Yale 8880, 8884, 8886, 8888, 8890 Installation Instructions Manual

...
8800 Series Electrified Mortise Solenoid Locks
Installation Instructions
Instructions for Wiring 8800 Series Electrified Mortise Solenoid Locks, 8800 Series Monitoring Suffixes REX, LBM & DBM & Combined Solenoid & Monitoring Suffixes with Pluggable "ElectroLynx Connector System"
For Technical Assistance call Yale at 1-800-810-WIRE (9473)
An ASSA ABLOY Group brand
®
NOTE TO INSTALLER
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN DAMAGE TO THE LOCK AND VOID THE FACTORY WARRANTY.
Any retrofit or other field modification to a fire rated opening can potentially impact the fire rating of the opening, and Yale Locks & Hardware makes no representations or warranties concerning what such impact may be in any specific situation. When retrofitting any portion of an existing fire rated opening, or specifying and installing a new fire-rated opening, please consult with a code specialist or local code official (Authority Having Jurisdiction) to ensure compliance with all applicable codes and ratings.
80-8800-0005-000 (07-14)
Introduction
This instruction manual includes wiring instructions for all electrical types of 8800 series electric mortise locks to ElectroLynx Hinge Connector System. The correct wiring configuration must be selected depending on type and function of the mortise lock being installed. Multiple functions can be combined (ex: 8890FL REX-LBM). Refer to table on page 4 to select appropriate wiring instruction for mortise product being installed.
Important
Disconnect all input power before beginning installation to prevent electrical shock and equipment damage. Installer must be a trained, experienced service person. All wiring must comply with applicable local electrical codes, ordinances and regulations.
CAUTION: The DC voltage applied to the lock solenoid must not exceed If the voltage12 / 24 VDC +/- 10%
exceeds these values the solenoid may be damaged or not function.
Specifications / Functions
Solenoid
Type: 12 or 24VDC, Intermittent or Continuous Duty
612mA Peak @12VDC 500mA Steadystate @12VDC 330mA Peak @24VDC 612mA Steadystate @24VDC
Fail Safe: Models 8880, 8884, 8886, 8888, 8890, 8894-2, 8896 and 8898 Fail Secure: Models 8881, 8885, 8887, 8889, 8891,8895-2, 8897 and 8899
REX-, LBM-, and DBM- Lock Switches: contact rating for all switches: 2 Amp max @ 30VDC
REX (Request to Exit). Lever Monitor Switches. The 8800 REX series mortise lock is designed to allow monitoring of inside and outside lever rotation. The lock uses two switches to monitor the inside and outside lever hubs.
LBM (latchbolt monitor switch). The 8800 LBM series mortise lock provides positive indication of latchbolt extension or retraction when the lever is rotated retracting the latchbolt, latchbolt being retracted by key, or if the latchbolt itself is depressed.
DBM (deadbolt monitor switch). The 8800 DBM series is designed to monitor the position of the dead bolt.
LPM (Lock Performance Monitor). The 8800 LPM series provides a status check on the lock’s main components.
Molex Connectors:
®
8-Pin: Lock Options
Case
4-Pin: REX
2
An ASSA ABLOY Group brand
Cover
80-8800-0005-000 (07-14)
Loading...