Yaskawa CM092 User Manual

WARNING
Applicable products: Yaskawa F7U, G7U, P7U, E7U, G5M (Spec F), G5M(600V) and G5HHP drives.
CM092 EtherNet/IP Option Kit Parts Qty.
EtherNet/IP Option Card 1
Shielded RJ-45 M-F Cable 1
Ground Wire 1
4" x 1" Insulated Tubing 1
Cable Ties 2
MAC ID Label (Unique for each EtherNet/IP Option Card 1
Installation Guide (IG.AFD.26) 1
2. Connect power to the Yaskawa AC drive and verify that the drive functions correctly.
This includes running the drive from the operator keypad. Refer to the appropriate drive technical manual for information on connecting and operating the drive.
3. Remove power from the drive and wait for the charge lamp to be completely extinguished.
Wait at least five additional minutes for the drive to be completely discharged. Measure the DC bus voltage and verify that it is at a safe level.
EtherNet/IP Option Kit
CM092
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC (460V drives) are present at the DC bus terminals of the drive.
4. Remove the operator keypad and drive cover.
a. Remove the operator keypad.
b. Remove the terminal and control covers.
c. Remove the option card hold-down by carefully
compressing the top and bottom until it becomes free of its holder. Lift it out.
5. Mount the EtherNet/IP Option Card on the drive
Note: Skip to step 6 for G5HHP drives.
a. Connect the RJ-45 M-F cable supplied in this kit to the EtherNet/IP
Option Card.
b. Connect the ground wire supplied to ground terminal J6 on the EtherNet/
IP Option Card.
c. Align the J2 connector on the back of the EtherNet/IP Option Card with
its mating 2CN connector on the drive control card.
d. Align the two standoffs on the front of the drive control board with the
two holes on the right side of the EtherNet/IP Option Card.
e. Press the EtherNet/IP Option Card firmly onto the drive 2CN connector
and standoffs until the J2 connector is fully seated on 2CN and the drive standoffs have locked into their appropriate holes.
f. Route the RJ-45 M-F cable and the ground wire along the left-inside of
the AC drive enclosure.
g. Replace the option card hold-down.
h. Connect the ground wire from the option card terminal J6 to the terminal
assembly ground connection.
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 1 of 16
Date: 08/18/2011 Rev: 11-08
6. Mount the EtherNet/IP Option Card on the G5HHP drive.
a. Attach the CM092 EtherNet/IP Option ground wire to the ground
terminal as shown. Make sure that the terminal is connected to a reliable, noise free ground.
b. Connect the CM092 EtherNet/IP Option card to the 2CN connector on
the master control board.
c. Secure the Cat-5 Ethernet cable to the support with a tie wrap to provide
strain relief for the connector.
d. Attach the Ethernet cable to the CM092 EtherNet/IP Option card as
shown.
e. Fully engage the stand-offs in the mounting holes on the card.
f. Route the Ethernet cable away from any power wires within the cabinet.
When outside of the cabinet, run the Ethernet cable in its own conduit. However, it may be run along with low voltage signals such as feedback wiring.
EtherNet/IP Option Kit
CM092
7. Diagnostic LED power-up test sequence
A power-up test is performed each time the AC drive is powered up after the initial boot-up sequence. The initial boot-up sequence may take several seconds. When this sequence is complete, the LEDs will assume their normal conditions.
Seq MS/RUN NS/CON Time
1GREEN OFF 250ms
2RED OFF 250ms
3GREEN OFF 250ms
4 GREEN GREEN 250ms
5 GREEN RED 250ms
6GREEN OFF
The EtherNet/IP Option Card is successfully initialized after the LEDs have completed the above sequence.
The EtherNet/IP Option Card LED status after the power-up sequence is described below. Please wait for at least five seconds for the loading process to complete before verifying the status of the LEDs.
8. LED descriptions
LED Label Description
GREEN – Card Functioning Normally
D1 MS/RUN
D2 NS/CON
D3 10/100 GREEN – 100Mbs Connection Speed
GREEN BLINK – Standby/Initializing (500ms cycle) RED BLINK – Minor Fault (500ms cycle) RED – Major Fault GREEN/RED BLINK – Module Test (500ms cycle)
GREEN – Connected GREEN BLINK – Waiting for Connections (500ms cycle)
RED BLINK – Connection Timeout (500ms cycle) RED – Duplicate IP Address GREEN/RED BLINK – Network Test (500ms cycle)
Successful Initialization:
The EtherNet/IP Option Card hardware is installed and operating correctly with the LEDs in the states shown in bold text in step 8 per the "LED Descriptions" table. The LINK LED represents the status of the physical connection to the network and is not indicative of any card state.
LED Label Description
D4 LINK GREEN – Link Established
D5 Rx GREEN – Message Being Received
D8 PWR GREEN - Appropriate Power Supplied to Card
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 2 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
IP address: 192.168.1.19
Subnet mask: 255.255.255.0
CM092
9. Connect to the EtherNet/IP Option Card.
Note: Due to the presence of high voltage in the area of the network
connection, insulating the RJ-45 M-F cable connection is required.
a. Prior to connecting the RJ-45 M-F network cable, slide the supplied
insulated tubing (4"x1") over the female end of the supplied RJ-45 M-F cable.
1. Direct connection: To connect directly to the EtherNet/IP Option Card, plug one end of a CAT-5 EtherNet/IP crossover cable into the RJ-45 socket on the supplied RJ-45 M-F cable. Connect the other
10. Configure the EtherNet/IP network.
a. The default configuration option for the EtherNet/IP Option Card is
DHCP (Dynamic Host Configuration Protocol). Thus there must be a DHCP Server connected to the network in order to have the IP address of the EtherNet/IP Option Card set. For detailed information on how to set up the Rockwell BOOTP/DHCP Server on a PC refer to the appropriate Rockwell document or Yaskawa's Application Note AN.AFD.10.
11. Configuring a PC with a static IP address
a. Select an existing connection or create a new network connection for communication with the EtherNet/IP Option Card.
1. Select Start ==> Settings ==> Network Connections from the task bar in the Windows OS.
2. Select the network connection to be used.
b. Right click on the network connection and select Properties from the drop-down menu.
c. Select Internet Protocol (TCP/IP) from the components displayed.
Note: If a TCP/IP selection is not available, it may be installed by selecting Install. Administrator access to the PC and the OS operating system installation CD-ROMs may also be required.
1. Select Properties.
Note: If the PC is on a building or office network, disconnect it from that network before proceeding. Record the existing network settings. If the network connection already has an IP address assigned on the EtherNet/IP Local network, ignore the following instructions and just click on Cancel.
2. Select the Use the following IP address radio button.
3. Enter the IP address of a vacant IP address on the EtherNet/IP Local Network (192.168.1.19 in this example).
4. Enter the subnet mask for the EtherNet/IP Local Network (255.255.255.0 in this example).
5. Check the system network schematic or with your network administrator to ensure that the IP address does not already exist on the network.
6. Once the IP address and Subnet mask are entered, select OK.
Note: It may be necessary to reboot the PC in order for the changes to take effect.
end to the RJ-45 EtherNet/IP socket on the configuration device, typically a controller, laptop or other PC.
2. Connection through hub or switch: To connect through a switch, hub or router, connect the RJ-45 socket on the RJ-45 M-F cable to the switch, hub or router using a standard CAT-5 patch cable.
b. After the network connection is made, slide the insulated tubing
(4"x1" Insulated Tubing) over the connection and secure it in place using the supplied cable ties.
b. If the network configuration requires that devices have a static IP
address, the EtherNet/IP Option Card's configuration can be changed to USER and the appropriate static IP address can be entered via the EtherNet/IP Option Card's web pages as shown below.
Note that the EtherNet/IP Option Card must first have been assigned an IP address via DHCP before its configuration can be changed.
12. Accessing the EtherNet/IP Option Card web pages
The browser interface to the EtherNet/IP Option Card can be used for configuring the card or for network and drive information and diagnostics. To access the web pages:
a. Obtain the IP address of the desired drive and enter that IP address in the browser address bar. Hit Enter. The IP address of the desired drive is 192.168.1.20 in
this example. The main web page should be displayed.
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 3 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
Configuration: USE
R
IP Address: 192.168.1.37 Subnet mask: 255.255.255.0
Enable Browser Interface Gateway Usage Disabled
CM092
13. Configuring the EtherNet/IP Option Card
a. Select Configuration from the main web page.
b. After the Configuration page has been displayed, select the method in
which the EtherNet/IP Option Card will obtain its IP address.
1. User: The EtherNet/IP Option Card will use the network address as entered in the IP, Subnet and Gateway fields. Check with the system schematic or network administrator to insure that the IP address is valid and unique and that the subnet mask is correct.
The USER radio button is used in this example.
Enter the new IP address, 192.168.1.37 in this example.
2. DHCP: The EtherNet/IP Option Card will use the network address assigned to it by the DHCP server.
3. BOOTP: The EtherNet/IP Option Card will use the network address assigned to it by the BOOTP server.
c. Select the Gateway Usage. Connectivity to the EtherNet/IP Option Card
may be limited or nonfunctional if the gateway usage setting and gateway address do not match the network infrastructure in which it is installed.
1. Do not use default gateway in system. Select this radio button to disable the gateway when there is no external gateway in the system.
2. Use default gateway in system. Select this radio button to enable the gateway when there is an external gateway in the system. Verify and/or update the gateway address as necessary, so that it matches the address of the system gateway.
3. In all cases the Gateway field must contain a valid IP address and must not be blank.
d. When the new configuration, IP address and subnet mask have been
entered, click the Submit button.
e. Verify that the information is correct on the Submit Results page.
f. Power cycle the drive in order to store the new information on the
EtherNet/IP Option Card.
g. Note: The IP address in the browser address bar will have to be changed
to the drive's new IP address and the web page refreshed in order to continue to communicate with the EtherNet/IP Option Card web pages.
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 4 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
WARNING
WARNING
CM092
14. Finish the EtherNet/IP Option Card installation.
a. Remove power from the AC drive and wait for the charge lamp to be
completely extinguished. Wait at least five additional minutes for the drive to be completely discharged. Measure the AC drive DC bus voltage and verify that it is at a safe level.
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC (460V drives) are present at the DC bus terminals of the drive.
b. Reinstall all drive covers and the operator keypad. Apply power to the
drive.
c. Set parameters b1-01 and b1-02 to their appropriate values.
Refer to the table to the right for available b1-01 and b1-02 values.
15. Resetting the EtherNet/IP Option Card to its default configuration
The factory default settings are as follows:
Configure Network Parameters: DHCP
IP Address: 192.168.1.20
Subnet: 255.255.255.0
Gateway: 192.168.1.1
Symptom: The Yaskawa EtherNet/IP Option Card Main web page does not display on the PC web browser screen.
Corrective Action: Check that the PC is set up, properly connected and that an IP address has been assigned to both the server and the node and that they are on the same local network.
If the web page is still not visible after confirming PC set up, then reset the configuration of the EtherNet/IP Option Card to its factory default as follows:
a. Remove power from the AC drive and wait for the charge lamp to be
completely extinguished. Wait at least five additional minutes for the drive to be completely discharged. Measure the AC drive DC bus voltage and verify that it is at a safe level.
Parameter Function Data Description Default
0 Digital Operator
1Terminal Strip
b1-01
b1-02
Reference
Source
Run
Source
Built-in Modbus RTU RS-485
2
Terminals
3 Option Kit (EtherNet/IP Option)
4 Pulse Input (F7 and G7 Only)
0 Digital Operator
1Terminal Strip
Built-in Modbus RTU RS-485
2
Terminals
3 Option Kit (EtherNet/IP Option)
1
1
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC (460V drives) are present at the DC bus terminals of the drive.
b. Place an insulated wire reset jumper between test points C and /LD on
the EtherNet/IP Option Card as shown in the figure to the right.
c. Reapply power to the AC drive and wait approximately 10 seconds for
the power-up cycle to complete.
d. Remove power from the AC drive and remove the jumper between C and
/LD on the EtherNet/IP Option Card.
e. Reapply power to the AC drive and wait approximately 10 seconds for
the power-up sequence to complete.
16. Important notes
a. It is strongly recommended that shielded CAT-5 patch or crossover cable
be used for all network cables. (Refer to step 9 above for the proper selection of patch or crossover cable).
b. Switches implementing IGMP snooping are strongly recommended.
When IGMP snooping is used, devices will only receive the multicast packets in which they are interested.
c. The maximum number of simultaneous connections is: 1 for I/O, 4 for
Explicit, 2 for Drive Wizard.
d. To simplify the drive configuration, EDS file can be obtained at
www.yaskawa.com. Select Downloads, By Inverter Drives, By
Product, and Network Comms-Ethernet. Then select the appropriate EDS file based on the drive series and the latest version from those listed. EDS files for individual drive models are compressed into a single Zip file and need to be un-zipped into a temporary directory in order to be installed.
e. Refer to the appropriate user, programming or parameter access manual
for a complete list of drive parameters and registers available. A list of applicable manuals is available at the end of this document.
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 5 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
MODEL:
CIMR-G7U20P4
SPEC: 20P41A
INPUT: AC3PH 200 - 240V 50/60Hz 3.8A
OUTPUT: AC3PH 0 - 240V 0 – 400Hz 3.2A 1.2kVA
O/N: MASS: 3.0kg
S/N: 1W0149999991W0001 PRG:
1W0149999991W0001
FILE NO: E131457
MAC ID: 00-20-B5-24-11-13
INVERTER MODULE
CODE NO.: EUJ615162
SERV. NO.: 4W06X7847760001
MASS: 125KG
YASKAWA AMERICA, INC.
MAC ID: 00-20-B5-24-11-13
CM092
17. Drive labeling and EDS files
a. Place the supplied MAC ID label on the side of the drive either above or below the drive nameplate.
Nameplate for all drives except G5HHP drives Nameplate for G5HHP drives
b. To simplify the drive configuration, EDS file can be obtained at www.yaskawa.com. Select Downloads, By Inverter Drives, By Product, and Network
Comms-Ethernet. Then select the appropriate EDS file based on the drive series and the latest version from those listed. EDS files for individual drive models are compressed into a single Zip file.
18. EtherNet/IP Option Card fault codes
The table of EtherNet/IP Option Card fault codes returned by the drive is shown below. Refer to the appropriate drive user and/or programming manual(s) for drive specific information on the fault returned.
Note: G5HHP drive differences are denoted by bold text inside carets <> in the following table.
EtherNet/IP Fault Code
[hex]
0000h None 5300h OPE errors (01,02,03,05,06,07,08,09,10,11)
2120h Ground Fault (GF) 6320h EEPROM R/W Error (ERR)
2130h Short Circuit (SC) 7110h Dynamic Braking Transistor (RR) <Reserved>
2200h
2220h Motor Overload (OL1) 7301h PG Open (PGO)
2221h Overtorque Detection 1 (OL3) 7310h Overspeed Detection (OS)
2222h Overtorque Detection 2 (OL4) 7310h Speed Deviation (DEV)
2300h Overcurrent (OC) 7500h EtherNet/IP Communication Error (BUS)
2310h High Slip Braking (OL7)
3130h Input Phase Loss (PF) 8313h Zero Servo Fault (SVE)
3130h Output Phase Loss (LF) 8321h Out of Control (CF)
3210h DC Bus Overvoltage (OV) 8321h Undertorque Detection 1 (UL3)
3220h DC Bus Undervoltage (UV1) 8321h Undertorque Detection 2 (UL4)
3222h MC Answerback (UV3) 9000h External Fault on Terminal S3 (EF3) <External Fault 3 (EF3) (Terminal 11)>
4200h Heatsink Over-temperature (OH) 9000h External Fault on Terminal S4 (EF4) <External Fault 4 (EF4) (Terminal 12)>
4210h Heatsink Maximum Temperature
4300h Motor Overheat 1 (OH3) 9000h External Fault on Terminal S6 (EF6) <External Fault 6 (EF6) (Terminal 14)>
4310h Motor Overheat 2 (OH4) 9000h External Fault on Terminal S7 (EF7) <External Fault 7 (EF7) (Terminal 15)>
5110h CTL PS Undervoltage (UV2) 9000h External Fault on Terminal S8 (EF8) <External Fault 8 (EF8) (Terminal 16)>
5120h DC Bus Fuse Open (PUF) 9000h External Fault Through Option Card (EF0)
5300h Operator Disconnected (OPR) - -
Description
EtherNet/IP
Fault Code
Description
[hex]
Inverter Overload (OL2) 7112h Dynamic Braking Resistor (RH) <Reserved>
8110h Feedback Loss (FBL)
<Reserved>
9000h External Fault on Terminal S5 (EF5) <External Fault 5 (EF5) (Terminal 13)>
(OH1)
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 6 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Card Supported Class Summary
EtherNet/IP Option Kit
CM092
01 – Identity Object 02 – Message Router Object 04 – Assembly Object
06 – Connection Manager Object 28 – Motor Object 29 – Control Supervisor Object
Supported Output Instances for Assembly Object Class 04
Basic Speed Control Output Instance 20 (14h)
Output
Instance
20 (14h)
Extended Speed Control Output Instance 21 (15h)
Output
Instance
21 (15h)
Speed and Torque Control Output Instance 22 (16h)
Output
Instance
22 (16h)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h - - - - - Fault Reset - Run Forward
1h Reserved
2h Speed Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]
3h Speed Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h -
1h Reserved
2h Speed Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]
3h Speed Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h-- ---Fault Reset-Run Forward
1h Reserved
2h Speed Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]
3h Speed Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
4h Torque Reference (Low Byte) [0.1%] [U1-09]
5h Torque Reference (High Byte) [0.1%] [U1-09]
Net Reference
<Not Available>
Net Run/Stop
<Not Available>
2A – AC Drive Object 64 – Yaskawa Command Object 65 – Yaskawa Status Object
F5 – TCP/IP Object F6 – Ethernet Link Object
Note: G5HHP drive differences are denoted by bold text inside carets <> in the following tables.
- - Fault Reset Run Reverse Run Forward
Extended Speed and Torque Control Output Instance 23 (17h)
Output
Instance
23 (17h)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h -
1h Reserved
2h Speed Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]
3h Speed Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
4h Torque Reference (Low Byte) [0.1%] [U1-09]
5h Torque Reference (High Byte) [0.1%] [U1-09]
Net Reference
<Not Available>
Net Run/Stop
<Not Available>
- - Fault Reset Run Reverse Run Forward
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 7 of 16
Date: 08/18/2011 Rev: 11-08
Yaskawa Standard Speed/Torque Control Output Instance 101 (65h)
Output
Instance
101
(65h)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h
1h
2h Speed Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]>
3h Speed Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
4h Torque Reference (Low Byte) [0.1%] [U1-09]
5h Torque Reference (High Byte) [0.1%] [U1-09]
6h
7h
Terminal S8
<Terminal 16>
Terminal M5-M6
<Terminals 20-50>
Terminal S7
<Terminal 15>
Terminal M3-M4
<Terminals 19-50>
Terminal S6
<Terminal 14>
Terminal M1-M2
<Terminals 53-57>
<Torque Compensation (Low Byte) [0.1%]>
<Torque Compensation (High Byte) [0.1%]>
<Terminal 13>
Reserved
Reserved
Yaskawa Extended Speed/Torque Control Output Instance 115 (73h)
Output
Instance
115
(73h)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h
1h
2h Speed Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]
3h Speed Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
4h Torque Reference (Low Byte) [0.1%] [U1-09]
5h Torque Reference (High Byte) [0.1%] [U1-09]
6h Torque Compensation (Low Byte) [0.1%]
7h Torque Compensation (High Byte) [0.1%]
8h ~ Bh Reserved
Ch
Dh
Eh
Fh
10h
11h
12h ~
13h
14h ~
15h
16h ~
27h
Terminal S8
<Terminal 16>
Terminal M5-M6
<Terminals 20-50>
Terminal S7
<Terminal 15>
Terminal M3-M4
<Terminals 19-50>
Analog Output Terminal FM (Low Byte) [-726 ~ +726 (-11VDC ~ +11VDC)]
Analog Output Terminal FM (High Byte) [-726 ~ +726 (-11VDC ~ +11VDC)]
Analog Output Terminal AM (Low Byte) [-726 ~ +726 (-11VDC ~ +11VDC)]
Analog Output Terminal AM (High Byte) [-726 ~ +726 (-11VDC ~ +11VDC)]
Network Control (bit 0: Network Speed Reference, bit 1: Network Run Command)
Terminal S6
<Terminal 14>
Terminal M1-M2
<Terminals 53-57>
<Analog Input Terminal 36 (Low Byte)>
<Analog Input Terminal 36 (High Byte)>
<Analog Input Terminal 39 (Low Byte)>
<Analog Input Terminal 39 (High Byte)>
Digital Output Terminal M1-M2 (Low Byte)
<Digital Output (Low Byte) U1-11>
Digital Output Terminal M3-M4 (High Byte)
<Digital Output (High Byte) U1-11>
<Terminal 13>
Reserved
<Reserved>
Reserved
EtherNet/IP Option Kit
Terminal S5
---
Terminal S5
---
Terminal S4
<Terminal 12>
Terminal S4
<Terminal 12>
Terminal S3
<Terminal 11>
Terminal S3
<Terminal 11>
CM092
Run
Run
Forward
External
Forward
External
Reverse
Fault
Reset
Reverse
Fault
Reset
Run
Fault
Run
Fault
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 8 of 16
Date: 08/18/2011 Rev: 11-08
Supported Input Instances for Assembly Object Class 04
Note: G5HHP drive differences are denoted by bold text inside carets <> in the following tables.
Basic Speed Control Input Instance 70 (46h)
Output
Instance
70 (46h)
Extended Speed Control Input Instance 71 (47h)
Output
Instance
71 (47h)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h---- -
1h Reserved
2h
3h
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h
1h Reserved
2h
3h
Speed Agree
Net
Reference
Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
<Speed Actual (Low Byte) [Scaled by parameter o1-03]>
Output Frequency (High Byte) [Scaled by parameter o1-03] [U1-02]
<Speed Actual (High Byte) [Scaled by parameter o1-03]>
Net Run/
Stop
Drive Ready
Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
<Speed Actual (Low Byte) [Scaled by parameter o1-03]>
Output Frequency (High Byte) [Scaled by parameter o1-03] [U1-02]
<Speed Actual (High Byte) [Scaled by parameter o1-03]>
Running Rev
<Running 2 (REV)>
Running Fwd
<Running 1 FWD>
<Running 1 (FWD)>
EtherNet/IP Option Kit
CM092
- Fault
Running Fwd
Alarm Fault
Speed and Torque Control Input Instance 72 (48h)
Output
Instance
72 (48h)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h-----
1h Reserved
2h
3h
4h
5h
Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
<Speed Actual (Low Byte) [Scaled by parameter o1-03]>
Output Frequency (High Byte) [Scaled by parameter o1-03] [U1-02]
<Speed Actual (High Byte) [Scaled by parameter o1-03]>
Torque Reference (Low Byte) [0.1%] [U1-09]
<Torque Actual (Low Byte) [0.1%]>
Torque Reference (High Byte) [0.1%] [U1-09]
<Torque Actual (High Byte) [0.1%]>
Extended Speed and Torque Control Input Instance 73 (49h)
Output
Instance
73 (49h)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h
1h Reserved
2h
3h
4h
5h
Speed Agree
Net
Reference
Net Run/
Stop
Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
Output Frequency (High Byte) [Scaled by parameter o1-03] [U1-02]
Drive Ready
<Speed Actual (Low Byte) [Scaled by parameter o1-03]>
<Speed Actual (High Byte) [Scaled by parameter o1-03]>
Torque Reference (Low Byte) [0.1%] [U1-09]
<Torque Actual (Low Byte) [0.1%]>
Torque Reference (High Byte) [0.1%] [U1-09]
<Torque Actual (High Byte) [0.1%]>
Running Rev
<Running 2 (REV)>
Running Fwd
<Running 1 FWD>
Running Fwd
<Running 1 FWD>
-Fault
Alarm Fault
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 9 of 16
Date: 08/18/2011 Rev: 11-08
Yaskawa Standard Speed/Torque Input Instance 151 (97h)
Output
Instance
151 (97h)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h @Fault @Alarm @Drive Ready @Speed Agree @Reset
@Zero Servo
1h
2h Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
3h Output Frequency (High Byte) [Scaled by parameter o1-03] [U1-02]
4h Torque Reference (Low Byte) [0.1%] [U1-09]
5h Torque Reference (High Byte) [0.1%] [U1-09]
6h Output Current (Low Byte) [0.01A up to 11kW, 0.1A 15kW and above] [U1-03]
7h Output Current (High Byte) [0.01A up to 11kW, 0.1A 15kW and above] [U1-03]
Complete
<Zero Servo>
Terminal M5-M6
-
<Terminals 20-50>
Terminal M3-M4
<Terminals 19-50>
Table 1: Yaskawa Extended Speed/Torque Input Instance 155 (9Bh)
Output
Instance
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0h Fault Alarm Drive Ready Speed Agree Reset Active
EtherNet/IP Option Kit
Terminal M1-M2
<Terminals 53-
57>
@Running
Rev
@Local
Mode
Running
Rev Zero Speed
@Zero Speed
Undervoltage @OPE Error
CM092
@Running
Fwd
Running Fwd
155 (9Bh)
Refer to
Table 2 for
G5HHP
Error Alarm
Details
Zero Servo
1h
2h Motor Speed (Low Byte) [Scaled by parameter o1-03] [U1-05] [Not available in V/F control mode (A1-02 = 0)]
3h Motor Speed (High Byte) [Scaled by parameter o1-03] [U1-05] [Not available in V/F control mode (A1-02 = 0)]
4h Torque Reference (Low Byte) [0.1%] [U1-09]
5h Torque Reference (High Byte) [0.1%] [U1-09]
6h
7h
8h Frequency Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]
9h Frequency Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
Ah Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
Bh Output Frequency (High Byte) [Scaled by parameter o1-03] [U1-02]
Ch Output Current (Low Byte) [0.01A up to 11kW, 0.1A 15kW and above] [U1-03]
Dh Output Current (High Byte) [0.01A up to 11kW, 0.1A 15kW and above] [U1-03]
Eh
Fh
10h Main Circuit DC Voltage (Low Byte) [1VDC] [U1-07]
11h Main Circuit DC Voltage (High Byte) [1VDC] [U1-07]
12h Error Alarm 1 (Low Byte) [See Section 18 on Page 7 for a list of fault codes]
13h Error Alarm 1 (High Byte) [See Section 18 on Page 7 for a list of fault codes]
14h Error Alarm 2 (Low Byte) [See Section 18 on Page 7 for a list of fault codes]
15h Error Alarm 2 (High Byte) [See Section 18 on Page 7 for a list of fault codes]
16h Error Alarm 3 (Low Byte) [See Section 18 on Page 7 for a list of fault codes]
17h Error Alarm 3 (High Byte) [See Section 18 on Page 7 for a list of fault codes]
Complete
<Zero
Servo>
Terminal M5-M6
-
<Terminal 20-50>
Terminal M3-M4
<Terminals 19-50>
PG Counter Channel 1 (Low Byte) [rolling counter from -32,766 ~ 32,767]
PG Counter Channel 1 (High Byte) [rolling counter from -32,766 ~ 32,767]
<PG Count Value (PG-X2) (Low Byte)*>
<PG Count Value (PG-X2) (High Byte)*>
Terminal A2 Output (Low Byte) [0.1%] [U1-16]
<Inverter AI Terminal 39 Output (Low Byte)>
Terminal A2 Output (High Byte) [0.1%] [U1-16]
<Inverter AI Terminal 39 Output (High Byte)>
Terminal M1-M2
<Terminals 53-
57>
Local Mode
Undervoltag
e
OPE Error
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 10 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
Table 1: (continued) Yaskawa Extended Speed/Torque Input Instance 155
Output
Instance
155 (9Bh)
* Encoder pulse count from PG-X2 option when in flux vector mode. There is no associated drive parameter
** Encoder pulse count from PG-W2 option when in flux vector mode and using motor 2. Speed detection PG counter value.
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
18h
19h
1Ah
1Bh
1Ch
1Dh
1Eh
1Fh
20h
21h ~
27h
Digital Input Terminal Bit Field (Low Byte) [Terminals S1 ~ S8] [U1-10]
Digital Input Terminal Bit Field (High Byte) [Terminals S1 ~ S8] [U1-10]
PG Counter Channel 2 (Low Byte) [rolling counter from -32,766 ~ 32,767]
PG Counter Channel 2 (High Byte) [rolling counter from -32,766 ~ 32,767]
Terminal A3 Output (Low Byte) [0.1%] [U1-17]
<Inverter AI Terminal 42 Input (Low Byte)>
Terminal A3 Output (High Byte) [0.1%] [U1-17]
<Inverter AI Terminal 42 Input (High Byte)>
<Inverter DI Terminals 9~16 Input (Low Byte)>
<Inverter DI Terminals 9~16 Input (High Byte)>
Terminal A1 Output (Low Byte) [0.1%] [U1-15]
<Inverter AI Terminal 36 Input (Low Byte)>
Terminal A1 Output (High Byte) [0.1%] [U1-15]
<Inverter AI Terminal 36 Input (High Byte)>
<PG Counter (Ch2) (PG-W2) (Low Byte)**>
<PG Counter (Ch2) (PG-W2) (High Byte)**>
Drive Software Number (U1-14)
<Reserved>
Reserved
CM092
Table 1 Details: G5HHP bytes 12 to 17 for Instance 155 (9Bh)
Reference details in Table 1: Yaskawa Extended Speed/Torque Input Instance 155 (9Bh) for G5HHP drives bytes 12 to 17.
Bytes 12 (Low) and 13 (High) -
Error Alarm Signal 1
Bit Fault Bit Fault Bit Fault
0h PUF DC Bus Fuse Open 0h EF3 External Fault - Terminal 11 0h CE Modbus Communication Error
1h UV1 DC Bus Undervoltage 1h EF4 External Fault - Terminal 12 1h BUS EtherNet/IP Bus Fault
2h UV2 Control Circuit Undervoltage 2h EF5 External Fault - Terminal 13 2h <Reserved>
UV3 Main Circuit Contactor Answerback
3h
Fault
4h <Reserved> 4h EF7 External Fault - Terminal 15 4h
5h GF Ground Fault 5h EF8 External Fault - Terminal 16 5h
6h OC Overcurrent Fault 6h <Reserved> 6h EF0 External Communications Fault
7h OV Overvoltage Fault 7h OS Overspeed Fault 7h <Reserved>
8h OH Heatsink Over Temperature Fault 8h DEV Speed Deviation Fault 8h <Reserved>
9h OH1 Drive Overheat Fault 9h
Ah OL1 Motor Overload Fault Ah PF Input Phase Loss Fault Ah <Reserved>
Bh OL2 Drive Overload Fault Bh LF Output Phase Loss Bh <Reserved>
Ch OL3 Overtorque Fault 1 (L6-02) Ch <Reserved> Ch <Reserved>
Dh OL4 Overtorque Fault 2 (L6-05) Dh OPR Operator Disconnected Dh <Reserved>
Eh RR Not possible in HHP Eh ERR EEPROM R/W Error Eh <Reserved>
Fh RH Not possible in HHP Fh <Reserved> Fh <Reserved>
Bytes 14 (Low) and 15 (High) -
Error Alarm Signal 2
3h EF6 External Fault - Terminal 14 3h <Reserved>
PGO PG Open, Encoder (Pulse Generator open circuit)
9h <Reserved>
Bytes 16 (Low) and 17 (High) -
CF Out of Control Fault No Determination of Motor Speed
SVE Zero Servo Fault (Closed loop flux vector only)
Error Alarm Signal 3
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 11 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
CM092
Parameter Specific data for G5HHP Modular Drives
Motor
Name Addr Text Limits Default
A1-00 100 Language Select 0 ~ 1 0 b3-01 18E
A1-01 101 Access Level Select 0 ~ 4 2 b3-02 18F
A1-02 102 Control Mode Select 0 ~ 3 0 b3-03 190
A1-03 103 Initialization Select 0 ~ 3330 0 b4-01 192 Timer On Delay 0.0 ~ 300.0 0.0
A1-04 104 Password 0 ~ 9999 0 b4-02 193 Timer Off Delay 0.0 ~ 300.0 0.0
A1-05 105 Password 0 ~ 9999 0 b5-01 194 PID Mode Select 0 ~ 2 0
A2-01 106 User Parameter 01 180h ~ 0 b5-02 195 PID P Gain 0.00 ~ 25.00 1.00
A2-02 107 User Parameter 02 180h ~ 0 b5-03 196 PID I Time 0.0 ~ 360.0 1.0
A2-03 108 User Parameter 03 180h ~ 0 b5-04 197 PID I Limit 0.00 ~ 100.0 100.0
A2-04 109 User Parameter 04 180h ~ 0 b5-05 198 PID D Time 0.0 ~ 10.00 0.00
A2-05 10A User Parameter 05 180h ~ 0 b5-06 199 PID Limit 0.0 ~ 100.0 100
A2-06 10B User Parameter 06 180h ~ 0 b5-07 19A PID Offset
A2-07 10C User Parameter 07 180h ~ 0 b5-08 19B PID Delay 0.00 ~ 10.00 0.00
A2-08 10D User Parameter 08 180h ~ 0 b6-01 19C
A2-09 10E User Parameter 09 180h ~ 0 b6-02 19D Dwell Time at Start 0.0 ~ 10.0 0.0
A2-10 10F User Parameter 10 180h ~ 0 b6-03 19E
A2-11 110 User Parameter 11 180h ~ 0 b6-04 19F Dwell Time at Stop 0.0 ~ 10.0 0.0
A2-12 111 User Parameter 12 180h ~ 0 b7-01 1A0 Droop Gain 0.0 ~ 100.0 0.0 FV
A2-13 112 User Parameter 13 180h ~ 0 b7-02 1A1 Droop Delay 0.03 ~ 2.00 0.05 FV
A2-14 113 User Parameter 14 180h ~ 0 b8-01 1A2 Energy Savings Gain 0 ~ 100 80
A2-15 114 User Parameter 15 180h ~ 0 b8-02 1A3
A2-16 115 User Parameter 16 180h ~ 0 b9-01 1A4 Zero Servo Gain 0 ~ 100 5 FV
A2-17 116 User Parameter 17 180h ~ 0 b9-02 1A5
A2-18 117 User Parameter 18 180h ~ 0 C1-01 200 Accel Time 1 0.0 ~ 6000.0 30.0
A2-19 118 User Parameter 19 180h ~ 0 C1-02 201 Decel Time 1 0.0 ~ 6000.0 30.0
A2-20 119 User Parameter 20 180h ~ 0 C1-03 202 Accel Time 2 0.0 ~ 6000.0 30.0
A2-21 11A User Parameter 21 180h ~ 0 C1-04 203 Decel Time 2 0.0 ~ 6000.0 30.0
A2-22 11B User Parameter 22 180h ~ 0 C1-05 204 Accel Time 3 0.0 ~ 6000.0 30.0
A2-23 11C User Parameter 23 180h ~ 0 C1-06 205 Decel Time 3 0.0 ~ 6000.0 30.0
A2-24 11D User Parameter 24 180h ~ 0 C1-07 205 Accel Time 4 0.0 ~ 6000.0 30.0
A2-25 11E User Parameter 25 180h ~ 0 C1-08 207 Decel Time 4 0.0 ~ 6000.0 30.0
A2-26 11F User Parameter 26 180h ~ 0 C1-09 208 Fast Stop Time 0.0 ~ 6000.0 30.0
A2-27 120 User Parameter 27 180h ~ 0 C1-10 209 Accel/Decel Unit Select 0 ~ 1 0
A2-28 121 User Parameter 28 180h ~ 0 C1-11 20A
A2-29 122 User Parameter 29 180h ~ 0 C2-01 20B S-Curve Accel at Start 0.00 ~ 2.50 0.20
A2-30 123 User Parameter 30 180h ~ 0 C2-02 20C S-Curve Accel at End 0.00 ~ 2.50 0.20
A2-31 124 User Parameter 31 180h ~ 0 C2-03 20D S-Curve Decel at Start 0.00 ~ 2.50 0.20
A2-32 125 User Parameter 32 180h ~ 0 C2-04 20E S-Curve Decel at End 0.00 ~ 2.50 0.20
b1-01 180 Reference Source Select 0 ~ 3 1 C3-01 20F Slip Comp Gain 0.00 ~ 2.50 0.00
b1-02 181
b1-03 182 Stopping Method Select 0 ~ 3 0 C3-03 211 Slip Comp Limit 0 ~ 250 200
Run Command Source Select
0 ~ 3 1 C3-02 210 Slip Comp Time 0 ~ 10000 2000
Control Method
_
Name Addr Text Limits Default
_
Speed Search Mode Select
Speed Search Current Level
Speed Search Decel Time
Dwell Reference at Start
Dwell Reference at Stop
Energy Savings Reference
Zero Servo Completion Width
Accel/Decel Switch Frequency
0 ~ 1 0
0 ~ 200 150
0.1 ~ 10.0 10.0
-100.0 ~ +100.0
0.0 ~ 150.0 0.0
0.0 ~ 150.0 0.0
0.0 ~ 150.0 0.0
0 ~ 16383 10 FV
0.0 ~ 150.0 0.0
0.0
Motor Control Method
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 12 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
CM092
b1-04 183 Reverse Prohibit Select 0 ~ 1 0 C3-04 212
b1-05 184 Zero Speed Mode Select 0 ~ 3 0 FV C3-05 242 Flux Select 0 ~ 1 0 OLV
b1-06 185 I/O Scan Time Select 0 ~ 1 1 C4-01 213 Torque Comp Gain 0.00 ~ 2.50 1.00
b1-07 186 Local/Remote Select 0 ~ 1 0 C4-02 214 Torque Comp Time 0 ~ 10000 1000
b2-01 187
b2-02 188
b2-03 189 DC Injection Time at Start 0.00 ~ 10.00 0.00 C5-03 217 ASR P Gain 2 0.00 ~ 300.00 20.00 w/ PG
b2-04 18A DC Injection Time at Stop 0.00 ~ 10.00 0.00 C5-04 218 ASR I Time 2
C5-05 219 ASR Limit 0.0 ~ 20.0 5.0 V/f w/PG E2-03 310 No-Load Current 0.0 ~ 2000.0 192.0
C5-06 21A ASR Delay Time 0.000 ~ 0.500 0.004 FV E2-04 311 Number of Motor Poles 2 ~ 48 4 w/ PG
C5-07 21B
C5-08 241 ASR I Limit 0 ~ 400 400 FV E2-06 313 Leakage Inductance 0.0 ~ 30.0 5.0 OLV, FV
C6-01 21C
C6-02 21D
C6-03 21E Carrier Frequency Gain 00 ~ 99 36 E2-09 316 Mechanical Loss 0.0 ~ 10.0 0.0 OLV, FV
C7-01 21F Hunting Prevention Select 0 ~ 1 1 E3-01 317
C7-02 220 Hunting Prevention Gain 0.00 ~ 2.50 1.00 E4-01 318
C8-08 22A AFR Gain 0.00 ~ 10.00 1.00 OLV E4-02 319
C8-09 22B AFR Time 0 ~ 200 50 OLV E4-03 31A
C8-30 240
C9-04 24B
d1-01 280 Frequency Reference 1 0.0 ~ 150.0 0.0 E4-06 31D
d1-02 281 Frequency Reference 2 0.0 ~ 150.0 0.0 E4-07 31E
d1-03 282 Frequency Reference 3 0.0 ~ 150.0 0.0 E5-01 31F Motor 2 Rated Current 0.0 ~ 2000.0 740.0
d1-04 283 Frequency Reference 4 0.0 ~ 150.0 0.0 E5-02 320 Motor 2 Rated Slip 0.00 ~ 20.00 1.30
d1-05 284 Frequency Reference 5 0.0 ~ 150.0 0.0 E5-03 321
d1-06 285 Frequency Reference 6 0.0 ~ 150.0 0.0 E5-05 323
d1-07 286 Frequency Reference 7 0.0 ~ 150.0 0.0 F1-01 380 Encoder (PG) PPR 0 ~ 60000 1024 w/ PG
d1-08 287 Frequency Reference 8 0.0 ~ 150.0 0.0 F1-02 381
d1-09 288 Jog Frequency Reference 0.0 ~ 150.0 6.0 F1-03 382 PG Overspeed Select 0 ~ 3 1 w/ PG
d2-01 289
d2-02 28A
d3-01 28B Jump Frequency 1 0.0 ~ 150.0 0.0 F1-06 385
d3-02 28C Jump Frequency 2 0.0 ~ 150.0 0.0 F1-07 386
d3-03 28D Jump Frequency 3 0.0 ~ 150.0 0.0 F1-08 387 PG Overspeed Level 0 ~ 120 115 w/ PG
d3-04 28E Jump Bandwidth 0.0 ~ 20.0 1.0 F1-09 388 PG Overspeed Time 0.0 ~ 2.0 0.0 w/ PG
DC Injection Start Frequency
DC Injection Current Level
ASR Switchover Frequency
Carrier Frequency Upper Limit
Carrier Frequency Lower Limit
Carrier Frequency in Auto Tune
CT/VT Operation Mode Select
Frequency Reference Upper Limit
Frequency Reference Lower Limit
0.0 ~ 10.0 0.5 C5-01 215 ASR P Gain 0.00 ~ 300.00 20.00 w/ PG
0 ~ 100 50 C5-02 216 ASR I Time
0.0 ~ 150.0 0.0 FV E2-05 312
0.4 ~ 2.0 2.0 E2-07 314 Saturation Coefficient 1 0.00 ~ 0.50 0.50 OLV, FV
0.4 ~ 2.0 1.0 E2-08 315 Saturation Coefficient 2 0.00 ~ 0.75 0.75 OLV, FV
0 ~ 1 0 OLV E4-04 31B
0 ~ 1 E4-05 31C
0.0 ~ 110.0 100.0 F1-04 383 PG Deviation Select 0 ~ 3 3 w/ PG
0.0 ~ 109.0 0.0 F1-05 384 PG Rotation Select 0 ~ 1 0 w/ PG
Slip Comp Regen Select
Motor Line-to-Line Resistance
Motor 2 Control Mode Select
Motor 2 Max Output Frequency
Motor 2 Max Output Voltage
Motor 2 Base Frequency
Motor 2 Mid Output Frequency A
Motor 2 Mid Output Voltage A
Motor 2 Min Output Frequency
Motor 2 Min Output Voltage
Motor 2 No-Load Current
Motor 2 Line-to-Line Resistance
PG Feedback Loss Select
PG Output Monitor Ratio
PG Integral Accel/ Decel Select
0 ~ 1 0
0.000 ~
10.000
0.000 ~
10.000
0.000 ~
65.000
0 ~ 1 1
50.0 ~ 150.0 60.0
0.0 ~ 510.0 460.0
0.0 ~ 150.0 60.0
0.0 ~ 150.0 3.0
0.0 ~ 510.0 27.6
0.0 ~ 150.0 1.5
0.0 ~ 510.0 13.8
0.0 ~ 2000.0 192.0
0.000 ~
65.000
0 ~ 3 1 w/ PG
1 ~ 132 1 w/ PG
0 ~ 1 0 V/f w/PG
0.500 w/ PG
0.500 w/ PG
0.010
0.010
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 13 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
CM092
d4-01 28F
d4-02 290 Trim Control Level 0 ~ 100 10 F1-11 38A
d5-01 291 Torque Control Select 0 ~ 1 0 FV F1-12 38B PG Gear Teeth 1 0 ~ 1000 0 V/f w/PG
d5-02 292 Torque Reference Filter 0 ~ 1000 0 FV F1-13 38C PG Gear Teeth 2 0 ~ 1000 0 V/f w/PG
d5-03 293 Speed Limit Select 1 ~ 2 1 FV F1-14 397
d5-04 294 Speed Limit Value -120 ~ +120 0 FV F2-01 38D A1-14B Input Select 0 ~ 1 0
d5-05 295 Speed Limit Bias 0 ~ 120 10 FV F3-01 38E
d5-06 296
E1-01 300 Input Voltage 360 ~ 460 460 F4-02 390
E1-02 301
E1-03 302 V/f Pattern Select 0 ~ F F F4-04 392
E1-04 303
E1-05 304 Maximum Output Voltage 0.0 ~ 510.0 460.0 F5-02 394
E1-06 305 Base Frequency 0.0 ~ 150.0 60.0 F6-01 395 DO-08 Output Select 0 ~ 1 0
E1-07 306 Mid Output Frequency A 0.0 ~ 150.0 3.0 F7-01 396 PO-36F Output Select 0 ~ 4 1
E1-08 307 Mid Output Voltage A 0.0 ~ 510.0 27.6 F8-01 398
E1-09 308
E1-10 309 Minimum Output Voltage 0.0 ~ 510.0 13.8 F9-02 39A EF0 Detection Select 0 ~ 1 0
E1-11 30A Mid Output Frequency B 0.0 ~ 150.0 0.0 F9-03 39B EF0 Response Select 0 ~ 3 1
E1-12 30B Mid Output Voltage B 0.0 ~ 510.0 0.0 F9-04 39C Trace Sample Time 0 ~ 60000 0
E1-13 30C Base Voltage 0.0 ~ 510.0 0.0 F9-06 39F BUS Fault Select 0 ~ 3 1
E2-01 30E Motor Rated Current 80.0 ~ 1600.0 740.0 H1-01 400
E2-02 30F Motor Rated Slip 0.00 ~ 20.00 1.30 H1-02 401
H1-03 402
H1-04 403
H1-05 404
H1-06 405
H2-01 406
H2-02 407
H2-03 408
H3-01 409
H3-02 40A AI Terminal 36 Gain 0.0 ~ 100.0 100.0 L4-05 494
H3-03 40B AI Terminal 36 Bias
H3-04 40C
MOP Reference Memory Select
Speed/Torque Switchover Time
Motor Overload Curve Select
Maximum Output Frequency
Minimum Output Frequency
DI Terminal 13 Function Select
DI Terminal 14 Function Select
DI Terminal 15 Function Select
DI Terminal 16 Function Select
DO Terminal 53-57 Function
DO Terminal 19-50 Function
DO Terminal 20-50 Function
AI Terminal 36 Signal Type Select
AI Terminal 42 Signal Type Select
0 ~ 1 0 F1-10 389 Speed Deviation Level 0 ~ 50 10 w/ PG
Speed Deviation Delay Time
PG Loss Detection Delay Time
DI-08/DI-16H2 Input Select
0 ~ 1000 0 FV F4-01 38F
0 ~ 1 0 F4-03 391
50.0 ~ 150.0 60.0 F5-01 393
0.0 ~ 150.0 1.5 F9-01 399 EF0 Fault Select 0 ~ 1 0
0 ~ 77h 3 L3-03 48A
0 ~ 77h 4 L3-04 48B
0 ~ 77h 6 L3-05 48C
0 ~ 77h 8 L3-06 48D
0 ~ 37h 0 L4-01 490 Speed Agree Level 0.0 ~ 150.0 0.0
0 ~ 37h 1 L4-02 491 Speed Agree Width 0.0 ~ 20.0 2.0
0 ~ 37h 2 L4-03 492
0 ~ 1 0 L4-04 493
-100.0 ~ +100.0
0 ~ 1 0 L5-02 496
0.0 L5-01 495
AO-08/AO-12 Channel 1 Select
AO-08/AO-12 Channel 1 Gain
AO-08/AO-12 Channel 2 Select
AO-08/AO-12 Channel 2 Gain
DO-02C Channel 1 Select
DO-02C Channel 2 Select
SI-F/G E-15 Detection Select
DI Terminal 11 Function Select
DI Terminal 12 Function Select
Stall Prevention Accel CHP Limit
Stall Prevention Decel Select
Stall Prevention Run Select
Stall Prevention Run Level
Speed Agree Detection Level
Speed Agree Detection Width
Reference Loss Detection Select
Number of Auto Restarts Select
Auto Restart Fault Select
0.0 ~ 10.0 0.5 w/ PG
0.0 ~ 10.0 2.0 w/ PG
0 ~ 7 0
1 ~ 33 2
0.00 ~ 2.50 1.00
1 ~ 33 3
0.00 ~ 2.50 0.50
0 ~ 37 0
0 ~ 37 1
0 ~ 3 1
0 ~ 77h 24
0 ~ 77h 14
0 ~ 100 50
0 ~ 2 1
0 ~ 2 1
30 ~ 200 160
0.0 ~ 150.0 0.0
0.0 ~ 20.0 2.0
0 ~ 1 0
0 ~ 10 0
0 ~ 1 0
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 14 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
CM092
H3-05 40D
H3-06 40E AI Terminal 42 Gain 0.0 ~ 100.0 100.0 L6-02 499
H3-07 40F AI Terminal 42 Bias
H3-08 410
H3-09 411
H3-10 412 AI Terminal 39 Gain 0.0 ~ 100.0 100.0 L6-06 49D
H3-11 413 AI Terminal 39 Bias
H3-12 414 AI Terminals Filter Time 0.00 ~ 2.00 0.00 L7-02 49F Reverse Torque Limit 0 ~ 300 200 OLV, FV
H4-01 415
H4-02 416 AO Terminal 45 Gain 0.00 ~ 2.50 1.00 L7-04 4A1
H4-03 417 AO Terminal 45 Bias -10 ~ +10 0.0 L8-01 4A4
H4-04 418
H4-05 419 AO Terminal 48 Gain 0.00 ~ 2.50 0.50 L8-03 4A6 OH Pre-Alarm Select 0 ~ 3 3
H4-06 41A AO Terminal 48 Bias -10.0 ~ +10.0 0.0 L8-05 4A8 Input Phase Loss Select 0 ~ 1 0
H4-07 41B
H5-01 41C Modbus Node Address 0 ~ 20 1F o1-01 500 User Monitor Select 4 ~ 33 6
H5-02 41D Modbus Baud Rate Select 0 ~ 3 3 o1-02 501
H5-03 41E Modbus Parity Select 0 ~ 2 0 o1-03 502 Display Scaling Select 0 ~ 39999 0
H5-04 41F
H5-05 420
L1-01 480
L1-02 481
L2-01 482
L2-02 483
L2-03 484
L2-04 485
L2-05 486
L2-06 487 KEB Decel Time 0.0 ~ 100.0 0.0 o2-08 50C
L3-01 488
L3-02 489
Note: 1. Default values were determined through a 2-wire reset on drive model 4400. Default values may be different for different drive models.
2. Use address FFDDh for the ACCEPT command
3. Use address FFFDh for the ENTER command
IMPORTANT: Limit the use of the ENTER command. The drive has limited writes when using the ENTER command.
AI Terminal 42 Function Select
AI Terminal 39 Signal Type Select
AI Terminal 39 Function Select
AO Terminal 45 Function Select
AO Terminal 48 Function Select
AO Terminal Signal Type Select
Serial Fault Stopping Method
Serial Fault Detection Select
Motor Overload Fault Select
Motor Overload Time Constant
Power Loss Detection Select
Power Loss Ride-Thru Time
Minimum Baseblock Time
Voltage Recovery Ramp Time
Undervoltage Detection Level
Stall Prevention Accel Select
Stall Prevention Accel Level
1 ~ 1Fh 0 L6-01 498
-100.0 ~ +100.0
0 ~ 2 2 L6-04 49B
1 ~ 1Fh 1F L6-05 49C
-100.0 ~ +100.0
1 ~ 33h 2 L7-03 4A0
1 ~ 33h 3 L8-02 4A5 OH Pre-Alarm Level 50 ~ 110 95
0 ~ 1 0 L8-07 4AA
0 ~ 3 3 o1-04 503 V/f Pattern Unit Select 0 ~ 1 0
0 ~ 1 1 o1-05 504
0 ~ 1 1 o2-01 505
0.1 ~ 5.0 1.0 o2-02 506
0 ~ 2 0 o2-03 507
0.0 ~ 2.0 1.0 o2-04 508
0.0 ~ 25.5 10.0 o2-05 509
0.0 ~ 5.0 3.0 o2-06 50A
300 ~ 420 380 o2-07 50B
0 ~ 2 1 o2-09 50D
0 ~ 200 150 - - - - -
0.0 L6-03 49A
0.0 L7-01 49E Forward Torque Limit 0 ~ 300 200 OLV, FV
Torque Detection Select 1
Torque Detection Level 1
Torque Detection Time 1
Torque Detection Select 2
Torque Detection Level 2
Torque Detection Time 2
Forward Regen Torque Limit
Reverse Regen Torque Limit
DB Resistor Protection Select
Output Phase Loss Select
Power-On Monitor Select
Modbus Address Display Select
Local/Remote Key Select
Stop Key Function Select
User Initialize Default Select
Drive Model kVA Select
Operator MOP Function Select
Operator Detection Select
Elapsed Time Initial Setting
Elapsed Time Function Select
Initialization Mode Select
0 ~ 4 0
0 ~ 300 150
0.0 ~ 10.0 0.1
0 ~ 4 0
0 ~ 300 150
0.0 ~ 10.0 0.1
0 ~ 300 200 OLV, FV
0 ~ 300 200 OLV, FV
0 ~ 1 0
0 ~ 1 1
1 ~ 4 1
0 ~ 1 6
0 ~ 1 1
0 ~ 1 1
0 ~ 2 0
0 ~ FFh 4400
0 ~ 1 0
0 ~ 1 1
0 ~ 65535 0
0 ~ 1 0
0 ~ 2 1
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 15 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
CM092
Copies of this Installation Guide along with all technical manuals in ".pdf" format and support files may be obtained from either the CD supplied with the drive or from
www.yaskawa.com. Printed copies of any Yaskawa manual may be obtained by contacting the nearest Yaskawa office. Information on EtherNet/IP may be obtained
from www.odva.org.
Reference documents:
EtherNet/IP Option Card Installation Guide - IG.AFD.26
EtherNet/IP Option Card Technical Manual - TM.AFD.26
Application Note - Using the Yaskawa AC Drive "EtherNet/IP" Option with Controllogix / Compactlogix Programmable Controllers - AN.AFD.09
Application Note - Commissioning the Yaskawa Drive EtherNet/IP Option with the Rockwell BOOTP/DHCP Server - AN.AFD.10
G5U Technical Manual - TM.4515
G5M Modbus Technical Manual - TM.4025
G5HHP Drive Technical Manual - TM.G5HHP.01
E7U Drive User Manual - TM.E7.01
E7U Drive Programming Manual - TM.E7.02
F7U Drive User Manual - TM.F7.01
F7U Drive Programming Manual - TM.F7.02
F7U Drive Parameter Access Technical Manual - TM.F7.11
G7U Drive Technical Manual - TM.G7.01
P7U Drive User Manual - TM.P7.01
P7U Drive Programming Manual - TM.P7.02
EtherNet/IP CONFORMANCE TESTED™ is a certification mark of the ODVA.
®
Modbus
is a registered trademark of Schneider Automation, Inc.
YASKAWA AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: (800) YASKAWA (800-927-5292) Fax: (847) 887-7310 Internet: http://www.yaskawa.com
Data subject to change without notice
Yaskawa America, Inc. – www.yaskawa.com
IG.AFD.26, Page 16 of 16
Date: 08/18/2011 Rev: 11-08
Loading...