To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
CIMR-R5U
200 V Class, Three-Phase Input: 3.7 to 37 kW
400 V Class, Three-Phase Input: 3.7 to 75 kW
MANUAL NO. TOEP C710656 01C
This Page Intentionally Blank
Copyright 2008 YASKAWA ELECTRIC CORPORATION. All rights reserved.
All rights reserved. No part of this publication may be reproduced, stored in a retrieva l system, or transmitted, in any form or by any means, mechanical,
electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the
information contained herein. Moreover, because Yaskawa is constantly striving to im prove its high-quality products, the information contained in this manual
is subject to change without notice. Every precaution has been taken in the prepa ration of this manual. Yaskawa assumes no responsibility for errors or
omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication
YASKAWA’s RC5 is a power regenerative unit which has both braking and regenerative functions. This instruction
manual describes installation, maintenance and inspection, troubleshooting, and specifications of the RC5. Read this
instruction manual thoroughly before operation.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual3
i.1 Conditions of Acceptability
i.1Conditions of Acceptability
◆ NEC, CEC and UL Compliance
In order to comply with the NEC, CEC and UL, the following conditions of use must be strictly adhered to:
■Surge Protector Installation
• An MOV must be installed on the input of the RC5 Unit.
■Current Suppression Reactor Installation
• The Current Suppression Reactor must be installed as shown in Figure 3.1.
■Terminal Blocks
• The Power Terminal Blocks of the RC5 unit are for factory wiring use only.
■Installation Environment
• Install the RC5 Unit in a protective enclosure suitable to its environment.
◆ CSA Standards Compliance
The RC5 is CSA certified as following.
■Products
CLASS 3211 06
INDUSTRIAL CONTROL EQUIPMENT
Motor Controllers Miscellaneous
CLASS 2411 02
ELEVATOR EQUIPMENT
Enclosed Elevator and Escalator Electrical Equipment
■Applicable Requirements
CAN/CSA C22.2 No.0.4-04
Bonding of Electrical Equipment
CAN/CSA C22.2 No.14-05
Industrial Control Equipment
CSA B44.1-04/ASME A17.5-2004
Elevator and Escalator Electrical Equipment
Figure i.1
CSA B44.1 /
ASME A17.5
Figure i.1 CSA B44.1-04/ASME A17.5-2004 Mark
4YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
i.2 Safety Information
W ARNING
DANGER
W ARNING
CAUTION
NOTICE
i.2Safety Information
Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the RC5. In this manual, NOTES FOR SAFE
OPERATION are classified as “WARNING” or “CAUTION.”
◆ Supplemental Safety Information
General Precautions
• Some drawings in this manual are shown with the protective cover or shields removed, in order to describe detail with more clarity. Make sure all covers and shields
are replaced before operating this product.
• This manual may be modified when necessary because of improvement of the product, modification, or changes in specifications.
• Such modifications are denoted by a revised manual No.
• To order a copy of this manual, if your copy has been damaged or lost, contact your YASKAWA representative.
• YASKAWA is not responsible for any modification of the product made by the user, since that will void your guarantee.
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according to this manual and local
codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or possibly
even fatal injury or damage to the products or to related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
Indicates a property damage message.
NOTICE: will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
Even items described in a Caution may result in a vital accident in some situations. In either case, follow these important notes.
Note: These are steps to be taken to insure proper operation.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual5
i.3 Notes for Safe Operation
CAUTION
CAUTION
W ARNING
CAUTION
i.3Notes for Safe Operation
◆ Receiving
Do not install or operate any power regenerative unit which is damaged or has missing parts.
Failure to observe this caution may result in personal injury or equipment damage (Refer to page 12)
◆ Installation
Lift the cabinet by the base. When moving the unit, never lift by the front cover or the front panel.
Otherwise, the main unit may be dropped causing damage to the unit. (Refer to page 16)
Mount the power regenerative unit on nonflammable material (i.e. metal).
Failure to observe this caution can result in a fire. (Refer to page 16)
When mounting units in an enclosure, install a fan or other cooling device to keep the intake air temperature below 45°C.
Overheating may cause a fire or damage to the unit. (Refer to page 16)
In order to comply to UL regulations, the MOV and current suppression reactor must be installed on the input of the R5 unit.
Refer to the installation diagram. (Refer to page 16)
◆ Wiring
Only commence wiring after verifying that the power supply is turned OFF.
Failure to observe this warning can result in an electric shock or a fire. (Refer to page 24)
Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in an electric shock or a fire. (Refer to page 24)
Make sure to ground the ground terminal before connecting the other terminals.
Failure to observe this warning can result in an electric shock or a fire. (Refer to page 24)
Install adequate branch short circuit protection according to applicable codes.
Failure to comply could result in damage to the drive.
The device is suitable for circuits capable of delivering up to 100 kA RMS Symmetrical Amperes, 240 Vac maximum (200 V Class), 480 Vac
maximum (400 V Class) or equivalent to the SCCR rating of the VFD to which it is connected - whichever value is less.
R5 Series of Power Regenerative devices shall be connected to a VFD which incorporates Solid State Short Circuit Protection Circuitry and was
found to comply with the High Fault Current Short Circuit Test.
Verify that the power regenerative unit rated voltage coincides with the AC power supply voltage.
Failure to observe this caution can result in personal injury or a fire. (Refer to page 24)
Do not perform a withstand voltage test of the power regenerative unit.
It may cause semi–conductor elements to be damaged. (Refer to page 24)
Connect the power coordinating reactor and the power suppressing reactor as described in this instruction manual.
Improper connection may cause a fire. (Refer to page 24)
Verify that the rated voltage of the power regenerative unit coincides with the rated voltage of the power regenerative unit to be
connected.
Failure to observe this caution can result in a fire. (Refer to page 24)
Tighten terminal screws.
Failure to observe this caution can result in a fire. (Refer to page 24)
6YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
i.3 Notes for Safe Operation
W ARNING
CAUTION
W ARNING
CAUTION
◆ Operation
Only turn ON the input power supply after replacing the front cover or the terminal cover. Do not remove the cover while power is on.
Failure to observe this warning can result in an electric shock. (Refer to page 34)
Never operate the digital operator or other switches when your hand is wet.
Failure to observe this warning can result in an electric shock. (Refer to page 34)
Never touch the terminals while power is on, even if the power regenerative unit stops.
Failure to observe this warning can result in an electric shock. (Refer to page 34)
Never touch the heatsink or input reactors since their temperature may be very high.
Failure to observe this caution can result in harmful burns to the body. (Refer to page 34)
All the parameters of the power regenerative unit have been preset at the factory. Do not change the settings unnecessarily.
The power regenerative unit may be damaged. (Refer to page 34)
◆ Maintenance and Inspection
Never touch high-voltage terminals in the power regenerative unit.
Failure to observe this warning can result in an electric shock. (Refer to page 46)
Perform maintenance or inspection only after verifying that the CHARGE LED goes OFF, after the main circuit power supply is turned
OFF.
The capacitors are still charged and can be dangerous. (Refer to page 46)
Only authorized personnel should be permitted to perform maintenance, inspections or parts replacement.
[Remove all metal objects (watches, bracelets, etc.) before operation.] (Use tools which are insulated against electric shock.)
Failure to observe this warning can result in an electric shock. (Refer to page 46)
Never modify the product.
Failure to observe this warning can result in an electric shock or personal injury and will invalidate the guarantee. (Refer to page 46)
The power regenerative unit employs semi-conductor elements. Do not touch the CMOS elements.
They are easily damaged by static electricity. (Refer to page 46)
Do not connect or disconnect wires or connectors while power is applied to the circuit.
Failure to observe this caution can result in personal injury. (Refer to page 46)
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual7
i.3 Notes for Safe Operation
Model CIMR-R5U23P7
656RC5
WARNING
-Riskofelectricshock.
Read manual before installing.
Wait 5 minutes for capacitor discharge after
disconnecting power supply.
To conform torequirements, make sure to
ground the supply neutral.
AVERTISSEMENT
- Risque de décharge électrique
Lisez le manuel avant installation.
Attendez 5 minutes après la coupure de l’ alimentation
électrique afin que les condensateurs soient complètement décharges.
Assurez vous de connecter a la masse le fil du neutre
afin d’ être en accord avec la règlementation.
◆ Warning Label
A warning label is displayed on the front cover of the power regenerative unit, as shown below. Follow these instructions when handling the power
regenerative unit.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual11
1.1 Section Safety
CAUTION
1.1Section Safety
Do not install or operate any power regenerative unit which is damaged or has missing parts.
Failure to observe this caution may result in personal injury or equipment damage.
12YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
1.2 Inspection Checkpoints
1.2Inspection Checkpoints
◆ Receiving Checkpoints
Table 1.1 Checkpoints
CheckpointsDescription
Does the power regenerative unit model number correspond with the
purchase order?
Are any parts damaged?Visually check the exterior and verify that there was no damage during transport.
Is hardware properly seated and securely tightened?
If any of the above checkpoints are not satisfactory, contact your YASKAWA representative.
◆ Checking the Nameplate Data
■Nameplate Data
Example of standard domestic model CIMR-R5U2011.
Figure1.1
Check the model number on the nameplate on the side of the RC5. (Refer to Figure 1.2.)
Remove the front cover of the power regenerative unit.
Check all visible hardware with appropriate tools.
Figure 1.1 Nameplate Data
■Model Designation
Figure1.2
CIMR - R5 U 2 011 1 A
Power Regenerative
Unit
VS - 656RC5 Series
Symbol
U
A
Symbol
23-phase 200 V class
43-phase 400 V class
■Protective Structure
Specifications
Standard domestic model
Japan standard model
Volta ge
SymbolMax. applicable motor output
3P73.7kW
5P5
to
37
“P” indicates the decimal point.
Figure 1.2 Model Designation
• Open Chassis Type (IEC IP00)
Protected so that parts of the human body cannot reach electrically charged parts from the front when the Power regenerative unit is mounted in a
control panel.
• Enclosed Wall-mounted Type (IEC IP20, NEMA 1)
The power regenerative unit is structured so that the power regenerative unit is shielded from the exterior, and can thus be mounted to the interior
wall of a standard building (not necessarily enclosed in a control panel). The protective structure conforms to the standards of NEMA 1 in the
USA.
Version (Enter the specifications
form number when special specifications are required.)
No.
0Open chassis (IEC IP00)
1
5.5kW
37kW
Protective Structure
Enclosed wall-mounted
(IEC IP20, NEMA1)
to
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual13
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual15
2.1 Section Safety
CAUTION
2.1Section Safety
Lift the cabinet by the base. When moving the unit, never lift by the front cover or the front panel.
Otherwise, the main unit may be dropped causing damage to the unit.
Mount the power regenerative unit on nonflammable material (i.e. metal).
Failure to observe this caution can result in a fire.
When mounting units in an enclosure, install a fan or other cooling device to keep the intake air temperature below 45°C.
Overheating may cause a fire or damage to the unit.
16YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
2.2 Checking Installation Site
2.2Checking Installation Site
◆ Installation Site
Install the power regenerative unit under the following conditions.
NOTICE: Do not install the power regenerative unit to an area greater than pollution degree 2 (UL standard).
Typ eAmbient Operating TemperatureHumidity
Enclosed wall-mounted–10 to +40°C90% RH or less (no condensation)
Open chassis–10 to +45°C90% RH or less (no condensation)
Protection covers are attached to the top and bottom of the power regenerative unit. Be sure to remove the protection covers before installing a 200
or 400 V Class power regenerative unit with an output of 30 kW or less in a panel.
To ensure proper performance and long operating life, follow the recommendations below when choosing a location for installing the RC5. Make
sure the power regenerative unit is protected from the following conditions:
• Extreme cold and heat.
Use only within ambient temperature range: -10°C to +40°C
• Dust or metallic particles in the air. (For enclosed wall-mounted type)
• Physical shock, vibration.
• Magnetic noise. (Example: welding machines, power devices, etc.)
• High humidity.
• Radioactive materials.
• Combustibles: thinners, solvents, etc.
◆ Controlling the Ambient Temperature
To enhance the reliability of operation, the power regenerative unit should be installed in an environment free from extreme temperature increases. If
the power regenerative unit is installed in an enclosed environment, such as a box, use a cooling fan or air conditioner to maintain the internal air
temperature below 45°C.
◆ Protecting the Power Regenerative Unit from Foreign Matter
Place a cover over the power regenerative unit during installation to shield it from metal power produced by drilling.
Always remove the cover from the power regenerative unit after completing installation. Otherwise, ventilation will be reduced, causing the power
regenerative unit to overheat.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual17
2.3 Clearances
50 mm or more (1.97 in)
30 mm or more (1.18 in)
*
30 mm or more
(1.18 in)
50 mm or more (1.97 in)
*
120mmormore
(4.72 in)
120mmormore
(4.72 in)
Air
Air
(b) Side View
(a) Front View
2.3Clearances
Install the RC5 vertically and allow sufficient clearances for effective cooling as shown in Figure 2.1.
Figure 2.1
Note: 1. The clearances required at top/bottom and both sides are common in open chassis type (IP00) and enclosed wall–mounted type (NEMA 1).
Figure 2.1 Clearances
2. Remove the top and bottom covers to use the open chassis type of 200 V/400 V 30 kW or less.
3. When installing the models of 200 V/400 V 37 kW or more equipped with eyebolts, extra spacing will be required on either side. For detailed dimensions, contact your
YASKAWA representative.
4. Ensure sufficient space for the sections at the upper and lower parts marked with * in order to permit the flow of intake/exhaust air to / from the unit.
18YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
2.4 Dimensions
W1
W
-
H2
4
d
H1
H
D
2.4Dimensions
◆ Models of 200 V/400 V 30 kW and Lower
Figure 2.2 shows a 200 V 3.7 kW model. Use open chassis type 200 V/400 V 30 kW and lower with the top and bottom covers removed.
Figure2.2
◆ Models of 200 V/400 V 37 kW and Higher
Figure 2.3 shows a 200 V 37 kW model.
Figure2.3
W1
W
Figure 2.2 Dimensions of RC5
STATUS
RUN
READY
:LIGHT:BLINK
:LIGHTOFF
RUN
ALARM
EF
OLOH
OVUV
OCCPF
H1
H
H2
4-d
Figure 2.3
D
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual19
2.4 Dimensions
Vol tag eRC5 CIMR–R5U
23P7
25P5
27P5
2011
200V Class
400V Class
400V Class
20156
2018
2022
2030
2037
43P7
45P5
47P5
4011
4015
4018
4030
4037
4045
4055
4075
Table 2.1 RC5 Dimensions mm (in) and Approx. Mass (kg)
Dimensions
mm (in)
Mounting Dimension mm (in)
WHDW1H1H2
140
(5.51
200
(7.87)
250
(9.84)
325
(12.80)
140
(5.51
200
(7.87)
250
(9.84)
325
(12.80)
280
(11.02)
300
(11.81)
380
(14.96)
400
(15.75
450
(17.72)
280
(11.02)
300
(11.81)
380
(14.96)
450
(17.72)
635
25.0)
180
(7.09)
205
(8.07)
225
(8.86)
285
(11.22)
180
(7.09)
205
(8.07)
225
(8.86)
285
(11.22)
285
(11.22)
285
(11.22)
285
(11.22)
126
(4.96)
186
(7.32)
236
(9.29)
275
(10.83)
126
(4.96)
186
(7.32)
236
(9.29)
275
(10.83)
275
(10.83)
275
(10.83)
275
(10.83)
266
(10.47)
285
(11.22)
365
(14.37)
435
(17.13)
266
(10.47)
285
(11.22)
365
(14.37)
435
(17.13)
610
(24.02)
7.0
(0.28)
8.0
(0.32)
7.5
(0.30)
27.5
(1.08)
7.5
(0.30)
7.0
(0.28)
8.0
(0.32)
7.5
(0.30)
7.5
(0.30)
Approx. Mass
(kg)
Mounting Hole
d
4.5M5
5.5
10
M6
11
23IP00
3.5
4
M5
6
M6
10.54022
25
26
M6IP00
34
36
Enclosure Type
IP20
IP20
Note: RC5 is offered in the following enclosure types:
To remove the front cover, first move the LCD monitor/digital operator in the direction shown by arrow 1. Then squeeze the cover in the direction
shown by arrows 2 on both sides and lift in the direction shown by arrow 3.
Figure2.4
1
Front Cover
2
3
2
Figure 2.4 Removing and Replacing the Front Cover
Note: Do not replace the front cover with the LCD monitor/digital operator connected. The LCD monitor/digital operator will not be connected to the power regenerative unit.
Replace the front cover first and then install the LCD monitor/digital operator on the cover. Refer to Removing and Replacing the LCD Monitor/Digital Operator on
page 22 for replacing the LCD monitor/digital operator.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual21
2.6 Removing and Replacing the LCD Monitor/Digital Operator
LCD Monitor/
Digital Operator
1
2
Front Cover
LCD Monitor/
Digital Operator
Front Cover
2
1
Claws A
Claws B
2.6Removing and Replacing the LCD Monitor/Digital Operator
Remove and replace the LCD monitor/digital operator as follows.
◆ Removing the LCD Monitor/Digital Operator
Push the LCD monitor/digital operator lever in the direction shown by arrow 1 and lift the LCD monitor/digital operator in the direction shown by
arrow 2 to remove the LCD monitor/digital operator from the front cover.
Figure 2.5
◆ Replacing the LCD Monitor/Digital Operator
Engage the LCD monitor/digital operator on claws A in the direction shown by arrow 1 and then on claws B in the direction shown by arrow 2 to
lock the LCD monitor/digital operator.
Figure 2.6
Note: Never fit the LCD monitor/digital operator in any other direction or by any other method. The LCD monitor/digital operator will not be connected to the inverter.
Figure 2.5 Removing the LCD Monitor/Digital Operator
Figure 2.6 Replacing the LCD Monitor/Digital Operator
22YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual23
3.1 Section Safety
W ARNING
CAUTION
3.1Section Safety
Only commence wiring after verifying that the power supply is turned OFF.
Failure to observe this warning can result in an electric shock or a fire.
Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in an electric shock or a fire.
Make sure to ground the ground terminal before connecting the other terminals.
Failure to observe this warning can result in an electric shock or a fire.
Install adequate branch short circuit protection according to applicable codes.
Failure to comply could result in damage to the drive.
The device is suitable for circuits capable of delivering up to 100 kA RMS Symmetrical Amperes, 240 Vac maximum (200 V Class), 480 Vac
maximum (400 V Class) or equivalent to the SCCR rating of the VFD to which it is connected - whichever value is less.
R5 Series of Power Regenerative devices shall be connected to a VFD which incorporates Solid State Short Circuit Protection Circuitry and was
found to comply with the High Fault Current Short Circuit Test.
Verify that the power regenerative unit rated voltage coincides with the AC power supply voltage.
Failure to observe this caution can result in personal injury or a fire.
Do not perform a withstand voltage test of the power regenerative unit.
It may cause semi-conductor elements to be damaged.
Connect the power coordinating reactor and the power suppressing reactor as described in this instruction manual.
Improper connection may cause a fire.
Verify that the rated voltage of the power regenerative unit coincides with the rated voltage of the power regenerative unit to be
connected.
Failure to observe this caution can result in a fire.
Tighten terminal screws.
Failure to observe this caution can result in a fire.
24YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
3.2 Connection Diagram
3.2Connection Diagram
◆ Connection Diagram with Drive
Figure 3.1 shows a diagram of a typical connection of the RC5 with the Yaskawa AC Drive.
Note: The RC5 is compatible with other Yaskawa drive (inverter) products. Refer to the application technical manual for the equivalent connection diagram.
Figure3.1
MCCB MC
<4>
Power Coordination Reactor
<4>
Current
Suppression
<4>
Reactor
FU
MOV
MANUAL RUN
AUTO RUN
EXFLT
RESET
<6>
VS-656RC5
R/L1
<2>
S/L2
T/L3
11
r1/
<3>
21
1/
31
t1/
CONV
READY
Running
S1
S2
S3
<5>
S4
SS
SP
+24V
SC
Sequence
Common
E
Shield Sheath
Connection Terminal
Analog Output
-10 to +10V
M1
M2
M3
M4
MA
MB
MC
AM
AC
<9>
<8>
Yaskawa AC Drive
R/L1
S/L2
T/L3
r/
/
<2>
1
<3>
2
<1>
1
U/T1
V/T2
W/T3
IM
Figure 3.1 Connection Diagram (When connecting a RC5 and a Yaskawa AC Drive)
<1> Connect to the terminal (+)1 for 200 V class 0.4 to 22 kW, and 400 V class 0.4 to 45 kW Yaskawa AC drive. Use terminal (+)3 for 200 V class
30 to 37 kW, and 400 V class 55 to 75 kW VS-616G5 drivers or another Yaskawa drive (inverter) product.
<2> Connect the Yaskawa AC Drive power supply terminals R/L1, S/L2, and T/L3 to the secondary side of the power coordinating reactor. Connect
the RC5 AC power supply terminals R/L1, S/L2, and T/L3 to the secondary side of the power suppressing reactor.
<3> Connect terminals r/l 1, s/l 2 of VS-616G5, and terminals r1/l 11, s 1/l 21, and t1/l 31 of the RC5 to the primary side of the power coordinating
reactor.
<4> Make sure to use the specified reactor, fuse and fuse holder.
<5> The sequence input terminal of RC5 is the same as terminal S1.
<6> The wiring distance between the power coordinating reactor, and RC5 and a Yaskawa AC Drive should be 10 m or less.
<7> DC bus wiring [(+) 1 - (+), ] between the Drive and the power regenerative unit should be 5 m or less.
<8> Remove the wiring of terminals r/l 1 and s/l 2 since they were connected at the factory.
<9> If installing a circuit breaker or a magnetic contactor on the RC5 output (DC) side to shut down the power supply in an emergency, observe the
following precautions.
• Be sure to confirm that the charge lamps on the RC5 and the Inverter are not lit, and then turn on the circuit breaker or contactor. If the circuit
breaker or contactor is turned on while power is supplied to the RC5 and the Inverter, an overcurrent may occur and damage the circuit breaker or
contactor.
• Be sure to confirm that the circuit breaker or contactor is turned on before the power is turned on for the RC5.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual25
3.3 Selecting Peripheral Devices
3.3Selecting Peripheral Devices
Selecting Heavy Duty or Standard Duty RC5 Application
The RC5 overload rating has the capability of 150% braking torque for 30 seconds and 200% peak braking torque. The overload capability is based
on the standard duty rating. The RC5 overload rating can be applied to heavy duty applications. The following is a description of the heavy duty and
standard duty ratings.
■Heavy Duty
Heavy duty applications require continuous energy dissipation (100% braking torque).
The overload rating is 125% for 60 seconds with a duty cycle of 25%. Braking torque of 187.5% is available for 30 seconds. Please note the peak
torque should be less than 250%.
The RC5 requires selecting Power Coordination and Current Suppression reactors according to specifications in Table 3.3.
■Standard Duty
Standard duty applications require intermittent full energy dissipation. The continuous rating is 80% or less braking torque and 100% braking torque
for 60 seconds with a duty cycle of 25% (60 seconds maximum on-time of every 240 seconds). The overload rating is 150% braking torque for 30
seconds. Please note the peak torque should be less than 200%.
The RC5 requires selecting Power Coordination and Current Suppression reactors according to specifications in Table 3.3
◆ Main Circuit Input Fuse
■Fuse Kits
The Fuse Kit is sized for both Heavy Duty and Standard Duty applications.
Connect a fuse at the primary side of the power suppression reactor. Recommended fuses are shown in Table 3.1 and Ta bl e 3. 2.
Table 3.1 200 V Class Input Fuse
RC5Input fuseFuse holder
Rated
Model
CIMR-R5U
23P71A2.210UFU000151A30QS20-13UFU000157703181
25P51A3.715UFU000152A30QS30-13UFU000157703181
27P51A5.520UFU000152A30QS30-13UFU000157703181
20111A7.530UFU000153A30QS50-43FU-002082P243G3
20151A1140UFU000154A30QS80-43FU-002083P2433
20181A1550UFU000154A30QS80-43FU-002083P2433
20221A1860UFU000155A30QS100-43FU-002083P2433
20301A2280UFU000156A30QS150-43FU-002083P2433
20370A30100UFU000156A30QS150-43FU-002083P2433
Note: These fuses and fuse holders are made by FERRAZ.
regenerative
capacity (kW)
25%ED
Rated input
current
(Aac)
25%ED
Yaskawa
Part Number
Ferraz
Part Number
Amount
per unit
Yaskawa
Part Number
Ferraz
Part Number
Amount
per unit
26YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
3.3 Selecting Peripheral Devices
Table 3.2 400 V Class Input Fuse
RC5Input fuseFuse holder
Model
CIMR-R5U
43P71A2.25FU-002029A60Q10-23FU-002055303231
45P51A3.77.5FU-002030A60Q15-23FU-002055303231
47P51A5.510FU-002030A60Q15-23FU-002055303231
40111A7.515FU-002032A60Q30-23FU-002055303231
40151A1120FU-002032A60Q30-23FU-002055303231
40181A1525FU-000783A50P50-43FU-002082P243G3
40221A1830FU-000783A50P50-43FU-002082P243G3
40301A2240FU-000806A50P80-43FU-002084P243E3
40370A3050FU-000806A50P80-43FU-002084P243E3
40450A3760FU-000807A50P100-43FU-002084P243E3
40550A4575FU-000809A50P150-43FU-002084P243E3
40750A55100FU-000809A50P150-43FU-002084P243E3
Note: These fuses and fuse holders are made by FERRAZ.
Rated
regenerative
capacity (kW)
25%ED
Rated input
current
(Aac)
25%ED
Yaskawa
Part Number
Ferraz
Part Number
Amount
per unit
Yaskawa
Part Number
Ferraz
Part Number
Amount
per unit
◆ Power Coordination and Current Suppression Reactors
Both Power Coordination and Current Suppression Reactors are 3-phase input reactors that correspond to each RC5 model and are necessary when
operating the RC5. Use a single Power Coordination and a single Current Suppression reactor for each RC5 application.
■Recommended RC5 Power Cooridination and Suppression Reactor Specifications
Table 3.3 shows Yaskawa recommended specifications for Power Coordination and Current Suppression reactors for each RC5 model.
Table 3.3 Recommended RC5 Power Cooridination and Suppression Reactor Specifications
RC5Power Coordination ReactorCurrent Suppression
Model CIMR-R5URated Current (Arms)Inductance (mH)Rated Current (Arms)Inductance (mH)
23P71A200.53150.31
25P51A300.35150.31
27P51A400.265200.15
20111A600.18400.1
200 V Class
400 V Class
20151A800.13400.1
20181A900.12500.06
20221A1200.09600.05
20301A1600.07800.04
20370A2000.051000.03
43P71A102.27.51.2
45P51A151.427.51.2
47P51A201.06100.6
40111A300.7150.4
40151A400.53250.3
40181A500.42250.3
40221A600.36300.2
40301A800.26400.15
40370A900.24500.12
40450A1200.18600.1
40550A1500.15750.08
40750A2000.111000.06
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual27
3.3 Selecting Peripheral Devices
0.6 mm max
3.5 mm max
Screwdriver Blade Width
7mm
OK
OK
NO!
◆ Wiring Precautions
The external interconnection wiring must be performed with following procedures. After completing RC5 interconnections, be sure to check that the
connections are correct. Never use control circuit buzzer check.
■Precautions on Control Circuit Wiring
• Separate control circuit wires from main circuit wires and other power cables to prevent erroneous operation caused by noise interference.
• Separate the wiring of control circuit terminals from other control terminals or main circuit wirings.
• Wiring distance should be less than 50 m.
• Insert the wire into the lower part of the terminal block and connect it tightly with a screwdriver. Wire sheath strip length must be 7 mm.
Figure 3.2
Figure 3.2 Control Circuit Terminal Wiring
• Use twisted shielded or twisted-pair shielded wire for the control circuit line and connect the shielded sheath to inverter terminal E. (See
Figure 3.3)
Figure 3.3
Shielded Sheath
Armor
Never connect.
To power regenerative unit
shielded sheath terminal E
Figure 3.3 Shielded Wire Termination
Insulate these parts
with insulating tape.
■Ground Wiring
• Do not share the ground wire with other devices, such as welding machines or power tools. Separate the grounding cables from the wirings for
power tools.
• Always use a ground wire that complies with technical standards on electrical equipment and minimize the length of the ground wire.
Leakage current flows through the power regenerative unit. Therefore, if the distance between the ground electrode and the ground terminal is too
long, potential on the ground terminal of the power regenerative unit will become unstable.
• When using more than one power regenerative unit, be careful not to loop the ground wire.
Select wires to be used for wiring from Table 3.4 and Table 3.5.
Table 3.4 200 V Class Wire Size
3.4 Wiring Main Circuit Terminals
Circuit
Main
ControlCommon to all models
<1> Wire size is determined by 75°C temperature-rated copper wire.
Note: Cable size is selected assuming external wiring of single 3-core cables at an ambient temperature of 30°C.
Note: For model number 2015, use closed-loop connectors that are recommended by JST (JST 14-5).
<1> Wire size is determined by 75°C temperature-rated copper wire.
Note: Cable size is selected assuming external wiring of single 3-core cables at an ambient temperature of 30°C
Note: For model number 4011 and 4015, use closed-loop connectors that are recommended by JST (JST 3.5 - R5).
3.5 to 5.512 to 10
M5
2 to 5.514 to 10
5.510
M5
5.510
M688
M688
M688
M688
M688
M6146
M6146
twisted wire
—
0.5 to 1.25
single
0.5 to 1.25
twisted wire
20 to 16
single
20 to 16
Power cable:
600 V vinyl
sheathed wire or
equivalent
Note: Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line voltage drop is calculated as follows:
(If there is a possibility of excessive voltage drop, use a larger wire suitable to the required length.)
Line voltage drop (V) = 3 x wire resistance (Ω/km) x wire length (m) x current (A) x 10
-3
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual31
3.5 External Terminals
3.5External Terminals
◆ Main Circuit Terminal Functions
Terminal SymbolDescription
R/L1
S/L2
T/L3
(+),
r1/ 11 1/ 21
t1/ 31
◆ Control Circuit Terminal Functions
Typ e No. <1>
Sequence Input
Photocoupler Output
Relay Output
Analog Output
<1> Indicates the terminal number of the control card.
Power Regenerative Unit
Main Circuit Input
Power Supply Voltage
Detection
Power Input for FAN and MC Supplies power for the cooling fan and inrush prevention MC of the power regenerative unit.
S1MANUAL RUNRun when CLOSED, stops when OPEN
S2AUTO RUNAuto run (regenerative operation) when CLOSED
S3EXTERNAL FAULT INPUT
S4FAULT RESET INPUT
SCSequence Common
SSPhotocoupler internal common
SPSequence +24 V Power Supply
M1 - M2CONV READY
M3 - M4RUNCLOSE during run
MA - MC
MB - MC
AMInput Current
ACAnalog Ground
Table 3.7 Main Circuit Terminal Functions
Main circuit AC power supply terminal for the power regenerative unit.
Connect to the Drive’s DC power supply voltage input terminals.
• Two terminals are provided for both (+) and .
Detects the phase sequence and the voltage level.
• Connect to the power side of the power coordinating reactor.
Table 3.8 Control Circuit Terminal Functions
Signal InputFunctionFunctionSignal Level
External fault when
FAULT Output
CLOSED
Fault reset when
CLOSED
Closed when power
regenerative unit is
READY
Outputs when a fault is
detected.
Terminal MA-MC:
Closed during fault
detection
Ter m inal M B-M C :
Open during fault
detection
5 V: 100% of rated input
current
Multi-function Contact
Inputs (H1-01 to H1-02)
H2-01 to H2-0248 VDC 80 mA or less
Outputs when a fault is
detected.
Terminal MA-MC:
Closed during fault
detection
Ter m inal M B-M C :
Open during fault
detection
Multi-function Analog
Output (H1-04)
24 VDC 8 mA Photocoupler
isolation
250 VAC 1 A or less
30 VDC 1 A or less
- 10 V to + 10 VDC 2 mA or
less
32YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual33
4.1 Section Safety
W ARNING
CAUTION
4.1Section Safety
Only turn ON the input power supply after replacing the front cover or the terminal cover. Do not remove the cover while power is on.
Failure to observe this warning can result in an electric shock.
Never operate the digital operator or other switches when your hand is wet.
Failure to observe this warning can result in an electric shock.
Never touch the terminals while current is flowing, even if the power regenerative unit stops.
Failure to observe this warning can result in an electric shock.
Never touch the heatsink or input reactors since their temperature may be very high.
Failure to observe this caution can result in harmful burns to the body.
All the constants of the power regenerative unit have been preset at the factory. Do not change the settings unnecessarily.
The power regenerative unit may be damaged.
34YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
4.2 Checks Prior to Main Power Application
4.2Checks Prior to Main Power Application
Check the following before turning ON the power supply.
• Check that the power supply is of the correct voltage.
200 V class: 200 to 230 VAC, 50/60 Hz
400 V class: 380 to 460 VAC, 50/60 Hz
• Make sure that the power regenerative unit and the Drive are connected correctly.
• Make sure that the phase sequence of the main circuit terminals (R/L1, S/L2, T/L3) and the power supply voltage detection terminals (r1/ 11, 1/
21, t1/ 31) are correct.
• Make sure that the power regenerative unit and the control device are wired correctly.
• Set the run command of the power regenerative unit and the drive to OFF.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual35
4.3 Setting the Power Supply Voltage Jumper
400/415V
21CN
380V440V 460V
23CN 24CN 25CN 26CN 22CN FU2
20CN
TB2
r
Jumper
4.3Setting the Power Supply Voltage Jumper
Note: 400 V CLASS REGENERATIVE UNITS OF 37 kW OR HIGHER
Set the power supply voltage jumper for 400 V class power regenerative unit of 37 kW or higher. Insert the jumper into the voltage connector nearest
to the actual power supply voltage.
Incorrect connector setting may negatively impact the performance of the power regenerative unit.
The jumper is factory-set to 460 V when shipped. If the power supply voltage is not 460 V, use the following procedure to change the setting.
1. Turn OFF the power supply switch and wait for at least five minutes before removing the front panel and setting the jumper.
2. Remove the front cover.
3. Insert the jumper at the position for the voltage supplied to the power regenerative unit (see Figure 4.1).
4. Replace the front cover.
Figure 4.1
Figure 4.1 Setting the Power Supply Voltage (For 400 V Class Power Regenerative Unit between 37 kW and 75 kW)
36YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
4.4 Using the Digital Operator
LOCAL
REMOTE
MENU
DIGITAL OPERATOR
JVOP-130
ESC
DATA
ENTER
JOG
FWD
REV
RESET
RUNSTOP
DRIVE FWD REVREMOTE
SEQREF
Dc Bus Voltage
U1-02 =300 VDC
Keys
Execute operations such as setting
user parameters and monitoring.
Data Display
Two-line LCD that displays data for monitoring, parameters, and set values with 16
characters per line.
Operation Mode Indicators
DRIVE: Lit when in operation mode.
FWD:Not used
REV:Not used
SEQ:Lit when the run command from the
control circuit terminal is enabled.
REF:Not used
4.4Using the Digital Operator
This section describes the component names and functions of the Digital Operator. The component names and functions are shown in Figure 4.2 and
Key function are described in Table 4.1.
Figure4.2
Figure 4.2 Digital Operator Component Names and Functions
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual37
4.4 Using the Digital Operator
LOCAL
REMOTE
MENU
ESC
JOG
FWD
REV
RESET
DATA
ENTER
RUN
STOP
KeyNameFunction
LOCAL/REMOTE Key
MENU KeyDisplays menus.
ESC KeyReturns to the status before the DATA/ENTER Key was pressed.
JOG KeyNot used.
FWD/REV KeyNot used.
Table 4.1 Key Function
Switches between operation (LOCAL) via the Digital Operator and control circuit terminal (REMOTE)
operation.
This key can be enabled or disabled by setting o2-01.
RESET Key
Set the number of digits for parameter settings.
Also acts as the reset Key when a fault has occurred.
Increment KeySelects menu items, groups, functions, and parameter names, and increments set values.
Decrement KeySelects menu items, groups, functions, and parameter names, and decrements set values.
DATA/ENTER KeyEnters menu items, functions, parameters, and set values after they are set.
RUN KeyStarts the RC5 operation when the RC5 in operation with the Digital Operator.
STOP Key
Stops RC5 operation.
This Key can be enabled or disabled by setting o2-02 when operating from the control circuit terminal.
Note: Except diagrams, keys are referred to using the key names listed in the above table.
This section describes the RC5’s monitor modes, switching between modes, and accessing/setting user parameters.
◆ Modes
The RC5’s user parameters and monitoring functions have been organized in groups called modes that make it easier to read and set user parameters.
The RC5 is equipped with 4 modes, as shown in Ta bl e 4 .2 .
Table 4.2 Modes
ModePrimary function(s)
Operation mode
Initialize mode
Programming mode
Modified constants modeUse this mode to read/set user parameters that have been changed from their factory set values.
The power regenerative unit can be run in this mode.
Use this mode when monitoring values such as frequency references or output current, displaying fault information, or
displaying the fault history.
Use this mode when selecting the language displayed on the Digital Operator, selecting the access level for reading/
setting user parameters, selecting the control mode, or initializing the user parameters.
Factory setting: English (A1-00=0)
Use this mode when reading/setting the user constants required for operation.
The program mode functions are subdivided into the following groups:
• Application: Operation mode selection
• Tuning: No Auto-Tuning
• Option: No Option Card support
• Terminal: Settings for sequential I/O and analog I/O
• Protection: Settings for the motor and power regenerative unit protection function
• Operator: Selects the Digital Operator’s display and Key function
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual39
4.5 Digital Operator Modes
All modes / parameter
status
** Main Menu **
Operation
** Main Menu **
Initialize
** Main Menu **
Programming
** Main Menu **
Modified Parameters
Power ON
Dc Bus Voltage
U1-02=300VDC
Select Language
English
Group b
Application
None Modified
MENU
ESC
DATA
ENTER
ESC
DATA
ENTER
ESC
DATA
ENTER
ESC
DATA
ENTER
A1-00 = 0***
English
Function b1
Sequence
ESC
DATA
ENTER
ESC
DATA
ENTER
Operation mode
Initialize mode
Programming mode
Modified parameter mode
(Mode Display)
Monitor (DC bus voltage)
Operator display language selection
Operation mode selection
Displays parameterss changed from
factory settings
Function
(Parameter Reading)
Parameter Display
(Parameter Setting)
◆ Navigating Digital Operator Modes
Once the power regenerative unit has been put into operation mode by pressing the Menu Key, the Increment and Decrement Keys can be pressed to
switch to other modes. Press the DATA/ENTER Key to read/set the user parameters in each mode.
Press the ESC Key to return to the mode display from the user parameter display.
Press the DATA/ENTER Key twice to write a parameter and then press the ESC Key to return to the mode display. This is the most Basic operation,
so you should remember it.
Figure 4.3
Note: When running the power regenerative unit after using the digital operator, press the MENU Key to enter the operation mode and then press the DATA/ENTER Key from
the operation mode display to bring up the monitor display. Run commands can’t be received from any other display. (Monitor display in the operation mode appears
when the power is turned ON.)
The group level will be displayed when the DATA/ENTER Key is pressed at the programming mode display.
StepKey SequenceDigital Operator DisplayRemarks
1
MENU
** Main Menu **
Operation
4.5 Digital Operator Modes
2
** Main Menu **
Programming
Press twice.
3
4
5
6
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
7
Group b
Application
Function b1
Sequence
Run Source
Terminals
b1-02 = 1***
Terminals
b1-02 = 0
Operator
Changed to parameter reading
(function) level.
Press twice.
8
DATA
ENTER
Entry Accepted
Run Source
Operator
9
ESC
Function b1
Sequence
Writes-in the new setting.
After a few seconds, the operator
display is as shown on the left.
The parameter setting has been completed (operation mode has changed from the external terminals to the operator).
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual41
4.5 Digital Operator Modes
All modes /parameters
status
** Main Menu **
Operation
Output Current
U1-05 = 0.0 A
Ac Frequency
U1-08 = 60.00 Hz
Function U2
Fault Trace
Power ON
(When o1-02=2 )
DC Bus Voltage
U1-02 = 300 VDC
Current Fault
None
MENU
ESC
DATA
ENTER
ESC
DATA
ENTER
Operation Mode
Output current on power side
Power supply frequency
(can be changed at parameter o1-01)
Function selection U2 (fault trace)
DC Bus Voltage display
Contents of fault trace
Function U3
Fault History
Function U1
Monitor
Last Fault
None
DC Bus Voltage
U1-02= 300VDC
ESC
DATA
ENTER
ESC
DATA
ENTER
Function selection U3 (fault history)
Function selection U1 (Monitor)
Contents of fault history
Various monitors
Power ON
(When o1-02=3)
Power ON
(When o1-02=4)
◆ Operation Mode
Operation mode is the mode in which the power regenerative unit can be operated.
Many user parameters can’t be changed when the power regenerative unit is operating.
Viewing monitor displays, fault information and fault history are possible in operation mode.
Note: When running the power regenerative unit after using digital operator, press the MENU Key to enter the operation mode and then press the DATA/ENTER Key from the
operation mode display to bring up the monitor display. Run commands can’t be received from any other display. (Monitor display in the operation mode appears when
the power is turned ON.)
■Operations in Operation Mode
Key operations in operation mode are shown in Figure 4.4.
Refer to Figure 4.5 when building a power ON/OFF sequence for the RC5.
Figure4.5
4.6 Power On/Off Sequence
FFONO
AC Power Supply
Power Regenerative Unit
READY
Drive
READY
Drive
Run Command
Drive
Output during Run
Power Regenerative Unit
Run Command
Power Regenerative Unit
Output during Run
Drive
Output Frequency
OFF
OFF
STOP
STOP
STOP
STOP
Figure 4.5 Power Supply ON/OFF Sequence
ON
ON
RUN
RUN
RUN
RUN
1sec
DC Injection Braking
Check the following when using the power regenerative unit.
• Run commands of the drive and the power regenerative unit should be turned ON after confirming that the drive and the power regenerative unit
are READY.
• Run commands of the drive and the power regenerative unit should be turned ON at the same time.
• Never turn the run command of the power regenerative unit OFF while the drive output during run is ON.
• Run output of the power regenerative unit turns OFF one second after the run command is turned OFF.
• Turn the power OFF after the run output of the power regenerative unit is OFF.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual43
4.7 Run Command Selection
AUTO RUN
ON
Drive Status
Auto Run
Regeneration
DC Bus Voltage
Regenerative Unit
Run Status
Current at Power Side
RUN
AC Power Supply Voltage x 1.35
Operation Start Level
Operation Stop Level
STOP
C8-20: default setting 1 sec
MANUAL RUN
Drive Status
Regenerative Unit
Run Status
Current at Power Side
DC Bus Voltage
ON
RUN
Regeneration
Auto Run
AC Power Supply Voltage x 1.35
C8-20: default setting 1 sec
4.7Run Command Selection
This section explains the two run command modes of the power regenerative unit. Select the mode according to the application.
◆ Auto Run
Auto run is the mode in which the power regenerative unit detects any increase/decrease of the bus voltage and performs an auto run/stop if the
terminal S2-SC is “closed.”
When the DC voltage is less than the voltage set at the auto run/stop level, the RC5 will stop after the preset time value in parameter C8-20 is passed
(default: 1 sec).
Figure 4.6
Figure 4.6 Time chart of the Auto Run Mode
◆ Manual Run
Manual run is the mode in which the RC5 starts running when the terminal S1-SC is “closed,” and stops one second after S1-SC is “open.”
Figure 4.7
Figure 4.7 Time chart of the Manual Run mode
Build a sequence so that the run commands of the power regenerative unit and the inverter are turned ON at the same time.
44YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual45
5.1 Section Safety
W ARNING
CAUTION
5.1Section Safety
Never touch high-voltage terminals in the power regenerative unit.
Failure to observe this warning can result in an electric shock.
Perform maintenance or inspection only after verifying that the CHARGE LED goes OFF, after the main circuit power supply is turned
OFF.
The capacitors are still charged and can be dangerous.
Only authorized personnel should be permitted to perform maintenance, inspections or parts replacement.
[Remove all metal objects (watches, bracelets, etc.) before operation.] (Use tools which are insulated against electric shock.) Failure to observe
this warning can result in an electric shock.
Never modify the product.
Failure to observe this warning can result in an electric shock or personal injury and will invalidate the guarantee.
The power regenerative unit employs semi-conductor elements. Do not touch the CMOS elements.
They are easily damaged by static electricity.
Do not connect or disconnect wires or connectors while power is applied to the circuit.
Failure to observe this caution can result in personal injury.
46YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
5.2 Periodic Inspection and Maintenance
5.2Periodic Inspection and Maintenance
The maintenance period of the power regenerative unit is as follows.
Maintenance period: Within 18 months of shipping from the factory or within 12 months of being delivered to the final user, whichever comes first.
◆ Daily Inspection
Check the following items with the system in operation.
• There should be no abnormal heat generation.
• The ambient temperature should not be too high.
• The cooling fan on the power regenerative unit should be operating normally.
◆ Periodic Inspection
Check the following items during periodic maintenance.
Always turn OFF the power supply before beginning inspection. Confirm that the LED indicators on the front cover have all turned OFF, and then
wait at least five minutes have elapsed before beginning the inspection. Be sure not to touch terminals right after the power has been turned OFF.
Doing so can result in an electric shock.
Table 5.1 Periodic Inspections
ItemInspectionCorrective Procedure
External terminals, mounting
bolts, connectors, etc.
HeatsinkAre the fins dirty?
PCBsIs there any conductive dirt or oil mist on the PCBs?
Cooling fan
Power elementsIs there any conductive dirt or oil mist on the elements?
Smoothing capacitorAre there any irregularities, such as discoloration or odor? Replace the capacitor or power regenerative unit.
Are all screws and bolts tight?Tighten loose screws and bolts firmly.
Are connectors tight?Reconnect the loose connectors.
Is there any abnormal noise or vibration or has the total
operating time exceeded 20,000 hours? <1>
Clean off any dirt and dust with an air gun using dry air at a
pressure of 39.2x10
Clean off any dirt and dust with an air gun using dry air at a
pressure of 39.2x104 to 58.8x104 Pa (4 to 6 kg•cm2).
Replace the boards if they cannot be made clean.
Replace the cooling fan.
Clean off any dirt and dust with an air gun using dry air at a
pressure of 39.2x10
4
to 58.8x104 Pa (4 to 6 kg•cm2).
4
to 58.8x104 Pa (4 to 6 kg•cm2).
<1> Unit power must be ON to perform this check.
◆ Periodic Maintenance of Parts
The power regenerative unit is configured of many parts, and these parts must be operating properly in order to make full use of its functionality.
Among the electronic components, there are some that require maintenance depending on their usage conditions. In order to keep the power
regenerative unit operating normally over a long period of time, it is necessary to perform period inspections and replace parts according to their
service life.
When replacing parts, be careful not to drop any, such as screws, inside the RC5. Failure to observe this caution may result in a short-circuit and a
fire.
Periodic inspection standards vary depending the installation environment and usage conditions of the power regenerative unit. The power
regenerative unit’s maintenance periods are noted below. Keep them as reference.
Table 5.2 Part Replacement Guidelines
PartStandard Replacement PeriodReplacement Method
Smoothing capacitor5 yearsReplace with new part. (Determine need by inspection.)
Breaker relays—Determine need by inspection.
Fuses10 yearsReplace with new part.
Aluminum capacitors on PCBs5 yearsReplace with new board. (Determine need by inspection.)
Note: Usage conditions are as follows: • Ambient temperature: Yearly average of 30°C • Load factor: 80% max. • Operating rate: 12 hours max. per day.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual47
Fuse Blown
The fuse in the main circuit is blown.
The main transistor has damaged.
Main Circuit Undervoltage
The main circuit DC voltage is below
the undervoltage detection level
(L2-05).
200 V class: Approx. 190 VDC
400 V class: Approx. 380 VDC
Control Power Fault
The control power supply voltage
dropped.
Inrush Prevention Circuit Fault
A fault occurred in the inrush
prevention circuit.
AC Power Undervoltage
AC power undervoltage occurred
during running.
200 V class: Approx. 150 VAC or less
400 V class: Approx. 300 VAC or less
Power Supply Frequency Fault
AC power supply frequency has
exceeded the setting value (F1-10).
Power Supply Fault
The phase of the input power supply has
changed after turning ON the control
power supply.
Overcurrent
The output current of the power
regenerative unit exceeded the
overcurrent detection level.
(200% of rated current)
IGBT Short-circuit
The IGBT gate signal was shortcircuited.
Main Circuit Overvoltage
The main circuit DC voltage exceeded
the overvoltage detection level.
200 V class: Approx. 400 VDC
400 V class: Approx. 800 VDC
Heatsink Overheating
The temperature of the power
regenerative unit’s cooling fins
exceeded the setting in L8-02.
(Stopping method can be changed by
L8-03.)
Heatsink Overheating
The temperature of the power
regenerative unit’s cooling fins
exceeded 105°C.
(Stopping method: Coast to stop)
The output transistor has failed because
of a short-circuit or overcurrent.
• An open-phase occurred with the
input power supply.
• A momentary power loss occurred.
• The wiring terminals for the input
power supply are loose.
—
—
• An open-phase occurred with the
input power supply.
• A momentary power loss occurred.
• The wiring terminals for the input
power supply are loose.
• The power supply fluctuations
occurred during running.
• Power loss occurred during running.
• An open-phase occurred with the
input power supply.
• A momentary power loss occurred.
• The wiring terminals for the input
power supply are loose.
• A short-circuit occurred at the power
regenerative output.
• Power supply drop
• Faulty wiring
A short-circuit of the PWM signal
occurred.
The deceleration time is too short and
the regenerative energy from the motor
is too large.
The power supply voltage is too high.
The ambient temperature is too high.Install a cooling unit.
There is a heat source nearby.Remove the heat source.
The cooling fan of the power
regenerative unit has stopped.
The ambient temperature is too high.Install a cooling unit.
There is a heat source nearby.Remove the heat source.
The cooling fan of the power
regenerative unit has stopped.
Replace the power regenerative unit
after correcting the cause.
Reset the fault after correcting its cause.
• Try turning the power supply off and
on.
• Replace the power regenerative unit if
the fault continues to occur.
• Try turning the power supply off and
on.
• Replace the power regenerative unit if
the fault continues to occur.
Reset the fault after correcting its cause.
Reset the fault after correcting its cause.
Reset the fault after correcting its cause.
Reset the fault after correcting its cause.
Replace the control card.
• Increase the deceleration time.
• Check the capacity of the power
regenerative unit.
• (Increase the capacity.)
Decrease the voltage so it is within
specifications.
Replace the cooling fan. (Contact our
sales representative.)
Replace the cooling fan. (Contact our
sales representative.)
50YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
Power Regenerative Unit Input
Overload
Power regenerative unit input exceeded
the overload capacity.
External fault
(terminal S3-SC)
External fault
(terminal S4-SC)
Operator Connection Fault
The Operator was disconnected during
operation started by a run command
from the Operator.
EEPROM Write Error—
Control Circuit Error 1
(Operator Communications Error)
Control Circuit Error 2
(Operator Communications Error)
Baseblock Circuit Error
EEPROM Error
CPU Internal A/D Converter Error
The load is too heavy.Check the size of the load.
An external fault was input from a
multi-function input.
• Communications with the digital
operator were not established within 5
seconds after the power was turned
on.
• MPU peripheral element check fault.
• After communications were
established, there was a transmission
error with the digital operator for
more than 2 seconds.
• MPU peripheral element check fault
The control circuit is damaged.Replace the control card.
6.1 Fault Detection
• Reset external fault inputs to the
multi-function inputs.
• Remove the cause of the external
fault.
—Check the Operator connection.
A verification error occurred when
writing EEPROM.
Try turning the power supply off and on
again.
Try setting the constants again.
• Disconnect the digital operator and
then connect it again.
• Check the wiring of the control circuit
power supply.
• Replace the control card.
• Disconnect the digital operator and
then connect it again.
• Check the wiring of the control circuit
power supply.
• Replace the control card.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual51
6.2 Minor Fault Detection
6.2Minor Fault Detection
Minor faults are a type of the protection function that do not operate the fault contact output and are automatically returned to their original status
once the cause of the minor fault has been removed.
The Digital Operator display blinks.
Take appropriate countermeasures according to the table below.
Table 6.2 Minor Fault Displays and Processing
Minor Fault DisplayMeaningProbable CausesCorrective Actions
Main Circuit Undervoltage
UV
Dc Bus Undervolt
OV
Dc Bus Overvolt
OH
Heatsink Overtmp
OL
Input Over Loaded
EF3
External Fault 3
EF4
External Fault 4
The main circuit DC voltage was below
the undervoltage detection level
(L2-05).
200 V class: Approx. 190 VDC or less
400 V class: Approx. 380 VDC or less
Main Circuit Overvoltage
The main circuit DC voltage exceeded
the overvoltage detection level.
200 V class: Approx. 400 VDC
400 V class: Approx. 800 VDC
Heatsink Overheating
The temperature of the power
regenerative unit’s cooling fins
exceeded the setting in L8-02.
(Stopping method can be changed by
L8-03.)
Power Regenerative Unit Input
Overload
Power regenerative unit input exceeded
the overload capacity.
External fault (terminal S3-SC)
External fault (terminal S4-SC)
See causes for AUv, FdVe, SrC, and
UV3 faults.
The regenerative energy from the motor
is too large.
The power supply voltage is too high.
The ambient temperature is too high.Install a cooling unit.
There is a heat source nearby.Remove the heat source.
The cooling fan of the power
regenerative unit has stopped.
The load is too heavy.Check the size of the load.
An external fault was input from a
multi-function input.
Check the capacity of the power
regenerative unit. (Increase the
capacity.)
Decrease the voltage so it is within
specifications.
Replace the cooling fan. (Contact your
YASKAWA representative.)
• Reset external fault inputs to the
multi-function inputs.
• Remove the cause of the external
fault.
—
52YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
6.3 Operation Errors
6.3Operation Errors
After the parameters have been set, an operation error will occur if there is an invalid setting or a contradiction between two parameter settings.
It won’t be possible to start the power regenerative unit until the parameters have been set correctly. (The minor fault output and fault contact output
will not operate, either.)
When an operation error has occurred, refer to the following table to identify and correct the cause of the errors.
Table 6.3 Operation Error Displays and Incorrect Settings
DisplayMeaningIncorrect settings
OPE01
kVA Selection
OPE02
Limit
OPE03
Ter mi nal
Incorrect Power Regenerative Unit
Capacity Setting
Parameter Setting Range ErrorThe parameter setting is outside of the valid setting range.
Multi-function Input Selection Error
The power regenerative unit capacity setting does not match the Unit. (Contact
your YASKAWA representative.)
The same setting has been selected for two or more multi-function inputs
(H1-01, H1-02)
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual53
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual55
Note: 1. Consult the factory if connecting more than one inverter to one power regenerative unit.
2. Heavy duty applications require continuous energy dissipation (100% braking torque). The overload rating is 125% for 60 seconds with a duty cycle of 25%. Braking torque
of 187.5% is available for 30 seconds. Please note the peak torque should be less than 250%.
3. Standard duty applications require intermittent full energy dissipation. The continuous rating is 80% or less braking torque and 100% braking torque for 60 seconds with a
duty cycle of 25% (60 seconds maximum on-time of every 240 seconds). The overload rating is 150% braking torque for 30 seconds. Please note the peak torque should be less
than 200%.
4. Do not use this unit with single-phase power. Use three-phase power.
5. Imbalance rate between phases can be calculated using the following formula (Conforming to IEC1800-3). Imbalance rate between phases [%] = Three-phase average voltage
divided by (Max. voltage - Min. voltage) x 67. Use a power regenerative unit with larger output capacity if the imbalance rate between phases exceeds 2%
Table 7.1 200 V Class Specifications
Model CIMR-R5U23P725P527P5201120152018202220302037
HP (kW)
Heavy Duty
(See Note 2)
Rated
Current on
Input Side
Rating
Rated
Capacity
Standard
Duty
(See Note 3)
(100% Cont.)
HP (kW)
Rated
Current on
Input Side
(100%, 60s)
Rated DC Current A13192637516477102126
Regenerative Torque
Input Power
Supply
Voltage Frequency200 to 220 VAC 50 Hz, 200 to 230 VAC 60 Hz
Allowable Voltage Fluctuation+ 10 to - 15% (Imbalance rate between phases: within 2%) (See Note 5)
Allowable Frequency Fluctuation± 3 Hz (3 phase rotation)
Control Method120° current conduction
Control
Characteristics
Input Power Factor0.9 or more (Rated current)
Overload Capacity
Programmable Input / OutputTwo Digital Inputs, Two Digital Outputs, One Analog Output.
Operation InputExternal terminals
Fault1C contact output
Status Output
PHC OutputPhotocoupler output: 1 point can be selected (ready)
Analog OutputAnalog output: 1 point can be selected (current monitor)
Instantaneous Overcurrent
Blown FuseMotor stops by blown fuse.
Overload
Protective
Function
Undervoltage (DC Voltage)Stops at approx. 190 VDC or less.
Undervoltage (Power Side Voltage)Stops at approx. 150 VAC or less.
OverloadStops at approx. 400 VDC or more.
Fin OverheatProtected by thermistor
Power Supply Open Phase (See Note 4)Stops at power supply open phase detection.
Power Frequency ErrorStops by fluctuation more than ± 3 Hz of rated input frequency.
Power Charge IndicationIndicated until main output voltage is approx. 50 V or less.
LocationIndoor (Protected from corrosive gases and dust)
Environmental
Conditions
Ambient Temperature
Humidity90% RH or less (non-condensing)
Vibr ation9.8 m/s2 (1G) less than 20 Hz, up to 1.96 m/s2 (0.2G) at 20 to 50 Hz
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
8 1216243240486480
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
1015203040506080100
Heavy Duty: 100% cont., 125% for 60 s (25% ED), 187.5% for 30 s, max. torque < 250%
Standard Duty: 80% cont., 100% for 60s (25% ED), 150% for 30s, max. torque < 200%
Standard Duty: 150% for 30 seconds
Heavy Duty: 187.5% for 30 seconds
Standard Duty: Stops at approx. 200% of the current on power side
Heavy Duty: Stops at approx. 250% of the current on power side
Standard Duty: Stops after 30 seconds at 150% of rated current.
Heavy Duty: Stops after 30 seconds at 187.5% of rated current.
Heavy Duty: 100% cont., 125% for 60 s (25% ED), 187.5% for 30 s, max. torque < 250%
Standard Duty: 80% cont., 100% for 60s (25% ED), 150% for 30s, max. torque < 200%
Input Power
Supply
Regenerative Torque
Voltage Frequency380 to 460 VAC 50/60 Hz,
Allowable Voltage Fluctuation+ 10 to - 15% (Imbalance rate between phases: within 2%) <1>
Allowable Frequency Fluctuation± 3 Hz (3 phase rotation)
Control Method120° current conduction
Control
Characteristics
Input Power Factor0.9 or more (Rated current)
Overload Capacity
Standard Duty: 150% for 30 seconds
Heavy Duty: 187.5% for 30 seconds
Operation InputExternal terminals
Fault1C contact output
Status Output
Running, READY SignalPhotocoupler output
Analog OutputAnalog output: 1 point can be selected (current monitor)
Instantaneous Overcurrent
Standard Duty: Stops at approx. 200% of the current on power side
Heavy Duty: Stops at approx. 250% of the current on power side
Blown FuseMotor stops by blown fuse.
Standard Duty: Stops after 30 seconds at 150% of rated current.
Heavy Duty: Stops after 30 seconds at 187.5% of rated current.
Protective
Function
Overload
Undervoltage (DC Voltage)Stops at approx. 380 VDC or less.
Undervoltage (Power Side Voltage)Stops at approx. 300 VAC or less.
OverloadStops at approx. 800 VDC or less.
Fin OverheatProtected by thermistor
Power Supply Open PhaseStops at power supply open phase detection.
Power Frequency ErrorStops by fluctuation more than ± 3 Hz of rated input frequency.
Power Charge IndicationIndicated until main output voltage is approx. 50 V or less.
LocationIndoor (Protected from corrosive gases and dust)
Environmental
Conditions
Ambient Temperature
Humidity90% RH or less (non–condensing)
- 10°C to + 40°C (Closed wall–mounted)
- 10°C to + 45°C (Open chassis type)
Vibr ation9.8 m/s2 (1G) less than 20 Hz, up to 1.96 m/s2 (0.2G) at 20 to 50 Hz
30
40
(22)
(30)50(37)60(45)75(55)
40
(30)50(37)60(45)75(55)
100
(75)
Note: Use a power regenerative unit with larger output capacity if the imbalance rate between phases exceeds 2%.
Note: <1> Imbalance rate between phases can be calculated using the following formula (Conforming to IEC1800-3). Imbalance rate between phases [%] = Three-phase
average voltage divided by (Max. voltage - Min. voltage) x 67.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual57
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual59
U1-12 = 00000000
1:Running
0:Notused.(always0)
t
1 : Reset input ON
0:Notused.(always0)
1 : Powerregenerative unitready
0 : Minor fault detected
1 : Major fault detected
Ta bl e A. 1 shows the items that can be monitored in operation mode. The output signal levels for multi-function analog outputs shown in the table are
for a gain of 100.0 and a bias of 0.00.
Table A.1 Parameters Monitored in Operation Mode
Function
Status
Monitor
Parameter
No.
U1-02
U1-04
U1-05
U1-07
U1-08
U1-10
U1-11
Parameter Name /
Display
DC bus voltage
DC Bus Voltage
Monitors the DC voltage of the power regenerative unit’s internal
main circuit
Function
AC power supply voltage
AC Voltage
Current at power side
AC Current
Power at power side
AC Power
AC power supply frequency
AC Frequency
Monitors the AC power supply voltage.
Monitors the AC power supply current.
Monitors the AC power supply power.
Monitors the AC power supply frequency.
Input terminal statusShows input ON/OFF status.
Shows input ON/OFF status.
U1-10 =
Input Term Sts
00000000
1:MANUALRUN(terminalS1)ON
1 : AUTO RUN (terminal S2) ON
1:EXFLT(terminalS3)ON<1>
1 : RESET (terminal S4) ON <1>
1:Notused.(always0)
<1 > : Can be selected by H1-01 or H1-02.
Output terminal statusShows output ON/OFF status.
U1-11 = 00000000
0:Notused. (always0)
1 : Multi-function output 1
Output Term Sts
<2 > : Can be selected by H2-02 or H2-03.
(terminals M1-M2) ON <2>
1 : Multi-function output 2
(terminals M3-M4) ON <2>
0:Notused.(always0)
1 : Fault output
(terminal MA/MB-MC) ON
Operation statusPower regenerative unit operating status.
Output Signal Level for
Multi-function Analog
Outputs
200 V class: 400 V/10 V
400 V class: 800 V/10 V
(0 to +10 V Output)
200 V class: 200 V/5 V
400 V class: 400 V/5 V
(0 to +10 V Output)
Monitors the power regenerative unit’s elapsed operating time.
Can be set with uparameter o2-07 or o2-08.
—
(Manufacturer’s ID number)—
Monitors the deviation between the AC power supply voltage and
the main circuit DC voltage.
200 V class: 400 V/10 V
400 V class: 800 V/10 V
1 V
(Manufacturer’s ID number)(Cannot be output)—
Function
Fault
Trace
Fault
History
Parameter
No.
U2-01
U2-02
U2-04
U2-06
U2-07
U2-08
U2-10
U2-11
U2-12
U2-13
U2-14
U2-20
U3-01
U3-02
U3-03
U3-04
U3-05
U3-06
U3-07
U3-08
Parameter Name /
Display
Current fault
Current Fault
Last fault
Last Fault
DC bus voltage at fault
DC Bus Voltage
Power supply voltage at fault
AC Voltage
Power side current at fault
AC Current
Power at fault
AC Power
Power side frequency at fault
AC Frequency
Input terminal status at fault
Input Term Sts
Output terminal status at fault
Output Term Sts
Operation status at fault
Regen Unit Sts
Cumulative operation time at
fault
Elapsed Time
Voltage deviation input at fault
V Deviation
Most recent fault
Last Fault
Second most recent fault
Fault Message 2
Third most recent fault
Fault Message 3
Fourth/oldest fault
Fault Message 4
Cumulative operation time at
fault
Elapsed Time 1
Accumulated time of second
fault
Elapsed Time 2
Accumulated time of third fault
Elapsed Time 3
Accumulated time of fourth/
oldest fault
Elapsed Time 4
Function
Information on the current fault
Output Signal Level for
Multi-function Analog
Outputs
Min.
Unit
—
Information on the last fault—
Main circuit DC voltage value when the “last fault” occurred.1 V
AC power supply voltage value when the “last fault” occurred.1 V
Current value at AC power side when the “last fault” occurred.1 A
Power at AC power side when the “last fault” occurred.1 kW
Frequency at AC power side when the “last fault” occurred.0.01 Hz
Input terminal status when the “last fault” occurred.
(Same format as U1-10.)
Output terminal status when the “last fault” occurred.
(Same format as U1-11.)
Operating status when the “last fault” occurred.
(Same format as U1-12.)
Elapsed operating or power-on time when the “last fault” occurred.1 H
(Cannot be output)
—
—
—
Voltage deviation when the “last fault” occurred.1 V
Information on the last fault.—
Information on the 2nd to last fault.—
Information on the 3rd to last fault.—
Information on the 4th to last fault.—
Elapsed running or power-on time when the last fault occurred.1 H
Elapsed running or power-on time when the 2nd to last fault
occurred.
Elapsed running or power-on time when the 3rd to last fault
occurred.
Elapsed running or power-on time when the 4th to last fault
occurred.
1 H
1 H
1 H
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual61
Parameter
No.
A1-00
A1-01
A1-03
A1-04
b1-02
b1-06
C8-17
C8-18
C8-19
C8-20
F1-10
F1-11
H1-01
H1-02
H2-02
H2-03
Parameter Name
Display
Language selection for operator
display
[Select Language]
Parameter access level
[Access Level]
Initialize
[Init Parameters]
Password 1 (Input)
[Enter Password]
Operation method selection
[Run Source]
Read sequence input twice
[Cntl Input Scans]
Automatic operation stop current
[Autorun Iout]
Bias voltage at operation start
[V Bias of Run]
Hysteresis voltage width at
operation start/stop
[V Width of Stop]
Min. operating time
[Minimum Run Time]
Excessive frequency deviation
detection level
[FDEV DetectLevel]
Excessive frequency deviation
detection delay time
[FDEV Detect Time]
Multi-function input (terminal S3)
[Terminal S3 Sel]
Multi-function input (terminal S4)
[Terminal S4 Sel]
Multi-function output (terminal M1M2)
[Terminal M1 Sel]
Multi-function output (terminal M3M4)
[Terminal M3 Sel]
Table A.2 Parameter List
Setting Range
0, 10OA
0 to 99994OA
0000 to 99990000xA
0000 to 99990xA
0, 11xA
0, 11xA
10 to 100%50xA—
0.0 to 50.0 V2.0xA
0.5 to 50.0 V3.0xA
0.0 to 600.0 sec1.0xA—
1.0 to 10.0 Hz3.0xA
0.0 to 255.0 sec70.0xA
0 to 2F24OA
0 to 2F14OA
0 to 206OA
0 to 200OA
Factory
Setting
Change
during
Operation
Access
Level
Description
Language selection for the Digital Operator.
This parameter is not reset to the factory setting by
A1-03.
0: English
1: Japanese
Selects which parameters are accessible via the
Digital Operator.
0: Operation only
4: Advanced Level
Used to return all parameters to their factory or user
default settings. (Initializes and then returns A1-03 to
zero.)
2220: 2-Wire Initialization
When the value set into A1-04 does NOT match the
value set into A1-05, parameters A1-01 thru A1-03
cannot be changed. All other parameters as
determined by A1-01 can be changed. Parameter A105 can be accessed by pressing the MENU key while
holding the RESET key.
Selects the run command input source.
0: Operator- RUN and STOP keys on Digital
Operator.
1: Terminals - Contact closure on terminals S1 or S2.
Sets the scan rate of terminals S1 to S4
0: 500 ms - 2 scans (for quick response)
1: 5 ms - 2 scans (for noisy environments)
For 400 V class power regenerative units, double the
initial setting and setting range.
For 400 V class power regenerative units, double the
initial setting and setting range.
Configures the frequency deviation fault (DEV)
detection. DEV fault will occur if the frequency
deviation is greater than the F1-10 setting for a time
longer than F1-11. F1-10 is set as a percentage of the
maximum output frequency (E1-04). Frequency
deviation is the difference between actual input
supply frequency and the frequency reference
command.
Selects the function of terminal S3.
24: External fault, Normally Open, Always Detected,
Coast To Stop.
Refer to Tab l e A .3 .
Selects the function of terminal S4.
14: Fault reset
Closed = Resets the Drive after the fault and the run
command have been removed.
Refer to Tab l e A .3 .
Selects the function of terminals M1 to M2.
6: Drive ready
Closed - When the Drive is powered up, not in a fault
state and in the DRIVE mode.
Refer to Tab l e A .4 .
Selects the function of terminals M2 - M4.
0: During Run 1
Closed - When a run command is input or the Drive
is outputting voltage.
Refer to Tab l e A .4 .
Selects which monitor will be output on terminals
AM and AC.
0: Not used
2: DC bus voltage (U1-02)
4: AC power supply voltage (U1-04)
5: Current at power side (U1-05)
7: Power at power side (U1-07)
8: AC power supply frequency (U1-08)
21: Voltage deviation (U1-21)
Refer to Ta bl e A. 5 .
Sets terminal AM output level when selected monitor
is at 100%.
Sets terminal AM output level when selected monitor
is at 0%.
Selects the signal level of terminal AM.
0: 0 to 10 Vdc
1: -10 to +10 Vdc
Enables and disables the momentary power loss
function.
0: Disabled - Unit trips on (UV1) fault when power is
lost.
1: Power Loss Ride Thru Time - Unit will restart if
power returns within the time set in L2-02.*
2: CPU Power Active - Unit will restart if power
returns prior to control power supply shut down.*
* In order for a restart to occur, the run command
must be maintained throughout the ride thru period.
Sets the power loss ride-thru time. This value is
dependent on the capacity of the Unit. Only effective
when L2-01 = 1.
Sets the Unit’s DC Bus undervoltage trip level. If this
is set lower than the factory setting, additional AC
input reactance or DC bus reactance may be
necessary. Consult the factory before changing this
parameter setting.
Sets the counter for the number of times the Unit will
perform an automatic restart. Auto restart will check
to see if the fault has cleared every 5 ms. When no
fault is present, the Unit will attempt an auto restart.
If the Unit faults after an auto restart attempt, the
counter is incremented. When the Unit operates
without fault for 10 minutes, the counter will reset to
the value set in L5-01.
Determines if the fault contact activates during an
automatic restart attempt.
0: No Fault Relay - fault contact will not activate
during an automatic restart attempt.
1: Fault Relay Active - fault contact will activate
during an automatic restart attempt.
When the cooling fin temperature exceeds the value
set in this parameter, an overheat alarm (OH) will
occur.
Selects the Unit operation upon an OH pre-alarm
detection.
1: Coast to Stop
3: Alarm Only
Selects the detection of output current open-phase.
When applied motor capacity is too small for Unit
capacity, output phase loss may be detected
inadvertently. In this case, set to 0.
0: Disabled
1: Enabled
Selects which monitor will be displayed in the
operation menu upon power-up when o1-02 = 4.
4: Power supply voltage (U1-04)
7: Power at power side (U1-07)
8: Power supply frequency (U1-08)
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual63
Parameter
No.
o1-02
o2-01
o2-02
o2-04
o2-06
o2-07
o2-08
Parameter Name
Display
Monitor selection after power up
[Power-On Monitor]
LOCAL/REMOTE key enable/
disable
[Local/Remote Key]
STOP key during remote operation
[Oper STOP Key]
kVA selection
[Regen Unit Model]
Operation selection when digital
operator is disconnected
[Oper Detection]
Cumulative operation time setting
[Elapsed Time Set]
Cumulative operation time selection
[Elapsed Time Run]
Setting Range
2 to 42OA
0, 11xA
0, 10xA
00 to FF*xA
0, 10xA
0 to 65535H—xA
0, 10xA
Factory
Setting
Change
during
Operation
Access
Level
Description
Selects which monitor will be displayed upon powerup.
2: DC Bus Voltage (U1-02)
3: Output Current at the power side (U1-05)
4: Monitor set in o1-01
Determines if the Digital Operator Local / Remote
key is functional.
0: Disabled
1: Enabled
Determines if the STOP key on the Digital Operator
will stop the Unit when the Unit is operating from
external terminals.
0: Enabled during run command from the digital
operator
1: Enabled
Sets the kVA of the Unit. Enter the number based on
the Unit model number. Use the last four digits of the
model number.
This parameter only needs to be set when installing a
new control board. Do not change for any other
reason.
Determines if the Unit will stop when the Digital
Operator is removed when in LOCAL mode or
b1-02 = 0.
0: Disabled - the Unit will not stop when the Digital
Operator is removed.
1: Enables - The Unit will fault (OPR) and coast to
stop when the Digital Operator is removed.
Sets the initial value of the elapsed operation timer
U1-13.
Sets how time is accumulated for the elapsed
operation timer U1-13.
0: Power-On Time - Time accumulates when the Unit
is powered.
1: Running Time - time accumulates only when the
Unit is running.
151 Lorong Chuan, #04-01, New Tech Park, 556741, Singapore
Phone: 65-6282-3003
http://www.yaskawa.com.sg
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
No. 18 Xizang Zhong Road, 17F, Harbour Ring Plaza, Shanghai, 200001, China
Phone: 86-21-5385-2200
http://www.yaskawa.com.cn
YASKAWA ELECTRIC (SHANGHAI) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: 886-2-2502-5003
Fax: 55-11-5581-8795
Fax: 44-1236-458182
Fax: 82-2-784-8495
Fax: 65-6289-3003
Fax: 86-21-5385-3299
Fax: 86-10-8518-4082
Fax: 886-2-2505-1280
YASKAWA ELECTRIC CORPORATION
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.