Yaskawa VARISPEED-616G5 User Manual

YASKAWA
VARISPEED-616G5
INSTRUCTION MANUAL
MULTI-FUNCTION ALL-DIGITAL TYPE (VS-616G5)
MODEL: CIMR-G5A
SPEC: F 200V CLASS 0.4 to 75kW (1.2 to 110kVA) 400V CLASS 0.4 to 300kW (1.4 to 460kVA)
Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference.
YA S K A WA
MANUAL NO. TOE-S616-10.30
Preface
Preface
The VARISPEED-616G5 Series of general-purpose Inverters provides V/f control and vector con-
trol as standard features along with user-friendly operation.
This manual is designed to ensure correct and suitable application of VARISPEED-616G5-series
Inverters. Read this manual before attempting to install, operate, maintain, or inspect an Inverter and
keep it in a safe, convenient location for future reference. Be sure you understand all precautions
and safety information before attempting application.
i

Safety Information

The following conventions are used to indicate precautions in this manual. Failure to heed precautions provided in this manual can result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
WARNING
!
Indicates precautions that, if not heeded, could possibly result in loss of life or serious injury.
CAUTION Indicates precautions that, if not heeded, could result in relatively serious or minor
!
injury, damage to the product, or faulty operation.
The warning symbols for ISO and JIS standards are different, as shown below.
ISO JIS
The ISO symbol is used in this manual. Both of thesesymbolsappearonwarninglabels on Yaskawaproducts. Please abide by thesewarninglabelsregard-
less of which symbol is used.
Yaskawa, 1998
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
ii

Visual Aids

The following aids are used to indicate certain types of information for easier reference.
Visual Aids
A
EXAMPLE
INFO
IMPORTANT
"
Indicates application examples.
Indicates supplemental information.
Indicates important information that should be memorized.
iii

General Precautions

D The diagrams in this manual may be indicated without covers or safety shields to show de-
tails. Be sure to restore covers or shields before operating the Units and run the Units ac­cording to the instructions described in this manual.
D Any illustrations, photographs, or examples used in this manual are provided as examples
only and may not apply to all products to which this manual is applicable.
D The products and specifications described in this manual or the content and presentation
of the manual may be changed without notice to improve the product and/or the manual.
D When ordering a new copy of the manual due to damage or loss, contact your Yaskawa rep-
resentatives or the nearest Yaskawa sales office and provide the manual number shown on the front cover.
D If nameplates become warn or damaged, order new ones from your Yaskawa representa-
tives or the nearest Yaskawa sales office.
iv

Safety Precautions

Confirmations upon Delivery
J
D Never install an Inverter that is damaged or missing components.
Doing so can result in injury.
J Installation
D Always hold the case when carrying the Inverter.
If theInverterisheldbythefrontcover,the main body of the Inverter may fall, possibly result­ing in injury.
D Attach the Inverter to a metal or other noncombustible material.
Fire can result if the Inverter is attached to a combustible material.
D Install a cooling fan or other cooling device when installing more than one Inverter in
the same enclosure so that the temperature of the air entering the Inverters is below 45_C.
Overheating can result in fires or other accidents.
Safety Precautions
CAUTION
Page 2-2
CAUTION
Page
2-6
2-6
2-6
J Wiring
WARNING
D Always turn OFF the input power supply before wiring terminals.
Otherwise, an electric shock or fire can occur.
D Wiring must be performed by an authorized person qualified in electrical work.
Otherwise, an electric shock or fire can occur.
D Be sure to ground the ground terminal.
(200 V class: Ground to 100 or less, 400 V class: Ground to 10 Ω or less) Otherwise, an electric shock or fire can occur.
D Always check the operation of any emergency stop circuits after they are wired.
Otherwise, there is the possibility of injury. (Wiring is the responsibility of the user.)
D Never touch the output terminals directly with your hands or allow the output lines to
come into contact with the Inverter case. Never short the output circuits.
Otherwise, electric shock or grounding can occur.
CAUTION
D Check to be sure that the voltage of the main AC power supply satisfies the rated
voltage of the Inverter.
Injury or fire can occur if the voltage is not correct.
D Do not perform voltage withstand tests on the Inverter.
Otherwise, semiconductor elements and other devices can be damaged.
D Connect braking resistors, Braking Resistor Units, and Braking Units as shown in the
I/O wiring examples.
Otherwise, a fire can occur.
D Tighten all terminal screws to the specified tightening torque.
Otherwise, a fire may occur.
Page
3-2
3-2
3-2
3-2
3-2
Page
3-2
3-2
3-2
3-2
v
D Do not connect AC power to output terminals U, V, and W.
The interior parts of the Inverter will be damaged if voltage is applied to the output terminals.
D Do not connect phase-advancing capacitors or LC/RC noise filters to the output cir-
cuits.
The Inverter can be damaged or internal parts burnt if these devices are connected.
D Do not connect electromagnetic switches or contactors to the output circuits.
If a load is connected while the Inverter is operating, surge current will cause the overcurrent protection circuit inside the Inverter to operate.
J Setting User Constants
D Disconnect the load (machine, device) from the motor before autotuning.
The motor may turn, possibly resulting in injury or damage to equipment. Also, motor constants cannot be correctly set with the motor attached to a load.
J Trial Operation
D Check to be sure that the front cover is attached before turning ON the power supply.
Do not remove the front cover during operation.
An electric shock may occur.
D Do not come close to the machine when the fault reset function is used. If the alarmed
is cleared, the machine may start moving suddenly.
Also, design the machine so that human safety is ensured even when it is restarted. Injury may occur.
D Provide a separate emergency stop switch; the Digital Operator STOP Key is valid
only when its function is set.
Injury may occur.
D Reset alarms only after confirming that the RUN signal is OFF.Ifanalarmis reset with
the RUN signal turned ON, the machine may suddenly start.
Injury may occur.
CAUTION
Page
3-2
3-2
3-2
CAUTION
Page
4-30
WARNING
Page
5-2
5-2
5-2
5-2
CAUTION
D Don’t touch the radiation fins (heat sink), braking resistor, or Braking Resistor Unit.
These can become very hot.
Otherwise, a burn injury may occur.
D Be sure that the motor and machine is within the applicable ranges before starting
operation.
Otherwise, an injury may occur.
D Provide a separate holding brake if necessary.
Always construct the external sequence to confirm that the holding brake is activated in the event of an emergency,a power failure, or an abnormality in the inverter occur­ing.
Failure to observe this caution can result in personal injury.
D If using with an elevator, take safety measures on the machine’s side to prevent the
elevator from dropping.
Failure to observe this caution can result in personal injury.
vi
Page
5-2
5-2
5-2
5-2
CAUTION
Safety Precautions
D Don’t check signals while the Inverter is running.
Otherwise, the equipment may be damaged.
D Be careful when changing Inverter settings. The Inverter is factory set to suitable set-
tings.
Otherwise, the equipment may be damaged. You must, however, you must set the power sup­ply voltage jumper for 400 V class Inverters of 18.5 kW or higher (see 5.2.4).
J Maintenance and Inspection
D Do not touch the Inverter terminals. Some of the terminals carry high voltages and
are extremely dangerous.
Doing so can result in electric shock.
D Always have the protective cover in place when power is being supplied to the Invert-
er. When attaching the cover, always turn OFF power to the Inverter through the MCCB.
Doing so can result in electric shock.
D After turning OFF the main circuit power supply, wait until the CHARGE indicator light
goes out before performing maintenance or inspections.
The capacitor will remain charged and is dangerous.
D Maintenance, inspection, and replacement of parts must be performed only by au-
thorized personnel. Remove all metal objects, such as watches and rings, before starting work. Always
use grounded tools.
Failure to heed these warning can result in electric shock.
5-2
5-2
WARNING
Page
10-2
10-2
10-2
10-2
J Other
CAUTION
Page
D A CMOS IC is used in the control board. Handle the control board and CMOS IC care-
fully. The CMOS IC can be destroyed by static electricity if touched directly.
D Do not change the wiring, or remove connectors or the Digital Operator, during op-
eration.
Doing so can result in personal injury.
10-2
10-2
WARNING
D Do not attempt to modify or alter the Inverter.
Doing so can result in electric shock or injury.
CAUTION
D Do not subject the Inverter to halogen gases, such as fluorine, chlorine, bromine, and iodine, at
any time even during transportation or installation.
Otherwise, the Inverter can be damaged or interior parts burnt.
vii

Warning Label Contents and Position

There is a warning label on the Inverter in the position shown in the following illustration. Always heed the warn­ings given on this label.
Warning label position
Illustration shows the CIMR-G5A23P7
Warning Label Contents
viii

How to Change the Digital Operator Display from Japanese to English

How to Change the Digital Operator Display from Japanese to English
If the Digital Operator displays messages in Japanese, change to the English mode using the follow-
ing steps.
(This manual provides descriptions for the English mode.)
ix

Warranty Information

J Free Warranty Period and Scope
Warranty Period
This product is warranted for twelve months after being delivered to Yaskawa’s customer or if appli-
cable eighteen months from the date of shipment from Yaskawa’s factory whichever comes first.
Scope of Warranty
Inspections
Periodic inspections must be conducted by the customer. However, upon request, Yaskawa or one
of Yaskawa’s Service Centers can inspect the product for a fee. In this case, if after conferring with
the customer, a Yaskawa product is found to be defective due to Yaskawa workmanship or materials
and the defect occurs during the warranty period, then this fee will be waived and the problem reme-
died free of charge.
Repairs
If a Yaskawa product is found to be defective due to Yaskawa workmanship or materials and the de-
fect occurs during the warranty period, Yaskawa will provide a replacement, repair the defective
product, and provide shipping to and from the site free of charge.
However, if the Yaskawa Authorized Service Center determines that the problem with a Yaskawa
product is not due to defects in Yaskawa’s workmanship or materials, then the customer will be re-
sponsible for the cost of any necessary repairs. Some problems that are outside the scope of this war-
ranty are:
D Problems due to improper maintenance or handling, carelessness, or other reasons where
the customer is determined to be responsible.
D Problems due to additions or modifications made to a Yaskawa product without Yaskawa’s
understanding.
D Problems due to the use of a Yaskawa product under conditions that do not meet the recom-
mended specifications.
D Problems caused by natural disaster or fire.
D Or other problems not due to defects in Yaskawa workmanship or materials.
Warranty service is only applicable within Japan.
However, aftersales service is available for customers outside of Japan for a reasonable fee. Contact
your local Yaskawa representative for more information.
J Exceptions
Any inconvenience to the customer or damage to non−Yaskawa products due to Yaskawa’s defective
products whether within or outside the warranty period are NOT covered by this warranty.
x
J Restrictions
D The Varispeed F7 was not designed or manufactured for use in devices or systems that may
directly affect or threaten human lives or health.
D Customers who intend to use the product described in this manual for devices or systems
relating to transportation, health care, space aviation, atomic or electric power, or underwa­ter use must contact their Yaskawa representatives or the nearest Yaskawa sales office be­forehand.
D This product has been manufactured under strict quality−control guidelines. However, if
this product is to be installed in any location where failure of this product could involve or result in a lifeand−death situation or loss of human life or in a facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident.

Before Reading This Manual

Before Reading This Manual
This manual explains both the conventional VS-616G5 Inverters and the G5-series Inverters for SPEC:F.
The shaded sections or those specified as being for SPEC:F apply only to G5-series Inverters for SPEC:F ( Inverters with revised version letters of F or later.)
Be certain to check the specification on the Inverter nameplate.
Example of Inverter Nameplate
Version code
MODEL : CIMRG5A20P4 SPEC : 20P41F
INPUT : AC 3PH 200-220 V 50Hz
OUTPUT: AC 3PH 0-230 V 1.2kVA 3.2 A
LOT NO : MASS : 3.0kg
SER NO :
YASKAWA ELECTRIC CORPORATION
200-230 V 60Hz
JAPAN
xi

CONTENTS

11 Introduction
12 Handling Inverters
13 Wiring
14 Setting User Constants
15 Trial Operation
16 Basic Operation
17 Advanced Operation
1
2
3
4
5
6
7
xiii
18 User Constants
19 Troubleshooting
10 Maintenance and Inspection
11 Specifications
12 Appendix
8
9
10
11
12

Table of Contents

Table of Contents
Safety Information ii..................................................
Visual Aids iii........................................................
General Precautions iv................................................
Safety Precautions v.................................................
Warning Label Contents and Position viii.................................
How to Change the Digital Operator Display from Japanese to English ix....
Warranty Information x...............................................
Before Reading This Manual xi.........................................
1 Introduction 1 - 1........................................
1.1 Outline and Functions 1 - 2........................................
1.1.1 VS-616G5 Inverter Models 1 - 2............................................
1.1.2 Outline of Control Methods 1 - 4............................................
1.1.3 Functions 1-4...........................................................
1.2 Nomenclature 1 - 7...............................................
1.2.1 VS-616G5 Components 1 - 7...............................................
1.2.2 Digital Operator Components 1 - 8..........................................
2 Handling Inverters 2 - 1..................................
2.1 Confirmations upon Delivery 2 - 2..................................
2.1.1 Nameplate Information 2 - 2................................................
2.2 Exterior and Mounting Dimensions 2 - 4.............................
2.3 Checking and Controlling the Installation Site 2 - 6...................
2.3.1 Installation Site 2 - 6......................................................
2.3.2 Controlling the Ambient Temperature 2 - 6...................................
2.3.3 Protecting the Inverter from Foreign Matter 2 - 6..............................
2.4 Installation Orientation and Space 2 - 7.............................
2.5 Removing/Attaching the Digital Operator and Front Cover 2 - 8........
2.5.1 Inverters of 15 kW or Less 2 - 8............................................
2.5.2 Inverters of 18.5 kW or Higher 2 - 9.........................................
3 Wiring 3 - 1.............................................
3.1 Connections to Peripheral Devices 3 - 3............................
3.2 Connection Diagram 3 - 4.........................................
3.3 Terminal Block Configuration 3 - 5..................................
3.4 Wiring Main Circuit Terminals 3 - 6.................................
3.4.1 Applicable Wire Sizes and Closed-loop Connectors 3 - 6.......................
3.4.2 Main Circuit Terminal Functions 3 - 9........................................
3.4.3 Main Circuit Configurations 3 - 10............................................
3.4.4 Standard Connection Diagrams 3 - 12........................................
3.4.5 Wiring the Main Circuits 3 - 13...............................................
xv
3.5 Wiring Control Circuit Terminals 3 - 20...............................
3.5.1 Wire Sizes and Closed-loop Connectors 3 - 20................................
3.5.2 Control Circuit Terminal Functions 3 - 21......................................
3.5.3 Control Circuit Terminal Connections (All Models) 3 - 22........................
3.5.4 Control Circuit Wiring Precautions 3 - 23......................................
3.6 Wiring Check 3 - 23...............................................
3.7 Installing and Wiring PG Speed Control Cards 3 - 24..................
3.7.1 Installing a PG Speed Control Card 3 - 24.....................................
3.7.2 PG Speed Control Card Terminal Blocks 3 - 25................................
3.7.3 Wiring a PG Speed Control Card 3 - 27.......................................
3.7.4 Wiring PG Speed Control Card Terminal Blocks 3 - 31..........................
3.7.5 Selecting the Number of PG (Encoder) Pulses 3 - 33...........................
4 Setting User Constants 4 - 1..............................
4.1 Using the Digital Operator 4 - 2....................................
4.2 Modes 4 - 5.....................................................
4.2.1 Inverter Modes 4 - 5......................................................
4.2.2 Switching Modes 4 - 6.....................................................
4.2.3 User Constant Access Levels 4 - 7..........................................
4.2.4 Operation Mode 4 - 12.....................................................
4.2.5 Initialize Mode 4 - 20.......................................................
4.2.6 Programming Mode 4 - 27..................................................
4.2.7 Autotuning Mode 4 - 31.....................................................
4.2.8 Modified Constants Mode 4 - 33.............................................
5 Trial Operation 5 - 1......................................
5.1 Procedure 5 - 3..................................................
5.2 Trial Operation Procedures 5 - 4...................................
5.2.1 Power ON 5-4...........................................................
5.2.2 Checking the Display Status 5 - 4...........................................
5.2.3 Initializing Constants 5 - 4.................................................
5.2.4 Setting Input Voltage 5 - 5.................................................
5.2.5 Autotuning 5 - 6..........................................................
5.2.6 No-load Operation 5 - 9...................................................
5.2.7 Loaded Operation 5 - 10....................................................
6 Basic Operation 6 - 1....................................
6.1 Common Settings 6 - 2...........................................
6.1.1 Setting the Access Level and Control Method: A1-01, A1-02 6 - 2...............
6.1.2 Frequency Reference Settings: b1-01, H3-01, H3-08, H3-09 6 - 4...............
6.1.3 Frequency Reference from Digital Operator: b1-01, o1-03, d1-01 to d1-09 6 - 7...
6.1.4 Run Source and Sequence Input Responsiveness: b1-02, b1-06, b1-07 6 - 9.....
6.1.5 Acceleration/Deceleration Times: C1-01 through C1-08, C1-09, C1-10, C1-11 6 - 10
6.1.6 Prohibiting Reverse Operation: b1-04 6 - 11...................................
6.1.7 Selecting the Stopping Method: b1-03 6 - 12..................................
6.1.8 Multi-function Input Settings: H1-01 through H1-06 6 - 13.......................
6.2 Open-loop Vector Control 6 - 18.....................................
6.2.1 Autotuning 6 - 18..........................................................
6.2.2 Autotuning Faults 6 - 19....................................................
6.3 V/f Control 6 - 21..................................................
6.3.1 Setting the Motor Constants: E1-01, E1-02, E2-01 6 - 21........................
6.3.2 V/f Pattern Selection: E1-03 6 - 22...........................................
xvi
Table of Contents
6.4 Flux Vector Control 6 - 28..........................................
6.4.1 PG Speed Control Card Settings 6 - 28.......................................
6.4.2 Setting the Zero-speed Operation Constants 6 - 31.............................
6.4.3 Autotuning 6 - 33..........................................................
6.4.4 Speed Control (ASR) Structure 6 - 36........................................
6.4.5 Speed Control (ASR) Gain 6 - 38............................................
6.5 V/f Control with PG 6 - 40..........................................
6.5.1 Motor Constants: E1-01, E1-02, E2-01, E2-04 6-40..........................
6.5.2 V/f Pattern Selection: E1-03 6 - 41...........................................
6.5.3 PG Speed Control Card Settings 6 - 42.......................................
6.5.4 Speed Control (ASR) Structure 6 - 44........................................
6.5.5 Adjusting Speed Control (ASR) Gain 6 - 45....................................
7 Advanced Operation 7 - 1................................
7.1 Open-loop Vector Control 7 - 2.....................................
7.1.1 Torque Limit Function 7 - 4.................................................
7.1.2 Adjusting Speed Feedback 7 - 5............................................
7.1.3 Setting/Adjusting Motor Constants 7 - 6......................................
7.1.4 Operation Selection when Output Voltage Saturated 7 - 8......................
7.1.5 Starting Torque Compensation Function (for SPEC:F) 7 - 9.....................
7.2 V/f Control without PG 7 - 11.......................................
7.2.1 Energy-saving Control Function 7 - 13........................................
7.2.2 Hunting-prevention Function 7 - 13...........................................
7.2.3 Setting Motor Constants 7 - 14..............................................
7.3 Flux Vector Control 7 - 16..........................................
7.3.1 Droop Control Function 7 - 18...............................................
7.3.2 Zero-servo Function 7 - 19..................................................
7.3.3 Torque Control 7 - 21.......................................................
7.3.4 Speed/Torque Control Switching Function 7 - 27...............................
7.3.5 Torque Limit Function 7 - 30.................................................
7.3.6 Setting/Adjusting Motor Constants 7 - 31......................................
7.3.7 Operation Selection when Output Voltage Saturated 7 - 34......................
7.4 V/f Control with PG 7 - 36..........................................
7.4.1 Energy-saving Control Function 7 - 38........................................
7.4.2 Hunting-prevention Function 7 - 38...........................................
7.4.3 Setting Motor Constants 7 - 39...............................................
7.5 Common Functions 7 - 41..........................................
7.5.1 Application Constants: b 7 - 43..............................................
7.5.2 Tuning Constants: C 7 - 52..................................................
7.5.3 Reference Constants: d 7 - 57...............................................
7.5.4 Option Constants: F 7 - 59..................................................
7.5.5 External Terminal Functions: H 7 - 64.........................................
7.5.6 Protective Functions: L 7 - 84...............................................
7.5.7 Operator Constants: o 7 - 97................................................
8 User Constants 8 - 1.....................................
8.1 Initialize Mode Constants 8 - 3.....................................
8.2 Programming Mode Constants 8 - 5................................
8.2.1 Application Constants: b 8 - 5..............................................
8.2.2 Autotuning Constants: C 8 - 11..............................................
8.2.3 Reference Constants: d 8 - 17...............................................
8.2.4 Motor Constant Constants: E 8 - 20..........................................
8.2.5 Options Constants: F 8 - 24.................................................
xvii
8.2.6 Terminal Constants: H 8 - 28................................................
8.2.7 Protection Constants: L 8 - 35...............................................
8.2.8 Operator Constants: o 8 - 43................................................
8.2.9 Factory Settings that Change with the Control Method (A1-02) 8 - 45.............
8.2.10 Factory Settings that Change with the Inverter Capacity (o2-04) 8 - 47...........
9 Troubleshooting 9 - 1....................................
9.1 Protective and Diagnostic Functions 9 - 2...........................
9.1.1 Fault Detection 9 - 2......................................................
9.1.2 Minor Fault Detection 9 - 6.................................................
9.1.3 Operation Errors 9 - 8.....................................................
9.2 Troubleshooting 9 - 9.............................................
9.2.1 If Constant Constants Cannot Be Set 9 - 9...................................
9.2.2 If the Motor Does Not Operate 9 - 9.........................................
9.2.3 If the Direction of the Motor Rotation is Reversed 9 - 11.........................
9.2.4 If the Motor Does Not Put Out Torque or If Acceleration is Slow 9 - 11.............
9.2.5 If the Motor Does Not Operate According to Reference 9 - 11....................
9.2.6 If the Slip Compensation Function Has Low Speed Precision 9 - 11...............
9.2.7 If There is Low Speed Control Accuracy at High-speed Rotation in Open-loop
9.2.8 If Motor Deceleration is Slow 9 - 12..........................................
9.2.9 If the Motor Overheats 9 - 12................................................
9.2.10 If There is Noise When the Inverter is Started or From an AM Radio 9 - 13.......
9.2.11 If the Ground Fault Interrupter Operates When the Inverter is Run 9 - 13.........
9.2.12 If There is Mechanical Oscillation 9 - 13.....................................
9.2.13 If the Motor Rotates Even When Inverter Output is Stopped 9 - 14...............
9.2.14 If 0 V is Detected When the Fan is Started, or Fan Stalls 9 - 14.................
9.2.15 If Output Frequency Does Not Rise to Frequency Reference 9 - 14..............
Vector Control Mode 9 - 11................................................
10 Maintenance and Inspection 10 - 1.........................
10.1 Maintenance and Inspection 10 - 3.................................
10.1.1 Daily Inspection 10 - 3....................................................
10.1.2 Periodic Inspection 10 - 3..................................................
10.1.3 Periodic Maintenance of Parts 10 - 3........................................
11 Specifications 11 - 1......................................
11.1 Standard Inverter Specifications 11 - 2..............................
11.2 Specifications of Options and Peripheral Devices 11 - 5...............
12 Appendix 12 - 1...........................................
12.1 Inverter Application Precautions 12 - 2..............................
12.1.1 Selection 12 - 2..........................................................
12.1.2 Installation 12 - 2........................................................
12.1.3 Settings 12 - 3...........................................................
12.1.4 Handling 12 - 3..........................................................
12.2 Motor Application Precautions 12 - 4...............................
12.2.1 Using the Inverter for an Existing Standard Motor 12 - 4.......................
12.2.2 Using the Inverter for Special Motors 12 - 5.................................
12.2.3 Power Transmission Mechanism (Speed Reducers, Belts, and Chains) 12 - 5....
12.3 Peripheral Device Application Precautions 12 - 6.....................
xviii
12.4 Wiring Examples 12 - 8...........................................
12.4.1 Using a Braking Resistor Unit 12 - 8.........................................
12.4.2 Using a Braking Unit and Braking Resistor Unit 12 - 8..........................
12.4.3 Using Braking Units in Parallel 12 - 11........................................
12.4.4 Using a Braking Unit and Three Braking Resistor Units in Parallel 12 - 12..........
12.4.5 Using a JVOP-95-j, -96-j VS Operator 12 - 13...............................
12.4.6 Using an Open-collector Transistor for Operation Signals 12 - 14.................
12.4.7 Using Open-collector, Contact Outputs 12 - 14.................................
12.5 User Constants 12 - 15............................................
12.6 Function Block Diagram 12 - 20.....................................
INDEX
Table of Contents
xix
1

Introduction

This chapter provides an overview of the VS-616G5 Inverter and describes its functions and components.
1.1 Outline and Functions 1 - 2..................
1.1.1 VS-616G5 Inverter Models 1 - 2....................
1.1.2 Outline of Control Methods 1 - 4...................
1.1.3 Functions 1 - 4..................................
1.2 Nomenclature 1 - 7.........................
1.2.1 VS-616G5 Components 1 - 7......................
1.2.2 Digital Operator Components 1 - 8.................
1
1-1
Introduction
Maximum
p
g
listedatthe
right

1.1.1 VS-616G5 Inverter Models

1.1 Outline and Functions

The VS-616G5 Inverters provides full-current vector control based on advanced control logic. An autotuning function is included for easy vector control.
The Digital Operator provides a liquid crystal display that is 2 lines by 16 characters in size. User constant set­tings and monitor items are easily read in interactive operations in either Japanese or English. (The display lan­guage can be changed by setting a user constant.)
1
Voltage
Class
200 V class
1.1.1 VS-616G5 Inverter Models
VS-616G5 Inverters are available in 200 and 400 V class models. These are listed in the following table. A total of 37 models is available for motor capacities of 0.4 to 300 kW.
Table 1.1 VS-616G5 Inverter Models
Maximum
Applicable
Motor Out-
put [kW]
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
Output Ca-
pacity [kVA]
1.2 CIMR-G5A20P4 20P41j *
2.3 CIMR-G5A20P7 20P71j *
3.0 CIMR-G5A21P5 21P51j *
4.2 CIMR-G5A22P2
6.7 CIMR-G5A23P7
9.5 CIMR-G5A25P5
13 CIMR-G5A27P5 27P51j *
19 CIMR-G5A2011 20111j *
24 CIMR-G5A2015 20151j *
30 CIMR-G5A2018 20180j * 20181j ‡
37 CIMR-G5A2022 20220j * 20221j ‡
50 CIMR-G5A2030 20300j † 20301j ‡
61 CIMR-G5A2037 20370j † 20371j ‡
70 CIMR-G5A2045 20450j † 20451j ‡
85 CIMR-G5A2055 20550j † 20551j ‡
110 CIMR-G5A2075 20750j ‡ 20751j ‡
VS-616G5
Model Number
(Specify all required standards when ordering.)
Open Chassis Type
(IEC IP 00)
CIMR-G5Ajjjjjj
Remove the top and bottom covers from the models listed at the ri
Inverter Specifications
ht.
.
*
Enclosed Wall-mounted
(IEC IP 20, NEMA 1)
CIMR-G5Ajjjjjj
Type
22P21j *
23P71j *
25P51j *
1-2
1.1 Outline and Functions
p
g
listedatthe
right
Voltage
Voltage
Class
Class
400 V class
Maximum
Maximum
Applicable
Applicable Motor Out-
Motor Out-
put [kW]
put [kW]
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
110
160
185
220
300
VS-616G5
Output Ca-
pacity [kVA]
1.4 CIMR-G5A40P4 40P41j *
2.6 CIMR-G5A40P7 40P71j *
3.7 CIMR-G5A41P5 41P51j *
4.7 CIMR-G5A42P2
6.1 CIMR-G5A43P7
11 CIMR-G5A45P5
14 CIMR-G5A47P5 47P51j *
21 CIMR-G5A4011 40111j *
26 CIMR-G5A4015 40151j *
31 CIMR-G5A4018 40180j * 40181j ‡
37 CIMR-G5A4022 40220j * 40221j ‡
50 CIMR-G5A4030 40300j * 40301j ‡
61 CIMR-G5A4037 40370j * 40371j ‡
73 CIMR-G5A4045 40450j * 40451j ‡
98 CIMR-G5A4055 40550j † 40551j ‡
130 CIMR-G5A4075 40750j † 40751j ‡
170 CIMR-G5A4110 41100j † 41101j ‡
230 CIMR-G5A4160 41600j † 41601j ‡
260 CIMR-G5A4185 41850j ‡
340 CIMR-G5A4220 42200j ‡
460 CIMR-G5A4300 43000j ‡
Model Number
(Specify all required standards when ordering.)
Open Chassis Type
(IEC IP 00)
CIMR-G5Ajjjjjj
Remove the top and bottom covers from the models listed at the ri
Inverter Specifications
ht.
.
*
Enclosed Wall-mounted
(IEC IP 20, NEMA 1)
CIMR-G5Ajjjjjj
Type
42P21j *
43P71j *
45P51j *
1
*: Immediate delivery †: Available from factory ‡: Manufactured upon order
1-3
1
Introduction

1.1.2 Outline of Control Methods

1.1.2 Outline of Control Methods
The VS-616G5 uses four control methods.
Open-loop vector control (factory setting)
D
Flux vector control
D
V/f control without PG
D
V/f control with PG feedback
D
PG stands for pulse generator (encoder).
Vector control is a method for removing interference with magnetic flux and torque, and controlling torque according to references.
Current vector control independently controls magnetic flux current and torque current by simultaneously controlling the motor primary current and phases. This ensures smooth rotation, high torque, and accurate speed/torque control at low speeds.
Vector control can be replaced by the conventional V/f control system. If the motor constants required for vector control are not known, the motor constants can be automatically set with autotuning.
The control methods are effective for the following applications:
Open-loop vector control: General variable-speed drive.
D
Flux vector control: Simple servodrive, high-precision speed control/torque control.
D
V/f control without PG: Conventional Inverter control mode. Used for multi-drive operation
D
(connecting multiple motors to one Inverter).
V/f control with PG feedback:Simple speed feedback control. (For applications with the PG
D
connected to the machine shaft rather than the motor shaft.)
The control characteristics for each mode are shown in Table 1.2.
Table 1.2 Control Method Characteristics

1.1.3 Functions

J Autotuning
Autotuning is effective for vector control. It solves problems in applicable motor restrictions and difficult constant settings. The motor constants are automatically set by entering a value from the motor’s rating nameplate.
Autotuning allows flux vector control to operate accurately with virtually any normal AC induction motor, regardless of the supplier.
Always autotune the motor separately before operating using vector control. Refer to 5.2.5 Autotuning and
6.4.3 Autotuning for details.
J Torque Control
Torque control is effective for flux vector control with PG. Torque is controlled by taking multi-function analog input signals as torque references. Torque control accuracy is ±5%. Switching is possible between torque control and speed control.
V/f Pattern Settings
J
V/f pattern settings are effective for V/f control. Select a V/f pattern according to the application from among the 15 preset V/f patterns. Custom V/f patterns can also be set.
Characteristic
Speed Control
Range
Speed Control
Precision
Initial Drive
Vector Control V/f Control
Open-loop Flux Vector Without PG With PG feedback
1:100 1:1000 1:40 1:40
±0.2 % ±0.02 % ±2to3% ±0.03 %
150% at 1 Hz 150% at 0 r/min 150% at 3 Hz
J Frequency References
The following five types of frequency references can be used to control the output frequency of the Invert­er.
Numeric input from the Digital Operator
D
Voltage input within a range from 0 to 10 V
D
Voltage input within a range from 0 to ±10 V (with negative voltages, rotation is in the opposite direc-
D
tion from the run command.)
1-4
Current input within a range from 4 to 20 mA
D
Input from Option Card
D
Any of the above frequency references can be used by setting a constant.
A maximum of nine frequency references can be registered with the Inverter. With remote multi-step speed reference inputs, the Inverter can operate in multi-step speed operation with a maximum of nine speed steps.
PID Control
J
The Inverter has a PID control function for easy follow-up control. Follow-up control is a control method in which the Inverter varies the output frequency to match the feedback value from the sensor for a set target value.
Follow-up control can be applied to a variety of control operations, such as those listed below, depending on the contents detected by the sensor.
Speed Control: With a speed sensor, such as a tacho-generator,the Inverter regulates the rotat-
D
Pressure Control: With a pressure sensor, the Inverter performs constant pressure control.
D
Flow-rate Control: By sensing the flow rate of a fluid, the Inverter performs precise flow-rate
D
Temperature Control: With a temperature sensor, the Inverter performs temperature control by fan
D
J Zero-servo Control
Zero-servo control is effective with flux vector control. Even at a motor speed of zero (r/min), a torque of 150% of the motor’s rated torque can be generated and the average servomotor holding power (stopping power) can be obtained.
1.1 Outline and Functions
1
ing speed of the motor regardless of the load of the motor or synchronizes the rotating speed of the motor with that of another motor.
control.
speed.
Speed Control By Feedback
J
Speed control using feedback is effective with a PG. An optional PG Speed Control Card be used to enable feedback control for speeds, thereby improving speed control accuracy.
J Dwell Function
By holding the output frequency for a constant time during acceleration and deceleration, acceleration and deceleration can be performed without stepping out even when driving a motor with a large startup load.
J Low Noise
The output transistor of the Inverter is an IGBT (insulated gate bipolar transistor). Using sine-wave PWM with a high-frequency carrier, the motor does not generate metallic noise.
J Monitor Function
The following items can be monitored with the Digital Operator: Frequency reference, output frequency, output current, motor speed, output voltage reference, main-circuit DC voltage, output power, torque ref­erence, status of input terminals, status of output terminals, operating status, total operating time, software number, speed deviation value, PID feedback value, fault status, fault history, etc.
All types of data can be monitored even with multi-function analog output.
J Multilingual Digital Operator (SPEC:F)
The Digital Operator can display in seven languages (Japanese, English, German, French, Italian, Spanish, and Portuguese). The Digital Operator’s liquid crystal display provides a 16-character x 2-line display area.
Easy-to-read displays in each language allow the advanced functions of the Inverter to be set in interactive operations to input constants, monitoring items, etc. Change the constant setting to select the display lan­guage.
J Harmonic Countermeasures (0.4 to 160 kW Models)
The VS-616G5 Inverters up to 160 kW support DC reactors to easily handle high-frequency control guide­lines.
DC reactors (optional) can be connected to 0.4 to 15 kW models.
D
Models from 18.5 to 160 kW have a built-in DC reactor.
D
An optional AC reactor can be connected to Inverters from 185 to 300 kW.
D
1-5
1
Introduction
1.1.3 Functions
User Constant Structure and Three Access Levels
J
The VS-616G5 has a number of user constants for setting various functions. These user constants are clas­sified into a hierarchy to make them easier to use.
The levels are as follows from top to bottom: Modes, Groups, Functions, and Constants. The access levels for the user constants are shown in Table 1.3.
Table 1.3 Access Levels for User Constants
Level Contents
Mode
Groups
Functions
Constants
Classified according to operation
Operation: For operating the Inverter. (All kinds of monitoring are possible.)
Initialize: For selecting the language displayed at the Digital Operator, set-
ting access levels, initialization, and the control modes.
Programming: For setting user constants for operation.
Autotuning: For automatic calculation or setting motor constants. (Only under
the vector control mode.)
Modified constants: For referencing or changing user constants after shipping.
Classified by application.
Classified by function. (See user constants.)
Individual user constant settings.
The VS-616G5 allows the following three access levels to be set in order to further simplify setting user constants. (An access level is a range of user constants that can be referenced or set.)
Quick-Start
Basic
Advanced
Reads/sets user constants required for trial operation. [Factory setting]
Reads/sets user constants that are commonly used.
Reads/sets all the user constants that can be used.
MENU
In general, press the DATA/ENTER Key to move from an upper to a lower level. This varies somewhat, however, according to the access level, as shown in Fig. 1.1. For the Quick-Start access level, which has few user constants that can be set, pressing the DATA/ENTER Key jumps directly to the user constant lev­el; whereas for the Advanced access level, which has many user constants, pressing the DATA/ENTER Key first leads to the Group level.
Operation mode
Initialize mode
Programming mode
DATA
ENTER
[Advanced] [Basic] [Quick-Start]
Displays group level.
Application
Displays function level.
b1 Sequence
Constant to be changed
Displays constant level.
b1-01 Reference source
b1-02 Run source
b1-03 Stopping method
Tuning
Reference
[Mode]
[Groups]
Fig 1.1 Access Level Structure
1-6
C1 Accel/Decel
C2 S-curve Acc/Dec
[Functions]
C1-01 Accel Time 1
C1-02 Decel Time 1
[Constants]

1.2 Nomenclature

This section provides the names of VS-616G5 components, and the components and functions of the Digital Operator.

1.2.1 VS-616G5 Components

The appearance of Inverter and the names of its components are shown in Figure 1.2.
1.2 Nomenclature
Protective cover (top)
Mounting hole
Front cover
Digital Operator JVOP-130
Die-cast case
Protective cover (bottom)
Fig 1.2 Appearance of VS-616G5, Model CIMR-G5A20P4 (200 V, 0.4 kW)
A 200 V Class Inverter with 0.4 kW Output is shown below with the front cover removed.
1
Control circuit terminals
11 12(G) 13 14 15 16 17 25 26 27 33 18 19 20
1234567821 22 23 9
R
L1
S
Power input
L2
T
L3
¨1
©
¨2B1
Braking Resistor
B2
U
T1
Motor output
V
T2
10
W/T3
CHARGE
Fig 1.3 Terminal Arrangement
Main circuit terminals
1-7
Introduction

1.2.2 Digital Operator Components

1.2.2 Digital Operator Components
This section describes the component names and functions of the Digital Operator. The component names and functions are shown in Figure 1.4 and key functions are described in Table 1.4.
1
DRIVE FWD REV REMOTE
Frequency Ref
U101 = 00.00 HZ
DIGITAL OPERATOR JVOP130
LOCAL
REMOTE
JOG
FWD
REV
RUN STOP
SEQ REF
MENU
ESC
DATA
ENTER
RESET
Operation Mode Indicators
DRIVE: Lit when in operation mode. FWD: Lit when there is a forward reference input. REV: Lit when there is a reverse reference input. SEQ: Lit when an operation reference from the
control circuit terminal is enabled.
REF: Lit when the frequency reference from con-
trol circuit terminals 13 and 14 is enabled.
Data Display
Two-line LCD that displays data for monitoring, user constants, and set values with 16 characters per line.
Keys
Execute operations such as setting user constants, monitoring, jogging, and autotuning.
Fig 1.4 Digital Operator Component Names and Functions
1-8
Table 1.4 Key Functions
Key Name Function
Switches between (LOCAL) operation via the Digital Operator
LOCAL
REMOTE
LOCAL/REMOTE Key
and control circuit terminal (REMOTE) operation.
This key can be enabled or disabled by setting a user constant (o2-01).
1.2 Nomenclature
MENU
ESC
JOG
FWD REV
RESET
DATA
ENTER
RUN
MENU Key Displays menus.
ESC Key
JOG Key
FWD/REV Key
RESET Key
Increment Key
Decrement Key
DATA/ENTER Key
RUN Key
Returns to the status before the DATA/ENTER Key was pressed.
Enables jog operation when the VS-616G5 is being operated from the Digital Operator.
Selects the rotation direction of the motor when the VS-616G5 is being operated from the Digital Operator.
Sets the number of digits for user constant settings.
Also acts as the reset key when a fault has occurred.
Selects menu items, groups, functions, and user constant names, and increments set values.
Selects menu items, groups, functions, and user constant names, and decrements set values.
Enters menu items, functions, constants, and set values after they are set.
Starts the VS-616G5 operation when the VS-616G5 is in opera­tion with the Digital Operator.
Stops VS-616G5 operation.
STOP
STOP Key
This key can be enabled or disabled by setting a user constant (o2-02) when operating from the control circuit terminal.
Note Except in diagrams, keys are referred to using the key names listed in the above table.
1
FWD
REV
RUN STOP
RESET
Inverter output frequency
STOP
Frequency setting
RUN
OP
ST
:
:
Blinking:Not lit
Lit
RUN
The RUN and STOP indicators light and blink to indicate operating status. During DB (initial excitation), RUN blinks and STOP is turned ON.
Fig 1.5 RUN and STOP Indicators
STOP
1-9
2

Handling Inverters

This chapter describes the checks required upon receiving a VS-616G5 In­verter and describes installation methods.
2.1 Confirmations upon Delivery 2 - 2............
2.1.1 Nameplate Information 2 -
2.2 Exterior and Mounting Dimensions 2 - 4.......
2.3 Checking and Controlling the
Installation Site 2 - 6.......................
2.3.1 Installation Site 2 - 6..............................
2.3.2 Controlling the Ambient Temperature 2 - 6...........
2.3.3 Protecting the Inverter from Foreign Matter 2 - 6......
2.4 Installation Orientation and Space 2 - 7.......
2.5 Removing/Attaching the Digital Operator
and Front Cover 2 - 8......................
2.5.1 Inverters of 15 kW or Less 2 - 8....................
2.5.2 Inverters of 18.5 kW or Higher 2 - 9.................
.......................
2
2
2-1






2
Handling Inverters

2.1.1 Nameplate Information

2.1 Confirmations upon Delivery



D Never install an Inverter that is damaged or missing components.
Doing so can result in injury.
Check the following items as soon as the Inverter is delivered.
Table 2.1 Checks
Item Method
Has the correct model of Inverter been delivered?
Is the Inverter damaged in any way? Inspect the entire exterior of the Inverter to see if there are any scratches or
Are any screws or other components loose?
If you find any irregularities in the above items, contact the agency from which you purchased the Inverter or your Yaskawa representative immediately.
CAUTION
Check the model number on the nameplate on the side of the Inverter (See
2.1.1).
other damage resulting from shipping.
Use a screwdriver or other tools to check for tightness.
2.1.1 Nameplate Information
Example Nameplate
J
Standard domestic (Japan) Inverter: 3-phase, 200 VAC, 0.4 kW, IEC IP20 and NEMA 1 standards
Model number
Input specifications
Output specifications
Lot number
Serial number
J Inverter Model Numbers
Inverter
VS-616G5
No. Specification
A Standard domestic model V UL/C-UL model
No. Voltage Class
2 AC input, 3-phase, 200 V 4 AC input, 3-phase, 400 V D DC input, 3-phase, 200 V E DC input, 3-phase, 400 V
MODEL : CIMR-G5A20P4 SPEC: 20P41F
INPUT : AC 3PH 200-220 V 50Hz
OUTPUT: AC 3PH 0-230 V 1.2kVA 3.2 A
LOT NO : MASS : 3.0kg
SER NO :
YASKAWA ELECTRIC CORPORATION
200-230 V 60Hz
JAPAN
CIMR -G5A 2 0P4
No. Max. Motor Capacity
0P4 0P7
to
075
“P” indicates the decimal point.
Inverter specifications
Mass
0.4 kW
0.75 kW to
75kW
2-2
Inverter Specifications
J
2.1 Confirmations upon Delivery
2 0P4 1 F
No. Voltage Class
2 AC input, 3-phase, 200 V 4 AC input, 3-phase, 400 V D DC input, 3-phase, 200 V E DC input, 3-phase, 400 V
No. Max. Motor Capacity
0P4 0P7
to
075
“P” indicates the decimal point.
Open Chassis Type (IEC IP00)
D
0.4 kW
0.75 kW to
75kW
Protected so that parts of the human body cannot reach electrically charged parts from the front when the Inverter is mounted in a control panel.
Enclosed Wall-mounted Type (IEC IP20, NEMA 1)
D
The Inverter is structured so that the Inverter is shielded from the exterior, and can thus be mounted to the interior wall of a standard building (not necessarily enclosed in a control panel). The protective structure conforms to the standards of NEMA 1 in the USA.
Version (Enter the specifications form number when special spec­ifications are required.)
No. Protective Structure
0 1
Enclosed wall-mounted (IEC IP20, NEMA 1)
Open chassis (IEC IP00)
2
2-3
Loading...
+ 329 hidden pages