XMART 33-30K User Manual

0 (0)

ENGLISH

USER MANUAL

OPTIMA-33 10K / 20K / 30K

3 Phases IN - 3 Phases Out

ONLINE-DOUBLE CONVERSION UPS 400/230V & 208/120V

Technical information on this manual is property of XMART . This manual Information cannot be copied or distributed totally or partially without written approval of XMART.

XMART can introduce modifications in their products or manuals without further notice. .

XMART is not responsible of mistakes or missing information in this manual.

XMART is not responsible for wrong use a third part can do of this information.

Trademarks and logos in this manual are property of their owners.

Xmart Optima-33 10K / 20K

USER MANUAL - OPTIMA-33 10K / 20K / 30K

TABLE OF CONTENTS

1.SAFETY

2.AVAILABLE MODELS

3.- UPS INSTALLATION: SITE PLANING

SITE INSPECTION & INSTALLATION CONDITIONS

TOWER UPS INSTALLATION

EXTERNAL CIRCUIT BREAKERS & WIRING SELECTION

4.- UPS INSTALLATION: SINGLE UPS - TERMINAL BLOCK

UPS AC LINES CONFIGURATION

AC TERMINAL BLOCKS

EXTERNAL BATTERY CONNECTION

5.- UPS INSTALLATION: PARALLEL UPS - TERMINAL BLOCK

GENERAL COMMENTS

UPS AC LINES CONNECTION

PARALLEL CONTROL CABLES CONNECTION

6.- START-UP: SINGLE UPS

INSPECTION BEFORE START-UP

SINGLE UPS - START UP PROCEDURE

7.- START-UP: PARALLEL UPS

REQUIREMENTS FOR PARALLEL UPS SYSTEMS

INSPECTION BEFORE START-UP

PARALLL UPS - START UP PROCEDURE

8.- OPERATION INTERFACE

FRONT PÀNEL: PUSH BUTTONS / LEDS / LCD

9.- OPERATION: SINGLE UPS

10.- OPERATION: PARALLEL UPS

REMOVING UPS FROM PARALLEL SYSTEM

ADDING UPS TO PARALLEL SYSTEM

11.- UPS CONFIGUIRATION

12.- ERROR CODES, ALARMS & TROUBLESHOOTING

13.- TECHNICAL SPECIFICATIONS

14.- LIMITED WARRANTY

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 0

USER MANUAL - OPTIMA-33 10K / 20K / 30K

1. GENERAL SAFETY INSTRUCTIONS

WARNING: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and operating this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for future consults.

WARNING: This product operates with dangerous voltages. It must be installed, operated and maintained ONLY by qualified technicians trained for this kind of products. Service personnel MUST know and understand very well all electric risks related to this product. UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or negligent practices at the moment of install, starting up or maintain this product.

UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation. WARNING: If you are not qualified technician do not try to install, operate or repair this product.

WARNING: Do not try to install, operate or repair this product if you are not accompanied by another qualified person able to offer first aid support in case of emergency or accidents.

WARNING: Internal area of this product is locked by screws. Do not try to access inside the UPS unless you are a qualified technician. UPS must be checked, repaired and maintained by qualified personnel only.

CAUTION!!: ELECTRIC SHOCK RISK

CAUTION: There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line. CAUTION: Inside this equipment, due to internal batteries, there are ALWAYS dangerous voltages, thought the UPS is OFF and unplugged of power line.

CAUTION: There are dangerous voltages in DC (Direct Current) Capacitors. Please Check Capacitor location in Figure 8.4.1. Wait at least 10 minutes after turning off UPS before opening it to access inside.

DANGER: Power off UPS and unplugged it from AC Line before opening it to Access inside this unit.

CAUTION: Before starting the opening procedure, remove all jewelry and metallic objects such as: Rings, Watches, Bracelets, etc., because they could contact conductive parts and components inside the UPS and this might cause discharges and/or short circuits. Make sure using tools properly isolated to avoid electrical risks.

Transportation and Storage: Warnings and Recommendations

WARNING:

WARNING:

WARNING:

WARNING:

This UPS must be transported only in its original package to be properly protected This equipment must be storage in dry and ventilated site, in upright position. Before storage this UPS, batteries must be recharged for 8 to 10 hours

During long term storage UPS must be recharged periodically according to this manual.

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 1

USER MANUAL - OPTIMA-33 10K / 20K / 30K

WARNING: EQUIPMENT DISPOSAL

Out of service units : It is strongly recommended to dispose this piece of equipment according to valid directives in your country. At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for some materials to be recycled.

Batteries : Do not throw it to fire (risk of explosion). Do not open the batteries, there are dangerous liquids inside

WARNING: BATTERIES MAINTENANCE

Batteries capacity, in general (of all kinds), decrease with time and use.

Our products contain high quality batteries only.

Batteries useful life in our UPS is between 4 and 5 years, considering environment temperature under 25 ºC and optimal operational conditions. This time can be dramatically reduced by high temperature and other adverse operation condition.

Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipments connected to UPS

Batteries should be periodically tested to check capacity and assure and appropriate back up.

To enlarge batteries life expectancy it is recommendable to fully discharge UPS one every 2 to 3 months

During UPS storage recharge batteries according to the following table:

Storage Temperature

Recharging Frequency

Recharging Time

 

 

 

-25°C a +30°C

Every 4 months

During 6 hours

 

 

 

+30°C a +45°C

Every 2 months

During 6 hours

 

 

 

SAFETY STANDARDS

SAFETY:

IEC/EN 62040-1

 

 

EMI (Radiated):

FCC part15, Subpart B (Class A)

 

 

 

EMI (Radiated):

IEC/EN 62040-2

(Cat 3)

 

 

 

EMI (Conducted):

IEC/EN 62040-2

(Cat 3)

 

 

SURGE IMMUNITY

IEEE / ANSI C62.41 (Cat A & B)

 

 

EMS Power-Frequency Magnetic Field:

IEC/EN 61000-4-8 (Level 4)

 

 

EMS Low Freq. Signals:

IEC/EN 61000-2-2

 

 

EMS (ESD):

IEC/EN 61000-4-2 (Level 4)

 

 

EMS (RS):

IEC/EN 61000-4-3 (Level 3)

 

 

EMS (EFT):

IEC/EN 61000-4-4 (Level 4)

 

 

EMS (SURGE):

IEC/EN 61000-4-5 (Level 4)

 

 

EMS (CS):

IEC/EN 61000-4-6 (Level 3)

 

 

 

TRANSPORTATION:

 

ISTA 1A

 

 

 

This product has been designed to operate in industrial and commercial applications. If it is used in different application some considerations for avoiding interferences could be necessary.

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 2

USER MANUAL - OPTIMA-33 10K / 20K / 30K

2.- AVAILABLE MODELS

OPTIMA-33 10K / 20K / 30K - 400/230V

UPS 3 phases IN & 3 phases OUT for 400/230V systems. Usually this kind of UPS include electronic and internal batteries in same UPS cabinet.

OPTIMA-33 10K / 20K / 30K - 208/120V

UPS 3 phases IN & 3 phases OUT for 208/120V systems. It is based on 400/230V model but including internal transformers to adjust external voltage values to internal working values.

UPS cabinet includes all electronic and I/O transformers. Batteries are located in dedicated external battery cabinet.

EXBATT BATTERY CABINETS

If external batteries are required for 230/120V models or for extending runtime, EXBATT external batteries can be connected directly to the UPS.

EXBATT-33-T10K:

EXBATT for OPTIMA-33 10K. Includes 20 batteries 12V/9AH with DC breaker 50Amps.

DC voltage: 240Vdc (nominal).

EXBATT-33-T20K:

EXBATT for OPTIMA-33 20K. Includes 40 batteries 12V/9AH with DC breaker 100Amps.

DC voltage: 240Vdc (nominal).

EXBATT-33-T30K:

EXBATT for EPRO-33 30K. Includes 60 batteries 12V/9AH with DC breaker 150Amps.

DC voltage: 240Vdc (nominal).

WARNING

External battery packs for OPTIMA-33 models could be not compatible with some other OPTIMA UPS models.

Make sure you will connect compatible external battery pack to your UPS to avoid permanent damages not covered by warranty.

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 3

XMART 33-30K User Manual

USER MANUAL - OPTIMA-33 10K / 20K / 30K

REAR PANEL

1.- RS232

7.- FAN for power stage / Ventilación Forzada etapa de potencia

 

 

2.- USB

8.- EXBATT connector / Conector Baterías Externas

 

 

3.- EPO (Emergency Stop / Parada Emergencia)

9.- AC Input Breaker / Breaker de Entrada AC

 

 

4.- Share Current (for parallel UPS / para UPS paralelas)

10.- Terminal block cover / Tapa Regleta Conexiones

 

 

5.- Parallel Port (for parallel UPS / para UPS paralelas)

11.- MBS (Bypass Switch / Interruptor Bypass)

 

 

6.- Smart port / Puerto Inteligente

12.- FAN for TX (Ventilación del transformador)

 

 

MODEL: 208 / 120 VAC

MODEL: 400 / 230 VAC

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 4

USER MANUAL - OPTIMA-33 10K / 20K / 30K

3.- UPS INSTALLATION: SITE PLANNING

SAFETY INSTRUCTIONS

WARNING: Before revising this section you must read and understand very well section 1 of this manual: “GENERAL SAFETY INSTRUCTIONS”.

WARNINGS, RECOMMENDATIONS AND LIABILITY LIMITATION

REACH AND LIABILITY LIMITATION: The preparation of the site, wiring and all protection devices must be supplied by end user and it will not be responsibility neither the UPS distributor nor the UPS technician in charge of the start-up.

The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS technical requirements.

This manual describes minimal conditions and technical requirements with which the site must accomplish.

Directives and requirements described in this manual, do not pretend to substitute in any way local electrical directives or normative.

In some cases, local directives or regulations might be more exigent than UPS technical requirements described by this manual. In that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives.

WARNING: Power lines must be protected by protection devices against over current (breakers) or leak currents with capacity and technology

appropriate to effectively accomplish its function. Moreover, installation grounding must be correct.

WARNING: Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures

WARNING: Do not connect to UPS equipments or devices that exceed its capacity, this would overload the UPS.

WARNING: This product has been designed to be used indoors protected from water, direct sun light, dust and extreme temperature.

WARNING: Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.

WARNING: This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS

shows the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently.

WARNING: Connect only computer related equipments to this UPS. DO NOT connect medical equipments or critical availability equipments to

this UPS. DO NOT connect AC motor based equipments. DO NOT connect home appliances (ovens, vacuum cleaners, refrigerators, etc.) to this

UPS.

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 5

USER MANUAL - OPTIMA-33 10K / 20K / 30K

SITE INSPECTION AND INSTALLATION CONDITIONS

REGULATIONS AND LEGAL DIRECTIVES

It is necessary to check that installation site, wiring and power protection in the installation supplied by end user, fulfill technical parameters required by UPS.

A particular installation might accomplish with UPS requirements but not with local directives and regulations.

The end user and/or electrical contractor will be responsible of watching for complying with electrical regulations and normative during electrical installation managed by end user.

Inspection performed by installation technician is not intended to confirm regulations and directives accomplishing but only with technical needs for optimal UPS operation.

SITE INSPECTION

During transport of this UPS from a cold place to a warmer and more humid one, some condensation could be generated. Leave the UPS for at least 2 hours to climate to new installation site.

Do not install the UPS outdoors or near water sources nor in wet environment

Do not install the UPS in sites exposed to sun light or heat sources. Temperature at operation site should never rise over 35 ºC. Batteries’ life shortens over 25 ºC.

Installation site must be dry, fresh, free of dust, fibers and any other objects (conductors or not) suspended in the air that could get into the UPS thru the ventilation system (Fan).

Do not block UPS ventilations

UPS INPUT AND OUTPUT POWER LINES PROTECTION

AC LINES PROTECTIONS DEVICES:

All UPS Inputs and outputs must be protected by circuit breakers and current leak protections. Protection capacity and type must fulfill local regulations as well as directives from this manual. Grounding must be according to local directives as well.

DC PROTECTIONS DEVICES:

For Ex models (with external batteries) there must be also DC Circuit Breakers between UPS and battery bank.

Some Models include a DC breaker on the rear panel for external battery pack protection; otherwise an external DC Circuit breaker must be installed.

MATERIALS AND ELECTRICAL DEVICES

WARNING: Verify that all electrical lines involved in installation are open circuits and free of dangerous voltages before starting inspection tasks. All switches related to these electrical lines must be in “OFF” position before starting UPS installation. After disconnecting power from electrical lines involved in installation, check again with a digital voltmeter that are free of dangerous voltages.

IMPORTANT: Warning label must be placed on primary involved circuit breakers to alert there are maintenance personnel working on these circuits to avoid accidental actuation on involved breakers.

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 6

USER MANUAL - OPTIMA-33 10K / 20K / 30K

TOWER UPS INSTALLATION

SITE CONSIDERATIONS

*This product has been designed to be used indoors, protected from water, direct sun light, dust and extreme temperature.

*Install the UPS in well ventilated location or air conditioned room. Temperature must be always in acceptable range according to technical specifications table of this manual. It is strongly recommendable controlled room temperature between 21ºC to 24ºC for longer battery and UPS life.

*There must be minimum 1 meter free room distance between UPS and any wall or object. It will allow better ventilation and it will allow service UPS when required.

*Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.

ELECTRICAL REQUIREMENTS (MANDATORY)

*All Power lines must be protected by magneto-thermal protection devices against over current (breakers) with capacity and technology appropriate to effectively accomplish its function as indicated in this manual. Moreover, installation grounding must be correct.

*This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS shows the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently.

*If external battery cabinets are connected to UPS, it is necessary to install one DC breaker between UPS and each external battery cabinet. Original External Battery cabinets normally include its own input breaker.

LEAK CURRENT PROTECTION

In many countries, now a day, it is legally required to install protections against current leakage to protect human beings in cases of leaks o discharges to ground. It is responsibility of the end user and/or electrical contractor selecting and including these protection devices in the electrical circuit of the UPS.

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 7

USER MANUAL - OPTIMA-33 10K / 20K / 30K

CIRCUIT BREAKERS AND WIRING SELECTION

Breakers and Gauge of the wires used in the installation must be rated to drive current values in Amps as indicated in below tables.

NOTE every country has its local electrical requirements and regulations. If local electrical regulations require higher rates than suggested values in this section, please follow local regulations.

400/230VAC

INPUT

OUTPUT

EXT. BATT

MODEL

BREAKER & WIRING

BREAKER & WIRING

BREAKER & WIRING

 

 

 

 

 

Breaker: 32A AC (Curve D)

Breaker: 32A AC (Curve D)

Breaker: 50Amps DC (Curve C)

 

Max. Nominal Current (Ph-N):

Max. Nominal Current (Ph-N):

 

10KVA

- 19A in normal mode (@200V)

- 15A in normal mode (@220V)

Wiring (min. recommended size):

Wiring (min. recommended size):

Wiring (min. recommended size):

* 8 AWG (10mm2)

(400/230VAC)

* Phase: 10AWG (6 mm2)

* Phase: 10AWG (6 mm2)

 

 

 

 

* Neutral: 8AWG (10 mm2)

* Neutral: 8AWG (10 mm2)

 

 

* Ground: 8AWG (10 mm2)

* Ground: 8AWG (10 mm2)

 

 

 

 

 

 

Breaker: 50 Amps AC (Curve D)

Breaker: 50 Amps AC (Curve D) Max.

Breaker: 100Amps DC (Curve C)

 

Max. Nominal Current (Ph-N):

Nominal Current (Ph-N):

 

20KVA

- 38A in normal mode (@200V)

- 30A in normal mode (@220V)

 

Wiring (min. recommended size):

Wiring (min. recommended size):

Wiring (min. recommended size):

(400/230VAC)

* Phase: 8 AWG (10 mm2)

* Phase: 8 AWG (10 mm2)

* 6 AWG (16mm2)

 

 

* Neutral: 6 AWG (16 mm2)

* Neutral: 6 AWG (16 mm2)

 

 

* Ground: 6 AWG (16 mm2)

* Ground: 6 AWG (16 mm2)

 

 

 

 

 

 

Breaker: 63 Amps AC (Curve D)

Breaker: 63 Amps AC (Curve D) Max.

Breaker: 150Amps DC (Curve C)

 

Max. Nominal Current (Ph-N):

Nominal Current (Ph-N):

 

30KVA

- 56A in normal mode (@200V)

- 45A in normal mode (@220V)

 

Wiring (min. recommended size):

Wiring (min. recommended size):

Wiring (min. recommended size):

(400/230VAC)

* Phase: 8 AWG (10 mm2)

* Phase: 8 AWG (10 mm2)

* 3 AWG (35mm2)

 

 

* Neutral: 6 AWG (16 mm2)

* Neutral: 6 AWG (16 mm2)

 

 

* Ground: 6 AWG (16 mm2)

* Ground: 6 AWG (16 mm2)

 

 

 

 

 

Recommended cable size according to 1999 NEC (301-17) based on 30ºC air ambient temperature for single cable.

WARNING:

Above wiring and breakers rates are only a suggestion. The wire size is strongly affected by diverse factors such as: Operation temperature, wire length, type of wire, quantity of conductors and kind of installation. Electrical contractor must assure an appropriate selection for wire and protection devices sizing for complying with local regulations for electrical installations. Wiring colors must be selected according to local directives and regulations

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 8

USER MANUAL - OPTIMA-33 10K / 20K / 30K

208/120VAC

INPUT

OUTPUT

EXT. BATT

 

Breaker: 63 Amps AC (Curve D)

Breaker: 63 Amps AC (Curve D)

Breaker: 50 Amps DC (Curve C)

 

Max. Nominal Current (Ph-N):

Max. Nominal Current (Ph-N):

 

10KVA

- 38A in normal mode (@100V)

- 30A in normal mode (@110V)

 

Wiring (min. recommended size):

Wiring (min. recommended size):

Wiring (min. recommended size):

(208/120VAC)

Phase: 8 AWG (10 mm2)

Phase: 8 AWG (10 mm2)

8 AWG (10mm2)

 

 

Neutral: 6 AWG (16 mm2)

Neutral: 6 AWG (16 mm2)

 

 

Ground: 6 AWG (16 mm2)

Ground: 6 AWG (16 mm2)

 

 

 

 

 

 

Breaker: 80 Amps AC (Curve D)

Breaker: 80 Amps AC (Curve D)

Breaker: 100Amps DC (Curve C)

 

Max. Nominal Current (Ph-N):

Max. Nominal Current (Ph-N):

 

20KVA

- 75A in normal mode (@100V)

- 60A in normal mode (@110V)

 

Wiring (min. recommended size):

Wiring (min. recommended size):

Wiring (min. recommended size):

(208/120VAC)

Phase: 6 AWG (16 mm2)

Phase: 6 AWG (16 mm2)

* 6 AWG (16mm2)

 

 

Neutral: 4 AWG (25 mm2)

Neutral: 4 AWG (25 mm2)

 

 

Ground: 4 AWG (25 mm2)

Ground: 4 AWG (25 mm2)

 

 

 

 

 

 

Breaker: 125 Amps AC (Curve D)

Breaker: 125 Amps AC (Curve D) Max.

Breaker: 150Amps DC (Curve C)

 

Max. Nominal Current (Ph-N):

Nominal Current (Ph-N):

 

30KVA

- 111A in normal mode (@100V)

- 90A in normal mode (@110V)

 

Wiring (min. recommended size):

Wiring (min. recommended size):

Wiring (min. recommended size):

(208/120VAC)

Phase: 3 AWG (35 mm2)

Phase: 3 AWG (35 mm2)

* 3 AWG (35mm2)

 

 

Neutral: 2 AWG (35 mm2)

Neutral: 2 AWG (35 mm2)

 

 

Ground: 2 AWG (35 mm2)

Ground: 2 AWG (35 mm2)

 

 

 

 

 

Recommended cable size according to 1999 NEC (301-17) based on 30ºC air ambient temperature for single cable.

WARNING:

Above wiring and breakers rates are only a suggestion. The wire size is strongly affected by diverse factors such as: Operation temperature, wire length, type of wire, quantity of conductors and kind of installation. Electrical contractor must assure an appropriate selection for wire and protection devices sizing for complying with local regulations for electrical installations. Wiring colors must be selected according to local directives and regulations

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 9

USER MANUAL - OPTIMA-33 10K / 20K / 30K

4.- UPS INSTALLATION: SINGLE UPS - TERMINAL BLOCK

AC LINES CONNECTION PROCEDURE

Make sure the UPS is Off before starting the installation.

Remember to check all wires to be connected are not powered (including external batteries).

UPS terminal block preparation

Remove cover of terminal block at the UPS rear panel, identified as "10" in rear panel section of this manual

UPS Input wires must come from electric panel board and they must be protected by a circuit breaker protection device.

UPS Input and Output Connection

Connect input and output ground wires to proper place on the UPS chassis or terminal block. Ground wires must be FIRST to be connected and LAST to be disconnected.

Connect UPS input and output wires according to your UPS model as described in following figures:

IMPORTANT NOTE: If terminal block information printed on rear panel of the UPS is different to information given in this manual, please follow terminal block information printed on UPS.

OPTIMA-33 208/120VAC

OPTIMA-33 400/230VAC

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 10

USER MANUAL - OPTIMA-33 10K / 20K / 30K

EXTERNAL BATTERY CABINETS – CONNECTION PROCEDURE

UPS Tower type

WARNING

Make sure EXBATT model to be connected is compatible with UPS model. For OPTIMA-33 models, battery pack voltage is 240Vdc. Measure and verify DC voltage supplied by battery pack before making connections.

1.- Check all DC breakers are in OFF position

2.- Remove all DC connector covers in UPS and EXBATT cabinets

3.- Using appropriate cable (supplied with the EXBATT) connect UPS with EXBATT 1. In case of more than 1 EXBATT connect EXBATT 1 with EXBATT 2 and so on until last EXBATT.

4.- Activate DC breakers one by one in EXBATT cabinets to connect EXBATT batteries with internal UPS Main batteries.

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 11

Loading...
+ 30 hidden pages