DESCRIPTION
The HRA Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be custom
matched with one of UPG’s complete line of evaporator sections, each designed to serve a specific function. Matchi ng
Air Handlers are available for upflow, downflow or horizontal
applications to provide a complete system. Electric Heaters
are available if required. Add-On coils are available for use
with upflow, downflow or horizontal furnaces and air handlers.
FEATURES
• QUALITY CONDENSER COILS - The coil is constructed
of enhanced copper tube and aluminum fins.
• COIL PROTECTION - Coils are protected from damage by
a polymer mesh applied between the coil face, and a PVC
coated steel coil guard.
• PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature.
This is accomplished by the simultaneous operation of
high pressure relief valve and a temperature sensor which
protects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the
compressor.
• DURABLE FINISH - Cabinet is made of pre-painted steel.
The pre-treated flat galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and matted-textured finish insure
less fading when exposed to sunlight.
• LOWER INSTALLED COST - Installation time and costs
are reduced by easy power and control wiring connections.
Discharge line heat exchanger knockouts are provided, if
required. Available in sweat connect models only. The unit
contains enough refrigerant for matching indoor coils and
15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof.
• TOP DISCHARGE - The warm air from the top mounted
fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
• LOW OPERATING SOUND LEVEL - The upward air flow
carries the normal operating noise up away from the livi ng
area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins of
the condenser coil muffle the normal fan motor and compressor operating sounds.
• LOW MAINTENANCE - Long life permanently lubricated
motor-bearings need no annual servicing.
• EASY SERVICE ACCESS - Fully exposed refrigerant connections, a single panel covering the electrical controls
and the molex plug in the control box connecting the condenser fan, make for easy servicing of the unit.
• SECURED SERVICE VALVES - Secured re-usable ser-
vice valves are provided on both the liquid and vapor
sweat connections for ease of evacuating and charging.
• FACTORY TESTED - to verify system operation and con-
trol functioning before shipment .
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
339293-YTG-C-0208
Physical and Electrical Data
Model
Unit Supply Voltage220 - 240V, 1φ, 50Hz
Normal Voltage Range
Compressor Type RecipRecipRecipRecip
Compressor Amps
Rated Load7.411.315.215.5
Locked Rotor53659082
Crankcase HeaterNoNoNoNo
Fan Motor AmpsRated Load.5.51.81.8
Fan Diameter Inches18181818
Rated HP1/121/121/41/4
Fan Motor
Nominal RPM970970900900
Nominal CFM1,6501,6502,3502,350
Face Area Sq. Ft.8.008.009.159.15
Coil
Rows Deep1111
Fin / Inches14141616
Liquid Line Set OD (Field Installed)3/83/83/83/8
Vapor Line Set OD (Field Installed)3/43/43/43/4
Unit Charge (Lbs. - Oz.)
3
Charge Per Foot, Oz.0.660.660.680.68
Operating Weight Lbs.118123135137
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker.
3.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
H1RA018S78H1RA024S78H1RA030S78H1RA036S78
207 to 253
15253535
3 - 133 - 143 - 124 - 11
All dimensions are in inches. They are subject to
change without notice. Certified dimensions will be provided upon request.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor.
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 15°F superheat and 15°F sub-cooling at condensing unit.
a. Increase capacity 1% for each 2°F increase in sub-cooling.
b. Decrease capacity 1% for each 2°F decrease in sub-cooling.
3. Sub-cooling in excess of 20°F may result in excessively high condensing temperature with air on condenser above 115°F Maximum
recommended condensing temperature is 140°F.
Unitary Products Group3