YOKOGAWA DPharp EJA110A, Dpharp vigilantplant EJA Series, DPharp EJA210A, DPharp EJA120A, DPharp EJA130A User Manual

...
Page 1
User’s Manual
Model EJA Series HART Protocol
IM 01C22T01-01E
Yokogawa Electric Corporation
IM 01C22T01-01E
7th Edition
Page 2
CONTENTS
CONTENTS
PRELIMINARY ........................................................................................................ ii
1. ZERO POINT ADJUSTMENT .......................................................................1-1
1.1 Zero Point Adjustment ........................................................................ 1-1
1.1.1 Using the HART Communicator................................................... 1-2
1.1.2 Using the Transmitter Zero-adjustment Screw ............................ 1-2
1.2 Auto LRV (Change Low Range Value)............................................... 1-3
1.2.1 Using Model 275 — Apply Values ............................................... 1-3
1.2.2 Setting the Range Using the Range-setting Switch .................... 1-3
2. HART COMMUNICATOR OPERATION ....................................................... 2-1
2.1 Conditions of Communication Line ..................................................... 2-1
2.1.1 Interconnection Between DPharp and HART Communicator ...... 2-1
2.1.2 Communication Line Requirements ............................................. 2-1
2.2 Basic Operation of the HART Communicator (Model 275) ................ 2-2
2.2.1 Keys and Functions ...................................................................... 2-2
2.2.2 Display.......................................................................................... 2-3
2.2.3 Calling Up Menu Addresses ........................................................ 2-3
2.2.4 Entering, Setting, and Sending Data ........................................... 2-4
2.3 Parameters.......................................................................................... 2-5
2.3.1 Parameter Usage and Selection .................................................. 2-5
2.3.2 Menu Tree .................................................................................... 2-6
2.3.3 Setting Parameters ....................................................................... 2-7
(1) Tag No......................................................................................... 2-7
(2) Unit.............................................................................................. 2-7
(3) Range Change............................................................................ 2-7
(4) Output Mode (Linear/Sq root) ..................................................... 2-8
(5) Damping Time Constants............................................................ 2-9
(6) Output Signal Low Cut Mode Setup............................................ 2-9
(7) Bi-directional Flow Measurement.............................................. 2-10
(8) Integral Indicator Display Mode................................................. 2-10
(9) Integral Indicator Scale ............................................................. 2-10
(10) Unit for Displayed Temperature ................................................. 2-12
(11) Unit for Displayed Static Pressure ............................................ 2-12
(12) Test Output................................................................................ 2-12
(13) Sensor Trim ............................................................................... 2-13
(14) Trim Analog Output ................................................................... 2-14
(15) Burst Mode................................................................................ 2-16
(16) Multidrop Mode ......................................................................... 2-16
(17) External Switch Mode ............................................................... 2-17
(18) Software Write Protect .............................................................. 2-17
(19) Hardware Write Protect and Burnout Direction
(with Optional code /F1)............................................................ 2-19
(20) H2O Unit Select......................................................................... 2-19
2.4 Self-Diagnostics ................................................................................ 2-19
2.4.1 Checking for Problems............................................................... 2-19
(1) Identify Problems with HART Communicator............................ 2-19
(2) Checking with Integral Indicator................................................ 2-20
3. PARAMETER LISTS ..................................................................................... 3-1
REVISION RECORD
FD No. IM 01C22T01-01E 7th Edition: Jan. 2008(KP) All Rights Reserved, Copyright © 1995, Yokogawa Electric Corporation
IM 01C22T01-01E
Page 3

PRELIMINARY

This manual describes the function, performance, and operating procedures of the DPharp EJA Series with HART protocol. The DPharp EJA Series with HART protocol uses the same pressure sensing element as in DPharp EJA with BRAIN protocol. Therefore, this manual describes only the functions unique to HART Communicator operating procedures which are not covered in the DPharp EJA with BRAIN protocol instruction manual. For the items listed below which are common to both the HART protocol and BRAIN protocol, see the applicable user’s manuals listed in Table 1.
Contents of Individual User’s Manuals
•INTRODUCTION
•HANDLING CAUTIONS
• COMPONENT NAMES
•INSTALLATION
•INSTALLING IMPULSE PIPING
•WIRING
•OPERATION — Zero Point Adjustment
(For BRAIN Protocol)
BRAIN TERMINAL BT200 OPERATION
(For BRAIN Protocol)
•MAINTENANCE
PARAMETER SUMMARY
(For BRAIN Protocol)
•GENERAL SPECIFICATIONS
Contents of this User’s Manual for HART Protocol —IM 01C22T01-01E—
ZERO POINT ADJUSTMENT
HART Communicator OPERATION
PARAMETER LISTS
F01.EPS
Figure 1. Relationship between Individual Manuals and
HART Manual Contents
Table 1. Individual User’s Manuals
Manual No.Model
EJA110A, EJA120A, EJA130A IM 01C21B01-01E EJA210A, EJA220A IM 01C21C01-01E EJA310A, EJA430A, EJA440A IM 01C21D01-01E EJA510A, EJA530A IM 01C21F01-01E EJA110, EJA120 IM 01C22B01-01E EJA210, EJA220 IM 01C22C01-01E EJA310, EJA430 IM 01C22D01-01E EJA118W, EJA118N, EJA118Y IM 01C22H01-01E EJA438W, EJA438N IM 01C22J01-01E EJA115 IM 01C22K01-01E
T01.EPS
PRELIMINARY
CAUTION
Matching of communicator DD and instrument DD Before using model 275 HART communicator, check that the DD(Device Description) installed in the communicator matches to that of instruments to set up. To check the DD in the instrument or the HART communicator, follow the steps below. If the correct DD is not installed in the communi­cator, you must upgrade the DD at the HART official programming sites. For communication tools other than Model 275 HART communicator, contact vendors of each for upgrade information.
1. Checking the DD in the instrument
1) Connect the communicator to the instrument to set up.
[]
[]
.
.
2) Call "Device setup" and press
3) Call "Review" and press
4) By pressing [NEXT] or [PREV], find "Fld dev rev" to show the DD of the instrument.
[Example]
EJA: Review Fld dev rev 2
"The instrument DD is
HELP PREV NEXT EXIT
Version 2."
F02.EPS
2. Checking the DD in Model 275 HART commu­nicator
1) Turn on the communicator alone.
2) Call "Utility" from main menu and press
3) Call "Simulation" and press
[]
.
[]
4) Select "YOKOGAWA" from manufacturers
list by pressing
and press
[ ]
[]
.
5) Select the model name of the instrument(i.e.
EJA) by pressing
[ ]
and press
[]
to
show the DD of the communicator.
[Example]
HART Communicator Fld dev rev 1 Dev v1, DD v2 2 Dev v2, DD v1
Version 1 and 2.
"The communicator DD supports Version 1 and 2."
F03.EPS
.
ii
IM 01C22T01-01E
Page 4
1. ZERO POINT ADJUSTMENT

1. ZERO POINT ADJUSTMENT

After operating preparation is completed, adjust the zero point. The zero point adjustment can be made using either of the following two methods.
For output signal checking, display the parameter % rnge in the HART Communicator.
EJA: Process variable 1 Pres 0.012nnH2O 2 % range 0.00% 3 A01 Out 4.002mA 4 Snsr temp 38.1C 5 Static pres
HELP DIAG HOME ESC
HART Communication display
Zero-adjustment screw
F0101.EPS
Using the Transmitter Zero-adjustment
Screw
Before using the zero-adjustment screw outside the transmitter case, confirm the following.
Ext SW mode must be ENABLE. See Subsection
2.3.3 (17) for the setting procedure.
• Use a slotted screwdriver to turn the zero-adjustment screw. Turn the screw clockwise to increase the output or counterclockwise to decrease the output, the zero point adjustment can be adjusted with a resolution of 0.01% of the setting range.
The degree of zero adjustments varies with the screw turning speed. Therefore, turn the screw slowly for fine adjustment and quickly for coarse adjustment.
Using the HART Communicator
Zero point can be adjusted by simple key operation of the HART Communicator.
Select parameter Zero Trim, and press the OK (F4) key twice. The zero point will be adjusted automati­cally to the output signal 0% (4 mA DC). Confirm that the setting value displayed for the parameter % rnge is 0.0% before pressing the OK (F4) key. See Subsec­tion for HART Communicator operating procedures.

1.1 Zero Point Adjustment

The DPharp supports several adjustment methods. Select the method best suited for conditions matching
the state of the site. Note that output signal can be checked by HART
Communicator.
Adjustment Method
Zero adjustment using the HART Communicator
Zero adjustment using the external zero­adjustment screw
Set the present input to 0%. P.1-2 ‘Zero trim’
Adjust output to the reference value obtained using other means. P.1-2 ‘Lower sensor trim’
Adjust zero point using the zero­adjustment screw on the transmitter. This permits zero adjustment without using the HART Communicator. Accurately adjust the output current to 4mA DC or other target output value using an ammeter that accurately reads output currents.
Description
Adjust for 0% output at input level of 0%.
If the input level cannot easily be made 0% (because of tank level, etc.), adjust output to the reference value obtained using other means, such as a glass gauge.
T0101.EPS
CAUTION
Do not turn off the power to the transmitter immediately after a zero adjustment. Powering off within 30 seconds after a zero adjustment will return the adjustment back to the previous settings.
1-1
IM 01C22T01-01E
Page 5
1. ZERO POINT ADJUSTMENT

1.1.1 Using the HART Communicator

(1) Zeroing — Zero trim
NOTE
Zero trim carries out the zero adjustment and
sets the input values at present, equal to 0 mmH2O. Use this setting to set LRV = 0 mmH2O.
1. Device setup
2. Diag/Service
3. Calibration
3. Sensor trim
1. Zero trim
1
EJA: WARN-LOOP should be removed from automatic control
ABORT OK
2
EJA: WARN-This will affect sensor calibration
ABORT OK
3
EJA: Apply O input to sensor
ABORT OK
(2) Arbitrary Level Adjustment — Lower
Sensor Trim
This zero adjustment applies to tank level measure­ments, etc. where the actual tank level cannot be set to zero. For this adjustment, use the actual tank level obtained with a glass gauge or the like to meet the DPharp output.
DPharp span: 0 to 2500 mmH Actual level: 1350 mmH2O Transmitter output: 1383 mmH2O
(OK)
Press OK (F4).
(OK)
Press OK (F4).
(OK)
A pressure of 0 mmH2O is applied. Press OK (F4) after the pressure has become stable.
F0102.EPS
O
2
1. Device setup
2. Diag/Service
3. Calibration
3. Sensor trim
2. Lower Sensor Trim
1
EJA: Apply low pressure
(OK)
ABORT OK
2
EJA: Press OK when pressure is stable
ABORT OK
3
EJA: ENTER applied Pressure Value
0.000 mmH2O
0.000
HELP DEL ABORT ENTER
Check the tank level at present, and press OK (F4).
(OK)
Press OK (F4).
‘1 3 5 0’
(ENTER)
Enter the value of the actual level (1350 mmH (F4).
O), and press ENTER
2
F0104.EPS
NOTE
Lower Sensor trim adjusts the input value at
present. See Fine Input Adjustment for detail.
1.1.2 Using the Transmitter Zero-adjust­ment Screw
Turn the zero-adjustment screw on the outside of the transmitter case using a slotted screwdriver. Turn the screw to the right to increase the zero point or to the left to decrease the zero output; the zero adjusts in increments of 0.01% of the range setting.
Note that the amount of adjustment to the zero point changes according to the speed at which the screw is turned. To make fine adjustments, turn the screw slowly; to make coarse adjustments, turn the screw quickly.
Note: When a zero point adjustment has been made do not turn of
the transmitter less than 30 seconds after adjustment.
DPharp
2500 mmH2O
Actual level 1350 mmH
0 mmH
2
O
2
O
F0103.EPS
1-2
IM 01C22T01-01E
Page 6
1. ZERO POINT ADJUSTMENT

1.2 Auto LRV (Change Low Range Value)

1.2.1 Using Model 275 — Apply Values

Display the Apply Values display, and adjust the zero point as follows:
1. Device setup
3. Basic setup
3. Re-range
2. Apply values
1
EJA: WARN-LOOP should be removed from automatic control
ABORT OK
2
EJA: Set the: 1 4mA 2 20mA 3 Exit
ABORT ENTER
3
EJA: Apply New 4ma input
ABORT OK
‘Pressure stabilizing’
4
EJA: Current applied Process value:
0.06 mmH2O 1 Set as 4mA value 2 Read new value 3 Leave as found
ABORT ENTER
(OK)
Press OK (F4).
(ENTER)
Select 4 mA, and press ENTER (F4).
(OK)
Apply a pressure corresponding to 0% of the measurement range.
(ENTER)
LRV (0%) is read as –0.06 mmH2O. Select Set as 4mA value, and press ENTER (F4).
F0105.EPS
1.2.2 Setting the Range Using the Range­setting Switch
With actual pressure(s) being applied to the transmitter, the range-setting switch (push-button) attached to the integral indicator plate and the external zero-adjust­ment screw allow users to change the lower- and upper-range values for the measurement range (LRV and URV) without the use of a HART Communicator. However, a change in the display settings (scale range and engineering unit) for the integral indicator requires a HART Communicator.
Follow the procedure below to change the LRV and URV settings.
Example: Rerange LRV to 0 and HRV to 20 kPa.
1) Connect the transmitter and allow them to warm up
for at least five minutes.
2) Press the range-setting push-button.
The integral indicator then displays LSET.
3) Apply a pressure of 0 kPa (atmospheric pressure) to
the high-pressure side of the transmitter.
4) Turn the external zero-adjustment screw (either in
the output-increase or -decrease direction). The integral indicator displays the output signal (in
(Note 2)
%).
5) Adjust the output signal to 0% (1 V DC) by
rotating the external zero-adjustment screw. Doing so completes the LRV setting.
6) Press the range-setting pushbutton.
The integral indicator then displays USET.
7) Apply a pressure of 20 kPa to the high-pressure
side of the transmitter.
(Note 1)
8) Turn the external zero-adjustment screw (either in
the output-increase or -decrease direction). The integral indicator displays the output signal (in
(Note 2)
%).
9) Adjust the output signal to 100% (5 V DC) by
rotating the external zero-adjustment screw. Doing so completes the URV setting.
10) Press the range-setting pushbutton.
The transmitter then switches back to the normal operation mode while maintaining the measurement range at 0 to 20 kPa.
Note 1: Wait until the pressure inside the pressure-detector section
has stabilized before proceeding to the next step.
Note 2: If the pressure applied to the transmitter exceeds the
previous LRV (or URV) , the integral indicator may display error number “Er.07” (In this case, the output signal percent and “Er.07” are displayed alternately every two seconds). Although “Er.07” is displayed, there is no need to worry and you may proceed to the next step. However, should any other error number be displayed, take the appropriate measure in reference to Section 2.4 Self-Diagnostics, “Errors Messages.”
(Note 1)
1-3
IM 01C22T01-01E
Page 7
IMPORTANT
1. Do not turn off the power to the transmitter immediately after completion of the change in the LRV (and/or URV) setting(s). Note that powering off within thirty seconds after setting will ca use a return to the previous settings.
2. Changing LRV automatically changes URV to the following value.
URV previous URV (new LRV previous LRV)
3. If the range-setting push-button and external zero-adjustment screw are not touched during a range-change operation, the transmitter automatically switches back to the normal operation mode.
Integral indicator
1. ZERO POINT ADJUSTMENT
Note: Use a thin bar which has a blunt tip, e.g.,
a hexagonal wrench, to press the range­setting push-button.
Figure 1.2.1Range-setting Switch
Range-setting switch (Push-button)
F0106.EPS
1-4
IM 01C22T01-01E
Page 8

2. HART COMMUNICATOR OPERATION

L =
65×10
6
(R×C)
(Cf+10,000)
C
2. HART COMMUNICATOR OPERATION
2.1 Conditions of Communica­tion Line
2.1.1 Interconnection Between DPharp
and HART Communicator
The HART Communicator can interface with the transmitter from the control room, the transmitter site, or any other wiring termination point in the loop, provided there is a minimum of 250 between the connection and the power supply. To communicate, it must be connected in parallel with the transmitter; the connections are non-polarized. Figure 2.1.1 illustrates the wiring connections for direct interface at the transmitter site for the DPharp. The HART Communi­cator can be used for remote access from any terminal strip as well.
Control room
Relaying terminals
Terminal
board
Distributor

2.1.2 Communication Line Requirements

Specifications for Communication Line:
Supply voltage(general use type); 16.4 to 42 V DC Load resistance; 250 to 600 W (Including cable
resistance) Minimum cable size; 24 AWG, (0.51 mm diameter) Cable type; Single pair shielded or multiple pair with
overall shield Maximum twisted-pair length; 10,000 ft (3,048 m) Maximum multiple twisted-pair length; 5,000 ft
(1,524 m) Use the following formula to determine cable length
for a specific application;
Where: L = length in feet or meters.
R=resistance in ohms, current sense
resistance plus barrier resistance. C=cable capacitance in pF/ft, or pF/m. Cf=Maximum shunt capacitance of field
devices in pF.
DPharp
HART communicator
Figure 2.1.1 Interconnection Diagram
HART
communicator
F0201.EPS
2-1
IM 01C22T01-01E
Page 9
2. HART COMMUNICATOR OPERATION

2.2 Basic Operation of the HART Communicator (Model 275)

2.2.1 Keys and Functions

Communication Cable
LCD (Liquid crystal display)
(21 characters×8 lines)
Function keys
Functions of the keys are indicated on the display.
Pressing (HOME) when the display is
EJA:YOKOGAWA Process variables 1 Pres 0.00 mmH2O 2 % rnge 0.00 % 3 A01 Out 4.000mA 4 Snsr temp 37.0C 5 Static Pres
HELP HOME
as shown changes the display to “Online” menu. (See 2.2.2 “Display”.)
Moves the highlighting cursor on the display to select the desired item.
Power ON/OFF
Shift keys
Use to enter alphabetic characters.
Hot key
Call up setting menu
1. Keypad Input
2. Enable Write
3. New Password
1. Changes the display contents.
2. Moves the position where a number or character is to be entered.
Pressing calls up the display corresponding to the item pointed with the highlighting cursor.
Pressing returns to the previous display. (See 2.2.3.)
Alphanumeric keys
1.Enters numbers and characters.
2.Selects the desired menu item with the corresponding number. (See 2.2.4.)
Pressing single key enters the number. Pressing the key with shift key enters the alphabetic character.
(Press) (ENTER)
To enter “7”,
To enter “C”,
“7”
“C”
F0202.EPS
Figure 2.2.1 The HART Communicator
2-2
IM 01C22T01-01E
Page 10
2. HART COMMUNICATOR OPERATION

2.2.2 Display

The HART communicator searches for a transmitter on the 4 to 20mA loop when it is turned on. When the HART communicator is connected to the transmitter, Online menu (Top menu) is started automatically and the following display appears. If no transmitter is found, you select Online menu.
Manufacturer’s transmitter type
EJA :YOKOGAWA
<b>
<c>
<d> <e>
Figure 2.2.2 Display
Online 1 Device setup 2 Pres 0.13 mmH2O 3 A01 Out 4.001 mA 4 LRV 0.00 mmH2O 5 URV 3000.00 mmH2O
Pressing one of the SHIFT keys makes the arrow mark corresponding to the pressed key appear.
Appears when the voltage level of the battery is low.
<a> appears and flashes during communication
between the HART communicator and the transmitter. At Burst mode, appears.
<b> The menu items selected from the previous menu. <c> The items to be used from the menu of <b>.
<d> or appears when the item is scrolled out of
the display.
<e> The labels of function corresponding to each
function key appears. These labels reflect cur­rently available choices.
Tag (8 Characters)
Function keys
The highlighting cursor
<a>
F0203.EPS
Function Key Labels
F1
HELP
access on-line
help
RETRY
try to re-
establish
communication
EXIT
leave the
current menu
YES
answer to
yes/no question
ALL
include current
Hot Key item on
Hot Key Menu for all devices
SAVE
save information
to
communicator
SEND
send data to
device, or mark
data to send
F2
ON/OFF
activates or
deactivates a
binary variable
DEL
delete current
character or Hot
Key Menu item
SEND
send data to
device, or mark
data to send
PGUP
move up one
help screen
PREV
go to previous message in a
list of messages
EDIT
edit a variable
value
ADD
add current item
to Hot Key
Menu
F3
ABORT
terminate
current task
ESC
leave value
unchanged
QUIT
terminate session
because of a comunication
error
PGDN
move down one
help screen
NEXT
go to next
message in the
list of messages
HOME
go to the top
menu in the
device
description
BACK
go back to
menu from which HOME was pressed
F4
OK
acknowledge
information on
screen
ENTER
accept user­entered data
NEXT
leave the
current menu
NO
answer to
yes/no question
SKIP
do not mark
variable to be
sent in off-line
configuration
ONE
include Hot Key
item for one
device
F0204.EPS
Key Operation
There are two choices to select the desired menu item.
1. Use the or key to select the desired item, and then press the key.
2. Press the number displayed for the desired item.
• To return to the previous display, press the key.
* If
ABORT, ESC
and
are displayed,
EXIT
press the desired function key.
Example: Call up the Tag item, to change the tag.
Check to see where item Tag is located in the menu configuration. Then, call up Tag item on the display according to the menu configuration.

2.2.3 Calling Up Menu Addresses

Subsection 2.3.2 shows the configuration of all menu items available with the HART communicator. The desired item can be displayed with ease by understand­ing the menu configuration.
When the HART communicator is connected to the transmitter, Online menu will be displayed after power is turned on. Call up the desired item as follows:
2-3
Device setup Pres P01 Out LRV URV
Tag Unit Re-range Device information .
. .
Process variables Diag/Service Basic Setup Detailed Setup Review
EJA:YOKOGAWA Tag YOKOGAWA YOKOGAWA
HELP DEL ESC ENTER
IM 01C22T01-01E
Page 11
2. HART COMMUNICATOR OPERATION
Display Operation
1
EJA:YOKOGAWA Online 1 Device setup 2 Pres 3 A01 Out 4 LRV 5 URV
DEL SET ESC ENTER
2
EJA:YOKOGAWA Device setup 1 Process Varlables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5 Review
DEL SAVE HOME ENTER
3
EJA:YOKOGAWA Basic Setup 1 Tag 2 Unit 3 Re-range 4 Device information 5 Xfer fnctn
HELP
DEL SAVE HOME ENTER
4
EJA:YOKOGAWA Tag YOKOGAWA YOKOGAWA
or
Display appears when the
1 HART Communicator is turned on. Select Device setup.
×2
or
Select Basic setup.
Select Tag.
The display for Tag setting appears.
When the setting display shown above appears, enter the data as follows:
Character to
be entered
F
I
C
-
1
A
Deletes
characters.
Operation Display
FOKOGAWA
FIKOGAWA
FICOGAWA
FIC-GAWA
FIC-1AWA
FIC-1AWA
FIC-1A
(DEL)
F0207.EPS
DEL ESC
HELP DEL ENTER
F0205.EPS

2.2.4 Entering, Setting, and Sending Data

The data input using the keys are set in the HART communicator by pressing ENTER (F4). Then, by pressing SEND (F2), the data is sent to the transmitter. Note that the data is not set in the transmitter if SEND (F2) is not pressed. All the data set with the HART communicator is held in memory unless power is turned off, every data can be sent to the transmitter at once.
Operation Entering data on the Tag setting display.
Example: To change from Tag YOKOGAWA to FIC-1A.
Call up the Tag setting display.
1. Device setup
3. Basic setup
1. T ag
Display Operation
5
EJA:YOKOGAWA Tag YOKOGAWA FIC-IA
HELP DEL ESC ENTER
6
EJA:YOKOGAWA Basic setup 1 Tag 2 Unit 3 Re-range 4 Device information 5 Xfer fncth
HELP SEND HOME ENTER
7
EJA:FIC-1A Basic Setup 1 Tag 2 Unit 3 Re-range 4 Device information 5 Xfer fncth
HELP SAVE HOME ENTER
(ENTER)
After entering the data, set the HART communicator with the data entered by pressing ENTER (F4).
(SEND)
Send the data to the transmitter by pressing SEND (F2).
* is flashed during communica­tion.
disappears, and the
SEND
transmission is complete.
F0208.EPS
EJA:YOKOGAWA Tag YOKOGAWA YOKOGAWA
HELP DEL ESC ENTER
F0206.EPS
2-4
IM 01C22T01-01E
Page 12
2. HART COMMUNICATOR OPERATION

2.3 Parameters

2.3.1 Parameter Usage and Selection

Before describing the procedure for setting parameters, we present the following table showing how the prameters are used and in what case.
Table 2.3.1 Parameter Usage and Selection
Item HART Communicator Description Page
Memory
Transmitter
Display
HART output
Monitoring
Maintenance
Adjustment
Engineering unit Range
Output mode
Damping time constant
Output signal low cut mode
Bi-direction flow measurement mode
H
O unit selection
2
Unit for displayed temperature
Unit for displayed static pressure
Integral indicator display mode
Integral indicator scale Burst mode
Multi-drop mode
Test output Self-diagnostics
Output when CPU error has occurred
External volume protect/permit
Software Write Protect
Zeroing Sensor trim Analog output trim
Tag Descriptor Message Date Unit LRV/URV Apply values Xfer fnctn
Damp
Low cut
Cut mode Bi-dire mode
H
O Unit select
2
Snsr temp unit
Static pres unit
Display fnctn
Display mode
Engr disp range Burst option Burst mode Poll addr Auto poll Pres % rnge A01 out Snsr temp Static pres Engr display Loop test Self test
Status A01 Alarm typ
Ext SW mode
Write protect Enable write New password Zero trim Lower/Upper sensor trim D/A trim, Scaled D/A trim
Tag number, Up to 8 characters Up to 16 characters Up to 32 characters xx/yy/zz inH2O, inHG, ftH2O, mmH2O, mmHG, psi, bar, mbar, g/cm2, kg/cm2, Pa, kPa, MPa, torr, atm Set the calibration range by the keypad Range for 4 to 20 mA DC signal is set with actual input applied. Sets mode for output signal to “linear mode” (proportional to input differential pressure)
or to “Square root mode” (proportional to flow). Adjust the output response speed for 4 to 20 mA DC. 0.2, 0.5, 1, 1.5, 2, 4, 6, 8, 16, 32
(sec) Used mainly to stabilize output near 0 if output signal is the square root mode. Two
mode are available: forcing output to 0% for input below a specific value, or changing to proportional output for input below a specific value.
Linear or Zero Used to measure bi-directional flows.
at 4°C (39.2°F)/at 20°C (68°F) Sets a unit for temperature displayed on the model 275.
Sets a unit for static pressure displayed on the model 275.
Sets mode for integral indicator to “linear mode” (proportional to input differential pressure) or to “Square root mode” (proportional to flow).
Set the following 5 types of integral indicator scale ranges and unit: “% scale indicator”, “use set scale indicator”, “alternate indication of user set scale and % scale”, “input pressure display” and “alternate indication of input pressure and % scale.
Engr unit/Engr disp LRV/Engr disp URV/Engr disp point. Selection of the data to be sent continuously (Pres/% rnge/A01 out). ON/OFF switching of burst mode. Setting the polling address (1 to 15). ON/OFF switching of multi-drop mode. Pressure variable % output variable 4 to 20 mA output variable Sensor temperature Static pressure Displays output as on an LCD. settable in the engr disp range. Used for loop checks. Output can be set freely from –5% to 110% in 1% step.
Check using the self-test command. If an error is detected, the corresponding message is displayed.
Display of the result of self-test, calibration of transmitter. Display the status of 4 to 20 mA DC output when a failure
Display/set the external volume protect/permit for LRV (URV) setting.
Displays the permit/protect status of setting changes depending on communications. Write protect status is released for 10 minutes when the password is entered. Setting a new password. Set the current input value to 0 kPa. Adjust only measured pressure variable. Adjust the output value at the points of 4 mA and 20 mA.
NOTE
Do not turn off the transmitter as soon as HART Communicator settings (sending) have been made. If the transmitter is turned of less than 30 seconds after parameters have been set, the set data will not be stored and the terminal returns to previous settings.
P.2-7
P.2-8
P.2-9
P.2-10 P.2-19
P.2-12
P.2-10
P.2-11
P.2-10
P.2-16
P.2-12
P.2-19
P.2-17
P.1-2 P.2-13 P.2-14
T0201.EPS
2-5
IM 01C22T01-01E
Page 13

2.3.2 Menu Tree

2. HART COMMUNICATOR OPERATION
Online Menu
1 DEVICE SETUP 2 Pres 3 A01 Out 4LRV 5URV
1 PROCESS
VARIABLES
2DIAGNOSTICS
AND SERVICE
3 BASIC SETUP
4 DETAILED
SETUP
1 Pressure 2 Percent Range 3 Analog Output 4 Sensor Temperature 5Static Pressure 6 Engineering Unit 7 Engineering Display
1 TEST/STATUS
2 Loop Test
3 CALIBRATION
1Tag 2 Unit 3 RERANGE
4 DEVICE INFO 5Transfer Function 6 Damp 7 Low Cut 8 Cut Mode
1 SENSORS
2SIGNAL
CONDITION
3 OUTPUT
CONDITION
Hot Key 1LRV
1 Self Test 2Status
1 RERANGE
2 TRIM ANALOG
OUTPUT
3 SENSOR TRIM
1 Keypad Input 2 Apply Values
1 Date 2 Descriptor 3 Message 4Write Protect
1Pressure Sensor
2Temperature
Sensor
3Static Pressure
Sensor
1 PROCESS
VARIABLES
2 RERANGE 3 Unit 4Transfer Function 5 Damp 6 Low Cut 7 Cut Mode 8Bi-dir Mode 9 H2O Unit Select
1 PROCESS
VARIABLES
1 Keypad Input
2Wrt protect menu
1 Keypad Input 2 Apply Values
1Digital-to-Analog Trim 2 Scaled Digital-to-Analog Trim
1 Zero Trim 2 Pressure 3 Lower Sensor Trim 4 Upper Sensor Trim 5 Sensor Trim Points
1 Zero Trim
1 Percent Range 2 Pressure 3 Unit 4 Sensor Trim
1 Sensor Temperature 2 Sensor Temperature Unit
1Static Pressure 2Static Pressure Unit
1 Pressure 2 Percent Range 3 Sensor Temperature
1 Keypad Input 2 Apply Values
1 Pressure 2 Percent Range 3 Analog Output 4 Sensor Temperature 5Static Pressure 6 Engineering Unit 7 Engineering Display
2 Pressure 3 Lower Sensor Trim 4 Upper Sensor Trim 5 Sensor Trim Point
2URV 3 Unit 4 LSL 5 USL 6Min Span
1Write protect 2 Enable wrt 10 min 3 New password 4 Software seal
5 REVIEW
4DISPLAY
CONDITION
5 DEVICE
INFORMATION
2 ANALOG
OUTPUT
3 Analog Output
Alarm
4 HART OUTPUT
1Display Mode 2Display Function 3 Engineering
Display Range
1Field Device Info 2 Sensor Info 3 Self Test
2-6
1 Loop Test 2Digital-to-Analog Trim 3 Scaled D/A Trim
1 Poll Address 2 Number of Request Preambles 3 Burst Mode 4 Burst Option
1 Engineering Unit 2 Engineering Display LRV 3 Engineering Display URV 4 Engineering Display Point
F0209.EPS
IM 01C22T01-01E
Page 14
2. HART COMMUNICATOR OPERATION

2.3.3 Setting Parameters

(1) Tag No.
To change the Tag No., see section 2.2.4 Entering, Setting, and Sending Data.
Up to 8 characters can be set with Tag. The maximum number of characters to be set for other items is as shown below. With Option code /CA, the Descriptor is filled in at the factory as specified in the order.
Item The Number of Characters
Tag Descriptor Message Date
Example: To change from Tag YOKOGAWA to FIC-1A.
Call up the Tag setting display.
1. Device setup
3. Basic setup
1. T ag
See Section 2.2.4.
(2) Unit
The unit is set at the factory before shipment if specified at the time of order. Follow the procedure below to change the unit.
Example: To change the unit from mmH2O to inH2O
1
EJA: Hot Key 1 Keypad input 2 Enable Write 3 New Password
DEL SET ESC ENTER
2
EJA: keypad input 1 LRV 0.00 mmH2O 2 URV 3000.00 mmH2O 3 Unit mmH2O 4 LSL -3500 mmH2O 5 USL -3500 mmH2O
HELP SAVE HOME ENTER
3
EJA: Pressure unit mmH2O mmH2O mmHg psi bar
HELP
DEL SAVE ESC ENTER
Press Hot key and call up Range values.
Select the Press Unit item to set the units of pressure.
×3
(ENTER)
Select the desired engineering unit and press ENTER (F4).
8 16 32
2/2/2
T0202.EPS
EJA:YOKOGAWA Tag YOKOGAWA YOKOGAWA
HELP DEL ESC ENTER
F0210.EPS
F0211.EPS
4
EJA: keypad input 1 LRV 0.00 mmH2O 2 URV 3000.00 mmH2O 3 Unit inH2O 4 LSL -3500 mmH2O 5 USL 3500 mmH2O
DEL ESC
HELP SEND ENTER
(SEND)
Press SEND (F2) to send the new unit to the transmitter memory.
5
EJA: keypad input 1 LRV 0.00 inH2O 2 URV 118.000 inH2O 3 Unit inH2O 4 LSL -140.0 inH2O 5 USL 140.0 inH2O
DEL ESC
HELP SEND ENTER
Check that disappears.
SEND
F02111.EPS
(3) Range Change
Ranges are factory-set as specified by the customer. To rerange, change the settings as follows:
(a) Keypad — LRV, URV
Example: To change the range from 0 to 2500 mmH2O to
500 to 3500 mmH
1
EJA: Online 1 Device setup 2 Pres 3 A01 Out 4 LRV 5 URV
DEL SET ESC ENTER
2
EJA: 1 LRV 0.0 mmH2O 2 URV 2500 mmH2O
HELP SAVE HOME ENTER
3
EJA: LRV
0.0 mmH2O
0.0
HELP DEL ESC ENTER
4
EJA: 1 LRV 500 mmH2O 2 URV 3000.0 mmH2O
DEL HOME
HELP SEND ENTER
5
EJA: URV
2500.0 mmH2O
2500.0
HELP ESC
DEL ENTER
6
EJA: 1 LRV 500.0 mmH2O 2 URV 3500.0 mmH2O
HELP HOME
SEND ENTER
O
2
Select the 4. LRV item.
To set the Lower Range Valve, select the LRV item.
‘5 0 0’
(ENTER)
Enter 500, and press ENTER (F4).
To change the Upper Range Valve, select the URV item.
‘3 5 0 0’
(ENTER)
Enter 3500, and press ENTER (F4).
(SEND)
Press SEND (F2) to send the changed data to the transmitter. Check that disappears.
SEND
F0212.EPS
2-7
IM 01C22T01-01E
Page 15
2. HART COMMUNICATOR OPERATION
NOTE
It is possible to set LRV URV. This setting reverses the 4 to 20 mA output signal. Conditions: LSL LRV USL
LSL URV USL
|URV LRV| Min. Span The 4 to 20 mA output does not correspond to the scale of the indicator under the following conditions in which;
•the equipment with standard specification is
used with the setting changed to the above setting.
• the customer specified equipment (with the
above factory-setting) is used with the setting
changed to the normal (standard) setting. In the cases above, replace the scale with one which corresponds correctly to the 4 to 20 mA.
(b) Changing the Ranges While Applying an
Actual Input — Apply values
This feature allows the lower and upper range values to be setup automatically with the actual input applied. If the upper and lower range values are set, “URV” and “LRV” are changed at the same time.
The measurement span is determined by the upper and lower range valves. Changing the lower range value results in the upper range value change automatically, keeping the span constant.
4
EJA: Current applied process value:
500.01 mmH2O 1 Set as 4mA value 2 Read new value 3 Leave as found
HELP SEND ENTER
DEL ABORT
(ENTER)
The LRV to be changed is 500.01 mmH2O.
• Selecting item 1 sets LRV to
500.01 mmH2O.
• Selecting item 2 reads LRV again. To set LRV = 500.01, select item 1
5
EJA: Set the 1 4mA 2 20mA 3 Exit
DEL ENTER
HELP ABORT
and press ENTER (F4).
×2
(ENTER)
Select Exit and press ENTER (F4). Check the value after completing the range change with URV and LRV. * The span is maintained the same
as when changing LRV with Apply values. In this case, if LRV is changed from 0 to 500, URV is changed automatically to 3000.
(4) Output Mode (Linear/Sq root)
The output mode has already been set to a Linear output (Linear). Follow the procedure below to change the mode.
Example: To change the mode from Linear to Sq root.
Call up the Xfer fnctn display.
F02131.EPS
Example: To change the range from 0 to 2500 mmH2O to
500 to 3000 mmH
O
2
Call up the Apply Values display.
1. Device setup
3. Basic setup
3. Re-range
2. Apply values
1
EJA: WARN-Loop should be removed from automatic control
DEL SET ABORT OK
2
EJA: Set the: 1 4mA 2 20mA 3 Exit
HELP SAVE ABORT ENTER
3
EJA: Apply new 4ma input
HELP DEL ABORT OK
(OK)
Press OK (F4).
(ENTER)
To set the lower range value, select 4mA and press ENTER (F4).
(OK)
Apply the pressure of 500mmH2O. After obtaining a stable pressure, press OK (F4).
F0213.EPS
1. Device setup
3. Basic setup
5. Xfer fnctn
1
EJA: Transfer function Linear Linear Sq root
DEL SET ESC ENTER
(ENTER)
(SEND)
[1] Select Sq root, and press
ENTER (F4).
[2] Press SEND (F2) to send the
data to the transmitter, then check to confirm that disappears.
The output mode is set as specified in the order when the instrument is shipped.
If the instrument is equipped with an integral indicator and Transfer function is sq root, “ ” is displayed on the integral indicator.
2-8
IM 01C22T01-01E
SEND
F0214.EPS
Page 16
2. HART COMMUNICATOR OPERATION
0.2 Sec
0.5 Sec
1.0 Sec
2.0 Sec
4.0 Sec
8.0 Sec
16.0 Sec
32.0 Sec
64.0 Sec
T0203.EPS
(5) Damping Time Constants
The damping constant is set to 2.0 seconds at the factory. When changing the damping constant, proceed as follows:
Example: To change from 2.0 seconds to 0.2 seconds
Call up the Damp display.
1. Device setup
3. Basic setup
6. Damp
1
EJA: Damping
2.00 s
2.00
HELP DEL ESC ENTER
2
EJA: Basic Setup 1 Unit kPa 2 Re-range 3 Device information 4 Xfer fncfn Linear 5 Damp 0.20s
HELP SEND HOME ENTER
3
EJA: Set to nearest possible value occurred writing Pres damping Press OK...
DEL SET ESC OK
‘0 . 2’
(ENTER)
Enter 0.2 and press ENTER (F4).
Press SEND (F2) to send the data to the transmitter.
(OK)
A confirmation display appears. Press OK (F4), then check to confirm that disappears.
SEND
F0215.EPS
(6) Output Signal Low Cut Mode Setup
Low cut can be used on the output signal to stabilize the output near the zero point.
The low cut point can be set in a range from 0 to 20% of output. (Hysteresis of cut point: ±1%)
Either LINEAR or ZERO can be selected as the low cut mode.
Unless otherwise specified, the cut mode is set to LINEAR at the factory.
Example: To set the low cut range to 20% and the cut mode
50
Output
20
For low cut in linear mode
Figure 2.2.2 Low Cut Mode
1. Device setup
3. Basic setup
7. Low Cut, 8. Cut mode
to ZERO, proceed as follows:
(%)
0
Input
50
(%)
(%)
50
Output
20
0
Input
For low cut in zero mode
F0216.EPS
50
(%)
NOTE
1. Only the damping constants listed in Table 2
are available. When a value not listed in Table 2 is entered, the value in Table 2 nearest the entered value is set.
2. The damping constant set with the procedure
here is of the damping constant in the trans­mission part (electric circuit). The damping constant of the capsule assembly shall be added to obtain the overall damping constant of the transmitter.
Table 2
EJA: Low cut
10.00%
10.00
HELP DEL ESC ENTER
EJA: Cut mode Linear Linear Zero
HELP SEND ESC ENTER
EJA: Basic Setup 4 Device information 5 Xfer fnctn Linear 6 Damp 0.50s 7 Low cut 20.00 % 8 Cut mode Zero
DEL SEND HOME OK
2-9
‘2 0’
(ENTER)
Call up the Low cut, and set to 20%.
(ENTER)
Select the Cut mode, and set to Zero.
(SEND)
Press SEND (F2) to send the date, then check to confirm that
SEND
disappears.
F0217.EPS
IM 01C22T01-01E
Page 17
2. HART COMMUNICATOR OPERATION
(7) Bi-directional Flow Measurement
(a) Bi-dir mode enables selection of 50% output at an
input of 0 mmH2O.
Example: If measurement range is 0 to 3000mmH2O
1. Device setup
4. Detailed setup
2. Signal condition
8. Bi-dir mode
EJA: Bi-dir mode OFF off on
HELP SEND ESC ENTER
Note: The measurement range changes to –3000 to 0 to
(LRV = 0 mmH2O, URV = 3000 mmH2O)
(ENTER)
(SEND)
Call up the Bi-dir mode Display Select on, and press ENTER (F4). Press SEND (F2) to send the data to the transmitter, then check to confirm that disappears.
SEND
3000mmH2O (output 0% to 50% to 100%). Note that LRV and URV are not changed.
F0218.EPS
(b) Combining Bi-dir mode with Xfer fnctn provides
a square root output computed independently for
0% to 50% output and for 50% to 100% output.
20 mA (100% display)
LRV HRV
(8) Integral Indicator Display Mode
Example: Change from Linear to Sq root
1. Device setup
4. Detailed setup
4. Display condition
2. Display fnctn
EJA: Display fnctn Linear Linear Square Root
HELP SEND ESC ENTER
(ENTER)
(SEND)
Select Square Root and press ENTER (F4). Press SEND (F2) to send data.
(9) Integral Indicator Scale
Display
Mode
NORMAL %
USER SET
USER & %
Display
Related
Parameters
% rnge 45.6%
Engr disp range
20.0M
% rnge
45.6%
Engr disp range
20.0M
F0220.EPS
Description
Indicates –5 to 110% range depending on the set range (LRV, URV).
Displays values depending on engr disp LRV and engr disp URV Units set using engr disp unit are not indicated.
Indicates user set and % alternately in 3 second intervals.
Output mode “LINEAR”
20 mA (100% display)
Low Cut
Output mode “SQUARE ROOT”
4 mA (–100% display)
LRV HRV
4 mA (–100% display)
F0219.EPS
INP PRES
PRES & %
* The number of lines displayed on the LCD is determined by the
number of LRV and URV lines set on the brain terminal.
Pres 456 kPa
% rnge 45.6% Pres 456 kPa
See (a) through (c) for each setting procedure.
2-10
Indicates input pressure.
Indicates input pressure and % alternately in 3 second intervals.
T0204.EPS
IM 01C22T01-01E
Page 18
2. HART COMMUNICATOR OPERATION
% indication and input pressure indication
Normal % Input press Input press & %
Transmitter is set for “NORMAL %” when shipped.
User-set engineering unit display
User set User set & %
Set for user-set engineering unit display.
Engr disp unit
Set a unit to be displayed on the HART Com­munication.
For % display, set this parameter only.
Engr disp LRV
Set a numeric value for engi­neering unit for 4 mA output (LRV).
Set a numeric value for engi-
Engr disp URV
neering unit for 20 mA output (HRV).
(a) Display Mode
Follow the instructions given to the below to
change the range of integral indication scale.
When USER SET is selected, the user set values
of integral indication.
F0221.EPS
Example: Set an engineering unit M.
1. Device setup
4. Detailed setup
4. Display condition
3. Engr disp range
1. Engr unit
EJA: Engr unit
HELP DEL ESC ENTER
(ENTER)
(SEND)
Set M, and press ENTER (F4).
(c) Lower and Upper Range Value Setup in
Engineering Unit
Engr disp LRV and Engr disp URV are used to
set the lower and higher range values for the engineering unit display. When the instrument is shipped, these are set as specified in the order. Note that these items need not be set for % display.
F0223.EPS
Example: Set the integral indicator scale to engineering units
display
1. Device setup
4. Detailed setup
4. Display condition
1. Display mode
EJA: Display mode Normal % Normal % User set User set & % Input press
HELP SEND ESC ENTER
(ENTER)
(SEND)
Select User set and press ENTER (F4). Press SEND (F2) to send the data to the transmitter.
F0222.EPS
(b) Setting User-set Engineering Unit
Engr unit allows entry of the engineering units to
be displayed on the HART communicator. When
the instrument is shipped, this is set as specified in
the order. Follow the procedure below to change
this setting.
Since these units are not displayed on the integral
indicator, use the adhesive labels provided Engr
unit need not be set for % display.
Example: Set low range value (LRV) to –50 and upper range
value (URV) to 50.
1. Device setup
4. Detailed setup
4. Display condition
3. Engr disp range
2. Engr disp LRV, 3. Engr disp URV
EJA: Engr disp LRV
0.0
0.0
DEL DEL ESC ENTER
‘– 5 0’
(ENTER)
Set –50, and press ENTER (F4).
EJA: Engr disp range 1 Engr unit 2 Engr disp LRV 3 Engr disp URV 4 Engr disp point
HELP SEND HOME ENTER
EJA: Engr disp URV
0.0
0.0
HELP
DEL DEL ESC ENTER
Press to select engr disp URV.
‘–5 0’
(ENTER)
(SEND)
Set 50, and press ENTER (F4). Press SEND (F2) to send data.
F0224.EPS
2-11
IM 01C22T01-01E
Page 19
2. HART COMMUNICATOR OPERATION
(10) Unit for Displayed Temperature
When the instrument is shipped, the temperature units are set to C (Centigrade). Follow the procedure below to change this setting.
The unit changed here corresponds the unit for Snsr temp.
Example: Change the unit for the temperature display.
1. Device setup
4. Detailed setup
1. Sensors
2. T emp sensor
2. Snsr temp unit
EJA: Snsr temp unit C C F
HELP SEND ESC ENTER
(ENTER)
Select F (Fahrenheit), and Press ENTER (F4).
F0225.EPS
(11) Unit for Displayed Static Pressure
Follow the procedure to change the static pressure unit. Changing this parameter also changes the unit for the
static pressure display.
Example: Change the static pressure unit from mmH2O to
1. Device setup
4. Detailed setup
1. Sensors
3. Static Pres sensor
2. Static Pres unit
EJA: Static Pres unit mmH2O mmH2O mmHg psi bar
HELP SEND ESC ENTER
kPa.
inH2O inHg
O
ftH
2
mmH mmHg psi bar mbar g/cm kg/cm Pa kPa torr atm
(ENTER)
(SEND)
O
2
Select kPa and Press ENTER (F4). Select SEND (F2) to send the data.
2
2
F0226.EPS
(12) Test Output
This feature can be used to output a fixed current from
3.2 mA (–5%) to 21.6 mA (110%) for loop checks.
Example: To output 12 mA (50%)
1. Device setup
2. Diag/Service
2. Loop test
1
EJA: WARN-loop should be removed from automatic control
DEL SET ABORT OK
2
EJA: Choose analog output level 1 4mA 2 20mA 3 Other 4 End
DEL SET ABORT ENTER
3
EJA: Output
4.000
HELP DEL ABORT ENTER
4
EJA: Fld dev output is fixed at 12.000 mA
HELP SEND OK
DEL ABORT
5
EJA: Choose analog output level 1 4mA 2 20mA 3 Other 4 End
HELP SEND ENTER
DEL ABORT
6
EJA: NOTE-loop may be returned to automatic control
HELP SEND OK
DEL ESC
(OK)
Set the control loop in manual mode, and press OK (F4).
×2
(ENTER)
Select Other, and press ENTER (F4). Supplementary explanation.
1. 4 mA: Outputs a 4 mA current signal
2. 20 mA: Outputs a 20 mA current signal
3. Other: Sets a desired output using the alphanumeric keys
4. End: Exits
‘1 2’
(ENTER)
Enter 12, and press ENTER (F4). A fixed current of 12 mA is output.
(OK)
Press OK (F4).
×3
(ENTER)
To finish the loop test, select End, and press ENTER (F4).
(OK)
Press OK (F4).
F0227.EPS
2-12
IM 01C22T01-01E
Page 20
2. HART COMMUNICATOR OPERATION
CAUTION
1. Test output is held for approximately 10 minutes, and then released automatically after the time has elapsed. Even if the HART Communicator power supply is turned off or the communication cable is disconnected during test output, it is held for approximately 10 minutes.
2. Press the (OK) key to release test output immediately.
(13) Sensor Trim
Each DPharp EJA Series Transmitter is factory characterized. Factory characterization is the process of comparing a known pressure input with the output of each transmitter sensor module over the entire pressure and temperature operating range. During the character­ization process, this comparison information is stored in the transmitter EEPROM. In operation, the transmit­ter uses this factory-stored curve to produce a process variable output (PV), in engineering units, dependent on the pressure input. The sensor trim calibration procedure allows you to make corrections to the calculated process variable.
There are two ways to trim the sensor: full sensor trim and zero trim. A full sensor trim is a two point process, in which two accurate end-point pressures are applied (equal to or greater than the range values), and all output is linearized between them. A zero trim is a one-point adjustment typically used to compensate for mounting position effects or zero shifts caused by static pressure. (See section 1.1.1)
Example 1: For the range of 1000 to 3000 mmH2O
1. Device setup
2. Diag/Service
3. Calibration
3. Sensor Trim
1
EJA: Sensor trim 1 Zero trim 2 Pres 3 Lower sensor trim 4 Upper sensor trim 5 Sensor trim points
HELP SET HOME OK
2
EJA: Apply low pressure
DEL SET ABORT OK
Select the Lower Sensor trim.
(OK)
Apply a standard pressure of 1000
O to the transmitter. After
mmH
2
obtaining a stable pressure, press OK (F4).
F02281.EPS
3
EJA: Press OK when pressure is stable
(OK)
HELP DEL ABORT OK
4
EJA: Enter applied pressure value
0.00 mmH2O
0.00
HELP ABORT
DEL ENTER
Press OK (F4).
‘1 0 0 0’
(ENTER)
Enter 1000, and press ENTER (F4). Remove pressure appears for a while. Fine input adjustment (0%) is complete.
F02282.EPS
SPAN adjustment shall be carried out with Upper Sensor trim. After selecting Upper Sensor trim,
apply a pressure of 3000 mmH2O (corresponding to 100% of the measurement range). Then, proceed the same as for the operations for Lower Sensor trim.
1
EJA: Sensor trim 1 Zero Trim 2 Pres 3 Lower sensor trim 4 Upper sensor trim 5 Sensor trim points
HELP SET HOME OK
2
EJA: Apply hi pressure
DEL SET ABORT OK
3
EJA: Press OK when pressure is stable
HELP DEL ABORT OK
4
EJA: Enter applied Pressure value
0.00 mmH2O
0.00
HELP ABORT
DEL ENTER
Select the Upper Sensor trim item.
(OK)
Apply a standard pressure of 300 mmH
O to the transmitter. After
2
obtaining a stable pressure, press OK (F4).
(OK)
Press OK (F4).
‘3 0 0 0’
(OK)
Enter 3000, and press ENTER (F4). Remove pressure appears for a while. Fine input adjustment (100%) is complete.
F0229.EPS
2-13
IM 01C22T01-01E
Page 21
2. HART COMMUNICATOR OPERATION
(14) Trim Analog Output Fine output adjustment is carried out with D/A trim or
Scaled D/A trim.
• D/A Trim D/A trim is to be carried out if the calibration
digital ammeter does not read 4.000 mA and 20.000 mA exactly with the output signal of 0% and 100%.
• Scaled D/A Trim Scaled D/A trim is to be carried out if the output
is adjusted using a voltmeter or other types of meters or using a meter whose the scale unit is 0 to 100%.
Example 1: For the adjustment using an ammeter (±1µA is
1. Device setup 2 Diag/Service
3. Calibration
2. Trim analog output
1
EJA: Trim analog output 1 D/A trim 2 Scaled D/A trim
HELP SET HOME OK
2
EJA: WARN-LOOP should be removed from automatic control
DEL SET ABORT OK
3
EJA: Connect reference meter
HELP DEL ABORT OK
4
EJA: Setting fld dev output to 4mA
HELP ABORT
5
EJA: Enter meter value
4.000
HELP ESC
measurable)
DEL OK
DEL ENTER
Select the D/A trim item.
(OK)
Press OK (F4).
(OK)
Connect the ammeter (±1µA is measurable), and press OK (F4).
(OK)
Press OK (F4), and the transmitter outputs the output signal of 0%.
‘4 . 1 1 5’
(ENTER)
Ammeter reading: 4.115
Enter the read value 4.115 of the ammeter, and press ENTER (F4). (The output of the transmitter changes.)
F0230.EPS
6
EJA: Fld dev output 4.000 mA equal to reference meter? 1 Yes 2 No
HELP SET ABORT ENTER
7
EJA: Setting fld dev output to 20mA
DEL SET ABORT OK
8
EJA: Enter meter value
20.000
HELP DEL ABORT ENTER
9
EJA: Fld dev output 20.000 mA equal to reference meter? 1 Yes 2 No
HELP ABORT
DEL ENTER
10
EJA: NOTE-Loop may be returned to automatic control
DEL OK
HELP ESC
(ENTER)
Ammeter reading: 4.000
Because the reading on the ammeter is 4.000 mA, select YES and press ENTER (F4). If the reading is not 4.000 mA, select item 2. NO. Repeat steps
5
and until the ammeter reads
4
4.000 mA.
(OK)
Press OK (F4), and the transmitter outputs the output signal of 100%.
‘1 9.0 5 0‘
(ENTER)
Ammeter reading: 19.050
Carry out the same procedures as
4
those described under and .
5
(ENTER)
Ammeter reading: 20.000
Returning fld dev to original output appears.
(OK)
Press OK (F4).
F0231.EPS
2-14
IM 01C22T01-01E
Page 22
2. HART COMMUNICATOR OPERATION
Example 2: To adjust using a voltmeter
1
EJA: Trim analog output 1 D/A trim 2 Scaled D/A trim
HELP SET HOME OK
Select the Scaled D/A trim item.
2
EJA: WARN-Loop should be removed from automatic control
DEL SET ABORT OK
(OK)
Press OK (F4).
3
EJA: Trim will be scaled from 4.000 to 20.000 1 Proceed 2 Change
HELP DEL ABORT ENTER
Select Change, and press ENTER (F4). The same operations as for D/A trim are required when selecting
item 3. Proceed.
4
EJA: Set scale- Lo output value 4 4
HELP ABORT
DEL ENTER
‘1’
(ENTER)
Enter the value read on the meter when the signal is 4 mA. In this case, Enter the value of the voltage across a 250 Ω resistor (1 V), and press ENTER (F4).
5
EJA: Set scale- Hi output value 20 20
HELP ABORT
DEL ENTER
‘5’
(ENTER)
Enter the value read on the meter when the signal is 20 mA. Then, enter 5, and press ENTER (F4).
6
EJA: Trim will be scaled from 1.000 to 5.000 1 Proceed 2 Change
HELP SET ABORT ENTER
7
EJA: Connect reference meter
DEL SET ABORT OK
8
EJA: Setting fld dev output to 4mA
HELP DEL ABORT OK
(ENTER)
Select Proceed and press ENTER (F4).
(OK)
Connect the voltmeter, and press OK (F4).
(OK)
Press OK (F4). The output signal of 0% is output.
F0232.EPS
9
EJA: Enter meter value
1.000
HELP ABORT
DEL ENTER
10
EJA: Scaled output: 1.000 equal readout device? 1 Yes 2 No
HELP ABORT
DEL ENTER
11
EJA: Setting fld dev output to 20mA
HELP SET ABORT OK
12
EJA: Enter meter value
5.000
HELP DEL ABORT ENTER
13
EJA: Scaled output: 5.000 equal readout device? 1 Yes 2 No
HELP DEL ABORT ENTER
“Returning fid dev to original output”
14
EJA: NOTE-Loop may be returned to automatic control
HELP ABORT
DEL OK
‘1 . 0 1’
(ENTER)
Voltmeter reading: 1.010
Enter the reading of the voltmeter (1.010), and press ENTER (F4). (The output of the transmitter changes.)
(ENTER)
Voltmeter reading: 1.000
Because the reading on the voltmeter is 1.000, select Yes and press ENTER (F4). If the reading is not 1.000, select No. Repeat steps and until
98
the voltmeter reads 1.000 V.
(OK)
Press OK (F4). The output signal of 100% is output.
‘5 . 2 1’
(ENTER)
Voltmeter reading: 5.210
Enter the reading of the voltmeter (5.210), and press ENTER (F4).
(ENTER)
Voltmeter reading: 5.000
Select Yes and press ENTER (F4).
(OK)
Press OK (F4).
F0233.EPS
2-15
IM 01C22T01-01E
Page 23
2. HART COMMUNICATOR OPERATION
(15) Burst Mode
The transmitter continuously sends the data stored in it when the burst mode is set on. Either one of measured pressure variable, % output value, or 4 to 20 mA output value can be selected and sent. The data is sent intermittently as a digital signal at 75 ms intervals when the transmitter is set in the burst mode. There­fore, communication by the HART simultaneous communicator is also possible.
Setting of Burst Mode
1. Device setup
4. Detailed setup
3. Output condition
4. HART output
3. Burst mode, 4. Burst option
EJA: Burst option ******** PV % range/current Process vars/crnt
HELP DEL ESC ENTER
(ENTER)
Call up the Burst option, and set the data to be sent.
•Pressure variable (PV)
•% output value (% range/current)
•4 to 20 mA output value (Process vars/crnt)
EJA: Burst mode Off On Off
DEL DEL ESC ENTER
HELP
(ENTER)
(SEND)
Call up the Burst mode and set to On. Then, Press SEND (F2).
F0234.EPS
To Release from the Burst Mode: Call up the Burst mode display, and set to OFF.
(16) Multidrop Mode
“Multidropping” transmitters refers to the connection of several transmitters to a single communications transmission line. Up to 15 transmitters can be con­nected when set in the multidrop mode. To activate multidrop communication, the transmitter address must be changed to a number from 1 to 15. This change deactivates the 4 to 20 mA analog output, sending it to 4 mA. The alarm current also is disabled.
Setting of Multidrop Mode
1. Device setup
4. Detailed Setup
3. Output condition
4. HART Output
1. Poll addr
EJA: Poll addr O 0
Call up the Poll addr and set the polling address. (a number from 1 to
15) And press SEND (F2) to send the
HELP DEL ESC ENTER
data.
Online Utility Auto Poll
HART Communicator Auto Poll No No Yes
HELP
DEL DEL ESC ENTER
(ENTER)
Call up the Auto Poll and set to Yes.
F0235.EPS
NOTE
1. When the address is set and the multi-drop mode is set to “No” at the same time, Online menus cannot be called up and displayed. Be sure to turn the multidrop mode to “Yes” after setting the address with “Poll addr.”
2. When the same polling address is set for two or more transmitters in multidrop mode, communication with these transmitters is disabled.
2-16
IM 01C22T01-01E
Page 24
2. HART COMMUNICATOR OPERATION
Example: Communication when set in the multi-drop mode
1
HART Communicator Online 1 EJA110-1 2 EJA110-2 3 EJA110-3
HELP SET HOME OK
(1) The HART communicator
searches for the transmitter that is set in the multi-drop mode when the HART communicator is turned on. When the HART communicator
2
EJA:EJA110-1: Online 1 Device setup 2 Pres 0.00 mmH2O 3 A01 Out .000 mA 4 LRV 0.00 mmH2O 5 URM 3500.00 mmH2O
DEL SET ABORT OK
3
HART Communicator 1 Offline 2 Online 3 Transfer 4 Frequency Device 5 Utility
HELP DEL ABORT OK
is connected to the transmitter, the manufacturer’s x’ter type code and the tag will be displayed (display ).
1
(2) Select the desired transmitter.
After that, normal communication to the selected transmitter is possible. However, the communication speed is slow in this case (display ).
2
(3) To communicate with another
transmitter, turn off the power once and then turn on it again, or call up display , and select
3
Online.
(4) Display will appear. Select
1
the desired transmitter.
F0236.EPS
To Release the Multi-drop Mode:
Follow the procedure below.
1. Call up the Poll addr display, and set the address
to 0.
2. Call up the Auto Poll display, and set to No.
(17) External Switch Mode
• Enabling/inhibiting zero point adjustment using the external zero-adjustment screw on the transmitter.
Follow the procedure below to enable or inhibit zero point adjustment from the zero-adjustment screw on the transmitter.
This is set to ENABLE when the instrument is shipped.
(18) Software Write Protect
EJA configured data is saved by the write protect function. Write protect status is set to YES when 8 alphanumerics are entered in the New password field and transferred to the transmitter. In write protect YES status, the transmitter does not accept parameter changes. When the 8 alphanumeric string entered in the
New password field is also entered in the Enable write field and transferred to the transmitter, it will be
possible to change transmitter parameters during a 10 minute period.
To change the transmitter from Write protect YES status back to Write protect NO status, enter 8 spaces in the New password field after Write protect has been released using enable write.
(a) Setting Password
Example: Set the password to 1 2 3 4
EJA: Hot key 1 keypad input 2 Enable Write 3 New password
HELP SEND ESC ENTER
EJA: Enter New Password ******** ********
HELP DEL ABORT ENTER
EJA: Re-Enter New Password 1234 1234
HELP DEL ABORT ENTER
Press Hot key. Select the New password.
(ENTER)
Set 1 2 3 4 and press ENTER (F4).
×4
(DEL)
(ENTER)
Press ENTER (F4).
Example: Inhibiting zero adjustment by the external zero-
adjustment screw
1. Device setup
4. Detailed setup
5. Device information
1. Field device info
7. Ext SW mode
EJA: Ext SW mode Enable Enable Inhibit
HELP SEND ESC ENTER
(ENTER)
(SEND)
Select Inhibit and press ENTER (F4). Press SEND (F2) to send the data.
F0237.EPS
2-17
EJA: Set New Password OK
HELP DEL ABORT OK
EJA: Method Aborted
HELP DEL ABORT OK
(OK)
Press OK (F4).
Write Protect status changes from NO to YES.
(OK)
Press OK (F4).
F0238.EPS
IM 01C22T01-01E
Page 25
(b) Changing the Password
Example: To change the password from 1 2 3 4
EJA: Input password ******** ********
HELP DEL ABORT ENTER
EJA: Write enable in 10 minutes
HELP DEL ABORT OK
EJA: Method Aborted
HELP DEL ABORT OK
EJA: Hot key 1 keypad input 2 Enable write 3 New password
HELP DEL ABPRT OK
EJA: Enter New Password ******** ********
HELP DEL ABORT ENTER
EJA: Re-Enter New Password 6789A 6789A
HELP DEL ABORT ENTER
to 6 7 8 9 A
1 2 3 4
(ENTER)
Press Hot key and call up Enable Write. Enter the password and press ENTER (F4).
(OK)
Press OK (F4). Write protect status is released for 10 minutes.
(OK)
Press ENTER (F4).
Select the New password.
6 7 8 9 A
(ENTER)
Set 6 7 8 9 A .
(OK)
Press ENTER (F4).
2. HART COMMUNICATOR OPERATION
NOTE
1. Enable Wrt 10 min releases Write Protect status for 10 minutes. While Write Protect status is released, enter a new password in the New Password field. It will not be possible to set a new password when 10 minutes have elapsed.
2. To release Write Protect status completely, enter 8 spaces in the New Password field according to the instructions given in (b),
Changing the Password. This causes Write Protect status to change from YES to NO.
EJA: Enter New Password ******** ********
HELP DEL ABORT ENTER
EJA: Re-Enter New Password
1
HELP DEL ABORT ENTER
(ENTER)
(ENTER)
*"Joker password" and "Software Seal"
When you lose the password that has been registered, it is possible to release the mode for 10 minutes by using a joker password. Enter "YOKOGAWA" to release Write protect status for 10 minutes. If this joker password is used, the status shown in the parameter "Software seal" is changed from "Keep" to "Break." Press Hot key and select "2. Wrt Protect menu." Current status is shown in "4. Software seal." This status will be returned from "Break" to "Keep" by registering a new password.
8
F0240.EPS
EJA: Set New Password OK
HELP DEL ABORT OK
EJA: Method Aborted
HELP DEL ABORT OK
(OK)
(OK)
Press OK (F4).
F0239.EPS
2-18
IM 01C22T01-01E
Page 26
2. HART COMMUNICATOR OPERATION
(19) Hardware Write Protect and Burnout
Direction(with Optional code /F1)
This function prohibits parameter changes through a slide switch on a CPU assembly board. In the case the hardware write protection switch is set to YES, none of the communication method including the handheld terminal such as model 275 is allowed for the alter­ation of parameters. The write protection switch is factory set to NO(N position in the figure below).
CPU assembly
Slide switch
Burnout direction switch
LH
YN
Write protection switch
Hardware write protection switch
Write Protection
Switch Position
Write Protection
L H
YN
L H
YN
YESNO
Burnout direction switch
Burnout Direction
Switch Position
Burnout Direction
LH
Y N
HIGH LOW
LH
Y N
F02F1.EPS
(20) H2O Unit Select
When mmH2O, inH2O or ftH2O is set, the pressure varies with the standard temperature definition. The Yokogawa default setting for the standard temperature is 4°C (39.2°F). Use the procedure described below when a standard temperature of 20°C (68°F) is re­quired.
Call up the H2O Unit select.
1. Device setup
4. Detailed setup
2. Signal condition
9. H2O Unit select
EJA: H2O Unit select @4C @4C @20C(68F)

2.4 Self-Diagnostics

2.4.1 Checking for Problems

(1) Identify Problems with HART Communica-
tor
Self-diagnostics of the transmitter and check of incorrect data setting can be carried out with the HART communicator. There are two methods for self­diagnosis of the transmitter, self-diagnosis for every transmission and manually executing the SELF TEST command. When an error message appears, follow “ERROR MESSAGES”.
Diagnostic by “self test”
1. Device setup
2. Diag/Service
1. Test/Status
1
EJA: Test/status 1 Self test 2 Status
HELP SET HOME OK
2
EJA: Self test OK
DEL SET ABORT OK
1
EJA: Test/status 1 Self test 2 Status
HELP SET HOME OK
2
EJA: Status Field device not installed OFF
DEL PREV NEXT EXIT
Call up the Test/Status, and select Self test.
If there is no error detected, Self test OK will be displayed.
When an error occurs, an error message appears, and the results of self-diagnosis appear in the Status item.
Call up the Status item.
(NEXT)
If there is no error, the result of diagnostics is indicated as OFF. If ON is indicated, a countermeasure for that error is necessary.
F0242.EPS
HELP SEND ESC ENTER
(ENTER)
(SEND)
Select @20C (68F) and press ENTER (F4). Press SEND (F2) to send data.
F0241.EPS
2-19
IM 01C22T01-01E
Page 27
2. HART COMMUNICATOR OPERATION
• Error Messages — HART Communicator
Error Message Probable Cause Countermeasure
Pressure sensor error
Temp (Cap) sensor error
EEPROM (Cap) failure
Sensor board not initialized
Temp (Amp) sensor error
EEPROM (Amp) failure
Dev id not entered CPU board not
initialized Invalid Selection Parameter Too High
Parameter Too Low Incorrect Byte Count In Write Protect
Mode Set to Nearest
Possible Value Lower Range Value
too High Lower Range Value
too Low Upper Range Value
too High Upper Range Value
too Low Span too Small Applied Process
Value too High Applied process
Value too Low New LRV pushed
URV Over Sensor Limit
Excess Correction Attempted
In Proper Current Mode
In Multidrop Mode
Capsule problem
Amplifier problem
Set value is too high. Set value is too low.
Operation is set in the Write Protect mode.
Value is set to a nearest possible value.
LRV set point is too high.
LRV set point is too low.
URV set point is too high.
URV set point is too low.
Set span is too small. Applied pressure is
too high. Applied pressure is
too low. The shift of URV
according to the new LRV setting exceeds USL.
Amount of correction is too much.
The fixed current mode is desired but not set in that mode.
Operation is set in the multi-drop mode.
Replace capsule.
Replace amplifier.
Change the setting.
— —
Change the range.
Adjust the applied pressure.
Change the setting within the range of USL.
Adjust the amount of correction.
Set in the fixed current mode.
(2) Checking with Integral Indicator
If an error is detected in the self-diagnostic, an error number is displayed on the integral indicator. If there is more than one error, the error number changes at two­second intervals.
See Table 2.4.1 regarding the error numbers.
F0243.EPS
Figure 2.4.1 Identifying Problems Using the Integral
Indicator
T0205.EPS
2-20
IM 01C22T01-01E
Page 28
• Error Messages — DPharp Integral Indicator
Integral
Integral
Indicator
Indicator
Display
Display
None
None
----
---­Er. 01
Er. 01
Er. 02
Er. 02
Er. 03
Er. 03
Er. 04
Er. 04
Er. 05
Er. 05
Er. 06
Er. 06
Er. 07
Er. 07
Er. 08
Er. 08
Er. 09
Er. 09
Er. 10
Er. 10
Er. 11
Er. 11
Er. 12
Er. 12
Description Cause Countermeasure
Description Cause Countermeasure
GOOD
GOOD ERROR
ERROR
Capsule problem
CAP MODULE
CAP MODULE FAULT
FAULT
AMP MODULE
AMP MODULE FAULT
FAULT
OUT OF RANGE
OUT OF RANGE
OUT OF SP
OUT OF SP RANGE
RANGE
OVER TEMP
OVER TEMP (CAP)
(CAP)
OVER TEMP
OVER TEMP (AMP)
(AMP)
OVER OUTPUT
OVER OUTPUT
OVER DISPLAY
OVER DISPLAY
ILLEGAL LRV
ILLEGAL LRV
ILLEGAL URV
ILLEGAL URV
ILLEGAL SPAN
ILLEGAL SPAN
ZERO ADJ OVER
ZERO ADJ OVER
Capsule problem
Amplifier problem
Amplifier problem
Input is outside
Input is outside measurement range
measurement range limit of capsule.
limit of capsule. Static pressure
Static pressure exceeds specified
exceeds specified range.
range. Capsule temperature
Capsule temperature is outside range
is outside range (–50 to 130°C).
(–50 to 130°C).
Amplifier temperature
Amplifier temperature is outside range
is outside range (–50 to 95°C).
(–50 to 95°C).
Output is outside high
Output is outside high or low range limit
or low range limit value.
value. Displayed value is
Displayed value is outside high or low
outside high or low range limit value.
range limit value.
LRV is outside setting
LRV is outside setting range.
range.
URV is outside setting
URV is outside setting range.
range.
SPAN is outside
SPAN is outside setting range.
setting range.
Zero adjustment is too
Zero adjustment is too large.
large.
Output Operation
Output Operation
during Error
during Error
Outputs the signal
Outputs the signal according to status of
according to status of burnout direction
burnout direction switch (High or Low).
switch (High or Low). Outputs the signal
Outputs the signal according to status of
according to status of burnout direction
burnout direction switch (High or Low).
switch (High or Low). Outputs high range
Outputs high range limit value or low
limit value or low range limit value.
range limit value. Displays present
Displays present output.
output.
Displays present
Displays present output.
output.
Displays present
Displays present output.
output.
Outputs high or low
Outputs high or low range limit value.
range limit value.
Displays high or low
Displays high or low range limit value.
range limit value.
Holds output
Holds output immediately before
immediately before error occurrence.
error occurrence. Holds output
Holds output immediately before
immediately before error occurrence.
error occurrence. Holds output
Holds output immediately before
immediately before error occurrence.
error occurrence. Displays present
Displays present output.
output.
2. HART COMMUNICATOR OPERATION
Replace capsule.
Replace capsule.
Replace amplifier.
Replace amplifier.
Check input.
Check input.
Check line pressure
Check line pressure (static pressure).
(static pressure).
Use heat insulation or
Use heat insulation or make lagging to keep
make lagging to keep temperature within
temperature within range.
range. Use heat insulation or
Use heat insulation or make lagging to keep
make lagging to keep temperature within
temperature within range.
range. Check input and range
Check input and range setting, and change
setting, and change them as needed.
them as needed. Check input and
Check input and display conditions and
display conditions and modify them as
modify them as needed.
needed. Check LRV and
Check LRV and modify as needed.
modify as needed.
Check URV and
Check URV and modify as needed.
modify as needed.
Check SPAN and
Check SPAN and change as needed.
change as needed.
Readjust zero point.
Readjust zero point.
T0206.EPS
T0206.EPS
2-21
IM 01C22T01-01E
Page 29
3. PARAMETER LISTS
Item UHI Description Remarks
Transmitter
Display
HART output
Monitoring
Maintenance
Adjustment
Tag Descriptor Message Date Unit
LRV URV
Apply values Damp Xfer fnctn Low cut Cut mode Bi-dire mode
O Unit select
H
2
Snsr temp unit Static pres unit
Display mode Display fnctn Engr unit Engr disp LRV Engr disp URV Engr disp point Poll addr Auto poll Burst option Burst mode Pres
% rnge A01 out Snsr temp Static pres Engr display
Loop test Self test Status A01 Alarm typ Write Protect Enable Write New password Ext SW mode Software seal Zero trim Lower sensor trim
Upper sensor trim D/A trim
Scaled D/A trim
Tag number Descriptor Message Date Unit
Lower range value Lower range value
Apply values Damping time constant Transfer function Low cut Cut mode Bi-directional mode H2O Unit select Sensor temperature unit Static pressure unit
Display mode Display fnctn Engineering unit Engineering display LRV Engineering display URV Engineering display decimal point Polling address Auto poll Burst mode option Burst mode Pressure variable
% output variable 4 to 20 mA output variable Sensor temperature Static pressure Output (in Engr unit)
Test output % setting Self test Status Status of analog output alarm Write Protect Enable Write New password Ext SW mode Software seal Zero trim Lower sensor trim
Upper sensor trim Digital/Analog output trim
Scaled D/A trim
Tag number, Up to 8 characters Up to 16 characters Up to 32 characters xx/yy/zz
O, inHg, ftH2O, mmH2O, mmHg, psi, bar, mbar, g/cm2,
inH
2
2
, Pa, kPa, MPa, torr, atm
kg/cm Set the calibration range by the keypad
Range for 4 to 20 mA DC signal is set with actual input applied.
0.2, 0.5, 1, 1.5, 2, 4, 6, 8, 16, 32 sec linear/Square root 0 to 20 % Linear/Zero On/Off @4°C/@20°C (68°F) °C/°F
O, inHg, ftH2O, mmH2O, mmHg, psi, bar, mbar, g/cm2,
inH
2
2
, Pa, kPa, torr, atm
kg/cm Normal % , User set , User set & % , Inp pres , Pres & % linear/Square root Up to 8 characters –19999 to 19999 –19999 to 19999 0, 1, 2, 3 1 to 15 No/Yes Pres , % rnge , A01 out ON/OFF
–5.0% to 110.0% –3.2 mA to 21.6 mA
–19999 to 19999 –5.0% to 110.0% Check using the self-test command. Display of the result of self-test, calibration of transmitter. High/Low Yes/No 8 characters 8 characters Enable/Inhibit Keep/Break Set the current input value to 0 kPa. Adjust only measured pressure variable.
Adjust the output value at the points of 4 mA and 20 mA.

3. PARAMETER LISTS

T0301.EPS
3-1
IM 01C22T01-01E
Page 30
Item UHI Description Remarks
Sensor information
Isoltr matl Fill fluid Gasket matl Flange matl Drain vent matl Flange type RS isoltr matl Flange size Num remote seal RS fill fluid
Isolator material Fill fluid gasket material Flange material Drain vent material Flange type Remote seal isolator material Flange size Number of remote seal Remote seal fill fluid
Hast-C, Tantalum, 316L, Unknown, Special Silicone oil, F oil, Unknown, Special PTFE, 316L, Unknown, Special Carbon Steel, Hast-C, 316L, Unknown, Special 316SST, Hast-C, 316L, None, Unknown, Special Conventional, Remote seal, Level, Unknown, Special 316 SST, Hast-C, Monel, Tantalum, 316L, Unknown, Special ANSI 150, ANSI 300, ANSI 600, None, Unknown, Special One seal, Two seal, None, Unknown Silicone oil, SH704, SH705, Ethy Gly/H
None, Unknown, Special Wafer, Nozzle, HTV-W, HTV-N, None, Unknown, Special YOKOGAWA
EJA
Additional information
RS type Distributor
Dev type Dev ID Final asmbly num Universal rev Fld dev rev Software rev Model Style LSL USL MIN SPAN Manufacturer Lo snsr trim pt Up snsr trim pt Serial No.
Remote seal type Distributor
Device type Device ID Final assembly number Universal revision Fld dev revision Software revision Model Style Lower range limit Upper range limit Minimum span Manufacturer Lower snsr trim pt Upper snsr trim pt Serial Number
3. PARAMETER LISTS
O, Prop Gly/H2O,
2
T0302.EPS
3-2
IM 01C22T01-01E
Page 31

REVISION RECORD

Title: Model EJA Series HART Protocol Manual No.: IM 01C22T01-01E
Edition Date Page Revised Item
1st Nov. 1995 New publication
2nd Mar. 1998 1
3
2-1 2.1.1
3rd Mar. 2000
2-19
4th July 2000 ii
2-6
2-18
3-1
5th Oct. 2000 2-5
2-21
6th Apr. 2003 2-7 2.3.3 7th Jan. 2008 Miscellaneous corrections.
Revised a book in a new format.
2.3.3(19)
2.3.2
2.3.3 3
2.3.1 • Add "MPa" to engineering unit.
• Add EJA-A Series IM numbers to Table 1.
• Add REVISION RECORD
• Change the figure of terminal configuration
The location of contents and the associated page numbers may not coincide with the one in old edition.
• Add Hardware Write Protect and Burnout Direction(with optional code /F1).
• Add Caution for matching communicator DD and instrument DD.
• Add Software seal parameter.
• Change NOTE for Write Protect.
• Add software seal
• Correct the description of Output Operation during Error for Er.01 and Er. 02.
• Add Option code /CA.
REVISION RECORD.EPS
IM 01C22T01-01E
Loading...