YOKOGAWA AR-LP User's Manual

User’s Manual
IM AR05-01E
Model AR-LP Arrester for two-wire system pulse signal (50V DC or less)
Scott
Please read through this Manual before using the arresters for correct handling. Please keep this Manual carefully after use.
1st Edition Feb. 1997(MC)
3rd Edition Sep. 2001(MC)
1.
Cautionary Notes for Safe Use of the Product
IM AR05-01E
For the correct use of this product,read through this manual before use.The following safety symbol is indicated on the product to ensure safe use.
If this symbol is indicated on the product, the operator should refer to the explanation given in the instruction manual in order to avoid personnel injury or death to either themselves or other personnel, and/or damage to the in­strument. The manual describes the special care the opera­tor should exercise to avoid shock or other dangers that may result in injury or loss of life. The following symbol marks are used only in this manual.
Musashino Center Bldg. 1-19-18, Naka-cho Musashino-shi, Tokyo 180-0006 Japan Phone: +81-422-55-8755 Facsimile: +81-422-55-8954
FRK-16 (Panel)
19
24.5
89
99
73
2.2 External Dimensions
23.5
483
465
36-M4 8-ø5.510
441.6
55
28.5
26.5
Unit : mm
(8.5) (3.8)
Oval hole
50
24.7
76.2
16.5
IMPORTANT
Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure.
NOTE
Draws attention to information that is essential for understanding the operations and/or features of the product.
2. Mounting and Wiring
WARNING
Wiring should be done after ensuring the break of each cable.
2.1 Mounting
Mount the arrester referring the figure below.
24
90
Panel
M4 screw
100
90
Main body
Terminal base
2.3 Terminal Arrangement
A
B
C
Use
Protect side terminal B – C
3
Surge side 1
1
2
terminal 2 – 3
Terminal
A
2.4 Wiring
IMPORTANT
Use of arresters ignoring the specifications may cause electric shock, overheating or damage. (a) Input signal value applied to the arrester should
meet the required specifications.
(b) The external wiring to the terminals and wiring to
ground are as specifications.
High voltage is applied on the terminals of arresters for pulse signal during power on, as shown in the figure below. Do not touch the terminals.
AR8 DIN rail adapter
No.
104
AR-LP
CAUTION FOR HIGH VOLTAGE
50V DC
Flexible twisted wire and durable round crimp-on terminal (JIS C2805) are recommended to use.
(1) Signal cable Nominal cross-sectional area of conductor: 0.5 to 0.75 mm2. Example of suitable cable: Vinyl code (VJF) (JIS C3306) for electronic instrument. (2) Grounding cables Nominal cross-sectional area of conductor:
2.0 mm2 or more for grounding. Example of suitable cable: 600V vinyl insulated cable (IV) (JIS C3307), Vinyl insulated cable (KIV) (JIS C3316) for electronic instrument
4. Environmental Conditions
Ambient temperature: 0 to 50°C Relative humidity: 5 to 90%RH (No condensation) Altitude at installation site: Max.2000m above sea level Installation category based on EN61010-1: II (see Note.)
NOTE
The Installation Category implies the regulation for impulse withstand voltage.It is also called the “Overvoltage category”.“ II applies to electrical equipment.Pollution level describes the degree to which a solid,liquid or gas which deteriorates dielectric strength is adhering.“2” applies to a normal indoor atmosphere.
5. Maintenance
5.1 Arrester main body replacement
The arrester main body and terminal base are connected by plug-in. Circuit between surge side and protect side would not be open even if the main body is removed from the socket on terminal base by loosing mounting screw. So the arrester main body can easily be replaced with new one.
2.5 Grounding
Interconnect the ground terminals of the arrester and the instrument to be protected. Touch ground from the arreter side as shown in the figure below. Install the arrester and instrument as close as possible, and make the cable as short as possible. The wires for interconnect ground­ing should have lower effective resistance than ground resistance. Ground resistance should be 100 or less. (JIS Class 3 grounding)
NOTE
Wire tightening torque for arrester should not be 1.2 Nm or more.
(1) Interconnect Grounding
Arrester
Instrument
(2) Interconnect Grounding (when using shield line)
Arrester
Grounding for serial installation of arresters is to connect ground terminal board in zigzag and touch ground at one point from last arrester according to JIS Class 3 grounding. Grounding wire should be 2.0 mm
Instrument
2
or more.
NOTE
When replacing the arrester main body, make sure that the model and suffix codes indicated on the labels of the main body and terminal base are the same.
When replacing the arrester main body having specifications of surge discharge withstand current rating of 5000A, make sure that the style code indicated on the label of terminal base is “S2.0”. If mounted to the terminal base of style code “S1.0”, the specifications of the arrester main body can not be satisfied, because the surge discharge withstand current rating will be for 1000A specifications. To operate the arrester for 5000A specifications, the replacement of terminal base is also required.
5.2 Arrester checking
To check the arrester performance, remove main body from the socket and check it by using the checker (option). Replace the main body if re­quired.
5.3 Arrester check period
To protect the instrument from damage by induced lightning, the arrester should be checked periodically at least once a year. In areas where lightning occurs frequently, check should be done more often particularly after thunderstorms.
6. Hardware Specification
Permissible current leakage Instrument side voltage limit
Ground terminal board
3.
Connection of Arresters with Instruments to be Protected
Pulse generator
JIS Class 3 grounding
AR-LP AR-LP
Lightning surge
1
A
B
2
Ground terminal Ground terminal
Ground Ground
1
A
2
B
Pulse signal
transmitter
GND
(at 10 kV, 1.2/50 s) Suge discharge withstand capacity
(at 8/20 ␮s) Discharge starting voltage
Safety standards
- 2 -
Between lines Between ground Between lines Between ground Between lines Between ground Between lines Between ground
Conforms to EN61010-1 Installation Category II
10 ␮A or less (at 50 V DC) 10 ␮A or less (at 50 V DC) 90 V or less 250 V or less 1000 A 5000 A 74 V or more 74 V or more
IM AR05-01E 3rd Edition Sep.5 2001-00
Loading...