York 10 SEER 50HZ R22 User Manual

TECHNICAL GUIDE
SPLIT -SYSTEM HEAT PUMPS 10 SEER – R-22 MODELS:
10 SEER 50 HZ R22 H*RA018S78 THRU H*RA036S78 (1 PH) (1.5 THRU 3 NOMINAL TONS)
Due to continuous product improvement, speci fic a t ion s are subject to change without notice.
Visit us on the web at www.york.com
339293-YTG-C-0208
DESCRIPTION
The HRA Series condensing unit is the outdoor part of a ver­satile system of air conditioning. It is designed to be custom matched with one of UPG’s complete line of evaporator sec­tions, each designed to serve a specific function. Matchi ng Air Handlers are available for upflow, downflow or horizontal applications to provide a complete system. Electric Heaters are available if required. Add-On coils are available for use with upflow, downflow or horizontal furnaces and air handlers.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed of enhanced copper tube and aluminum fins.
COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi­tions occur. A liquid line filter-drier further protects the compressor.
DURABLE FINISH - Cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimen­sion means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up away from the livi ng area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and com­pressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, a single panel covering the electrical controls and the molex plug in the control box connecting the con­denser fan, make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
FACTORY TESTED - to verify system operation and con- trol functioning before shipment .
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
339293-YTG-C-0208
Physical and Electrical Data
Model
Unit Supply Voltage 220 - 240V, 1φ, 50Hz Normal Voltage Range
1
Minimum Circuit Ampacity 9.8 14.6 20.4 20.8 Max. Overcurrent Device Amps
2
Compressor Type Recip Recip Recip Recip Compressor Amps
Rated Load 7.4 11.3 15.2 15.5
Locked Rotor53659082 Crankcase Heater No No No No Fan Motor Amps Rated Load .5 .5 1.8 1.8 Fan Diameter Inches 18 18 18 18
Rated HP 1/12 1/12 1/4 1/4 Fan Motor
Nominal RPM 970 970 900 900
Nominal CFM 1,650 1,650 2,350 2,350
Face Area Sq. Ft.8.008.009.159.15 Coil
Rows Deep 1 1 1 1
Fin / Inches 14 14 16 16 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 3/4 3/4 3/4 3/4
Unit Charge (Lbs. - Oz.)
3
Charge Per Foot, Oz. 0.66 0.66 0.68 0.68 Operating Weight Lbs. 118 123 135 137
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker.
3.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
H1RA018S78 H1RA024S78 H1RA030S78 H1RA036S78
207 to 253
15 25 35 35
3 - 13 3 - 14 3 - 12 4 - 11
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be pro­vided upon request.
Refrigerant
Unit
Model
Dimensions
(Inches)
1
A
B C Liquid Vapor
Connection
Service Valve
Size
018S78 17 35 23 024S78 17 35 23 030S78 19 35 23
3/8” 3/4”
036S78 19 35 23
1.Including Fan Guard
2 Unitary Products Group
339293-YTG-C-0208
COOLING CAPACITY - With Air Handler Coils
AIR HANDLER
UNIT MODEL
MODEL
ELECTRIC
HEAT KW
W
COIL
MODEL
RATED
CFM
1 PHASE HRA / FRP (SINGLE PHASE)
H1RA018S78 F2RP024N93 5,7.5,10 18 650 18.1 12.9 1.86 H1RA024S78 F2RP024N93 5,7.5,10 18 850 23.4 16.8 2.87 H1RA030S78 F2RP036N93 5,7.5,10,15 21 1000 29.6 20.6 3.57 H1RA036S78 F2RP036N93 5,7.5,10,15 21 1250 34.3 25.6 3.86
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor.
COOLING NET MBH
TOTAL SENS.
COOLING PERFORMANCE
KW
AIR TEMP ON CONDENSER
MODEL
SUCT. T/P
@ COMPR.
75°F 95°F 115°F 125°F
TEMP. PSIG MBH KW MBH KW MBH KW MBH KW
35 61.5 13.1 1.36 13.1 1.36 10.6 1.46 9.3 1.52
H1RA018S78
40 68.5 14.8 1.42 14.8 1.42 12.8 1.55 10.6 1.61 45 76.0 16.5 1.48 16.5 1.48 13.7 1.62 12.2 1.69 50 84.0 18.4 1.55 18.4 1.55 15.2 1.71 13.7 1.78 35 61.5 21.3 1.59 17.7 1.93 14.7 2.14 13.3 2.23
H1RA024S78
40 68.5 24.1 1.68 20.1 2.04 16.7 2.27 15.1 2.38 45 76.0 26.7 1.77 22.3 2.16 18.9 2.40 17.1 2.53 50 84.0 29.6 1.85 24.9 2.27 21.1 2.55 19.4 2.67 35 61.5 28.0 2.31 24.4 2.65 20.1 2.86 18.0 2.96
H1RA030S78
40 68.5 31.5 2.44 27.5 2.78 22.8 3.02 23.4 3.31 45 76.0 35.1 2.52 30.7 2.91 25.9 3.17 23.4 3.48 50 84.0 38.9 2.62 34.2 3.04 28.8 3.34 26.3 3.48 35 61.5 30.6 3.14 27.0 3.48 23.1 3.79 21.0 3.89
H1RA036S78
40 68.5 34.4 3.28 30.4 3.64 26.1 3.98 23.7 4.10 45 76.0 38.3 3.42 33.9 3.81 29.1 4.17 26.6 4.30 50 84.0 38.9 2.62 34.2 3.04 28.8 3.34 26.3 3.48
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 15°F superheat and 15°F sub-cooling at condensing unit. a. Increase capacity 1% for each 2°F increase in sub-cooling.
b. Decrease capacity 1% for each 2°F decrease in sub-cooling.
3. Sub-cooling in excess of 20°F may result in excessively high condensing temperature with air on condenser above 115°F Maximum recommended condensing temperature is 140°F.
Unitary Products Group 3