Xylem RG700 User Manual

Global Water

800-876-1172 globalw.com
00-663 Rev. B Publication Number 38590512
Global Water
Instrumentation, Inc.
P. O. Box 9010
College Station, TX 77842-9010
T: 800-876-1172

Int’l: (979) 690-5560, F: (979) 690-0440

4-20 mA Output Module

RG700

- 1 -
Global Water
800-876-1172 globalw.com
Congratulations on your purchase of the Global Water RG700 4-20 mA Output Module. This instrument has been quality tested and approved for providing accurate and reliable measurements. We are confident that you will find the RG700 to be a valuable asset for your application. Should you require assistance, our technical staff will be happy to help.

Table of Contents

I. RG700 Checklist ............................................................................... 3
II. Inspection .......................................................................................... 3
III. Description ........................................................................................ 3
IV. Installing the 4-20 mA Output Modul e .............................................. 3
V. Using the 4-20 mA Output Module ................................................... 4
VI. Specifications .................................................................................... 4
VII. Maintenance ...................................................................................... 4
VIII. Trouble Shooting ............................................................................... 5
IX. Warranty ............................................................................................ 6
X. Appendix A: RG700 terminal diagram .............................................. 7
* Copyright  Global Water Instrumentatio n, I nc. 2012
- 2 -

I. RG700 Checklist

a. 4-20 mA Output Module b. RG700 Manual

II. Inspection

a. Your RG700 unit was carefully inspected and certif ied by our Quality
Assurance Team before shipping. If any signific ant damage has occurred during shipping, please not ify Global Water Instrumentation, Inc. and file a claim with the carrier involv ed. Use the checklist to ensure that you have received everything need ed to operate the RG700.
Global Water
800-876-1172 globalw.com

III. Description

a. The Global 4-20 mA Output Module, RG700, is a rugged, reliable, and
accurate instrument for converting input puls es into a 4-20mA analog output signal.

IV. Installing the 4-20 mA Output Modul e

a. Place the module in an area that is protected from direct rainfall and
immersion in water. The module is water resis tant , not water proof.
b. The pulse device is connected to terminals 1 and 2. Polar ity is not an
issue. Please refer to Appendix A: RG700 t er minal diagram.
c. Terminals 3-5 ar e output ports which are not used. Terminal 4 is the
4-20mA current output.
d. Terminals 6-8 are the module’s power terminals. Terminal 6 is the
positive voltage input switch to the attached sensor. Positive voltage goes into terminal 7. Terminal 8 is for the ground signal.
e. If the unit is intended to operate indefinitely, c onnect terminals 6 and 7
together.
- 3 -