Yaskawa CM061 User Manual

Profibus-DP® Option Card
CM061 (SI-P1)
This document applies to the Yaskawa G5HHP drive. Please disregard the installation guide packed in the option kit.
Unpack the CM061 Profibus-DP Option kit and verify that all com ponents are present and undamaged.
CM061 Profibus-DP Option Kit Parts List Qty.
Profibus-DP Option Card (SI-P1) 1 Installation Guide (IG.AFD.12) (Disregard for G5HHP) 1
manual for information on connecting and operating the drive. Remove power from the drive and wait for the charge lamp to be completely extinguished. Wa it at least five additional minutes for the drive to be completely discharged.
Measure the DC bus voltage and verify that it is at a safe level.
Attach the CM061 Profibus-DP Option (SI-P1 card) to the master control board.
 Attach the CM061 Profibus-DP Option ground wire to the ground terminal
as shown. Make sure that the terminal is connected to a reliable, noise free ground.
Connect the CM061 Profibus-DP Option card to the 2CN connector on the
master control board.
Secure the Profibus cable to the support with a tie wrap to provide strain
relief for the connector.
Attach the Profibus cable to the CM061 Profibus-DP Option card as shown
(this picture shows the standard Phoenix connector shrink-wrapped for additional protection).
Fully engage the stand-offs in the mounting holes on the card. Route the Profibus cable away from any power wires within the cabinet.
When outside of the cabinet, run the Profibus cable in its own conduit. However, it may be run with low voltage signals such as feedback wiring.
SI-P1 Card Ground Terminal
2CN Connector
Profibus Cable Support
SI-P1 Card
Stand-offs
Attaching the CM061 Profibus-DP Option on a G5HHP master control board.
Yaskawa Electric America, Inc. – www.yaskawa.com
IG.G5HHP.12 Page 1 of 9
Date: 11/06/06 Rev: 06-11
Connect the drive to the Profibus-DP communication network.
Connect the Profibus-DP network cable as shown in the figure to the right. The cable shield must be contiguous between the beginning and end of any network segment. It is recommended
that the shield of the in cable and the out cable be twisted together. Do not connect the shield to the shield connector, rather fold it back and secure it to the cable.
Use the pluggable connector that came with the CM061 Profibus-DP Option. The pluggable connector contains a
circuit board that remaps the terminal connections. Do not use an alternate connector. Damage to the CM061 Profibus-DP Option and/or associated network devices could be damaged if an alternate connector is used.
Plug Socket
Pin Description Definition Pin Description Definition
1 A In (Green) Negative 1 Reserved No Connection 2 B In (Red) Positive 2 Reserved No Connection 3 A Out (Green) Negative 3 A In/Out (Green) Negative 4 B Out (Red) Positive 4 B In/Out (Red) Positive 5 Shield Shield 5 Shield Shield 6 Reserved No Connection
Set the node address.
Set the node address for the drive by setting the 10‘s digit with S2
and the 1’s digit with S1.
All devices on the network must have unique node addresses. Check
the network layout to verify that the node address selected is unique and falls between 3 – 99.
Node addresses 0 and 1 are typically reserved for master controllers. Node address 2 is typically reserved for diagnostic equipment.
Set network termination.
If this drive is either the first or the last device on the network, including any PLC and/or
Profibus-DP Master, and active termination is not used, set the termination resistor switch to ON.
If this device is not the first or last device on the network or active termination is used, set
the termination resistor switch to OFF.
Active termination is the recommended termination method and is required for networks
operating above 1.5Mbps. Active termination will eliminate the possibility of network failure due to the removal of a terminated device.
The Siemens Profibus Terminator part number is 6ES7 972-0DA00-0AA0.
6 Reserved No Connection
Set address switch 2 to "1" Set address switch 1 to "5"
0
9
8
7
6
S2
Address = S2 (x10) + S1
Example: Set node address to 15
1
2
3
4
5
0
1
9
8
7
2
3
4
6
5
S1
OFF
Yaskawa Electric America, Inc. – www.yaskawa.com
IG.G5HHP.12 Page 2 of 9
Date: 11/06/06 Rev: 06-11
ON
Configure the Profibus-DP network for the drive. Refer to the documentation included with the
Profibus configuration utility supplied with the Profibus-DP Master controller. Apply power to the drive and verify that the diagnostic LEDs on the front of the CM061
Profibus-DP Option are in their correct state.
LED Display
PWR COM ERR WD
Solid Green
Solid Green
OFF
Flashing Green
Content Cause
Normal Normal communication
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wa it at least five additional minutes for the drive to be completely discharged.
Measure the DC bus voltage and verify that it is at a safe level. Reinstall the operator keypad and all drive covers. Apply power to the drive.
Set parameters b1-01 and b1-02 to their appropriate values. Refer to the table below for available b1-01 and b1-02 values.
Parameter Function Data Description Default
0 Digital Operator
b1-01 Reference Source Select
b1-02 Run Command Source Select
1 Terminals 2 Built-in Modbus RTU Terminals 3
Option Card (CM061 Profibus-DP Option)
0 Digital Operator 1 Terminals 2 Built-in Modbus RTU Terminals 3
Option Card (CM061 Profibus-DP Option)
1
1
Yaskawa Electric America, Inc. – www.yaskawa.com
IG.G5HHP.12 Page 3 of 9
Date: 11/06/06 Rev: 06-11
Loading...
+ 6 hidden pages