Technical information on this manual is proper ty of XMART
partially without written approval of XMART.
XMART can introduce modifications in their products or manuals without further notice. .
XMART is not responsible of mistakes or missing information in this manual.
XMART is not responsible for wrong use a third par t can do of this information.
Trademarks and logos in this manual are property of their owners.
Xmart Optima-33 10K / 20K
.
This manual Information cannot be copied or distributed totally or
WARNING: It is required to read and understand this manual. Follow all instructions given in this manual for star ting up and
operating this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for
future consults.
WARNING: This product operates with dangerous voltages. It must be installed, operated and maintained ONLY by qualified
technicians trained for this kind of products. Service personnel MUST know and understand very well all electric risks related to
this product. UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or
negligent practices at the moment of install, starting up or maintain this product.
UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation.
WARNING: If you are not qualified technician do not try to install, operate or repair this product.
WARNING: Do not try to install, operate or repair this product if you are not accompanied by another qualified person able to offer first aid support in case of emergency or accidents.
WARNING: Internal area of this product is locked by screws. Do not try to access inside the UPS unless you are a qualified
technician. UPS must be checked, repaired and maintained by qualified personnel only.
CAUTION!!: ELECTRIC SHOCK RISK
CAUTION: There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line.
CAUTION: Inside this equipment, due to internal batteries, there are ALWAYS dangerous voltages, thought the UPS is OFF and
unplugged of power line.
CAUTION: There are dangerous voltages in DC (Direct Current) Capacitors. Please Check Capacitor location in Figure 8.4.1. Wait
at least 10 minutes after turning off UPS before opening it to access inside.
DANGER: Power off UPS and unplugged it from AC Line before opening it to Access inside this unit.
CAUTION: Before starting the opening procedure, remove all jewelry and metallic objects such as: Rings, Watches, Bracelets,
etc., because they could contact conductive par ts and components inside the UPS and this might cause discharges and/or short
circuits. Make sure using tools properly isolated to avoid electrical risks.
Transportation and Storage: Warnings and Recommendations
WARNING: This UPS must be transported only in its original package to be properly protected
WARNING: This equipment must be storage in dry and ventilated site, in upright position.
WARNING: Before storage this UPS, batteries must be recharged for 8 to 10 hours
WARNING: During long term storage UPS must be recharged periodically according to this manual.
Out of service units :It is strongly recommended to dispose this piece of equipment according to valid directives in your
country. At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for
some materials to be recycled.
Batteries : Do not throw it to fire (risk of explosion). Do not open the batteries, there are dangerous liquids inside
WARNING: BATTERIES MAINTENANCE
• Batteries capacity, in general (of all kinds), decrease with time and use.
• Our products contain high quality batteries only.
• Batteries useful life in our UPS is between 4 and 5 years, considering environment temperature under 25 ºC and optimal
operational conditions. This time can be dramatically reduced by high temperature and other adverse operation
condition.
•Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as
number and kind of equipments connected to UPS
•Batteries should be periodically tested to check capacity and assure and appropriate back up.
To enlarge batteries life expectancy it is recommendable to fully discharge UPS one every 2 to 3 months
•During UPS storage recharge batteries according to the following table:
Storage Temperature Recharging Frequency Recharging Time
-25°C a +30°C Every 4 months During 6 hours
+30°C a +45°C Every 2 months During 6 hours
SAFETY STANDARDS
SAFETY: IEC/EN 62040-1
EMI (Radiated): FCC part15, Subpart B (Class A)
EMI (Radiated): IEC/EN 62040-2 (Cat 3)
EMI (Conducted): IEC/EN 62040-2 (Cat 3)
SURGE IMMUNITY IEEE / ANSI C62.41 (Cat A & B)
EMS Power-Frequency Magnetic Field: IEC/EN 61000-4-8 (Level 4)
EMS Low Freq. Signals: IEC/EN 61000-2-2
EMS (ESD): IEC/EN 61000-4-2 (Level 4)
EMS (RS): IEC/EN 61000-4-3 (Level 3)
EMS (EFT): IEC/EN 61000-4-4 (Level 4)
EMS (SURGE): IEC/EN 61000-4-5 (Level 4)
EMS (CS): IEC/EN 61000-4-6 (Level 3)
TRANSPORTATION: ISTA 1A
This product has been designed to operate in industrial and commercial applications. If it is used in different application some
considerations for avoiding interferences could be necessary.
UPS 3 phases IN & 3 phases OUT for 400/230V systems. Usually this kind of UPS include electronic and internal batteries in
same UPS cabinet.
OPTIMA-33 10K / 20K / 30K - 208/120V
UPS 3 phases IN & 3 phases OUT for 208/120V systems. It is based on 400/230V model but including internal transformers
to adjust external voltage values to internal working values.
UPS cabinet includes all electronic and I/O transformers. Batteries are located in dedicated external battery cabinet.
EXBATT BATTERY CABINETS
If external batteries are required for 230/120V models or for extending runtime, EXBATT external batteries can be connected
directly to the UPS.
EXBATT-33-T10K:
EXBATT for OPTIMA-33 10K. Includes 20 batteries 12V/9AH with DC breaker 50Amps.
DC voltage: 240Vdc (nominal).
EXBATT-33-T20K:
EXBATT for OPTIMA-33 20K. Includes 40 batteries 12V/9AH with DC breaker 100Amps.
DC voltage: 240Vdc (nominal).
EXBATT-33-T30K:
EXBATT for EPRO-33 30K. Includes 60 batteries 12V/9AH with DC breaker 150Amps.
DC voltage: 240Vdc (nominal).
WARNING
External battery packs for OPTIMA-33 models could be not compatible with some other OPTIMA UPS models.
Make sure you will connect compatible external battery pack to your UPS to avoid permanent damages not covered by
warranty.
WARNING: Before revising this section you must read and understand very well section 1 of this manual: “GENERAL SAFETY
INSTRUCTIONS”.
WARNINGS, RECOMMENDATIONS AND LIABILITY LIMITATION
REACH AND LIABILITY LIMITATION: The preparation of the site, wiring and all protection devices must be supplied by end user and it will not
be responsibility neither the UPS distributor nor the UPS technician in charge of the star t-up.
The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS technical
requirements.
This manual describes minimal conditions and technical requirements with which the site must accomplish.
Directives and requirements described in this manual, do not pretend to substitute in any way local electrical directives or normative.
In some cases, local directives or regulations might be more exigent than UPS technical requirements described by this manual. In that case
end user electrical contractor must be sure to comply with all related local electrical regulations and directives.
WARNING: Power lines must be protected by protection devices against over current (breakers) or leak currents with capacity and technology
appropriate to effectively accomplish its function. Moreover, installation grounding must be correct.
WARNING: Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures
WARNING: Do not connect to UPS equipments or devices that exceed its capacity, this would overload the UPS.
WARNING: This product has been designed to be used indoors protected from water, direct sun light, dust and extreme temperature.
WARNING: Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.
WARNING: This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS
shows the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently.
WARNING: Connect only computer related equipments to this UPS. DO NOT connect medical equipments or critical availability equipments to
this UPS. DO NOT connect AC motor based equipments. DO NOT connect home appliances (ovens, vacuum cleaners, refrigerators, etc.) to this
It is necessary to check that installation site, wiring and power protection in the installation supplied by end user, fulfill technical parameters
required by UPS.
A particular installation might accomplish with UPS requirements but not with local directives and regulations.
The end user and/or electrical contractor will be responsible of watching for complying with electrical regulations and normative during electrical
installation managed by end user.
Inspection performed by installation technician is not intended to confirm regulations and directives accomplishing but only with technical needs
for optimal UPS operation.
SITE INSPECTION
•During transport of this UPS from a cold place to a warmer and more humid one, some condensation could be generated. Leave the
UPS for at least 2 hours to climate to new installation site.
• Do not install the UPS outdoors or near water sources nor in wet environment
• Do not install the UPS in sites exposed to sun light or heat sources. Temperature at operation site should never rise over 35 ºC.
Batteries’ life shortens over 25 ºC.
•Installation site must be dry, fresh, free of dust, fibers and any other objects (conductors or not) suspended in the air that could get
into the UPS thru the ventilation system (Fan).
•Do not block UPS ventilations
UPS INPUT AND OUTPUT POWER LINES PROTECTION
AC LINES PROTECTIONS DEVICES:
All UPS Inputs and outputs must be protected by circuit breakers and current leak protections. Protection capacity and type must fulfill local
regulations as well as directives from this manual. Grounding must be according to local directives as well.
DC PROTECTIONS DEVICES:
For Ex models (with external batteries) there must be also DC Circuit Breakers between UPS and battery bank.
Some Models include a DC breaker on the rear panel for external battery pack protection; otherwise an external DC Circuit breaker must be
installed.
MATERIALS AND ELECTRICAL DEVICES
WARNING: Verify that all electrical lines involved in installation are open circuits and free of dangerous voltages before star ting inspection
tasks. All switches related to these electrical lines must be in “OFF” position before starting UPS installation. After disconnecting power from
electrical lines involved in installation, check again with a digital voltmeter that are free of dangerous voltages.
IMPORTANT: Warning label must be placed on primary involved circuit breakers to alert there are maintenance personnel working on these
circuits to avoid accidental actuation on involved breakers.
* This product has been designed to be used indoors, protected from water, direct sun light, dust and extreme temperature.
* Install the UPS in well ventilated location or air conditioned room. Temperature must be always in acceptable range according to technical
specifications table of this manual. It is strongly recommendable controlled room temperature between 21ºC to 24ºC for longer battery and UPS
life.
* There must be minimum 1 meter free room distance between UPS and any wall or object. It will allow better ventilation and it will allow
service UPS when required.
* Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.
ELECTRICAL REQUIREMENTS (MANDATORY)
* All Power lines must be protected by magneto-thermal protection devices against over current (breakers) with capacity and technology
appropriate to effectively accomplish its function as indicated in this manual. Moreover, installation grounding must be correct.
* This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS shows the UPS
power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently.
* If external battery cabinets are connected to UPS, it is necessary to install one DC breaker between UPS and each external battery cabinet.
Original External Battery cabinets normally include its own input breaker.
LEAK CURRENT PROTECTION
In many countries, now a day, it is legally required to install protections against current leakage to protect human beings in cases of leaks o
discharges to ground. It is responsibility of the end user and/or electrical contractor selecting and including these protection devices in the
electrical circuit of the UPS.
Breakers and Gauge of the wires used in the installation must be rated to drive current values in Amps as indicated in below tables.
NOTE every country has its local electrical requirements and regulations. If local electrical regulations require higher rates than suggested values
in this section, please follow local regulations.
400/230VAC
MODEL BREAKER & WIRING BREAKER & WIRING BREAKER & WIRING
INPUT OUTPUT EXT. BAT T
10KVA
(400/230VAC)
20KVA
(400/230VAC)
30KVA
(400/230VAC)
Breaker: 32A AC (Curve D)
Max. Nominal Current (Ph-N):
- 19A in normal mode (@200V)
Wiring (min. recommended size):
* Phase: 10AWG (6 mm2)
* Neutral: 8AWG (10 mm2)
* Ground: 8AWG (10 mm2)
Breaker: 50 Amps AC (Curve D)
Max. Nominal Current (Ph-N):
- 38A in normal mode (@200V)
Wiring (min. recommended size):
* Phase: 8 AWG (10 mm2)
* Neutral: 6 AWG (16 mm2)
* Ground: 6 AWG (16 mm2)
Breaker: 63 Amps AC (Curve D)
Max. Nominal Current (Ph-N):
- 56A in normal mode (@200V)
Wiring (min. recommended size):
* Phase: 8 AWG (10 mm2)
Breaker: 32A AC (Curve D)
Max. Nominal Current (Ph-N):
- 15A in normal mode (@220V)
Wiring (min. recommended size):
* Phase: 10AWG (6 mm2)
* Neutral: 8AWG (10 mm2)
* Ground: 8AWG (10 mm2)
Breaker: 50 Amps AC (Curve D) Max.
Nominal Current (Ph-N):
- 30A in normal mode (@220V)
Wiring (min. recommended size):
* Phase: 8 AWG (10 mm2)
* Neutral: 6 AWG (16 mm2)
* Ground: 6 AWG (16 mm2)
Breaker: 63 Amps AC (Curve D) Max.
Nominal Current (Ph-N):
- 45A in normal mode (@220V)
Wiring (min. recommended size):
* Phase: 8 AWG (10 mm2)
Breaker: 50Amps DC (Curve C)
Wiring (min. recommended size):
* 8 AWG (10mm2)
Breaker: 100Amps DC (Curve C)
Wiring (min. recommended size):
* 6 AWG (16mm2)
Breaker: 150Amps DC (Curve C)
Wiring (min. recommended size):
* 3 AWG (35mm2)
* Neutral: 6 AWG (16 mm2)
* Ground: 6 AWG (16 mm2)
* Neutral: 6 AWG (16 mm2)
* Ground: 6 AWG (16 mm2)
Recommended cable size according to 1999 NEC (301-17) based on 30ºC air ambient temperature for single cable.
WARNING:
Above wiring and breakers rates are only a suggestion. The wire size is strongly affected by diverse factors such as: Operation
temperature, wire length, type of wire, quantity of conductors and kind of installation. Electrical contractor must assure an
appropriate selection for wire and protection devices sizing for complying with local regulations for electrical installations. Wiring
colors must be selected according to local directives and regulations
Recommended cable size according to 1999 NEC (301-17) based on 30ºC air ambient temperature for single cable.
WARNING:
Above wiring and breakers rates are only a suggestion. The wire size is strongly affected by diverse factors such as: Operation
temperature, wire length, type of wire, quantity of conductors and kind of installation. Electrical contractor must assure an
appropriate selection for wire and protection devices sizing for complying with local regulations for electrical installations. Wiring
colors must be selected according to local directives and regulations
• Make sure the UPS is Off before starting the installation.
UPS terminal block preparation
Remove cover of terminal block at the UPS rear panel, identified as "10" in rear panel section of this manual
UPS Input wires must come from electric panel board and they must be protected by a circuit breaker protection device.
UPS Input and Output Connection
Connect input and output ground wires to proper place on the UPS chassis or terminal block. Ground wires must be FIRST to be connected and
LAST to be disconnected.
Connect UPS input and output wires according to your UPS model as described in following figures:
• Remember to check all wires to be connected are not powered (including external batteries).
IMPORTANT NOTE: If terminal block information printed on rear panel of the UPS is different
to information given in this manual, please follow terminal block information printed on UPS.
Make sure EXBATT model to be connected is compatible with UPS model. For OPTIMA-33 models, battery pack voltage is 240Vdc.
Measure and verify DC voltage supplied by battery pack before making connections.
1.- Check all DC breakers are in OFF position
2.- Remove all DC connector covers in UPS and EXBATT cabinets
3.- Using appropriate cable (supplied with the EXBATT) connect UPS with EXBATT 1. In case of more than 1 EXBATT connect EXBATT 1 with
EXBATT 2 and so on until last EXBATT.
4.- Activate DC breakers one by one in EXBATT cabinets to connect EXBATT batteries with internal UPS Main batteries.