage cool
thermostats - with or without the economizer.
LOW AMBIENT KIT
Kit provides necessary hardware to convert unit to
operate in cooling cycle down to 0∞ F. Standard unit
operation 45∞ F.
TRANSFORMER KIT (SINGLE PHASE ONLY)
Kit provides necessary hardware to provide single
phase models from factory furnished 40 VA transformer capability to 75 VA transformer capability.
ELECTRIC HEATERS
Each heater package provides easy installation of electric heat strips. Slide in design with plug in harness and
agency approved. Heaters are available from 5.0 KW
sizes and are designed for single point and dual connection.
Certified in accordance with the Uniary Small Equipment certification program, which is based on ARI Standard 210/240.
2.
Rated in accordance with ARI Standard 270.
SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric
power input in watt-hours during the same period.
COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary resistance (BGUís per hour) divided by the total electric input (watts) x 3.412.
These capacities are net capacities - indoor fan heat deducted.
1
MBH
Sensible Capacity
NET CAP. MBH27.224.222.122.027.724.622.522.4
POWER INPUT kW2.072.062.022.022.092.082.052.04
1
MBH
Sensible Capacity
NET CAP. MBH23.822.420.520.624.222.820.820.9
POWER INPUT kW2.202.212.172.162.242.242.202.19
1
MBH
Sensible Capacity
NET CAP. MBH20.420.718.919.220.620.919.119.4
POWER INPUT kW2.342.362.322.312.382.402.362.35
1
MBH
Sensible Capacity
NET CAP. MBH17.018.917.317.817.019.017.517.9
POWER INPUT kW2.472.512.462.452.522.562.512.50
1
MBH
Sensible Capacity
Entering Dry
Entering Dry
Entering Dry
Entering Dry
Entering Dry
8014.518.521.922.715.619.823.423.6
7712.216.119.520.312.917.220.720.9
Bulb ∞F
749.913.817.218.010.314.518.018.2
71#N/A11.514.915.7#N/A11.915.415.6
68#N/A9.112.513.3#N/A9.212.712.9
8618.622.322.122.020.123.722.522.4
8316.220.0
8013.917.720.821.414.818.921.822.1
7711.615.318.419.012.216.219.219.4
Bulb ∞F
749.213.016.116.79.513.516.516.8
71#N/A10.713.814.4#N/A10.913.814.1
68#N/A8.311.412.0#N/A8.211.211.5
8619.521.520.520.620.422.320.820.9
8317.219.2
8014.916.919.720.015.918.120.420.6
7712.614.617.417.713.315.417.818.0
Bulb ∞F
7410.212.215.115.310.612.715.115.3
71#N/A9.912.713.0#N/A10.112.412.6
68#N/A7.610.410.7#N/A7.49.810.0
8620.420.718.919.220.620.919.119.4
8318.218.518.919.219.519.819.119.4
8015.916.118.718.617.017.319.019.1
7713.613.816.416.314.414.616.416.5
Bulb ∞F
7411.211.514.114.011.711.913.713.8
71#N/A9.111.711.6#N/A9.311.111.2
68#N/A6.89.49.3#N/A6.68.48.5
8621.319.917.317.820.819.517.517.9
8319.217.7
8016.915.4
7714.613.015.415.015.413.815.015.0
Bulb ∞F
7412.210.713.112.612.811.112.312.3
71#N/A8.410.710.3#N/A8.59.79.7
68#N/A6.08.48.0#N/A5.87.07.0
036-21528-001-A-0303
TEMPERATURE OF AIR ON INDOOR COIL
800 CFM900 CFM
WB ∞FWB ∞F
23.823.418.322.524.323.9
22.122.017.521.522.522.4
20.520.618.520.720.820.9
17.317.820.618.917.517.9
17.717.318.116.517.617.7
ALL SENSIBLE CAPACITY
6Unitary Products Group
03 6-21528-00 1-A-0303
TABLE 4: COOLING CAPACITIES - 2-1/2 TON (BHP030)
TEMPERATURE OF AIR ON INDOOR COIL
TEMPERATURE AIR ON
OUTDOOR COIL
7267625772676257
NET CAP. MBH34.131.528.429.935.432.729.531.0
POWER INPUT kW2.522.482.442.432.642.582.542.53
8623.929.828.429.925.731.829.531.0
8321.026.9
85 ∞F
95 ∞F
105 ∞F
115 ∞F
125 ∞F
1.
These capacities are net capacities - indoor fan heat deducted.
1
MBH
Sensible Capacity
NET CAP. MBH32.629.426.828.933.730.427.729.8
POWER INPUT kW2.832.812.712.702.932.912.812.79
1
MBH
Sensible Capacity
NET CAP. MBH30.327.225.026.731.528.226.027.7
POWER INPUT kW3.143.123.043.063.243.223.143.16
1
MBH
Sensible Capacity
NET CAP. MBH28.024.923.224.429.326.124.425.6
POWER INPUT kW3.453.433.373.423.563.543.483.53
1
MBH
Sensible Capacity
NET CAP. MBH25.622.721.422.227.224.022.723.5
POWER INPUT kW3.763.743.703.783.873.853.823.89
1
MBH
Sensible Capacity
Entering Dry
Entering Dry
Entering Dry
Entering Dry
Entering Dry
8018.123.927.929.619.025.229.230.8
7715.221.024.926.615.721.925.927.5
Bulb ∞F
7412.318.122.023.712.418.522.624.2
71#N/A15.219.120.8#N/A15.219.220.9
68#N/A12.316.217.9#N/A11.915.917.5
8622.828.226.828.925.029.727.729.8
8319.925.3
8017.022.426.628.318.324.227.529.5
7714.119.523.625.415.020.824.226.2
Bulb ∞F
7411.116.520.722.511.717.520.922.9
71#N/A13.617.819.6#N/A14.217.619.6
68#N/A10.714.916.7#N/A10.914.316.2
8621.726.625.026.723.927.926.027.7
8318.824.1
8015.921.125.426.317.222.926.227.5
7713.018.222.423.313.919.622.924.2
Bulb ∞F
7410.115.319.520.410.616.319.620.9
71#N/A12.416.617.5#N/A13.016.217.6
68#N/A9.513.714.6#N/A9.712.914.2
8620.724.923.224.422.826.124.425.6
8317.722.823.224.419.525.024.425.6
8014.819.924.224.216.221.724.825.5
7711.917.021.321.312.818.421.522.2
Bulb ∞F
749.014.118.318.49.515.118.218.9
71#N/A11.215.415.4#N/A11.814.915.5
68#N/A8.312.512.5#N/A8.411.612.2
8619.623.321.422.221.724.322.723.5
8316.721.6
8013.718.723.022.115.120.5
7710.815.820.119.211.717.220.220.2
Bulb ∞F
747.912.917.116.38.413.916.816.8
71#N/A10.014.213.4#N/A10.513.513.5
68#N/A7.111.310.4#N/A7.210.210.2
1000 CFM1125 CFM
WB ∞FWB ∞F
28.429.922.428.529.531.0
26.828.921.727.527.729.8
25.026.720.626.326.027.7
21.422.218.423.822.723.5
23.523.5
ALL SENSIBLE CAPACITY
Unitary Products Group7
TABLE 5: COOLING CAPACITIES - 3 TON (BHP036)
TEMPERATURE AIR ON
OUTDOOR COIL
7267625772676257
NET CAP. MBH41.137.534.534.342.438.635.535.3
POWER INPUT kW2.892.812.732.733.002.912.832.82
8625.632.334.534.328.235.535.535.3
8322.529.333.533.624.732.0
85 ∞F
95 ∞F
105 ∞F
115 ∞F
125 ∞F
1.
These capacities are net capacities - indoor fan heat deducted.
1
MBH
Sensible Capacity
NET CAP. MBH38.534.932.532.639.435.833.333.4
POWER INPUT kW3.213.153.053.063.313.253.153.16
1
MBH
Sensible Capacity
NET CAP. MBH35.632.129.530.436.432.830.231.1
POWER INPUT kW3.613.523.443.453.703.613.533.54
1
MBH
Sensible Capacity
NET CAP. MBH32.629.326.528.233.329.927.028.8
POWER INPUT kW4.013.883.833.844.103.973.913.92
1
MBH
Sensible Capacity
NET CAP. MBH29.726.423.526.030.226.923.926.4
POWER INPUT kW4.414.254.214.224.494.334.294.30
1
MBH
Sensible Capacity
Entering Dry
Entering Dry
Entering Dry
Entering Dry
Entering Dry
8019.526.331.732.221.228.534.535.0
7716.523.228.729.117.725.031.031.5
Bulb ∞F
7413.420.225.726.114.221.627.528.0
71#N/A17.222.623.1#N/A18.124.024.5
68#N/A14.119.620.0#N/A14.620.521.0
8625.030.932.532.627.533.933.333.4
8322.027.931.932.024.030.4
8019.024.830.530.620.526.933.033.1
7715.921.827.527.517.023.429.529.6
Bulb ∞F
7412.918.824.424.513.519.926.026.1
71#N/A15.721.421.5#N/A16.422.522.6
68#N/A12.718.418.5#N/A12.919.019.1
8623.929.429.530.426.231.930.231.1
8320.926.629.230.022.728.9
8017.923.627.828.619.225.430.030.8
7714.820.524.825.515.721.926.527.3
Bulb ∞F
7411.817.521.822.512.218.423.023.8
71#N/A14.518.719.5#N/A14.919.520.3
68#N/A11.415.716.4#N/A11.416.016.8
8622.827.826.528.225.029.927.028.8
8319.825.326.528.021.527.427.028.8
8016.822.325.226.518.023.927.028.5
7713.719.222.223.514.520.423.525.0
Bulb ∞F
7410.716.219.120.511.016.920.021.5
71#N/A13.216.117.4#N/A13.416.518.0
68#N/A10.113.114.4#N/A9.913.014.5
8621.726.323.526.023.727.923.926.4
8318.724.023.825.920.225.9
8015.721.022.624.516.722.424.126.2
7712.617.919.521.513.218.920.622.7
Bulb ∞F
749.614.916.518.49.715.417.119.2
71#N/A11.913.515.4#N/A11.913.615.7
#78#N/A8.810.412.4#N/A8.410.112.2
1050 CFM1200 CFM
036-21528-001-A-0303
TEMPERATURE OF AIR ON INDOOR COIL
WB ∞FWB ∞F
35.535.3
33.333.4
30.231.1
23.926.4
ALL SENSIBLE CAPACITY
8Unitary Products Group
03 6-21528-00 1-A-0303
TABLE 6: COOLING CAPACITIES - 3-1/2 TON (BHP042)
TEMPERATURE OF AIR ON INDOOR COIL
TEMPERATURE AIR ON
OUTDOOR COIL
7267625772676257
NET CAP. MBH48.844.540.540.649.244.940.841.0
POWER INPUT kW3.373.323.213.203.433.383.273.26
8631.639.440.540.633.041.040.841.0
8327.835.640.140.528.936.9
85 ∞F
95 ∞F
105 ∞F
115 ∞F
125 ∞F
1.
These capacities are net capacities - indoor fan heat deducted.
1
MBH
Sensible Capacity
NET CAP. MBH45.441.538.338.545.741.938.638.8
POWER INPUT kW3.673.663.543.543.723.713.603.60
1
MBH
Sensible Capacity
NET CAP. MBH41.937.735.235.642.137.935.435.7
POWER INPUT kW4.013.983.893.884.064.033.943.93
1
MBH
Sensible Capacity
NET CAP. MBH38.734.232.432.938.834.332.533.0
POWER INPUT kW4.414.354.284.284.464.404.334.32
1
MBH
Sensible Capacity
NET CAP. MBH35.630.729.630.335.530.629.630.2
POWER INPUT kW4.814.734.684.674.854.774.724.71
1
MBH
Sensible Capacity
Entering Dry
Entering Dry
Entering Dry
Entering Dry
Entering Dry
8024.031.838.840.224.832.840.141.5
7720.227.935.036.420.728.836.037.4
Bulb ∞F
7416.424.131.232.616.724.731.933.4
71#N/A20.327.428.7#N/A20.627.929.3
68#N/A16.523.524.9#N/A16.523.825.2
8630.738.238.338.532.039.838.638.8
8326.934.438.138.327.935.7
8023.030.637.537.923.931.638.839.2
7719.226.833.634.019.827.634.735.1
Bulb ∞F
7415.423.029.830.215.723.530.631.0
71#N/A19.126.026.4#N/A19.426.526.9
68#N/A15.322.222.6#N/A15.322.422.8
8628.134.535.235.629.435.835.435.7
8324.531.634.835.125.633.035.235.5
8021.028.133.733.821.829.134.935.1
7717.424.630.130.318.025.331.131.2
Bulb ∞F
7413.921.026.626.714.121.527.327.4
71#N/A17.523.023.2#N/A17.723.523.6
68#N/A13.919.519.6#N/A13.919.719.8
8626.832.532.432.928.133.432.533.0
8323.330.232.132.324.331.532.332.7
8019.726.731.231.020.527.732.432.2
7716.223.127.627.516.723.928.628.4
Bulb ∞F
7412.619.624.124.012.920.124.824.6
71#N/A16.120.620.4#N/A16.320.920.8
68#N/A12.517.016.9#N/A12.517.117.0
8625.530.429.630.326.831.029.630.2
8322.028.829.429.623.030.129.529.9
8018.525.328.728.319.226.329.829.4
7714.921.725.124.815.422.526.025.6
Bulb ∞F
7411.418.221.621.211.618.622.221.8
71#N/A14.618.117.7#N/A14.818.418.0
68#N/A11.114.514.1#N/A11.014.614.2
1300 CFM1400 CFM
WB ∞FWB ∞F
40.841.0
38.638.8
ALL SENSIBLE CAPACITY
Unitary Products Group9
TABLE 7: COOLING CAPACITIES - 4 TON (BHP048)
TEMPERATURE AIR ON
OUTDOOR COIL
7267625772676257
NET CAP. MBH54.350.445.748.254.951.046.348.8
POWER INPUT kW3.973.853.753.744.063.943.833.83
8635.545.145.748.237.247.146.348.8
8331.240.845.347.532.542.4
85 ∞F
95 ∞F
105 ∞F
115 ∞F
125 ∞F
1.
These capacities are net capacities - indoor fan heat deducted.
1
MBH
Sensible Capacity
NET CAP. MBH52.047.443.546.152.347.743.846.4
POWER INPUT kW4.334.254.174.114.434.354.264.20
1
MBH
Sensible Capacity
NET CAP. MBH48.844.240.143.249.044.540.343.5
POWER INPUT kW4.714.624.524.474.814.714.614.56
1
MBH
Sensible Capacity
NET CAP. MBH45.941.437.040.746.141.537.140.8
POWER INPUT kW5.195.084.964.935.285.175.055.02
1
MBH
Sensible Capacity
NET CAP. MBH43.138.533.938.143.238.634.038.2
POWER INPUT kW5.665.535.405.395.765.635.505.48
1
MBH
Sensible Capacity
Entering Dry
Entering Dry
Entering Dry
Entering Dry
Entering Dry
8026.836.443.745.227.837.845.346.9
7722.532.039.340.923.233.140.642.3
Bulb ∞F
7418.127.735.036.518.528.436.037.6
71#N/A23.330.632.2#N/A23.831.332.9
68#N/A19.026.327.8#N/A19.126.628.3
8634.643.543.546.136.145.343.846.4
8330.339.143.145.431.540.6
8025.934.842.143.226.836.043.644.7
7721.530.437.838.822.131.338.940.0
Bulb ∞F
7417.226.133.434.517.526.634.335.3
71#N/A21.729.130.1#N/A22.029.630.7
68#N/A17.324.725.8#N/A17.324.926.0
8632.040.240.143.233.541.840.343.5
8328.036.539.741.829.238.040.142.7
8023.932.439.639.324.833.641.040.8
7719.928.435.535.320.529.336.736.4
Bulb ∞F
7415.924.331.531.216.124.932.332.0
71#N/A20.327.427.2#N/A20.628.027.7
68#N/A16.223.423.1#N/A16.223.623.3
8631.038.737.040.732.540.237.140.8
8326.935.337.039.328.136.837.140.1
8022.931.338.436.923.832.539.938.3
7718.827.234.432.919.428.135.634.0
Bulb ∞F
7414.823.230.428.815.023.831.229.6
71#N/A19.126.324.8#N/A19.426.825.3
68#N/A15.122.320.7#N/A15.022.520.9
8629.937.333.938.131.438.634.038.2
8325.934.234.236.827.035.734.137.5
8021.830.137.334.522.731.338.835.9
7717.826.133.330.518.327.034.531.5
Bulb ∞F
7413.722.029.326.414.022.630.127.2
71#N/A18.025.222.4#N/A18.325.722.8
68#N/A14.021.218.4#N/A13.921.418.5
1500 CFM1600 CFM
036-21528-001-A-0303
TEMPERATURE OF AIR ON INDOOR COIL
WB ∞FWB ∞F
46.348.8
43.846.4
ALL SENSIBLE CAPACITY
10Unitary Products Group
03 6-21528-00 1-A-0303
TABLE 8: HEATING CAPACITIES - 2 TON (BHP024)
CFM
600
800
1000
1.
RETURN
AIR ∞F
55
70
80
55
70
80
55
70
80
These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.
These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.
These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.
These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.
These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.
Electric Heat0.020.030.030.030.040.040.050.060.070.080.090.100.010.110.110.12
CFM
14Unitary Products Group
03 6-21528-00 1-A-0303
THERMOSTATUNIT TERMINAL STRIP
** = Minimum wire size of 18 AWG
wire should be used for all field
installed 24 volt wire.
R
G
**
R
G
YY
NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.25
AMPS FOR ALL MODELS
PROGRAMMABLE
THERMOSTAT ONLY
* = Only required on units with
supplemental electric heat.
CAUTION:
Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper operation after servicing.
W
OO
C
*
W2
W1
C
24 VOLT TRANSFORMER
FIGURE 2 - FIELD WIRING DIAGRAM
Unitary Products Group15
036-21528-001-A-0303
TABLE 15: ELECTRICAL DATA (BASIC UNIT)
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
VO LTAG E
MODEL
BHP
024208/230-1-601872539.357.01.15.017.725250.9640
030
036
042
048
POWER
SUPPLY
208/230-1-6018725315.072.51.15.024.935350.9640
208/230-3-6018725310.063.01.15.018.625250.9675
460-3-604145045.031.00.65.011.915150.9675
208/230-1-6018725317.294.01.17.329.945450.9640
208/230-3-6018725311.478.01.17.322.730300.9675
460-3-604145045.740.00.67.315.420200.9675
208/230-1-6018725320.0104.01.17.333.450500.9640
208/230-3-6018725313.988.01.17.325.835350.9675
460-3-604145046.444.00.67.316.120200.9675
208/230-1-6018725323.4126.01.57.338.160600.9640
208/230-3-6018725313.093.01.57.325.135350.9675
460-3-604145046.446.50.87.316.320200.9675
1.
Rated in accordance with ARI Standard 100, utilization range ìAî .
2.
Dual element, time delay type.
LIMITATIONS
MIN.MAX.RLALRA
COMPRESSOR
1
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX
FUSE
SIZE,
AMPS
TRANSFORMER
SIZE (VA)
ELECTRIC HEAT
CORRECTION
FAC TORS
NOMINAL VOLTAGEVOLTAGE KW CAP. MULTIPLIER
240
208
230
0.75
0.92
4804600.92
16Unitary Products Group
03 6-21528-00 1-A-0303
TABLE 16: ELECTRICAL DATA (13 SEER HEAT PUMP / ELECTRIC HEAT)
COMPRESSOR
POWER
SUPPLY
BHP
MODEL
024208/230-1-609.357.01.15.0
030208/230-1-6015.072.51.15.0
036208/230-1-6017.294.01.17.3
042208/230-1-6020.0104.01.17.3
048208/230-1-6023.4126.01.57.3
030208/230-3-6010.063.01.15.0
036208/230-3-6011.478.01.17.3
042208/230-3-6013.988.01.17.3
048208/230-3-6013.093.01.57.3
030460-3-605.031.00.65.0
036460-3-605.740.00.67.3
042460-3-606.444.00.67.3
048460-3-606.446.50.87.3
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
* KW listed is for 240 volts, use Table 15 for 208 or 230 volts.
** KW listed is for 480 volts, use Table 15 for 460 volts.
FIGURE 8 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY)
22Unitary Products Group
03 6-21528-00 1-A-0303
FIGURE 9 - TYPICAL WIRING DIAGRAM (230-3-60 POWER SUPPLY)
Unitary Products Group23
036-21528-001-A-0303
FIGURE 10 - TYPICAL WIRING DIAGRAM (460-3-60 POWER SUPPLY)
24Unitary Products Group
03 6-21528-00 1-A-0303
MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be factory-assembled, single packaged,
Heat Pumps, designed for outdoor mounted installation. Units shall have minimum SEER ratings of 13.0.
They shall have built in, equal size, field convertible
duct connections for down discharge supply/return or
horizontal discharge supply/return.
The units shall be factory wired, piped, charged with R22 refrigerant and factory tested prior to shipment. All
unit wiring shall be both numbered and color coded.
All units shall be manufactured in a facility certified to
ISO 9001 standards, and the cooling performance shall
be rated in accordance with DOE and ARI test procedures. Units shall be classified to UL 1995/CAN/CSA
No. 236-M90 conditions.
UNIT CABINET
1.Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a
non-chalking, powered paint finish, certified at 750
hours salt spray test per ASTM-B117 standards.
2.The unit top shall be a single piece ìWater Shedî
design, with drip edges and no-seam corners to
provide optimum water integrity.
3.Unit shall have a rigidly mounted condenser coil
guard to provide protection from objects and personnel after installation.
4.Indoor blower section shall be insulated with up to
3/4î thick, aluminum, foil faced insulation, fastened
to prevent insulation from entering the air stream.
5.Cabinet panels shall be ìlargeî size, easily removable for servicing and maintenance, with built-in lift
handles.
6.Unit shall be built on a formed, ìSuper-Structureî
design base pan, with embossments at critical
points to add strength, rigidity and aid in minimizing
sound.
7.Full perimeter base rails shall be provided to
assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof
curb applications. Base rails shall be removable,
when required, to lower unit height.
8.Filters shall be furnished and be accessible
through a removable access door, sealed air tight.
(Single phase models - accessory kit available.
Three phase models - standard from factory.)
9.Units vertical discharge and return duct configuration shall be designed to fit between standard 24î
O.C. beams without modification to building structure, duct work and base unit.
10. Condensate pan shall be internally sloped and
conform to ASHARE 62-89 self-draining standards,
with " NPTI copper, ridged mount connection.
INDOOR (SUPPLY) FAN ASSEMBLY
1.Fan shall be direct drive, constant CFM, ECM
design. Job site selected (BHP) brake horse power
shall not exceed the motors nameplate horse
power rating.
2.Fan wheel shall be double-inlet type with forwardcurved blades, dynamically balanced to operate
smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.
3.Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
4.Fan assembly shall be ìSlip Trackî (slide-out)
design for easy removal and cleaning.
OUTDOOR FAN ASSEMBLY
1.The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum
blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth
operation.
2.The outdoor fan motor shall be totally enclosed
with permanently lubricated bearings and internally
protected against overload conditions.
REFRIGERANT COMPONENTS
1.Compressors:
A.Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.
Unitary Products Group25
036-21528-001-A-0303
B. Shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
2.Coils:
A. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally-enhanced copper tubes with all joints
brazed.
B. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru design.
3.Refrigerant Circuit and Refrigerant Safety Components shall include:
A. Independent thermal expansion devices (TXV).
B. Solid-core filter dryer to eliminate any foreign matter.
C. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge
and without disrupting condenser or evaporator air
flow.
D. The refrigeration system shall provide at least 10∞ F
of liquid sub-cooling at design conditions.
E. Unit shall have a suction line accumulator and auto-
matic reversing valve.
room thermostat ìLEDî indication of unit lockout.
Plus a built in 5 minute anti-short cycle protection.
D. Unit shall have large, easily removable panels, cov-
ering electrical controls and compressor, allowing
easy access for any maintenance or servicing.
ELECTRIC HEATING SECTION
1.An electric heating section, with nickel chromium
elements, shall be provided in a range of 5 thru 25
KW.
2.The heating section shall have an automatic reset
primary limit control to prevent the heating element
system from operating at an excessive temperature.
3.The heating section assembly shall slide out of the
unit for easy maintenance and service.
4.Units with electric heating sections shall be wired
for a single point power supply, with branch circuit
fusing (where required).
UNIT OPERATING CHARACTERISTICS
1.Unit shall be capable of starting and running at
125∞ F outdoor temperature, exceeding maximum
load criteria of ARI Standard 210/240.
4.Unit Controls:
A. Unit shall contain a large, low voltage Terminal
Board for easy connection of field low voltage wiring.
B. Controls shall be mounted in a large control box with
tilt-out, hinged access door, allowing easy access
for trouble shooting and maintenance without affecting the normal system operation pressures.
C. Unit shall contain a reliable demand defrost control
to provide defrost. The defrost control shall also
have an ìXî terminal to provide a 24 volt signal for
2.The compressor, with standard controls, shall be
capable of operation down to 45∞ F outdoor tem-
perature. Accessory low ambient kit shall be available for operation to 0∞ F.
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single
factory provided location and be capable of side or bottom entry. This will minimize roof penetrations and
avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
26Unitary Products Group
03 6-21528-00 1-A-0303
Unitary Products Group27
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.