Yaskawa Z1000U User Manual

Z1000U HVAC MATRIX Bypass
Low Harmonic Drive Bypass for HVAC Applications
Technical Manual
Type: Z1D1 Models:
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
208 V: 7.5 to 75 HP 480 V: 7.5 to 350 HP
Mechanical Installation
Electrical Installation
Start-Up Programming &
Operation
Programming
Diagnostics &
Troubleshooting
Periodic Inspection &
Maintenance
Specifications
Parameter List
BACnet Communications
MEMOBUS/Modbus
Communications
1
2
3
4
5
6
7
A
B
C
D
MANUAL NO. SIEP YAIZ1D 01A
Apogee FLN Network
Protocol
Metasys N2 Network
Protocol
Standards Compliance
Quick Reference Sheet
E
F
G
H
Copyright © 2015 YASKAWA AMERICA, INC. All rights reserved.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.

Quick Start Procedure

u
This procedure is a supplement to other documentation supplied with this equipment and guides the user in properly wiring the Z1000U Bypass and motor.
WARNING! Read and adhere to all safety messages contained in this manual prior to performing this procedure. When installing the system be sure to follow good wiring practices and all applicable codes. Ensure that the mounting of the various components are secure and that the environment, such as extreme dampness, poor ventilation etc. will not cause system degradation. Please read this cheat sheet and other documentation provided with the bypass thoroughly before attempting any installation.
The setup procedure begins on the next page.
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
3
4
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
5
6
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
7
8
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
9
10
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
11
12
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
13
14
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
15
16
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
17
18
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
19
20
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
21
22
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
23
24
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
25
operation mode.
26
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
27
28
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
29
30
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
desired
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
31
32
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
33
34
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
Table of Contents
QUICK START PROCEDURE.......................................................................... 3
i. PREFACE & GENERAL SAFETY.................................................................. 45
i.1 Preface ....................................................................................................................... 46
Product Description ................................................................................................................. 46
Applicable Documentation....................................................................................................... 46
Symbols................................................................................................................................... 46
Terms and Abbreviations ........................................................................................................ 47
Trademarks ............................................................................................................................. 47
i.2 General Safety ........................................................................................................... 48
Supplemental Safety Information ............................................................................................ 48
Safety Messages..................................................................................................................... 49
General Application Precautions ............................................................................................. 50
Motor Application Precautions................................................................................................. 51
Drive Label Warning Example................................................................................................. 52
Bypass Label Warning Example ............................................................................................. 53
Warranty Information............................................................................................................... 54
1. RECEIVING .................................................................................................... 55
1.1 Section Safety............................................................................................................ 56
1.2 General Description .................................................................................................. 57
Control Mode Details............................................................................................................... 57
1.3 Model Numbers and Nameplate Checks ................................................................. 58
Drive Nameplate...................................................................................................................... 58
Bypass Nameplate .................................................................................................................. 59
Bypass Enclosures.................................................................................................................. 61
Bypass Product Options.......................................................................................................... 61
1.4 Bypass Component Names...................................................................................... 62
1.5 Bypass Component Descriptions............................................................................ 63
Bypass Front Control Panel .................................................................................................... 63
Bypass Internal Components .................................................................................................. 63
Front Views of Drive ................................................................................................................ 66
2. MECHANICAL INSTALLATION..................................................................... 67
2.1 Section Safety............................................................................................................ 68
2.2 Mechanical Installation ............................................................................................. 70
Installation Environment .......................................................................................................... 70
YASKAWA
SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
35
Table of Contents
Installation Orientation and Spacing.................................................................................................. 71
Exterior and Mounting Dimensions ................................................................................................... 71
3. ELECTRICAL INSTALLATION .............................................................................. 73
3.1 Section Safety......................................................................................................................74
3.2 Standard Connection Diagram...........................................................................................76
3.3 Main Circuit Wiring..............................................................................................................80
Opening the Bypass Enclosure ......................................................................................................... 80
Bypass Main Circuit Terminal Block Configuration ........................................................................... 84
3.4 Input and Output Power Wiring Connections...................................................................85
Factory Recommended Branch Circuit Protection ............................................................................ 85
Main Circuit Terminal Functions........................................................................................................ 86
Wire Gauge and Tightening Torque Specifications........................................................................... 86
Main Input Circuit and Motor Wiring .................................................................................................. 88
Wiring the Main Input Circuit ............................................................................................................. 93
3.5 Control Circuit Wiring .........................................................................................................96
Control Circuit Connection Diagram.................................................................................................. 96
Control Circuit Terminal Block Functions .......................................................................................... 96
Bypass Analog Outputs..................................................................................................................... 97
Serial Communications ..................................................................................................................... 98
Drive Cover Removal ........................................................................................................................ 99
Drives in Bypass Models D024 to D114 and B011 and B124 ........................................................... 99
Drives in Bypass Models D143 to D211 and B156 to B414 ............................................................ 100
Removing/Reattaching the Front Cover .......................................................................................... 100
Wiring the Drive Control Circuit Terminal ........................................................................................ 102
Switches and Jumpers on the Terminal Board................................................................................ 104
3.6 Bypass and Drive Control I/O Connections....................................................................105
Terminals A1, A2, and A3 Input Signal Selection............................................................................ 105
Terminal AM/FM Signal Selection ................................................................................................... 105
MEMOBUS/Modbus Termination .................................................................................................... 106
3.7 External Interlock ..............................................................................................................107
Annunciation Contact Outputs......................................................................................................... 107
Building Automation System Run/Stop Circuit ................................................................................ 107
Safety Interlock Circuit .................................................................................................................... 107
Building Automation System Interlock Circuit (Drive and Bypass Enable Input)............................. 107
Remote Transfer to Bypass............................................................................................................. 108
Smoke Purge Operation.................................................................................................................. 108
Spare Multi-Function Digital Inputs ................................................................................................. 108
4. START-UP PROGRAMMING & OPERATION..................................................... 109
4.1 Section Safety....................................................................................................................110
4.2 Using the HOA Keypad .....................................................................................................111
HOA Keypad Keys and Displays..................................................................................................... 111
LCD Display .................................................................................................................................... 112
Bypass Control Board LEDs............................................................................................................ 113
ALARM (ALM) LED Displays........................................................................................................... 114
AUTO LED and HAND LED Indications .......................................................................................... 114
HOA Keypad Menu Structure.......................................................................................................... 116
HOA Keypad Parameter Display (Drive Off) ................................................................................... 116
4.3 The Drive and Programming Modes................................................................................118
36
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
Table of Contents
Changing Parameter Settings or Values ......................................................................................... 118
Verifying Parameter Changes: Modified Constants ........................................................................ 119
Simplified Setup Using the Quick Setting Group............................................................................. 120
4.4 Powering Up the Drive ......................................................................................................122
Powering Up the Drive and Operation Status Display..................................................................... 122
4.5 Application Selection........................................................................................................123
Setting 1: Fan Application ............................................................................................................... 123
Setting 2: Fan with PID Control Application .................................................................................... 123
Setting 3: Return Fan with PID Control Application......................................................................... 123
Setting 4: Cooling Tower Fan Application ....................................................................................... 124
Setting 5: Cooling Tower Fan with PID Control Application ............................................................ 124
Setting 6: Pump (Secondary) Application........................................................................................ 125
Setting 7: Pump with PID Control Application ................................................................................. 125
4.6 Auto-Tuning .......................................................................................................................126
Types of Auto-Tuning ...................................................................................................................... 126
Before Auto-Tuning the Drive.......................................................................................................... 126
Auto-Tuning Interruption and Fault Codes ...................................................................................... 127
Auto-Tuning Operation Example ..................................................................................................... 127
T1: Parameter Settings during Induction Motor Auto-Tuning .......................................................... 129
5. PROGRAMMING .................................................................................................. 131
5.1 A: Initialization...................................................................................................................132
A1: Initialization ............................................................................................................................... 132
5.2 b: Application.....................................................................................................................133
b1: Operation Mode Selection......................................................................................................... 133
b2: DC Injection Braking and Short Circuit Braking......................................................................... 135
b3: Speed Search............................................................................................................................ 136
b5: PID Control................................................................................................................................ 142
5.3 C: Tuning............................................................................................................................153
C1: Acceleration and Deceleration Times ....................................................................................... 153
C2: S-Curve Characteristics............................................................................................................ 153
C4: Torque Compensation .............................................................................................................. 154
C6: Carrier Frequency..................................................................................................................... 154
C7: Voltage Adjustment................................................................................................................... 155
5.4 d: Reference Settings .......................................................................................................156
d1: Frequency Reference................................................................................................................ 156
d2: Frequency Upper/Lower Limits ................................................................................................. 157
d3: Jump Frequency........................................................................................................................ 158
5.5 E: Motor Parameters .........................................................................................................159
E1: V/f Pattern for Motor 1............................................................................................................... 159
E2: Motor 1 Parameters .................................................................................................................. 163
5.6 F: Options...........................................................................................................................164
F6: Drive/Bypass Communications ................................................................................................. 164
5.7 H: Terminal Functions.......................................................................................................165
H1: Multi-Function Digital Inputs ..................................................................................................... 165
H2: Multi-Function Digital Outputs................................................................................................... 167
H3: Multi-Function Analog Inputs .................................................................................................... 174
H4: Multi-Function Analog Outputs ................................................................................................. 180
5.8 L: Protection Functions ....................................................................................................182
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
37
Table of Contents
L1: Motor Protection ........................................................................................................................ 182
L2: Momentary Power Loss Ride-Thru............................................................................................ 183
L3: Stall Prevention ......................................................................................................................... 184
L4: Reference Detection.................................................................................................................. 186
L5: Fault Restart.............................................................................................................................. 187
L6: Torque Detection....................................................................................................................... 190
L8: Drive Protection......................................................................................................................... 192
5.9 n: Special Adjustments.....................................................................................................194
n1: Hunting Prevention.................................................................................................................... 194
n3: Overexcitation Braking .............................................................................................................. 194
5.10 o: Operator-Related Settings ...........................................................................................195
o1: HOA Keypad Display Selection................................................................................................. 195
o2: HOA Keypad Functions............................................................................................................. 196
o4: Maintenance Monitor Settings................................................................................................... 196
5.11 S: Special Parameters.......................................................................................................198
S1: Dynamic Audible Noise Control Function ................................................................................. 198
S2: Sequence Timers...................................................................................................................... 199
Examples of Sequence Timers ....................................................................................................... 201
5.12 T: Motor Tuning .................................................................................................................205
5.13 U: Monitor Parameters......................................................................................................206
UB: Bypass Monitors....................................................................................................................... 206
U1: Operation Status Monitors ........................................................................................................ 206
U2: Fault Trace................................................................................................................................ 206
U3: Fault History.............................................................................................................................. 206
U4: Maintenance Monitors .............................................................................................................. 206
U5: PID Monitors ............................................................................................................................. 206
U9: Power Monitors......................................................................................................................... 206
5.14 Z: Bypass Parameters.......................................................................................................207
Z1: Bypass Control System............................................................................................................. 207
Z2: Bypass Control Input/Output ..................................................................................................... 216
Z3: Bypass Control Communication................................................................................................ 220
Z4: Ethernet Option Bypass Control................................................................................................ 223
6. DIAGNOSTICS & TROUBLESHOOTING ............................................................ 227
6.1 Section Safety....................................................................................................................228
6.2 Motor Performance Fine-Tuning......................................................................................230
Fine-Tuning V/f Control ................................................................................................................... 230
Parameters to Minimize Motor Hunting and Oscillation .................................................................. 230
6.3 Drive Alarms, Faults, and Errors .....................................................................................231
Types of Alarms, Faults, and Errors................................................................................................ 231
Alarm and Error Displays ................................................................................................................ 232
6.4 Fault Detection ..................................................................................................................235
Fault Displays, Causes, and Possible Solutions ............................................................................. 235
6.5 Alarm Detection.................................................................................................................251
Alarm Codes, Causes, and Possible Solutions ............................................................................... 251
6.6 Operator Programming Errors .........................................................................................259
Operator Programming Error Codes, Causes, and Possible Solutions........................................... 259
6.7 Auto-Tuning Fault Detection ............................................................................................262
38
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
Table of Contents
Auto-Tuning Codes, Causes, and Possible Solutions..................................................................... 262
6.8 Diagnosing and Resetting Faults.....................................................................................264
Fault Occurs Simultaneously with Power Loss ............................................................................... 264
If the Drive Still has Power After a Fault Occurs ............................................................................. 264
Viewing Fault Trace Data After Fault .............................................................................................. 264
Fault Reset Methods ....................................................................................................................... 264
6.9 Troubleshooting without Fault Display...........................................................................266
Common Problems.......................................................................................................................... 266
Cannot Change Parameter Settings ............................................................................................... 266
Motor Does Not Rotate Properly after Pressing AUTO Button or after Entering External Run
Command ...................................................................................................................................... 267
Motor is Too Hot.............................................................................................................................. 269
oPE02 Error Occurs When Lowering the Motor Rated Current Setting .......................................... 270
Motor Stalls during Acceleration or Acceleration Time is Too Long................................................ 270
Drive Frequency Reference Differs from the Controller Frequency Reference Command ............. 270
Excessive Motor Oscillation and Erratic Rotation............................................................................ 271
Deceleration Takes Longer than Expected ..................................................................................... 271
Noise From Drive or Motor Cables When the Drive is Powered On ............................................... 271
Ground Fault Circuit Interrupter (GFCI) Trips During Run .............................................................. 271
Connected Machinery Vibrates When Motor Rotates ..................................................................... 271
PID Output Fault.............................................................................................................................. 272
Motor Rotates after the Drive Output is Shut Off (Motor Rotates During DC Injection Braking) ..... 272
Output Frequency is Not as High as Frequency Reference............................................................ 272
Sound from Motor............................................................................................................................ 273
Motor Does Not Restart after Power Loss....................................................................................... 273
The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals (Terminals DM
+ and DM-) ..................................................................................................................................... 273
7. PERIODIC INSPECTION & MAINTENANCE....................................................... 275
7.1 Section Safety....................................................................................................................276
7.2 Inspection ..........................................................................................................................278
Recommended Daily Inspection...................................................................................................... 278
Recommended Periodic Inspection................................................................................................. 279
7.3 Periodic Maintenance .......................................................................................................281
Replacement Parts.......................................................................................................................... 281
7.4 HOA Keypad Battery Replacement..................................................................................283
Real-Time Clock Adjustment........................................................................................................... 283
7.5 Drive Cooling Fans............................................................................................................285
Number of Cooling Fans ................................................................................................................. 285
Drive Cooling Fan Component Names............................................................................................ 285
Cooling Fan Replacement: 2o0028 to 2o0130 and 4o0011 to 4o0124 ...................................... 287
Cooling Fan Replacement: 2o0154, 2o0192, 4o0156, and 4o0180 ........................................... 289
Cooling Fan Replacement: 2o0248 and 4o0240 to 4o0414 ........................................................ 293
Installing the Cooling Fan................................................................................................................ 295
A. SPECIFICATIONS ................................................................................................ 299
A.1 Power Ratings ...................................................................................................................300
Three-Phase 208 Vac Models D024 to D211.................................................................................. 300
Three-Phase 480 Vac Models B011 to B077 .................................................................................. 301
Three-Phase 480 Vac Models B096 to B414 .................................................................................. 302
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
39
Table of Contents
A.2 Drive Specifications ..........................................................................................................303
A.3 Drive Derating Data ...........................................................................................................304
Carrier Frequency Derating............................................................................................................. 304
A.4 Bypass Options .................................................................................................................305
Option B .......................................................................................................................................... 305
Option D .......................................................................................................................................... 305
Option G .......................................................................................................................................... 305
Option K (Control) ........................................................................................................................... 305
Option K (Power)............................................................................................................................. 305
Option L........................................................................................................................................... 305
Option N .......................................................................................................................................... 305
Option W (Control) .......................................................................................................................... 305
Option W (Power)............................................................................................................................ 305
Option Z........................................................................................................................................... 305
B. PARAMETER LIST............................................................................................... 307
B.1 Parameter Groups .............................................................................................................308
Parameters Listed in Dark Gray Rows ............................................................................................ 309
B.2 A: Initialization Parameters ..............................................................................................310
A1: Initialization ............................................................................................................................... 310
B.3 b: Application.....................................................................................................................311
b1: Operation Mode Selection......................................................................................................... 311
b2: DC Injection Braking.................................................................................................................. 311
b3: Speed Search............................................................................................................................ 312
b5: PID Control................................................................................................................................ 313
b8: Energy Saving ........................................................................................................................... 315
B.4 C: Tuning............................................................................................................................316
C1: Acceleration and Deceleration Times ....................................................................................... 316
C2: S-Curve Characteristics............................................................................................................ 316
C4: Torque Compensation .............................................................................................................. 316
C6: Carrier Frequency..................................................................................................................... 317
C7: Voltage Adjustment................................................................................................................... 317
B.5 d: References.....................................................................................................................318
d1: Frequency Reference................................................................................................................ 318
d2: Frequency Upper/Lower Limits ................................................................................................. 318
d3: Jump Frequency........................................................................................................................ 318
d4: Frequency Reference Hold Function......................................................................................... 319
d7: Offset Frequency....................................................................................................................... 319
B.6 E: Motor Parameters .........................................................................................................320
E1: V/f Pattern for Motor 1............................................................................................................... 320
E2: Motor 1 Parameters .................................................................................................................. 321
B.7 F: Options...........................................................................................................................322
F6: Drive/Bypass Communications ................................................................................................. 322
B.8 H Parameters: Multi-Function Terminals ........................................................................323
H1: Multi-Function Digital Inputs ..................................................................................................... 323
H2: Multi-Function Digital Outputs................................................................................................... 325
H3: Multi-Function Analog Inputs .................................................................................................... 326
H4: Analog Outputs ......................................................................................................................... 328
H5: MEMOBUS/Modbus Serial Communication ............................................................................. 329
40
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
Table of Contents
B.9 L: Protection Function ......................................................................................................330
L1: Motor Protection ........................................................................................................................ 330
L2: Momentary Power Loss Ride-Thru............................................................................................ 330
L3: Stall Prevention ......................................................................................................................... 331
L4: Speed Detection........................................................................................................................ 331
L5: Fault Restart.............................................................................................................................. 332
L6: Torque Detection....................................................................................................................... 332
L8: Drive Protection......................................................................................................................... 333
B.10 n: Special Adjustment.......................................................................................................334
n1: Hunting Prevention.................................................................................................................... 334
n3: Overexcitation Braking .............................................................................................................. 334
B.11 o: Operator-Related Settings ...........................................................................................335
o1: HOA Keypad Display Selection................................................................................................. 335
o2: HOA Keypad Functions............................................................................................................. 335
o4: Maintenance Monitor Settings................................................................................................... 336
B.12 S: HVAC Function..............................................................................................................337
S1: Dynamic Noise Control Function .............................................................................................. 337
S2: Sequence Timers...................................................................................................................... 337
B.13 T: Motor Tuning .................................................................................................................340
T1: Induction Motor Auto-Tuning..................................................................................................... 340
B.14 U: Monitors.........................................................................................................................341
UB: Bypass Control Monitors .......................................................................................................... 341
U1: Operation Status Monitors ........................................................................................................ 342
U2: Fault Trace................................................................................................................................ 344
U3: Fault History.............................................................................................................................. 345
U4: Maintenance Monitors .............................................................................................................. 347
U5: PID Monitors ............................................................................................................................. 348
U9: Power Monitors......................................................................................................................... 349
B.15 Z: Bypass Parameters.......................................................................................................350
Z1: Bypass Control System............................................................................................................. 350
Z2: Bypass Control Input/Output ..................................................................................................... 353
Z3: Bypass Control Communication................................................................................................ 354
Z4: Bypass Control Option Boards.................................................................................................. 355
B.16 Defaults by Drive Model....................................................................................................358
C. BACNET COMMUNICATIONS ............................................................................ 361
C.1 BACnet Configuration.......................................................................................................362
C.2 Communication Specifications........................................................................................363
C.3 Connecting to a Network ..................................................................................................364
Network Cable Connection.............................................................................................................. 364
Wiring Diagram for Multiple Connections ........................................................................................ 365
Network Termination ....................................................................................................................... 365
C.4 BACnet Setup Parameters................................................................................................366
BACnet Serial Communication........................................................................................................ 366
C.5 Bypass Operations by BACnet ........................................................................................368
Observing the Bypass Operation .................................................................................................... 368
Controlling the Bypass .................................................................................................................... 368
C.6 BACnet Objects Supported ..............................................................................................369
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
41
Table of Contents
Present Value Access ..................................................................................................................... 369
Supported Properties of Objects ..................................................................................................... 369
Analog Input Objects ....................................................................................................................... 370
Analog Output Objects .................................................................................................................... 370
Analog Value Objects...................................................................................................................... 370
Binary Input Objects ........................................................................................................................ 371
Binary Output Objects ..................................................................................................................... 372
Binary Value Objects....................................................................................................................... 372
Device Object .................................................................................................................................. 374
C.7 Accessing Bypass Parameters and the Enter Command .............................................376
Reading Bypass Parameters........................................................................................................... 376
Writing Bypass Parameters............................................................................................................. 376
Enter Command .............................................................................................................................. 376
C.8 Communication Errors .....................................................................................................377
C.9 BACnet Protocol Implementation Conformance Statement..........................................378
D. MEMOBUS/MODBUS COMMUNICATIONS........................................................ 381
D.1 MEMOBUS/Modbus Configuration ..................................................................................382
D.2 Communication Specifications........................................................................................383
D.3 Connecting to a Network ..................................................................................................384
Network Cable Connection.............................................................................................................. 384
Wiring Diagram for Multiple Connections ........................................................................................ 385
Network Termination ....................................................................................................................... 385
D.4 MEMOBUS/Modbus Setup Parameters ...........................................................................386
MEMOBUS/Modbus Serial Communication.................................................................................... 386
D.5 Bypass Operations by MEMOBUS/Modbus....................................................................388
Observing the Bypass Operation .................................................................................................... 388
D.6 Communications Timing...................................................................................................389
Command Messages from Master to Bypass ................................................................................. 389
Response Messages from Bypass to Master.................................................................................. 389
D.7 Message Format ................................................................................................................390
Message Content ............................................................................................................................ 390
Slave Address ................................................................................................................................. 390
Function Code ................................................................................................................................. 390
Data................................................................................................................................................. 390
Error Check ..................................................................................................................................... 390
D.8 Message Examples ...........................................................................................................392
Reading Drive MEMOBUS/Modbus Register Contents .................................................................. 392
Loopback Test................................................................................................................................. 392
Writing to Multiple Registers............................................................................................................ 393
D.9 MEMOBUS/Modbus Data Table........................................................................................394
Command Data ............................................................................................................................... 394
Monitor Data.................................................................................................................................... 395
Broadcast Messages....................................................................................................................... 407
Fault Trace Contents....................................................................................................................... 408
Bypass Fault Codes ........................................................................................................................ 410
Alarm Register Contents ................................................................................................................. 410
D.10 Enter Command.................................................................................................................412
Enter Command Behavior ............................................................................................................... 412
42
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
Table of Contents
D.11 Communication Errors .....................................................................................................413
MEMOBUS/Modbus Error Codes.................................................................................................... 413
Slave Not Responding..................................................................................................................... 413
E. APOGEE FLN NETWORK PROTOCOL.............................................................. 415
E.1 APOGEE FLN Set-Up.........................................................................................................416
Bypass Parameter Settings for APOGEE FLN Communications.................................................... 416
E.2 Connecting to a Network ..................................................................................................417
Network Cable Connection.............................................................................................................. 417
Wiring Diagram for Multiple Connections ........................................................................................ 418
Network Termination ....................................................................................................................... 418
Recommended Cable...................................................................................................................... 418
E.3 Slope and Intercept Conversion ......................................................................................419
Drive Controlled Feedback.............................................................................................................. 419
Field Panel Controlled Feedback .................................................................................................... 419
Other Functionality .......................................................................................................................... 420
E.4 APOGEE FLN Point List Summary ..................................................................................421
E.5 Cable Loss Configuration and Behavior.........................................................................425
Drive Behavior at Loss of Communication ...................................................................................... 425
Apogee FLN Points ......................................................................................................................... 425
E.6 Mailbox Function...............................................................................................................427
Mailbox Function Points .................................................................................................................. 427
E.7 Fault Codes........................................................................................................................428
Communications Fault..................................................................................................................... 428
Bypass Faults–Apogee FLN Configuration ..................................................................................... 428
F. METASYS N2 NETWORK PROTOCOL .............................................................. 431
F.1 N2 Specifications and Configuration...............................................................................432
F.2 Connecting to a Network..................................................................................................433
Network Cable Connection.............................................................................................................. 433
Wiring Diagram for Multiple Connections ........................................................................................ 434
Network Termination ....................................................................................................................... 434
F.3 N2 Setup Parameters ........................................................................................................435
N2 Serial Communication................................................................................................................ 435
F.4 Bypass Operations by N2.................................................................................................437
Observing the Bypass Operation .................................................................................................... 437
Controlling the Bypass .................................................................................................................... 437
F.5 Communications Timing...................................................................................................441
Command Messages from Master to Bypass ................................................................................. 441
Response Messages from Bypass to Master.................................................................................. 441
F.6 Metasys N2 Point Database..............................................................................................442
Metasys N2 Analog Input (AI) Summary ......................................................................................... 442
Metasys N2 Analog Output (AO) Summary .................................................................................... 443
Metasys N2 Binary Input (BI) Summary .......................................................................................... 443
Metasys N2 Binary Output (BO) Summary ..................................................................................... 444
F.7 Mailbox Function...............................................................................................................445
Reading Drive Parameters .............................................................................................................. 445
Writing Drive Parameters ................................................................................................................ 445
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
43
Table of Contents
G. STANDARDS COMPLIANCE .............................................................................. 447
G.1 Section Safety....................................................................................................................448
G.2 UL/cUL Standards .............................................................................................................450
UL Standards Compliance .............................................................................................................. 450
H. QUICK REFERENCE SHEET .............................................................................. 451
H.1 Z1000U Bypass and Motor Specifications ......................................................................452
Z1000U Bypass Specifications........................................................................................................ 452
Motor Specifications ........................................................................................................................ 452
H.2 Basic Parameter Settings .................................................................................................453
Quick Setting Parameters ............................................................................................................... 453
Motor Setup..................................................................................................................................... 453
Multi-Function Digital Inputs ............................................................................................................ 453
Analog Inputs .................................................................................................................................. 453
Multi-Function Digital Outputs ......................................................................................................... 454
Monitor Outputs............................................................................................................................... 454
H.3 User Setting Table.............................................................................................................455
INDEX ................................................................................................................... 461
44
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
i

Preface & General Safety

This section provides safety messages pertinent to this product that, if not heeded, may result in fatality, personal injury, or equipment damage. Yaskawa is not responsible for the consequences of ignoring these instructions.
i.1 PREFACE...............................................................................................................46
i.2 GENERAL SAFETY...............................................................................................48
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
45
TERMSTERMS
i.1 Preface

i.1 Preface

Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
This manual is designed to ensure correct and suitable application of the Z1000U Bypass. Read this manual before attempting to install, operate, maintain, or inspect the bypass unit and keep it in a safe, convenient location for future reference. Be sure you understand all precautions and safety information before attempting application.
u

Product Description

The Z1000U MATRIX HVAC Bypass combines excellent harmonic mitigation, input power factor control, and energy saving capabilities in a design specifically suited for use in HVAC building automation applications that require reliable motor control.
The bypass package provides a Z1000U MATRIX drive in a NEMA rated enclosure with a 2-contactor style bypass to allow motor operation from the drive or across the line. The Z1000U MATRIX drive incorporates MATRIX technology to directly convert input AC voltage to output AC voltage. The Z1000U MATRIX drive offers real choices and benefits for green HVAC applications.
The Z1000U features HVAC application-specific software macros, a Hand/Off/Auto LCD keypad, and a real time clock for system accuracy. Popular building automation communication protocols BACnet, Siemens APOGEE, Johnson Controls Metasys, and MEMOBUS/ Modbus are embedded in the drive.
u

Applicable Documentation

The following manuals are available for the Z1000U MATRIX Bypass:
Z1000U HVAC MATRIX Bypass Technical Manual
Read this manual first. This manual is packaged together with the product and contains basic information required to install and wire the bypass. It also gives detailed information on fault diagnostics, parameter settings, and serial communication specifications. The purpose of this manual is to prepare the Z1000U Bypass for a trial run with an application and for basic operation. This manual is also available for download on the Yaskawa documentation website, www.yaskawa.com.
Z1000U HVAC MATRIX Drive User Manual
This manual contains detailed information on fault diagnostics, parameter settings, and BACnet specifications. The most recent version of this manual is available for download on our documentation website, www.yaskawa.com.
Z1000U HVAC MATRIX Drive Programming Manual
This manual provides detailed information on parameter settings, drive functions, and MEMOBUS/ Modbus specifications. Use this manual to expand drive functionality and to take advantage of higher performance features. The most recent version of this manual is available for download on our documentation website, www.yaskawa.com.
u

Symbols

Note: Indicates a supplement or precaution that does not cause drive damage.
Indicates a term or definition used in this manual.
46
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
TERMSTERMS
i.1 Preface
u

Terms and Abbreviations

Bypass: Yaskawa Z1000U MATRIX Bypass
Drive: Yaskawa Z1000U-Series Drive
H: Hexadecimal Number Format
IGBT: Insulated Gate Bipolar Transistor
kbps: Kilobits per Second
MAC: Media Access Control
r/min: Revolutions per Minute
V/f: V/f Control
u

Trademarks

This manual may describe trademarked equipment, which is the property of other companies. These trademarks are the property of the registered owner companies and may include the following:
• BACnet is a trademark of the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE).
APOGEE FLN, trademark of Siemens Building Technologies, Inc.
• Metasys®, trademark of Johnson Controls Inc.
• Modbus®, trademark of Schneider Automation, Inc.
• LONWORKS®, trademark of Echelon Corporation
• Other companies and product names mentioned in this manual are trademarks of those companies.
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
47
i.2 General Safety

i.2 General Safety

u

Supplemental Safety Information

General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details. Replace the covers or shields before operating the drive and run the drive according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on the front cover.
• If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.
WARNING
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or fatal injury or damage to the products or to related equipment and systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
48
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
i.2 General Safety
u

Safety Messages

WARNING
Heed the safety messages in this manual.
Failure to comply could result in death or serious injury. The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in
this manual.
Sudden Movement Hazard
System may start unexpectedly upon application of power, resulting in death or serious injury.
Clear all personnel from the drive, motor and machine area before applying power. Secure covers, couplings, shaft keys and machine loads before applying power to the drive.
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply could result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply
is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait for at least the time specified on the warning label, once all indicators are OFF, measure for unsafe voltages to confirm the drive is safe prior to servicing.
Do not attempt to modify or alter the drive in any way not explained in this manual.
Failure to comply could result in death or serious injury. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation,
adjustment and maintenance of AC drives.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
Because the leakage current exceeds 3.5 mA, IEC/EN 61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor with a cross­section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to comply may result in death or serious injury.
Always use appropriate equipment for Ground Fault Circuit Interrupters (GFCIs).
The drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual current operated protective or monitoring device is used for protection in case of direct or indirect contact, always use a type B GFCI according to IEC/EN 60755.
Fire Hazard
Branch Circuit protection is required to be installed according to applicable local codes and the requirements listed on the bypass nameplate. Failure to comply could result in fire and damage to the bypass and drive or injury to personnel. Bypass models without soft-starter option PW are suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 208 Vac and 480 Vac. Bypass models D169 to D211 and B180 to B414 with option PW are also suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 208 Vac and 480 Vac. Bypass models D024 to D143 and B011 to B156 with option PW are suitable for use on a circuit capable of delivering not more than 65,000 RMS symmetrical amperes, 208 Vac and 480 Vac.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
49
i.2 General Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment. Do not connect or operate any equipment with visible damage or missing parts.
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive. Do not pack the drive in wooden materials that have been fumigated or sterilized. Do not sterilize the entire package after the product is packed.
u

General Application Precautions

Selection
n
Installing a Reactor
Use an AC reactor in the following situations:
• to suppress harmonic current.
• when the drive is running from a power supply system with thyristor converters.
Drive Capacity
For specialized motors, make sure that the motor rated current is less than the rated output current for the drive.
When running more than one motor in parallel from a single drive, the capacity of the drive should be larger than [total motor rated current × 1.1].
Starting Torque
The startup and acceleration characteristics of the motor are restricted to the drive overload current rating.
The overload rating for the drive determines the starting and accelerating characteristics of the motor. Expect lower torque than when running from line power. To achieve a higher starting torque, use a larger drive or a drive and motor with larger capacity.
Emergency Stop
During a drive fault condition, the output shuts off but the motor does not stop immediately. A mechanical brake may be required when it is necessary to stop the motor faster than the ability of the Fast Stop function of the drive.
Installation
n
Enclosure Panels
Keep the drive in a clean environment. Be sure to leave the required space between drives to provide for cooling, and take proper measures so the ambient temperature remains within allowable limits and keep flammable materials away from the drive.
Installation Direction
NOTICE: Install the drive upright as specified in the manual. Refer to Mechanical Installation on page 70 for more information on
installation. Failure to comply may damage the drive due to improper cooling.
Settings
n
Upper Limits
NOTICE: The drive is capable of running the motor up to 240 Hz. Be sure to set the upper limit for the frequency of the drive to prevent the
possible danger of accidentally operating equipment at higher than rated speed. The default setting for the maximum output frequency is 60 Hz.
DC Injection Braking
NOTICE: Excessive current during DC Injection Braking and excessive duration of DC Injection Braking can cause motor overheat.
50
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
i.2 General Safety
Acceleration/Deceleration Times
Acceleration and deceleration times are affected by the amount of torque generated by the motor, the load torque, and the inertia moment. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as long as the Stall Prevention function is in operation. Install one of the available braking options or increase the capacity of the drive for faster acceleration and deceleration.
General Handling
n
Wiring Check
NOTICE: Do not connect power supply lines to output terminals U/T1, V/T2, or W/T3. Failure to comply will destroy the drive. Be sure to
perform a final check of all sequence wiring and other connections before turning on the power and also check for short circuits on the control terminals, which may damage the drive.
Inspection and Maintenance
WARNING! Electrical Shock Hazard. Capacitors in the drive do not immediately discharge after shutting off the power. Wait for at least the
amount of time specified on the drive before touching any components after shutting off the power. Failure to comply may cause injury to personnel from electrical shock.
Transporting the Drive
NOTICE: Never steam clean the drive. During transport, keep the drive from coming into contact with salts, fluorine, bromine, phthalate
ester, and other such harmful chemicals.
u

Motor Application Precautions

Insulation Tolerance
NOTICE: Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 480 V or particularly
long wiring distances.
High-Speed Operation
NOTICE: Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated speed.
Contact the motor or machine manufacturer.
Torque Characteristics
Torque characteristics differ compared to operating the motor directly from line power. The user should have a full understanding of the load torque characteristics for the application.
Vibration and Shock
The drive allows selection of high carrier PWM control and low carrier PWM. Selecting high carrier PWM can help reduce motor oscillation.
Take particular caution when adding a variable speed drive to an application running a motor from line power at a constant speed. If resonance occurs, install shock-absorbing isolation mounts around the base of the motor and enable the Jump frequency selection to prevent continuous operation in the resonant frequency range.
Audible Noise
The audible noise of the motor varies based on the carrier frequency setting. However, drive current derating may be required. When using a high carrier frequency, audible noise from the motor is comparable to the motor noise generated when running from line power.
Specialized Motors
n
Multi-Pole Motor
The rated current of a multi-pole motor differs from that of a standard motor, so be sure to check the maximum current when selecting a drive. Always stop the motor before switching between the number of motor poles. The motor will coast to stop if a regen overvoltage (ov) fault occurs or if overcurrent (oC) protection is triggered.
Submersible Motor
The rated current of a submersible motor is greater than that of a standard motor, so select the drive accordingly. Use a motor cable large enough to avoid decreasing the maximum torque level from voltage drop caused by a long motor cable.
Explosion-Proof Motor
The motor and the drive must be tested together to be certified as explosion-proof. The drive is not designed for explosion­proof areas.
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
51
WARNING
Read manual before installing. Wait 5 minutes for capacitor discharge after disconnecting power supply. To conform to requirements, make sure to ground the supply neutral for 400V class. After disconnecting from power supply,please wait 5 minutes before inspecting, performing maintenance or wiring the converter.
Risk of electric shock.
Hot Surfaces
Wait 5 minutes or longer until the unit has cooled.
i.2 General Safety
Geared Motor
Make sure that the gear and the lubricant are rated for the desired speed range to avoid gear damage when operating at low speeds or very high speeds. Consult with the manufacturer for applications that require operation outside the rated speed range of the motor or gear box.
Single-Phase Motor
Variable speed drives are not designed to operate with single phase motors. Using capacitors to start the motor causes excessive current to flow and can damage drive components. A split-phase start or a repulsion start can burn out the starter coils because the internal centrifugal switch is not activated. The drive is for use with three-phase motors only.
Motor with Brake
Take caution when using the drive to operate a motor with a built-in holding brake. If the brake is connected to the output side of the drive, it may not release at start due to low voltage levels, so be sure to install a separate power supply for the motor brake. Note that motors with built-in brakes tend to generate a fair amount of noise when running at low speeds.
u

Drive Label Warning Example

Always heed the warning information listed in Figure i.1.
52
Figure i.1 Warning Information Example and Position
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
Warning Label B
Warning Label A (inside enclosure)
i.2 General Safety
u

Bypass Label Warning Example

Always heed the warning information listed in Figure i.2 and Figure i.3 in the positions shown in Figure i.4.
Figure i.2 Warning Information Example A
Figure i.3 Warning Information Example B
Figure i.4 Bypass Warning Label Locations
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
53
i.2 General Safety
u
Warranty Information
Scope of Warranty
n
Inspections
Customers are responsible for periodic inspections of the drive. Upon request, a Yaskawa representative will inspect the drive for a fee. If the Yaskawa representative finds the drive to be defective due to Yaskawa workmanship or materials and the defect occurs during the warranty period, this inspection fee will be waived and the problem remedied free of charge.
Repairs
If a Yaskawa product is found to be defective due to Yaskawa workmanship or materials and the defect occurs during the warranty period, Yaskawa will provide a replacement, repair the defective product, and provide shipping to and from the site free of charge.
However, if the Yaskawa Authorized Service Center determines that the problem with the drive is not due to defective workmanship or materials, the customer will be responsible for the cost of any necessary repairs. Some problems that are outside the scope of this warranty are:
Problems due to improper maintenance or handling, carelessness, or other reasons where the customer is determined to be responsible.
Problems due to additions or modifications made to a Yaskawa product without Yaskawa’s understanding.
Problems due to the use of a Yaskawa product under conditions that do not meet the recommended specifications.
Problems caused by natural disaster or fire.
After the free warranty period elapses.
Replenishment or replacement of consumables or expendables.
Defective products due to packaging or fumigation.
Other problems not due to defects in Yaskawa workmanship or materials.
Warranty service is only applicable within the country where the product was purchased. However, after-sales service is available for customers outside of the country where the product was purchased for a reasonable fee.
Contact your local Yaskawa representative for more information.
Exceptions
Any inconvenience to the customer or damage to non-Yaskawa products due to Yaskawa’s defective products whether within or outside of the warranty period are NOT covered by warranty.
Restrictions
n
The drive is not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or health.
Customers who intend to use the product described in this manual for devices or systems relating to transportation, health care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa representatives or the nearest Yaskawa sales office.
WARNING! Injury to Personnel. This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident.
54
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
1

Receiving

This chapter explains how to inspect the bypass upon receipt, and gives an overview of the different enclosure types and components.
1.1 SECTION SAFETY.................................................................................................56
1.2 GENERAL DESCRIPTION.....................................................................................57
1.3 MODEL NUMBERS AND NAMEPLATE CHECKS................................................58
1.4 BYPASS COMPONENT NAMES...........................................................................62
1.5 BYPASS COMPONENT DESCRIPTIONS.............................................................63
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
55
1.1 Section Safety

1.1 Section Safety

NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
A motor connected to a PWM drive may operate at a higher temperature than a utility-fed motor and the operating speed range may reduce motor cooling capacity.
Ensure that the motor is suitable for drive duty and/or the motor service factor is adequate to accommodate the additional heating with the intended operating conditions.
56
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

1.2 General Description

u

Control Mode Details

Table 1.1 gives an overview of the various features associated with the bypass.
Table 1.1 Control Mode Features
Motor Type Induction Motors Comments
Control Mode V/f
Basic Description V/f control
Motor Type IM
Type of Applications
Control
Characteristics
Application-Specific
Commercial Power Switching
Multi Motor YES
Motor data unknown YES
High Speed Accuracy
Speed Control Range 1:40
Speed Accuracy ±2 to 3%
Speed Response 3 Hz (approx.)
Starting Torque 150% at 3 Hz
Auto-Tuning
Speed Search YES
Energy-Saving Control YES
Overexcitation
Deceleration
Selection
• Energy Saving Tuning
• Line to line resistance
YES
YES
1.2 General Description
May fluctuate with characteristics and motor temperature.
Speed deviation when operating at constant speed may fluctuate with characteristics and motor temperature.
Max. frequency of a speed reference signal that the drive can follow may fluctuate with characteristics and motor temperature.
Starting torque may fluctuate with characteristics and motor temperature.
Automatically adjusts parameter settings that concern electrical characteristics of the motor.
Bi-directional speed detection of a coasting motor to restart it without stopping.
Saves energy by always operating the motor at its maximum efficiency.
Provides fast deceleration without using a braking resistor.
When the output frequency matches the power supply frequency (60 Hz), the PWM switching operation stops and switches to operation with a direct commercial power supply connection.
Receiving
1
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
57
MADE IN JAPAN
PRG : 6110
IND.CONT.EQ.
7J48
CIMR-ZU4U0011AAA
:
: AC3PH 380-500V 50/60Hz 10A : AC3PH 0-475V 0-400Hz 11A : 20 kg : 6W3050-2-100 : J0065F575310100
: E131457
PASS
MODEL REV : A INPUT OUTPUT MASS O / N S / N
FILE NO
YASKAWA ELECTRIC CORPORATION 2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan
H
G F
E D
B
A
C
1.3 Model Numbers and Nameplate Checks

1.3 Model Numbers and Nameplate Checks

Please perform the following tasks after receiving the bypass
• Inspect the bypass for damage.
If the bypass appears damaged upon receipt, contact the shipper immediately.
• Verify receipt of the correct model by checking the information on the nameplate.
• If you have received the wrong model or the bypass does not function properly, contact your supplier. If you find any irregularities in the above items, contact the shipping company, the distributor or representative you purchased
the bypass from or your Yaskawa office immediately. The bypass is thoroughly tested at the factory. Any damages or shortages evident when the equipment is received must be reported immediately to the commercial carrier that transported the material. Shipping damage is not covered by the Yaskawa warranty. After unpacking and inspecting for damage, verify that internal wire connections have not come loose during shipment by spot checking wire terminations with a screwdriver or the appropriate tool. Bypass storage must be in a clean and dry location. Maintain the factory packaging and provide covering as needed to protect the bypass from construction site dirt, water, debris and traffic prior to and during construction.
u

Drive Nameplate

A – Rated Output Current B – Software version C –
Address
D – Serial number
<1> The address of the head office of Yaskawa Electric Corporation (responsible for product liability) is shown on the nameplate.
58
E – Lot number F – Output specifications
<1>
G – Input specifications H – AC drive model
Refer to Figure 1.2 for details.
Figure 1.1 Drive Nameplate Information Example
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
CIMR
-
Z U 4 E A
0096
U A
Z1000U
Series
No.
Enclosure
Type
Design Revision Order
No.
Region Code
U USA
IP00
A
No. Voltage Class
No.
Environmental Specification
3-phase, 380-480 Vac
3-phase, 200-240 Vac
2
4
<1>
U
Humidity and dust resistant
No.
Customized Specifications
E
Without EMC Noise Filter
Built-in EMC Noise Filter
U
Drive Model Amp Rating
A
A.C. INPUT
A.C. OUTPUT
Designator Rating
Serial No.:4W14Z5747540001 Model No. :Z1D1D002PM
Type: Z1000U BYPASS W.D.: DS.Z1D1.01
Inst. Manual:SIEPYAIZ1D01,
TOEPC71063611
F1,F2 FNQ-R1.5A,600V
Type
Volts: 480
Volts: 0-460
Hz: 50/60
Hz: 0-60
Phase: 3
Phase: 3
SCCR: 65kA rms sym.,480V max.
Amps:114.0
Amps:124.0
B
F
C
D
E
1.3 Model Numbers and Nameplate Checks
Figure 1.2 Drive Model Number Definition
<1> Drives with these specifications do not guarantee complete protection for the environmental conditions indicated.
u

Bypass Nameplate

The nameplate is located on the inside of the enclosure door.
The nameplate shown below is an example for a standard Z1000U Bypass.
Receiving
1
A – Input specifications B – Output specifications C – Control transformer fuse
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
specifications
Figure 1.3 Bypass Nameplate Information Example
D – Serial number E – Bypass model number F – Schematic document number
59
Z1D 1 B
Z1000U Bypass
No. Voltage
Refer to the following table
D 208 Vac B 480 Vac
No. Enclosure Type
1 IP20/NEMA Type 1
040 P T
No. Control Options
L LonWorks
D Ethernet/IP
W Custom Nameplate
K
200 VA Transformer (CPT)
Z Speed Pot
No. Power Options
K Output Reactor 5%
B 3-Contactor Bypass
G Drive Service Switch
N EMC Filter
D/L
Z
W
K
W Soft Start Bypass
B/G
K
W
N
1.3 Model Numbers and Nameplate Checks
Bypass Models, Drive Models, and Capacities
n
Bypass Unit Model Z1D1
D024 7.5 23.3 24.2
D030 10 29.5 30.8
D046 15 43.6 16.2
D059 20 55.8 59.4
D074 25 70 74.8
D088 30 82.1 88.0
D114 40 105.2 114.0
D143 50 132.4 143.0
D169 60 156.4 169.0
D211 75 194.7 211.0
B011 7.5 10.7 11.0
B014 10 13.7 14.0
B021 15 19.7 21.0
B027 20 25.7 27.0
B034 25 31.7 34.0
B040 30 36.7 40.0
B052 40 47.7 52.0
B065 50 60 65.0
B077 60 71 77.0
B096 75 88 96.0
B124 100 114 124
B156 125 143 156
B180 150 165 180
B240 200 219 240
B302 250 276 302
B361 300 330 361
B414 350 378 414
60
HP Input (A) Output (A)
Capacity
Drive Model Electrical Schematic Weight (lb)
208 Vac
2o0028 2o0042 2o0054 2o0068 2o0081 2o0104 2o0130 2o0154 2o0192 2o0248
480 Vac
4o0011 4o0014 4o0021 4o0027 4o0034 4o0040 4o0052 4o0065 4o0077 4o0096 4o0124 4o0156 4o0180 4o0240 4o0302 4o0361 4o0414
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
DS.Z1D1.01 230
DS.Z1D1.01 325
DS.Z1D1.01 340
DS.Z1D1.01 350
DS.Z1D1.01 350
DS.Z1D1.01 465
DS.Z1D1.01 475
DS.Z1D1.01 825
DS.Z1D1.01 825
DS.Z1D1.01 1050
DS.Z1D1.01 220
DS.Z1D1.01 230
DS.Z1D1.01 230
DS.Z1D1.01 300
DS.Z1D1.01 300
DS.Z1D1.01 315
DS.Z1D1.01 350
DS.Z1D1.01 360
DS.Z1D1.01 375
DS.Z1D1.01 475
DS.Z1D1.01 490
DS.Z1D1.01 850
DS.Z1D1.01 900
DS.Z1D1.01 1100
DS.Z1D1.01 1600
DS.Z1D1.01 1750
DS.Z1D1.01 1800
1.3 Model Numbers and Nameplate Checks
u

Bypass Enclosures

All bypass units are intended for non-hazardous locations. All NEMA Type 1 Enclosure bypass units are constructed for indoor use to provide a degree of protection against incidental contact with enclosed electrical equipment and falling dust or dirt.
u

Bypass Product Options

Refer to Bypass Options on page 305 for details on available bypass product configuration options.
Receiving
1
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
61
B
H
D
A
I
G
F
C
E
F
D
I
E
G
J
H
1.4 Bypass Component Names

1.4 Bypass Component Names

This section gives an overview of the bypass components described in this manual.
Note: Arrangement of components differs on models B302 to B414.
A – Bypass bracket mounting hole B – Disconnect shaft C – Bypass enclosure fan D – Bypass front door E – Bypass control board
Figure 1.4 View of Bypass Components
F – Circuit breaker handle G – Z1000U drive H – Bypass enclosure I – HOA keypad J – Floor mount door handle
62
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
HOA keypad
Circuit breaker
F2F1
ESC
M M
AUTO OFF
ENTERRESET
ALM
DIGITAL OPERATOR JVOP-183
HAND
1.5 Bypass Component Descriptions

1.5 Bypass Component Descriptions

u

Bypass Front Control Panel

The external appearance and component names of the bypass are shown in Figure 1.5.
Figure 1.5 Bypass Control Panel with Keypad Operator Controls
Refer to Using the HOA Keypad on page 111 for details on the HOA keypad.
u

Bypass Internal Components

The appearance and internal component names of the bypass are shown in Figure 1.6.
Note: Arrangement of components differs on models B302 to B414.
Receiving
1
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
63
B
G
E
F
M
A
D
A
B
C
D
C
C
G
C
L
H
I
J
K
1.5 Bypass Component Descriptions
A – Main input disconnect B – Motor overload C – Bypass contactor D – Soft starter option PW E – Air filter F – Enclosure cooling fan G – 120 V control transformer
Circuit Breaker (100 kAIC)
n
Electrically located on the input power side of the bypass, the door mounted circuit breaker provides a means of disconnecting
Figure 1.6 Interior View of Bypass Unit
H – Terminal TB1 I – Terminal TB2 J – Terminal TB3 K – Communications port CN2 L – Option card connector CN5 M – Ground terminal
the bypass from line power for equipment maintenance. The circuit breaker must be in the OFF position to open the bypass enclosure door. When opened, the handle can be locked in the OFF position using a padlock.
Branch short circuit protection for the bypass must be supplied by the customer.
Contactors
n
The bypass is a 2-contactor or 3-contactor bypass circuit employing IEC rated contactors in an electrically interlocked arrangement to allow mutually exclusive operation in Drive or Bypass modes.
The control logic and “soft start” characteristic of the drive limit the drive input and output contactors to motor FLA current or less. For this reason, the drive output contactor has a lower current rating than the bypass contactor. The bypass contactor is exposed to motor inrush current (LRA) when starting the motor across-the-line and therefore requires a higher current rating.
64
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
1.5 Bypass Component Descriptions
Use an optional soft starter on the line side of the bypass contactor to limit the current on the bypass circuit to motor FLA or less. In this case, the bypass contactor is tested for a short-circuit combination rating of 65 kA or greater with the soft starter and large enough to handle the motor FLA current.
Overload Relay
n
The adjustable thermal overload relay (OLR) provides overload protection for the motor in Drive and Bypass operating modes. The bypass three-phase output power connection to the motor is made to the output terminals of the OLR. The OLR is set up in the factory to be a manual reset device, requiring operator attention if an overload trip-out is experienced.
Control Power Transformer
n
A Control Power Transformer (CPT) is provided to power the bypass 120 Vac control circuit. The VA capacity is determined by the control circuit and optional functions specified for the unit. The CPT primary is fused in both legs, the secondary is fused when required by NEC (transformer VA and wire size dependent). One side of the transformer secondary is grounded to the bypass enclosure.
Electronic Bypass Control Logic
n
Operating elements such as indicating LEDs, selector buttons, and control logic are incorporated into a PCB assembly to eliminate the potential for loose wires after shipment.
The operating elements are located on PCB A3 and the control logic PCB A2 contains the control circuit field wiring terminal blocks TB1 through TB5.
Drive/Bypass Logic Interlocks
n
The bypass 120 Vac logic circuit is interconnected with the drive multi-function digital input terminals and multi-function digital output terminals to allow a single customer interface to control both drive and bypass circuits. These drive terminals are not available for field connections. All field control connections are landed at terminal blocks TB1 through TB5 on control logic PCB A2 and drive PCB A1.
Receiving
1
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
65
A
A
C
B
B
C
E(G)
IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AMAC 24VRP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
E(G)
IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7S8 SN SC SP
V+AC A1 A2 A3 FM AM AC 24VRPAC
M1 M2 M3 M4
MD ME MF
MA MB MC
1.5 Bypass Component Descriptions
u

Front Views of Drive

A – Terminal board (Refer to Control
Circuit Wiring on page 96)
B – Main circuit terminal (Refer to
Wiring the Main Input Circuit on page 93)
C – EMC filter switch (Drive Models
ZUoEoooo and ZUoWoooo)
Figure 1.7 Front Views of Drives
66
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
2

Mechanical Installation

This chapter explains how to properly mount and install the bypass.
2.1 SECTION SAFETY.................................................................................................68
2.2 MECHANICAL INSTALLATION.............................................................................70
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
67
2.1 Section Safety

2.1 Section Safety

WARNING
Crush Hazard
Use a dedicated lifting device when moving or positioning the drive.
Failure to comply may result in serious injury or death from falling equipment.
Use screws to securely affix the drive front cover, terminal blocks, and other drive components prior to vertical suspension.
Failure to comply may result in serious injury or death from falling equipment.
Do not subject the drive to vibration or impact greater than 1.96 m/s2 (0.2 G) while it is suspended by the cables.
Failure to comply may result in serious injury or death from falling equipment.
Do not attempt to flip the drive over or leave the drive unattended while it is suspended by the wires.
Failure to comply may result in serious injury or death from falling equipment.
CAUTION
Crush Hazard
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
NOTICE
Equipment Hazard
Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during drive installation and project construction.
Failure to comply could result in damage to the drive. Place a temporary cover over the top during installation. Be sure to remove the temporary cover before start-up, as the cover will reduce ventilation and cause the unit to overheat.
Observe proper electrostatic discharge (ESD) procedures when handling the drive.
Failure to comply could result in ESD damage to the drive circuitry.
Operating the motor in the low-speed range diminishes the cooling effects, increases motor temperature, and may lead to motor damage by overheating.
Reduce the motor torque in the low-speed range whenever using a standard blower cooled motor. If 100% torque is required continuously at low speed, consider using a special drive or vector-control motor. Select a motor that is compatible with the required load torque and operating speed range.
The speed range for continuous operation differs according to the lubrication method and motor manufacturer.
If the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer. Continuously operating an oil-lubricated motor in the low-speed range may result in burning.
68
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
2.1 Section Safety
NOTICE
When the input voltage is 480 V or higher or the wiring distance is greater than 100 meters, pay special attention to the motor insulation voltage or use a drive-rated motor with reinforced insulation.
Failure to comply could lead to motor winding failure.
Motor vibration may increase when operating a machine in variable-speed mode, if that machine previously operated at a constant speed.
Install vibration-proof rubber on the motor base or use the frequency jump function to skip a frequency resonating the machine.
The motor may require more acceleration torque with drive operation than with a commercial power supply.
Set a proper V/f pattern by checking the load torque characteristics of the machine to be used with the motor.
The rated input current of submersible motors is higher than the rated input current of standard motors.
Select an appropriate drive according to its rated output current. When the distance between the motor and drive is long, use a cable thick enough to connect the motor to the drive to prevent motor torque reduction.
The current rating for a motor with variable pole pitches differs from a standard motor.
Check the maximum current of the motor before selecting the drive capacity. Only switch motor poles when the motor is stopped. Switching between motor during run will trigger overcurrent protection circuitry or result in overvoltage from regeneration, and the motor will simply coast to stop.
Never lift or move the drive while the cover is removed.
This can damage the terminal board and other components.
Mechanical Installation
2
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
69
2.2 Mechanical Installation

2.2 Mechanical Installation

This section outlines specifications, procedures, and the environment for proper mechanical installation of the bypass.
u

Installation Environment

Install the bypass in an environment matching the conditions below to prolong its optimum performance life.
Table 2.1 Installation Environment
Environment Conditions
Installation Area Indoors
Ambient Temperature
Humidity 95% RH or less and free of condensation
Storage Temperature
Surrounding Area
Altitude Up to 1000 meters without derating. Up to 3000 meters with output current and voltage derating
Orientation Install the bypass vertically to maintain maximum cooling effects.
-10 to + 40 °C (+14 to +104 °F) NEMA Type 1 Enclosure
-20 °C to +60 °C (-4 °F to +104 °F)
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
NOTICE: Avoid placing peripheral devices, transformers, or other electronics near the bypass as the noise created can lead to erroneous operation. If such devices must be used in close proximity to the bypass, take proper steps to shield the bypass from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the bypass during installation. Failure to comply could result in damage to the bypass. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before bypass start-up, as the cover will reduce ventilation and cause the bypass to overheat.
70
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
2.2 Mechanical Installation
u

Installation Orientation and Spacing

Install the bypass upright as illustrated in Figure 2.1 to maintain proper cooling.
Figure 2.1 Correct Installation Orientation
u

Exterior and Mounting Dimensions

Refer to bypass dimension drawing DD.Z1U.1.oo.01 packaged with the bypass for bypass enclosure dimensions and proper installation clearances necessary to maintain sufficient space for airflow and wiring.
Mechanical Installation
2
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
71
2.2 Mechanical Installation
This Page Intentionally Blank
72
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
3

Electrical Installation

This chapter explains the proper procedures for wiring the control circuit terminals, motor, and power supply.
3.1 SECTION SAFETY.................................................................................................74
3.2 STANDARD CONNECTION DIAGRAM.................................................................76
3.3 MAIN CIRCUIT WIRING.........................................................................................80
3.4 INPUT AND OUTPUT POWER WIRING CONNECTIONS....................................85
3.5 CONTROL CIRCUIT WIRING................................................................................96
3.6 BYPASS AND DRIVE CONTROL I/O CONNECTIONS......................................105
3.7 EXTERNAL INTERLOCK.....................................................................................107
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
73
3.1 Section Safety

3.1 Section Safety

WARNING
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply may result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply
is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait for at least the time specified on the warning label, once all indicators are OFF, measure for unsafe voltages to confirm the drive is safe prior to servicing.
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or
shields before operating the drives and run the drives according to the instructions described in this manual.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
Because the leakage current exceeds 3.5 mA, IEC/EN 61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor with a cross­section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to comply may result in death or serious injury.
Always use appropriate equipment for Ground Fault Circuit Interrupters (GFCIs).
The drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual current operated protective or monitoring device is used for protection in case of direct or indirect contact, always use a type B GFCI according to IEC/EN 60755.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work
on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with
installation, adjustment, and maintenance of AC drives.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply
is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait for at least the time specified on the warning label, once all indicators are OFF, measure for unsafe voltages to confirm the drive is safe prior to servicing.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire. Do not install the drive to a combustible surface. Never place combustible materials on the drive.
74
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
3.1 Section Safety
WARNING
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Properly handle the HOA keypad battery.
Improper use of the battery may cause fire by explosion and personal injury. Correctly install the battery, paying attention to polarity (+/-). Do not attempt to charge the battery or improperly disassemble the HOA keypad.
CAUTION
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices.
Failure to comply could result in damage to the drive.
Do not heat or throw the battery into fire.
The battery remains in use even when power to the drive has been shut off. Be sure to also remove the battery in the HOA keypad when the drive will be shut off for long periods of time.
A dead battery left inside the HOA keypad may leak and damage the keypad and drive. Be sure to replace the battery with a new one immediately after the expected lifespan has passed or when the “bAT” error is displayed on the HOA keypad.
Be sure to observe the Perchlorate Best Management Practices (BMPs).
BMPs apply to primary lithium (manganese dioxide) coin batteries sold or distributed in California. Perchlorate Material­special handling may apply, please refer to: www.dtsc.ca.gov/hazardouswaste/perchlorate.
Electrical Installation
3
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
75
3.2 Standard Connection Diagram

3.2 Standard Connection Diagram

Connect the bypass and peripheral devices as shown in Figure 3.1. It is possible to set and run the bypass via the HOA keypad without connecting digital I/O wiring. This section does not discuss drive operation; Refer to Start-Up Programming &
Operation on page 109 for instructions on operating the drive.
WARNING! Fire Hazard. Branch Circuit protection is required to be installed according to applicable local codes and the requirements listed on the bypass nameplate. Failure to comply could result in fire and damage to the bypass and drive or injury to personnel. Bypass models without soft-starter option PW are suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 208 Vac and 480 Vac. Bypass models D169 to D211 and B180 to B414 with option PW are also suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 208 Vac and 480 Vac. Bypass models D024 to D143 and B011 to B156 with option PW are suitable for use on a circuit capable of delivering not more than 65,000 RMS symmetrical amperes, 208 Vac and 480 Vac.
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to the motor insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.
NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
Note: The minimum load for relay outputs DO-7, DO-8, DO-9, DO-10, M1-M2, M3-M4, M5-M6, and MA-MB-MC is 10 mA.
WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction input terminal parameters are properly set. Improper sequencing of run/stop circuitry could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. Ensure start/stop circuits are wired properly and in the correct state before energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary closure on terminal S1 may cause the drive to start.
WARNING! Sudden Movement Hazard. When using a 3-Wire sequence, set the drive to 3-Wire sequence prior to wiring the control terminals and set parameter b1-17 to 0 so the drive will not accept a Run command at power up (default). If the drive is wired for a 3-Wire sequence but set up for a 2-Wire sequence (default), and parameter b1-17 is set to 1 so the drive accepts a Run command at power up, the motor will rotate in reverse direction at drive power up and may cause injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before executing the application preset function. Executing the application preset function or setting A1-06 ≠ 0 will change the drive I/O terminal functions and may cause unexpected equipment operation. Failure to comply may cause death or serious injury.
NOTICE: When using the automatic fault restart function with wiring designed to shut off the power supply upon drive fault, make sure the drive does not trigger a fault output during fault restart (L5-02 = 0, default). Failure to comply will prevent the automatic fault restart function from working properly.
76
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
<4>
3.2 Standard Connection Diagram
<3>
<1>
<6>
<6>
<7>
<9>
<2>
<1>
<5>
<10>
Electrical Installation
3
<1>
<2>
<8>
Figure 3.1 Z1000U Bypass Standard Connection Diagram
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
77
3.2 Standard Connection Diagram
This Page Intentionally Blank
78
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
3.2 Standard Connection Diagram
<1> Connect the cabinet ground lug to earth ground and utility ground.
<2> Insulated twisted shielded wire is required. Connect the shield only at one end to avoid ground loops. Do not run these wires in the same conduit as AC power or AC control wires.
<3> Secondary fuse F6 is added with control transformer T1 or a power rating 350 VA or greater.
<4> Set E1-05 to 208 for 208 Vac applications.
<5> The motor overload relay is factory set for manual reset. Adjust the motor overload relay trip setting for the actual AC motor full load amps.
<6> Bypasses with option PW should set Z1-42 to 1, and Z2-07 to 36 and Z2-15 to 1 to trigger an “EFb” fault with the motor coasting to stop when the soft starter faults.
<7> R1 is a fail-safe contact. It is shown de-energized.
<8> Set DIP switch S1 to the ON position to enable the termination resistor only in the last drive in a MEMOBUS/Modbus network.
<9> The maximum output current capacity for the +V terminal on the control circuit is 20 mA. Never short terminals +V and AC, as it can cause erroneous operation or damage the drive.
<10> Use jumper S5 to select between voltage or current output signals at terminals FM and AM. Set parameters H4-07 and H4-08 accordingly.
Electrical Installation
3
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
79
OFF
ON
3.3 Main Circuit Wiring

3.3 Main Circuit Wiring

This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in the bypass.
NOTICE: Do not solder the ends of wire connections to the bypass. Soldered wiring connections can loosen over time. Improper wiring practices could result in malfunction due to loose terminal connections.
NOTICE: Do not switch the bypass input to start or stop the motor. Frequently switching the bypass on and off shortens the life of the DC bus charge circuit and the DC bus capacitors, and can cause premature bypass failures. For the full performance life, refrain from switching the bypass on and off more than once every 30 minutes.
u

Opening the Bypass Enclosure

WARNING! Electrical Shock Hazard. Do not open the bypass enclosure while the power is on. Failure to comply may result in death or
serious injury. Make sure that the circuit breaker is in the “OFF” position before attempting to open the doors.
Models D024 to D114 and B011 to B124
n
Turn the circuit breaker to the “OFF” position.
1.
80
Figure 3.2 Disconnect Power
Turn the flat head screw fasteners on the cover 1/2 turn counter-clockwise.
2.
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
OFF
ON
Figure 3.3 Turn Fasteners
3.3 Main Circuit Wiring
Door will now swing open on hinges located on left side of the bypass.
3.
Electrical Installation
3
Figure 3.4 Swing Open Door
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
81
3.3 Main Circuit Wiring
Models D143 to D211, B156 to B240, and B302 to B414
n
Move the circuit breaker handle to the “OFF” position.
1.
Figure 3.5 Disconnect Power
Turn the door handle 1/4 towards the door hinges and open the door.
2.
Note: Models B302 to B414 have two doors.
82
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
3.3 Main Circuit Wiring
Figure 3.6 Turn Door Handle
Electrical Installation
3
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
83
D024 to D114 B011 to B124
D143 to D211 B156 to B414
L1 L2 L3
T1 T2 T3
T1 T2 T3
L1 L2 L3
3.3 Main Circuit Wiring
u

Bypass Main Circuit Terminal Block Configuration

Figure 3.7 shows the different main circuit terminal arrangements by model.
Figure 3.7 Main Circuit Terminal Block Configuration
84
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
C
G
E
F
A
B
D
H
I
3.4 Input and Output Power Wiring Connections

3.4 Input and Output Power Wiring Connections

The input disconnect switch is located in the upper right hand side of the bypass. The three-phase input power connection is made to the input terminals of the disconnect. Refer to Figure 3.8 for a representative example.
The Overload Relay (OLR) is mounted to the contactor assembly or back panel (depending on rating), just above the bypass contactor. The bypass three-phase output power connection to the motor is made to the output terminals of the Overload Relay.
A – Ground screw B – Input power terminals C – Motor overload relay D – Motor connections E – Drive output contactor K2
u

Factory Recommended Branch Circuit Protection

WARNING! Fire Hazard. Branch Circuit protection is required to be installed according to applicable local codes and the requirements listed
on the bypass nameplate. Failure to comply could result in fire and damage to the bypass and drive or injury to personnel. Bypass models without soft-starter option PW are suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 208 Vac and 480 Vac. Bypass models D169 to D211 and B180 to B414 with option PW are also suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 208 Vac and 480 Vac. Bypass models D024 to D143 and B011 to B156 with option PW are suitable for use on a circuit capable of delivering not more than 65,000 RMS symmetrical amperes, 208 Vac and 480 Vac.
Figure 3.8 Bypass Circuit Components
F – Bypass contactor K3 G – 120 V control transformer H – A2 bypass control board I – 5 V bypass power supply board
Yaskawa recommends installing branch circuit protection according to maintain compliance with UL508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in this manual.
Electrical Installation
3
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
85
3.4 Input and Output Power Wiring Connections
u

Main Circuit Terminal Functions

Table 3.1 Main Circuit Terminal Functions
Terminal Description Function Page
1/L1
Main circuit power supply input Connects line power to the bypass 762/L2
3/L3
1/T1
Drive output Connects to the motor 762/T2
3/T3
For 208 Vac: 100 Ω or less
For 480 Vac: 10 Ω or less
u

Wire Gauge and Tightening Torque Specifications

Note: 1. For 0 to 100 A, use a minimum of 60 °C - 75 °C copper wire.
2. For above 100 A, use a minimum of 75 °C copper wire.
3. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient
temperature within 40 °C and wiring distance less than 100 m.
Grounding terminal 88
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
Refer to UL Standards Compliance on page 450 for information on UL compliance.
Table 3.2 Main Input Circuit Wiring Tightening Torques and Wire Gauges With Option PW
Bypass Model Z1D1 Standard Circuit Breaker With Option PW
208 Vac 480 Vac Current Rating (A) Wire Size Range (AWG) Tightening Torque (lb. in.)
B011 25
B014 30
B021 45
D024 B027 60
D030 B034 70
B040 80
D046 B052 110
D059 B065 125
D074 B077
150D088 B096
D114
B124
D143 B156
D169 B180
D211 400
B032
B361
B414
250
600
(1-2) x (2/0-500 kcmil) (1-2) x 442 B240
(1-3) x (3/0-500 kcmil) (1-3) x 450
14-10
or
8-3/0
4-4/0 225
3/0-350 kcmil 225
50
or
120
86
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
3.4 Input and Output Power Wiring Connections
Table 3.3 Main Input Circuit Wiring Tightening Torques and Wire Gauges Without Option PW
Bypass Model Z1D1 Standard Circuit Breaker Without Option PW
208 Vac 480 Vac Current Rating (A) Wire Size Range (AWG) Tightening Torque (lb. in.)
B011
B014
B021 40
D024 45
B027 50
D030 B034 60
B040 80
D046 B052
D074 B077
D088 B096 125
D114 175
B156 225
D169 B180
D211
B240
B032
B361
B414
25
110D059 B065
400
600
14-10
or
8-3/0
4-4/0 225D143 B124 200
(1-2) x (2/0-500 kcmil) (1-2) x 442
(1-3) x (3/0-500 kcmil) (1-3) x 450
50
or
120
Table 3.4 Motor and Ground Wire Gauges and Tightening Torques
Bypass Model Z1D1
208 Vac 480 Vac Wire Size Range (AWG)
B011
B014
D024 B021
D030 B027
B034
B040
D046
D059 B052
B065
D074 B077
D088 B096
D143
D169 B156
B180
D211 B240
(1-2) x (2-600 kcmil) (1-2) x 500 B302
B361
B414 (1-3) x (2-600 kcmil) (1-3) x 500
Output Circuit Motor Wiring Earth Ground Wiring
Motor Overload Relay Ground Lug
Tightening Torque
18-8 15
16-2 70
10-1/0 100
6-3/0 200D114 B124
6–300 kcmil 275
(lb. in.)
Wire Size Range (AWG)
14-10 or 8
or
6-4 or 2
14-2/0 120
Tightening Torque
(lb. in.)
35 or 40
or
45 or 50
Electrical Installation
3
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
87
3.4 Input and Output Power Wiring Connections
u

Main Input Circuit and Motor Wiring

This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
WARNING! Electrical Shock Hazard. Do not connect the AC power line to the bypass output terminals. Failure to comply could result in death or serious injury by fire as a result of bypass damage from line voltage application to output terminals.
NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to comply may result in abnormal operation of drive and nearby equipment.
NOTICE: When connecting the motor to the output terminals T1, T2, and T3, the phase order for the drive and motor should match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.
Cable Length Between Bypass and Motor
n
Voltage drop along the motor cable may cause reduced motor torque when the wiring between the bypass and the motor is too long, especially at low frequency output. This can also be a problem when motors are connected in parallel with a fairly long motor cable. Bypass output current will increase as the leakage current from the cable increases. An increase in leakage current may trigger an overcurrent situation and weaken the accuracy of the current detection.
Adjust the carrier frequency according to Table 3.5. If the motor wiring distance exceeds 100 m because of the system configuration, reduce the ground currents. Refer to C6-02: Carrier Frequency Selection on page 154.
Table 3.5 Cable Length Between Bypass and Motor
Cable Length 50 m or less 100 m or less Greater than 100 m
Carrier Frequency 12.5 kHz or less 5 kHz or less 2 kHz or less
Note: 1. When setting carrier frequency for bypasses running multiple motors, calculate cable length as the total wiring distance to all connected
Ground Wiring
n
motors.
2. Do not use a long distance shielded line if there is an overvoltage problem at start. Either lower the carrier frequency or switch on the internal EMC filter if the power supply has a neutral ground.
Follow the precautions below when wiring the ground for one bypass or a series of bypasses.
WARNING! Electrical Shock Hazard. Do not touch SW screw while power is applied to the drive. Failure to comply could result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait for at least the time specified on the warning label, once all indicators are OFF, measure for unsafe voltages to confirm the drive is safe prior to servicing.
WARNING! Electrical Shock Hazard. Make sure the protective earthing conductor complies with technical standards and local safety regulations. Because the leakage current exceeds 3.5 mA, IEC/EN 61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to comply may result in death or serious injury.
WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could result in death or serious injury.
WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal (208 Vac: ground to 100 Ω or less and 480 Vac: ground to 10 Ω or less). Improper equipment grounding could result in death or serious injury by contacting ungrounded electrical equipment.
NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper equipment grounding could result in drive or equipment malfunction due to electrical interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in abnormal operation of drive or equipment.
Refer to Figure 3.9 when using multiple drives. Do not loop the ground wire.
The drive ground lug (terminal
) is connected to the enclosure. The enclosure ground lug must be connected to earth ground.
See Figure 3.8.
The drive has a second ground lug to accept the motor ground lead.
88
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
3.4 Input and Output Power Wiring Connections
Figure 3.9 Ground Wiring for Multiple Bypass Units
Enable the Internal EMC Filter
n
If EMC is a concern and the network is grounded symmetrically, install the SW screw to the ON position. Installing the SW screw enables the internal EMC filter (Drives are shipped with the SW screw installed at the OFF position).
DANGER! Electrical Shock Hazard. Do not touch SW screw while power is applied to the drive. Failure to comply will result in death or serious injury.
WARNING! Electrical Shock Hazard. Connect the ground cable correctly. Failure to comply may result in death or serious injury.
NOTICE: When disabling the internal EMC filter, move the screws from ON to OFF and then tighten to the specified torque. Completely
removing the screws or tightening the screws to an incorrect torque may cause drive failure.
Note: For floating, impedance grounded, or asymmetrically grounded networks, disconnect the internal EMC filter by moving the SW screw to
the OFF position.
Table 3.6 shows asymmetrical grounded networks. Asymmetrical networks require first moving the SW screw to disconnect
the internal ground connection. (Drives are shipped with the SW screw installed at the OFF position.)
Table 3.6 Asymmetrical Grounded Network
L1
Electrical Installation
3
Grounded at the corner of the delta
Grounded at the middle of the side
Single-phase, grounded at the end point
L3
L2
L1
L2L3
L1
N
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
89
L1
L2
L3
L1
L2
L3
ON
OFF
SW
A
B
E(G)
IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC 24VRP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
3.4 Input and Output Power Wiring Connections
Three-phase variable transformer without solidly grounded neutral
L1
L3
Figure 3.10 Symmetrical Grounded Network
A – SW (ON) B – Screw (OFF)
Figure 3.11 EMC Filter Switch Location
(Models 2E0028, 2W0028, 4E0011 to 4E0034, and 4W0011 to 4W0034)
L2
90
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
ON
OFF
SW
A
B
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC 24VRP AC
MD ME MF
MA MB MC
ON
OFF
SW
A
B
3.4 Input and Output Power Wiring Connections
A – SW (ON) B – Screw (OFF)
Figure 3.12 EMC Filter Switch Location
(Models 2E0042, 2W0042, 2E0054, 2W0054, 4E0040 to 4E0077, and 4W0040 to 4W0077)
Electrical Installation
3
A – SW (ON)
Figure 3.13 EMC Filter Switch Location
(Models 2E0104, 2W0104, 2E0130, 2W0130, 4E0096, 4W0096, 4E0124, and 4W0124)
B – Screw (OFF)
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
91
A
B
B
A
B
A
3.4 Input and Output Power Wiring Connections
A – SW (ON) B – Screw (OFF)
Figure 3.14 EMC Filter Switch Location
(Models 2E0154, 2W0154, 2E0192, 2W0192, 4E0156, 4W0156, 4E0180, and 4W0180)
A – SW (ON)
B – Screw (OFF)
Figure 3.15 EMC Filter Switch Location
(Models 2E0248, 2W0248, 4EU0216, 4W0216, 4E0240, and 4W0240)
92
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
A
B
B A
n1 p1
3.4 Input and Output Power Wiring Connections
A – SW (ON) B – Screw (OFF)
Figure 3.16 EMC Filter Switch Location
(Models 4E0302 to 4E0414 and 4W0302 to 4W0414)
u

Wiring the Main Input Circuit

WARNING! Electrical Shock Hazard. Shut off the power supply to the drive before wiring the main circuit terminals. Failure to comply may
result in death or serious injury.
Wire the main circuit terminals after the terminal board has been properly grounded.
Electrical Installation
3
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
93
3.4 Input and Output Power Wiring Connections
Main Input Circuit Wire Routing
n
Figure 3.17 shows suggested wire entry and bending areas for representative enclosures.
NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to comply may result in abnormal operation of drive and nearby equipment.
94
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
C
B
E(G)
IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6S7 S8SN SCSP
V+AC A1 A2 A3FM AM AC 24VRPAC
M1 M2 M3 M4
MD ME MF
MA MB MC
C
B
E(G)
IG R+ R- S+ S-
S1S2 S3 S4S5 S6 S7 S8 SN SC SP
V+AC A1 A2 A3 FM AM AC 24VRPAC
M1 M2 M3 M4
MD ME MF
MA MB MC
A
Models D024 to D114 and B011 to B124
Models D143 to D211 and B156 to B414
A
3.4 Input and Output Power Wiring Connections
A – Control, frequency reference, and
communications wiring
B – Motor output circuit
Figure 3.17 Bypass Wire Routing Example
C – Main input circuit
Electrical Installation
3
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
95
12. SHIELD
11. SHIELD
10. IG24
9. IG24
8. DI-8
7. DI-7
6. DI-6
5. DI-5
4. DI-4
3. DI-3
2. DI-2
1. DI-1
TB2
TB3
4. SHIELD
3. TXRX-
2. TXRX+
1. IG5
TB1
12. DO-10 NO
11. DO-10 C
10. DO-10 NC
9. DO-9 NO
8. DO-9 C
7. DO-9 NC
6. DO-8 NO
5. DO-8 C
4. DO-8 NC
3. DO-7 NO
2. DO-7 C
1. DO-7 NC
3.5 Control Circuit Wiring

3.5 Control Circuit Wiring

u

Control Circuit Connection Diagram

Refer to Figure 3.1 on page 77 when wiring terminals on the bypass and drive control circuits.
u

Control Circuit Terminal Block Functions

WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a bypass with
untested control circuits could result in death or serious injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting parameter Z1-01 may change the I/O terminal function automatically from the default setting. Refer to Application Selection on page 123. Failure to comply may result in death or serious injury.
The functions of the control circuit terminals are shown in Table 3.7.
The control circuit terminals on Terminal Board A2 are arranged as shown in Figure 3.18.
Type Signal Name Description Specification
Digital Inputs
96
DI-1 Digital Input 1
DI-2 Digital Input 2
DI-3 Digital Input 3
DI-4 Digital Input 4
DI-5 Digital Input 5
DI-6 Digital Input 6
DI-7 Digital Input 7
DI-8 Digital Input 8
IG24 Isolated Ground Digital Input Common
Figure 3.18 Control Circuit Terminal Board A2 Arrangement
Table 3.7 Bypass Control Circuit Terminal Board A2
Dry contact rated, photocoupler sinking input to IG, 24 Vdc 8 mA,
ground fault protected
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
E(G)
IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC 24VRP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
E(G)
IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC 24VRP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
TB5
3.5 Control Circuit Wiring
Type Signal Name Description Specification
DO-1 Digital Output 1
DO-2 Digital Output 2
Digital Outputs
120 Vac
DO-3 Digital Output 3
(Factory use only) 120 Vac, 66 VA sealed, 1650 inrush
DO-4 Digital Output 4
DO-5 Digital Output 5
DO-6 Digital Output 6
Digital Outputs
DO-7 Digital Output 7
DO-8 Digital Output 8
DO-9 Digital Output 9
Relay, dry contact form C, 30 Vdc or 120 Vac,
DO-6 (factory use only), 3.7 Amp 360 VA,
DO-7 to DO-10 for customer use, 2 Amp
DO-10 Digital Output 10
Table 3.8 lists the available control circuit input terminals on the drive. Text in parenthesis indicates the default setting for
each multi-function input.
The drive control circuit terminals on Terminal Board A1 are arranged as shown in Figure 3.19.
Figure 3.19 Control Circuit Terminal Arrangement
Table 3.8 Control Circuit Input Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting Page
+V Power supply for analog inputs 10.5 Vdc (max allowable current 20 mA) 208
+24 Vdc transducer power supply for customer
Analog Inputs
24 V
use
Multi-function analog input 1
A1
(Frequency reference bias)
Multi-function analog input 2
A2
(Frequency reference bias)
Multi-function analog input 3
A3
(Aux reference 1)
150 mA maximum capacity
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-01.
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-09.
208 174
208 208 176
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
208
• Voltage or current input must be selected by jumper S1 and H3-05.
AC Frequency reference common 0 V 208
E (G) Ground for shielded lines
u

Bypass Analog Outputs

There are two analog outputs that can be configured for a signal level of 0 to 10 Vdc or 4 to 20 mA. The signal level is controlled by the position of jumpers J2 and J3 on Control PCB A2 and by the values set to drive parameters H4-07 and H4-08.
Electrical Installation
3
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
97
3.5 Control Circuit Wiring
u

Serial Communications

Refer to BACnet Communications on page 361 or Refer to MEMOBUS/Modbus Communications on page 381 for details
depending on the applicable serial communications protocol.
Serial Communication Terminals
n
Table 3.9 Control Circuit Terminals: Serial Communications
Type Name Description Notes
Ground reference for RS-485 signals. This is an isolated ground
MEMOBUS/Modbus, BACnet, Metasys N2, or Apogee P1 Communication
Bypass and Drive Control Circuit Wire Size and Torque Specifications
n
IG5 Isolated ground
TXRX+ (+) Differential communication signal
TXRX- (-) Differential communication signal
SHIELD Shield tie point Connected to chassis ground
used only for communications and may be used in certain circumstances to connect to other communication devices floating ground references.
RS-485 signal levels
Select appropriate wire type and gauges from Table 3.10. For simpler and more reliable wiring, use crimp ferrules on the wire ends. Refer to Table 3.11 for ferrule terminal types and sizes.
Table 3.10 Bypass and Drive Control Circuit Gauge and Torque Values
Bare Wire Terminal Ferrule-Type Terminal
Applicable
wire size
mm2 (AWG)
Stranded wire:
0.2 to 1.0
(24 to 16)
Solid wire:
0.2 to 1.5
(24 to 16)
Stranded wire:
0.2 to 1.0
(24 to 16)
Solid wire:
0.2 to 1.5
(24 to 16)
Recomm.
wire size
mm2 (AWG)
0.75 (18)
0.75 (18)
Applicable
wire size
mm2 (AWG)
0.25 to 0.5 (24 to 20)
0.25 to 0.5 (24 to 20)
Recomm.
wire size
mm2 (AWG)
0.5 (20)
0.5 (20)
Wire Type
Shielded wire, etc.
Shielded wire, etc.
Terminal
DO-7, DO-8, DO-9, DO-10 DI-1, DI-2, DI-3, DI-4, DI-5, DI-6, DI-7, DI-8, IG24 IG5, TXRX+, TXRX-, SHIELD
+V, A1, A2, AC FM, AM, AC R+, R-, S+, S-, IG
Screw
Size
M3
M3
Tightening
Torque
Nm
(lb. in)
0.5 to 0.6
(4.4 to 5.3)
0.5 to 0.6
(4.4 to 5.3)
Ferrule-Type Wire Terminals
n
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire ends with insulated sleeves before connecting to the drive. See Table 3.11 for dimensions.
d1
8 mm
L
d2
Figure 3.20 Ferrule Dimensions
Table 3.11 Ferrule Terminal Types and Sizes
98
2
Size mm
(AWG)
0.25 (24) AI 0.25-8YE 12.5 0.8 1.8
0.34 (22) AI 0.34-8TQ 10.5 0.8 1.8
0.5 (20)
Type L (mm) d1 (mm) d2 (mm) Manufacturer
AI 0.5-8WH or
AI 0.5-8OG
14 1.1 2.5
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
PHOENIX CONTACT
u
<1>

Drive Cover Removal

Follow the procedures below to remove and reattach the drive covers for wiring.
u

Drives in Bypass Models D024 to D114 and B011 and B124

Removing the Terminal Cover
n
Loosen the terminal cover screw.
1.
3.5 Control Circuit Wiring
Figure 3.21 Removing the Terminal Cover
Push in on the tab located on the bottom of the terminal cover and gently pull forward to remove the terminal cover.
2.
Figure 3.22 Removing the Terminal Cover
Reattaching the Terminal Cover
n
Power lines and signal wiring should pass through the opening provided. Refer to Wiring the Main Input Circuit on page
93 and Wiring the Drive Control Circuit Terminal on page 102 for details on wiring.
Reattach the terminal cover after completing the wiring to the drive and other devices.
Electrical Installation
3
Figure 3.23 Reattaching the Terminal Cover
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
99
<1>
3.5 Control Circuit Wiring
<1> Connect the ground wiring first, then the main circuit wiring, and finally the control circuit wiring.
u

Drives in Bypass Models D143 to D211 and B156 to B414

Removing the Terminal Cover
n
Loosen the screws on the terminal cover, then pull down on the cover.
1.
CAUTION! Do not completely remove the cover screws, just loosen them. If the cover screws are removed completely, the terminal
cover may fall off causing an injury.
Figure 3.24 Removing the Terminal Cover
Pull forward on the terminal cover to free it from the drive.
2.
Figure 3.25 Removing the Terminal Cover
Reattaching the Terminal Cover
n
After wiring the terminal board and other devices, double-check connections and reattach the terminal cover. Refer to Wiring
the Main Input Circuit on page 93 and Wiring the Drive Control Circuit Terminal on page 102 for details on wiring.
Figure 3.26 Reattaching the Terminal Cover
<1> Connect the ground wiring first, then the main circuit wiring, and finally the control circuit wiring.
u

Removing/Reattaching the Front Cover

Removing the Front Cover
n
Models 2o0028 to 2o0130 and 4o0011 to 4o0124
100
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
Loading...