York 036-21103-003 User Manual

036-21103-003 Rev. A (0403)
®
TECHNICAL GUIDE
SPLIT-SYSTEM AIR CONDITIONERS 10 SEER 50 HZ H*RA018S78 THRU H*RA036S78 (1 PH)
H*RA036S50 THRU H*RA060S50 (3PH) (1.5 THRU 5 NOMINAL TONS)
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at www.york.com for the most up-to-date technical information.

DESCRIPTION

The HRA Series condensing unit is the outdoor part of a ver­satile system of air conditioning. It is designed to be custom matched with one of UPG’s complete line of evaporator sec­tions, each designed to serve a specific function. Matching Air Handlers are available for upflow, downflow or horizontal applications to provide a complete system. Electric Heaters are available if required. Add-On coils are available for use with upflow, downflow or horiz ont al fur naces and ai r handle rs.

FEATURES

QUALITY CONDENSER COILS - The coil is constructed of enhanced copper tube and aluminum fins.
COIL PROTECTION - Coils are protected from dam age by a polymer mesh applied between the coil face, and a PVC coated steel coil guard.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi­tions occur. A liquid line filter-drier further protects the compressor.
DURABLE FINISH - Cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by e asy p ower and contro l wi ring c onnec tions. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimen­sion means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mou nted c ompre ssor a nd the ripple d fins of the condenser coil muffle the normal fan motor and com­pressor operating sounds.
LOW MAINTENANCE - Long life perm anently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant c on­nections, a single panel covering the electrical controls and the molex plug in the control box connecting the con­denser fan, make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
FACTORY TESTED - to verify system operation and con- trol functioning before shipment.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21103-003 Rev. A (0403)
PHYSICAL AND ELECTRICAL DATA - 1 & 3 Phase
MODEL
H1RA018S78 H1RA024S78 H1RA030S78 H1RA036S78 H1RA036S50 H1RA048S50 H1RA060S50
Unit Supply Voltage 230 – 1 – 50 380/415 – 3 – 50 Normal Voltage Range
1
207 to 253 342 to 455 Minimum Circuit Ampacity 9.8 14.6 20.4 20.8 7.3 10.8 13.3 Max. Qvercurrent Device Amps
2
15 25 35 35 15 15 20
Compressor Type Recip Recip Recip Recip Recip Recip Recip
Compressor Amps
Rated Load 7.4 11.3 15.2 15.5 5.2 7.2 9.2
Locked Rotor53659082395379 Crankcase Heater No No No No No No No Fan Motor Amps Rated Load .5 .5 1.8 1.8 .8 1.8 1.8 Fan Diameter Inches 18 18 18 18 18 22 22
Rated HP 1/12 1/12 1/4 1/4 1/4 1/3 1/3 Fan Motor
Nominal RPM 970 970 900 900 1,100 1,075 1,075
Nominal CFM 1,650 1,650 2,350 2,350 2,250 3,200 3,300
Face Area Sq. Ft. 8.00 8.00 9.15 9.15 9.15 15.72 23.58
Coil
Rows Deep 1111111
Fin / Inches 14 14 16 16 18 18 18 Liquid Line OD 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Va por Line OD 3/4 3/4 3/4 3/4 3/4 7/8 7/8
Unit Charge (Lbs. - Oz.)
3
3 - 13 3 - 14 3 - 15 4 - 11 4 - 11 7 - 10 9 - 12 Charge Per Foot, Oz. 0.66 0.66 0.68 0.68 0.68 0.70 0.70 Operating Weight Lbs. 118 123 135 137 137 206 228
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, refer to publication 035-15893-60*
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
UNIT
MODEL
H1RA
DIMENSIONS
(INCHES)
1
A
B C Liquid Vapor
REFRIGERANT
CONNECTION
LINE SIZE
018S78 17 35 23 024S78 17 35 23 030S78 19 35 23 036S78 19 35 23
3/8”
3/4”
036S50 19 35 23 048S50 27 37 27 060S50 39 37 27
7/8”
1. Including fan guard
2 Unitary Products Group
036-21103-003 Rev. A (0403)
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 & 3 Phase
Additional R-22 Charge / Orifice Size for Various Matched Systems
Outdoor Unit (H1RA) 018S78 024S78 030S78 036S78 036S50 048S50 060S50 Unit Orifice(s)
1
Factory R-22 Charge, lbs-oz 3 - 13 3 - 14 3 - 14 4 - 11 4 - 11 7 - 10 9 - 12
51 57 69 71 71 84
Indoor Coil
Coil Orifice
2
System Orifice + Additional Charge, Oz G2FD024S14,17 61 51 + 0 G2FD030S17 65 57 + 0 69 + 0
G2FD036S17 75 69 + 3 71 + 0 71 + 0 G2FD036S21 75 71 + 2 71 + 2 G2FD042S21 78 71 + 4 G2FD048S21,24 78 84 + 0 G2FD060S24 90 90 + 0
COOLING CAPACITY - With Air Handler Coils
AIR HANDLER
UNIT MODEL
MODEL
ELECTRIC
HEAT KW
2
W
COIL
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
3
1 PHASE HRA / NAH
H1RA018S78 N1AHB1293 5,8,10,15,18 17 G2FD024S17 650 18.1 12.9 1.86 -- -- -­H1RA024S78 N1AHB1293 5,8,10,15,18 17 G2FD030S17 850 23.4 16.8 2.87 -- -- --
H1RA030S78
N1AHB1293 5,8,10,15,18 17 G2FD030S17 1000 28.9 20.0 3.45 -- -- -­N1AHB1293 5,8,10,15,18 17 G2FD036S17 1000 29.6 20.6 3.57 -- -- --
H1RA036S78 N1AHB1293 5,8,10,15,18 17 G2FD036S17 1250 33.5 25.2 3.83 -- -- --
3 PHASE HRA / NAH
N1AHB1293 5,8,10,15,18 17 G2FD036S17 1200 33.6 24.9 3.81 -- -- --
H1RA036S50
N1AHB1293 5,8,10,15,18 17 G2FD036S21 1200 34.4 25.5 3.87
N1AHC1693 5,8,10,15,20 21 G2FD042S21 1250 35.1 25.9 3.93 H1RA048S50 N1AHC1693 5,8,10,15,18 21 G2FD048S21 1600 48.8 35.9 4.82 -- -- -­H1RA060S50 N1AHD2093 5,8,10,15,18 24 G2FD060S24 1900 60.5 43.0 6.29 -- -- --
1 PHASE HRA / FRP (SINGLE PHASE)
H1RA018S78 F2RP024N93 5,7.5,10 18 -- 650 18.1 12.9 1.86 -- -- -­H1RA024S78 F2RP024N93 5,7.5,10 18 -- 850 23.4 16.8 2.87 -- -- -­H1RA030S78 F2RP036N93 5,7.5,10,15 21 -- 1000 29.6 20.6 3.57 -- -- -­H1RA036S78 F2RP036N93 5,7.5,10,15 21 -- 1250 34.3 25.6 3.86 -- -- --
3 PHASE HRA / FRP (SINGLE PHASE)
H1RA036S50 F2RP036N93 10,15 21 -- 1200 34.4 25.5 3.87 -- -- -­H1RA048S50 F2RP048N93 10,15 24 -- 1600 48.8 35.9 4.82 -- -- -­H1RA060S50 F2RP060N93 10,15 24 -- 1900 60.5 43.0 6.29 -- -- --
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at
those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the
total electric power input in watt-hours during the same period.
1.
TXV = Thermal Expansion Valve kit required. Use 1TV700 series kit.
2.
Single phase units require single phase 2HK heaters — Three phase units require three phase 2HK heaters. (29) indicates 460 volt use only.
3.
G2FD coils available with a factory installed horizontal drain pan. Replace “S” with “H” in the model number.
— = Not Applicable.
COOLING
KW SEER
SEER/TXV
1
EER
Unitary Products Group 3
036-21103-003 Rev. A (0403)
COOLING PERFORMANCE
AIR TEMP ON CONDENSER
MODEL
SUCT. T/P
@ COMPR.
75°F 95°F 115°F 125°F
TEMP. PSIG MBH KW MBH KW MBH KW MBH KW
35 6 1.5 13.1 1.36 13.1 1.36 10.6 1.46 9.3 1.52
H1RA018S78
40 6 8.5 14.8 1.42 14.8 1.42 12.8 1.55 10.6 1.61 45 7 6.0 16.5 1.48 16.5 1.48 13.7 1.62 12.2 1.69 50 8 4.0 18.4 1.55 18.4 1.55 15.2 1.71 13.7 1.78 35 6 1.5 21.3 1.59 17.7 1.93 14.7 2.14 13.3 2.23
H1RA024S78
40 6 8.5 24.1 1.68 20.1 2.04 16.7 2.27 15.1 2.38 45 7 6.0 26.7 1.77 22.3 2.16 18.9 2.40 17.1 2.53 50 8 4.0 29.6 1.85 24.9 2.27 21.1 2.55 19.4 2.67 35 6 1.5 28.0 2.31 24.4 2.65 20.1 2.86 18.0 2.96
H1RA030S78
40 6 8.5 31.5 2.44 27.5 2.78 22.8 3.02 23.4 3.31 45 7 6.0 35.1 2.52 30.7 2.91 25.9 3.17 23.4 3.48 50 8 4.0 38.9 2.62 34.2 3.04 28.8 3.34 26.3 3.48 35 6 1.5 30.6 3.14 27.0 3.48 23.1 3.79 21.0 3.89
H1RA036S78
40 6 8.5 34.4 3.28 30.4 3.64 26.1 3.98 23.7 4.10 45 7 6.0 38.3 3.42 33.9 3.81 29.1 4.17 26.6 4.30 50 8 4.0 38.9 2.62 34.2 3.04 28.8 3.34 26.3 3.48 35 6 1.5 29.6 3.24 27.8 3.52 25.1 3.73 23.4 3.78
H1RA036S50
40 6 8.5 33.2 3.37 31.2 3.68 28.2 3.91 26.4 3.97 45 7 6.0 36.9 3.51 34.7 3.84 31.4 4.10 29.3 4.16 50 8 4.0 40.7 3.65 38.2 4.00 34.6 4.28 32.4 4.36 35 6 1.5 43.2 4.17 39.1 4.87 34.4 5.50 31.9 5.87
H1RA048S50
40 6 8.5 48.1 4.37 43.6 5.11 38.5 5.80 35.8 6.22 45 7 6.0 53.2 4.58 48.3 5.35 42.8 6.11 39.8 6.57 50 8 4.0 58.4 4.79 53.2 5.60 47.2 6.41 44.0 6.91 35 6 1.5 50.6 5.23 48.7 5.73 45.2 6.11 42.7 6.24
H1RA060S50
40 6 8.5 55.6 5.37 54.1 5.97 50.8 6.44 48.4 6.61 45 7 6.0 60.9 5.48 59.7 6.19 56.7 6.76 54.5 6.98 50 8 4.0 66.3 5.58 65.6 6.40 62.8 7.08 60.8 7.35
1.For condensing unit only. Does not include effect of evaporator motor power or heat.
2.Performance based on 15” superheat and 15" sub-cooling at condensing unit. a.Increase capacity 1% for each 2...increase in sub-cooling.
b.Decrease capacity 1% for each 2 decrease in sub-cooling.
3.Sub-cooling in excess of 20...may result in excessively high condensing temperature with air on condenser above 115° Maximum recommended condensing temperature is 140..F.
4 Unitary Products Group

ACCESSORIES

Refer to Price Manual for specific model numbers.
036-21103-003 Rev. A (0403)

SOUND RATINGS

Compressor Blanket - Designed to further reduce the nor-
mal operating sound. Hard Start Kit (Single Phase Units) - provides required
starting torque for use with thermal expansion valve. Outdoor Thermostat - 2TD06700124 - Consists of an
adjustable outdoor thermostat and relay in a vented enclo­sure. It provides additional second stage control of the sup­plemental resistance heat.(Balance Point Control)
UNIT MODEL
018 76 024 78 030 82 036 82 048 82 060 80
SOUND
RATINGS
DECIBELS

TYPICAL INSTALLATION - H*RA018S78 THRU 036S78 (1 PH) & H*RA 036S50 THRU 060S50 (3 PH)

60” OVERHEAD CLEARANCE
10” CLEARANCE COIL AREA
MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE
WEATHERPROOF DISCONNECT SWITCH
THERMOSTAT
TO FURNACE OR AIR HANDLER TERMINAL BLOCK
NEC CLASS 1 WIRING
NEC CLASS 2 WIRING
TO INDOOR COIL
NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
CONTROL ACCESS PANEL
Unitary Products Group 5