To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system,
or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording,
or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed
with respect to the use of the information contained herein. Moreover, because Yaskawa is
constantly striving to improve its high-quality products, the information contained in this
manual is subject to change without notice. Every precaution has been taken in the preparation
of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained
in this publication.
株式会社 安川電機
YASKAWA ELECTRIC CORPORATION
1 Introduction
This safety precautions manual covers Σ-III series SERVOPACK controlling Σ-III series AC
servomotor. To properly use the Σ-III series SERVOPACK, read this safety precautions manual
and user’s manual (see the following table) thoroughly, and retain for easy reference for inspections and maintenance, and so on. Make sure that these manuals reach the end user.
2 Reference Manuals
This table lists related reference manuals:
Σ-III Series SGMS/SGDS User’s ManualSIEPS80000000
Σ-III Series SGMS/SGDS Digital Operator INSTRUCTIONSTOBPS80000001
Σ-III Series SGMS/SGDS User’s Manual
For DeviceNet communications
Σ-III Series SGMS/SGDS User’s Manual
For MECHATROLINK-II communications
Linear Σ Series SGL/SGDS User’s ManualSIEPS80000016
3 General Precautions
The following describes general precautions. Note the following to ensure safe application.
• The drawings presented in this manual are sometimes shown without covers or protec-
tive guards. Always replace the cover or protective guard as specified first, and then
operate the products in accordance with the manual.
• The drawings presented in this manual are typical examples and may not match the
product you received.
• This manual is subject to change due to product improvement, specification modifica-
tion, and manual improvement. When this manual is revised, the manual code is
updated and the new manual is published as a next edition. The edition number appears
on the front and back covers.
• If the manual must be ordered due to loss or damage, inform your nearest Yaskawa rep-
resentative or one of the offices listed on the back of this manual.
• Yaskawa will not take responsibility for the results of unauthorized modifications of this
product. Yaskawa shall not be liable for any damages or troubles resulting from unau-
thorized modification.
1 Introduction
Manual TitlesManual No.
SIEPS80000002
SIEPS80000011
E-1
4 Safety Information
WARNING
CAUTION
PROHIBITED
MANDATORY
The following conventions are used to indicate precautions in this manual. Failure to heed pre-
cautions provided in this manual can result in serious or possibly even fatal injury or damage to
the products or to related equipment and systems.
Indicates precautions that, if not heeded, could possibly result in loss of life or serious
injury.
Indicates precautions that, if not heeded, could result in relatively serious or minor injury,
damage to the product, or faulty operation.
In some situations, the precautions indicated could have series consequences if not heeded.
Indicates prohibited actions that must not be performed. For example, this symbol would
be used to indicate that fire is prohibited as follows: .
Indicates compulsory actions that must be performed. For example, this symbol
would be used as follows to indicate that grounding is compulsory: .
E-2
5 Notes for Safe Operation
WARNING
Read this manual thoroughly before checking products on delivery, storage and transportation,
installation, wiring, operation and inspection, and disposal of the AC servo drives.
• Never touch any rotating motor parts while the motor is running.
Failure to observe this warning may result in injury.
• Before starting operation with a machine connected, make sure that an emergency stop can be
applied at any time.
Failure to observe this warning may result in injury.
• Never touch the inside of the SERVOPACKs.
Failure to observe this warning may result in electric shock.
• Do not remove the panel cover while the power is ON.
Failure to observe this warning may result in electric shock.
• Do not touch terminals for five minutes after the power is turned OFF.
Residual voltage may cause electric shock.
• Do not touch terminals for five minutes after voltage resistance test.
Residual voltage may cause electric shock.
• Follow the procedures and instructions for trial operation precisely as noted in the Σ-ΙΙΙ series User’s
Manual (Manual No.: SIEPS80000000A).
• Follow the procedures and instructions for the trial operation as noted in the applicable manual for
that product.
Malfunctions that occur after the servomotor is connected to the equipment not only damage the equipment,
but may also cause an accident resulting in death or injury.
• The output range of multi-turn data for Σ-ΙΙΙ series absolute detection system differs from that for con-
ventional systems (15-bit encoder and 12-bit encoder). Especially when “Infinite length positioning
system” of conventional type is to be configured with Σ-ΙΙΙ series, be sure to make the system modi-
fication.
• The multi-turn limit value must be changed only for special applications.
Changing it inappropriately or unintentionally can be dangerous.
• If the Multi-turn Limit Disagreement alarm occurs, check the setting of parameter Pn205 in the SER-
VOPACK to be sure that it is correct.
If Fn013 is executed when an incorrect value is set in Pn205, an incorrect value will be set in the encoder. The
alarm will disappear even if an incorrect value is set, but incorrect positions will be detected, resulting in a dangerous situation where the machine will move to unexpected positions.
5 Notes for Safe Operation
E-3
• Do not remove the front cover, cables, connectors, or optional items while the power is ON.
WARNING
CAUTION
Failure to observe this warning may result in electric shock.
• Do not damage, press, exert excessive force or place heavy objects on the cables.
Failure to observe this warning may result in electric shock, stopping operation of the product, or burning.
• Do not modify the product.
Failure to observe this warning may result in injury or damage to the product.
• Provide an appropriate stopping device on the machine side to ensure safety. A holding brake for a
servomotor with brake is not a stopping device for ensuring safety.
Failure to observe this warning may result in injury.
• Do not come close to the machine immediately after resetting momentary power loss to avoid an
unexpected restart. Take appropriate measures to ensure safety against an unexpected restart.
Failure to observe this warning may result in injury.
• Connect the ground terminal to electrical codes (ground resistance: 100 Ω or less).
Improper grounding may result in electric shock or fire.
• Installation, disassembly, or repair must be performed only by authorized personnel.
Failure to observe this warning may result in electric shock or injury.
Checking on Delivery
• Always use the servomotor and SERVOPACK in one of the specified combinations.
Failure to observe this caution so may result in fire or malfunction.
E-4
5 Notes for Safe Operation
CAUTION
CAUTION
Storage and Transportation
• Do not store or install the product in the following places.
• Locations subject to direct sunlight.
• Locations subject to temperatures outside the range specified in the storage/installation temperature conditions.
• Locations subject to humidity outside the range specified in the storage/installation humidity conditions.
• Locations subject to condensation as the result of extreme changes in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust, salts, or iron dust.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
Failure to observe this caution may result in fire, electric shock, or damage to the product.
• Do not hold the product by the cables or motor shaft while transporting it.
Failure to observe this caution may result in injury or malfunction.
• Do not place any load exceeding the limit specified on the packing box.
Failure to observe this caution may result in injury or malfunction.
• If disinfectants or insecticides must be used to treat packing materials such as wooden frames, pallets, or
plywood, the packing materials must be treated before the product is packaged, and methods other than
fumigation must be used.
Example: Heat treatment, where materials are kiln-dried to a core temperature of 56°C for 30
minutes or more.
If the electronic products, which include stand-alone products and products installed in machines, are packed with
fumigated wooden materials, the electrical components may be greatly damaged by the gases or fumes resulting from
the fumigation process. In particular, disinfectants containing halogen, which includes chlorine, fluorine, bromine, or
iodine can contribute to the erosion of the capacitors.
Installation
• Never use the products in an environment subject to water, corrosive gases, inflammable gases, or com-
bustibles.
Failure to observe this caution may result in electric shock or fire.
• Do not step on or place a heavy object on the product.
Failure to observe this caution may result in injury.
• Do not cover the inlet or outlet ports and prevent any foreign objects from entering the product.
Failure to observe this caution may cause internal elements to deteriorate resulting in malfunction or fire.
• Be sure to install the product in the correct direction.
Failure to observe this caution may result in malfunction.
• Provide the specified clearances between the SERVOPACK and the control panel or with other devices.
Failure to observe this caution may result in fire or malfunction.
• Do not apply any strong impact.
Failure to observe this caution may result in malfunction.
E-5
Wiring
CAUTION
• Do not connect a three-phase power supply to the U, V, or W output terminals.
Failure to observe this caution may result in injury or fire.
• Securely connect the power supply terminal screws and motor output terminal screws.
Failure to observe this caution may result in fire.
• Do not bundle or run power and signal lines together in the same duct. Keep power and signal lines sepa-
rated by at least 30 cm (11.81 in).
• Use twisted-pair shielded wires or multi-core twisted pair shielded wires for signal and encoder (PG) feed-
back lines.
The maximum length is 3 m (118.11 in) for reference input lines and is 20 m (787.40 in) for PG feedback lines.
• Do not touch the power terminals for 5 minutes after turning power OFF because high voltage may still
remain in the SERVOPACK.
Make sure the charge indicator is out first before starting an inspection.
• Avoid frequently turning power ON and OFF. Do not turn power ON or OFF more than once per minute.
Since the SERVOPACK has a capacitor in the power supply, a high charging current flows for 0.2 seconds when
power is turned ON. Frequently turning power ON and OFF causes main power devices like capacitors and fuses to
deteriorate, resulting in unexpected problems.
• Observe the following precautions when wiring main circuit terminal blocks.
• Remove the terminal block from the SERVOPACK prior to wiring.
• Insert only one wire per terminal on the terminal block.
• Make sure that the core wire is not electrically shorted to adjacent core wires.
• Do not connect the SERVOPACK for 100 V and 200 V directly to a voltage of 400 V.
The SERVOPACK will be destroyed.
• Install the battery at either the host controller or the battery unit of the encoder.
It is dangerous to install batteries at both simultane ously, because that sets up a loop circuit between the batteries.
• Be sure to wire correctly and securely.
Failure to observe this caution may result in motor overrun, injury, or malfunction.
• Always use the specified power supply voltage.
An incorrect voltage may result in burning.
• Take appropriate measures to ensure that the input power supply is supplied within the specified voltage
fluctuation range. Be particularly careful in places where the power supply is unstable.
An incorrect power supply may result in damage to the product.
• Install external breakers or other safety devices against short-circuiting in external wiring.
Failure to observe this caution may result in fire.
E-6
5 Notes for Safe Operation
CAUTION
CAUTION
• Take appropriate and sufficient countermeasures for each when installing systems in the following loca-
tions.
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields and magnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
Failure to observe this caution may result in damage to the product.
• Do not reverse the polarity of the battery when connecting it.
Failure to observe this caution may damage the battery or cause it to explode.
Operation
• Conduct trial operation on the servomotor alone with the motor shaft disconnected from machine to avoid
any unexpected accidents.
Failure to observe this caution may result in injury.
• Before starting operation with a machine connected, change the settings to match the parameters of the
machine.
Starting operation without matching the proper settings may cause the machine to run out of control or malfunction.
• Forward run prohibited (P-OT) and reverse run prohibited (N-OT) signals are not effective during JOG
mode operation using parameter Fn002 and zero point search mode using parameter Fn003.
• When using the servomotor for a vertical axis, install the safety devices to prevent workpieces to fall off due
to occurrence of alarm or overtravel. Set the servomotor so that it will stop in the zero clamp state at occur-
rence of overtravel.
Failure to observe this caution may cause workpieces to fall off due to overtravel.
• When not using the normal autotuning, set to the correct moment of inertia ratio.
Setting to an incorrect moment of inertia ratio may cause vibration.
• Do not touch the SERVOPACK heatsinks, regenerative resistor, or servomotor while power is ON or soon
after the power is turned OFF.
Failure to observe this caution may result in burns due to high temperatures.
• Do not make any extreme adjustments or setting changes of parameters.
Failure to observe this caution may result in injury due to unstable operation.
• When an alarm occurs, remove the cause, reset the alarm after confirming safety, and then resume opera-
tion.
Failure to observe this caution may result in injury.
• Do not use the servo brake of the servomotor for ordinary braking.
Failure to observe this caution may result in malfunction.
E-7
Maintenance and Inspection
CAUTION
CAUTION
• Do not disassemble the SERVOPACK.
Failure to observe this caution may result in electric shock or injury.
• Do not attempt to change wiring while the power is ON.
Failure to observe this caution may result in electric shock or injury.
• When replacing the SERVOPACK, resume operation only after transferring the previous SERVOPACK
parameters to the new SERVOPACK.
Failure to observe this caution may result in damage to the product.
Disposal
• When disposing of the products, treat them as ordinary industrial waste.
E-8
6 Checking Products on Delivery
Disconnect all power and wait 5 min.
before servicing. May cause electric shock.
Use proper grounding techniques.
CAUTION
WARNING
5
Do not touch heat sink when power is ON.
May cause burn.
SERVOPACK warning label
SERVOPACK type
SERVOPACK nameplate
Serial number
Applicable
power supply
Applicable
servomotor capacity
SGDS-02A01A
AC-OUTPUT
S/N
O/N
AC-INPUT
SERVOPACK
MODEL
YASKAWA ELECTRIC
MADE IN JAPAN
The following procedure is used to check Σ-ΙΙΙ Series products upon delivery. Check the follow-
ing items when Σ-ΙΙΙ Series products are delivered.
Check ItemsComments
Are the delivered products the ones that
were ordered?
Is there any damage?
Are there any loose screws?Check screws for looseness using a screwdriver.
If any of the above items are faulty or incorrect, contact your Yaskawa sales representative or
the dealer from whom you purchased the products.
7 Warning Label
The following illustration shows the SERVOPACK warning label.
6 Checking Products on Delivery
Check the model numbers marked on the nameplates of
the SERVOPACK.
Check the overall appearance, and check for damage or
scratches that may have occurred during shipping.
8 Nameplate
The following illustration shows the SERVOPACK nameplate
E-9
.
9 Installation
Cooling fan
Cooling fan
30 mm (1.2 in.) or more
10 mm (0.4 in.) or more
50 mm (2 in.) or more
50 mm (2 in.) or more
Observe the following precautions when installing SERVOPACK.
• Install SERVOPACK perpendicular to the wall so that the front panel (digital operator
mounted face) faces outward.
• Firmly secure the SERVOPACK through two or three mounting holes depending on the
SERVOPACK capacity.
• Install SERVOPACK so that SERVOPACK can be cooled by natural convection or fan.
Installation Sites
For installation sites, use proper care with the following notes.
SituationNotes on Installation
• Design the control panel size, unit layout, and cooling
method so that the temperature around the periphery of the
When installed in a control panel
When installed near a heating unit
When installed near a source of
vibration
When installed in a place receiving
corrosive gases
Others
SERVOPACK does not exceed 55°C.
• When installing multiple SERVOPACKs side by side in a
control panel, install cooling fans and provide sufficient
space around each SERVOPACK to allow cooling by fan
and natural convection.
Suppress radiation heat from the heating unit and a temperature rise caused by convection so that the temperature around
the periphery of the SERVOPACK does not exceed 55
Install a vibration isolator underneath the SERVOPACK to
prevent it from receiving vibration.
Corrosive gases do not immediately affect the SERVOPACK
but will eventually cause contactor-related devices to malfunction. Take appropriate action to protect against corrosive gases.
• Avoid installation in a hot and humid place or where excessive dust or iron powder is present in the air.
• Be sure there is no condensation or freezing.
• Keep the surrounding air temperature 45 °C or less to ensure
long-term reliability.
°C.
E-10
10 Wiring
10.1 Molded-case Circuit Breaker and Fuse Capacity
10 Wiring
Main Circuit
Power Supply
Single-phase
100 V
Single-phase
200 V
Three-phase
200 V
* 1. Nominal value at the rated load. The specified derating is required to select an appropriate
* 2. Cutoff characteristics (25
Note: 1. Do not use a fast-acting fuse. Because the SERVOPACK’s power supply is a capacitor
SERVOPACK Model
Capacity
fuse capacity.
(kW)
0.03A3B0.25
0.05A5F0.25
0.1001F0.40
0.2002F0.606
0.4004F1.212
0.05A5A0.25
0.2002A0.75
0.4004A1.28
0.8008A2.216
0.4505A1.44
SGDS
1.010A2.37
1.515A3.210
2.020A4.313
3.030A5.917
5.050A7.528
6.060A12.532
7.575A15.541
°C): 200% two seconds min. and 700% 0.01 seconds min.
input type, a fast-acting fuse may blow when the power is turned ON.
2. The SGDS SERVOPACK does not include a protective grounding circuit. Install a
ground-fault protector to protect the system against overload and short-circuit or protective grounding combined with the molded-case circuit breaker.
-
Power Supply
Capacity per
SERVOPACK
(kVA)
Current Capacity of the
Molded-case Circuit Breaker
and the Fuse
(A
)
rms
4
40.1001A0.40
∗1,∗
Rated Voltage
2
Fuse MCCB
250 V 240 V
10.2 Main Circuit Wiring
SGDS SERVOPACKs are suitable under the following conditions.
• With 100 V class: Less than 5000 Arms,120 V maximum.
• With 200 V class: Less than 5000 Arms, 240 V maximum.
SERVOPACKs must be used with UL-listed fuses or circuit breakers, in accordance with the
National Electrical Code (NEC).
Use 75 °C heat-resistant copper wires or an equivalent.
E-11
10.3 SERVOPACK Main Circuit Wire Size
Cable Types
Cable Types
SymbolName
PVCNormal vinyl cable
IV600-V vinyl cable
HIV
Temperature-resistant
vinyl cable
Allowable Conductor
Temperature °C (°F)
−
60 (140)
75 (167)
• Wire sizes are selected for three cables per bundle at 40 °C (104 °F) surrounding air
temperature with the rated current.
• Use cable with a minimum withstand voltage of 600 V for main circuits.
• If cables are bundled in PVC or metal ducts, consider the reduction ratio of the allow-
able current.
• Use heat-resistant cables under high surrounding air or panel temperatures where
normal vinyl cables will rapidly deteriorate.
• Use cables within the allowable moment of inertia.
• Do not use cables under continuous regenerative state.
The following table shows the wire size and allowable current for three cables. Use a cable
whose specifications meet or are less than the values in the table.
• 600-V Heat-resistant Vinyl Cables (HIV)
Allowable Current at Surrounding Air
(86°F)
30°C
Temperature A
40°C
(104°F)
AWG Size
20
−
18
16
14
12
10
88.0 (0.0124)
6
4
Nominal
Section
Diameter
mm
(0.00078)
(0.00116)
(0.00140)
(0.00193)
(0.00310)
(0.00543)
(0.00853)
(0.0217)
(0.0341)
Note: The values in the table are only for reference.
Cross
2
(in2)
0.5
0.75
0.9
1.25
2.0
3.5
5.5
14.0
22.0
Configuration
Number of
wires/mm
2
)
(in
19/0.18
(0.00028)
30/0.18
(0.00028)
37/0.18
(0.00028)
50/0.18
(0.00028)
7/0.6
(0.00093)
7/0.8
(0.00124)
7/1.0
(0.00155)
7/1.2
(0.00186)
7/1.6
(0.00248)
7/2.0
(0.00310)
E-12
Conductive
Resistance
2
Ω/km
39.56.65.64.5
26.08.87.05.5
24.49.07.76.0
15.612.011.08.5
9.53232016
5.41332924
3.47433831
2.41554940
1.35797057
0.85918166
50°C
(122°F)
10 Wiring
Main Circuit Power Supply Input Terminals (L1, L2, L3), Servomotor
Connection Terminals (U, V, W), Control Power Input Terminals (L1C,
L2C), External Regenerative Resistor Terminals (B1, B2)
Units: mm
Main
Circuit
Power
Supply
Single-
phase
100 V
Single-
phase
200 V
Threephase
200 V
Capacity
(kW)
0.03A3B
0.05A5F
0.101F
0.202FHIV2.0
0.05A5A
0.101A
0.202A
0.404A
0.7508A
0.4505A
1.515A
2.020A
3.030AHIV5.5HIV3.5
5.050AHIV5.5HIV8.0HIV5.5
6.060AHIV8.0
7.575AHIV14
SERVO-
PACK Model
SGDS-L1, L2, L3U, V, WL1C, L2CB1, B2
HIV1.25
HIV1.25
HIV2.0
HIV2.0HIV2.0
HIV3.5
Terminal Symbol
HIV1.25HIV1.25HIV1.25
HIV1.25HIV1.25HIV1.25
HIV3.5HIV2.0
HIV14HIV8.0
HIV1.25
HIV1.251.010A
2
Note: The wires for 0.03 kW to 1.5 kW SERVOPACKs need connectors for
wiring. The wires for 2.0 kW to 7.5 kW SERVOPACKs do not need
connectors for wiring.
E-13
Ground Terminal
Main
Circuit
Power
Supply
Single-
phase
100 V
SERVOPACK
Capacity
(kW)
0.05A5F
0.202F
Model
SGDS-
Wire Size
2
(mm
HIV2.0 or
more
Ground Terminal
Te rm i na l
Screw
)
Size
M41.2 to 1.40.101F
Tightening
Torque
(N
m)
0.05A5A
Single-
phase
200 V
0.101A
0.202A
0.404A
HIV2.0 or
more
M41.2 to 1.4
0.7508A
0.4505A
1.010A
Three-
phase
200 V
1.515A
2.020A
3.030A
5.050A
6.060A
7.575A
HIV2.0 or
more
M41.2 to 1.4
M62.5 to 3.8
Signal Line Wire Sizes
Following table shows appropriate cables for CN1 and CN2 SERVOPACK connectors.
Wire sizes were selected for three cables per bundle at 40
with the rated current.
Connector Name and
Signal
Control I/O
Signal
Connector
PG Signal
Connector
CN1
CN2
ItemSpecification
CableUse twisted-pair or shielded twisted-pair wire.
Applicable wire
Finished cable
dimension
CableUse Yaskawa cable, or shielded twisted-pair
Applicable wire
Finished cable
dimension
°C surrounding air temperature
AWG24 (0.2 mm
2
), AWG26 (0.12 mm2),
AWG28 (0.08 mm2), AWG30 (0.05 mm2)
φ16.0 mm (φ0.63 in) MAX.
wire if Yaskawa cable is not used.
AWG24 (0.2 mm
AWG28 (0.08 mm
Use AWG22 (0.33 mm
supply and AWG26 (0.12 mm
nals. These conditions permit wiring distances
up to 20 m (65.6 ft).
SGDS-15A1A to -50A1A: Three-phase 200 VAC, 1.5 kW to 5.0 kW
SymbolCable NameSpecification
Serial communication cableShield cable
c
Servomotor cableShield cable
d
Encoder cableShield cable
e
AC Line cableShield cable
f
E-27
SGDS-60A1A to -75A1A: Three-phase 200 VAC, 6.0 kW to 7.5 kW
Power supply
Three-phase 200 VAC
PE
Ground plate
Brake power supply
SERVOPACK
Noise
filter
Clamp
4
Surge
absorber
Regenerative
resistor
L1, L2, L3
L1C, L2C
B1, B2
5
U, V, W
CN1
Core
1
Host controller
CN2
The cable must be
coiled four times.
SymbolCable NameSpecification
I/O signal cableShield cable
c
Servomotor cableShield cable
d
Encoder cableShield cable
e
AC Line cableShield cable
f
Regenerative resistor cableShield cable
g
Fan cable (only for SGMSS-70A) Shield cable
h
Clamp
ClampClamp
6
2
3
Fan
Brake
Servo-
motor
Encoder
PE
E-28
13 Installation Conditions of EMC Directive
Cable
Ferrite core
Cable
Ferrite core
Host controller side
Ground plate
Cable
Cable
clamp
Shield (cable sheath stripped)
Fix and ground the cable shield
using a piece of conductive metal.
Remove paint on mounting surface.
Attaching the Ferrite Core
One turnTwo turn
Recommended Ferrite Core
Cable NameFerrite Core ModelManufacturer
Servomotor main circuit cable
ESD-SR-25NEC TOKIN Corp.
Fixing the Cable
Fix and ground the cable shield using a piece of conductive metal.
• Example of Cable Clamp
Shield Box
A shield box, which is a closed metallic enclosure, should be used for shielding magnetic
interference. The structure of the box should allow the main body, door, and cooling unit to
be attached to the ground. The box opening should be as small as possible.
13.2 Hand-held Digital Operator and Analog Monitor Cable
Do not connect the hand-held digital operator and the analog monitor cable to the SERVO-
PACK during operations. Connect them only when the machinery is stopped during mainte-
nance.
E-29
13.3 Peripheral Device Types and Capacities
Main
Circuit
Power
Supply
Singlephase
100 V
Singlephase
200 V
Threephase
200V
Model
Capacity
SGDS-ModelSpecFuse MCCB
(kW)
0.03A3B0.254
0.05A5F0.254
0.1001F0.404
0.2002F0.606
0.4004F1.28
0.05A5A0.254
0.1001A0.40
0.2002A0.75
0.4004A1.28
0.8008A2.216
0.5005A1.44
1.010A2.37
1.515A3.210
2.020A4.313
3.030A5.917
5.050A7.528
6.060A12.532
7.575A15.541
* 1. This is the net value for a rated load.
When selecting fuse, determine the capacity using the prescribed derating.
Braking characteristics 25 °C: 200 % for 2s min.; 700 % for 0.01s min.
* 2. The FN-type noise filter is made by SCHAFFNER.
The FMAC-type noise filter is made by SCHURTER (previously TIMONTA).
* 3. The R.C.M type surge absorber is made by OKAYA ELECTRIC INDUSTRIES CO., LTD.
* 4. Made by YASKAWA Controls Co., Ltd.
Power
Supply
Capacity
per
SERVOPACK
(kVA)
MCCB
or Fuse
Capacity
(Arms)
Recommended Noise
∗1
FN2070
-6/07
FN2070
-10/07
FN2070
-6/07
FN2070
4
-6/07
FN2070
-10/07
FN2070
-16/07
FN258L
-7/07
FN258L
-16/07
FN258L
-30/07
FMAC
-0934
-5010
FMAC
-0953
-6410
∗2
Filter
Single-phase
250VAC, 6A
Single-phase
250VAC, 6A
Single-phase
250VAC, 6A
Single-phase
250VAC, 10A
Single-phase
250VAC, 10A
Single-phase
250VAC, 6A
Single-phase
250VAC, 6A
Single-phase
250VAC, 10A
Single-phase
250VAC, 16A
Three-phase
480VAC, 7A
Three-phase
480VAC, 16A
Three-phase
480VAC, 30A
Three-phase
480VAC, 50A
Three-phase
480VAC, 64A
Recommended
Surge
Absorber
∗3
R.C.M601BQZ-4
R.C.M601BQZ-4
R.C.M-
601BUZ-4
Magnetic
Contactor
∗4
HI-11J
(20A)
HI-11J
(20A)
HI-15J
(35A)
HI-11J
(20A)
HI-15J
(35A)
HI-20J
(35A)
HI-25J
(50A)
HI-35J
(6
5A)
Rated Voltage
250 V 240 V
Noise Filter for Brake Power Supply
Use an FN2070-6107 made by SCHAFFNER for a servomotor of 400 W or less.
E-30
14 Installation Conditions of UL Standards
8.0
1.2
φ4.5
φ7.1
φ4.3
9.3
8.5
21.8
12.0
1.5
φ5.8
φ9.0
φ5.3
13.3
10.5
29.8
To adapt SERVOPACKs to UL Standards, use the following ring terminal kit for cables to con-
nect the motor output terminals U,V, and W.
SERVOPACK ModelTerminalsTerminal Kit Model
SGDS-50A
(5.0 kW)
U, V, W
(Motor output)
JZSP-CST9-50A
(Crimp terminals and Sleeves × 3 sets)
Dimensional Drawings
(Crimp terminal)
14 Installation Conditions of UL Standards
SGDS-60A
(6.0 kW)
SGDS-75A
(7.5 kW)
U, V, W
(Motor output)
JZSP-CST9-75A
(Crimp terminals and Sleeves × 3 sets)
Dimensional Drawings
(Crimp terminal)
E-31
15 Overload Characteristics
The overload detection level is set under hot start* conditions at a servomotor surrounding air
temperature of 40°C (104°F).
10000.0
1000.0
Detecting time (s)
100.0
A
10.0
1.0
100%
B
C
* A hot start indicates that both the SERVOPACK and the servomotor have
run long enough at the rated load to be thermally saturated.
Note: The overload protection characteristics of A, B, and C in the figure
are applicable when the SERVOPACK is combined with one of the
following servomotors.
Graph
Type
SGMAS SGMPS SGMSS SGMCS SGMMJ SGMGH
-A5 to -04 -01 to -04−-02 to -35 -A1 to -A3−
A
-06 to -12 -08 to -15 -10 to -30 -45 to -2Z−-03 to -30
B
−−-40 to -70−−-40 to -75
C
Motor Type
Maximum torque
Rated torque
Maximum torqueRated torque
(Maximum current)(Rated current)
× 100%
E-32
Revision History
Date of
publication
Revision Number
Date of original
publication
MANUAL NO. TOBP S800000 00A
Published in Japan June 2002 02-3
00
20
19
18
17
1615141312
111098765
432
1
The revision dates and numbers of the revised manuals are given on the bottom of the back cover.
Date of
Publication
January 2014Back coverRevision: Address
February 2013Back coverRevision: Address
August 2012Back coverRevision: Address
March 2012
November 2010
July 2010
August 2008
June 2008Back coverRevision: Address
December 2007Back coverRevision: Address
November 2007
July 2006All chaptersAddition: 6- kW and 7.5-kW SERVOPACKs
July 2005Back coverRevision: Address
May 2005All chaptersAddition: Description of SGMGH servomotor
September 200414Addition: Installation conditions of UL standards
September 2004All chaptersAddition: 5.0-kW SERVOPACK
August 2003All chaptersAddition: New models of SERVOPACKs and servomotors
June 2003Back coverRevision: Address
March 200313Addition: EMC Directive
October 200212Revision: Installation category (overvoltage category)
June 2002Back coverRevision: Address
March 2002
Rev.
SectionRevised Content
No.
Inside of
back cover
Back coverRevision: Address
Front coverRevision: Format
Back coverRevision: Address, format
10.1, 13.3Addition: Rated voltage
15Addition: Current description
Back coverRevision: Address
12Revision: Protection class 1X → 10
All chaptersRevision: Ambient temperature → surrounding air temperature
5Addition: PL on fumigation
All chaptersRevision: Surge protector → surge absorber
Room 1011, Tower W3 Oriental Plaza, No.1 East Chang An Ave.,
Dong Cheng District, Beijing 100738, China
Phone 86-10-8518-4086 Fax 86-10-8518-4082
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei 104, Taiwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
YASKAWA ELECTRIC CORPORATION
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to
follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.