This manual describes the function, performance, and
operating procedures of the DPharp EJA Series with
HART protocol. The DPharp EJA Series with HART
protocol uses the same pressure sensing element as in
DPharp EJA with BRAIN protocol. Therefore, this
manual describes only the functions unique to HART
Communicator operating procedures which are not
covered in the DPharp EJA with BRAIN protocol
instruction manual. For the items listed below which
are common to both the HART protocol and BRAIN
protocol, see the applicable user’s manuals listed in
Table 1.
Contents of Individual User’s Manuals
•INTRODUCTION
•HANDLING CAUTIONS
• COMPONENT NAMES
•INSTALLATION
•INSTALLING IMPULSE PIPING
•WIRING
•OPERATION
— Zero Point Adjustment
(For BRAIN Protocol)
• BRAIN TERMINAL BT200 OPERATION
(For BRAIN Protocol)
•MAINTENANCE
• PARAMETER SUMMARY
(For BRAIN Protocol)
•GENERAL SPECIFICATIONS
Contents of this User’s Manual for HART Protocol
—IM 01C22T01-01E—
• ZERO POINT ADJUSTMENT
• HART Communicator OPERATION
• PARAMETER LISTS
F01.EPS
Figure 1.Relationship between Individual Manuals and
Matching of communicator DD and instrument DD
Before using model 275 HART communicator,
check that the DD(Device Description) installed in
the communicator matches to that of instruments
to set up. To check the DD in the instrument or
the HART communicator, follow the steps below.
If the correct DD is not installed in the communicator, you must upgrade the DD at the HART
official programming sites. For communication
tools other than Model 275 HART communicator,
contact vendors of each for upgrade information.
1. Checking the DD in the instrument
1) Connect the communicator to the instrument
to set up.
[→]
[→]
.
.
2) Call "Device setup" and press
3) Call "Review" and press
4) By pressing [NEXT] or [PREV], find "Fld dev
rev" to show the DD of the instrument.
[Example]
EJA:
Review
Fld dev rev
2
"The instrument DD is
HELP PREV NEXT EXIT
Version 2."
F02.EPS
2. Checking the DD in Model 275 HART communicator
1) Turn on the communicator alone.
2) Call "Utility" from main menu and press
3) Call "Simulation" and press
[→]
.
[→]
4) Select "YOKOGAWA" from manufacturers
list by pressing
and press
[ ]
↓
[→]
.
5) Select the model name of the instrument(i.e.
EJA) by pressing
[ ]
and press
↓
[→]
to
show the DD of the communicator.
[Example]
HART Communicator
Fld dev rev
1 Dev v1, DD v2
2 Dev v2, DD v1
Version 1 and 2.
"The communicator DD
supports Version 1 and 2."
F03.EPS
.
ii
IM 01C22T01-01E
Page 4
1.ZERO POINT ADJUSTMENT
1. ZERO POINT ADJUSTMENT
After operating preparation is completed, adjust the
zero point. The zero point adjustment can be made
using either of the following two methods.
For output signal checking, display the parameter %rnge in the HART Communicator.
EJA:
Process variable
1 Pres0.012nnH2O
2 % range 0.00%
3 A01 Out4.002mA
4 Snsr temp38.1C
5 Static pres
HELPDIAGHOMEESC
HART Communication
display
Zero-adjustment
screw
F0101.EPS
䊏 Using the Transmitter Zero-adjustment
Screw
Before using the zero-adjustment screw outside the
transmitter case, confirm the following.
• Ext SW mode must be ENABLE. See Subsection
2.3.3 (17) for the setting procedure.
• Use a slotted screwdriver to turn the zero-adjustment
screw. Turn the screw clockwise to increase the
output or counterclockwise to decrease the output,
the zero point adjustment can be adjusted with a
resolution of 0.01% of the setting range.
The degree of zero adjustments varies with the
screw turning speed. Therefore, turn the screw
slowly for fine adjustment and quickly for coarse
adjustment.
䊏 Using the HART Communicator
Zero point can be adjusted by simple key operation of
the HART Communicator.
Select parameter Zero Trim, and press the OK (F4)
key twice. The zero point will be adjusted automatically to the output signal 0% (4 mA DC). Confirm that
the setting value displayed for the parameter % rnge
is 0.0% before pressing the OK (F4) key. See Subsection for HART Communicator operating procedures.
1.1 Zero Point Adjustment
The DPharp supports several adjustment methods.
Select the method best suited for conditions matching
the state of the site.
Note that output signal can be checked by HART
Communicator.
Adjustment Method
Zero adjustment
using the HART
Communicator
Zero adjustment
using the
external zeroadjustment
screw
Set the present
input to 0%.
P.1-2 ‘Zero trim’
Adjust output to
the reference
value obtained
using other
means.
P.1-2 ‘Lower
sensor trim’
Adjust zero point using the zeroadjustment screw on the transmitter.
This permits zero adjustment without
using the HART Communicator.
Accurately adjust the output current to
4mA DC or other target output value
using an ammeter that accurately reads
output currents.
Description
Adjust for 0% output
at input level of 0%.
If the input level
cannot easily be
made 0% (because of
tank level, etc.),
adjust output to the
reference value
obtained using other
means, such as a
glass gauge.
T0101.EPS
CAUTION
Do not turn off the power to the transmitter
immediately after a zero adjustment. Powering
off within 30 seconds after a zero adjustment will
return the adjustment back to the previous
settings.
1-1
IM 01C22T01-01E
Page 5
1. ZERO POINT ADJUSTMENT
1.1.1 Using the HART Communicator
(1) Zeroing — Zero trim
NOTE
Zero trim carries out the zero adjustment and
sets the input values at present, equal to 0
mmH2O. Use this setting to set LRV = 0 mmH2O.
1. Device setup
2. Diag/Service
3. Calibration
3. Sensor trim
1. Zero trim
1
EJA:
WARN-LOOP should be
removed from
automatic control
ABORTOK
2
EJA:
WARN-This will affect
sensor calibration
ABORTOK
3
EJA:
Apply O input to
sensor
ABORTOK
(2) Arbitrary Level Adjustment — Lower
Sensor Trim
This zero adjustment applies to tank level measurements, etc. where the actual tank level cannot be set to
zero. For this adjustment, use the actual tank level
obtained with a glass gauge or the like to meet the
DPharp output.
DPharp span:0 to 2500 mmH
Actual level:1350 mmH2O
Transmitter output: 1383 mmH2O
(OK)
Press OK (F4).
(OK)
Press OK (F4).
(OK)
A pressure of 0 mmH2O is applied.
Press OK (F4) after the pressure
has become stable.
F0102.EPS
O
2
1. Device setup
2. Diag/Service
3. Calibration
3. Sensor trim
2. Lower Sensor Trim
1
EJA:
Apply low pressure
(OK)
ABORTOK
2
EJA:
Press OK when
pressure is stable
ABORTOK
3
EJA:
ENTER applied
Pressure Value
0.000 mmH2O
0.000
HELPDEL ABORT ENTER
Check the tank level at present, and
press OK (F4).
(OK)
Press OK (F4).
‘1 3 5 0’
(ENTER)
Enter the value of the actual level
(1350 mmH
(F4).
O), and press ENTER
2
F0104.EPS
NOTE
Lower Sensor trim adjusts the input value at
present. See Fine Input Adjustment for detail.
1.1.2 Using the Transmitter Zero-adjustment Screw
Turn the zero-adjustment screw on the outside of the
transmitter case using a slotted screwdriver. Turn the
screw to the right to increase the zero point or to the
left to decrease the zero output; the zero adjusts in
increments of 0.01% of the range setting.
Note that the amount of adjustment to the zero point
changes according to the speed at which the screw is
turned. To make fine adjustments, turn the screw
slowly; to make coarse adjustments, turn the screw
quickly.
Note: When a zero point adjustment has been made do not turn of
the transmitter less than 30 seconds after adjustment.
DPharp
2500 mmH2O
Actual level
1350 mmH
0 mmH
2
O
2
O
F0103.EPS
1-2
IM 01C22T01-01E
Page 6
1. ZERO POINT ADJUSTMENT
1.2 Auto LRV (Change Low
Range Value)
1.2.1 Using Model 275 — Apply Values
Display the Apply Values display, and adjust the zero
point as follows:
1. Device setup
3. Basic setup
3. Re-range
2. Apply values
1
EJA:
WARN-LOOP should be
removed from
automatic control
ABORTOK
2
EJA:
Set the:
1 4mA
2 20mA
3 Exit
ABORT ENTER
3
EJA:
Apply New 4ma input
ABORTOK
‘Pressure stabilizing’
4
EJA:
Current applied
Process value:
0.06 mmH2O
1 Set as 4mA value
2 Read new value
3 Leave as found
ABORT ENTER
(OK)
Press OK (F4).
(ENTER)
Select 4 mA, and press ENTER (F4).
(OK)
Apply a pressure corresponding to
0% of the measurement range.
(ENTER)
LRV (0%) is read as –0.06 mmH2O.
Select Set as 4mA value, and
press ENTER (F4).
F0105.EPS
1.2.2 Setting the Range Using the Rangesetting Switch
With actual pressure(s) being applied to the transmitter,
the range-setting switch (push-button) attached to the
integral indicator plate and the external zero-adjustment screw allow users to change the lower- and
upper-range values for the measurement range (LRV
and URV) without the use of a HART Communicator.
However, a change in the display settings (scale range
and engineering unit) for the integral indicator requires
a HART Communicator.
Follow the procedure below to change the LRV and
URV settings.
Example: Rerange LRV to 0 and HRV to 20 kPa.
1) Connect the transmitter and allow them to warm up
for at least five minutes.
2) Press the range-setting push-button.
The integral indicator then displays LSET.
3) Apply a pressure of 0 kPa (atmospheric pressure) to
the high-pressure side of the transmitter.
4) Turn the external zero-adjustment screw (either in
the output-increase or -decrease direction).
The integral indicator displays the output signal (in
(Note 2)
%).
5) Adjust the output signal to 0% (1 V DC) by
rotating the external zero-adjustment screw. Doing
so completes the LRV setting.
6) Press the range-setting pushbutton.
The integral indicator then displays USET.
7) Apply a pressure of 20 kPa to the high-pressure
side of the transmitter.
(Note 1)
8) Turn the external zero-adjustment screw (either in
the output-increase or -decrease direction).
The integral indicator displays the output signal (in
(Note 2)
%).
9) Adjust the output signal to 100% (5 V DC) by
rotating the external zero-adjustment screw. Doing
so completes the URV setting.
10) Press the range-setting pushbutton.
The transmitter then switches back to the normal
operation mode while maintaining the measurement
range at 0 to 20 kPa.
Note 1: Wait until the pressure inside the pressure-detector section
has stabilized before proceeding to the next step.
Note 2: If the pressure applied to the transmitter exceeds the
previous LRV (or URV) , the integral indicator may display
error number “Er.07” (In this case, the output signal percent
and “Er.07” are displayed alternately every two seconds).
Although “Er.07” is displayed, there is no need to worry and
you may proceed to the next step. However, should any
other error number be displayed, take the appropriate
measure in reference to Section 2.4 Self-Diagnostics,
“Errors Messages.”
(Note 1)
1-3
IM 01C22T01-01E
Page 7
IMPORTANT
1. Do not turn off the power to the transmitter
immediately after completion of the change in
the LRV (and/or URV) setting(s). Note that
powering off within thirty seconds after setting
will ca use a return to the previous settings.
2. Changing LRV automatically changes URV to
the following value.
URV previous URV (new LRV previous LRV)
3. If the range-setting push-button and external
zero-adjustment screw are not touched during
a range-change operation, the transmitter
automatically switches back to the normal
operation mode.
Integral indicator
1. ZERO POINT ADJUSTMENT
Note: Use a thin bar which has a blunt tip, e.g.,
a hexagonal wrench, to press the rangesetting push-button.
Figure 1.2.1Range-setting Switch
Range-setting switch
(Push-button)
F0106.EPS
1-4
IM 01C22T01-01E
Page 8
2. HART COMMUNICATOR OPERATION
L =–
65×10
6
(R×C)
(Cf+10,000)
C
2.HART COMMUNICATOR OPERATION
2.1 Conditions of Communication Line
2.1.1 Interconnection Between DPharp
and HART Communicator
The HART Communicator can interface with the
transmitter from the control room, the transmitter site,
or any other wiring termination point in the loop,
provided there is a minimum of 250 Ω between the
connection and the power supply. To communicate, it
must be connected in parallel with the transmitter; the
connections are non-polarized. Figure 2.1.1 illustrates
the wiring connections for direct interface at the
transmitter site for the DPharp. The HART Communicator can be used for remote access from any terminal
strip as well.
Control room
Relaying
terminals
Terminal
board
Distributor
2.1.2 Communication Line Requirements
Specifications for Communication Line:
Supply voltage(general use type); 16.4 to 42 V DC
Load resistance; 250 to 600 W (Including cable
resistance)
Minimum cable size; 24 AWG, (0.51 mm diameter)
Cable type; Single pair shielded or multiple pair with
overall shield
Maximum twisted-pair length; 10,000 ft (3,048 m)
Maximum multiple twisted-pair length; 5,000 ft
(1,524 m)
Use the following formula to determine cable length
for a specific application;
Where: L = length in feet or meters.
R=resistance in ohms, current sense
resistance plus barrier resistance.
C=cable capacitance in pF/ft, or pF/m.
Cf=Maximum shunt capacitance of field
devices in pF.
DPharp
HART communicator
Figure 2.1.1 Interconnection Diagram
HART
communicator
F0201.EPS
2-1
IM 01C22T01-01E
Page 9
2. HART COMMUNICATOR OPERATION
2.2 Basic Operation of the HART Communicator (Model 275)
2.2.1 Keys and Functions
Communication Cable
LCD (Liquid crystal display)
(21 characters×8 lines)
Function keys
Functions of the keys are indicated on the
display.
as shown changes the display to “Online”
menu. (See 2.2.2 “Display”.)
Moves the highlighting cursor on the display to
select the desired item.
Power ON/OFF
Shift keys
Use to enter alphabetic characters.
Hot key
Call up setting menu
1. Keypad Input
2. Enable Write
3. New Password
1. Changes the display contents.
2. Moves the position where a number or
character is to be entered.
Pressing calls up the display
corresponding to the item pointed with the
highlighting cursor.
Pressing returns to the previous
display. (See 2.2.3.)
Alphanumeric keys
1.Enters numbers and characters.
2.Selects the desired menu item with the
corresponding number. (See 2.2.4.)
Pressing single key enters the number.
Pressing the key with shift key enters the
alphabetic character.
(Press)(ENTER)
To enter “7”,
To enter “C”,
“7”
“C”
F0202.EPS
Figure 2.2.1 The HART Communicator
2-2
IM 01C22T01-01E
Page 10
2. HART COMMUNICATOR OPERATION
2.2.2 Display
The HART communicator searches for a transmitter on
the 4 to 20mA loop when it is turned on. When the
HART communicator is connected to the transmitter,
Online menu (Top menu) is started automatically and
the following display appears. If no transmitter is
found, you select Online menu.
Pressing one of the SHIFT keys makes the arrow
mark corresponding to the pressed key appear.
Appears when the voltage level of the battery is low.
<a> appears and flashes during communication
between the HART communicator and the
transmitter. At Burst mode, appears.
<b> The menu items selected from the previous menu.
<c> The items to be used from the menu of <b>.
<d> or appears when the item is scrolled out of
the display.
<e> The labels of function corresponding to each
function key appears. These labels reflect currently available choices.
Tag (8 Characters)
Function keys
The highlighting cursor
<a>
F0203.EPS
Function Key Labels
F1
HELP
access on-line
help
RETRY
try to re-
establish
communication
EXIT
leave the
current menu
YES
answer to
yes/no question
ALL
include current
Hot Key item on
Hot Key Menu
for all devices
SAVE
save information
to
communicator
SEND
send data to
device, or mark
data to send
F2
ON/OFF
activates or
deactivates a
binary variable
DEL
delete current
character or Hot
Key Menu item
SEND
send data to
device, or mark
data to send
PGUP
move up one
help screen
PREV
go to previous
message in a
list of messages
EDIT
edit a variable
value
ADD
add current item
to Hot Key
Menu
F3
ABORT
terminate
current task
ESC
leave value
unchanged
QUIT
terminate session
because of a
comunication
error
PGDN
move down one
help screen
NEXT
go to next
message in the
list of messages
HOME
go to the top
menu in the
device
description
BACK
go back to
menu from
which HOME
was pressed
F4
OK
acknowledge
information on
screen
ENTER
accept userentered data
NEXT
leave the
current menu
NO
answer to
yes/no question
SKIP
do not mark
variable to be
sent in off-line
configuration
ONE
include Hot Key
item for one
device
F0204.EPS
Key Operation
There are two choices to select the desired menu item.
1. Use the or key to select the desired item,
and then press the key.
2. Press the number displayed for the desired item.
• To return to the previous display, press the key.
* If
ABORT, ESC
and
are displayed,
EXIT
press the desired function key.
Example: Call up the Tag item, to change the tag.
Check to see where item Tag is located in the menu
configuration. Then, call up Tag item on the display
according to the menu configuration.
2.2.3 Calling Up Menu Addresses
Subsection 2.3.2 shows the configuration of all menu
items available with the HART communicator. The
desired item can be displayed with ease by understanding the menu configuration.
When the HART communicator is connected to the
transmitter, Online menu will be displayed after power
is turned on. Call up the desired item as follows:
2-3
Device setup
Pres
P01 Out
LRV
URV
Tag
Unit
Re-range
Device information
.
.
.
Process variables
Diag/Service
Basic Setup
Detailed Setup
Review
EJA:YOKOGAWA
Basic Setup
1 Tag
2 Unit
3 Re-range
4 Device information
5 Xfer fnctn
HELP
DELSAVE HOME ENTER
4
EJA:YOKOGAWA
Tag
YOKOGAWA
YOKOGAWA
or
Display appears when the
1
HART Communicator is turned on.
Select Device setup.
×2
or
Select Basic setup.
Select Tag.
The display for Tag setting appears.
When the setting display shown above appears, enter
the data as follows:
Character to
be entered
F
I
C
-
1
A
Deletes
characters.
OperationDisplay
FOKOGAWA
FIKOGAWA
FICOGAWA
FIC-GAWA
FIC-1AWA
FIC-1AWA
FIC-1A
(DEL)
F0207.EPS
DELESC
HELPDELENTER
F0205.EPS
2.2.4 Entering, Setting, and Sending Data
The data input using the keys are set in the HART
communicator by pressing ENTER (F4). Then, by
pressing SEND (F2), the data is sent to the transmitter.
Note that the data is not set in the transmitter if SEND(F2) is not pressed. All the data set with the HART
communicator is held in memory unless power is
turned off, every data can be sent to the transmitter at
once.
Operation
Entering data on the Tag setting display.
Example: To change from Tag YOKOGAWA to FIC-1A.
Call up the Tag setting display.
1. Device setup
3. Basic setup
1. T ag
DisplayOperation
5
EJA:YOKOGAWA
Tag
YOKOGAWA
FIC-IA
HELPDELESC ENTER
6
EJA:YOKOGAWA
Basic setup
1 Tag
2 Unit
3 Re-range
4 Device information
5 Xfer fncth
HELP SEND HOME ENTER
7
EJA:FIC-1A
Basic Setup
1 Tag
2 Unit
3 Re-range
4 Device information
5 Xfer fncth
HELP SAVE HOME ENTER
(ENTER)
After entering the data, set the
HART communicator with the data
entered by pressing ENTER (F4).
(SEND)
Send the data to the transmitter by
pressing SEND (F2).
* is flashed during communication.
disappears, and the
SEND
transmission is complete.
F0208.EPS
EJA:YOKOGAWA
Tag
YOKOGAWA
YOKOGAWA
HELPDELESC ENTER
F0206.EPS
2-4
IM 01C22T01-01E
Page 12
2. HART COMMUNICATOR OPERATION
2.3 Parameters
2.3.1 Parameter Usage and Selection
Before describing the procedure for setting parameters,
we present the following table showing how the
prameters are used and in what case.
Table 2.3.1 Parameter Usage and Selection
ItemHART CommunicatorDescriptionPage
Memory
Transmitter
Display
HART output
Monitoring
Maintenance
Adjustment
Engineering unit
Range
Output mode
Damping time constant
Output signal low cut
mode
Bi-direction flow
measurement mode
H
O unit selection
2
Unit for displayed
temperature
Unit for displayed static
pressure
Integral indicator display
mode
Integral indicator scale
Burst mode
Multi-drop mode
Test output
Self-diagnostics
Output when CPU error
has occurred
External volume
protect/permit
Software Write Protect
Zeroing
Sensor trim
Analog output trim
Tag
Descriptor
Message
Date
Unit
LRV/URV
Apply values
Xfer fnctn
Damp
Low cut
Cut mode
Bi-dire mode
H
O Unit select
2
Snsr temp unit
Static pres unit
Display fnctn
Display mode
Engr disp range
Burst option
Burst mode
Poll addr
Auto poll
Pres
% rnge
A01 out
Snsr temp
Static pres
Engr display
Loop test
Self test
Status
A01 Alarm typ
Ext SW mode
Write protect
Enable write
New password
Zero trim
Lower/Upper sensor trim
D/A trim, Scaled D/A trim
Tag number, Up to 8 characters
Up to 16 characters
Up to 32 characters
xx/yy/zz
inH2O, inHG, ftH2O, mmH2O, mmHG, psi, bar, mbar, g/cm2, kg/cm2, Pa, kPa, MPa, torr, atm
Set the calibration range by the keypad
Range for 4 to 20 mA DC signal is set with actual input applied.
Sets mode for output signal to “linear mode” (proportional to input differential pressure)
or to “Square root mode” (proportional to flow).
Adjust the output response speed for 4 to 20 mA DC. 0.2, 0.5, 1, 1.5, 2, 4, 6, 8, 16, 32
(sec)
Used mainly to stabilize output near 0 if output signal is the square root mode. Two
mode are available: forcing output to 0% for input below a specific value, or changing to
proportional output for input below a specific value.
Linear or Zero
Used to measure bi-directional flows.
at 4°C (39.2°F)/at 20°C (68°F)
Sets a unit for temperature displayed on the model 275.
Sets a unit for static pressure displayed on the model 275.
Sets mode for integral indicator to “linear mode” (proportional to input differential
pressure) or to “Square root mode” (proportional to flow).
Set the following 5 types of integral indicator scale ranges and unit: “% scale indicator”,
“use set scale indicator”, “alternate indication of user set scale and % scale”, “input
pressure display” and “alternate indication of input pressure and % scale.
Engr unit/Engr disp LRV/Engr disp URV/Engr disp point.
Selection of the data to be sent continuously (Pres/% rnge/A01 out).
ON/OFF switching of burst mode.
Setting the polling address (1 to 15).
ON/OFF switching of multi-drop mode.
Pressure variable
% output variable
4 to 20 mA output variable
Sensor temperature
Static pressure
Displays output as on an LCD. settable in the engr disp range.
Used for loop checks. Output can be set freely from –5% to 110% in 1% step.
Check using the self-test command. If an error is detected, the corresponding message
is displayed.
Display of the result of self-test, calibration of transmitter.
Display the status of 4 to 20 mA DC output when a failure
Display/set the external volume protect/permit for LRV (URV) setting.
Displays the permit/protect status of setting changes depending on communications.
Write protect status is released for 10 minutes when the password is entered.
Setting a new password.
Set the current input value to 0 kPa.
Adjust only measured pressure variable.
Adjust the output value at the points of 4 mA and 20 mA.
NOTE
Do not turn off the transmitter as soon as HART
Communicator settings (sending) have been
made. If the transmitter is turned of less than 30
seconds after parameters have been set, the set
data will not be stored and the terminal returns
to previous settings.
P.2-7
P.2-8
P.2-9
P.2-10
P.2-19
P.2-12
P.2-10
P.2-11
P.2-10
P.2-16
—
P.2-12
P.2-19
—
P.2-17
P.1-2
P.2-13
P.2-14
T0201.EPS
2-5
IM 01C22T01-01E
Page 13
2.3.2 Menu Tree
2. HART COMMUNICATOR OPERATION
Online Menu
1 DEVICE SETUP
2 Pres
3 A01 Out
4LRV
5URV
1 PROCESS
VARIABLES
2DIAGNOSTICS
AND SERVICE
3 BASIC SETUP
4 DETAILED
SETUP
1 Pressure
2 Percent Range
3 Analog Output
4 Sensor Temperature
5Static Pressure
6 Engineering Unit
7 Engineering Display
1 TEST/STATUS
2 Loop Test
3 CALIBRATION
1Tag
2 Unit
3 RERANGE
4 DEVICE INFO
5Transfer Function
6 Damp
7 Low Cut
8 Cut Mode
1 SENSORS
2SIGNAL
CONDITION
3 OUTPUT
CONDITION
Hot Key1LRV
1 Self Test
2Status
1 RERANGE
2 TRIM ANALOG
OUTPUT
3 SENSOR TRIM
1 Keypad Input
2 Apply Values
1 Date
2 Descriptor
3 Message
4Write Protect
1Pressure Sensor
2Temperature
Sensor
3Static Pressure
Sensor
1 PROCESS
VARIABLES
2 RERANGE
3 Unit
4Transfer Function
5 Damp
6 Low Cut
7 Cut Mode
8Bi-dir Mode
9 H2O Unit Select
1 PROCESS
VARIABLES
1 Keypad Input
2Wrt protect menu
1 Keypad Input
2 Apply Values
1Digital-to-Analog Trim
2 Scaled Digital-to-Analog Trim
1 Zero Trim
2 Pressure
3 Lower Sensor Trim
4 Upper Sensor Trim
5 Sensor Trim Points
1 Zero Trim
1 Percent Range
2 Pressure
3 Unit
4 Sensor Trim
1 Sensor Temperature
2 Sensor Temperature Unit
1Static Pressure
2Static Pressure Unit
1 Pressure
2 Percent Range
3 Sensor Temperature
1 Keypad Input
2 Apply Values
1 Pressure
2 Percent Range
3 Analog Output
4 Sensor Temperature
5Static Pressure
6 Engineering Unit
7 Engineering Display
2 Pressure
3 Lower Sensor Trim
4 Upper Sensor Trim
5 Sensor Trim Point
2URV
3 Unit
4 LSL
5 USL
6Min Span
1Write protect
2 Enable wrt 10 min
3 New password
4 Software seal
5 REVIEW
4DISPLAY
CONDITION
5 DEVICE
INFORMATION
2 ANALOG
OUTPUT
3 Analog Output
Alarm
4 HART OUTPUT
1Display Mode
2Display Function
3 Engineering
Display Range
1Field Device Info
2 Sensor Info
3 Self Test
2-6
1 Loop Test
2Digital-to-Analog Trim
3 Scaled D/A Trim
1 Poll Address
2 Number of Request Preambles
3 Burst Mode
4 Burst Option
1 Engineering Unit
2 Engineering Display LRV
3 Engineering Display URV
4 Engineering Display Point
F0209.EPS
IM 01C22T01-01E
Page 14
2. HART COMMUNICATOR OPERATION
2.3.3 Setting Parameters
(1) Tag No.
To change the Tag No., see section 2.2.4 Entering,
Setting, and Sending Data.
Up to 8 characters can be set with Tag. The maximum
number of characters to be set for other items is as
shown below. With Option code /CA, the Descriptor is
filled in at the factory as specified in the order.
ItemThe Number of Characters
Tag
Descriptor
Message
Date
Example: To change from Tag YOKOGAWA to FIC-1A.
Call up the Tag setting display.
1. Device setup
3. Basic setup
1. T ag
See Section 2.2.4.
(2) Unit
The unit is set at the factory before shipment if
specified at the time of order. Follow the procedure
below to change the unit.
Example: To change the unit from mmH2O to inH2O
1
EJA:
Hot Key
1 Keypad input
2 Enable Write
3 New Password
To set the Lower Range Valve,
select the LRV item.
‘5 0 0’
(ENTER)
Enter 500, and press ENTER (F4).
To change the Upper Range Valve,
select the URV item.
‘3 5 0 0’
(ENTER)
Enter 3500, and press ENTER (F4).
(SEND)
Press SEND (F2) to send the
changed data to the transmitter.
Check that disappears.
SEND
F0212.EPS
2-7
IM 01C22T01-01E
Page 15
2. HART COMMUNICATOR OPERATION
NOTE
It is possible to set LRV URV. This setting
reverses the 4 to 20 mA output signal.
Conditions:LSL LRV USL
LSL URV USL
|URV LRV| Min. Span
The 4 to 20 mA output does not correspond to
the scale of the indicator under the following
conditions in which;
•the equipment with standard specification is
used with the setting changed to the above
setting.
• the customer specified equipment (with the
above factory-setting) is used with the setting
changed to the normal (standard) setting.
In the cases above, replace the scale with one
which corresponds correctly to the 4 to 20 mA.
(b) Changing the Ranges While Applying an
Actual Input — Apply values
This feature allows the lower and upper range values to
be setup automatically with the actual input applied. If
the upper and lower range values are set, “URV” and
“LRV” are changed at the same time.
The measurement span is determined by the upper and
lower range valves. Changing the lower range value
results in the upper range value change automatically,
keeping the span constant.
4
EJA:
Current applied
process value:
500.01 mmH2O
1 Set as 4mA value
2 Read new value
3 Leave as found
HELPSENDENTER
DELABORT
(ENTER)
The LRV to be changed is 500.01
mmH2O.
• Selecting item 1 sets LRV to
500.01 mmH2O.
• Selecting item 2 reads LRV again.
To set LRV = 500.01, select item 1
5
EJA:
Set the
1 4mA
2 20mA
3 Exit
DELENTER
HELPABORT
and press ENTER (F4).
×2
(ENTER)
Select Exit and press ENTER (F4).
Check the value after completing
the range change with URV and
LRV.
* The span is maintained the same
as when changing LRV with Apply values. In this case, if LRV is
changed from 0 to 500, URV is
changed automatically to 3000.
(4) Output Mode (Linear/Sq root)
The output mode has already been set to a Linear
output (Linear). Follow the procedure below to
change the mode.
Example: To change the mode from Linear to Sq root.
Call up the Xfer fnctn display.
F02131.EPS
Example: To change the range from 0 to 2500 mmH2O to
500 to 3000 mmH
O
2
Call up the Apply Values display.
1. Device setup
3. Basic setup
3. Re-range
2. Apply values
1
EJA:
WARN-Loop should be
removed from
automatic control
DELSET ABORTOK
2
EJA:
Set the:
1 4mA
2 20mA
3 Exit
HELPSAVE ABORT ENTER
3
EJA:
Apply new 4ma input
HELPDEL ABORTOK
(OK)
Press OK (F4).
(ENTER)
To set the lower range value, select
4mA and press ENTER (F4).
(OK)
Apply the pressure of 500mmH2O.
After obtaining a stable pressure,
press OK (F4).
F0213.EPS
1. Device setup
3. Basic setup
5. Xfer fnctn
1
EJA:
Transfer function
Linear
Linear
Sq root
DELSETESC ENTER
(ENTER)
(SEND)
[1] Select Sq root, and press
ENTER (F4).
[2] Press SEND (F2) to send the
data to the transmitter, then
check to confirm that
disappears.
The output mode is set as specified in the order when
the instrument is shipped.
If the instrument is equipped with an integral indicator
and Transfer function is sq root, “” is displayed on
the integral indicator.
2-8
IM 01C22T01-01E
SEND
F0214.EPS
Page 16
2. HART COMMUNICATOR OPERATION
0.2 Sec
0.5 Sec
1.0 Sec
2.0 Sec
4.0 Sec
8.0 Sec
16.0 Sec
32.0 Sec
64.0 Sec
T0203.EPS
(5) Damping Time Constants
The damping constant is set to 2.0 seconds at the
factory. When changing the damping constant, proceed
as follows:
Example: To change from 2.0 seconds to 0.2 seconds
Call up the Damp display.
1. Device setup
3. Basic setup
6. Damp
1
EJA:
Damping
2.00 s
2.00
HELPDELESC ENTER
2
EJA:
Basic Setup
1 Unit kPa
2 Re-range
3 Device information
4 Xfer fncfn Linear
5 Damp 0.20s
HELP SEND HOME ENTER
3
EJA:
Set to nearest
possible value
occurred writing Pres
damping
Press OK...
DELSETESCOK
‘0 . 2’
(ENTER)
Enter 0.2 and press ENTER (F4).
Press SEND (F2) to send the data
to the transmitter.
(OK)
A confirmation display appears.
Press OK (F4), then check to
confirm that disappears.
SEND
F0215.EPS
(6) Output Signal Low Cut Mode Setup
Low cut can be used on the output signal to stabilize
the output near the zero point.
The low cut point can be set in a range from 0 to 20%
of output. (Hysteresis of cut point: ±1%)
Either LINEAR or ZERO can be selected as the low
cut mode.
Unless otherwise specified, the cut mode is set to
LINEAR at the factory.
Example: To set the low cut range to 20% and the cut mode
50
Output
20
For low cut in linear mode
Figure 2.2.2 Low Cut Mode
1. Device setup
3. Basic setup
7. Low Cut, 8. Cut mode
to ZERO, proceed as follows:
(%)
0
Input
50
(%)
(%)
50
Output
20
0
Input
For low cut in zero mode
F0216.EPS
50
(%)
NOTE
1. Only the damping constants listed in Table 2
are available. When a value not listed in
Table 2 is entered, the value in Table 2
nearest the entered value is set.
2. The damping constant set with the procedure
here is of the damping constant in the transmission part (electric circuit). The damping
constant of the capsule assembly shall be
added to obtain the overall damping constant
of the transmitter.
Table 2
EJA:
Low cut
10.00%
10.00
HELPDELESC ENTER
EJA:
Cut mode
Linear
Linear
Zero
HELPSENDESC ENTER
EJA:
Basic Setup
4 Device information
5 Xfer fnctn Linear
6 Damp 0.50s
7 Low cut 20.00 %
8 Cut mode Zero
DELSEND HOMEOK
2-9
‘2 0’
(ENTER)
Call up the Low cut, and set to
20%.
(ENTER)
Select the Cut mode, and set to
Zero.
(SEND)
Press SEND (F2) to send the date,
then check to confirm that
SEND
disappears.
F0217.EPS
IM 01C22T01-01E
Page 17
2. HART COMMUNICATOR OPERATION
(7) Bi-directional Flow Measurement
(a) Bi-dir mode enables selection of 50% output at an
input of 0 mmH2O.
Example: If measurement range is 0 to 3000mmH2O
1. Device setup
4. Detailed setup
2. Signal condition
8. Bi-dir mode
EJA:
Bi-dir mode
OFF
off
on
HELPSENDESC ENTER
Note: The measurement range changes to –3000 to 0 to
(LRV = 0 mmH2O, URV = 3000 mmH2O)
(ENTER)
(SEND)
Call up the Bi-dir mode Display
Select on, and press ENTER (F4).
Press SEND (F2) to send the data
to the transmitter, then check to
confirm that disappears.
SEND
3000mmH2O (output 0% to 50% to 100%).
Note that LRV and URV are not changed.
F0218.EPS
(b) Combining Bi-dir mode with Xfer fnctn provides
a square root output computed independently for
0% to 50% output and for 50% to 100% output.
20 mA (100% display)
LRVHRV
(8) Integral Indicator Display Mode
Example: Change from Linear to Sq root
1. Device setup
4. Detailed setup
4. Display condition
2. Display fnctn
EJA:
Display fnctn
Linear
Linear
Square Root
HELPSENDESC ENTER
(ENTER)
(SEND)
Select Square Root and press
ENTER (F4).
Press SEND (F2) to send data.
(9) Integral Indicator Scale
Display
Mode
NORMAL %
USER SET
USER & %
Display
Related
Parameters
% rnge 45.6%
Engr disp range
20.0M
% rnge
45.6%
Engr disp range
20.0M
F0220.EPS
Description
Indicates –5 to
110% range
depending on the
set range (LRV,
URV).
Displays values
depending on
engr disp LRV
and engr disp
URV Units set
using engr disp
unit are not
indicated.
Indicates user set
and % alternately
in 3 second
intervals.
Output mode “LINEAR”
20 mA (100% display)
Low Cut
Output mode “SQUARE ROOT”
4 mA (–100% display)
LRVHRV
4 mA (–100% display)
F0219.EPS
INP PRES
PRES & %
* The number of lines displayed on the LCD is determined by the
number of LRV and URV lines set on the brain terminal.
Pres 456 kPa
% rnge 45.6%
Pres 456 kPa
See (a) through (c) for each setting procedure.
2-10
Indicates input
pressure.
Indicates input
pressure and %
alternately in 3
second intervals.
T0204.EPS
IM 01C22T01-01E
Page 18
2. HART COMMUNICATOR OPERATION
% indication and input
pressure indication
Normal %
Input press
Input press & %
Transmitter is set
for “NORMAL %”
when shipped.
User-set engineering
unit display
User set
User set & %
Set for user-set
engineering unit
display.
Engr disp unit
Set a unit to be
displayed on
the HART Communication.
For % display, set
this parameter
only.
Engr disp LRV
Set a numeric
value for engineering unit for
4 mA output
(LRV).
Set a numeric
value for engi-
Engr disp URV
neering unit for
20 mA output
(HRV).
(a) Display Mode
Follow the instructions given to the below to
change the range of integral indication scale.
When USER SET is selected, the user set values
of integral indication.
F0221.EPS
Example: Set an engineering unit M.
1. Device setup
4. Detailed setup
4. Display condition
3. Engr disp range
1. Engr unit
EJA:
Engr unit
HELPDELESC ENTER
(ENTER)
(SEND)
Set M, and press ENTER (F4).
(c) Lower and Upper Range Value Setup in
Engineering Unit
Engr disp LRV and Engr disp URV are used to
set the lower and higher range values for the
engineering unit display. When the instrument is
shipped, these are set as specified in the order.
Note that these items need not be set for % display.
F0223.EPS
Example: Set the integral indicator scale to engineering units
display
1. Device setup
4. Detailed setup
4. Display condition
1. Display mode
EJA:
Display mode
Normal %
Normal %
User set
User set & %
Input press
HELPSENDESC ENTER
(ENTER)
(SEND)
Select User set and press ENTER (F4).
Press SEND (F2) to send the data
to the transmitter.
F0222.EPS
(b) Setting User-set Engineering Unit
Engr unit allows entry of the engineering units to
be displayed on the HART communicator. When
the instrument is shipped, this is set as specified in
the order. Follow the procedure below to change
this setting.
Since these units are not displayed on the integral
indicator, use the adhesive labels provided Engr
unit need not be set for % display.
Example: Set low range value (LRV) to –50 and upper range
value (URV) to 50.
1. Device setup
4. Detailed setup
4. Display condition
3. Engr disp range
2. Engr disp LRV, 3. Engr disp URV
EJA:
Engr disp LRV
0.0
0.0
DELDELESC ENTER
‘– 5 0’
(ENTER)
Set –50, and press ENTER (F4).
EJA:
Engr disp range
1 Engr unit
2 Engr disp LRV
3 Engr disp URV
4 Engr disp point
HELP SEND HOME ENTER
EJA:
Engr disp URV
0.0
0.0
HELP
DELDELESC ENTER
Press to select engr disp URV.
‘–5 0’
(ENTER)
(SEND)
Set 50, and press ENTER (F4).
Press SEND (F2) to send data.
F0224.EPS
2-11
IM 01C22T01-01E
Page 19
2. HART COMMUNICATOR OPERATION
(10) Unit for Displayed Temperature
When the instrument is shipped, the temperature units
are set to C (Centigrade). Follow the procedure below
to change this setting.
The unit changed here corresponds the unit for Snsrtemp.
Example: Change the unit for the temperature display.
1. Device setup
4. Detailed setup
1. Sensors
2. T emp sensor
2. Snsr temp unit
EJA:
Snsr temp unit
C
C
F
HELPSENDESC ENTER
(ENTER)
Select F (Fahrenheit), and Press
ENTER (F4).
F0225.EPS
(11) Unit for Displayed Static Pressure
Follow the procedure to change the static pressure unit.
Changing this parameter also changes the unit for the
static pressure display.
Example: Change the static pressure unit from mmH2O to
1. Device setup
4. Detailed setup
1. Sensors
3. Static Pres sensor
2. Static Pres unit
EJA:
Static Pres unit
mmH2O
mmH2O
mmHg
psi
bar
HELPSENDESC ENTER
kPa.
inH2O
inHg
O
ftH
2
mmH
mmHg
psi
bar
mbar
g/cm
kg/cm
Pa
kPa
torr
atm
(ENTER)
(SEND)
O
2
Select kPa and Press ENTER (F4).
Select SEND (F2) to send the data.
2
2
F0226.EPS
(12) Test Output
This feature can be used to output a fixed current from
3.2 mA (–5%) to 21.6 mA (110%) for loop checks.
Example: To output 12 mA (50%)
1. Device setup
2. Diag/Service
2. Loop test
1
EJA:
WARN-loop should be
removed from
automatic control
DELSET ABORTOK
2
EJA:
Choose analog output
level
1 4mA
2 20mA
3 Other
4 End
DELSET ABORT ENTER
3
EJA:
Output
4.000
HELPDEL ABORT ENTER
4
EJA:
Fld dev output is
fixed at 12.000 mA
HELPSENDOK
DELABORT
5
EJA:
Choose analog output
level
1 4mA
2 20mA
3 Other
4 End
HELPSENDENTER
DELABORT
6
EJA:
NOTE-loop may be
returned to automatic
control
HELPSENDOK
DELESC
(OK)
Set the control loop in manual
mode, and press OK (F4).
×2
(ENTER)
Select Other, and press ENTER (F4).
Supplementary explanation.
1. 4 mA:
Outputs a 4 mA current signal
2. 20 mA:
Outputs a 20 mA current signal
3. Other:
Sets a desired output using the
alphanumeric keys
4. End: Exits
‘1 2’
(ENTER)
Enter 12, and press ENTER (F4).
A fixed current of 12 mA is output.
(OK)
Press OK (F4).
×3
(ENTER)
To finish the loop test, select End,
and press ENTER (F4).
(OK)
Press OK (F4).
F0227.EPS
2-12
IM 01C22T01-01E
Page 20
2. HART COMMUNICATOR OPERATION
CAUTION
1. Test output is held for approximately 10
minutes, and then released automatically
after the time has elapsed. Even if the HART
Communicator power supply is turned off or
the communication cable is disconnected
during test output, it is held for approximately
10 minutes.
2. Press the (OK) key to release test output
immediately.
(13) Sensor Trim
Each DPharp EJA Series Transmitter is factory
characterized. Factory characterization is the process of
comparing a known pressure input with the output of
each transmitter sensor module over the entire pressure
and temperature operating range. During the characterization process, this comparison information is stored
in the transmitter EEPROM. In operation, the transmitter uses this factory-stored curve to produce a process
variable output (PV), in engineering units, dependent
on the pressure input. The sensor trim calibration
procedure allows you to make corrections to the
calculated process variable.
There are two ways to trim the sensor: full sensor trim
and zero trim. A full sensor trim is a two point process,
in which two accurate end-point pressures are applied
(equal to or greater than the range values), and all
output is linearized between them. A zero trim is a
one-point adjustment typically used to compensate for
mounting position effects or zero shifts caused by static
pressure. (See section 1.1.1)
Example 1: For the range of 1000 to 3000 mmH2O
1. Device setup
2. Diag/Service
3. Calibration
3. Sensor Trim
1
EJA:
Sensor trim
1 Zero trim
2 Pres
3 Lower sensor trim
4 Upper sensor trim
5 Sensor trim points
HELPSETHOMEOK
2
EJA:
Apply low pressure
DELSET ABORTOK
Select the Lower Sensor trim.
(OK)
Apply a standard pressure of 1000
O to the transmitter. After
mmH
2
obtaining a stable pressure, press
OK (F4).
F02281.EPS
3
EJA:
Press OK when
pressure is stable
(OK)
HELPDEL ABORTOK
4
EJA:
Enter applied
pressure value
0.00 mmH2O
0.00
HELPABORT
DELENTER
Press OK (F4).
‘1 0 0 0’
(ENTER)
Enter 1000, and press ENTER (F4).
Remove pressure appears for a
while.
Fine input adjustment (0%) is
complete.
F02282.EPS
SPAN adjustment shall be carried out with Upper
Sensor trim. After selecting Upper Sensor trim,
apply a pressure of 3000 mmH2O (corresponding to
100% of the measurement range). Then, proceed the
same as for the operations for Lower Sensor trim.
1
EJA:
Sensor trim
1 Zero Trim
2 Pres
3 Lower sensor trim
4 Upper sensor trim
5 Sensor trim points
HELPSETHOMEOK
2
EJA:
Apply hi pressure
DELSET ABORTOK
3
EJA:
Press OK when
pressure is stable
HELPDEL ABORTOK
4
EJA:
Enter applied
Pressure value
0.00 mmH2O
0.00
HELPABORT
DELENTER
Select the Upper Sensor trim item.
(OK)
Apply a standard pressure of 300
mmH
O to the transmitter. After
2
obtaining a stable pressure, press
OK (F4).
(OK)
Press OK (F4).
‘3 0 0 0’
(OK)
Enter 3000, and press ENTER (F4).
Remove pressure appears for a
while.
Fine input adjustment (100%) is
complete.
F0229.EPS
2-13
IM 01C22T01-01E
Page 21
2. HART COMMUNICATOR OPERATION
(14) Trim Analog Output
Fine output adjustment is carried out with D/A trim or
Scaled D/A trim.
• D/A Trim
D/A trim is to be carried out if the calibration
digital ammeter does not read 4.000 mA and 20.000
mA exactly with the output signal of 0% and 100%.
• Scaled D/A Trim
Scaled D/A trim is to be carried out if the output
is adjusted using a voltmeter or other types of
meters or using a meter whose the scale unit is 0 to
100%.
Example 1: For the adjustment using an ammeter (±1µA is
1. Device setup
2 Diag/Service
3. Calibration
2. Trim analog output
1
EJA:
Trim analog output
1 D/A trim
2 Scaled D/A trim
HELPSETHOMEOK
2
EJA:
WARN-LOOP should be
removed from
automatic control
DELSET ABORTOK
3
EJA:
Connect reference
meter
HELPDEL ABORTOK
4
EJA:
Setting fld dev
output to 4mA
HELPABORT
5
EJA:
Enter meter value
4.000
HELPESC
measurable)
DELOK
DELENTER
Select the D/A trim item.
(OK)
Press OK (F4).
(OK)
Connect the ammeter (±1µA is
measurable), and press OK (F4).
(OK)
Press OK (F4), and the transmitter
outputs the output signal of 0%.
‘4 . 1 1 5’
(ENTER)
Ammeter reading: 4.115
Enter the read value 4.115 of the
ammeter, and press ENTER (F4).
(The output of the transmitter
changes.)
F0230.EPS
6
EJA:
Fld dev output 4.000
mA equal to reference
meter?
1 Yes
2 No
HELPSET ABORT ENTER
7
EJA:
Setting fld dev
output to 20mA
DELSET ABORTOK
8
EJA:
Enter meter value
20.000
HELPDEL ABORT ENTER
9
EJA:
Fld dev output 20.000
mA equal to reference
meter?
1 Yes
2 No
HELPABORT
DELENTER
10
EJA:
NOTE-Loop may be
returned to automatic
control
DELOK
HELPESC
(ENTER)
Ammeter reading: 4.000
Because the reading on the
ammeter is 4.000 mA, select YES
and press ENTER (F4).
If the reading is not 4.000 mA,
select item 2. NO. Repeat steps
5
and until the ammeter reads
4
4.000 mA.
(OK)
Press OK (F4), and the transmitter
outputs the output signal of 100%.
‘1 9.0 5 0‘
(ENTER)
Ammeter reading: 19.050
Carry out the same procedures as
4
those described under and .
5
(ENTER)
Ammeter reading: 20.000
Returning fld dev to original
output appears.
(OK)
Press OK (F4).
F0231.EPS
2-14
IM 01C22T01-01E
Page 22
2. HART COMMUNICATOR OPERATION
Example 2: To adjust using a voltmeter
1
EJA:
Trim analog output
1 D/A trim
2 Scaled D/A trim
HELPSETHOMEOK
Select the Scaled D/A trim item.
2
EJA:
WARN-Loop should be
removed from
automatic control
DELSET ABORTOK
(OK)
Press OK (F4).
3
EJA:
Trim will be scaled
from 4.000 to 20.000
1 Proceed
2 Change
HELPDEL ABORT ENTER
Select Change, and press ENTER
(F4).
The same operations as for D/A
trim are required when selecting
item 3. Proceed.
4
EJA:
Set scale- Lo output
value
4
4
HELPABORT
DELENTER
‘1’
(ENTER)
Enter the value read on the meter
when the signal is 4 mA. In this
case, Enter the value of the voltage
across a 250 Ω resistor (1 V), and
press ENTER (F4).
5
EJA:
Set scale- Hi output
value
20
20
HELPABORT
DELENTER
‘5’
(ENTER)
Enter the value read on the meter
when the signal is 20 mA. Then,
enter 5, and press ENTER (F4).
6
EJA:
Trim will be scaled
from 1.000 to 5.000
1 Proceed
2 Change
EJA:
NOTE-Loop may be
returned to automatic
control
HELPABORT
DELOK
‘1 . 0 1’
(ENTER)
Voltmeter reading: 1.010
Enter the reading of the voltmeter
(1.010), and press ENTER (F4).
(The output of the transmitter
changes.)
(ENTER)
Voltmeter reading: 1.000
Because the reading on the
voltmeter is 1.000, select Yes and
press ENTER (F4).
If the reading is not 1.000, select
No. Repeat steps and until
98
the voltmeter reads 1.000 V.
(OK)
Press OK (F4). The output signal of
100% is output.
‘5 . 2 1’
(ENTER)
Voltmeter reading: 5.210
Enter the reading of the voltmeter
(5.210), and press ENTER (F4).
(ENTER)
Voltmeter reading: 5.000
Select Yes and press ENTER (F4).
(OK)
Press OK (F4).
F0233.EPS
2-15
IM 01C22T01-01E
Page 23
2. HART COMMUNICATOR OPERATION
(15) Burst Mode
The transmitter continuously sends the data stored in it
when the burst mode is set on. Either one of measured
pressure variable, % output value, or 4 to 20 mA
output value can be selected and sent. The data is sent
intermittently as a digital signal at 75 ms intervals
when the transmitter is set in the burst mode. Therefore, communication by the HART simultaneous
communicator is also possible.
Setting of Burst Mode
1. Device setup
4. Detailed setup
3. Output condition
4. HART output
3. Burst mode, 4. Burst option
EJA:
Burst option
********
PV
% range/current
Process vars/crnt
HELPDELESC ENTER
(ENTER)
Call up the Burst option, and set
the data to be sent.
•Pressure variable (PV)
•% output value (% range/current)
•4 to 20 mA output value (Process
vars/crnt)
EJA:
Burst mode
Off
On
Off
DELDELESC ENTER
HELP
(ENTER)
(SEND)
Call up the Burst mode and set to
On.
Then, Press SEND (F2).
F0234.EPS
To Release from the Burst Mode:
Call up the Burst mode display, and set to OFF.
(16) Multidrop Mode
“Multidropping” transmitters refers to the connection
of several transmitters to a single communications
transmission line. Up to 15 transmitters can be connected when set in the multidrop mode. To activate
multidrop communication, the transmitter address must
be changed to a number from 1 to 15. This change
deactivates the 4 to 20 mA analog output, sending it to
4 mA. The alarm current also is disabled.
Setting of Multidrop Mode
1. Device setup
4. Detailed Setup
3. Output condition
4. HART Output
1. Poll addr
EJA:
Poll addr
O
0
Call up the Poll addr and set the
polling address. (a number from 1 to
15)
And press SEND (F2) to send the
HELPDELESC ENTER
data.
Online
Utility
Auto Poll
HART Communicator
Auto Poll
No
No
Yes
HELP
DELDELESC ENTER
(ENTER)
Call up the Auto Poll and set to
Yes.
F0235.EPS
NOTE
1. When the address is set and the multi-drop
mode is set to “No” at the same time, Online
menus cannot be called up and displayed. Be
sure to turn the multidrop mode to “Yes” after
setting the address with “Poll addr.”
2. When the same polling address is set for two
or more transmitters in multidrop mode,
communication with these transmitters is
disabled.
2-16
IM 01C22T01-01E
Page 24
2. HART COMMUNICATOR OPERATION
Example: Communication when set in the multi-drop mode
HART Communicator
1 Offline
2 Online
3 Transfer
4 Frequency Device
5 Utility
HELPDELABORTOK
is connected to the transmitter,
the manufacturer’s x’ter type
code and the tag will be
displayed (display ).
1
(2) Select the desired transmitter.
After that, normal
communication to the selected
transmitter is possible. However,
the communication speed is
slow in this case (display ).
2
(3) To communicate with another
transmitter, turn off the power
once and then turn on it again,
or call up display , and select
3
Online.
(4) Display will appear. Select
1
the desired transmitter.
F0236.EPS
To Release the Multi-drop Mode:
Follow the procedure below.
1. Call up the Poll addr display, and set the address
to 0.
2. Call up the Auto Poll display, and set to No.
(17) External Switch Mode
• Enabling/inhibiting zero point adjustment using the
external zero-adjustment screw on the transmitter.
Follow the procedure below to enable or inhibit zero
point adjustment from the zero-adjustment screw on
the transmitter.
This is set to ENABLE when the instrument is
shipped.
(18) Software Write Protect
EJA configured data is saved by the write protect
function. Write protect status is set to YES when 8
alphanumerics are entered in the New password
field and transferred to the transmitter. In write protect
YES status, the transmitter does not accept parameter
changes. When the 8 alphanumeric string entered in the
New password field is also entered in the Enable
write field and transferred to the transmitter, it will be
possible to change transmitter parameters during a 10
minute period.
To change the transmitter from Write protect YES
status back to Write protect NO status, enter 8 spaces
in the New password field after Write protect has been
released using enable write.
(a) Setting Password
Example: Set the password to 1 2 3 4
EJA:
Hot key
1 keypad input
2 Enable Write
3 New password
HELPSENDESCENTER
EJA:
Enter New Password
********
********
HELPDEL ABORT ENTER
EJA:
Re-Enter New
Password
1234
1234
HELPDEL ABORT ENTER
Press Hot key.
Select the New password.
(ENTER)
Set 1 2 3 4 and press
ENTER (F4).
×4
(DEL)
(ENTER)
Press ENTER (F4).
Example: Inhibiting zero adjustment by the external zero-
adjustment screw
1. Device setup
4. Detailed setup
5. Device information
1. Field device info
7. Ext SW mode
EJA:
Ext SW mode
Enable
Enable
Inhibit
HELPSENDESC ENTER
(ENTER)
(SEND)
Select Inhibit and press ENTER (F4).
Press SEND (F2) to send the data.
F0237.EPS
2-17
EJA:
Set New Password OK
HELPDEL ABORTOK
EJA:
Method Aborted
HELPDEL ABORTOK
(OK)
Press OK (F4).
Write Protect status changes from
NO to YES.
(OK)
Press OK (F4).
F0238.EPS
IM 01C22T01-01E
Page 25
(b) Changing the Password
Example: To change the password from 1 2 3 4
EJA:
Input password
********
********
HELPDEL ABORT ENTER
EJA:
Write enable in 10
minutes
HELPDEL ABORTOK
EJA:
Method Aborted
HELPDEL ABORTOK
EJA:
Hot key
1 keypad input
2 Enable write
3 New password
HELPDELABPRTOK
EJA:
Enter New Password
********
********
HELPDEL ABORT ENTER
EJA:
Re-Enter New
Password
6789A
6789A
HELPDEL ABORT ENTER
to 6 7 8 9 A
1 2 3 4
(ENTER)
Press Hot key and call up Enable Write.
Enter the password and press
ENTER (F4).
(OK)
Press OK (F4).
Write protect status is released for
10 minutes.
(OK)
Press ENTER (F4).
Select the New password.
6 7 8 9 A
(ENTER)
Set 6 7 8 9 A .
(OK)
Press ENTER (F4).
2. HART COMMUNICATOR OPERATION
NOTE
1. Enable Wrt 10 min releases Write Protect
status for 10 minutes. While Write Protect
status is released, enter a new password in
the New Password field.
It will not be possible to set a new password
when 10 minutes have elapsed.
2. To release Write Protect status completely,
enter 8 spaces in the New Password field
according to the instructions given in (b),
Changing the Password. This causes Write
Protect status to change from YES to NO.
EJA:
Enter New Password
********
********
HELP DEL ABORT ENTER
EJA:
Re-Enter New
Password
1
HELPDEL ABORT ENTER
(ENTER)
(ENTER)
*"Joker password" and "Software Seal"
When you lose the password that has been registered, it is
possible to release the mode for 10 minutes by using a
joker password. Enter "YOKOGAWA" to release Write
protect status for 10 minutes. If this joker password is
used, the status shown in the parameter "Software seal" is
changed from "Keep" to "Break." Press Hot key and select
"2. Wrt Protect menu." Current status is shown in "4.
Software seal." This status will be returned from "Break" to
"Keep" by registering a new password.
8
F0240.EPS
EJA:
Set New Password OK
HELPDEL ABORTOK
EJA:
Method Aborted
HELPDEL ABORTOK
(OK)
(OK)
Press OK (F4).
F0239.EPS
2-18
IM 01C22T01-01E
Page 26
2. HART COMMUNICATOR OPERATION
(19) Hardware Write Protect and Burnout
Direction(with Optional code /F1)
This function prohibits parameter changes through a
slide switch on a CPU assembly board. In the case the
hardware write protection switch is set to YES, none of
the communication method including the handheld
terminal such as model 275 is allowed for the alteration of parameters. The write protection switch is
factory set to NO(N position in the figure below).
CPU assembly
Slide switch
Burnout direction switch
LH
YN
Write protection switch
Hardware write protection switch
Write Protection
Switch Position
Write Protection
LH
YN
LH
YN
YESNO
Burnout direction switch
Burnout Direction
Switch Position
Burnout Direction
LH
YN
HIGHLOW
LH
YN
F02F1.EPS
(20) H2O Unit Select
When mmH2O, inH2O or ftH2O is set, the pressure
varies with the standard temperature definition. The
Yokogawa default setting for the standard temperature
is 4°C (39.2°F). Use the procedure described below
when a standard temperature of 20°C (68°F) is required.
Call up the H2O Unit select.
1. Device setup
4. Detailed setup
2. Signal condition
9. H2O Unit select
EJA:
H2O Unit select
@4C
@4C
@20C(68F)
2.4 Self-Diagnostics
2.4.1 Checking for Problems
(1) Identify Problems with HART Communica-
tor
Self-diagnostics of the transmitter and check of
incorrect data setting can be carried out with the
HART communicator. There are two methods for selfdiagnosis of the transmitter, self-diagnosis for every
transmission and manually executing the SELF TEST
command. When an error message appears, follow
“ERROR MESSAGES”.
Diagnostic by “self test”
1. Device setup
2. Diag/Service
1. Test/Status
1
EJA:
Test/status
1 Self test
2 Status
HELPSETHOMEOK
2
EJA:
Self test OK
DELSET ABORTOK
1
EJA:
Test/status
1 Self test
2 Status
HELPSETHOMEOK
2
EJA:
Status
Field device not
installed
OFF
DELPREV NEXT EXIT
Call up the Test/Status, and select
Self test.
If there is no error detected, Self
test OK will be displayed.
When an error occurs, an error
message appears, and the results
of self-diagnosis appear in the
Status item.
Call up the Status item.
(NEXT)
If there is no error, the result of
diagnostics is indicated as OFF. If
ON is indicated, a countermeasure
for that error is necessary.
F0242.EPS
HELPSENDESC ENTER
(ENTER)
(SEND)
Select @20C (68F) and press
ENTER (F4).
Press SEND (F2) to send data.
F0241.EPS
2-19
IM 01C22T01-01E
Page 27
2. HART COMMUNICATOR OPERATION
• Error Messages — HART Communicator
Error MessageProbable CauseCountermeasure
Pressure sensor
error
Temp (Cap) sensor
error
EEPROM (Cap)
failure
Sensor board not
initialized
Temp (Amp) sensor
error
EEPROM (Amp)
failure
Dev id not entered
CPU board not
initialized
Invalid Selection
Parameter Too High
Parameter Too Low
Incorrect Byte Count
In Write Protect
Mode
Set to Nearest
Possible Value
Lower Range Value
too High
Lower Range Value
too Low
Upper Range Value
too High
Upper Range Value
too Low
Span too Small
Applied Process
Value too High
Applied process
Value too Low
New LRV pushed
URV Over Sensor
Limit
Excess Correction
Attempted
In Proper Current
Mode
In Multidrop Mode
Capsule problem
Amplifier problem
Set value is too high.
Set value is too low.
Operation is set in the
Write Protect mode.
Value is set to a
nearest possible value.
LRV set point is too
high.
LRV set point is too
low.
URV set point is too
high.
URV set point is too
low.
Set span is too small.
Applied pressure is
too high.
Applied pressure is
too low.
The shift of URV
according to the new
LRV setting exceeds
USL.
Amount of correction
is too much.
The fixed current
mode is desired but
not set in that mode.
Operation is set in
the multi-drop mode.
Replace capsule.
Replace
amplifier.
Change the
setting.
—
—
—
Change the
range.
Adjust the
applied pressure.
Change the
setting within the
range of USL.
Adjust the amount
of correction.
Set in the fixed
current mode.
—
(2) Checking with Integral Indicator
If an error is detected in the self-diagnostic, an error
number is displayed on the integral indicator. If there is
more than one error, the error number changes at twosecond intervals.
See Table 2.4.1 regarding the error numbers.
F0243.EPS
Figure 2.4.1 Identifying Problems Using the Integral
Display mode
Display fnctn
Engr unit
Engr disp LRV
Engr disp URV
Engr disp point
Poll addr
Auto poll
Burst option
Burst mode
Pres
% rnge
A01 out
Snsr temp
Static pres
Engr display
Loop test
Self test
Status
A01 Alarm typ
Write Protect
Enable Write
New password
Ext SW mode
Software seal
Zero trim
Lower sensor trim
Upper sensor trim
D/A trim
Scaled D/A trim
Tag number
Descriptor
Message
Date
Unit
Lower range value
Lower range value
Apply values
Damping time constant
Transfer function
Low cut
Cut mode
Bi-directional mode
H2O Unit select
Sensor temperature unit
Static pressure unit
Display mode
Display fnctn
Engineering unit
Engineering display LRV
Engineering display URV
Engineering display decimal point
Polling address
Auto poll
Burst mode option
Burst mode
Pressure variable
% output variable
4 to 20 mA output variable
Sensor temperature
Static pressure
Output (in Engr unit)
Test output % setting
Self test
Status
Status of analog output alarm
Write Protect
Enable Write
New password
Ext SW mode
Software seal
Zero trim
Lower sensor trim
Upper sensor trim
Digital/Analog output trim
Scaled D/A trim
Tag number, Up to 8 characters
Up to 16 characters
Up to 32 characters
xx/yy/zz
O, inHg, ftH2O, mmH2O, mmHg, psi, bar, mbar, g/cm2,
inH
2
2
, Pa, kPa, MPa, torr, atm
kg/cm
Set the calibration range by the keypad
Range for 4 to 20 mA DC signal is set with actual input applied.
O, inHg, ftH2O, mmH2O, mmHg, psi, bar, mbar, g/cm2,
inH
2
2
, Pa, kPa, torr, atm
kg/cm
Normal % , User set , User set & % , Inp pres , Pres & %
linear/Square root
Up to 8 characters
–19999 to 19999
–19999 to 19999
0, 1, 2, 3
1 to 15
No/Yes
Pres , % rnge , A01 out
ON/OFF
–5.0% to 110.0%
–3.2 mA to 21.6 mA
–19999 to 19999
–5.0% to 110.0%
Check using the self-test command.
Display of the result of self-test, calibration of transmitter.
High/Low
Yes/No
8 characters
8 characters
Enable/Inhibit
Keep/Break
Set the current input value to 0 kPa.
Adjust only measured pressure variable.
Adjust the output value at the points of 4 mA and 20 mA.
3. PARAMETER LISTS
T0301.EPS
3-1
IM 01C22T01-01E
Page 30
ItemUHIDescriptionRemarks
Sensor
information
Isoltr matl
Fill fluid
Gasket matl
Flange matl
Drain vent matl
Flange type
RS isoltr matl
Flange size
Num remote seal
RS fill fluid
Isolator material
Fill fluid
gasket material
Flange material
Drain vent material
Flange type
Remote seal isolator material
Flange size
Number of remote seal
Remote seal fill fluid
Hast-C, Tantalum, 316L, Unknown, Special
Silicone oil, F oil, Unknown, Special
PTFE, 316L, Unknown, Special
Carbon Steel, Hast-C, 316L, Unknown, Special
316SST, Hast-C, 316L, None, Unknown, Special
Conventional, Remote seal, Level, Unknown, Special
316 SST, Hast-C, Monel, Tantalum, 316L, Unknown, Special
ANSI 150, ANSI 300, ANSI 600, None, Unknown, Special
One seal, Two seal, None, Unknown
Silicone oil, SH704, SH705, Ethy Gly/H
None, Unknown, Special
Wafer, Nozzle, HTV-W, HTV-N, None, Unknown, Special
YOKOGAWA
EJA
Additional
information
RS type
Distributor
Dev type
Dev ID
Final asmbly num
Universal rev
Fld dev rev
Software rev
Model
Style
LSL
USL
MIN SPAN
Manufacturer
Lo snsr trim pt
Up snsr trim pt
Serial No.
Remote seal type
Distributor
Device type
Device ID
Final assembly number
Universal revision
Fld dev revision
Software revision
Model
Style
Lower range limit
Upper range limit
Minimum span
Manufacturer
Lower snsr trim pt
Upper snsr trim pt
Serial Number
3. PARAMETER LISTS
O, Prop Gly/H2O,
2
T0302.EPS
3-2
IM 01C22T01-01E
Page 31
REVISION RECORD
Title: Model EJA Series HART Protocol
Manual No.: IM 01C22T01-01E