Note: G5HHP drive response is governed by parameters
F6-01, F6-02 and F6-03. Refer to the appropriate user,
programming or technical manual for parameter
information
SW 8 – Global Read Function
0 Disabled
1Enabled
Connect the drive to the Modbus Plus communication network.
Connect the Modbus Plus network cable to the Modicon 9-pin D-shell connector.
● Recommended cable is Belden 9841
● Available Modicon cables
▪ 97-9841-100 – Modbus Plus 100ft
▪ 97-9841-500100 – Modbus Plus 500ft
▪ 97-9841-01k100 – Modbus Plus 1000ft
● Modicon offers two connectors along with an assembly tool.
▪ AS-MBKT-085 – Modbus Plus In-line Connector
▪ AS-MBKT-185 – Modbus Plus Terminating Connector
▪ AS-MBPL-001 – Modbus Plus Connector Assembly Tool
● Assemble the cable to one of the connectors listed above. If this node is either at
the beginning or end of the network segment, use the terminating connector. For
all devices not at either end of the network segment, use the in-line connector.
Attach the Modicon connector to the 9-pin D-shell connector on top of the Modbus
Plus Option Card.
Apply power to the drive and verify that the diagnostic LED (D2) on the front of the Modbus Plus Option Card is in its correct state.
LED D2 States
Color State Timing Description
ON
Green Continuous slow blinking
Green Continuous rapid blinking
Green Two (2) rapid blinks
Green Three (3) rapid blinks
Green Four (4) rapid blinks
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
340ms
640ms
80ms
80ms
160ms
160ms
160ms
160ms
160ms
160ms
Drive is off-line and cannot transmit. It does, however, listen on the network and
build an active node table
Normal operation
Drive is permanently in the idle state and cannot be communicated with. Possibly a
bad transmitter
Drive cannot find any other nodes on the network. It claims and wins the token but
has nowhere to pass it, disrupting network communication. Possible network wiring
error
Duplicate node address found. Drive will stay off-line until the duplicate node
address has not been heard on the network for 5 seconds
Yaskawa Electric America, Inc – www.yaskawa.com
IG.AFD.17, Page 2 of 4
Date: 11/17/06, Rev: 06-11
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the drive to be
completely discharged. Measure the DC bus voltage and verify that it is at a safe level.
Reinstall the operator keypad and all drive covers. Apply power to the drive.
Set the following parameters in the table below. Use F6-02 and F6-03 for F7, G7 and P7 drives. Use F9-02 and F9-03 for G5 drives.
Parameter Function Data Description Default
0 Digital Operator
b1-01
b1-02 Run Command Source Selection
F6-02
F6-03
F9-02
F9-03
Frequency Reference Source
Selection
External Fault Detection
(F7, G7, and P7 drives only)
Stopping Method for External Fault
(F7, G7, and P7 drives only)
External Fault Detection
(G5 drive only)
Stopping Method for External Fault
(G5 drive only)
1 Terminal Strip
2 Built-in Modbus RTU Terminals
3
Option Card (Modbus Plus Option Card)
4 Pulse Input (F7 and G7 only)
0 Digital Operator
1 Terminal Strip
2 Built-in Modbus RTU Terminals
3
Option Card (Modbus Plus Option Card)
0 Always Detect
1 Detect Only During Run
0 Ramp to Stop
1 Coast to Stop
2 Emergency Stop (Deceleration time set by C1-09)
3 Operation Continues
0 Always Detect
1 Detect Only During Run
0 Ramp to Stop
1 Coast to Stop
2 Emergency Stop (Deceleration time set by C1-09)
3 Operation Continues
1
1
0
1
0
1
Yaskawa Electric America, Inc – www.yaskawa.com
IG.AFD.17, Page 3 of 4
Date: 11/17/06, Rev: 06-11
Modbus® Plus Option Kit
CM071
Copies of this Installation Guide along with all technical manuals in “.pdf” format and support files may be obtained from either the CD supplied with the drive or from
www.yaskawa.com
www.modbus.org
. Printed manuals may be obtained by contacting the Yaskawa Help Desk at 800-927-5292. Information on Modbus and Modbus Plus may be obtained from
Reference documents:
Modbus
Modbus
G5M Modbus
Plus Option Installation Guide – IG.AFD.17
Plus Option Installation Guide for G5HHP – IG.G5HHP.17
Plus T echnical Manual – TM.4557
G5M Technical Manual – TM.4515 G5M Modbus
Modbus® is a registered trademark of Schneider Electric, Inc.
YASKAWA ELECTRIC AMERICA, INC.
Drives Division
16555 West Ryerson Road, New Berlin, WI 53151, U.S.A.
Phone: (800) YASKAWA (800-927-5292) Fax: (262) 782-3418
Internet: http://www.yaskawa.com
YASKAWA ELECTRIC AMERICA, INC.
Chicago-Corporate Headquarters
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: (800) YASKAWA (800-927-5292) Fax: (847) 887-7310
Internet: http://www.yaskawa.com
MOTOMAN INC.
805 Liberty Lane, West Carrollton, OH 45449, U.S.A.
Phone: (937) 847-6200 Fax: (937) 847-6277
Internet: http://www.motoman.com
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-0022, Japan
Phone: 81-3-5402-4511 Fax: 81-3-5402-4580
Internet: http://www.yaskawa.co.jp
YASKAWA ELETRICO DO BRASIL COMERCIO LTDA.
Avenida Fagundes Filho, 620 Bairro Saude Sao Paolo-SP, Brasil CEP: 04304-000
Phone: 55-11-5071-2552 Fax: 55-11-5581-8795
Internet: http://www.yaskawa.com.br
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone: 49-6196-569-300 Fax: 49-6196-888-301
MOTOMAN ROBOTICS AB
Box 504 S38525, Torsas, Sweden
Phone: 46-486-48800 Fax: 46-486-41410