York 00497VIP User Manual

Page 1
OPTIVIEW
TM
REMOTE CONTROL CENTER
INSTALLATION, OPERATION & SERVICE
OPTIVIEW™ REMOTE CONTROL CENTER
New Release

Form 50.40-OM2 (601)

00497VIP
Page 2
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe
personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized operating/service personnel. It is expected that this individual possesses independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or seri­ous injury.
CAUTION identifies a hazard which could lead to damage to the machine, damage to other equip­ment and/or environmental pollu­tion. Usually an instruction will be given, togeth e r wit h a brief explanation.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or
NOTE is used to highlight additional information which may be helpful to you.
serious injury.
External wiring, unless specied as an optional connection in the manufacturer’s product line, is not to be connected inside the micro panel cabinet. Devices such as relays, switches, transducers and controls may not be installed inside the micro panel. No external wiring is allowed to be run through the micro panel. All wiring must be in accordance with YORK’s published specications and must be performed only by qualied YORK personnel. YORK will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this will void the manufacturer’s warranty and cause serious damage to property or injury to persons.
Page 3
CHANGEABILITY OF THIS DOCUMENT
FORM 50.40-OM2
In complying with YORK’s policy for continuous product improvement, the information contained in this document is subject to change without notice. While YORK makes no commitment to update or provide current information automatically to the manual owner, that information, if applicable, can be obtained by contacting the nearest YORK Applied Systems Service ofce.
It is the responsibility of operating/service personnel as to the applicability of these documents to the equipment in question. If there is any question in the mind of operating/service personnel as to the ap plicability of these do cuments, then, prior to working on the equipment, they should verify with the owner whether the equipment has been modied and if current literature is available.
3YORK INTERNATIONAL
Page 4

TABLE OF CONTENTS

SECTION 1 PRODUCT DESCRIPTION ....................................................................... 8
Chiller/Condensing Control Panel(s) .......................................................... 9
SECTION 2 INSTALLATION........................................................................................ 10
Mounting ..................................................................................................10
Installation Checklist ................................................................................ 10
Wiring ................................................................................................... 10
Lan Transient Installation ......................................................................... 14
Eprom Compatibility ................................................................................ 14
Troubleshooting .......................................................................................14
Safety ................................................................................................... 14
Proper Installation Practices ..................................................................... 15
SECTION 3 OPERATION............................................................................................. 18
OptiView Remote Control Center ............................................................. 18
Screen Descriptions and Usage................................................................. 19
Home Screen............................................................................................. 22
Unit Screen ..........................................................................................24
Systems Screen............................................................................... 29
Individual System Screen.......................................................... 32
Hours/Starts Screen ........................................................................ 34
Options Screen ...............................................................................36
Trending Screen .............................................................................38
Trend Setup Screen................................................................... 40
Setpoints Screen ............................................................................. 44
History Screen ................................................................................ 47
History Details Screen .............................................................. 48
RCC Setpoints Screen ......................................................................... 49
RCC Setup Screen .......................................................................... 50
Comms Screen .......................................................................... 52
Printer Screen ............................................................................53
Diagnostics Screen ....................................................................54
Diagnostics (I/O) Screen ..................................................... 55
Diagnostics (RCC Comms) Screen ..................................... 56
Display Messages ..................................................................................... 58
SECTION 4 PRINTERS ............................................................................................... 59
SECTION 5 SERVICE ................................................................................................. 65
Introduction............................................................................................... 65
Page 5
FORM 50.40-OM2
System Architecture.................................................................................. 66
Microboard................................................................................................ 68
Microboard Program Jumpers .................................................................. 76
Microboard Program Switches .................................................................78
Liquid Crystal Display.............................................................................. 81
Display Interface Board ............................................................................ 87
Display Backlight Inverter Board ............................................................. 89
Keypad .................................................................................................... 91
Power Supply............................................................................................ 94
Ofine Diagnostics & Troubleshooting.................................................... 96
Main Diagnostics ...................................................................................... 97
Keypad Test............................................................................................... 98
Display Test .............................................................................................. 99
Bit Pattern Test ....................................................................................... 100
Serial Inputs / Outputs Tests ................................................................... 101
Digital Inputs / Outputs Tests ................................................................. 103
Analog Inputs Test ..................................................................................104
System Commissioning Checklist .......................................................... 105
SECTION 6 PART NUMBER AND RENEWAL PARTS........................................... 106
LIST OF TABLES
TABLE 1 – Required Software Version of the Chiller/Condensing Unit Eproms .......... 11
TABLE 2 – Program Jumpers ......................................................................................... 76
TABLE 3 – Program Switches ........................................................................................78
TABLE 4 – Part Number ...............................................................................................106
TABLE 5 – Renewal Parts ............................................................................................106
5YORK INTERNATIONAL
Page 6
LIST OF FIGURES
FIG. 1 – EU DECLARATION OF CONFORMITY ............... 7
FIG. 2 – FIELD WIRING ................................................... 12
FIG. 3 – CONTROL INSTALLATION ................................ 16
FIG. 4 – GROUNDING ..................................................... 16
FIG. 5 – SEPARATE CONDUIT INSTALLATION .............. 17
FIG. 6 – POWER & GROUND WIRE CONNECTIONS.... 17
FIG. 7 – OPTIVIEW REMOTE CONTROL CENTER ....... 18
FIG. 8 – SCREEN NAVIGATION LAYOUT ....................... 20
FIG. 9 – HOME SCREEN ................................................. 22
FIG. 10 – UNIT SCREEN ................................................... 24
FIG. 11 – SYSTEMS SCREEN .......................................... 29
FIG. 12 – INDIVIDUAL SYSTEM SCREEN........................ 32
FIG. 13 – HOURS AND STARTS SCREEN ....................... 34
FIG. 14 – OPTIONS SCREEN ........................................... 36
FIG. 15 – TRENDING SCREEN ......................................... 38
FIG. 16 – TRENDING SETUP SCREEN ............................ 40
FIG. 17 – SETPOINTS SCREEN ....................................... 44
FIG. 18 – HISTORY SCREEN............................................ 47
FIG. 19 – HISTORY DETAILS SCREEN ............................ 48
FIG. 20 – RCC SETPOINTS SCREEN .............................. 49
FIG. 21 – RCC SETUP SCREEN ....................................... 50
FIG. 22 – COMMS SCREEN .............................................. 52
FIG. 23 – PRINTER SCREEN ............................................ 53
FIG. 24 – DIAGNOSTICS SCREEN ................................... 54
FIG. 25 – DIAGNOSTICS I/O SCREEN ............................. 55
FIG. 26 – DIAGNOSTICS RCC COMMS SCREEN ........... 56
FIG. 27 – PRINTERS ......................................................... 59
FIG. 28 – EXAMPLE PRINTOUT (OPERATING DATA)...... 63
FIG. 29 – EXAMPLE PRINTOUT (HISTORY HEADER) .... 64
FIG. 30 – CONTROL CENTER BLOCK DIAGRAM ........... 67
FIG. 31 – MICROBOARD ................................................... 73
FIG. 32 – FLASH MEMORY CARD.................................... 74
FIG. 33 – BLOCK DIAGRAM, MICROBOARD .................. 75
FIG. 34 – MICROBOARD LAMP DIMMER CIRCUIT ......... 78
FIG. 35 – SERIAL DATA COMMUNICATIONS PORTS...... 79
FIG. 36 – CONFIGURABLE ANALOG INPUTS ................. 80
FIG. 37 – DISPLAY, MOUNTING........................................ 84
FIG. 38 – LCD TYPICAL CONTROL SIGNAL TIMING ...... 84
FIG. 39 – LG SEMICON LP104V2 DISPLAY ASSEMBLY - 85
FIG. 40 – SHARP LQ10D367 DISPLAY ASSEMBLY - ...... 85
FIG. 41 – SHARP LQ10D367 BACKLIGHT LAMP
REPLACEMENT ................................................ 86
FIG. 42 – LG SEMICON LP104V2 BACKLIGHT LAMP
REPLACEMENT................................................. 86
FIG. 43 – DISPLAY INTERFACE BOARD .......................... 88
FIG. 44 – DISPLAY BACKLIGHT INVERTER BOARD....... 90
FIG. 45 – KEYPAD ............................................................. 92
FIG. 46 – DIAGRAM, KEYPAD........................................... 93
FIG. 47 – BLOCK DIAGRAM, DC POWER DISTRIBUTION. 95
FIG. 48 – MAIN DIAGNOSTIC SCREEN ........................... 97
FIG. 49 – KEYPAD TEST SCREEN ................................... 98
FIG. 50 – DISPLAY TEST SCREEN................................... 99
FIG. 51 – BIT PATTERNS TEST SCREEN....................... 100
FIG. 52 – SERIAL INPUTS/OUTPUTS TESTS SCREEN 101
FIG. 53 – DIGITAL INPUTS/OUTPUTS TESTS SCREEN 103
FIG. 54 – ANALOG INPUTS TEST SCREEN .................. 104
FIG. 55 – FRONT OF OPTIVIEW RCC ............................ 107
FIG.56 – INSIDE OF OPTIVIEW RCC ............................ 107
FIG.57 – INSIDE DOOR OF OPTIVIEW RCC ................ 108
FIG.58 – LOCATION OF FUSE, F1 & F2 ........................ 109
Page 7
FORM 50.40-OM2

FIG. 1 – EU DECLARATION OF CONFORMITY

7YORK INTERNATIONAL
Page 8
Product Description

SECTION 1 – PRODUCT DESCRIPTION

The YORK OptiView Remote Control Center is a microprocessor based control system capable of remotely monitoring certain chillers and condensing units. It can monitor and individually control 1 to 8 of these chiller/condensing units.
The panel comes congured with a full screen color LCD Graphic Display mounted in the middle of a keypad interface. The graphic display allows the presentation of the current information all at once. In addition, the operator may view a graphical representa­tion of several operating parameters. For the novice user, the locations of various parameters are clearly and intuitively marked. Instructions for specic operations are provided on many of the screens.
The graphic display also allows information to be represented in Imperial units (temperatures in °F and pressures in PSIG or PSID) or SI units (temperatures in °C and pressures in BARG or BARD).
All values that are modiable at the Remote Control Center are recorded in memory and preserved even through a power failure condition. During operation, the chillers are continually polled and the user is advised of the operating conditions by various status and warning messages. A complete listing of shutdown, status, and warning messages is within the chiller/condensing unit’s operation manual.
If the chiller/condensing unit is in remote control mode the OptiView Remote Control Center provides the capability to program the following:
1. Start Command
2. Stop Command
3. Local Setpoint
4. Local Control Range
5. Daily/Holiday Schedule
6. Current or Load Limit Setpoint
The Remote Control Center is also designed to enable the user to obtain chiller/condensing unit printouts directly from this panel.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reason­able protection against harmful interference when the equipment is operated in a commercial environ­ment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruc­tion manual, may cause harmful interference to radio communica­tions. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Page 9
FORM 50.40-OM2

CHILLER/CONDENSING CONTROL PANEL(S)

All communication with the chiller/condensing units will occur over a single RS-485 port. Reference Figure 2 and the Installation instructions.
When the OptiView RCC is first turned on it will initialize by requesting current data and history buffer information from the units connected. After the history buffers are lled, only current data will be continuously requested. Every eight hours the OptiView RCC will re­initialize. If the control panel updates the history buffer (a safety shutdown has occurred), the control panel will send the chiller shutdown data to the OptiView RCC upon receipt of the next valid OptiView RCC transmission. The OptiView RCC will recognize that a safety shutdown has occurred by the Update History Buffer bit being set. If this bit is ever 1, the data dump is assumed to be a shutdown data dump and the OptiView RCC will update its history buffers with the new data and start a printout of the transmitted data through its RS232 port. If the OptiView RCC had been requesting another type of data dump (i.e. a daily schedule dump), the OptiView RCC will repeat its request on the next transmission.
While at the Home Screen, the OptiView RCC will communicate with each unit in order. Once a unit has been selected by entering the Unit Screen or any screen below it, that unit will be polled between every unit in order. This will allow the selected unit to update its information quickly while still maintaining information for the Home Screen.
A command string is used to indicate what data the OptiView RCC is requesting and to modify control data in the chiller control panel. If the chiller/condensing unit is in remote control mode then its Local Set Point, Local Range, Daily Schedule, Holiday, Start
/ Stop Command, and Current / Load Limit can be programmed from the OptiView RCC. The OptiView RCC will send a command string once any of these are modied at the OptiView RCC. If the OptiView RCC sends a Stop command, the chiller/condensing unit will turn off. If the OptiView RCC sends a start command, the chiller/condensing unit will be allowed to run if all the other run requirements of the unit are made.
A chiller/condensing unit that is in remote control mode will use local control (set points and start / stop information), if a valid transmission has not been received for 5 minutes from the OptiView RCC. The remote commands will be used again once a valid new transmission has been processed. The OptiView RCC will display an error message indicating the communications problem when such a condition occurs.
A general status message for each unit is displayed on the Home Screen. The messages displayed will include communications status. Not Initialized will be displayed upon power-up for all units until the OptiView RCC begins to poll and receive data from that unit. Initializing… will be displayed while the OptiView RCC is polling a unit for all current, schedule, and history data the rst time after power-up. Loss of Comms will be displayed after 5 minutes have elapsed with no response from a previously initialized unit. If any of these messages is displayed, the unit’s button will be disabled not allowing it to be selected.
The Control Center Microboard (J12) communicates with this board via a 0/+5VDC serial data communica­tions link. If this communications link does not operate properly, correct Microboard J12 serial port operation can be veried using the Serial Inputs and Outputs diagnostic procedure in the “Service” section of this book.
1
9YORK INTERNATIONAL
Page 10
Installation

SECTION 2 – INSTALLATION

MOUNTING

Mount the Remote Control Center at a level that provides for easy viewing of the color graphic display by all users. Securely mount it at the desired location. The panel may be mounted away from the chiller as far as 4000 ft. (1219 m.) of wiring will allow.

INSTALLATION CHECKLIST

(Reference Fig. 2 for wiring)
A communications cable must connect the OptiView
RCC to the chiller/condenser control panel. This cable should be a three-conductor with foil shield and drain wire, 20 awg or larger wire, 300v, 80 Deg. C, UL Style 2464, UL listed and CSA approved. Three sources are Alpha 5463, Belden 9364, or Quabbin 0220. The cable length (sum of lengths of all cables) must not exceed 4000 ft. (1219 m.). The cable is user supplied.
Obtain ferrite (part number 025-35154-000) from
the cloth bag found in the OptiView RCC and install it as shown on Fig. 2. This must be installed to meet FCC and CE requirements.
Make sure that the Transient Voltage Suppressors are
installed at J12. One is installed from “+” to “GND” and one is installed from “-” to “GND”.
At J12 of the OptiView RCC, red wire on RS485(+),
black wire on RS485(-) and white wire on Ground.
At the OptiView RCC, connect the shield to the
panel.
Use a tie wrap between the J12 connector and the
Ferrite (part number 025-35154-000) to secure the shielded cable to the OptiView RCC. The tie wrap can help prevent the wires from being accidentally pulled out of the J12 connector by someone working in the panel or by the weight of the ferrite.
Install a LAN transient protection module at the
chiller/condenser control panel and connect the cable according to the type of control panel.
Make sure the correct EPROM is installed at the
chiller/condenser control panel(s). See Table 1.
From the Setpoints Screen of the OptiView RCC,
enter the Number of Units Connected (Maximum value allowed is 8).
At the chiller/condenser control panel that uses
a rotary switch to set the ID, use a small screw driver to rotate the rotary switch so that the arrow points at the number that coincides with the Unit’s Identication number (ID#). Unit 1 - Unit 8 coincide to rotary switches 0 - 7. Otherwise program the panel’s ID through keypad entry.
Never skip an ID#. For example, if you have four units then they must be identied from ID#0 - ID#3.
At the chiller/condenser unit’s control panel, select
the type of control mode. Select REMOTE only if remote control is desired. Select LOCAL to only monitor this unit.
From the Comms Screen of the OptiView RCC,
enter the RCC Poll Time. This is how often (time in seconds) to request data. This time should be set long enough to allow for receiving the data.

WIRING

A communications cable must connect the chiller to the remote panel. This cable should be a three-conductor with foil shield and drain wire, 20 awg or larger sized wire, 300v, 80 Deg. C, U.L. Style 2464, U.L. listed and CSA approved. Three sources are Alpha 5463, Belden 9364, or Quabbin 0220. The cable length (sum of lengths of all cables) must not exceed 4000 ft. (1219 m.).
Never run the communication cable in close proximity to any power wiring. For best results, it should be run in dedicated, grounded conduit. See Proper Installation Practices.
YORK INTERNATIONAL10
Page 11
FORM 50.40-OM2
REQUIRED SOFTWARE VERSION OF THE
CHILLER / CONDENSING UNIT EPROMS

TABLE 1 – REQUIRED SOFTWARE VERSION OF THE CHILLER/CONDENSING UNIT EPROMS

UNIT TYPE EPROM PART NO. VERSION YCAL / YCUL w/microboard 031-01314-000 031-02011-001 C.MMC.01.05 YCAL / YCUL w/microboard 031-02050-000 031-02049-001 C.MMC.03.02 YCAS - F 2 Compressors 031-01798-001 C.ACS.09.03 YCAS - F 3 & 4 Compressors 031-01798-002 C.ACS.10.02 YCAR 2 Compressors 031-02013-001 C.RCP.23.02
The software version is printed on a label adhered to the EPROM chip’s surface. A revision level higher than the one listed in the table is acceptable. An example version code is as follows:
C. ACS. 09. XX.
2
Revision Level. Increments 01, 02 etc.
Product Code
YCAS (RCP = YCAR, MMC =YCAL/YCUL)
Commercial
11YORK INTERNATIONAL
Page 12
Tie Wrap (To help keep wires connected)
Ferrite (025-35154-000) (FCC & CE Requirement)
A
A
A
Transient Voltage Suppressor (031-02076-000) (Factory Installed)
Installation

OPTIVIEW REMOTE CONTROL CENTER

FIG. 2 – FIELD WIRING OPTIVIEW RCC PANEL
LD06725
YORK INTERNATIONAL12
Page 13
SHLD
BLK
SHLD
RED
(TOTAL NOT TO EXCEED 8)
WHT
BLK
SHLD
RED
FROM OPTIVIEW RCC
WHT
BLK
RED
WHT
(COMPONENT SIDE UP)
(COMPONENT SIDE DOWN)
(COMPONENT SIDE DOWN)
X
X
CUT PINS AS SHORT AS POSSIBLE
X
X
CUT PINS AS SHORT AS POSSIBLE
FORM 50.40-OM2
2
FIG. 2 – FIELD WIRING OPTIVIEW RCC PANEL (CONT.)
LD06726
13YORK INTERNATIONAL
Page 14
Installation

LAN TRANSIENT INSTALLATION

The properly installed Lan Transient Protection Module, (part number 031-01586-000) will limit the voltage levels seen by the chiller control panel’s RS-485 driver while allowing normal RS-485 network operation under non-transient conditions. For installation of the module refer to Fig. 2 and the specic installation instructions for the microboard.
Unit Microboard 031-01314-000 and 031-02050-001:
Step 1: Label all wires, cables, or components con-
nected to TB1.
Step 2: Carefully loosen each terminal of TB1. Remove all wires, cables, or components. Be extremely careful to not allow them to short together or to the enclosure.
Step 3: Refer to the Module. Replace all wires, cables, or components taken from TB1 into the cor­rect terminals of the Module terminal strip J1 being extremely careful to not allow them to short together or to the enclosure.
Step 4: Carefully tighten all screws on the Module Terminal strip J1.
Step 5: Orient the Module as shown (component side down) and cut the unused pins. Insert the four P1 Module pins into TB1 as shown.
Step 6: Carefully tighten each terminal of TB1. Double check all wiring to the Module before closing up.
Unit Microboard 031-01095-000:
Step 1: Label all wires, cables, or components con-
nected to TB7.
Step 2: Carefully loosen each terminal of TB7. Remove all wires, cables, or components. Be extremely careful to not allow them to short together or to the enclosure.
Step 3: Replace all wires, cables, or components taken from TB7 into the Module terminal strip J1 being extremely careful to not allow them to short together or to the enclosure.
Step 4: Carefully tighten all screws on the Module Terminal strip J1.
Step 5: Orient the Module as shown (component side up) and insert all six P1 Module pins into TB7 as shown.
Step 6: Carefully tighten each terminal of TB7. Double check all wiring to the Module before closing up.

EPROM COMPATIBILITY

Since the concept and design of the OptiView Remote Control Center may have occurred after the original EPROM (software) for the chiller/condenser control panel, the EPROM may need to be replaced with one that allows for OptiView Remote Control Center operation. See Table 1.

TROUBLESHOOTING

From the Home Screen you can determine if you are communicating to the chiller/condensing unit.
If the message Not Initialized.. remains shown on this screen, proper communication between the panels has not occurred and you will need to troubleshoot.
Step 1: If you are trying to communicate with more than one unit, simplify the troubleshooting by isolating the communication to one unit at a time. Remove any wiring to a secondary unit and from the Setpoints Screen of the OptiView RCC, enter one as the Number of Units Connected and at the chiller/condenser control
panel set it’s ID to zero.
Step 2: Check if there is any communication problem occurring on the Diagnostic RCC Comms Screen. See the description of this screen.
You could also check that the RX3 I/O communication activity LED on the OptiView Main Processor Board is blinking as it receives data from the chiller/condensing
unit’s control panel. A steady lit RX3 LED is a sign of improper wiring. If the RX3 LED is not blinking check the wiring and the installation of the Lan Transient Protection Module. If everything is properly connected
replace the 485 driver on the chiller/condenser
microboard (part number 031-02074-000).

SAFETY

It is recommended that all maintenance and service repair work be performed by experienced personnel. There must be recognition of the potential hazards that can exist. Those hazards may include (but are not limited to):
YORK INTERNATIONAL14
Page 15
FORM 50.40-OM2
There can be electrical circuitry that presents an electrocution hazard. Be sure that the sources of all power supplies have been properly isolated and secured before attempting any service related activities.
External wiring, unless specied as an optional connection in the manu­facturer’s product line, is not to be connected inside the OptiView Remote Control Center cabinet. Devices such as relays, switches, transducers and controls may not be installed inside the OptiView Remote Control Center.
No external wiring is allowed to be run through the OptiView Remote Control Center. All wiring must be in accordance with YORK’s published specications and must be performed only by qualified YORK personnel. YORK will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this will void the manufacturer’s warranty and cause serious damage to property or injury to persons.

PROPER INSTALLATION PRACTICES

Earlier relay systems were virtually immune to radio frequency interference (RFI), electromagnetic interfer­ence (EMI), and ground loop currents. Installation consisted of hooking up the point-to-point wiring and sizing the wire properly.
In an electronic system, improper installation will cause problems that outweigh the benets of electronic control. Electronic equipment is susceptible to RFI, EMI, and ground loop currents which can cause equip­ment shutdowns, processor memory and program loss, erratic behavior, and false readings. Manufacturers of industrial electronic equipment take into consideration the effects of RFI, EMI, and ground loop currents and incorporate protection of the electronics in their designs. These manufacturers require that certain installation precautions be taken to protect the electronics from these effects. All electronic equipment must be viewed
as sensitive instrumentation and therefore requires careful attention to proper installation procedures.
There are a few basics, that if followed, will result in a trouble-free installation. The National Electric Code (N.E.C.) is a guideline for safe wiring practices, but it does not deal with procedures used for electronic control installation. Use the following procedures for electronic equipment installation. These procedures are to be used in conjunction with the N.E.C.
Wire Sizing
Size supply wires one size larger than required for amperage draw to reduce instantaneous voltage dips caused by large loads such as heaters, contactors and solenoids. Sudden dips in voltage can cause the processor to momentarily malfunction or cause a complete reset of the control system. If the wire is loaded to its maximum capacity, the voltage dips are much larger, and the potential for a malfunction is very high. If the wire is sized one size larger than required, the voltage dips are smaller than in a fully loaded supply wire, and the potential for malfunction is much lower.
The NEC code requires specic wire sizes to be used based on current draw. An example would be to use #14 gauge wire for circuits up to 15 amp or #12 gauge wire for circuits of up to 20 amp. Therefore, when connecting the power feed circuit to an electronic industrial control, use #12 gauge wire for a maximum current draw of 15 amp and #10 wire for a maximum current draw of 20 amp.
Voltage Source (Figure 3)
Selecting the voltage source is extremely important for proper operation of electronic equipment in an industrial environment. Standard procedure for electronic instrumentation is to provide a “clean” separate source voltage in order to prevent EMI, from other equipment in the plant, from interfering with the operation of the electronic equipment. Connecting electronic equipment to a breaker panel (also known as lighting panels and fuse panels) subjects the electronic equipment to noise generated by other devices con­nected to the breaker panel. This noise is known as electromagnetic interference (EMI). EMI ows on the wires that are common to a circuit. EMI cannot travel easily through transformers and therefore can be isolated from selected circuits. Use a control transformer to isolate the electronic control panel from other equipment in the plant that generate EMI.
2
15YORK INTERNATIONAL
Page 16
Installation
equipment in the plant on the same circuits will ground themselves to the ground stake causing large ground ow at the electronic equipment.
LD06728
LD06727
FIG. 3 – CONTROL INSTALLATION
Grounding
Grounding is the most important factor for successful operation. Electronic equipment reacts to very small currents and must have a good ground in order to operate properly. The NEC states that control equipment may be grounded by using the rigid conduit as a conductor. This is not acceptable for electronic control equipment. Conduit is a poor conductor compared to a copper wire. Copper grounds are required for proper operation.
Ground Wire Size (Figure 4)
The ground wire must be the same size as the supply wires or one size smaller as a minimum. The three phase power brought into the plant must also have a ground wire, making a total of four wires. In many installations that are having electronic control problems, this essential wire is usually missing. A good ground circuit must be continuous from the plant source transformer to the electronic control panel for proper operation. Driving a ground stake at the electronic control will cause additional problems since other
FIG 4 – GROUNDING
Wiring Practices (Figure 5)
Do not mix wires of different voltages in conduit. For an example refer to Figure 5. The motor voltage is 480 volts and the panel control power is 120 volts. The 480 volt circuit must be run from the motor starter to the motor in its own conduit. The 120 volt circuit must be run from the motor starter control transformer to the control panel in its own separate conduit. If the two circuits are run in the same conduit, transients on the 480 volt circuit will be inducted into the 120 volt circuit causing functional problems with the electronic control. Dividers must be used in wire way systems (conduit trays) to separate unlike voltages. The same rule applies for 120 volt wires and 220 volt wires. Also, never run low voltage wires in the same conduit with 120 volt wires.
Never run any wires through an electronic control panel that do not relate to the function of the panel. Electronic control panels should never be used as a junction box. These wires may be carrying large
transients that will interfere with the operation of the control.
When running conduit to an electronic control panel, note that the access holes (knockouts) are strategically placed so that the eld wiring does not interfere with the electronics in the panel. Never allow eld wiring to
come in close proximity with the controller boards since this will almost always cause problems.
YORK INTERNATIONAL16
Page 17
LD06738
FIG. 5 – SEPARATE CONDUIT INSTALLATION
Do not drill a control panel to locate conduit con­nections. Drilling can cause metal chips to land in the
electronics and create a short circuit. If you must drill the panel, take the following precautions:
1. Call the panel manufacturer, if possible, before drilling the panel to be sure you are entering the panel at the right place.
2. Cover the electronics with plastic. Tape the plastic to the board with masking or electrical tape.
3. Place masking tape or duct tape on the inside of the panel at the point of drill bit entry.
FORM 50.40-OM2
Never run refrigerant, water or brine tubing inside an electronic control panel. A leak could damage or in
some cases totally destroy the electronics.
If the electronic control panel has a starter built into the same panel, be sure to run the higher voltage wires where indicated by the manufacturer. EMI
from the wires can interfere with the electronics if run too close to the circuitry.
Never daisy-chain or parallel-connect power or ground wires to electronic control panels. Each
electronic control panel must have its own supply wires back to the power source. Multiple electronic control panels on the same power wires create current surges in the supply wires which can cause controller malfunctions. Daisy-chaining ground wires allows ground loop currents to ow between electronic control panels which also causes malfunctions. (See Figure 6)
It is very important to read the installation instructions thoroughly before beginning the project. Make sure you have drawings and instructions with your equipment. If not, call the manufacturer and have them send you the proper instructions. Following correct wiring procedures will ensure proper installation of your electronic equipment.
2
4. Remove all of the remaining chips from the panel before removing the protective plastic.
When routing conduit to the top of an electronic control panel, condensation must be taken into consideration. Water can condense in the conduit and run into the panel causing catastrophic failure. Route the conduit to the sides or bottom of the panel and use a conduit drain. If the conduit must be routed to the top of the panel, use a sealable conduit tting which is poured with a sealer after the wires have been pulled, terminated and the control functions have been checked. A conduit
entering the top of the enclosure must have an “O” ring-type tting between the conduit and the enclosure, so that if water gets on top of the enclosure,
it cannot run in between the conduit and the enclosure. This is extremely important in outdoor applications.
Never add relays, starters, timers, transformers, etc. inside an electronic control panel without rst contacting the manufacturer. Contact arcing and
EMI emitted from these devices can interfere with the electronics. If you need to add these devices contact the manufacturer for the proper device types and placement.
LD06739
LD06740
FIG. 6 – POWER & GROUND WIRE CONNECTIONS
17YORK INTERNATIONAL
Page 18
Operation
SECTION 3 – OPERATION
OPTIVIEW REMOTE CONTROL CENTER
FIG. 7
The OptiView Remote Control Center display is highlighted by a full screen graphics display. This display is nested within a standard keypad, and is surrounded by “soft” keys which are redened based on the currently displayed screen. Eight buttons are available on the right side of the panel, and are primarily used for navigation between the system screens. At the base of the display are 5 additional buttons. The area to the right of the keypad is used for data entry with a standard numeric keypad provided for entry of system setpoints and limits.
The Decimal key is used prior to entering decimal values.
A +/- key has also been provided to allow entry of negative values and AM/PM selection during time entry.
00500VIP
In order to accept changes made to the chiller setpoints, the Check key is provided as a universal ‘Enter’ key or ‘Accept’’ symbol.
In order to reject entry of a setpoint or dismiss an entry form, the ‘X’ key is provided as a universal ‘Cancel’ symbol.
Cursor Arrow keys are pro­vided to allow movement on screens which contain a large amount of entry data. In addi­tion, these keys can be used to scroll through history and event logs.
YORK INTERNATIONAL18
Page 19

SCREEN DESCRIPTIONS AND USAGE

FORM 50.40-OM2

OVERVIEW

The new graphical display on each control panel allows a wide variety of information to be presented to the user. Each screen description in this document will begin with a section entitled Overview which will describe the graphical elements on the screen and give a short summary of the functions available. Each element on the screen will then be categorized into three distinct groups: Display Only, Programmable, and Navigation. Below is a short description of what types of information are included in these groups.

DISPLAY ONLY

Values in this group are read-only parameters of information about chiller operation. This type of information may be represented by a numerical value, a text string, or an LED image. For numerical values, if the monitored parameter is above the normal operating range, the high limit value will be displayed along with the ‘>’ symbol; if it is below the normal operating range, the low limit value will be displayed along with the ‘<’ symbol. In some cases, the value may be rendered invalid by other conditions and the display will use X’s to indicate this.

PROGRAMMABLE

Values in this group are available for change by the user if the chiller/condensing unit is in remote mode. If there are no values that can be changed then “None” is shown.
Setpoint / Change Schedule
On screens containing programmable setpoints, a key with one of these labels will be visible. This key allows the user to modify setpoints on that screen.
Setpoints
1. Press the desired setpoint key. A dialog box appears displaying the present value, the upper and lower limits of the programmable range, and the default value.
2. If the dialog box begins with the word “ENTER”, use the numeric keys to enter the desired value. Leading zeroes are not necessary. If a decimal point is necessary, press the ‘•’ key (i.e. 45.0).
Pressing the key, sets the entry value to the
default for that setpoint. Pressing the key, clears the present entry. The ◄ key is a backspace key and causes the entry point to move back one space.
If the dialog box begins with “SELECT”, use the
and ► keys to select the desired value.
If the previously dened setpoint is desired, press
the ‘X’ (Cancel) key to dismiss the dialog box.
3. Press the ‘ü’ (Enter) key.
If the value is within range, it is accepted and the
dialog box disappears. The chiller will begin to operate based on the new programmed value. If out of range, the value will not be accepted and the user is prompted to try again.
Manual Controls
So m e keys are used to perform manual control functions. These may initiate/terminate processes such as a report.
Free Cursor
On screens containing many setpoints, a specic “soft” key may not be assigned to each setpoint value. A soft key will be assigned to enable the cursor arrow keys below the numeric keypad which are used to “highlight” the desired setpoint eld. At this point, the ‘ü’ key is pressed to bring up a dialog prompting the user to enter a new setpoint value. The ‘X’ key cancels cursor mode. (See “Change Schedule” from the Setpoints Screen for an example.)
3
Setpoint values are used to control chillers/condensing units and other devices connected to the units. Setpoints can fall into several categories. They could be numeric values (such as 45.0°F for the Leaving Chilled Liquid Temperature), or they could Enable/Yes or Disable/No a feature or function.
Regardless of which setpoint is being programmed, the following procedure applies:

NAVIGATION

In order to maximize the amount of values which the panel can display to the user, and in order to place those values in context, multiple screens have been designed to describe each unit’s operation. In order to move from one screen to the next, navigation keys have been dened. These keys allow the user to either
19YORK INTERNATIONAL
Page 20
Operation
move “forward” to a sub-screen of the present screen, or move “backward” to the previous screen. Except for the Home Screen display, the upper-right “soft” key will always return the user to the Home Screen. Navigating with “soft” keys is as simple as pressing the key next to the label containing the name of the desired screen. The system will immediately refresh the display with the graphics for that screen. Following is a layout of all the screens and how they are connected.
Home (page 22)
Unit Data (page 24)
System Data (page 29)
Individual System (page 32)
Hours/Starts (page 34)
Options (page 36)
Trending (page 38)
Trend Setup (page 40)
Setpoints (page 44)
History (page 47)
History Details (page 48)
RCC Setpoints (page 49)
RCC Setup (page 50)
Comms (page 52)
Printer (page 53)
Diagnostics (page 54)
Diagnostics (I/O) (page 55)
Diag. (RCC Comms) (page 56)
FIG. 8 – SCREEN NAVIGATION LAYOUT
This section of the manual will describe each screen in the order they are accessed as shown in this screen navigation layout.
YORK INTERNATIONAL20
Page 21
FORM 50.40-OM2
This page intentionally left blank to maintain formatting
3
21YORK INTERNATIONAL
Page 22
Operation

HOME SCREEN

FIG. 9 – HOME SCREEN - EXAMPLE
OVERVIEW
When the OptiView Remote Control Center is powered on, the above default display appears. This screen gives a general overview of the operating status of each unit connected to the OptiView Remote Control Center. The data and control of an individual unit is accessed from the Home Screen display. Fig. 9 is an example that shows eight units were programmed.
DISPLAY ONLY
Unit Control Temperature
Displays the temperature of what the unit is using for control such as leaving chilled liquid temperature. This is not shown if suction pressure is being used for control.
Unit Type
Displays the type of chiller the unit is.
Unit Status
Displays a general status message for the unit. The general status message will include communications status, running status, and fault status, etc. Following is a complete listing of the general status messages:
00499VIPC
this message is displayed, the unit’s button will be disabled, not allowing it to be selected.
Initializing… will be displayed while the OptiView
Remote Control Center is polling a unit for all current, schedule, and history data the rst time after power-up. While this message is displayed, the unit’s button will be disabled not allowing it to be selected.
Loss of Comms will be displayed after 5 minutes
have elapsed with no response from a previously initialized unit. While this message is displayed, the unit’s button will be disabled not allowing it to be selected.
Running will be displayed when at least 1 system is
running on a unit with no faults on any system. This message will be displayed even if the chiller is in any kind of limiting as long as there are no faults present. While this message is displayed, the unit’s button will be enabled allowing it to be selected.
Not Running will be displayed when no systems
on the unit are running for a non-fault reason but can run when demand requires. This would be for the No Cool Load state. While this message is displayed, the unit’s button will be enabled allowing it to be selected.
Not Initialized will be displayed upon power-up for
all units until the OptiView Remote Control Center begins to poll and receive data from that unit. While
Faulted will be displayed when no systems on
the unit are running and there is a fault on one or more systems or a unit fault. While this message
YORK INTERNATIONAL22
Page 23
FORM 50.40-OM2
is displayed, the unit’s button will be enabled allowing it to be selected.
Running / Faulted will be displayed when at least
one system on the unit is running and at least one system is faulted. While this message is displayed, the unit’s button will be enabled allowing it to be selected.
Cannot Run will be displayed for any non-fault
condition preventing the entire chiller from run­ning. This would include such things as the daily schedule, unit switch, all system switches, run perm, etc. While this message is displayed, the unit’s button will be enabled allowing it to be selected.
Unit Run Indicator (LED) Is ON when the unit is running.
Average Ambient Temperature
Displays the average Ambient Air Temperature of all the units connected.
PROGRAMMABLE
None
NAVIGATION
Unit #
A detailed view of data relevant to the specied (#) unit. If the “Not Initialized” status message is displayed, the unit’s button will be disabled, not allowing it to be selected.
Setpoints
This screen provides the gateway to many of the OptiView Remote Control Center’s general setup parameters such as Date/Time, Comm Setup, Printer Setup, etc.
3
23YORK INTERNATIONAL
Page 24
Operation

UNIT SCREEN - EXAMPLES

FIG. 10A – YCAL CHILLER
00569VIPC
FIG. 10B – YCAR CHILLER
00570VIPC
YORK INTERNATIONAL24
Page 25
UNIT SCREEN - EXAMPLES
FORM 50.40-OM2
FIG. 10C – YCAS CHILLER
3
00571VIPC
FIG. 10D – YCUL CONDENSING UNIT
00572VIPC
25YORK INTERNATIONAL
Page 26
UNIT SCREEN - EXAMPLES
FIG. 10E – YCWS CHILLER
00573VIPC
YORK INTERNATIONAL26
Page 27

UNIT SCREEN

FORM 50.40-OM2
OVERVIEW
This screen is accessed from the Home Screen. The primary values of the chiller or condensing unit which must be monitored and controlled are shown on this screen. The data available depends on the type of unit. This screen display depicts a visual representation of the unit itself. Animation indicates chilled liquid ow and condenser fans running.
DISPLAY ONLY
Systems Statuses
Displays the individual refrigerant systems operational statuses. The messages displayed include running status, cooling demand, fault status, external cycling device status, load limiting, and anti-recycle timer status. The status message that is displayed on the microprocessor is represented here.
System Run (LED)
Is ON when the individual refrigerant systems compres- sor is running. If any of these are ON, the fans will be animated to show that they are running.
Slide Valve Step (If Screw)
Displays the individual refrigerant systems slide valve step.
Load Stage (If Recip)
Indicates the number of solenoids on the compressor of a YCAR unit that are de-energized and loaded.
Return Chilled Liquid Temperature
Displays the temperature of the liquid as it enters the evaporator.
Discharge Air Temperature
Displays the discharge air temperature leaving the evaporator when the condensing unit is programmed for Discharge Air control.
Systems Suction Pressure
Displays the suction pressure for each individual system on a condensing unit when the unit was programmed for Suction Pressure control.
Ambient Temperature
Displays the outdoor Ambient Air Temperature.
PROGRAMMABLE
Print
Init i a t e s a printout of current system operating parameters for the currently selected unit.
Cancel Print
Terminates the printing in process. This key is only visible while printing is in process.
NAVIGATION
Home
Causes an instant return to the Home Screen.
Number Of Compressors Running (If a system has more than one)
Displays how many compressors are running on the unit.
System Run Time
Displays the individual refrigerant systems logged run time since the last compressor start, in days (Days), hours (Hr), minutes (Min) or seconds (Sec).
Lead System
This message indicates which system is in the lead.
Evaporator Pump Contact (LED)
Is ON when the evaporator pump signal from the microprocessor is on. If this is ON, the chilled liquid will be animated to show that it is owing.
Evaporator Heater (LED) Is ON when the evaporator heater signal from the
microprocessor is on.
Leaving Chilled Liquid Temperature
Displays the temperature of the liquid as it leaves the evaporator.
System Data Used to provide additional system information.
Hours/Starts
This screen shows the cumulative operating hours and start count of each compressor.
Options
Used to provide information of the options that were programmed at the Unit Control Panel.
Trending
This screen provides the user a view of trending data on selected parameters of this chiller/condensing unit.
Setpoints
This screen provides a single location to program the unit setpoints for the selected unit.
History
This screen provides access to a snapshot of system data at each of the last 4-6 shutdown conditions.
27YORK INTERNATIONAL
Page 28
Operation
This page intentionally left blank.
YORK INTERNATIONAL28
Page 29

SYSTEMS SCREEN - EXAMPLES

FORM 50.40-OM2
FIG. 11A – YCAL CHILLER
3
00505VIPC
FIG. 11B – YCAR CHILLER
00506VIPC
29YORK INTERNATIONAL
Page 30
Operation
SYSTEMS SCREEN - EXAMPLES
FIG. 11C – YCAS CHILLER
00507VIPC
FIG. 11D – YCUL CONDENSING UNIT
00508VIPC
Page 31

SYSTEMS SCREEN

OVERVIEW
This screen is accessed from the Unit Screen. A chiller can consist of separate refrigerant circuits. Each refrigerant circuit is referred to as a system. This screen shows system specic information for each of the unit’s refrigerant systems. This information can vary according to the type of chiller. Reference the chiller’s Installation, Operation, Maintenance Manual (IOM) for details.
DISPLAY ONLY
System Status
Displays this refrigerant systems operational status. The messages displayed include running status, cooling demand, fault status, external cycling device status, load limiting, and antirecycle timer status. The status message that is displayed on the Unit’s microprocessor is represented here.
System Run (LED)
Displays this refrigerant systems operational status. Is
ON when the system is running.
Locked Out (LED)
Is ON when a system is locked out on a fault requiring a manual reset at the chiller or condenser unit micro panel.
System Run Time
Displays the amount of time the system has run.
Compressors Running (If more than one compressor per circuit)
Indicates the number of compressors running
Load Limit Stage
Indicates which stage of Load Limiting a unit is in.
Load Stage
Indicates the number of solenoids on the compressor of a YCAR unit that are de-energized and loaded.
Condenser Fan Stage
Displays the stage of condenser fan operation on the system.
Cooler Inlet Refrigerant temperature (Only if in R-407c mode)
Displays the refrigerant temperature at the inlet of the cooler.
Liquid Line Solenoid (LED)
Is ON when the Liquid Line Solenoid Valve is energized/ open.
Economizer Solenoid (LED)
Is ON when the economizer Thermal Expansion Valve Solenoid is energized/open.
Oil Cooling Solenoid (LED)
Is ON when the Oil Cooling Solenoid Valve is energized/ open.
3
Temperatures and pressures are either measured directly by transducers and temperature sensors, or computed from these measurements. Depending on the type of chiller, the following temperatures and pressures could be displayed:
• Discharge Pressure • Oil Pressure
• Suction Pressure • Oil Temperature
• Discharge Temperature • Suction Superheat
• Saturated Discharge Temperature
• Discharge Superheat
• Suction Temperature
• Saturated Suction Temperature
Motor Current (%FLA)
This displays the motor current of the system in percent of full load amps.
Slide Valve Step (If screw)
This indicates the compressor slide valve step.
Compressor Heater (LED) Is ON when the compressor heater is on.
Hot Gas Bypass (LED) Is ON when the hot gas bypass valve is open.
PROGRAMMABLE
None
NAVIGATION
Home
Causes an instant return to the Home Screen.
Unit Data
Causes an instant return to the Unit Screen of the selected unit.
System #
A detailed view of the specied (#) system information.
Page 32
Operation

INDIVIDUAL SYSTEM SCREEN

FIG. 12A – YCAS CHILLER
00509VIPC
FIG. 12B – YCAR CHILLER
00510VIPC
YORK INTERNATIONAL32
Page 33
FORM 50.40-OM2
OVERVIEW
This screen is accessible from the SYSTEM screen when there is much data to view about an individual system. It displays data only from the selected system. Reference the chiller’s Installation, Operation, Main­tenance Manual (IOM) for details about the data. Depending on the type of chiller, the following data might be displayed:
DISPLAY ONLY
The following system information is displayed at the top of the screen: Locked Out (LED)s
System Run Time System Run (LED) Liquid Line Solenoid (LED)
The following discharge readings are grouped together and displayed:
Discharge Pressure Saturated Discharge Temperature Discharge Temperature Discharge Superheat
The following miscellaneous readings are grouped together and displayed:
Motor Current (%FLA) Slide Valve Step or Load Stage Pressure Ratio Ambient Temperature
The following miscellaneous information is displayed separately:
Economizer Solenoid (LED) Hot Gas Bypass Solenoid (LED) Oil Cooling Solenoid (LED) Condenser Fan Stage
PROGRAMMABLE
None
3
NAVIGATION
Home
Causes an instant return to the Home Screen.
Unit Data
Causes an instant return to the Unit Screen.
The following suction readings are grouped together and displayed:
Suction Pressure Saturated Suction Temperature Suction Temperature Suction Superheat
The following oil readings are grouped together and displayed:
Oil Pressure Low Differential Oil Pressure High Differential Oil Pressure Oil Temperature
System Data
Causes an instant return to the System Screen.
33YORK INTERNATIONAL
Page 34
Operation

HOURS AND STARTS SCREEN

FIG. 13A – YCAL CHILLER
00511VIPC
FIG. 13B – YCAS CHILLER
00512VIPC
YORK INTERNATIONAL34
Page 35
FORM 50.40-OM2
OVERVIEW
This screen, accessed from the UNIT screen, displays the total operating hours and the total number of starts for all systems on the unit.
DISPLAY ONLY
Total Starts
Displays the number of times the compressor has been started.
Operating Hours
Displays the number of hours the compressor has run.
PROGRAMMABLE
None
NAVIGATION
Home
Causes an instant return to the Home Screen.
Unit Data
Causes an instant return to the Unit Screen.
3
35YORK INTERNATIONAL
Page 36
Operation

OPTIONS SCREEN

FIG. 14A – YCAL CHILLER
00513VIPC
FIG. 14B – YCAS CHILLER / YCAR CHILLER
00514VIPC
YORK INTERNATIONAL36
Page 37
FORM 50.40-OM2
OVERVIEW
This screen, accessed from the UNIT screen, displays all the dip switch settings and other programmable options at the chiller micro panel. These items can only be changed at the chiller micro panel and not at the OptiView Control Center. Depending on the type of chiller, the following data might be displayed:
DISPLAY ONLY
Units Display Mode
The units selected at the OptiView Remote Control Center, either Imperial or SI, is displayed. In Imperial Units temperatures will be in °F and pressures will be in PSIG or PSID. In SI units temperatures will be in °C and pressures will be in BARG or BARD.
The values at the OptiView Remote Control Center will be displayed in the units that are selected on it’s Setpoints screen regardless of what is programmed at the chiller/condensing unit.
Language Display Mode
The language selected at the chiller micro panel (i.e.
English) is displayed.
Lead/Lag Control Mode
The Lead/Lag control at the chiller micro panel is displayed, either Automatic or Manual. This control is used to select which compressor starts. See the unit’s Installation, Operation and Maintenance Manual for a description.
Fan Control Mode
The fan control at the unit’s micro panel is displayed, either Discharge Pressure or Ambient and Discharge
Pressure.
Unit Control Mode
What the chiller/condensing unit control is based on is displayed, either Leaving Liquid, Return Liquid,
Suction Pressure, or Discharge Air Temperature.
Unit Software Version
The software version of the EPROMS at the chiller/ condensing unit’s micro panel .
3
Refrigerant Type
The refrigerant, either R-407C or R-22, selected at the chiller micro panel is displayed.
Chilled Liquid Type
The cooling mode, either Water or Glycol, selected at the chiller micro panel is displayed.
Ambient Control Mode
The ambient mode, either Standard or Low Ambient, selected at the chiller micro panel is displayed.
Local/Remote Control Mode
The control mode selected at the chiller micro panel, either Local or Remote, is displayed.
PROGRAMMABLE
None
NAVIGATION
Home
Causes an instant return to the Home Screen.
Unit Data
Causes an instant return to the Unit Screen.
37YORK INTERNATIONAL
Page 38
Operation

TRENDING SCREEN

FIG. 15 TRENDING
OVERVIEW
This screen is accessed from the UNIT screen. As many as six Operator selected parameters can be plotted in an X/Y graph format. The X-Axis is scaled per the selected Data Collection Interval and displayed in a time of day or elapsed time format, as selected with the X-axis toggle key. The Y-Axis is scaled for each parameter per the selected minimum and maximum value for each parameter. Analog parameters are scaled in pressure, temperature, volts, amps, hertz or time. Digital on/off parameters are scaled as zero (off) and one (on). Only one Y-Axis label is displayed at a time. The Y-Axis Toggle Key is used to toggle the Y-Axis labels through the different parameters. The Y-Axis label that is being displayed is identied at the top of the graph. All parameters are displayed simultaneously. For identication, each plotted parameter and associated Y-Axis labeling is color coordinated.
The parameters are sampled at the selected Data Collection Interval and plotted using 450 data points across the X-Axis. If the actual value of the sampled parameter is less than the Y-Axis label minimum for that parameter, the value will be plotted at the minimum value. Similarly, if the actual value is greater than the Y-Axis label maximum for that parameter, the value will be plotted at the maximum value.
00574VIPC
There are two types of charts that can be created: ONE SCREEN or CONTINUOUS. When the plotting has reached the end of the X-Axis, one of the following will occur, depending on which is selected: If ONE SCREEN has been selected, the trending stops and the data is frozen. If CONTINUOUS has been selected, the oldest data is dropped from the left-hand side of the graph at the next Data Collection Interval. Thereafter, the oldest data is dropped from left-hand side of the graph at each Data Collection Interval.
Only parameters from the selected Unit are trended. The same parameters that have been selected for a Unit, will be selected by default for the next selected Unit. When on the Home screen, a Unit is not selected and any trending is stopped. Trending is also stopped if a power failure occurs while it is running. After trending is stopped, the last screen of data that was collected will be displayed on the trending screen and the START key must be pressed to initiate a new trend screen.
DISPLAY ONLY
This screen allows the user to view the graphical trending of the selected parameters and is also a gateway to the graph setup screens.
YORK INTERNATIONAL38
Page 39
FORM 50.40-OM2
A red screen with the words “TREND MAX MUST BE > TREND MIN” will appear if the Y-Axis minimum has been programmed to a value that is greater than the Y-Axis maximum for any parameter. If this appears, proceed to the Trend Setup Screen to
change the values.
PROGRAMMABLE
Start
Pressing this key clears the graph, starts a new graph and begins the trending. The trending will continue until the STOP key is pressed, the Home screen is displayed, or a power failure occurs. This key is only available if trending is stopped.
Stop
Pressing this key stops the trending. The trend data is frozen on the display until another graph is started with the START key. The Stop key is only available if trending is running.
X-Axis
This key toggles the X-Axis labels of the graph. Each key press alternates the scaling between time of day and elapsed time. The Time of Day scaling is in 24-hour format. The Elapsed Time scaling is the time elapsed since the START key was pressed, starting the trending.
NAVIGATION
Home
Causes a return to the Home Screen.
Unit Data
Causes a return to the Unit Screen.
Trend Setup
Only displayed if the trending is stopped. Causes a jump to a sub-screen for conguring the trending display.
3
Y-Axis
This key toggles the Y-Axis labels of the graph. Each key press changes the label to another of the selected parameters.
39YORK INTERNATIONAL
Page 40
Operation

TREND SETUP SCREEN

FIG. 16 TREND SETUP
OVERVIEW
This screen is accessed from the Trending screen. This screen is used to congure the trending screen. The parameters to be trended are selected from the Common Slots Screen or Common Slots Master list and entered as Slot Numbers for Data Points 1 through
6. The Y-Axis minimum and maximum values for each parameter are entered as Data Point Min and Data Point Max for Data Points 1 through 6. The interval at which all the parameters are sampled is selected as the Data Collection Interval.
DISPLAY ONLY
None
PROGRAMMABLE
Chart Type
Selects either CONTINUOUS or ONE SCREEN type of graph.
Collection Interval
Selects the interval at which the parameters are sampled. There are 450 data points displayed across the X-Axis of the graph. Each point represents the instantaneous value of the parameter. The user selects the time interval between these points. This is called the DATA
00575VIPC
COLLECTION INTERVAL, or the interval at which the parameter is sampled. This interval is programmable over the range of 1 second to 3600 seconds (1 hour), in one second increments. The selected interval not only determines the sample interval, but also the full screen time display. The full screen time display is a result of the selected interval in seconds, multiplied by the 450 data points. For example, if the Data Collection Interval is programmed for 900 seconds, the parameter would be sampled every 900 seconds, with the last 112.5 hours (4.7 days) of data viewable on the screen. Therefore, the selected interval is a compromise between resolution and full screen time display. Select the desired Data Collection Interval as follows:
1. Determine the desired time interval (in seconds), between data samples.
2. Calculate the full screen time display as follows:
450 x Data Collection Interval = full screen
seconds
full screen seconds / 60 = full screen minutes
full screen minutes / 60 = full screen hours
full screen hours / 24 = full screen days
3. Decide if the resultant sample interval and full screen display meet the requirements. If not, select a different sample interval.
YORK INTERNATIONAL40
Page 41
FORM 50.40-OM2
Select
This key is used to enter the slot numbers and the minimum and maximum Y-Axis values of each param­eter to be trended. Pressing this key places a yellow box around Data Point 1 Slot Number. Use the and navigation keys to place the box around the value of Data Points 1 through 6 to be changed. With the desired value selected, press the ‘4’ (Enter) key. A dialog box is displayed permitting data entry.
Data Point Slot # (1-6)
Use the SELECT key as described above and enter the slot number from the Trend Common Slots Screen of the desired parameter to be trended. The selected parameter description will be displayed for the Data Point. Setting this slot number to zero will disable trending for that particular Data Point. Any or all points can be disabled.
Data Point Min (1-6)
Only displayed if the Associated Slot Number is not Zero. This is the minimum value displayed for the Y-Axis. Selecting a parameter for a Data Point sets this to the default value, which is the lowest value allowed for that parameter. It can be changed to a value that provides a more appropriate resolution for the parameter being monitored. To change, use the SELECT key as described above and enter the desired value. The value must always be set to a value less than the Data Point Max. Otherwise, a red graph is displayed on the Trend Screen with the words “TREND MAX MUST BE > TREND MIN”. If the parameter selected for this data point is a digital type (on/off), this value must be set to zero (0). Zero indicates the OFF state.
Data Point Max (1-6)
Only displayed if the associated slot number is not zero. This is the maximum value displayed for the Y-Axis. Selecting a parameter for a Data Point sets this to the default value, which is the highest value allowed for that parameter. It can be changed to a value that provides a more appropriate resolution for the parameter being monitored. To change, use the SELECT key as described above and enter the desired value. The value must always be set to a value greater than the Data Point Min. Otherwise, a red graph is displayed on the Trend Screen with the words “TREND MAX MUST BE > TREND MIN”. There are 20 Y-axis divisions. If a MIN-MAX span is selected that is not evenly divided by 20, the Program will automatically select the next higher MAX value that makes the span evenly divided by 20. For example, if 0.0 is selected as the MIN, and 69.0 as the MAX, the Program will insert
70.0 as the MAX value. If the parameter selected for this data point is a digital type (on/off), this value must be set to one (1). One indicates the on state.
3
NAVIGATION
Home
Causes a return to the Home Screen.
Unit Data
Causes a return to the Unit Screen.
Trending
Causes a return to the Trending Screen.
Slot Numbers
Causes a jump to the Trend Common Slots Screen. The slot numbers of the most commonly monitored parameters are listed on this screen. The parameters are arranged to make it easier to nd the slot number of the desired parameter to plot.
41YORK INTERNATIONAL
Page 42
This page intentionally left blank.
YORK INTERNATIONAL42
Page 43
FORM 50.40-OM2
This page intentionally left blank.
43YORK INTERNATIONAL
Page 44
Operation

SETPOINTS SCREEN - EXAMPLES

FIG. 17A – YCAL CHILLER
00515VIPC
FIG. 17B – YCAS CHILLER
00516VIPC
YORK INTERNATIONAL44
Page 45
FORM 50.40-OM2
FIG. 17C – YCAR CHILLER
00517VIPC
3
45YORK INTERNATIONAL
Page 46
Operation

SETPOINTS SCREEN

OVERVIEW
This screen, accessed from the Unit screen, provides a convenient location for programming the most common setpoints involved in the chiller/condensing unit control. The setpoints depend on the type of unit.
Values on this screen are only pro­grammable if the chiller/condensing unit is in remote control mode. These values are only viewable if the unit is in local mode.
DISPLAY ONLY
None
PROGRAMMABLE
Leaving Chilled Liquid Temperature or Return Chilled Liquid Temperature or Suction Pressure or Discharge Air Temperature Setpoint
This value allows the user to dene the cooling setpoint that is to be maintained by the chiller/condensing unit. See the unit’s Installation, Operation and Maintenance Manual (IOM) for it’s programmable range.
Leaving Chilled Liquid Temperature or Return Chilled Liquid Temperature or Suction Pressure or Discharge Air Temperature - Control Range
This is the maximum allowable positive and negative deviation that is acceptable from setpoint in the system application. See the unit’s Installation, Operation and Maintenance Manual (IOM) for it’s programmable range.
Remote Chiller Run or Remote Unit Run
The chiller/condensing unit can be selected to either Run or Stop . Selecting Stop will command the chiller/condensing unit to shut down. Selecting Run will allow the chiller/condensing unit to turn on.
Current Limit Setpoint
This is the motor current limiting setpoint. The chiller will be limited from loading when the motor current equals or exceeds this value. Typically, for most instal­lations, no limiting is required and the programmed limiting will be set at or above 100%.
Load Limit Setpoint (YCAL Chillers)
Load Limiting can be programmed from 0 to 2. Load Limit 0 = no load limit Load Limit 1 = 50% load limit - 2/4 compressor units. Load Limit 1 = 66% load limit - 3/6 compressor units. Load Limit 2 = 33 % - 3/6 compressor units only.
Change Schedule
The daily schedule is a 1 week schedule and must be programmed for the start and stop time for each week day and a holiday if desired. A box is provided to specify which days are to use the holiday schedule.
Programming the same time for both Start and Stop times will cause the display to enter 00.00 for both times which will cause the chiller to always be allowed to run.
Repeat Monday
The other days can be selected to change to the Monday schedule.
Clear Schedule
In a situation where it is required to run the chiller 24 hours a day, 7 days a week, the Chiller Control panel should rst have its entire Daily Schedule zeroed (00.00) for all Start and Stop times. This puts the chiller in the run mode at all times. The OptiView Remote Control Center may now be programmed with all zeroes (00.00) for all Start and Stop times by pressing the Clear Schedule button. Since the chiller panel is already in the run mode, programming the OptiView Remote Control Center for all zeroes will keep the chiller in this mode indenitely, allowing the chiller to run whenever demand requires.
NAVIGATION
Home
Causes an instant return to the Home Screen.
Unit Data
Causes an instant return to the Unit Screen.
YORK INTERNATIONAL46
Page 47

HISTORY SCREEN

FORM 50.40-OM2
FIG. 18
OVERVIEW
This screen allows the user to browse through the faults. In order to get a more thorough reporting of the system conditions at the time of the recorded shutdown, move to the sub-screen HISTORY DETAILS.
The user may use the Select Fault button to select the history to view. At this point the View Details button is used to jump to a sub-screen containing stored chiller parameters values at the time of the shutdown. Additionally, the Print History button can be used to generate a hard-copy report of the parameter values at the time of the shutdown.
DISPLAY ONLY
Last Faults
This window displays a chronological listing (most recent rst) of the date and time and the description of the last four to six safety shutdowns (depending upon the type of chiller) that occurred while the system was running.
3
00518VIPC
PROGRAMMABLE
Print History
This generates a report listing the status of the chiller parameters at the time of the selected shutdown.
Print All Histories
This generates a report listing the status of the chiller parameters at the time of each of the stored shutdowns.
Cancel Print
Terminates the printing in process. This key is only visible while printing is in process.
NAVIGATION
Home
Causes an instant return to the Home Screen.
Unit Data
Causes an instant return to the Unit Screen.
View Details
Causes a move to a sub-screen containing the value of select chiller parameters at the time of the associated shutdown.
47YORK INTERNATIONAL
Page 48
Operation

HISTORY DETAILS SCREEN

FIG. 19
OVERVIEW
This screen allows the user to see an on-screen printout of all the system parameters at the time of the selected shutdown. Not all screens are shown above. The number of screens required to display all of the data varies according to the type of unit selected.
DISPLAY ONLY
History Printout
This is the on-screen printout of the system param­eters.
PROGRAMMABLE
Page Up
Scroll up in the displayed data (if applicable).
00519VIPC
NAVIGATION
Home
Causes an instant return to the Home Screen.
Unit Data
Causes an instant return to the Unit Screen.
History
Causes a return to the History Screen.
Page Down
Scroll down in the displayed data (if applicable).
YORK INTERNATIONAL48
Page 49

RCC SETPOINTS SCREEN

FORM 50.40-OM2
FIG. 20
OVERVIEW
This screen is accessed from the Home Screen. This screen shows conguration parameters for this OptiView Remote Control Center. This screen also serves as a gateway to more sub-screens for dening general system parameters.
DISPLAY ONLY
None
PROGRAMMABLE
Number of Units Connected
Allows the user to program how many units the Control Center will need to communicate to.
3
00520VIPC
NAVIGATION
Home
Causes an instant return to the Home Screen.
Setup
This screen provides a single location to program the general system setup parameters such as Date/Time. It is also the gateway to many of the general system setup parameters such as Communications, Printer Setup, etc.
49YORK INTERNATIONAL
Page 50
Operation

RCC SETUP SCREEN

FIG. 21
OVERVIEW
Th i s screen is accessed from the RCC Setpoint Screen. This screen shows the general conguration parameters for this OptiView Remote Control Center. It allows programming of the time and date, along with specications as to how the time will be displayed (12 or 24 hour format). This time is used for display purposes on the OptiView Remote Control Center. It is not used to reset individual chiller clocks and has no effect on individual chiller schedules. This screen also serves as a gateway to more sub-screens for dening general RCC system parameters.
DISPLAY ONLY
None
PROGRAMMABLE
00521VIPC
Set Date
Allows the user to specify the present date. When prompted to enter a date value, the user must enter the day, month, and four-digit year (using leading zeroes as necessary). If within range, the value will be accepted. If out of range, the user is prompted for the information again. At this point the user may retry the date entry, or cancel the programming attempt.
Set Time
Allows the user to specify the present time. When prompted to enter a time value, the user must enter the hour and minute desired (using leading zeroes as necessary). If the chiller is presently set to 24-hour mode, the time must be entered in the 24-hour format. Otherwise, the user must also select AM or PM for the entered time. If out of range, the user is prompted for the information again. At this point the user may retry the time entry, or cancel the programming attempt.
Clock (Enabled / Disabled)
Allows the user to enable or disable the real-time clock in order to conserve battery life. The clock will be disabled during manufacturing and must be enabled at system commissioning. In addition, when preparing for prolonged shutdown the clock should once again be disabled.
12/24 Hr
Allows the user to specify the format in which the time will be presented to the user. This setpoint will only affect the display of the time on the OptiView RCC panel and on all reports generated. 12-Hour time format will include the AM and PM modiers and show the range of time between 1:00 and 12:59, while the 24-Hour time format will show the range of time between 0:00 and 23:59.
YORK INTERNATIONAL50
Page 51
FORM 50.40-OM2
Units
Dene the unit system (Imperial or SI) used by the OptiView RCC display. This selection has no effect on the chiller/condensing unit micro panel.
NAVIGATION
Home
Causes an instant return to the Home Screen.
Setpoints
Causes a return to the Setpoints Screen.
Comms
Moves to the sub-screen allowing configuration of system communications.
Printer
Moves to the sub-screen allowing conguration and control of printer functions.
Diagnostics
Moves to the sub-screen allowing limited diagnostic capability while operating.
3
51YORK INTERNATIONAL
Page 52
Operation

COMMS SCREEN

FIG. 22
OVERVIEW
This screen is accessed from the RCC Setup Screen. This screen allows denition of the necessary com­munications parameters. Refer to PRINTER Section of this book for details of the Printer connections and setup.
DISPLAY ONLY
RS-485 Baud Rate 4800
Shows the baud rate at which the panel shall com­municate through the Com3 port to the remote control panel(s). The baud rate of the remote control panel(s) must be set for 4800 in the EPROM. Make sure the correct EPROM is installed at the chiller/condenser control panel(s). See Table 1.
00522VIPC
PROGRAMMABLE
RCC Poll Time (5-30 sec.)
Dene the poll time (how frequently) this panel requests for data from another panel through the Com3 port.
NAVIGATION
Home
Causes an instant return to the Home Screen.
Setup
Return to the Setup Screen.
YORK INTERNATIONAL52
Page 53

PRINTER SCREEN

FORM 50.40-OM2
FIG. 23
OVERVIEW
This screen is accessed from the RCC Setup Screen. This screen allows denition of the necessary com­munications parameters for the printer. Refer to PRINTER section of this book for details of the Printer connections and setup.
DISPLAY ONLY
None.
PROGRAMMABLE
Automatic Printer Logging (Enabled / Disabled)
Enable the printer to begin printing status reports beginning at the programmed start time and recurring at the interval dened above.
3
00523VIPC
Printer Type
Dene the printer type connected to the OptiView RCC.
Printer Baud Rate
Dene the baud rate at which the panel shall com­municate to the printer.
Printer Data Bit(s)
Dene the number of data bits with which the panel shall communicate to the printer.
Printer Parity Bit(s)
Dene the number of parity bits with which the panel shall communicate to the printer.
Printer Stop Bit(s)
Dene the number of stop bits with which the panel shall communicate to the printer.
Log Start Time
Set the time at which scheduled logs will begin.
Log Output Interval
Dene the interval at which logging will occur. We suggest you select a reasonable amount of time so that it is not occurring too much.
Log Unit Selected
Select a unit or all units to logs of.
Cancel Print
Terminates the printing in process. This key is only visible while printing is in process.
NAVIGATION
Home
Causes an instant return to the Home Screen.
Setup
Return to the Setup Screen.
53YORK INTERNATIONAL
Page 54
Operation

DIAGNOSTICS SCREEN

FIG. 24
OVERVIEW
This screen is accessed from the RCC Setup Screen. This screen provides a view of what software is in use and provides access to a screen for troubleshooting analog and digital inputs.
DISPLAY ONLY
Software Versions
The following software versions are displayed:
• RCC - FLASH Memory Card on Microboard
• BIOS - BIOS EPROM on Microboard
• Kernel - Software that is part of FLASH Memory Card
• GUI - Software that is part of FLASH Memory Card
• SIO - Software that is part of FLASH Memory Card
00524VIPC
PROGRAMMABLE
None
NAVIGATION
Home Causes an instant return to the Home Screen.
Setup
Return to the Setup Screen.
I/O
Moves to the sub-screen allowing diagnostics of the analog and digital inputs.
RCC Comms
Moves to the sub-screen allowing diagnostics of communications with the RCC.
YORK INTERNATIONAL54
Page 55

DIAGNOSTICS I/O SCREEN

FORM 50.40-OM2
FIG. 25
OVERVIEW
This screen is accessed from the Diagnostics Screen. This screen provides a view of the analog and digital inputs for troubleshooting .
DISPLAY ONLY
Diagnostics is used to analyze the Analog Inputs at the Microboard. The voltage level of each Analog Input, as interpreted by the Microboard, is displayed. “Counts” is an Analog-to-Digital (A/D) converter value and is for manufacturing and engineering use only.
Diagnostics is also used to analyze the state of each Microboard Program Jumper and Program DIP Switch as interpreted by the Microboard. These are depicted by an LED.
00525VIPC
3
2. If a Program Jumper is present, the applicable LED should be extinguished. If the LED is not extinguished, the Microboard is defective.
3. If a Program Jumper is not present, the applicable LED should be illuminated. If the LED is not illuminated, the Microboard is defective.
4. If a Program Switch (DIP) is in the ON position, the applicable LED should be illuminated. If the LED is not illuminated, the Microboard is defective.
5. If the Program Switch (DIP) is in the OFF position, the applicable LED should be extinguished. If the LED is not extinguished, the Microboard is defective.
6. When all desired tes t s have been per f ormed, press DIAGNOSTICS key to return to MAIN DIAGNOSTICS Screen.
PROGRAMMABLE
PROCEDURE
Digital Inputs:
1. The Digital Inputs are listed on this screen according to a.) Microboard Program Jumpers and Program DIP Switches. Tables 2 and 3 list the functions of the Program Jumpers and Switches.
None
NAVIGATION
Home
Causes an instant return to the Home Screen.
Diagnostics
Causes a return to the previous screen.
55YORK INTERNATIONAL
Page 56
Operation

DIAGNOSTICS RCC COMMS SCREEN

FIG. 26
OVERVIEW
This screen is accessed from the Diagnostics Screen. This screen provides a view of communication for troubleshooting .
Communication between the OptiView RCC and the chiller/condenser control panel(s) should consist of the RCC polling (requesting a response from) each chiller/condenser control panel starting with Unit 1 and continuing to Unit “x”, where “x” is the Number of Units Connected as entered on the RCC Setpoints Screen. Each poll will increment the Poll Count. A reply should be sent back to the RCC from the Unit that was polled within a certain amount of time. If this reply does not happen within this time period the Timeout Count will be incremented. If the reply is returned but contains improper data, then the Bad Csum Count will be incremented. If the reply is successfully received by the RCC then the Reply Count is incremented.
00526VIPC
DISPLAY ONLY
Unit Type
Displays the chiller type, whether it is a “Screw”, “Recip”, or Scroll” and the number of compressors for the “Unit x”, where x is the number of the unit.
Poll Indicator (LED)
Is on when the last noted communication through the Com3 port was to poll a chiller/condenser control panel.
Reply Indicator (LED)
Is on when the last noted communication through the Com3 port was to receive a reply from a chiller/ condenser control panel.
Poll Count
A count of each poll request through the Com3 port to a chiller/condenser control panel.
Good communication is indicated by the Poll Count and the Reply Count keeping close to the same count. A high Timeout Count could imply that the chiller/condenser control panel did not properly receive the request or it did not properly send a response. Check the wiring and the Installation Checklist. A high Bad Csum Count could be indicative of noise being transmitted. This can happen because of improper wiring or grounding.
Reply Count
A count of each reply successfully received through the Com3 port from a chiller/condenser control panel.
Bad Csum Count
A count of each reply received through the Com3 port from a chiller/condenser control panel that had a bad Csum calculation. This indicates that improper data was received.
YORK INTERNATIONAL56
Page 57
FORM 50.40-OM2
Timeout Count
A count of each poll request through the Com3 port to a chiller/condenser control panel that did not get a reply within the timeout period (time to wait for a reply).
PROGRAMMABLE
Clear Counters
Resets all the counts to zero.
NAVIGATION
Home
Causes an instant return to the Home Screen.
Diagnostics
Causes a return to the previous screen.
3
57YORK INTERNATIONAL
Page 58
Operation

DISPLAY MESSAGES

A title bar will be displayed on all screens. This title bar will contain the OptiView Remote Control Center date and time on all RCC screens. This title bar will contain the Chiller/Condensing unit’s date and time on all unit screens. On the Home Screen the message will read “YORK REMOTE CONTROL CENTER”. On all other screens it will contain the unit selected and either the chiller type or will be based on the number of compressors of that unit.
When a unit has been selected the title bar will display a dual message on every screen. The rst message will display the Unit Selected in the format “Unit x”, where x is the number (1 – 8) of the unit selected. The second message will display the chiller type, whether it is a “Screw”, “Recip” or “Scroll” and the number of compressors.
On the Unit Screen and all System Screens the title bar contains another message called a Status. The current status of each unit is displayed in this message. These messages will include running status, cooling demand, fault status, external cycling device status, load limiting and anti-recycle timer status, etc. A System Status message and a Unit Status message are never displayed simultaneously. A single message is displayed for a Unit Status message, while a separate System Status message will display for each system on multi-circuit units.
Status messages fall into the categories of warning, safety, and normal with each of the categories discussed following:
Warning messages are denoted by yellow message
text. A warning message is shown for any special running condition and for all unit warnings. Any kind of load limiting would be an example of a warning message. An incorrect refrigerant programmed warning would also be an example of a warning message.
Safety messages are denoted by red message text.
A safety message is shown for any type of safety shutdown, lock-out, or run inhibit. High discharge pressure would be an example of a safety shutdown message.
Normal messages are denoted by green text.
A normal message is shown for any non-fault normal condition. The compressor running and no cooling load messages would be examples of normal messages.
Note that there are two types of shutdowns. If the chiller shuts down on a SAFETY shutdown, it requires the operator to perform a manual reset at the keypad. A NORMAL shutdown occurs from a properly requested or scheduled shutdown. The event that caused the shutdown is displayed on the Status Line.
STATUS MESSAGES
Status messages will be much like those displayed at the chiller panel. Explanation of these displays will be outlined in the Installation Manual for each specic chiller. Subtle differences may be noted in the exact wording displayed versus the display which is shown on the chiller panel. An example of this is apparent in the anti-recycle and anti-coincidence timers. In the case of these messages, the chiller control panel indicates actual time left on the timers. The OptiView Remote Control Center will only indicate that the timers are “Active”.
The new message “Loss of Communications” indicates that the communications link between the chiller control panel and the OptiView Remote Control Center has been lost. This loss of communications is normally a result of disconnecting the RS-485 communications cable between the two panels or the loss of power to the chiller control panel.
If communications is lost and not re-established, local chiller setpoints will command chiller control after 5 minutes.
In addition to the chiller status messages there are the Optiview Remote Control Center general status messages that are displayed on a single line on the Home Screen for each chiller. See the description of the Home Screen in this manual.
SAFETY SHUTDOWN MESSAGE
“WATCHDOG – SOFTWARE REBOOT”
The Microboard’s software Watchdog initiated a Microprocessor reset because it detected that a portion of the chiller operating Program was not being executed. The result of this reset is a Safety shutdown and re-initialization of the Program. This is generally indicative of a severe electrical power disturbance or impending Microboard Failure. The chiller can be started after the COMPRESSOR switch is placed in the Stop-Reset (O) position.
YORK INTERNATIONAL58
Page 59
OKIDATA MICROLINE 184
FORM 50.40-OM2

SECTION 4 – PRINTERS

23887A
SEIKO DPU-414
4
23889A
WEIGH-TRONIX
00085VIP
FIG. 27 – PRINTERS
59YORK INTERNATIONAL
Page 60

Printers

PRINTERS
A printer can be connected to the OptiView Remote Control Center’s Microboard to print the following reports. The screen from which each report can be generated is listed in parenthesis.
Operating Data - Present system parameters (Unit)
History - System parameters at the time of the last fault while running and last saved faults (History)
The printer can be permanently connected to the Remote Control Center or connected as required to produce a report. If permanently connected, a DATA LOGGING feature can produce a Status report automatically, beginning at an Operator selected start time and occurring at an Operator selected interval thereafter.
The following gures are examples of the different print reports.
• Figure 28 - Operating Data
• Figure 29 - History (Header)
PRINTERS
The following Printers can be used. Printers must be equipped with an RS-232 Serial interface.
Okidata
Models: 182,182 turbo, 184 turbo Dimensions: 14 in. wide x 10.5 in. deep Paper: 8.5 in. wide Type: Dot matrix impact
Weigh-Tronix –
Models: 2600, 1220 Dimensions: 2.3 in. wide x 2.8 in. deep Paper: 2.25 in. wide Type: Dot matrix impact
Seiko –
Model: DPU414-30B (Power supply PW4007-U
I required)
Dimensions: 6.3 in. wide x 6.7 in. deep Paper: 4.4 in. wide Type: Thermal
Purchase: Contact your local YORK Service Ofce
The OptiView Remote Control Center provides the required formatting control codes for the printers above
when the printer is selected on the PRINTER Screen in the instructions below. These codes are transmitted through the serial interface to the printer to provide a proper print format. Different printers require different formatting control codes. Other printers might provide proper operation when connected to the OptiView Remote Control Center. However, the print format may not be correct or as desired. Proceed with caution and use the following guidelines if an unlisted printer is selected:
1. All must be capable of RS-232 Serial communications.
2. Primary differences between printers involve the formatting control codes required by the printer. These codes are sent from the Control Center to the printer. For example, Weigh-Tronix printers require a control code to select 40 column width. This same code is interpreted by the Okidata printer as an instruction to print wide characters. In some instances, a printer will ignore a code it cannot interpret.
3. The OptiView Remote Control Center requires a busy signal from the printer when the printer receive buffer is full. This causes the OptiView Remote Control Center to momentarily terminate data transmission until the printer can accept more data. The busy signal polarity must be asserted low when busy.

PRINTER CONNECTIONS

Connect the printers to the Control Center Microboard as follows. Only one printer can be connected at a time.
• OKIDATA 182, 182 turbo, 184 turbo
Microboard Printer Function
J2-4 pin 3 Tx (data to printer) J2-2 pin 11 DSR (busy signal from printer) J2-9 pin 7 Gnd Cabinet shield
WEIGH-TRONIX
Microboard Printer Function J2-4 pin 2 Tx (data to printer) J2-2 pin 5 DSR (busy signal from printer) J2-9 pin 7 Gnd
Cabinet shield
YORK INTERNATIONAL60
Page 61
FORM 50.40-OM2
• SEIKO
Microboard Printer Function J2-4 pin 3 Tx (data to printer) J2-2 pin 8 DSR (busy signal from printer) J2-9 pin 5 Gnd
Cabinet shield
Hardware required:
Cable – #18 AWG stranded 50ft. maximum length.
Connectors –
- Microboard: None. Strip 1/4" insulation from wire and insert into screw terminal block.
- Printers: Okidata - 25 pin plug DB-25P or equiva­lent; Shell DB-C2-J9 or equivalent. Weigh-Tronix
- Same as Okidata. Cable assembly available from Weigh-Tronix. Seiko - 9-Pin D-type Subminiature (DB-9 pin male).

PRINTER SETUP

The selected printer must be congured as follows. Refer to manual provided by Printer manufacturer with respective Printer.
• OKIDATA 182, 182 turbo, 184 turbo Printer
CONTROL BOARD Switch settings: SW1 - on Unslashed 0 2 - off Unslashed 0 3 - off Unslashed 0 4 - off Form Length 11 in. 5 - on Form Length 11 in. 6 - off Auto Line Feed off 7 - on 8 bit data 8 - off Enable front panel
If equipped with a SUPER SPEED serial Board: SW1-1 - on Odd or even parity 1-2 - on No parity 1-3 - on 8 bit data 1-4 - on Protocol ready/busy 1-5 - on Test select 1-6 - on Print mode 1-7 - off SDD(-) pin 11 1-8 - on SDD(-) pin 11 2-1 - on 1200 Baud* 2-2 - on 1200 Baud* 2-3 - off 1200 Baud* 2-4 - off DSR active
2-5 - on Buffer threshold 32 bytes 2-6 - on Busy signal 200ms 2-7 - on DTR space after power on 2-8 - not used
If equipped with HIGH SPEED serial board: SW1 - off (-) Low when busy 2 - off 1200 Baud* 3 - off 1200 Baud* 4 - on 1200 Baud* 5 - not used 6 - off no parity 7 - off Pin 20 & pin 11 act as busy line
• WEIGH-TRONIX Printer
- IMP-24 Model 2600 SW1 - off 1200 Baud* 2 - on 1200 Baud*
Model 1220
- Congure Menu Baud= 1200 Data Bits = 8 Stop Bits = 1 Hshake = Busy-Line Cols = 32 Invert = No Font = 5 x 8 Mag = None
- Custom Menu Auto Seq = No Zero = 0 Pound sign = # _(Underscore) Busy invert = no Online/ofine = yes Ext Ch Set = no Print ready = yes
Set Clock = not used Reset Seq = not used
• SEIKO
DipSW1-1 = off Input-Serial 1-2 = on Printing speed high 1-3 = on Auto loading - on 1-4 = off Auto LF - off 1-5 = on Setting Command - Enable 1-6 = off Printing density - 100% 1-7 = on Printing density - 100% 1-8 = on Printing, density - 100%
4
61YORK INTERNATIONAL
Page 62
Printers
DipSW 2-1= on Printing Columns - 40 2-2 = on User Font Back-up - on 2-3 = on Character Select - normal 2-4 = off Zero - slash 2-5 = on International character set -
American 2-6 = on International character set -
American 2-7 = on International character set -
American 2-8 = off International character set -
American
DipSW 3-1= on Data length - 8 bits 3-2 = on Parity Setting - no 3-3 = on Parity condition - odd 3-4 = on Busy control - H/W busy 3-5 = on Baud rate select - 1200* 3-6 = off Baud rate select - 1200* 3-7 = on Baud rate select - 1200* 3-8 = off Baud rate select - 1200*
* Settings shown for 1200 Baud. Other Baud rates can be selected. Refer to Printer manufacturer’s manual supplied with Printer.
OPTIVIEW REMOTE
CONTROL CENTER SETUP
Printer Type
Using the PRINTER Screen, the actual Printer type connected to the OptiView Remote Control Center must be entered. Selection determines the control codes that are sent to the Printer. These codes determine such things as lines per inch, character width and general formatting. Available selections are: Okidata, Weigh-Tronix and Seiko.
Automatic Data Logging
If automatic data logging is desired, a Status Report can be automatically printed at a specied interval beginning at a specified time, using the PRINTER Screen. The interval is programmable over the range of 1 minute to 1440 minutes in 1 minute increments. The rst print will occur at the programmed START time and occur at the programmed OUTPUT INTERVAL thereafter. The time remaining until the next print is displayed on the PRINTER Screen.
• Automatic Printer Logging - Enables and disables automatic data logging
• Log Start Time - Enter the time the rst print is desired.
• Log Unit Selected - Select a unit or all units to print logs of.
• Output Interval - Enter the desired interval between prints.
Number of Units Connected
Using the Setpoints Screen, enter the number of chiller units to communicate with. The identication number of the chiller unit which is setup at the unit’s control panel can not exceed this number. The identication number will appear at the top of each report.
Printer Setup
Using the PRINTER Screen, the OptiView Remote Control Center must be congured to transmit data in the same format as the Printer is congured to receive the data. The following values must be entered.
• Baud Rate - Set as desired. Value selected must be the same as Printer conguration above.
• Data Bits - 8
• Parity - None
• Stop Bits - 1
Print
Pressing the Print button from the Unit Screen allows the operator to obtain a printout of current system operating parameters for the currently selected unit. A sample operating data printout for a YCAS chiller is shown following.
YORK INTERNATIONAL62
Page 63
FORM 50.40-OM2
York International Corporation Unit X Status X Comp Screw
Liquid Line Solenoid = On Economizer Solenoid = Off Condenser Fan Stage = 0 Compressor Heater = On
2:04PM 18 JUN 01
System 2 Data
System 1 No Cooling Load System 2 Compressor Running System 3 No Cooling Load System 4 Compressor Running
Options Chilled Liquid Type = Water Ambient Control Mode = Standard Refrigerant Type = R-22
Program Values Current Limit Setpoint = 100 % Local/Remote Control Mode = Remote
Unit Data Leaving Chilled Liquid Temperature = 49.0 °F Return Chilled Liquid Temperature = 58.2 °F Leaving Chilled Liquid Setpoint = 20.0 °F Control Range = 2.0 °F
System Run = On System Run Time = 15 Min Motor Current (%FLA) = 87 % Suction Pressure = 57.2 Psig Discharge Pressure = 233.1 Psig Oil Pressure = 218.0 Psig Suction Temperature = 42.9 °F Discharge Temperature = 145.5 °F Oil Temperature = 102.8 °F Saturated Suction Temp = 31.7 °F Suction Superheat = 11.2 °F Saturated Discharge Temp = 112.1 °F Discharge Superheat = 33.4 °F Slide Valve Step = 70 Cooler Inlet Refrig Temp = 23.6 °F Liquid Line Solenoid = On Economizer Solenoid = On Condenser Fan Stage = 3 Compressor Heater = Off
Ambient Temerature = 74.8 °F Lead System = 2 Evaporator Pump Contact = On Evaporator Heater = Off Software Version = C.ACS.09.03
System 1 Data System Run = Off System Run Time = 0 Min Motor Current (%FLA) = 0 % Suction Pressure = 125.4 Psig Discharge Pressure = 131.3 Psig Oil Pressure = 130.6 Psig Suction Temperature = 68.4 °F Discharge Temperature = 68.8 °F Oil Temperature = 68.8 °F Saturated Suction Temp = 71.8 °F Suction Superheat = 3.4 °F Saturated Discharge Temp = 74.5 °F Discharge Superheat = 6.3 °F
System 3 Data System Run = Off System Run Time = 0 Min Motor Current (%FLA) = 0 % Suction Pressure = 125.4 Psig Discharge Pressure = 131.3 Psig Oil Pressure = 130.6 Psig Suction Temperature = 68.4 °F Discharge Temperature = 68.8 °F Oil Temperature = 68.8 °F Saturated Suction Temp = 71.8 °F Suction Superheat = 3.4 °F Saturated Discharge Temp = 74.5 °F Discharge Superheat = 6.3 °F Slide Valve Step = 0 Cooler Inlet Refrig Temp = 44.6 °F Liquid Line Solenoid = Off Economizer Solenoid = Off Condenser Fan Stage = 0 Compressor Heater = On
Slide Valve Step = 0 Cooler Inlet Refrig Temp = 44.6 °F
4
FIG. 28 – OPERATING DATA PRINTOUT EXAMPLE (YCAS CHILLER)
63YORK INTERNATIONAL
Page 64
Printers
York International Corporation Unit X Status X Comp Screw
2:04PM 18 JUN 01
The history printout is similar to the operational data printout shown previously. The differences are in the header and the schedule information. The daily schedule is not printed for a history print. One example history buffer header printout is shown following. The data part of the printout will be exactly the same as the operating data printout.
System 1 No Cooling Load System 2 Compressor Running System 3 No Cooling Load System 4 Compressor Running
Options Liquid Line Solenoid = On Economizer Solenoid = Off Condenser Fan Stage = 0 Compressor Heater = On
System 2 Data System Run = On System Run Time = 15 Min Motor Current (%FLA) = 87 % Suction Pressure = 57.2 Psig Discharge Pressure = 233.1 Psig Oil Pressure = 218.0 Psig Suction Temperature = 42.9 °F Discharge Temperature = 145.5 °F Oil Temperature = 102.8 °F Saturated Suction Temp = 31.7 °F Suction Superheat = 11.2 °F Saturated Discharge Temp = 112.1 °F Discharge Superheat = 33.4 °F Slide Valve Step = 70
York International Corporation Unit X Safety Shutdown Number X X Comp Screw
2:04PM 18 JUN 01
System 1 High Dsch Press Shutdown System 2 No Faults System 3 No Faults System 4 No Faults
FIG. 29 – HISTORY HEADER PRINTOUT
EXAMPLE (YCAS CHILLER)
FIG. 28 – CONTINUED
YORK INTERNATIONAL64
Page 65
SECTION 5 – SERVICE
INTRODUCTION
FORM 50.40-OM2
This document explains the operation of the printed circuit boards and major components of the OptiView Remote Control Center to a level that allows a Service Technician to troubleshoot and locate the source of a problem.
The overall system architecture is described and illustrated with block diagrams. This describes the general function of each component and provides the system interface and signal ow. The function of each component and signal ow between components must be understood before effective troubleshooting can commence.
The operation of each printed circuit board is described and illustrated with a block diagram that is a simplied representation of board circuitry. The expected voltage level at all inputs and outputs of each board for any operating condition is provided.
Included in this document are procedures that have to be performed at commissioning or during service. They should not be performed by anyone other than a Service Technician. For example, calibration procedures have to be performed or veried at commissioning or when a component is replaced. Since the operating program supplied in each OptiView Remote Control Center is universal to all applications, special setpoints, program jumpers and program switches are required to congure the OptiView Remote Control Center for this locations operating conditions.
A System Commissioning Checklist is provided as reference of items to be performed during control panel commissioning.
Diagnostic Routines allow service analysis of the following functions:
• Display
• Analog inputs
• Dip switches and jumpers
Before beginning any troubleshooting, observe all display messages. The conditions required to produce the message must be clearly understood before proceeding. (If this is not heeded, much time will be wasted). Armed with a knowledge of the overall system architecture and the function of each printed circuit board and signal ow provided by this manual, proceed with the appropriate Wiring Diagram listed above to trace the problem through the system. Use the Diagnostic Routines where appropriate.
5
65YORK INTERNATIONAL
Page 66
Service

SYSTEM ARCHITECTURE

(REFER TO FIG. 28)
The OptiView Remote Control Center (RCC) performs the following functions:
• Displays chiller operating conditions, alarms, shutdown messages and history data.
• Accepts operator-programmed setpoints.
• Provides chiller operating data and status to remote devices via serial communications.
• Allows real-time data and history data to be printed on an optional printer.
The RCC is a microprocessor based control system that receives analog and serial data inputs and controls serial data outputs per instructions in the operating program. A panel mounted display and touch-sensitive keypad permit remote operation.
In some applications, overall system temperatures are sensed by thermistors connected to the Remote Control Center. The output of each thermistor is a DC voltage that is analogous to the temperature it is sensing. Typical output voltage range of both is 0.5 to 4.5VDC. These are analog inputs to the Remote Control Center.
Figure 33 is a Remote Control Center block diagram of the standard components.
The microprocessor and all supporting logic circuits, along with the memory devices containing the operating program, reside on the Microboard. All remote control decisions are made here. In some applications it receives analog inputs from devices. The analog inputs are connected directly to the Microboard.
A front panel-mounted Keypad allows Operator and Service Technician user interface. Membrane keys are used to display chiller and system parameters, enter setpoints and perform chiller and Remote Control Center diagnostics.
A front panel mounted liquid crystal Display allows graphic animated display of the connected chiller units, chiller unit subsystems and system parameters. The chiller and working components of the chiller are displayed, along with chiller operating pressures and temperatures. The Keypad is used to select displays showing increasing levels of detail of chiller working components.
Serial Data is transmitted to and received from devices in RS-232, RS-485 and TX/RX (opto-couple) form.
All OptiView Remote Control Centers contain the following standard components:
• Microboard
• Keypad
• Display
• Power Supply
A self-contained Power Supply supplies the necessary DC voltages for all the components within the Remote Control Center.
Serial data interface to the YORK ISN Building Automation System is through the J12 connector.
YORK INTERNATIONAL66
Page 67
FORM 50.40-OM2
POWER
SUPPLY
MICRO BOARD
KEYPAD
DISPLAY
INTERFACE
BOARD
LIQUID
CRYSTAL
DISPLAY
LAMP
BACKLIGHT
INVERTER
BOARD
LAMP
CONTROL
ROW IN
COLUMN OUT
DISPLAY DATA
+12 / +5 VDC
RS-232 / RS-485 SERIAL DATA
LD06742
5
FIG. 30 – CONTROL CENTER
67YORK INTERNATIONAL
Page 68
Service

MICROBOARD

(REFER TO FIG. 31 - 36)
The Microboard contains the operating software (Program), microprocessor (Micro), and supporting circuits for the Micro.
The Program is a set of instructions to control remote chillers and the display. It also contains the Display messages and screens. It is stored in a memory device called a ash memory card. This is a type of nonvolatile memory that can be read from or written to, but requires the locations to be erased before they are written to. With the exception of a write/read sequence that occurs during the Boot-up process explained below, this device is used primarily as read-only in this application. A write protect switch is located on the left edge of the card as shown in Fig. 32. It must be placed in the “Write Enabled” position in order to allow successful Boot-up. The card is located in socket location U46 (Ref. Fig. 31). It connects to the Board via an Elastomeric connector that is a silicon rubber strip embedded with silver conductors. The Card can be removed from its socket by using the thumb to press down on the socket’s plastic tension spring. The card is installed by inserting it into the socket/holder and pressing on the surface of the Card until it snaps into place. The Memory card is a replaceable component. Refer to the YORK Renewal Parts List. The version of the Memory card is an alphanumeric code that represents the application and revision level. The version is printed on a label adhered to the memory card’s surface. The version code is as follows:
C. RCC. 01. XX.
Revision level. Increments 00, 01 etc.
Product Code for OptiView RCC
Remote Control Center
Commercial
The Micro monitors and controls the chiller by reading and executing the Program instructions in a sequence determined by the Program. Under Program control, the Micro communicates with the chillers via RS-485 serial communications to determine the operating conditions. As operating conditions require, status messages are retrieved and displayed. The Keypad is read as Digital Inputs. When an operator presses a key to request a display, the Micro interprets the request, retrieves the display from the Program and displays it. The Program assembles data in the correct format for transmission
through the Serial Data Ports to the chiller(s) and peripheral devices. The Program also instructs the Micro to respond to requests from peripheral devices for serial data transmissions.
The Mux (multiplexer) is a switching device that only allows one analog input through at a time. The inputs are selected sequentially by the Micro per Program instructions.
The A/D Converter converts each analog input to a 12-bit word. In this form, the values can be stored in memory devices, compared to values in the Program, transmitted through Serial Ports or sent to the Display Controller for display. Control signals to start conversion process are from the Micro via the FPGA.
The Watchdog circuit monitors the +5VDC supply from the Power Supply to determine when a power failure is occurring. Just prior to the supply decreasing to a level where the Micro and supporting circuits can no longer operate, it applies a reset signal to the Micro. The Micro responds by shutting down the remote control center and retrieving the Power Failure message from the Program and sending it to the Display Controller for display. Similarly, when power is first applied after a power failure, it maintains the Micro in a reset state until the +5VDC has returned to a sufcient level. The Watchdog circuit also assures that all the Program instructions are being performed and that the Program has not latched-up, bypassing important safety thresholds. If the Program has latched-up, the Micro displays WATCHDOG – SOFTWARE REBOOT message.
The Program Jumpers (Table 2) and Program Switches (Table 3) are used to alter the Program operation or congure the Microboard hardware for specic operation. This allows the Program and Microboard to be universal for all applications. Refer to Table 2 and 3 for the function of each jumper and switch. The position of some can be determined and set by the Service Technician to meet the desired operation. The position of others is dictated by the size, type or style of certain Control Center components and thus the position is determined by the YORK Factory. The required position of each is listed in these tables. The Program Jumpers are wire bridges that are either left in place or cut. The Program Switches are miniature switches that are placed in either the ON or OFF position.
YORK INTERNATIONAL68
Page 69
FORM 50.40-OM2
The DRAM (dynamic random access memory) is a non battery-backed memory device. The Micro stores data here temporarily for further processing. Data in this device is lost during power failures. DRAM differs from RAM in that DRAM must be periodically refreshed in circuit.
The BIOS EPROM (basic input/output system erasable programmable read only memory) is a memory device that contains the bootstrap or power-up program. It is located in socket location U45. This EPROM is replaceable. Refer to the YORK Renewal Parts List. The EPROM version is an alphanumeric code that represents the application and revision level. The version is printed on a label adhered to the EPROM’s surface. The version code is as follows:
C. MLM. 00. XX.
Revision level. Increments 01, 02 etc.
OptiView BIOS EPROM
MILLENNIUM
Commercial
When power is applied to the Control Center following a power failure, the Micro executes the instructions in the BIOS EPROM program to initialize, congure and start operation of certain Microboard components before the main program (stored in the Flash Memory Card) is started. Depending upon the application, the Microboard could be equipped with an EPROM that has either 128K, 256K or 512K capacity. Microboard Program Jumper JP38 must be positioned according to the actual EPROM installed. Refer to Table 2 (Program Jumpers). There are 5 steps to the boot-up process. During the boot-up process, there is a visual indication as each step is performed, followed by a Pass/Fail status of the step. On the Microboard, a green LED ashes to indicate the step was successful. If a step is unsuccessful, a red LED ashes and the Boot-up process terminates. The execution and Pass/Fail status of steps 3 through 5 are displayed on a white Keypad Display Screen as they are performed. This white display screen also lists the BIOS EPROM Version. The steps of the Boot-up process are as follows. Also, below is listed the LED activity associated with each step.
BOOT-UP STEP AND DESCRIPTION
1. First initiate table complete.
Registers in the Micro are congured to allow it to perform basic memory read/write functions.
2. FPGA conguration.
The Field Programmable Gate Array (FPGA) is congured to process Digital Inputs and Outputs.
3. Mini-card signature test.
A location in the Flash Memory Card that contains a code identifying the Manufacturer is compared to other locations that contain the manufacturer’s name. If these values are the same, it is pass. If they are different, it is fail.
4. Mini-card checksum.
The Flash Memory Card checksum is calculated and compared to the checksum value that is stored in the Card at the time the Card was initially programmed at the YORK factory. If both values are the same, it is considered pass. If the calculated value is different than the stored value, it is considered fail.
5. BRAM quick test. Test data is written to and then read from several memory locations to verify BRAM operation.
LED INDICATORS
When power is applied to the Control Center, both the red and green LED’s simultaneously illuminate for 1 second, then the Boot-up process begins in the following sequence (Note: While one LED ashes the other is off.). When all steps have been completed, both the green and the red LED’s illuminate and remain illuminated.
STEP PASS FAIL
1 Green on, Red off
initiate a re-boot.
2 Green ash once
One red ash repeating
3 Green ash once
Two red ashes repeating
4 Green ash once
Three red ashes repeating
5 Green ash once
Four red ashes repeating
Watchdog will
Boot-up process halts.
Boot-up process halts.
Boot-up process halts.
Boot-up process halts.
5
69YORK INTERNATIONAL
Page 70
Service
The BRAM (battery backed random access memory) is a memory device that contains a battery that preserves the data during power failures. It is a replaceable part. Refer to the YORK Renewal Parts List. It is located in socket location U52. The Micro stores the setpoints programmed by the Operator or Service Technician, History Data and other data that requires preservation, in this device. Also, the day of week, time of day and calendar date time-keeping are done here.
The keypad is a matrix of conductors arranged in rows and columns (ref. Fig. 45 & 46). There are 4 rows and 8 columns. When a key is pressed, the conductors are pressed together at that point, creating continuity between that row conductor and the column conductor. The Keypad is read by applying a logic low to a row while leaving +5VDC pullup on all the other rows. The Micro then reads the 8 columns. If any column has a logic low on it, the key corresponding to that coordinate (row, column) is being pressed. The Micro reads the entire Keypad by repeating this routine beginning with row 1 and ending with row 4. The entire Keypad is read every Program cycle. The Micro selects the MUX inputs (Microboard J7, J8, J9) for input to the A/D Converter by writing sequential addresses to the FPGA. The FPGA holds each address until a new one is received from the Micro. As each address is applied to the MUX, the input corresponding to that address is passed through the MUX to the A/D Converter. The A/D Converter will convert the analog value to a digital word when the Micro writes a “start conversion” pulse to the FPGA. The FPGA passes this to the A/D Converter. The Micro allows access to the PC-104 port (Microboard J16, J17) by writing an enable pulse to the FPGA. The FPGA applies this to the data transceiver, allowing data to be output to or input from the PC-104 Port.
To provide flexibility for future Analog Inputs (to Microboard J7), 2 analog inputs can be congured for either 0-10VDC or 4-20mA, Transducer or Thermistor inputs using Program Jumpers JP21 and JP22. The position of the jumper determines which type of input can be connected. Refer to Fig. 36 and Table 2, “Program Jumpers”.
These inputs are for future YORK Factory expansion use only. They are not general application spare inputs that will support arbitrarily installed devices. Devices CANNOT be connected to these inputs until the program has been modified to read and process the input. Unless YORK documentation shows a device connected to the input with a dened function, the input cannot be used.
The Microboard receives 2 supply voltages (Microboard J1) from the Power Supply; +12VDC, +5VDC and Ground. The +12VDC and +5VDC are input to Voltage Regulators to derive other regulated voltages. The +5VDC is input to a +3.3VDC regulator. The output is a 3.3VDC regulated voltage. The +12VDC is input to a 5VDC regulator. The output of this regulator powers only the Analog circuits. This includes the MUX, A/D converter, and Thermistors. As depicted on Fig. 33, these voltages can be monitored at Test Posts TP1 through TP6.
The Microboard is equipped with 5 Serial Data Ports (ref. Fig. 35). Connector J2 is shared with both COM 1 and COM 4B. Each Port is dedicated for a specic function as follows: a. COM 1 (J2) - RS-232. Printer. b. COM 2 (J13) - RS-232. Not Used. c. COM 3 (J12) - RS-485. Chiller panel communica-
tions .
d. COM 4 (4A-J11), (4B-J2) - This port is actually two
ports. However, they cannot be used simultaneously; only one of these ports can be connected to a device at a time. The position of Microboard Program Jumper J27 determines which port can be used (refer to Table 2). COM 4A (J11) is an RS-485 port that is used for Multi-Unit Communications. COM 4B (J2) is an RS-232 port that is used for MicroGateway.
e. COM 5 (J15) – Not Used.
YORK INTERNATIONAL70
Page 71
FORM 50.40-OM2
COM 1 is connected directly to the Micro. COM 2 through 5 are connected directly to the UART (Universal Asynchronous Receive Transmit). The UART converts the parallel data to serial form for transmission to the peripheral device and converts the incoming serial data to parallel form for use by the Micro. It also generates and processes control signals for the Modem communications (DTR, CTS, DSR, RTS). Under Program control, the Micro instructs the UART of the desired data transmission Baud rate. A crystal oscillator provides the frequency reference. Each port is equipped with two LED’S; a red one indicates when data is being transmitted to the remote device and a green one indicates when data is being received from the remote device. The RS-232 output voltages are industry standard +3 to +15VDC, with +9VDC typical. The RS-485 output voltages are industry standard +1.5 to +5VDC, with +2.5VDC typical. A loopback diagnostic test can be performed on each serial port. This test permits verication of the data transmitted from the serial port. Refer to the “Serial Inputs / Outputs Tests” description in this book for details of these tests. The graphic screens that are displayed on the Liquid Crystal Display are created from preformed graphics and messages that are stored in the Program (FLASH Memory Card), and real-time system operating parameters, such as temperatures. The graphics, message and number data are in the form of digital words. The Display Controller converts this data into display drive signals and sends them to the Display from Microboard J5. The Display has 307,200 pixels arranged in a 640 columns x 480 rows matrix conguration. Each pixel consists of 3 windows; red, green and blue, through which a variable amount of light from the Display backlight is permitted to pass through the front of the display. Imbedded in each window of the pixel is a transistor, the conduction of which determines the amount of light that will pass. The drive signal determines the amount of conduction of the transistor and therefore the amount of light passed through the window. The overall pixel color becomes a result of the gradient of red, green and blue light allowed to pass. The drive signal for each pixel is an 18 bit binary word; 6 for each of the 3 colors, red, green and blue. The greater the binary value, the greater the amount of light permitted to pass. The pixels are driven sequentially from left to right, beginning with the top row. To coordinate the drive signals and assure the pixels in each row are driven sequentially from left to right and the columns are driven from top to bottom, each drive signal contains a horizontal and vertical sync signal.
The Display DRAM is a memory device that supports the operation of the display controller. This device could be either of two types; FPM (fast page mode) or EDO (extended data out) type. Program Jumper JP6 must be positioned according to the type of DRAM device installed in the Microboard; JP6 in - EDO, out - FPM. Refer to Table 2, “Program Jumpers”. Depending upon the requirement, there could be one or two DRAM devices installed in the Microboard. If the design requires only one DRAM, it is installed in socket U27. If an additional one is required, it is installed in socket U25.
During the power-up sequence, the program in the BIOS EPROM reads Program Jumper JP6 to determine the type of Display DRAM installed (as explained above). It also reads wire jumpers PID0 through PID3 (via Microboard J5) on the Display Interface Board to determine the manufacturer of the display (refer to description of Display Interface Board). Each display manufacturer requires a slightly different control. The program in the BIOS EPROM then congures the Display Controller for operation with the actual display that is present.
Different Display manufacturers can require different supply and control voltages for their displays and backlights. Program Jumpers JP 2 through 4 and 5 through 8 must be congured to provide the required supply and control voltages to the display and backlight control. Table 2 lists the required Program Jumper conguration for the Display. Also, a label attached to the Display mounting plate lists the required Program Jumper conguration for that particular Display.
The power supply voltage that operates the Display is provided by the Microboard J5. The position of Program Jumper JP2 determines whether this supply voltage is +5VDC or +3.3VDC. The Display requires a specic power-up and power-off sequencing to prevent damage. During power-up, the supply voltage must be applied to the Display before the drive signals are applied. Similarly, during power-off sequencing, the display drive signals must be removed prior to removing the supply voltage. The Display Controller applies the supply voltage and data drive signals to the Display in the proper sequence. The Display Controller controls the Display Backlight by applying control signals (from Microboard J6) to the Backlight Inverter Board. The Backlight Inverter Board converts low voltage DC (+12VDC or +5VDC, depending on position of
5
71YORK INTERNATIONAL
Page 72
Service
Program Jumper JP5) to high voltage AC (500 to 1500VAC). This high voltage AC is applied to the lamp to cause it to illuminate. The Backlight is turned on and off with the “Enable Backlight” (J6-5) signal. The position of Program Jumper JP4 determines whether this is a +12VDC or +5VDC signal. In some displays, the Backlight turns on when this signal transitions from low to high; others turn on when it transitions from high to low. The position of Program Jumper JP3 determines the transition that will occur when the Display Controller outputs the “Enable Backlight” signal. Program Jumper JP3 must be positioned accord­ing to the Display manufacturer’s requirement.
Under Program control, the Display Controller controls the Backlight brightness via the Lamp Dimmer circuit. In order to extend the life of the backlight lamp, the lamp brightness is driven to 50% brightness after 10 minutes of Keypad inactivity. At this brightness level, the Display can still be read. Subsequently, when Keypad activity is detected (i.e. a Keypad key is pressed), the lamp is driven back to full brightness (100% brightness). Some display manufacturers require a variable voltage to vary the brightness; others require a variable resistance. Program Jumpers JP7 and JP8 allow either method to be used. The Lamp Dimmer is an integrated circuit that is the electrical equivalent of a 10K ohm potentiometer with 100 positions or steps (ref. Fig. 34). The Display
Controller controls the position of the potentiometer. The Lamp Dimmer varies the brightness of the Backlight
by applying either a variable voltage (0-5.0VDC) or a variable resistance (0-10K ohms), to the Backlight Inverter Board. If Program Jumpers JP7 and JP8 are installed, the Lamp Dimmer output is a variable voltage; if both are removed, the output is a variable resistance. The Lamp Dimmer outputs “Brightness Control Wiper” (J6-7) and “Brightness Control -“ (J6-8) to the Backlight Inverter Board. If configured for variable voltage output, the voltage between J6-7 and J6-8 can be varied from 0 (100% brightness) to 5.0VDC (0% brightness). If congured for variable resistance, the resistance between J6-7 and J6-8 would vary from 0 ohms (0% brightness) to 10K ohms (100% brightness).
The PC-104 Port (J16 & J17) is an industry standard arrangement of two connectors that allows the stacking of 3.6 x 3.8 inch printed circuit boards (PC-104 Modules) on the Microboard. The circuits on these boards have access to the Microboard’s address/data bus, and therefore become an extension of the Microboard. This provides expansion of the Microboard’s capabili­ties without redesigning or changing the size of the Microboard. PC-104 Modules are not used in all Remote Control Center applications.
System tem peratures, in the form of analog DC voltages from temperature thermistors, are input to the MUX (multiplexers). Under Program control, the Micro selects these values, one at a time, for input to the Analog to Digital (A/D) converter. As each one is selected, it is passed to the A/D Converter for conversion to a 12-bit digital word that is then input in parallel form to the Micro. The Micro stores each value in the DRAM for display requests, further processing or Serial Port transmission. Each value is also stored in the BRAM for History data.
Service Replacement: Microboards are supplied as Service Replacement parts without the following components:
• BRAM (U52)
• Flash Memory Card (U46)
• BIOS EPROM (U45)
Upon receipt of the replacement Microboard, remove these components from the Board being replaced and install in the replacement Board. Although these components have YORK Part Numbers as listed in the Parts List and can be individually replaced, it is recommended that these existing components be used in the new Board since the BRAM memory device contains all of the programmed setpoints.
YORK INTERNATIONAL72
Page 73
FORM 50.40-OM2
FLASH MEMORY CARD
BIOS EPROM
BRAM
RS485
Driver
RS485
Driver
5
FIG. 31 – MICROBOARD
LD06743
73YORK INTERNATIONAL
Page 74
R
AUGAT
R
MEMORY CARD
RETAINER CLIP
PRESS DOWN TO RELEASE CARD
ELASTOMERIC
CONNECTOR
WRITE PROTECT SWITCH (OPTIONAL) (MUST BE IN "ENABLED POSITION")
CINSCINS GND
VCC
3V/5V
KEY
ALIGNMENT
NOTCH
PAD 60
PAD 30
PAD 31
PAD 1
WRITE ENABLED
WRITE DISABLED
Service
MEMORY CARD SOCKET
MEMORY CARD -
TOP SURFACE
LD06745
TOP SURFACE
LD06744
MEMORY CARD - BOTTOM SURFACE
MEMORY CARD - SIDE VIEW
LD06746
FIG. 32 – FLASH MEMORY CARD
LD06747
YORK INTERNATIONAL74
Page 75
FORM 50.40-OM2
FPGA
MUX
MUX
A/D
CONVERTER
WATCH-
DOG
PROGRAM
SWITCHES
MICRO
DRAM
DISPLAY
CONTROLLER
DRAM
FLASH
EPROM
BIOS
EPROM
BRAM
XCVR
PC-104
PORT
UART
INPUT
BUFFER
PROGRAM
JUMPERS
BACKLIGHT
CONTROL
DATA
BUS
XCVR
SERIAL DATA
PORT 1
DISPLAY INTERFACE
BOARD
BACKLIGHT INVERTER
BOARD
DIGITAL
INPUTS
DIGITAL
OUTPUTS
SERIAL
DATA PORTS
2 THROUGH 5
ANALOG
INPUTS
+5VDC REF
LVG CHILLED
R25
R28
VOLTAGE
REG
VOLTAGE
REG
+ 12VDC
+ 5VDC
GND
Y
Y
Y
Y
TP2
TP1
TP4
TP3
+ 12VDC
+ 5VDC (ANALOG)
+ 5VDC (DIGITAL)
+ 3.3VDC
FROM
POWER
SUPPLY
LD06748
FIG. 33 – MICROBOARD
5
75YORK INTERNATIONAL
Page 76
Service
TABLE 2 – MICROBOARD PROGRAM JUMPERS

MICROBOARD PROGRAM JUMPERS

JP1 - Watchdog enable/disable. The position of this
jumper, in conjunction with Program switch SW 1 position 12 enables or disables the program Watchdog protection.
Never disable the watchdog protec­tion. Severe compressor or chiller damage could result. The ability to disable the watchdog protection is provided for factory testing only!!!
IN - Watchdog protection enabled.
OUT - Permits Program switch SW1 position 12 to
enable or disable the program
Watchdog protection as follows: Position 12 ON - Watchdog protection enabled
OFF - Watchdog protection disabled
JP2 - Display power and logic levels. Determines the
power supply voltage applied to the display.
Pins 1-2: +5VDC SHARP LQ10D367
Pins 2-3: +3.3VDC LG Semicon LP104V2
displays.
JP4 - Display backlight enable signal logic levels.
Determines the logic levels of the Backlight enable signal.
Pins 1-2: +12VDC/0VD (Not used)
Pins 2-3:+5VDC/0VDC LG Semicon LP104V2
displays.
JP5 - Display backlight power. Determines the power
supply voltage applied to the Display Backlight Inverter Board.
Pins 1-2: +12VDC. SHARP LQ10D367 and
LG Semicon LP104V2 displays.
Pins 2-3: +5VDC. (Not used)
JP6 - Display memory type. Jumper must be posi-
tioned according to type of RAM used for display memory devices (U25 & U27).
IN - EDO: (extended data out) type. Jumper
should be IN.
OUT - FPM: (fast page mode) type. Not used
at this time.
JP7, JP8 - Display brightness control technique.
Determines whether the display brightness is controlled by a variable voltage or variable resistance.
If this jumper is not correctly installed the display could become damaged.
JP3 - Display backlight enable signal level polarity.
Jumper must be positioned according to the voltage level required to turn on the Display Backlight.
Pins 1-2: 0VDC (Not used)
Pins 2-3: +12VDC or +5VDC as determined
by position of JP4. SHARP LQ10D367 and LG Semicon LP104V2 displays.
IN: Variable voltage (0-5.0VDC). SHARP
LQ10D367 and LG Semicon LP104V2 displays.
OUT: Variable resistance. (Not used)
JP9 - COM 2 serial communications port. Congures
COM 4 port to be either RS-485 or RS-232.
Pins 1-2: RS-232
Pins 2-3: RS-485
JP10 - JP26 - Not used.
YORK INTERNATIONAL76
Page 77
FORM 50.40-OM2
JP27 - COM 4 serial communications port. Congures
COM 4 port to be either RS-485 for Multi-Unit Communications (COM 4A) or RS-232 for MicroGateway board (COM4B).
Pins 1-2: Enables port 4A. Allows an RS-485
connection to Microboard J11 for MultiUnit Communications.
Pins 2-3: Enables port 4B. Allows an RS-232
connection to Microboard J2 for MicroGateway communications.
JP28 - PC-104 Port interrupt assignment. Assigns
selected PC-104 interrupt request to PDRQ7 on the microprocessor. Interrupt request selections are silk screened on the Microboard adjacent to the program jumper. Not used.
JP29 - PC-104 Port interrupt assignment. Assigns
selected PC-104 interrupt request to PDRQ6 on the microprocessor. Interrupt request selec­tions are silk screened on the Microboard adjacent to the program jumper. Future modem application.
JP30 - PC-104 Port DMA assignment. Assigns selected
PC-104 DMA request to PDRQ0 on the micro­processor. DMA request selections are silk screened on the Microboard adjacent to the program jumper. Not used.
JP31 - PC-104 Port DMA assignment. Assigns selected
PC-104 DMA request to PDRQ1 on the micro­processor. DMA request selections are silk screened on the Microboard adjacent to the program jumper. Not used.
JP32 - PC-104 Port DMA acknowledge assignment.
Assigns selected PC-104 DMA acknowledge to PDACK0 on the microprocessor. DMA acknowledge selections are silk screened on the Microboard adjacent to the program jumper. Not used.
JP33 - PC-104 Port DMA acknowledge assignment.
Assigns selected PC-104 DMA acknowledge to PDACK1 on the microprocessor. DMA acknowledge selections are silk screened on the Microboard adjacent to the program jumper. Not used.
JP34, JP35, JP36, JP37 - Not Used
JP38 - BIOS EPROM U45 size. Jumper must be
positioned according to size of U45. Jumper is a 10 Ohm resistor that is soldered to board. It is not a shunt jumper.
IN: 512K
OUT: 128K or 256K. Should be OUT for
OptiView Remote Control Center applications.
JP39, JP40, JP41, JP42 - Not used.
5
77YORK INTERNATIONAL
Page 78
6
7
8
J6
BRIGHTNESS CONTROL (+) OR (N.C.)
BRIGHTNESS CONTROL (WIPER)
BRIGHTNESS CONTROL (-)
TO
BACKLIGHT
INVERTER
BOARD
JP8
JP7
5.0 VDC
10 K
Service
TABLE 3 – MICROBOARD PROGRAM SWITCHES
SW1
1 - Simulator mode - When this switch is closed
or in the ON position, the RCC simulates the data from 4 chillers and will not communicate with any attached units.
ON: Simulator mode enabled. Used for dem-
onstration.
OFF: Simulator mode is disabled. The unit
must be powered on with the switch in this position for the RCC to communicate with attached units and operate normally.
2 - Not Used
3 - Not Used
4 - Diagnostics - Enables or disables software
diagnostics
ON: Enables software diagnostics. Disables
normal control center operation
OFF: Disables software diagnostics. Enables
normal control center operation.
5 - 11 Not Used
12 - Watchdog Protection -Used in conjunction with
Program Jumper JP1 (see above) to enable/disable the program watchdog protection. With JP1
IN, this switch setting has no effect. With JP1 OUT, this switch setting determines whether the
watchdog protection is enabled or disabled.
NEVER disable the watchdog protec­tion! Severe compressor or chiller damage could result. The ability to dis­able the watchdog protection is provided for YORK factory testing only.
ON: Watchdog protection enabled.
OFF: Watchdog protection disabled.
NOTES:
1. J6-6 not connected (N.C.) to Backlight Inverter Board when display is manufactured by Sharp or NEC.
2. The position of Program Jumpers JP7 & JP8 determine the output at J6-7; In = Variable Voltage; Out = Variable Resistance. Refer to
Program Jumper Listing in Table 2 for applications.
3. Potentiometer is actually an integrated circuit that is the electrical equivalent of a 10K potentiometer.
FIG. 34 – MICROBOARD LAMP DIMMER CIRCUIT
YORK INTERNATIONAL78
LD04054
Page 79
FORM 50.40-OM2
MICRO
UART
COM 1
COM 4B
(NOTE 1)
COM 4A
(NOTE 1)
COM 2
COM 3
COM 5
OPTO-COUPLE
RS-485
RS-232
RS-485
RS-232
MICROGATEWAY
PRINTER
NOT USED
NOT USED
CONNECTION TO CHILLER / CONDENSING CONTROL PANELS
NOT USED
4 3 5 2
7 6 8 9
3
2 1 4 5
1 2 3 4 5 6 7
9
3 2 1 4 5
1 2 3 4 5 6
J2
J11
J13
J12
J15
TX RX
COMMON
NOTE 2 NOTE 2
+
--
+ 5VDC
GND
SHIELD
DCD DSR
RX
RTS
TX CTS DTR
GND
--
+ 5VDC
GND
SHIELD
+
TX
RX DTR DSR
GTX
GRX
12
3
TX1 RX1
TX4 RX4
TX2 RX2
TX3
RX3
TX5
RX5
JP27
5
NOTE:
1. Microboard Program Jumper JP27 determines whether COM 4A or 4B can be used. 1 & 2 - 4A, 2 & 3, 4B. Refer to Table 2.
FIG. 35 – MICROBOARD SERIAL DATA COMMUNICATIONS PORTS
LD06749
79YORK INTERNATIONAL
Page 80
NOT USED
NOT USED
NOT USED
NOT USED
0 10 VDC
4 - 20 MA
0-10 VDC
4 - 20 MA
4
3
1
2
16
4
14
2
13
1
MUX
47K
JP21
JP22
JP23
JP24
200
7.5 K
1
2
3
1
2
3
1
2
3
1
2
3
71.5 K
+5V
3
15
+5V
J7
J22
0-10 VDC /
0 - 20 MA /
2-10 VDC
4 - 20 MA
0-10 VDC /
0 - 20 MA /
2-10 VDC
4 - 20 MA
Service
NOTE:
1. Program Jumpers JP21 – JP24 must be positioned on pins 1-2 or 3-4 according to input signal type. Refer to Table 2.
LD04636
FIG. 36 – CONFIGURABLE ANALOG INPUTS
YORK INTERNATIONAL80
Page 81

LIQUID CRYSTAL DISPLAY

(REFER TO FIG. 37 - 42)
FORM 50.40-OM2
A 10.4 inch color Liquid Crystal Display, along with supporting components Display Interface Board and Backlight Inverter Board are mounted on a plate that is attached to the OptiView Control Center door. A clear plexiglass faceplate prevents display surface damage. System operating parameters are displayed on various color graphic screens. The various display screens are selected for display using the Keypad keys.
The Display provided in the OptiView RCC or from YORK as a service replacement part, could be manufac­tured by any of several approved manufacturers. Each Display requires a specific Display Interface Board, Backlight Inverter Board, Inverter Board interface cable and Program command set. Therefore, Service replace-
ment Displays or supporting components cannot be arbitrarily selected!!! As explained below, replacement
Displays are provided from YORK as kits to assure compatibility of all components. Non-compatibility of components will result in incorrect operation!!! Refer to “Display Interface Board” and “Backlight Inverter Board” descriptions that follow. The following displays could be provided from YORK in new OptiView RCCs or as replacement parts:
• LG SEMICON LP104V2
• SHARP LQ10D367
The YORK part numbers of the Display Interface Board, Backlight Inverter Board and Inverter ribbon cable provided, are listed on a label attached to the Display mounting plate. These are the part numbers of the supporting components that are compatible with the installed display. These supporting components can be individually replaced. However, if the Liquid Crystal Display fails, Display replacement kit 331-02053-000 must be ordered as detailed below. This kit contains a replacement Display and all compatible supporting components.
The Display has 307,200 pixels arranged in a 640 columns X 480 rows matrix conguration. Each pixel consists of 3 windows; red, green and blue, through which a variable amount of light from the Display Backlight is permitted to pass through the front of the display. Imbedded in each window of the pixel is a transistor, the conduction of which determines the amount of light that will pass through the window. The conduction of each transistor is controlled by a signal from the Display Controller on the Microboard. The overall pixel color is a result of the gradient of red, green and blue light allowed to pass.
Under Program control, the Display Controller on the Microboard sends a drive signal for each pixel to create the image on the display. Each pixel’s drive signal is an 18 bit binary word; 6 bits for each of the 3 colors, red green and blue. The greater the binary value, the greater the amount of light permitted to pass. The columns of pixels are driven from left to right and the rows are driven top to bottom. To coordinate the drive signals and assure the columns are driven from left to right and the rows are driven from top to bottom, each drive signal contains a horizontal and vertical sync signal. The Display Interface Board receives these display drive signals from the Microboard J5 and applies them to the Display at connector CN1. Refer to Fig. 43.
Although there are variations in control signal timing between different display manufacturers, Fig. 38 depicts typical control signals. Since these control signals occur at rates greater than can be read with a Voltmeter, the following description is for information only. There are 480 horizontal rows of pixels. Each row contains 640 3-window pixels. Beginning with the top row, the drive signals are applied within each row, sequentially left to right, beginning with the left most pixel and ending with the right most pixel. The rows are driven from top to bottom. The Vertical Sync (VSYNC) pulse starts the scan in the upper left corner. The rst Horizontal Sync (HSYNC) pulse initiates the sequential application of RGB drive signals to the 640 pixels in row 1. Upon receipt of the ENABLE signal, an RGB drive signal is applied to the rst pixel. As long as the ENABLE signal is present, RGB drive signals are then applied to the remaining 639 pixels at the CLK rate of 25.18MHz, or one every 39.72 nanoseconds. Typically it takes 31 microseconds to address all 640 pixels. Similarly, the next HSYNC pulse applies drive signals to row 2. This continues until all 480 rows have been addressed. Total elapsed time to address all 480 rows is approximately 16 milliseconds. The next VSYNC pulse causes the above cycle to repeat. Displays can be operated in FIXED mode or DISPLAY ENABLE mode. In FIXED mode, the rst pixel drive signal is applied a xed number (48) of clock (CLK) cycles from the end of the HSYNC pulse and the drive signals are terminated a xed number (16) of CLK cycles prior to the next HSYNC pulse. In DISPLAY ENABLE mode, the pixel drive signals are applied to the pixels only while ENABLE signal is present. This signal is typically present 4-48 CLKS after the end of the HSYNC pulse and 2-16 CLKS prior
5
81YORK INTERNATIONAL
Page 82
Service
to the next HSYNC pulse. All YORK applications operate in the DISPLAY ENABLE mode. The state of the ENABLE (Display Interface Board J1-27) signal from the Microboard places the Display in the desired mode as follows:
• LG SEMICON Display does not have the xed mode feature.
As described above, in OptiView Control Center applications, the Display scan is left to right, beginning with the top row and continuing sequentially through the rows to the last row. However, in Display applications other than OptiView Control Centers, image reversal is sometimes required. In image reversal applications, the scan is reversed; the scan is right to left, beginning with the last row and proceeding to the top row.
Displays by different manufacturers can require different timing and control signals. The Microboard must know which Display is present in order to provide the correct signals. Therefore, when AC control power is rst applied to the OptiView Control Center, as part of the power-up sequence, the Microboard reads the Panel ID wire jumpers P1D0 - P1D3 on the Display Interface Board and determines which Display is present. It can then provide the correct timing and control signals to produce the graphic image, as required by the Display manufacturer. Since the Display Interface Board identies the Display for the Microboard, there is a different Display Interface Board required for each Display application and each has a unique jumper conguration that identies the Display. A complete explanation of this process is included in the preceding “Microboard” description and the “Display Interface Board” description that follows.
The DC power source to operate the Display is provided by the Microboard J5. Some Display manufacturers require +5VDC; others require +3.3VDC. The position of Microboard Program Jumper JP2 determines which of these power sources is supplied to the Display. JP2 must be positioned according to the Display manufacturers requirements. Refer to Table 2, “Program Jumpers”.
The Backlight Lamp provides the illumination for the display. Average lamp life is 25000 hours (2.9 years). Some displays use one lamp. Others use two lamps. Lamps are replaceable, but not interchangeable between different displays. Each Display manufacturer species the required lamp for their display. Refer to replacement parts list for appropriate replacement lamp. Service replacement lamps are stocked in the YORK Service Parts
Distribution Center. The lamp is illuminated by applying a high voltage AC (500 to 1500VAC) to it. This illumination voltage is created from a low level DC voltage (+12VDC or +5VDC as required by the Display manufacturer) by the Backlight Inverter Board. Lamp brightness is controlled by varying the high voltage AC. The greater the voltage the brighter the illumination. The lamp is controlled by on/off commands and brightness control signals applied to the Backlight Inverter Board from the Microboard. The Microboard Program determines when the lamp is turned on and off and the lamp brightness. Each Display manufacturer species the Backlight Inverter Board to be used. Therefore, it will vary according to the Display manufacturer. The ribbon cable that connects the Microboard to the Backlight Inverter Board also varies according to the Display manufacturer’s requirements. Refer to Fig. 44. Microboard Program Jumpers JP3, 4, 5, 7 and 8 determine the voltage levels of the control signals sent to the Backlight Inverter Board and must be congured per the Display manufacturer’s requirements as listed in Table 2. A detailed description of the operation of this board is in the “Backlight Inverter Board” description that follows. Also refer to the preceding “Microboard” description for a detailed description of the Lamp Dimmer circuit.
The actual Display that is installed in the OptiView Control Center of the new chiller is determined by the Display manufacturer contractual agreement in place during the time of OptiView Control Center production. Displays stocked for Service replacement are a result of that same agreement. Therefore, the Display received for service replacement may be by a different manufacturer than the one in the OptiView Control Center. Since each Display manufacturer requires a specic Display Interface Board, Backlight Inverter Board and Inverter Ribbon Cable, replacement Displays are ordered and supplied as a Display Replacement Kit (YORK Part Number 331-02053-000) to assure component compat­ibility. The items supplied in the kit are compatible with the supplied Display. The kit consists of the following items mounted on a Display mounting plate:
Display Replacement Kit 331-02053-000:
1. Liquid Crystal Display with Lamp
2. Appropriate Display Interface Board for item 1
3. Appropriate Backlight Inverter Board for item 1
4. Appropriate ribbon cable (Backlight Inverter Board to Microboard) for item 1
5. Ribbon cable (Display Interface Board to Microboard)
6. All mounting hardware
7. Installation instructions. A label attached to the
YORK INTERNATIONAL82
Page 83
FORM 50.40-OM2
Display mounting plate lists the YORK part numbers of the Display supporting components mounted on the Display mounting plate and the required Microboard Program Jumper (JP2 through 8) congurations. Microboard Program Jumpers
JP2 - JP8 will have to be congured appropriately for the replacement display. Refer to Table 2 “Program Jumpers”.
Display Handling:
1. The display is made of glass. It could break if dropped.
2. The display front surface is easily scratched. If soiled, wipe with a dry cotton cloth. Use no water or chemicals.
3. The display is static sensitive. Electrostatic dis­charges may damage the display.
4. A laminated lm is adhered to the display front glass surface to prevent it from being scratched. Peel off very slowly to prevent static damage.
Always remove control power from the OptiView Remote Control Center before connecting or disconnecting wires to the display. Connecting or disconnecting wires to the display with power applied will damage the display!!!
4. Using ngernail or thin at blade screwdriver, bend the locking tab outward slightly to clear the Lamp housing protrusion.
5. Grasp Lamp AC power connector and gently pull until Lamp housing clears locking tab.
6. Grasp Lamp housing and pull until Lamp housing is completely removed from the Display.
Installation:
1. Slide new Lamp into Display from left to right until Lamp housing protrusion locks into Display locking tab.
2. Connect Lamp AC power connector to Backlight Inverter Board.
3. Apply Control Power to OptiView Control Center.
LG Semicon LP104V2 Display (refer to Fig. 42) Removal:
The Lamp slides into the Display from left to right and is secured with a screw.
1. Remove Control Power from the OptiView Remote Control Center.
2. Remove protective cover from rear of Display.
3. Disconnect Lamp AC power connector from Back­light Inverter Board.
4. Using small Phillips screwdriver, remove lamp retaining screw.
5. Grasp Lamp AC power connector and gently pull until Lamp housing is completely removed from the Display.
BACKLIGHT LAMP REPLACEMENT:
SHARP LQ10D367 Display: (Refer to Fig. 41) Removal:
The Lamp slides into the Display from left to right and
is secured with a locking tab.
1. Remove Control Power from the OptiView Control Center.
2. Remove protective cover from rear of Display.
3. Disconnect Lamp AC power connector from Backlight Inverter Board.
Installation:
1. Slide new Lamp into Display from left to right until Lamp housing is fully inserted.
2. Secure Lamp with Lamp retaining screw.
3. Connect Lamp AC power connector to Backlight Inverter Board.
4. Apply AC power to OptiView Remote Control Center.
5
83YORK INTERNATIONAL
Page 84
640 CLKS
640
COLUMNS
31US
VSYNC
480 ROWS
16MS
ROW 480
ROW 1
ROW 2
BP FP
DISPLAY
PERIOD
DISPLAY
PERIOD
DISPLAY
PERIOD
HSYNC
ENABLE
CLK
(25.18
MHz)
RGB
39.72 NS
Service
FIG. 37 – DISPLAY, MOUNTING
NOTES:
1. BP = Back Porch = 4-48 CLKS
2. FP = Front Porch = 2-16 CLKS
FIG. 38 – LIQUID CRYSTAL DISPLAY TYPICAL CONTROL SIGNAL TIMING
LD06751
LD04066
YORK INTERNATIONAL84
Page 85
FORM 50.40-OM2
LIQUID CRYSTAL DISPLAY
SHARP LQ10D367
MOUNTING PLATE
DISPLAY INTERFACE
BOARD 031-01765-002
DISPLAY CABLE
031-01769-000
INVERTER CABLE
031-01770-003
BACKLIGHT
INVERTER
BOARD
031-01789-000
LABEL
BACKLIGHT BULB
025-33752-000
LIQUID CRYSTAL DISPLAY
LG SEMICON LP104V2
MOUNTING PLATE
DISPLAY INTERFACE
BOARD 031-01765-001
DISPLAY CABLE
031-02055-000
INVERTER CABLE
031-02054-001
BACKLIGHT
INVERTER
BOARD
031-01789-000
LABEL
BACKLIGHT BULB
025-34564-000
331-02053-000
031-02054-001
035-17813-002
031-01789-000
025-34564-000
031-01765-001
NOTE:
1. Congure Microboard Program Jumpers per label.
FIG. 39 – LIQUID CRYSTAL DISPLAY ASSEMBLY - LG SEMICON LP104V2
LD06752
5
NOTE:
1. Congure Microboard Program Jumpers per label.
FIG. 40 – LIQUID CRYSTAL DISPLAY ASSEMBLY - SHARP LQ10D367
LD06753
85YORK INTERNATIONAL
Page 86
LAMP HOLDER
BEZEL
PROTRUSION
HOLE
LOCKING TAB
WIRE
(white/GND side)
WIRE
(pink/HOT side)
DIRECTION A
DIRECTION B
DIRECTION C
LAMP HOLDER
BEZEL
RETAINING SCREW
WIRE
(white/GND side)
WIRE
(pink/HOT side)
DIRECTION B
DIRECTION C
Service
FIG. 41 – DISPLAY (SHARP LQ10D367) LAMP REPLACEMENT
LD04067
FIG. 42 – DISPLAY (LG SEMICON LP104V2) LAMP REPLACEMENT
LD06754
YORK INTERNATIONAL86
Page 87

DISPLAY INTERFACE BOARD

(REFER TO FIG. 43)
FORM 50.40-OM2
The Display Interface Board is located on the Liquid Crystal Display mounting plate and is part of the
Microboard interface to the Display. It permits the use of Displays by different manufacturers, by providing the Microboard with a means of automatically determining which Display is present.
Since different Display manufacturers require different timing and control signals, the Display Controller on the Microboard must be congured to meet the requirements of the actual Display installed. When AC power is applied to the OptiView Remote Control Center, as part of the power-up sequence, the Microboard reads the four Panel ID wire jumpers, PID0 through PID3, on the Display Interface Board to determine which Display is present. The conguration of these jumpers indicates the actual Display that is installed on the OptiView Remote Control Center door. The Display Controller on the Microboard is then congured appropriately.
On Sharp displays the conguration of wire jumpers P30 and P31 determines whether the Display scan orientation is Normal or Reverse (image reversal) scan. As described in the preceding “Display” description, Normal scan is left to right, beginning with the top row and continuing sequentially through the rows to the bottom row. Normal scan is used in OptiView Remote Control Center applications. In Display applications other than OptiView RCC applications, image reversal is sometimes required. In image reversal applications, the scan is reversed; the scan is right to left, beginning with the bottom row and proceeding to the top row. The jumper congurations determine the voltage level at Display Interface Board J1-30 (P30) and J1-31 (P31). If P30 is IN, the voltage at J1-30 is +5.0VDC or +3.3VDC (as determined by position of Microboard Program Jumper JP2); if OUT, 0VDC. If P31 is IN, the voltage at J1-31 is GND; if OUT, 0VDC. The Display reads these voltages and adopts a scan mode as follows:
SHARP LQ10D367 & LQ10D421 Displays: SHARP displays require conguration of both jumpers to achieve total image reversal.
P30 IN - Normal scan; left to right OUT - Reverse scan: right to left
P31 IN - Normal scan; top to bottom OUT - Reverse scan; bottom to top
The wire jumpers on this board are not eld congu­rable, as with typical Program Jumpers. There are two variations of the Display Interface Board. Each board has the wire jumpers congured appropriately for the display to which it is attached, as shown below. Display Interface Boards are available individually for service replacement. The YORK part number of the Display Interface Board compatible with the installed Display is listed on a label attached to the Display mounting plate. However, service replacement Displays are provided as a kit (331-02053-000) that includes, among other items, the appropriate Display Interface Board for the Display included in the kit. Refer to explanation in “Liquid Crystal Display” description.
031-01765-001:
Display applicability - LG Semicon LP104V2 Jumper conguration - PID0 - IN PID1 - OUT PID2 - OUT PID3 - OUT P30 - OUT P31 - OUT
031-01765-002:
Display applicability - SHARP LQ10D367 Jumper conguration - PID0 - OUT PID1 - IN PID2 - OUT PID3 - OUT P30 - IN
P31 - IN
The red, green and blue display drive and control signals are simply passed through the Display Interface Board. The value of VCC is either +5VDC or +3.3VDC, as determined by the position of Program Jumper JP2 on the Microboard. PID0 through PID3, when installed, connect their respective Microboard (J5) inputs to GND; when removed, the Microboard pulls these signals up to +5VDC. When P30 is installed, the Display input (CN1-30) is connected to VCC (+5VDC or +3.3VDC as determined by Microboard Program Jumper JP2). When P31 is installed, the Display input (CN1-31) is connected to GND.
5
87YORK INTERNATIONAL
Page 88
Service
LD04070
LG SEMICON LP104V2
031-01765-001 - PID0 IN
PID1-3 OUT
P30, P31 OUT
SHARP LQ10D367
031-01765-002 - PID0 OUT
PID1 IN
PID2, 3 OUT
P30, 31 IN
FIG. 43 – DISPLAY INTERFACE BOARD
YORK INTERNATIONAL88
Page 89

DISPLAY BACKLIGHT INVERTER BOARD

(REFER TO FIG. 44)
FORM 50.40-OM2
The Display Backlight Inverter Board generates a high voltage AC signal that is applied to the backlight lamp, causing it to illuminate. The magnitude of the signal determines the lamp brightness. Displays by some manufacturers have two lamps; one at the top and one at the bottom of the display. Other Display manufacturers have only a lamp at the top of the display.
An Inverter converts low level DC voltage (+12VDC or +5VDC, as required by the manufacturer) from the Microboard to a 500 to 1500VAC 60KHz signal that is applied to the lamp. The higher the AC voltage, the greater the brightness of the lamp. When this voltage is not present, the lamp is turned off.
High voltage, up to 1500VAC, is pres­ent at the output of the backlight inverter board. Refer to Figure 44 and locate the output connectors. Use extreme caution when working in this area!!!
Program Jumper JP4 must be positioned to provide the required voltage. Further, some applications require this signal to be a +VDC (+12VDC or +5VDC) to turn on the lamp. Others require this signal to be 0VDC to turn on the lamp. Program Jumper JP3 must be positioned to provide the required polarity.
Depending upon the Display manufacturer, the brightness control input from the Microboard must be either a variable voltage or a variable resistance. Microboard Program Jumpers JP7 and JP8 are used to provide the appropriate technique (refer to Fig. 34). The lamp dimmer circuit on the Microboard is an IC that is the electrical equivalent of a 10K ohm potentiometer with 100 positions or steps. The Program adjusts the position of the potentiometer. When congured for variable voltage (JP7 & JP8 installed), the output between Microboard J6-7 and J6-8 is a 0 to +5.0VDC signal. Not all applications require the full
5.0VDC range. If congured for variable resistance (JP7 and JP8 removed), the output between Microboard J6-7 and J6-8 is a 0 to 10K ohm variable resistance.
Different Display manufacturers require different Backlight Inverter Boards. The different board designs require different control voltage inputs. To accommodate these variations, Microboard Program Jumpers JP3 - JP5, JP7 and JP8 must be congured to provide the required voltage levels. A label attached to the Display mounting plate lists the required Program Jumper conguration for that particular display. Refer to Table 2 for required Program Jumper congurations for the various Display applications.
Under Program control, the Microboard generates the control signals that are applied to the Backlight Inverter Board. The Program determines when the lamp is turned on and off. It also adjusts the lamp brightness. To increase the average lamp life of 25000 hours, the lamp brightness is normally adjusted to 50%. This brightness level will still allow the display to be visible. When the Program senses a Keypad key has been pressed, it adjusts the brightness to 100% (maximum).
The lamp illumination high voltage AC is generated from either +12VDC or +5VDC as required by the manufacturer. Microboard Program Jumper JP5 must be positioned to provide the required voltage. The Microboard provides the Backlight Enable signal. This signal turns the lamp on and off. Some manufacturers require this signal to be +12VDC, others require +5VDC.
The OptiView Remote Control Center could be supplied with any of several approved Displays. Each Display requires a specic Backlight Inverter Board. This board is available as a service replacement part (the required Backlight Inverter Board part number is listed on the label attached to the Display mounting plate). However, service replacement Displays are provided in a kit (YORK P/N 331-02053-000) that includes the appropriate Backlight Inverter Board (refer to “Liquid Crystal Display” description).
SHARP model LQ10D367 and LG Semicon LP104V2 display requires a TDK CXA-LO612-VJL Backlight Inverter Board (YORK P/N 031-01789-000) (ref. Fig. 39 and Fig. 40). These boards generate a lamp illumination high voltage AC from +12VDC. When the Backlight Enable signal at connector CN1-3 is +5VDC, the high voltage signal is applied to the lamp. When CN1-3 is 0VDC, the high voltage signal is removed from the lamp, turning it off. The lamp brightness is controlled by a variable voltage signal, developed by the lamp dimmer circuit (ref. Fig. 34) on the Microboard and applied to connector CN1-4. The lamp dimmer circuit varies the voltage at CN1-4 over the range of 0 to +3.0VDC. 0VDC produces maximum (100%) brightness; +3.0VDC produces minimum (0%) brightness. Voltages between these values produce a linear brightness 0 and 100%. Connector CN2 applies the high voltage lamp illumination signal to the lamp.
89YORK INTERNATIONAL
5
Page 90
J6
10
9
8
7
6
5
4
3
2
1
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
MICRO
BOARD
INVERTER
BOARD
1 2 3 4 5
N.C.
CN1
CN2
3 2 1
N.C.
RETURN
500 - 1400 VAC
BACKLIGHT LAMP
BRIGHTNESS CONTROL (NOTE 2)
BACKLIGHT ENABLE (NOTE 1)
GND
+ 12 VDC (NOTE 3)
INVERTER CABLE 031-02054-001
DISPLAY BACKLIGHT INVERTER BOARD
TYPE: TDK CXA-L0612-VJL
PART NUMBER: 031-01789-000
FOR: SHARP LQ10D367 &
LG SEMICON LP104V2-W DISPLAYS
Service
NOTES:
1. OFF = 0VDC; ON = +5VDC. Refer to Microboard Program Jumpers JP3 & JP4 in Table 2.
2. 0 - +3.0VDC. 0VDC = MAX (100%) Brightness; +3.0VDC = MIN (0%) Brightness. Refer to Fig. 34 and Microboard Jumpers JP7 & JP8.
3. Refer to Microboard Program Jumper JP5.
4. N.C. = No Connection.
FIG. 44 – DISPLAY BACKLIGHT INVERTER BOARD
LD06755
YORK INTERNATIONAL90
Page 91

KEYPAD

(REFER TO FIGURES 45 & 46)
FORM 50.40-OM2
The Keypad contains touch-sensitive keys that allow the Operator to interface with the Control Center. The Operator presses the keys to request the desired screens of information and enter System Setpoints.
The top layer of the Keypad contains embossed areas identifying the keys. Under each embossed key area are two conductors, one on top of the other, separated by an air space. The conductors are arranged in a matrix of rows and columns and connected to the Keypad connector as shown in Fig. 46. The embossed area of each key is located directly over the intersection point of the conductors. Pressing the embossed key area causes contact and electrical continuity between the two conductors. For example, pressing the “1” key creates continuity between the Keypad connector pin 5 (column 3) and pin 13 (row 4). Since this connector is interfaced to the Microboard (J18), the Microboard senses this continuity as described below and concludes the “1” key is pressed.
The Microboard Program continuously scans the Keypad to determine if a key is pressed. Beginning with row 1 and proceeding through all rows, the Program places a “logic low” (<1VDC) on a row, a “logic high” (>4VDC) on the remaining rows and reads the columns. A logic low in any column indicates a key in that column and row is pressed. For example, if at the time row 4 is being driven low, if column 3 is low, then the Micro
concludes the key at coordinate of row 4 and column 3 is pressed. Since the coordinates of all keys are stored in the Microboard’s Program, it can identify which key is at this coordinate and responds accordingly. In this example the “1” key is pressed.
In order for the Microboard to reliably detect closed and open keys, each key must meet a closed circuit and open circuit resistance requirement. When a key is pressed, the contact resistance must be < 100 Ohms. When a key is not pressed, the contact resistance must be > 1 Meg Ohm. If the Microboard is not responding to a pressed key, or if it’s detecting a closed key when none are pressed, it could be because the contact resistance requirements are not being met. The operation of each key can be checked with an Ohmmeter. To check the open and closed contact resistance of any key, refer to the “Diagnostics and Troubleshooting” description in this book.
The Keypad is attached to the front of the Remote Control Center door with an adhesive backing. If service replacement is required, start at one corner and slowly peel the Keypad from the door. The rear side of the replacement Keypad is coated with an adhesive covered with a paper backing. Remove the paper backing, align the Display opening and apply the Keypad to the door.
5
91YORK INTERNATIONAL
Page 92
Service
FIG. 45 – KEYPAD
LD06756
YORK INTERNATIONAL92
Page 93
FORM 50.40-OM2
FIG. 46 – KEYPAD
LD04075
5
LD04076
93YORK INTERNATIONAL
Page 94
Service

POWER SUPPLY

(REFER TO FIG 47)
The Power Supply provides the DC power for the LCD Display and all the printed circuit boards in the Control Center. It receives a 100 to 250VAC input from an external power source and provides the following DC outputs:
• +12VDC
• +5VDC
• Ground
The +12VDC, Gnd and +5VDC outputs are applied to the Microboard. There, these voltages are applied to the circuits requiring the respective voltage. From the Microboard, the +12VDC and +5VDC are distributed to other system components requiring these voltages. These include the MicroGateway, LCD Display and Display Backlight Inverter Board.
As shown in Fig. 47, the Microboard contains two voltage regulators that create separate +5VDC and +3.3VDC supplies. The +5VDC supply is dedicated to all the Microboard Analog circuits and is labeled
as the +5VDC (Analog) supply. It is also routed to all Temperature Thermistors. This permits all Analog circuits to be powered by the same supply, eliminating any offsets caused by voltage regulator drift. The +3.3VDC supply is utilized by the Microprocessor, Flash Memory Card and other digital circuits. It could also be applied to the Backlight Inverter Board, depending on the Display manufacturer’s requirements as explained next.
Different Display manufacturers can require different supply voltages for their display and supporting circuits. To accommodate the different Display manufacturer’s voltage requirements, Microboard Program Jumpers JP2 and JP5 must be positioned to provide the required supply voltages to the Display and the Display Backlight Inverter Board. Either +5VDC or +3.3VDC, as determined by JP2, is applied to the Display. Either +12VDC or +5VDC, as determined by JP5, is applied to the Display Backlight Inverter Board. Refer to Table 2 “Microboard Program Jumpers”.
YORK INTERNATIONAL94
Page 95
DC
POWER
SUPPLY
MICRO
BOARD
MICROGATEWAY
LCD
DISPLAY
DISPLAY BACKLIGHT
INVERTER BOARD
+5VDC (ANALOG)
ALL TRANSDUCERS & THERMISTORS
+12VDC
GND
VDD (NOTE 1)
GND
+V (NOTE 2)
GND
+12VDC
GND
+5VDC
FORM 50.40-OM2
LD06757
5
NOTES:
1. +5 or +3.3VDC as determined by Microboard Program Jumper JP2
& display requirements.
& display requirements.
2. +12 or +5VDC as determined by Microboard Program Jumper JP5
FIG. 47 – POWER SUPPLY – DC POWER DISTRIBUTION (REFER TO CONTROL CENTER WIRING DIAGRAM FOR WIRE CONNECTIONS)
95YORK INTERNATIONAL
Page 96
Service

OFFLINE DIAGNOSTICS & TROUBLESHOOTING

(REFER TO FIG 48 & 49)
The problems that could be encountered in the Control Center are in the following categories:
• Keypad
• Display
• Serial Input/Output (I/O)
• Digital Input/Output (I/O)
• Analog Inputs
There is a Diagnostic and associated Troubleshooting procedure for each category. They are described on the following pages. The ofine diagnostics are accessed from the Diagnostics Main Screen, which is entered using the procedure below. If there is a Remote Control Center problem, determine the category of the problem. Then perform the applicable Diagnostic. If the Diagnostic reveals a malfunction, perform the Troubleshooting procedure to locate the defective component.
There are several documents that must be referred to while performing the Diagnostics and Troubleshooting procedures. Each procedure references the Section and gures of this book that describe the operation of the component being tested.
The Offline diagnostic screens are only available when the panel is powered on (or rebooted) with the Diagnostics Enable dip switch in the Enabled position. When in this mode all normal RCC functions are disabled. If the Diagnostics Enable dip switch is placed in the Disabled position while the panel is in the Ofine Diagnostics mode, the Diagnostics task will cause the panel to reboot into the online diagnostics mode.
YORK INTERNATIONAL96
Page 97

MAIN DIAGNOSTICS SCREEN

FORM 50.40-OM2
FIG. 48
Each of the Ofine Diagnostics is accessed from this screen. Press the appropriate key to select the desired diagnostic. After each diagnostic is performed, return to this MAIN Screen, from which the next diagnostic can be selected.
Some of the diagnostics have sub-screens that are accessed from the selected diagnostic screen. The sub-screens are shown indented:
Main screen
- Keypad test
- Display test
- Bit patterns test
- All red
- All green
- All blue
- All white
- All black
- Serial 1/0
- Digital 1/0
- Analog Inputs
00527VIPC
5
97YORK INTERNATIONAL
Page 98
Service

KEYPAD TEST

FIG. 49
This diagnostic is used to verify Keypad operation and the Microboard’s ability to respond to a pressed key. Refer to description of Keypad operation in Section 5 of this book.
Procedure
1. Press each keypad key. As the key is pressed, an illuminated LED is displayed corresponding to the key location on the keypad.
2. Press the DIAGNOSTICS key to return to the MAIN DIAGNOSTICS Screen.
Troubleshooting If an LED is not displayed when a key is pressed, the Keypad, Keypad ribbon cable or Microboard could be defective. Use the following procedure to locate the defective component.
1. Keypad a. Disconnect the ribbon cable from the Keypad.
b. Identify row/column coordinate of the key to
be tested. Refer to Figure 46.
00568VIPC
c. In the Keypad connector, locate the pins of
the row/column coordinate of the key of the key to be tested.
d. Insert the leads of an Ohmmeter into the pins
identied in step “c” above.
e. Press the key to be tested. If the contact
resistance is >100 Ohms, the Keypad is defec­tive.
f. Release the key. If the contact resistance is < 1
Meg Ohm, the Keypad is defective.
2. Ribbon Cable Using an Ohmmeter, perform a continuity test on all conductors in the ribbon cable. An open circuit would indicate the ribbon Cable is defective.
3. Microboard There are no checks or measurements to be made on the Microboard. If the Keypad and Ribbon Cable check OK per the above procedures, the Microboard is most likely the cause of the problem.
YORK INTERNATIONAL98
Page 99

DISPLAY TEST

FORM 50.40-OM2
FIG. 50
Each of the Display Diagnostics is accessed from this screen. After each diagnostic is performed, return to this screen, from which the next diagnostic can be selected. Refer to description of Display operation in Section 5 of this book.
PROCEDURE
1. Press the appropriate keypad key to perform the desired test from the list below.
2. Press the CANCEL (X) or ENTER (T) key to terminate test and return to DISPLAY TEST MAIN Screen, from which another test can be selected.
3. When all the desired tests have been performed, press the DIAGNOSTICS key to return to the MAIN DIAGNOSTICS Screen.
Bit Patterns - This test is used to detect
jitter and alignment defects. It veries proper operation and compatibility of the Microboard Display Controller with the display. Four vertical bars of green, dark blue, light blue and yellow, outlined by a red border are displayed. If the vertical bars are not stable or straight, or the red border is not completely visible, then either the Microboard Program Jumpers are not congured correctly for the installed display or the Microboard Display controller is defective. Refer to Figure 51.
All Red - This test veries the operation of all
of the red pixels. All of the red pixels are turned on to create a completely red screen. Any red
00528VIPC
pixels that do not turn on will appear as black dots on the display. If any black dots appear, rst ascertain it is not caused by dirt that is lodged between the display surface and the protective plastic cover. It is normal for a small number of randomly spaced pixels to not illuminate. It is not necessary to replace the display if a small number of black dots appear. They will not be visible on the normal screens displayed outside of this diagnostic mode. However, large black areas would be indicative of a defective display.
All Green - This test verifies the operation of all of the green pixels. All of the green pixels are turned on to create a completely green screen. Refer to description of “All Red” test above.
All Blue - This test veries the operation of all of the blue pixels. All of the blue pixels are turned on to create a completely blue screen. Refer to description of “All Red” test above.
All White - This test veries the display’s ability to turn on all pixels to display a completely white screen. Any pixel that does not turn on will appear as a black dot. Refer to description of “All Red” test above.
All Black - This test veries the display’s ability to turn off all pixels to display a completely black screen. Any pixel that does not turn off will appear as a red, green, blue or white dot. Refer to description “All Red” test above.
5
99YORK INTERNATIONAL
Page 100
Service

BIT PATTERNS TEST SCREEN

FIG. 51
TROUBLESHOOTING
If any of the above tests do not perform correctly as described above, perform the applicable procedure below:
Test Failed: Bit Patterns - If the vertical bars are not straight
or if the red border is not completely visible, either the Microboard Program Jumpers are not congured correctly or for the installed Display or the Microboard is defective.
All Red, All Green, All Blue, All White or All Black:
If these tests do not produce appropriate solid color screens, the Display Ribbon Cable, Display Interface Board, Microboard or Display could be defective. To locate the defective component perform tests in the following order:
1. Display Ribbon Cable: Using an Ohmmeter, perform a continuity
test on all conductors in the ribbon cable. An open circuit would indicate the ribbon cable is defective.
2. Display Interface Board: Using an Ohmmeter, perform a continuity test
on all conductors of the Interface Board. An open circuit would indicate the Interface Board is defective.
00529VIPC
3. Microboard: a. With the “All Red” test selected, the voltage
at Microboard J5-6 through J5-11 (Red drivers bits 0-5), as measured to Gnd, should be >
3.0VDC. If not, the Microboard is defective.
b. With the “All Green” test selected, the voltage
at Microboard J5-13 through J5-18 (Green drivers bits 0-5), as measured to Gnd, should be >3.0VDC. If not, the Microboard is defective.
c. With the “All Blue” test selected, the voltage at
Microboard J5-20 through J5-25 (Blue drivers bits 0-5), as measured to Grid, should be >3.0VDC. If not, the Microboard is defective.
d. With the “All White” test selected, the voltage at
Microboard J5-6 through J5-11, J5-13 through J5-18 and J5-20 through J5-25 should be >3.0VDC. If not, the Microboard is defective.
e. With “All Black” selected, the voltage at
Microboard J5-6 through J5-11, J5-13 through J5-18 and J5-20 through J5-25 should be <1.0VDC. If not, the Microboard is defective.
4. Display: If the Display Ribbon Cable, Display Interface
Board and Microboard check OK per the above procedures, the Display is most likely the cause of the problem.
YORK INTERNATIONAL100
Loading...