Yaskawa CM059 User Manual

DeviceNet™ CM059 (SI-N1) Option
For Option: CM059 (SI-N1) Models: CIMR-G5*, CIMR-F7*, CIMR-G7*, CIMR-ACA* Document Number TM.AFD.13
Technical Manual
This page intentionally blank.
2

Warnings and Cautions

This Section provides warnings and cautions pertinent to this product, that if not heeded, may result in personal injury, fatality, or equipment damage. Yaskawa is not responsible for consequences of ignoring these instructions.
WARNING
YASKAWA manufactures component parts that can be used in a wide variety of industrial applications. The selection and application of YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any YASKAWA product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and to fail safely under all circumstances. All products designed to incorporate a component part manufactured by YASKAWA must be supplied to the end user with appropriate warnings and instructions as to that part’s safe use and operation. Any warnings provided by YASKAWA must be promptly provided to the end user. YASKAWA offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the YASKAWA manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. YASKAWA assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
WARNING
Read and understand this manual before installing, operating, or servicidriveng this drive. All warnings, cautions, and
instructions must be followed. All activity must be performed by qualified personnel. The drive must be installed
according to this manual and local codes.
Do not connect or disconnect wiring while the power is on. Do not remove covers or touch circuit boards while the power
is on. Do not remove or insert the Digital Operator while power is on.
Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. Status indicator LEDs and Digital Operator display will be extinguished when the DC bus voltage is
below 50VDC. To prevent electric shock, wait at least 5 minutes after all indicators are OFF and measure the DC bus
voltage level to confirm that it is at a safe level.
Do not perform a withstand voltage test on any part of the unit. This equipment uses sensitive devices and may be
damaged by high voltage.
The drive is not suitable for circuits capable of delivering more than the specified RMS symmetrical amperes. Install
adequate branch short circuit protection per applicable codes. Refer to the specification. Failure to do so may result in
equipment damage and/or personal injury.
Do not connect unapproved LC or RC interference suppression filters, capacitors, or overvoltage protection devices to the
output of the drive. Capacitors may generate peak currents that exceed drive specifications.
To avoid unnecessary fault displays, caused by contactors or output switches placed between drive and motor, auxiliary
contacts must be properly integrated into the control logic circuit.
YASKAWA is not responsible for any modification of the product made by the user, doing so will void the warranty. This
product must not be modified.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.To meet CE directives, proper line filters and proper installation are required.Some drawings in this manual may be shown with protective covers or shields removed, to describe details. These must
be replaced before operation.
Observe Electrostatic Discharge Procedures when handling the drive and drive components to prevent ESD damage.The attached equipment may start unexpectedly upon application of power to the drive. Clear all personnel from the drive,
motor and machine area prior to applying power. Secure covers, couplings, shaft keys, machine beds and all safety
equipment before energizing the drive.
3
Introduction
This manual explains the specifications and handling of the Yaskawa DeviceNet™ CM059 (SI-N1) option.
The Option connects the drive to a DeviceNet™ network and facilitates the exchange of data.

Option Compatibility

The CM059 (SI-N1) option is compatible with these Yaskawa drive products:

Table 1: Compatible Yaskawa Drive Products for the CM059 (SI-N1) Option

Product
Series
GPD/515/G5 CIMR-G5
F7 CIMR-F7
G7 CIMR-G7
ACA CIMR-ACA

Terminology

Models
(Drive Nameplate)
Notes
1. The CM059 (SI-N1) option firmware must be version 2.4 or later for operation with the ACA product series. Refer to the firmware lable on the CM059 (SI-N1) option to identify the firmware. Contact Yaskawa to obtain an updated CM059 (SI-N1) option if required.
2. The ACA product will appear the the same as the G7 product series when viewed on the network.
CM059 (SI-N1):
The CM059 option is also known as the SI-N1 option. They are one in the same.
Option: Throughout this manual the term “option” will be used when referring to the CM059 (SI-N1) Option.
Inverter, drive, AC drive:
In this document, the word “inverter”, “ac drive” and “drive” may be used interchangeably.

Related Documents

To ensure proper operation of this product, read and understand this manual. For details on installation and operation of the drive, refer to the appropriate drive Technical Manual. For details on specific parameters, refer to the appropriate drive MODBUS technical manual. All technical manuals and support files can be found on the CD that came with the drive and are available for download at www.yaskawa.com
For information on DeviceNet™ contact the Open DeviceNet™ Vendor Association at www.odva.org
GPD515/G5 Technical Manual document reference TM 4515
F 7 document reference T M . F 7 . 0 1 ( F 7 U s e r M a n u a l ) o r T M . F 7 . 0 2 ( F 7 P r o g r a m m i n g M a n u a l )
G7 document reference TM.G7.01 (G7 User Manual)
CIMR-ACA* document reference TOEPC71063600 (Instruction Manual)
GPD515/G5 MODBUS Technical Manual document reference TM 4025
F7 MODBUS Technical Manual document reference TM.F7.11
GPD is a trademark of Yaskawa, Inc.
MODBUS
®
is a registered trademark of Schneider Automation, Inc.
.
.
DeviceNet™ is a registered trademark of the Open DeviceNet™ Vendor Association.
RSNetWorx™ is a registered trademark of Rockwell Automation.
All trademarks are the property of their respective owners.
4

Overview

R
R
RS-232
Interface
Module
Master
24Vdc
G5
F7
G7
Trunkline
Droplines
Terminating
Resistor
Terminating
Resistor

Fig. 1 Sample DeviceNet Network

This manual describes the set-up and programming of the option. The option will allow communication between a DeviceNet Communication Network and one drive.
To connect a drive to the DeviceNet network, the following materials will be necessary:
CM059 (SI-N1) option CM059 (SI-N1) option Technical Manual CM059 (SI-N1) option EDS Files (Found on www.yaskawa.com or CD.AFD7.01 included with the drive)Drive User Manual (TM 4515, TM.F7.01, or TM.G7.01).

The DeviceNet Network

DeviceNet is a low-cost communications link to connect industrial devices (such as limit switches, photoelectric switches, valve manifolds, motor starters, smart motor controllers, operator interfaces, and variable frequency drives) as well as control devices (such as programmable controllers and computers) to a network. Figure 1 shows an example DeviceNet network.
DeviceNet is a simple, networking solution that reduces the cost and time to wire and install factory automation devices, while providing interchangeability of “like” components from multiple vendors.
DeviceNet is an “open device network standard”. The specifications and protocol are open - vendors are not required to purchase hardware, software, or licensing rights to connect devices to a system. Vendors who choose to participate may obtain the set of specifications from the Open DeviceNet Vendor Association (ODVA).
DeviceNet provides:
DeviceNet has two primary purposes:
A cost effective solution to low-level device networkingAccess to intelligence present in the devicesMaster/Slave capabilities
Transport of control-oriented information associated with the control/monitoring of devicesTransport of configuration parameters which are indirectly related to system control
5
The list below presents a summary of the Physical/Media specific characteristics of DeviceNet:
Trunkline-dropline configurationSupport for up to 64 nodesNode removal without severing the networkSimultaneous support for both network-powered and self-powered devicesUse of sealed or open-type connectorsProtection from wiring errorsSelectable data rates of 125kBaud, 250kBaud, and 500kBaudAdjustable power configuration to meet individual application needsHigh current capability (up to 16 Amps per supply)Operation with off-the-shelf power suppliesPower taps that allow the connection of several power supplies from multiple vendors that comply with DeviceNet
standards
The list below summarizes additional communication features provided by DeviceNet:
Use of Controller Area Network (CAN) technologyConnection-based model to facilitate application to application communicationsProvisions for the typical request/response oriented network communicationsProvisions for the efficient movement of I/O dataFragmentation for moving larger quantities of dataDuplicate MAC ID detection
The communication platform for the DeviceNet Network is based on the CAN (Controller Area Network) technology, which was first developed by Bosch for the automotive industry. Some of the benefits of this protocol are high noise immunity and high temperature operation. Because it uses a serial bus, it reduces signal wiring complexity and cost while providing high­speed digital control for optimum performance. These benefits make DeviceNet especially suitable for the industrial automation environment.
6
Table of Contents
Warnings and Cautions....................................................................................2
Introduction ......................................................................................................3
Overview of the DeviceNet Network ................................................................4
Chapter 1- Installation................................................................................................... 9
DeviceNet™ Simplified Start-up Procedure .................................................. 11
Unpack and Inspect....................................................................................... 13
Part Names ................................................................................................... 13
Installation and Wiring ................................................................................... 14
Verify Drive Operation ................................................................................... 14
Installation of DeviceNet Option .....................................................................14
Connect The Drive To The DeviceNet Network..............................................15
Set Baud Rate and Node Address .................................................................15
Baud Rate Setting Switch...............................................................................16
MAC ID Setting Switch ...................................................................................16
Termination Resistors.....................................................................................16
Option Indication LEDs...................................................................................16
Verify DeviceNet Option Operation ................................................................17
Initial Settings .................................................................................................17
Run/Stop and Frequency Selection................................................................17
DeviceNet Indication LEDs.............................................................................18
Chapter 2- Network Configuration .............................................................................19
DeviceNet Configuration ............................................................................... 20
EDS Files in General..................................................................................... 20
Install EDS File.............................................................................................. 21
Set Application Parameters........................................................................... 23
Configure the Scanner .................................................................................. 24
Add Drive to Scanlist and Specify Settings ................................................... 25
Data Storage of Option and Drive ................................................................. 30
Save Data to EEPROM with the ENTER Command..................................... 31
7
Chapter 3- Network Communications........................................................................33
DeviceNet Polled I/O Messaging Communications ..................................... 34
Basic Speed Control Input Instance 20 (14 Hex) ......................................... 35
Basic Speed Control Output Instance 70 (46 Hex) ...................................... 36
Extended Speed Control Input Instance 21 (15 Hex)................................... 37
Extended Speed Control Output Instance 71 (47Hex)................................. 38
Drive Modbus I/O Control Input Instance 100 (64 Hex) ............................... 39
Drive Modbus I/O Control Output Instance 150 (96 Hex) ............................. 40
Standard Drive Control Input Instance 101 (65 Hex) .................................... 41
Standard Drive Control Output Instance 151 (97 Hex) ................................. 43
DeviceNet Explicit Messaging Communications........................................... 45
Identity Object Class (01 Hex): ..................................................................... 46
Message Router Object Class (02 Hex): ...................................................... 48
DeviceNet Object Class (03 Hex): ................................................................ 48
Assembly Object Class (04 Hex): ................................................................. 49
DeviceNet Connection Object Class (05 Hex): ............................................. 50
Motor Data Object Class (28 Hex): ............................................................... 52
Control Supervisor Object Class (29 Hex): ................................................... 52
AC/DC Drive Object Class (2A Hex):............................................................ 54
Drive Parameters Object Class 100 (64 Hex):.............................................. 56
DeviceNet Fault Diagnostics......................................................................... 58
Drive Faults................................................................................................... 58
Fault Diagnostics .......................................................................................... 59
DeviceNet Communication LED Faults and Operation................................. 60
Explicit Message Communication Error ........................................................ 61
I/O Message Communication Modbus I/O Instance Errors........................... 61
Appendix A- Product Specifications..........................................................................63
DeviceNet Product Specification Table .....................................................................64
Appendix B- Cable Specifications .............................................................................65
DeviceNet Cable Specifications ................................................................... 66
DeviceNet Cable Vendor Table .................................................................... 66
DeviceNet Network Topology ....................................................................... 67
DeviceNet Maximum Cable Distance........................................................... 67
8
Chapter 1
Installation
This chapter describes how to install and setup the DeviceNet Option
DeviceNet™ Simplified Start-up Procedure ........................ 11
Unpack and Inspect............................................................... 13
Part Names............................................................................. 13
Installation and Wiring .......................................................... 14
Verify Drive Operation ........................................................... 14
Installation of DeviceNet Option ...........................................14
Connect The Drive To The DeviceNet Network.................... 15
Set Baud Rate and Node Address.........................................15
Baud Rate Setting Switch ......................................................16
MAC ID Setting Switch ...........................................................16
Termination Resistors ............................................................16
Option Indication LEDs ..........................................................16
Verify DeviceNet Option Operation ....................................... 17
Initial Settings .........................................................................17
Run/Stop and Frequency Selection ......................................17
DeviceNet Indication LEDs ....................................................18
9

This page intentionally left blank.

10

DeviceNet™ Simplified Start-up Procedure

1
2
3
4
5
BK BL WH RD
GR
BL WH
BK GR RD

Table 2: DeviceNet Terminal Block Connections

Ter minal
No.
Ter minal
Color
Name
Wiring
Color
Content
1 Black V- Black Communication power supply GND
2 Blue CAN_L Blue Communication data low side
3 Green Shield Bare Shield wire
4 White CAN_H White Communication data high side
5 Red V+ Red Communication power supply +24V
dc
ON
OFF
1 2 3 4 5 6 7 8
Baud Rate
1 2 OFF OFF 125kbps
OFF
ON 250kbps
ON OFF 500kbps ON ON Not Allowed
MAC ID
3 4 5 6 7 8
OFF OFF OFF OFF OFF OFF 0
OFF OFF OFF OFF OFF
ON 1
OFF OFF OFF OFF
ON OFF 2
OFF OFF OFF OFF
ON ON 3
ON ON ON ON ON OFF 62
ON ON ON ON ON ON 63
Note: Setting the “Not Allowed”
baud rate configuration (Switch 1 and 2 “ON”) causes a “BUS” fault on the Digital Operator.

Fig. 2 DeviceNet DIP Switch Settings

DR 1
DR 0
ADR5
ADR4
ADR3
ADR2
ADR1
ADR0
1234 567
The following is a quick reference guide to install and configure the drive’s option. For more details, please refer to the drive’s DeviceNet Technical Manual sections referenced.
1. Verify that the drive functions properly without the option installed. This includes running the drive from the operator keypad, without communications.
2. Turn off the drive power supply and wait for at least 1 minute for the charge lamp to be completely out before removing the operator and front cover. Remove the option hold-down tab on the left side of the drive case by carefully compressing the top and bottom until it becomes free of its holder. Lift it out.
3. Install the option onto the drive. Mount the DeviceNet unit onto the drive making sure to connect 2CN securely. Replace the option hold-down. Install the operator keypad and front cover back onto the unit after securing the DeviceNet unit with screw.
4. Connect the DeviceNet communication wires to the screw terminals on the option.
5. Using the DIP switch bank on the DeviceNet option kit, set communication baud rate (switch 1, 2) and MAC ID (switch 3 – 8). Be sure to verify that no devices on the network have duplicate MAC IDs.
11
6. Power up the drive and set the number of motor poles in parameter o1-03 to read and set the speed in motor RPMs.
7. Set the drive’s run/stop and frequency reference to meet the application requirements as explained below.
Example 1. Control from DeviceNet network
When the drive is set to be controlled by the DeviceNet network, the frequency and the start/stop commands are issued through the master device. Set the drive parameters b1-01 and b1-02 as shown in the table.

Table 3: Drive Parameter Settings for DeviceNet Control

Parameter Display Text Value Description
b1-01
b1-02
Example 2. Monitor only
The drive can be connected to the DeviceNet network without being controlled.The motor speed and the status of the drive can be monitored via DeviceNet while controlling the drive from another source specified by parameters b1-01 and b1-02. Please refer to the drive Technical Manual for the proper settings of parameters b1-01 and b1-02.
8. Download the proper EDS file for the corresponding drive model number from CD ROM - CD.AFD7.01 included with the drive or from www.yaskawa.com Product Codes for a complete list of EDS files with the model number of the drive. Each model of drive has its own EDS file, so it is important to select the EDS file that matches the drive capacity. The EDS file is necessary to map the DeviceNet and drive parameters into the configuration tool where the user can access the parameters through DeviceNet. Install the EDS file in the configuration tool software, such as RSNetWorx™ for DeviceNet™ from Rockwell Software (Appendix B DeviceNet Configuration for RSNetWorx).
Note: The EDS files will be in zip format, so you must unzip the file before installing it in the configuration tool.
Reference Source
Option
Run Source
Option
3
3 Sets the sequence to come from the option.
in the “Software Downloads” area. Refer to the table of EDS Files and
Sets the frequency reference to come from the option.
12

Unpack and Inspect

Connector for Options (60-pin)
Indication LEDs
DeviceNet
DIP Switch
Ground Wire
Terminal Block
Prior to unpacking, check the package label and verify that the product received matches the product ordered. Unpack the option and verify that the following items are included in the product package and are undamaged.

Part Names

Option components are as follows:
DeviceNet Option CM059 (SI-N1) 1
Installation Guide IG.AFD.13. DeviceNet CM059 (SI-N1) 1

Fig. 3 CM059 (SI-N1) Option

Table 4: Option Kit Parts List

Part Qty.
13

Installation and Wiring

Grounding Term inal
4CN Option Card A
2CN Option Card C
3CN Option Card D
Option Clip
The following describes the installation and configuration of the option. For detailed information about the drive or the DeviceNet option, please refer to the appropriate sections of this manual or the appropriate drive Technical Manual.

Verify Drive Operation

Connect power to the drive and verify that the drive functions properly. This includes running the drive from the operator
keypad. Refer to the appropriate drive Technical Manual for information on connecting and operating the drive.
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional
minutes for the drive to be completely discharged. Measure the DC BUS voltage and verify that it is at a safe level.
Remove the operator keypad and drive cover(s). Remove the option hold-down on the left side of the drive case by carefully compressing the top and bottom until it
becomes free of its holder. Lift it out.

Installation of the Option

Install the option on the drive control PCB after having removed the front cover of the drive body. Install the option in
accordance with the following procedure:
Align the JP2 connector on the back of the option with its mating 2CN connector on the drive control card.Align the two standoffs on the front of the drive control board with the two holes on the right side of the option.Press the option firmly onto the drive 2CN connector and standoffs until the JP2 connector is fully seated on 2CN and
the drive standoffs have locked into their appropriate holes.
Replace the option hold down.
Connect the ground wire from the ground terminal E on the option to a ground terminal on the terminal assembly. After installing the option, make the terminal connections per the instructions on the next page and set the DIP switch
to the correct settings. Thereafter, re-install the front cover and the operator in their original positions.
Fig. 4 Option Locations
14

Connect The Drive To The DeviceNet Network

1
2
3
4
5
BK BL WH RD
GR
BK GR RD
BL WH

Table 5: DeviceNet Terminal Block Connections

Ter minal
No.
Ter minal
Color
Name
Wiring
Color
Content
1 Black V- Black Communication power supply GND
2 Blue CAN_L Blue Communication data low side
3 Green Shield Bare Shield wire
4 White CAN_H White Communication data high side
5 Red V+ Red Communication power supply +24V
dc
DR 1
DR 0
ADR5
ADR4
ADR3
ADR2
ADR1
ADR0
1234 567
OFF
ON
MAC ID Setting
Baud Rate Setting

Fig. 5 DIP Switch Settings for Baud Rate and Node Address

Wire the DeviceNet communication cable to the terminal block according to the following procedures:
Loosen terminal screws using a slotted screwdriver. Strip about 5.5mm of insulation from the end of each DeviceNet wire and insert it into the corresponding terminal
according to the table and diagram below.
Secure wires by tightening terminal screws (Tightening torque: 0.22 0.25 [N m]). Tie the DeviceNet cable to a point near the terminal block to provide strain relief for the terminal block and cable
connection.
Note: The shield is daisy chained between devices and should be grounded at the 24 V
the Open DeviceNet Vendor Association (ODVA).
dc power supply as specified by

Set Baud Rate and Node Address

The option is equipped with one 8-bit DIP switch for baud rate and node address set-up. The DIP switches are located next to the DeviceNet connector on the short side of the option. Set the network node address (MAC ID) by setting the DIP switches. All devices on the network must have unique node addresses. Check the network layout to verify that the node address selected is unique, falls between 3 and 62, and matches the master device configuration for that device. Node addresses 0 and 1 are typically reserved for master devices, while node address 2 is reserved for diagnostic/monitoring equipment, and address 63 for vendor-specific functions in some systems.
15

Baud Rate Setting Switch

R
R
RS-232
Interface
Module
Master
24Vdc
G5
F7
G7
Trunkline
Droplines
Terminating
Resistor
Terminating
Resistor
PLC/
Scanner
Power (PWR)
DeviceNet Module Status (MS)
DeviceNet Network Status (NS)
Option Status (WD)

Fig. 7 DeviceNet Status Indication LEDs

Table 6: Baud Rate DIP Switch Setting

Switch 500 kbps 250 kbps 125 kbps Setting Prohibited
DR1 ON OFF OFF ON DR0 OFF ON OFF ON
Note: If DR1 and DR0 are ON and set to Setting Prohibited, both MS and NS LEDs light up solid red.

MAC ID Setting Switch

Table 7: MAC ID Switch Setting

DIP Switch
ADR5 OFF OFF OFF OFF OFF OFF OFF OFF OFF ADR4 OFF OFF OFF OFF OFF OFF OFF OFF OFF ADR3 OFF OFF OFF OFF OFF OFF OFF OFF ON ADR2 OFF OFF OFF OFF ON ON ON ON OFF ADR1 OFF OFF ON ON OFF OFF ON ON OFF ADR0 OFF ON OFF ON OFF ON OFF ON OFF
012345678
MAC ID
・・・ ・・・ ・・・ ・・・ ・・・ ・・・ ・・・
62 63 ON ON ON ON ON ON ON ON ON ON
OFF ON

Termination Resistors

Terminating resistors must be mounted on the first and last node in a DeviceNet network, at both of the furthest ends of the cable. The value of the Terminating resistor is specified by the ODVA (Open DeviceNet Vendors Association) and is a value of 121 Ohms, 1% tolerance, and ¼ watt. Terminating resistors can be found in the ODVA product catalog.

Option Indication LEDs

The option is equipped with four indication LEDs for module and DeviceNet status indication. The LEDs are located on the option according to the figure below.

Fig. 6 Terminating Resistor Placement on DeviceNet Network

16

Verify Option Operation

Apply power to the drive.Verify that the diagnostic LEDs on the front of the option are in their correct state.

Table 8: Diagnostic LED States

LED Display
PWR MS NS WD
Solid Green Solid Green Solid Green Flashing Green Normal Normal Communication
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five
additional minutes for the drive to be completely discharged. Measure the DC BUS voltage and verify that it is at a safe level.
Install the operator keypad and all drive covers.
Content State

Initial Settings

Since the option utilizes the AC drive for many of its calculations; such as speed, please check the following parameters to verify the correct setting.
Table 9: Parameter o1-03 – Digital Operator Display Mode
Setting No. Name Description
o1-03 Frequency reference
set/display unit selec­tion
Make sure to set number of motor poles (2 ~ 39) to input and output motor speed in RPMs on DeviceNet control and operator display. DeviceNet indicates the motor speed unit as RPM. o1-03 setting value is used since the option converts frequency to RPM. Initial value is 0 for frequency reference in Hz.

Run/Stop and Frequency Selection

The run/stop commands and frequency reference command can originate from serial communication, the Digital Operator, the external terminals, or the option. The origin of the run/stop command does not have to be the same as the origin for the fre­quency reference command. Parameter b1-01 (Reference Selection) allows you to set up the origin of the frequency reference and parameter b1-02 (Operation Method Selection) sets up the origin of the run/stop commands. When the DeviceNet network is connected to the drive, the motor speed and the status of the drive can be monitored via DeviceNet while controlling the drive from another source specified by parameters b1-01 and b1-02. The table shown below illustrates the possible frequency reference and run/stop selections.

Table 10: Possible Frequency Reference and Run/Stop Selections

Parameter b1-01 Setting Frequency Reference Selection
0 Digital Operator 1 Terminals 2 Serial Communication (Modbus) 3 Option (DeviceNet) 4 Pulse Input
Note: The default setting of parameter b1-01 is ‘1’. For DeviceNet Operation, use Setting ‘3’ – Option.
Parameter b1-02 Setting Operation Method Selection (Run/Stop)
0 Digital Operator 1Terminals 2 Serial Communication (Modbus) 3
Note: The default setting of parameter b1-02 is ‘1’. For DeviceNet Operation, use Setting ‘3’ – Option.
17
Option (DeviceNet)

Option Indication LEDs

The table below describes the function of DeviceNet specific LEDs.

Table 11: DeviceNet LED Function

LED
Name
MS
NS
PWR
WD
Notes:
1) If the baud rate configuration is set for “Not Allowed”, both the NS and MS diagnostic LEDs will be solid RED.
2) The LEDs will flash red once (100 ms) during initialization (Internal testing process to verify that the red LED is working properly).
Display
Color Status
Green Lit During option operation The option is operating normally.
Green Flashing During option preparation Initial setting status or communication is not ready.
Red Lit
Red Flashing Recovery from fault possible Possible recovery fault such as switch settings occurred.
Green Lit
Green Flashing
Red Lit Communication fault
Red Flashing Communication timeout Communication time out with master occurred.
Green Lit Power ON Power to the option is supplied from the drive.
Green Flashing During CPU operation CPU of the option is operating normally.
Red Lit CPU fault Option CPU is being ready or has fault.
Not lit Power OFF
Not lit Offline, Power OFF
Not lit Power OFF
Not lit Power OFF
Operation Status Description
Recovery from fault impossible
Online communication is taking place
Online communication is not taking place.
Impossible recovery fault occurred in the option.
Power is not being supplied to the drive. the option has not been properly connected. Therefore, the
power is not being supplied to the option.
DeviceNet is communicating normally.
DeviceNet network is normal, but is not communicating with the master.
A fault that makes it impossible for the DeviceNet to communicate has occurred.
MAC ID overlap Bus-off detection
DeviceNet is not set to online. Power is not being supplied to the option. Mismatch of baud rate.
Power is not being supplied to the drive. The option has not been properly connected. Therefore, the power is not supplied to the option.
Power is not being supplied to the drive. The option has not been properly connected. Therefore, power is not being supplied to the option.
18
Chapter 2
Network Configuration
This chapter describes how to properly adjust the parameter settings of a DeviceNet slave in a network system.
DeviceNet Configuration .................................................................... 20
EDS Files in General ........................................................................... 20
Install EDS File .................................................................................... 21
Set Application Parameters................................................................ 23
Configure the Scanner........................................................................ 24
Add Drive to Scanlist and Specify Settings...................................... 25
Data Storage of Option and Drive...................................................... 30
Save Data to EEPROM with the ENTER Command.......................... 31
19

DeviceNet Configuration

1770-KFD
F7
SLC500
1747-SDN
1770-KFD1770-KFD
F7F7
SLC500
1747-SDN
DeviceNet configuration refers to properly setting the DeviceNet slave in a network system through its parameter settings. The option allows accessibility to DeviceNet parameters and drive parameters through its EDS file. The configuration software uses the EDS file to map the DeviceNet and drive parameters. The user can read and set parameters and save the configuration. The configuration software that this document will address is RSNetWorx for DeviceNet™ from Rockwell Software.
Note: This section is only intended to be used as a guide for configuration of the option using configuration tool software
RSNetWorx. Any updates to the configuration tool software will not be noted in this section. Please reference the configuration tool technical manual as the primary reference. Use the contents of this section only as a general guide.
EDS files can be downloaded from the internet at www. sure to select the version of the EDS file that corresponds to the drive capacity and version number of the Option. Each Yaskawa drive capacity has its own EDS file, so it is important to select the EDS file that matches the drive capacity. Install the EDS files in a subdirectory of the PC where the configuration software is located.
Note: The EDS files will be compressed in zip format, so unzip the file before installing in the configuration too.
The following steps will outline how to configure the Yaskawa drive on DeviceNet using RSNetWorx.
1. Install the drive EDS file.
2. Set drive parameters and select the proper Polled Producing Assembly (PPA) and Polled Consuming Assembly (PCA) of the drive for the application.
3. Configure the scanner by adding the drive to the scanner module scanlist.
4. AutoMap the drive in the Input and Output of the scanner’s M File Memory.
yaskawa.com or www.odva.org. For correct scaling of parameters, be

EDS Files in General

EDS files are typically used together with a DeviceNet Network Configuration tool.
DeviceNet Network Configuration tools are used to configure all nodes on a DeviceNet network. Network Configuration tools provide the ability to upload data from a device and download data to a device. The EDS files provide the Network Configuration tool with the following information:
Description of each device parameterMaximum and Minimum values for each device parameterDefault values for each device parameterRead/Write access for each device parameterHelp Information for each device parameterVendor ID of the deviceDevice Type of the deviceProduct Code of the deviceRevision of the device
Each device on the network has the following values assigned to it:
Vendor ID Device TypeProduct CodeRevisionSerial Number
The Network Configuration tool will read these values from the device. When using EDS files, the tool will compare the values of Vendor ID, Device Type, Product Code, and Revision that were read from the device to the values in the EDS file. They must match.
20

Install EDS File

Install the drive’s EDS file by selecting EDS Wizard and follow the appropriate steps. In RSNetWorx, select EDS Wizard under Tools. Be sure that you have the drive EDS files downloaded and unzipped.
Follow the appropriate steps in the EDS Wizard.
21
Once the proper EDS file is installed, the drive icon will appear along with the drive model number.
Yas kaw a
Yaskawa [44]
Double-click on the drive icon to access the drive’s specifications and parameters.
22

Set Application Parameters

Select the Parameters tab to access DeviceNet and drive parameters and set the parameters according to the application.
The parameters are categorized into Groups, which allows you to filter the parameters that are displayed. DN: Polled Config group shows Polled Producing Assembly (PPA) and Polled Consuming Assembly (PCA).
23
Enter appropriate PPA and PCA to use for polled communications. See Chapter 3 for a complete list of available PPA and PCA.
Yaskawa
Click OK or Apply to save any changes.

Configure the Scanner

Double-click on the Scanner Module icon to configure the Scanner.
24

Add Drive to Scanlist and Specify Settings

Select the Scanlist tab to show available devices for the scanlist. Add the drive to the scanlist by highlighting the drive and click on the right arrow button (>).
Click on Edit I/O Parameters to set the I/O data settings.
25
Select Polled communications and the correct amount of bytes for PCA (Rx) and PPA(Tx). Click OK.
Select the Input tab and Unmap any data in the Discrete Memory.
26
Select the M File Memory.
Click on the AutoMap button. The selected bytes of polled input data should appear in the scanlist. Click OK.
27
Select the Output tab and Unmap any data in the Discrete Memory.
Select the M File Memory. Click on the AutoMap button. The selected bytes of polled output data should appear in the scanlist.
28
Select the Summary tab to make sure the correct number of I/O bytes are selected and are mapped.
Save the changes and download the configuration to the scanner by clicking Apply.
29

Data Storage of Option and Drive

Power-Up
ENTER
Drive Application
Parameters
Drive Application
Parameters
Drive Application
Parameters
Drive Inactive
RAM
Drive Active
RAM
Drive EEPROM
ENTER
ACCEPT
Drive Runtime
Commands
Drive Runtime
Status/Diagnostics
The drive with option stores data in four locations:
Active RAM memory on the driveInactive RAM memory on the driveEEPROM memory on the driveEEPROM memory on the option
Data held in RAM memory, both Active and Inactive, is “Volatile”. Data held in Volatile memory will be lost when power is removed from the drive.
Data held in drive EEPROM and option EEPROM memory is “Non-Volatile”. Data held in Non-Volatile memory will be retained when power is removed from the drive.
The following table shows which memory location is used for the data available over the DeviceNet network.
DataType MemoryType
Drive Runtime Commands
Run/Stop Frequency Reference
Drive Runtime Status and Diagnostics
Run/Stop Status Frequency Output Current Output Fault Diagnostics
Drive Application Parameters
A1-00 through o3-02
DeviceNet Network Parameters
Polled Consuming Assembly Polled Producing Assembly Motor Nameplate Data
Drive RAM
Drive RAM
Drive EEPROM
& Drive RAM
Option
EEPROM
The drive Application Parameters are held both in drive EEPROM and drive RAM. On power-up, the drive Application Parameters that are stored in drive EEPROM memory are transferred to drive RAM memory.
If drive Application Parameters are changed via DeviceNet, the new data will be placed into drive Inactive RAM memory. At this point, the new data will not be activated or retained if a drive power loss occurs. In order for the new data to be retained, the ‘ACCEPT’ command must be executed. When the ‘ACCEPT’ command is executed, the new data is transferred into Active RAM memory. In order for the new data to be retained, the ‘ENTER’ command must be executed. When the ‘ENTER’ command is executed, all of the drive Application Parameters in drive RAM memory are transferred into drive EEPROM memory.
30
Some Parameter Data registers may be written to while the drive is running. These parameters are called run operative
CAUTION
Use the ENTER Command only when necessary! The life of the EEPROM on the drive will support a finite number of operations. This means that the ENTER command can only be used a maximum of 100,000 times to store data in the EEPROM. After the specified number of operations, the EEPROM may fault (CPF04) requiring the drive control board to be replaced.
CAUTION
The DeviceNet Network parameters do not require the use of the ENTER Command. They are automatically stored in EEPROM memory. The life of the EEPROM on the option will support a finite number of operations. This means that the DeviceNet Network parameters can only be changed a maximum of 100,000 times. After the specified number of operations, the EEPROM may fault, requiring the option to be replaced.
parameters. For a list of these parameters refer to Appendix A of the drive User Manual.
All other Parameter Data registers may only be written to when the drive is stopped. These are called non-run operative parameters.
If new data is written to any parameter serially, and is not followed by an ‘ENTER’ command, a Busy Write Protected” message will flash on the Digital Operator display if an attempt is then made to change a parameter using the Digital Operator.

Save Data to EEPROM with the ENTER Command

The ENTER Command can be accomplished in the following way:
Perform a SET service on Yaskawa Class 64 Hex, Instance 09 Hex, Attribute 00 Hex
The value ‘0’ should be SET to the ENTER Command attribute.
31
Notes:
32
Chapter 3
Network Communications
This chapter describes how to install and setup the DeviceNet Option
DeviceNet Polled I/O Messaging Communications.......................... 34
Basic Speed Control Input Instance 20 (14 Hex).............................. 35
Basic Speed Control Output Instance 70 (46 Hex)........................... 36
Extended Speed Control Input Instance 21 (15 Hex) ....................... 37
Extended Speed Control Output Instance 71 (47Hex) ..................... 38
Drive Modbus I/O Control Input Instance 100 (64 Hex).................... 39
Drive Modbus I/O Control Output Instance 150 (96 Hex).................. 40
Standard Drive Control Input Instance 101 (65 Hex)......................... 41
Standard Drive Control Output Instance 151 (97 Hex)...................... 43
DeviceNet Explicit Messaging Communications ..............................45
Identity Object Class (01 Hex):............................................................46
Message Router Object Class (02 Hex):.............................................48
DeviceNet Object Class (03 Hex): .......................................................48
Assembly Object Class (04 Hex): .......................................................49
DeviceNet Connection Object Class (05 Hex): ..................................50
Motor Data Object Class (28 Hex):......................................................52
Control Supervisor Object Class (29 Hex):........................................52
AC/DC Drive Object Class (2A Hex): .................................................. 54
Drive Parameters Object Class 100 (64 Hex):....................................56
DeviceNet Fault Diagnostics ...............................................................58
Drive Faults...........................................................................................58
Fault Diagnostics .................................................................................59
DeviceNet Communication LED Faults and Operation.....................60
Explicit Message Communication Error ............................................61
I/O Message Communication Modbus I/O Instance Errors .............. 61
33

DeviceNet Polled I/O Messaging Communications

DeviceNet Communications between a Master (PLC or PC) and the drive (Slave) uses Polled I/O messaging, based from the following I/O Assemblies, to transfer control and diagnostic information to and from the drive. The “Input Data Assemblies” or “Polled Consuming Assemblies (PCA)” refer to a message sent from the Master to the drive. The “Output Data Assemblies” or “Polled Producing Assemblies (PPA)” refer to the response from the drive back to the Master. The factory default of the drive DeviceNet is Extended Speed Control Input Instance 21 and Extended Speed Control Output Instance 71.
The configuration software uses the EDS file to change the PCA and PPA. By accessing the EDS file through configuration software, the PCA and PPA can be accessed under the DeviceNet Parameter Groups “Polled Consuming Assembly” and “Polled Producing Assembly”. Set the appropriate value using the table below and save the changes to the device.
Be sure to power down the drive, then power up to store the changes made to the PCA and PPA.

Table 12: Supported Service

Service Code
(Hex)
0E Get_Attribute_Single Designated attribute content is read. 10 Set_Attribute_Single Designated attribute content is changed.
Class Instance Attribute Type Data Description
101
(65 Hex)
1
Service Name Description of Service
70
(46 Hex)
PPA
1
2
(Output Data
Assembly)
PCA
(Input Data
Assembly)
71
(47 Hex)
150
(96 Hex)
151
(97 Hex)
20
(14 Hex)
21
(15 Hex)
100
(64 Hex)
101
(65 Hex)
Bas ic Spe ed Co nt rol Ou tp ut I ns ta nc e 70
E x te n d e d Sp e e d Co n t r ol O ut p u t I ns t a n ce 7 1
Drive Modbus I/O Control Output Instance 150
D r i v e S t a n d a r d D r i v e C o n t r o l O u t p u t I n s t a n c e 1 5 1
Basic Speed Control Input Instance 20
E x t e n d e d S p e e d C o n t r o l I n p u t I n s t a n c e 2 1
Drive Modbus I/O Control Input Instance 100
D r i v e S t a n d a r d D r i v e C o n t r o l I n p u t I n s t a n c e 1 0 1
*default
*default
The tables in the following pages indicate the format and structure of the I/O Assemblies.
Note: 1. Regardless if I/O Data Exchange is enabled or disabled, communications will occur at the determined intervals
set by the Master.
2. Input Data Assemblies = Polled Consuming Assemblies Output Data Assemblies = Polled Producing Assemblies
34

Basic Speed Control Input Instance 20 (14 Hex)

This function is the basic I/O instance of Assembly Object Class (04 Hex) Attribute (03 Hex), which defines DeviceNet AC Drive Profile. Both input/output use 4 bytes each.

Table 13: Drive Basic Speed Control Instance 20 (14 Hex) (INPUT ASSEMBLY)

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 1
----- --------
2 Speed Reference (Lower Byte) 3 Speed Reference (Upper Byte)
Data Name Description
Byte 0, Bit 0
Byte 0, Bit 2
Run Fwd
Fault Reset
The drive runs forward 0: Stop
The drive from fault detection status is reset. 0: Fault reset off
The drive speed reference is set.
Speed command data: Frequency reference [RPM]×1/2
Byte 2, 3
Speed Reference
Setting range: 0xFFFF Hex Example: When setting 1800r/min reference, (Speed scale = 0)
Speed reference data: 1800 X 1/2
Lower Byte (byte 2) = 08 Hex, Upper Byte (byte 3) = 07 Hex
Notes: *1 Speed scale can be set by explicit messaging communication AC/DC Drive Object (Class 2A Hex) attribute 16.
*2 Setting of a speed exceeding the drive maximum output frequency (E1-04) will be limited by the maximum output frequency (E1-04). *3 When applying a speed reference make sure to set No. of poles (2 ~ 39) to the drive parameter o1-03 (frequency reference set/display unit
selection).
Fault Reset
1: FWD run
where SS: Speed Scale
*2
0
= 0708 Hex
1: Fault reset
SS
*1
Fwd Run
35

Basic Speed Control Output Instance 70 (46 Hex)

This function is the basic I/O instance of Assembly Object Class (04 Hex) Attribute (03 Hex), which defines DeviceNet AC Drive Profile. Both input/output use 4 bytes each.

Table 14: Drive Basic Speed Control Instance 70 (46 Hex) (OUTPUT ASSEMBLY)

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1 2 Speed Monitor (Lower Byte) 3 Speed Monitor (Upper Byte)
Byte 0, Bit 0
Byte 0, Bit 2
Byte 2, 3 Speed Monitor
Note: *1 Speed scale can be set by explicit messages communication AC/DC Drive Object (Class 2A Hex) attribute 16.
-----
----- - - -
Data Name Description
Fault
During FWD
*2 When applying a speed reference make sure to set No. of poles (2 ~ 39) to the drive parameter o1-03 (frequency reference set/display unit
selection).
The drive fault detection status is displayed. 0: Normal
The drive run status is displayed. 0: During Stop/REV.
The drive speed is displayed.
Speed monitor data: Frequency monitor [r/min]×1/2
where SS: Speed Scale
Example: If speed monitor data is 1000RPM (03E8 Hex), speed scale = 0
Lower Byte (byte 2) = E8 Hex, Upper Byte (byte 3) = 03 Hex
Frequency monitor: 03E8 Hex X 1/2
During FWD Run (Fwd)
1: During FWD/DC braking
0
X = 1000r/min.
1: During fault detection
*1
SS
Fault
36

Extended Speed Control Input Instance 21 (15 Hex)

This function is the basic I/O instance of Assembly Object Class (04 Hex) Attribute (03 Hex), which is defined by the DeviceNet AC Drive Profile. This is the Factory Default. Both I/O Assemblies use 4 bytes.

Table 15: Drive Extended Speed Control Instance21 (15 Hex) (INPUT ASSEMBLY)

ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0
1 2 Speed Reference (Lower Byte) 3 Speed Reference (Upper Byte)
- --------
Data Name Description
Byte 0, Bit 0
Byte 0, Bit 1
Byte 0, Bit 2
Byte 0, Bit 5
Byte 0, Bit 6
Byte 2, 3
NetRef NetCtrl
Fwd Run
Rev Run
Fault Reset
NetCtrl
NetRef
Speed Reference
--
Fault Reset Rev Run Fwd Run
The drive runs forward. 0: Stop
1: Fwd run
The drive runs reverse. 0: Stop
1: Rev. run
The drive resets at fault detection status. 0: Fault reset off
1: Fault reset
Run command rights are set. 0: Run command input procedures are set by set run command selection (b1-02) 1: Run command (Byte 0 – Bit 0, 1) through DeviceNet enabled.
Frequency reference rights are set. 0: Frequency reference input procedures set by frequency reference selection (b1-01) 1: Frequency reference (Byte 2, 3) through DeviceNet enabled.
The drive speed reference is set. This function is the same as the Speed Reference in the Basic Speed Control Input Instance 20 (14 Hex) section.
37

Extended Speed Control Output Instance 71 (47 Hex)

This function is the basic I/O instance of Assembly Object Class (04 Hex) Attribute (03 Hex), which is defined by the DeviceNet AC Drive Profile. This is the Factory default. Both I/O Assemblies use 4 bytes.

Table 16: Drive Extended Speed Control Instance 71 (47 Hex) (OUTPUT ASSEMBLY)

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Speed
0
Agree
1 2 Speed Monitor (Lower Byte) 3Speed Monitor (Upper Byte)
Data Name Description
Byte 0, Bit 0
Byte 0, Bit 1
Byte 0, Bit 2
Byte 0, Bit 3
Byte 0, Bit 4
Byte 0, Bit 5
Byte 0, Bit 6
Byte 0, Bit 7
Byte 2, 3
--------
During Fwd Run
During Rev Run
Inverter Ready
Ctrl From Net
Ref From Net
Speed Agree
Speed Monitor
Fault
Alarm
Ref From Net
Ctrl From Net
The drive fault detection status is displayed: 0: Normal
The drive alarm detection status is displayed: 0: Normal
The drive run status is displayed: 0: During stop/reverse
The drive run status is displayed: 0: During stop/forward run/DC brake
The drive ready status is displayed: 0: During fault detection/ready 1: Ready The drive run command input selection status is displayed. 0: Run command input is enabled other than the DeviceNet. 1: Run command input is enabled from the DeviceNet. The drive frequency input selection status is displayed. 0: Run command input is enabled other than the DeviceNet. 1: Run command input is enabled from the DeviceNet. The drive frequency agree detection status is displayed. 0: During stop/acceleration and deceleration 1: Frequency agree The drive speed is displayed. This function is the same as the Speed Monitor in the Basic Speed Control Output Instance 70 (46 Hex) section.
Inverter Ready
During Reverse Run
During Forward Run
1: During fault detection
1: During alarm detection
1: During forward run/DC braking
1: During reverse run
Alarm Fault
38

Drive Modbus I/O Control Input Instance 100 (64 Hex)

This I/O instance allows all drive parameters and monitors to be read/set. This instance is for Yaskawa drives only, and is not interchangeable with other DeviceNet drives, Assembly Object Class (04 Hex) Attribute (03 Hex). Both input/output use 5 bytes each. Refer to the Appendix A for a list of Modbus Registers.

Table 17: Drive Modbus I/O Control Instance 100 (64 Hex) (INPUT ASSEMBLY)

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Function Code 1 Register Number (Upper Byte) 2 Register Number (Lower Byte) 3 Register Data (Upper Byte) 4 Register Data (Lower Byte)
Data Name Description
Modbus (reference message) function code is set.
Byte 0
Byte 1, 2 Register Number (Upper and Lower Byte) A drive Modbus register No. is set. Byte 3, 4 Register Data (Upper and Lower Byte) The write data at Modbus write command is set.
Function Code
03 Hex: Read 10 Hex: Write 00 Hex: Undetermined
39

Drive Modbus I/O Control Output Instance 150 (96 Hex)

CAUTION
Use the ENTER Command only when necessary! The life of the EEPROM on the drive will support a finite number of operations. This means that the ENTER command can only be used a maximum of 100,000 times to store data in the EEPROM. After the specified number of operations, the EEPROM may fault (CPF04) requiring the drive control board to be replaced.
This I/O instance allows all drive parameters and monitors to be read/set. This instance is for Yaskawa drives only, and is not interchangeable with other DeviceNet drives, Assembly Object Class (04 Hex) Attribute (03 Hex). Both input/output use 5 bytes each. Refer to the Appendix A for a list of Modbus Registers.

Table 18: Drive Modbus I/O Control Instance 150 (96 Hex) (OUTPUT ASSEMBLY)

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Function Code 1 Register Number (Upper Byte) 2 Register Number (Lower Byte) 3 Register Data (Upper Byte) 4 Register Data (Lower Byte)
Data Name Description
The Modbus (response message) function code No. is displayed. 03 Hex: Read normal
Byte 0
Byte 1, 2
Byte 3, 4
Register Number (Upper and Lower Byte)
Register Data (Upper and Lower Byte)
Function Code
10 Hex: Write normal 83 Hex: Read fault 90 Hex: Write fault The processed Modbus register No. is displayed. For Read/write faults, Modbus error code is displayed. The read data at Modbus read command is displayed.
The ACCEPT/ENTER parameter group contains only two parameters, the ACCEPT and ENTER parameters.
If the value of ‘0’ is written to the ACCEPT parameter (0910 Hex), the drive will save the current values of the all drive parameters (A1-00 through o3-02) into RAM memory on the drive. Values saved in RAM memory will not be retained in case of power loss to the drive. If the value of ‘0’ is written to the ENTER parameter (0900 Hex), the drive will save the current values of all of the drive parameters (A1-00 through o3-02) into EEPROM memory on the drive. Values saved in EEPROM memory will be retained in case of power loss to the drive.
40

Standard Drive Control Input Instance 101 (65 Hex)

This I/O instance is for the input/output functions as well as the expansion I/O instance functions. This instance is for Yaskawa series drives only, and is not interchangeable with other DeviceNet drives, Assembly Object Class (04 Hex) Attribute (03 Hex). Both input and output use 8 bytes each.
Table 19: Standard Drive Control Instance 101 (65 Hex) (INPUT ASSEMBLY)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
2 Speed Reference (Lower Byte) 3 Speed Reference (Upper Byte) 4 Torque Reference/Torque Limit (Low Order Byte) 5 Torque Reference/Torque Limit (High Order Byte) 6 Torque Compensation (Low Order Byte) 7 Torque Compensation (High Order Byte)
Terminal S8Terminal S7Terminal S6Terminal S5Terminal S4Terminal
S3 Terminal M5-M6
Terminal M3-M4
Terminal M1-M2
---
Rev Run Fwd Run
Fault Reset
*1
External Fault

Table 20: Standard Drive Control Instance 101 (65 Hex) (INPUT ASSEMBLY)*1

Data Name
The drive runs forward.
Byte 0, Bit 0
Byte 0, Bit 1
Byte 0, Bit 2
Byte 0, Bit 3
Byte 0, Bit 4
Byte 0, Bit 5
Byte 0, Bit 6
Byte 0, Bit 7
*1 Drive products may provide additional inputs and outputs that are not supported through DeviceNet. For example, G7 has
12 digital inputs; however; only 8 digital inputs are supported through DeviceNet.
Forward Run
Reverse Run
Terminal S3
Terminal S4
Terminal S5
Terminal S6
Terminal S7
Terminal S8
0: Stop 1: Forward run The drive runs reverse. 0: Stop 1: Reverse run Functions set in the drive multi-function input terminal S3 is input. The drive parameter H1-01 sets multi-function input terminal S3 functions. 0: Terminal S3 multi-function OFF 1: Terminal S3 multi-function ON Functions set in the drive multi-function input terminal S4 is input. The drive parameter H1-02 sets multi-function input terminal S4 functions. 0: Terminal S4 multi-function OFF 1: Terminal S4 multi-function ON Functions set in the drive multi-function input terminal S5 is input. The drive parameter H1-03 sets multi-function input terminal S5 functions. 0: Terminal S5 multi-function OFF 1: Terminal S5 multi-function ON Functions set in the drive multi-function input terminal S6 is input. The drive parameter H1-04 sets multi-function input terminal S6 functions. 0: Terminal S6 multi-function OFF 1: Terminal S6 multi-function ON Functions set in the drive multi-function input terminal S7 is input. The drive parameter H1-05 sets multi-function input terminal S7 functions. 0: Terminal S7 multi-function OFF 1: Terminal S7 multi-function ON Functions set in the drive multi-function input terminal S8 is input. The drive parameter H1-06 sets multi-function input terminal S8 functions. 0: Terminal S8 multi-function OFF 1: Terminal S8 multi-function ON
Description
41
Table 20: Standard Drive Control Instance 101 (65 Hex) (INPUT ASSEMBLY) *1 (Cont.)
Byte 1, Bit 0
Byte 1, Bit 1
Byte 1, Bit 5
Byte 1, Bit 6
Byte 1, Bit 7
Byte 2, 3
Byte 4,5
Byte 6,7
*1 Drive products may provide additional inputs and outputs that are not supported through DeviceNet. For example, G7 has 5
digital outputs; however, only 3 digital outputs are supported through DeviceNet.
External Fault
Fault Reset
Terminal M1-M2
Terminal M3-M4
Terminal M5-M6
Speed Reference
Torque Reference/
Torque Limit
Torque Compensation
External fault (EF0) is input from option. 0: External Fault Off
1: External fault (EF0)
The drive is reset at fault detection status. 0: Fault reset Off
1: Fault reset The drive multi-function output terminal M1-M2 is operated. Only when “F” is set to the drive parameter H2-01 becomes enabled. 0: Terminal M1-M2 OFF 1: Terminal M1-M2 ON The drive multi-function output terminal M3-M4 is operated. Only when “F” is set to the drive parameter H2-02 becomes enabled. 0: Terminal M3-M4 OFF 1: Terminal M3-M4 ON The drive multi-function output terminal M5-M6 is operated. Only when “F” is set to the drive parameter H2-03 becomes enabled. 0: Terminal M5-M6 OFF 1: Terminal M5-M6 ON Drive speed reference is set. This function is the same as the Speed Reference in Basic Speed Control Input Instance 20 (14 Hex) section. Sets the torque reference torque limit of the drive. The setting unit is fixed at 0.1%. Enabled only when the drive is set to the vector control mode with PG (A1-02=3). When the drive is in the torque control mode (d5-01=1), the torque reference is enabled. When in the speed control mode (d5-01=0), functions as the torque limit. When the drive parameter F6-06 is set to 0, it becomes disabled. Sets the drive torque compensation. The setting unit is fixed at 0.1%. Enabled only when the drive is set into the torque control with Flux Vector Control mode (A1-02=3).
42

Standard Drive Control Output Instance 151 (97 Hex)

This I/O instance is for the input/output functions as well as the expansion I/O instance functions. This instance is for Yaskawa series drives only, and is not interchangeable with other DeviceNet drives, Assembly Object Class (04 Hex) Attribute (03 Hex). Both input and output use 8 bytes each.
Table 21: Standard Drive Control Instance 151 (97 Hex) (OUTPUT ASSEMBLY)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Fault Alarm
1
2 Speed Actual (Lower Byte) 3 Speed Actual (Upper Byte) 4 5 6 Output Current Monitor (Lower Byte) 7 Output Current Monitor (Upper Byte)
Byte 0, Bit 0
Byte 0, Bit 1
Byte 0, Bit 2
Byte 0, Bit 3
Byte 0, Bit 4
Byte 0, Bit 5
Byte 0, Bit 6
Byte 0, Bit 7
Byte 1, Bit 0
--
Data
During Run
During Zero Speed
During Reverse Run
During Reset Input
Speed Agree
Inverter Ready
During OPE
Inverter
Ready
Ter mi na l
M5-M6
Name
Alarm
Fault
Speed Agree
Terminal
M3-M4
The drive run status is displayed. 0: During stop 1: During Forward/reverse/DC braking The drive run status is displayed. 0: During forward/reverse 1: During stop/DC braking The drive run status is displayed. 0: During forward run 1: During reverse run/reverse command input The drive reset signal input status is displayed. 0: Off 1: During reset signal input The drive frequency agree detection status is displayed. 0: During stop/acceleration and deceleration 1: Frequency agree The drive ready status is displayed. 0: During fault detection/ready 1: Ready The drive alarm detection status is displayed. 0: Normal 1: During alarm detection The drive fault detection status is displayed. 0: Normal 1: During fault detection The drive Modbus parameter setting error (OPE) detection status is displayed. 0: Normal 1: During OPE, (OPE1-OPE11) fault detection
During
reset
Terminal
M1-M2
- -
During reverse
Local/
Remote
Description
During
zero
speed
During
UV
*1
During Run
During
OPE
*1 Drive products may provide additional inputs and outputs that are not supported through DeviceNet. For example, G7 has 5
digital outputs; however, only 3 digital outputs are supported through DeviceNet.
43
Table 21: Standard Drive Control Instance 151 (97 Hex) (OUTPUT ASSEMBLY)
The drive low voltage error (UV) detection status is displayed.
Byte 1, Bit 1
Byte 1, Bit 2
Byte 1, Bit 3
Byte 1, Bit 4
Byte 1, Bit 5
Byte 1, Bit 6
Byte 1, Bit 7
Byte 2, 3
Byte 4, 5
Byte 6, 7
*1 Drive products may provide additional inputs and outputs that are not supported through DeviceNet. For example, G7 has 5
digital outputs; however, only 3 digital outputs are supported through DeviceNet.
During UV
Local/Remote
Term i na l M1 - M 2
Term i na l M3 - M 4
Term i na l M5 - M 6
Not Used
During Zero Servo
Speed Monitor
Torque Reference
Output Current Monitor
0: Normal 1: During UV detection The drive run command input selection status is displayed. 0: Run command input is enabled other than the DeviceNet. 1: Run command input is enabled from DeviceNet. The drive multi-function output terminal M1-M2 output status is displayed. 0: Terminal M1-M2 OFF 1: Terminal M1-M2 ON The drive multi-function output terminal M3-M4 output status is displayed. 0: Terminal M3-M4 OFF 1: Terminal M3-M4 ON The drive multi-function output terminal M5-M6 output status is displayed. 0: Terminal M5-M6 OFF 1: Terminal M5-M6 ON
­Displays the zero servo complete status of drive. 0: Zero servo not complete or not input. 1: Zero servo complete. The drive speed is displayed. This function is the same as the Speed Monitor in Basic Speed Control Output Instance 70 (46 Hex) section. Displays the torque reference of the drive. The unit is fixed at 0.1%. The drive output current is displayed. The unit (0.1A) is fixed.
There is no effect on the current scale
setting.
*1
(Cont.)
44

DeviceNet Explicit Messaging Communications

The DeviceNet communications may also be accomplished by utilizing an “Explicit Message” to communicate with the master PLC or controller. The Explicit messaging communications is performed differently than Polled I/O type messaging in that commands are not sent cyclically in the scan of the controlling master, but one message is sent and one response is received. See table below for details on Explicit Message Format.

Table 22: Explicit Message Format

Header MAC ID Service Code Class Instance Attribute Data Footer
Item Description
Header Since it is automatically set, there is no need to do anything.
MAC ID Master/slave MAC ID is input for communication.
Code, which shows data write/read, is input in the requested message. Also, the requested service code MSB (the most significant bit) inputs “1” at normal
Service Code
Class
Instance
Attribute
Data
Footer Since it is automatically set, there is no need to do anything.
response, and “94” at fault. Example: 0E: Read request 8E: Read normal response
10: Write request 90: Write normal response 94: Fault response
Each function of DeviceNet is classified by three codes. When you wish to designate data, use these 3 codes to do so.
Request: Write data is input. Response: Read data and error code are input.
The following pages define the supported DeviceNet implemented objects and services for the drive option.
45

Identity Object Class (01 Hex):

The Identity object stores DeviceNet product information.

Table 23: Supported Services

Service Code (Hex) Service Name Description of Service
0E Get_Attribute_Single Designated attribute content is returned.
05 Reset Option unit status is reset. (returns to initial status)

Table 24: Object Content

Instance
(Hex)
00 01
01
Attribute
(Hex)
01 Vendor ID
02 Device Type
03 Product Code Manufacturer’s code.
04 Revision Option unit software revision 2003 * Word
05 Status
06 Serial Number Option unit serial number
07 Product Name
08 Present Status
Name Description
Object Software
Revision
Identity object software revision is displayed. Manufacturer code No. is displayed. 44 (2C Hex): Yaskawa Electric Device profile of the compatible DeviceNet is displayed. The DeviceNet product is compatible with AC Drive Profile. 2: AC drive
Option unit communication status is displayed.
Product model is displayed.
Drive status is displayed. 3: Inverter ready
Initial Va lu e (Hex)
0001 * Word
002C * Word
0002 * Word
(See Table
of EDS
Files and
Product
Codes on
the
following
page)
0000 * Word
Depends on product (See Table
of EDS
Files and
Product
Codes on
the
following
page)
03 * Byte
Read Write Size
*Word
*Long
* String
46

Table 25: Option Product Name and Product Codes

CIMR-
F7U
or
CIMR-
Drive
Capacity
o2-04
Product Name Product Code Product Name Product Code
F7/SI-N1 G7/SI-N1
G7U
20P4 00 Hex CIMRF7U20P4_SI-N1 8960 (2500 Hex) CIMRG7U20P4_SI-N1 9984 (2700 Hex)
20P7 01 Hex CIMRF7U20P7_SI-N1 8961 (2501 Hex) CIMRG7U20P7_SI-N1 9985 (2701 Hex)
21P5 02 Hex CIMRF7U21P5_SI-N1 8962 (2502 Hex) CIMRG7U21P5_SI-N1 9986 (2702 Hex)
22P2 03 Hex CIMRF7U22P2_SI-N1 8963 (2503 Hex) CIMRG7U22P2_SI-N1 9987 (2703 Hex)
23P7 04 Hex CIMRF7U23P7_SI-N1 8964 (2504 Hex) CIMRG7U23P7_SI-N1 9988 (2704 Hex)
25P5 05 Hex CIMRF7U25P5_SI-N1 8965 (2505 Hex) CIMRG7U25P5_SI-N1 9989 (2705 Hex)
27P5 06 Hex CIMRF7U27P5_SI-N1 8966 (2506 Hex) CIMRG7U27P5_SI-N1 9990 (2706 Hex)
2011 07 Hex CIMRF7U2011_SI-N1 8967 (2507 Hex) CIMRG7U2011_SI-N1 9991 (2707 Hex)
2015 08 Hex CIMRF7U2015_SI-N1 8968 (2508 Hex) CIMRG7U2015_SI-N1 9992 (2708 Hex)
2018 09 Hex CIMRF7U2018_SI-N1 8969 (2509 Hex) CIMRG7U2018_SI-N1 9993 (2709 Hex)
2022 0A Hex CIMRF7U2022_SI-N1 8070 (250A Hex) CIMRG7U2022_SI-N1 9994 (270A Hex)
2030 0B Hex CIMRF7U2030_SI-N1 8071 (250B Hex) CIMRG7U2030_SI-N1 9995 (270B Hex)
208 - 230Vac
2037 0C Hex CIMRF7U2037_SI-N1 8072 (250C Hex) CIMRG7U2037_SI-N1 9996 (270C Hex)
2045 0D Hex CIMRF7U2045_SI-N1 8973 (250D Hex) CIMRG7U2045_SI-N1 9997 (270D Hex)
2055 0E Hex CIMRF7U2055_SI-N1 8974 (250E Hex) CIMRG7U2055_SI-N1 9998 (270E Hex)
2075 0F Hex CIMRF7U2075_SI-N1 8975 (250F Hex) CIMRG7U2075_SI-N1 9999 (270F Hex)
2090 10 Hex CIMRF7U2090_SI-N1 8976 (2510 Hex) CIMRG7U2090_SI-N1 10000 (2710 Hex)
2110 11 Hex CIMRF7U2110_SI-N1 8977 (2511 Hex) CIMRG7U2110_SI-N1 10001 (2711 Hex)
40P4 20 Hex CIMRF7U40P4_SI-N1 8992 (2520 Hex) CIMRG7U40P4_SI-N1 10016 (2720 Hex)
40P7 21 Hex CIMRF7U40P7_SI-N1 8993 (2521 Hex) CIMRG7U40P7_SI-N1 10017 (2721 Hex)
41P5 22 Hex CIMRF7U41P5_SI-N1 8994 (2522 Hex) CIMRG7U41P5_SI-N1 10018 (2722 Hex)
42P2 23 Hex CIMRF7U42P2_SI-N1 8995 (2523 Hex) CIMRG7U42P2_SI-N1 10019 (2722 Hex)
43P7 24 Hex CIMRF7U43P7_SI-N1 8996 (2524 Hex) CIMRG7U43P7_SI-N1 10020 (2724 Hex)
44P0 25 Hex CIMRF7U44P0_SI-N1 8997 (2525 Hex) CIMRG7U44P0_SI-N1 10021 (2725 Hex)
45P5 26 Hex CIMRF7U45P5_SI-N1 8998 (2526 Hex) CIMRG7U45P5_SI-N1 10022 (2726 Hex)
47P5 27 Hex CIMRF7U47P5_SI-N1 8999 (2527 Hex) CIMRG7U47P5_SI-N1 10023 (2727 Hex)
4011 28 Hex CIMRF7U4011_SI-N1 9000 (2528 Hex) CIMRG7U4011_SI-N1 10024 (2728 Hex)
4015 29 Hex CIMRF7U4015_SI-N1 9001 (2529 Hex) CIMRG7U4015_SI-N1 10025 (2729 Hex)
4018 2A Hex CIMRF7U4018_SI-N1 9002 (252A Hex) CIMRG7U4018_SI-N1 10026 (272A Hex)
4022 2B Hex CIMRF7U4022_SI-N1 9003 (252B Hex) CIMRG7U4022_SI-N1 10027 (272B Hex)
4030 2C Hex CIMRF7U4030_SI-N1 9004 (252C Hex) CIMRG7U4030_SI-N1 10028 (272C Hex)
4037 2D Hex CIMRF7U4037_SI-N1 9005 (252D Hex) CIMRG7U4037_SI-N1 10029 (272D Hex)
480Vac
4045 2E Hex CIMRF7U4045_SI-N1 9006 (252E Hex) CIMRG7U4045_SI-N1 10030 (272E Hex)
4055 2F Hex CIMRF7U4055_SI-N1 9007 (252F Hex) CIMRG7U4055_SI-N1 10031 (272F Hex)
4075 30 Hex CIMRF7U4075_SI-N1 9008 (2530 Hex) CIMRG7U4075_SI-N1 10032 (2730 Hex)
4090 31 Hex CIMRF7U4090_SI-N1 9009 (2531 Hex) CIMRG7U4090_SI-N1 10033 (2731 Hex)
4110 32 Hex CIMRF7U4110_SI-N1 9010 (2532 Hex) CIMRG7U4110_SI-N1 10034 (2732 Hex)
4132 33 Hex CIMRF7U4132_SI-N1 9011 (2533 Hex) CIMRG7U4132_SI-N1 10035 (2733 Hex)
4160 34 Hex CIMRF7U4160_SI-N1 9012 (2534 Hex) CIMRG7U4160_SI-N1 10036 (2734 Hex)
4185 35 Hex CIMRF7U4185_SI-N1 9013 (2535 Hex) CIMRG7U4185_SI-N1 10037 (2735 Hex)
4220 36 Hex CIMRF7U4220_SI-N1 9014 (2536 Hex) CIMRG7U4220_SI-N1 10038 (2736 Hex)
4300 37 Hex CIMRF7U4300_SI-N1 9015 (2537 Hex) CIMRG7U4300_SI-N1 10039 (2737 Hex)
Note: The EDS files will be in zip format, so unzip the file before installing in the DeviceNet configuration software tool.
47

Message Router Object Class (02 Hex):

The Message Router object has the function of routing DeviceNet communication information to the correct object. DeviceNet messages are routed to each function through this object. The Message Router object itself performs the internal processes only.

Table 26: Supported Service

Service Code (Hex) Service Name Description of Service
0E Get_Attribute_Single Designated attribute content is returned.

Table 27: Object Content

Instance
(Hex)
Attribute
(Hex)
Name Description
Setting
Range
Initial Va lu e (Hex)
Read Write Size
00 01
Object Software Revision
Message Router object software revision is displayed.

DeviceNet Object Class (03 Hex):

This object is for the DeviceNet communication information/functions.

Table 28: Supported Service

Service Code (Hex)
0E Get_Attribute_Single Designated attribute content is returned.
10 Set_Attribute_Single Designated attribute content is changed.
Instance
(Hex)
00 01
01
Attribute
(Hex)
01
02
05
Service Name Description of Service

Table 29: Object Content

Name Description
Object Software Revision
MAC ID
Baud Rate
Allocation
Information
DeviceNet object software revision is displayed.
MAC ID setting value is displayed according to the DIP switch setting.
Baud rate setting value is displayed according to the DIP switch settings. 0: 125kbps 1: 250kbps 2: 500kbps
DeviceNet communication connection information is displayed.
Setting
Range
Initial Va lu e (Hex)
0x63 00
0x02 00
00,00
0001
0002
o
Read Write Size
o
o
o
o
Word
Word
Byte
Byte
Byte
×2
48

Assembly Object Class (04 Hex):

The Assembly object is for the polled I/O message functions.

Table 30: Supported Service

Service Code (Hex) Service Name Description of Service
0E Get_Attribute_Single Designated attribute content is returned.
10 Set_Attribute_Single Designated attribute content is changed.

Table 31: Object Content

Instance
(Hex)
00 01
14 03
15 03
46 03
47 03
64 03
65 03
96 03
Attribute
(Hex)
Name Description
Object Software
Revision
I/O Data
I/O Data
I/O Data
I/O Data
I/O Data
I/O Data
I/O Data
Assembly object software revision is displayed.
Same function as the basic I/O instance 20 (input/PCA)
Same function as the extended I/O instance 21 (input/PCA)
Same function as the basic I/O instance 70 (output/PPA)
Same function as the extended I/O instance 71 (output/PPA)
Same function as the Modbus I/O instance 100 (input/PCA)
Same function as the drive standard control I/O instance 101 (input/PCA/PPA)
Same function as the Modbus I/O instance 150 (output/PPA)
Setting
Range
*1
*1
Initial Va lu e (Hex)
0002 o
−−
−−
*1
*1
−−
Read Write Size
Word
oo
oo
o
o
oo
oo
o
Byte
×4
Byte
×4
Byte
×4
Byte
×4
Byte
×5
Byte
×8
Byte
×5
Same function as the drive
97 03
*1 Setting range is the same as the individual I/O message function.
I/O Data
standard control I/O instance 151 (output/PPA)
49
−−
o
Byte
×8

DeviceNet Connection Object Class (05 Hex):

The DeviceNet Connection object has the function of keeping track of the DeviceNet communication connection information/ functions. On initialization, the communication connection with the master is established by using information and functions
from this object. Please note that Instance 2 of DeviceNet Object Class 05 Hex supports only polled messaging.

Table 32: Supported Service

Service Code (Hex) Service Name Description of Service
0E Get_Attribute_Single Designated attribute content is returned.
10 Set_Attribute_Single Designated attribute content is changed.

Table 33: Object Content

Instance
(Hex)
00 01
01
Explicit
Message
Attribute
(Hex)
01
02
03
04
05
06
07
08
09
0C
0D
0E
0F
10
Name
Object Software
Revision
Instance State
Instance type
Connection
operation
Output (PPA)
connection ID
Input (PCA)
connection ID
Message group
No. of Max. output
(PPA) bytes
No. of Max. input
(PCA) bytes
Timeout time
Watchdog timeout
process
No. of output (PPA)
connection bus bytes
Output (PPA)
Connection Bus
No. of input (PCA)
connection bus bytes
Input (PCA)
connection bus
Description
DeviceNet connection object software revision is displayed.
This instance status is displayed. 00: It does not exist in the Network yet,
and is being prepared.
01: On-line status and waiting for the
connection from the master. 02: Waiting for the connection ID write. 03: Connection is completed. 04: Time out.
This instance type is displayed. 00: Explicit message 01: I/O message
The option unit communication status is displayed by a code.
The level used by the option unit communication header is displayed. This function is set when communication connection is completed.
The option unit communication status is displayed by a code.
No. of Max. output (PPA) bytes is displayed.
No. of Max. input (PCA) bytes is displayed.
Internal process timeout time is displayed when communication request is received. (Round up 10ms unit)
Timeout internal process regarding communication is displayed. 00: Holds until reset/shut off 01: Automatically shut off 02: Restart with connected status.
No. of output (PPA) connection bus bytes is displayed.
The application object received the data through this instance is displayed.
No. of input (PCA) connection bus bytes is displayed.
The application object received the data through this instance is displayed.
Setting
Range
65535
(ms)
−−
−−
Initial Va l ue (Hex)
0001
03
00
83
71
21
21
0020
0020
09C4
(2500ms)
01
0000
0000
Read Write Size
o
o
o
o
o
o
o
o
o
oo
o
o
o
o
o
Wor d
Byte
Byte
Byte
Wor d
Wor d
Byte
Wor d
Wor d
Wor d
Byte
Wor d
Array
Wor d
Array
50
Instance
(Hex)
02
Polled
Message
Only
Attribute
(Hex)
01
02
03
04
05
06
07
08
09
0C
0D
0E
0F
10
Name
Instance status
Instance type
Connection
operation
Output (PPA)
Connection ID
Input (PCA)
connection ID
Message group
No. of Max. output
(PPA) bytes
No. of Max. input
(PCA) bytes
Tim eou t tim e
Watchdog timeout
process
No. of output (PPA)
connection path bytes
Output
communication path
Polled Producing
Assembly (PPA)
No. of input (PCA)
communication path
bytes
Input communication
path
Polled Consuming
Assembly (PCA)
Table 33: Object Content (Continued)
Description
This instance status is displayed. 00: It does not exist in the Network yet,
and is being prepared. 01: On-line status and waiting for the
connection from the master. 02: Waiting for the connection ID write. 03: Connection is completed. 04: Time out.
This instance type is displayed. 00: Explicit message 01: I/O message
The option unit communication status is displayed by a code.
The level used by the option unit communication header is displayed. This function is set when communication connection is completed.
The option unit communication status is displayed by the code.
No. of max. output (PPA) bytes is displayed.
No. of max. input (PCA) bytes is displayed.
Internal process timeout time is displayed when communication request is received. (Round up 10ms unit)
Timeout internal process regarding communication is displayed. 00: Holds until reset/shut off 01: Automatically shut off 02: Restart with connected status.
No. of output (PPA) connection path bytes is displayed.
The application object received the data through this instance is displayed.
No. of input (PCA) connection bus bytes is displayed.
The application object received the data through this instance is displayed.
Setting
Range
65535
(ms)
Initial Va l ue (Hex)
03
01
82
71
21
01
0004
0004
0000
(0ms)
01
0003
62 34 37
0003
62 31 35
Read Write Size
o
o
o
o
o
o
o
o
oo
oo
o
oo
o
oo
Byte
Byte
Byte
Wor d
Wor d
Byte
Wor d
Wor d
Wor d
Byte
Wor d
Array
Wor d
Array
51

Motor Data Object Class (28 Hex):

The motor data object is for the information and functions related to the motor connected to the drive. Motor rated current and rated voltage can be set and read.

Table 34: Supported Service

Service Code No. (Hex) Service Name Description of Service
0E Get_Attribute_Single Designated attribute content is returned.
10 Set_Attribute_Single Designated attribute content is changed.

Table 35: Object Content

Instance
(Hex)
00 01
01
*1   The motor rated current initial value varies according to drive capacity.
*2   The initial value and setting range are for the 200V class. For the 400V class, the value is twice that of the 200V class.
Attribute
(Hex)
03
06
07
Name Description
Object
Software
Revision
Motor Type
Motor Rated
Current
Motor Rated
Voltage
Motor Data object software revision is displayed.
Used motor type is displayed, 7: Squirrel-cage induction motor
Motor rated current can be set and read. Setting unit: 0.1A
Motor rated voltage can be set and read. Setting unit: 1V
Setting
Range
10~20%
of drive
rated
current
255V
*2
Initial Va lu e (Hex)
0001 o
07 o
*1 o o Word
00C8
*2
Read Write Size
Word
ooWord
Byte

Control Supervisor Object Class (29 Hex):

The control supervisor object is dedicated to the information and services related to the drive control functions. The basic control functions such as, inverter run, stop, and fault detect are implemented. The control supervisor object functions are commonly used with polled I/O messaging functions.

Table 36: Supported Service

Service Code No. (Hex) Service Name Description of Service
0E Get_Attribute_Single Designated attribute content is returned.
10 Set_Attribute_Single Designated attribute content is changed. 05 Reset Option unit status is reset. (returns to initial status)
52

Table 37: Object Content

Instance
(Hex)
00 01
01
Notes:
*1 A setting during drive operation cannot be changed. *2 DeviceNet communication fault cannot be set. The drive detects fault and stops at DeviceNet communication fault. The drive stopping method at
communication fault can be selected by time-over detection selection parameter (n151).
*3 Fault Code (See below table for interpretation)
Attribute
(Hex)
03
04
05
06
07
08
09
0A
0B
0C
0D
0F
10
11
12
Name
Object Software
Revision
Forward Run
Reverse Run
NetCtrl
Inverter Status
During
Forward Run
During Reverse
Run
Inverter Ready
Fault
Alarm
Fault Reset
Fault Code
Ctrl From Net
DeviceNet
Fault Mode
External Fault
from Option
External Fault
Input Status from Option
Description
Control supervisor object software revision is displayed. The drive runs forward. 00: Stop 01: Forward run The drive runs reverse. 00: Stop 01: Reverse run Run command rights displayed. *1 00: Run command input method set by run
command selection (n003)
01: Run command (byte 0 – bit 0, 1) is enabled
through DeviceNet. The drive status is displayed. 03: Inverter ready The drive run status is displayed. 00: During stop/reverse 01: During forward run/DC braking The drive run status is displayed. 00: During stop/forward/DC braking 01: During reverse The drive operation preparing status is displayed. 00: During fault detection/preparation 01: Ready The drive fault detection status is displayed. 00: Normal 01: During fault detection The drive alarm detection status is displayed. 00: Normal 01: During alarm detection The drive is reset through fault detection status. 00: Fault reset off 01: Fault reset The drive fault detection content is displayed by the code listed in the table below. *3 The drive run command input selection status is displayed.*1 00: Run command input other than the DeviceNet is
enabled. 01: Run command input is enabled through
DeviceNet. Mode selection is displayed when DeviceNet becomes fault.*2 02: Manufacturer External fault (EF0) is input 00: EF0 Not Active 01: External fault (EF0) External fault (EF0) input status is displayed. 00: EF0 Not Active 01: During external fault (EF0) input
Setting
Range
00,01 00
00,01 00
00,01 00
00,01 00
00,01 00
Initial Va lu e (Hex)
0001
Read Write Size
o
oo
oo
oo
03
00
00
00
00
00
o
o
o
o
o
o
oo
0000
00
02
o
o
o
oo
00
o
Wor d
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Wor d
Byte
Byte
Byte
Byte
53

AC/DC Drive Object Class (2A Hex):

The AC/DC Drive Object is also dedicated to the information and function related to the drive operation. Frequency reference settings, individual monitor parameters, and data unit settings can be changed. The AC/DC Drive Object function is com-
monly used with I/O message functions for setting or returning drive status information.

Table 38: Supported Service

Service Code No. (Hex) Service Name Description of Service
0E Get_Attribute_Single Designated attribute content is returned.
10 Set_Attribute_Single Designated attribute content is changed.

Table 39: Object Content

Instance
(Hex)
00 01
01
Attribute
(Hex)
03
04
06
07
08
09
0F
10
11
12
13
14
Name Description
Object Software Revision
Speed agree
NetRef
Control mode
Speed monitor
Spe ed referen ce
Output current
Output power
Input Voltage
Output Voltage
Accel Time
Decel Time
Low Speed Limit
AC/DC Drive Object software revision is displayed.
Drive frequency agree detection status is displayed. 00: During stop/decel/accel 01: Frequency agree
Frequency reference rights is set.*1 00: Frequency reference input method set by
frequency reference selection (b1-01).
01: Frequency reference (byte 2, 3) through
DeviceNet is enabled. Drive control mode is set.*3 00: V/F control 01: Vector control Drive speed is displayed.*2
Min. unit: [r/min/2 where SS: Speed scale: attribute 16
Frequency Reference is set/read
Min. unit: [r/min/2SS] where SS: Speed scale: attribute 16
Drive output current is displayed:*2
Current Unit: [0.1A/2 where CS: Current scale: attribute 17
Drive output power is displayed:*2
Power Unit: [W/2 where PS: Power scale: attribute 1A
Drive input voltage is displayed:
Min. Unit: [V/2 where VS: Voltage scale: attribute 1B
Drive output voltage is displayed:
Min. Unit: [V/2 where VS: Voltage scale: attribute 1B
Acceleration time 1 is set/read.
Min. Unit: [ms/2 where TS: Time scale: attribute 1C
Deceleration time 1 is set/read.
Min. : Unit: [ms/2 where TS: Time scale: attribute 1C Drive Frequency Reference lower limit value is
*2 *3
set/read.
Min. : Unit: [r/min/2SS] where SS: Speed scale: attribute 16
VS
VS
SS
]
*2
CS
]
PS
]
]
]
TS
]
TS
]
Setting
Range
00,01 00
00,01 00
00,03 01
0- E1-04 000 0
655.35s
655.35s
100.0%
Initial Va l ue (Hex)
0-
0-
0-
0001
0000
0000
0000
0000
0000
0x2710 (10.0s)
0x2710 (10.0s)
0000
Read Write Size
o
o
oo
oo
o
oo
o
o
o
o
oo
oo
oo
Wor d
Byte
Byte
Byte
Wor d
Wor d
Wor d
Wor d
Wor d
Wor d
Wor d
Wor d
Wor d
54
Table 38: Object Content (continued)
Drive Frequency Reference upper limit value is
*2 *3
set/read.
Min. :Unit: [r/min/2SS] where SS: Speed scale: attribute 16
Data unit coefficient regarding speed is set/read.
Min. Unit: 1 [r/min]×1/2 where SS: Speed scale setting value
Data Coefficient regarding current is set/read.
Current Unit: 0.1 [A]×1/2 where CS: Current scale setting value
Data Coefficient regarding power is set/read.
Power Unit: 1 [W]×1/2 where PS: Power scale setting value
Data unit coefficient regarding voltage is set/ read.
Voltage Unit: 1 [V]×1/2 where VS: Voltage scale setting value
Data unit coefficient regarding time is set and read.
Time Unit: 1 [ms]×1/2 where TS: Time scale setting value
Drive frequency reference input selection status
is displayed 00: Frequency Reference input other than
01: Frequency Reference input from DeviceNet
*1
DeviceNet is enabled.
is enabled.
SS
CS
PS
VS
TS
100.0%
-15-15
(F1-0F)
-15-15
(F1-0F)
-15-15
(F1-0F)
-15-15
(F1-0F)
-15-15
(F1-0F)
00,01 00
01
15
16
17
1A
1B
1C
1D
High Speed Limit
Speed Scale
Current Scale
Power Scale
Voltage Scale
Time S cale
Ref From Net
Notes:
*1 A setting during drive operation cannot be changed.
*2 An application of speed command, speed monitor, speed lower limit value, and speed upper limit value must be set
as a motor pole value (2~39) to the drive parameter o1-03 (frequency reference set/display unit selection)
*3 Control mode, speed lower limit, and speed upper limit cannot be set during drive operation.
SS: Speed Scale (AC/DC Drive Object Attr. 22)
0x0708
0-
(1800r/
m)
00
00
00
00
00
oo
oo
oo
oo
oo
oo
o
Wor d
Byte
Byte
Byte
Byte
Byte
Byte
CS: Current Scale (AC/DC Drive Object Attr. 23)
PS: Power Scale (AC/DC Drive Object Attr. 26)
VS: Voltage Scale (AC/DC Drive Object Attr. 27)
TS: Time Scale (AC/DC Drive Object Attr. 28)
55

Drive Parameters Object Class 100 (64 Hex):

Modbus register 01 80 hex = Instance 01 hex and Attribute 80 hex
This DeviceNet Object Class can read and write all of the same parameters and monitors available via drive digital operator keypad. This Object Class is designed specifically for Yaskawa drives.
A built-in Modbus protocol and addressing scheme is standard in all Yaskawa drives. The option converts the DeviceNet message to Modbus for use internally in the drive.
Yaskawa Drive Parameter Object Class 100 is modeled after the drive's internal Modbus addressing scheme. The DeviceNet path for each drive parameter is derived by converting the drive's Modbus register number to the DeviceNet path, Class/ Instance/Attribute. Reading or writing parameters to the drive via DeviceNet is simplified because the DeviceNet path closely matches the drive's Modbus register numbers.

Table 40: Supported Service

Service Code No. (Hex) Service Name Description of Service
0E Get_Attribute_Single Designated attribute content is returned.
10 Set_Attribute_Single Designated attribute content is changed.

Table 41: Converting the Modbus Register Number to the DeviceNet Path

Modbus Register: 0180 Hex DeviceNet Path: 64/01/80 Hex
Example Data Example Data
- - Class 64 Hex
Byte 1 01 Hex
Byte 0 80 Hex Attribute 80 Hex
Instance 01 Hex
The DeviceNet Class for parameter access is always “64”.
The DeviceNet Instance is always equal to Modbus register byte 1 or the MSB (most significant byte).
The DeviceNet Instance is always equal to Modbus register byte 0 or the LSB (least significant byte).
The data size for each Attribute is 2 bytes.
Refer to the drive User Manual for description on the parameters and Modbus Manual for Modbus registers.
Example 1:
Reading the Reference Source Parameter b1-01 Value by Explicit Messaging
To read parameter b1-01 (Modbus register 0180 Hex) Reference Source, first convert the Modbus register number to DeviceNet Instance and Attribute.
Then, send an explicit message with Service Code 0E Hex (Get Attribute Single) to Class 64/Instance 1/Attribute 80 Hex. If the returned value is 0001 Hex, then Reference Source is set to Parameter Setting 1, Terminals.
Note: The same Class/Instance/Attribute paths are used in the EDS file provided by Yaskawa.
56

Table 42: Reference Source Parameter b1-01 Settings

Modbus register 02 00 hex = Instance 02 hex and Attribute 00 hex
Class 100/ Instance/ Attribute (Hex)
64/1/80 180 b1-01 Reference
Example 2:
Setting the Accel Time 1 Parameter C1-01 Value by Explicit Messaging
To set parameter C1-01 (Modbus register 0200 Hex) Acceleration Time 1 to 3.5 seconds, first convert the Modbus register number to DeviceNet Instance and Attribute.
Then, send an explicit message with Service Code 10 Hex (Set Attribute Single) to Class 64/Instance 2/Attribute 00 Hex, with the data field as 23 Hex (35). The data field does not recognize decimal places, so the data must be written as a whole number. Also, in reading and setting to parameters C1-01 to C1-09 Accel/Decel Time 1 to 4, be sure to check the setting of parameter C1-10 Accel/Decel Time Setting Unit. For instance, in the above example, if C1-10 is set to value of 1 (0.01 – two decimal places) instead of the default value (0.1 - one decimal place), the data field to set acceleration time to 3.50 seconds would be 15E Hex (350). Refer to the drive User Manual for further drive parameter descriptions.
Modbus Register (Hex)
Parameter Function Setting Description
0 Operator
Source
1 Terminals
2 Serial Communication
3 Option
4 Pulse Input

Table 43: Accel Time 1 Parameter C1-01 Settings

Class 100/ Instance/ Attribute (Hex)
64/2/00 200 C1-01 Acceleration
64/2/09 209 C1-10 Accel/Decel
Modbus Register (Hex)
Parameter Function Setting Description
Time 1
Time Setting Unit
0.00 to 600.0 seconds or 0.0 to 6000.0 seconds
0 0.01 (two decimal places)
1 default 0.1 (one decimal place)
57
DeviceNet Fault Diagnostics Drive Faults

Table 44: DeviceNet Fault Codes

DeviceNet
Fault Code No. (Hex)
0000 2120 2130
2200 OL2 Drive overload
2220 OL1 Motor overload
2221 OL3 Overtorque 1
2222 OL4 Overtorque 2
2300 OC Overcurrent
3130
3210 OV Main circuit overvoltage
3220 UV1 Main circuit low voltage
3222 UV3 Surge protection circuit fault
4200 OH Heat sink fin overheat
5110 UV2 Control power fault
5120 PUF Fuse open
5300 OPR Operator not connected
6320 ERR EEPROM write failure
7110 RR Braking transistor fault
7112 RH Braking resistor overheat
7301 PGO PG wire broken detection
7310
7500 BUS Option communication error
9000
Operator Fault
Display
-
GH
SC
PF Main circuit voltage fault
LF Output phase missing
OS Excessive speed
DEV Speed deviation excessive
EF3 External fault (Input terminal S3)
EF4 External fault (Input terminal S4)
EF5 External fault (Input terminal S5)
EF6 External fault (Input terminal S6)
EF7 External fault (Input terminal S7)
EF8 External fault (Input terminal S8)
EF0 Option external fault
Content
Drive normal
Ground fault
Load short
58
Fault Diagnostics
The following is a table of faults caused by the option that will be displayed on the Digital Operator, their causes, and possible solutions. For any fault displayed on the operator that is not listed in the following table, please see the drive Users Manual.

Table 45: Drive Faults Caused by the Option

Fault
Display
BUS
EF0
CPF06
CPF21
CPF22
CPF23
Content Cause Solution
Option
Communication error
External Fault from
Option
Option Connection
Fault
Communication
Option Self-diagnostic
Fault
Communication
Option Model Code
No. Fault
Communication
Option Mutual
Diagnostic Fault
Communication is not established between DeviceNet master and the drive.
External fault is active from DeviceNet option.
The drive and communication are not correctly connected.
Communication option is not working.
Check DeviceNet communication LED display and connection at DeviceNet terminal. The network and/or 24VDC power supply may be down.
Turn OFF external fault input.
Turn OFF the drive power supply. Check the connection of the option and drive, and then, turn ON the drive power supply. If the fault persists, change the option.
Turn the drive power supply back ON. If the fault persists, change the option.
59

DeviceNet Communication LED Faults and Operation

Table 46: DeviceNet Communication LED Faults and Operation

LED Display
PWR MS NS WD
Not Lit Not Lit Not Lit Not Lit Power OFF
Solid
Green
Solid
Green
Solid
Green
Solid
Green
Solid
Green
Solid
Green
Solid
Green
Solid
Green
Solid
Green
Not Lit Not Lit
FlashG reen
Flash
Red
Solid
Red
Solid
Red
Solid
Green
SolidG
reen
Solid
Green
Solid
Green
Not Lit
Not Lit
Not Lit
Solid
Red
Flash
Red
Solid
Red
FlashG
reen
SolidG
reen
Solid
Red
FlashG reen
Flash
Green
Flash
Green
Flash
Green
Flash
Green
Flash
Green
Flash
Green
Flash
Green
Content Cause Solution
CPU Fault
During Option
Unit
Preparation
Option Unit
Possible Fault
Option Unit
Unrecoverable
Fault
Baud Rate
Setting Fault
Communicatio
n Timeout
Communicatio
n
Error
Normal
(Communicati
on data: No)
Normal
(Communicati
on data: Yes)
The drive is not powered.
The option is not correctly connected, thus, the power does not supply to the option.
The option CPU is being initialized or has a fault.
Initial setting status or the communication is being initialized.
A wrong setting of a switch or a recovery fault is occurring.
An Unrecoverable fault is occurring to the option.
Baud rate settings (DIP switch, DR1 and DR0) are both ON.
A master communication timeout occurred.
Communication Unrecoverable fault occurred.
Although the fault does not occur, it is connected to the master controller.
Drive is communicating normally.
Check the drive main circuit wiring, and then turn ON the power.
Turn Off the drive power, check the connection of the option and the drive, and re-power the drive.
Cycle drive power. If the fault persists, change the option.
Cycle drive power. If the fault persists, change the option.
Check baud rate setting (DIP switch, DR1 and DR0), and then re-cycle the power. If the fault persists, change the option.
Cycle drive power. If the fault persists, change the option.
Set the baud rate switches correctly, and cycle the drive power.
Check if the end termination resistor is correctly connected to the communication bus. Check if the communication device is correctly connected per wiring diagrams. Check if the communication bus wiring is separated from the main circuit wiring.
Check if other device’s MAC ID is not unique per the network. Check if the master is correctly configured. Check if the end termination resistor is correctly connected to the communication bus. Check if the communication device is correctly connected per wiring diagrams. Check if the communication bus wiring is separated from the main circuit wiring.
Send explicit message or I/O message from the master as necessary.
60

Explicit Message Communication Error

If a requested message has an error response from the master when performing Explicit message communication, the communication option sends a response message which the following error code shown in the table, is attached as data, as well as the service code “94”.

Table 47: Explicit Message Communication Error Codes

Error Code Content Cause Solution
08FF
09FF
0CFF
0EFF
13FF
14FF
15FF
16FF
1FFF
20FF
Service not requested Wrong service code. Correct service code.
Invalid attribute value detection Wrong attribute value. Correct attribute value.
Executing requested service is impossible
Setting prohibit attribute Cannot write to Attribute. Correct service code and attribute value.
Not enough data Data size is not matched. Correct data size.
Unauthorized Attribute
Excessive data Data size is not matched. Correct data size.
Object does not exist Object is not defined in the option. Correct class and option value.
Manufacturer specific error
Parameter fault
A non run-operative drive parameter is being attempted to be set during drive operation.
Unauthorized service was attempted to operate on the attribute.
An unsettable drive setting was attempted to be written to during drive operation. A drive setting is attempted to be written outside the setting range.
A data write is attempted that is outside of the setting range.
Stop drive operation.
Correct service code and attribute value.
Stop the drive. Correct the data within the setting range.
Correct the data within the setting range.
61

I/O Message Communication Modbus I/O Instance Errors

Table 48: Modbus I/O Instance Errors and Their Causes

Error Code
01 Hex Function code error Function code from the master was other than 00 Hex, 03 Hex, and 10 Hex.
02 Hex Register No. error
21 Hex Data setting error
22 Hex Write mode error
23 Hex Write during UV
24 Hex
Content Causes
A register # was not found. Enter command (0900 Hex) registered for write started to read. Parameter setting error occurred by a parameter write. Upper and lower byte values were out of alignment, swapped.
A parameter was attempted to write from the master during run. Enter command was attempted write from the master during UV. A parameter was attempted to write from the master during UV. Enter command was attempted to write from the master during UV. A parameter was attempted to write from the master during data store. Data for read only was attempted to write from the master.
Attempted to write a parameter from the master while UV was occurring. Attempted to write an enter command from the master while UV was occurring.
Write during
parameter processing
Attempted to write a parameter from the master while data was being stored.
62
Appendix A
Product Specifications
This chapter describes the product specifications of a DeviceNet network system.
DeviceNet Product Specification ....................................................... 64
63

Product Specifications

Item Specifications
I/O Message 4 types of I/O instance are supported:
1) Basic I/O instance (Input 4 bytes, output 4 bytes)
2) Expansion I/O instance (Input 4 bytes, output 4 bytes)
3) Modbus I/O instance (Input 5 bytes, output 5 bytes)
4) Standard drive control I/O instance (Input 8 bytes, output 8 bytes)
Explicit Message Suitable for DeviceNet AC/DC Drive Profile.
Data communication Max. 32 byte
Communication Power Supply DC 11V~25V (20mA or less)
Operation Power Supply DC 4.75V~5.25V (Supplied from the drive)
Ambient Temperature -10°C ~ +45°C
Humidity 95%RH or less (Non-condensing)
Storage Temperature -20°C ~ +60°C
Location Indoor (Protected from corrosive gas and dust)
Altitude 1000m or less
Voltage 11~25 Vdc
Current 100mA
64
Appendix B
Cable Specifications
This chapter describes the cable specifications for a DeviceNet network system.
DeviceNet Cable Specifications......................................................... 66
DeviceNet Cable Vendor Table........................................................... 66
DeviceNet Network Topology............................................................. 67
DeviceNet Maximum Cable Distance................................................. 67
65
Cable Specifications
Thick Cable
This cable consists of two shielded pairs twisted on a common axis with a drain wire in the center covered with an overall braid shield and is commonly used as trunkline when length is important.
The thick cable specified for DeviceNet network connections consists of:
· One twisted signal pair (#18): blue/white
· One twisted power pair (#15): black/red
· Separate aluminized mylar shields around power pair and signal pair
· Overall foil/braid shield with drain wire (#18): bare
Thin Cable
Thin Cable is smaller and more flexible than Thick Cable. It is commonly used for droplines, but can also be used, for shorter distances, as trunkline.
The thin cable specified for DeviceNet network connections consists of:
·One twisted signal pair (#24): blue/white
·One twisted power pair (#22): black/red
·Separate aluminized mylar shields around power pair and signal pair
·Overall foil/braid shield with drain wire (#22): bare

Cable Vendors

DeviceNet cables are available from various vendors. Two sources are listed below:

Table 49: DeviceNet Cable Sources

Belden Wire & Cable Company
Part # Thick/Thin Pair AWG Insulation Outer Jacket
3082A Thick
3084A Thin
3083A Thick
3085A Thin
Part # Thick/Thin Pair AWG Insulation Outer Jacket
210051 Thick
210144 Thin
Data 18 Datalene
Power 15 PVC/Nylon
Data 24 Datalene
Power 22 PVC/Nylon
Data 18 Datalene
Power 15 PVC/Nylon
Data 24 Datalene
Power 22 PVC/Nylon
Berk-Tek
Data 18 FPE/HDPE
Power 15 PVC/Nylon
Data 24 FPE/HDPE
Power 22 PVC/Nylon
Lt. Gray PVC
Lt. Gray PVC
Yellow CPE
Yellow CPE
Lt. Gray PVC
Lt. Gray PVC
66
DeviceNet Network Topology
Drop Line
N
N
N
pTap
Multi-Port
p
N
N
N
Multi-Port
p
Terminating Resistor
Terminating Resistor
Multiple Node
Daisy Chain
Drop Line
Multiple Node
Branching Drop Line
Fig. 8 DeviceNet Topology
Dropline
Dropline
Dropline
The DeviceNet media has a linear bus topology. Terminating resistors are required on each end of the trunkline. Droplines as long as 6 meters (20 feet) each are permitted, allowing one or more nodes to be attached. DeviceNet allows branching structures only on the dropline. The figure below shows an example of a DeviceNet network. The thick lines indicate a trunkline, whereas the thin lines indicate a dropline.
Tap
ode
ode
ode
ode
Node
Node
Node
Zero Length
Node
Ta
Ta
Node
Ta
ode
ode

Maximum Cable Distance

The total amount of trunkline allowable on the network depends upon the data rate and the type of cable (thick or thin) used. The cable distance between any two points in the cable system must not exceed the Maximum Cable Distance allowed for the baud rate. For trunklines constructed of only one type of cable, refer to the following table to determine the Maximum Cable Distance based on the data rate and the type of cable used. Cable distance between two points includes both trunkline cable and dropline cable length that exists between the two points.
Baud Rate
125 kbaud 500 meters (1640 feet)
500 kbaud 100 meters (328 feet)
DeviceNet allows the use of either thick or thin cable to be used to construct trunklines. DeviceNet also allows a combination of both types of cable to be used on the same network. To determine the maximum cable distance with a mix of both thick and thin cable, use the following figure.

Table 50: Maximum Cable Distance Allowed per Baud Rate

Maximum Cable Distance
for 100% Thick Cable
67
Maximum Cable Distance
for 100% Thin Cable
100 meters (328 feet)250 kbaud 250 meters (820 feet)
0
80
10
0
125
kbaud
250
kbaud
500
kbaud
Length of Thin Cable (meters)
Length of Thick Cable (meters)
At 125 kbaud: L
thick
+ (5.0 x L
thin
) = 500
At 250 kbaud: L
thick
+ (2.5 x L
thin
) = 250
At 500 kbaud: L
thick
+ L
thin
= 100
(where L
thick
is the length of thick cable and L
thin
is the length of thin cable.)
Fig. 9 Maximum Cable Distance
60 40 20
100 200 300 400 500
Dropline length is the longest cable distance measured from the tap on the trunkline to each of the transceivers of the nodes on the dropline. The total amount of dropline allowable on the network depends upon the data rate. Refer to the following dropline budget when determining the number and length of droplines.
Baud Rate
125 kbaud
250 kbaud 78 meters (256 feet)
500 kbaud 39 meters (128 feet)
Maximum Cumulative
6 meters (20 ft)
Drop Length
156 meters (512 feet)
68
This page intentionally blank.
69
DeviceNet™ CM059 (SI-N1) Option
YASKAWA ELECTRIC AMERICA, INC.
Chicago-Corporate Headquarters 2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: (800) YASKAWA (800-927-5292) Fax: (847) 887-7310 Internet: http://www.yaskawa.com
MOTOMAN INC.
805 Liberty Lane, West Carrollton, OH 45449, U.S.A. Phone: (937) 847-6200 Fax: (937) 847-6277 Internet: http://www.motoman.com
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-0022, Japan Phone: 81-3-5402-4511 Fax: 81-3-5402-4580 Internet: http://www.yaskawa.co.jp
YASKAWA ELETRICO DO BRASIL COMERCIO LTDA.
Avenida Fagundes Filho, 620 Bairro Saude Sao Paolo-SP, Brasil CEP: 04304-000 Phone: 55-11-5071-2552 Fax: 55-11-5581-8795 Internet: http://www.yaskawa.com.br
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany Phone: 49-6196-569-300 Fax: 49-6196-888-301
MOTOMAN ROBOTICS AB
Box 504 S38525, Torsas, Sweden Phone: 46-486-48800 Fax: 46-486-41410
MOTOMAN ROBOTEC GmbH
Kammerfeldstrabe 1, 85391 Allershausen, Germany Phone: 49-8166-900 Fax: 49-8166-9039
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, Scotland, United Kingdom
Phone: 44-12-3673-5000 Fax: 44-12-3645-8182
YASKAWA ELECTRIC KOREA CORPORATION
Paik Nam Bldg. 901 188-3, 1-Ga Euljiro, Joong-Gu, Seoul, Korea Phone: 82-2-776-7844 Fax: 82-2-753-2639
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
Head Office: 151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, Singapore Phone: 65-282-3003 Fax: 65-289-3003
TAIPEI OFFICE (AND YATEC ENGINEERING CORPORATION)
10F 146 Sung Chiang Road, Taipei, Taiwan Phone: 886-2-2563-0010 Fax: 886-2-2567-4677
YASKAWA JASON (HK) COMPANY LIMITED
Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong Phone: 852-2803-2385 Fax: 852-2547-5773
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club, 21 Jianguomanwai Avenue, Beijing 100020, China Phone: 86-10-6532-1850 Fax: 86-10-6532-1851
SHANGHAI OFFICE
27 Hui He Road Shanghai 200437 China Phone: 86-21-6553-6600 Fax: 86-21-6531-4242
SHANGHAI YASKAWA-TONJI M & E CO., LTD.
27 Hui He Road Shanghai 200437 China Phone: 86-21-6533-2828 Fax: 86-21-6553-6677
BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD.
30 Xue Yuan Road, Haidian, Beijing 100083 China Phone: 86-10-6232-9943 Fax: 86-10-6234-5002
SHOUGANG MOTOMAN ROBOT CO., LTD.
7, Yongchang-North Street, Beijing Economic & Technological Development Area, Beijing 100076 China Phone: 86-10-6788-0551 Fax: 86-10-6788-2878
YEA Document Number: TM.AFD.13 9/30/2009 Rev: 09-09
Data subject to change without notice. Yaskawa Electric America, Inc.
YEA, TAICHUNG OFFICE IN TAIWAIN
B1, 6F, No.51, Section 2, Kung-Yi Road, Taichung City, Taiwan, R.O.C. Phone: 886-4-2320-2227 Fax:886-4-2320-2239
Loading...