YOKOGAWA DpharpEJX vigilantplant EJX440A, DpharpEJX vigilantplant EJX110, DpharpEJX vigilantplant EJX430A, Dpharp EJX110A, Dpharp EJX130A User Manual

...
Page 1
User’s Manual
IM 01C25B01-01E
okogawa Electric Corporation
IM 01C25B01-01E
5th Edition
Page 2
CONTENTS
CONTENTS
1. INTRODUCTION............................................................................................1-1
Regarding This Manual.................................................................................1-1
1.1 Safe Use of This Product.................................................................... 1-2
1.2 Warranty.............................................................................................. 1-3
1.3 ATEX Documentation.......................................................................... 1-4
2. HANDLING CAUTIONS ................................................................................2-1
2.1 Model and Specifications Check......................................................... 2-1
2.2 Unpacking ........................................................................................... 2-1
2.3 Storage................................................................................................ 2-1
2.4 Selecting the Installation Location ...................................................... 2-2
2.5 Pressure Connection........................................................................... 2-2
2.6 Waterproofing of Cable Conduit Connections .................................... 2-2
2.7 Restrictions on Use of Radio Transceivers ........................................ 2-2
2.8 Insulation Resistance and Dielectric Strength Test............................ 2-2
2.9 Installation of an Explosion-Protected Instrument .............................. 2-3
2.9.1 FM Approval ................................................................................. 2-3
2.9.2 CSA Certification .......................................................................... 2-5
2.9.3 CENELEC ATEX (KEMA) Certification ........................................ 2-7
2.9.4 IECEx Certification ..................................................................... 2-10
2.10 EMC Conformity Standards .............................................................. 2-11
2.11 Pressure Equipment Directive (PED) ............................................... 2-11
2.12 Low Volage Directive ........................................................................ 2-12
3. COMPONENT NAMES .................................................................................. 3-1
4. INSTALLATION.............................................................................................4-1
4.1 Precautions ......................................................................................... 4-1
4.2 Mounting.............................................................................................. 4-1
4.3 Changing the Process Connection ..................................................... 4-2
4.4 Swapping the High/Low-pressure Side Connection ........................... 4-3
4.4.1 Rotating Pressure-detector Section 180°..................................... 4-3
4.4.2 Using the Communicator .............................................................. 4-3
4.5 Rotating Transmitter Section .............................................................. 4-4
4.6 Changing the Direction of Integral Indicator ....................................... 4-4
5. INSTALLING IMPULSE PIPING...................................................................5-1
5.1 Impulse Piping Installation Precautions .............................................. 5-1
5.1.1 Connecting Impulse Piping to a Transmitter................................ 5-1
5.1.2 Routing the Impulse Piping .......................................................... 5-2
5.2 Impulse Piping Connection Examples ................................................ 5-4
6. WIRING..........................................................................................................6-1
6.1 Wiring Precautions .............................................................................. 6-1
6.2 Selecting the Wiring Materials ............................................................ 6-1
6.3 Connections of External Wiring to Terminal Box................................ 6-1
6.3.1 Power Supply Wiring Connection ................................................ 6-1
FD No. IM 01C25B01-01E 5th Edition: July 2006(YK) All Rights Reserved, Copyright © 2004, Yokogawa Electric Corporation
i
IM 01C25B01-01E
Page 3
CONTENTS
6.3.2 External Indicator Connection ...................................................... 6-1
6.3.3 Communicator Connection........................................................... 6-1
6.3.4 Check Meter Connection .............................................................. 6-2
6.3.5 Status Output Connection ............................................................ 6-2
6.4 Wiring .................................................................................................. 6-2
6.4.1 Loop Configuration ....................................................................... 6-2
(1) General-use Type and Flameproof Type ..................................... 6-2
(2) Intrinsically Safe Type ................................................................. 6-2
6.4.2 Wiring Installation ......................................................................... 6-2
(1) General-use Type and Intrinsically Safe Type ............................. 6-2
(2) Flameproof T ype ......................................................................... 6-3
6.5 Grounding............................................................................................ 6-3
6.6 Power Supply Voltage and Load Resistance ..................................... 6-3
7. OPERATION..................................................................................................7-1
7.1 Preparation for Starting Operation...................................................... 7-1
7.2 Zero Point Adjustment ........................................................................ 7-2
7.2.1 Adjusting Zero Point for Differential Pressure Transmitters ........ 7-3
7.2.2
7.3 Starting Operation ............................................................................... 7-3
7.4 Shutting Down the Transmitter ........................................................... 7-4
7.5 Venting or Draining Transmitter Pressure-detector Section............... 7-4
7.5.1 Draining Condensate.................................................................... 7-4
7.5.2 Venting Gas.................................................................................. 7-4
7.6 Setting the Range Using the Range-setting Switch ........................... 7-5
Adjusting Zero Point for Gauge/Absolute Pressure Transmitters
.. 7-3
8. MAINTENANCE.............................................................................................8-1
8.1 Overview ............................................................................................. 8-1
8.2 Calibration Instruments Selection ....................................................... 8-1
8.3 Calibration ........................................................................................... 8-1
8.4 Disassembly and Reassembly............................................................ 8-3
8.4.1 Replacing the Integral Indicator ................................................... 8-3
8.4.2 Replacing the CPU Board Assembly ........................................... 8-4
8.4.3 Cleaning and Replacing the Capsule Assembly .......................... 8-4
8.4.4 Replacing the Process Connector Gaskets ................................. 8-5
8.5 Troubleshooting................................................................................... 8-6
8.5.1 Basic Troubleshooting.................................................................. 8-6
8.5.2 Troubleshooting Flowcharts ......................................................... 8-7
8.5.3 Alarms and Countermeasures ..................................................... 8-9
9. GENERAL SPECIFICATIONS ...................................................................... 9-1
9.1 Standard Specifications ...................................................................... 9-5
9.2 MODEL AND SUFFIX CODES........................................................... 9-4
9.3 OPTIONAL SPECIFICATIONS ......................................................... 9-10
9.4 DIMENSIONS.................................................................................... 9-13
REVISION RECORD
When using the EJX in a Safety Instrumented Systems(SIS) application, refer to Appendix A in either IM 01C25T01-01E for the HART protocol or IM 01C25T03-01E for the BRAIN protocol.
ii
IM 01C25B01-01E
Page 4
1. INTRODUCTION

1. INTRODUCTION

Thank you for purchasing the DPharp EJX Differential Pressure and pressure transmitter.
Your EJX Pressure Transmitter was precisely cali­brated at the factory before shipment. To ensure both safety and efficiency, please read this manual carefully before you operate the instrument.
NOTE
This manual describes the hardware configura­tions of EJX series transmitters. For information on the software configuration and operation, please refer to either IM 01C25T03-01E for the EJX series BRAIN communication type or IM 01C25T01-01E for the EJX series HART communication type.
For FOUNDATION Fieldbus protocol type, please refer to IM 01C25T02-01E.
To ensure correct use of this instrument, read both the hardware and software manuals thor­oughly before use.
WARNING
When using the EJX in a Safety Instrumented Systems (SIS) application, refer to Appendix A in either IM 01C25T01-01E for the HART protocol or IM 01C25T03-01E for the BRAIN protocol. The instructions and procedures in this section must be strictly followed in order to maintain the transmitter for this safety level.

Regarding This Manual

• This manual should be provided to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
•Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office.
• The specifications covered by this manual are limited to those for the standard type under the specified model number break-down and do not cover custom-made instruments.
• Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsi­bility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
NOTE
This manual covers the EJX110A and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter, and EJX310A absolute pressure transmitter. Unless otherwise stated, the illustrations in this manual are of the EJX110A differential pressure transmitter. Users of the other models should bear in mind that certain features of their instru­ment will differ from those shown in the illustra­tions of the EJX110A.
1-1
IM 01C25B01-01E
Page 5
1. INTRODUCTION
• The following safety symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against
unsafe practices
could
result in death or serious
.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.

1.1 Safe Use of This Product

For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be im­paired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an engi­neer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.
•With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.
• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process fluids.
•When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and the contact of toxic process fluids with the skin or eyes.
NOTE
Draws attention to information essential for understanding the operation and features.
Direct current
• When removing the instrument from a hazardous process, avoid contact with the fluid and the interior of the meter.
• All installation shall comply with local installation requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.
• Before connecting the power cables, please confirm that there is no current flowing through the cables and that the power supply to the instrument is switched off.
(c) Operation
• Wait 5 min. after the power is turned off, before opening the covers.
1-2
IM 01C25B01-01E
Page 6
1. INTRODUCTION
(d) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearest Yokogawa office.
•Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.
(e) Explosion Protected Type Instrument
•Users of explosion proof instruments should refer first to section 2.9 (Installation of an Explosion Protected Instrument) of this manual.
• The use of this instrument is restricted to those who have received appropriate training in the device.
• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.
(f) Modification
• Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument by the customer.

1.2 Warranty

•The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.
• If any problems are experienced with this instru­ment, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa office.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specification and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• The party responsible for the cost of fixing the problem shall be determined by Yokogawa follow­ing an investigation conducted by Yokogawa.
• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by the purchaser.
- Malfunction or damage due to a failure to handle, use, or store the instrument in accordance with the design specifications.
- Use of the product in question in a location not conforming to the standards specified by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modification or repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper relocation of the product in question after delivery.
- Reason of force majeure such as fires, earthquakes, storms/floods, thunder/lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
1-3
IM 01C25B01-01E
Page 7
1. INTRODUCTION

1.3 ATEX Documentation

This is only applicable to the countries in European Union.
GB
All instruction manuals for ATEX Ex related products are available in English, German and French. Should you require Ex related instructions in your local language, you are to contact your nearest Yokogawa office or representative.
DK
Alle brugervejledninger for produkter relateret til ATEX Ex er tilgængelige på engelsk, tysk og fransk. Skulle De ønske yderligere oplysninger om håndtering af Ex produkter på eget sprog, kan De rette henvendelse herom til den nærmeste Yokogawa afdeling eller forhandler.
I
Tutti i manuali operativi di prodotti ATEX contrassegnati con Ex sono disponibili in inglese, tedesco e francese. Se si desidera ricevere i manuali operativi di prodotti Ex in lingua locale, mettersi in contatto con l’ufficio Yokogawa più vicino o con un rappresentante.
E
Todos los manuales de instrucciones para los productos antiexplosivos de ATEX están disponibles en inglés, alemán y francés. Si desea solicitar las instrucciones de estos artículos antiexplosivos en su idioma local, deberá ponerse en contacto con la oficina o el representante de Yokogawa más cercano.
NL
SF
Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet ovat saatavilla englannin-, saksan- ja ranskankielisinä. Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita omalla paikallisella kielellännne, ottakaa yhteyttä lähimpään Yokogawa-toimistoon tai -edustajaan.
P
Todos os manuais de instruções referentes aos produtos Ex da ATEX estão disponíveis em Inglês, Alemão e Francês. Se necessitar de instruções na sua língua relacionadas com produtos Ex, deverá entrar em contacto com a delegação mais próxima ou com um representante da Yokogawa.
F
Tous les manuels d’instruction des produits ATEX Ex sont disponibles en langue anglaise, allemande et française. Si vous nécessitez des instructions relatives aux produits Ex dans votre langue, veuillez bien contacter votre représentant Yokogawa le plus proche.
D
Alle Betriebsanleitungen für ATEX Ex bezogene Produkte stehen in den Sprachen Englisch, Deutsch und Französisch zur Verfügung. Sollten Sie die Betriebsanleitungen für Ex-Produkte in Ihrer Landessprache benötigen, setzen Sie sich bitte mit Ihrem örtlichen Yokogawa-Vertreter in Verbindung.
S
Alla instruktionsböcker för ATEX Ex (explosionssäkra) produkter är tillgängliga på engelska, tyska och franska. Om Ni behöver instruktioner för dessa explosionssäkra produkter på annat språk, skall Ni kontakta närmaste Yokogawakontor eller representant.
Alle handleidingen voor producten die te maken hebben met ATEX explosiebeveiliging (Ex) zijn verkrijgbaar in het Engels, Duits en Frans. Neem, indien u aanwijzingen op het gebied van explosiebeveiliging nodig hebt in uw eigen taal, contact op met de dichtstbijzijnde vestiging van Yokogawa of met een vertegenwoordiger.
GR
       ATEX Ex   ,   .        Ex           Yokogawa   .
1-4
IM 01C25B01-01E
Page 8
2. HANDLING CAUTIONS

2. HANDLING CAUTIONS

This chapter provides important information on how to handle the transmitter. Read this carefully before using the transmitter.
EJX Series transmitters are thoroughly tested at the factory before shipment. When taking delivery of an instrument, visually check them to make sure that no damage occurred during shipment.
Also check that all transmitter mounting hardware shown in figure 2.1 is included. If the transmitter is ordered without the mounting bracket and the process connector, the transmitter mounting hardware will not be included. After checking the transmitter, carefully repack it in its box and keep it there until you are ready to install it.
Bolt Process connector Process connector
Gasket
U-bolt
(Note 1)

2.1 Model and Specifications Check

The model name and specifications are written on the name plate attached to the case.
F0202.EPS
Figure 2.2 Name Plate

2.2 Unpacking

Keep the transmitter in its original packaging to prevent it from being damaged during shipment. Do not unpack the transmitter until it reaches the installa­tion site.

2.3 Storage

The following precautions must be observed when storing the instrument, especially for a long period.
Mounting bracket (L type)
U-bolt nut
Figure 2.1 Transmitter Mounting Hardware
Transmitter mounting bolt
Mounting bracket (Flat type)
F0201.EPS
(a) Select a storage area which meets the following
conditions:
• It is not exposed to rain or subject to water seepage/leaks.
• Vibration and shock are kept to a minimum.
•It has an ambient temperature and relative humidity within the following ranges.
Ambient temperature:
–40 to 85°C without integral indicator –30 to 80°C with integral indicator
Relative humidity:
0% to 100% R.H.
Preferred temperature and humidity:
approx. 25°C and 65% R.H.
(b) When storing the transmitter, repack it carefully in
the packaging that it was originally shipped with.
(c) If the transmitter has been used, thoroughly clean
the chambers inside the cover flanges, so that there is no process fluid remaining inside. Before placing it in storage, also make sure that the pressure­detector is securely connected to the transmitter section.
2-1
IM 01C25B01-01E
Page 9
2. HANDLING CAUTIONS

2.4 Selecting the Installation Location

The transmitter is designed to withstand severe environmental conditions. However, to ensure that it will provide years of stable and accurate performance, take the following precautions when selecting the installation location.
(a) Ambient Temperature
Avoid locations subject to wide temperature variations or a significant temperature gradient. If the location is exposed to radiant heat from plant equipment, provide adequate thermal insulation and/or ventilation.
(b) Ambient Atmosphere
Do not install the transmitter in a corrosive atmo­sphere. If this cannot be avoided, there must be adequate ventilation as well as measures to prevent the leaking of rain water and the presence of standing water in the conduits.
(c) Shock and Vibration
Although the transmitter is designed to be relatively resistant to shock and vibration, an installation site should be selected where this is kept to a minimum.
(d) Installation of Explosion-protected Transmitters
An explosion-protected transmitters is certified for installation in a hazardous area containing specific gas types. See subsection 2.9 “Installation of an Explosion-Protected Transmitters.”
(b) Make sure that there are no leaks in the impulse
piping.
(c) Never apply a pressure higher than the specified
maximum working pressure.

2.6 Waterproofing of Cable Conduit Connections

Apply a non-hardening sealant to the threads to waterproof the transmitter cable conduit connections. (See figure 6.8, 6.9 and 6.10.)

2.7 Restrictions on Use of Radio Transceivers

IMPORTANT
Although the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitter or its external wiring, the transmitter may be affected by high frequency noise pickup. To test this, start out from a distance of several meters and slowly approach the transmitter with the trans­ceiver while observing the measurement loop for noise effects. Thereafter use the transceiver outside the range where the noise effects were first observed.

2.5 Pressure Connection

WARNING
•Never loosen the process connector bolts when an instrument is installed in a process. The device is under pressure, and a loss of seal can result in a sudden and uncontrolled release of process fluid.
•When draining toxic process fluids that have condensed inside the pressure detector, take appropriate steps to prevent the contact of such fluids with the skin or eyes and the inhalation of vapors from these fluids.
The following precautions must be observed in order to safely operate the transmitter under pressure.
(a) Make sure that all the process connector bolts are
tightened firmly.

2.8 Insulation Resistance and Dielectric Strength Test

Since the transmitter has undergone insulation resis­tance and dielectric strength tests at the factory before shipment, normally these tests are not required. If the need arises to conduct these tests, heed the following:
(a) Do not perform such tests more frequently than is
absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins.
(b) Never apply a voltage exceeding 500 V DC (100 V
DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding 500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test.
(c) Before conducting these tests, disconnect all signal
lines from the transmitter terminals. The procedure for conducting these tests is as follows:
2-2
IM 01C25B01-01E
Page 10
2. HANDLING CAUTIONS
• Insulation Resistance Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted SUPPLY terminals and the minus (–) leadwire to the grounding terminal.
3) Turn ON the insulation tester power and measure the insulation resistance. The voltage should be applied as briefly as possible to verify that the insulation resistance is at least 20 MΩ.
4) After completing the test and being very careful not to touch exposed conductors disconnect the insulation tester and connect a 100 kΩ resistor between the grounding terminal and the short­circuiting SUPPLY terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging.
• Dielectric Strength Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the dielectric strength tester. Then connect the tester between the shorted SUPPLY terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.
3) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to the specified voltage.
4) When the specified voltage is reached, hold it for one minute.
5) After completing this test, slowly decrease the voltage to avoid any voltage surges.
2.9 Installation of an Explosion-
Protected Instrument
NOTE
For FOUNDATION Fieldbus explosion protected type, please refer to IM 01C22T02-01E.
If a customer makes a repair or modification to an intrinsically safe or explosionproof instrument and the instrument is not restored to its original condition, its intrinsically safe or explosionproof construction may be compromised and the instrument may be hazardous to operate. Please contact Yokogawa before making any repair or modification to an instrument.
CAUTION
This instrument has been tested and certified as being intrinsically safe or explosionproof. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair. A failure to abide by these restrictions could make the instrument a hazard to operate.
WARNING
Maintaining the safety of explosionproof equip­ment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair. Please read the following sections very carefully.
WARNING
The range setting switch must not be used in a hazardous area.

2.9.1 FM Approval

a. FM Intrinsically Safe Type
Caution for FM intrinsically safe type. (Following contents refer “DOC. No. IFM022-A12”)
Note 1. Model EJX Series Differential, gauge and
absolute pressure transmitters with optional code /FS1 are applicable for use in hazardous locations.
• Applicable Standard: FM3600, FM3610, FM3611, FM3810
• Intrinsically Safe for Class I, Division 1, Groups A, B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1, Class I, Zone 0 in Hazardous Locations, AEx ia IIC
• Nonincendive for Class I, Division 2, Groups A, B, C & D. Class II, Division 2, Groups F & G and Class III, Division 1, Class I, Zone 2, Groups IIC, in Hazardous Locations.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
• Ambient temperature: –60 to 60°C
2-3
IM 01C25B01-01E
Page 11
2. HANDLING CAUTIONS
Note 2. Entity Parameters
• Intrinsically Safe Apparatus Parameters [Groups A, B, C, D, E, F and G] Vmax = 30 V Ci = 6 nF Imax = 200 mA Li = 0 µH Pmax = 1 W
* Associated Apparatus Parameters
(FM approved barriers) Voc ≤ 30 V Ca > 6 nF Isc 200 mA La > 0 µH Pmax 1W
• Intrinsically Safe Apparatus Parameters [Groups C, D, E, F and G] Vmax = 30 V Ci = 6 nF Imax = 225 mA Li = 0 µH Pmax = 1 W
* Associated Apparatus Parameters
(FM approved barriers) Voc ≤ 30 V Ca > 6 nF Isc 225 mA La > 0 µH Pmax 1 W
• Entity Installation Requirements Vmax Voc or Uo or Vt, Imax Isc or Io or It, Pmax (or Po) Pi, Ca or Co Ci + Ccable, La or Lo Li + Lcable
Note 3. Installation
• Barrier must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01.
• Control equipment connected to barrier must not use or generate more than 250 V rms or V dc.
• Installation should be in accordance with ANSI/ISA RP12.6 “Installation of Intrinsically Safe Systems for Hazardous (Classified) Locations” and the National Electric Code (ANSI/NFPA 70).
• The configuration of associated apparatus must be FMRC Approved.
• Dust-tight conduit seal must be used when installed in a Class II, III, Group E, F and G environments.
• Associated apparatus manufacturer’s installation drawing must be followed when installing this apparatus.
• The maximum power delivered from the barrier must not exceed 1 W.
• Note a warning label worded “SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY,” and “INSTALL IN ACCORDANCE WITH DOC. No. IFM022-A12”
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Intrinsically safe and Nonincendive Approval.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G Class 1, Zone 0 in Hazardous (Classified) Locations AEx ia IIC
EJX Series Pressure Transmitters Safety Barrier
+
Supply
Hazardous Location Nonhazardous Location
Class I, II, Division 2, Groups A, B, C, D, F, G Class III, Division 1. Class 1, Zone 2, Group IIC, in Hazardous (Classified) Locations
EJX Series Pressure Transmitters
Supply
[Nonincendive]
+ –
+
+
Not Use Safety Barrier
General Purpose Equipment
F0203-1.EPS
General Purpose Equipment
F0203-2.EPS
b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model EJX Series differential, gauge,
and absolute pressure transmitters with optional code /FF1 are applicable for use in hazardous locations.
• Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
• Explosionproof for Class I, Division 1, Groups B, C and D.
• Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G.
• Enclosure rating: NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with National Electrical Code ANSI/NFPA70 and Local Electrical Codes.
+ –
+ –
2-4
IM 01C25B01-01E
Page 12
2. HANDLING CAUTIONS
• When installed in Division 1, “FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”
Note 3. Operation
• Keep the “WARNING” nameplate attached to the transmitter. WARNING: OPEN CIRCUIT BEFORE REMOV­ING COVER. FACTORY SEALED, CONDUIT SEAL NOT REQUIRED. INSTALL IN ACCOR­DANCE WITH THE USERS MANUAL IM 01C25.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Explosionproof Approval.
c. FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJX Series pressure transmitters with optional code /FU1 can be selected the type of protection (FM Intrinsically Safe or FM Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other than the selected type of protection when the transmitter is installed.

2.9.2 CSA Certification

a. CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe and nonincendive type. (Following contents refer to “DOC No. ICS013-A13”)
Note 1. Model EJX Series differential, gauge, and
absolute pressure transmitters with optional code /CS1 are applicable for use in hazardous locations
Certificate: 1606623 [For CSA C22.2]
• Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.1010.1
• Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III, Division 1
• Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2, Groups E, F & G, Class III, Division 1
• Enclosure: Type 4X,
• Temp. Code: T4
• Amb. Temp.:–50 to 60°C
• Process Temperature: 120°C max.
[For CSA E60079]
• Applicable Standard: CAN/CSA E60079-0,
CAN/CSA E60079-11, CAN/CSA E60079-15, IEC 60529:2001-02
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature :–50 to 60°C
• Max. Process Temp.: 120°C
• Enclosure: IP66 and IP67
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Input Current (Imax/Ii) = 200 mA Maximum Input Power (Pmax/Pi) = 0.9 W Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH
• Type "n" or Nonincendive ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH
• Installation Requirements
Uo Ui, Io Ii, Po Pi, Co Ci + Ccable, Lo Li + Lcable Voc Vmax, Isc Imax, Ca Ci + Ccable, La Li + Lcable Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are parameters of barrier.
Note 3. Installation
• In any safety barreir used output current must be limited by a resistor 'R' such that Io=Uo/R or Isc=Voc/R.
• The safety barrier must be CSA certified.
• Input voltage of the safety barrier must be less than 250 Vrms/Vdc.
• Installation should be in accordance with Canadian Electrical Code Part I and Local Electrical Code.
• Dust-tight conduit seal must be used when installed in Class II and III environments.
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation and Yokogawa Corporation of America is prohibited and will void Canadian Standards Intrinsically safe and nonincendive Certification.
2-5
IM 01C25B01-01E
Page 13
2. HANDLING CAUTIONS
[Intrinsically Safe]
Hazardous Location Nonhazardous Location Group IIC, Zone 0 Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G EJX Series Pressure
Transmitters
+
Supply
Safety Barrier
+
+
General Purpose Equipment
+ –
F0204-1.EPS
[Nonincendive]
Hazardous Location Nonhazardous Location
Group IIC, Zone 2
Class I, II, Division 2, Groups A, B, C, D, E, F, G Class III, Division 1.
EJX Series Pressure
EJX Series Pressure
Transmitters
Transmitters
+
Supply
CSA Certified Equipment ([nL] or nonincendive)
+ –
Not Use Safety Barrier
F0204-2.EPS
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJX Series differential, gauge, and
absolute pressure transmitters with optional code /CF1 are applicable for use in hazardous locations:
Certificate: 1589701 [For CSA C22.2]
• Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,
C22.2 No.94, C22.2 No.61010.1-01
• Explosion-proof for Class I, Groups B, C and D.
• Dustignition-proof for Class II/III, Groups E, F and G.
• Enclosure: TYPE 4X
• Temperature Code: T6...T4
[For CSA E60079]
• Applicable Standard: CAN/CSA E60079-0,
CAN/CSA E60079-1
• Flameproof for Zone 1, Ex d IIC T6...T4
• Enclosure: IP66 and IP67
• Maximum Process Temperature: 120°C (T4), 100°C (T5), 85°C (T6)
• Ambient Temperature: –50 to 75°C (T4), –50 to 80°C (T5), –50 to 70°C (T6)
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc
Note 2. Wiring
[For CSA C22.2]
• All wiring shall comply with Canadian Electrical Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as shown in the figure.
• WARNING:
A SEAL SHALL BE INSTALLED WITHIN 50cm
OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
• WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL NOT
REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Non-Hazardous
Locations
Non-hazardous Location Equipment
42 V DC Max. 4 to 20 mA DC Signal
Non-Hazardous
Locations
Non-hazardous Location Equipment
42 V DC Max. 4 to 20 mA DC Signal
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Conduit
EJX Series
Hazardous Locations Division 2
Sealing Fitting
EJX Series
S U
P P
S U
P P
F0205.EPS
[For CSA E60079]
• All wiring shall comply with local installation requirements and local electrical code.
• In hazardous locations, the cable entry devices shall be of a certified flameproof type, suitable for the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable flameproof certified blanking elements. (The plug attached is flameproof certified.)
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5 MINUTES
BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5 MINUTES
AVANT D'OUVRIR.
• WARNING:
WHEN AMBIENT TEMPERATURE 65°C,
USE THE HEAT-RESISTING CABLES ≥ 90°C.
SE PUL
L Y
CK
CHE
RM
A L A
E S UL P
L Y
K C
E H C
M R A
L A
2-6
IM 01C25B01-01E
Page 14
2. HANDLING CAUTIONS
QUAND LA TEMPÉRATURE AMBIANTE
65°C, UTILISEZ DES CÂBLES RÉSISTANTES Á LA CHALEUR ≥ 90°C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation and Yokogawa Corporation of America is prohibited and will void Canadian Standards Explosionproof Certification.
c. CSA Intrinsically Safe Type/CSA
Explosionproof Type
Model EJX Series pressure transmitters with
optional code /CU1 can be selected the type of protection (CSA Intrinsically Safe or CSA Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other than the selected type of protection when the transmitter is installed.

2.9.3 CENELEC ATEX (KEMA) Certification

(1) Technical Data a. CENELEC ATEX (KEMA) Intrinsically Safe
Type
Caution for CENELEC ATEX (KEMA) Intrinsi­cally safe type.
Note 1. Model EJX Series differential, gauge, and
absolute pressure transmitters with optional code /KS2 for potentially explo­sive atmospheres:
• No. KEMA 03ATEX1544 X
• Applicable Standard: EN 50014, EN 50020, EN 50284, EN 50281-1-1
• Type of Protection and Marking code: EEx ia IIC T4
• Group: II
• Category: 1G, 1D
• Ambient Temperature for gas-proof: –50 to 60°C
• Process Temperature (Tp.): 120°C max.
• Maximum Surface Temperature for dust-proof:
T85°C (Tamb.: –40 to 60°C, Tp.: 80°C) T100°C (Tamb.: –40 to 60°C, Tp.: 100°C) T120°C (Tamb.: –40 to 60°C, Tp.: 120°C)
• Enclosure: IP66 and IP67
Note 2. Electrical Data
• In type of explosion protection intrinsic safety EEx ia IIC only for connection to a certified intrinsically safe circuit with following maximum values:
Ui = 30 V Ii = 200 mA Pi = 0.9 W Effective internal capacitance; Ci = 10 nF Effective internal inductance; Li = 0 mH
Note 3. Installation
• All wiring shall comply with local installation requirements. (Refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void KEMA Intrinsically safe Certification.
Note 5. Special Conditions for Safe Use
• In the case where the enclosure of the Pressure Transmitter is made of aluminium, if it is mounted in an area where the use of category 1 G apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
[Installation Diagram]
Hazardous Location
Transmitter
+
Supply
*1: In any safety barriers used the output current must be limited by a resistor “R” such that Imaxout-Uz/R.
Nonhazardous Location
+
Safety Barrier
F0208.EPS
*1
b. CENELEC ATEX (KEMA) Flameproof Type
Caution for CENELEC ATEX (KEMA) flameproof type.
Note 1. Model EJX Series differential, gauge, and
absolute pressure transmitters with optional code /KF2 for potentially explo­sive atmospheres:
• No. KEMA 03ATEX2570
• Applicable Standard: EN 50014, EN 50018, EN 50281-1-1
2-7
IM 01C25B01-01E
Page 15
2. HANDLING CAUTIONS
• Type of Protection and Marking Code: EEx d IIC T6...T4
• Group: II
• Category: 2G, 1D
• Temperature Class: T6, T5, and T4
• Enclosure: IP66 and IP67
• Ambient Temperature for gas-proof: –50 to 70°C (T6), –50 to 80°C (T5), and –50 to 75°C (T4)
• Maximum Process Temperature (Tp.) for gas-proof: 85°C (T6), 100°C (T5), and 120°C (T4)
• Maximum Surface Temperature for dust-proof: T80°C (Tamb.: –40 to 40°C, Tp.: 80°C) T100°C (Tamb.: –40 to 60°C, Tp.: 100°C) T120°C (Tamb.: –40 to 80°C, Tp.: 120°C)
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
• All wiring shall comply with local installation requirement.
• The cable entry devices shall be of a certified flameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep the “WARNING” label attached to the transmitter.
WARNING: AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP.65°C, USE HEAT-RESISTING CABLES90°C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or part replacement by other than an authorized representative of Yokogawa Electric Corporation is prohibited and will void KEMA Flameproof Certification.
c. CENELEC ATEX (KEMA) Intrinsically Safe
Type/CENELEC ATEX (KEMA) Flameproof Type/CENELEC ATEX Type n
Model EJX Series differential, gauge and absolute pressure transmitters with optional code /KU2 can be selected the type of protec­tion CENELEC ATEX (KEMA) Intrinsically Safe, Flameproof or CENELEC ATEX Type n for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this user’s manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
CENELEC ATEX Type of Protection “n”
• Applicable Standard: EN 60079-15:2003
• Referential Standards: IEC60079-0:1998, IEC 60079-11:1999
• Type of Protection and Marking Code: EEx nL IIC T4
• Temperature Class: T4
• Enclosure: IP66 and IP67
• Process Temperature: 120°C max.
• Ambient Temperature: –50 to 60°C
Note 1. Electrical Data
Ui = 30 V Effective internal capacitance; Ci = 10 nF Effective internal inductance; Li = 0 mH
Note 2. Installation
• All wiring shall comply with local installation requirements. (refer to the installation diagram)
Note 3. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Type of Protection “n”.
[Installation Diagram]
Hazardous Location
Transmitter
Ratings of the Power Supply as follows;
(Zone 2 only)
Supply
Maximum Voltage: 30 V
+ –
Nonhazardous Location
+
[EEx nL] Power Supply
F0209.EPS
CENELEC ATEX Type of Protection “Dust”
• Type of Protection and Marking Code: II 1D
• Maximum Surface Temperature:
T80°C (Tamb.: –40 to 40°C, Tp.: 80°C)
T100°C (Tamb.: –40 to 60°C, Tp.: 100°C) T120°C (Tamb.: –40 to 80°C, Tp.: 120°C)
2-8
IM 01C25B01-01E
Page 16
2. HANDLING CAUTIONS
WARNING
To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.
(2) Electrical Connection
A mark indicating the electrical connection type is stamped near the electrical connection port. These marks are as followed.
Location of the mark
F0210.EPS
(6) Name Plate
Name plate
Tag plate for flameproof type
D
WARNING
Tag plate for intrinsically safe type
D
Tag plate for type n protection
No. KEMA 03ATEX2570 EEx d IIC T6...T4 IP66 andIP67 TEMP. CLASS T6 T5 T4 MAX PROCESS TEMP.(Tp.) 85 100 120 °C Tamb. -50 to 70 80 75 °C T80°C(Tamb.:40°C, Tp.:80°C),T100°C(Tamb.:60°C, Tp.:100°C), T120°C(Tamb.:80°C, Tp.:120°C) Min.Tamb.:-40°C(for DUST)
AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP.  65°C, USE THE HEAT -RESISTING CABLES  90°C
No. KEMA 03ATEX1544 X EEx ia IIC T4 IP66 and IP67 Tamb. -50 to 60°C MIN. Tamb.:-40°C(for DUST) MAX. PROCESS TEMP.(Tp.) 120°C T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C) Ui=30V, Ii=200mA , Pi=0.9W, Ci=10nF, Li=0
EEx nLIIC T4 IP66 and IP67 Tamb. -50 to 60°C MAX. PROCESS TEMP.(Tp.) 120°C Ui=30V, Ci=10nF, Li=0
(3) Installation
WARNING
•All wiring shall comply with local installation requirements and the local electrical code.
•There is no need for conduit seal in Division 1 and Division 2 hazardous locations because this product is sealed at the factory.
(4) Operation
WARNING
•OPEN CIRCUIT BEFORE REMOVING COVER. INSTALL IN ACCORDANCE WITH THIS USER’S MANUAL
•Take care not to generate mechanical sparking when access to the instrument and peripheral devices in a hazardous location.
(5) Maintenance and Repair
WARNING
The instrument modification or parts replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certification.
F0211.EPS
MODEL: Specified model code. STYLE: Style code SUFFIX: Specified suffix code. SUPPLY: Supply voltage. OUTPUT: Output signal. MWP: Maximum working pressure. CAL RNG: Specified calibration range. NO.: Serial number and year of production*1. TOKYO 180-8750 JAPAN:
The manufacturer name and the ad­dress*2.
*1: The first ditital in the final three numbers of the serial number appearing after “NO.” on the nameplate indicates the year of production. The following is an example of a serial number for a product that was produced in 2004:
12A819857 432
The year 2004
*2: “180-8750” is a zip code which represents the following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
2-9
IM 01C25B01-01E
Page 17
2. HANDLING CAUTIONS

2.9.4 IECEx Certification

Model EJX Series pressure transmitters with
optional code /SU2 can be selected the type of protection (IECEx Intrinsically Safe/type n or flameproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
a. IECEx Intrinsically Safe Type / type n
Caution for IECEx Intrinsically safe and type n.
Note 1. Model EJX Series differential, gauge, and
absolute pressure transmitters with optional code /SU2 are applicable for use in hazardous locations
• No. IECEx CSA 05.0005
• Applicable Standard: IEC 60079-0:2000, IEC 60079-11:1999, IEC 60079-15:2001
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature :–50 to 60°C
• Max. Process Temp.: 120°C
• Enclosure: IP66 and IP67
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows: Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Input Current (Imax/Ii) = 200 mA Maximum Input Power (Pmax/Pi) = 0.9 W Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH
• Type "n" ratings are as follows: Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH
• Installation Requirements Uo Ui, Io Ii, Po Pi, Co Ci + Ccable, Lo Li + Lcable Voc Vmax, Isc Imax, Ca Ci + Ccable, La Li + Lcable Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are parameters of barrier.
Note 3. Installation
• In any safety barreir used output current must be
limited by a resistor 'R' such that Io=Uo/R.
• The safety barrier must be IECEx certified.
• Input voltage of the safety barrier must be less than 250 Vrms/Vdc.
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation and will void IECEx Intrinsically safe and type n certification.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Group IIC, Zone 0
EJX Series Pressure Transmitters
+
Supply
Hazardous Location Nonhazardous Location
Group IIC, Zone 2
EJX Series Pressure
EJX Series Pressure Transmitters
Transmitters
Supply
[type n]
+ –
IECEx certified Safety Barrier
+ –
Not Use Safety Barrier
+ –
General Purpose Equipment
+ –
F0213-1.EPS
IECEx Certified Equipment [nL]
+ –
F0213-2.EPS
b. IECEx Flameproof Type
Caution for IECEx flameproof type.
Note 1. Model EJX Series differential, gauge, and
absolute pressure transmitters with optional code /SF2 and /SU2 are appli­cable for use in hazardous locations:
• No. IECEx CSA 05.0002
• Applicable Standard: IEC60079-0:2000,
IEC60079-1:2001
• Flameproof for Zone 1, Ex d IIC T6...T4
• Enclosure: IP66 and IP67
• Maximum Process Temperature: 120°C (T4), 100°C (T5), 85°C (T6)
• Ambient Temperature: –50 to 75°C (T4), –50 to 80°C (T5), –50 to 70°C (T6)
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc
Note 2. Wiring
• In hazardous locations, the cable entry devices shall be of a certified flameproof type, suitable for the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable flameproof certified blanking elements.
2-10
IM 01C25B01-01E
Page 18
2. HANDLING CAUTIONS
Model
EJX110A
EJX110A
with code /PE3
EJX130A EJX130A
with code /PE3
EJX310A
EJX430A
EJX440A EJX440A
with code /PE3
EJX510A
EJX510A
with code /PE3
EJX530A
EJX510A
with code /PE3
Category
*2
Article 3, Paragraph 3
(SEP)
III
Article 3, Paragraph 3
(SEP)
III
Article 3, Paragraph 3
(SEP)
Article 3, Paragraph 3
(SEP)
Article 3, Paragraph 3
(SEP)
III
Article 3, Paragraph 3
(SEP)
III
Article 3, Paragraph 3
(SEP)
III
PS.V
(bar.L)
1.6
2.5
2.5
5.0
5.0
1.6
1.6
5.0
5.0
10 70
70 10
70 70
V(L)
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
PS
(bar)
*1
160 250
250
500
500 160
160
500 500
100 700
700 100
700 700
*1: PS is maximum allowable pressure for vessel itself. *2: Referred to Table 1 covered by ANNEX II of EC Directive on Pressure Equipment Directive 97/23/EC
T0202.EPS
Capsule
code
L
M, H M, H
M, H
M, H
M, A, B
H, A, B
C, D C, D
A, B, C
D D
A, B, C
D D
Note 3. Operation
• WARNING: AFTER DE-ENERGIZING, DELAY 5 MINUTES
BEFORE OPENING.
• WARNING: WHEN AMBIENT TEMPERATURE 65°C,
USE THE HEAT-RESISTING CABLES ≥ 90°C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void IECEx Certification.

2.10 EMC Conformity Standards

EN61326, AS/NZS CISPR11
CAUTION
Type of Equipment :Pressure Accessory - Vessel Type of fluid : Liquid and Gas Group of fluid : 1 and 2
To meet EMC regulations, Yokogawa recom­mends that customers run signal wiring through metal conduits or use shielded twisted-pair cabling when installing EJX series transmitters in a plant.

2.11 Pressure Equipment Directive (PED)

(1) General
• EJX series pressure transmitters are categorized as pressure accessories under the vessel section of
• EJX110A-M, EJX110A-H, EJX130A,
(2) Technical Data
• Models without /PE3
directive 97/23/EC, which corresponds to Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP).
EJX440A, EJX510A-D, and EJX530A-D can be used above 200 bar and therefore considered as a part of a pressure retaining vessel where category III, Module H applies. These models with option code /PE3 conform to that category.
Article 3, Paragraph 3 of PED, denoted as Sound
Engineering Practice (SEP).
• Models with /PE3
Module : H
(3) Operation
CAUTION
•The temperature and pressure of fluid should be maintained at levels that are consistent with normal operating conditions.
•The ambient temperature should be maintained at a level that is consistent with normal operating conditions.
•Please take care to prevent water hammer and the like from inducing excessive pressures in pipes and valves. If phenomena are likely, install a safety valve or take some other appropriate measure to prevent pressure from exceeding PS.
•Take appropriate measures at the device or system level to protect transmitters if they are to be operated near an external heat source.
2-11
IM 01C25B01-01E
Page 19

2.12 Low Voltage Directive

Applicable standard : EN61010-1
(1) Pollution Degree 2
"Pollution degree" describes the degree to which a
soild, liquid, or gas which deteriorates dielectric strength or surface resistivity is adhering. " 2 " applies to normal indoor atmosphere. Normally, only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by condenstaion must be expected.
(2) Installation Category I
"Overvoltage category(Installation category)"
describes a number which defines a transient overvoltage condition. It implies the regulattion for impulse withstand voltage. " I " applies to electrical equipment which is supplied from the circuit when appropriate transient overvoltage control means (interfaces) are provided.
2. HANDLING CAUTIONS
2-12
IM 01C25B01-01E
Page 20
3. COMPONENT NAMES
ED
ED
Vertical impulse piping type
Pressure-detector section

3. COMPONENT NAMES

Terminal box cover
Cover flange
Integral indicator
Mounting screw
Amplifier Cover
(Note 1)
(Note 2)
Slide switch
Range-setting
(Note 1)
switch (See section 7.6)
Transmitter section
Vent plug
CPU assembly
Burnout direction switch
BO H L WR E D
Drain plug
Horizontal impulse piping type
External indicator conduit connection
Process connector (Note 1)
(Note 1)
Conduit connection
Zero­adjustment screw
Process connection
Write protection switch
Burnout Direction
Switch Position
Burnout Direction
Burnout direction switch (BO)
HL
HIGH LOW
HL
Write Protection
Write Protection
Hardware write protection switch (WR)
Switch Position
H L ED
NO
(Write enabled)
H L ED
YES
(Write disabled)
F0301.EPS
Note 1: See subsection 9.2, “Model and Suffix Codes,” for details. A process connector will not be applied for lower side of EJX430A. Note 2: Applicable for BRAIN/HART communication type. Set the switches as shown in the figure above to set the burn-out direction
and write protection. The Burnout switch is set to the H side for delivery (unless option code /C1 or /C2 is specified in the order), and the hardware write protection switch is set to E side. The setting of the switches can be confirmed via communica­tion. An external zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating the hardware write protect function. See each communicaion manual.
Figure 3.1 Component Names
Table 3.1 Display Symbol
Display Symbol Meaning of Display Symbol
Display mode is ‘square root’. (Display is not lit when ‘linear’ mode.) The output signal being zero-adjusted is increasing. The output signal being zero-adjusted is decreasing. Write protect function is enabled.
T0301.EPS
3-1
IM 01C25B01-01E
Page 21
4. INSTALLATION

4 . INSTALLATION

4.1 Precautions

Before installing the transmitter, read the cautionary notes in section 2.4, “Selecting the Installation Loca­tion.” For additional information on the ambient conditions allowed at the installation location, refer to subsection 9.1 “Standard Specifications.”
IMPORTANT
• When welding piping during construction, take care not to allow welding currents to flow through the transmitter.
• Do not step on this instrument after installation.
• For the EJX430A and EJX440A, the atmo­spheric opening is located on the low pressure side cover flange. The opening must not face upward. See section 9.4, “Dimensions,” for the location of the opening.

4.2 Mounting

Vertical pipe mounting
U-bolt nut
Mounting bracket
Horizontal pipe mounting
Transmitter mounting bolt
U-bolt
50 mm(2-inch) pipe
Transmitter mounting bolt
The transmitter is shipped with the process connec-
tion, according to the ordering specifications. To change the orientation of the process connections, refer to section 4.3.
With differential pressure transmitters, the distance
between the impulse piping connection ports is usually 54 mm (figure 4.1). By changing the orientation of the process connector, the dimension can be changed to 51 mm or 57 mm.
The transmitter can be mounted on a nominal 50
mm (2-inch) pipe using the mounting bracket supplied, as shown in figure 4.2 and 4.3 The transmitter can be mounted on either a horizontal or a vertical pipe.
When mounting the bracket on the transmitter,
tighten the (four) bolts that hold the transmitter with a torque of approximately 39 N·m {4kgf·m}.
U-bolt nut
Mounting bracket
50 mm(2-inch) pipe
Figure 4.2 Transmitter Mounting (Horizontal Impulse
Piping Type)
U-bolt
F0402.EPS
57 mm 54 mm 51 mm
F0401.EPS
Figure 4.1 Process Connector Impulse Piping Connec-
tion Distances for Differential Pressure Transmitters
4-1
IM 01C25B01-01E
Page 22
4 . INSTALLATION
Vertical pipe mounting (Process connector downside)
U-bolt nut
Vertical pipe mounting (Process connector upside)
U-bolt nut
Transmitter mounting bolt
Mounting bracket
U-bolt
50 mm(2-inch) pipe
Mounting bracket
4.3 Changing the Process Con­nection
The transmitter is shipped with the process connection specified at the time of ordering. To change the process connection,the drain (vent) plug must be repositioned.
To reposition a drain (vent) plug, use a wrench to slowly and gently unscrew it. Then, remove and remount it on the opposite side. Wrap sealing tape around the drain (vent) plug threads (*1 in the figure below), and apply a lubricant to the threads of the drain (vent) screw(s) (*2 below). To tighten the drain (vent) plugs, apply a torque of 34 to 39 N·m {3.5 to 4 kgf·m}. Process connector bolts are to be tightened uniformly to a torque shown in table 4.1.
Table 4.1 Torque
Model
Torque(N·m) {kgf·m} {5 to 6}
Vertical impulse piping type Horizontal impulse piping type
EJX110A, EJX130A, EJX310A, EJX430A
39 to 49 {4 to 5}
EJX440A
C capsule D capsule
49 to 59
T0401.EPS
Transmitter mounting bolt
Figure 4.3 Transmitter Mounting (Vertical Impulse Piping
Type)
U-bolt
50 mm(2-inch) pipe
F0403.EPS
Bolt
Process
connector
Drain/vent plug
Figure 4.4 Changing Process Connection
gasket
1
Note: For a horizontal impulse
2
piping type, moving the process connectors from the front side to the back is not allowed.
F0404.EPS
4-2
IM 01C25B01-01E
Page 23
4 . INSTALLATION
4.4 Swapping the High/Low­pressure Side Connection
IMPORTANT
This section is applicable only for EJX110A and EJX130A differential transmitters, and not applicable for gauge or absolute pressure transmitters.
4.4.1 Rotating Pressure-detector Section
°
180
This procedure can be applied only to a transmitter with a vertical impulse piping type.
The procedure below can be used to turn the pressure detector assembly 180°. Perform this operation in a maintenance shop with the necessary tools laid out and ready for use, and then install the transmitter in the field after making the change.
1) Use an Allen wrench (JIS B4648, nominal 2.5 mm)
to remove the two setscrews at the joint between the pressure-detector section and transmitter section.
2) Leaving the transmitter section in position, rotate
the pressure-detector section 180°.
3) Tighten the two setscrews to fix the pressure-
detector section and transmitter section together (at a torque of 1.5 N·m). Reposition the process connector and drain (vent) plugs to the opposite side as described in subsection
4.3.
Process connector

4.4.2 Using the Communicator

This method is applicable only to the Model EJX110A and EJX130A.
With a communicator, you can change which process connection is used as the high-pressure side without mechanically rotating the pressure-detector section 180 as described in subsection 4.4.1. To change, call parameter ‘D15: H/L SWAP’ for BRAIN Communica­tion or ‘H/L swap’ for HART Communication and select REVERSE (right side: low pressure; left side: high pressure) or select NORMAL to change back to normal (right side: high pressure; left side: low pressure).
NORMAL
Output
Input
REVERSE
F0406.EPS
Figure 4.6 Input/Output Relationship
IMPORTANT
Since the H/L label plate on the capsule assem­bly will remain unchanged, use this function only when you cannot switch the impulse piping. If the ‘H/L SWAP’ parameter setting is changed, the input/output relationship is reversed as shown in figure 4.6; be sure this is understood by all. After reversing the setting, modify the H/L label plate to clearly indicate this change.
Setscrew
Before
Figure 4.5 Before and After Modification
After rotating 180°
F0405.EPS
4-3
IM 01C25B01-01E
Page 24
4 . INSTALLATION

4.5 Rotating T ransmitter Section

The transmitter section can be rotated approximately 360° (180° to either direction or 360° to one direction from the original position at shipment, depending on the configuration of the instrument.) It can be fixed at any angle within above range.
1) Remove the two setscrews that fasten the transmitter
section and capsule assembly, using the Allen wrench.
2) Rotate the transmitter section slowly and stop it at
designated position.
3) Tighten the two setscrews to a torque of 1.5 N·m.
IMPORTANT
Do not rotate the transmitter section more than the above limit.
Vertical impulse piping type
Pressure-detector section
Stopper
Rotate 0 to ±180° segments

4.6 Changing the Direction of Integral Indicator

IMPORTANT
Always turn OFF power, release pressure and remove a transmitter to non-hazardous area before disassembling and reassmbling an indicator.
An integral indicator can be installed in the following three directions. Follow the instructions in section 8.4 for removing and attaching the integral indicator.
F0408.EPS
Figure 4.8 Integral Indicator Direction
Conduit connection
Transmitter section
Horizontal impulse piping type
Transmitter section
Rotate 0 to ±180° segments
Conduit connection Zero-adjustment screw
Pressure-detector section
F0407.EPS
Figure 4.7 Rotating Transmitter Section (Left Side High
Pressure Type)
4-4
IM 01C25B01-01E
Page 25

5. INSTALLING IMPULSE PIPING

5. INSTALLING IMPULSE PIPING

5.1 Impulse Piping Installation Precautions

The impulse piping that connects the process outputs to the transmitter must convey the process pressure accurately. If, for example, gas collects in a liquid­filled impulse line, or the drain for a gas-filled impulse line becomes plugged, it will not convey the pressure accurately. Since this will cause errors in the measure­ment output, select the proper piping method for the process fluid (gas, liquid, or steam). Pay careful attention to the following points when routing the impulse piping and connecting the impulse piping to a transmitter.
5.1.1 Connecting Impulse Piping to a
Transmitter
(1) Check the High and Low Pressure Connec-
tions on the Transmitter (Figure 5.1)
Symbols “H” and “L” have been placed on the capsule assembly to indicate high and low pressure side. With differential pressure transmitters, connect the high pressure side impulse line to the “H” side, and the low pressure side impulse line to the “L” side.
With gauge/absolute pressure transmitters, connect the impulse line to the ‘H’ side.
Differential Pressure Transmitter
“H” and “L” are shown
Pressure
connection
Gauge/Absolute Pressure Transmitters
Figure 5.1 “H” and “L” Symbols on a Capsule
Assembly
Process connection Process connector
Bolt
“H” and “L” are shown
Process connection Process connector
Bolt
F0501.EPS
(2) Changing the Process Connector Piping
Connections (Figure 4.1) (for differential pressure transmitters)
The impulse piping connection distances can be changed between 51 mm, 54 mm and 57 mm by changing the orientation of the process connectors. This is convenient for aligning an impulse line with a process connectors.
(3) Tightening the Process Connector Mount-
ing Bolts
After connecting an impulse line, tighten the process connector mounting bolts uniformly.
(4) Removing the Impulse Piping Connecting
Port Dustproof Cap
The impulse piping connecting port on the transmitter is covered with a plastic cap to keep out dust. This cap must be removed before connecting the line. (Be careful not to damage the threads when removing this cap. Never insert a screwdriver or other tool between the cap and port threads to remove the cap.)
(5) Connecting the Transmitter and 3-Valve
Manifold (for differential pressure transmit­ters)
A 3-valve manifold consists of two stop valves to block process pressure and an equalizing valve to equalize the pressures on the high and low pressure sides of the transmitter. Such a manifold makes it easier to disconnect the transmitter from the impulse piping, and is convenient when adjusting the transmit­ter zero point.
There are two 3-valve manifold types: the pipe­mounting type and the direct-mounting type; care should be taken with respect to the following points when connecting the manifold to the transmitter.
Pipe-Mounting Type 3-Valve Manifold
(Figure 5.2)
1) Screw nipples into the connection ports on the transmitter side of the 3-valve manifold, and into the impulse piping connecting ports on the process connectors. (To maintain proper sealing, wind sealing tape around the nipple threads.)
2) Mount the 3-valve manifold on the 50 mm (2-inch) pipe by fastening a U-bolt to its mounting bracket. Tighten the U-bolt nuts only lightly at this time.
5-1
IM 01C25B01-01E
Page 26
3) Install the pipe assemblies between the 3-valve
NOTE
NOTE
manifold and the process connectors and lightly tighten the ball head lock nuts. (The ball-shaped ends of the pipes must be handled carefully, since they will not seal properly if the ball surface is scratched or otherwise damaged.)
4) Now tighten the nuts and bolts securely in the following sequence: Process connector bolts transmitter-end ball head lock nuts 3-valve manifold ball head lock nuts 3-valve manifold mounting bracket U-bolt nuts
Impulse piping Vent plug
(optional) Stop valve
(low pressure side) Equalizing valve
(balancing)
Stop valve (high pressure side)
50 mm(2-inch) pipe
Process connector bolts
Figure 5.2 3-Valve Manifold (Pipe-Mounting Type)
3-valve manifold
Pipes
Nipple
Ball head lock nut
Pipe
Ball head lock nut
Nipple Process
connector
5. INSTALLING IMPULSE PIPING
After completing the connection of the transmit­ter and 3-valve manifold, be sure to CLOSE the low pressure and high pressure stop valves, OPEN the equalizing valve, and leave the manifold with the equalizing valve OPEN. You must do this in order to avoid overloading the transmitter from either the high or the low pressure side when beginning operation. This instruction must also be followed as part of the startup procedure (chapter 7.)

5.1.2 Routing the Impulse Piping

(1) Process Pressure Tap Angles
If condensate, gas, sediment or other extraneous material in the process piping gets into the impulse piping, pressure measurement errors may result. To prevent such problems, the process pressure taps must be angled as shown in figure 5.4 according to the kind of fluid being measured.
F0502.EPS
Direct-Mounting Type 3-Valve Manifold
(Figure 5.3)
1) Mount the 3-valve manifold on the transmitter. (When mounting, use the two gaskets and the four bolts provided with the 3-valve manifold. Tighten the bolts evenly.)
2) Mount the process connectors and gaskets on the top of the 3-valve manifold (the side on which the impulse piping will be connected).
Bolts
Process
connector
Gasket
Stop valve
Equalizing
valve
Impulse
piping
3-valve
manifold
Stop valve
Equalizing valve
Stop valve
Impulse
piping
• If the process fluid is a gas, the taps must be vertical or within 45° either side of vertical.
• If the process fluid is a liquid, the taps must be horizontal or below horizontal, but not more than 45° below horizontal.
• If the process fluid is steam or other condens­ing vapor, the taps must be horizontal or above horizontal, but not more than 45° above hori- zontal.
[Gas]
45°
Pressure
taps
Process
piping
Figure 5.4 Process Pressure Tap Angle (For Horizontal
45°
45° 45°
Piping)
[Steam][Liquid]
45°
F0504.EPS
45°
Gasket
Process
connector
Figure 5.3 3-Valve Manifold (Direct-Mounting Type)
Bolts
Stop valve
3-valve manifold
F0503.EPS
5-2
IM 01C25B01-01E
Page 27
5. INSTALLING IMPULSE PIPING
NOTE
(2) Position of Process Pressure Taps and
Transmitter
If condensate (or gas) accumulates in the impulse piping, it should be removed periodically by opening the drain (or vent) plugs. However, this will generate a transient disturbance in the pressure measurement, and therefore it is necessary to position the taps and route the impulse piping so that any extraneous liquid or gas generated in the leadlines returns naturally to the process piping.
• If the process fluid is a gas, then as a rule the transmitter must be located higher than the process pressure taps.
• If the process fluid is a liquid or steam, then as a rule the transmitter must be located lower than the process pressure taps.
(3) Impulse Piping Slope
The impulse piping must be routed with only an upward or downward slope. Even for horizontal routing, the impulse piping should have a slope of at least 1/10 to prevent condensate (or gases) from accumulating in the pipes.
(6) Preventing Wind Speed Effects in Very
Low Differential Pressure Measurement (for differential pressure transmitters)
IMPORTANT
When using a differential pressure transmitter to measure very low pressures (draft pressure), the low pressure connection port is left open to atmospheric pressure (the reference pressure). Any wind around the differential pressure transmitter will therefore cause errors in the measurement. To prevent this, it will be neces­sary either to enclose the transmitter in a box, or to connect an impulse line to the low pres­sure side and insert its end into a wind-exclud­ing pot (cylindrical with a base plate).
(7) Preventing Freezing
If there is any risk that the process fluid in the impulse piping or transmitter could freeze, use a steam jacket or heater to maintain the temperature of the fluid.
(4) Temperature Difference Between Impulse
Lines (for differential pressure transmit­ters)
If there is a temperature difference between the high and low impulse lines, the density difference of the fluids in the two lines will cause an error in the measurement pressure. When measuring flow, impulse lines must be routed together so that there is no temperature difference between them.
(5) Condensate Pots for Steam Flow Measure-
ment (for differential pressure transmitters)
If the liquid in the impulse piping repeatedly condenses or vaporizes as a result of changes in the ambient or process temperature, this will cause a difference in the fluid head between the high pressure and low pressure sides. To prevent measurement errors due to these head differences, condensate pots are used when measuring steam flow.
After completing the connections, close the valves on the process pressure taps ( valves at the transmitter (
main valves
stop valves
), the
), and the impulse piping drain valves, so that condensate, sediment, dust and other extraneous material cannot enter the impulse piping.
5-3
IM 01C25B01-01E
Page 28
5. INSTALLING IMPULSE PIPING

5.2 Impulse Piping Connection Examples

Figure 5.5 and 5.6 show examples of typical impulse piping connections. Before connecting the transmitter to the process, study the transmitter installation location, the process piping layout, and the characteris­tics of the process fluid (corrosiveness, toxicity, flammability, etc.), in order to make appropriate changes and additions to the connection configurations.
Note the following points when referring to these piping examples.
• The high pressure connecting port on the transmit­ter is shown on the right (as viewed from the front).
• The transmitter impulse piping connection is shown for a vertical impulse piping connection configura­tion in which the direction of connection is either upwards or downwards.
• If the impulse line is long, bracing or supports should be provided to prevent vibration.
• The impulse piping material used must be compat­ible with the process pressure, temperature, and other conditions.
•A variety of process pressure tap valves (main valves) are available according to the type of connection (flanged, screwed, welded), construction (globe, gate, or ball valve), temperature and pressure. Select the type of valve most appropriate for the application.
Liguid
Tap
valve
Union
or flange
Tee
3-valve
manifold
Drain valve
Union or flange
Pipe
Figure 5.5 Impulse Piping Connection Examples for
Differential Pressure Transmitters
Orifice
Drain
plug
Open tank
Tap valve
Tee
Drain valve Drain plug
Gas
Liquid Level - Closed TankLiquid Level - Open Tank
3-valve
manifold
Steam
Condensate pot
Vent plug
Closed tank
F0505.EPS
Liquid Gas Steam
Tap valve
Union or flange
Union or
flange
Tee
Union or flange
Tap valve
Drain valve Drain plug
Figure 5.6 Impulse Piping Connection Examples for
Gauge/absolute Pressure Transmitters
Union or flange
Drain plug Drain valve
Tee
5-4
Tap valve
Tee
Drain valve Drain plug
F0506.EPS
IM 01C25B01-01E
Page 29
6. WIRING

6. WIRING

6.1 Wiring Precautions

IMPORTANT
• Lay wiring as far as possible from electrical noise sources such as large capacity transform­ers, motors, and power supplies.
• Remove the electrical connection dust cap before wiring.
• All threaded parts must be treated with water­proofing sealant. (A non-hardening silicone group sealant is recommended.)
• To prevent noise pickup, do not pass signal and power cables through the same ducts.
• Explosion-protected instruments must be wired in accordance with specific requirements (and, in certain countries, legal regulations) in order to preserve the effectiveness of their explosion­protected features.
• The terminal box cover is locked by an Allen head bolt (a shrouding bolt) on ATEX flameproof type transmitters. When the shroud­ing bolt is driven clockwise using an Allen wrench, it goes in. The cover lock can then be released and the cover can be opened by hand. See subsection 8.4 “Disassembly and Reassembly” for details.
• Plug and seal an unused conduit connection.

6.3 Connections of External Wiring to Terminal Box

6.3.1 Power Supply Wiring Connection

Connect the power supply wiring to the SUPPLY + and – terminals. When /AL is specified, also refer to subsection 6.3.5.
+
Power supply
Figure 6.1 Power Supply Wiring Connection

6.3.2 External Indicator Connection

Available only when /AL is not specified. Connect wiring for external indicators to the CHECK +
and – terminals.
(Note) Use a external indicator whose internal resistance is 10 Ω or
less.
Power supply
+
Transmitter terminal box
E
S
L
U
P
S
UP
P
L
Y
CHECK
ARM
AL
External indicator
E
S
L
U
P
SUP
P
L
Y
K
EC
H
C
M
R
ALA
F0601.EPS
6.2 Selecting the Wiring Materi­als
(a) Use stranded leadwires or cables which are the
same as or better than 600 V grade PVC insulated wire (JIS C3307) or its equivalent.
(b) Use shielded wires in areas that are susceptible to
electrical noise.
(c) In areas with higher or lower ambient temperatures,
use appropriate wires or cables.
(d) In environment where oils, solvents, corrosive gases
or liquids may be present, use wires or cables that are resistant to such substances.
(e) It is recommended that crimp-on solderless terminal
lugs (for 4 mm screws) with insulating sleeves be used for leadwire ends.
Transmitter terminal box
Figure 6.2 External Indicator Connection

6.3.3 Communicator Connection

Connect the BT200 or HART275 HHT to the SUPPLY + and – terminals. (Use hooks.)
Transmitter terminal box
BT200
Figure 6.3 BT200 Connection
6-1
PULSE
SU
PPL
Y
K
EC
H
C
M
R
ALA
+
Power supply
Ignore the polarity since the BT200 is AC-coupled to the terminal box.
IM 01C25B01-01E
F0602.EPS
F0603.EPS
Page 30
6. WIRING

6.3.4 Check Meter Connection

Available only when /AL is not specified. Connect the check meter to the CHECK + and –
terminals. (Use hooks.)
•A 4 to 20 mA DC output signal from the CHECK +
and – terminals.
(Note) Use a check meter whose internal resistance is 10 or less.
Check meter
Figure 6.4 Check Meter Connection
Transmitter terminal box
E LS
PU
S
U
P
P
L
Y
K
C
E
H
C
M
R
ALA
Power supply
+
F0604.EPS

6.3.5 Status Output Connection

When option code /AL is specified, connect the external wiring as shown in Figure 6.3.5.
To configure and activate the process alarm function and status output, it is necessary to set some param­eters. Refer to each communication manual for procedures.
(1) General-use Type and Flameproof Type
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor (Power supply unit)
PULSE
SUPPLY
CHECK
ALARM
Receiver instrument
F0606.EPS
Figure 6.6 Connection between Transmitter and
Distributor
(2) Intrinsically Safe Type
With the intrinsically safe type, a safety barrier must be included in the loop.
Hazardous Location Nonhazardous Location
Transmitter terminal box
E
S
L
U
P
S
U
P
P
LY
K
C
E
H
C
M
R
A
L
A
Distributor (Power supply unit)
Receiver instrument
Transmitter
terminal box
E
S
L
U
P
S
U
P
P
L
Y
K
C
E
H
C
M
R
A
L
A
Shielded cable
External power
24V DC
+
250
Distributor
Magnetic
valve
supply 30V DC, 120mA max
Use two-wire separately shielded cables.
AC power supply
F0605.EPS
Figure 6.5 Status Output Connection

6.4 Wiring

6.4.1 Loop Configuration

Since the DPharp uses a two-wire transmission system, signal wiring is also used as power wiring.
DC power is required for the transmitter loop. The transmitter and distributor are connected as shown below.
For details of the power supply voltage and load resistance, see section 6.6; for communications line requirements, see section 9.1.
Safety barrier
Figure 6.7 Connection between Transmitter and
Distributor

6.4.2 Wiring Installation

(1) General-use Type and Intrinsically Safe
Type
With the cable wiring, use a metallic conduit or waterproof glands.
• Apply a non-hardening sealant to the terminal box connection port and to the threads on the flexible metal conduit for waterproofing.
Flexible metal conduit
Apply a non-hardening
Wiring metal conduit
Tee
Drain plug
Figure 6.8 Typical Wiring Using Flexible Metal Conduit
sealant to the threads for waterproofing.
F0608.EPS
F0607.EPS
6-2
IM 01C25B01-01E
Page 31
6. WIRING
(2) Flameproof Type
Wire cables through a flameproof packing adapter, or use a flameproof metal conduit.
Wiring cable through flameproof packing adapter.
• Apply a non-hardening sealant to the terminal box connection port and to the threads on the flameproof packing adapter for waterproofing.
Flameproof packing adapter
Flexible metal conduit
Wiring metal conduit
Apply a non-hardening sealant to the threads for waterproofing.
Tee
Drain plug
F0609.EPS
Figure 6.9 Typical Cable Wiring Using Flameproof Packing
Adapter
Flameproof metal conduit wiring
•A seal fitting must be installed near the terminal box connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of the terminal box connection port, flexible metal conduit and seal fitting for waterproofing.

6.5 Grounding

Grounding is always required for the proper operation of transmitters. Follow the domestic electrical require­ments as regulated in each country. For a transmitter with a built-in lightning protector, grounding should satisfy ground resistance of 10or less.
Ground terminals are located on the inside and outside of the terminal box. Either of these terminals may be used.
PULSE
S
U
P
P
L
Y
K
C
E
H
C
M
R
A
L
Ground terminal (inside)
Ground terminal (outside)
Figure 6.11 Ground Terminals
A
F0611.EPS

6.6 Power Supply Voltage and Load Resistance

Non-hazardous area
Gas sealing device
Flameproof flexible metal conduit
Hazardous area Flameproof
heavy-gauge steel conduit
Tee
Drain plug
Seal fitting
After wiring, impregnate the fitting with a compound to seal tubing.
Apply a non-hardening sealant to the threads of these fittings for waterproofing
Figure 6.10 Typical Wiring Using Flameproof Metal
Conduit
F0610.EPS
When configuring the loop, make sure that the external load resistance is within the range in the figure below.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.
600
External
load
resistance
R (Ω)
250
0 10.5 16.6 25.2 42
Figure 6.12 Relationship between Power Supply Voltage
and External Load Resistance
E–10.5
R=
0.0244
Power supply voltage E (V DC)
Communication
applicable range
BRAIN and HART
F0612.EPS
6-3
IM 01C25B01-01E
Page 32
7. OPERATION

7. OPERATION

7.1 Preparation for Starting Operation

This section describes the operation procedure for the EJX110A as shown in figure 7.1a (vertical impulse piping type, high-pressure connection: right side) when measuring the liquid flow rate, and EJX430A and EJX310A as shown in figure 7.1b when measuring pressure.
NOTE
Check that the process pressure tap valves, drain valves, and 3-valve manifold stop valves on both the low pressure and high pressure sides are closed, and that the 3-valve manifold equalizing valve is opened.
(a) Follow the procedures below to introduce process
pressure into the impulse piping and transmitter.
Differential Pressure Transmitters
1) Open the low pressure and high pressure tap valves
to fill the impulse piping with process liquid.
2) Slowly open the high pressure stop valve to fill the
transmitter pressure-detector section with process liquid.
3) Close the high pressure stop valve.
4) Gradually open the low pressure stop valve and
completely fill the transmitter pressure-detector section with process liquid.
5) Close the low pressure stop valve.
6) Gradually open the high pressure stop valve. At this
time, equal pressure is applied to the low and high pressure sides of the transmitter.
7) Check that there are no liquid leaks in the impulse
piping, 3-valve manifold, transmitter, or other components.
Gauge/Absolute Pressure Transmitters
1) Open the tap valve (main valve) to fill the impulse
piping with process fluid.
2) Gradually open the stop valve to introduce process
fluid into the transmitter pressure-detector section.
3) Confirm that there is no pressure leak in the
impulse piping, transmitter, or other components.
Venting Gas from the Transmitter Pressure­detector Section
• Since the piping in the example of figure 7.1 is constructed to be self-venting, no venting operation is required. If it is not possible to make the piping self­venting, refer to subsection 7.5 for instructions. Leave the equalizing valve open even after venting gas.
(b) Turn ON power and connect the communicator.
Open the terminal box cover, and connect the communicator to the SUPPLY + and – terminals.
(c) Using the communicator, confirm that the transmit-
ter is operating properly. Check parameter values or change the setpoints as necessary. See IM 01C25T03-01E (BRAIN communication) or IM 01C25T01-01E (HART communication) for communicator operation. If the transmitter is equipped with an integral indicator, its indication can be used to confirm that the transmitter is operating properly.
Orifice
Tap valve
Tap valve (low pressure)
Stop valve (low pressure)
Equalizing valve
Stop valve (high pressure)
Figure 7.1a Liquid Flow Measurement
3-valve manifold
Drain valve (high pressure)
(high pressure)
F0701a.EPS
7-1
IM 01C25B01-01E
Page 33
7. OPERATION
NOTE
NOTE
Vent plug (Fill plug)
Tap valve
Stop valve
Drain valve
F0701b.EPS
Figure 7.1b Liquid Pressure Measurement
Confirming that Transmitter is Operating
Properly
Using the BT200
• If the wiring system is faulty, ‘communication error’ appears on the display.
• If the transmitter is faulty, ‘SELF CHECK ERROR’ appears on the display.
If any of the above errors are indicated on the display of the integral indicator or the communi­cator, refer to subsection 8.5.3 for the corrective action.
Verify and Change Transmitter Parameter
Setting and Values
The parameters related to the following items are set at factory as specified in order.
• Calibration range
• Integral indicator display
•Output mode
• Software damping (optional) Other parameters like following are shipped with the default setting.
• Low-cut
• Process alarm setting
• Static pressure range
• Signal characterizer
•Write protection To confirm or change the values, see IM 01C25T01­01E or 01C25T03-01E.
PARAM C60:SELF CHECK ERROR
communication error
DATA DIAG PRNT ESC
Communication error (Faulty wiring)
Figure 7.2 BT200 Display
Self-diagnostic error (Faulty transmitter)
F0702.EPS
Using the integral indicator
• If the wiring system is faulty, the display stays blank.
• If the transmitter is faulty, an error code is displayed.
Self-diagnostic error on the integral indicator (Faulty transmitter)
Figure 7.3 Integral Indicator with Error Code
F0703.EPS

7.2 Zero Point Adjustment

After completing preparations for operating the transmitter, adjust the zero point.
Zero point adjustment can be done by turning the transmitter’s zero-adjustment screw or by using the communicator. This section describes the procedure for the zero-adjustment screw. For the communicator procedure, see the communication manual.
IMPORTANT
Do not turn off the power to the transmitter immediately after performing a zero point adjust­ment. Powering off within 30 seconds of per­forming this procedure will return the zero point to its previous setting.
Before performing this adjustment, make sure that the external zero adjustment function has NOT been disabled by a parameter setting.
To check the output signal, use a digital multimeter, calibrator, or communicator.
7-2
IM 01C25B01-01E
Page 34

7.2.1 Adjusting Zero Point for Differential Pressure Transmitters

Before adjusting zero point, make sure that the equaliz­ing valve is open.
7. OPERATION
(2)
When you cannot obtain the Low Range Value from the actual measured value of 0%;
Adjust the transmitter output to the actual measured value obtained by a digital manometer or a glass gauge.
[Example]
The measuring range of 50 to 250 kPa; the actual measured value of 130 kPa.
Zero-adjustment screw cover
F0704.EPS
Figure 7.4 External Zero Adjustment Screw
The zero-adjustment screw is located inside the cover. Use a slotted screwdriver to turn the zero-adjustment screw. Equalize the transmitter, then turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of 0.01% of the setting range. The degree of zero adjustments varies with the screw turning speed; turn the screw slowly to make a fine adjustment, quickly to make a rough adjustment.
When using differential pressure transmitters for level measurement and if you cannot obtain the lower range value from the actual measurement value of 0%, refer to subsection 7.2.2(2).

7.2.2 Adjusting Zero Point for Gauge/ Absolute Pressure Transmitters

(1) When you can obtain the Low Range
Value from the actual measured value of 0% (0 kPa, atmospheric pressure);
For pressure measurement using gauge pressure transmitters, follow the steps below before performing zero point adjustment.
1) Close the tap valve (main valve).
2) Loosen the fill plug so that the pressure applied to
the transmitter is only the head of the seal liquid.
3) Adjust the zero point at this status.
4) After the adjustment, close the fill plug and then
gradually open the tap valve.
Use a slotted screwdriver to turn the zero-adjustment screw. Turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of
0.01% of the setting range. Since the degree of the zero
adjustment varies with the screw turning speed, turn the screw slowly to make a fine adjustment and quickly to make a rough adjustment.
Actual measured value= x 100=40.0%
130–50 250–50
(=10.4mA)
Turn the screw to match the output signal to the actual measured value.

7.3 Starting Operation

After completing the zero point adjustment, follow the procedures below to start operation. Steps 1) and 2) are specific to the differential pressure transmitters.
1) Close the equalizing valve.
2) Gradually open the low pressure stop valve. This places the transmitter in an operational condition.
3) Confirm the operating status. If the output signal exhibits wide fluctuations (hunting) due to periodic variation in the process pressure, use the communi­cator to dampen the transmitter output signal. Confirm the hunting using a receiving instrument or the integral indicator, and set the optimum damping time constant.
4) After confirming the operating status, perform the following.
IMPORTANT
• Remove the communicator from the terminal box, and confirm that none of the terminal screws are loose.
• Close the terminal box cover and the amplifier cover. Screw each cover in tightly until it will not turn further.
• There are two covers that must be locked on the ATEX Flameproof type transmitters. An Allen head bolt (shrouding bolt) under the edge of each cover is used to lock the cover. When the shrouding bolt is driven counterclockwise with an Allen wrench, the bolt rotates upward and locks the cover. (See section 8.4.) After locking the covers, confirm that they are secure and cannot be opened by hand. Tighten the zero-adjustment cover mounting screw to secure the cover.
7-3
IM 01C25B01-01E
Page 35
7. OPERATION
• Tighten the zero-adjustment cover mounting screw to secure the cover.

7.4 Shutting Down the Transmitter

Shut down the transmitter as follows. Steps 2) and 3) are specific to the differential pressure transmitters.
1) Turn off the power.
2) Close the low pressure stop valve.
3) Open the equalizing valve.
4) Close the high pressure stop valve.
5) Close the high pressure and low pressure tap
valves.
NOTE
•Whenever shutting down the transmitter for a long period, remove any process fluid that is in the transmitter pressure-detector section.
•The equalizing valve must be left OPEN.

7.5.1 Draining Condensate

1) Gradually open the drain screw or drain plug and drain the transmitter pressure-detector section. (See figure 7.5.)
2) When all accumulated liquid is completely re­moved, close the drain screw or drain plug.
3) Tighten the drain screw to a torque of 10 N·m, and the drain plug to a torque of 34 to 39 N·m.
Drain plug
Drain screw
When you loosen the drain screw or drain plug, the accumulated liquid will be expelled in the direction of the arrow.
F0705.EPS
Figure 7.5 Draining the Transmitter
7.5 Venting or Draining Transmit­ter Pressure-detector Section
Since this transmitter is designed to be self-draining and self-venting with vertical impulse piping connec­tions, neither draining nor venting will be required if the impulse piping is configured appropriately for self­draining or self-venting operation.
If condensate (or gas) collects in the transmitter pressure-detector section, the measured pressure may be in error. If it is not possible to configure the piping for self-draining (or self-venting) operation, you will need to loosen the drain (vent) screw on the transmitter to completely drain (vent) any stagnated liquid (gas.)
However, since draining condensate or bleeding off gas disturbs the pressure measurement, this should not be done when the loop is in operation.
WARNING
Since the accumulated liquid (or gas) may be toxic or otherwise harmful, take appropriate care to avoid contact with the body, or inhalation of vapors.

7.5.2 Venting Gas

1) Gradually open the vent screw to vent gas from the transmitter pressure-detector section. (See figure
7.6.)
2) When the transmitter is completely vented, close the vent screw.
3) Tighten the vent screw to a torque of 10 N·m.
Vent screw
Vent screw
When you loosen the vent screw, the gas escpes in the direction of the arrow.
Figure 7.6 Venting the Transmitter
F0706.EPS
7-4
IM 01C25B01-01E
Page 36
7. OPERATION

7.6 Setting the Range Using the Range-setting Switch

WARNING
The range setting switch must not be used in the hazardous area. When it is necessary to use the switch, operate it in a non-hazardous location.
When pressure is applied to the transmitter, the low­and high-limit values for the measurement range (LRV and URV) can be changed (re-ranged) using the range­setting switch (push-button) located on the optional integral indicator plate and the external zero adjustment screw. This procedure does not require use of the communicator. However, changes in the scale range and engineering unit display settings for the integral indicator require use of the communicator.
Follow the procedure below to change the LRV and URV settings.
[Example]
Rerange LRV to 0 and URV to 3 MPa.
1) Connect the transmitter and apparatus as shown in
Figure 8.1 and warm it up for at least five minutes.
2) Press the range-setting push-button.
The integral indicator then displays “LRV.SET.”
3) Apply a pressure of 0 kPa (atmospheric pressure) to
the transmitter.
4) Turn the external zero-adjustment screw in the
desired direction. The integral indicator displays the output signal in %.
5) Adjust the output signal to 0% (1 V DC) by rotating
the external zero-adjustment screw. Doing so completes the LRV setting.
6) Press the range-setting push-button. The integral
indicator then displays “URV.SET.”
7) Apply a pressure of 3 MPa to the transmitter.
8) Turn the external zero-adjustment screw in the
desired direction. The integral indicator displays the output signal in %.
9) Adjust the output signal to 100% (5 V DC) by
rotating the external zero-adjustment screw. Doing so completes the URV setting.
10) Press the range-setting push-button. The transmitter
then switches back to the normal operation mode with the measurement range of 0 to 3 MPa.
(Note 1)
(Note 2)
(Note 1)
(Note 2)
Note 1: Wait until the pressure inside the pressure-detector section
has stabilized before proceeding to the next step.
Note 2: If the pressure applied to the transmitter exceeds the previous
LRV (or URV), the integral indicator may display error number “AL.30” (In this case, the output signal percent and “AL.30” are displayed alternately every two seconds). Although “AL.30” is displayed, you may proceed to the next step. However, should any other error number be displayed, take the appropriate measure in reference to , “Errors and Countermeasures” in each communication manual.
IMPORTANT
• Do not turn off the power to the transmitter immediately after completion of the change in the LRV and/or URV setting(s). Note that powering off within thirty seconds after setting will cause a return to the previous settings.
• Changing LRV automatically changes URV to the following value.
URV = previous URV + (new LRV – previous LRV)
• If the range-setting push-button and external zero-adjustment screw are not touched during a range-change operation, the transmitter auto­matically switches back to the normal operation mode.
Integral indicator
Note : Use a thin bar which
has a blunt tip, e.g., a hexagonal wrench, to press the range­setting push-button
Range-setting switch (Push-button)
Figure 7.7 Range-setting Switch
F0707.EPS
7-5
IM 01C25B01-01E
Page 37
8. MAINTENANCE

8. MAINTENANCE

8.1 Overview

WARNING
Since the accumulated process fluid may be toxic or otherwise harmful, take appropriate care to avoid contact with the body or inhalation of vapors when draining condensate or venting gas from the transmitter pressure-detector section and even after dismounting the instru­ment from the process line for maintenance.
Maintenance of the transmitter is easy due to its modular construction. This chapter describes the procedures for calibration, adjustment, and the disas­sembly and reassembly procedures required for component replacement.
Transmitters are precision instruments. Please carefully and thoroughly read the following sections for informa­tion on how to properly handle them while performing maintenance.
IMPORTANT
• As a rule, maintenance of this transmitter should be done in a shop that has all the necessary tools.
• The CPU assembly contains sensitive parts that can be damaged by static electricity. Take precautions such as using a grounded wrist strap when handling electronic parts or touching the board circuit patterns. Also be sure to place the removed CPU assembly into a bag with an antistatic coating.
8.2 Calibration Instruments Se­lection
Table 8.1 lists the instruments that can be used to calibrate a transmitter. When selecting an instrument, consider the required accuracy level. Exercise care when handling these instruments to ensure they maintain the specified accuracy.

8.3 Calibration

Use the procedure below to check instrument operation and accuracy during periodic maintenance or trouble­shooting.
1) Connect the instruments as shown in figure 8.1 and
warm up the instruments for at least five minutes.
IMPORTANT
• To adjust the transmitter for highest accuracy, make adjustments with the power supply voltage and load resistance including leadwire resistances set close to the conditions under which the transmitter is installed.
• If the measurement range 0% point is 0 kPa or shifted in the positive direction (suppressed zero), the reference pressure should be applied as shown in the figure. If the measurement range 0% point is shifted in the negative direction (elevated zero), the reference pressure should be applied using a vacuum pump.
2) Apply reference pressures of 0%, 50%, and 100% of the measurement range to the transmitter. Calculate the errors (differences between digital voltmeter readings and reference pressures) as the pressure is increased from 0% to 100% and is decreased from 100% to 0%, and confirm that the errors are within the required accuracy.
8-1
IM 01C25B01-01E
Page 38
8. MAINTENANCE
Table 8.1 Instruments Required for Calibration
Name RemarksYokogawa-recommended Instrument
Power
supply
Load
resistor
Voltmeter
Model SDBT or SDBS distributor Model 2792 standard resistor [250 ±0.005%, 3 W]
Load adjustment resistor [100 ±1%, 1 W] Model 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
4 to 20 mA DC signal
Model MT220 precision digital manometer
1) For 10 kPa class for 0 to 10 kPa
Accuracy: ±(0.015% of rdg + 0.015% of F.S.)
±(0.2% of rdg + 0.1% of F.S.)
. . . . .
. . . . . . . . .
for -10 to 0 kPa
2) For 130 kPa class for 25 to 130 kPa for 0 to 25 kPa for -80 to 0 kPa
for 100 to 700 kPa for 0 to 100 kPa for -80 to 0 kPa
Select a manometer having a pressure range close to that of the transmitter.
Digital
manometer
Accuracy: ±0.02% of rdg
±5digits
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
±(0.2% of rdg + 0.1% of F.S.)
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits)
±5 digits
. . . . . . . . . . . . . . . . . . . . . . . . .
±(0.2% of rdg + 0.1% of F.S.)
. . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . .
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits)
±(0.2% of rdg + 0.1% of F.S.)
. . . . . . . . . . .
. . . . . . . . .
for 0 to 3000 kPa for -80 to 0 kPa
5) For 130 kPa abs class for 0 to 130 kPa abs
O}
2
}, 25 kPa {2500 mmH2O}
Requires air pressure supply.
Select the one having a pressure range close to
Pressure generator
Accuracy: ±(0.03% of rdg + 6 digits)
. . . . . . . . . . . .
Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm
Accuracy: ±0.05% of F.S.
Dead weight gauge tester 25 kPa {2500mmH
2
Accuracy: ±0.03% of setting
that of the transmitter.
Pressure
source
Model 6919 pressure regulator (pressure pump)
Pressure range: 0 to 133 kPa {1000 mmHg}
Prepare the vacuum pump for negative pressure ranges.
T0801.EPS
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and management
procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa representatives from which the instrument was purchased or the nearest Yokogawa office.
Using pressure
Supply pressure
generator
Pressure generator
P
Low pressure side open to atmosphere
Reference pressure
High pressure side High pressure side
Load resistance,
Load adjusting resistance, 100
Figure 8.1 Instrument Connections (EJX110A)
Low pressure side open to atmosphere
Power
250
supply E
RRc V
Digital voltmeter
Using pressure source with manometer
8-2
Pressure source
Model MT220
P
precision digital manometer
Reference pressure
Load resistance,
Load adjusting resistance, 100
Digital voltmeter
250 RRc
V
Power supply E
F0801.EPS
IM 01C25B01-01E
Page 39
8. MAINTENANCE
8.4 Disassembly and Reassem­bly
This section describes procedures for disassembly and reassembly for maintenance and component replace­ment.
Always turn OFF power and shut off and release pressures before disassembly. Use proper tools for all operations. Table 8.2 shows the tools required.
Table 8.2 Tools for Disassembly and Reassembly
Tool RemarksQuantity
1
Phillips screwdriver Slotted screwdriver
Allen wrenches JIS B4648
Wrench
Torque wrench
Adjustable wrench
Socket wrench
Socket driver
Tweezers
CAUTION
Precautions for ATEX Flameproof Type Transmitters
• Flameproof type transmitters must be, as a rule, removed to a non-hazardous area for maintenance and be disassembled and reas­sembled to the original state.
• On the flameproof type transmitters the two covers are locked, each by an Allen head bolt (shrouding bolt). When a shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cover can be opened.
When a cover is closed it should be locked by a shrouding bolt without fail. Tighten the shroud­ing bolt to a torque of 0.7 N·m.
Shrouding Bolt
JIS B4633, No. 2 1 3
One each, nominal 3, 4 and
2.5 mm Allen wrenches
1
Width across flats, 17 mm 1 1 1
Width across flats, 16 mm 1
Width across flats, 5.5 mm 1
T0802.EPS
Shrouding Bolt

8.4.1 Replacing the Integral Indicator

CAUTION
Cautions for Flameproof Type Transmitters
Users are prohibited by law from modifying the construction of a flameproof type transmitter. This would invalidate the agency approval for the use of the transmitter in a rated area. It follows that the user is prohibited from using a flameproof type transmitter with its integral indicator removed, or from adding an integral indicator to a transmitter. If such modification is absolutely required, contact Yokogawa.
This subsection describes the procedure for replacing an integral indicator. (See figure 8.3)
Removing the Integral Indicator
1) Remove the cover.
2) While supporting the integral indicator with one hand, loosen its two mounting screws.
3) Dismount the LCD board assembly from the CPU assembly.
When doing this, carefully pull the LCD board assembly straight forward so as not to damage the connector pins between it and the CPU assembly.
Attaching the Integral Indicator
1) Align both the LCD board assembly and CPU assembly connectors and engage them.
2) Insert and tighten the two mounting screws.
3) Replace the cover.
Output terminal cable
Press forward
Integral indicator
Slide switch
LCD board assembly
Mounting screw
Amplifier Cover
Boss
CPU assembly Bracket (for zero-adjustment screw pin)
Zero-adjustment screw pin
Zero­adjustment screw
Figure 8.2 Shrouding Bolts
F0802.EPS
Figure 8.3 Removing and Attaching LCD Board Assembly
and CPU Assembly
8-3
IM 01C25B01-01E
F0803.EPS
Page 40

8.4.2 Replacing the CPU Board Assembly

NOTE
8. MAINTENANCE
This subsection describes the procedure for replacing the CPU assembly. (See figure 8.3)
Removing the CPU Assembly
1) Remove the cover. If an integral indicator is mounted, refer to subsection 8.4.1 and remove the indicator.
2) Turn the zero-adjustment screw to the position (where the screw head slot is horizontal) as shown in figure 8.3.
3) Disconnect the output terminal cable (cable with brown connector at the end). When doing this, lightly press the side of the CPU assembly connec­tor and pull the cable connector to disengage.
4) Use a socket driver (width across flats, 5.5mm) to loosen the two bosses.
5) Carefully pull the CPU assembly straight forward to remove it.
6) Disconnect the flat cable (cable with white connec­tor at the end) that connects the CPU assembly and the capsule.
NOTE
Be careful not to apply excessive force to the CPU assembly when removing it.
Mounting the CPU Assembly
1) Connect the flat cable (with white connector) between the CPU assembly and the capsule.
2) Connect the output terminal cable (with brown connector).
NOTE
Make certain that the cables do not get pinched between the case and the edge of the CPU assembly.
Confirm that the zero-adjustment screw pin is placed properly in the groove on the bracket prior to tightening the two bosses. If it is not, the zero-adjustment mechanism will be damaged.
5) Replace the cover.

8.4.3 Cleaning and Replacing the Capsule Assembly

This subsection describes the procedures for cleaning and replacing the capsule assembly. (See figure 8.4.)
CAUTION
Cautions for Flameproof Type Transmitters
Users are prohibited by law from modifying the construction of a flameproof type transmitter. If you wish to replace the capsule assembly with one of a different measurement range, contact Yokogawa. The user is permitted, however, to replace a capsule assembly with another of the same measurement range. When doing so, be sure to observe the following.
• The replacement capsule assembly must have the same part number as the one being re­placed.
• The section connecting the transmitter and capsule assembly is a critical element in preservation of flameproof performance, and must be checked to verify that it is free of dents, scratches, and other defects.
• After completing maintenance, be sure to securely tighten the setscrews that fasten the transmitter section and pressure-detector section together.
3) Align and engage the zero-adjustment screw pin with the groove on the bracket on the CPU assem­bly. Then insert the CPU board assembly straight onto the post in the amplifier case.
4) Tighten the two bosses. If the transmitter is equipped with an integral indicator, refer to subsec­tion 8.4.1 to mount the indicator.
8-4
IM 01C25B01-01E
Page 41
8. MAINTENANCE
Removing the Capsule Assembly
IMPORTANT
Exercise care as follows when cleaning the capsule assembly.
• Handle the capsule assembly with care, and be especially careful not to damage or distort the diaphragms that contact the process fluid.
• Do not use a chlorinated or acidic solution for cleaning.
• Rinse thoroughly with clean water after clean­ing.
1) Remove the CPU assembly as shown in subsection
8.4.2.
2) Remove the two setscrews that connect the transmitter section and pressure-detector section.
3) Remove the hexagon-head screw and the stopper.
4) Separate the transmitter section and pressure­detector section.
5) Remove the nuts from the four flange bolts.
6) While supporting the capsule assembly with one hand, remove the cover flange.
7) Remove the capsule assembly.
8) Clean the capsule assembly or replace with a new one.
Reassembling the Capsule Assembly
1) Insert the capsule assembly between the flange bolts, paying close attention to the relative positions of the H (high pressure side) and L (low pressure side) marks on the capsule assembly. Replace the two capsule gaskets with new gaskets.
2) Install the cover flange on the high pressure side, and use a torque wrench to tighten the four nuts uniformly to a torque shown below.
Model EJX110A,
EJX310A, EJX430A
Torque(N·m)
{kgf·m}
17 {1.7}
EJX130A, EJX440A
Bolts and nuts material code
G, C J
70 {69}
100 {98}
T0803.EPS
3) After the pressure-detector section has been reas­sembled, a leak test must be performed to verify that there are no pressure leaks.
4) Reattach the transmitter section to the pressure­detector section. Reattach the stopper with the hexagon-head screw.
5) Tighten the two setscrews. (Tighten the screws to a torque of 1.5 N·m)
6) Install the CPU assembly according to subsection
8.4.2.
7) After completing reassembly, adjust the zero point and recheck the parameters.
Transmitter section
Setscrew
Nut
Capsule gasket
Flange bolt
Pressure-detector section
Cover flange
Figure 8.4 Removing and Mounting the Pressure-
detector Section
F0804.EPS
IMPORTANT
If you remove the drain/vent plugs when disas­sembling EJX130A and EJX440A transmitters, install the plugs again before reassembling the cover flanges with the capsule assmbly.
8.4.4 Replacing the Process Connector
Gaskets
This subsection describes process connector gasket replacement. (See figure 8.5.)
(a)Loosen the two bolts, and remove the process
connectors.
(b) Replace the process connector gaskets. (c)Remount the process connectors. Tighten the bolts
securely and uniformly to a torque shown below, and verify that there are no pressure leaks.
Model
Torque(N·m) {kgf·m} {5 to 6}
EJX110A, EJX130A, EJX310A, EJX430A
39 to 49 {4 to 5}
EJX440A
C capsule D capsule
49 to 59
T0805.EPS
8-5
IM 01C25B01-01E
Page 42
8. MAINTENANCE
Bolt
Process connector
Process connector gasket
Figure 8.5 Removing and Mounting the Process
Connector
F0805.EPS

8.5 Troubleshooting

If any abnormality appears in the measured values, use the troubleshooting flow chart below to isolate and remedy the problem. Since some problems have complex causes, these flow charts may not identify all. If you have difficulty isolating or correcting a problem, contact Yokogawa service personnel.

8.5.1 Basic Troubleshooting

First determine whether the process variable is actually abnormal or a problem exists in the measurement system.
If the problem is in the measurement system, isolate the problem and decide what corrective action to take.
This transmitter is equipped with a self-diagnostic function which will be useful in troubleshooting, and the transmitter equipped with an integral indicator will show an alarm code as a result of self-diagnosis. See subsection 8.5.3 for the list of alarms. See also each communication manual.
YES
Inspect the
process system.
YES
Inspect receiver.
: Areas where self-diagnostic offers support
Abnormalities appear in measurement.
Is process variable
itself abnormal?
NO
Measurement system problem
Isolate problem in
measurement system.
Does problem exist in receiving instrument?
NO
Environmental conditions
Check/correct
environmental conditions.
Operating conditions
Check/correct operating
conditions.
Figure 8.5.1 Basic Flow and Self-Diagnostics
8-6
Transmitter itself
Check transmitter.
F0806.EPS
IM 01C25B01-01E
Page 43
8. MAINTENANCE

8.5.2 Troubleshooting Flowcharts

The following sorts of symptoms indicate that transmitter may not be operating properly. Example : • There is no output signal.
• Output signal does not change even though process variable is known to be varying.
• Output value is inconsistent with value inferred for process variable.
Connect communicator and check self-diagnostics.
Does the self-diagnostic
indicate problem location?
NO
Is power supply
polarity correct?
YES
Are power
supply voltage and load
resistance correct?
YES
Are valves opened or
closed correctly?
YES
Is there any pressure leak?
NO
Refer to error message summary in Subsection 8.5.3 or in each communication manual to take actions.
Refer to Section 6.3 to check/correct polarity at each terminal from power supply to the terminal box.
Refer to Section 6.6 for rated voltage and load resistance.
Fully close equalizing valve, and fully open high pressure and low pressure valves.
Fix pressure leaks, paying particular attention to connections for impulse piping,pressure-detector section, etc.
YES
NO
NO
NO
YES
Output travels beyond 0% or 100%.
Connect a communicator and check self-diagnostics.
Does the self-
diagnostic indicate problem
location?
NO
Is power supply
polarity correct?
YES
Are valves opened or
closed correctly?
YES
Is there any pressure leak?
NO
Is impulse piping
to high pressure and low
pressure side correct?
YES
Is zero point
adjusted correctly?
YES
Refer to error message summary in each communication manual to take actions.
Refer to Section 6.3 to check/correct polarity at each terminal from power supply to the terminal box.
Fully close equalizing valve, and fully open high pressure and low pressure valves.
Fix pressure leaks, paying particular attention to connections for impulse piping, pressure-detector section, etc.
Refer to individual model user manuals and connect piping as appropriate for the measurement purpose.
Adjust the zero point.
YES
NO
NO
YES
NO
NO
Is there
continuity through the
transmitter loop wiring?
Do the loop numbers
match?
YES
Contact Y okogaw a service personnel.
Find/correct broken conductor or wiring error.
NO
F0807.EPS
8-7
Contact Yokogawa service personnel.
F0808.EPS
IM 01C25B01-01E
Page 44
Large output error.
Connect a communicator and check self-diagnostics.
8. MAINTENANCE
Does the self-
diagnostic indicate problem
location?
NO
Are valves opened or
closed correctly?
YES
Is impulse piping
connected correctly?
YES
Are power supply
voltage and load resistance
correct?
YES
Refer to error message summary in each communication manual to take actions.
NO
Fully close equalizing valve, and fully open high pressure and low pressure valves.
NO
Refer to individual model user manuals and connect piping as appropriate for the measurement purpose.
NO
YES
Is transmitter
installed where there is
marked variation in
temperature?
NO
Were appropriate
instruments used for
calibration?
YES
Is output adjusted correctly?
YES
Contact Y okogaw a service personnel.
Refer to Section 6.6 for rated voltage and load resistance.
Provide lagging and/or cooling, or allow adequate ventilation.
Refer to Section 8.2 when selecting instruments for calibration.
Adjust the output.
YES
NO
NO
F0809.EPS
8-8
IM 01C25B01-01E
Page 45
8. MAINTENANCE

8.5.3 Alarms and Countermeasures

Table 8.1 Alarm Message Summary
Indicator Cause Countermeasure
None AL. 01
Sensor problem.
CAP. ERR
Capsule temperature sensor problem. Capsule EEPROM problem.
AL. 02 AMP. ERR
Amplifier temperature sensor problem. Amplifier EEPROM problem. Amplifier problem.
AL. 10 PRESS
AL. 11
Input is outside measurement range limit of capsule.
Static pressure exceeds limit.
ST. PRSS AL. 12
CAP . TMP AL. 13
AMP . TMP AL. 30
RANGE AL. 31
Capsule temperature is outside range (–50 to 130°C).
Amplifier temperature is outside range (–50 to 95°C).
Output is outside upper or lower range limit value.
Static pressure exceeds specified range.
SP. RNG AL. 35
*1
Input pressure exceeds specified threshold.
P. HI
*1
AL. 36 P. LO
AL. 37 SP. HI
AL. 38
*1
*1
Input static pressure exceeds specified threshold.
SP. LO
*1
AL. 39 TMP. HI
AL. 40
*1
Detected temperature exceeds specified threshold.
TMP. LO AL. 50
Specified value is outside of setting range.
P. LRV AL. 51
P. URV AL. 52
P. SPN AL. 53
P. ADJ AL. 54
SP. RNG
AL. 55 SP. ADJ
AL. 60 SC. CFG
Specified values or settings to define signal characterizer function do not satisfy the condition.
AL. 79
Displayed value exceeds limit.
OV. DISP
*1: These alarms may appear only when process alarm function is activated.
Output Operation
during Error
Outputs the signal (Hold, High, or Low) set with parameter.
Outputs the signal (Hold, High, or Low) set with parameter.
Outputs high range limit value or low range limit value.
Continues to operate and output.
Outputs high range limit value or low range limit value.
Holds output immediately before error occurred.
Continues to operate and output.
Holds output immediately before error occurred.
Continues to operate and output.
Continues to operate and output holding static pressure in %.
Continues to operate and output.
Replace capsule when error keeps appearing even after restart.
Replace amplifier.
Check input or replace capsule when necessary.
Use heat insulation or make lagging to keep temperature within range.
Check input and range setting, and change them as needed.
Check input.
Check setting and change them as needed.
Check input.
Check setting and change them as needed.
Check input.
Check setting and change them as needed.
T0804.EPS
8-9
IM 01C25B01-01E
Page 46

9. GENERAL SPECIFICATIONS

9. GENERAL SPECIFICATIONS

9.1 Standard Specifications

Refer to IM 01C25T02-01E for FOUNDATION Fieldbus communication type marked with “”.
Performance Specifications
See General Specifications sheet of each model.
Functional Specifications Span & Range Limits
EJX110A
Measurement
Span/Range
Span
L
Range Span
M
Range Span
H
Range
kPa
0.1 to 10
10 to 10
0.5 to 100
100 to 100
2.5 to 500
500 to 500
EJX130A
Measurement
Span/Range
Span
M
Range Span
H
Range
kPa
1 to 100
100 to 100
5 to 500
500 to 500
EJX310A
Measurement
Span/Range
Span
M
Range Span
A
Range
Span
B
Range
kPa abs
1.3 to 130 0 to 130
0.0175 to
3.5 MPa
0 to 3.5 MPa
0.08 to 16 0 to 16 MPa
EJX430A
Measurement
Span/Range
Span
H
Range Span
A
Range Span
B
Range
MPa
2.5 to 500 kPa
100 to 500 kPa
0.0175 to 3.5
0.1 to 3.5
0.08 to 16
0.1 to 16
EJX440A
Measurement
Span/Range
Span
C
Range Span
D
Range
MPa
0.25 to 32
0.1 to 32
0.25 to 50
0.1 to 50
Output “”
Two wire 4 to 20 mA DC output with digital communica­tions, linear or square root programmable. BRAIN or HART FSK protocol are superimposed on the 4 to 20 mA signal. Output range: 3.6 mA to 21.6 mA Output limits conform to NAMUR NE43 can be pre-set by option C2 or C3.
MPa
2000 to 2000
0.39 to 38
inH
O(/D1)
2
0.4 to 40
40 to 40
2 to 400
400 to 400
10 to 2000
2000 to 2000
O(/D1)
inH
2
4 to 400
400 to 400
20 to 2000
psi abs (/D1)
inHg
0 to 38 inHg
2.5 to 500 0 to 500
12 to 2300
0 to 2300
psi (/D1)
10 to 2000 inH
400 to 2000 inH2O
2.5 to 500
15 to 500
12 to 2300
14.7 to 2300
psi (/D1)
36 to 4500
14.5 to 4500 36 to 7200
14.5 to 7200
mbar(/D3)
1 to 100
100 to 100 5 to 1000
1000 to 1000
25 to 5000
5000 to 5000
mbar(/D3)
10 to 1000
1000 to 1000
50 to 5000
5000 to 5000
mbar abs(/D3)
13 to 1300
0 to 1300
0.175 to 35 0 to 35 bar
0.8 to 160 bar 0 to 160 bar
bar(/D3)
0.025 to 5
O
2
0.175 to 35
0.8 to 160
1 to 160
bar(/D3)
2.5 to 320
1 to 320
2.5 to 500
1 to 500
10000 to 10000
0.025 to 5 kgf/cm
10000 to 10000
0.05 to 5 kgf/cm
mmHg abs(/D4)
bar
0 to 160
1 to 5
1 to 35
mmH2O(/D4)
10 to 1000 1000 to 1000 50 to 10000
5 to 5 kgf/cm
mmH 100 to 10000
5 to 5 kgf/cm
9.8 to 970 0 to 970
0.175 to 35
0 to 35 kgf/cm
0.8 to 160
kgf/cm2(/D4)
0.025 to 5
0.175 to 35
kgf/cm2(/D4)
2.5 to 320
T0901.EPS
O(/D4)
2
T0902.EPS
kgf/cm
kgf/cm
kgf/cm
T0903.EPS
1 to 5
1 to 35
0.8 to 160
1 to 160
T0904.EPS
1 to 320
2.5 to 500
1 to 500
T0905.EPS
Failure Alarm “”
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more (standard) Down-scale: –5%, 3.2 mA DC or less Note: Applicable for Output signal code D and E
Damping Time Constant (1st order)
Amplifier damping time constant is adjustable from 0 to
100.00 seconds and added to response time. Note: For BRAIN protocol type, when amplifier
damping is set to less than 0.5 seconds, communi­cation may occasionally be unavailable during the operation, especially while output changes dynamically. The default setting of damping ensures stable communication.
Update Period “”
2
2
Differential Pressure: 45 msec Static Pressure: 360 msec
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the lower and upper range limits of the capsule.
External Zero Adjustment “”
2
2
External Zero is continuously adjustable with 0.01% incremental resolution of span. Re-range can be done locally using the digital indicator with range-setting switch.
Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display and Bar graph. The indicator is configurable to display one or up to four of
2
2
2 2
the following variables periodically.; Differential pressure in %, Scaled Differential pressure, Differential Pressure in Engineering unit, Static Pressure in Engineering unit. See “Setting When Shipped” for factory setting.
Burst Pressure Limits
[EJX110A, EJX310A, EJX430A] 69 MPa (10000 psi) [EJX130A, EJX440A] 132 MPa (19100 psi)
NORMAL OPERATING CONDITION
(Optional features or approval codes may affect limits.)
Ambient Temperature Limits
–40 to 85°C (–40 to 185°F) –30 to 80°C (–22 to 176°F) with LCD display
Process Temperature Limits
–40 to 120°C (–40 to 248°F)
Ambient Humidity Limits
0 to 100% RH
Working Pressure Limits (Silicone oil)
Maximum Pressure Limits EJX110A
Capsule Pressure
L 16 MPa (2300 psi) M, H 25 MPa (3600 psi)
9-1
IM 01C25B01-01E
Page 47
9. GENERAL SPECIFICATIONS
EJX130A
Capsule Pressure
M, H 32 MPa (4500 psi)
EJX310A Capsule Pressure
M 130 kPa abs (38 inHg abs) A3.5 MPa abs (500 psia) B 16 MPa abs (2300 psia)
EJX430A Capsule Pressure
H 500 kPa (2000 inH2O) A3.5 MPa (500 psi) B 16 MPa (2300 psi)
EJX440A Capsule Pressure
C 32 MPa (4500 psi) D 50 MPa (7200 psi)
Minimum Pressure Limit
See graph below
EJX110A, EJX130A, EJX430A, EJX440A
100(14.5)
Working pressure kPa abs
(psi abs)
Applicable range
10(1.4)
Atmospheric pressure
EJX310A
100(750)
M,A and B capsule
L capsule
10(75)
Working pressure kPa abs
(mmHg abs)
Figure 9.1 Working Pressure and Process Temperature
2.7(20)
1(7.5)
0.13(1)
0.1(0.75)
0.013(0.1)
0.01(0.075)
Applicable range
-40 (-40)
0 (32)40(104)80(176)
Process temperature C(F)
0.46
(3.45)
120 (248)
85 (185)
F0902.EPS
Maximum Over Pressure EJX310A
Capsule Pressure
M 500 kPa abs (72 psia) A 16 Mpa abs (2300 psia) B 25 MPa abs (3600 psia)
EJX430A Capsule Pressure
H, A 16 MPa (2300 psi) B 25 MPa (3600 psi)
2.7(0.38)
1(0.14)
-40 (-40)
0 (32)40(104)80(176)
Process temperature C (F)
120 (248)
F0901.EPS
EJX440A Capsule Pressure
C 48 MPa (6750 psi) D 75 MPa (10800 psi)
9-2
IM 01C25B01-01E
Page 48
9. GENERAL SPECIFICATIONS
Supply & Load Requirements “” (Optional features
or approval codes may affect electrical require­ments.)
With 24 V DC supply, up to a 550 load can be used. See graph below.
600
E-10.5
R=
0.0244
External load resistance
250
()
R
10.5 16.6
Power supply voltage E (V DC)
Figure 9.2 Relationship Between Power Supply Voltage
and External Load Resistance
25.2 42
Digital
Communication
range
BRAIN and HART
F0904.EPS
Supply Voltage
10.5 to 42 V DC for general use and flameproof type.
10.5 to 32 V DC for lightning protector (Option code /A).
10.5 to 30 V DC for intrinsically safe, type n or non­incendive type.
Minimum voltage limited at 16.6 V DC for digital
communications, BRAIN and HART
Load (Output signal code D and E)
0 to 1290 for operation 250 to 600 for digital communication
Communication Requirements “”
(Safety approvals may affect electrical require­ments.)
BRAIN Communication Distance
Up to 2 km (1.25 miles) when using CEV polyethylene­insulated PVC-sheathed cables. Communication distance varies depending on type of cable used.
Load Capacitance
0.22 F or less
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10 k or more at 2.4 kHz.
HART Communication Distance
Up to 1.5 km (1 mile) when using multiple twisted pair cables. Communication distance varies depending on type of cable used.
Use the following formula to determine cable length for specific applications:
65 10
L= –
(R C)
6
(Cf + 10,000)
C
Where: L = length in meters or feet R = resistance in (including barrier resistance) C = cable capacitance in pF/m or pF/ft C
= maximum shunt capacitance of receiving devices in
f
pF/m or pF/ft
EMC Conformity Standards ,
EN 61326, AS/NZS CISPR11
PHYSICAL SPECIFICATIONS
Wetted Parts Materials
Diaphragm, Cover Flange, Process Connector, Capsule Gasket, and Vent/Drain Plug
Refer to “MODEL AND SUFFIX CODE.”
Process Connector Gasket/o-ring
[EJX110A, EJX430A, EJX310A] PTFE Teflon Fluorinated rubber for Option code /N2 and /N3 [EJX130A] Fluorinated rubber(O-ring) [EJX440A] Fluorinated rubber(O-ring) for C capsule Glass reinforced Teflon(gasket) for D capsule
Non-wetted Parts Materials
Bolting
ASTM-B7M carbon steel, 316 SST(ISO A4-70) stainless steel, or ASTM grade 660 stainless steel
Housing
Low copper cast aluminum alloy with polyurethane, mint­green paint (Munsell 5.6BG 3.3/2.9 or its equivalent) or ASTM CF-8M stainless steel
Degrees of Protection
IP67, NEMA4X, JIS C0920
Cover O-rings
Buna-N
Name plate and tag
304 SST
Fill Fluid
Silicone, Fluorinated oil (option)
Weight
[Installation code 7, 8 and 9 for EJX110A, EJ310A and EJX430A]
2.7 kg (6.0 lb) without integral indicator, mounting bracket, and process connector. [Installation code 7, 8 and 9 for EJX130A,and EJX440A]
4.8 kg (10.6lb) without integral indicator, mounting bracket, and process connector.
Add 1.5 kg(3.3lb) for amplifier housing code 2.
9-3
IM 01C25B01-01E
Page 49
Connections
Refer to “MODEL AND SUFFIX CODE.”
Process Connection of Cover Flange(models except for EJX440A-D) : IEC61518
9. GENERAL SPECIFICATIONS
9-4
IM 01C25B01-01E
Page 50
9. GENERAL SPECIFICATIONS

9.2 MODEL AND SUFFIX CODES

MODEL EJX110A
Model DescriptionSuffix Codes
EJX110A
Output signal
· · · · · · · · · · · · · · · · · · · · · · · · ·
-D · · · · · · · · · · · · · · · · · · · · · · ·
-E · · · · · · · · · · · · · · · · · · · · · · ·
-F · · · · · · · · · · · · · · · · · · · · · · ·
Measurement span (capsule)
L · · · · · · · · · · · · · · · · · · · · · M · · · · · · · · · · · · · · · · · · · · · H · · · · · · · · · · · · · · · · · · · · ·
Wetted parts material *
1
Process connections
· · · · · · · · · · · · · · · · · · ·
0 · · · · · · · · · · · · · · · · · · 1 · · · · · · · · · · · · · · · · · · 2 · · · · · · · · · · · · · · · · · · 3 · · · · · · · · · · · · · · · · · · 4 · · · · · · · · · · · · · · · · · · 5 · · · · · · · · · · · · · · · · · ·
Bolts and nuts material
J · · · · · · · · · · · · · · · · G · · · · · · · · · · · · · · · · C · · · · · · · · · · · · · · · ·
Installation
-7 · · · · · · · · · · · · · ·
-8 · · · · · · · · · · · · · ·
-9 · · · · · · · · · · · · · ·
-B · · · · · · · · · · · · · ·
Amplifier housing
1 · · · · · · · · · · · · 2 · · · · · · · · · · · ·
Electrical connection
0 · · · · · · · · · · ·
2 · · · · · · · · · · · 4 · · · · · · · · · · · 5 · · · · · · · · · · · 7 · · · · · · · · · · · 9 · · · · · · · · · · ·
Integral indicator
D · · · · · · · · E · · · · · · · ·
N · · · · · · · ·
Mounting bracket
B · · · · · D · · · · · G · · · · · N · · · · ·
Optional Codes
The “” marks indicate the most typical selection for each specification. *1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate materials
has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosive process fluids.
Differential pressure transmitter 4 to 20 mA DC with digital communication (BRAIN protocol) 4 to 20 mA DC with digital communication (HART protocol) Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)
0.1 to 10 kPa (0.4 to 40 inH
0.5 to 100 kPa (2 to 400 inH
2.5 to 500 kPa (10 to 2000 inH
O)
2
O)
2
O)
2
Refer to "Wetted Parts Material" Table below.
without process connector (Rc1/4 female on the cover flanges) with Rc1/4 female process connector with Rc1/2 female process connector with 1/4 NPT female process connector with 1/2 NPT female process connector without process connector (1/4 NPT female on the cover flanges) ASTM-B7M carbon steel 316 SST (ISO A4-70) stainless steel ASTM grade 660 stainless steel Vertical piping, left side high pressure, and process connection downside Horizontal piping and right side high pressure Horizontal piping and left side high pressure Bottom Process Connection, left side high pressure Cast alluminum alloy ASTM CF-8M Stainless Steel G1/2 female, one electrical connection without blind plugs 1/2 NPT female, two electrical connections without blind plugs M20 female, two electrical connections without blind plugs G1/2 female, two electrical connections and a blind plug 1/2 NPT female, two electrical connections and a blind plug M20 female, two electrical connections and a blind plug Digital indicator Digital indicator with the range setting switch None
304 SST 2-inch pipe mounting, flat type (for horizontal piping) 304 SST 2-inch pipe mounting, L type (for vertical piping) 304 SST 2-inch pipe mounting (for bottom process connection type) None
/ Optional specification
T0906.EPS
Table. Wetted Parts Materials
Wetted parts
material code
S
– – – – – –
#
#
#
Cover flange and
process connector
ASTM CF-8M
ASTM CF-8M ASTM CF-8M
ASTM CF-8M Hastelloy C-276 equivalent Hastelloy C-276 equivalent
Monel equivalent
Capsule Capsule gasket Drain/Vent plug
Hastelloy C-276 (Diaphragm)
316L SST (Others)
Hastelloy C-276
Monel
Tantalum
Hastelloy C-276
Tantalum
Monel
Teflon-coated 316L SST
PTFE (Teflon) PTFE (Teflon) PTFE (Teflon) PTFE (Teflon) PTFE (Teflon) PTFE (Teflon)
316 SST
316 SST 316 SST
316 SST Hastelloy C-276 Hastelloy C-276
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
9-5
Monel
T0907.EPS
IM 01C25B01-01E
Page 51
MODEL EJX310A
9. GENERAL SPECIFICATIONS
Model Description
EJX310A
Output Signal
· · · · · · · · · · · · · · · · · · · · · · · · ·
-D · · · · · · · · · · · · · · · · · · · · · · ·
-E · · · · · · · · · · · · · · · · · · · · · · ·
-F · · · · · · · · · · · · · · · · · · · · · · ·
Measurement span (capsule)
Wetted parts material
*1
Process connections
Bolts and nuts material
Installation
Amplifier housing
Electrical connection
Integral indicator
Mounting bracket
Optional code
Suffix Codes
M · · · · · · · · · · · · · · · · · · · · · A · · · · · · · · · · · · · · · · · · · · · B · · · · · · · · · · · · · · · · · · · · · ·
S · · · · · · · · · · · · · · · · · · ·
0 · · · · · · · · · · · · · · · · · · 1 · · · · · · · · · · · · · · · · · · 2 · · · · · · · · · · · · · · · · · · 3 · · · · · · · · · · · · · · · · · · 4 · · · · · · · · · · · · · · · · · · 5 · · · · · · · · · · · · · · · · · ·
J · · · · · · · · · · · · · · · · G · · · · · · · · · · · · · · · · C · · · · · · · · · · · · · · · ·
-3 · · · · · · · · · · · · · ·
-7 · · · · · · · · · · · · · ·
-8 · · · · · · · · · · · · · ·
-9 · · · · · · · · · · · · · ·
-B · · · · · · · · · · · · · · 1 · · · · · · · · · · · ·
2 · · · · · · · · · · · ·
0 · · · · · · · · · · ·
2 · · · · · · · · · · · 4 · · · · · · · · · · · 5 · · · · · · · · · · · 7 · · · · · · · · · · · 9 · · · · · · · · · · ·
D · · · · · · · · E · · · · · · · · N · · · · · · · ·
B · · · · · D · · · · · G · · · · · N · · · · ·
Absolute pressure transmitter 4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART protocol) Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)
1.3 to 130 kPa abs (0.39 to 38 inHg abs)
0.0175 to 3.5 MPa abs (2.5 to 500 psia)
0.08 to 16 MPa abs (12 to 2300 psia) Refer to "Wetted Parts Material" Table
without process connector (Rc1/4 female on the cover flanges) with Rc1/4 female process connector with Rc1/2 female process connector with 1/4 NPT female process connector with 1/2 NPT female process connector without process connector (1/4 NPT female on the cover flanges)
ASTM-B7M carbon steel 316 SST (ISO A4-70) stainless steel ASTM grade 660 stainless steel
Vertical piping, right side high pressure, and process connection down side Vertical piping, left side high pressure, and process connection down side Horizontal piping and right side high pressure Horizontal piping and left side high pressure Bottom process connection, left side high pressure
Cast alluminum alloy ASTM CF-8M stainless steel
G1/2 female, one electrical connection without blind plugs 1/2 NPT female, two electrical connections without blind plugs M20 female, two electrical connections without blind plugs G1/2 female, two electrical connections and a blind plug 1/2 NPT female, two electrical connections and a blind plug
M20 female, two electrical connections and a blind plug Digital indicator
Digital indicator with the range setting switch (None)
304 SST 2-inch pipe mounting, flat type (for horizontal piping) 304 SST 2-inch pipe mounting, L type (for vertical piping) 304 SST 2-inch pipe mounting (for bottom process connction) (None)
/
Optional specification
The “” marks indicate the most typical selection for each specification. *1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate materials
has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosive process fluids.
T0909.EPS
9-6
IM 01C25B01-01E
Page 52
9. GENERAL SPECIFICATIONS
MODEL EJX430A
Model DescriptionSuffix Codes
EJX430A
Output Signal
· · · · · · · · · · · · · · · · · · · · · · · · ·
-D · · · · · · · · · · · · · · · · · · · · · · ·
-E · · · · · · · · · · · · · · · · · · · · · · ·
-F · · · · · · · · · · · · · · · · · · · · · · ·
Measurement span (capsule)
H · · · · · · · · · · · · · · · · · · · · · A · · · · · · · · · · · · · · · · · · · · · B · · · · · · · · · · · · · · · · · · · · ·
Wetted parts material*
1
Process connections
· · · · · · · · · · · · · · · · · · ·
0 · · · · · · · · · · · · · · · · · · 1 · · · · · · · · · · · · · · · · · · 2 · · · · · · · · · · · · · · · · · · 3 · · · · · · · · · · · · · · · · · · 4 · · · · · · · · · · · · · · · · · · 5 · · · · · · · · · · · · · · · · · ·
Bolts and nuts material
J · · · · · · · · · · · · · · · · G · · · · · · · · · · · · · · · · C · · · · · · · · · · · · · · · ·
Installation
-3 · · · · · · · · · · · · · ·
-7 · · · · · · · · · · · · · ·
-8 · · · · · · · · · · · · · ·
-9 · · · · · · · · · · · · · ·
-B · · · · · · · · · · · · · ·
Amplifier housing
1 · · · · · · · · · · · · 2 · · · · · · · · · · · ·
Electrical connection
0 · · · · · · · · · · ·
2 · · · · · · · · · · · 4 · · · · · · · · · · · 5 · · · · · · · · · · · 7 · · · · · · · · · · · 9 · · · · · · · · · · ·
Integral indicator
D · · · · · · · · E · · · · · · · ·
N · · · · · · · ·
Mounting bracket
B · · · · · D · · · · · G · · · · · N · · · · ·
Optional Codes
The “” marks indicate the most typical selection for each specification. *1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate materials
has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosive process fluids.
Gauge pressure transmitter 4 to 20 mA DC with digital communication (BRAIN protocol) 4 to 20 mA DC with digital communication (HART protocol) Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)
2.5 to 500 kPa (10 to 2000 inH
O)
2
0.0175 to 3.5 MPa (2.5 to 500 psi)
0.08 to 16 MPa (12 to 2300 psi) Refer to "Wetted Parts Material" Table.
without process connector (Rc1/4 female on the cover flanges) with Rc1/4 female process connector with Rc1/2 female process connector with 1/4 NPT female process connector with 1/2 NPT female process connector without process connector (1/4 NPT female on the cover flanges) ASTM-B7M carbon steel 316SST(ISO A4-70) stainless steel ASTM grade 660 stainless steel Vertical piping, right side high pressure, and process connection down side Vertical piping, left side high pressure, and process connection down side Horizontal piping and right side high pressure Horizontal piping and left side high pressure Bottom Process Connection, left side high pressure Cast alluminum alloy ASTM CF-8M Stainless Steel G1/2 female, one electrical connection without blind plugs 1/2 NPT female, two electrical connections without blind plugs M20 female, two electrical connections without blind plugs G1/2 female, two electrical connections and a blind plug 1/2 NPT female, two electrical connections and a blind plug M20 female, two electrical connections and a blind plug Digital indicator Digital indicator with the range setting switch None 304 SST 2-inch pipe mounting, flat type (for horizontal piping) 304 SST 2-inch pipe mounting, L type (for vertical piping) 304 SST 2-inch pipe mounting (for bottom process connection type) None / Optional specification
T0910.EPS
9-7
IM 01C25B01-01E
Page 53
9. GENERAL SPECIFICATIONS
MODEL EJX130A
Model DescriptionSuffix Codes
EJX130A
Output signal
· · · · · · · · · · · · · · · · · · · · · · · · ·
-D · · · · · · · · · · · · · · · · · · · · · · ·
-E · · · · · · · · · · · · · · · · · · · · · · ·
-F · · · · · · · · · · · · · · · · · · · · · · ·
Measurement span (capsule) Wetted parts material*
1
Process connections
M · · · · · · · · · · · · · · · · · · · · · H · · · · · · · · · · · · · · · · · · · · ·
S · · · · · · · · · · · · · · · · · · ·
3 · · · · · · · · · · · · · · · · · · 4 · · · · · · · · · · · · · · · · · · 5 · · · · · · · · · · · · · · · · · ·
Bolts and nuts material
J · · · · · · · · · · · · · · · · G · · · · · · · · · · · · · · · · C · · · · · · · · · · · · · · · ·
Installation
-7 · · · · · · · · · · · · · ·
-8 · · · · · · · · · · · · · ·
-9 · · · · · · · · · · · · · ·
Amplifier housing
1 · · · · · · · · · · · · 2 · · · · · · · · · · · ·
Electrical connection
0 · · · · · · · · · · ·
2 · · · · · · · · · · · 4 · · · · · · · · · · · 5 · · · · · · · · · · · 7 · · · · · · · · · · · 9 · · · · · · · · · · ·
Integral indicator
D · · · · · · · · E · · · · · · · ·
N · · · · · · · ·
Mounting bracket
B · · · · · D · · · · · N · · · · ·
Optional code
The “” marks indicate the most typical selection for each specification. *1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate materials
has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosive process fluids.
*2: Lower limit of ambient and process temperature is -15˚C.
Differential pressure transmitter 4 to 20 mA DC with digital communication (BRAIN protocol) 4 to 20 mA DC with digital communication (HART protocol)
Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E) 1 to 100 kPa (4 to 400 inH 5 to 500 kPa (20 to 2000 inH
O)
2
O)
2
Refer to "Wetted Parts Material for EJX130A" Table below.
with 1/4 NPT female process connector with 1/2 NPT female process connector
*2 *2
without process connector (1/4 NPT female on the cover flanges) ASTM-B7M carbon steel 316 SST (ISO A4-70) stainless steel ASTM grade 660 stainless steel Vertical piping, left side high pressure, and process connection downside Horizontal piping and right side high pressure Horizontal piping and left side high pressure Cast alluminum alloy ASTM CF-8M Stainless Steel G1/2 female, one electrical connection without blind plugs 1/2 NPT female, two electrical connections without blind plugs M20 female, two electrical connections without blind plugs G1/2 female, two electrical connections and a blind plug 1/2 NPT female, two electrical connections and a blind plug M20 female, two electrical connections and a blind plug Digital indicator Digital indicator with the range setting switch None 304 SST 2-inch pipe mounting, flat type (for horizontal piping) 304 SST 2-inch pipe mounting, L type (for vertical piping) None
/
Optional specifications
T0908.EPS
Table. Wetted Parts Materials for EJX130A
Wetted parts
material code
#
S
Cover flange Capsule Capsule gasket Drain/Vent plug
316 SST
Process connector
ASTM CF-8M
*1
Hastelloy C-276 *2 (Diaphragm)
316L SST (Others)
Teflon-coated 316L SST 316 SST
*1: Cast version of 316 SST. Equivalent to SCS14A. *2: Hastelloy C-276 or ASTM N10276. The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
9-8
M02E.EPS
IM 01C25B01-01E
Page 54
MODEL EJX440A
9. GENERAL SPECIFICATIONS
Model Description
EJX440A
Output Signal
· · · · · · · · · · · · · · · · · · · · · · · · ·
-D · · · · · · · · · · · · · · · · · · · · · · ·
-E · · · · · · · · · · · · · · · · · · · · · · ·
-F · · · · · · · · · · · · · · · · · · · · · · ·
Measurement span (capsule) Wetted parts material
*1
Process connections
Bolts and nuts material
Installation
Amplifier housing
Electrical connection
Integral indicator
Mounting bracket
Optional code
The “” marks indicate the most typical selection for each specification.
Suffix Codes
C · · · · · · · · · · · · · · · · · · · · · D · · · · · · · · · · · · · · · · · · · · ·
S · · · · · · · · · · · · · · · · · · ·
3 · · · · · · · · · · · · · · · · · · 4 · · · · · · · · · · · · · · · · · ·
5 · · · · · · · · · · · · · · · · · ·
J · · · · · · · · · · · · · · · · G · · · · · · · · · · · · · · · · C · · · · · · · · · · · · · · · ·
-3 · · · · · · · · · · · · · ·
-7 · · · · · · · · · · · · · ·
-8 · · · · · · · · · · · · · ·
-9 · · · · · · · · · · · · · · 1 · · · · · · · · · · · · 2 · · · · · · · · · · · ·
0 · · · · · · · · · · · 2 · · · · · · · · · · ·
4 · · · · · · · · · · · 5 · · · · · · · · · · · 7 · · · · · · · · · · · 9 · · · · · · · · · · ·
D · · · · · · · · E · · · · · · · · N · · · · · · · ·
B · · · · · D · · · · · N · · · · ·
Absolute pressure transmitter 4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART protocol) Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)
0.25 to 32 MPa (36 to 4500 psi)
0.25 to 50 MPa abs (36 to 7200 psi) Refer to "Wetted Parts Material for EJX440A" Table below.
with 1/4 NPT female process connector* with 1/2 NPT female process connector*2*
2*3
3
without process connector (1/4 NPT female on the cover flanges) ASTM-B7M carbon steel
316 SST (ISO A4-70) stainless steel ASTM grade 660 stainless steel
Vertical piping, right side high pressure, and process connection down side Vertical piping, left side high pressure, and process connection down side Horizontal piping and right side high pressure Horizontal piping and left side high pressure
Cast alluminum alloy ASTM CF-8M stainless steel G1/2 female, one electrical connection without blind plugs 1/2 NPT female, two electrical connections without blind plugs M20 female, two electrical connections without blind plugs G1/2 female, two electrical connections and a blind plug 1/2 NPT female, two electrical connections and a blind plug
M20 female, two electrical connections and a blind plug Digital indicator
Digital indicator with the range setting switch (None)
304 SST 2-inch pipe mounting, flat type (for horizontal piping) 304 SST 2-inch pipe mounting, L type (for vertical piping) (None)
Optional specification
/
T0911.EPS
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate materials
has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosive process fluids.
*2: Lower limit of ambient and process temperature is -15°C for capsule code C. *3: Specify the process connections code 3 or 4, when using the process connector for D capsule. Without the process connector, use the 1/4
NPT male piping to directly connect to the cover flange.
Table. Wetted Parts Materials for EJX440A
Wetted parts
material code
#
S
Cover flange Capsule Capsule gasket Drain/Vent plug
316 SST
Process connector
ASTM CF-8M *1 (C-capsule)
316L SST (D-capsule)
Hastelloy C-276 *2 (Diaphragm)
316L SST (Others)
Teflon-coated 316L SST 316 SST
*1: Cast version of 316 SST. Equivalent to SCS14A. *2: Hastelloy C-276 or ASTM N10276. The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
9-9
M03E.EPS
IM 01C25B01-01E
Page 55

9.3 OPTIONAL SPECIFICATIONS

9. GENERAL SPECIFICATIONS
Item Description Code
FM Explosionproof Approval * Explosionproof for Class I, Division 1, Groups B, C and D Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
Factory Mutual (FM)
FM Intrinsically safe Approval * Intrinsically Safe for Class I, Division 1, Groups A, B, C and D, Class II, Division 1, Groups E, F and G and Class III, Division 1 Hazardous Locations. Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II, Division. 2, Groups F and G, and Class III, Division 1 Hazardous Locations.
Combined FF1 and FS1 *
1*3
CENELEC ATEX (KEMA) Flameproof Approval * II 2G EExd IIC T4, T5, T6
CENELEC ATEX
CENELEC ATEX (KEMA) Intrinsically safe Approval * II 1G EEx ia IIC T4
Combined KF2, KS2 and Type n * Type n: II 3G EEx nL IIC T4
CSA Explosionproof Approval *
[For CSA C22.2] Canadian Standards Association (CSA)
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
[For CSA E60079]
Flameproof for Zone1, Ex d IIC T6...T4 Enclosure IP66 and IP67
CSA Intrinsically safe Approval *
[For CSA C22.2]
Intrinsically safe for Class I, Division 1, Groups A, B, C and D, Class II, Division 1,
Groups E,F and G, Class III, Division 1
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II, Division 2,
Groups E,F and G, Class III, Division 1
[For CSA E60079]
Ex ia IIC T4, Ex nL IIC T4
2*3
IECEx Scheme
Combined CF1 and CS1 *
IECEx Intrinsically safe, type n and flameproof Approval *
Intrinsically safe and type n [No. IECEx CSA 05.0005]
Ex ia IIC T4, Ex nL IIC T4
Flameproof [No. IECEx CSA 05.0002]
Flameproof for Zone1, Ex d IIC T6...T4
Contact Yokogawa representative for the codes indicated as ‘-’. *1: Applicable for Electrical connection code 2, 4, 7, and 9. *2: Applicable for Electrical connection code 2 and 7. *3: Not applicable for option code /AL.
1
FF1
1*3
FS1
1
1*3
1*3
FU1
KF2
KS2
KU2
2
CF1
2 *3
CS1
CU1
1*3
SU2
T0912.EPS
9-10
IM 01C25B01-01E
Page 56
9. GENERAL SPECIFICATIONS
Item Description Code
Painting
Color change
Coating change
Terminal cover only
Both sides of amplifier covers, Munsell 7.5 R4/14
Anti-corrosion coating
P PR
X2
Transmitter power supply voltage: 10.5 to 32 V DC ( 10.5 to 30 V DC for intrinsically
Lightning protector
safe type.) Allowable current: Max. 6000 A ( 140 s ), Repeating 1000 A ( 140 s ) 100 times Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Status output
Oil-prohibited use
Oil-prohibited use with dehydrating treatment
*8
*1
*1
Capsule fill fluid
Calibration units
Long vent
Output limits and failure operation
Body option
*2
*3
*4
*5
Stainless steel tag plate Data configuration at factory
European Pressure Directive
Transistor output (sink type) Contact rating :10.5 to 30 VDC, 120 mA DC(max) Low level : 0 to 2 VDC
Degrease cleansing treatment Degrease cleansing treatment and with fluorinated oilfilled capsule.
Operating temperature 20 to 80C( –4 to 176F) Degrease cleansing treatment and dehydrating treatment
Degrease cleansing treatment and dehydrating treatment with fluorinated oilfilled capsule. Operating temperature 20 to 80C( –4 to 176F)
Fluorinated oil filled in capsule P calibration (psi unit) bar calibration (bar unit) M calibration (kgf/cm
2
unit)
(See Table for Span and
Range Limits.)
Total length: 119 mm (standard: 34 mm); Total length when combining with Optional code K1, K2, K5, and K6: 130 mm. Material: 316SST.
Failure alarm down-scale : Output status at CPU failure and hardware error is –5%,
3.2mA DC or less.
NAMUR NE43 Compliant
Output signal limits : 3.8 mA to
20.5 mA
Failure alarm down-scale : Output status at CPU failure and hardware error is –5%, 3.2 mA DC or less.
Failure alarm up-scale : Output status at CPU
failure and hardware error is –110%, 21.6 mA or more. Without drain and vent plugs N1 and Process connection, based on IEC61518 with female thread on both sides of
cover flange, with blind kidney flanges on back. N2 and Material certificate for cover flange, diaphragm, capsule body, and blind kidney
flange 304SST tag plate wired onto transmitter
Data configuration for HART communication type
*6
Data configuration for BRAIN communication type PED 97/23/EC
*7
Category: III, Module: H, Type of Equipment; Pressure Accessory-Vessel, Type of Fluid;
Software damping, Descriptor, Message Software damping
AL K1 K2 K5 K6
K3 D1 D3 D4
U1
C1
C2
C3 N1 N2
N3
N4
CA CB
PE3
Liquid and gas, Group of Fluid: 1 and 2
*1: Applicable for Wetted parts material code S.
T09913.EPS
*2: The unit of MWP (Max. working pressure) on the name plate of the housing is the same unit as specified by Option code D1, D3, and D4. *3: Applicable for vertical impulse piping type (Installation code 7) and Wetted parts material code S. *4: Applicable for output signal code D and E. The hardware error indicates faulty amplifier or capsule. *5: Applicable for Wetted parts material code S; Process connection code 3, 4, and 5; Installation code 9; and Mounting bracket code N.
Process connection faces on the other side of zero adjustment screw. *6: Also see ‘Ordering Instructions’. *7: Applicable for M and H capsule of EJX110A, and all the range of EJX130A and EJX440A. *8: Not applicable for output signal code F.
A
9-11
IM 01C25B01-01E
Page 57
Item Description Code
Material certificate
Pressure test/ Leak test certificate
*1
Cover flange Cover flange, Process connector Test Pressure: 16 MPa(2300 psi) Test Pressure: 25 MPa(3600 psi) Test Pressure: 3.5 MPa(500 psi) Test Pressure: 500 kPa(2000 inH2O) Test Pressure: 50 kPa(200 inH2O) Test Pressure: 32 MPa(4500 psi) Test Pressure: 50 MPa(7200 psi)
*2
*3 *4 *5
*6
*7
*8 *9 *10
*1: Material traceability certification, per EN 10204 3.1B. *2: Applicable for Process connections code 0 and 5. *3: Applicable for Process connections code 1, 2, 3, and 4. *4: Applicable for Capsule code L of EJX110A and Capsule code B of EJX430A and EJX310A. *5: Applicable for Capsule code M and H of EJX110A. *6: Applicable for Capsule code A of EJX430A and EJX310A. *7: Applicable for Capsule code H of EJX430A. *8: Applicable for Capsule code M of EJX310A. *9: Applicable for EJX130A and Capsule code C of EJX440A. *10: Applicable for Capsule code D of EJX440A. *11: Pure nitrogen gas is used for oil-prohibited use (Option code K1, K2, K5, and K6). *12: Pure nitrogen gas or pure water is used for oil-prohibited use (Option code K1, K2, K5, and K6).
9. GENERAL SPECIFICATIONS
Nitrogen(N2) Gas
*11
Retention time: one minute
Nitrogen(N2) Gas or water Retention time: one minute
*12
M01 M11 T12 T13 T01 T11 T04 T09 T08
T0914.EPS
9-12
IM 01C25B01-01E
Page 58

9.4 DIMENSIONS

Model EJX110A
Vertical Impulse Piping Type
52
(2.05)
97
(3.82)
223(9.17)
41
67
(1.61)
(2.64)
Process connector
(optional)
(Installation code 7)
245(9.65)
97
(3.82)
178(7.01)
129
(5.08)
Mounting bracket (L-type, optional)
Vent/drain plugs
Ground terminal
Electrical connection for code 5 and 9.
External indicator Conduit connection
(optional)
Integral
95(3.74)
indicator (optional)
Zero adjustment
Shrouding bolt
for ATEX flameproof
Conduit connection
6
(0.23)
54
(2.13)
9. GENERAL SPECIFICATIONS
Unit: mm (approx. inch)
110(4.33)
12
77(3.03)
ø
High pressure side
(0.47)
54
(2.13)
39
(1.54)
2-inch pipe (O.D. 60.5 mm)
Vent/drain plugs
69(2.72)
ø
Low pressure side
*2
138(5.43)
Horizontal Impulse Piping Type
External indicator Conduit connection
(optional)
54
(2.13)
6
(0.23)
148
(5.83)
Electrical connection for code 5 and 9.
124
(4.88)
(Installation code 9)
89(3.50)
67(2.64)
95(3.74)
41
(1.61)
Conduit connection
Integral Indicator
(optional)
Shrouding bolt
for ATEX flameproof
178(7.01)
Process connector
(optional)
Zero adjustment
Ground
terminal
Vent plug
Drain plug
77(3.03) ø
High pressure side
115
(4.53)
47
(1.85)
Mounting bracket
(flat-type, optional)
2-inch pipe (O.D. 60.5 mm)
*1: When Installation code 8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.) *2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure. *3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.
110 (4.33)
12
(0.47)
54
(2.13)
*3
117
(4.61)
39
(1.54)
129
(5.08)
Low pressure side
F0905.EPS
69 ø
(2.72)
9-13
IM 01C25B01-01E
Page 59
9. GENERAL SPECIFICATIONS
Bottom Process Connection Type
External indicator conduit connection
54
(optional)
(2.13)
6
(0.23)
Electrical connection for code 5 and 9.
Mounting bracket
(optional)
Vent plug
2-inch pipe (O.D. 60.5 mm)
(Installation code B)
95 (3.74)
79
(3.11)
Conduit connection
Integral indicator
(optional)
221 (8.70)
Shrouding bolt (for flame-proof type)
Process connector (optional)
Zero adjustment
Ground terminal
High pressure side
ø77 (3.03)
110 (4.33)
12
(0.47)
(2.13)
(4.61)
188 (7.40)
(1.54)
54
117
Unit : mm (approx.inch)
39
ø69
(2.72)
Low pressure side
129
(5.08)
109 (4.29)
F0906.EPS
9-14
IM 01C25B01-01E
Page 60
Model EJX130A
9. GENERAL SPECIFICATIONS
Vertical Impulse Piping Type
97
(3.82)
52
(2.05)
119
(4.69)
267(10.51)
63
88
(2.48)
(3.46)
Process connector
(optional)
Horizontal Impulse Piping Type
External indicator Conduit connection (optional)
54
(2.13)
6
(0.23)
(Installation code 7)
245(9.65)
178(7.01)
129
(5.08)
Mounting bracket (L-type, optional)
Vent/drain plugs
Ground terminal
(Installation code 9)
111(4.37)
95(3.74)
External indicator Conduit connection (optional)
Zero adjustment
88(3.46)
Electrical connection for code 5 and 9.
95
(3.74)
Integral indicator (optional)
Conduit connection
Conduit connection
Integral Indicator (optional)
6
(0.23)
54
(2.13)
Zero adjustment
12
(0.47)
ø77(3.03)
High pressure side
(0.47)39(1.54)
120(4.72) 110(4.33)
(1.54)
54
(2.13)
110 (4.33) 12
39
Low pressure side
2-inch pipe (O.D. 60.5 mm)
Vent/drain plugs
*2
ø69(2.72)
182(7.17)
Ground
terminal
Vent plug
Drain plug
High pressure side
Electrical connection for code 5 and 9.
Shrouding bolt
(for flame-proof type)
148
124
(5.83)
(4.88)
63
(2.48)
159
178(7.01)
Process connector (optional)
(6.26)
47
(1.85)
Mounting bracket (Flat-type, optional)
2-inch pipe (O.D. 60.5 mm)
*1: When Installation code 8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.) *2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure. *3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the flange.
ø77(3.03)
54
(2.13)
140 (5.51)
ø69(2.72)
129(5.08)
Low pressure side
*3
9-15
IM 01C25B01-01E
Page 61
Model EJX430A, EJX310A
9. GENERAL SPECIFICATIONS
Vertical Impulse Piping Type
(Installation code 7)
245(9.65)
178(7.01)
52
(2.05)
97
(3.82)
223(9.17)
67
(2.64)
41
(1.61)
Process connector
(optional)
97
(3.82)
129
(5.08)
Mounting bracket (L-type, optional)
Vent/drain plugs
Ground terminal
Horizontal Impulse Piping Type (Installation code 9)
(2.13)
6
(0.23)
Electrical connection for code 5 and 9.
External indicator
54
Conduit connection (optional)
89(3.50)
148(5.83)124(4.88)
67(2.64)
95(3.74)
41
(1.61)
115
(4.53)
Electrical connection for code 5 and 9.
External indicator Conduit connection
(optional)
Integral
95(3.74)
indicator (optional)
Zero adjustment
Shrouding bolt
for ATEX flameproof
Conduit connection
Conduit connection
Integral Indicator
(optional)
Shrouding bolt
for ATEX flameproof
178(7.01)
Process connector
(optional)
6
(0.23)
54
Ground
terminal
Drain plug
(2.13)
77(3.03)
ø
High pressure side
Zero adjustment
Vent plug
59(2.32)
110(4.33)
12
(0.47)
77(3.03) ø
High pressure side
*2
39
(1.54)
Vent/drain plug
27
(1.06)
110 (4.33)
12
(0.47)
Unit: mm (approx. inch)
2-inch pipe (O.D. 60.5 mm)
Open to atmosphere (for EJX430A)
ø10(0.39)
*2
69(2.72)
ø
138(5.43)
Low pressure side
39
(1.54)
69 ø
(2.72)
129(5.08)
Open to atmosphere (for EJX430A)
Low
ø5(0.20)
pressure side
27(1.06)
47
(1.85)
Mounting bracket
(flat-type, optional)
2-inch pipe (O.D. 60.5 mm)
*1: When Installation code 8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.) *2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
9-16
F0907.EPS
IM 01C25B01-01E
Page 62
9. GENERAL SPECIFICATIONS
Bottom Process Connection Type
External indicator conduit connection
54
(optional)
(2.13)
6
(0.23)
Electrical connection for code 5 and 9.
Mounting bracket
(optional)
Vent plug
2-inch pipe (O.D. 60.5 mm)
79
(3.11)
(Installation code B)
95 (3.74)
Process connector (optional)
Zero adjustment
Conduit connection
Integral indicator
(optional)
Ground
221 (8.70)
Shrouding bolt (for flame-proof type)
terminal
ø77 (3.03)
High pressure side
110 (4.33)
12
(0.47)
59
(2.32)
188 (7.40)
39
(1.54)
Open to atomosphere (for EJX430A)
ø10 (0.39)
27
(1.06)
Unit : mm (approx.inch)
ø69
(2.72)
Low pressure side
129
(5.08)
109 (4.29)
F0909.EPS
9-17
IM 01C25B01-01E
Page 63
Model EJX440A
9. GENERAL SPECIFICATIONS
Vertical Impulse Piping Type
(Installation code 7)
245(9.65)
178(7.01)
52
119
97
(3.82)
(2.05)
(4.69)
129
(5.08)
Mounting bracket (L-type, optional)
Vent/drain plugs
267(10.51)
63
88
(2.48)
(3.46)
Process connector
(optional)
Ground terminal
Horizontal Impulse Piping Type (Installation code 9)
111(4.37)
95(3.74)
6
(0.23)
54
(2.13)
External indicator Conduit connection (optional)
External indicator Conduit connection (optional)
Zero adjustment
88(3.46)
Electrical connection for code 5 and 9.
95
(3.74)
Integral
indicator
(optional)
Conduit
connection
Conduit connection
Integral Indicator (optional)
6
(0.23)
54
(2.13)
Zero adjustment
ø77(3.03)
High pressure side
120(4.72) 110(4.33)
12
(0.47)
110 (4.33) 12
(0.47)
39
(1.54)
27
(1.06)
39
(1.54)
2-inch pipe (O.D. 60.5 mm)
Vent/drain plugs
*2
ø69(2.72)
182(7.17)
Low pressure side
Ground
terminal
Vent plug
Drain plug
High pressure side
70
(2.76)
2-inch pipe (O.D. 60.5 mm)
*2
Electrical connection for code 5 and 9.
Shrouding bolt
(for flame-proof type)
148
124
47
(5.83)
(4.88)
(1.85)
63
(2.48)
159
(6.26)
Mounting bracket (Flat-type, optional)
178(7.01)
Process connector (optional)
*1: When Installation code 8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.) *2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
ø77(3.03)
ø69(2.72)
129(5.08)
Open to atmosphere
ø5(0.20)
Low pressure side
27
(1.06)
F0910.EPS
9-18
IM 01C25B01-01E
Page 64
9. GENERAL SPECIFICATIONS
Terminal Configuration
Communication terminals (BT200 etc.) connection hook
SUPPLY +
SUPPLY –
Check meter connection hook
CHECK + or ALARM +
CHECK – or ALARM –
< Factory Setting >
Tag Number
Amplifier
Damping
Output Mode
Calibration Range
Lower Range Value
Calibration Range
Upper Range Value Calibration Range
Units
Display Setting
Static Pressure
Display Range
*1: For differential pressure transmitters only. *2: To specify these items at factory, /CA or /CB option is
required.
As specified in order ‘2 sec.’ or as specified in order
*2
‘Linear’ unless otherwise specified in order As specified in order As specified in order Selected from the followings. Only one
unit can be specified. [Differential/gauge pressure transmitter] mmH2O, mmH2O(68˚F),mmAq, mmWG, mmHg, Pa, hPa, kPa, MPa, mbar, bar, gf/cm2, kgf/cm2, inH2O, inH2O(68˚F),inHg, ftH2O, ftH2O(68˚F) or psi. [Absolute pressure transmitter] torr, Pa abs, hPa abs, kPa abs, MPa abs, mbar abs, bar abs, mmH2O abs, mmH2O(68˚F) abs, mmHg abs, gf/cm2 abs, kgf/cm2 abs, inH2O abs, inH2O abs(68˚F), inHg abs, ftH2O abs, ftH2O abs(68˚F) , atm, or psia.
Designated differential pressure value specified in order. (%, Engineering unit or user scaled value.) Display mode 'Linear' or 'Square root' is also as specified in order.
'0 to 25 MPa' for M and H capsule of
*1
EJX110A, '0 to 16 MPa' for L capsule, and '0 to 32 MPa' for EJX130A. Display unit is selectable from the units listed in above 'Calibration Range Units'.
Terminal Wiring
*1*2
*1: When using an external indicator or check meter, the internal resistance must be 10 or less. A check meter or indicator cannot be connected when /AL option is specified. *2: Not available for fieldbus communication type.
T0915.EPS
SUPPLY CHECK
or
ALARM
+
Power supply and output terminal
– +
External indicator (ammeter) terminal
or Status contact output terminal
+ –
(when /AL is specified) Ground terminal
*1*2
*2
F0911.EPS
9-19
IM 01C25B01-01E
Page 65

REVISION RECORD

Title: EJX110A, EJX130A, EJX310A, EJX430A and EJX440A
Differential Pressure and Pressure Transmitters
Manual No.: IM 01C25B01-01E
Edition Date Page Revised Item
1st Mar. 2004 New publication
2nd Apr. 2004 Revise words and phrases.
2-6 2.9.3 • Correct Ambient temperature –60 ⇒ –50 4-4 4.5 • Change the description of rotation angle. 8-3 8.4 • Add Allen wrench nominal 3mm to Table 8.4.1.
3rd Feb. 2005 Re-number figure and table title.
i Add subsection 6.3.5.
ii Add note for Safety Transmitter. 1-1 1. • Add note for Fieldbus communication type. 1-3 1.1 • Add (f) Modification. 2-5 2.9.2 • Modify descriptions and instructions for CSA certification 2-3 2.9 • Add NOTE for fieldbus communication type. 2-7 2.9.3 • Correct number in Note 4. 10 MINUTES 5 MINUTES 2-8 • Delete WARNING on non-incendive power supply.
• Correct number for Electrical data Ci. 6 nF ⇒ 10 nF
3-1 3. • Correct label of the switch in the figure. N ⇒ E, Y ⇒ D
• Add descriptions in Note 2. 4-3 4.4.1 • Add description about process connector in 3). 4-4 4.6 • Add section 4.6. 6-1 6.3.1, 6.3.2 • Add limitation/note when /AL is specified. 6-2 6.3.4 • Add limitation when /AL is specified. 6-2 6.3.5 • Add subsection 6.3.5. 7-3 7.2.1 • Add descriptions about zero adjustment.
9-1, 9-2 9.1 • Add notes for FOUNDATION fieldbus communication type.
• Add capsule code H.
9-4, 9-5 9.2 • Add output signal code -F and capsule code H.
9-6 9.3 • Add CSA approvals and note *2 and *3 9-8 9.4 • Add note *3.
9-10 9.4 • Add notes for /AL and FOUNDATION Fieldbus.
4th Sep.2005 1-1 1. Add model names to the manual coverage.
2-3 through 2-8 2 Add applicable standard and certificate number for each approval.
2-11 2.10 Change australian reference standard. 2-11 2.11 Add descriptions for PED. 2-12 2.11 Add section 2.12.
4-1 4.1 Add model name. 4-2 4.3 Add table 4.1.
IM 01C25B01-01E
Page 66
8-5 8.4.3 Add table for torque.
Add notes for reassembling EJX130A and EJX440A.
8.4.4 Add table for torque.
9-1 through 9-18 9. Add specifications, codes, and dimensions for EJX130A,
EJX310Aand EJX440A.
5th July 2006 2-8 2.9.3 Change applicable standards for ATEX type n.
IM 01C25B01-01E
Loading...