Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from
50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup
power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery
chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute
electrical power.
Trademarks
Sine Wave Plus Long DC Conduit Box is a trademark of Xantrex International. Xantrex is a registered trademark of
Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used
herein for identification purposes only.
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH
INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Date and Revision
July 2004 Revision A
Part Number
973-0032-01-01 Rev A
Contact Information
Telephone: 1 800 670 0707 (toll free North America)
Fax:1 800 994 7828 (toll free North America)
Email:customerservice@xantrex.com
Web:www.xantrex.com
1 360 925 5097 (direct)
1 360 925 5143 (direct)
About This Guide
Purpose
The purpose of this Owner’s Guide is to provide explanations and procedures for
installing the Long DC Conduit Box (DCCB-L) on a Sine Wave Inverter/charger.
Scope
The Owner’s Guide provides safety guidelines and procedures for installing the
Long DC Conduit Box.
Audience
The information in this Guide is intended for the experienced electrician who need
to install the Long DC Conduit Box into a power system. Only skilled personnel,
such as certified electricians and certified Renewable Energy technicians should
attempt installation of this equipment. Skills required include the ability to read
and understand how to follow single-line wiring diagrams.
Organization
This Guide consists of two chapters.
Chapter 1, “Introduction” provides basic information about the design and
purpose of the Sine Wave Plus Long DC Conduit Box.
Chapter 2, “Installation” provides installation and wiring instructions for the Sine
Wave Plus Long DC Conduit Box (DCCB-L).
Warranty and Product Information is provided at the end of the manual.
973-0032-01-01 Rev Aiii
About This Guide
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions that could result in personal injury or loss of life.
CAUTION
Cautions identify conditions or practices that could result in damage to the unit or other
equipment.
Important:
know, but not as serious as a caution or warning.
These notes describe things which are important for you to
Product Naming Conventions
DCCB-L refers to the Long DC Conduit Box without any factory installed wiring.
DCCB-L-175/L-250 refers to the Long DC Conduit Box with either a GJ175F or a
GJ250F Circuit Breaker installed. It includes some factory-installed wiring.
DCCB-RE describes a field-installed, dual-conduit box installation intended for
supporting multiple RE sources.
Long DC Conduit Box refers to all products and is used in situations where all
three products are treated the same.
iv973-0032-01-01 Rev A
Abbreviations and Acronyms
ACAlternating Current
AHJAuthority Having Jurisdiction
ASCAuthorized Service Center
AWGAmerican Wire Gauge
BSMBattery Status Meter
BTSBattery Temperature Sensor
CECCanadian Electrical Code
CSACanadian Standards Association
DCDirect Current
DCCB-LDC Conduit Box Long Version for the SW Plus Inverter/Charger
DCCB-L-175/L-250A DCCB-L that includes factory-installed hardware.
PVGFPPV Ground Fault Protection
NECNational Electrical Code (US)
RERenewable Energy
RMAReturn Material Authorization
ULUnderwriters Laboratory
About This Guide
Related Information
You can find more information about Xantrex Technology Inc. as well as its
products and services at www.xantrex.com.
973-0032-01-01 Rev Av
vi
Important Safety Instructions
WARNING
This chapter contains important safety and operating instructions for the Sine
Wave Plus Long DC Conduit Box (all models). Read and keep this Installation
Guide for future reference.
1. Installations of this equipment should only be performed by skilled personnel
such as qualified electricians and certified Renewable Energy (RE) system
installers to ensure adherence to the local and national electrical codes
applicable in your installation. For a list of Xantrex Certified RE dealers,
please visit our website at www.xantrexREdealers.com.
2. Before installing any components, read all instructions and cautionary
markings on the Long DC Conduit Box, the batteries, and all appropriate
sections of this guide.
3. The Long DC Conduit Box is designed to be permanently connected to your
Sine Wave Plus inverter to prevent accidental exposure to shock hazards.
4. Do not expose the Long DC Conduit Box to rain, snow, or spray. To reduce
risk of fire hazard, do not cover or obstruct the ventilation openings.
5. Do not install the Long DC Conduit Box in a zero-clearance compartment.
The Sine Wave Plus inverter that is attached may overheat. Minimum
clearance for ventilation around unit must be 12 inches (305 mm) at the end
and the top.
6. To avoid a risk of fire and electric shock, make sure that existing wiring is in
good condition and that wire is not undersized. Do not operate the inverter
with damaged or substandard wiring.
7. To reduce the risk of electrical shock, disconnect both AC and DC power
from the system before attempting any maintenance or cleaning or working
on the Long DC Conduit Box.
8. The Long DC Conduit Box is provided with an equipment-grounding bar that
must be connected to the inverter equipment ground and the system ground.
9. Do not store any flammable materials near the primary system panel.
973-0032-01-01 Rev Avii
Safety
Explosive gas precautions
1. Working in the vicinity of lead-acid batteries is dangerous. Batteries generate
explosive gases during normal operation. Therefore you must read this guide
and follow the instructions exactly before installing the DCCB-L.
2. To reduce the risk of battery explosion, follow these instructions and those
published by the battery manufacturer and the manufacturer of the equipment
in which the battery is installed.
Figure 2-21 DC Wiring for a Dual Inverters, Dual Long DC Conduit Box System with Multiple RE 2–30
Figure 2-22 Installing the BSM on the Long DC Conduit Box - - - - - - - - - - - - - - - - - - - - - - - - - -2–31
Figure 2-23 Wiring the C-Series Multifunction Charge Controllers to the Long DC Conduit Box
Chapter 1, “Introduction” provides basic information about the
design and purpose of the Sine Wave Plus Long DC Conduit Box.
The following topics are covered in this chapter.
For this topic:See...
“Introduction”page 1–2
“Specifications”page 1–3
“Blockoff Plates”page 1–5
“Options/Accessories”page 1–6
Introduction
Introduction
The Sine Wave Plus Long DC Conduit Box (DCCB-L) connects to the DC side of
the inverter and accepts DC conduit runs. The conduit box provides protection to
the DC cables connected to the inverter and provides a centralized location for the
DC circuit breakers and PV Ground Fault Protection (GFP) breakers. It is also
designed to incorporate cabling from up to two Multi-function DC Charge
Controllers, such as the Xantrex C-Series Charge Controllers, and cabling from a
battery meter, such as the Xantrex Battery Status Meter.
The Long DC Conduit Box is available in three different configurations.
•The DCCB-L Basic provides an internal ground bar only and space to add
additional circuit breakers; three large and six small.
•The DCCB-L-175 includes a 175 amp GJ, F-Type, circuit breaker, a DC
negative bus bar and 500A/50 mV shunt, battery cables (1 set) and a ground
wire connected to the ground bar.
•The DCCB-L-250 includes a 250 amp GJ, F-type, circuit breaker a DC
negative bus bar and 500A/50 mV shunt, battery cables (1 set) and a ground
wire connected to the ground bar.
For expandability, the Long DC Conduit Boxis designed so that a second DCCBL (any model) can be added on for additional breaker spaces, wiring, room and
controller mounting spaces. Dual configurations have been certified to meet
UL1741-2001 (First Edition) standards when using the field-installable
accessories as listed page 1–6.
Blockoff
Plates
Upper
Lower
DCCB-L includes:
A
❐ Front Cover
❐ Blockoff Plates (top and bottom)
B
C
❐ DC Ground Bar
D
❐ 6CF/3GJ Mounting Plate
E
❐ Battery Meter Mounting Box
Figure 1-1
1–2973-0032-01-01 Rev A
Sine Wave Plus Long DC Conduit Box
B
B
Front Cover
A
D
C
DCCB-L
DCCB-L-175 or DCCB-L-250 adds:
F
❐ One GJ175F or GJ250F Circuit Breaker
G
❐ DC Negative Bus Bar and Shunt
H
❐One Positive (+) Battery Cable
I
❐One Negative (–) Battery Cable
J
❐ One length green GROUND wire
E
H
I
F
J
G
DCCB-L-175 or
DCCB-L-250
Specifications
Specifications
The following table provides the operational and environmental specifications for
the Long DC Conduit Box (all models).
Table 1-1
Operational and Environmental Specifications for the Long DC Conduit Box
DCCB-L BasicDCCB-L-175DCCB-L-250
Dimensions33" (H) x 13 1/2" (W) x 8 7/8" (D)
(384 mm x 343 mm x 225 mm)
Weight22 lbs (10 kg)33 lbs (15 kg)33 lbs (15 kg)
Shipping
Weight
Factoryinstalled
hardware
Factoryinstalled
wiring
Rated
Temperature
Storage
Temperature
EnclosureIndoor rated, Galveneel, White,
25 lbs (11.5 kg)36 lbs (16.5 kg)36 lbs (16.5 kg)
• DC Ground Bar (with 12 holes,
accepts #2 - 14 AWG wires)
• 6CF/3GJ Mounting Plate
• Mounting box for BSM (w cover)
None• One - Ground Wire (#4 AWG, 18",
0 to 25 °C
(32 to 77 °F)
-55 to +100 °C
(-67 to 212 °F)
Powdercoat Finish
33" (H) x 13 1/2" (W) x 8 7/8" (D)
(384 mm x 343 mm x 225 mm)
• DC Ground Bar (with 12 holes,
accepts #2 - 14 AWG wires)
• 6CF/3GJ Mounting Plate
• Mounting box for BSM (w cover)
• DC Negative Bus Bar
• 500 A/50 mV Shunt
• GJ175F Circuit Breaker
rated to 105 °C, stranded copper) (
• One - Positive (+) Battery Cable
(#2/0 AWG, 16" Cable)
• One - Negative (–) Battery Cable
(#2/0 AWG, 30" Cable)
0 to 25 °C
(32 to 77 °F)
-55 to +100 °C
(-67 to 212 °F)
Indoor rated, Galveneel, White,
Powdercoat Finish
33" (H) x 13 1/2" (W) x 8 7/8" (D)
(384 mm x 343 mm x 225 mm)
• DC Ground Bar (with 12 holes,
accepts #2 - 14 AWG wires)
• 6CF/3GJ Mounting Plate
• Mounting box for BSM (w cover)
• DC Negative Bus Bar
• 500 A/50 mV Shunt
• GJ250F Circuit Breaker
• One - Ground Wire (#4 AWG, 18",
rated to 105 °C, stranded copper)
• One - Positive (+) Battery Cable
(#4/0 AWG, 16" Cable)
• One - Negative (–) Battery Cable
(#4/0 AWG, 30" Cable)
0 to 25 °C
(32 to 77 °F)
-55 to +100 °C
(-67 to 212 °F)
Indoor rated, Galveneel, White,
Powdercoat Finish
Ratings• 160 Vdc maximum (Open Circuit)
• 250 amps maximum each inverter
• 250 amps max. renewable energy
Charge
Controllers
RegulatoryCertified by CSA to UL 1741-2001
Accommodates: 2 Charge
Controllers, 60 amps max. each
(First Edition) and CSA C22.2
No. 107.1-01
• 160 Vdc maximum (Open Circuit)
• 250 amps maximum each inverter
• 250 amps max. renewable energy
Accommodates: 2 Charge
Controllers, 60 amps max. each
Certified by CSA to UL 1741-2001
(First Edition) and CSA C22.2
No. 107.1-01
• 160 Vdc maximum (Open Circuit)
• 250 amps maximum each inverter
• 250 amps max. renewable energy
Accommodates: 2 Charge
Controllers, 60 amps max. each
Certified by CSA to UL 1741-2001
(First Edition) and CSA C22.2
No. 107.1-01
973-0032-01-01 Rev A1–3
Introduction
Table 1-1
Optional
hardware
available at
Xantrex
Operational and Environmental Specifications for the Long DC Conduit Box
DCCB-L BasicDCCB-L-175DCCB-L-250
• Charge Controllers (60 A max ea.)
• Charge Controller Kit (CC PCK)
• Power Distribution Blocks
(PDB-6 or PDB-12)
• PVGFP-CF (-1, -2, -3, -4)
• GJ175F or GJ250F Circuit
Breakers
• GJ175F-PCK (includes wiring)
• GJ250F-PCK (includes wiring)
• Battery Status Meter (TM500A,
TM500A-NS, and TM48)
• CF60 Circuit Breakers
• CF Mounting Plate (CFMP)
• DC Negative Bus Bar with shunt
(DCBUSBAR)
• Battery Temperature Sensor (BTS)
• BC-L2-175 (#2/0 AWG cable)
• BC-L2-250 (#4/0 AWG cable)
Inverter Side
• Charge Controllers (60 A max ea.)
• Charge Controller Kit (CC PCK)
• Power Distribution Blocks
(PDB-6 or PDB-12)
• PVGFP-CF (-1, -2, -3, -4)
• GJ175F or GJ250F Circuit
Breakers
• GJ175F-PCK (includes wiring)
• GJ250F-PCK (includes wiring)
• Battery Status Meter (TM500A,
TM500A-NS, and TM48)
• CF60 Circuit Breakers
• CF Mounting Plate (CFMP)
• DC Negative Bus Bar with shunt
(DCBUSBAR)
• Battery Temperature Sensor (BTS)
• BC-L2-175 (#2/0 AWG cable)
• BC-L2-250 (#4/0 AWG cable)
DCCB-L Base
• Charge Controllers (60 A max ea.)
• Charge Controller Kit (CC PCK)
• Power Distribution Blocks
(PDB-6 or PDB-12)
• PVGFP-CF (-1, -2, -3, -4)
• GJ175F or GJ250F Circuit
Breakers
• GJ175F-PCK (includes wiring)
• GJ250F-PCK (includes wiring)
• Battery Status Meter (TM500A,
TM500A-NS, and TM48)
• CF60 Circuit Breakers
• CF Mounting Plate (CFMP)
• DC Negative Bus Bar with shunt
(DCBUSBAR)
• Battery Temperature Sensor (BTS)
• BC-L2-175 (#2/0 AWG cable)
• BC-L2-250 (#4/0 AWG cable)
Outside
Figure 1-2
0.265 x 1”
(Obround x4)
0.188”
(fits up to #8
screw x2)
Long DC Conduit Box Dimensions (Not To Scale)
1–4973-0032-01-01 Rev A
Blockoff Plates
Blockoff Plates
Upper and Lower Blockoff Plates are included to enclose the open portions of the
Long DC Conduit Box chassis. In the event that an inverter is removed, the
Blockoff Plates secure the enclosure to prevent accidental contact with any AC
power within the Long DC Conduit Box.
Remove the Blockoff Plate (upper or lower) from its position for the inverter used
in your installation. The Blockoff Plates will not be needed at all in a dual SW
Plus inverter installation.
See “Installing or Removing the Blockoff Plates” on page 2–6 for additional
information.
Important:
single-inverter systems to use the upper mounting location for the inverter. Mounting an
inverter in the lower mounting position for a single-inverter system will required sitefabricated cables.
The cable lengths provided in the DCCB-L-175/L-250 were designed for
WARNING: Shock Hazard
Be sure to disconnect all DC and AC power before removing the inverter and installing the
blockoff plate.
Upper Blockoff
Plate
Lower Blockoff
Plate
Knockout panel
(if needed)
Figure 1-3
973-0032-01-01 Rev A1–5
The Blockoff Plates
Introduction
Options/Accessories
The following CSA-approved accessories are available through Xantrex to
expand or monitor the DC side of the system.
•C-Series Multi-function DC Controllers (C35, C40, C60)
•GJ-F Series Flag Style Circuit Breakers 175A or 250A (without wiring)
(GJ175F, GJ250F)
•GJ Series Flag Style Breakers 175A or 250A (with battery cables to connect
second inverter) (GJ175F-PCK, and GJ250F-PCK)
•Dual-pole or Triple-pole GJ Flag Terminal Bus bars (GJ-FT2, GJ-FT3)
•CF Breaker Mounting Plate (CFMP)
•60 Amp CF Series Circuit Breakers for loads (CF60)
•Power Distribution Blocks 6:1 and 12:1 (PDB-6 or PDB-12)
•Battery Status Meter (TM500A-NS without shunt) or (TM500A with shunt)
•Battery Temperature Sensors (BTS)
•Battery Cables for adding a second inverter (BC-L2-175 or BC-L2-250).
These battery cables are the same as those included with the appropriate
breaker with the GJF175-PCK or GJF250-PCK.
•DC Negative Bus Bar (DCBUSBAR)
Important:
configuration. Other components may be used, but may not allow continuous operation of
the SW Plus Inverter and should be approved by the AHJ.
The components shown in this section are to be used in a DCCB-L-RE
Charge Controllers or Diversion Load Controllers
If charge control or diversion control is required, spaces are provided for
mounting up to two DC controllers on the top of the DCCB-L chassis. Xantrex
offers the C-Series Multi-function DC Controller to provide either charge control
or diversion control.
Charge controllers not purchased from Xantrex may be used also, but might not fit
the mounting holes on the top of DCCB-L. If this occurs, the non-Xantrex
supplied charge controllers will need to be mounted somewhere off the DCCB-L
chassis.
Any charge controllers used on this component (Xantrex and Non-Xantrex)
should not exceed 60 A each (120 A total).
If more charge controllers are required, then it may be desirable to have two
DCCB-Ls (any model combination) installed in a dual-configuration.
1–6973-0032-01-01 Rev A
Options/Accessories
Figure 1-4
CM Faceplate
Meter Display
CM/R
Meter
Display
The C-Series Multi-function DC Controller Family
C35
Charge Controller Installation Package
The following hardware can be purchased upon request for installing the C-Series
Multi-function DC Controller to the Sine Wave Plus Long DC Conduit Box. The
Charge Controller add-on package (CC PCK) includes the following:
•one 48-inch white #6 AWG wire (temperature rated at 90° C),
•one 96-inch red #6 AWG wire (temperature rated at 90° C),
•one 48-inch green #10 AWG wire (temperature rated at 105° C), and
•two conduit chase nipples, two lock nuts, and two plastic bushings for
1" knockouts.
C40
C60
Figure 1-5
Charge Controller Installation Package (CC PCK)
See Figure 2-23 on page 2–32 for instructions on cutting and installing the CC
PCK wiring.
973-0032-01-01 Rev A1–7
Introduction
PV Ground Fault Protection (PVGFP-CF)
PV ground fault protection is available in up to four CF-Series breaker
configurations. It’s designed to minimize the possibility of a fire resulting from
ground faults in a PV array in accordance with the National Electric Code (NEC)
for roof-mounting arrays on homes. Each switch is rated for 100 amps maximum
per circuit and mounts directly to the breaker mounting plate. It is not designed or
intended to prevent electrical shock or to be used for PV DC over-current
protection. They can be used as an array disconnect.
PVGFP-CF-3
Figure 1-6
PVGFP-CF-1
Note: Wiring shown in this figure has been trimmed for visual purposes only
and does not represent the actual length of wires that are attached to the
breakers.
PVGFP-CF-2
PVGFP-CF Breakers (-1, -2, -3 and -4)
Each charge controller that is connected to a roof mounted PV array on a home
requires a “pole” on one of the four available PV-GFV-CF configurations.
For example: If three controllers are used, one for a ground mounted PV array,
one for a roof mounted PV array on a home, and one with a diversion load, only
the one used for a roof-mounted array requires a ground fault pole.
CAUTION: Equipment Damage
Never install a PVGFP-CF between the diversion load and controller. Overcharging may
occur during a “ground fault condition”.
GJ175F and GJ250F Breakers and Flag Terminals
GJ breakers are available in sizes 175A and 250A. The GJ175F and GJ250F
breakers have single-pole “flag” terminals on them that are designed for use with
lugged cables with ring terminals. These breakers can be used as a disconnect and/
or an over-current device for the inverter(s) and PDBs.
PVGFP-CF-4
1–8973-0032-01-01 Rev A
Options/Accessories
If more than one GJ F-Series breaker is being used, they can be tied together using
the double-pole or triple-pole flag terminals. The double-pole and triple-pole flag
terminals are used to provide power to additional GJ175F or a GJ250F breakers
that in turn can feed a PDB-6 or PDB-12. This eliminates the need for an extra
cable from the battery bank.
Regular GJ breakers use “box lugs” and are intended for use with cables that do
not have ring terminals. These breakers can be used in the DCCB-L, but can not
use the flag terminals.
GJ Breaker
A
C
D
(GJ175, GJ250)
GJ F-Series Breaker
B
(GJ175F, GJ250F)
Dual-Pole Flag Terminal
C
(GJ-FT2)
Triple-Pole Flag Terminal
D
(GJ-FT3)
A
Figure 1-7
E
B
GJ Breakers and Flag Terminals
GJ250F-PCK consists of the following parts.
GJ250F Circuit Breaker
E
#6 (THHN) AWG, 7", Ground Wire
F
#4/0 AWG, 26", Positive Cable
F
G
H
G
#4/0 AWG, 20", Negative Cable
H
GJ175F-PCK consists of the following parts.
GJ175F Circuit Breaker
E
#6 (THHN) AWG, 7", Ground Wire
F
#2/0 AWG, 26", Positive Cable
G
#2/0 AWG, 20", Negative Cable
H
(Assembly hardware not shown.)
Figure 1-8
GJ 175F-PCK or the GJ250F-PCK
Charge controllers and other loads may use a CF60 breaker. Ensure the wiring is
properly sized according to local codes.
973-0032-01-01 Rev A1–9
Introduction
CF60 Circuit Breakers
CF-Type (60 amp/160 Vdc Open Circuit) breakers are available at Xantrex for
charge controllers and other DC loads. Smaller sizes can be used if properly sized
for the load. Smaller breakers can be purchased at the local, electrical supply
dealer. Ensure the wiring is properly sized for the breaker according to local code.
Figure 1-9
CF60 Circuit Breaker
CF-Series Breaker Mounting Plate
The CF-Series Mounting Plate (CFMP) replaces the standard 3GJ/6CF Mounting
Plate already in the DCCB-L and provides spaces for up to 10 CF-Series breakers.
Figure 1-10
CF-Series Mounting Plate (CFMP)
Power Distribution Blocks (PDB)
Two Power Distribution Blocks are available for use as a DC positive bus.
PDB-6PDB-12
Figure 1-11
1–10973-0032-01-01 Rev A
Power Distribution Blocks
Battery Status Monitor (BSM)
The Xantrex Battery Status Monitor (BSM) (p/n TM500A and TM500A/NS)
features six data monitoring functions and three indicators including:
•State of charge/amp-hour content (full or percent of capacity)
•State of charge/voltage (real-time voltage level, historical high and low
system voltage)
•Amps (real-time amps, total charging amps, total load amps)
•Amp hours removed
•Days since fully charged
•Cumulative amp hours
•Recharge indicator
•Low-voltage indicator
•Full-charge indicator
The unit is configurable for specific system or application functions such as
setting the CHARGED indication parameters, battery capacity, charging
efficiency, low-battery warning conditions and a recharge reminder. The BSM can
monitor any battery supply from approximately 8 to 65 volts, track energy
consumption, and estimate remaining battery life.
Options/Accessories
The BSM operates on 12-, 24-, or 48-volt battery systems (48-volt systems require
an optional shunt board--the TM48).
The BSM (TM500A) includes a 500A/50mV shunt.
The BSM (TM500A-NS) does not include the shunt.
Figure 1-12
Battery Status Monitor
The DCCB-L-175/L-250 both include a shunt mounted to the DC negative bus
bar. This shunt can be used with the TM500A/NS.
The DCCB-L will require the TM500A (with a shunt).
973-0032-01-01 Rev A1–11
Introduction
Battery Temperature Sensors
A Battery Temperature Sensor (BTS) is provided with each SW Plus Inverter. A
BTS can also be purchased separately for use with the C-Series Multi-function
DC Controllers. This sensor can easily be installed in the system to ensure proper
charging of the batteries based on temperature. Installing a BTS extends battery
life by preventing overcharging in warm temperatures and undercharging in cold
temperatures.
If more than one BTS is being used, install them adjacent to each other so that
they all detect a common temperature.
Battery Cables
Figure 1-13
Battery Temperature Sensor
Xantrex offers battery cables in a variety of lengths and sizes. Consult your dealer
for more specific information on size and length requirements depending on the
configuration of your system.
For dual configurations, Xantrex offers two sets of precut cables that are
specifically designed to accommodate adding the second inverter.
•The BC-L2-175 provides a pair of #2/0 AWG battery cables.
•The BC-L2-250 provides a pair of #4/0 AWG battery cables.
BA
A
Posistive Cables are 26" (66 cm)
Negative Cables are 20" (51 cm)
B
BC-L2-250 shown.
Figure 1-14
1–12973-0032-01-01 Rev A
Battery Cable Set (BC-L2-250 or BC-L2-175)
DC Negative Bus Bar
Xantrex has custom-designed a DC Negative Bus Bar. The DC Negative Bus Bar
(p/n DCBUSBAR) comes with a 500 A/50 mV shunt and is factory-installed in
the DCCB-L-175 and DCCB-L-250. It can also be purchased separately and fieldinstalled at a later time, either to convert a single DCCB-L into a dual-RE
configuration or to add to a DCCB-L (basic model).
1 1/2"
(1.27 cm)
E
AAA
7" (17.78 cm)
B
AAAA
B
CCCCC
B
Options/Accessories
D
Figure 1-15
A
B
C
D
E
DC Negative Bus Bar
Important:
provided with this kit needs to be color-coated for code compliance, electrical tape or nonconductive paint may be used.
#1/4-20 stainless steel, hex head, cap screws with
stainless steel flat washers.
#5/16-18 stainless steel, hex head, cap screws with
stainless steel flat washers
#10-32 threaded holes
500 A/50 mV Shunt
Standoff with #1/4-20 screw and washer
The standoff provided in this kit is only available in red. If the standoff
973-0032-01-01 Rev A1–13
1–14
2
Installation
Chapter 2, “Installation” provides installation and wiring instructions
for the Sine Wave Plus Long DC Conduit Box (DCCB-L).
The following topics are covered in this chapter.
For this topic:See...
“Preparing for the Installation”page 2–2
“Pre-installation”page 2–3
“Mounting”page 2–8
“Installing Accessories”page 2–11
“Wiring - General”page 2–16
“Wiring - Specific”page 2–27
“Single Inverter System”page 2–27
“Single Inverter System with Renewable Energy”page 2–28
“Dual Inverter System with Renewable Energy”page 2–29
“Dual Inverter System with Multiple Renewable
Energy”
page 2–30
Installation
Preparing for the Installation
Code Compliance
Governing installation codes vary depending on the location and type of
installation. Installations of this equipment should only be performed by skilled
personnel such as qualified electricians and Certified Renewable Energy (RE)
System Installers to ensure adherence to the local and national electrical codes
applicable in your application.
Important:
starting this installation.
Be sure to obtain the appropriate permits, if necessary, prior to
Installation Tools and Materials
Tools RequiredThe following tools may be required for installing this equipment.
The following materials may be required for completing this installation.
❐ Conduits (flexible conduit recommended), bushings, and appropriate fittings
for wire runs. See “Service Planning” on page 2–3.
❐ DC fuses and/or DC disconnects
❐ Electrical wire of appropriate size and length and wire nuts
❐ Battery cables and battery cable lugs (depending on the type of battery
cables used)
❐ Breaker panel(s)
❐ Power Distribution Block (optional)
❐ Ground busses, bars, and/or rods
❐ Six appropriately sized wood screws and/or lagbolts and washers (for
plywood mounting)
2–2973-0032-01-01 Rev A
Pre-installation
Pre-installation
WARNING: Shock Hazard
Ensure that no DC voltage is being supplied to the inverter and that no AC voltage is
present on the AC wiring. Failure to do so could cause serious injury or death. A warning
label is provided to inform all personnel that multiple sources of power are available
inside. This label should be installed on the outside cover to be clearly visible. Ensure all
sources are OFF or disconnected before servicing.
Location
Service Planning
WARNING
PN 3550
ELECTRICAL SHOCK
HAZARD
THIS ELECTRICAL SYSTEM IS EQUIPPED WITH A
DC TO AC P O WE R INV ERTE R. DISCO NNE CT THE
DC AND AC SOURCES BEFORE SERVICING.
Figure 2-1
Be sure to allow sufficient space for the Long DC Conduit Box to be mounted
directly adjacent to the inverter’s DC side. Be sure to leave room for expansion if
necessary. Also consider the additional weight and ventilation space requirements
of the Long DC Conduit Box and another components (such as the ACCB-L) that
will be mounted with the SW Plus Inverter.
If for any reason the inverter may need service or needs to be removed from the
position where it’s mounted, the following recommendations should be
considered to make this task easier.
Warning Label
To make servicing the inverter easier to accomplish:
•Use flexible conduit.
•When mounting the components such as the ACCB-L or DCCB-L next to the
inverter, bias the mounting screws away from the inverter. This will allow
"sliding" room within the mounting holes, so that the ends can slide apart
without being removed from their mounted position.
Figure 2-8, “Mounting the Long DC Conduit Box and the Sine Wave Plus Inverter
Charger on Plywood” on page 2–10for details.
973-0032-01-01 Rev A2–3
Installation
Ventilation Requirements
Minimum clearance for ventilation around Long DC Conduit Box must be at least
12 inches (305 mm) at the end and at the top. The minimum clearance is needed to
prevent recirculating hot air from the inverter’s exhaust (DC side) from going
back into the inverter’s intake (AC side).
Please refer to the Sine Wave Plus Inverter/Charger Owner’s Guide for additional
location considerations.
12” (305 mm)
Minimum Required
Figure 2-2
Shock Hazard
Warning Label
Space and Clearance Requirements
WARNING
ELECTRICAL SHOCK
HAZARD
THIS ELECTRICAL SYSTEM IS EQUIPPED WITH A
DC TO AC POWER INVERTER. DISCONNECT THE
DC AND AC SOURCES BEFORE SERVICING.
PN 3550
12” (305 mm)
Minimum Required
2–4973-0032-01-01 Rev A
Removing and Replacing the Long DC Conduit Box Cover
s
Remove the top cover to install additional breakers and to connect the DC wiring
of the inverter to the Long DC Conduit Box.
Remove these 3 #8 phillips
screws from the top of the
cover.
Slide these 3
cover tabs into
the cover slots on
the SW Plus
Inverter.
Pre-installation
Replace these screws
and torque to 19-21 in lbs.
Only remove this screw if
you are going to install a
Battery Status Meter.
Slide these 3
cover tabs into
the cover slots on
the 2nd SW Plus
Inverter (if used).
Figure 2-3
Remove these 8 #12 phillips
screws from the front of the
cover.
Replace these screws
and torque to 26-28 in lbs.
Remove these 3 #8 phillips
screws from the bottom of
the cover.
Replace these screws
and torque to 19-21 in lb
Removing and Replacing the Long DC Conduit Box Top Cover
973-0032-01-01 Rev A2–5
Installation
Installing or Removing the Blockoff Plates
The unit is shipped with both upper and lower blockoff plates installed. If you are
installing a single-inverter system, remove the upper blockoff plate only. If you
are installing a dual-inverter system, then remove the lower blockoff plate as well.
If a TX Autotransformer will be installed, then remove the rectangular knockout
in the lower blockoff plate, but leave the blockoff plate installed. The two bottom
screws that hold the lower blockoff plate may need to be removed to ensure a tight
fit between the TX and Long DC Conduit Box.
Store the blockoff plates (if removed) in a safe place, where they can be easily
retrieved and reinstalled in the event that the inverter is removed for service. This
will prevent accidental contact with potentially live and lethal circuits.
WARNING: Shock Hazard
Be sure to disconnect all DC and AC power before removing the inverter and
installing the blockoff plate.
Align holes on Blockoff
Plate behind the mounting
holes provided on the Long
DC Conduit Box
Secure with hardware provided.
Figure 2-4
2–6973-0032-01-01 Rev A
The Blockoff Plates on the Long DC Conduit Box
Knockout Preparation
Knockout preparation should be done before mounting either the inverter or the
Long DC Conduit Box.
To prepare the knockouts:
1. Remove the appropriate knockouts from the Long DC Conduit Box for wire
2. If additional CF- or GJ-type circuit breakers are to be added to the Long DC
3. Ensure that there are no metal shavings in the Long DC Conduit Box or
4. Install bushings in knockouts to protect the wires from damage.
Pre-installation
runs from the battery bank, Renewable Energy sources and/or DC Generator,
and Multi-function DC Charge Controllers (if used).
Conduit Box, remove one knockout on the circuit breaker mounting plate for
each additional circuit breaker to be installed.
inverter before proceeding with the rest of the installation.
3/4 and 1” Dual
Knockouts (x4)
(two are not visible
behind BSM mounting
box in this illustration)
2” Knockouts (x2)
Knockout panel for
CF- or GJ-type
breakers
2 and 2 ½” Dual
Knockouts (x2)
3/4 and 1” Dual
Knockouts (x3)
Bottom
Important:
If larger knockouts are required, an electricians knockout punch
may be used for larger size knockout holes if necessary.
Base
Outside Wall
2” Knockouts (x3)
Lower
Blockoff Plate
One Rectangular
Knockout only
Top
3/4 and 1” Dual
Knockouts (x13)
Figure 2-5
½” Knockout (x3)
2 and 2 ½” Dual Knockouts (x2)*
2” Knockouts (x1)*
3/4 and 1” Dual Knockouts (x5)
Knockout Locations on the Long DC Conduit Box
*The 2” Knockouts on the outside wall are spaced 1 5/8” off
the mounting surface (wall). This allows the use of 1 5/8”
conduit mounting strut (aka Unistrut) to provide secure
mounting for the large battery cable conduits. If using the
XBP, a 1” spacer will be required.
973-0032-01-01 Rev A2–7
Installation
Mounting
The Long DC Conduit Box is designed to mount directly to the DC side of a SW
Plus inverter. The SW Plus inverter can weigh up to 136 lbs (62 kg). The DCCBL weighs up to 17 lbs (8 kg). Ensure the supporting surface is strong enough to
hold twice the total weight being installed. Remember to include the weight of
any other accessory, such as the AC conduit box and/or controllers, when
considering the strength of the support surface.
Xantrex provides a steel back plate (XBP) that provides the additional support. A
sheet of 3/4" plywood could also provide adequate support.
Mounting the Long DC Conduit Box on the Xantrex Back Plate (XBP)
A two-piece steel, back plate is available for providing extra support to the
mounting surface. The back plate comes with mounting hooks that can be
attached to the panel to hang the components on as they’re installed. If two Long
DC Conduit Boxs are to be installed, an additional back plate (XBP-DC) is
available to provide the extra support required.
Pass through
holes for
conduits
running
through the
back of the
back plate
Hand Holds for
installing
Pass through
holes for
conduits
running
through the
back of the
back plate
Figure 2-6
XBP Left Side
The XBP Back Plate
To mount the Long DC Conduit Box on the Back Plate (XBP):
1. Install the mounting hook (if used) onto the back plate in the position
indicated in Figure 2-6.
2. Mount the back plate according to the instructions provided with the XBP
Installation Instructions.
46”
(117 cm)
XBP Right Side
Mounting Hook
for 1st DCCB-L
XBP-DC
13 1/2”
(34 cm)
Mounting Hook
for 2nd DCCB-L
35”
(89 cm)
Side View
2–8973-0032-01-01 Rev A
Mounting
3. Lift the inverter and place the mounting rail holes directly over the mounting
hooks on the panel and lower into place.
4. Next, lift the Long DC Conduit Box and place it over the mounting hook for
the DCCB-L and into the hole on the mounting rail.
Important:
rails. If you can not see the hooks, the unit is not installed properly and will not be secure
to the wall.
5. Secure the inverter to the panel using the ten of the ¼-20 phillips screws
provided with the back plate hardware kit. Torque to 76 in-lbs.
6. Push the Long DC Conduit Box as close to the inverter as it will possibly go
and secure it to the panel using four of the ¼-20 phillips screws provided with
the back plate hardware kit. Torque to 76 in-lbs.
IMPORTANT: Be sure to consult local
electrical and building codes for additional
mounting requirements.
Mounting hook from
backplate for Long DC
Conduit Box
Ensure the mounting hooks are visible through the holes in the mounting
Be sure the
mounting hooks
are visible in the
mounting rail
holes
Secure the inverter and
Long DC Conduit Box
to the backplate with
twelve ¼-20 phillips
screws provided with
the back plate.
Figure 2-7
Mounting the Long DC Conduit Box and the SW Plus Inverter Charger on the XBP
973-0032-01-01 Rev A2–9
Installation
Mounting on Plywood
To install the Long DC Conduit Box on plywood:
1. Mount the inverter into placeand secured with appropriate lag bolts.
2. Line up the Long DC Conduit Box at the DC end of the inverter, so that the
3. Secure the Long DC Conduit Box in place with six #10 wood screws of an
4. Leave the top cover off the Long DC Conduit Box to proceed with wire
mounting rails are aligned together and the Long DC Conduit Box base is as
close to the inverter as possible. The gap between the Long DC Conduit Box
and the inverter should be no more than 1/16 inch.
appropriate length (or lag bolts) in the six mounting and keyhole slots on the
mounting rails of the Long DC Conduit Box. Bias the screws away from the
inverter.
connections.
Mounting Rails
Mounting holes
and keyhole slots
for Long DC
Conduit Box
Long DC Conduit
Box Base with top
cover removed
Bias the screws
(top and bottom)
away from the
inverter for easier
removal if necessary
Mounting holes
and keyhole slots
for Long DC
Conduit Box
Figure 2-8
2–10973-0032-01-01 Rev A
Mounting the Long DC Conduit Box and the Sine Wave Plus Inverter Charger on Plywood
Installing Accessories
Installing Accessories
Additional components may be required depending on the desired installation. Be
sure to consult NEC/CEC regulations to ensure all installations meet code
requirements.
GJ-Series BreakersSpace is provided for up to three GJ-Series Breakers for over-current protection.
Use either regular GJ-Series or GJ F-Series depending on the type of lugs used on
the battery cables.
Flag TerminalsIf more than one GJ F-Type breaker is being used, they can be tied together using
the dual-pole or triple-pole flag terminals. Regular GJ breakers can not use flag
terminals.
Both kinds of breakers can be used as a disconnect and/or an over-current device
for the inverter(s) and the optional PDBs.
PVGFP-CF or CF60Space is provided for up to six additional CF-Series Breakers for PV ground fault
protection (PVGFP-CF)or load protection (CF60).
To mount the GJ-Series or CF-Series Breakers:
1. Place the circuit breaker behind the mounting plate in the position of the
knockout that was removed.
2. Align the hole of the circuit breaker with the hole in the mounting plate.
3. Insert the mounting screw from the front of the mounting plate.
Tighten to the torque value indicated on the side of the breaker.
Power Distribution
Blocks (PDB)
CF Mounting Plate
(CFMP)
Important:
the Breaker Mounting plate.
Ensure the position of the breaker lines up with the knockout removed in
CAUTION: Fire Hazard
Ensure the size of the breaker meets NEC/CEC requirements and is not oversized for the
wire/cable used.
Install the PDB (if used) on the back wall of the Long DC Conduit Box chassis.
Mounting holes are provided. PDBs are available in 6:1 and 12:1 sizes.
A separate mounting plate can be used if only CF breakers will be used. This
mounting plate has 10 positions for CF-type Breakers. The CF Mounting replaces
the existing mounting plate in the chassis.
To install the CFMP:
1. Remove the four nuts on the mounting screws holding the original mounting
plate in place. See Figure 2-10 on page 2–12.
2. Slide the original mounting plate toward the back of the chassis away from
the screws and remove it.
3. Slide the new CFMP into place and replace the nuts.
4. Tighten to 31 in-lbs.
973-0032-01-01 Rev A2–11
Installation
To install GJ or CF Circuit Breakers:
1.Place the breaker behind the
mounting plate.
2. Inserting mounting screws into
mounting holes from top, or front,
of mounting plate.
3.Tighten to 20-25 in-lb.
Breaker Enlargement
DCCB-L
Figure 2-9
Installing Circuit Breakers on the Long DC Conduit Box
Battery Status Meter
Power Distribution Block
GJ F-type Breakers
Triple Flag Terminal
PVGFP-CF or CF-Type
Breakers
(PVGFP-CF -4 shown)
DC Negative Bus Bar and
Shunt*
*Tighten the 10-32 phillips screws
to 31 in-lbs when field-installing.
Callout “C” in Figure 1-15 on page
1–13.
**Tighten the 1/4 x 20 phillips
screws to 76 in-lbs when fieldinstalling. Callout “A” in Figure 1-15
on page 1–13.
To install the CFMP:
1.Loosen the four nuts on the mounting
2.Slide the original mounting plate toward
3.Slide the new CFMP into place and
4.Tighten to 31 in-lbs.
screws holding the original mounting
plate in place (as shown above).
the back of the chassis away from the
screws and remove it.
tighten the nuts.
Figure 2-10
Optional Component Locations on the Long DC Conduit Box
2–12973-0032-01-01 Rev A
Dual DCCB-L Configurations (DCCB-L-RE)
Dual DCCB-L Configurations (DCCB-L-RE)
If additional breakers or other accessories are needed, dual-DCCB-Ls can be
installed and organized into a DCCB-L-RE configuration. The DCCB-L-RE is a
CSA approved, field-installable configuration when used with the factory
installed hardware and wiring, and optional hardware as shown in Table 1-1. In
this configuration, some hardware components may need to be installed, or
mounted, onto the second Long DC Conduit Box prior to wiring. The following
section provides a basic list of additional hardware that may be needed. Consult
the local codes for specific requirements.
Dual DCCB-Ls
2
1
1
4
Important:
The components shown in this section are approved by CSA to be used in a
DCCB-L-RE configuration. Other components may be used, but may not allow
continuous, full power, operation of the inverter and should be approved by the AHJ.
Dual Configurations can be created from the following combinations of DCCB-L
models:
•two DCCB-L Basics
•one DCCB-L-175 (or L250) and one DCCB-L Basic
•one DCCB-L-175 (or L250) and one DCCB-L-175 (or L-250)
If creating a dual-configuration with two DCCB-Ls (basic models), the following
components can be added.
1
Circuit Breakers
Up to three GJ circuit breakers and six CF-type circuit breakers can be
installed using the standard breaker mounting plate. Bond the larger
2
1
3
4
GJxxxF breakers together with the dual or triple flag terminals as
required.
Power Distribution Block(s) (PDB)
2
Space is provided for a PDB-6 or a PDB-12, if needed.
3
CF Mounting Plate (CFMP)
The standard breaker mounting plate can be replaced with the CFMP.
This provides space for up to 11 CF-type breakers. Remove the
appropriate number of knockouts and install the desired number,
type(s) and size(s) of breaker(s) on the CFMP.
4
A DC Negative Bus Bar can be added for Negative Bonding.
5
Negative Bonding Jumper
A battery cable (BC 1.5-2/0 or BC1.5-4/0) can be installed on the
negative bus bar to tie the two bus bars together. Cable size will depend
on the overall size of the system to be installed.
DCCB-L
Figure 2-11
5
DCCB-L
Creating a DCCB-L-RE Configuration from Dual DCCB-Ls
973-0032-01-01 Rev A2–13
Installation
Dual DCCB-L-175s (or L-250s)
It is also possible to add a second DCCB-L-175 or DCCB-L-250 to the end of an
existing DCCB-L-175 or DCCB-L-250 to create the dual DC end shown in Figure
2-12. Minor reconfiguring of the factory installed 175A or 250A breaker and
associated cables will be necessary.
To prepare the second DCCB-L-175 (or DCCB-L-250) for use as the second DC
end, the following steps will be necessary.
4
5
3
7
6
1st DCCB-L-175
(or L-250)
2nd DCCB-L-175
(or L-250)
To convert a DCCB-L-175 or DCCB-L-250 to a
Dual Configuration:
1
1.Remove the DC breaker, positive cable, and
negative cable from the second DC end.
2
2.If more than 6 CF breakers are needed in the
second DC end, remove the original GJ/CF
breaker mounting plate in the second DC end
4
2
6
and replace it with a CFMP.
3
3.Install the DC breaker (removed in step 1) in the
first DC end adjacent to the inverter breakers.
This new breaker will be used as the DC main
bus overcurrent device/disconnect for charge
controllers, other DC sources, and DC loads.
4.If needed, install a Power Distribution block
4
(PDB-6 or PDB-12) in the second DC end.
5.Connect the DC positive cable (removed during
5
step 1) to the DC main bus breaker (installed in
step 3) and connect it to the PDB (Installed in
step 4). Note: one end of the cable will need to
be cut to length to fit into the PDB and a 2"
chase bushing will be needed.
6.Use the negative cable (removed during step 1)
6
as the negative bonding jumper between both
DC negative bus bars in each DC end. Note:
This cable can be used “as is” or cut to the
required length if the appropriate crimper/lug is
available or a Xantrex 18” cable may be
purchased (p/n BC1.5B-2/0 or BC1.5B-4/0). A
2" chase bushing will also be needed.
7.Connect the #4 AWG ground wire from the
7
second DC end equipment grounding bar to the
first DC end equipment grounding bar.
Figure 2-12
Creating a DCCB-L-RE Configuration from two DCCB-L-175 (or L-250)
2–14973-0032-01-01 Rev A
Charge/Load Controllers
Each Long DC Conduit Box accommodates up to two C-Series Multi-function
DC controllers on the top of it’s chassis. If installing charge or diversion load
controllers, install them at this time according to the manufacturer’s instructions.
If using C-Series Multi-function DC Controllers, the CC PCK provides the
necessary bushings, conduit, and wiring to install one controller.
Mount up to 2 Charge/Diversion
Load controllers on the top of
each Long DC Conduit Box.
Charge/Load Controllers
Figure 2-13
973-0032-01-01 Rev A2–15
Adding Charge or Diversion Load Controllers on the Long DC Conduit Box
Important:
model) may restrict airflow enough to cause the inverter to over-heat. Only use two charge
controllers (maximum 60 amps DC each) per DCCB-L (any model). Installing more than
two charge controllers per DCCB-L is not approved by CSA.
Installing more than two charge controllers in the same DCCB-L (any
Installation
Wiring - General
WARNING: Shock Hazard
Although the DC electrical system may be “low voltage”, significant hazards may still be
present, particularly from short-circuits of the battery system. Inverter systems, by their
nature, involve power from multiple sources (e.g., inverter, generator, utility, batteries,
and solar arrays) that add hazards and complexity that can be very challenging.
CAUTION
The battery negative connection is only grounded at one point. This is usually the chassis
bonding lug to the DC negative bus or bonded using the PVGFP-CF assembly.
CAUTION: Equipment Damage
When making your DC connections, ensure there is nothing between the cable terminal/
lug and the terminal surface (i.e., washers, anti-oxidant paste etc.). Overheating of the
terminal may occur.
Grounding the Long DC Conduit Box
The Long DC Conduit Box is used to ground the DC system. The purpose of
grounding is to maintain all DC equipment at the same “ground” potential to
avoid a shock hazard. It also provides a low impedance connection to shunt fault
currents to earth.
The following points should be taken into consideration when planning how to
properly ground the DC system, whether or not you’re installing a new system or
integrating new parts into an older system.
•DC Equipment Grounding
•Bonding DC Negative to Ground
•Connecting to the Primary grounding system
•Connecting DC and AC electrical system grounds together
Important:
installations must comply with national and local codes and ordinances. Consult local and/
or national codes to ensure that proper grounding techniques are being employed and that
the desired installation will meet all the code requirements when inspected. It is the
responsibility of the installer to ensure the system meets all electrical codes for that
jurisdiction. The following information is provided as a guide and is not intended to
override applicable codes/requirements.
The grounding requirements vary by county and by application. All
2–16973-0032-01-01 Rev A
Wiring - General
Important:
which is the normal configuration in most DC systems. If your system requires a positive
ground, the information below will differ on what conductors are grounded and which are
not. Consult the NEC/CEC regulations for positive grounding requirements.
DC Equipment Grounding
All DC components that have non-current carrying exposed metal parts require
appropriate grounding. The Long DC Conduit Box provides the DC ground bar
which will allow you to connect all the exposed metal chassis of the various DC
components to the same point. The DC equipment will need to be connected to the
DC ground bar using appropriately sized wires, referred to as equipment
grounding conductors. Connecting these equipment grounding conductors to the
DC ground bar will tie them together at the same voltage potential and provide a
path to ground through the grounding electrode conductor. This reduces the
possibility for electric shock and also provides a path for fault currents to flow
through to blow fuses or trip circuit breakers. If two Long DC Conduit Boxes are
used, ensure both DC ground bars are connected together using an appropriately
sized equipment grounding conductor.
Equipment
Grounding
Conductor size
The equipment grounding conductor must have adequate ampacity and low
enough impedance to cause the overcurrent device (fuse or circuit breaker) to
open on the supply side in case an ungrounded conductor comes in contact with
any exposed metal part of the DC system or equipment.
The information in this section is based on a negative grounded DC system
In the United States, homes that have roof-mounted photovoltaic arrays are
required to have ground-fault protection. In a DC system where there is groundfault protection equipment, the size of the equipment grounding conductor should
be coordinated with the size of the over-current devices for the DC equipment
involved, as shown in Table 2-1. This table determines the minimum wire size of
copper conductor you require, which is based on the size of the circuit breaker
protecting the equipment that you are using in the DC system. This table also
provides guidance on the torque requirements needed when attaching the
corresponding wire to the ground bus bar.
Table 2-1
Battery DC
Disconnect Size
60 Amp#10 AWG35 in-lb
175 Amp#6 AWG45 in-lb
250 Amp#4 AWG50 in-lb
Minimum Equipment Ground Wire and DC Disconnect Size Chart
Minimum Size of
Copper Ground Wire
DCCB Ground Lug
Wire Torque Spec
In DC systems not required to use ground-fault protection equipment, the size of
the equipment grounding conductor is required to be sized for 125 percent of the
photovoltaic-originated short-circuit currents in that circuit. Consult PV array
specifications and the NEC/CEC for proper wire sizes.
973-0032-01-01 Rev A2–17
Installation
Important:
size (i.e. voltage drop, increased surge requirements), the DC Equipment Grounding
Conductors shall be increased in size proportionately according to circular mil area of the
ungrounded conductors.
Per the NEC, where ungrounded conductors (DC Positive) are increased in
Bonding DC Negative to Ground
The current carrying grounded conductors (DC negative) and the Equipment
Grounding Conductors (green ground wires, equipment grounds) shall be tied or
“bonded” together at a single point in the DC System. This connection is made
with an appropriately sized wire as shown on Figure 2-15 on page 2–21, referred
to as the Main Bonding Jumper. When an ungrounded conductor (DC positive)
touches the grounding system, current will flow to the common grounding point
(DC Ground Bar) through the Main Bonding Jumper to the grounded conductor
(DC negative) and back to the source. This will cause the over-current protection
device to open, which will stop the flow of current, protecting the system. In DC
systems where there is a requirement to have a ground-fault protection device
(PVGFP-CF) as shown on Figure 2-14 on page 2–20, it will effectively be the
single point connection between the DC negative and the common grounding
point (DC Ground Bar). In this application, if a DC ground-fault is detected, the
ground-fault protection device will open and switch the grounding system from a
low impedance, DC negative-to-ground bond to a high-impedance bond that will
limit fault currents to a safe level.
Bonding location This single connection point or DC negative to ground “bond” is usually located
in the over-current protection device enclosure (Long DC Conduit Box). The DC
bond should not be done at the inverter. Codes do not generally allow this because
the inverter is considered a “serviceable” item that may be removed from the
system, in which case, the ground bond would be broken.
Size of the bonding
jumper
For DC systems, the size of the bonding jumper that is used to bond the DC
negative to the DC ground bar shall not be smaller than the size of the DC
grounding electrode conductor used, which is the conductor that connects the DC
ground bar to the primary system ground.
Connecting to the Primary System Ground
The common grounding point (DC Ground Bar) in the Long DC Conduit Box will
need to be grounded to the Primary System Ground. The Primary System Ground
is normally referred to as the grounding electrode or rod and usually is a copperplated rod usually 5/8 inch round by 8 feet long and driven into the earth. It is also
common to use copper wire placed in the concrete foundation of the building as a
grounding system. Either method may be acceptable, but the local code will
prevail. Connection to the Primary System Ground (ground rod/grounding
electrode system) from the DC Ground Bar is done by the DC Grounding
Electrode Conductor. The DC Grounding Electrode Conductor normally only
carries current when there is a ground fault.
2–18973-0032-01-01 Rev A
Wiring - General
DC
Grounding
Electrode
Conductor
Size
The size for the DC Grounding Electrode Conductor when it is the DC systems sole
connection to the Primary System Ground is not required to be larger than 6 AWG
copper wire. It is recommended that the size of the DC Grounding Electrode Conductor
should be larger than the NEC/CEC minimum requirements when installing power
sources such as inverter/chargers, generators or for lightning protection.
WARNING: Explosion Hazard
Under no circumstance should a gas pipe or gas line be used for grounding purposes.
Connecting DC and AC Electrical System Grounds Together
Inherently, Xantrex inverter systems have two separate electrical systems, a DC system
and an AC system. This means the grounding consideration for both systems need to be
accounted for and that the two electrical systems should be connected to a grounded,
permanent wiring system with the AC and DC grounds common to each other.
The NEC has provided two requirements, either using a single grounding electrode or
using multiple grounding electrodes, when both DC and AC electrical systems are
together:
1. Single grounding electrode: The DC grounding electrode conductor and AC
grounding electrode conductor will be connected to a single grounding electrode. or,
2. Multiple grounding electrodes: The DC grounding electrode conductor will be
connected between the DC grounding point to a separate DC grounding electrode.
The DC grounding electrode will be connected to the AC grounding electrode to
make a grounding electrode system. The conductor that connects the two ground
electrodes will be no smaller than the largest grounding electrode conductor used –
either AC or DC.
973-0032-01-01 Rev A2–19
Installation
Figure 2-14
2–20973-0032-01-01 Rev A
Grounding Using PVGFP-CF
Wiring - General
Figure 2-15
973-0032-01-01 Rev A2–21
Grounding Without PVGFP-CF
Installation
Over-current Protection
For safety and compliance with regulations, battery overcurrent protection is
required. Fuses and disconnects must be sized to protect the wiring in the system
and are required to open before the wire reaches its maximum current carrying
capability.
Table 2-2
Recommended Battery Cable Size Versus Length
Maximum
Inverter
Model
Continuous
DC amps
2524134167#2/0 AWG
25486784#2/0 AWG
4024214267#4/0 AWG
4048107134#2/0 AWG
5548147184#4/0 AWG
a.“Maximum Continuous DC amps”, as shown in this table, is based on low
battery voltage with an efficiency of 85%.
b.“NEC amps”, as shown in this table, is based on low battery voltage, an
efficiency of 85%, and a 125% NEC derating.
NEC
a
amps
Up to 5 Feet
b
One-way
(67.4 mm
(67.4 mm
(107 mm
(67.4 mm
(107 mm
2
)
2
)
2
)
2
)
2
)
Up to 10 Feet
One-way
#4/0 AWG
(107 mm2)
#4/0 AWG
(107 mm2)
#4/0 AWG x 2
(107 mm2 x 2)
#4/0 AWG
(107 mm2)
#4/0 AWG x 2
(107 mm2 x 2)
Up to 15 Feet
One-way
Not
Recommended
#4/0 AWG x 2
(107 mm2 x 2)
Not
Recommended
Not
Recommended
Not
Recommended
After selecting battery cables based on the distance from the battery bank to the
inverter, add battery overcurrent protection in the battery cable line, based on
Table 2-3. This table will help you to determine your maximum breaker/fuse size
based on the cable size you selected previously.
Table 2-3
Cable Size Required
#2/0 (00) AWG175 Amps175 Amps265 Amps
#4/0 (0000) AWG250 Amps250 Amps360 Amps
Battery Cable to Maximum Breaker/Fuse Size
Maximum
Rating in
Conduit
a.The term “free air” is defined by the NEC/CEC as cabling that is not
enclosed in a conduit or a raceway. Cables enclosed in conduit or
raceways have substantially lower continuous current carrying ability due
to heating factors.
b.The NEC/CEC allows rounding to the next highest standard fuse size
from the cable rating (i.e., 150 amp cable size rounds up to a standard
175 amp size).
Breaker/Fuse
Size
Rating in
“Free Air”
Maximum
Breaker/Fuse
a
Size
300 Amps
400 Amps
b
b
2–22973-0032-01-01 Rev A
Master DC Disconnect
The DCCB-L has been designed for the use of a DC main breaker as a master
disconnect for charge controllers, DC loads, and other DC sources. The same
disconnect(s) used for the inverter(s) should not be used as a controller and/or DC
load disconnect. Instead, an independent disconnect for a DC bus is recommended
to allow controllers and/or DC loads to operate when an inverter has been
disconnected or vise versa (see Figure 2-21 on page 2–30).
A CF60 may be used as a 60A DC bus disconnect using a 1" breaker slot and a
GJ175F or GJ250F can be used as a 175A or 250A DC bus disconnect using a
1.5" breaker slot. The use of a main DC disconnect can help comply with the
intent of the NEC’s "six hand throw requirement" to disable an electrical system
within six motions of the hand.
Some wind and water turbines, along with their controllers, may need to be wired
directly to the battery bank or on a dedicated line to prevent from being
inadvertently disconnected and causing a damaging, over-speed condition.
Consult your turbine manufacturer's instructions for a wiring schematic and to
determine if the turbine is fail-safe with loss of connection to the battery.
Wiring - General
CAUTION: Equipment Damage
Do not allow any device to be wired so that an inverter will be exposed to the open circuit
voltage if any disconnects are opened. If the voltage is high enough it may damage the
inverter and would not be covered under warranty.
973-0032-01-01 Rev A2–23
Installation
Additional Over-current Protection
Depending on individual installation requirements, additional over-current
devices (fuses or circuit breakers) may be desirable and/or required. The GJ F
breakers used on DCCB-L models can be used both as a disconnect and an overcurrent device if inverter is overloaded or has an internal fault. However,
additional over-current devices may be required.
Near battery bankThe GJ F breakers will not provide over-current protection if there is a wiring
fault between the battery bank and the breaker(s). It may be desirable to add an
over-current device adjacent to the battery bank positive terminal particularly if
metallic (conductive) conduits are used. Non-metallic (PVC etc.) conduits may
negate this risk and need.
When using triple
flag terminals
Large Loads or
Diversion Loads
Charge ControllersCharge controllers should be connected to a dedicated breaker that will allow
When using the triple flag terminals for the GJ F breakers, additional steps may be
required to prevent over loading of the battery cables in the event of one cable is
removed or becomes inadvertently disconnected. Use of the triple flag terminal on
dual inverters will functionally "parallel" the battery cable conductors. This is
permitted by the NEC 310.4 for cable 1/0 and larger. Specialized lugs are required
to connect multiple parallel conductors into a common single conductor.
In addition, the dual-pole and triple-pole flag terminals when used on systems
with large diversion loads and/or DC loads with inverters operating at full load
could theoretically exceed the rated capacity of the conductors between the
battery bank and the dual-pole or triple-pole flag terminal attached on the GJ F
breakers thus requiring an additional over-current device. If the battery bank can
not provide this level of current (+500 Adc for #4/0 AWG cable) for a theoretical
continuous load (greater than 3 hours), then a over-current device sized
specifically for the paralleled cable assembly may not be required.
them to function while the inverter breaker is in the off position. Connecting the
"battery terminal" on charge controllers to the inverter side connection of a GJ F
breaker will operate but is not recommended.
2–24973-0032-01-01 Rev A
Battery Cable Connection
Connect the battery cables for a single-inverter system as shown in Figure 2-16.
Wiring - General
Important:
battery cables) to be marked with white tape or heat shrink on their ends to visibly show
correct polarity to prevent reverse polarity and shorting.
NEC requires all grounded conductors larger than #6 AWG (such as
Figure 2-16
973-0032-01-01 Rev A2–25
Battery Connections for a Single-inverter System
Installation
Connect the battery cables for a dual-inverter system as shown in Figure 2-17.
Important:
battery cables) to be marked with white tape or heat shrink on their ends to visibly show
correct polarity to prevent reverse polarity and shorting.
NEC requires all grounded conductors larger than #6 AWG (such as
Figure 2-17
2–26973-0032-01-01 Rev A
Battery Connections for a Dual-inverter System
Wiring - Specific
The following four diagrams illustrate how to make all the ground connections,
battery connections, controller connections, and renewable energy connections for
the basic configurations. They include:
•Single inverter systems with no renewable energy
•Single inverter systems with renewable energy
•Dual inverters with renewable energy
•Dual inverters with multiple renewable energy.
These diagrams are basic examples only and may vary depending upon your
specific installation. Ensure appropriate local electrical codes are followed at all
times.
Single Inverter System
The following example diagram illustrates the proper DC wiring for a basic,
single-inverter system.
Wiring - Specific
Figure 2-18
973-0032-01-01 Rev A2–27
DC Wiring for a Single Inverter System
Installation
Single Inverter System with Renewable Energy
The following example diagram illustrates the proper DC wiring for a single
inverter system with renewable energy.
Figure 2-19
2–28973-0032-01-01 Rev A
DC Wiring for a Single Inverter System with Renewable Energy
Dual Inverter System with Renewable Energy
The following example diagram illustrates the proper DC wiring for a dual
inverter system with renewable energy.
Wiring - Specific
Figure 2-20
973-0032-01-01 Rev A2–29
DC Wiring for a Dual Inverter System with Renewable Energy
Installation
Dual Inverter System with Multiple Renewable Energy
The following example diagram illustrates the proper DC wiring for a dual
inverter system with dual DCCB-Ls and multiple renewable energy.
Figure 2-21
2–30973-0032-01-01 Rev A
DC Wiring for a Dual Inverters, Dual Long DC Conduit Box System with Multiple RE
Additional Accessory Wiring
Install additional accessories at this time, such as the Battery Status Monitor
(BSM) (p/n TM500A and TM500A-NS) and Battery Temperature Sensors.
Battery Status Monitor (BSM) (p/n TM500A or TM500A-NS)
To install the BSM on the Long DC Conduit Box:
1. Remove the cover plate from the BSM Mounting Box.
2. Install the shunt board from the BSM to the shunt in the DCCB-L.
3. Secure the BSM to the mounting box.
4. Connect the BSM communications cable to the back of the BSM.
5. Connect the other end of the BSM communications cable to the port on the
shunt.
5
1
4
7
Wiring - Specific
Remove the phillips screw to remove
1
cover plate from the mounting box.
2
Install the 2 amp, 250 Vac, 3AG
style in-line fuse that’s provided with
the BSM.
Install the shunt board from the BSM
3
to the shunt in the DCCB-L.
2
Plastic Push
Rivets (4x)
BSM Mounting Bracket
Figure 2-22
3
8
6
Enlargement of Back of BSM
Installing the BSM on the Long DC Conduit Box
See the Installation and Operator’s Guide for the BSM (TM500A) for additional
information.
Place the mounting bracket over the
4
mounting box and secure with the
four plastic push rivets provided with
the Long DC Conduit Box. The rivets
will snap into place when pressed
into the holes.
5
Install the bushing provided in the
hole in the mounting box to protect
the communications cable.
6
Connect the J1 communications
cable to the back of the BSM and
route it through the hole in the back of
the mounting box.
7
Place the faceplate of the BSM over
the mounting bracket and snap into
place.
Route the other end of the communi-
8
cations cable to the current shunt
board installed on the DC negative
bus bar.
973-0032-01-01 Rev A2–31
Installation
Charge Controller Wiring using the C-Series Multifunction DC Controller and the CC PCK
The Charge Controller add-on package (CC PCK) includes the following
hardware to facilitate wiring one C-Series Multifunction DC Controller to the
Long DC Conduit Box:
•two conduit chase nipples, two lock nuts, and two plastic bushings for
1" knockouts,
•one 48-inch white #6 AWG wire (temperature rated at 90° C),
•one 96-inch red #6 AWG wire (temperature rated at 90° C), and
•one 48-inch green #10 AWG wire (temperature rated at 105° C).
Follow the procedure below to prepare the units and install the wires.
To prepare the units for wiring:
Remove two 1” knockouts in the bottom of the
1
controller. (Step not shown in illustration).
2
Remove two corresponding 1” knockout s in the
top of the DCCB-L (Step not shown in illustration).
3
Align the knockouts in the controller over the
7
8
knockouts in the DCCB-L and install the conduit
chase nipples, bushings, and lock nuts.
(Step not shown in illustration).
4
Cut the 96-inch red #6 AWG wire into two pieces
(length to depend on the placement of the circuit
breakers). (Step not shown in illustration.)
Overcurrent
Protection
5
Figure 2-23
PV Array/Load
Disconnect
6
Wiring the C-Series Multifunction Charge Controllers to the Long DC Conduit Box
To connect the wiring:
5
Connect one end of the green ground wire (#10
AWG) to the chassis ground in the controller. Route
the other end to the DC ground bar in the DCCB-L.
6
Connect one end of the white wire (#6 AWG) to one
of the common negatives in the controller. Route the
other end to the DC Negative Bus Bar.
7
Connect one of the pieces of red #6 AWG wire to
the Battery Positive terminal in the Controller and
the other end to the top of the CF Circuit Breaker for
the over-current protection.
Connect the other piece of red #6 AWG wire to the
8
PV/Load Positive terminal in the Controller and the
other end to the top of the CF Circuit Breaker for the
PV or Load Disconnect. If PVGFP is required, then
substitute the CF Circuit Breaker for the Load with a
PVGFP-CF.
9
Repeat for each controller to be installed.
using the CC PCK
2–32973-0032-01-01 Rev A
Battery Temperature Sensor
If you have a BTS connected to your battery, then you will need to pass its
connecting wire through the Long DC Conduit Box to the DC side of the inverter
(see Figure 2-24).
If you have a BTS connected to your C-Series Multi-function DC controller, you
can also run that wire through the Long DC Conduit Box.
To run the BTS through the Long DC Conduit Box:
1. Secure the BTS to a battery in the battery box. Connect multiple sensors to
one battery in a centralized location that will give the best representation of all
the batteries temperatures.
2. Run the BTS cable(s) through the DC cable conduit.
3. Connect the cable(s) to the inverter’s Battery Temperature Sensor Ports or the
C-Series Battery Temperature Ports.
See your inverter manual and BTS manual for further information about the
installation of this accessory.
Wiring - Specific
Positive (+) Battery
Cable Terminal
Figure 2-24
Negative (–) Battery
Cable Terminal
Battery
Temperature
Sensor Port
Chassis Ground Lug
BTS Port locations on the Sine Wave Plus Inverter
Battery
Temperature
Sensor Port
Figure 2-25
973-0032-01-01 Rev A2–33
BTS Port locations on the C-Series DC Controller
Installation
Battery Temperature
Sensor Cable. Can
also be routed to DC
Controller.
Figure 2-26
Installing the Battery Temperature Sensor
This completes the basic wiring for the Long DC Conduit Box. Once all wiring is
complete, refer to the Sine Wave Plus Owner’s Manual for functional test,
configuration, and operational instructions.
2–34973-0032-01-01 Rev A
Warranty and Return Information
Warranty
What does this warranty cover? This Limited Warranty is provided by Xantrex Technology, Inc. ("Xantrex")
and covers defects in workmanship and materials in your Long DC Conduit Box. This warranty period lasts for two
years from the date of purchase at the point of sale to you, the original end user customer. You require proof of
purchase to make warranty claims.
This Limited Warranty is transferable to subsequent owners but only for the unexpired portion of the Warranty
Period. Subsequent owners also require proof of purchase.
What will Xantrex do? Xantrex will, at its option, repair or replace the defective product free of charge,
provided that you notify Xantrex of the product defect within the Warranty Period, and provided that Xantrex through
inspection establishes the existence of such a defect and that it is covered by this Limited Warranty.
Xantrex will, at its option, use new and/or reconditioned parts in performing warranty repair and building
replacement products. Xantrex reserves the right to use parts or products of original or improved design in the repair
or replacement. If Xantrex repairs or replaces a product, its warranty continues for the remaining portion of the
original Warranty Period or 90 days from the date of the return shipment to the customer, whichever is greater. All
replaced products and all parts removed from repaired products become the property of Xantrex.
Xantrex covers both parts and labor necessary to repair the product, and return shipment to the customer via a
Xantrex-selected non-expedited surface freight within the contiguous United States and Canada. Alaska and Hawaii
are excluded. Contact Xantrex Customer Service for details on freight policy for return shipments outside of the
contiguous United States and Canada.
How do you get service? If your product requires troubleshooting or warranty service, contact your merchant. If
you are unable to contact your merchant, or the merchant is unable to provide service, contact Xantrex directly at:
Telephone:1 800 670 0707 (toll free North America)
1 360 925 5097 (direct)
Fax:1 800 994 7828 (toll free North America)
1 360 925 5143 (direct)
Email:customerservice@xantrex.com
Direct returns may be performed according to the Xantrex Return Material Authorization Policy described in your
product manual. For some products, Xantrex maintains a network of regional Authorized Service Centers. Call
Xantrex or check our website to see if your product can be repaired at one of these facilities.
What proof of purchase is required? In any warranty claim, dated proof of purchase must accompany the
product and the product must not have been disassembled or modified without prior written authorization by Xantrex.
Proof of purchase may be in any one of the following forms:
•The dated purchase receipt from the original purchase of the product at point of sale to the end user, or
•The dated dealer invoice or purchase receipt showing original equipment manufacturer (OEM) status, or
•The dated invoice or purchase receipt showing the product exchanged under warranty
973-0032-01-01 Rev AWA–1
Warranty and Return
What does this warranty not cover? This Limited Warranty does not cover normal wear and tear of the
product or costs related to the removal, installation, or troubleshooting of the customer's electrical systems. This
warranty does not apply to and Xantrex will not be responsible for any defect in or damage to:
a) the product if it has been misused, neglected, improperly installed, physically damaged or altered, either inter-
nally or externally, or damaged from improper use or use in an unsuitable environment;
b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or input voltage
that creates operating conditions beyond the maximum or minimum limits listed in the Xantrex product specifications including high input voltage from generators and lightning strikes;
c) the product if repairs have been done to it other than by Xantrex or its authorized service centers (hereafter
"ASCs");
d) the product if it is used as a component part of a product expressly warranted by another manufacturer;
e) the product if its original identification (trade-mark, serial number) markings have been defaced, altered, or
removed.
Disclaimer
Product
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY XANTREX IN CONNECTION WITH YOUR
XANTREX PRODUCT AND IS, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS,
GUARANTEES, REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR IMPLIED, STATUTORY OR OTHERWISE IN
CONNECTION WITH THE PRODUCT, HOWEVER ARISING (WHETHER BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF
MANUFACTURER'S LIABILITY, OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT
RESTRICTION ANY IMPLIED WARRANTY OR CONDITION OF QUALITY, MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT
REQUIRED UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT SHALL BE LIMITED IN DURATION TO THE PERIOD
STIPULATED UNDER THIS LIMITED WARRANTY.
IN NO EVENT WILL XANTREX BE LIABLE FOR ANY SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL
DAMAGES, LOSSES, COSTS OR EXPENSES HOWEVER ARISING WHETHER IN CONTRACT OR TORT INCLUDING WITHOUT
RESTRICTION ANY ECONOMIC LOSSES OF ANY KIND, ANY LOSS OR DAMAGE TO PROPERTY, ANY PERSONAL INJURY, ANY
DAMAGE OR INJURY ARISING FROM OR AS A RESULT OF MISUSE OR ABUSE, OR THE INCORRECT INSTALLATION,
INTEGRATION OR OPERATION OF THE PRODUCT.
Exclusions
If this product is a consumer product, federal law does not allow an exclusion of implied warranties. To the extent you
are entitled to implied warranties under federal law, to the extent permitted by applicable law they are limited to the
duration of this Limited Warranty. Some states and provinces do not allow limitations or exclusions on implied
warranties or on the duration of an implied warranty or on the limitation or exclusion of incidental or consequential
damages, so the above limitation(s) or exclusion(s) may not apply to you. This Limited Warranty gives you specific
legal rights. You may have other rights which may vary from state to state or province to province.
Warning: Limitations On Use
Please refer to your product manual for limitations on uses of the product.
SPECIFICALLY, PLEASE NOTE THAT THE SINE WAVE PLUS LONG DC CONDUIT BOXSHOULD NOT BE USED IN
CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES. WITHOUT LIMITING THE
GENERALITY OF THE FOREGOING, XANTREX MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE USE OF THE
XANTREX
MEDICAL EQUIPMENT OR DEVICES.
Please note that the Sine Wave Plus Long DC Conduit Box is not intended for use as an uninterruptible power supply
and Xantrex makes no warranty or representation in connection with any use of the product for such purposes.
WA–2973-0032-01-01 Rev A
SINE WAVE PLUS LONG DC CONDUIT BOX IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER
Warranty and Return
Return Material Authorization Policy
Before returning a product directly to Xantrex you must obtain a Return Material Authorization (RMA) number and
the correct factory "Ship To" address. Products must also be shipped prepaid. Product shipments will be refused and
returned at your expense if they are unauthorized, returned without an RMA number clearly marked on the outside of
the shipping box, if they are shipped collect, or if they are shipped to the wrong location.
When you contact Xantrex to obtain service, please have your instruction manual ready for reference and be prepared
to supply:
•The serial number of your product
•Information about the installation and use of the unit
•Information about the failure and/or reason for the return
•A copy of your dated proof of purchase
Record these details in on page WA–4.
Return Procedure
1.Package the unit safely, preferably using the original box and packing materials. Please ensure that your product
is shipped fully insured in the original packaging or equivalent. This warranty will not apply where the product is
damaged due to improper packaging.
2.Include the following:
•The RMA number supplied by Xantrex Technology, Inc. clearly marked on the outside of the box.
•A return address where the unit can be shipped. Post office boxes are not acceptable.
•A contact telephone number where you can be reached during work hours.
•A brief description of the problem.
3.Ship the unit prepaid to the address provided by your Xantrex customer service representative.
If you are returning a product from outside of the USA or Canada In addition to the above, you MUST
include return freight funds and are fully responsible for all documents, duties, tariffs, and deposits.
If you are returning a product to a Xantrex Authorized Service Center (ASC)A Xantrex return material
authorization (RMA) number is not required. However, you must contact the ASC prior to returning the product or
presenting the unit to verify any return procedures that may apply to that particular facility.
Out of Warranty Service
If the warranty period for your Sine Wave Plus Long DC Conduit Box has expired, if the unit was damaged by misuse
or incorrect installation, if other conditions of the warranty have not been met, or if no dated proof of purchase is
available, your inverter may be serviced or replaced for a flat fee.
To return your Sine Wave Plus Long DC Conduit Box for out of warranty service, contact Xantrex Customer Service
for a Return Material Authorization (RMA) number and follow the other steps outlined in “Return Procedure” on
page WA–3.
Payment options such as credit card or money order will be explained by the Customer Service Representative. In
cases where the minimum flat fee does not apply, as with incomplete units or units with excessive damage, an
additional fee will be charged. If applicable, you will be contacted by Customer Service once your unit has been
received.
973-0032-01-01 Rev AWA–3
Warranty and Return
Information About Your System
As soon as you open your Sine Wave Plus Long DC Conduit Box package, record the following information and be
sure to keep your proof of purchase.
❐ Serial Number
❐ Purchased From
❐ Purchase Date
If you need to contact Customer Service, please record the following details before calling. This information will help
our representatives give you better service.
❐ Type of installation (e.g. RV, truck, residential)
❐ Length of time inverter has been installed
❐ Battery/battery bank size
❐ Battery type (e.g. flooded, sealed gel cell, AGM)
❐ DC wiring size and length
❐ Alarm sounding?
❐ Description of indicators on front panel
❐ Appliances operating when problem occurred
❐ Description of problem
abbreviations and acronyms v
Accessories 2–11
Accessory Wiring 2–31
additional accessory wiring 2–33
B
Battery Status Monitor 2–31
Battery Temperature Sensor 2–33
Battery Temperature Sensor (BTS) 2–33
Blockoff Plates 2–6
Bonding DC Negative to Ground 2–18
Bonding location 2–18
C
CF Mounting Plate (CFMP) 2–11
CF60 2–11
Charge/Load Controllers 2–15
Connecting DC and AC Electrical System Grounds
Together
Customer Service
preparing to call
2–19
WA–4
D
DC conduit box
introduction
DC Equipment Grounding 2–17
DC Grounding Electrode Conductor Size 2–19
DCCB-L-RE 2–13
Dual DCCB-L Configurations 2–13
1–2
I
Information about Your System form WA–4
installation
codes
2–2
knockout preparation 2–7
materials 2–2
tools 2–2
inverter
purchase date
serial number WA–4
WA–4
K
Knockout Preparation 2–7
knockouts
preparation
2–7
M
Master DC Disconnect 2–23
materials required for installation 2–2
Mounting 2–8
O
overcurrent protection, requirements 2–22
P
Power Distribution Blocks (PDB) 2–11
proof of purchase WA–4
purchase date WA–4
PV GFP 2–11
F
Flag Terminals 2–11
G
GJ-Series Breakers 2–11
Grounding 2–16
S
Safety Instructions vii
serial number WA–4
Size of the bonding jumper 2–18
T
TM500A 2–31
TM500A-NS) 2–31
tools required for installation 2–2
V
Ventilation Requirements 2–4
W
warranty
out of warranty service
terms and conditions WA–1
wiring
additional accessory
WA–3
2–33
X
Xantrex
web site
v
IX-2
Xantrex Technology Inc.
1 800 670 0707 Tel. toll free NA
1 360 925 5097 Tel. direct
1 800 994 7828 Fax toll free NA
1 360 925 5143 Fax direct
customerservice@xantrex.com
www.xantrex.com
973-0032-01-01
PC Printed in USA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.