SSW-07 / SSW-08 Quick Parameter Reference
Referência Rápida de los Parámetros SSW-07 / SSW-08
Referência Rápida dos Parâmetros SSW-07 / SSW-08
10000506541 / 01
Software V1.4X
Par. English Español Português
P000 Access to parameters
0 to 9999
READ ONLY PARAMETERS
P001 to P099
P001 Motor current %In of
SSW-07/SSW-08
0.0 to 999.9 %
P002 Motor current %In of Motor
0.0 to 999.9 %
P003 Motor current
0.0 to 6553 A
P005 Power supply frequency
0.0 to 99.9 Hz
P006 Soft-Starter Status
0 = rdy - ready
2 = Exx - Error
3 = ruP - Ramp Up
5 = PASS - By-pass
7 = rdo - Ramp Down
8 = br - Braking
9 = rEv - FWD/REV
10 = JoG - Jog
11 = dly - Delay P630
12 = G.di - General Disable
P007 Voltage imposed by the
Soft-Starter over the load
(%Un)
0 to 100 %
P011 Apparent output power
0.0 to 999.9 kVA
P012 DI1 to DI3 status
0 = Inactive
1 = Active
P013 Relay RL1 and RL2 output
status
0 = Inactive
1 = Active
P014 Last fault occurred
E00 to E77
P015 Second fault occurred
E00 to E77
P016 Third fault occurred
E00 to E77
P017 Fourth fault occurred
E00 to E77
P020 Actual Fault
0...99
P023 Software version Versión de software Versão de software P030 Phase R current
0.0 to 6553 A
P031 Phase S current
0.0 to 6553 A
P032 Phase T current
0.0 to 6553 A
P050 Motor thermal protection
status
0 to 250 %
P081 Heatsink temperature
10.0 to 110.0 ºC
P090 CAN Controller Status
0 = Inactive
1 = Autobaud
2 = Active CAN Interface
3 = Warning
4 = Error passive
5 = Bus off
6 = No Bus Power
P091 DeviceNet Network Status
0 = Offline
1 = Online, Not Connected
2 = Online, Connected
3 = Expire Connection
4 = Connection Failure
5 = Auto-Baud
P092 DeviceNet Master Status
0 = Run
1 = Idle
P093 Received CAN Telegram
Counter
0 to 9999
P094 Transmitted CAN Telegram
Counter
0 to 9999
P095 Buss Off Error Counter
0 to 9999
P096 Lost Can Message Counter
0 to 9999
REGULATION
PARAMETERS
P100 to P199
Ramps Rampas Rampas
(3)
Initial voltage (%Un)
P101
30 to 90 %
(3)
Acceleration ramp time
P102
1 to 999 s
P103 Deceleration Voltage Step
(% Un)
100 = Inactive
99...60
(3)
Deceleration ramp time
P104
0=Inactive
1 to 240 s
P105 End Deceleration Voltage
(% Un)
30...55
Current Limitation Limitación de Corriente Limitação de Corrente
(3)
Current limitation
P110
(%In of the Soft-Starter)
30 to 500 %
Acceso a los parámetros
0 a 9999
PARÁMETROS DE
LECTURA P001 a P099
Corriente del motor %In del
SSW-07/SSW-08
0.0 a 999.9 %
Corriente del motor %In
del Motor
0.0 a 999.9 %
Corriente del motor
0.0 a 6553 A
Frecuencia de la red de
alimentación
0.0 a 99.9 Hz
Estado del Arrancador
Suave
0 = rdy - ready
2 = Exx - Error
3 = ruP - Ramp p
5 = PASS - By-pass
7 = rdo - Ramp Down
8 = br - Braking
9 = rEv - FWD/REV
10 = JoG - Jog
11 = dly - Delay P630
12 = G.di - General Disable
Tensión impueta por el
Arrancador sobre la carga
(%Un)
0 a 100 %
Potencia aparente de salida
0.0 a 999.9 kVA
Estado DI1 a DI3
0 = Inactiva
1 = Activa
Estado de las salidas a relé
RL1 y RL2
0 = Inactiva
1 = Activa
Ultimo error ocurrido
E00 a E77
Segundo error ocurrido
E00 a E77
Tercero error ocurrido
E00 a E77
Cuarto error ocurrido
E00 a E77
Actual Error
0...99
Corriente de la fase R
0.0 a 6553 A
Corriente de la fase S
0.0 a 6553 A
Corriente de la fase T
0.0 a 6553 A
Estado de la proteccíon
térmica del motor
0 a 250 %
Temperatura del disipador
10.0 a 110.0 ºC
Estado del controlador CAN
0 = Inactivo
1 = Autobaud
2 = CAN ativo
3 = Warning
4 = Error passive
5 = Bus off
6 = No alimentado
Estado Rede DeviceNet
0 = Offline
1 = OnLine, No conectado
2 = OnLine, Conectado
3 = Conexión Caduco
4 = Falla Conexión
5 = Auto-Baud
Estado Maestro DeviceNet
0 = Run
1 = Idle
Telegramas CAN RX
0 a 9999
Telegramas CAN TX
0 a 9999
Contador de Bus Off
0 a 9999
Mensajes CAN perdidas
0 a 9999
PARÁMETROS DE
REGULACIÓN
P100 a P199
Tensión inicial (%Un)
30 a 90 %
Tiempo de la rampa de
aceleración
1 a 999 s
Escalón de tensión em la
desaceleración (%Un)
100 = Inactiva
99...60
Tiempo de la rampa de
desaceleración
0 = Inactiva
1 a 240 s
Tensión Final de
Desaceleración (% Un)
30...55
Limitación de corriente
(%In del Arrancador Suave)
30 a 500 %
Acesso aos parâmetros
0 a 9999
PARÂMETROS DE LEITURA
P001 a P099
Corrente do motor %In da
SSW-07/SSW-08
0.0 a 999.9 %
Corrente do motor %In do
Motor
0.0 a 999.9 %
Corrente do motor
0.0 a 6553 A
Freqüência da rede de
alimentação
0.0 a 99.9 Hz
Estado da Soft-Starter
0 = rdy - ready
2 = Exx - Error
3 = ruP - Ramp p
5 = PASS - By-pass
7 = rdo - Ramp Down
8 = br - Braking
9 = rEv - FWD/REV
10 = JoG - Jog
11 = dly - Delay P630
12 = G.di - General Disable
Tensão imposta pela chave
sobre à carga (%Un)
0 a 100 %
Potência aparente de saída
0.0 a 999.9 kVA
Estado DI1 a DI3
0 = Inativa
1 = Ativa
Estado das saídas a relé
RL1 e RL2
0 = Inativa
1 = Ativa
Último erro ocorrido
E00 a E77
Segundo erro ocorrido
E00 a E77
Terceiro erro ocorrido
E00 a E77
Quarto erro ocorrido
E00 a E77
Erro Atual
0...99
Corrente da fase R
0.0 a 6553 A
Corrente da fase S
0.0 a 6553 A
Corrente da fase T
0.0 a 6553 A
Estado da proteção térmica
do motor
0 a 250 %
Temperatura do dissipador
10.0 a 110.0 ºC
Estado controlador CAN
0 = Inativo
1 = Autobaud
2 = CAN ativo
3 = Warning
4 = Error passive
5 = Bus off
6 = Não alimentado
Estado Rede DeviceNet
0 = Offline
1 = OnLine, Não conectado
2 = OnLine, Conectado
3 = Conexão Expirou
4 = Falha Conexão
5 = Auto-Baud
Estado Mestre DeviceNet
0 = Run
1 = Idle
Telegramas CAN RX
0 a 9999
Telegramas CAN TX
0 a 9999
Contador de Bus Off
0 a 9999
Mensagens CAN perdidas
0 a 9999
PARÂMETROS DE
REGULAÇÃO
P100 a P199
Tensão inicial (%Un)
30 a 90 %
Tempo da rampa de
aceleração
1 a 999 s
Degrau de tensão na
desaceleração (% Un)
100 = Inativa
99...60
Tempo da rampa de
desaceleração
0 = Inativa
1 a 240 s
Tensão Final de
Desaceleração (% Un)
30...55
Limitação de corrente
(%In da Soft-Starter)
30 a 500 %
Factory
Setting
Par. English Español Português
P111 Initial Current for Current
Ramp (%In of the SoftStarter)
30...500
P112 Time for the Current Ramp
(% of P102)
1...99
CONFIGURATION
PARAMETERS
P200 to P299
Generic Parameters Parámetros Genéricos Parâmetros Genéricos
P200 The password is
0 (5)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
50
20
100
0
30
300
0 = Inactive
1 = Active
P202 Type of Control
0=Voltage Ramp
1=Current Limit
2=Pump Control
3=No Function
4=Current Ramp
5=Direct Online (DOL)
P203 Fan Control
0 = Fan is always OFF
1 = Fan is always ON
2 = Fan controlled by software
(1)
Load parameters with
P204
factory default values
0 = No function
1 = No function
2 = No function
3 = No function
4 = No function
5 = Loads factory default values
P205 Reading parameter
selection
0 to 999
(3)
Auto-reset time
P206
0 = Inactive
1 to 1200 s
(1)
Copy function
P215
0 = Inactive
1 = SSW → Keypad
2 = Keypad → SSW
P219 Parameterization via Keypad
/ (Trimpots and DIP Switch)
0=Trimpots and DIP Switch
1=Keypad
2=P202=2 / Trimpots and DIP
Local/Remote Definition Definición de Local/Remoto Definição de Local/Remoto
(1)
Local/remote supply
P220
selection
0 = Always local
1 = Always remote
2 = Keypad (local default)
3 = Keypad (remote default)
4 = DI1 to DI3
5 = Serial (local default)
6 = Serial (remote default)
7 = Fieldbus (Default Local)
8 = Fieldbus (Default Remote)
(1)
Command selection – local
P229
situation
0 = Keypad
1 = Digital Input DIx
2 = Serial
3 = Fieldbus
(1)
Command selection –
P230
remote situation
0 = Keypad
1 = Digital Input DIx
2 = Serial
3 = Fieldbus
Digital Inputs Entradas Digitales Entradas Digitais
P263 Digital Input DI1 Function
0=No Function
1=Start/Stop (two wires) or
Start (three wires)
2=Local/Remote
3=No External Fault
4=FWD/REV
5=Brake Off
6=Reset
7=No Function
8=Jog
P264 Digital Input DI2 Function
0=No Function
1=Stop (three wires)
2=Local/Remote
3=No External Fault
4=FWD/REV
5=Brake Off
6=Reset
7=Emergency Start
8=Jog
P265 Digital Input DI3 Function
0=No Function
1=General Enabling
2=Local/Remote
3=No External Fault
4=FWD/REV
5=Brake Off
6=Reset
7=Emergency Start
8=Jog
Relay Outputs Salidas a Relé Saídas à Relé
P277 RL1 Relay Function
0=No Function
1=Running
2=Full Voltage
3=No Function
4=FWD/REV - K1
5=DC-Brake
6=No Fault
7=Fault
8=No Function
9=Serial
P278 RL2 Relay Function
0=No Function
1=Running
2=Full Voltage
3=No Function
4=FWD/REV - K2
5=DC-Brake
6=No Fault
7=Fault
8=No Function
9=Serial
Corriente Inicial para
Rampa de Corriente (% In
del Arrancador Suave)
30...500
Tiempo para Rampa de
Corriente (% de P102)
1...99
PARÁMETROS DE
CONFIGURACIÓN
P200 a P299
La clave esta
0 = Inactiva
1 = Activa
Tipo de Control
0=Rampa de tensión
1=Limitación de corriente
2=Control de bombas
3=Sin Función
4=Rampa de Corriente
5=Arranque Directo
Control del ventilador
0 = Ventilador siempre apagado
1 = Ventilador siempre
encendido
2 = Ventilador controlado por
el software
Carga parámetros con
valor padrón de fábrica
0 = Sin función
1 = Sin función
2 = Sin función
3 = Sin función
4 = Sin función
5 = Carga padrón de fábrica
Selección del parámetro
de lectura
0 a 999
Tiempo de autoreset
0 = Inactiva
1 a 1200 s
Función copy
0 = Inactiva
1 = SSW → HMI
2 = HMI → SSW
Parametrización vía HMI /
(Trimpots y DIP Switch)
0=Trimpots y DIP Switch
1=HMI
2=P202=2 / Trimpots y DIP
Seleción de la fuente local/
remoto
0 = Siempre local
1 = Siempre remoto
2 = HMI (default local)
3 = HMI (default remoto)
4 = DI1 a DI3
5 = Serial (default local)
6 = Serial (default remoto)
7 = Fieldbus (Default Local)
8 = Fieldbus (Default Remoto)
Seleción de los comandos situación local
0 = HMI
1 = Bornes
2 = Serial
3 = Fieldbus
Seleción de los comandos situación remoto
0 = HMI
1 = Bornes
2 = Serial
3 = Fieldbus
Función entrada DI1
0=Sin función
1=Start/Stop (dos cables) o
Start (tres cables)
2=Local/Remoto
3=Sin error externo
4=Sentido de giro
5=Sin Frenado
6=Reset
7=Sin función
8=Jog
Función entrada DI2
0=Sin función
1=Stop (tres cables)
2=Local/Remoto
3=Sin erro externo
4=Sentido de giro
5=Sin Frenado
6=Reset
7=Arranque de Emergencia
8=Jog
Función entrada DI3
0=Sin función
1=Habilita general
2=Local/Remoto
3=Sin erro externo
4=Sentido de giro
5=Sin Frenado
6=Reset
7=Arranque de Emergencia
8=Jog
Función Relé RL1
0=Sin función
1=En Funcionamiento
2=En Tensión Plena
3=Sin función
4=Sentido de giro K1
5=Frenado CC
6=Sin Error
7=Con Error
8=Sin función
9=Serial
Función Relé RL2
0=Sin función
1=En Funcionamiento
2=En Tensión Plena
3=Sin función
4=Sentido de giro K2
5=Frenado CC
6=Sin Error
7=Con Error
8=Sin función
9=Serial
Corrente Inicial para Rampa
de Corrente (% In da SoftStarter)
30...500
Tempo para Rampa de
Corrente (% de P102)
1...99
PARÂMETROS DE
CONFIGURAÇÃO
P200 a P299
A senha está
0 = Inativa
1 = Ativa
Tipo de Controle
0=Rampa de tensão
1=Limitação de corrente
2=Controle de bombas
3=Sem função
4=Rampa de corrente
5=Partida direta (DOL)
Controle do ventilador
0 = Ventilador sempre
desligado
1 = Ventilador sempre ligado
2 = Ventilador controlado por
software
Carrega parâmetros com
padrão de fábrica
0 = Sem função
1 = Sem função
2 = Sem função
3 = Sem função
4 = Sem função
5 = Carrega padrão de fábrica
Seleção do parâmetro de
leitura
0 a 999
Tempo de Auto-Reset
0 = Inativa
1 a 1200 s
Função copy
0 = Inativa
1 = SSW → HMI
2 = HMI → SSW
Parametrização via HMI /
(Trimpots e DIP Switch)
0=Trimpots e DIP Switch
1=HMI
2=P202=2 / Trimpots e DIP
Seleção da fonte local/
remoto
0 = Sempre local
1 = Sempre remoto
2 = HMI (default local)
3 = HMI (default remoto)
4 = DI1 a DI3
5 = Serial (default local)
6 = Serial (default remoto)
7 = Fieldbus (Default Local)
8 = Fieldbus (Default Remoto)
Seleção de comandos –
situação local
0 = HMI
1 = Bornes
2 = Serial
3 = Fieldbus
Seleção de comandos –
situação remoto
0 = HMI
1 = Bornes
2 = Serial
3 = Fieldbus
Função entrada DI1
0=Sem função
1=Start/Stop (dois fios) ou Start
(três fios)
2=Local/Remoto
3=Sem erro externo
4=Sentido de giro
5=Sem frenagem
6=Reset
7=Sem função
8=Jog
Função entrada DI2
0=Sem função
1=Stop (três fios)
2=Local/Remoto
3=Sem erro externo
4=Sentido de giro
5=Sem frenagem
6=Reset
7=Partida de emergência
8=Jog
Função entrada DI3
0=Sem função
1=Habilita geral
2=Local/Remoto
3=Sem erro externo
4=Sentido de giro
5=Sem frenagem
6=Reset
7=Partida de emergência
8=Jog
Função Relé RL1
0=Sem função
1=Em Funcionamento
2=Em Tensão Plena
3=Sem função
4=Sentido de giro K1
5=Frenagem CC
6=Sem Erro
7=Com Erro
8=Sem função
9=Serial
Função Relé RL2
0=Sem função
1=Em Funcionamento
2=Em Tensão Plena
3=Sem função
4=Sentido de giro K2
5=Frenagem CC
6=Sem Erro
7=Com Erro
8=Sem função
9=Serial
Factory
Setting
150
20
1
0
2
0
1
900
0
0
3
0
1
1
6
6
1
2
Par. English Español Português
Soft-Starter Data
(1)(2)
P295
Nominal current
0 = 1.7 A
1 = 17 A
2 = 24 A
3 = 30 A
4 = 45 A
5 = 61 A
6 = 85 A
7 = 130 A
8 = 171 A
9 = 200 A
10 = 255 A
11 = 312 A
12 = 365 A
13 = 412 A
COMMUNICATION
PARAMETERS
P300 to P399
Serial Communication Comunicación Serial Comunicação Serial
(1)(2)
Soft-Starter address
P308
1 to 247
(1)(2)
Type of protocol and
P312
serial communication
transmission rate
1 = Modbus 9600 bps no
parity
2 = Modbus 9600 bps odd
3 = Modbus 9600 bps even
4 = Modbus 19200 bps no
parity
5 = Modbus 19200 bps odd
6 = Modbus 19200 bps even
7 = Modbus 38400 bps no
parity
8 = Modbus 38400 bps odd
9 = Modbus 38400 bps even
P313 Serial communication error
action (E28)
0 = Inactive
1 = Disable
2 = General disable
3 = Change to local
(1)
Serial communication
P314
verification time
0 = Inactive
1 to 999 s
Fieldbus Communication Comunicación Fieldbus Comunicação Fieldbus
P331 CAN Address
0 to 63
P332 CAN Baud Rate
0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Autobaud
P333 Bus Off Reset
0 = Manual
1 = Automatic
P335 DeviceNet I/O Instances
0 = ODVA
1 = WEG Specific 1 W
2 = WEG Specific 2 W
3 = WEG Specific 3 W
4 = WEG Specific 4 W
5 = WEG Specific 5 W
6 = WEG Specific 6 W
7 = WEG Specific 7 W
P336 DeviceNet Reading Word #2
0 to 999
P337 DeviceNet Reading Word #3
0 to 999
P338 DeviceNet Reading Word #4
0 to 999
P339 DeviceNet Reading Word #5
0 to 999
P340 DeviceNet Reading Word #6
0 to 999
P341 DeviceNet Reading Word #7
0 to 999
P342 DeviceNet Writing Word #2
0 to 999
P343 DeviceNet Writing Word #3
0 to 999
P344 DeviceNet Writing Word #4
0 to 999
P345 DeviceNet Writing Word #5
0 to 999
P346 DeviceNet Writing Word #6
0 to 999
P347 DeviceNet Writing Word #7
0 to 999
P348 Fieldbus communication
error action
0 = Inactive
1 = Disable
2 = General Disable
3 = Change to local
MOTOR PARAMETERS
P400 to P499
Nominal Parameters Parámetros Nominales Parâmetros Nominais
(1)
Motor nominal voltage
P400
1 to 999 V
(1)(3)
Motor current setting
P401
30.0 to 100.0 %
(1)
Service factor
P406
1.00 to 1.50
SPECIAL FUNCTIONS
PARAMETERS
P500 to P599
Braking Frenado Frenagem
DC Braking Time
P501
0...299
0=Inactive
P502 DC Braking Voltage Level
30...70
P510 Jog
0=Inactive
1=Active
P511 Jog Level
30...70
Kick Start Kick Start Kick Start
(1)(3)
Voltage pulse at start
P520
(Kick Start)
0 = Inactive
1 = Active
Datos del Arrancador
Suave
Corriente nominal
0 = 1.7 A
1 = 17 A
2 = 24 A
3 = 30 A
4 = 45 A
5 = 61 A
6 = 85 A
7 = 130 A
8 = 171 A
9 = 200 A
10 = 255 A
11 = 312 A
12 = 365 A
13 = 412 A
PARÁMETROS DE
COMUNICACIÓN
P300 a P399
Dirección del Arrancador
Suave
1 a 247
Tipo de protocolo y tasa de
transmisión de la
comunicación serial
1 = Modbus 9600 bps sin
paridad
2 = Modbus 9600 bps impar
3 = Modbus 9600 bps par
4 = Modbus 19200 bps sin
paridad
5 = Modbus 19200 bps impar
6 = Modbus 19200 bps par
7 = Modbus 38400 bps sin
paridad
8 = Modbus 38400 bps impar
9 = Modbus 38400 bps par
Acción del error de
comunicación serial (E28)
0 = Inactiva
1 = Deshabilita
2 = Deshabilita General
3 = Se va para local
Tiempo de verificación de
la comunicación serial
0 = Inactiva
1 a 999 s
Dirección CAN
0 a 63
Tasa Comunicación CAN
0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Autobaud
Reset de Bus Off
0 = Manual
1 = Automático
Instancias I/O Dnet
0 = ODVA
1 = Especif. WEG 1 W
2 = Especif. WEG 2 W
3 = Especif. WEG 3 W
4 = Especif. WEG 4 W
5 = Especif. WEG 5 W
6 = Especif. WEG 6 W
7 = Especif. WEG 7 W
Lectura #2 Dnet
0 a 999
Lectura #3 Dnet
0 a 999
Lectura #4 Dnet
0 a 999
Lectura #5 Dnet
0 a 999
Lectura #6 Dnet
0 a 999
Lectura #7 Dnet
0 a 999
Escrita #2 Dnet
0 a 999
Escrita #3 Dnet
0 a 999
Escrita #4 Dnet
0 a 999
Escrita #5 Dnet
0 a 999
Escrita #6 Dnet
0 a 999
Escrita #7 Dnet
0 a 999
Acción del error de
comunicación Fieldbus
0 = Inactiva
1 = Deshabilita
2 = Deshabilita General
3 = Se va para local
PARÁMETROS DEL MOTOR
P400 a P499
Tensión nominal del motor
1 a 999 V
Ajuste de la corriente del
motor
30.0 a 100.0 %
Factor de servicio
1.00 a 1.50
PARÁMETROS DE LAS
FUNCIONES ESPECIALES
P500 a P599
Tiempo de Frenado
0...299
0=Inactivo
Nivel de Frenadol
30...70
Jog
0=Inactivo
1=Activo
Nivel do Jog
30...70
Pulso de tensión en el
arranque (Kick Start)
0 = Inactiva
1 = Ativa
Dados da Soft-Starter
Corrente nominal
0 = 1.7 A
1 = 17 A
2 = 24 A
3 = 30 A
4 = 45 A
5 = 61 A
6 = 85 A
7 = 130 A
8 = 171 A
9 = 200 A
10 = 255 A
11 = 312 A
12 = 365 A
13 = 412 A
PARÂMETROS DE
COMUNICAÇÃO
P300 a P399
Endereço da Soft-Starter
1 a 247
Tipo de protocolo e taxa de
transmissão da
comunicação serial
1 = Modbus 9600 bps sem
paridade
2 = Modbus 9600 bps impar
3 = Modbus 9600 bps par
4 = Modbus 19200 bps sem
paridade
5 = Modbus 19200 bps impar
6 = Modbus 19200 bps par
7 = Modbus 38400 bps sem
paridade
8 = Modbus 38400 bps impar
9 = Modbus 38400 bps par
Ação do erro de
comunicação serial (E28)
0 = Inativa
1 = Desabilita
2 = Desabilita geral
3 = Vai para local
Tempo de verificação da
comunicação serial
0 = Inativa
1 a 999 s
Endereço CAN
0 a 63
Taxa Comunicação CAN
0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Autobaud
Reset de Bus Off
0 = Manual
1 = Automático
Instâncias I/O Dnet
0 = ODVA
1 = Especif. WEG 1 W
2 = Especif. WEG 2 W
3 = Especif. WEG 3 W
4 = Especif. WEG 4 W
5 = Especif. WEG 5 W
6 = Especif. WEG 6 W
7 = Especif. WEG 7 W
Leitura #2 Dnet
0 a 999
Leitura #3 Dnet
0 a 999
Leitura #4 Dnet
0 a 999
Leitura #5 Dnet
0 a 999
Leitura #6 Dnet
0 a 999
Leitura #7 Dnet
0 a 999
Escrita #2 Dnet
0 a 999
Escrita #3 Dnet
0 a 999
Escrita #4 Dnet
0 a 999
Escrita #5 Dnet
0 a 999
Escrita #6 Dnet
0 a 999
Escrita #7 Dnet
0 a 999
Ação do erro de
Comunicação Fieldbus
0 = Inativa
1 = Desabilita
2 = Desabilita Geral
3 = Vai para local
PARÂMETROS DO
MOTOR P400 a P499
Tensão nominal do motor
1 a 999 V
Ajuste da corrente do motor
30.0 a 100.0 %
Fator de serviço
1.00 a 1.50
PARÂMETROS DAS
FUNÇÕES ESPECIAIS
P500 a P599
Tempo de Frenagem
0...299
0=Inativo
Nível da Frenagem
30...70
Jog
0=Inativo
1=Ativo
Nível do Jog
30...70
Pulso de tensão na partida
(Kick Start)
0 = Inativa
1 = Ativa
Factory
Setting
Par. English Español Português
(3)
P521
Pulse time at start
-
1
1
1
0
63
3
0
0
0
0
0
0
0
0
0.2 to 2.0 s
P522 Voltage pulse level at start
(%Un)
70 to 90 %
PROTECTION
PARAMETERS
P600 to P699
Current Protections Protecciones de Corriente Proteções de Corrente
(1)
Phase Loss or Immediate
P610
Undercurrent
(% In of the Motor)
1 to 80 %
(1)(3)
Immediate undercurrent
P611
time or phase loss
0 = Inactive
1 to 99 s
(1)
Immediate overcurrent (%In
P612
of motor)
1 to 200 %
(1)(3)
Immediate overcurrent time
P613
0 = Inactive
1 to 99 s
(1)
Current imbalance between
P614
phases (%In of motor)
0 to 30 %
(1)
Current imbalance time
P615
between phases
0 = Inactive
1 to 99 s
(1)
Undercurrent before
P616
By-Pass closing
0 = Inactive
1 = Active
(1)(3)
Blocked Rotor
P617
0 = Inactive
1 = Active
Phase Sequence Secuencia de Fase Seqüência de Fase
(1)(3)
RST phase sequence
P620
0 = Inactive
1 = Active
P621 E77 Enabling
0=Inactive
1=Active
Interval Between Starts Intervalo entre Partidas Intervalo entre Partidas
P630 Time interval after stopping
2 to 999 s
Motor Thermal Protection
(1)(3)
Motor protection thermal
P640
class
0 = Inactive
1 = 5
2 = 10
3 = 15
4 = 20
5 = 25
6 = 30
(1)
Thermal memory auto-reset
P641
0 = Inactive
1 to 600 s
(1) Changeable parameters only when the motor is disabled.
Solamente se permite modificar el valor del parámetro con el motor parado.
Parâmetros alteráveis somente com motor parado.
(2) Unchanged parameters at factory default settings (P204=5).
No cambia el valor del parámetro cuando se ejecuta el comando cargar valores padrón de fábrica (P204 = 5).
Parâmetros não alterados no padrão de fábrica (P204 = 5).
(3) Changeable parameters only in keypad mode (P219=1). If P219=0 the parameters are read only.
Se permite modificar el parámetro solamente en el modo HMI (P219 = 1). Con P219 = 0 los parámetros son
considerados del tipo lectura.
Parâmetros alteráveis somente em modo HMI (P219 = 1). Com P219 = 0 os parâmetros são considerados do
tipo leitura.
Tiempo del pulso en el
arranque
0.2 a 2.0 s
Nivel del pulso de tensión
en el arranque (%Un)
70 a 90 %
PARÁMETROS DE
PROTECCIÓN
P600 a P699
Falta de fase o
Subcorriente Inmediata
(% In del Motor)
1 a 80 %
Tiempo de subcorriente
inmediata o falta de fase
0 = Inactiva
1 a 99 s
Sobrecorriente inmediata
(%In del motor)
1 a 200 %
Tempo de sobrecorrente
imediata
0 = Inactiva
1 a 99 s
Desbalanceo de corriente)
entre fases (%In del motor)
0 a 30 %
Tiempo de desbalanceo de
corriente entre fases
0 = Inactiva
1 a 99 s
Subcorriente antes del
cierre del By-pass
0 = Inactiva
1 = Activa
Rotor Bloqueado
0 = Inactiva
1 = Activa
Secuencia de fase RST
0 = Inactiva
1 = Activa
Habilitación E77
0=Inactivo
1=Activo
Intervalo de tiempo luego
de la parada
2 a 999 s
Protección Térmica
del Motor
Clase térmica de
protección del motor
0 = Inactiva
1 = 5
2 = 10
3 = 15
4 = 20
5 = 25
6 = 30
Autoreset de la memoria
térmica
0 = Inactiva
1 a 600 s
Tempo do pulso na partida
0.2 a 2.0 s
Nível do pulso de tensão na
partida (%Un)
70 a 90 %
PARÂMETROS DE
PROTEÇÃO
P600 a P699
Falta de Fase ou
Subcorrente
Imediata (% In do Motor)
1 a 80 %
Tempo de subcorrente
imediata ou falta de fase
0 = Inativa
1 a 99 s
Sobrecorrente imediata
(%In do motor)
1 a 200 %
Tempo de sobrecorrente
imediata
0 = Inativa
1 a 99 s
Desbalanceamento de
corrente entre fases
(%In do motor)
0 a 30 %
Tempo de
desbalanceamento de
corrente entre fases
0 = Inativa
1 a 99 s
Subcorrente antes do
fechamento do By-pass
0 = Inativa
1 = Ativa
Rotor Bloqueado
0 = Inativa
1 = Ativa
Seqüência de fase RST
0 = Inativa
1 = Ativa
Habilitação E77
0=Inativo
1=Ativo
Intervalo de tempo após
parada
2 a 999 s
Proteção Térmica do Motor
Classe térmica de proteção
do motor
0 = Inativa
1 = 5
2 = 10
3 = 15
4 = 20
5 = 25
6 = 30
Auto-reset da memória
térmica
0 = Inativa
1 a 600 s
0
Fault Messages / Mensajes de Error / Mensagens de Erro
0
0
E03 Phase loss or undercurrent Falta de Fase o Subcorriente Falta de Fase ou Subcorrente
E04 Overtemperature on power Sobretemperatura en la potencia Sobretemperatura na potência
0
E05 Overload on motor Sobrecarga en el motor Sobrecarga no motor
E06 External fault (DI) Error externo (DI) Erro externo (DI)
0
E10 Function copy fault Error en la función copy Erro na função copy
0
E24 Programming fault Error de programación Erro de programação
Timeout fault at telegram
E28
1
reception
E31 Keypad connection failure Fallo en la conexión de la HMI Falha na conexão da HMI
E62 Current limitation start timeout
E63 Stall Rotor bloqueado Rotor bloqueado
E66 Overcurrent Sobrecorriente Sobrecorrente
E67 Inverted phase sequence Secuencia de fase invertida Seqüência de fase invertida
380
100.0
Undervoltage at electronic
E70
supply
E71 By-pass contact open Contacto del By-pass abierto Contato do By-pass aberto
E72 Overcurrent before By-pass
1.00
E74 Current imbalance Desbalanceo de corriente Desbalanceamento de corrente
Power supply frequency out of
E75
allowed range
Overcurrent before closing
E76
0
30
0
30
0
By-pass
Closed by-pass contact or
E77
shorted SCR’s
To get the detailed description of the parameters, consult the Programming Manual. This manual is supplied in
electronic format on CD-ROM and at WEG’s web site: www.weg.net
Para obtener la descripción detallada de los parámetros, consulte el Manual de Programación. Este manual es
suministrado en formato electrónico en CD-ROM y en la pagina web de WEG www.weg.net
Para obter a descrição detalhada dos parâmetros, consulte o Manual de Programação. Este manual é fornecido
em formato eletrônico no CD-ROM e no site da WEG www.weg.net
English Español Português
Error de timeout en la recepción
de los telegramas
Exceso de tiempo de limitación
de corriente durante el arranque
Subtensión en la alimentación
de la electrónica
Sobrecorriente antes del
By-pass
Frecuencia de la red de
alimentación fuera del rango
permitido
Subcorriente antes del cierre del
By-pass
Contactor de By-pass cerrado o
SCRs en cortocircuito
Erro de timeout na recepção de
telegramas
Excesso de tempo de limitação
de corrente durante a partida
Subtensão na alimentação da
eletrônica
Sobrecorrente antes do By-pass
Freqüência da rede de
alimentação fora da faixa
permitida
Subcorrente antes do
fechamento do By-pass
Contato de By-pass fechado ou
SCRs em curto-circuito
Factory
Setting
0.2
80
80
1
100
1
15
0
0
1
1
1
2
6 = 30