York AHE18, 60 User Manual

TECHNICAL GUIDE
SINGLE PIECE STANDARD ECM AIR HANDLERS
FOR USE WITH SPLIT-SYSTEM COOLING & HEA T PUMPS
MODELS: AHE18 THRU 60*
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at:
www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY
Standard 5-year limited parts warranty.
Extended 10-year limited pa rt s warranty when product is registered online within 90 days of purchase for replace­ment or closing for new home construction.
ISO 9001
Certified Quality
Management System
680210-YTG-B-0311
DESCRIPTION
The Air Handler line offers the ultimate in comfort, sound and application flexibility. The air handler is shipped ready to be installed in upflow, horizontal left or right position, with minor adjustments. No special kits are required to install this deluxe product.
All JCI Unitary Products air handlers and coils use a TXV to pro­vide our customers with the optimum performance and refriger­ant control. Air handlers are shipped with “Flex-coils” without a factory installed metering device. For added flexibility, an R-22 or R-410A TXV or orifice can be field installed to meet your refrigerant choice.
FEATURE
Thermal Expansion Valve - Provides the ultimate refrigerant control required for today’s high efficient product. The UPG bolt­on TXV provides easy installation to convert the air handler to the required refrigerant, which is a true bolt-on design that does not require brazing to replace or install.
Insulated Cabinet - All air handler cabinets are thermally insu­lated with 3/4” foil faced insulation to prevent sweating.
Factory Sealed - Achieves 2% or less total airflow leakage rate at duct blaster field test conditions for system airflow verifica­tion.
Durable Finish Inside and Out - Air handler casings are made of pre-painted galvanized steel which provides a better paint to steel bond that resists corrosion and rust creep. All internal coil sheet metal parts are made of G60 galvanized or prepainted G30 galvanized.
Filters - All models have internal filter racks provided for use with 1” thick standard size filters.
Electric Heat Kits - New 6HK series of field installed electric heat kits are available for installation friendly and easy service applications. These 6HK kits are unique to these new models.
High Efficiency Blowers - All models use high efficiency brushless DC motors to provide cooling SEER rating enhance­ment.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
680210-YTG-B-0311
J
D
Blower Compartment
Circuit Breaker
Panel
Drain Pan Connections for Horizontal Applications
Refrigerant Connections
Drain Connections
for Upflow
Applications
7-11/32”
B
A
K
C
1-1/2”
Top Outlet
Dimensions
Filter Access
18-9/32”
E
Bottom Inlet Dimensions
13”
F
DIMENSIONS & DUCT CONNECTION DIMENSIONS
Dimensions
Dimensions Wiring Knockouts Refrigerant
Models
AHE18B3XH21 AHE24B3XH21 AHE30B3XH21 AHE36C3XH21 AHE42D3XH21
AHE60D3XH21
1. Actual size (Conduit size).
ABC
DEF
Height Width Depth Power Control Liquid Vapor
46” 17 1/2”
16 1/2” 13-29/32" 16 1/2” 46” 17 1/2” 16 1/2” 13-29/32" 16 1/2” 46” 17 1/2” 16 1/2” 13-29/32" 16 1/2” 52” 21” 21 1/2” 17-13/32" 20”
21 1/2”
57’ 24 1/2” 26” 20-29/32" 23-1/2”
57” 24 1/2” 26” 20-29/32" 23-1/2”
JK
7/8" (1/2")
1-3/8"(1")
1
7/8" (1/2") 3/8"
1-23/32" (1-1/4")
Connections
Line Size
3/4"
7/8"AHE48D3XH21 57” 24 1/2” 26” 20-29/32" 23-1/2”
COIL TECHNICAL DATA
Models Application
AHE18B3XH21
AHE24B3XH21
AHE30B3XH21
AHE36C3XH21
AHE42D3XH21
AHE48D3XH21
AHE60D3XH21
Heat Pump
Heat Pump
Heat Pump
Heat Pump
Heat Pump
Heat Pump
Heat Pump
Cooling /
Cooling /
Cooling /
Cooling /
Cooling /
Cooling /
Cooling /
Refrig.
Conn. Types
Sweat 3.40 2 14 (2) 14 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 3.90 3 12 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 3.90 3 12 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 4.86 3 12 (2) 20 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 5.35 3 12 (2) 22 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 5.83 3 11 (2) 24 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 6.80 3 12 (2) 28 x 17.5 1 x 0.866 3/8 Enhanced
2 Johnson Controls Unitary Products
Face Area
(Sq. Ft.)
Rows
Deep
Fin
Per In.
Coil Size
Tube
Geometry
Tube
Dia.
Fin
Type
COOLING CAPACITY
Models Rated CFM
AHE18B3XH21
AHE24B3XH21
AHE30B3XH21
AHE36C3XH21
For notes see Page 4.
610
850
585
795
985
585
795
985
730
855
1000
1190
680210-YTG-B-0311
Entering Air °F (Dry/Wet Bulb)
FULL-CASED “A” TYPE MULTI-POSITION
72 37.9 33.7 28.3 23.3 67 31.8 27.0 22.5 17.6 62 26.4 21.5 16.7 11.6 57 20.7 18.4 15.8 13.5 72 49.7 43.2 36.9 28.4 67 42.1 35.1 28.8 22.5 62 33.7 28.0 21.4 14.7 57 26.5 23.8 20.3 16.9 72 38.7 34.4 30.1 24.7 67 33.6 28.9 23.9 18.9 62 27.2 22.7 17.8 12.8 57 21.2 18.6 16.2 13.7 72 50.8 45.2 38.4 32.0 67 43.7 36.8 31.0 24.0 62 35.7 29.5 23.1 16.1 57 27.9 24.5 21.0 17.6 72 64.9 54.0 45.6 37.8 67 52.3 44.6 36.9 28.4 62 42.2 35.2 26.8 19.3 57 33.6 29.6 25.4 21.4 72 38.7 34.4 30.1 24.7 67 33.6 28.9 23.9 18.9 62 27.2 22.7 17.8 12.8 57 21.2 18.6 16.2 13.7 72 50.8 45.2 38.4 32.0 67 43.7 36.8 31.0 24.0 62 35.7 29.5 23.1 16.1 57 27.9 24.5 21.0 17.6 72 64.9 54.0 45.6 37.8 67 52.3 44.6 36.9 28.4 62 42.2 35.2 26.8 19.3 57 33.6 29.6 25.4 21.4 72 49.3 45.2 38.3 31.4 67 43.0 37.3 31.0 24.0 62 34.7 28.8 22.8 16.2 57 26.8 23.4 20.4 16.9 72 59.1 51.0 44.1 36.5 67 49.3 42.4 35.4 27.6 62 39.9 33.1 26.1 18.2 57 31.1 26.9 23.5 19.7 72 65.2 59.5 51.2 41.3 67 56.4 48.3 39.9 31.3 62 45.8 38.1 29.7 20.8 57 35.7 31.2 26.9 22.6 72 67.5 65.9 59.8 48.7 67 64.9 56.7 46.2 35.7 62 53.5 43.2 34.1 24.0 57 41.4 36.6 31.5 26.2
MBH@ Evaporator Temperature and Corresponding Pressure °F/PSIG
35/61.5 40/68.5 45/76.0 50/84.0
Johnson Controls Unitary Products 3
680210-YTG-B-0311
COOLING CAPACITY (Continued)
Models Rated CFM
820
1000
AHE42D3XH21
1180
1385
1000
1195
AHE48D3XH21
1385
1600
1190
1390
AHE60D3XH21
1565
1835
Note: Airflow is calculated for each system tonnage. Capacity varies with O.D. product.
Entering Air °F (Dry/Wet Bulb)
FULL-CASED “A” TYPE MULTI-POSITION
72 56.6 51.1 42.8 35.6 67 48.6 41.1 34.8 27.6 62 39.4 33.0 26.0 18.3 57 30.5 26.6 23.1 19.6 72 65.7 61.0 52.7 42.9 67 58.0 49.6 41.1 32.1 62 46.7 38.9 30.4 21.8 57 36.4 31.6 27.6 23.3 72 67.9 71.4 60.2 48.8 67 65.6 56.9 47.1 37.1 62 53.8 45.2 34.7 24.6 57 42.2 37.1 31.9 27.0 72 69.4 81.0 68.0 57.2 67 77.1 65.4 54.1 41.6 62 62.1 51.0 39.8 28.1 57 48.1 42.5 36.8 30.6 72 69.0 59.8 51.3 41.5 67 56.5 48.2 39.7 29.9 62 45.1 36.8 28.3 18.9 57 34.4 31.0 26.8 22.5 72 79.5 69.7 59.9 48.6 67 65.2 55.5 45.5 34.9 62 52.2 42.5 32.6 21.8 57 40.1 36.1 31.1 26.2 72 90.0 78.1 66.0 54.5 67 73.5 62.7 51.3 38.7 62 59.2 48.2 36.9 24.0 57 45.2 41.0 35.4 29.7 72 102.2 90.0 74.3 60.4 67 83.6 70.6 57.2 43.1 62 66.1 54.0 41.2 27.0 57 50.7 46.1 39.8 33.4 72 83.6 73.7 62.9 51.6 67 68.2 58.4 48.4 37.1 62 54.9 45.3 34.8 23.9 57 42.2 37.3 31.9 26.9 72 95.9 84.1 71.9 58.8 67 79.2 67.4 54.4 41.6 62 62.4 51.2 39.7 26.9 57 48.0 42.5 36.8 30.6 72 106.3 94.2 78.5 63.5 67 87.6 73.9 60.2 45.9 62 69.3 56.8 43.5 29.7 57 53.1 46.9 40.5 34.1 72 122.1 107.1 90.9 72.6 67 100.2 85.9 69.8 51.8 62 79.7 65.3 49.8 32.9 57 60.8 54.1 46.4 38.7
MBH@ Evaporator Temperature and Corresponding Pressure °F/PSIG
35/61.5 40/68.5 45/76.0 50/84.0
4 Johnson Controls Unitary Products
680210-YTG-B-0311
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow (CFM)
Capacity Factor
80% 90% 100% 110% 120%
0.96 0.98 1.00 1.02 1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models AHE18B AHE24B AHE30B AHE36C AHE42D AHE48D AHE60D
Blower - Diameter x Width 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 11 x 10
Motor
HP 1/3 HP 1/3 HP 1/3 HP 1/2 HP 1/2 HP 3/4 HP 3/4 HP
Nominal RPM 1050 1050 1050 1050 1050 1050 1050
Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Amps Full Load (230) 2.8 2.8 2.8 4.1 4.1 6.0 6.0
Type DISPOSABLE OR PERMANENT
1
Filter
Size 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1
Permanent Type Kit 1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK
Shipping / Operating Weight (lbs.) 115/103 120/105 120/105 152/137 168/150 171/153 174/156
1. Field Supplied.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
FOR
208V 230V 240V .918
OPERATION MULTIPLY
220V 240V .840
240V
.751
TABULATED KW & MBH BY
ELECTRICAL DATA - COOLING ONLY (60 Hz)
Total Motor Amps Minimum Circuit Ampacity
Models
60 Hertz 60 Hertz
208V 230V 208V 230V
Max. O.C.P.
Amps/Type
AHE MODELS
AHE18B3XH21 2.8 2.8 3.5 3.5 15 14 AHE24B3XH21 2.8 2.8 3.5 3.5 15 14 AHE30B3XH21 2.8 2.8 3.5 3.5 15 14 AHE36C3XH21 4.1 4.1 5.1 5.1 15 14 AHE42D3XH21 4.1 4.1 5.1 5.1 15 14 AHE48D3XH21 6.0 6.0 7.5 7.5 15 14 AHE60D3XH21 6.0 6.0 7.5 7.5 15 14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. * May be 0 (no Circuit Breaker) or 1 (with Circuit Breaker).
1
Minimum Wire
Size A.W.G.
Johnson Controls Unitary Products 5