Modbus® Plus Option Kit
This document applies to the Yaskawa F7U, G7U, P7U, E7U, G5M(Spec F), and G5M(600V) drives. For
G5U(HHP) drives, refer to IG.G5HHP.17.
Unpack the CM071 Modbus Plus Option Card and verify that all components are present and undamaged.
CM071 Option Kit Parts List Qty.
Modbus Plus Option Card (46S03364-0010 or UTC000063) 1
Installation Guide (IG.AFD.17) 1
Connect power to the drive and verify that the drive functions correctly. This includes running the drive from the operator keypad. Refer to the
appropriate drive technical manual for information on connecting and operating the drive.
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the drive to be
completely discharged. Measure the DC bus voltage and verify that it is at a safe level.
Remove the operator keypad and drive cover.
Remove the operator keypad.
Remove any and all covers necessary to expose the drive terminal
assembly and control board. Refer to the appropriate drive
documentation for information on removing drive covers.
Remove the option card hold-down on the left side of the drive.
CM071
Mount the Modbus Plus Option Card on the drive.
Align the 2CN connector on the back of the Modbus Plus Option Card
with its mating 2CN connector on the front of the drive control card.
Align the three standoffs on the front of the drive control board with
the three holes on the right side of the Modbus Plus Option Card.
Press the Modbus Plus Option Card firmly onto the drive 2CN
connector and standoffs until the 2CN connector is fully seated and the
drive standoffs have locked into their appropriate holes.
For the F7, G7, and P7 drives, connect a ground wire from the ground
terminal on the Modbus Plus Option Card to a ground terminal on the
terminal assembly.
For the G5 drive, connect a ground wire from the ground terminal on
the Modbus Plus Option Card to terminal 12 on the drive’s terminal
strip.
Yaskawa Electric America, Inc – www.yaskawa.com
IG.AFD.17, Page 1 of 4
Date: 11/17/06, Rev: 06-11
DIP Switch Settings
Set the Modbus Plus network node address
Set cable loss and global read behavior.
Sw
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
2 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0
3 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0
4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0
5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
6 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Modbus Plus Network Node Address
Sw
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
2 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0
3 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0
4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0
5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Modbus Plus Network Node Address
SW 7 – Cable Loss Detection
0 Disabled
1 Enabled
Note: G5HHP drive response is governed by parameters
F6-01, F6-02 and F6-03. Refer to the appropriate user,
programming or technical manual for parameter
information
SW 8 – Global Read Function
0 Disabled
1 Enabled
Connect the drive to the Modbus Plus communication network.
Connect the Modbus Plus network cable to the Modicon 9-pin D-shell connector.
● Recommended cable is Belden 9841
● Available Modicon cables
▪ 97-9841-100 – Modbus Plus 100ft
▪ 97-9841-500100 – Modbus Plus 500ft
▪ 97-9841-01k100 – Modbus Plus 1000ft
● Modicon offers two connectors along with an assembly tool.
▪ AS-MBKT-085 – Modbus Plus In-line Connector
▪ AS-MBKT-185 – Modbus Plus Terminating Connector
▪ AS-MBPL-001 – Modbus Plus Connector Assembly Tool
● Assemble the cable to one of the connectors listed above. If this node is either at
the beginning or end of the network segment, use the terminating connector. For
all devices not at either end of the network segment, use the in-line connector.
Attach the Modicon connector to the 9-pin D-shell connector on top of the Modbus
Plus Option Card.
Apply power to the drive and verify that the diagnostic LED (D2) on the front of the Modbus Plus Option Card is in its correct state.
LED D2 States
Color State Timing Description
ON
Green Continuous slow blinking
Green Continuous rapid blinking
Green Two (2) rapid blinks
Green Three (3) rapid blinks
Green Four (4) rapid blinks
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
340ms
640ms
80ms
80ms
160ms
160ms
160ms
160ms
160ms
160ms
Drive is off-line and cannot transmit. It does, however, listen on the network and
build an active node table
Normal operation
Drive is permanently in the idle state and cannot be communicated with. Possibly a
bad transmitter
Drive cannot find any other nodes on the network. It claims and wins the token but
has nowhere to pass it, disrupting network communication. Possible network wiring
error
Duplicate node address found. Drive will stay off-line until the duplicate node
address has not been heard on the network for 5 seconds
Yaskawa Electric America, Inc – www.yaskawa.com