TECHNICAL GUIDE SPLIT -SYSTEM HEAT PUMPS 10 SEER – R-22 MODELS: E*RA036 THRU 060
MODELS: 036-048 (3 PH)
MODELS: 060, 090 (3 PH)
ISO 9001
Certified Quality
LISTED
Due to continuous product improve m ent, specifications are subject to change without notice.
Visit us on the web at www.york.com Additional rating information can be found at
www.ari.org/aridirectory.
Management System
279104-YTG-B-0307
DESCRIPTION
The 10 SEER Series heat pumps is the outdoor part of a ver­satile system of heat pumps. It is designed to be custom­matched with one of UPG’s complete line of evaporator sec­tions, with each serving a specific function. Matching Air Han­dlers are available for upflow, downflow, or horizontal applications to provide a complete system. Electric Heaters are available, if required. Add-On coils are availa ble for use with upflow, downflow, or horizontal furnaces and air han­dlers.
WARRANTY
1-year limited parts warranty.
5-year limited compressor warranty.
FEATURES
QUALITY COILS - The coil is constructed of copper tube and aluminum fins.
COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi­tions occur. A liquid line filter-drier further protects the compressor.
DURABLE FINISH - Cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimen­sion means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and com­pressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, a single panel covering the electrical controls, and the molex plug in the control box connecting the con­denser fan make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment cer­tification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
279104-YTG-B-0307
Physical and Electrical Data
MODEL E1RA036S25 E2RA048S25 E1RA060S25 E1RA036S46 E2RA048S46 E1RA060S46
Unit Supply Voltage
Normal Voltage Range Minimum Circuit Ampacity 15.0 18.9 24.5 8.0 10.1 12.0
Max. Qvercurrent Device Amps Compressor Type
Compressor Amps Rated Load 10.9 14.1 18.6 5.8 7.0 9.0
Crankcase Heater Yes No No Yes No No Fan Motor Amps Rated Load 1.4 1.3 1.3 .8 .7 .8 Fan Diameter Inches 18 22 24 18 22 24 Fan Motor Rated HP 1/4 1/4 1/4 1/4 1/5 1/4
Coil Face Area Sq. Ft. 12.58 19.65 18.00 12.58 19.65 18.00
Rows Deep 112112
Fin / Inches 14 13 14 14 13 14 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 3/4 7/8 7/8 3/4 7/8 7/8
Unit Charge (Lbs. - Oz.) Charge Per Foot, Oz. .68 .70 .70 .68 .70 .70 Operating Weight Lbs. 178 232 243 178 232 243
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
1
2
3
25 30 40 15 15 20
Inertia
Locked Rotor 78 125 128 40 55 63
Nominal RPM 1,100 850 850 1,100 825 850 Nominal CFM 2,750 3,500 3,100 2,750 3,500 3,100
4
5 - 12 8 - 3 11 - 3 5 - 12 8 - 3 11 - 3
208/230-3-60 460 - 3 - 60
187 to 252 432 to 504
Scroll
D
Scroll
C
Inertia
Scroll
D
Scroll
C
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon
C
request.
DIMENSIONS
A
Unit
Model
Dimensions
(Inches)
1
A
B C Liquid Vapor
036 25 35 23 048 33 37 27 7/8”
B
060 26 43 32 7/8”
1. Including fan guard.
Refrigerant Connection
Service Valve Size
3/4”
3/8”
2 Unitary Products Group
Page 3
279104-YTG-B-0307
Additional R-22 Charge / Orifice Size for Various Matched Systems
Outdoor Unit E1RA036S(25,46) E1RA048S(25,46) E1RA060S(25,46)
Unit Orifice (s) Factory R-22 Charge, lbs-oz 5 - 12 8 - 3 11 - 3
Indoor Coil System Orifice = Additional Charge, Oz FC/MC/PC35(B,C)3X 81 + 8 – FC/MC/PC/UC36(A,B,C)3X 71 + 7 – FC/MC/PC/UC42(B,C)3X 81 + 8 – FC/MC/PC/UC48C3X 87 + 6 – FC/MC/PC/UC48D3X 87 + 6 – FC/MC/PC/UC60C3X 84 + 4 99 + 0 FC/MC/PC/UC60D3X 84 + 4 99 + 0 AHP36C3X 81 + 13 84 + 3 – AHP42C3X 81 + 13 84 + 3 – AHP/SHP48D3X 84 + 4 99 + 0 AHP60D3X 84 + 4 99 + 0 G1NA036S17L 71 + 7 – G1NA048S21D 71 + 7 81 + 8 – G1NA048S24P 81 + 8 – G1UA048S21/24 81 + 13 84 + 3 – G1UA060S24 84 + 4 99 + 0 G1FA048S21/24 81 + 13 84 + 3 – G1FA060S24 84 + 4 99 + 0 G2FD042S21 81 + 8 – G2FD048S21/24 87 + 6 – G2FD060S24 84 + 4 99 + 0
FOOTNOTES:
1. These orifices are packed in the instruction/warranty packet of each outdoor unit.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refri gerant for the condenser, the smallest evaporator and 15 feet of intercon­necting line tubing.
2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaportor + adder for line set.
5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
1
71, 81 81, 84, 87 99
Unitary Products Group 3
Page 4
279104-YTG-B-0307
COOLING CAPACITY - With Air Handler Coils
COOLING
SEER
W/O TXV
SEER
WITH TXV
EER
3
UNIT MODEL
MODEL
AIR HANDLER
ELECTRIC
HEAT KW
2
W
COIL
MODEL
1
RATED
CFM
NET MBH
TOTAL SENS.
3 PH 10 SEER HP WITH MA / MC / N-AH / G2FD
MA12BN2,4 10 17 FC/MC35B3X 1250 34.4 25.3 10 8.95
E1RA036S(25,46)
MA12BN2,4 10 17 FC/MC36B3X 1250 34.4 25.3 10 8.95 MA12BN2,4 10 17 FC/MC42B3X 1250 34.4 25.3 10 8.95
N1AHC1646 10, 15 21 G2FD042(S,H)21 1250 34.2 25.3 10 8.95
MA16CN4 10, 15 21 FC/MC48C3X 1600 45.5 33.7 10 9.45 MA20DN2 10, 15, 25 24 FC/MC48D3X 1725 45.5 33.7 10 9.45
E2RA048S(25,46
MA20DN4 10, 15, 29 24 FC/MC48D3X 1725 45.5 33.7 10 9.45 N1AHC1646 10, 15 21 G2FD048(S,H)21 1600 45.5 33.7 10 9.45 N1AHD2046 10, 15, 29 24 G2FD048(S,H)24 1600 45.5 33.7 10 9.45
E1RA060S(25,46)
MA20DN4 10, 15, 29 24 FC/MC60D3X 2000 57.0 41.0 10 9.80 N1AHD2046 10, 15, 29 24 G2FD048(S,H)24 1700 57.0 41.0 10 9.80
3 PH 10 SEER HP WITH AHP / SHP / F2RP / RC / FP / FC
4,5
F2RP/FP036 5, 8, 10, 15, 19 21 1250 34.0 24.9 10 9.00
E1RA036S25
F2RD/FP042 5, 8, 10, 15 21 1250 34.0 25.6 10 9.00
AHP36C3X 10, 15 21 1250 34.0 25.6 10 9.00 AHP42C3X 10, 15, 18 21 1250 34.0 25.6 10 9.00
F2FP048 5, 8, 10, 15, 20, 25 24 1600 45.0 33.5 10 9.40
E2RA048S25
F2FP060 5, 8, 10, 15, 20, 25 24 1600 46.5 34.4 10 9.60
AHP/SHP48D3X 10, 15, 18 24 1600 46.5 34.4 10 9.60
E1RA060S25
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. KW includes compressor, out door fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters.
F2FP060 5, 8, 10, 15, 20, 25 24 1700 56.0 40.0 10 9.40
AHP/SHP60D3X 10, 15 24 1700 56.0 40.0 10 9.40
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulat ion requirements, substitute F2FP for F2RP, and F2FC for F2RC. models. All ratings remain the same.
5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D. standard.
- = Not applicable
4 Unitary Products Group
Page 5
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils
FURNACE**
UNIT MODEL
E1RA036S(25,46
E2RA048S(25,46
E1RA060S(25,46)
1. TXV = Use 1TV700 Series Kit. * Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one.
**
Refer to Quick Selection Chart for specific furnace match-up.
CFM RANGE
(MIN.-MAX.)
1100 1400
1400 1800
1600 2100
W
21,24 G1FA048S21 1250 34.4 24.7 10 9.05
17 G1NA036S17L 1250 35.0 26.2 10 9.00 21 G1NA048S21D 1250 35.0 26.2 10 8.95
21,24 G1UA048S21 1250 34.4 24.7 10 9.05
21 G2FD042S21 1250 34.2 25.3 10 8.95
17,21 FC/MC/PC35*3X 1250 34.4 24.7 10 9.5
14,17,21 FC/MC/PC/UC36*3X 1250 34.4 24.7 10 9.5
17,21 FC/MC/PC/UC42*3X 1250 34.4 24.7 10 9.5 21,24 G1FA048S21 1600 45.5 32.7 10 9.30
21 G1NA048S21D 1600 45.0 31.2 10 9.50 21,24 G1UA048S21 1600 45.5 32.7 10 9.30 21,24 G2FD048(S,H)21,24 1600 45.5 33.7 10 9.40
21 FC/MC/PC/UC48C3X 1600 45.5 32.7 10 9.30
24 FC/MC/PC/UC48D3X 1600 45.5 32.7 10 9.30 21,24 G1FA060S21,24 1700 57.0 41.0 10 9.80 21,24 G1UA060S21,24 1700 57.0 41.0 10 9.80
24 G2FD060(S,H)24 1700 57.0 41.0 10 9.80
21 FC/MC/PC/UC60C3X 1725 57.0 41.0 10 9.80
24 FC/MC/PC/UC60D3X 2000 57.0 41.0 10 9.80
COIL
MODEL
RATED
CFM
NET MBH
TOTAL SENS.
COOLING
SEER
W/O TXV
279104-YTG-B-0307
SEER + TXV
+ TDR*
1
EER
Unitary Products Group 5
Page 6
279104-YTG-B-0307
HEATING PERFORMANCE - With Air Handler
UNIT
MODEL*
COIL
MODEL
1
ARI HEATING
2
47°F17°F HSPF -3°F7°F17°F27°F37°F47°F57°F
OUTDOOR TEMP
MBH COP MBH COP STD MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
E1RA036S(25,4
E2RA048S(25,46
E1RA060S(25,46)
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering ind oor a ir, 72% RH outdoor air with 25 feet of interconnecting piping and no supplement al electric heat operation.
3. Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur.
COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric
power input during the same period.
— = Not Applicable.
F2RP/F2FP036 34.0 3.00 20.4 2.16 7.2 15.5 2.40 15.6 2.54 20.4 2.80 24.9 3.03 29.9 3.20 34.0 3.32 38.5 3.50
AHP36,42 34.0 3.00 20.4 2.16 7.2 15.5 2.40 15.6 2.54 20.4 2.80 24.9 3.03 29.9 3.20 34.0 3.32 38.5 3.50
F2FP048 37.0 3.08 31.4 2.32 7.5 20.8 3.64 26.1 3.80 31.4 3.97 36.7 4.13 40.1 4.27 47.0 4.47 54.6 4.71
AHP48,60 37.0 3.08 31.4 2.32 7.5 20.8 3.64 26.1 3.80 31.4 3.97 36.7 4.13 40.1 4.27 47.0 4.47 54.6 4.71
F2FP060 58.5 3.12 39.0 2.34 7.6 26.0 4.48 32.5 4.68 39.0 4.88 42.1 4.98 45.1 5.07 58.5 5.49 65.0 5.70
AHP48,60 58.5 3.12 39.0 2.34 7.6 26.0 4.48 32.5 4.68 39.0 4.88 42.1 4.98 45.1 5.07 58.5 5.49 65.0 5.70
3
HEATING PERFORMANCE - With Furnace Coils
UNIT
MODEL*
G2FD042(S,H)21 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.94 29.5 3.15 34.0 3.32 40.5 3.50
G1NA036S17L 35.0 3.20 22.0 2.26 7.6 13.3 2.62 17.7 2.74 22.0 2.85 23.3 2.71 24.5 2.57 35.0 3.21 39.3 3.32
G1NA048S21D 35.0 3.20 22.0 2.26 7.6 13.3 2.62 17.7 2.74 22.0 2.85 23.3 2.71 24.5 2.57 35.0 3.21 39.3 3.32
E1RA036S25,46
FC/MC/PC35*3X 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 FC/MC/PC/UC36*3X 34.03.0020.22.14 7.2 11.32.4015.72.5820.22.7724.72.9529.53.1534.03.3240.53.50 FC/MC/PC/UC42*3X 34.03.0020.22.14 7.2 11.32.4015.72.5820.22.7724.72.9529.53.1534.03.3240.53.50 G2FD048(S,H)21,24 47.0 3.02 31.2 2.32 7.5 21.0 3.56 26.1 3.75 31.2 3.94 36.3 4.13 40.1 4.32 47.0 4.56 54.1 4.59
G1NA048S21D 47.0 2.96 31.2 2.30 7.5 20.7 3.52 25.9 3.75 31.2 3.98 35.2 4.13 39.2 4.29 47.0 4.65 52.3 4.88
E2RA048S25,46
FC/MC/PC/UC48C3X47.03.0231.22.32 7.5 21.03.5626.13.7531.23.9436.34.1340.14.3247.04.5654.14.59 FC/MC/PC/UC48D3X47.03.0231.22.32 7.5 21.03.5626.13.7531.23.9436.34.1340.14.3247.04.5654.14.59
G2FD060(S,H)24 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51
E1RA060S25,46
FC/MC/PC/UC60C3X 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51 FC/MC/PC/UC60D3X 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental elec­tric heat operation.
3. Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur.
COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric
power input during the same period.
— = Not Applicable.
1
COIL
MODEL
G1UA048S21 34.03.0020.22.14 7.2 11.32.4015.72.5820.22.7724.72.9529.53.1534.03.3240.53.50 G1FA048S21 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50
G1UA048S21 47.0 3.00 31.2 2.30 7.50 20.9 3.60 26.1 3.79 31.2 3.98 36.3 4.16 42.0 4.39 47.0 4.56 54.0 4.61 G1FA048S21 47.0 3.00 31.2 2.30 7.5 20.9 3.60 26.1 3.79 31.2 3.98 36.3 4.16 42.0 4.39 47.0 4.59 54.0 4.61
G1UA060S24 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51 G1FA060S24 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51
47°F17°F
MBH COP MBH COP STD MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
ARI HEATING
2
HSP
-3°F7°F17°F27°F37°F47°F57°F
F
OUTDOOR TEMP
3
6 Unitary Products Group
Page 7
279104-YTG-B-0307
ACCESSORIES
Refer to Price Manual for specific model numbers. Start Assist Kit (2SA067*) Blower Time Delay - Available to increase efficiency when
installed. Installs on indoor section and maintains blower for approximately one minute after cooling thermostat has been satisfied.
Hard Start Kits - Provides required starting torque for use with Thermal Expansion Valve Kit.
Low Temperature Cutout (2LT06700224) - Prevents heat pump operation below -10°F ambient temperature.
Compressor Blanket - Designed to further reduce the nor­mal operating sound.
Add-on Fossil Fuel Control - Interface contro ls for use with gas, oil furnaces and the heat pump system are available.
Thermal Expansion Valve Kit - 1TVM700 Series TXV kit used to improve system performance.
Outdoor Thermostat (2TD06700124) - Provides additional staging of supplemental electric heat.
TYPICAL INSTALLATION
Room Thermostats - A wide selection of matching thermo-
stats is available to provide features required for any installa­tion.
2H/1C, manual changeover electronic non-programmable thermostat.
3H/2C, non-programmable digital thermostat. 3H/2C, auto/manual changeover, electronic programmable,
7-day, thermostat. * For the most current accessory information, refer to the
price book or consult factroy.
SOUND POWER RATINGS*
UNIT
MODEL
018 80 024 80 030 80 036 82 042 82 048 77 060 82
* Rated in accordance with ARI 270-95 Standards.
(dBA)
60” OVERHEAD CLEARANCE
10” CLEARANCE COIL AREA
NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
MINIMUM 24” SERVICE ACCESS CLEARANCE ON ONE SIDE
WEATHERPROOF DISCONNECT SWITCH
CONTROL ACCESS PANEL
THERMOSTAT
TO FURNACE OR AIR HANDLER TERMINAL BLOCK
NEC CLASS 1 WIRING
NEC CLASS 2 WIRING
TO INDOOR COIL
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
Unitary Products Group 7
Page 8
279104-YTG-B-0307
TYPICAL FIELD WIRING - 3 PH (036 - 060)
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
THERMOSTAT
LOW VOLTAGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEAT
R
BorC
Y
O
W
LorX
G
T
E
1
JUMPER TERMINALS E AND W TOHEAT ON FIRST STAGE DURING EMERGENCY HEAT.
2
TERMINAL NOT USED ON ALL THERMOSTATS.
1
2
2
POWER WIRING 24V CONTROL WIRING
(NEC CLASS 2)
FIELD INSTALLED JUMPER
GND.
LUG
3
CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.
4
CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.
5
GRAY FOR USE WITH OPTIONAL OUTDOOR THERMOSTAT KITS.
INDOOR UNIT
R
BorC
Y
O
W2
G
W1
3,4
DEFROST CONTROL
RED
BLK
YEL
ORG
BRN
PUR
WHT
5
GRY
208/230-3-60
R
C
Y
O
W
X
/66
W1
CC
POWER SUPPLY
460-3-50
CONTACTOR
T3
T2
M
L3
L2
POWER WIRING
208/230-3-60
460-3-50
T1
L1
GND.
SCREW
OUTDOOR UNIT
TYPICAL FIELD WIRING - 3 PH (090)
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
THERMOSTAT
R
BorC
Y
O
W
X
G
T
E
1
JUMPER TERMINALS E AND W TOHEAT ON FIRST STAGE DURING EMERGENCY HEAT.
2
TERMINAL NOT USED ON ALL THERMOSTATS.
3
TERMINAL NOT USED ON ALL THERMOSTATS.
1
2
2
FIELD INSTALLED JUMPER
POWER WIRING 24V CONTROL WIRING
(NEC CLASS 2)
3
CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.
4
CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.
5
REQUIRED ON ALL ELECTRIC HEAT
INDOOR UNIT
LOW VOLTAGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEAT
R
C
Y
O
W
X
GND.
LUG
53
G
60
60
5
FIELD INSTALLED JUMPER
3,4
DEFROST CONTROL
RED
BLK
YEL
ORG
BRN
PUR
WHT
208/230-3-60
R
C
Y
O
W
X
/66
W1
POWER SUPPLY
460-3-50
CONTACTOR
T3
T2
M
L3
L2
POWER WIRING
208/230-3-60
460-3-50
T1
L1
GND.
SCREW
OUTDOOR UNIT
8 Unitary Products Group
Page 9
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. E1RA036S(25,46) INDOOR COIL MODEL NO. F2RP/F2FP036
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
NOTE:
ID CFM 1000 1250 1400
ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70
ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 38.1 35.0 32.5 29.4 38.6 35.5 32.9 29.9 38.8 35.7 33.2 30.2 S.C. 22.9 22.9 22.1 23.6 24.1 24.2 23.4 24.8 24.9 24.9 24.1 25.5
KW 3.15 3.08 3.02 2.94 3.16 3.10 3.03 2.96 3.17 3.10 3.04 2.97 T.C. 37.6 34.6 32.0 28.9 38.1 35.1 32.7 29.4 38.3 35.3 33.0 29.7 S.C. 23.3 23.4 22.6 23.9 24.8 24.9 24.1 25.3 25.7 25.7 25.0 26.1
KW 3.39 3.30 3.22 3.12 3.40 3.32 3.24 3.14 3.41 3.33 3.25 3.15 T.C. 36.2 33.3 30.9 27.7 36.7 33.7 31.4 28.3 36.8 34.0 31.6 28.6 S.C. 23.3 23.3 22.6 23.7 24.9 24.9 24.0 25.4 25.8 25.9 24.9 26.2
KW 3.71 3.60 3.51 3.38 3.72 3.62 3.53 3.40 3.74 3.64 3.55 3.42 T.C. 34.4 31.5 29.2 26.3 34.7 32.0 29.6 26.8 35.0 32.2 29.9 27.3 S.C. 22.9 22.9 22.1 23.3 24.5 24.5 23.5 24.7 25.6 25.5 24.6 25.5
KW 4.03 3.90 3.79 3.63 4.06 3.93 3.82 3.67 4.06 3.94 3.82 3.71 T.C. 32.2 29.6 27.4 24.7 32.6 30.0 27.8 25.5 32.8 30.2 28.1 25.8 S.C. 22.2 22.2 21.4 22.4 23.9 23.8 22.9 23.8 24.8 24.8 23.8 24.1
KW 4.34 4.19 4.05 3.88 4.37 4.22 4.09 3.93 4.38 4.24 4.10 3.96 T.C. 30.0 27.7 25.6 23.1 30.5 28.0 26.0 24.2 30.6 28.2 26.3 24.3 S.C. 21.5 21.5 20.6 21.5 23.3 23.1 22.2 22.9 24.0 24.1 23.1 22.7
KW 4.65 4.48 4.31 4.13 4.68 4.51 4.36 4.19 4.70 4.54 4.38 4.21
279104-YTG-B-0307
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
MA12BN2,4 FC/MC35B3X 1.01 1.02 1.01 MA12BN2,4 FC/MC36B3X 1.01 1.02 1.01 MA12BN2,4 FC/MC42B3X 1.01 1.02 1.01 MA12BN2,4 G2FD042(S,H)21 1.01 1.02 1.01 AHP42C3X 1.00 1.00 1.00 F2RP/F2FP042 – 1.00 1.00 1.00 – G1FA048S21 1.01 0.99 1.01 – G1NA036S17L 1.03 1.05 1.03 – G1NA048S21D 1.03 1.05 1.04 – FC/MC/PC35*3X 1.01 0.99 1.01 – FC/MC/PC/UC36*3X 1.01 0.99 1.01 – FC/MC/PC-UC42*3X 1.01 0.99 1.01 – G1UA048S21 1.01 0.9 9 1.01 – G2FD042(S,H)21 1.01 1.02 1.01
T.C. S.C. KW
Unitary Products Group 9
Page 10
279104-YTG-B-0307
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. E2RA048S(25,46) INDOOR COIL MODEL NO. F2FP048
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
NOTE:
ID CFM 1300 1450 1550 ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57
T.C. 52.3 48.3 45.0 40.6 53.0 49.0 45.7 41.3 53.4 49.4 46.1 41.9
S.C. 32.5 32.8 31.7 33.5 34.0 34.3 33.2 35.1 35.0 35.2 34.1 36.3
KW 4.14 4.07 4.02 3.95 4.16 4.08 4.04 3.97 4.17 4.09 4.05 3.97
T.C. 50.9 47.0 43.7 39.4 51.5 47.6 44.4 40.3 51.9 48.0 44.7 40.6
S.C. 32.4 32.6 31.6 33.3 34.0 34.2 33.2 35.1 35.2 35.4 34.2 36.2
KW 4.44 4.36 4.30 4.22 4.46 4.38 4.32 4.24 4.47 4.38 4.33 4.25
T.C. 48.8 45.0 41.8 37.9 49.2 45.5 42.4 38.4 49.6 45.8 42.7 38.7
S.C. 32.0 32.2 31.2 32.9 33.6 33.8 32.9 34.5 34.9 35.1 33.8 35.6
KW 4.87 4.79 4.73 4.64 4.90 4.81 4.74 4.66 4.91 4.81 4.76 4.67
T.C. 46.1 42.5 39.5 35.8 46.6 43.0 40.1 36.3 46.4 43.3 40.4 36.7
S.C. 31.0 31.1 30.1 32.0 32.9 32.9 31.9 33.7 33.8 34.3 32.9 35.1
KW 5.37 5.28 5.22 5.12 5.38 5.30 5.22 5.14 5.34 5.30 5.24 5.14
T.C. 43.2 39.9 37.0 33.5 43.6 40.3 37.6 34.2 43.8 40.6 37.9 35.0
S.C. 29.9 30.2 29.2 30.7 31.8 32.1 30.8 32.8 32.9 33.1 31.8 34.5
KW 5.90 5.80 5.74 5.66 5.90 5.80 5.76 5.66 5.92 5.83 5.78 5.68
T.C. 40.3 37.3 34.6 31.2 40.6 37.6 35.0 32.1 41.2 37.9 35.3 33.3
S.C. 28.8 29.3 28.2 29.4 30.7 31.3 29.7 31.9 32.0 31.9 30.8 33.9
KW 6.43 6.32 6.27 6.20 6.42 6.30 6.31 6.18 6.50 6.36 6.31 6.22
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
MA16CN2,4 FC/MC48C3X 1.00 1.00 0.97 N1AHC1646 G2FD048(S,H)21 1.00 1.00 0.97 MA20DN2,4 FC/MC48D3X 1.00 1.00 0.97 N1AHD2046 G2FD048(S,H)24 1.00 1.00 0.97 AHP/SHP48D3X – 1.02 1.01 1.02 F2FP060 1.02 1.01 1.02 – G1FA048S21 1.00 0.97 0.98 – G1NA048S21D 0.99 0.93 0.95 – G1UA048S21 1.00 0.97 0.98 – FC/MC/PC/UC48C,D3X 1.00 1.00 0.97 – G2FD048(S,H)21,24 1.00 1.00 0.97
T.C. S.C. KW
10 Unitary Products Group
Page 11
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. E1RA060S(25,46 INDOOR COIL MODEL NO. G2FD060(S,H)24
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
NOTE:
ID CFM 1600 1800 2000
ID DB (°F) 85 80 75 85 80 75 85 80 75
ID WB (°F) 71 67 63 71 67 63 71 67 63
T.C. 63.0 61.1 60.7 62.9 60.9 61.1 62.9 60.6 61.4 S.C. 39.6 39.7 40.3 41.6 41.5 42.2 43.7 43.3 44.1
KW 3.71 3.66 3.68 3.71 3.66 3.67 3.71 3.67 3.67 T.C. 62.3 59.8 57.9 62.5 60.0 58.5 62.6 60.1 59.0 S.C. 39.6 39.3 39.1 41.8 41.3 41.1 43.9 43.3 43.1
KW 4.20 4.14 4.12 4.21 4.15 4.13 4.21 4.16 4.13 T.C. 61.7 58.5 55.1 62.0 59.1 55.9 62.3 59.6 56.6 S.C. 39.6 38.9 38.0 41.9 41.1 40.1 44.2 43.3 42.2
KW 4.70 4.63 4.57 4.71 4.64 4.58 4.72 4.65 4.60 T.C. 61.0 57.2 52.3 61.5 58.2 53.3 62.0 59.1 54.2 S.C. 39.6 38.5 36.8 42.0 40.9 39.0 44.4 43.3 41.2
KW 5.19 5.11 5.01 5.21 5.13 5.04 5.22 5.14 5.06 T.C. 58.3 53.9 49.1 59.1 54.7 49.9 60.0 55.6 50.7 S.C. 38.5 37.2 35.4 41.0 39.6 37.6 43.6 41.9 39.8
KW 5.78 5.67 5.55 5.80 5.69 5.57 5.82 5.71 5.60 T.C. 55.5 50.5 45.9 56.8 51.3 46.5 58.0 52.1 47.1 S.C. 37.4 35.9 34.0 40.1 38.2 36.2 42.7 40.5 38.3
KW 6.36 6.22 6.08 6.39 6.25 6.11 6.41 6.27 6.13
279104-YTG-B-0307
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler Coil
MA20DN2,4 FC/MC60D3X 1.00 1.00 1.00 N1AHD2046 G2FD060(S,H)24 1.00 1.00 1.00 AHP/SHP60D3X 0.98 0.98 1.02 F2FP060 0.98 0.98 1.02 – G1FA060S21,24 1.00 1.00 1.00 – G1UA060S21,24 1.00 1.00 1.00 – FC/MC/PC/UC60*3X 1.00 1.00 1.00
T.C. S.C. KW
Unitary Products Group 11
Page 12
279104-YTG-B-0307
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO E1RA036S(25,46) EVAPORATOR COIL MODEL NO F2RP/F2FP036
AIR TEMP. ENTERING OUTDOOR
UNIT
60
47
40
30
17
10
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
NOTE:
AIR TEMP.
ENTERING
INDOOR
COIL
60 41.63.373.6242.03.303.7341.33.273.70 70 39.13.543.2440.23.493.3740.23.493.38 80 37.43.702.9739.13.673.1239.73.693.16 60 35.33.173.2635.73.153.3234.83.153.24 70 33.13.322.9334.03.323.0033.83.332.98 80 31.53.462.6732.73.482.7633.33.492.80 60 30.23.022.9431.23.033.0231.93.053.08 70 28.73.142.6829.53.162.7430.43.182.81 80 27.13.282.4327.93.302.4828.93.322.55 60 26.12.892.6527.42.932.7427.52.962.73 70 24.42.962.4225.83.012.5126.13.042.51 80 22.43.072.1423.83.132.2324.33.162.25 60 21.42.662.3621.92.712.3722.02.742.36 70 19.72.732.1220.42.792.1520.72.822.15 80 18.02.791.8918.92.861.9419.32.891.96 60 18.12.502.1218.82.562.1619.12.602.16 70 16.52.551.9017.42.621.9517.72.661.96 80 14.82.581.6815.82.651.7516.22.691.77
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1000 1250 1400
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil
MA12BN2,4 FC/MC35B3X 1.01 1.02 1.01 MA12BN2,4 FC/MC36B3X 1.01 1.02 1.01 MA12BN2,4 FC/MC42B3X 1.01 1.02 1.01 MA12BN2,4 G2FD042(S,H)21 1.00 1.00 1.00 AHP42C3X 1.00 1.00 1.00 F2RP/F2FP042 1.00 1.00 1.00 – G1FA048S21 1.00 1.00 1.00 – G1NA036S17L 1.03 0.97 1.07 – G1NA048S21D 1.03 0.97 1.07 – FC/MC/PC35*3X 1.01 0.99 1.01 – FC/MC/PC/UC36*3X 1.01 0.99 1.01 – FC/MC/PC-UC42*3X 1.01 0.99 1.01 – G1UA048S21 1.00 1.00 1.00 – G2FD042(S,H)21 1.00 1.00 1.00
MBH KW COP
12 Unitary Products Group
Page 13
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO E2RA048S(25,46) EVAPORATOR COIL MODEL NO F2RP/F2FP048
AIR TEMP. ENTERING OUTDOOR
UNIT
60
47
40
30
17
10
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
NOTE:
AIR TEMP.
ENTERING
INDOOR
COIL
60 53.44.863.2352.94.723.2852.24.253.61 70 54.24.763.3454.14.613.4453.74.143.80 80 54.15.572.8554.45.392.9654.44.833.30 60 47.04.543.0346.64.453.0746.54.053.36 70 46.94.563.0247.04.473.0847.24.063.41 80 46.35.242.5946.95.132.6847.34.652.98 60 37.73.543.1242.94.312.9243.43.933.24 70 37.33.982.7542.94.402.8642.64.133.02 80 36.65.791.8542.55.002.5040.05.472.14 60 37.74.012.7638.74.032.8237.93.703.00 70 36.74.162.5838.24.222.6538.43.932.86 80 35.34.602.2537.34.702.3338.74.442.55 60 32.23.672.5732.73.682.6133.03.402.85 70 30.83.982.2731.43.972.3231.83.662.55 80 29.44.302.0030.14.292.0630.63.942.28 60 29.23.462.4829.63.462.5130.13.192.77 70 27.53.812.1227.93.802.1528.43.512.37 80 25.84.021.8826.34.021.9226.73.712.12
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1250 1400 1550
279104-YTG-B-0307
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil
MA16CN2,4 FC/MC48C3X 1.00 1.00 0.97 N1AHC1646 G2FD048(S,H)21 1.00 1.02 0.98 MA20DN2,4 MC48D3X 1.00 1.02 0.98 N1AHD2046 G2FD048(S,H)24 1.00 1.02 0.98 AHP/SHP48D3X – 1.01 1.02 0.99 F2FP060 1.01 1.02 0.99 – G1FA048S21 1.00 1.02 0.98 – G1NA048S21D 1.00 1.04 0.96 – G1UA048S21 1.00 1.03 0.97 – FC/MC/PC/UC48C,D3X 1.00 1.03 0.97 – G2FD048(S,H)21,24 1.00 1.03 0.97
MBH KW COP
Unitary Products Group 13
Page 14
279104-YTG-B-0307
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO E1RA060S(25,46) EVAPORATOR COIL MODEL NO G2FD060(S,H)24
AIR TEMP. ENTERING OUTDOOR
UNIT
60
47
40
30
17
10
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
NOTE:
AIR TEMP.
ENTERING
INDOOR
COIL
60 63.65.093.6761.94.983.6460.14.873.62 70 64.85.333.5663.55.183.5962.25.043.62 80 65.95.603.4565.15.393.5464.25.203.62 60 56.94.154.0355.74.024.0654.43.904.10 70 58.34.623.7058.04.543.7556.34.353.80 80 59.75.193.3859.05.033.4458.24.883.50 60 54.54.053.9553.33.933.9752.03.814.00 70 53.74.413.5753.44.323.6353.24.223.69 80 52.94.873.1953.64.783.2954.34.713.38 60 49.63.893.7449.83.803.8449.93.723.93 70 47.74.183.3448.04.103.4448.44.023.53 80 45.84.572.9446.34.473.0446.84.393.13 60 40.63.563.3441.03.513.4241.33.463.50 70 38.83.862.9439.23.803.0239.73.743.11 80 36.94.262.5437.54.182.6338.04.102.71 60 36.3 3.53 3.01 36.7 3.46 3.11 37.1 3.38 3.21 70 34.33.822.6334.73.742.7235.23.672.81 80 32.24.192.2532.74.122.3333.24.052.40
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1600 1800 2000
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil
MA20DN2,4 FC/MC60D3X 1.00 1.00 1.00 N1AHD2046 G2FD060(S,H)24 1.00 1.00 1.00 AHP/SHP60D3X 1.01 1.03 0.98 F2FP060 1.01 1.03 0.98 – G1FA060S21,24 1.00 1.00 1.00 – G1UA060S21,24 1.00 1.00 1.00 – FC/MC/PC/UC60*3X 1.00 1.00 1.00
MBH KW COP
14 Unitary Products Group